TR-Electronic AMV58, AEV58, AES58, AEV65 Series User Manual

TR - ECE - BA - GB - 0101 - 05 02/21/2018
User Manual
_Basic safety instructions
_Intended use
_Product description
_Technical data
_Explosion protection characteristics
_Assembly
TR-Explosionsschutzgehäuse
A*V70
A*W70
A**88
TR - Explosion Protection Enclosure with integrated measuring system
Explosion Protection Enclosure - Type
_A**58*
II 3 G Ex nAc IIC T6 X II 3 D Ex tc IIIC T80°C IP64 X
Date of manufacture: DD.MM.YYYY
Translation of the original manual
AEV58 / AMV58
AES58
TR-Electronic GmbH 2013, All Rights Reserved Printed in the Federal Republic of Germany
Page 2 of 29 TR - ECE - BA - GB - 0101 - 05 02/21/2018
TR-Electronic GmbH
D-78647 Trossingen Eglishalde 6 Tel.: (0049) 07425/228-0 Fax: (0049) 07425/228-33 E-mail: info@tr-electronic.de
www.tr-electronic.de
Copyright
This manual, including the therein contained images, is protected by copyright. Third party usage of this manual, which deviates from copyright provisions, is prohibited. Reproduction, translation as well as electronic and photographic archiving or modification requires the author's written authorization. Infringements will lead to liability for damage compensation.
The right to amendment is reserved
The right to make any changes in the interest of technical progress is reserved.
Document information
Edition-/Rev.-Date: 02/21/2018 Document-/Rev.-No.: TR - ECE - BA - GB - 0101 - 05 File name: TR-ECE-BA-GB-0101-05.docx Author: MÜJ
Text
Cursive or bold text represents the title of a document or is used for emphasis. Courier-text shows text which is visible on the display or screen as well as
software menu-selections.
< > refers to keys on your computer keyboard (e.g. <RETURN>).
Printed in the Federal Republic of Germany TR-Electronic GmbH 2013, All Rights Reserved
02/21/2018 TR - ECE - BA - GB - 0101 - 05 Page 3 of 29
Table of contents
Table of contents ................................................................................................................................ 3
Amendment-index .............................................................................................................................. 5
1 General ............................................................................................................................................. 6
1.1 Type designation code, Explosion Protection Enclosure ....................................................... 6
1.2 Scope ...................................................................................................................................... 7
1.3 Relevant directives and standards ......................................................................................... 7
1.4 Used abbreviations / Terms .................................................................................................... 8
1.5 Product description ................................................................................................................. 8
2 Basic safety instructions ................................................................................................................ 9
2.1 Symbol- and note definition .................................................................................................... 9
2.2 Obligation of the operator prior to commissioning .................................................................. 10
2.3 General dangers with the use of this product ......................................................................... 10
2.4 Intended use ........................................................................................................................... 11
2.5 Non-intended use ................................................................................................................... 11
2.6 Warranty and liability .............................................................................................................. 12
2.7 Organizational measures ........................................................................................................ 12
2.8 Personnel selection and -qualification; basic obligations ....................................................... 13
2.8.1 Electrical installations design, device selection and erection ................................. 13
2.8.2 Inspection, maintenance and repair ........................................................................ 13
2.9 First commissioning / Commissioning .................................................................................... 14
2.10 Assembly, installation and dismantling ................................................................................. 14
2.11 Inspection, maintenance and repair ..................................................................................... 15
2.12 Special conditions for safe use, marking "X" ........................................................................ 15
3 Transport / Storage ......................................................................................................................... 16
4 Technical data .................................................................................................................................. 17
4.1 Power supply .......................................................................................................................... 17
4.2 Mechanical characteristics ...................................................................................................... 17
4.3 Environmental conditions ........................................................................................................ 17
4.4 Enclosure materials ................................................................................................................ 18
4.5 Explosion protection characteristics ....................................................................................... 19
4.5.1 Ex-labeling, gas ...................................................................................................... 19
4.5.2 Ex-labeling, dust ..................................................................................................... 20
Table of contents
TR-Electronic GmbH 2013, All Rights Reserved Printed in the Federal Republic of Germany
Page 4 of 29 TR - ECE - BA - GB - 0101 - 05 02/21/2018
5 Assembly .......................................................................................................................................... 21
5.1 Solid shaft ............................................................................................................................... 21
5.1.1 Flange-assembly ..................................................................................................... 21
5.1.2 Clamp flange - assembly ........................................................................................ 22
5.1.3 Fixing clamps - assembly ........................................................................................ 23
5.1.4 Servo clamps - assembly ........................................................................................ 24
5.2 Blind hollow shaft .................................................................................................................... 25
6 Equipotential bonding conductor - Connection ........................................................................... 26
7 Disposal ............................................................................................................................................ 27
8 Annex ................................................................................................................................................ 28
8.1 EU declaration of conformity ................................................................................................... 28
8.2 Accessories ............................................................................................................................. 29
8.2.1 Interface-specific user manual ................................................................................ 29
Printed in the Federal Republic of Germany TR-Electronic GmbH 2013, All Rights Reserved
02/21/2018 TR - ECE - BA - GB - 0101 - 05 Page 5 of 29
Amendment-index
Amendment
Date
Index
First edition
05/08/13
02
New production series: AMV58 Standards: Version numbers modified
08/05/14
03
EU directives 2014/30/EU (EMC) and 2014/34/EU (ATEX) added
12/21/15
04
Declaration of conformity updated
02/21/18
05
General
TR-Electronic GmbH 2013, All Rights Reserved Printed in the Federal Republic of Germany
Page 6 of 29 TR - ECE - BA - GB - 0101 - 05 02/21/2018
1 General
This -User manual contains all relevant explosion-safety information and includes the following topics:
Basic safety instructions Intended use Product description Technical data Explosion protection characteristics Assembly
Since the documentation has a modular structure, this -User manual represents a supplement to the other documentation such as for example product data sheets, dimensional drawings and leaflets etc.
The -User manual is included, but can also be ordered separately.
1.1 Type designation code, Explosion Protection Enclosure
A
* 1
* 2
* 3
* 4 - * 5
* 5
* 5
* 5
* 5
Position
Notation
Description
A
A
Explosion protection (ATEX)
* 1
E
Optical scanning unit 15 bit
M
Magnetic scanning unit
* 2
V
Solid shaft
S
Blind shaft
* 3
58
External diameter 58 mm
* 4
S
Single turn
M
Multi turn
* 5
-
Consecutive number
* = Wild cards
Printed in the Federal Republic of Germany TR-Electronic GmbH 2013, All Rights Reserved
02/21/2018 TR - ECE - BA - GB - 0101 - 05 Page 7 of 29
1.2 Scope
This -User manual applies exclusively to the following explosion protection enclosure series:
A**58*, II 3G Ex nAc IIC T6 X II 3D Ex tc IIIC T80°C IP64 X The products are labelled with affixed nameplates and are components of a system. It thus applies together with the following documentation:
the operator's system-specific operation instructions,
this -User manual
and the interface-specific user manual
1.3 Relevant directives and standards
The explosion protection enclosure is developed, constructed and finished under compliance with the applicable European- or International standards and directives.
EU-Directives 2004/108/EC, valid until 04/19/2016
2014/30/EU, valid from 04/20/2016
Electromagnetic compatibility
EU-Directives 94/9/EC, valid until 04/19/2016
2014/34/EU, valid from 04/20/2016
Equipment and protective systems intended for use in potentially explosive atmospheres
EN 61000-6-2
EMC: Interference immunity
EN 61000-6-3
EMC: Interference emission
EN 60079-0
Explosive atmospheres: General requirements
DIN EN 60079-14
Explosive atmospheres: Electrical installations design, selection and erection
EN 60079-15
Explosive atmospheres:
Equipment protection by type of protection "n"
EN 60079-31
Explosive atmospheres:
Equipment dust ignition protection by enclosure "t"
DIN EN 60529
Degrees of protection provided by enclosures (IP code)
General
TR-Electronic GmbH 2013, All Rights Reserved Printed in the Federal Republic of Germany
Page 8 of 29 TR - ECE - BA - GB - 0101 - 05 02/21/2018
1.4 Used abbreviations / Terms
A**58*
Explosion protection enclosure with integrated measuring system of the 58 series, all versions.
EU
European Union
EMC
Electromagnetic compatibility
ESD
Electro Static Discharge
IEC
International Electro-technical Commission
VDE
Association for Electrical, Electronic & Information Technologies
1.5 Product description
The aluminum explosion protection enclosure with built-in systems and integrated evaluation electronics serves the detection of changes in angle for fixed installations. The changes in angle are transmitted to the evaluation electronics via shaft.
The explosion protection enclosure has the ignition protection type
"n": non-sparking operating equipment (potential gas-explosive atmosphere) and
"t": protection by the enclosure (potential dust-explosive atmosphere)
Through its manner of construction, the types of ignition protection and additional measures, the enclosure is suitable for the incorporation of non-explosion protected installation devices such as the measuring system of the series 58.
The construction, as well as the interaction of the individual components and the housing with regards to their possibilities for use in potentially explosive areas, are tested by the company TR-Electronic GmbH and confirmed by identification with the nameplate.
Printed in the Federal Republic of Germany TR-Electronic GmbH 2013, All Rights Reserved
02/21/2018 TR - ECE - BA - GB - 0101 - 05 Page 9 of 29
2 Basic safety instructions
2.1 Symbol- and note definition
means that death or serious injury can occur if the required precautions are not met.
means that minor injuries can occur if the required precautions are not met.
means that damage to property can occur if the required precautions are not met.
indicates important information or features and application tips for the product used.
signifies that respective ESD-safety measures according to DIN EN 61340-5-1 supplement 1 are to be observed.
Basic safety instructions
TR-Electronic GmbH 2013, All Rights Reserved Printed in the Federal Republic of Germany
Page 10 of 29 TR - ECE - BA - GB - 0101 - 05 02/21/2018
2.2 Obligation of the operator prior to commissioning
As an electronic device and for use in potentially explosive areas, the explosion protection enclosure with integrated measuring system is subject to the provisions of the EU-directives EMC and ATEX.
Therefore commissioning of the device is only allowed once it has been established that the system/machine in which the device is to be installed, complies with the provisions of the EU-directives EMC and ATEX, the harmonized standards, European standards or the respective national standards.
2.3 General dangers with the use of this product
The product, hereafter referred to as equipment is manufactured using the latest technology and according to recognized safety regulations. Nevertheless, non-
intended use can cause danger to life and limb of the user or third parties or cause damage to the equipment and other property!
Only use the equipment for its intended use, with safety- and danger awareness and in compliance with the -user manual and the interface specific user manual!
The operator of an electrical system in a potentially explosive environment should keep the equipment in a proper condition, it should be properly operated and monitored and maintenance- as well as repairs are to be performed. This also includes inspection of the equipment for possible transport damage prior to commissioning. Power connections may not be connected or disconnected with the power engaged. The equipment may not be used in case of defects, as a basic principle it may not be opened and dust deposits > 5 mm must be removed.
Printed in the Federal Republic of Germany TR-Electronic GmbH 2013, All Rights Reserved
02/21/2018 TR - ECE - BA - GB - 0101 - 05 Page 11 of 29
2.4 Intended use
The equipment is used for the detection of angular movements as well as the processing of the measurement data for a downstream control through industrial process- and control procedures.
The equipment is a fixed-installation device for use in the Ex-Zone 2 (potentially gas­explosive areas, Il 3 G, device protection level Gc) or 22 (areas with combustible dust II 3 D, device protection level Dc).
The assembly takes place through the established attachment possibilities. The electrical data provided on the nameplate, as well as the device category, temperature class etc. for the place of use are to be observed. The operating temperature range of the equipment is -20°C to +60°C.
Intended use also includes:
observation of all instructions contained in this -User manual and in the
interface-specific user manual,
observation of the nameplate and possible prohibition- or instruction labels on the
equipment,
observation of the supplementary documentation e.g. the accompanying product
sheet, connector assignments etc.,
observation of the machine- or system manufacturer's operating manual, operating of the equipment within the limits indicated in the technical data
( -User manual/interface-specific user manual).
2.5 Non-intended use
Risk of death, bodily injury or damage resulting from non-intended use of the equipment!
Since the equipment is not a safety component according to the EC-
machine directive, a plausibility test of the measuring-system-values has to be performed through the downstream control.
It is compulsory for the operator to incorporate the equipment into their own
safety system.
The following uses are especially prohibited:
- in environments with an explosive atmosphere of the Zones
0, 1, 20 and 21
- for medical aims
- commissioning of the equipment if the nameplate is no longer readable
or is completely missing.
Basic safety instructions
TR-Electronic GmbH 2013, All Rights Reserved Printed in the Federal Republic of Germany
Page 12 of 29 TR - ECE - BA - GB - 0101 - 05 02/21/2018
2.6 Warranty and liability
The "General terms and conditions" (“Allgemeine Geschäftsbedingungen”) of the company TR-Electronic GmbH apply in general. This will be available to the operator with the contract confirmation or –conclusion at the latest. Warranty- or liability claims with regards to personal- and property damage are excluded, if they are the result of one or more of the following causes:
Non-intended use of the equipment.  Improper assembly, installation, commissioning, programming, maintenance
or dismantling of the equipment.
Improperly executed work on the equipment by unqualified personnel.  Operating of the equipment in the presence of technical defects.  The performance of unauthorized mechanical or electrical modifications of the
equipment.
The performance of unauthorized repairs  Catastrophic incidents caused by external forces or acts of God.
2.7 Organizational measures
The -User manual must always be kept within reach in the equipment's
operating location.
In addition to the -User manual, the generally applicable legal regulations and
other mandatory directives for work safety, accident prevention and environmental conservation are to be observed and conveyed.
The applicable national-, site- and system-specific provisions and requirements
are to be observed and conveyed.
The operator has the obligation to point out any special operational features and
requirements to the personnel.
Before starting work, the personnel responsible for work on or with the equipment
must have read and understood the -User manual, in particular the chapter on Basic safety instructions”.
The nameplate and possible affixed prohibition- or instruction labels on the
equipment must be kept in a readable condition.
Do not perform any mechanical or electrical modifications to the equipment,
except those which are specifically described in this -User manual.
Repairs may only be performed by the manufacturer, or by a person or body who
carries the manufacturer's authorization.
Printed in the Federal Republic of Germany TR-Electronic GmbH 2013, All Rights Reserved
02/21/2018 TR - ECE - BA - GB - 0101 - 05 Page 13 of 29
2.8 Personnel selection and -qualification; basic obligations
2.8.1 Electrical installations design, device selection and erection
The project development of electrical systems, the selection of the devices and the installation in potentially explosive atmospheres may only be performed by persons whose training includes instruction in various types of ignition and installation techniques, applicable regulations and prescriptions as well as general principles of the Zone-classification. The persons must have the relevant competence for the type of work to be performed.
The personnel must regularly undergo corresponding further training or courses. For definitions on the knowledge, expertise and competence of the "responsible
persons", "manual workers" and "planners", the IEC 60079-14 or DIN EN 60079-14 standards are to be additionally consulted [suppliers e.g. Beuth Verlag GmbH, VDE­Verlag GmbH].
2.8.2 Inspection, maintenance and repair
The inspection, maintenance and repair of electrical systems in potentially explosive environments may only be performed by experienced personnel who have also gained knowledge on the various types of ignition and installation procedures, the requirements of the IEC / DIN EN 60079-17 standard, relevant national provisions and company regulations for the system as well as on the general principles of the Zone­classification during their training.
Personnel are to undergo appropriate further training or instruction regularly. Proof of the relevant experience and completed training must be available.
For definitions on the knowledge, expertise and competence of the "responsible persons", "expert person with leadership functions" and the "performing personnel", the IEC 60079-17 or DIN EN 60079-17 standards are to be additionally consulted [suppliers e.g. Beuth Verlag GmbH, VDE-Verlag GmbH].
Basic safety instructions
TR-Electronic GmbH 2013, All Rights Reserved Printed in the Federal Republic of Germany
Page 14 of 29 TR - ECE - BA - GB - 0101 - 05 02/21/2018
2.9 First commissioning / Commissioning
Prior to the first commissioning the equipment is to be checked regarding its suitability in the respective zone according to its labeling. The values indicated on the nameplate are not to be exceeded. With use of the equipment in areas which are potentially explosive because of dust, a deposit of dust on the top-side which is more than 5 mm thick is not permissible. Here the installation of an additional covering may be required in circumstances where the deposit of dust cannot be reliably avoided.
The operational safety of the equipment and the correct functional arrangement of the equipment inside the plant must be checked before commissioning. It may only be used in a clean and undamaged condition.
2.10 Assembly, installation and dismantling
With installation and operation of the explosion protective equipment, one should consider protection against hazardous environmental influences which limit the intended use of the equipment. This could be protection against aggressive fluids or weather protection for example. During installation, the IEC 60079-14 and DIN EN 60079-14 as well as other national standards and regulations applicable at the installation site are to be adhered to.
The information on the nameplate must be complied with. The assembly of the equipment takes place according to the enclosure's established
mounting possibilities, but impacts on the shaft such as from hammer blows are to be avoided.
In potentially explosive areas, the equipment's power supply line with mating connector is to be routed in such a way that it is protected from damage and mechanical failure. The maximum connection information on the nameplate must be complied with.
For metal enclosures in potentially explosive areas an equipotential line with at least 4 mm2 is required.
Wiring work, opening and closing of electrical connections may only be performed with the power switched off. Do not perform any welding work once the equipment has already been wired and switched on.
Touching the equipment-connection contacts with bare hands is to be avoided, or the respective ESD-protective measures are to be implemented.
Printed in the Federal Republic of Germany TR-Electronic GmbH 2013, All Rights Reserved
02/21/2018 TR - ECE - BA - GB - 0101 - 05 Page 15 of 29
2.11 Inspection, maintenance and repair
The operator of an electrical system in a potentially explosive environment must keep the equipment in an good condition, operate it properly, monitor it and maintenance and repair work must be performed, also see IEC 60079-17 and DIN EN 60079-17 in this respect.
Maintenance work and defect repairs may only be performed by trained professionals. Before the maintenance or repair, the specified safety precautions are to be observed.
The warning notes on the equipment and in the -User manual and the interface­specific user manual are to be adhered to! The applicable laws and directives are complied with before recommissioning.
The equipment does not require any maintenance by the operator.
Nevertheless, inspections must be performed at regular intervals:
Visual inspection
- of the enclosure for damages
- of the supply line for external damages
- for dust deposits
Checking of the connection plug for a tight fit
In case of damages, the equipment is to be taken out of service immediately
and to be repaired by the manufacturer!
2.12 Special conditions for safe use, marking "X"
The "X" symbol in the labeling of the equipment is used to indicate special application conditions:
The equipment's installation location and -manner are generally to be selected in such a way that it is protected from external mechanical influences and in a way that no function limitations can result.
Misappropriations of the equipment as
support
tread plank
stirrup
are prohibited. The mating connector must be secured against accidental disconnection through the
use of a screw locking device.
Transport / Storage
TR-Electronic GmbH 2013, All Rights Reserved Printed in the Federal Republic of Germany
Page 16 of 29 TR - ECE - BA - GB - 0101 - 05 02/21/2018
3 Transport / Storage
Transport – instructions
Do not drop the device or allow hard impacts! Only use the original packaging!
Inappropriate packaging material may cause damage to the device during transport.
Storage
Storage temperature:
- AE*58: -30 to +80°C
- AM*58: -30 to +85°C Store in a dry place
Printed in the Federal Republic of Germany TR-Electronic GmbH 2013, All Rights Reserved
02/21/2018 TR - ECE - BA - GB - 0101 - 05 Page 17 of 29
4 Technical data
4.1 Power supply
Rated Voltage ........................................................
24 V DC
Power consumption .............................................
3 W
4.2 Mechanical characteristics
Mechanically permissible speed .........................
4000 min-1
Shaft load
A*V58 .....................................................................
10 N axial, 20 N radial; at the shaft end
A*S58 .....................................................................
Own mass
Bearing life time ....................................................
3,9 * 1010 revolutions at
Operating temperature ...........................................
60 °C
Shaft loading
A*V58 ......................................................................
5 N axial, 10 N radial; at the shaft end
A*S58 ......................................................................
Own mass
Angular acceleration ............................................
104 rad/s2
Moment of inertia
AE*58 .....................................................................
typically 2.5 * 10-6 kg m2
AM*58 .....................................................................
typically 1.3 * 10-6 kg m2
Start-up torque at 20 °C .......................................
typically 2 Ncm
Mass .......................................................................
0.3…0.5 kg
4.3 Environmental conditions
Vibration, DIN EN 60068-2-6 ................................
100 m/s2, sine 50-2000 Hz
Shock, DIN EN 60068-2-27 ...................................
1000 m/s2, half-sine 11ms
EMC
Immunity to disturbance, DIN EN 61000-6-2
Transient emissions, DIN EN 61000-6-3
Working temperature ...........................................
-20 °C…+60 °C
Storage temperature
AE*58 .....................................................................
-30 °C…+80 °C, dry
AM*58 .....................................................................
-30 °C…+85 °C, dry
Relative humidity, DIN EN 60068-3-4 ..................
98 %, non-condensing
1
Protection class .................................................
IP64: Degrees of protection provided by enclosures
according to DIN EN 60529
1
Observe instructions for plug connections / mating plugs, see chapter 2.12 on page 15
Technical data
TR-Electronic GmbH 2013, All Rights Reserved Printed in the Federal Republic of Germany
Page 18 of 29 TR - ECE - BA - GB - 0101 - 05 02/21/2018
4.4 Enclosure materials
Aluminum design
Enclosure material ..................................................
Al Mg Si 0.5 F22
Flange material .......................................................
EN AW-AlCu6BiPb
Shaft, stainless steel ............................................
WN 1.4305, corrosion resistant
Printed in the Federal Republic of Germany TR-Electronic GmbH 2013, All Rights Reserved
02/21/2018 TR - ECE - BA - GB - 0101 - 05 Page 19 of 29
4.5 Explosion protection characteristics
4.5.1 Ex-labeling, gas
II 3G Ex nAc IIC T6 X
II
3G
Ex
nAc
II C T6
X special conditions
Temperature (IEC/CENELEC)
Subgroup (IEC/CENELEC)
Group (IEC/CENELEC)
Ignition protection type (IEC/CENELEC)
Labeling (IEC/CENELEC)
Device category (ATEX)
Device group (ATEX)
Ex-labeling (ATEX)
Device group .........................................................
II: potentially gas-explosive areas
Device category ....................................................
3G: Zone 2
adequate safety with normal operation
Ignition protection type .......................................
nAc: non-sparking equipment
Ex-Atmosphere cannot be ignited in case of defined malfunction conditions
Group .....................................................................
II: potentially gas-explosive areas
Subgroup ..............................................................
C: typical gas: Hydrogen, acetylene
Temperature ..........................................................
T6: max. enclosure surface-temperature 85 °C
Special conditions ................................................
X: see chapter 2.12 on page 15
Technical data
TR-Electronic GmbH 2013, All Rights Reserved Printed in the Federal Republic of Germany
Page 20 of 29 TR - ECE - BA - GB - 0101 - 05 02/21/2018
4.5.2 Ex-labeling, dust
II 3D Ex tc IIIC T80°C IP64 X
II
3D
Ex
tc
III
C
T80°C
IP64
X
special conditions
Type of protection
Temperature
Subgroup (IEC/CENELEC)
Group (IEC/CENELEC)
Ignition protection type (IEC/CENELEC)
Labeling (IEC/CENELEC)
Device category (ATEX)
Device group (ATEX)
Ex-labeling (ATEX)
Device group .........................................................
II: potentially dust-explosive areas
Device category ....................................................
3D: Zone 22
adequate safety with normal operation
Ignition protection type .......................................
tc: Protection by enclosure
with adherence to the type of protection and within the surface temperature limits, Ex-atmosphere cannot be ignited
Group .....................................................................
III: potentially dust-explosive areas
Subgroup ..............................................................
C: Type of dust: conductive dust
Temperature ..........................................................
T80°C: max. enclosure surface-temperature 80 °C
2
Protection class .................................................
IP64: Degrees of protection provided by enclosures
according to DIN EN 60529
Special conditions ................................................
X: see chapter 2.12 on page 15
2
Observe instructions for plug connections / mating plugs, see chapter 2.12 on page 15
Printed in the Federal Republic of Germany TR-Electronic GmbH 2013, All Rights Reserved
02/21/2018 TR - ECE - BA - GB - 0101 - 05 Page 21 of 29
5 Assembly
Dimensions must be taken from the customer-specific drawing Tolerance specifications of the coupling manufacturer are to be adhered to
5.1 Solid shaft
The equipment with solid shaft is connected to the drive shaft via an elastic coupling. Deviations in axial and radial direction between the equipment and drive shaft are absorbed by means of the coupling. This avoids excessive loads.
Danger of explosion through the use of couplings which are not suitable for use in potentially explosive areas!
- Only couplings may be used which are approved for use in potentially
explosive areas and which meet the requirements of the defined characteristics, see the chapter “Technical data”, as from page 17.
- Adhere to the assembly and operating instructions of the manufacturer.
5.1.1 Flange-assembly
The centring collar with proper fit assures the centring of the shaft. Attachment to the machine takes place via bolts in the flange.
1: ATEX-conformant coupling 2: Machine 3: Centring collar
Principle
Figure 1: Flange-assembly
Assembly
TR-Electronic GmbH 2013, All Rights Reserved Printed in the Federal Republic of Germany
Page 22 of 29 TR - ECE - BA - GB - 0101 - 05 02/21/2018
5.1.2 Clamp flange - assembly
The centring collar with proper fit assures the centring of the shaft. Attachment to the machine takes place via a clamp flange.
1: ATEX-conformant coupling 2: Clamp flange 3: Centring collar
Principle
Figure 2: Clamp flange - assembly
Printed in the Federal Republic of Germany TR-Electronic GmbH 2013, All Rights Reserved
02/21/2018 TR - ECE - BA - GB - 0101 - 05 Page 23 of 29
5.1.3 Fixing clamps - assembly
The centring collar with proper fit assures the centring of the shaft. Attachment to the machine takes place via 2 fixing clamps, which are mounted with 4 bolts.
1: ATEX-conformant coupling 2: Machine 3: Centring collar 4: Fixing clamps, 2x
Principle
Figure 3: Fixing clamps - assembly
Assembly
TR-Electronic GmbH 2013, All Rights Reserved Printed in the Federal Republic of Germany
Page 24 of 29 TR - ECE - BA - GB - 0101 - 05 02/21/2018
5.1.4 Servo clamps - assembly
The centring collar with proper fit assures the centring of the shaft. Atachment to the machine takes place via three servo clamps
1: ATEX-conformant coupling 2: Machine 3: Centring collar 4: Servo clamps, 3x
Principle
Figure 4: Servo clamps - assembly
Printed in the Federal Republic of Germany TR-Electronic GmbH 2013, All Rights Reserved
02/21/2018 TR - ECE - BA - GB - 0101 - 05 Page 25 of 29
5.2 Blind hollow shaft
The equipment with blind hollow shaft is connected to the drive shaft via a clamp ring. The rotating of the equipment, caused by the resulting torque, is prevented through a torque holder (spring plate). The occurring axial- or radial displacements are offset and the machine vibrations damped at the same time.
1: Clamp ring 2: Drive shaft 3: Torque holder
Principle
Figure 5: Clamp ring/Torque holder - assembly
Equipotential bonding conductor - Connection
TR-Electronic GmbH 2013, All Rights Reserved Printed in the Federal Republic of Germany
Page 26 of 29 TR - ECE - BA - GB - 0101 - 05 02/21/2018
6 Equipotential bonding conductor - Connection
An equipotential is required for systems in potentially explosive areas. This is to be done with a minimum wire diameter of 4 mm2.
Not included: (1): M4 attachment bolt (2): Locking element (3): Cable lug
Figure 6: Equipotential bonding conductor - Connection
(1) (2)
(3)
Printed in the Federal Republic of Germany TR-Electronic GmbH 2013, All Rights Reserved
02/21/2018 TR - ECE - BA - GB - 0101 - 05 Page 27 of 29
7 Disposal
Electronic waste is hazardous waste. The applicable country-specific regulations are to be adhered to for disposal.
Annex
TR-Electronic GmbH 2013, All Rights Reserved Printed in the Federal Republic of Germany
Page 28 of 29 TR - ECE - BA - GB - 0101 - 05 02/21/2018
8 Annex
8.1 EU declaration of conformity
Printed in the Federal Republic of Germany TR-Electronic GmbH 2013, All Rights Reserved
02/21/2018 TR - ECE - BA - GB - 0101 - 05 Page 29 of 29
8.2 Accessories
490-00101
Info
Switchboard­module PT-6
TR-V-TI-GB-0020
490-00105
Info
Switchboard-
module PT-15/2
TR-V-TI-GB-0060
490-00310
Info
USB
PC-Adapter V4
TR-E-TI-DGB-0074
49-110-xxx
Info
Fixing clamps/
Servo-clamps
TR-V-TI-GB-0400
490-01001
Software- and Support-DVD:
- GSD-, EDS-, type- and XML-files + Documentation
- Programming-Software
- Driver
8.2.1 Interface-specific user manual
Document-No.:
Description
TR-ECE-BA-DGB-0039
Absolute Encoder Series C_ _-58 with SSI interface
TR-ECE-BA-DGB-0083
Absolute Encoder Series CM_-58 with Analog interface