Page 1
PRODUCT DATA &
INSTALLATION
Bulletin T30-TPLP-PDI-11
TPLP
Pre-Assembled
Low Prole
Evaporators
1087152
?
Questions about this product?
Email: evaps@t-rp.com
Call: 1-844-893-3222 x520
?
Air & Electric Defrost
Electrical Power:
115/1/60, 208-230/1/60, 208-230/3/60, 460/1/60
See Page 22 for details
CONTENTS
Page
Nomenclature................................................................................................................... 2
Features & Options.......................................................................................................... 2
Pre-Assembled Features................................................................................................. 3
Capacity Data.................................................................................................................. 4
Electrical Data.................................................................................................................. 5-7
Wiring Diagrams - Models with standard PSC motors .................................................... 8-15
Wiring Diagrams - Models with optional EC Motors /
Shipping Weights............................................................................................................. 20
Dimensional Data............................................................................................................. 21-22
Recommended Expansion Valve Selections................................................................... 23
Installation Instructions.................................................................................................... 24-25
Generic Service Parts ..................................................................................................... 26
Warranty........................................................................................................................... 27
Project Information........................................................................................................... 27
“As Built” Service Parts.................................................................................................... Back
.............................. 16-19
Page 2
NOMENCLATURE
TPLP
T = Trenton
Pre-Assembled
Low Prole Evaporator
Number of Fans
Nominal Capacity:
x 1000 @ 10°F TD, Btu/H, R404A
Application Range:
M = Medium to High Temp 6 FPI (10°F to 45°F (-12°C to 7°C ) Evap Temp)
L = Low Temp 6 FPI (-40°F to 0°F(-40°C to -17°C ) Evap Temp)
V = Low Temp 4 FPI (-40°F to 0°F (-40°C to -17°C ) Evap Temp)
T P LP 3 15 L E S2 B R6 - PSC
STANDARD FEATURES
60Hz
Motor Designation:
PSC = PSC Permanent Split Capacitor
EC2 = EC Motor
Refrigerant Designation:
R2 = R407A / R407C / R22
R6 = R404A
R7 = R407A
Generation: B = 2
Voltage:
S1 = 115/1/60 (air defrost models only)
S2 = 208-230/1/60
S4 = 460/1/60 (2 to 6 fan models only)
T3 = 208-230/3/60
Defrost*:
A = Air E = Electric
nd
• Compatable with Low GWP Refrigerants
• PSC motors
• Streamlined cabinet style
• Higheciency,durablefanguard
• Front access
• Compact
• Internally enhanced tubing
• Spacious electrical and refrigeration compartments
• Low heater wattage
• Proven motor/fan/motor mount design
OPTIONAL FEATURES
• EC motors with patented SmartSpeed® Technology.
See page 16
• Heat exchanger - shipped loose
• Heresite Coating
• Factory installed expansion valve,
solenoid valve and room thermostat
• Schrader valve on suction header
• Positive slope, hinged drain pan
• Central drain connections (approximate)
• 3/4”IDUniversaldrainttingfor3/4”MPT
or3/4”aretting
• Factory installed distributor nozzle
• 460/1/60 PSC motor only
• Copper or GW Aluminum “Gold Coat” Fins
• Wire fan guard
• Painted Cabinet
Page 3
TPLP
PRE-ASSEMBLED FEATURES
60Hz
Thermostat Mounted
on Front of Unit
Solenoid Valve and
TXV Mounted
Solenoid Valve Wire
pulled through and
labeled on each end
Schrader Valve
Located Outside
Page 4
CAPACITY DATA - ALL MODELS
TPLP
Medium Temperature Models - Capacity @ 6 F.P.I. *
Medium Temp. Models 104M 106M 107M 209M 211M 214M 317M 320M 423M 426M 532M 639M
Number Of Fans 1 1 1 2 2 2 3 3 4 4 5 6
R407A
Capacity
BTUH
(WATTS)
Evap
Temp.
25°F
(-4°C)
R407C
R404A
R507
R22
Air Flow CFM (L/S)
Refrigerant **
Charge
R407A
LB. (KG)
Low Temperature Models - Capacity @ 6 F.P.I. *
Low Temp. Models 104L 105L 106L 207L 209L 211L 314L 317L 419L 422L 527L 631L
Number Of Fans 1 1 1 2 2 2 3 3 4 4 5 6
Capacity
BTUH
(WATTS)
Air Flow CFM (L/S)
Refrigerant **
Charge
Evap
Temp.
-20°F
(-29°C)
R407A
R407A
R404A
R507
LB. (KG)
4090 5230 6460 8170 10450 13300 16200 19000 21900 24700 30400 37100
(1197) (1530) (1891) (2394) (3059) (3895) (4731) (5567) (6403) (7230) (8902) (10830)
3870 4950 6120 7740 9900 12600 15400 18100 20800 23500 28900 35200
(1134) (1449) (1791) (2268) (2898) (3690) (4482) (5274) (6066) (6849) (8433) (10260)
4300 5500 6800 8600 11000 14000 17000 20000 23000 26000 32000 39000
(1260) (1610) (1990) (2520) (3220) (4100) (4980) (5860) (6740) (7610) (9370) (11400)
4090 5230 6460 8170 10500 13300 16200 19000 21900 24700 30400 37100
(1197) (1530) (1891) (2394) (3059) (3895) (4731) (5567) (6403) (7230) (8902) (10830)
1010
(470)
0.7
(0.3)
3610 4560 5510 7030 8550 10500 13300 16200 18100 20900 25700 29500
(1055) (1340) (1615) (2062) (2508) (3059) (3895) (4731) (5292) (6118) (7515) (8626)
3800 4800 5800 7400 9000 11000 14000 17000 19000 22000 27000 31000
(1110) (1410) (1700) (2170) (2640) (3220) (4100) (4980) (5570) (6440) (7910) (9080)
1010
(470)
0.7
(0.3)
950
(450)
1.1
(0.5)
950
(450)
1.1
(0.5)
900
(430)
1.5
(0.7)
900
(430)
1.5
(0.7)
2020
(950)
1.3
(0.6)
2020
(950)
1.3
(0.6)
1910
(900)
1.4
(0.6)
1910
(900)
1.4
(0.6)
1800
(850)
2.0
(1.2)
1800
(850)
2.0
(1.2)
2860
(1350)
3.0
(1.4)
2860
(1350)
3.0
(1.4)
2700
(1270)
4.0
(1.8)
2700
(1270)
4.0
(1.8)
3810
(1800)
3.9
(1.8)
3810
(1800)
3.9
(1.8)
60Hz
3600
(1700)
(2.4)
3600
(1700)
(2.4)
(2120)
3.3
(2120)
3.3
4500
6.5
(3.0)
4500
6.5
(3.0)
5400
(2550)
7.8
(3.5)
5400
(2550)
7.8
(3.5)
Low Temperature Models - Capacity @ 4 F.P.I. *
Low Temp. 4 FPI Models 103V 104V 105V 206V 208V 209V 312V 315V 416V 419V 523V 627V
Number Of Fans 1 1 1 2 2 2 3 3 4 4 5 6
Capacity
BTUH
(WATTS)
Air Flow CFM (L/S)
Refrigerant **
Charge
Capacities rated using 10°F (5.6°C) TD & 100°F (38°C) liquid temperature.
Capacities at other TD within a range of 8 to 15 °F (4.4 to 8.3°C) are directly proportional to TD, or use formula: Capacity = Rated capacity ÷ 10 x TD.
For capacities at TD outside of range 8 to 15 °F (4.4 to 8.3°C) , or liquid temperature lower than 75°F (24°) , consult factory .
Capacities for R407A and R407C are based on mean temperature. Mean temperature is the average temperature between the saturated suction
temperature and the temperature feeding the evaporator. For dew point ratings, consult factory.
* CAPACITY CORRECTION FACTORS FOR LOW TEMPERATURE UNITS
SATURATED SUCTION
TEMPERATURE °F (°C) 0 (-17.8)
NO CORRECTION FACTOR REQUIRED FOR MEDIUM TEMP. UNITS
Evap
Temp.
-20°F
(-29°C)
R407A
FACTOR 1.06 1.03 1.0 0.92 0.85
R407A
R404A
R507
LB. (KG)
2850 3900 4750 6080 7410 8840 11400 14300 15200 18100 21900 25700
(836) (1140) (1397) (1786) (2176) (2584) (3344) (4171) (4456) (5292) (6403) (7515)
3000 4100 5000 6400 7800 9300 12000 15000 16000 19000 23000 27000
(880) (1200) (1470) (1880) (2290) (2720) (3520) (4390) (4690) (5570) (6740) (7910)
1070
(510)
(0.3)
0.7
-10
(23.3)
1010
(480)
1.1
(0.5)
(450)
-20
(-28.9)
950
1.5
(0.7)
2140
(1010)
(0.6)
-30
(-34.4)
1.3
-40
(-40)
2020
(950)
1.4
(0.6)
1910
(900)
2.0
(1.2)
3030
(1430)
3.0
(1.4)
** REFRIGERANT CHARGE CONVERSION FACTORS
R407C R404A
0.99 0.92 0.93 1.02 1.03
2860
(1350)
4.0
(1.8)
4040
(1910)
3.9
(1.8)
R507
3810
(1800)
3.3
(2.4)
R22
4770
(2250)
R134a
6.5
(3.0)
5720
(2700)
7.8
(3.5)
Page 5
ELECTRICAL DATA
TPLP
MODEL FPI
104MAS1
106MAS1 1 1/15 1.0 100 1.3 15 1/15 1.0 60 1.3 15
107MAS1 1 1/15 1.0 100 1.3 15 1/15 1.0 60 1.3 15
209MAS1 2 1/15 2.0 200 2.3 15 1/15 2.0 120 2.3 15
211MAS1 2 1/15 2.0 200 2.3 15 1/15 2.0 120 2.3 15
214MAS1 2 1/15 2.0 200 2.3 15 1/15 2.0 120 2.3 15
317MAS1 3 1/15 3.0 300 3.3 15 1/15 3.0 180 3.3 15
320MAS1 3 1/15 3.0 300 3.3 15 1/15 3.0 180 3.3 15
423MAS1 4 1/15 4.0 400 4.3 15 1/15 4.0 240 4.3 15
426MAS1 4 1/15 4.0 400 4.3 15 1/15 4.0 240 4.3 15
532MAS1 5 1/15 5.0 500 5.3 15 1/15 5.0 300 5.3 15
639MAS1 6 1/15 6.0 600 6.3 15 1/15 6.0 360 6.3 15
QTY.
1 1/15 1.0 100 1.3 15 1/15 1.0 60 1.3 15
6
115/1/60 - AIR DEFROST MODELS
FAN MOTORS
PSC MOTORS EC MOTORS
HP
FLA
TOTAL
WATTS
MIN. CIRC.
AMPACITY (A)
MAX. FUSE
(AMPS)
HP
FLA
TOTAL
WATTS
AMPACITY (A)
60Hz
MIN. CIRC.
ELECTRICAL DATA
208-230/1/60 - AIR DEFROST MODELS
MAX. FUSE
(AMPS)
FAN MOTORS
MODEL FPI
104MAS2
106MAS2 1 1/15 0.5 100 0.6 15 1/15 0.6 60 0.8 15
107MAS2 1 1/15 0.5 100 0.6 15 1/15 0.6 60 0.8 15
209MAS2 2 1/15 1.0 200 1.1 15 1/15 1.2 120 1.4 15
211MAS2 2 1/15 1.0 200 1.1 15 1/15 1.2 120 1.4 15
214MAS2 2 1/15 1.0 200 1.1 15 1/15 1.2 120 1.4 15
317MAS2 3 1/15 1.5 300 1.6 15 1/15 1.8 180 2.0 15
320MAS2 3 1/15 1.5 300 1.6 15 1/15 1.8 180 2.0 15
423MAS2 4 1/15 2.0 400 2.1 15 1/15 2.4 240 2.6 15
426MAS2 4 1/15 2.0 400 2.1 15 1/15 2.4 240 2.6 15
532MAS2 5 1/15 2.5 500 2.6 15 1/15 3.0 300 3.2 15
639MAS2 6 1/15 3.0 600 3.1 15 1/15 3.6 360 3.8 15
QTY.
1 1/15 0.5 100 0.6 15 1/15 0.6 60 0.8 15
6
HP
FLA
TOTAL
PSC MOTORS EC MOTORS
WATTS
MIN. CIRC.
AMPACITY (A)
MAX. FUSE
(AMPS)
HP
FLA
TOTAL
WATTS
MIN. CIRC.
AMPACITY (A)
MAX. FUSE
(AMPS)
ELECTRICAL DATA
460/1/60 - AIR DEFROST MODELS
FAN MOTORS
MODEL FPI
209MAS4
211MAS4 2 1/15 0.8 200 0.9 15
214MAS4 2 1/15 0.8 200 0.9 15
317MAS4 3 1/15 1.2 300 1.3 15
320MAS4 3 1/15 1.2 300 1.3 15
423MAS4 4 1/15 1.6 400 1.7 15
426MAS4 4 1/15 1.6 400 1.7 15
532MAS4 5 1/15 2.0 500 2.1 15
639MAS4 6 1/15 2.4 600 2.5 15
6
QUANTITY
2 1/15 0.8 200 0.9 15
HP
FLA
TOTAL
PSC MOTORS
WATTS
MIN. CIRC.
AMPACITY (A)
MAX. FUSE
(AMPS)
Page 6
ELECTRICAL DATA -
208-230/1/60 & 208-230/3/60
60Hz TPLP
ELECTRIC DEFROST MODELS
FAN MOTORS DEFROST HEATERS
MODEL FPI
104ME*
106ME* 1 1/15 0.5 100 0.6 15 1/15 0.6 60 0.8 15 1060 4.6 5.8 15 3.0 3.8 15
107ME* 1 1/15 0.5 100 0.6 15 1/15 0.6 60 0.8 15 1060 4.6 5.8 15 3.0 3.8 15
209ME* 2 1/15 1.0 200 1.1 15 1/15 1.2 120 1.4 15 1890 8.2 10.3 15 5.3 6.7 15
211ME* 2 1/15 1.0 200 1.1 15 1/15 1.2 120 1.4 15 1890 8.2 10.3 15 5.3 6.7 15
214ME* 2 1/15 1.0 200 1.1 15 1/15 1.2 120 1.4 15 1890 8.2 10.3 15 5.3 6.7 15
317ME* 3 1/15 1.5 300 1.6 15 1/15 1.8 180 2.0 15 2730 11.9 14.8 15 7.7 10 15
320ME* 3 1/15 1.5 300 1.6 15 1/15 1.8 180 2.0 15 2730 11.9 14.8 15 7.7 10 15
423ME* 4 1/15 2.0 400 2.1 15 1/15 2.4 240 2.6 15 3560 15.5 19.3 20 10 12 15
426ME* 4 1/15 2.0 400 2.1 15 1/15 2.4 240 2.6 15 3560 15.5 19.3 20 10 12 15
532ME* 5 1/15 2.5 500 2.6 15 1/15 3.0 300 3.2 15 4400 19.1 23.9 25 12 15.1 20
639ME* 6 1/15 3.0 600 3.1 15 1/15 3.6 360 3.8 15 5230 22.7 28.4 30 15 18 20
104LE*
105LE* 1 1/15 0.5 100 0.6 15 1/15 0.6 60 0.75 15 1060 4.6 5.8 15 3.0 3.8 15
106LE* 1 1/15 0.5 100 0.6 15 1/15 0.6 60 0.75 15 1060 4.6 5.8 15 3.0 3.8 15
207LE* 2 1/15 1.0 200 1.1 15 1/15 1.2 120 1.4 15 1890 8.2 10.3 15 5.3 6.7 15
209LE* 2 1/15 1.0 200 1.1 15 1/15 1.2 120 1.4 15 1890 8.2 10.3 15 5.3 6.7 15
211LE* 2 1/15 1.0 200 1.1 15 1/15 1.2 120 1.4 15 1890 8.2 10.3 15 5.3 6.7 15
314LE* 3 1/15 1.5 300 1.6 15 1/15 1.8 180 2.0 15 2730
317LE* 3 1/15 1.5 300 1.6 15 1/15 1.8 180 2.0 15 2730 11.9 14.8 15 7.7 10
419LE* 4 1/15 2.0 400 2.1 15 1/15 2.4 240 2.6 15 3560 15.5 19.3 20 10 12 15
422LE* 4 1/15 2.0 400 2.1 15 1/15 2.4 240 2.6 15 3560 15.5 19.3 20 10 12 15
527LE* 5 1/15 2.5 500 2.6 15 1/15 3.0 300 3.2 15 4400 19.1 23.9 25 12 15.1 20
631LE* 6 1/15 3.0 600 3.1 15 1/15 3.6 360 3.8 15 5230 22.7 28.4 30 15 18 20
103VE*
104VE* 1 1/15 0.5 100 0.6 15 1/15 0.6 60 0.75 15 1060 4.6 5.8 15 3.0 3.8 15
105VE* 1 1/15 0.5 100 0.6 15 1/15 0.6 60 0.75 15 1060 4.6 5.8 15 3.0 3.8 15
206VE* 2 1/15 1.0 200 1.1 15 1/15 1.2 120 1.4 15 1890 8.2 10.3 15 5.3 6.7 15
208VE* 2 1/15 1.0 200 1.1 15 1/15 1.2 120 1.4 15 1890 8.2 10.3 15 5.3 6.7 15
209VE* 2 1/15 1.0 200 1.1 15 1/15 1.2 120 1.4 15 1890 8.2 10.3 15 5.3 6.7 15
312VE* 3 1/15 1.5 300 1.6 15 1/15 1.8 180 2.0 15 2730 11.9 14.8 15 7.7 10 15
315VE* 3 1/15 1.5 300 1.6 15 1/15 1.8 180 2.0 15 2730 11.9 14.8 15 7.7 10 15
416VE* 4 1/15 2.0 400 2.1 15 1/15 2.4 240 2.6 15 3560 15.5 19.3 20 10 12 15
419VE* 4 1/15 2.0 400 2.1 15 1/15 2.4 240 2.6 15 3560 15.5 19.3 20 10 12 15
523VE* 5 1/15 2.5 500 2.6 15 1/15 3.0 300 3.2 15 4400 19.1 23.9 25 12 15.1 20
627VE* 6 1/15 3.0 600 3.1 15 1/15 3.6 360 3.8 15 5230 22.7 28.4 30 15 18 20
* = S2 or T3. Refer to Nomenclature for details
QTY.
HP
1 1/15 0.5 100 0.6 15 1/15 0.6 60 0.8 15 1060 4.6 5.8 15 3.0 3.8 15
6
1 1/15 0.5 100 0.6 15 1/15 0.6 60 0.75 15 1060 4.6 5.8 15 3.0 3.8 15
6
1 1/15 0.5 100 0.6 15 1/15 0.6 60 0.75 15 1060 4.6 5.8 15 3.0 3.8 15
4
PSC MOTORS EC MOTORS
FLA
TOTAL
WATTS
MCA
(A)
MAX.
FUSE
(AMPS)
HP
FLA
TOTAL
WATTS
MCA
(A)
MAX.
FUSE
(AMPS)
TOTAL
WATTS
208-230/1/60 208-230/3/60
MCA
(A)
MAX.
FUSE
(AMPS)
TOTAL
AMPS
MCA
(A)
TOTAL
AMPS
11.9 14.8 15 7.7 10 15
(AMPS)
MAX.
FUSE
15
Page 7
ELECTRICAL DATA - 460/1/60
TPLP
MODEL FPI
209MES4
211MES4 2 1/15 0.8 200 0.9 15 1890 4.1 5.1 15
214MES4 2 1/15 0.8 200 0.9 15
317MES4 3 1/15 1.2 300 1.3 15
320MES4 3 1/15 1.2 300 1.3 15
423MES4 4 1/15 1.6 400 1.7 15
426MES4 4 1/15 1.6 400 1.7 15
532MES4 5 1/15 2.0 500 2.1 15 4400 9.6 12.0 15
639MES4 6 1/15 2.4 600 2.5 15 5230 11.4 14.2 15
207LES4
209LES4 2 1/15 0.8 200 0.9 15 1890 4.1 5.1 15
211LES4 2 1/15 0.8 200 0.9 15
314LES4 3 1/15 1.2 300 1.3 15
317LES4 3 1/15 1.2 300 1.3 15
419LES4 4 1/15 1.6 400 1.7 15
422LES4 4 1/15 1.6 400 1.7 15
527LES4 5 1/15 2.0 500 2.1 15 4400 9.6 12.0 15
631LES4 6 1/15 2.4 600 2.5 15 5230 11.4 14.2 15
206VES4
208VES4 2 1/15 0.8 200 0.9 15 1890 4.1 5.1 15
209VES4 2 1/15 0.8 200 0.9 15
312VES4 3 1/15 1.2 300 1.3 15
315VES4 3 1/15 1.2 300 1.3 15
416VES4 4 1/15 1.6 400 1.7 15
419VES4 4 1/15 1.6 400 1.7 15
523VES4 5 1/15 2.0 500 2.1 15 4400 9.6 12.0 15
627VES4 6 1/15 2.4 600 2.5 15 5230 11.4 14.2 15
QTY.
2 1/15 0.8 200 0.9 15
6
2 1/15 0.8 200 0.9 15
6
2 1/15 0.8 200 0.9 15
4
ELECTRIC DEFROST MODELS
FAN MOTORS DEFROST HEATERS
HP
FLA
TOTAL
PSC MOTORS
WATTS
MCA
(A)
MAX. FUSE
(AMPS)
TOTAL
WATTS
1890 4.1 5.1 15
1890 4.1 5.1 15
2730 5.9 7.4 15
2730 5.9 7.4 15
3560 7.7 9.7 15
3560 7.7 9.7 15
1890 4.1 5.1 15
1890 4.1 5.1 15
2730 5.9 7.4 15
2730 5.9 7.4 15
3560 7.7 9.7 15
3560 7.7 9.7 15
1890 4.1 5.1 15
1890 4.1 5.1 15
2730 5.9 7.4 15
2730 5.9 7.4 15
3560 7.7 9.7 15
3560 7.7 9.7 15
TOTAL
AMPS
60Hz
MCA
(A)
MAX. FUSE
(AMPS)
Page 8
CONDUCTORS/WIRING
AND NATIONAL CODES.
-TERMINAL BLOCK TERMINAL
ALL FIELD WIRING MUST BE DONE IN
COMPLIANCE WITH ALL APPLICABLE LOCAL
-COMPONENT TERMINAL
4). MAY BE FACTORY INSTALLED-MOUNTED AND
3). OVERCURRENT PROTECTION FOR
1). USE COPPER CONDUCTORS ONLY
VALUE SHOWN ON EVAPORATOR NAMEPLATE.
HEATERS MUST NOT EXCEED MAXIMUM
EVAPORATOR FAN MOTORS AND DEFROST
2). USE 75°C WIRE (OR HIGHER)
WIRED ON EVAPORATOR .
NOTES
TERMINALS
OPTIONAL FACTORY OR
1-LP AIR 09/06
BY OTHERS
WIRING BY OTHERS
FACTORY WIRING
WITHOUT DEFROST TIME CLOCK
REQUIREMENTS
REFER TO EVAPORATOR
NAMEPLATE FOR ELECTRICAL
L1
PARAGON # 8145
DEFROST CLOCK
OR EQUIVALENT
THERMOSTAT
CIRCUIT
FUSE OR
NOTE #3
BREAKER
SWITCH
PUMP DOWN
(IF USED)
NOTE #4
SPACE
LIQUID LINE
SOLENOID VALVE
NOTE #4
N.C.
WITH DEFROST TIME CLOCK
GND
L1
GND
SOLENOID VALVE
THERMOSTAT
BREAKER
NOTE #3
FUSE OR
CIRCUIT
SPACE
NOTE #4
IF(N)
2ND FUSE
OMIT
LIQUID LINE
NOTE #4
N.C.
L2(N)
1
TM
3
2
4X
N
REFER TO
EVAPORATOR
DATA PLATE
FOR MOTOR
QUANTITY
GND.
FAN
MTR
FAN
MTR
FAN
MTR
EVAPORATOR
TERMINAL BOARD
F
4
FAN MOTOR
POWER
PLUGS
FAN
MTR
FAN
MTR
FAN
MTR
F
GND.
4
TERMINAL BOARD
REFER TO
EVAPORATOR
DATA PLATE
FOR MOTOR
QUANTITY
FAN MOTOR
POWER
PLUGS
EVAPORATOR
IF(N)
OMIT 2ND
L2(N)
4
F
TO MULTIPLE EVAPS
(IF APPLIC)
4
F
EVAPORATORS (IF APPLIC)
TO MULTIPLE
FUSE
GND
REQUIREMENTS
REFER TO EVAPORATOR
NAMEPLATE FOR ELECTRICAL
TPLP
WIRING DIAGRAM - 115/1/60, 208-230/1/60
STANDARD PSC MOTORS
AIR DEFROST MODELS
PSC
60Hz
Page 9
CONDUCTORS/WIRING
AND NATIONAL CODES.
-TERMINAL BLOCK TERMINAL
ALL FIELD WIRING MUST BE DONE IN
COMPLIANCE WITH ALL APPLICABLE LOCAL
-COMPONENT TERMINAL
4). MAY BE FACTORY INSTALLED-MOUNTED AND
3). OVERCURRENT PROTECTION FOR
1). USE COPPER CONDUCTORS ONLY
VALUE SHOWN ON EVAPORATOR NAMEPLATE.
HEATERS MUST NOT EXCEED MAXIMUM
EVAPORATOR FAN MOTORS AND DEFROST
2). USE 75°C WIRE (OR HIGHER)
WIRED ON EVAPORATOR .
NOTES
TERMINALS
OPTIONAL FACTORY OR
6-LP 460 AIR 09/06
BY OTHERS
WIRING BY OTHERS
FACTORY WIRING
WITHOUT DEFROST TIME CLOCK
L1
PARAGON # 8145
DEFROST CLOCK
OR EQUIVALENT
THERMOSTAT
CIRCUIT
FUSE OR
NOTE #3
BREAKER
SWITCH
PUMP DOWN
(IF USED)
NOTE #4
SPACE
LIQUID LINE
SOLENOID VALVE
NOTE #4
N.C.
WITH DEFROST TIME CLOCK
380/400-1-50Hz
CONTROL VOLTAGE
GND
L1
GND
IF(N)
2ND FUSE
OMIT
L2
1
TM
3
2
4X
N
REFER TO
EVAPORATOR
DATA PLATE
FOR MOTOR
QUANTITY
GND.
FAN
MTR
FAN
MTR
FAN
MTR
EVAPORATOR
FAN MOTOR
POWER
PLUGS
FAN
MTR
FAN
MTR
FAN
MTR
M2
GND.
M1
TERMINAL BOARD
REFER TO
EVAPORATOR
DATA PLATE
FOR MOTOR
QUANTITY
FAN MOTOR
POWER
PLUGS
EVAPORATOR
IF(N)
OMIT 2ND
L2
TO MULTIPLE
EVAPORATORS (IF APPLIC)
M1
M2
EVAPORATORS (IF APPLIC)
TO MULTIPLE
FUSE
GND
4
N
GND
L2(N)
L1
460-1-60 Hz
M2
M1
TERMINAL BOARD
N
4
THERMOSTAT
NOTE #4
N.C.
SOLENOID VALVE
SPACE
LIQUID LINE
NOTE #4
GND
L1
L2(N)
460-1-60 Hz
380/400-1-50Hz
CONTROL VOLTAGE
M1
M2
NOTE #3
CIRCUIT
BREAKER
FUSE OR
TPLP
WIRING DIAGRAM - 460/1/60
STANDARD PSC MOTORS
AIR DEFROST MODELS
PSC
60Hz
Page 10
WARNING
EVAP FIELD MODIFICATION
MUST BE MADE
REFER TO EVAPORATOR
COMPR INTERLOCK
FOR ALL MODELS WITHOUT DEFROST HEATER CONTACTOR
THERMOSTAT
NOTE #4
EVAPORATOR FAN MOTORS AND
DEFROST HEATERS MUST NOT EXCEED
1). USE COPPER CONDUCTORS ONLY
3). OVERCURRENT PROTECTION FOR
MAXIMUM VALUE SHOWN ON
EVAPORATOR NAMEPLATE.
NOTES
2). USE 75°C WIRE (OR HIGHER)
FAN
MTR
DEFROST TERMINATION
CONTROL
(10.0A MAX.)
& FAN DELAY
FD-FAN DELAY
DT-DEFROST TERM
X
F
4
BK
GND.
C
FD
DT
BN
RD
(IF USED)
SWITCH
OR EQUIVALENT
PUMP DOWN
SPACE
(IF USED)
2 1
N
TM
4X
3
DEFROST CLOCK
PARAGON # 8145
EVAPORATOR
OPTIONAL FACTORY
FACTORY WIRING
WIRING BY OTHERS
ALL FIELD WIRING MUST BE DONE IN
COMPLIANCE WITH ALL APPLICABLE LOCAL
AND NATIONAL CODES.
2-LP ED 12/07
-TERMINAL BLOCK TERMINAL
-COMPONENT TERMINAL
CONDUCTORS/WIRING
TERMINALS
DATA PLATE FOR
MOTOR QUANTITY
EVAPORATOR
REFER TO
POWER PLUGS
FAN MOTOR
H2
H1
NOTE #4
SOL VALVE
L2 L1
N.C.
LIQUID LINE
GND
NAMEPLATE FOR ELECTRICAL
REQUIREMENTS
OR BY OTHERS
AND WIRED ON EVAPORATOR
4.) MAY BE FACTORY INSTALLED-MOUNTED
DEFROST HEATERS
CIRCUIT
BREAKER
FUSE OR
USING MAXIMUM 15A HEATER OVERCURRENT PROTECTION
15A
N
1
FAN
MTR
2
FAN
MTR
6
H3
3
WH
YL
ORANGE JUMPER
SWITCH
LIMIT
HEATER
(10.0A MAX.)
1
2
FROM H2 TO N
INSTALL ORANGE JUMPER
(SUPPLIED LOOSE)
N TO H1 AS SHOWN
RELOCATE WHITE WIRE FROM
2
1
SEE NOTE:
TPLP
WIRING DIAGRAM - 208-230/1/60
STANDARD PSC MOTORS
PSC
60Hz
ELECTRIC DEFROST MODELS - SINGLE EVAPORATOR 10A MAX.
Page 11
COMPR INTERLOCK
FOR ALL MODELS USING DEFROST HEATER CONTACTOR
THERMOSTAT
NOTE #4
EVAPORATOR FAN MOTORS AND
DEFROST HEATERS MUST NOT EXCEED
1). USE COPPER CONDUCTORS ONLY
3). OVERCURRENT PROTECTION FOR
MAXIMUM VALUE SHOWN ON
EVAPORATOR NAMEPLATE.
NOTES
2). USE 75°C WIRE (OR HIGHER)
(IF USED)
SWITCH
OR EQUIVALENT
PUMP DOWN
SPACE
(IF USED)
2 1
N
TM
4X
3
DEFROST CLOCK
PARAGON # 8145
OPTIONAL FACTORY
FACTORY WIRING
WIRING BY OTHERS
ALL FIELD WIRING MUST BE DONE IN
COMPLIANCE WITH ALL APPLICABLE LOCAL
AND NATIONAL CODES.
3-LP ED CONTACTOR SINGLE 12/07
-TERMINAL BLOCK TERMINAL
-COMPONENT TERMINAL
CONDUCTORS/WIRING
TERMINALS
NOTE #4
SOL VALVE
N.C.
LIQUID LINE
OR BY OTHERS
AND WIRED ON EVAPORATOR
4.) MAY BE FACTORY INSTALLED-MOUNTED
CIRCUIT
BREAKER
NOTE #3
FUSE OR
CONTACTOR
DEFROST HEATER
T2
T1
C
L2
L1
NOTE #3
BREAKER
FUSE OR
CIRCUIT
GND
L2 L1
YL
(10.0A MAX.)
REFER TO
POWER PLUGS
MOTOR QUANTITY
DATA PLATE FOR
EVAPORATOR
FAN MOTOR
N
3
X
F
4
6 2 1
DEFROST TERMINATION
FD-FAN DELAY
DT-DEFROST TERM
FAN
MTR
GND.
BK
FAN
MTRM TR
FAN
RD
C
(10.0A MAX.)
CONTROL
& FAN DELAY
FD
DT
BN
LIMIT
SWITCH
HEATER
WH
H3
H2
H1
EVAPORATOR
DEFROST HEATERS
REFER TO EVAPORATOR NAMEPLATE
FOR ELECTRICAL REQUIREMENTS
TPLP
ELECTRIC DEFROST MODELS - SINGLE EVAPORATOR
WIRING DIAGRAM - 208-230/1/60
STANDARD PSC MOTORS
PSC
60Hz
Page 12
COMPR INTERLOCK
FOR ALL MODELS USING 3 PHASE DEFROST HEATER CONTACTOR
THERMOSTAT
NOTE #4
EVAPORATOR FAN MOTORS AND
DEFROST HEATERS MUST NOT EXCEED
1). USE COPPER CONDUCTORS ONLY
3). OVERCURRENT PROTECTION FOR
MAXIMUM VALUE SHOWN ON
EVAPORATOR NAMEPLATE.
NOTES
2). USE 75°C WIRE (OR HIGHER)
(IF USED)
SWITCH
OR EQUIVALENT
PUMP DOWN
SPACE
(IF USED)
2 1
N
TM
4X
3
DEFROST CLOCK
PARAGON # 8145
OPTIONAL FACTORY
FACTORY WIRING
WIRING BY OTHERS
ALL FIELD WIRING MUST BE DONE IN
COMPLIANCE WITH ALL APPLICABLE LOCAL
AND NATIONAL CODES.
3A-LP ED 3ph.CONTACTOR SINGLE 12/07
-TERMINAL BLOCK TERMINAL
-COMPONENT TERMINAL
CONDUCTORS/WIRING
TERMINALS
NOTE #4
SOL VALVE
N.C.
LIQUID LINE
OR BY OTHERS
AND WIRED ON EVAPORATOR
4.) MAY BE FACTORY INSTALLED-MOUNTED
CIRCUIT
BREAKER
NOTE #3
FUSE OR
CONTACTOR
DEFROST HEATER
T2
T1
C
L2
L1
NOTE #3
BREAKER
FUSE OR
CIRCUIT
GND
L2 L1
L3
T3
L3
DEFROST HEATERS
H1
H2 H3
DATA PLATE FOR
MOTOR QUANTITY
12 6
3
N
F
4
X
DT
CONTROL
(10.0A MAX.)
FD
& FAN DELAY
DT-DEFROST TERM
DEFROST TERMINATION
FD-FAN DELAY
MTR
FAN
MTR
FAN
GND.
BK
BN
SWITCH
(10.0A MAX.)
MTR
FAN
FAN MOTOR
REFER TO
EVAPORATOR
POWER PLUGS
HEATER
LIMIT
RD
WH
C
YL
EVAPORATOR
REFER TO EVAPORATOR NAMEPLATE
FOR ELECTRICAL REQUIREMENTS
TPLP
ELECTRIC DEFROST MODELS - SINGLE EVAPORATOR
WIRING DIAGRAM - 208-230/3/60
STANDARD PSC MOTORS
PSC
60Hz
Page 13
WIRING DIAGRAM - 460/1/60
REFER TO EVAPORATOR NAMEPLATE
FOR ELECTRICAL REQUIREMENTS
COMPR INTERLOCK
FOR ALL 460V MODELS USING DEFROST HEATER AND FAN CONTACTORS
THERMOSTAT
NOTE #4
EVAPORATOR FAN MOTORS AND
DEFROST HEATERS MUST NOT EXCEED
1). USE COPPER CONDUCTORS ONLY
3). OVERCURRENT PROTECTION FOR
MAXIMUM VALUE SHOWN ON
EVAPORATOR NAMEPLATE.
NOTES
2). USE 75°C WIRE (OR HIGHER)
MTR
FAN FAN
MTR
FAN
MTR
M2
M1
GND.
(IF USED)
SWITCH
OR EQUIVALENT
PUMP DOWN
SPACE
(IF USED)
BREAKER
2 1
N
NOTE #3
TM
4X
3
CIRCUIT
FUSE OR
DEFROST CLOCK
PARAGON # 8145
EVAPORATOR
OPTIONAL FACTORY
FACTORY WIRING
WIRING BY OTHERS
ALL FIELD WIRING MUST BE DONE IN
COMPLIANCE WITH ALL APPLICABLE LOCAL
AND NATIONAL CODES.
7-LP ED CONTACTOR SINGLE 12/07
-TERMINAL BLOCK TERMINAL
-COMPONENT TERMINAL
CONDUCTORS/WIRING
TERMINALS
DATA PLATE FOR
MOTOR QUANTITY
EVAPORTOR
REFER TO
POWER PLUGS
FAN MOTOR
NOTE #4
SOL VALVE
L2 L1
N.C.
LIQUID LINE
L2
T2
L1
C
T1
GND
OR BY OTHERS
AND WIRED ON EVAPORATOR
4.) MAY BE FACTORY INSTALLED-MOUNTED
CIRCUIT
BREAKER
NOTE #3
FUSE OR
GND
L2(N)
L1
CONTACTOR
DEFROST HEATER
EVAP FAN
C
CONTACTOR
T2
T1
L2
L1
COIL DEFROST HEATERS
H1 H2
DEFROST TERMINATION
CONTROL
& FAN DELAY
(10.0A MAX.)
FD-FAN DELAY
DT-DEFROST TERM
BK
FD
BN
DT
C
RD
3
X
N
4
F
YL
(10.0A MAX.)
LIMIT
SWITCH
HEATER
WH
TPLP
STANDARD PSC MOTORS
ELECTRIC DEFROST MODELS - SINGLE EVAPORATOR
PSC
60Hz
Page 14
MUST BE MADE
EVAP#2 FIELD MODIFICATION
WARNING
COMPR INTERLOCK
FOR ALL MODELS USING DEFROST HEATER CONTACTOR
THERMOSTAT
NOTE #4
EVAPORATOR FAN MOTORS AND
DEFROST HEATERS MUST NOT EXCEED
1). USE COPPER CONDUCTORS ONLY
3). OVERCURRENT PROTECTION FOR
MAXIMUM VALUE SHOWN ON
EVAPORATOR NAMEPLATE.
NOTES
2). USE 75°C WIRE (OR HIGHER)
MTR
FAN FAN
MTR
FAN
MTR
DEFROST TERMINATION
CONTROL
(10.0A MAX.)
& FAN DELAY
FD-FAN DELAY
DT-DEFROST TERM
X
F
4
BK
GND.
C
FD
DT
BN
RD
(IF USED)
SWITCH
OR EQUIVALENT
PUMP DOWN
SPACE
(IF USED)
BREAKER
2 1
N
NOTE #3
TM
4X
3
CIRCUIT
FUSE OR
DEFROST CLOCK
PARAGON # 8145
EVAPORATOR
OPTIONAL FACTORY
FACTORY WIRING
WIRING BY OTHERS
ALL FIELD WIRING MUST BE DONE IN
COMPLIANCE WITH ALL APPLICABLE LOCAL
AND NATIONAL CODES.
4-LP ED CONTACTOR MULTI 12/07
-TERMINAL BLOCK TERMINAL
-COMPONENT TERMINAL
CONDUCTORS/WIRING
TERMINALS
DATA PLATE FOR
MOTOR QUANTITY
EVAPORATOR
REFER TO
POWER PLUGS
FAN MOTOR
H2
NOTE #4
SOL VALVE
L2
L1
N.C.
LIQUID LINE
L2
T2
L1
C
T1
GND
OR BY OTHERS
AND WIRED ON EVAPORATOR
4.) MAY BE FACTORY INSTALLED-MOUNTED
DEFROST HEATERS
CIRCUIT
BREAKER
NOTE #3
FUSE OR
DEFROST HEATER
CONTACTOR
EVAPORATOR
MTR
FAN
MTR
FAN FAN
MTR
FAN MOTOR
POWER PLUGS
EVAPORATOR
MOTOR QUANTITY
DATA PLATE FOR
REFER TO
GND.
4
DT
RD
DEFROST TERMINATION
DT-DEFROST TERM
FD-FAN DELAY
(10.0A MAX.)
CONTROL
& FAN DELAY
BK
FD
C
DEFROST HEATERS
F
X
BN
* Remove & Insulate
* Fan delay not used on second evap / use fan contactor if total fan amps exceeds 10A
PRIMARY
SECONDARY
FUSE OR
BREAKER
NOTE #3
CIRCUIT
H1 NH 2
H1 N
LIMIT
YL
3
(10.0A MAX.)
SWITCH
HEATER
WH
LIMIT
YL
3
(10.0A MAX.)
SWITCH
HEATER
WH
REFER TO EVAPORATOR NAMEPLATE
FOR ELECTRICAL REQUIREMENTS
RELOCATE WHITE WIRE FROM
N AS SHOWN
SEE NOTE:
1
1
REMOVE AND INSULATE
2
AS SHOWN
2
TPLP
ELECTRIC DEFROST MODELS - MULTIPLE EVAPORATORS
WIRING DIAGRAM - 208-230/1/60
STANDARD PSC MOTORS
PSC
60Hz
Page 15
WARNING
EVAP#2 FIELD MODIFI-
CATION MUST BE MADE
COMPR INTERLOCK
FOR ALL 460V MODELS USING DEFROST HEATER AND FAN CONTACTORS
THERMOSTAT
NOTE #4
EVAPORATOR FAN MOTORS AND
DEFROST HEATERS MUST NOT EXCEED
1). USE COPPER CONDUCTORS ONLY
3). OVERCURRENT PROTECTION FOR
MAXIMUM VALUE SHOWN ON
EVAPORATOR NAMEPLATE.
NOTES
2). USE 75°C WIRE (OR HIGHER)
MTR
FAN FAN
MTR
FAN
MTR
M2
M1
GND.
(IF USED)
SWITCH
OR EQUIVALENT
PUMP DOWN
SPACE
(IF USED)
BREAKER
2 1
N
NOTE #3
TM
4X
3
CIRCUIT
FUSE OR
DEFROST CLOCK
PARAGON # 8145
EVAPORATOR
OPTIONAL FACTORY
FACTORY WIRING
WIRING BY OTHERS
ALL FIELD WIRING MUST BE DONE IN
COMPLIANCE WITH ALL APPLICABLE LOCAL
AND NATIONAL CODES.
8-LP 460v ED CONTACTOR MULTI 09/06
-TERMINAL BLOCK TERMINAL
-COMPONENT TERMINAL
CONDUCTORS/WIRING
TERMINALS
DATA PLATE FOR
MOTOR QUANTITY
EVAPORATOR
REFER TO
POWER PLUGS
FAN MOTOR
NOTE #4
SOL VALVE
L2
L1
N.C.
LIQUID LINE
L2
T2
L1
C
T1
GND
OR BY OTHERS
AND WIRED ON EVAPORATOR
4.) MAY BE FACTORY INSTALLED-MOUNTED
CIRCUIT
BREAKER
NOTE #3
FUSE OR
GND
L2(N)
L1
CONTACTOR
DEFROST HEATER
EVAP FAN
C
CONTACTOR
T2
T1
L2
L1
MTR
FAN
MTR
FAN
GND.
M1
M2
EVAPORATOR
REFER TO
EVAPORATOR
MOTOR QUANTITY
DATA PLATE FOR
MTR
FAN
POWER PLUGS
FAN MOTOR
NOTE #3
FUSE OR
CIRCUIT
BREAKER
PRIMARY
SECONDARY
* Note: Fan Delay not used on second evap
DEFROST HEATERS
H1 H2
DEFROST TERMINATION
DT-DEFROST TERM
FD-FAN DELAY
CONTROL
(10.0A MAX.)
BK
FD
& FAN DELAY
C
RD
X
4
BN
DT
N
DEFROST TERMINATION
DT-DEFROST TERM
FD-FAN DELAY
CONTROL
(10.0A MAX.)
BK
FD
& FAN DELAY
C
RD
X
4
BN
DT
N
DEFROST HEATERS
H1 H2
*
HEATER
SWITCH
LIMIT
(10.0A MAX.)
YL
WH
3
3
F
F
(10.0A MAX.)
LIMIT
SWITCH
HEATER
YL
WH
N AS SHOWN
RELOCATE WHITE WIRE FROM
1
1
REFER TO EVAPORATOR NAMEPLATE
FOR ELECTRICAL REQUIREMENTS
TPLP
ELECTRIC DEFROST MODELS - MULTIPLE EVAPORATORS
WIRING DIAGRAM - 460/1/60
STANDARD PSC MOTORS
PSC
60Hz
Page 16
TPLP
RE F RI G E RA T I O N = F ULL SP E E D = 6 0 W P E R M OT OR
O FF CY CL E = L O W S P EED = 1 3 W P E R M OT OR
40 % E X T R A E N E R G Y S AV I N G S v s . F I X E D S P E E D E C M OT OR ON E V AP OR AT OR
10 % E X T R A E N E RG Y SA V I N G S O N C O M P RE SSO R W H E N USI N G SM A R TSP E E D E V AP OR AT OR
D E S IGN H IGH L IGH T S
NO CO M P L E X C O N T RO LS, N O C O ST A D D E R, SI M P LE T O UN D E RST A N D
P ATE N T
P END I NG
US Patent No.
8,635,883
DESIGN FEATURES
• Standard on all EC Motors
ECM
60Hz
• Refrigeration mode – EC motor operates at full speed.
•OCyclemode–ECmotoroperatesatreducedspeed.
• NO special controls required.
Consumption 60 W per motor
Consumption 13 W per motor.
•Energysavingbenetonmotorandcompressorwattageconsumption:
20000
ENERGY CONSUMPTION COMPA RISON:
ADDITIONAL ENERGY SAVINGS WHEN
USING SMARTSPEED EVAPS
-Hours)
18000
16000
14000
12000
10000
8000
6000
with PSC vs ECM vs SmartSpeed Evaporator Fan Motors
Compressor w/ PSC
Compressor w/ ECM
Compressor w/ SmartSpeed
4000
2000
0
0 50 100 150 200 250 300 350 400 450 500
Time (minutes)
Note: Data collected on a typical freezer application with a 3HP low temp condensing unit and a 4 fan TPLP evaporator
EVAP w/ ECM
INSTALLATION NOTES
EC motors are factory wired for SmartSpeed operation on evaporators equipped with
a factory installed thermostat.
For SmartSpeed operation on Evaporators without a factory installed thermostat,
aeldwiredSPDTtypethermostatisrequired.
Page 17
TPLP
WIRING DIAGRAM - 115/1/60, 208-230/1/60
OPTIONAL EC MOTORS with
AIR DEFROST MODELS
ECM
60Hz
Page 18
TPLP
WIRING DIAGRAM - 208-230/1/60
OPTIONAL EC MOTORS with
ELECTRIC DEFROST MODELS
ECM
60Hz
Page 19
TPLP
ELECTRIC DEFROST MODELS - MULTIPLE EVAPORATORS
WIRING DIAGRAM - 208-230/1/60
OPTIONAL EC MOTORS with
ECM
60Hz
Page 20
TPLP
SHIPPING WEIGHTS
60Hz
Air Defrost Models
MODEL
NUMBER
104MA 45 (20)
106MA 47 (21)
107MA 49 (22)
209MA 70 (32)
211MA 74 (33)
214MA 78 (35)
317MA 101 (46)
320MA 107 (48)
423MA 117 (53)
426MA 135 (61)
532MA 163 (74)
639MA 192 (87)
SHIPPING WEIGHT
LB. (kg)
Electric Defrost Models
MODEL NUMBER
104ME 104LE 103VE 49 (22)
106ME 105LE 104VE 51 (23)
107ME 106LE 105VE 53 (24)
209ME 207LE 206VE 76 (34)
211ME 209LE 208VE 80 (36)
214ME 211LE 209VE 84 (38)
317ME 314LE 312VE 109 (49)
320ME 317LE 315VE 115 (52)
423ME 419LE 416VE 127 (58)
426ME 422LE 419VE 145 (66)
532ME 527LE 523VE 176 (80)
639ME 631LE 627VE 207 (94)
SHIPPING WEIGHT
LB. (kg)
Page 21
.438 SLOTS IN
MOUNTING BRACKETS
AIR THROW
APPROX 35'
IN OPEN
SPACE
12
MINIMUM
11 7/83 1/8
3
[305][ 302] [79]
[76]
[403]
15 7/8
[35]
1 3/8
3/4 MPT / 3/4 FLARE
DRAIN CONNECTION
4, 5 AND 6 FAN
MODELS.
6 1/2
C
A
B
[165 ]
MTG SLOTS
13 7/16
[341]
(TOP VIEW)
REFRIGERATION
CONNECTIONS.
SUCTION & LIQUID.
ELECTRICAL
CONNECTIONS.
A
B
13 7/16
MTG SLOTS
[165]
[165]
6 1/2 6 1/2
4
TYP
[102]
[341]
1, 2 AND 3 FAN
MODELS.
(TOP VIEW)
TPLP
DIMENSIONAL DATA
60Hz
LIQUID CONNECTION (ID)
SWEAT
R407A
R22
R404A
MODEL
NO. OF
FANS
A B C
IN (mm) IN (mm) IN (mm)
SUCTION
CONNECTION
(ID) SWEAT
104M^ 1 30 1/4 (768) 17 1/4 (438) N/A N/A 5/8 3/8 3/8
106M^ 1 30 1/4 (768) 17 1/4 (438) N/A N/A 5/8 3/8 3/8
107M^ 1 30 1/4 (768) 17 1/4 (438) N/A N/A 5/8 3/8 3/8
209M^ 2 46 1/4 (1175) 33 1/4 (845) N/A N/A 7/8 3/8 3/8
211M^ 2 46 1/4 (1175) 33 1/4 (845) N/A N/A 7/8 3/8 3/8
214M^ 2 46 1/4 (1175) 33 1/4 (845) N/A N/A 7/8 3/8 3/8
317M^ 3 62 1/4 (1581) 49 1/4 (1251) N/A N/A 7/8 3/8 3/8
320M^ 3 62 1/4 (1581) 49 1/4 (1251) N/A N/A 7/8 3/8 3/8
423M^ 4 78 1/4 (1988) 32 5/8 (829) 32 5/8 (829) 1 1/8 3/8 3/8
426M^ 4 78 1/4 (1988) 32 5/8 (829) 32 5/8 (829) 1 1/8 3/8 1/2
532M^ 5 94 1/4 (2394) 32 5/8 (829) 48 5/8 (1235) 1 3/8 1/2 1/2
639M^ 6 110 1/4 (2800) 48 5/8 (1235) 48 5/8 (1235) 1 3/8 1/2 1/2
104L^ 1 30 1/4 (768) 17 1/4 (438) N/A N/A 5/8 3/8 3/8
105L^ 1 30 1/4 (768) 17 1/4 (438) N/A N/A 5/8 3/8 3/8
106L^ 1 30 1/4 (768) 17 1/4 (438) N/A N/A 5/8 3/8 3/8
207L^ 2 46 1/4 (1175) 33 1/4 (845) N/A N/A 7/8 3/8 3/8
209L^ 2 46 1/4 (1175) 33 1/4 (845) N/A N/A 7/8 3/8 3/8
211L^ 2 46 1/4 (1175) 33 1/4 (845) N/A N/A 7/8 3/8 3/8
314L^ 3 62 1/4 (1581) 49 1/4 (1251) N/A N/A 7/8 3/8 3/8
317L^ 3 62 1/4 (1581) 49 1/4 (1251) N/A N/A 1 1/8 3/8 3/8
419L^ 4 78 1/4 (1988) 32 5/8 (829) 32 5/8 (829) 1 1/8 3/8 3/8
422L^ 4 78 1/4 (1988) 32 5/8 (829) 32 5/8 (829) 1 1/8 3/8 3/8
527L^ 5 94 1/4 (2394) 32 5/8 (829) 48 5/8 (1235) 1 3/8 3/8 1/2
631L^ 6 110 1/4 (2800) 48 5/8 (1235) 48 5/8 (1235) 1 3/8 1/2 1/2
^ = A or E. Refer to Nomenclature for details
103V^ 1 30 1/4 (768) 17 1/4 (438) N/A N/A 5/8 3/8 3/8
104V^ 1 30 1/4 (768) 17 1/4 (438) N/A N/A 5/8 3/8 3/8
105V^ 1 30 1/4 (768) 17 1/4 (438) N/A N/A 5/8 3/8 3/8
206V^ 2 46 1/4 (1175) 33 1/4 (845) N/A N/A 7/8 3/8 3/8
208V^ 2 46 1/4 (1175) 33 1/4 (845) N/A N/A 7/8 3/8 3/8
209V^ 2 46 1/4 (1175) 33 1/4 (845) N/A N/A 7/8 3/8 3/8
312V^ 3 62 1/4 (1581) 49 1/4 (1251) N/A N/A 7/8 3/8 3/8
315V^ 3 62 1/4 (1581) 49 1/4 (1251) N/A N/A 1 1/8 3/8 3/8
416V^ 4 78 1/4 (1988) 32 5/8 (829) 32 5/8 (829) 1 1/8 3/8 3/8
419V^ 4 78 1/4 (1988) 32 5/8 (829) 32 5/8 (829) 1 1/8 3/8 3/8
523V^ 5 94 1/4 (2394) 32 5/8 (829) 48 5/8 (1235) 1 3/8 3/8 1/2
627V^ 6 110 1/4 (2800) 48 5/8 (1235) 48 5/8 (1235) 1 3/8 3/8 1/2
Page 22
RECOMMENDED EXPANSION V ALVE
TPLP
SPORLAN
MODEL
104M N/A EBQE-AA-*C EBQE-AAA-VC EBQE-AAA-JC
106M L-1/2 EBQE-AA-*C EBQE-AA-VC EBQE-AA-JC
107M L-1/2 EBQE-A-*C EBQE-AA-VC EBQE-AA-JC
209M L-3/4 EBQE-A-*C EBQE-AA-VC EBQE-AA-JC
211M L-1 EBQE-A-*C EBQE-A-VC EBQE-A-JC
214M L-1 EBQE-B-*C EBQE-A-VC EBQE-A-JC
317M L-1 1/2 EBQE-B-*C EBQE-A-VC EBQE-A-JC
320M L-1 1/2 EBQE-B-*C EBQE-B-VC EBQE-A-JC
423M L-2 EBQE-B-*C EBQE-B-VC EBQE-A-JC
426M L-2 EBQE-C-*C EBQE-B-VC EBQE-B-JC
532M L-2 1/2 EBQE-C-*C EBQE-B-VC EBQE-B-JC
639M G-3 EBQE-C-*C EBQE-C-VC EBQE-C-JC
* Varies with refrigerant: S = R404A, P = R507
ALCO
MODEL
104M N/A HFESC 1/4 SC HFESC 1/2 HC HFESC 1/2 MC
106M L-1/2 HFESC 1/2 SC HFESC 1/2 HC HFESC 3/4 MC
107M L-1/2 HFESC 1/2 SC HFESC 1/2 HC HFESC 3/4 MC
209M L-3/4 HFESC 1 SC HFESC 1 HC HFESC 3/4 MC
211M L-1 HFESC 1 SC HFESC 1 HC HFESC 1 MC
214M L-1 HFESC 1-1/4 SC HFESC 1-1/2 HC HFESC 1 MC
317M L-1 1/2 HFESC 1-1/2 SC HFESC 1-1/2 HC HFESC 1-1/2 MC
320M L-1 1/2 HFESC 1-1/2 SC HFESC 2 HC HFESC 1-3/4 MC
423M L-2 HFESC 2 SC HFESC 2 HC HFESC 1-3/4 MC
426M L-2 HFESC 2 SC HFESC 2-1/2 HC HFESC 2-1/2 MC
532M L-2 1/2 HFESC 3-1/2 SC HFESC 2-1/2 HC HFESC 2-1/2 MC
639M G-3 HFESC 3-1/2 SC HFESC 3 HC HFESC 4 MC
DANFOSS
MODEL
104M N/A TUAE-R404A-4-N TUAE-R22-4-N TUAE-R134a-4-N
106M L-1/2 TUAE-R404A-5-N TUAE-R22-5-N TUAE-R134a-5-N
107M L-1/2 TUAE-R404A-6-N TUAE-R22-5-N TUAE-R134a-5-N
209M L-3/4 TUAE-R404A-7-N TUAE-R22-6-N TUAE-R134a-6-N
211M L-1 TUAE-R404A-7-N TUAE-R22-6-N TUAE-R134a-6-N
214M L-1 TUAE-R404A-8-N TUAE-R22-7-N TUAE-R134a-7-N
317M L-1 1/2 TUAE-R404A-8-N TUAE-R22-8-N TUAE-R134a-8-N
320M L-1 1/2 TUAE-R404A-9-N TUAE-R22-8-N TUAE-R134a-8-N
423M L-2 TUAE-R404A-9-N TUAE-R22-8-N TUAE-R134a-9-N
426M L-2 TCAE-R404A-TC1-N TUAE-R22-9-N TUAE-R134a-9-N
532M L-2 1/2 TCAE-R404A-TC2-N TUAE-R22-9-N TCAE-R134a-TC1-N
639M G-3 TCAE-R404A-TC3-N TCAE-R22-TC1-N TCAE-R134a-TC2-N
† If using 407C, superheat setting must be adjusted by turning 1 - 1.5 turns clockwise.
FACTORY
INSTALLED
NOZZLE
FACTORY
INSTALLED
NOZZLE
FACTORY
INSTALLED
NOZZLE
SELECTIONS - MEDIUM TEMP. MODELS
R404A
R507
R404A
R507
R404A
R507
R407A
R407C
R22
R407A
R407C
R22
R407A
R407C
R22
R134a
†
R134a
R134a
If correct nozzle is not
available, the proper
orice size can be
drilled in the eld using
the following chart
NOZZLE
ORIFICE
No.
1/2 .070
3/4 .086
1 .0995
1-1/2 .120
2 .1406
2-1/2 .157
3 .172
4 .199
5 .211
6 .242
8 .266
10 .281
DRILL
SIZE
IN.
60Hz
Above selections based on:
1) 100°F (38°C) vapor free liquid entering expansion valve
2) 110°F (43°C) Condensing temperature
3) 8 -12°F (4.4 -6.7°C) evaporator TD
Page 23
TPLP
RECOMMENDED EXPANSION V ALVE
SELECTIONS - LOW TEMP. MODELS
60Hz
SPORLAN -
MODEL
104L L-1/2 EBQE-AAA-VC EBQE-AA-VZP40 EBQE-AA-VZP40 EBQE-AA-VZP40 EBQE-AA-VZP40
105L L-3/4 EBQE-AA-VC EBQE-AA-VZP40 EBQE-AA-VZP40 EBQE-AA-VZP40 EBQE-AA-VZP40
106L L-1 EBQE-AA-VC EBQE-AA-VZP40 EBQE-AA-VZP40 EBQE-AA-VZP40 EBQE-AA-VZP40
207L L-1 EBQE-AA-VC EBQE-AA-VZP40 EBQE-A-VZP40 EBQE-A-VZP40 EBQE-A-VZP40
209L L-1-1/2 EBQE-AA-VC EBQE-A-VZP40 EBQE-A-VZP40 EBQE-A-VZP40 EBQE-A-VZP40
211L L-2 EBQE-A-VC EBQE-A-VZP40 EBQE-A-VZP40 EBQE-A-VZP40 EBQE-B-VZP40
314L L-2 EBQE-A-VC EBQE-A-VZP40 EBQE-B-VZP40 EBQE-B-VZP40 EBQE-B-VZP40
317L L-3 EBQE-A-VC EBQE-B-VZP40 EBQE-B-VZP40 EBQE-B-VZP40 EBQE-B-VZP40
419L L-3 EBQE-A-VC EBQE-B-VZP40 EBQE-B-VZP40 EBQE-B-VZP40 EBQE-B-VZP40
422L G-4 EBQE-B-VC EBQE-B-VZP40 EBQE-B-VZP40 EBQE-C-VZP40 EBQE-C-VZP40
527L G-4 EBQE-B-VC EBQE-C-VZP40 EBQE-C-VZP40 EBQE-C-VZP40 EBQE-C-VZP40
631L G-5 EBQE-C-VC EBQE-C-VZP40 EBQE-C-VZP40 EBQE-C-VZP40 EBQE-C-VZP40
103V L-1/2 EBQE-AAA-VC EBQE-AAA-VZP40 EBQE-AA-VZP40 EBQE-AA-VZP40 EBQE-AA-VZP40
104V L-3/4 EBQE-AAA-VC EBQE-AA-VZP40 EBQE-AA-VZP40 EBQE-AA-VZP40 EBQE-AA-VZP40
105V L-1 EBQE-AA-VC EBQE-AA-VZP40 EBQE-AA-VZP40 EBQE-AA-VZP40 EBQE-AA-VZP40
206V L-1 EBQE-AA-VC EBQE-AA-VZP40 EBQE-AA-VZP40 EBQE-AA-VZP40 EBQE-A-VZP40
208V L-1 1/2 EBQE-AA-VC EBQE-AA-VZP40 EBQE-A-VZP40 EBQE-A-VZP40 EBQE-A-VZP40
209V L-2 EBQE-A-VC EBQE-A-VZP40 EBQE-A-VZP40 EBQE-A-VZP40 EBQE-A-VZP40
312V L-2 EBQE-A-VC EBQE-A-VZP40 EBQE-A-VZP40 EBQE-B-VZP40 EBQE-B-VZP40
315V L-2 1/2 EBQE-A-VC EBQE-B-VZP40 EBQE-B-VZP40 EBQE-B-VZP40 EBQE-B-VZP40
416V L-2 1/2 EBQE-A-VC EBQE-B-VZP40 EBQE-B-VZP40 EBQE-B-VZP40 EBQE-B-VZP40
419V G-3 EBQE-A-VC EBQE-B-VZP40 EBQE-B-VZP40 EBQE-B-VZP40 EBQE-B-VZP40
523V G-4 EBQE-B-VC EBQE-B-VZP40 EBQE-C-VZP40 EBQE-C-VZP40 EBQE-C-VZP40
627V G-5 EBQE-B-VC EBQE-C-VZP40 EBQE-C-VZP40 EBQE-C-VZP40 EBQE-C-VZP40
FACTOR Y INSTALLED
R407A
NOZZLE
0° F (-18° C) EVAP. -10° F (-23° C) EVAP. -20° F (-29° C) EVAP. -30° F (-34° C) EVAP. -40° F (-40° C) EVAP.
SPORLAN -
MODEL
104L L-1/2 EBQE-AA-SC EBQE-AA-SZP EBQE-AA-SZP EBQE-AA-SZP EBQE-AA-SZP
105L L-3/4 EBQE-AA-SC EBQE-AA-SZP EBQE-AA-SZP EBQE-AA-SZP EBQE-AA-SZP
106L L-1 EBQE-AA-SC EBQE-A-SZP EBQE-A-SZP EBQE-A-SZP EBQE-A-SZP
207L L-1 EBQE-A-SC EBQE-A-SZP EBQE-A-SZP EBQE-A-SZP EBQE-A-SZP
209L 1-1/2 EBQE-A-SC EBQE-A-SZP EBQE-A-SZP EBQE-A-SZP EBQE-A-SZP
211L L-2 EBQE-A-SC EBQE-A-SZP EBQE-A-SZP EBQE-A-SZP EBQE-A-SZP
314L L-2 EBQE-B-SC EBQE-B-SZP EBQE-B-SZP EBQE-B-SZP EBQE-B-SZP
317L L-3 EBQE-B-SC EBQE-B-SZP EBQE-B-SZP EBQE-B-SZP EBQE-B-SZP
419L L-3 EBQE-B-SC EBQE-B-SZP EBQE-C-SZP EBQE-C-SZP EBQE-C-SZP
422L G-4 EBQE-C-SC EBQE-C-SZP EBQE-C-SZP EBQE-C-SZP EBQE-C-SZP
527L G-4 EBQE-C-SC EBQE-C-SZP EBQE-C-SZP EBSE-6-SZP EBSE-6-SZP
631L G-5 EBSE-6-SC EBSE-6-SZP EBSE-6-SZP EBSE-6-SZP EBSE-6-SZP
103V L-1/2 EBQE-AA-SC EBQE-AA-SZP EBQE-AA-SZP EBQE-AA-SZP EBQE-AA-SZP
104V L-3/4 EBQE-AA-SC EBQE-AA-SZP EBQE-AA-SZP EBQE-AA-SZP EBQE-AA-SZP
105V L-1 EBQE-AA-SC EBQE-AA-SZP EBQE-AA-SZP EBQE-AA-SZP EBQE-AA-SZP
206V L-1 EBQE-A-SC EBQE-A-SZP EBQE-A-SZP EBQE-A-SZP EBQE-A-SZP
208V L-1 1/2 EBQE-A-SC EBQE-A-SZP EBQE-A-SZP EBQE-A-SZP EBQE-A-SZP
209V L-2 EBQE-A-SC EBQE-A-SZP EBQE-A-SZP EBQE-A-SZP EBQE-A-SZP
312V L-2 EBQE-A-SC EBQE-A-SZP EBQE-A-SZP EBQE-B-SZP EBQE-B-SZP
315V L-2 1/2 EBQE-B-SC EBQE-B-SZP EBQE-B-SZP EBQE-B-SZP EBQE-B-SZP
416V L-2 1/2 EBQE-B-SC EBQE-B-SZP EBQE-B-SZP EBQE-B-SZP EBQE-B-SZP
419V G-3 EBQE-B-SC EBQE-B-SZP EBQE-C-SZP EBQE-C-SZP EBQE-C-SZP
523V G-4 EBQE-C-SC EBQE-C-SZP EBQE-C-SZP EBQE-C-SZP EBQE-C-SZP
627V G-5 EBQE-C-SC EBQE-C-SZP EBQE-C-SZP EBSE-6-SZP EBSE-6-SZP
FACTOR Y INSTALLED
R404A
NOZZLE
0° F (-18° C) EVAP. -10° F (-23° C) EVAP. -20° F (-29° C) EVAP. -30° F (-34° C) EVAP. -40° F (-40° C) EVAP.
Above selections based on:
1) 100°F (38°C) vapor free liquid entering expansion valve
2) 110°F (43°C) Condensing temperature
3) 8 -12°F (4.4 -6.7°C) evaporator TD
Page 24
TPLP
INSTALLATION INSTRUCTIONS
60Hz
INSTALLATION
The installation and start-up of evaporators should only
beperformedbyqualiedrefrigerationmechanics.
This equipment should be installed in accordance with
all applicable codes, ordinances and local by-laws.
INSPECTION
Inspect all equipment before unpacking for visible signs
of damage or loss. Check shipping list against material
received to ensure shipment is complete.
IMPORTANT: Remember, you, the consignee, must
make any claim necessary against the transportation
company. Shipping damage or missing parts, when
discovered at the outset, will prevent later unnecessary
and costly delays.
If damage or loss during transport is evident, make
claim to carrier, as this will be their responsibility,
not the manufacturer’s.
Should carton be damaged, but damage to equipment is
notobvious,aclaimshouldbeledfor“concealed
damage” with the carrier.
IMPORTANT: The electrical characteristics of the unit
should be checked at this time to make sure they
correspond to those ordered and to electrical power
available at the job site.
Save all shipping papers, tags and instruction sheets for
reference by installer and owner.
APPLICATION
TPLP evaporators are designed for walker-in cooler and
freezer applications used with a wide range of refrigerants. For room temperatures above 35°F (2°C) AND
evaporating temperatures above 26°F (-3°C) , positive
defrosting means (electric) may not be required,
otherwise, electric defrost defrost models should be
used. Electric defrost models come with defrost
termination and fan delay as standard to control the
defrost cycle termination and fan delay, while defrost
initiation means (e.g. defrost timer) is not included.
The coil must not be exposed to any abnormal
atmospheric or acidic environments. This may result in
corrosion to the cabinet and possible coil failure (leaks).
(Consult manufacturer for optional baked on phenolic
protective coatings).
LOCATION
The unit location in the room should be selected to ensure uniform air distribution throughout the entire space
to be refrigerated. Be sure that the product does not
obstruct the free circulation of air. Allow a minimum of
24” clearance at each end. Do not locate evaporators
over doors. Consideration should be given to the coil
location in order to minimize the piping run length to the
condensingunitandoordrain.
EXPANSION VALVE (TXV) PRE-SELECTED
Locate the expansion valve bulb on a horizontal length
of suction line preferably 3 to 6 inches from the suction
header. Locate the bulb at 4 or 8 clock position and
insulate with a waterproof type of insulation. Clamp the
bulb to ensure 100% contact of the bulb with the
suction line.
After following the manufacturer’s installation instructions
and after the room has reached the desired
temperature the valve superheat should be checked.
Thiswillconrmthattheevaporatorisoperating
properlyandperformingtomaximumeciency.The
superheat should be around 6 (3.3°C) to 8°F (4.4°C) for
a 10 to 12°F T.D (5.6 to 6.7°C). Too high or low a super
heat will result in unsatisfactory system
performance and possible compressor problems.
MOUNTING
Refer to dimensional drawing for recommended
mounting arrangements. Ensure adequate clearance
is provided behind the coil as well as each end. The
evaporatorsmaybemountedushwithceilingwith
bolts, or hanging down with rod hangers. When using
rod hangers, allow adequate space between the top of
the unit and the ceiling for cleaning to comply with NSF
Standard 7.
Ensure that the ceiling is level since the drain pan
has been sloped for drainage during the defrost
cycle.
DRAIN LINE
The drain line should be run from the drain connection,
sloping at least 1” (25 mm) per foot and should have
the size at least as large as the drain connection. A
P-Trap in a warm area outside the room must be
provided to allow proper draining through the tubing.
Connection should be made to proper drainage facilities
that comply with local regulations.
To prevent freeze-up when the temperature of the
refrigerated space is 35°F (2°C) or lower, the drain line
should be heated along its run inside the cold room.
The heated drain line should be insulated. It is recommended that the heater be energized at all times. A
heat input of 20 watts per foot in a 28°F (-2°C) room
and 30 watts per foot for -20°F (-29°C) rooms, is
satisfactory. Drain line heaters are not required for
constant room temperature above 35°F (2°C) .
Always trap evaporator drain line individually to prevent
vapor migration.
Ensure that the drain line has sucient slope for
proper drainage (prevention of ice build up/blockage in pan).
Page 25
TPLP
INSTALLATION INSTRUCTIONS
60Hz
PIPING
Refrigerationgradepipingmustbeusedforalleld
refrigeration piping. Refrigerant line sizes are important
and may not be the same size as the coil connections.
Consult ASHRAE handbook or other similar reference
book for proper line sizing.
Refrigerant piping and control system should be designed
to prevent possible liquid slugging (from oil or refrigerant)
of the compressors on start-up after the defrost cycle.
Also, it should prevent oil logging and minimize refrigerant
pressure drop.
WIRING
Wire system in accordance with governing standards and
local codes. See data and wiring diagrams on pages 4 to
20 for typical wiring arrangement. Electrical wiring is to be
sized in accordance with minimum circuit ampacity rating
(MCA). Size fuses used must not exceed the Maximum
Fuse Size ratings.
For ease of identifying the proper wiring terminal, unit
wiring is color coded and terminal block connections are
identied.
When fan delay thermostats (combination fan delay and
defrost termination) are installed, on start-up, the fans
do not operate until the coil temperature is reduced to
approximately 25oF (-4°C) . It is normal for the fans to
cycle a few times until the room temperature is brought
down. At higher evaporating temperatures this control
may not close and therefore should either be by-passed
temporarily or replaced with an adjustable type. (set for a
higher temperature cut-in point).
MAINTENANCE
The unit should be periodically inspected for any dirt or ice
build-uponthensurfaceandcleanedifnecessarywith
a soft whisk or brush. Also ensure coils inner (and outer)
drain pans do not have any ice build-up from improper
defrostoperation.Whenreplacingheaterelementsrst
remove heater retainer brackets and heater clips.
SYSTEM CHECK
Before Start-Up:
1. All wiring should be in accordance with local
codes.
2. Refrigerant lines should be properly sized.
3. Thorough evacuation and dehydration has been
performed.
4. The suction, discharge, and receiver service
valves must be open.
5.Thesystempreferablyincludealiquidlinelter
driermoistureindicatorandsuctionlter.
6. Pour enough water into the drain pan to allow a
good check on drainage and seal the trap.
After Start-Up:
1. Check the oil level to be sure the oil charge is
correct.
2. On initial start up the fans do not start until coil
temperature is pulled down to approximately 25°F
(-4°C) on the coil. Also, it is normal for the fan to
cycle a few times until the room temperature is
pulled down.
3. If necessary, temporarily by-pass fan delay control
(to run fans until room temp is lowered).
4. Be sure that the expansion valve is properly set to
provide the correct amount of superheat.
5. After the box temperature is close to reaching the
desired temperature, the evaporator superheat
must be checked and adjustment made if
necessary. In general, evaporators running with
a TD of 10°F (5.6°C ) should have a superheat
reading of 6° to 8°F (3.3°C to 4.4°C) . For
evaporators with another T.D., the general rule is
that the superheat should be around 60 to
80% of T .D.
6. Heavy moisture loads are usually encountered
whenstartingthesystemforthersttime.
This may cause a rapid build-up of frost on the
evaporator. During the initial pull down, we
suggest that the frost build-up be watched and
defrosted manually as required.
7. Observe that the system goes through at least
one complete DEFROST CYCLE.
Page 26
SERVICE PARTS
TPLP 60Hz
FOR SERVICE PARTS LOOK-UP:
visit: http://www.t-rp.com/serv_parts.htm
email: parts@t-rp.com
call: 1-844-893-3222 x501
Page 27
FINISHED GOODS WARRANTY
The terms and conditions as described below in the General Warranty Policy cover all products
manufactured by National Refrigeration.
GENERAL WARRANTY POLICY
Subject to the terms and conditions hereof, the Company warrants all Products, including Service
Parts, manufactured by the Company to be free of defects in material or workmanship, under normal use and application for a period of one (1) year from the original date of installation, or eighteen
(18)monthsfromthedateofshipmentfromtheCompany,whicheveroccursrst.Anyreplacement
part(s) so supplied will be warranted for the balance of the product’s original warranty. The part(s) to
be replaced must be made available in exchange for the replacement part(s) and reasonable proof
oftheoriginalinstallationdateoftheproductmustbepresentedinordertoestablishtheeective
dateofthewarranty,failingwhich,theeectivedatewillbebaseduponthedateofmanufactureplus
thirty (30) days. Any labour, material, refrigerant, transportation, freight or other charges incurred in
connection with the performance of this warranty will be the responsibility of the owner at the cur-
rentratesandpricesthenineect.Thiswarrantymaybetransferredtoasubsequentownerofthe
product.
THIS WARRANTY DOES NOT COVER
(a)Damagescausedbyaccident,abuse,negligence,misuse,riot,re,ood,orActsofGod(b)damages
caused by operating the product in a corrosive atmosphere (c) damages caused by any unauthorized
alterationorrepairofthesystemaectingtheproduct’sreliabilityorperformance(d)damagescaused
by improper matching or application of the product or the product’s components (e) damages caused by
failing to provide routine and proper maintenance or service to the product (f) expenses incurred for the
erecting, disconnecting, or dismantling the product (g) parts used in connection with normal maintenance,
suchasltersorbelts(h)productsnolongeratthesiteoftheoriginalinstallation(i)productsinstalled
or operated other than in accordance with the printed instructions, with the local installation or building
codes and with good trade practices (j) products lost or stolen.
No one is authorized to change this WARRANTY or to create for or on behalf of the Company any
other obligation or liability in connection with the Product(s). There is no other representation, warranty
or condition in any respect, expressed or implied, made by or binding upon the Company other than
the above or as provided by provincial or state law and which cannot be limited or excluded by such
law, nor will we be liable in any way for incidental, consequential, or special damages however caused.
Theprovisionsofthisadditionalwrittenwarrantyareinadditiontoandnotamodicationoforsubtraction
from the statutory warranties and other rights and remedies provided by Federal, Provincial or State laws.
PROJECT INFORMATION
System
Model Number Date of Start-Up
Serial Number Service Contractor
Refrigerant Phone
Electrical Supply Fax
Page 28
“AS BUILT” SERVICE PARTS LIST
Service Parts List
Label
To Be Attached
HERE