Trenton TCM009 Installation Manual

PRODUCT DATA &
03/10/15
INSTALLATION
TCM-LINE AIR COOLED
CONDENSERS
R407A
R22
Electrical Power: 208-230/1/60, 208-230/3/60, 460/1/60, 460/3/60, 575/1/60, 575/3/60
Bulletin T50-TCM-PDI-4
1087821
?
R407C
R410A
Questions about this product?
Email: acc-fc@t-rp.com
Call: 1-844-893-3222 x526
R404A
R134a
R507
?
CONTENTS
Page
Nomenclature....................................... 2
Features & Options.............................. 2
Capacity Data...................................... 3 - 4
Electrical Data (Standard Motors)........ 5
General Specications......................... 6 - 7
Wiring Diagrams (Standard Motors)..... 8 - 14
About EC Motors................................. 15
Power Consumption............................ 15
Electrical Data ..................................... 16
Wiring Diagrams ................................. 17 - 18
EC Motor Application .......................... 19
INCLUDES RATINGS FOR
Page
Dimensional Data (All Models)........... 20 - 23
Receiver Options............................... 24 - 25
Condenser Theory.............................. 26
Glossary of Terms.............................. 26 - 27
Condenser Selection.......................... 28 - 29
Low Ambient Operation...................... 30 - 34
Installation.......................................... 35 - 38
Service Parts..................................... 38
Warranty.............................................. 39
Project Information.............................. 39
“As Built” Service Parts List............. BACK
Brand Name:
03/10/15
T50-TCM-PDI-4
- 2 -
T = Trenton
Product name
CM = Medium Sized Condenser
NOMENCLATURE
T CM 095 - T3 A - A 2 4 V
Application
V = Vertical Air Discharge H = Horizontal Air Discharge
Nominal Tons (R404A, 25°F TD, 60Hz)
Voltage
S2 = 208-230/1/60 T3 = 208-230/3/60 S4 = 460/1/60 T4 = 460/3/60 S5 = 575/1/60 T5 = 575/3/60 S6 = 200-220/1/50
T7 = 200-220/3/50 S7 = 380-400/1/50 T9 = 380-400/3/50
STANDARD FEATURES INCLUDE
Compatable with Low GWP Refrigerants
• Horizontal or Vertical Air Discharge
• Heavy Gauge Galvanized Steel Cabinet
• ThermoSpan failures on tube sheet
• Internally Enhanced Tubing with Enhanced Fin optimizes coil performance
• Energy Efcient PSC and 3 Phase Fan Motors with Internal Overload Protection
TM
Coil Design eliminates tube
Fans Deep
Fans Wide
1 = Inline; 2 = Double Wide
Motor
A = 1075 RPM, 3/4 HP Motor M = EC Motor - Motor Only (Conventional Shafted Style Motor)
Design version
• Quiet ‘Swept Wing’ Fan Blade
• Fan Sections Individually Bafed with
Clean-out Panels
• Zinc Plated Huck Bolts
• Heavy Duty 24” Legs
• Double fan wide models have Two Equal Circuits
• Control Circuit Voltage – 230 V
• Unit shipped with Nitrogen Holding Charge
• Multiple Refrigeration Circuits
• Ambient or Pressure Fan Cycling Control with Contactor
• Efcient Variable Speed EC Motors (see pg. 15)
• Variable speed motor with controller for header fan motors
• Individual Fan Motor Fusing
• Non-Fused Disconnect
• Receiver with or without Heater and Insulation
OPTIONAL FEATURES
• Adjustable Flooded Head Pressure Control (factory mounted if ordered with receiver option)
• Optional Fin Materials and Coatings
• Voltages Available for 60Hz or 50Hz
• Extended 48” Leg Kit with Cross Bracing
• Horizontal Conguration
• Optional Fin Materials
• Optional Coil Coatings
CAPACITY DATA -
03/10/15
T50-TCM-PDI-4
- 3 -
TCM 60Hz
SINGLE ROW MODELS
MODEL
NUMBER
TCM009 10 1 x 1 4.05 (1.20) 4.18 (1.24) 4.40 (1.30) 4.49 (1.33) 4.27 (1.26) 8 TCM010 12 1 x 1 4.39 (1.29) 4.53 (1.33) 4.77 (1.40) 4.87 (1.43) 4.63 (1.36) 8 TCM011 10 1 x 1 4.88 (1.47) 5.04 (1.52) 5.30 (1.60) 5.41 (1.63) 5.14 (1.55) 8 TCM012 12 1 x 1 5.24 (1.56) 5.42 (1.62) 5.70 (1.70) 5.81 (1.73) 5.53 (1.65) 8 TCM013 8 1 x 2 5.72 (1.66) 5.91 (1.71) 6.22 (1.80) 6.34 (1.84) 6.03 (1.75) 10 TCM014 10 1 x 2 6.36 (1.84) 6.56 (1.90) 6.91 (2.00) 7.05 (2.04) 6.70 (1.94) 10 TCM016 12 1 x 2 7.04 (2.02) 7.27 (2.09) 7.65 (2.20) 7.80 (2.24) 7.42 (2.13) 10 TCM017 8 1 x 2 7.54 (2.21) 7.79 (2.28) 8.20 (2.40) 8.36 (2.45) 7.95 (2.33) 16 TCM018 10 1 x 2 8.10 (2.39) 8.36 (2.47) 8.80 (2.60) 8.98 (2.65) 8.54 (2.52) 16 TCM020 12 1 x 2 8.69 (2.58) 8.98 (2.66) 9.45 (2.80) 9.64 (2.86) 9.17 (2.72) 16 TCM021 8 1 x 2 9.39 (2.76) 9.70 (2.85) 10.2 (3.00) 10.4 (3.06) 9.90 (2.91) 16 TCM022 10 1 x 2 9.75 (2.85) 10.1 (2.95) 10.6 (3.10) 10.8 (3.16) 10.3 (3.01) 16 TCM024 12 1 x 2 10.4 (3.04) 10.8 (3.14) 11.3 (3.30) 11.6 (3.37) 11.0 (3.20) 16 TCM025 8 1 x 3 11.2 (3.31) 11.6 (3.42) 12.2 (3.60) 12.4 (3.67) 11.8 (3.49) 24 TCM028 10 1 x 3 12.3 (3.59) 12.7 (3.71) 13.3 (3.90) 13.6 (3.98) 12.9 (3.78) 24 TCM030 12 1 x 3 13.2 (3.86) 13.6 (3.99) 14.3 (4.20) 14.6 (4.28) 13.9 (4.07) 24 TCM032 8 1 x 3 13.9 (4.05) 14.4 (4.18) 15.1 (4.40) 15.4 (4.49) 14.7 (4.27) 21 TCM033 10 1 x 3 14.6 (4.23) 15.0 (4.37) 15.8 (4.60) 16.2 (4.69) 15.4 (4.46) 21 TCM035 12 1 x 3 15.5 (4.51) 16.0 (4.66) 16.8 (4.90) 17.1 (5.00) 16.3 (4.75) 21 TCM037 8 1 x 4 16.1 (4.69) 16.7 (4.85) 17.5 (5.10) 17.9 (5.20) 17.0 (4.95) 24 TCM039 10 1 x 4 17.2 (5.06) 17.7 (5.23) 18.7 (5.50) 19.1 (5.61) 18.1 (5.34) 24 TCM041 12 1 x 4 18.1 (5.34) 18.7 (5.51) 19.7 (5.80) 20.1 (5.92) 19.1 (5.63) 24 TCM043 8 1 x 4 19.0 (5.52) 19.6 (5.70) 20.6 (6.00) 21.0 (6.12) 20.0 (5.82) 32 TCM045 10 1 x 4 20.0 (5.89) 20.7 (6.08) 21.8 (6.40) 22.2 (6.53) 21.1 (6.21) 32 TCM048 12 1 x 4 21.1 (6.16) 21.7 (6.37) 22.9 (6.70) 23.3 (6.83) 22.2 (6.50) 32
FPI FAN CONFIG.
TOTAL HEAT OF REJECTION - MBH (KW) PER 1 °F (0.56 °C) TD MAX.
R407A
R407C R404A
R507
R22
R410A
R134a
NO. OF FEEDS
NOTES:
- Above capacity data based on 0oF subcooling and at sea level.
- For High Altitude applications apply the following correction factors: 0.94 for 2000 feet, 0.88 for 4000 feet and 0.81 for 6000 feet.
- Capacities at other TD within a range of 10 to 30 °F (-12.2 to -1°C) are directly proportional to TD, or use formula: Capacity = Rated capacity ÷ 10 x TD.
- For 50 HZ capacity multiply by 0.92. (no derate with EC motors)
- Capacities for R407A and R407C are based on mean temperature. Mean temperature is the average temperature between the saturated condensing temperatures at the inlet and outlet of the condenser. For dew point ratings, consult factory.
CAPACITY DATA -
03/10/15
T50-TCM-PDI-4
- 4 -
TCM 60Hz
DOUBLE ROW MODELS
MODEL
NUMBER
TCM 034 8 2 x 2 15.1 (4.42) 15.6 (4.56) 16.4 (4.80) 16.7 (4.90) 15.9 (4.66) 32 TCM 036 10 2 x 2 16.2 (4.78) 16.7 (4.94) 17.6 (5.20) 18.0 (5.30) 17.1 (5.04) 32 TCM 040 12 2 x 2 17.4 (5.06) 17.9 (5.23) 18.9 (5.50) 19.3 (5.61) 18.3 (5.34) 32 TCM 042 8 2 x 2 18.8 (5.52) 19.4 (5.70) 20.4 (6.00) 20.8 (6.12) 19.8 (5.82) 32 TCM 044 10 2 x 2 19.5 (5.70) 20.1 (5.89) 21.2 (6.20) 21.6 (6.32) 20.6 (6.01) 32 TCM 047 12 2 x 2 20.9 (6.07) 21.5 (6.27) 22.7 (6.60) 23.1 (6.73) 22.0 (6.40) 32 TCM 051 8 2 x 3 22.4 (6.53) 23.2 (6.75) 24.4 (7.10) 24.9 (7.24) 23.6 (6.89) 48 TCM 056 10 2 x 3 24.5 (7.18) 25.3 (7.41) 26.7 (7.80) 27.2 (7.96) 25.9 (7.57) 48 TCM 060 12 2 x 3 26.3 (7.73) 27.2 (7.98) 28.6 (8.40) 29.2 (8.57) 27.7 (8.15) 48 TCM 063 8 2 x 3 27.8 (8.19) 28.7 (8.46) 30.3 (8.90) 30.9 (9.08) 29.3 (8.63) 42 TCM 066 10 2 x 3 29.2 (8.56) 30.1 (8.84) 31.7 (9.30) 32.3 (9.49) 30.7 (9.02) 42 TCM 070 12 2 x 3 30.9 (9.02) 31.9 (9.31) 33.6 (9.80) 34.3 (10.0) 32.6 (9.51) 42 TCM 073 8 2 x 4 32.3 (9.48) 33.3 (9.79) 35.1 (10.3) 35.8 (10.5) 34.0 (9.99) 48 TCM 078 10 2 x 4 34.4 (10.0) 35.5 (10.4) 37.4 (10.9) 38.1 (11.1) 36.2 (10.6) 48 TCM 082 12 2 x 4 36.2 (10.6) 37.4 (10.9) 39.4 (11.5) 40.2 (11.7) 38.2 (11.2) 48 TCM 086 8 2 x 4 37.9 (11.1) 39.1 (11.5) 41.2 (12.1) 42.0 (12.3) 40.0 (11.7) 64 TCM 090 10 2 x 4 40.1 (11.8) 41.4 (12.2) 43.6 (12.8) 44.4 (13.1) 42.2 (12.4) 64 TCM 095 12 2 x 4 42.1 (12.3) 43.5 (12.7) 45.8 (13.4) 46.7 (13.7) 44.4 (13.0) 64
FPI FAN CONFIG.
TOTAL HEAT OF REJECTION - MBH (KW) PER 1 °F (0.56 °C) TD MAX.
R407A
R407C R404A
R507
R22
R410A
R134a
NO. OF FEEDS
NOTES:
- Above capacity data based on 0oF subcooling and at sea level.
- For High Altitude applications apply the following correction factors: 0.94 for 2000 feet, 0.88 for 4000 feet and 0.81 for 6000 feet.
- Capacities at other TD within a range of 10 to 30 °F (-12.2 to -1°C) are directly proportional to TD, or use formula: Capacity = Rated capacity ÷ 10 x TD.
- For 50 HZ capacity multiply by 0.92. (no derate with EC motors)
- Capacities for R407A and R407C are based on mean temperature. Mean temperature is the average temperature between the saturated condensing temperatures at the inlet and outlet of the condenser. For dew point ratings, consult factory.
ELECTRICAL DATA
03/10/15
T50-TCM-PDI-4
- 5 -
TCM 60Hz
SINGLE ROW MODELS
208-230/3/60 460/3/60 575/3/60 208-230/1/60 460/1/60 575/1/60
MODEL
TCM 009 1 2.3 2.9 15 1.2 1.4 15 0.9 1.1 15 3.6 4.5 15 1.7 2.1 15 1.4 1.8 15 TCM 010 1 2.3 2.9 15 1.2 1.4 15 0.9 1.1 15 3.6 4.5 15 1.7 2.1 15 1.4 1.8 15 TCM 011 1 2.3 2.9 15 1.2 1.4 15 0.9 1.1 15 3.6 4.5 15 1.7 2.1 15 1.4 1.8 15 TCM 012 1 2.3 2.9 15 1.2 1.4 15 0.9 1.1 15 3.6 4.5 15 1.7 2.1 15 1.4 1.8 15 TCM 013 2 4.6 5.2 15 2.3 2.6 15 1.8 2.0 15 7.2 8.1 15 3.4 3.8 15 2.8 3.2 15 TCM 014 2 4.6 5.2 15 2.3 2.6 15 1.8 2.0 15 7.2 8.1 15 3.4 3.8 15 2.8 3.2 15 TCM 016 2 4.6 5.2 15 2.3 2.6 15 1.8 2.0 15 7.2 8.1 15 3.4 3.8 15 2.8 3.2 15 TCM 017 2 4.6 5.2 15 2.3 2.6 15 1.8 2.0 15 7.2 8.1 15 3.4 3.8 15 2.8 3.2 15 TCM 018 2 4.6 5.2 15 2.3 2.6 15 1.8 2.0 15 7.2 8.1 15 3.4 3.8 15 2.8 3.2 15 TCM 020 2 4.6 5.2 15 2.3 2.6 15 1.8 2.0 15 7.2 8.1 15 3.4 3.8 15 2.8 3.2 15 TCM 021 2 4.6 5.2 15 2.3 2.6 15 1.8 2.0 15 7.2 8.1 15 3.4 3.8 15 2.8 3.2 15 TCM 022 2 4.6 5.2 15 2.3 2.6 15 1.8 2.0 15 7.2 8.1 15 3.4 3.8 15 2.8 3.2 15
TCM 024 2 4.6 5.2 15 2.3 2.6 15 1.8 2.0 15 7.2 8.1 15 3.4 3.8 15 2.8 3.2 15 TCM 025 3 6.9 7.5 15 3.5 3.7 15 2.7 2.9 15 10.8 15.1 20 5.1 5.5 15 4.2 4.6 15 TCM 028 3 6.9 7.5 15 3.5 3.7 15 2.7 2.9 15 10.8 15.1 20 5.1 5.5 15 4.2 4.6 15 TCM 030 3 6.9 7.5 15 3.5 3.7 15 2.7 2.9 15 10.8 15.1 20 5.1 5.5 15 4.2 4.6 15 TCM 032 3 6.9 7.5 15 3.5 3.7 15 2.7 2.9 15 10.8 15.1 20 5.1 5.5 15 4.2 4.6 15 TCM 033 3 6.9 7.5 15 3.5 3.7 15 2.7 2.9 15 10.8 15.1 20 5.1 5.5 15 4.2 4.6 15 TCM 035 3 6.9 7.5 15 3.5 3.7 15 2.7 2.9 15 10.8 15.1 20 5.1 5.5 15 4.2 4.6 15 TCM 037 4 9.2 9.8 15 4.6 4.9 15 3.6 3.8 15 14.4 15.3 20 6.8 7.2 15 5.6 6.0 15 TCM 039 4 9.2 9.8 15 4.6 4.9 15 3.6 3.8 15 14.4 15.3 20 6.8 7.2 15 5.6 6.0 15 TCM 041 4 9.2 9.8 15 4.6 4.9 15 3.6 3.8 15 14.4 15.3 20 6.8 7.2 15 5.6 6.0 15 TCM 043 4 9.2 9.8 15 4.6 4.9 15 3.6 3.8 15 14.4 15.3 20 6.8 7.2 15 5.6 6.0 15 TCM 045 4 9.2 9.8 15 4.6 4.9 15 3.6 3.8 15 14.4 15.3 20 6.8 7.2 15 5.6 6.0 15 TCM 048 4 9.2 9.8 15 4.6 4.9 15 3.6 3.8 15 14.4 15.3 20 6.8 7.2 15 5.6 6.0 15
#
FANS
FLA MCA MOP FLA MCA MOP FLA MCA MOP FLA MCA MOP FLA MCA MOP FLA MCA MOP
DOUBLE ROW MODELS
208-230/3/60 460/3/60 575/3/60 208-230/1/60 460/1/60 575/1/60
MODEL
TCM 034 4 9.2 9.8 15 4.6 4.9 15 3.6 3.8 15 14.4 15.3 20 6.8 7.2 15 5.6 6.0 15 TCM 036 4 9.2 9.8 15 4.6 4.9 15 3.6 3.8 15 14.4 15.3 20 6.8 7.2 15 5.6 6.0 15 TCM 040 4 9.2 9.8 15 4.6 4.9 15 3.6 3.8 15 14.4 15.3 20 6.8 7.2 15 5.6 6.0 15 TCM 042 4 9.2 9.8 15 4.6 4.9 15 3.6 3.8 15 14.4 15.3 20 6.8 7.2 15 5.6 6.0 15
TCM 044 4 9.2 9.8 15 4.6 4.9 15 3.6 3.8 15 14.4 15.3 20 6.8 7.2 15 5.6 6.0 15 TCM 047 4 9.2 9.8 15 4.6 4.9 15 3.6 3.8 15 14.4 15.3 20 6.8 7.2 15 5.6 6.0 15 TCM 051 6 13.8 14.4 20 6.9 7.2 15 5.4 5.6 15 21.6 25.1 30 10.2 10.6 15 8.4 8.8 15 TCM 056 6 13.8 14.4 20 6.9 7.2 15 5.4 5.6 15 21.6 25.1 30 10.2 10.6 15 8.4 8.8 15 TCM 060 6 13.8 14.4 20 6.9 7.2 15 5.4 5.6 15 21.6 25.1 30 10.2 10.6 15 8.4 8.8 15 TCM 063 6 13.8 14.4 20 6.9 7.2 15 5.4 5.6 15 21.6 25.1 30 10.2 10.6 15 8.4 8.8 15 TCM 066 6 13.8 14.4 20 6.9 7.2 15 5.4 5.6 15 21.6 25.1 30 10.2 10.6 15 8.4 8.8 15 TCM 070 6 13.8 14.4 20 6.9 7.2 15 5.4 5.6 15 21.6 25.1 30 10.2 10.6 15 8.4 8.8 15 TCM 073 8 18.4 20.1 25 9.2 9.5 15 7.2 7.4 15 28.8 30.1 35 13.6 15.1 20 11.2 11.6 15 TCM 078 8 18.4 20.1 25 9.2 9.5 15 7.2 7.4 15 28.8 30.1 35 13.6 15.1 20 11.2 11.6 15 TCM 082 8 18.4 20.1 25 9.2 9.5 15 7.2 7.4 15 28.8 30.1 35 13.6 15.1 20 11.2 11.6 15
TCM 086 8 18.4 20.1 25 9.2 9.5 15 7.2 7.4 15 28.8 30.1 35 13.6 15.1 20 11.2 11.6 15 TCM 090 8 18.4 20.1 25 9.2 9.5 15 7.2 7.4 15 28.8 30.1 35 13.6 15.1 20 11.2 11.6 15 TCM 095 8 18.4 20.1 25 9.2 9.5 15 7.2 7.4 15 28.8 30.1 35 13.6 15.1 20 11.2 11.6 15
M.C.A. = Minimum Circuit Ampacity M.O.P. = Maximum OverCurrent protection
#
FANS
FLA MCA MOP FLA MCA MOP FLA MCA MOP FLA MCA MOP FLA MCA MOP FLA MCA MOP
GENERAL SPECIFICATIONS -
03/10/15
T50-TCM-PDI-4
- 6 -
TCM 60Hz
SINGLE ROW MODELS
R407A
MODEL
NUMBER
TCM009 1
TCM010 1
TCM011 1
TCM012 1
TCM013 2
TCM014 2
TCM016 2
TCM017 2
TCM018 2
TCM020 2
TCM021 2
TCM022 2
TCM024 2
TCM025 3
TCM028 3
TCM030 3
TCM032 3
TCM033 3
TCM035 3
TCM037 4
TCM039 4
TCM041 4
TCM043 4
TCM045 4
TCM048 4
FANS
LONG
R407A
REFRIG. CHARGE
(2)
1)
90% FULL
(3)
LBS
(Kg)
15.4
(7.04)
15.4
(7.04)
19.8
(9.02)
19.8
(9.02)
20.9
(9.59)
20.9
(9.59)
20.9
(9.59)
30.8
(14.0)
30.8
(14.0)
30.8
(14.0)
39.6
(17.9)
39.6
(17.9)
39.6
(17.9)
46.2
(21.2)
46.2
(21.2)
46.2
(21.2)
59.4
(27.2)
59.4
(27.2)
59.4
(27.2)
63.8
(28.8)
63.8
(28.8)
63.8
(28.8)
81.4
(36.8)
81.4
(36.8)
81.4
(36.8)
NORMAL
LBS
(Kg)
4.07
(1.83)
4.07
(1.83)
4.95
(2.27)
4.95
(2.27)
5.72
(2.59)
5.72
(2.59)
5.72
(2.59)
7.81
(3.54)
7.81
(3.54)
7.81
(3.54)
9.68
(4.42)
9.68
(4.42)
9.68
(4.42)
11.9
(5.39)
11.9
(5.39)
11.9
(5.39)
14.7
(6.70)
14.7
(6.70)
14.7
(6.70)
16.2
(7.37)
16.2
(7.37)
16.2
(7.37)
20.0
(9.11)
20.0
(9.11)
20.0
(9.1
(1)
AIR FLOW
(10874)
(25145)
(24466)
(23616)
(24126)
(23276)
(22597)
(23276)
(22427)
(21747)
(36189)
(35000)
(33810)
(34830)
(33810)
(32621)
(48252)
(46723)
(45194)
(46553)
(45024)
(43495)
RATES
CFM
3
(m
/h)
6870
(11672)
6640
(11281)
6620
(11247)
6400
14800
14400
13900
14200
13700
13300
13700
13200
12800
21300
20600
19900
20500
19900
19200
28400
27500
26600
27400
26500
25600
SOUND
LEVEL
(5)
dBA
51
51
51
51
53
53
53
53
53
53
53
53
53
54
54
54
54
54
54
55
55
55
55
55
55
PIPING CONNECTIONS
16°F to 30°F DESIGN TD 10°F to 15°F DESIGN TD
INLET OUTLET
INCHES
(mm)
1 1/8
(29)
1 1/8
(29)
1 1/8
(29)
1 1/8
(29)
1 3/8
(35)
1 3/8
(35)
1 3/8
(35)
1 5/8
(41)
1 5/8
(41)
1 5/8
(41)
1 5/8
(41)
1 5/8
(41)
1 5/8
(41)
2 1/8
(54)
2 1/8
(54)
2 1/8
(54)
2 1/8
(54)
2 1/8
(54)
2 1/8
(54)
2 5/8
(67)
2 5/8
(67)
2 5/8
(67)
2 5/8
(67)
2 5/8
(67)
2 5/8
(67)
INCHES
(mm)
7/8
(22)
7/8
(22)
7/8
(22)
7/8
(22)
1 1/8
(29)
1 1/8
(29)
1 1/8
(29)
1 1/8
(29)
1 1/8
(29)
1 1/8
(29)
1 1/8
(29)
1 1/8
(29)
1 1/8
(29)
1 3/8
(35)
1 3/8
(35)
1 3/8
(35)
1 3/8
(35)
1 3/8
(35)
1 3/8
(35)
1 5/8
(41)
1 5/8
(41)
1 5/8
(41)
1 5/8
(41)
1 5/8
(41)
1 5/8
(41)
QTY
INLET OUTLET
INCHES
(mm)
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1 1/8
1 1/8
1 1/8
1 1/8
1 1/8
1 1/8
1 1/8
1 3/8
1 3/8
1 3/8
1 3/8
1 3/8
1 3/8
1 3/8
1 3/8
1 3/8
1 5/8
1 5/8
1 5/8
2 1/8
2 1/8
2 1/8
2 1/8
2 1/8
2 1/8
(29)
(29)
(29)
(29)
(29)
(29)
(29)
(35)
(35)
(35)
(35)
(35)
(35)
(35)
(35)
(35)
(41)
(41)
(41)
(54)
(54)
(54)
(54)
(54)
(54)
INCHES
(mm)
7/8
(22)
7/8
(22)
7/8
(22)
7/8
(22)
7/8
(22)
7/8
(22)
7/8
(22)
1 1/8
(29)
1 1/8
(29)
1 1/8
(29)
1 1/8
(29)
1 1/8
(29)
1 1/8
(29)
1 1/8
(29)
1 1/8
(29)
1 1/8
(29)
1 1/8
(29)
1 1/8
(29)
1 1/8
(29)
1 3/8
(35)
1 3/8
(35)
1 3/8
(35)
1 3/8
(35)
1 3/8
(35)
1 3/8
(35)
QTY
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
APPROX. SHIPPING WEIGHTS
LBS
(Kg)
245
(111)
250
(114)
265
(120)
270
(123)
410
(186)
415
(189)
420
(191)
450
(205)
455
(207)
460
(209)
480
(218)
490
(223)
500
(227)
630
(286)
640
(291)
650
(295)
680
(309)
695
(316)
710
(323)
810
(368)
825
(375)
840
(382)
880
(400)
900
(409)
920
(418)
(1) Refrigerant charge conversion factors:
(2) Normal charge is the refrigerant charge for warm ambient or summer operation. (3) 90% full is the liquid refrigerant weight at 90% of internal volume and is for reference only. (4) For 50 Hz fan data use 60 Hz CFM (m3/h) X 0.83 (no derate with EC motors) (5) Sound pressure level at 10 ft. (3 m)
R407C
1.0 0.91 0.91 1.05 0.92 1.06
R404A
R507
R22
R410A
R134a
GENERAL SPECIFICATIONS -
03/10/15
T50-TCM-PDI-4
- 7 -
TCM 60Hz
DOUBLE ROW MODELS
R407A
MODEL
NUMBER
TCM034 2
TCM036 2
TCM040 2
TCM042 2
TCM044 2
TCM047 2
TCM051 3
TCM056 3
TCM060 3
TCM063 3
TCM066 3
TCM070 3
TCM073 4
TCM078 4
TCM082 4
TCM086 4
TCM090 4
TCM095 4
FANS LONG
R407A
REFRIG. CHARGE
(2)
90% FULL
(3)
LBS
(Kg)
61.6
(27.9)
61.6
(27.9)
61.6
(27.9)
79.2
(35.9)
79.2
(35.9)
79.2
(35.9)
93.5
(42.4)
93.5
(42.4)
93.5
(42.4)
120
(54.4)
120
(54.4)
120
(54.4)
127
(57.7)
127
(57.7)
127
(57.7)
162
(73.5)
162
(73.5)
162
(73.5)
NORMAL
LBS
(Kg)
15.6
(7.10)
15.6
(7.10)
15.6
(7.10)
19.5
(8.83)
19.5
(8.83)
19.5
(8.83)
23.8
(10.8)
23.8
(10.8)
23.8
(10.8)
29.5
(13.4)
29.5
(13.4)
29.5
(13.4)
32.5
(14.7)
32.5
(14.7)
32.5
(14.7)
40.0
(18.2)
40.0
(18.2)
40.0
(18.2)
(1)
AIR FLOW
RATES
CFM
(m
28400
(48252)
27500
(46723)
26600
(45194)
27400
(46553)
26500
(45024)
25600
(43495)
42600
(72378)
41200
(69999)
39800
(67621)
41100
(69829)
39700
(67451)
38400
(65242)
56800
(96504)
55000
(93446)
53100
(90217)
54800
(93106)
53000
(90048)
51200
(86989)
SOUND
LEVEL
(5)
3
/h)
dBA
55
55
55
55
55
55
57
57
57
57
57
57
58
58
58
58
58
58
16°F to 30°F DESIGN TD 10°F to 15°F DESIGN TD
INLET OUTLET
INCHES
(mm)
1 5/8
(41)
1 5/8
(41)
1 5/8
(41)
1 5/8
(41)
1 5/8
(41)
1 5/8
(41)
2 1/8
(54)
2 1/8
(54)
2 1/8
(54)
2 1/8
(54)
2 1/8
(54)
2 1/8
(54)
2 5/8
(67)
2 5/8
(67)
2 5/8
(67)
2 5/8
(67)
2 5/8
(67)
2 5/8
(67)
PIPING CONNECTIONS
INCHES
(mm)
1 1/8
(29)
1 1/8
(29)
1 1/8
(29)
1 1/8
(29)
1 1/8
(29)
1 1/8
(29)
1 3/8
(35)
1 3/8
(35)
1 3/8
(35)
1 3/8
(35)
1 3/8
(35)
1 3/8
(35)
1 5/8
(41)
1 5/8
(41)
1 5/8
(41)
1 5/8
(41)
1 5/8
(41)
1 5/8
(41)
QTY
INCHES
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
INLET OUTLET
(mm)
1 3/8
(35)
1 3/8
(35)
1 3/8
(35)
1 3/8
(35)
1 3/8
(35)
1 3/8
(35)
1 3/8
(35)
1 3/8
(35)
1 3/8
(35)
1 5/8
(41)
1 5/8
(41)
1 5/8
(41)
2 1/8
(54)
2 1/8
(54)
2 1/8
(54)
2 1/8
(54)
2 1/8
(54)
2 1/8
(54)
INCHES
(mm)
1 1/8
(29)
1 1/8
(29)
1 1/8
(29)
1 1/8
(29)
1 1/8
(29)
1 1/8
(29)
1 1/8
(29)
1 1/8
(29)
1 1/8
(29)
1 1/8
(29)
1 1/8
(29)
1 1/8
(29)
1 3/8
(35)
1 3/8
(35)
1 3/8
(35)
1 3/8
(35)
1 3/8
(35)
1 3/8
(35)
QTY
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
APPROX. SHIPPING WEIGHTS
LBS
(Kg)
830
(377)
845
(384)
860
(391)
900
(409)
920
(418)
940
(427)
1190
(541)
1210
(550)
1230
(559)
1290
(586)
1320
(600)
1350
(614)
1540
(700)
1570
(714)
1600
(727)
1670
(759)
1710
(777)
1750
(795)
(1) Refrigerant charge conversion factors:
(2) Normal charge is the refrigerant charge for warm ambient or summer operation. (3) 90% full is the liquid refrigerant weight at 90% of internal volume and is for reference only. (4) For 50 Hz fan data use 60 Hz CFM (m3/h) X 0.83 (no derate with EC motors) (5) Sound pressure level at 30 ft. (10m)
R407C R404A
1.0 0.91 0.91 1.05 0.92 1.06
R507
R22
R410A
R134a
WIRING DIAGRAM
03/10/15
T50-TCM-PDI-4
- 8 -
TCM 60Hz
(SINGLE ROW MODELS - SINGLE PHASE UNITS)
WIRING DIAGRAM
03/10/15
T50-TCM-PDI-4
- 9 -
TCM 60Hz
(SINGLE ROW MODELS - THREE PHASE UNITS)
WIRING DIAGRAM
03/10/15
T50-TCM-PDI-4
- 10 -
TCM 60Hz
(DOUBLE ROW MODELS - THREE PHASE UNITS)
WIRING DIAGRAM
03/10/15
T50-TCM-PDI-4
- 11 -
TCM 60Hz
(VARIABLE SPEED MOTOR(S) WITH CONTROLLER
FOR HEADER FAN CONTROL - 208-230V MODELS)
WIRING DIAGRAM
03/10/15
T50-TCM-PDI-4
- 12 -
TCM 60Hz
(VARIABLE SPEED MOTOR(S) WITH CONTROLLER
FOR HEADER FAN CONTROL - 460V MODELS)
Loading...
+ 28 hidden pages