Important: Retain these instructions
UNPACKING
INSTALLATION
Installation Instructions
AQ/D
Duct Air Quality Sensor
AQ/D Installation Instructions
TG100525A
97 mm (3.82”)
TrendControl Systems
90 mm (3.54”)
85 mm (3.35”)
centres
3
AQ/D
Horsham, UK
105 mm (4.16”)_
Drill hole in duct
1
2
Dimensions
Location
45 mm (1.77”)
12 mm diam (0.47”)
190 mm (7.48”)
57 mm
(2.74”)
b
a
V <= 10 m/s, 33 ft/s
(e.g. return air)
Ø 15 mm
(0.59”)
c
-18 °C
(64 °F)
+24 °C
(75 °F)
65 %RH ± 5 %
HO
2
Protection :IP67, NEMA 6
Prepare duct
4
a
b
42.5mm
(1.67”)
AQ/D Installation Instructions TG100525A Issue 3, 2/03/2009
2 pilot holes
42.5 mm
(1.67”)
Mount Sensor
5
a
b
2 x No 6 x 20 mm screws DIN 7481
1
AQ/D Installation Instructions
LD1
VR1
Cal
OP0V24V
Run
VR2
-
+
DELAY
ADJUST
INSTALLATION (Continued)
Remove lid
6 7
Remove Connector
ba
Insert cable through gland
8 9
either use
flexible conduit
or use
M20 cable gland
Wire to Controller
10
C a l
O P0 V2 4 V
R u n
24V 0V OP
Caution: This unit contains static
taken throughtout the operation to
prevent damage to the units.
BS EN100015/1 Basic
Specification: protection of
electrostatic sensitive devices.
Check link is in ‘Run’ position
View of pcb from surface
mount side
Cal
position
IQ2
24V (AUX)
C (0V)
IN
sensitive devices.
Suitable anti-static
precautions should be
Run position
IQ analogue input
channel linked for
voltage (V)
- +
L D 1 V R 1
A D J U S T
- +
Note that sensor requires 96 mA from
24 V supply
Use auxiliary 24 Vdc output terminal as maximum current = 96 mA
Replace connector
11
D E L A Y
V R 2
24V 0V OP
12
Ensure clean
environment
0 (0V)
N (in)
24V
IQ3
N
13
IQ analogue input
channel linked for
voltage (V)
Set minimum delay
-
+
clean air
2
AQ/D Installation Instructions TG100525A Issue 3, 2/03/2009
Delay