S2 = 208-230/1/60
T3 = 208-230/3/60*
S4 = 460/1/60
T4 = 460/3/60*
S5 = 575/1/60
T5 = 575/3/60*
*3 Fan Models Only
• Internally Enhanced Tubing with Enhanced Fin
optimizes coil performance
• Energy Efcient PSC Motors with Internal
Overload Protection
• ThermoSpanTM Coil Design eliminates tube
failures on tube sheet
OPTIONAL FEATURES
• Optional leg kits for horizontal and vertical
congurations
• Multiple Refrigeration Circuits
• Ambient or Pressure Fan Cycling Control with
Contactor
• Variable speed motor with controller
for header fan motor
• Non-Fused Disconnect
• EC Motors (see pg. 10)
• Unit shipped with Nitrogen Holding Charge
• Individual Fan Motor Fusing
• Receiver with or without Heater and Insulation
• Adjustable Flooded Head Pressure Control
(Factory mounted if ordered with receiver option)
• Optional Fin Materials and Coatings
• Voltages for 60 Hz and 50 Hz
CAPACITY DATA
03/11/15
T50-TCS-PDI-4
- 3 -
60HzTCS
MODEL
NO.
TCS 0021 x 11.12(0.33)1.16(0.34)1.22(0.36)1.24(0.37)1.18(0.35)
TCS 0031 x 11.39(0.40)1.43(0.42)1.51(0.44)1.54(0.45)1.46(0.43)
TCS 0051 x 12.35(0.69)2.42(0.71)2.55(0.75)2.60(0.77)2.47(0.73)
TCS 0061 x 12.81(0.83)2.90(0.86)3.05(0.90)3.11(0.92)2.96(0.87)
TCS 0081 x 13.50(1.02)3.61(1.05)3.80(1.11)3.88(1.13)3.69(1.08)
TCS 0101 x 24.60(1.34)4.75(1.39)5.00(1.46)5.10(1.49)4.85(1.42)
TCS 0121 x 25.57(1.63)5.75(1.68)6.05(1.77)6.17(1.81)5.87(1.72)
TCS 0141 x 26.34(1.86)6.55(1.92)6.89(2.02)7.03(2.06)6.68(1.96)
TCS 0161 x 26.96(2.04)7.19(2.11)7.57(2.22)7.72(2.26)7.34(2.15)
TCS 0191 x 38.28(2.43)8.55(2.51)9.00(2.64)9.18(2.69)8.73(2.56)
TCS 0241 x 310.40(3.05)10.74(3.14)11.30(3.31)11.53(3.38)10.96(3.21)
NOTES:
- Above capacity data based on 0oF subcooling and at sea level.
- For High Altitude applications apply the following correction factors: 0.94 for 2000 feet, 0.88 for 4000 feet and 0.81 for 6000 feet.
- Capacities at other TD within a range of 10 to 30 °F (-12.2 to -1°C) are directly proportional to TD, or use formula: Capacity = Rated capacity ÷ 10 x TD.
- For 50 HZ capacity multiply by 0.92. (No derate for EC motors)
- Capacities for R407A and R407C are based on mean temperature. Mean temperature is the average temperature between the saturated condensing
temperatures at the inlet and outlet of the condenser. For dew point ratings, consult factory.
FAN
CONFIG.
R407A
TOTAL HEAT OF REJECTION - MBH (KW) PER 1 °F (0.56 °C) TD
R407CR404A
R507
R22
R410A
R134a
TCS
03/11/15
T50-TCS-PDI-4
- 4 -
ELECTRICAL DATA
60Hz
MODEL
TCS 0021 x 11/611.11.4152800.60.8152800.50.715280
TCS 0031 x 11/611.11.4152800.60.8152800.50.715280
TCS 0051 x 11/312.12.7154101.11.4154100.91.215410
TCS 0061 x 11/312.12.7154101.11.4154100.91.215410
TCS 0081 x 11/312.12.7154101.11.4154100.91.215410
TCS 0101 x 21/324.24.8158202.22.5158201.82.115820
TCS 0121 x 21/324.24.8158202.22.5158201.82.115820
TCS 0141 x 21/324.24.8158202.22.5158201.82.115820
TCS 0161 x 21/324.24.8158202.22.5158201.82.115820
TCS 0191 x 31/336.3 (3.6) 6.9 (4.6)1512303.3 (1.9) 3.6 (2.4)1512302.7 (1.6) 3.0 (2.0)151230
TCS 0241 x 31/336.3 (3.6) 6.9 (4.6)1512303.3 (1.9) 3.6 (2.4)1512302.7 (1.6) 3.0 (2.0)151230
TCS 0021 x 10.7(0.3)2.9(1.3)2180(1029)555725/85/8127(58)
TCS 0031 x 11.1(0.4)4.6(2.1)1950(920)555725/85/8131(59)
TCS 0051 x 11.4(0.7)6.4(2.9)4570(2157)606137/85/8150(68)
TCS 0061 x 12.1(1.0)9.4(4.3)4080(1925)606147/85/8157(71)
TCS 0081 x 13.2(1.4)14.1(6.4)4570(2157)606151 1/87/8197(89)
TCS 0101 x 23.1(1.4)13.8(6.3)9140(4313)626461 1/87/8254(115)
TCS 0121 x 24.4(2.0)19.7(8.9)8160(3851)626491 1/87/8269(122)
TCS 0141 x 25.9(2.6)26.7(12.1)9410(4441)626491 3/87/8305(138)
TCS 0161 x 25.9(2.6)26.7(12.1)9140(4313)636591 3/87/8325(147)
TCS 0191 x 36.8(3.1)30.5(13.8)12240 (5776)6365151 5/81 1/8381(173)
TCS 0241 x 38.9(4.1)40.0(18.2)13700 (6465)6365151 5/81 1/8447(203)
NORMAL
FAN
CONFIG.
LBS(kg)LBS(kg)VERT.HORIZ.
REFRIG. CHARGE
(2)
90% FULL
AIR FLOW
(3)
CFM(l/s)
SOUND LEVEL
dBA
DISCHARGE
(5)
AVAIL.
CIRCUITS
CONNECTION
SIZES
INLETOUTLETLBS(kg)
APPROX.
WEIGHT
(1) Refrigerant charge conversion factors:
(2) Normal charge is the refrigerant charge for warm ambient or summer operation.
(3) 90% full is the liquid refrigerant weight at 90% of internal volume and is for reference only.
(4) For 50 Hz fan data use 60 Hz CFM (m3/h) X 0.83 (no derate)
(5) Sound pressure level at 10 ft. (3 m)
R407CR404A
1.00.910.911.050.921.06
R507
R22
R410A
R134a
208-230 (200-220) VOLT
460 (380-400) VOLT
TCS
03/11/15
T50-TCS-PDI-4
- 5 -
WIRING DIAGRAM
(STANDARD WITHOUT OPTIONS)
60Hz
WIRING DIAGRAM
208-230 (200-220) VOLT
460 (380-400) VOLT
03/11/15
T50-TCS-PDI-4
- 6 -
TCS60Hz
(MODELS WITH FAN CYCLING CONTROL)
TCS
03/11/15
T50-TCS-PDI-4
- 7 -
WIRING DIAGRAM
(VARIABLE SPEED MOTOR WITH CONTROLLER
FOR HEADER FAN CONTROL - 208-230V MODELS)
60Hz
WIRING DIAGRAM
03/11/15
T50-TCS-PDI-4
- 8 -
TCS60Hz
(VARIABLE SPEED MOTOR WITH CONTROLLER
FOR HEADER FAN CONTROL - 460V AND 575V MODELS)
208-230 (200-220) VOLT460 (380-400) VOLT
TCS
03/11/15
T50-TCS-PDI-4
- 9 -
WIRING DIAGRAM
(THREE PHASE WIRING MODELS TCS 019 - 024)
60Hz
TCS
03/11/15
T50-TCS-PDI-4
- 10 -
ABOUT EC MOTORS
EC MOTORS
60Hz
Air cooled condensers utilizing electrically commutat-
ed motor (EC motor) technology offer many benets;
Improved Efciency, Reduced Sound Levels, Speed
Control, Simplicity and Reliability
Efciency
The speed control function of an EC motor allows the
condenser to run at optimized energy levels at different operating conditions. Up to 75% in energy savings can be realized when comparing the EC motor
speed control method to a conventional fan cycling
method. See table below for power consumption and
energy savings comparisons.
Sound
As EC motor speeds vary for different operating
conditions they also offer reduced sound levels when
compared to conventional motor running full speed.
Sound levels are reduced on cooler days and in
evenings.
ELECTRICAL DATA
TCS
(OPTIONAL EC MOTORS)
Head Pressure Control
EC motors make it easier to maintaining stable head
pressures when motor speeds are varied according to operating conditions. System optimization is
further enhanced compared to the system shock from
conventional cycling banks of fans off and on.
Simplicity and Reliability
The installation and control of EC motors is very
simple compared to other methods of speed control
used on conventional AC motors. Lower running operating temperatures and smooth transitional speed
changes make EC motors durable and reliable.
EC MOTORS
60Hz
MODEL
TCS 0021 x 11/311.72.115210N/AN/AN/AN/AN/AN/A
TCS 0031 x 11/311.72.115210N/AN/AN/AN/AN/AN/A
TCS 0051 x 11/3133.8153401/311.41.815340
TCS 0061 x 11/3133.8153401/311.41.815340
TCS 0081 x 11/3133.8153401/311.41.815340
TCS 0101 x 21/3266.8156801/322.83.215680
TCS 0121 x 21/3266.8156801/322.83.215680
TCS 0141 x 21/3266.8156801/322.83.215680
TCS 0161 x 21/3266.8156801/322.83.215680
TCS 0191 x 31/339 (5.2)9.8 (5.6)1510201/334.2 (2.4) 4.6 (2.6)151020
TCS 0241 x 31/339 (5.2)9.8 (5.6)1510201/334.2 (2.4) 4.6 (2.6)151020
FAN
CONFIG.
MOTOR
HPQty.HPQty.
208-230/1/60 (208-230/3/60)460/1/60 (460/3/60)
FLAMCAMOPWATTS
MOTOR
FLAMCAMOPWATTS
TCS
03/11/15
T50-TCS-PDI-4
- 11 -
EC MOTOR WIRING DIAGRAM
208-230/1/60 (208-230/3/60)
EC MOTORS
60Hz
TCS
03/11/15
T50-TCS-PDI-4
- 12 -
EC MOTOR WIRING DIAGRAM
460/1/60 (460/3/60)
EC MOTORS
60Hz
TCS
Full RPM
!
03/11/15
T50-TCS-PDI-4
- 13 -
EC MOTOR APPLICA TION
EC MOTORS
60Hz
Motors With Built-in Variable Speed –
Units with an EC (electronically commutated) motor provide
variable speed control. ECM motors use DC motors with
integral AC to DC conversion allowing direct connection to
AC mains with the energy saving and control benets of a
DC motor. Ideally the motors on the condenser should all
be EC and simultaneously slow down /speed up together.
This provides for maximum energy savings. However some
applications may exist where just the last fan or pair of fans
(ones closest to header) is solely EC motors. (The remaining conventional type motors are then cycled off by fan
cycling pressure controls).
Important Warnings:(Please read before handling motors)
1. When connecting the unit to the power supply, danger
ous voltages occur. Due to motor capacitor discharge
time, do not open the motor within 5 minutes after
disconnection of all phases.
2. With a Control voltage fed in or a set speed value being
saved, the motor will restart automatically after a power
failure.
3. Dangerous external voltages can be present at the
motor terminals even when the unit is turned off.
4. The Electronics housing can get hot.
Speed Adjustment Characteristics
The EC motor varies its speed linearly based on a
1-10V input signal. At 10 VDC, the motor runs at full
speed. At 0 to approx. 1 VDC, the motor turns off. A
chart of the speed control curve is shown below. The
motor can be controlled at any speed below its nominal
RPM.
RPM
1
Control voltage [V dc]
Control Signal
The input control signal can be supplied by an external
control signal or from a factory installed proportional
pressure control. Units with factory installed proportional pressure controls require no installation wiring
and are adjusted with initial factory settings. These
may require further adjustments to suit local eld conditions.
10
5. The cycling on and off of EC motors should be
controlled by the DC control voltage (i.e. 0V DC will turn
motor off). Excessive cycling of the motor by line
voltage contactors may cause stress on the motors and
reduce the motor life.
External Control Signal (Supplied by others)
Contact control manufacturer for setup of external controller to provide a 0-10 VDC control signal. Wire the
control signal to terminal board in unit control box. See
EC Diagram on P.12 for typical external signal control
wiring.
MT'G HOLES
B
9/16 (x4)O
6 7/8
ELECTRICAL
BOX.
OPTIONAL
LIFTING HOLES
O9/16
AIR FLOW
A
9/16 (x4)
MT'G HOLES
O
BOX.
9/16
ELECTRICAL
LIFTING HOLES
OPTIONAL
O
MT'G HOLES
O
9/16
ELECTRICAL
LIFTING HOLES
OPTIONAL
BOX.
O(x4)
9/16 (x6)
3 3/8
20
15
1/21/2
2
2
6 7/8
2
2
B
2
B
6 7/8
2
B
5 1/2
5 1/2
5 1/2
RECEIVER KITS.
OPTIONAL REMOTE
Legs included with receiver option.
unit leg configuration.
Optional Factory Mounted
Receiver kits fit within standard
(x4)
(x4)
2 FAN
1 FAN
3 FAN
SIDE VIEW
TYPICAL END VIEW
ELECT. BOX END
DIMENSIONAL DATA
03/11/15
T50-TCS-PDI-4
- 14 -
TCS60Hz
VERTICAL AIR DISCHARGE UNITS
ELECTRICAL CONNECTION 7/8”
UNITS ARE SHIPPED IN HORIZONTAL AIR
FLOW CONFIGURATION LESS OPTIONAL
MOUNTING LEGS AS STANDARD. VERTICAL AIR DISCHARGE MODELS REQUIRE
LEG KIT OPTION SHIPPED LOOSE AND
SOLD SEPARATELY .
MODEL
TCS 0021 x 124 1/8(613)25 1/2(648)
TCS 0031 x 124 1/8(613)25 1/2(648)
TCS 0051 x 131 5/8(803)38(965)
TCS 0061 x 131 5/8(803)38(965)
TCS 0081 x 141 5/8(1057)38(965)
TCS 0101 x 241 5/8(1057)55 1/2(1410)
TCS 0121 x 241 5/8(1057)55 1/2(1410)
TCS 0141 x 241 5/8(1057)75 1/2(1918)
TCS 0161 x 241 5/8(1057)75 1/2(1918)
TCS 0191 x 341 5/8(1057)41 1/2(1054)
TCS 0241 x 341 5/8(1057)56 1/2(1435)
CONFIG.
FAN
MOUNTING DIMENSIONS
AB
INCHES(mm)INCHES(mm)
OPTIONAL
1 9/16
1 9/16
5 1/2
B
6 7/8
BOX
ELECTRICAL
OPTIONAL
MT'G HOLES
9/16 (x8)
1 9/16
1 9/16
5 1/2
B
O
6 7/8
BOX
ELECTRICAL
5 1/2
1 9/16
1 9/16
B
ELECTRICAL
6 7/8
BOX
OPTIONAL
B
5/8
A
35
5/8
36 1/4
AIR FLOW
15
3 1/8
BASE RAILS
OPTIONAL
4
4
4
1 1/21 1/2
MT'G HOLES
13/32 (x8)
O
TYPICAL
9/16 (x8)
9/16 (x12)
ELECT. BOX END
TYPICAL END VIEW
3 FAN
1 FAN
2 FAN
MOUNTING DIMENSIONS
WITHOUT OPTIONAL
BASE RAILS.
FRONT VIEW
2
TCS
03/11/15
T50-TCS-PDI-4
- 15 -
DIMENSIONAL DATA
HORIZONTAL AIR DISCHARGE UNITS
ELECTRICAL CONNECTION 7/8”
UNITS ARE SHIPPED IN HORIZONTAL
AIR FLOW CONFIGURATION LESS
OPTIONAL MOUNTING LEGS AS
STANDARD.
60Hz
MOUNTING DIMENSIONS
MODELFAN CONFIG.
INCHES(mm)INCHES(mm)
TCS 0021 x 123 5/8(600)25 1/2(648)
AB
TCS 0031 x 123 5/8(600)25 1/2(648)
TCS 0051 x 131 1/8(791)38(965)
TCS 0061 x 131 1/8(791)38(965)
TCS 0081 x 141 1/8(1045)38(965)
TCS 0101 x 241 1/8(1045)55 1/2(1410)
TCS 0121 x 241 1/8(1045)55 1/2(1410)
TCS 0141 x 241 1/8(1045)75 1/2(1918)
TCS 0161 x 241 1/8(1045)75 1/2(1918)
TCS 0191 x 341 1/8(1045)41 1/2(1054)
TCS 0241 x 341 1/8(1045)56 1/2(1435)
LBS (kg) LBS (kg)IN(mm) IN (mm) LBS (kg)IN(mm) IN(mm) LBS (kg)IN(mm) IN (mm)
CAPACITY
OPTION 1OPTION 2OPTION 3
*
DIAMETER LENGTH
CAPACITY
*
DIAMETERLENGTH
CAPACITY
*
DIAMETERLENGTH
* Based on 90% full.
Refrigerant charge conversion factors:
R407CR404A
1.00.910.911.050.921.06
R507
R22
R410A
R134a
TCS
03/11/15
T50-TCS-PDI-4
- 17 -
LOW AMBIENT OPERATION
60Hz
GENERAL
When air-cooled condensers are installed outdoors, they
will be subjected to varying ambient temperatures. This
variance could be as much as 120°F (48.9 °C) of swing
throughout the summer and winter seasons and will have
a major impact on the performance of the condenser. As
the ambient temperature drops, the condenser capacity will increase due to the wider temperature difference
between ambient and condensing temperature. As this
happens, the condensing temperature will also drop as the
system nds a new balance point. Although overall system
capacity will increase, other problems can occur. The capacity of an expansion valve is affected by both the liquid
temperature entering the valve and the pressure drop
across it. As the condensing temperature decreases, the
pressure drop across the metering device also decreases.
This lower pressure drop will then decrease the capacity of
the valve. Although lower liquid temperatures increase the
capacity of the metering device, the increase is not large
enough to offset the loss due to the lower pressure drop.
To provide adequate pressure drop, some form of head
pressure control is required. Refer to the following design
methods (covered in order of simplicity and features).
(i) Fan Cycling (Multiple Fans)
Cycling of the condenser fans helps regulate the condensing temperature. Using this approach, as the ambient
drops the fans are taken off-line either one at a time, or in
pairs. With multiple fan condensers, it is not recommended
to cycle more than two fans per step. The reason is that
the pressure in the condenser will increase drastically
as several fans are taken off-line at the same time. This
will result in erratic operation of the refrigeration system
and applies additional stress to the condenser tubes. It
is preferable to regulate the condensing temperature as
smoothly as possible. Fans should be cycled independently on single row condenser fan models. On double wide
condensers, when used with a single refrigeration circuit,
the fans should be cycled in pairs.
(ii) Variable Motor Speed Control
If additional head pressure control is required beyond the
last step of fan cycling variable fan motor speed may be
used. Variable motor speed is optional on all condenser
models. A varying motor speed may be accomplished using
a modulating temperature or modulating pressure control. A
variable speed controller can be an electronic or solid state
device which varies the voltage going to the motor depending on the temperature or pressure of the medium being
sensed.
(iii) Refrigerant Regulating Controls
Pressure regulating controls are available from a number
of valve manufacturers. The purpose of such a control is
to regulate the refrigerant ow in such a way as to maintain a pre-selected condensing pressure. In lower ambient
temperatures, these valves throttle to maintain the desired
pressure and in doing so, ood the condenser with liquid
refrigerant.The larger the condenser surface is, the higher
its capacity will be. When a condenser is ooded, its useful
condensing surface is reduced. This is because the refrigerant occupies the space which would otherwise be used
for condensing.
Some control/check valve combinations will regulate
refrigerant ow depending on the pressure at the inlet of
the condenser.These are often referred to as inlet regulators. As the valve closes, hot gas bypasses the condenser
through a differential check valve to increase the pressure
at the receiver.
Ambient temperature or pressure sensing controls can be
set to bring on (or off) certain fans when the outdoor temperature or condensing pressures reach a predetermined
condition. Temperature or pressure set points and differentials should be correctly set to prevent short cycling of the
fans. Constant short cycling will produce volatile condensing pressures, erratic refrigeration performance, decreased
fan motor life, and added stress to the condenser tubes.
For recommended fan cycling switch settings, refer to
Tables 4 and 5. Differential settings on fan cycling temperature controls should be no lower than 3.5°F (2°C). On
fan cycling pressure controls with R404A, a differential of
approximately 35 psig is recommended. On supermarket
applications remote condenser fans may be cycled individually (not in pairs) and therefore lower differential settings
may apply and will depend on the specic application.
Fans closest to the inlet header must run whenever the
compressor is running and should NEVER be cycled since
sudden stress changes placed on these inlet tubes and
headers will dramatically shorten the life of the condenser.
Table 1 shows the fan cycling congurations and options
available for all remote condenser models.
LOW AMBIENT OPERATION
CONDENSER
SINGLEVALVE
HEAD
PRESSURE
CONTROL
LIQUID RECEIVER
CONDENSER
ORI
VALVE
LIQUID RECEIVER
03/11/15
T50-TCS-PDI-4
- 18 -
TCS60Hz
ORD
DIFFERENTIAL
CHECK VALVE
SINGLE VALVE CONDENSER PRESSURE CONTROL
(Regulates inlet pressure or outlet pressure depending on valve design)
This will ood the condenser until the condensing
pressure increases to a point which will again open
the valve. Other valves regulate the refrigerant at the
outlet of the condenser to provide a similar effect.
These are commonly referred to as outlet regulators.
There are also combination inlet/outlet
regulators with a differential check valve or other
type of condenser bypass arrangement incorporated
within the valve.
Controls which regulate the ow of refrigerant based
on condenser inlet pressure are typically used in
conjuction with a check valve having a minimum
opening differential across the condenser. Outlet
regulators typically require a check valve with a xed
pressure differential setting of between 20 and 35
psi. The differential is needed to compensate for
pressure drop through the condenser
during ooding and associated discharge piping.
Systems equipped with a condenser ooding
arrangement should always use a receiver having
sufcient liquid holding capacity. Additional liquid
required for ooding is only required during the winter
low ambients and must be stored somewhere in the
system at the higher ambients. Failure to use an
adequately sized receiver will result in liquid back-up
in the condenser during the warmer summer months.
This will cause the system to develop very high
pressures in the high side resulting in a high pressure
safety control trip.
ORI / ORD CONDENSER PRESSURE CONTROL
Determining Additional Flooded
Refrigerant Charge
Additional charge will vary with the condenser
design TD and the coldest expected ambient
temperature. Condensers designed for low TD
applications (low temperature evaporators) and
operating in colder ambients will require more
additional charge than those designed for higher
TD applications (high temperature evaporators)
and warmer ambients.
Refer to tables on pages 21-22 to determine
the required added refrigerant charge at the
selected TD and ambient temperatures.
These charges are based on condensers using Fan
Cycling options with their last fan (Single Row Fan
Models) running or last pair of fans running (Double
Row Fan models).
WARNING: Do not over charge when charging by a
sightglass. Liquid lines feeding the TXV at the
evaporator must have a solid column of liquid (no
bubbles) however bubbles at the sightglass (located
adjacient to the receiver) may be normal due to the
result of a higher pressure drop at that point. Bubbles
could also appear in the glass whenever the
regulating valves start to ood the condenser.
Always record the number of drums or the weight of
refrigerant that has been added or removed in the
system. Overcharged systems may result in
compressor failure as well as other serious mechanical
damage to the system components.
LOW AMBIENT OPERATION
FAN
1
FAN
2
FAN
1
FAN
3
FAN
1
FAN
2
03/11/15
T50-TCS-PDI-4
- 19 -
TCS
Table 1 - Fan Cycling Control Schedule
FAN ARRANGEMENT
SINGLE ROW
1 FAN
HEADER END
CONTROL
PANEL END
2 FAN
3 FAN
FANS CYCLED
1 STAGE
2’ND STAGE
1’ST STAGE
FANS AVAILABLE
FOR VARIABLE
SPEED CONTROL
60Hz
FANS IN CONSTANT
OPERATION
Table 2 - Ambient Fan Cycling Thermostat Cut-Out Settings
Table 3 - Pressure Fan Cycling Cut-In Control Settings
NUMBER OF FANS ON
CONDENSER
Single Row Models1st Stage 2nd Stage
220
320
DESIGN
T.D.
R407A
R407A
REFRIGERANT
R134a
R22
R134a
R22
R404A
R407C
R407C R404A
R507
R507
CONTROL SETTINGS
Pressure Switch
Cut-In Settings PSIG
147
215
220
147155
215245
220247
FAN CYCLING CONTROLS SHOULD BE SET TO MAINTAIN A
MINIMUM OF (5) FIVE MINUTES ON AND (5) MINUTES OFF.
SHORT CYCLING FANS CAN RESULT IN PREMATURE
FAILURE OF FAN BLADES AND/OR FAN MOTORS
LOW AMBIENT OPERATION
03/11/15
T50-TCS-PDI-4
- 20 -
TCS60Hz
FLOODED CONDENSER WITH FAN CYCLING
Design TD = 25
WINTER OPERATION CHARGE -
REFRIGERANT CHARGE
MODEL
TCS 0021 x 13.3(1.5)0.8(0.3)0.7(0.3)1.0(0.4)1.1(0.4)1.1(0.6)1.2(0.6)
TCS 0031 x 15.3(2.4)1.2(0.6)1.1(0.4)1.5(0.7)1.7(0.8)1.9(0.9)2.0(0.9)
TCS 0051 x 17.4(3.4)1.7(0.8)1.4(0.7)2.2(1.0)2.4(1.1)2.6(1.2)2.8(1.2)
TCS 0061 x 110.8(5.0)2.4(1.1)2.2(1.0)3.1(1.4)3.4(1.5)3.7(1.8)4.0(1.8)
TCS 0081 x 116.2(7.3)3.6(1.7)3.2(1.4)4.6(2.1)5.2(2.3)5.6(2.5)5.9(2.8)
TCS 0101 x 215.8(7.2)3.5(1.7)0.0(0.0)2.6(1.2)4.6(2.1)5.5(2.5)6.4(2.9)
TCS 0121 x 222.7(10.2)5.1(2.3)0.0(0.0)3.9(1.8)6.6(3.0)7.9(3.6)9.0(4.1)
TCS 0141 x 230.7(14.0)6.8(3.1)0.0(0.0)5.2(2.4)8.9(4.1)10.8(4.8)12.3(5.6)
TCS 0161 x 230.7(14.0)6.8(3.1)0.0(0.0)5.2(2.4)8.9(4.1)10.8(4.8)12.3(5.6)
TCS 0191 x 335.0(15.8)7.8(3.5)0.0(0.0)1.8(0.8)1.8(0.8)10.5(4.7)12.2(5.5)
TCS 0241 x 346.0(20.9)10.2(4.6)0.0(0.0)2.3(1.0)2.3(1.0)13.8(6.3)16.1(7.3)
NOTES:
To determine Winter Charge, ADD the sum of the Summer Charge and the Additional Winter Charge.
USING FAN CYCLING (2 and 3 FAN) and FLOODED CONTROLS
ADDITIONAL WINTER CHARGE -
AMBIENT TEMP. - °F (°C)
Design TD = 20
REFRIGERANT CHARGE
MODEL
TCS 0021 x 13.3(1.5)0.8(0.3)0.8(0.3)1.1(0.4)1.1(0.6)1.2(0.6)1.3(0.6)
TCS 0031 x 15.3(2.4)1.2(0.6)1.3(0.6)1.7(0.8)1.9(0.9)2.0(0.9)2.1(0.9)
TCS 0051 x 17.4(3.4)1.7(0.8)1.9(0.9)2.4(1.1)2.5(1.2)2.8(1.2)2.9(1.3)
TCS 0061 x 110.8(5.0)2.4(1.1)2.8(1.2)3.4(1.5)3.7(1.7)4.0(1.8)4.2(1.9)
TCS 0081 x 116.2(7.3)3.6(1.7)4.1(1.9)5.2(2.3)5.6(2.5)5.9(2.8)6.2(2.9)
TCS 0101 x 215.8(7.2)3.5(1.7)1.3(0.7)4.1(1.9)4.6(2.1)6.2(2.8)6.9(3.1)
TCS 0121 x 222.7(10.2)5.1(2.3)1.9(0.9)5.8(2.6)6.6(3.0)8.8(4.0)9.8(4.5)
TCS 0141 x 230.7(14.0)6.8(3.1)2.6(1.2)8.0(3.6)8.9(4.1)12.0(5.4)13.3(6.1)
TCS 0161 x 230.7(14.0)6.8(3.1)2.6(1.2)8.0(3.6)8.9(4.1)12.0(5.4)13.3(6.1)
TCS 0191 x 335.0(15.8)7.8(3.5)0.0(0.0)6.6(3.0)7.4(3.3)12.4(5.6)14.0(6.4)
TCS 0241 x 346.0(20.9)10.2(4.6)0.0(0.0)8.7(4.0)9.7(4.4)16.3(7.4)18.4(8.4)
NOTES:
To determine Winter Charge, ADD the sum of the Summer Charge and the Additional Winter Charge.
USING FAN CYCLING (2 and 3 FAN) and FLOODED CONTROLS
ADDITIONAL WINTER CHARGE -
AMBIENT TEMP. - °F (°C)
Refrigerant charge conversion factors:
R407CR404A
1.00.910.911.050.921.06
R507
R22
R410A
R134a
TCS
03/11/15
T50-TCS-PDI-4
- 21 -
Design TD = 15
LOW AMBIENT OPERATION
WINTER OPERATION CHARGE -
FLOODED CONDENSER WITH FAN CYCLING
60Hz
REFRIGERANT CHARGE
MODEL
TCS 0021 x 13.3(1.5)0.8(0.3)1.0(0.4)1.2(0.6)1.2(0.6)1.3(0.6)1.3(0.7)
TCS 0031 x 15.3(2.4)1.2(0.6)1.7(0.8)1.9(0.9)2.0(0.9)2.1(1.0)2.2(1.0)
TCS 0051 x 17.4(3.4)1.7(0.8)2.3(1.0)2.6(1.2)2.9(1.3)3.0(1.3)3.1(1.4)
TCS 0061 x 110.8(5.0)2.4(1.1)3.3(1.5)3.9(1.8)4.1(1.9)4.3(2.0)4.4(2.0)
TCS 0081 x 116.2(7.3)3.6(1.7)5.0(2.3)5.7(2.6)6.2(2.8)6.5(3.0)6.6(3.0)
TCS 0101 x 215.8(7.2)3.5(1.7)3.9(1.8)5.4(2.4)6.4(2.9)7.2(3.2)7.6(3.4)
TCS 0121 x 222.7(10.2)5.1(2.3)5.4(2.4)7.7(3.5)9.0(4.1)10.2(4.6)10.9(5.0)
TCS 0141 x 230.7(14.0)6.8(3.1)7.4(3.3)10.5(4.7)12.3(5.6)13.9(6.3)14.7(6.7)
TCS 0161 x 230.7(14.0)6.8(3.1)7.4(3.3)10.5(4.7)12.3(5.6)13.9(6.3)14.7(6.7)
TCS 0191 x 335.0(15.8)7.8(3.5)5.9(2.8)10.9(5.0)13.4(6.2)15.4(6.9)16.4(7.5)
TCS 0241 x 346.0(20.9)10.2(4.6)7.8(3.5)14.3(6.5)17.7(8.0)20.2(9.1)21.7(9.8)
NOTES:
To determine Winter Charge, ADD the sum of the Summer Charge and the Additional Winter Charge.
USING FAN CYCLING (2 and 3 FAN) and FLOODED CONTROLS
ADDITIONAL WINTER CHARGE -
AMBIENT TEMP. - ° F (°C)
Design TD = 10
REFRIGERANT CHARGE
MODEL
TCS 0021 x 13.3(1.5)0.8(0.3)1.2(0.6)1.3(0.6)1.3(0.7)1.4(0.7)1.4(0.7)
TCS 0031 x 15.3(2.4)1.2(0.6)1.9(0.9)2.1(1.0)2.2(1.0)2.2(1.0)2.2(1.0)
TCS 0051 x 17.4(3.4)1.7(0.8)2.6(1.2)2.9(1.3)3.1(1.4)3.1(1.4)3.2(1.4)
TCS 0061 x 110.8(5.0)2.4(1.1)3.9(1.8)4.2(1.9)4.4(2.0)4.5(2.1)4.6(2.1)
TCS 0081 x 116.2(7.3)3.6(1.7)5.7(2.6)6.3(2.9)6.6(3.0)6.8(3.1)6.8(3.1)
TCS 0101 x 215.8(7.2)3.5(1.7)5.8(2.6)7.2(3.2)7.8(3.5)8.4(3.9)8.9(4.1)
TCS 0121 x 222.7(10.2)5.1(2.3)8.3(3.7)10.2(4.6)11.1(5.1)12.0(5.4)12.7(5.7)
TCS 0141 x 230.7(14.0)6.8(3.1)11.2(5.1)13.9(6.3)15.1(6.8)16.3(7.4)17.2(7.8)
TCS 0161 x 230.7(14.0)6.8(3.1)11.2(5.1)13.9(6.3)15.1(6.8)16.3(7.4)17.2(7.8)
TCS 0191 x 335.0(15.8)7.8(3.5)11.7(5.3)15.1(6.8)16.9(7.7)18.2(8.3)19.6(8.9)
TCS 0241 x 346.0(20.9)10.2(4.6)15.4(7.0)19.8(9.0)22.3(10.1)23.9(10.9)25.7(11.7)
NOTES:
To determine Winter Charge, ADD the sum of the Summer Charge and the Additional Winter Charge.
USING FAN CYCLING (2 and 3 FAN) and FLOODED CONTROLS
ADDITIONAL WINTER CHARGE -
AMBIENT TEMP. - ° F (°C)
Refrigerant charge conversion factors:
R407CR404A
1.00.910.911.050.921.06
R507
R22
R410A
R134a
INSTALLATION
4 ft
(1.25 m)
min.
8 ft
(2.5 m)
min.
4 ft
(1.25 m)
min.
4 ft
(1.25 m)
min.
03/11/15
T50-TCS-PDI-4
- 22 -
TCS60Hz
INSPECTION
A thorough inspection of the equipment, including all
component parts and accessories, should be made
immediately upon delivery. Any damage caused in transit,
or missing parts, should be reported to the carrier at once.
The consignee is responsible for making any claim for
losses or damage. Electrical characteristics should also
be checked at this time to ensure that they are correct.
LOCATION
Before handling and placing the unit into position a review
of the most suitable location must be made. This
condenser is designed for outdoor installation.
A number of factors must be taken into consideration
Horizontal Air Discharge
(Standard Shipping Conguration)
when selecting a location. Most important is the provision
for a supply of ambient air to the condenser, and removal
of heated air from the condenser area.
Higher condensing temperatures, decreased
performance, and the possibility of equipment failure
may result from inadequate air supply.
Other considerations include:
1. Customer requests
2. Loading capacity of the roof or oor.
3. Distance to suitable electrical supply.
4. Accessibility for maintenance.
5. Local building codes.
6. Adjacent buildings relative to noise levels.
WALLS OR OBSTRUCTIONS
All sides of the unit must be a minimum of 4 feet
(1.25 m) away from any wall or obstruction. Overhead
obstructions are not permitted. If enclosed by three
walls, the condenser must be installed as indicated for
units in a pit.
LOUVERS/FENCES
Louvers/fences must have a minimum of 80% free area
and 4 feet (1.25 m) minimum clearance between the
unit and louvers/fence. Height of louver/fence
must not exceed top of unit.
MULTIPLE UNITS
A minimum of 8 feet (2.5 m) is required between
multiple units placed side by side. If placed end to end,
the minimum distance between units is 4 feet(1.25 m).
Note: Units shown without optional mounting legs
4 ft
(1.25 m)
min.
8 ft
(2.5 m)
min.
8 ft
(2.5 m)
min.
8 ft
(2.5 m)
min.
4 ft
(1.25 m)
min.
4 ft
(1.25 m)
min.
TCS
03/11/15
T50-TCS-PDI-4
- 23 -
INSTALLATION
60Hz
V ertical Air Discharge
(Requires Optional Mounting Leg Kit)
WALLS OR OBSTRUCTIONS
All sides of the unit must be a minimum of 4 feet
(1.25 m) away from any wall or obstruction. Overhead
obstructions are not permitted. If enclosed by three
walls, the condenser must be installed as indicated for
units in a pit.
UNITS IN PITS
The top of the condenser must be level with, or above
the top of the pit. In addition, a minimum of 8 feet (2.5 m) is required between the unit and the pit walls.
MULTIPLE UNITS
A minimum of 8 feet (2.5 m) is required between
multiple units placed side by side. If placed end to end,
the minimum distance between units is 4 feet(1.25 m).
LOUVERS/FENCES
Louvers/fences must have a minimum of 80% free area
and 4 feet (1.25 m) minimum clearance between the
unit and louvers/fence. Height of louver/fence
must not exceed top of unit.
PLACEMENT
Once a suitable location is selected ensure all the remote
mounting parts (legs and hardware) are available. Refer to
Fig.1b (P. 26) and the dimensional data on pages 14-15 for
the leg mounting locations.
Note: Units shown with optional mounting legs
INSTALLATION
03/11/15
T50-TCS-PDI-4
- 24 -
TCS60Hz
Fig. 1 - LIFTING / OPTIONAL LEG INSTRUCTIONS
Fig. 1a - LIFTING POSITIONS
FOR HORIZONTAL AIR FLOW
CONFIGURATION
Lower unit into vertical
air ow position, taking
care not to damage coil surface
under unit.
Optional horizontal
leg kit shown.
For horizontal air ow
conguration, Outlet
header connection
MUST be at the bottom.
Air cooled condensers are large, heavy mechanical
equipment and must be handled as such. A fully qualied
and properly equipped crew with necessary rigging should
be engaged to set the condenser into position. Lifting
brackets or holes have been provided at the
corners for attaching lifting slings. Spreader bars must be
used when lifting so that the lifting force must be
applied vertically. Under no circumstances should the
coil headers or return bends be used in lifting or
moving the condenser.
Ensure the unit is placed in a level position (to ensure
proper drainage of liquid refrigerant and oil). The legs
should be securely anchored to the building structure,
sleeper or concrete pad. The weight of the condenser is
not enough to hold in place during a strong wind, the legs
must be anchored.
Fig. 1b - LIFTING POSITIONS
FOR MOVING INTO VERTICAL
AIR FLOW POSITION
Legs are fastened to
end panel side anges
usiing 5/16-18 bolts and
lock-nuts provided with
optional leg kit.
DISCHARGE LINES
Discharge lines should be designed to minimize
refrigerant pressure drop, since high pressure losses
increase the required compressor horsepower per ton of
refrigeration.
Discharge lines must be pitched away from the
compressor to ensure proper drainage of oil being
carried in the line.
A discharge check-valve at the bottom of a vertical riser
will prevent oil (and liquid refrigerant) from draining back
to the compressor during the off-cycle. When the vertical
lift exceeds 30 feet(10 m), insert close-coupled traps in
the riser at 30 feet(10 m) intervals.
An alternate method of handling the oil problem would
be the addition of an oil separator see Figure 3 (b).
REFRIGERANT PIPING
All refrigeration piping must be installed by a qualied
refrigeration mechanic. The importance of correct
refrigerant pipe sizing and layout cannot be overemphasized. Failure to observe proper refrigerant piping
practices can result in equipment failure which may not be
covered under warranty.
All air cooled condensers are supplied complete with
headers and refrigerant connections sized for connecting
to standard refrigeration tubing.These connections may
not be the same as the actual line sizes required for the
eld installation. Refer to a recognized source (ASHRAE
charts, manufacturer’s engineering manuals etc.) for line
sizing.
A reverse trap should be installed at the top of all vertical
risers. The top of the reverse trap should be the highest
point in the discharge line and should have an access
valve installed to allow the reclaimation of non-condensible
gas from the system.
Pulsation of the hot gas in the discharge line is an inherent
characteristic of systems utilizing reciprocating
compressors. The discharge line must be rigidly
supported along its entire length to prevent transmission
of vibration and movement of the line.
CONDENSATE LINES
The condensate line must be designed to allow free
drainage of refrigerant from the condenser coil to the
receiver. Refer to Fig. 4 for typical condensate line piping
when utilizing head pressure regulating valves.
TCS
03/11/15
T50-TCS-PDI-4
- 25 -
Fig. 2 - 5
INSTALLATION
TYPICAL SYSTEM PIPING
60Hz
Figure 2 - Single Circuit
Figure 4 - Single circuit regulator valve
head pressure control
Figure 3(a) - Single circuit with
double discharge riser
(may be required with
capacity control)
Figure 5 - Multiple circuits
Figure 3(b) - Single circuit with
Oil Separator (may be
required with capacity
control)
All wiring and connections to the air cooled condenser
must be made in accordance with the National Electrical Code and all local codes and regulations. Any wiring
diagrams shown are basic and do not necessarily
include electrical components which must be eld
supplied. (see pages 5-9 and 11-12 for typical wiring
diagrams).
Refer to the Electrical Specications table on pages
4 and 10 for voltage availability and entering service
requirements.
SYSTEM START-UP CHECKS
1. Check the electrical characteristics of all components
to be sure they agree with the power supply.
2. Check tightness of all fans and motor mounts.
3. Check tightness of all electrical connections.
4. Upon start-up, check fans for correct rotation. Air is
drawn through the condenser coil. To change rotation
on 3 phase units reverse any two (2) fan motor leads.
5. All system piping must be thoroughly leak checked
before a refrigerant charge is introduced.
MAINTENANCE
03/11/15
T50-TCS-PDI-4
- 26 -
TCS
The most effective way to prevent potential problems with this air cooled condenser is to have a SEMI-ANNUAL
INSPECTION performed by a qualied refrigeration service mechanic.
60Hz
1. WHEN SERVICING EQUIPMENT, THE MAIN POWER
SUPPLY MUST BE DISCONNECTED TO PREVENT
POTENTIAL HAZARDOUS RISK.
2. Check all electrical components for damage.
Tighten any loose connections.
3. Check settings of all controls to ensure proper operation.
4. Look for any wear on wires or refrigerant lines that may
have been caused by excessive vibrations or rubbing on
metal parts
SERVICE PARTS
FOR SERVICE PARTS LOOK-UP:
visit: http://www.t-rp.com/serv_parts.htm
email: parts@t-rp.com
call: 1-844-893-3222 x501
5. Short cycling fan motors can result in premature failure
of the fan blades and/or motors. Failing to correct this
problem may, over time, cause the rivets on fan blades
to become loose. If this happens, the fan blade may
crack or tear, causing extreme vibration, potentially
triggering the motor and mounts to fail.
6. Check the tightness of all fan blades and motors.
Remove any dirt or debris that could affect the balance
of the fan blade.
7. Fan motors are permanently lubricated and require only
visual inspection
FINISHED GOODS WARRANTY
03/11/15
T50-TCS-PDI-4
- 27 -
The terms and conditions as described below in the General Warranty Policy cover all products
manufactured by National Refrigeration.
GENERAL WARRANTY POLICY
Subject to the terms and conditions hereof, the Company warrants all Products, including Service
Parts, manufactured by the Company to be free of defects in material or workmanship, under normal use and application for a period of one (1) year from the original date of installation, or eighteen
(18) months from the date of shipment from the Company, whichever occurs rst. Any replacement
part(s) so supplied will be warranted for the balance of the product’s original warranty. The part(s) to
be replaced must be made available in exchange for the replacement part(s) and reasonable proof
of the original installation date of the product must be presented in order to establish the effective
date of the warranty, failing which, the effective date will be based upon the date of manufacture plus
thirty (30) days. Any labour, material, refrigerant, transportation, freight or other charges incurred in
connection with the performance of this warranty will be the responsibility of the owner at the current rates and prices then in effect. This warranty may be transferred to a subsequent owner of the
product.
THIS WARRANTY DOES NOT COVER
(a) Damages caused by accident, abuse, negligence, misuse, riot, re, ood, or Acts of God (b) damages
caused by operating the product in a corrosive atmosphere (c) damages caused by any unauthorized
alteration or repair of the system affecting the product’s reliability or performance (d) damages caused
by improper matching or application of the product or the product’s components (e) damages caused by
failing to provide routine and proper maintenance or service to the product (f) expenses incurred for the
erecting, disconnecting, or dismantling the product (g) parts used in connection with normal maintenance,
such as lters or belts (h) products no longer at the site of the original installation (i) products installed
or operated other than in accordance with the printed instructions, with the local installation or building
codes and with good trade practices (j) products lost or stolen.
No one is authorized to change this WARRANTY or to create for or on behalf of the Company any
other obligation or liability in connection with the Product(s). There is no other representation, warranty
or condition in any respect, expressed or implied, made by or binding upon the Company other than
the above or as provided by provincial or state law and which cannot be limited or excluded by such
law, nor will we be liable in any way for incidental, consequential, or special damages however caused.
The provisions of this additional written warranty are in addition to and not a modication of or subtraction
from the statutory warranties and other rights and remedies provided by Federal, Provincial or State laws.
PROJECT INFORMATION
System
Model NumberDate of Start-Up
Serial NumberService Contractor
RefrigerantPhone
Electrical SupplyFax
“AS BUILT” SERVICE PARTS
03/11/15
Service Parts List
Label
To Be Attached
HERE
NATIONAL REFRIGERATION &
AIR CONDITIONING CANADA CORP.