TRC AECM20020 Operating Instructions Manual

This compact, easy to use instrument is made with advanced microelectronics and provides accurate testing and monitoring of electrical outlets and systems. Constantly monitors voltage and frequency indicating potential improper polarity and ground wiring. Its small size and rugged construc­tion allows for convenient installation in an electrical outlet or use as a portable service tool.
INSTALLATION
The AECM20020 Digital Monitor is for use in a standard 120V/15A outlet. It is suitable for continu­ous or occasional use.
The voltage is measured as RMS which is much more precise than AC average. RMS metering is the only method that can accurately measure all AC power sources. The RMS voltage and frequency readings are ideal for monitoring modified sine waves, such as solid-state generators, inverters and Uninterruptible Power Supply (UPS) products.
OPERATION
The Digital Monitor display will alternate between line voltage in RMS volts and line frequency in
Hertz. The LCD display shows an “F” in front of the reading to denote frequency.
There are three display modes available:
Alternating Voltage and Frequency (VOLT/FREQ.)
Voltage only (VOLTAGE)
Frequency only (FREQUENCY)
Pressing the MODE button on the front of the Digital Monitor will cycle through the display modes. Both voltage and frequency are constantly monitored regardless of the display mode.
When the Digital Monitor detects a fault condition the fault LED comes on immediately upon fault threshold being exceeded. If the fault threshold is exceeded and sustained for three seconds it sounds an audible alert for 5 seconds and shows the cause for the fault on the display. The wiring faults are Open Ground (GF) and Polarity Fault (PF). The voltage faults are Low voltage (Lo) of 102 Vac or lower and High voltage (HI) of 135 Vac or higher. The frequency faults are Low Frequency (LF) of less than 55 Hz and High Frequency (HF) of over 65 Hz. Fault reset thresholds must be obtained to re-enable the fault alarms. When a wiring fault (GF) or (PF) is displayed, the MODE button may be used to sequence the display to show the current voltage or frequency by successive button actuations.
For ground and wiring faults, consult a qualified electrician for correction.
CAUTION
Dangerous conditions may exist if not used in accordance with these instructions.
Equipment protected by Double Insulation.
STORAGE
When not in use the Digital Monitor should be stored in a dry location out of direct sunlight.
DIGITAL MONITOR OPERATING INSTRUCTIONS
MODEL AECM20020
RATING MINIMUM TYPICAL MAXIMUM
Voltage range 85 Vac RMS 120 Vac RMS 150 Vac RMS Frequency range 40 Hz 60 Hz 80 Hz Operating current 0.02 Amps Power rating 2.0 Watts Under voltage alarm 102 Vac RMS Over voltage alarm 135 Vac RMS Under frequency alarm 55 Hz Over frequency alarm 65 Hz Operating temperature 0° C 60° C Storage temperature -45° C 85° C
Description Class II, Pollution Degree 2, Measurement Category II
Environmental Conditions
Indoor use
Altitude up to 2000 M
Temperature: 5°C to 40°C
Maximum Relative Humidity 80%
Protected by Patent No. US 7,164,273,B2
TRC WARRANTY
TRC warrants that its devices are free from defects in materials and workmanship for a period of one year from the date of original purchase.
This one year warranty is in lieu of all other warranties, obligations, or liabilities expressed or implied by the company. Any properly installed device that proves defective in normal use will be repaired or replaced at TRC’s option provided the unit is returned through an authorized TRC dealer or representative or shipped directly to:
Sales Department
Technology Research Corporation
5250 140th Avenue North • Clearwater, Florida 33760
The product should be properly packaged and shipped postage prepaid. Please enclose the following:
Proof of purchase, including date of purchase.
An explanation of the defect or failure and a return address.
Warranty is void if the device has been opened, altered, misused and/or abused in any way.
TRC cannot assume responsibility for customer alterations, acts of God, or any other factors not under the control of TRC.
TRC cannot assume responsibility for damage in handling of shipment.
TRC shall have no responsibility for installation of this device or for any personal injury, property damage, any incidental, contingent, or consequential damages of any kind resulting in defects or failure of the unit to function in the event of a ground fault in the circuit.
Implied warranties (if any) including but not limited to implied warranties of fitness for a particular purpose and merchantability, are limited in duration to a period ending one year from the date of original customer purchase. The exclusive remedy for breach of the limited warranty contained herein is the repair or replacement of the defective product at TRC’s option. In no case shall TRC’s liability under any other remedy prescribed by law exceed the purchase price. Some states do not allow the exclusion or limitation of incidental or consequential damages or allow disclaimers or modifications of or limitation on how long an implied warranty lasts, so the above limitations may not apply to you. This warranty gives you specific legal rights and you may also have other rights which may vary from state to state.
Technology Research Corporation
5250 140th Avenue North • Clearwater, Florida 33760
(727) 535-0572
3000-04-08RB90864B
Loading...