Travis Industries AGP Troubleshooting Manual

Page 1
AGP
(All Grade Pellet)
Troubleshooting Guide
Document 176-01795
Travis Industries Certied Factory Training Program
Copyright © 2017
Page 2
Page 3
AGP™ Pellet Troubleshooting
The unit has been programmed to evacuate smoke in case of a power failure. When 110V is introduced to the unit the exhaust fan will start and operate approximately 15 minutes, and the
RED stop light will illuminate.
To START Manually
IF CONTROL BOARD IS FLASHING EITHER A RED LIGHT OR BLUE LIGHT, OR HAS CONSTANT RED AND GREEN, REFER TO DIAGNOSTIC CHART.
Press the START button on the control panel. The stove will enter the start-up sequence for approximately 22 min.
• 1. Green light will start to ash in start up mode.
• 2. Exhaust blower will come on.
• 3. Push Auger will turn.
Plug
stove into
outlet. Does
YES
convection fan
come
on?
• 4. Meter System will turn.
• 5. Pellets will start to feed the system.
• 6. Igniter will come on.
1. Check system disc for continuity.
NO
Green
light will
start to ash in
START-UP
mode
YES
Exhaust
Blower Comes
On?
YES
NO
GREEN
LIGHT
NO
1. If no power, check fuses on control board and the inline fuse on the back of the unit. (See Diagram 4).
2. If there is power to the board and GREEN light does not come on when the start button is depressed. Replace the control board.
1. Check continuity of exhaust blower or connect power directly to the blower. If blower does not function and there are no obstructions in the blower housing, replace blower.
2. Check wiring connection. (See Diagram 1). Check
pathway for continuity from pin #4 to the end of the Black wire and pin #7 to White wire.
3. Is the blower getting power? If not receiving power
check fuses on control board and power supply. If fuses are good you will see the ashing GREEN light, if not replace board. (See Diagram 4).
SEE NEXT PAGE.
Copyright © 5/5/2016- Travis Industries Certified Factory Training Program
1
Page 4
AGP™ Pellet Troubleshooting
1. Check vacuum and brass barb tube for blockage, kinks, or cracks.
2. Check ow switch for continuity. No continuity through ow switch when actuated, replace ow switch.
Push
Auger
Turning?
YES
Meter Motor
Turning
(HRD)?
NO
NO
3. Check continuity of motor.
4. Check jumper wire between ow switch and push auger for continuity. Check continuity from pin #7 to White wire. If no continuity replace wiring.
5. Check for power to motor, this should be a constant power supply (See Diagram 2).
6. Connect power direct to motor to determine if operational. If not turning replace motor.
7. Check auger ight for jam.
8. If the ow switch is good and still no power to motor, replace control board.
1. Push auger must be operational for meter motor to operate.
2. Is the Start light ashing?
3. Are there pellets in the hopper?
4. If push auger is turning and Stop light on control board is ashing, Check encoder for proper voltage to and from control board and if Molex is connected to the control board.
(See Diagram 3). Check continuity of metering motor.
5. Check for power to the meter motor, this will be an intermittent
YES
SEE NEXT PAGE.
Copyright © 5/5/2016- Travis Industries Certified Factory Training Program
power supply. (See Diagram 2).
6. Is hopper lid closed and lid switch actuated?
7. Connect power direct to motor to determine if operational. (If slight movements check for jam)
8. Check Hopper lid switch for continuity.
9. Check Horizontal Rotating Disc (HRD) assembly for
fouling or jam.
10. Check pathway (with hopper CLOSED) from pin #6 to the end
of the RED wire pin #7 to WHITE wire.
11. Check to see if encoder molex is plugged in at board.
12. Remove pellets from the hopper; disconnect metering
motor to determine if HRD is spinning freely.
NOTE: Do not use a wrench or socket drive on 7/16”
retaining bolt on HRD to free a jam. Serious damage can occur or bolt can be broken. If this happens the stove must be returned for repair.
2
Page 5
AGP™ Pellet Troubleshooting
1. Check to see if the wires are connected?
Igniter
Comes On
YES
Pellets
Ignite
NO
NO
2. Check igniter for continuity. Ohms should be (57Ω +10/-5) (If ohms not in range replace igniter).
(See Diagram 2).
3. Check for voltage to the Igniter? No voltage, check fuse. Check that unit is in start mode with ashing green light. Not working? Replace control board.
4. Check pathway continuity from pin #1 to the end of
the BLACK wire and pin #7 to the WHITE wire.
NOTE: Igniter is accessed through combustion chamber and behind burn platform.
(See Diagram 5).
1. Pellets should ignite between 5-15 minutes from the time the start button is pushed.
2. Check the gaskets on the door, the ash door and that both are latched.
3. Ensure exhaust access panel behind ash pan is in place.
Copyright © 5/5/2016- Travis Industries Certified Factory Training Program
3
Page 6
AGP™ Pellet Troubleshooting
RUN MODE
Convection
Blower Comes
On
YES
Green
Light Goes
to Constant
Glow?
NO
NO
1. Check Systems disc for continuity. If no continuity when hot replace System disc.
2. Jumper Systems disc and check power supply to convection blower. If no power when systems disc is jumped, replace control board.
3. Check continuity or connect power direct to blower. If there is no continuity or blower does not function with direct power, replace blower.
1. If the green light does not stay on and the red light comes on, this indicates the unit has gone into shut down.
2. Check the systems disc for continuity when heated. If no continuity, replace systems disc.
SHUT DOWN MODE
Press the STOP button on the control panel. The stove will begin the shut-down process, which takes approximately 45 minutes.
1. The metering auger will stop feeding pellets, but the push auger stays running.
2. When the unit gets cool the convection blower will shut off while the combustion
2. blower stays running for another 15 minutes.
3. The unit is now off and waiting to be started.
Copyright © 5/5/2016- Travis Industries Certified Factory Training Program
4
Page 7
AGP™ Pellet Troubleshooting
THERMOSTAT MODE
Tstat calls for heat.
1. Unit will go into start mode. Unit will start same as manually. See manual start.
The stove will enter the start-up sequence for approximately 22 min. See manual start.
Changing the TSTAT Program
This heater comes with three TSTAT programs built in. Each program is unique and allows you to modify your thermostat setting to your preference. The stove is shipped pre-pro­grammed in TSTAT program 1.
How to Tell Which TSTAT Program You Are In
When you press the “STOP” and “TSTAT” button simultaneously while the unit is cold the blue Auto-Fan LED light will ash. It will ash once for Program 1, twice for Program 2, and three times for Program 3. Flashes are quick.
Switching Between Program 1, 2, and 3
Each time you press the “STOP” and “TSTAT” button simultaneously while the unit is cold, the TSTAT program will toggle to the next program. Continue to press these two buttons until the blue Auto-Fan LED light ashes the program you wish to use.
Thermostat Program 1
When the thermostat stops calling for heat (the thermostat is open) the feed rate “steps down” to a lower heat setting. The heater will stay at this setting for 15 minutes. If the thermostat does not call for heat, the feed rate will “step down” again to a lower setting (or off).
At any time if the thermostat calls for heat (thermostat is closed) during this cycle, the heater will resume at the HEAT output setting set at the control board.
If it switches to off and there is a call for heat it will switch to start up mode for the 22 min. cycle before returning to its board setting.
Copyright © 5/5/2016- Travis Industries Certified Factory Training Program
5
Page 8
AGP™ Pellet Troubleshooting
THERMOSTAT MODE
THERMOSTAT PROGRAM 2
In Thermostat Mode Program 2 when the thermostat stops calling for heat (the thermostat is open) the following happens:
The burn rate decreases to Level 1 (low) for 15 minutes. If there is no call for heat during that time…
The unit turns off. If there is a call for heat by the thermostat (the thermostat is closed) at any point during this cool-down period then the burn rate resumes corresponding with the setting on the control panel.
THERMOSTAT PROGRAM 3
In Thermostat Mode Program 3 when the thermostat stops calling for heat (the thermostat is open) the following happens:
The burn rate decreases to Level 1 (low) and remains at this level until there is a call for heat by the thermostat (the thermostat is closed), then resumes corresponding with the set­ting on the control panel.
Run mode. Same as manual mode.
Shut Down. Same as manual mode.
Copyright © 5/5/2016- Travis Industries Certified Factory Training Program
6
Page 9
AGP™ Pellet Troubleshooting
Copyright © 5/5/2016- Travis Industries Certified Factory Training Program
7
Page 10
AGP™ Pellet Troubleshooting
Stove - Diagram 1
System Snap Disc
Exhaust/Combustion
Blower
Flow Switch
Copyright © 5/5/2016- Travis Industries Certified Factory Training Program
8
Page 11
AGP™ Pellet Troubleshooting
Stove - Diagram 2
Grey Wires
go to
Hopper Snap
Disc
Push Motor
with Encoder
Safety Snap
Disc
Meter Motor
(HRD)
Igniter
Encoder
Molex
Copyright © 5/5/2016- Travis Industries Certified Factory Training Program
Wires
Convection Blower
9
Page 12
AGP™ Pellet Troubleshooting
INSERT - Diagram 1
Meter Motor
Cooling Fan
Push Motor
with Encoder
Exhaust
Blower
Cooling
Fan Fuse
Encoder
Molex
(HRD)
Flow Switch
Push Auger
Igniter
Convection
Wires
Fan
Copyright © 5/5/2016- Travis Industries Certified Factory Training Program
10
Page 13
AGP™ Pellet Troubleshooting
Insert - Diagram 2
Cooling Fan Cooling
Fan Fuse
0.5 AMP/125 v
Control Panel Light Molex
Control
Panel
Light
Micro
Switch
Encoder Molex
Hopper Lid
Switch
Connection
Copyright © 5/5/2016- Travis Industries Certified Factory Training Program
Inline
Fuse
11
Page 14
AGP™ Pellet Troubleshooting
Diagram 3 - Encoder Voltage Test
Take measurements from the Molex Connector (either side)
Voltage DC
5
To Red and Black Wires
If no power check molex connection at control board. If good replace control board.
5 VDC
Set To DCV
Voltage DC
2.5
2.5 VDC
If not 2.5 VDC and you are reading 5 VDC through the RED and BLACK wires, replace the Pusher Auger.
Copyright © 5/5/2016- Travis Industries Certified Factory Training Program
Set To DCV
To White and Black Wires
12
Page 15
AGP™ Pellet Troubleshooting
Diagram 4
5amp/125v Fuse
5amp/250v Fuse
STOVE
Encoder Molex
Back Of Unit
INSERT
5amp/250v Fuse
Copyright © 5/5/2016- Travis Industries Certified Factory Training Program
Bottom of
Control Board
13
Page 16
AGP™ Pellet Troubleshooting
Diagram 5 - Ignitor
Burn Platform
Igniter
Copyright © 5/5/2016- Travis Industries Certified Factory Training Program
14
Page 17
AGP™ Pellet Troubleshooting
Copyright © 5/5/2016- Travis Industries Certified Factory Training Program
15
Page 18
AGP™ Pellet Troubleshooting
AGP™ Pellet Insert
Copyright © 5/5/2016- Travis Industries Certified Factory Training Program
16
Loading...