should comply with the HSE
Memorandum of Guidance on Electricity
at Work Regulations 1989.
For USA, install equipement in
accordance with National Electric Code.
For use with IQLVAV, IQL11+, 13+, 15+ controllers only
IQLs must have standard strategies or standard item
allocations as follows:
S9, S10, S1, S2, S3 (IQLVAV, IQL11+, 13+, 15+)
I9 (IQL11+, 13+, 15+), I12 (IQLVAV)
S11, S7 (IQL13+, 15+)
IQLVAV, IQL11+ can use RD/IQL/K, /KOS
IQL13+, 15+ can use RD/IQL/K, /KOS, /KOSF
The RD’s potentiometer must be used (if potentiometer
required); a direct connected potentiometer may not be
used. A direct connected temperature sensor may be
used rather than the RD’s.
RD-IQL/K precludes use of PIR/pushbutton inputs and
(on IQLVAV only) alarm contact input. A separate fan
speed switch may be used (IQL13+, 15+).
RD-IQL/KOS as RD-IQL/K except pushbutton is provided.
RD-IQL/KOSF as RD-IQL/KOS except Fan speed switch
is provided (for IQL13+, 15+). A separate Fan Speed
switch may be used (rather than the RD’s).
The following parameters must be set up (their configuration is facilitated by IQLTool2
‘Configure for RD-IQL’ feature):
Local Space Temp Type S9(Y=6) (use RD) - IQL11+, 13+, 15+, IQLVAV
Local SP Adjust Type S10(Y=6) (use RD) - IQL11+, 13+, 15+, IQLVAV
Local Fan Speed Type S11(Y=6) (use RD) - IQL13+, 15+
These settings are facilitated by IQLTool2.
If it is required to use a separate temperature sensor, leave Local Space Temp Type at default,
S9(Y=1).
If it is required to use a separate fan speed switch, leave Local Fan Speed Type at default, S11(Y=3).
The following parameters should be set up if they have been changed from default:
Note that these parameters are in the standard strategies; equivalent parameters may have to be
changed in non-standard strategies
Window Mode W5(S=O) (not window mode, default) - IQL11+
PIR Pb Select W6(S=O) (Pushbutton selected, default) - IQL11+, 13+, 15+
Remote Fan Spd K7(V=4) (auto, default) - IQL13+, 15+
The following command must be given:
R(z=1) :This writes changes to permanent flash memory, and causes the IQL/IQLVAV to start using
the new settings
Note that a PIN may be required to make
changes. If the PIN has been forgotten the
users should contact their supplier (installers
contact Trend Technical Support) quoting the
generator number and neuron id (both from Address
module) whereupon a default PIN will be supplied.
This will only work for three attempts at entering the
PIN. After the default PIN is entered a new PIN
should be set up and remembered.
* Note that when using an IQL standard strategy, in step ‘e’ the RD can override the occupation
on, but not off. The strategy will define when the occupation switches off.
At the end of their useful life the packaging
and product should be disposed of by a
Do not dispose of with normal household waste.
Do not burn.
suitable recycling centre.
Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Ecublens, Route
du Bois 37,Switzerland by its Authorized Representative, Trend Control Systems Limited.
Trend Control Systems Limited reserves the right to revise this publication from time to time and make changes to the content hereof
without obligation to notify any person of such revisions or changes.