if IQ is IQ3, IQ2xx, or IQ1xx (firmware v4.7 or greater)
5
+40 °C
+104 °F
90 %RH
l
1 2 3 4
S PE N G
c
Note that RD-IQ cannot be connected to a controller with local
supervisor port already used (e.g. wireless sensor receiver
XW/R/IQ, NDP, IQView (RS232), or local PC) or to /ADL, /ATM
or XNC220 controllers.
Note that sUperv port addr should set to zero (default)
Standard cables connect signal plus power for all IQ3s, IQ204,
later IQ21x, later IQ22x, IQ23x, IQ241/242, IQ246
IQ2xx
RD/SDU-IQ2COMMSCABLE/3M
maximum distance 25 m (28 yds)
Power cable only required for
IQs (early IQ21x early IQ22x,
IQ250, IQ251, IQ1xx) if not
using special adaptors - see
step 6
2
local supervisor
port
Note that the IQ controller may be connected while powered;
if not power up controller.
For controllers without power from RJ11, use of adapter,
in addition to RJ11 to RJ11 standard cable, facilitates
connection of power from IQ’s 24 Vdc auxiliary supply
For early IQ21x, early IQ22x, IQ250, IQ251, later IQ1xx
24 Vdc
auxiliary
IQ2xx
2 terminal
power
signal
RJ11
RD/SDU-ADAPTOR IQ2xx
RJ11
RJ11
Note that the IQ controller may be connected
For early IQ1xx with 5 in line RS232
24 Vdc
auxiliary
IQ1xx
2 terminal
power
signal
5 in line
RJ11
RJ11
while powered; if not power up controller.
RD/SDU-ADAPTOR IQ1xx+
Connect Input Supply
6
if early IQ21x, early IQ22x, IQ251, IQ250,
IQ1xx controllers and not using adapters
+24 Vdc
0 Vdc
+24 Vac (L)
+24 Vac (N)
*
24 Vdc Supply
24 Vdc
10 mA
24 Vac Supply
24 Vac
10 mA
RD
+
+
RD
+
* If one side of the 24 Vac supply is connected to 0 V,
that side must be connected to the RD - (negative) terminal
The IQ strategy must comply with default
modules used by RD-IQ or with those changed
the local temperature value. For example in
IQ1, 2, if the default S9 is used, sensor 9
must be an internal sensor sourced from
node 9 (the sensor should be sequenced)
to in step 12, ‘Engineer Communication’.
Defaults:Local TemperatureS9
SetpointK1
Occupation StatusK6
Fan Speed StatusK7
PINnone
In IQ3 the modules must be
created in SET, the sensor
must have its output looped
back to its input, and the
sensor must be sequenced
S9
I
9
7
Page 8
RD-IQInstallation Instructions
° C
° C
° C
INSTALLATION (continued)
19
Check System
Dependent on option
/K, /KOS, /KOSF see below
a
/K, /KOS, /KOSF
b
/K, /KOS, /KOSF
c
/K, /KOS, /KOSF
d
/K, /KOS, /KOSF
° C
Sx °C (°F) Temp
Kb Occupation, Kc Fan
Speed
Ka °C (°F) Setpoint
Ka °C (°F)
Ka °C (°F)
DP
A
B
C
D
V
24V
12345678910
e
/KOS, /KOSF
f
/KOSF only
AUTO
Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Ecublens, Route
du Bois 37,Switzerland by its Authorized Representative, Trend Control Systems Limited.
Trend Control Systems Limited reserves the right to revise this publication from time to time and make changes to the content hereof
without obligation to notify any person of such revisions or changes.