“As Built” Service Parts List............................................................................................ BACK
Model Name
07/25/15
T30-TTL-PDI-5
- 2 -
T = Trenton
NOMENCLATURE
T TL 1 1 5 M A - S1 A
Design Version
Product Name
TL = Two Way Low Prole Evaporator
X 100 = Nominal Capacity
(10°F TD, 60Hz), Btu/H
Evap Temp Range
M = Medium Temp (10 - 45°F), 8 FPI.
L = Low Temp(-20 - 0°F), 8 FPI.
STANDARD FEATURES
•Compatable with Low GWP Refrigerants
• Low height compact size maximizes useable
storage space
• Dual refrigeration coils and two-way air
distribution reduces air velocities to minimize
product dehydration.
• Air enters through fan and discharges two ways
out of each coil side.
Unit Electrical Designaton.
S1 = 115/1/60
S2 = 208-230/1/60
S6 = 200-220/1/50
Defrost Type.
A = Air Defrost
E = Electric Defrost
• Rugged heavy duty motor mount reduces
vibration and noise.
• Electric defrost models include factory installed
defrost termination and fan delay thermostat.
• NSF approved “ush to ceiling mount”
• Refrigerants R407A, R407C, R404A/R507,
R22 and R134a.
• Internally enhanced tube
• PSC Motors available on all models • EC Motors available for Medium Temperature
OPTIONAL FEATURES
models 032, 038, 060, 077 & 115 and Low
Temperature models 028, 033, 052, 066 & 099
CAPACITY DATA - ALL MODELS
07/25/15
T30-TTL-PDI-5
- 3 -
TTL
MEDIUM TEMPERATURE MODELS - CAPACITY *
Medium Temp. ModelsTTL010MTTL015MTTL020MTTL025MTTL032MTTL038MTTL060MTTL077MTTL115M
Number of Fans111111223
R407A
Capacity
BTUH
(WATTS)
Air FlowCFM (L/s)
Refrigerant **
Charge
Evap
Temp.
25°F
(-4°C)
R407A
R407C
R404A
R507
R22
R134a
Lbs (Kg)
LOW TEMPERATURE MODELS - CAPACITY *
Low Temp. ModelsTTL009LTTL013LTTL017LTTL021LTTL028LTTL033LTTL052LTTL066LTTL099L
Number of Fans111111223
R407A
Capacity
BTUH
(WATTS)
Air FlowCFM (L/s)
Refrigerant **
Charge
Evap
Temp.
-20°F
(-28.9°C)
R407A
R407C
R404A
R507
R22
R134a
Lbs
(Kg)
900138019002380304036005700730010900
(264)(404)(557)(696)(891)(1058)(1670)(2144)(3202)
860130518002250288034205400690010400
(250)(383)(527)(660)(844)(1003)(1582)(2031)(3033)
950145020002500320038006000770011500
(278)(425)(586)(733)(938)(1114)(1758)(2257)(3370)
900138019002380300036005700730010900
(264)(404)(557)(696)(891)(1058)(1670)(2144)(3202)
855130518002250288034205400693010350
(250)(383)(527)(660)(844)(1003)(1582)(2031)(3033)
130
(61.4)
0.4
(0.18)
81011901620200026603100490063009400
(237)(348)(473)(584)(780)(919)(1448)(1837)(2756)
77011251530189025202970470060008900
(224)(329)(448)(554)(739)(870)(1372)(1741)(2611)
85012501700210028003300520066009900
(249)(366)(498)(615)(821)(967)(1524)(1934)(2901)
81011901620200027003100490063009400
(237)(348)(473)(584)(780)(919)(1448)(1837)(2756)
76511251530189025202970468059408910
(224)(329)(448)(554)(739)(870)(1372)(1741)(2611)
130
(61.4)
0.4
(0.18)
180
(85.0)
0.5
(0.23)
180
(85.0)
0.5
(0.23)
237
(112)
0.7
(0.32)
237
(112)
0.7
(0.32)
270
(127)
0.8
(0.36)
270
(127)
0.8
(0.36)
440
(208)
0.9
(0.41)
440
(208)
0.9
(0.41)
440
(208)
1.2
(0.55)
440
(208)
1.2
(0.55)
928
(438)
1.4
(0.64)
928
(438)
1.4
(0.64)
60Hz
807
(381)
2.3
(1.05)
807
(381)
2.3
(1.05)
1242
(586)
3.4
(1.55)
1242
(586)
3.4
(1.55)
* Derate capacity by 5% when using EC Motors
Capacities rated using 10°F (5.6°C) TD & 100°F (38°C) liquid temperature.
Capacities at other TD within a range of 8 to 15 °F (4.4 to 8.3°C) are directly proportional to TD, or use formula: Capacity = Rated capacity ÷ 10 x TD.
For capacities at TD outside of range 8 to 15 °F (4.4 to 8.3°C), or liquid temperature lower than 75°F (24°), consult factory .
Capacities for R407A and R407C are based on mean temperature. Mean temperature is the average temperature between the saturated suction
temperature and the temperature feeding the evaporator. For dew point ratings, consult factory.
* CAPACITY CORRECTION FACTORS FOR LOW TEMPERATURE UNITS
SATURATED SUCTION
TEMPERATURE °F (°C)0 (-17.8)
FACTOR1.061.031.0
NO CORRECTION FACTOR REQUIRED FOR MEDIUM TEMP. UNITS