IQView../RPM
Installation Instructions
TG200712
IQView Manual
IQVIEW/P
ANEL
Important:Retain these instructions
NOTE:Print to size.
Check dimensions below
4
"
10cm
Trend Control Systems Ltd reserves the right to revise this publication from time to time and make changes to the content hereof
without obligation to notify any person of such revisions or changes.
Trend Control Systems Ltd P.O.Box 34 Horsham Sussex RH12 2YF EnglandTel:+44 (0)1403 211888 Fax:+44 (0)1403 241608 www.trend-controls.com
Installation Instructions -T
emplate
displaycutoutclearancedimensions
132mm(5.2"
)
A
)
"
06
c
utoutfordisplay
.
4
(
mm
103
A
VIEW FROM FRONT
IQVIEW/P
ANEL
Installation Instructions -Template
TE200719
Installation Instructions -Template
IQVIEW/P
ANEL
T
ouch Screen Display
A
m
ounti
ngholecentres
A
IQView../RPM Template
A
TG200723
1 - 1
TG200723
Issue 1/A
5/1
1/03
It is recommended that the installation should
comply with the HSE Memorandum of Guidance
on Electricity at Work Regulations 1989.
For USA install equipment in accordance with
National Electric Code
WARNING
Do not attempt to open the unit. Failure to
!
comply may cause damage to the unit
1
208 mm (8.19")
c
0 °C
(32 °F)
Dimensions
cable and terminal access
(113 °F)
234 mm (9.21")
+45 °C
60.62 mm (2.39")
65 mm (2.56")
0 %RH
80 %RH
H2O
Protection: IP54, NEMA3
(if correctly fitted in panel)
Requirements
2
a
b
The unit is UL rated as 'UL916, open energy
management equipment'
Clean Screen
Remove dust and
grease regularly
by wiping gently
with a soft cloth
such as that used
for spectacles
view from front
IQVIEW/PANELInstallation Instructi ons - T emplate
Important: Retain these instruc tions
display cutout clearance dimensions
A
NOTE: Print to size.
Check dimensions below
A
4"
10 cm
Trend Control Systems Ltd reserves the right to revise this publication from time to time and make changes to the content hereof
without obligation to notify any person of such revisions or changes.
Trend Control Systems Ltd P.O. Box 34 Horsham Sussex RH12 2YF England Tel:+44 (0)1403 211888 Fax:+44 (0)1403 241608 www.trend-controls.com
the RS232 connector (as is done with
NDP). This will damage the unit.
using 28 Vdc power supply
(e.g. PSR/230/24-2.5)
Connect Power
7
28 to 36 Vdc or 24 Vac ±10 %, 50/60 Hz
IQView consumption <= 24 VA maximum (13 VA typical).
The IQView consumes 13VA, but the input power supply
should be capable of 24 VA to cater for startup current.
~
OK
28-36 V
ETHERNET
24 V
LINK
DATA
28 - 36 V
24 V ~
2
24
Vac
28
Vdc
using 230V/24V ac
24 Vac
E
E
0V
+28V
transformer with one
side earthed (grounded)
1
Rx
Tx
R+ R- T+ T-
OK
7 6 5 4
3 2 1
RS232
terminal size 0.5 to 2.5 mm
(14 to 20 AWG)
rear view of
connector
using 230V/24V ac
transformer with isolated
output (e.g. ACC/24VAC)
0
I
DO NOT
SWITCH ON
100 to 240 Vac
Connect RS232
8
only connection for IQView Mono,
if required for IQView (standard version)
IQ3, IQ2xx, (some IQ1xx with RJ11)
IQView
1
Tx
Rx
R+ R- T+ T-
OK
7 6 5 4
3 2 1
OK
RS232
28-36 V
ETHERNET
24 V
LINK
DATA
RJ11
CABLE/EJ105650 (supplied with IQView
Mono, not IQView standard version)
IQ1xx or CNC with 25 Way D type female
IQ3xcite, IQ2xx, IQ1xx
RJ11
0V
E
PSR/230/24-2.5
E
N
28 Vdc
L
230 Vac
WARNING
Do not attempt to supply power through the
RS232 connector (as is done with NDP).
This will damage the unit.
Read and agree to End User
Licence Agreement ( see
Section 5)
Close Panel
4
2
Switch On
0
I
Check Power LED
3
Tx
Rx
R+ R- T+ T-
OK
7 6 5 4
power
(blue)
1
3 2 1
Check input power
supply
RS232
DATA
alarm present
OK
28-36 V
ETHERNET
24 V
LINK
Specify Site Connection
5
(a)Enter ‘Site Name’
Note that for IQView MONO, the RS232 connection will be selected, all other
selections will not be available, and the user should jump to stage (d) below
to ‘Connect to CNC’/’RS232’ and enter the baud rate.
(b)Select first connection stage:
either ‘Connect to CNC’ -If connecting to either Ethernet
or‘Connect as Device’ -If IQView is device on current loop
(c )Select second connection stage:
If ‘Connect to CNC’ was selected
either ‘Ethernet (vCNC)’ -If connecting to vCNC in EINC or IQ3
or ‘RS232’-If connecting to CNC module, or IQ controller’s local supervisor port CNC (sCNC)
If ‘Connect as Device’ was selected
either ‘Current Loop Lan’ - If connecting IQView as device on a current loop Lan (using IQView’s internal CNC)
or ‘Ethernet Lan’ -If connecting IQView as device on Ethernet Lan (using IQView’s internal vCNC)
(d)Setup up communication parameters
If ‘Connect to CNC’/’Ethernet (vCNC)’ -Set IP address (or hostname) of IQ3 or EINC and port number of the vCNC
If ‘Connect to CNC’/’RS232’ -Set baud rate for communication between IQView and CNC or IQ controller’s
If ‘Connect as Device’/’Current Loop Lan’ - Set up IQView’s Lan number (to be unique on internetwork and to match other
If ‘Connect as Device’/’Ethernet Lan’ -Set up IQView’s Lan number (to be unique on internetwork and to match other
vCNC (vCNC in EINC or IQ3) or RS232
(CNC module or IQ controller’s local
supervisor port)
Lan (using IQView’s internal CNC), or
device on Ethernet Lan (using
IQView’s internal vCNC)
local supervisor port to match the baud rate set in the remote device (IQ
controller local supervisor port baud rate is normally 9600 baud)
devices on Lan), network address (to be unique on Lan), and baud rate (to
be same as other nodes on Lan)
devices on Lan) and network address (to be unique on Lan). Set up UDP port
to match address used by rest of IQ system
(e)The IQView will now attempt to find its own Lan number (from an INC). If successful it will try to learn the internetwork and
display all the associated Lan icons including local Lan, if unsuccessful it will just display its own Lan icon (with Lan number
0).
If either Ethernet (vCNC), or Ethernet Lan have been selected, the default is for the Ethernet IP address details to
be automatically set up. If DHCP server is operating it will set up the IP address details, if not the details will be set up
by auto-negotiation with the other devices on the Ethernet Lan.
For Ethernet connections proceed with step 6 and for all other connections go to step 7.
if either ‘Connect to CNC’/’Ethernet vCNC’, or ‘Connect as Device’/’Ethernet Lan’ set up as above.
6
Note that if auto IP addressing is required (as per default) go to (d)
(a)Tap on IQView menu icon in the menu rail on the
top of the screen, and tap on ‘Settings/Network (Ethernet)’.
(b)Change IP address source:
from‘Obtain IP address via DHCP’ (default)
IP settings being set up automatically
to‘Specify an IP address’
IP settings being set up manually
(c)Enter IP Address
Note that the these details can be set up using IPTool (v1.1 or greater) rather than tapping them in on the screen
(d)If ‘Obtain IP address via DHCP’ selected, and there is no DHCP server on the segment, then enter
Note that the these details can be set up using IPTool (v1.1 or greater) rather than tapping them in on the screen
(e)Tap to close the box, and the unit will reset.
Subnet Mask
Default Gateway - router IP address (if communications
cross router)
Select servers tab and enter
WINS Server IP Address(es) (if host names being used
across router)
Go to (e)
Default Gateway - router IP address (if communications cross router)
Select servers tab and enter
WINS Server IP Address(es) (if host names being used across router)
IQView (standard version) only
(f)If network is to cross router enter remote devices’ IP addresses
(or host names) and subnet masks using IPTool
(g)Re - initialise the site connection by selecting and
‘ReInit Connection’.
The IQView will now attempt to find its own Lan number (from
an INC). If successful it will try to learn the internetwork, if
unsuccessful it will just display its own Lan icon.
Note that the time taken for the system to be available for mapping will
depend on the type of Ethernet connection. If connecting to ‘Connect to
CNC’, ‘Ethernet vCNC’ it can be instantaneous (if the rest of the system
is setup). If connecting ‘Connect as Device‘, ‘Ethernet Lan’ it can take
from <30s to <130s depending on its IP address and whether the network
crosses a router.
Learn Entire Site
7
(a) The IQView will display the adjacent dialogue box. Recommend select
‘Yes’ to learn of all controllers. The box times out after 5 s and will learn
the all controllers by default. (Selecting ‘No’ means that the controllers
should be learnt later when user selects the learn site/Lan functions).
Check Connection
8
A falure to connect in steps 5, 6, or 7 will produce a dialogue box detailing
the reason for failure.
The connection can be checked at any time by tapping on the comms icons
in the bottom right hand corner of the display.
(green flicker) Icons have been tapped and the check is in progress
(green steady) Communications OK
(red steady) Communications fail
·You have acquired an IQView (“Device”) that includes software licensed by Trend Control Systems Ltd from
one or more software licensors (“Trend Control Systems Ltd Software Suppliers”). Such software products,
as well as associated media printed materials and “online” or electronic documentation (“SOFTWARE”) are
protected by international intellectual property laws and treaties. The SOFTWARE is licensed, not sold.
All rights reserved.”
·IF YOU DO NOT AGREE TO THIS END USER LICENSE AGREEMENT (“EULA”), DO NOT USE THE
DEVICE OR COPY THE SOFTWARE. INSTEAD, PROMPTLY CONTACT TREND CONTROL SYSTEMS
LTD FOR INSTRUCTIONS ON RETURN OF THE UNUSED DEVICE(S) FOR A REFUND. ANY USE OF THE
SOFTWARE INCLUDING BUT NOT LIMITED TO USE ON THE DEVICE WILL CONSTITUTE YOUR
AGREEMENT TO THE EULA (OR RATIFICATION OF ANY PREVIOUS CONSENT).
·GRANT OF SOFTWARE LICENSE. This EULA grants you the following license:
•You may use the SOFTWARE only on the DEVICE
•NOT FAULT TOLERANT. THE SOFTWARE IS NOT FAULT TOLERANT. TREND CONTROL SYSTEMS
LTD HAS INDEPENDENTLY DETERMINED HOW TO USE THE SOFTWARE IN THE DEVICE, AND
TREND CONTROL SYSTEMS LTD’S SOFTWARE SUPPLIERS HAS RELIED UPON TREND CONTROL
SYSTEMS LTD TO CONDUCT SUFFICIENT TESTING TO DETERMINE THAT THE SOFTWARE IS
SUITABLE FOR SUCH USE.
•NO WARRANTIES FOR THE SOFTWARE. THE SOFTWARE is provided “AS IS” and with all
faults. THE ENTIRE RISK AS TO SATISFACTORY QUALITY, PERFORMANCE, ACCURACY, AND
EFFORT (INCLUDING LACK OF NEGLIGENCE) IS WITH YOU. ALSO, THERE IS NO WARRANTY
AGAINST INTERFERENCE WITH YOUR ENJOYMENT OF THE SOFTWARE OR AGAINST
INFRINGEMENT. IF YOU HAVE RECEIVED ANY WARRANTIES REGARDING THE DEVICE OR THE
SOFTWARE, THOSE WARRANTIES DO NOT ORIGINATE FROM, AND ARE NOT BINDING ON,
TREND CONTROL SYSTEMS LTD’S SOFTWARE SUPPLIERS.
•Note on Java Support. The SOFTWARE may contain support for programs written in Java. Java
technology is not fault tolerant and is not designed, manufactured, or intended for use or resale as online
control equipment in hazardous environments requiring fail-safe performance, such as in the operation
of nuclear facilities, aircraft navigation or communication systems, air traffic control, direct life support
machines, or weapons systems, in which the failure of Java technology could lead directly to death,
personal injury, or severe physical or environmental damage. Sun Microsystems, Inc. has contractually
obligated Trend Control Systems Ltd’s software suppliers to make this disclaimer.
•No Liability for Certain Damages. EXCEPT AS PROHIBITED BY LAW, TREND CONTROL SYSTEMS
LTD’S SOFTWARE SUPPLIERS SHALL HAVE NO LIABILITY FOR ANY INDIRECT, SPECIAL,
CONSEQUENTIAL OR INCIDENTAL DAMAGES ARISING FROM OR IN CONNECTION WITH THE
USE OR PERFORMANCE OF THE SOFTWARE. THIS LIMITATION SHALL APPLY EVEN IF ANY
REMEDY FAILS OF ITS ESSENTIAL PURPOSE. IN NO EVENT SHALL TREND CONTROL SYSTEMS
LTD’S SOFTWARE SUPPLIERS BE LIABLE FOR ANY AMOUNT IN EXCESS OF U.S. TWO
HUNDRED FIFTY DOLLARS (U.S.$250.00).
•Limitations on Reverse Engineering, Decompilation, and Disassembly. You may not reverse
engineer, decompile, or disassemble the SOFTWARE, except and only to the extent that such activity
is expressly permitted by applicable law notwithstanding this limitation.
•SOFTWARE TRANSFER ALLOWED BUT WITH RESTRICTIONS. You may permanently transfer
rights under this EULA only as part of a permanent sale or transfer of the Device, and only if the recipient
agrees to this EULA. If the SOFTWARE is an upgrade, any transfer must also include all prior versions
of the SOFTWARE.
Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Ecublens, Route
du Bois 37,Switzerland by its Authorized Representative, Trend Control Systems Limited.
Trend Control Systems Limited reserves the right to revise this publication from time to time and make changes to the content
hereof without obligation to notify any person of such revisions or changes.