• Internally Enhanced Tubing with Enhanced Fin
optimizes coil performance
• Energy Efcient PSC and 3 Phase Fan Motors with Internal Overload Protection
TM
Coil Design eliminates tube
Fans Deep
Fans Wide
1 = Inline; 2 = Double Wide
Motor
A = 1075 RPM, 3/4 HP Motor
M = EC Motor - Motor Only
(Conventional Shafted Style Motor)
Design version
• Quiet ‘Swept Wing’ Fan Blade
• Fan Sections Individually Bafed with
Clean-out Panels
• Zinc Plated Huck Bolts
• Heavy Duty 24” Legs
• Double fan wide models have Two Equal
Circuits
• Control Circuit Voltage – 230 V
• Unit shipped with Nitrogen Holding Charge
• Multiple Refrigeration Circuits
• Ambient or Pressure Fan Cycling Control with
Contactor
• Efcient Variable Speed EC Motors (see pg. 15)
• Variable speed motor with controller
for header fan motors
• Individual Fan Motor Fusing
• Non-Fused Disconnect
• Receiver with or without Heater and Insulation
OPTIONAL FEATURES
• Adjustable Flooded Head Pressure Control
(factory mounted if ordered with receiver option)
• Optional Fin Materials and Coatings
• Voltages Available for 60Hz or 50Hz
• Extended 48” Leg Kit with Cross Bracing
• Horizontal Conguration
• Optional Fin Materials
• Optional Coil Coatings
CAPACITY DATA -
03/10/15
T50-TCM-PDI-4
- 3 -
TCM60Hz
SINGLE ROW MODELS
MODEL
NUMBER
TCM009101 x 14.05(1.20)4.18(1.24)4.40(1.30)4.49(1.33)4.27(1.26)8
TCM010121 x 14.39(1.29)4.53(1.33)4.77(1.40)4.87(1.43)4.63(1.36)8
TCM011101 x 14.88(1.47)5.04(1.52)5.30(1.60)5.41(1.63)5.14(1.55)8
TCM012121 x 15.24(1.56)5.42(1.62)5.70(1.70)5.81(1.73)5.53(1.65)8
TCM01381 x 25.72(1.66)5.91(1.71)6.22(1.80)6.34(1.84)6.03(1.75)10
TCM014101 x 26.36(1.84)6.56(1.90)6.91(2.00)7.05(2.04)6.70(1.94)10
TCM016121 x 27.04(2.02)7.27(2.09)7.65(2.20)7.80(2.24)7.42(2.13)10
TCM01781 x 27.54(2.21)7.79(2.28)8.20(2.40)8.36(2.45)7.95(2.33)16
TCM018101 x 28.10(2.39)8.36(2.47)8.80(2.60)8.98(2.65)8.54(2.52)16
TCM020121 x 28.69(2.58)8.98(2.66)9.45(2.80)9.64(2.86)9.17(2.72)16
TCM02181 x 29.39(2.76)9.70(2.85)10.2(3.00)10.4(3.06)9.90(2.91)16
TCM022101 x 29.75(2.85)10.1(2.95)10.6(3.10)10.8(3.16)10.3(3.01)16
TCM024121 x 210.4(3.04)10.8(3.14)11.3(3.30)11.6(3.37)11.0(3.20)16
TCM02581 x 311.2(3.31)11.6(3.42)12.2(3.60)12.4(3.67)11.8(3.49)24
TCM028101 x 312.3(3.59)12.7(3.71)13.3(3.90)13.6(3.98)12.9(3.78)24
TCM030121 x 313.2(3.86)13.6(3.99)14.3(4.20)14.6(4.28)13.9(4.07)24
TCM03281 x 313.9(4.05)14.4(4.18)15.1(4.40)15.4(4.49)14.7(4.27)21
TCM033101 x 314.6(4.23)15.0(4.37)15.8(4.60)16.2(4.69)15.4(4.46)21
TCM035121 x 315.5(4.51)16.0(4.66)16.8(4.90)17.1(5.00)16.3(4.75)21
TCM03781 x 416.1(4.69)16.7(4.85)17.5(5.10)17.9(5.20)17.0(4.95)24
TCM039101 x 417.2(5.06)17.7(5.23)18.7(5.50)19.1(5.61)18.1(5.34)24
TCM041121 x 418.1(5.34)18.7(5.51)19.7(5.80)20.1(5.92)19.1(5.63)24
TCM04381 x 419.0(5.52)19.6(5.70)20.6(6.00)21.0(6.12)20.0(5.82)32
TCM045101 x 420.0(5.89)20.7(6.08)21.8(6.40)22.2(6.53)21.1(6.21)32
TCM048121 x 421.1(6.16)21.7(6.37)22.9(6.70)23.3(6.83)22.2(6.50)32
FPIFAN CONFIG.
TOTAL HEAT OF REJECTION - MBH (KW) PER 1 °F (0.56 °C) TDMAX.
R407A
R407CR404A
R507
R22
R410A
R134a
NO. OF
FEEDS
NOTES:
- Above capacity data based on 0oF subcooling and at sea level.
- For High Altitude applications apply the following correction factors: 0.94 for 2000 feet, 0.88 for 4000 feet and 0.81 for 6000 feet.
- Capacities at other TD within a range of 10 to 30 °F (-12.2 to -1°C) are directly proportional to TD, or use formula: Capacity = Rated capacity ÷ 10 x TD.
- For 50 HZ capacity multiply by 0.92. (no derate with EC motors)
- Capacities for R407A and R407C are based on mean temperature. Mean temperature is the average temperature between the saturated condensing
temperatures at the inlet and outlet of the condenser. For dew point ratings, consult factory.
CAPACITY DATA -
03/10/15
T50-TCM-PDI-4
- 4 -
TCM60Hz
DOUBLE ROW MODELS
MODEL
NUMBER
TCM 03482 x 215.1(4.42)15.6(4.56)16.4(4.80)16.7(4.90)15.9(4.66)32
TCM 036102 x 216.2(4.78)16.7(4.94)17.6(5.20)18.0(5.30)17.1(5.04)32
TCM 040122 x 217.4(5.06)17.9(5.23)18.9(5.50)19.3(5.61)18.3(5.34)32
TCM 04282 x 218.8(5.52)19.4(5.70)20.4(6.00)20.8(6.12)19.8(5.82)32
TCM 044102 x 219.5(5.70)20.1(5.89)21.2(6.20)21.6(6.32)20.6(6.01)32
TCM 047122 x 220.9(6.07)21.5(6.27)22.7(6.60)23.1(6.73)22.0(6.40)32
TCM 05182 x 322.4(6.53)23.2(6.75)24.4(7.10)24.9(7.24)23.6(6.89)48
TCM 056102 x 324.5(7.18)25.3(7.41)26.7(7.80)27.2(7.96)25.9(7.57)48
TCM 060122 x 326.3(7.73)27.2(7.98)28.6(8.40)29.2(8.57)27.7(8.15)48
TCM 06382 x 327.8(8.19)28.7(8.46)30.3(8.90)30.9(9.08)29.3(8.63)42
TCM 066102 x 329.2(8.56)30.1(8.84)31.7(9.30)32.3(9.49)30.7(9.02)42
TCM 070122 x 330.9(9.02)31.9(9.31)33.6(9.80)34.3(10.0)32.6(9.51)42
TCM 07382 x 432.3(9.48)33.3(9.79)35.1(10.3)35.8(10.5)34.0(9.99)48
TCM 078102 x 434.4(10.0)35.5(10.4)37.4(10.9)38.1(11.1)36.2(10.6)48
TCM 082122 x 436.2(10.6)37.4(10.9)39.4(11.5)40.2(11.7)38.2(11.2)48
TCM 08682 x 437.9(11.1)39.1(11.5)41.2(12.1)42.0(12.3)40.0(11.7)64
TCM 090102 x 440.1(11.8)41.4(12.2)43.6(12.8)44.4(13.1)42.2(12.4)64
TCM 095122 x 442.1(12.3)43.5(12.7)45.8(13.4)46.7(13.7)44.4(13.0)64
FPIFAN CONFIG.
TOTAL HEAT OF REJECTION - MBH (KW) PER 1 °F (0.56 °C) TDMAX.
R407A
R407CR404A
R507
R22
R410A
R134a
NO. OF
FEEDS
NOTES:
- Above capacity data based on 0oF subcooling and at sea level.
- For High Altitude applications apply the following correction factors: 0.94 for 2000 feet, 0.88 for 4000 feet and 0.81 for 6000 feet.
- Capacities at other TD within a range of 10 to 30 °F (-12.2 to -1°C) are directly proportional to TD, or use formula: Capacity = Rated capacity ÷ 10 x TD.
- For 50 HZ capacity multiply by 0.92. (no derate with EC motors)
- Capacities for R407A and R407C are based on mean temperature. Mean temperature is the average temperature between the saturated condensing
temperatures at the inlet and outlet of the condenser. For dew point ratings, consult factory.
(2) Normal charge is the refrigerant charge for warm ambient or summer operation.
(3) 90% full is the liquid refrigerant weight at 90% of internal volume and is for reference only.(4) For 50 Hz fan data use 60 Hz CFM (m3/h) X 0.83 (no derate with EC motors)
(5) Sound pressure level at 10 ft. (3 m)
R407C
1.00.910.911.050.921.06
R404A
R507
R22
R410A
R134a
GENERAL SPECIFICATIONS -
03/10/15
T50-TCM-PDI-4
- 7 -
TCM60Hz
DOUBLE ROW MODELS
R407A
MODEL
NUMBER
TCM0342
TCM0362
TCM0402
TCM0422
TCM0442
TCM0472
TCM0513
TCM0563
TCM0603
TCM0633
TCM0663
TCM0703
TCM0734
TCM0784
TCM0824
TCM0864
TCM0904
TCM0954
FANS
LONG
R407A
REFRIG. CHARGE
(2)
90% FULL
(3)
LBS
(Kg)
61.6
(27.9)
61.6
(27.9)
61.6
(27.9)
79.2
(35.9)
79.2
(35.9)
79.2
(35.9)
93.5
(42.4)
93.5
(42.4)
93.5
(42.4)
120
(54.4)
120
(54.4)
120
(54.4)
127
(57.7)
127
(57.7)
127
(57.7)
162
(73.5)
162
(73.5)
162
(73.5)
NORMAL
LBS
(Kg)
15.6
(7.10)
15.6
(7.10)
15.6
(7.10)
19.5
(8.83)
19.5
(8.83)
19.5
(8.83)
23.8
(10.8)
23.8
(10.8)
23.8
(10.8)
29.5
(13.4)
29.5
(13.4)
29.5
(13.4)
32.5
(14.7)
32.5
(14.7)
32.5
(14.7)
40.0
(18.2)
40.0
(18.2)
40.0
(18.2)
(1)
AIR FLOW
RATES
CFM
(m
28400
(48252)
27500
(46723)
26600
(45194)
27400
(46553)
26500
(45024)
25600
(43495)
42600
(72378)
41200
(69999)
39800
(67621)
41100
(69829)
39700
(67451)
38400
(65242)
56800
(96504)
55000
(93446)
53100
(90217)
54800
(93106)
53000
(90048)
51200
(86989)
SOUND
LEVEL
(5)
3
/h)
dBA
55
55
55
55
55
55
57
57
57
57
57
57
58
58
58
58
58
58
16°F to 30°F DESIGN TD10°F to 15°F DESIGN TD
INLETOUTLET
INCHES
(mm)
1 5/8
(41)
1 5/8
(41)
1 5/8
(41)
1 5/8
(41)
1 5/8
(41)
1 5/8
(41)
2 1/8
(54)
2 1/8
(54)
2 1/8
(54)
2 1/8
(54)
2 1/8
(54)
2 1/8
(54)
2 5/8
(67)
2 5/8
(67)
2 5/8
(67)
2 5/8
(67)
2 5/8
(67)
2 5/8
(67)
PIPING CONNECTIONS
INCHES
(mm)
1 1/8
(29)
1 1/8
(29)
1 1/8
(29)
1 1/8
(29)
1 1/8
(29)
1 1/8
(29)
1 3/8
(35)
1 3/8
(35)
1 3/8
(35)
1 3/8
(35)
1 3/8
(35)
1 3/8
(35)
1 5/8
(41)
1 5/8
(41)
1 5/8
(41)
1 5/8
(41)
1 5/8
(41)
1 5/8
(41)
QTY
INCHES
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
INLETOUTLET
(mm)
1 3/8
(35)
1 3/8
(35)
1 3/8
(35)
1 3/8
(35)
1 3/8
(35)
1 3/8
(35)
1 3/8
(35)
1 3/8
(35)
1 3/8
(35)
1 5/8
(41)
1 5/8
(41)
1 5/8
(41)
2 1/8
(54)
2 1/8
(54)
2 1/8
(54)
2 1/8
(54)
2 1/8
(54)
2 1/8
(54)
INCHES
(mm)
1 1/8
(29)
1 1/8
(29)
1 1/8
(29)
1 1/8
(29)
1 1/8
(29)
1 1/8
(29)
1 1/8
(29)
1 1/8
(29)
1 1/8
(29)
1 1/8
(29)
1 1/8
(29)
1 1/8
(29)
1 3/8
(35)
1 3/8
(35)
1 3/8
(35)
1 3/8
(35)
1 3/8
(35)
1 3/8
(35)
QTY
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
APPROX.
SHIPPING
WEIGHTS
LBS
(Kg)
830
(377)
845
(384)
860
(391)
900
(409)
920
(418)
940
(427)
1190
(541)
1210
(550)
1230
(559)
1290
(586)
1320
(600)
1350
(614)
1540
(700)
1570
(714)
1600
(727)
1670
(759)
1710
(777)
1750
(795)
(1) Refrigerant charge conversion factors:
(2) Normal charge is the refrigerant charge for warm ambient or summer operation.
(3) 90% full is the liquid refrigerant weight at 90% of internal volume and is for reference only.(4) For 50 Hz fan data use 60 Hz CFM (m3/h) X 0.83 (no derate with EC motors)
(5) Sound pressure level at 30 ft. (10m)
R407CR404A
1.00.910.911.050.921.06
R507
R22
R410A
R134a
WIRING DIAGRAM
03/10/15
T50-TCM-PDI-4
- 8 -
TCM60Hz
(SINGLE ROW MODELS - SINGLE PHASE UNITS)
WIRING DIAGRAM
03/10/15
T50-TCM-PDI-4
- 9 -
TCM60Hz
(SINGLE ROW MODELS - THREE PHASE UNITS)
WIRING DIAGRAM
03/10/15
T50-TCM-PDI-4
- 10 -
TCM60Hz
(DOUBLE ROW MODELS - THREE PHASE UNITS)
WIRING DIAGRAM
03/10/15
T50-TCM-PDI-4
- 11 -
TCM60Hz
(VARIABLE SPEED MOTOR(S) WITH CONTROLLER
FOR HEADER FAN CONTROL - 208-230V MODELS)
WIRING DIAGRAM
03/10/15
T50-TCM-PDI-4
- 12 -
TCM60Hz
(VARIABLE SPEED MOTOR(S) WITH CONTROLLER
FOR HEADER FAN CONTROL - 460V MODELS)