Travis Industries 864 HO NB, 864 HO GS, 864 HO NB GSR2 Installation Manual

Page 1
864 HO NB Fireplace
_
Featuring the
• Direct Vent Fireplace
• Vent Horizontally or Vertically
• Standard Residential
• Mobile Home Approved
Tested and Listed by
Report # 100162735PRT-001 - ANSI Z21.88
WARNING: If the information in these instructions is not followed exactly, a fire or explosion may result
causing property damage, personal injury or loss of life.
- Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call gas supplier from a neighbor's phone. Follow the gas supplier's instructions.
• If you cannot reach your gas supplier, call the fire department.
Burner
- Installation and service must be performed by a qualified installer, service agency or the gas supplier.
This appliance may be installed in an aftermarket permanently located, manufactured home (USA only) or mobile home, where not prohibited by local codes.
This appliance is only for use with the type(s) of gas indicated on the rating plate. A conversion kit is supplied with the appliance.
Installation Manual
Installer: After installation give this manual to
the home-owner and explain operation of this heater.
Copyright 2012, T.I. $10.00 100-01290
4120327
000
www.travisproducts.com
4800 Harbour Pointe Blvd. SW
Mukilteo, WA 98275
Page 2
2 Table of Contents
Overview ................................................................... 3
Listing Details ........................................................... 3
Installation Options .................................................. 6
Heating Specifications ............................................. 6
Dimensions ............................................................... 6
Packing List .............................................................. 7
Additional Items Required ....................................... 7
Recommended Installation Procedure ................... 7
Massachusetts Requirements ................................ 8
Requirements for the Commonwealth of
Massachusetts .................................................................8
MANUFACTURER REQUIREMENTS .............................8
Fireplace Placement Requirements ....................... 9
Clearances ......................................................................9
Raised Fireplaces ............................................................9
Minimum Framing Dimensions – Rear Vent ....................10
Minimum Framing Dimensions – Top Vent ......................11
Nailing Brackets ...............................................................12
Corner Installations - Rear Vent Configuration ................13
Gas Line Requirements ........................................... 14
Fuel .................................................................................14
Gas Line Connection .......................................................14
Gas Inlet Pressure ...........................................................14
Gas Line Location ............................................................15
Electrical Connection ............................................... 16
Optional Wall Switch or Thermostat Installation .. 17
Parallel ConnectionSeries Connection ...................17
Vent Requirements ................................................... 18
Vent Clearances ..............................................................18
Vent Firestop ...................................................................18
Altitude Considerations ....................................................18
Approved Vent .................................................................18
Vent Installation ...............................................................18
Vent Location and Vent Shield Position ...........................19
Approved Vent Configurations ............................... 20
Restrictor Position ...........................................................20
Exhaust Restrictor ...........................................................20
Intake Restrictor ..............................................................21
Vent Configuration: Horizontal Termination (no
vertical rise) .............................................................. 22
Vent Configuration: Horizontal Termination
(with vertical rise) ..................................................... 23
Vent Configuration: Vertical Termination .............. 24
Termination Requirements ...................................... 25
Hearth Requirements ............................................... 26
Facing Requirements ............................................... 27
Facing and Faceplate Installation ....................................28
Optional Faceplates – Sizing Chart .................................29
Special Instructions for Metropolitan and Victorian
Lace Faces ......................................................................29
Special Instructions for Wilmington Faces .......................29
Special Instructions for Louvered Grills / Rosario
Faces............................................................................... 30
Thin Facing Installation (tile, marble, or other non-
combustible under 1" (25mm) thick) ................................ 31
Thin Facing Installation (tile, marble, under 1" (25mm)
thick) - Side View ............................................................. 32
Thick Facing Installation (stone, brick, or other non-
combustible over 1" (25mm) thick) .................................. 33
Thick Facing with Fireplace Xtrordinair (FPX) Arched
Faces............................................................................... 34
Thick Facing Installation - Side View ............................... 35
Mantel Requirements ............................................... 36
Mantel Column Clearances ........................................... 36
Steps for Finalizing the Installation ........................ 37
Air Shutter Adjustment .................................................... 38
Glass Frame Removal and Installation .................. 39
Glass Frame Removal and Installation
(continued) ................................................................ 40
Fireback Installation ................................................. 41
LP Conversion Instructions .................................... 42
Andiron Installation .................................................. 45
GreenSmart™ Remote Control Installation ........... 46
GreenSmart Wiring Diagram ........................................... 48
GreenSmart Installation ................................................... 49
Power Heat Duct Installation ................................... 57
© Travis Industries 4120327 100-01290_000
Page 3
Introduction and Important Information 3
Overview
This manual details the installation requirements for the 864 HO NB fireplace. For operating and maintenance instructions, refer to the 864 HO NB Owner's Manual (part # 100-01289).
Listing Details
This appliance was listed by Intertek Test Labs to ANSI Z21.88. The listing label is attached to the appliance near the gas control valve. A copy is shown to the right.
Massachusetts Approval
This manual has been submitted to the Massachusetts Board of State Examiners of Plumbers and Gas Fitters.
National Fireplace Institute
© Travis Industries 4120327 100-01290_000
Page 4
4 Safety Precautions
Safety Warnings
Failure to follow all of the requirements may result in property damage, bodily injury, or even death.  This unit must be installed by a qualified installer to prevent the possibility of an explosion.  This appliance must be installed in accordance with all local codes, if any; if not, in U.S.A. follow ANSI
Z223.1 and NFPA 54(88), in Canada follow CSA B149.1.
A manufactured home (USA only) or mobile home OEM installation must conform with the
Manufactured Home Construction and Safety Standard, Title 24 CFR, Part 3280, or, when such a standard is not applicable, the Standard for Manufactured Home Installations, ANSI/NCSBCS A225.1, or Standard for Gas Equipped Recreational Vehicles and Mobile Housing, CSA Z240.4. This appliance may be installed in Manufactured Housing only after the home is site located.
All exhaust gases must be vented outside the structure of the living-area. Combustion air is drawn
from outside the living-area structure. The venting must not be connected to a chimney flue serving a separate solid-fuel burning appliance.
Notify your insurance company before hooking up this fireplace.  The room heater should be inspected before use and at least annually by a qualified service person.
More frequent cleaning may be required due to excessive lint from carpeting, bedding material, etc.
The instructions in this manual must be strictly adhered to. Do not use makeshift methods or
compromise in the installation. Improper installation will void the warranty and safety listing.
This heater is approved for use with natural gas (NG) or propane (LP). Burning the incorrect fuel will
void the warranty and safety listing and may cause an extreme safety hazard. Direct questions about the type of fuel used to your dealer.
Contact your local building officials to obtain a permit and information on any installation restrictions
or inspection requirements in your area.
If the flame becomes sooty, dark orange in color, or extremely tall, do not operate the heater. Call
your dealer and arrange for proper servicing.
It is imperative that control compartments, screens, or circulating air passageways of the heater be
kept clean and free of obstructions. These areas provide the air necessary for safe operation.
Do not operate the heater if it is not operating properly in any fashion or if you are uncertain. Call
your dealer for a full explanation of your heater and what to expect.
Do not store or use gasoline or other flammable liquids in the vicinity of this heater.  Do not operate if any portion of the heater was submerged in water or if any corrosion occurs.
Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
Do not place clothing or other flammable items on or near the heater. Because this heater can be
controlled by a thermostat there is a possibility of the heater turning on and igniting any items placed on or near it.
Light the heater using the built-in igniter. Do not use matches or any other external device to light
your heater.
Never remove, replace, modify or substitute any part of the heater unless instructions are given in this
manual. All other work must be done by a trained technician. Don't modify or replace orifices.
The viewing glass should be opened only for conducting service.  Any safety screen or guard removed for servicing must be replaced prior to operating the heater.
© Travis Industries 4120327 100-01290_000
Page 5
Safety Precautions 5
Safety Warnings (continued)
Allow the heater to cool before carrying out any maintenance or cleaning.  Operate the heater according to the instructions included in this manual.  If the main burners do not start correctly turn the gas off and call your dealer for service.  This unit is not for use with solid fuel.  Do not place anything inside the firebox (except approved Travis Industries components).  Warning: Do not operate appliance with the glass front removed, cracked or broken. Replacement
of the glass should be done by a licensed or qualified service person.
Do not throw this manual away. This manual has important operating and maintenance instructions
that you will need at a later time. Always follow the instructions in this manual.
Young children should be carefully supervised when they are in the same room as the appliance.
Toddlers, young children and others may be susceptible to accidental contact burns. A physical barrier is recommended if there are at risk individuals in the house. To restrict access to a fireplace or stove, install an adjustable safety gate to keep toddlers, young children and other at risk individuals out of the room and away from hot surfaces.
Children and adults should be alerted to the hazards of high surface temperature and should stay
away to avoid burns or clothing ignition. Do not touch the hot surfaces of the heater. Educate all children of the danger of a high-temperature heater.
Due to the high temperature, the heater should be located out of traffic and away from furniture and
draperies.
Instruct everyone in the house how to shut gas off to the appliance and at the gas main shutoff valve.
The gas main shutoff valve is usually next to the gas meter or propane tank and requires a wrench to shut off.
Travis Industries, Inc. grants no warranty, implied or stated, for the installation or
maintenance of your heater, and assumes no responsibility of any consequential damage(s).
© Travis Industries 4120327 100-01290_000
Page 6
6 Features and Specifications
Installation Options
Residential or Mobile Home  Straight or Corner Placement  Flush or Recessed Face
Raised or Floor Placement  Internal or External Chase Bedroom Approved
Heating Specifications
Approximate Heating Capacity (in square feet)* Up to 2,500 Up to 2,500 Maximum BTU Input Per Hour 46,700 46,700
* Heating capacity will vary with floor plan, insulation, and outside temperature.
Natural Gas Propane
Dimensions
1/2" 12mm
48" 1219mm
14" 356mm
a
29-1/4" 743mm
21-1/4" 540mm
37" 940mm
41" 1041mm
arrie’re
Left
a’ gauche
Rear
36-3/4" 933mm
35-1/4" 895mm
1" 25mm
44-1/2" 1130mm
Right
droit
Front
avant
8" (203mm) Dia.
225 Lbs. (102 Kg)
40-3/4" 1035mm
© Travis Industries 4120327 100-01290_000
Page 7
Installation
(for qualified installers only)
Packing List
Propane Conversion Kit  On/Off Switch, Cover Plate, and Wire
4 AA Batteries, 1 9Volt Battery
Additional Items Required
Gas Line Equipment (shutoff valve, pipe, etc.)  Electrical Equipment (min. 14 gauge, grounded line)
This Fireplace Requires: (a) Burner Kit, (b) Firebacks, (c) Logs/Media, and (d) Face/Grill
This fireplace is shipped without a burner or logs. This allows the fireplace to be configured in several unique designs. See the table below to verify you have all of the items required.
7
Burner Kit
Firebacks
Logs/Media
Face/Grill
EmberFyre™ Burner
96900143
96100824 Brick/Herringbone 96100825 Handmade Brick 96100826 Rock Creek 96100827 Black Enamel 96100828 Dia/Stucco 96100829 Stainless Steel
Included w Burner 94500562 Driftwood Logs
Use any 864 Face or Grill Use any 864 Face or Grill Use any 864 Face or Grill
Recommended Installation Procedure
Frame the opening for the fireplace. Make sure to allow for vent installation.  This fireplace is designed to accommodate 1/2" (13mm) or 5/8" (16mm) drywall (see "Nailing
Brackets" on page 11 for details). Secure the fireplace to the framing.
Install the vent, gas line and electrical hook-up.  Install the drywall.  Install the hearth (if applicable).  Install the facing (if applicable).  Install the mantel (if applicable).  Finalize the installation (see page 36) and install the grill or face.
DiamondFyre™ Burner
96900142 96100832 Stainless
96100833 Black Enamel 96100834 Black Painted
94700734 Fyre-Stones
DancingFyre™ Burner
96900141
Included w Burner (Black Painted)
Included w Burner
© Travis Industries 4120327 100-01290_000
Page 8
8 Installation (for qualified installers only)
Massachusetts Requirements
NOTE: The following requirements reference various Massachusetts and national codes not contained in this document.
Requirements for the Commonwealth of Massachusetts
For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:
Installation of Carbon Monoxide Detectors
At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors.
In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.
In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.
Approved Carbon Monoxide Detectors
Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
Signage
A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, “GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS”.
Inspection
The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4.
Exemptions
The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:
• The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current edition of NFPA 54 as adopted by the Board; and
• Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.
MANUFACTURER REQUIREMENTS
Gas Equipment Venting System Provided
When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
• Detailed instructions for the installation of the venting system design or the venting system components; and
• A complete parts list for the venting system design or venting system.
Gas Equipment Venting System NOT Provided
When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies “special venting systems”, the following requirements shall be satisfied by the manufacturer:
• The referenced “special venting system” instructions shall be included with the appliance or equipment installation instructions; and
• The “special venting systems” shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions.
A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.
See Gas Connection section for additional Commonwealth of Massachusetts requirements.
© Travis Industries 4120327 100-01290_000
Page 9
Installation (for qualified installers only) 9
Fireplace Placement Requirements
Fireplace must be installed on a level surface capable of supporting the fireplace and vent  Fireplace must be placed directly on wood or non-combustible surface (not on linoleum or carpet)  Fireplace should be located out of traffic and away from furniture and draperies.  Fireplace must be placed so the gaps below and above the glass frame do not become blocked.  Fireplace may be placed in a bedroom. Please be aware of the large amount of heat this appliance
produces when determining a location.
Clearances
(a) Clearance to Side and Rear of Fireplace 0” (0mm) (b) When installed, walls in front of the fireplace must be a minimum 5” (127mm) to the side of the
fireplace. Do not place insulation in this space.
(c) Clearance to Angled Sides of Fireplace ½” (12mm)
a
c
b
Raised Fireplaces
The fireplace (and hearth, if desired) may be placed on a platform designed to support the fireplace
and vent.
© Travis Industries 4120327 100-01290_000
Page 10
10 Installation (for qualified installers only)
Minimum Framing Dimensions – Rear Vent
56-3/8"
1432mm
48" 1219mm
41-1/4"
1048mm
20-3/4" (527mm)
© Travis Industries 4120327 100-01290_000
Page 11
Installation (for qualified installers only) 11
Minimum Framing Dimensions – Top Vent
NOTE: When the vent is routed vertically the framing must accommodate the vent and required 1”
clearance. The framing dimensions below reflect the additional 1” depth required.
a
56-3/8"
1432mm
48" 1219mm
41-1/4"
1048mm
21-3/4" (552mm)
© Travis Industries 4120327 100-01290_000
Page 12
12 Installation (for qualified installers only)
Nailing Brackets
The fireplace has nailing brackets on both sides. Secure the fireplace to the framing. NOTE: Make sure the fireplace is square and plumb when placed in the framing. Measured corner-
to-corner the fireplace should be square (approx. 54-7/8” – 1394mm). See the illustration below. Use shims to insure the fireplace is square.
54-7/8’’
(1394mm)
1/2''(13mm)
5/8''(16mm)
1/2" (13mm)
5/8" (16mm)
© Travis Industries 4120327 100-01290_000
Page 13
Installation (for qualified installers only) 13
Typically
Corner Installations - Rear Vent Configuration
A typical 45° installation uses the framing dimensions shown in the illustration below (NOTE: all clearances still apply).
NOTE: When venting horizontally, use minimum vent kit “C” (96200316) with one additional 45° elbow.
Typically
5-1/2"
140mm
1245mm
49" Min.
12.5"
318mm
Minimum 1/2" (13mm) Clearance
© Travis Industries 4120327 100-01290_000
Page 14
14 Installation (for qualified installers only)
Gas Line Requirements
MASSACHUSETTS INSTALLATIONS - WARNING:
THIS PRODUCT MUST BE INSTALLED BY A LICENSED PLUMBER OR GAS FITTER WHEN INSTALLED WITHIN THE COMMONWEALTH OF MASSACHUSETTS.
OTHER MASSACHUSETTS CODE REQUIREMENTS:
Flexible connector must not be longer than 36 inches.  Shutoff valve must be a “T” handle gas cock.  Only direct vent sealed combustion products are approved for bedrooms or bathrooms.  Fireplace dampers must be removed or welded in the open position prior to the installation of a fireplace insert or gas log.  A carbon monoxide (CO) detector is required in the same room as the appliance.
The gas line must be installed in accordance with all local codes, if any; if not, follow ANSI 223.1 and
NFPA 54(88), in Canada follow CSA B149.1 and the requirements listed below.
The fireplace and gas control valve must be disconnected from the gas supply piping during any
pressure testing of that system at test pressures in excess of 1/2 psig (3.5 kPA). For pressures under 1/2 psig (3.5 kPA), isolate the gas supply piping by closing the manual shutoff valve.
Leak test all gas line joints and the gas control valve prior to and after starting the fireplace.  This unit has been listed using the included internal gas shutoff valve.
Fuel
This fireplace is designed either for natural gas or for propane (but not for both).
Gas Line Connection
Installation must be performed by a qualified installer, service agency or the gas supplier (In Massachusetts a
licensed plumber/gasfitter).
Gas Inlet Pressure
If the pressure is not sufficient, make sure the piping used is large enough, the supply regulator is adequately
adjusted, and the total gas load for the residence does not exceed the amount supplied.
The supply regulator (the regulator that attaches directly to the residence inlet or to the propane tank) should
supply gas at the input pressure listed above. Contact the local gas supplier if the regulator is at an improper pressure.
Natural Gas 7" W.C. (1.74 kPA) 5.5” W.C. (1.37 kPA) Propane 13" W.C. (3.23 kPA) 11” W.C. (2.74 kPA)
Maximum Input Pressure Minimum Input Pressure
© Travis Industries 4120327 100-01290_000
Page 15
Installation (for qualified installers only) 15
Gas Line Location
6-1/4" 159mm
10-3/4" 273mm
3" (77mm)
3" (77mm)
7-3/4"(197mm)
10-3/4" 273mm
6-1/4" 159mm
© Travis Industries 4120327 100-01290_000
6-3/4"(172mm)
Page 16
16 Installation (for qualified installers only)
Electrical Connection
The electrical line to the grounded receptacle inside the fireplace must be installed by a qualified
installer and must meet all local codes.
Make sure the household breaker is shut off prior to working on any electrical lines.  The appliance, when installed, must be electrically grounded in accordance with local codes or, in the
absence of local codes, with the National Electrical Code, ANSI/NFPA 70, or the Canadian Electrical Code, CSA C22.1.
The electrical line must be a min. 14 gauge, and supply 120 Volts, 60 Hz, and 5.7 Amps.  Route the electrical connection through the junction box cover plate and attach to the hookup wires
pictured below.
Caution: Label all wires prior to disconnection when servicing controls. Wiring errors can cause
improper and dangerous operation.
Do not connect 110-120 VAC to the gas control valve or wiring system of this fireplace.
a
© Travis Industries 4120327 100-01290_000
b
c
d
Page 17
Installation (for qualified installers only) 17
Optional Wall Switch or Thermostat Installation
Do not connect 110-120 VAC to the gas control valve or wiring system of this fireplace. The switch and
wiring must be installed by a qualified installer.
This fireplace includes an optional wall switch (with wire) to operate the fireplace burner without accessing the internal
OPTIONAL WALL SWITCH
(included with fireplace)
on/off switch. A thermostat may be used instead. Route the wire from inside the fireplace, through the grommet
on either side of the fireplace near the gas inlet (see at right) to the switch. The wall switch (or thermostat) may bypass the fireplace on/off switch or be installed in parallel or series
Place "WARNING" label on switch cover.
configuration (see below). Caution: Label all wires prior to disconnection when
servicing controls. Wiring errors can cause improper and dangerous operation.
Note: When using a GreenSmart™ remote, use the
receiver for on/off operation (do not use a wall switch or thermostat).
Warning: Make sure all wiring is secure and does not
contact hot or moving components.
Parallel Connection Series Connection
On / Off Switch
Thermostat / External
Switch ON
Thermostat / External
Switch OFF
To wire the heater in parallel, follow the directions below: To wire the heater in series, follow the directions below:
ON
Heater is ON Heater is ON Thermostat /
Heater is ON Heater is OFF Thermostat /
On / Off Switch
OFF
On / Off Switch
External Switch ON
External Switch OFF
ON
Heater is ON Heater is OFF
Heater is OFF Heater is OFF
On / Off Switch
OFF
a
On / Off Switch
b
c
© Travis Industries 4120327 100-01290_000
Thermostat
(or External Switch) Wires
a
On / Off Switch
b
Thermostat
(or External Switch) Wires
c
Page 18
18 Installation (for qualified installers only)
Vent Requirements
The gas appliance and vent system must be vented directly to the outside of the building, and never
be attached to a chimney serving a separate solid fuel or gas-burning appliance. Each direct vent gas appliance must use its own separate vent system.
In addition to the requirements listed here, follow the requirements provided with the vent.
Vent Clearances
The vent must maintain the required clearance to combustible materials to prevent a fire. Do not fill
air spaces with insulation.
Minimum Clearance to Vent 1" (25mm)
Vent Firestop
A firestop is required whenever the vent penetrates a wall, floor, or ceiling (passes through framing
members). It may be provided by the vent manufacturer (1” clearance).
NOTE: A Wall thimble (part #58DVA-WT) is required when venting directly to the rear (no rise).
Altitude Considerations
This heater has been tested at altitudes ranging from sea level to 6,000 feet (1800 M). In this testing we have
found that the heater, with its standard orifice, burns correctly with just an air shutter adjustment.
Failure to adjust the air shutter properly may lead to improper combustion which can create a safety hazard.
Consult your dealer or installer if you suspect an improperly adjusted air shutter.
Approved Vent
Use 8" (203mm) diameter Simpson Dura-Vent Model Direct-Vent Pro (or GS)*.
* Other vent may be approved with this fireplace. Check with the vent manufacturer for details.
Always use the high-wind cap (58DVA-HC or 58DVA-VCH). The high-wind sconce cap is not
allowed.
Installation instructions for Simpson Dura-Vent may be found at www.duravent.com. May use 6-5/8” if terminated vertically.
Vent Installation
Slide the vent sections together and turn 1/4 turn until the sections lock in place.  Screws are not required to secure the vent. However, three screws may be used to secure vent
sections together if desired.
High temperature sealant is recommended at the appliance starter section connection (use high-
temperature silicone or Mill-Pac®).
If disassembly is required, at time of re-assembly check to see if the vent creates a tight fit. If it does
not, apply high temperature sealant to the joints of the affected sections.
Horizontal sections require a 1/4" (6mm) rise every 12" (305mm) of travel.  Horizontal sections require non-combustible support every three feet (e.g.: plumbing strap).
© Travis Industries 4120327 100-01290_000
Page 19
Installation (for qualified installers only) 19
Vent Location and Vent Shield Position
Make sure shield
is at 45 deg.
21-3/4" 552mm
43-1/2" 1105mm
Make sure shield
is at 90 deg.
16-3/4" 425mm
48" 1035mm
© Travis Industries 4120327 100-01290_000
Page 20
20 Installation (for qualified installers only)
Approved Vent Configurations
Restrictor Position
Intake and exhaust restrictors are built into the appliance to adjust the flow rate of intake air and
exhaust gases. Depending upon the vent configuration, you may be required to adjust the restrictor positions. The charts for acceptable vent configurations detail the correct vent restrictor positions.
Exhaust Restrictor
a
# 3
# 2
(closed) #8
#7
#6 # 5
# 4
(open - stock position) # 1
b
b
Position 3
Position 3
c
© Travis Industries 4120327 100-01290_000
Page 21
Installation (for qualified installers only) 21
Intake Restrictor
3/8" Wrench
a
(closed) # 5
# 4
# 3
# 2
(open - stock position) # 1
Position 3
b
c
© Travis Industries 4120327 100-01290_000
Page 22
22 Installation (for qualified installers only)
Termination
2
Vent Configuration: Horizontal Termination (no vertical rise)
NOTE: A Wall thimble (part #58DVA-WT) is required.  The termination must fall within the shaded area shown in the chart. Use the indicated restrictor
positions.
NOTE: When venting horizontally, use minimum vent kit “C” (96200316). If venting from a corner
installation, an additional 45° elbow is required.
Optional 45 Elbow
45 Elbow
Vent with No 45˚ Elbow
3 feet (0.915m)
0 feet
Vent with 1 45˚ Elbow
3 feet (0.915m)
0 feet
0 feet
0 feet
4’ max (1.22m)
’ max (0.61m)
Exhaust Restrictor # 1 (stock) Intake Restrictor # 1 (stock)
Min. 6" (152mm) Horizontal Section Max.48" (1219mm) Horizontal Section(s)
Exhaust Restrictor # 1 (stock) Intake Restrictor # 1 (stock)
Min. 6" (152mm) Horizontal Section Max. 24" (610mm) Horizontal Section(s)
© Travis Industries 4120327 100-01290_000
Page 23
Installation (for qualified installers only) 23
)
Vent Configuration: Horizontal Termination (with vertical rise)
The termination must fall within the shaded area shown in the chart. Use the indicated restrictor
positions.
Up to five elbows (45° or 90°) may be used.  Only one horizontal elbow may be used.
22’ max (6.7 m)
20 feet (6 m)
15 feet (4.5 m)
10 feet (3 m)
5 feet (1.5 m)
0 feet
0 feet
Exhaust Restrictor # 5 Intake Restrictor # 4
5 feet (1.5 m)
Exhaust Restrictor # 4 Intake Restrictor # 2
Exhaust Restrictor # 3 Intake Restrictor # 2
10 feet (3 m)
Exhaust Restrictor # 1 Intake Restrictor # 1
15 feet (4.5 m
20’ max (6 m)
22’ max (6.7 m)
20 feet (6 m)
15 feet (4.5 m)
10 feet (3 m)
5 feet (1.5 m)
0 feet
0 feet
This is considered a horizontal elbow (it does not matter whether it turns right or left). It may be a 90° or 45° elbow.
© Travis Industries 4120327 100-01290_000
5 feet (1.5 m)
H2
H1
10 feet (3 m)
Horizontal length is calculated by adding both lengths of horizontal run (Horizontal Length = H1 + H2).
15 feet (4.5 m)
This is considered a vertical elbow
20’ max (6 m)
Page 24
24 Installation (for qualified installers only)
Vent Configuration: Vertical Termination
The termination must fall
within the shaded area shown in the chart. Use the indicated restrictor positions.
Up to five elbows (45° or
90°) may be used.
Only one horizontal elbow
may be used.
6-5/8" (168mm) diameter
Simpson Dura-Vent Model Direct-Vent Pro (or GS)vent may be used for this configuration. Attach a 8” diameter 45° elbow to the fireplace, connect a reducer to the elbow (part #
98900165), then connect 6­5/8” vent to the reducer. Use the vertical high wind cap (46DVA-VCH).
0 feet
40’ (12m) max
35 feet (10.5m)
30 feet (9m)
25 feet (7.5m)
20 feet (6m)
5 feet (1.5m)
Exhaust Restrictor # 8 Intake Restrictor # 3
Exhaust Restrictor # 5 Intake Restrictor # 3
Exhaust Restrictor # 3 Intake Restrictor # 1
10 feet (3m)
15 feet (4.5m)
20’ (6m) max
40’ (12m) max
35 feet (10.5m)
30 feet (9m)
25 feet (7.5m)
20 feet (6m)
This is considered a horizontal elbow (it does not matter whether it turns right or left). It may be a 90° or 45° elbow.
15 feet (4.5m)
10 feet (3m)
5 feet (1.5m)
0 feet
H2
H1
Exhaust Restrictor # 1 Intake Restrictor # 1
0 feet
5 feet (1.5m)
Horizontal length is calculated by adding both lengths of horizontal run (Horizontal Length = H1 + H2).
This is considered a vertical elbow
10 feet (3m)
15 feet (4.5m)
15 feet (4.5m)
10 feet (3m)
5 feet (1.5m)
0 feet
20’ (6m) max
© Travis Industries 4120327 100-01290_000
Page 25
Installation (for qualified installers only) 25
Termination Requirements
! Venting terminals shall not be recessed into a wall or siding.
A Minimum 9" (229mm) clearance from any door or window B Minimum 12" (305mm) above any grade, veranda, porch, deck or balcony C Minimum 1" (25mm) from outside corner walls
NOTE: Clearance in accordance with local installation codes and the requirements of the gas supplier.
D Minimum 1" (25mm) from inside corner walls
NOTE: Clearance in accordance with local installation codes and the requirements of the gas supplier.
E Minimum 11" (279mm) clearance below unventilated soffits or roof surfaces
Minimum 18" (457mm) clearance below ventilated soffits Minimum 6" (152mm) clearance below roof eaves
NOTE: Vinyl surfaces require 24" (610mm) NOTE: Clearance in accordance with local installation codes and the requirements of the gas supplier.
F Minimum 12" (305mm) clearance below a veranda, porch, deck or balcony
NOTE: Permitted only if veranda, porch, deck, or balcony is fully open on a minumum of two sides beneath the floor. NOTE: Clearance in accordance with local installation codes and the requirements of the gas supplier.
G Minimum 48" (1219mm) clearance from any adjacent building H Minimum 84" (2134mm) clearance above any grade when adjacent to public walkways or driveways
NOTE: may not be used over a walkway or driveway shared by an adjacent building
I Minimum 9" (229mm) clearance to any nonmechanical air supply inlet to the building or the combustion air inlet
to any other appliance. J Minimum 36" (914mm) clearance above any mechanical air supply inlet if within 10’ (3M) horizontally K Minimum 36" (914mm) from the area above the meter/regulator (vent outlet) - this extends 15’ (4.5M) above the
regulator
NOTE: Clearance in accordance with local installation codes and the requirements of the gas supplier. L Minimum 36" (914mm) from the meter/regulator (vent outlet)
NOTE: Clearance in accordance with local installation codes and the requirements of the gas supplier. M Minimum 12” (305mm) above the roof line (for vertical terminations) N Minimum 24” (610mm) horizontal clearance to any surface (such as an exterior wall) – for vertical terminations
Roof Surface
11" Min.
(279mm)
Roof Eaves
6" Min. (152mm)
E
N
M
E
K
G
NOTE: Measure clearances to the nearest edge of the exhaust hood.
F
D
A
I
C
L
B
A
E
J
H
© Travis Industries 4120327 100-01290_000
Page 26
26 Installation (for qualified installers only)
Hearth Requirements
Do not build a hearth more than 1" (25mm) above the
Floor Mounted
Fireplaces
WARNING:
A non-combustible hearth is not required. However, if the heater is installed next to the floor, we recommend a hearth to protect the flooring surface from discoloration or other negative impact from the heater.
baseplate (this area must remain clear for the access door).
If installed near carpet or other combustible flooring, the fireplace must be raised so the base of the unit is above the carpet surface or flooring material.
Raised
Fireplaces
Fireplace Stand
© Travis Industries 4120327 100-01290_000
A hearth is not required when the fireplace is raised above the flooring surface.
Page 27
Installation (for qualified installers only) 27
Facing Requirements
The included fiber board is required and must remain attached to the fireplace (see “a” below).  Non-combustible facing must extend 7-3/4” (197mm) above the face of the fireplace (see “c” below).
Drywall or other combustible may not be place on top of this non-combustible area. Drywall (or other combustible) may be placed above the non-combustible facing (see “b” below) and
to the sides and below the fireplace face. This combustible facing must be a minimum 7-3/4”
(197mm) above the face of the fireplace (see “b” below). Tile or other non-combustible facing may be placed along the perimeter of the fireplace face, but must
not extend over the glass/grill opening (see “d”). This area must remain open to allow for glass frame
removal and air flow.
a
b
b
c
c
d
a
b
b
(a) Fiber Board (included with fireplace) (c) Tile (or other non-combustible) (b) Drywall (or other combustible) (d) Perimeter of Fireplace (may be covered)
© Travis Industries 4120327 100-01290_000
Page 28
28 Installation (for qualified installers only)
Facing and Faceplate Installation
Upgrade faces are available for this fireplace and may influence facing installation. Consult with your
Travis Dealer if you are using an upgrade face.
Tile Line Any non-combustible facing under 1" (25mm) thick (see "Thin Facing" on page 31). Masonry Line Any non-combustible over 1" (25mm) thick (see "Thick Facing" on page 33). Hearth Line Non-combustible hearth/facing should be installed up to this location (1" (25mm) above the base
of the fireplace). The fireplace may be raised to accommodate thicker hearth materials.
Masonry Line
Tile Line
Masonry Line
Tile Line
Drywall
Masonry Line
Tile Line
Tile Line
Masonry Line
Hearth Line
Tile Line
Masonry Line
Drywall
Hearth Line
Tile Line
Masonry Line
NOTE: The hearth or facing can extend no greater than 1" above the base of the fireplace. The fireplace may be raised to accommodate thicker hearth materials.
© Travis Industries 4120327 100-01290_000
Page 29
Installation (for qualified installers only) 29
Remove the outer deflector on both sides
Remove the outer deflector on both sides
Optional Faceplates – Sizing Chart
Name Height Width Notes
FPX Faces 35-3/4” (908mm) 41” (1041mm) Arch Faces have a 45-3/4” (1162mm) Radius – May fit
over top of tile facing Avalon Faces 34-1/8” (867mm) 36-7/8” (937mm) Optional facing will butt to edge of faceplate (tile line) Lopi Faces 35-3/4” (908mm) 41” (1041mm) May fit over top of tile facing Bungalow & Tree of Life Faces 34” (864mm) 36-7/8” (937mm) Optional facing will butt to edge of faceplate (tile line) Rosario Face 38” (965mm) 42” (1067mm)
Special Instructions for Metropolitan and Victorian Lace Faces
The above faces require the outer grill deflectors to be removed. See the instructions below.
(use needle-nose pliers if necessary).
These tabs bend down to allow for removal.
Re-attach the deflectors to the top louver for future use if using a different face or grill. Bend the tabs as shown, making sure the deflectors are secure and flat.
Special Instructions for Wilmington Faces
The above faces require the outer grill deflectors to be removed to allow for installation of the face mounting brackets. Once the brackets are installed, replace the deflectors. See the instructions below.
(use needle-nose pliers if necessary).
These tabs bend down to allow for removal.
Re-attach the deflectors once the mounting brackets are in place. Bend the tabs down, making sure the deflectors are secure and flat.
© Travis Industries 4120327 100-01290_000
Page 30
30 Installation (for qualified installers only)
Special Instructions for Louvered Grills / Rosario Faces
The above grill/faces require the inner grill deflectors to be removed. See the instructions below.
Remove the four inner deflectors (use needle-nose pliers if necessary).
These tabs bend down to allow for removal.
Re-attach the deflectors to the louvers for future use if using a different face or grill. Bend the tabs as shown, making sure the deflectors are secure and flat.
© Travis Industries 4120327 100-01290_000
Page 31
Installation (for qualified installers only) 31
Thin Facing Installation (tile, marble, or other non-combustible under 1" (25mm) thick)
Upgrade faces are available for this fireplace and may influence facing installation. Consult with your
Travis Dealer if you are using an upgrade face.
Tile Line
Tile Line
Facing is installed to this edge of the fireplace.
Do not install tile (or other material) in front of the glass frame, convection channel, or access panel openings. This area must remain open to access internal components and for convection air.
Hearth Line
TOP VIEW
Fireplace
Framing
Nailing Bracket
Drywall
Tile
NOTE FOR FPX FACES: FPX arched faces require the FPX Face Upgrade Kit (sku 98500686) and a triangular piece of facing in these upper corners. See the instructions included with the face for further details.
(73mm)
7-7/8" (200mm)
2-7/8"
Floor-Mounted Fireplaces or Raised Hearths: Build the hearth 1" (25mm) maximum above the base of the fireplace. The fireplace may be raised to
Raised Fireplaces: Facing is installed 1" (25mm) maximum above the base of the fireplace.
FRONT VIEW
37" 940mm
accommodate thicker hearth materials.
Tile Line
1-1/8" 29mm
34-1/4" 870mm
1" (25mm)
2" (51mm)
© Travis Industries 4120327 100-01290_000
Page 32
32 Installation (for qualified installers only)
Thin Facing Installation (tile, marble, under 1" (25mm) thick) - Side View
Raised Fireplace (with no Hearth)
Tile or other facing under 1’’ (25mm)
thick.
Face
SIDE OF FIREPLACE
Note how the facing extends 1’’ (25mm)
above the base of the fireplace.
1’’ (25mm)
Fireplace Support
Floor
Floor-Mounted Fireplace (with Hearth)
SIDE OF FIREPLACE
Tile or other facing under 1’’
(25mm) thick.
Face
Hearth: note how it extends under the face -
max. 1’’ (25mm) thick. The fireplace may be
raised to accommodate thicker hearth
materials.
Max. 1’’ (25mm)
Floor
© Travis Industries 4120327 100-01290_000
Page 33
Installation (for qualified installers only) 33
Thick Facing Installation (stone, brick, or other non-combustible over 1" (25mm) thick)
If using a Fireplace Xtrordinair (FPX) arched face, see "Thick Facing with a Fireplace Xtrordinair Arched
Faces" on page 34.
Masonry Line
Masonry Line
Do not install masonry (or other material) in front of the fireplace. This area must remain open to install the face.
Hearth Line
TOP VIEW - Protruding Masonry
Framing
Fireplace
TOP VIEW - Recessed Masonry
Fireplace
NOTE: The nailing brackets are not used for this type of installation - secure the fireplace to the floor with the brackets along the base of the fireplace.
Nailing Bracket
Drywall
Masonry
Framing
Drywall
(or cement board, etc.)
Masonry
Floor-Mounted Fireplaces or Raised Hearths: Build the hearth 1" (25mm) maximum above the
base of the fireplace. The fireplace may be Raised Fireplaces: Masonry is installed 1" (25mm) maximum above the base of the fireplace.
raised to accommodate thicker hearth materials.
FRONT VIEW
41" 1041mm
Masonry Line
35-3/4" 908mm
1"
© Travis Industries 4120327 100-01290_000
Page 34
34 Installation (for qualified installers only)
Thick Facing with Fireplace Xtrordinair (FPX) Arched Faces
The following illustration shows facing considerations for those fireplaces utilizing FPX arched faces.
The facing must be non-combustible and over 1" (25mm) in depth.
Masonry Line
The Fireplace Xtrordinair 864 Masonry Template is recommended for masonry installation (sku 98500688). The template helps locate and support the masonry as it being installed.
Hearth Line
Before installing masonry, install the FPX Face Upgrade Kit (98500686). This covers the upper corners.
TOP VIEW
Framing
Fireplace
Face
Nailing Bracket
Drywall
Masonry
Floor-Mounted Fireplaces or Raised Hearths: Build the hearth 1" (25mm) maximum above the base of the fireplace. The fireplace may be
Raised Fireplaces: Masonry is installed 1" (25mm) maximum above the base of the fireplace.
raised to accommodate thicker hearth materials.
FRONT VIEW
45-1/2" (1156mm) Radius
41" 1041mm
5" 127mm
35-3/4" 908mm
1"
© Travis Industries 4120327 100-01290_000
Page 35
Installation (for qualified installers only) 35
Thick Facing Installation - Side View
Floor-Mounted Fireplace (with Hearth)
Masonry or other non-combustible
over 1’’ (25mm) thick
SIDE OF FIREPLACE
Face
Hearth (note how it extends under the face - max. 1’’
(25mm) thick). The fireplace may be raised to
accommodate thicker hearth materials.
Max. 1’’ (25mm)
Raised Fireplace (with no Hearth)
Floor
Masonry or other non-combustible
over 1’’ (25mm) thick.
SIDE OF FIREPLACE
Face (Behind Masonry)
The masonry extends 1’’ (25mm)
above the base of the fireplace.
1’’ (25mm)
© Travis Industries 4120327 100-01290_000
Fireplace Support
Floor
Page 36
36 Installation (for qualified installers only)
Mantel Requirements
Use the table below to determine the maximum mantel depth allowed. The mantel depth (measured
from the non-combustible facing) must fall within the shaded portion of the table.
Any material above the fireplace that protrudes more than 3/4” (19mm) from the non-combustible
facing is considered a mantel and must meet the mantel requirements.
b
Maximum Mantel Depth (b)
53-3/4" (1365mm)
52-3/4" (1340mm) 51-3/4" (1314mm)
Mantel
50-3/4" (1289mm)
Height
49-3/4" (1264mm)
Above
48-3/4" (1238mm) 47-3/4" (1213mm)
Base (a)
46-3/4" (1187mm) 45-3/4" (1213mm) 44-3/4" (1213mm) 43-3/4" (1213mm)
Mantel Columns
1" (25mm)
0" (0mm)
2" (51mm)
3" (76mm)
4" (102mm)
5" (127mm)
6" (152mm)
7" (178mm)
9" (229mm)
10" (254mm)
8" (203mm)
12" (305mm)
11" (279mm)
a
Mantel Column Clearances
Combustible mantel columns (legs) that protrude more than ¾” (19mm) from the glass frame
require a 5” (127mm) clearance to the glass frame.
Combustible mantel columns (legs) that protrude ¾” (19mm) or less from the glass frame must
meet the facing clearances (minimum 2-1/4” (57mm) clearance to the side of the glass frame).
Non-combustible mantel columns do not have a minimum clearance.
© Travis Industries 4120327 100-01290_000
Mantel Column (see clearances below)
Page 37
Installation (for qualified installers only) 37
Steps for Finalizing the Installation
1. Remove the glass frame (see page 39).
NOTE: If using propane (LP) convert the appliance prior to installing the logs.
2. We recommend you purge the gas line at this time (with the glass frame removed). This allows gas to be detected once it enters the firebox, ensuring gas does not build up.
3. Make sure the two accent light bulbs are in place. NOTE: Take care to not touch the bulb with your fingers (use a cloth or paper towel).
4. Install the required firebacks (see page 41).
5. Install the burner and media (logs or stones). See the instructions included with the burner and media.
6. Replace the glass frame.
7. Install the four AA batteries (included in the owner’s pack) into battery holder (see the illustration below). The AA batteries act as a power backup in case the household (AC) power goes out. Install the 9v battery (included in the owner’s pack) into control panel light assembly (see the illustration below). The battery holder is held in place with Velcro and may be removed for easier access.
Battery Holder for Control Panel Lights
9v
Battery
Lift up and swing the lower grill down to acces the area below the firebox.
Swing the concealment cover up and slide it back to expose the controls.
AA Battery Tray
AA Battery
AA Battery
AA Battery
AA Battery
AA Battery Holder
© Travis Industries 4120327 100-01290_000
Page 38
38 Installation (for qualified installers only)
Front Burner Air Shutter Control
8. Start the heater.
9. Leak test all gas joints.
10. Check the air shutter following the directions below.
Air Shutter Adjustment
Let the heater burn for fifteen minutes (make sure the logs and glass are in place). The flames should be yellow with no sooting. Adjust the air shutter, if necessary, to achieve the correct looking flame.
Correct
Flames should be blue at the base, yellow-orange on the top.
If the flames are too tall or sooty on the ends, open the air shutter.
Not Enough Air
Too Much Air
If the flames are all blue and short, close the air shutter.
Air Shutter Adjustment
(RED)
Left = Less Air
Right = More Air
Rear Burner Air Shutter Control
(GOLD)
Left = Less Air
Right = More Air
NOTE: Use pliers to adjust the air shutters (they will be hot). Typically, the front air shutter is fully closed (left) on NG, fully open (right) on LP
11. Turn the flame adjust knob to its highest position - the flames should not contact the top of the firebox. Check the flame on low position. The flames should burn off of each burner hole. If the heater does not work correctly, contact your Travis dealer for a remedy.
12. Give this manual to the home owner for future reference and fully explain operation of this heater. For comprehensive operating and maintenance instructions, refer to the Owner's Manual (part # 100-01253).
ACID WASH WARNING: Before installing the faceplate, make sure any masonry that has been treated with acid wash has been properly neutralized (this is used primarily with brick faces). Acid wash (muriatic acid) is used to remove excess mortar. If not properly neutralized with an ammonia solution, the plated face may develop a permanent tarnish when the acid evaporates over time. Contact your dealer if uncertain your facing has been properly neutralized.
© Travis Industries 4120327 100-01290_000
Page 39
Installation (for qualified installers only) 39
Glass Frame Removal and Installation
Warning: The appliance must be completely cool before removing the glass frame. Warning: Do not strike or slam the glass frame. Warning: Do not operate appliance with the glass front removed, cracked or broken. Replacement of
the glass should be done by a licensed or qualified service person.
Based upon the face being used, either:
a
(a) swing the access door down and remove the top grill, (b) remove the face (unscrew or lift off - see the instructions included with the face for details).
Open the six latches holding the glass frame in place (start with the bottom three) - follow the directions shown to the right.
Top of Firebox
Latch
Glass
Lift the glass frame up and
b
pull it forward to remove.
NOTE: You may need to lift the glass frame while re-attaching.
Re-Attaching the Glass Frame:
a) Hang the glass frame on the firebox.
b) While holding in place, attach the upper latches (follow the instructions above in reverse).
c) Lift the glass frame slightly and attach the lower latches.
NOTE: Make sure the glass frame is all the way in place - it should be flush with the front of the fireplace when installed.
Catch (on glass frame)
© Travis Industries 4120327 100-01290_000
Page 40
40 Installation (for qualified installers only)
Hold the latch at an angle and insert it into the slot on the glass frame anchor.
d.
g
O
Glass Frame Removal and Installation (continued)
The latch can come loose from glass frame anchor. This occurs when it is turned 1/4 turn when it is disengaged. Follow the directions below to re-install the latch if it becomes loose.
Latch
Top of Firebox
Glass Frame Anchor
NOTE: this slot may be at a different angle than illustrate
Note how the washer on the latch fits behind the flange on the
lass frame anchor.
nce fully inserted, turn the latch until it is upright.
© Travis Industries 4120327 100-01290_000
Page 41
Installation (for qualified installers only) 41
Fireback Installation
WARNING:
Turn off gas to the appliance and make sure it has fully cooled prior to conducting service.
1. Remove the grate.
2. Install the firebacks following the directions below.
Remove the clips on both sides (these clips have key-
a
holes, allowing removal without removing the screw)
Place the rear fireback in place. The side
b
fireback holds the rear fireback in place ­hold the rear fireback while installing the
5/16" Nutdriver
side fireback.
Place the side firebacks
c
in place. Secure using the screws and clips removed in step "a".
d
Place the floor firebacks in place.
© Travis Industries 4120327 100-01290_000
Page 42
42 Installation (for qualified installers only)
LP Conversion Instructions
Convert the appliance prior to installing the gas line to ensure proper gas use.
1. Access the firebox.
2. Remove and discard the manifold cover (see below).
3. Follow the directions below to replace the orifices.
1/2" Wrench
Front Burner Orifice
Use a 1/2" open end wrench
a
to unscrew the two orifices.
Screw each LP orifice in so the orifice protrudes 15/16" (24mm) (indicating full insertion).
15/16" 24mm
© Travis Industries 4120327 100-01290_000
Rear Burner Orifice
c
b
Apply thread sealant to the LP orifices prior to installation. Use the chart below to identify the correct orifices.
Look here for the orifice identification
NG
LP
Front
#48
1.25mm
Rear
#39
.0625"
Page 43
Installation (for qualified installers only) 43
4. Install the new manifold cover included in the LP conversion kit (see illustration below).
5. Remove the pilot orifice following the instructions below. Replace with the propane pilot orifice.
Lift the pilot hood
a
off the pilot assembly.
Remove the orifice and replace with the LP orifice. Screw the
c
orifice all the way in and replace the pilot hood.
Orifice Identification:
LP (Propane) Orifice
Use a hex wrench to
b
unscrew the orifice.
35
35
NG (Natural Gas) Orifice
62
5/32" Hex
NOTE: when re-attaching, this pin lines up with the notch in the pilot hood.
6. Replace the burner. Push the burner to the right side to insure the manifold inserts over the orifices.
© Travis Industries 4120327 100-01290_000
Page 44
44 Installation (for qualified installers only)
8. Replace the remaining firebox components.
9. Replace the glass.
10. Remove and discard the screws (see “a” below) holding the stock regulator in place (see “b” below). Remove the stock regulator and gasket (see “c” below). Place the LP regulator in place, making sure the pre-fitted gasket (see ”c” below) is in place.
NOTE: There is a label on the base of the regulator knob indicating regulator type (NG or LP). Secure the regulator with the screws included with the regulator – tighten to 25 lb-in of torque (2.82 NM). Place the included label on the valve body where it can be easily seen to insure proper identification. NOTE: Leak test this area after the heater is installed, gas is connected, and the main burner is lit.
a
T-20 Torx or Slotted Screwdriver
b
c
d
11. Make the gas line connection, bleed the gas line (if applicable), start the heater and thoroughly leak­test all gas connections and the gas control valve.
© Travis Industries 4120327 100-01290_000
Page 45
Optional Equipment (for qualified installers only) 45
Andiron Installation
The optional andirons should be installed prior to installing the logs. See the directions below for installation.
1 Remove the grate from the
firebox. Remove and discard the two andiron prongs (see step “a” to the right). NOTE: The nuts do not need to be removed, they can be loosened to remove the prongs.
2 Attach the andiron brackets
(shipped with the fireplace) to the grate (see step “b”).
3 Attach the andirons the the
andiron brackets using the screws included with the andirons (see step “c”).
a
11/32" Nutdriver
b
5/32 Hex
Wrench
c
© Travis Industries 4120327 100-01290_000
Page 46
46 Optional Equipment (for qualified installers only)
GreenSmart™ Remote Control Installation
Packing List
 Transmitter  Receiver (with Cover Plate & Switch)  Fan Control Module  Velcro  LP or NG Stepper Motor (with screws and label - attaches to Valve)  Wire Harness  (2) Power Leads  (4) AA Batteries (inside receiver box)  (2) #8 x ½” Machine Screws  (2) Wire Ties  Torx T-20 Wrench  Wall Mount (for placing the transmitter on a wall)  (2) Drywall anchors (for wall mount)  (2) #8 x 3/8” Type B Screws
© Travis Industries 4120327 100-01290_000
Page 47
Optional Equipment (for qualified installers only) 47
Overview
The GreenSmart remote installs onto a 864 fireplace and replaces the stock wiring harness. Before installing, familiarize yourself with the stock and updated wiring diagrams (see the illustrations on this page and the following page).
Stock Wiring Diagram
120 V AC
Power In
Accent Light
Rheostat
Accent
Light (s)
Optional Blower Hookup
AC
ADAPTER
Spark Rod
Pilot Ground
Comfort Control
Valve
Pilot Sensor
CN4
CN3
PILOT SENSOR
SPARK ROD
CN2
DIGITAL
FIREPLACE
BURNER
CONTROL
GROUND
DIAGNOSTIC
VALVE COMMAND POWER
CN0
CN1
Yellow / Green
Orange
GREENSMART
© Travis Industries 4120327 100-01290_000
Green
Blue
White
CONTINUOUS
PILOT
PILOT
VALVE
IPI / CPI
Blue
Red
Red
COMFORT CONTROL
Blue
POWER SUPPLY
Black
Black
Red
Black
Red
Red
AA
BATTERY
TRAY
ON / OFF
Green
White
MAIN BURNER
Page 48
48 Optional Equipment (for qualified installers only)
GreenSmart Wiring Diagram
Caution: Label all wires prior to disconnection when servicing controls. Wiring errors can cause
improper and dangerous operation.
CN4
Comfort Control
Valve
Spark Rod
Pilot
Ground
Pilot Sensor
CN3
SPARK ROD
STEPPER MOTOR
PILOT SENSOR
CN2
DIGITAL
FIREPLACE
BURNER
CONTROL
VALVE COMMAND POWER
GROUND
BURNER CONTROL
CN0
DIAGNOSTIC
CN1
Orange
Yellow / Green
INTERMITTENT
NOTE: Some units use a jumper
in place of the thermodisk.
Thermodisk
Optional
Blower(s)
CONTINUOUS
PILOT
PILOT
Green
VALV E
IPI / CPI
Blue
White
Fan Controller
110V OUT FAN AUX OUT COM
RECEIVER
TOP
(4) AA Batteries
Remote Receiver
FAN CONTROL
POWER
120 VAC Power In
Accent
Light (s)
Accent Light
Rheostat
© Travis Industries 4120327 100-01290_000
Page 49
Optional Equipment
(for qualified installers only)
GreenSmart Installation
WARNING: Make sure power to the fireplace has been shut off prior to installation.
NOTE: Refer to the wiring diagram on page 62 while making wiring harness connections.
Special Instructions for this Fireplace
If using the Greensmart™ remote, the blower included with this fireplace should be attached to a
power lead (included with the remote) and connected to the Fan Controller (see wiring diagram on previous page). See the remote installation instructions for further details. In addition, bypass the blower rheostat following the directions below.
Bypassing the Rheostat - In
addition, you will need to bypass the rheostat (the remote controls the blower). This is done by disconnecting and discarding the electrical line that leads from the snap disk to the rheostat (carefully remove the wire tie from the wiring harness – see “a”). Attach the lead from the power input to the snap disk (see “b”).
1 Remove the concealment cove (see Figure 1).
49
2 Unscrew the four screws holding the control cover in place (see Figure 2). Carefully remove the
control cover (see Figure 3)
© Travis Industries 4120327 100-01290_000
Figure 2
Figure 1
Figure 3
Page 50
50 Optional Equipment
3 Unplug the ac adapter from the power harness (see Figure 4). You can leave the ac adapter
plugged into the wiring harness.
4 Disconnect the molex connector leading to the gas control valve (see Figure 5).
WARNING: The tabs on the gas control valve are fragile. Take care when removing the molex connector to not pull or damage the wires or tabs.
(for qualified installers only)
Figure 4
Figure 5
5 Disconnect the two leads on the back of the control panel for the IPI / CPI switch (continuous pilot
/ greensmart pilot – see Figure 6).
Figure 6
© Travis Industries 4120327 100-01290_000
Page 51
Optional Equipment
6 Disconnect the comfort control valve connection (see Figure 7). Disconnect the burner control
connector from the fireplace burner control (see Figure 8).
(for qualified installers only)
51
Figure 7
7 Unscrew the on/off/battery plate from the control panel (see Figure 9). Pull the plate and wiring
forward (see Figure 10).
Figure 9
8 The control panel has plastic wire-locks attached to the back (see Figure 11). Un-hook the wires
from the wire-locks and remove the wiring harness, plate, battery holder, and ac adapter (see Figure 12). These items may be discarded.
Figure 8
Figure 10
© Travis Industries 4120327 100-01290_000
Figure 11
Figure 12
Page 52
52 Optional Equipment
9 Use the included torx wrench to remove the stock regulator (see Figure 13). These items may be
discarded.
10 The stepper motor (adjustable regulator) has an installation sheet included with it – make sure to
follow all of the directions. Place the stepper motor on the gas control valve (see Figure 14) – MAKE SURE IT IS CORRECTLY ORIENTED. Secure using the screws included with the motor (see Figure 15) – tighten to 25 Lb-inches. Leak test this area after installation to verify proper installation.
(for qualified installers only)
Figure 13
Figure 14
11 Place the GreenSmart wiring harness in front of the fireplace, noting the position of each
connector (see .Figure 16).
© Travis Industries 4120327 100-01290_000
Figure 15
Figure 16
Page 53
Optional Equipment
12 Attach the wiring harness to the burner control (see Figure 17). Attach the gas control valve
molex connector (see Figure 18).
(for qualified installers only)
53
Figure 17
13 Attach the blue and white wires to the IPI/CPI switch (see Figure 19). Connect the wiring harness
to the stepper motor (see Figure 20).
Figure 19
14 Attach the wiring harness to the comfort control valve connection (see Figure 21).
Figure 18
Figure 20
© Travis Industries 4120327 100-01290_000
Figure 21
Page 54
54 Optional Equipment
15 Place the fan controller near the front of the fireplace to the left and connect it to the wiring
harness (see Figure 22). Attach the power cord from the fan controller to the AC connection (see Figure 23). MAKE SURE TO TURN THE FAN CONTROLLER ON (“-“ SYMBOL).
(for qualified installers only)
Figure 22
16 Disconnect the power lead from accent light and connect it to the power lead included with this kit
(see Figure 24). Attach the power lead to the fan controller in the “AUX OUT” receptacle (see Figure 25).
Figure 24
Figure 23
Figure 25
NOTE: If using the optional fan, you will want to disconnect its power lead and connect it to
the extra power lead included with this kit, then connect it to the “FAN” receptacle on
the fan controller.
© Travis Industries 4120327 100-01290_000
Page 55
Optional Equipment
17 Attach the included velcro to the bottom of the fan control module and to the base of the fireplace
near back left of the fireplace. Slide the fan controller into place and secure using the velcro (see Figure 26).
18 Pull the “RECEIVER” connector through the control panel and attach to the receiver (see Figure
27). Then attach the receiver to the control panel with the two #8 machine screws (see Figure 28).
(for qualified installers only)
55
Figure 26
Figure 27
19 Place batteries into the receiver and transmitter (see Figure 29). Calibrate the receiver to the
transmitter (see Figure 30 - use a paperclip to press the “PRG” button, let it beep, then press any button on the transmitter – the receiver should beep 5 times – see the operating instructions for further details).
Figure 29
Figure 28
Figure 30
© Travis Industries 4120327 100-01290_000
Page 56
56 Optional Equipment
20 Place the receiver coverplate (and switch) over the receiver (see Figure 31) and attach with the
two screws included with the receiver (see Figure 32)
(for qualified installers only)
Figure 31
21 Clip any excess wiring into the wire clips on the back of the control panel (see Figure 33). Use
the included wire ties, if necessary, to keep all wiring from contacting any hot or moving components. Re-attach the control panel (see Figure 34) and shroud (see Figure 1).
Figure 33
22 A wall mount is included with this kit for the remote. It may be mounted to the wall for easy
access and storage. Use the included drywall anchors (and screws) to secure it to the wall (see Figure 35).
Figure 32
Figure 34
23 Restore power to the fireplace and test operation of the remote (see the instructions included with
the remote).
© Travis Industries 4120327 100-01290_000
Figure 35
Page 57
Optional Equipment (for qualified installers only) 57
Power Heat Duct Installation
The optional power heat (98500769) duct may be used with this fireplace. Attach one or two heat ducts to the connections on top of the fireplace. Follow the directions included with the power heat duct for installation. The wiring may be routed through a snap disc on the fireplace (similar to the 864 HH).
NOTE: This fireplace has a snap disk pre-installed for the power heat duct. Attach the wiring included
with the power heat duct
The location of the power heat duct cover on the rear of the fireplace is shown below.
1. Remove the 4 screws on the power heat duct cover and remove the cover.
© Travis Industries 4120327 100-01290_000
Page 58
58 Optional Equipment (for qualified installers only)
Remove the 2 screws on the power heat duct cover plate and remove the cover.
© Travis Industries 4120327 100-01290_000
Page 59
Optional Equipment (for qualified installers only) 59
© Travis Industries 4120327 100-01290_000
Page 60
60 Index
Additional Items Required .................................. 7
Air Shutter Adjustment ..................................... 38
Altitude Considerations .................................... 18
Andiron Installation ........................................... 45
Approved Vent ................................................. 18
Approved Vent Configurations ......................... 20
Clearances ......................................................... 9
Corner Installations - Rear Vent Configuration 13
Dimensions ........................................................ 6
Electrical Connection ....................................... 16
Exhaust Restrictor ............................................ 20
Facing and Faceplate Installation .................... 28
Facing Requirements ....................................... 27
Fireback Installation ......................................... 41
Fireplace Placement Requirements ................... 9
Fuel .................................................................. 14
Gas Inlet Pressure ........................................... 14
Gas Line Connection ........................................ 14
Gas Line Location ............................................ 15
Gas Line Requirements ................................... 14
Glass Frame Removal and Installation ............ 39
GreenSmart Installation ................................... 49
GreenSmart Wiring Diagram ............................ 48
GreenSmart™ Remote Control Installation ..... 46
Hearth Requirements ....................................... 26
Heating Specifications ........................................ 6
Installation Options ............................................. 6
Intake Restrictor ............................................... 21
Listing Details ..................................................... 3
LP Conversion Instructions .............................. 42
Mantel Column Clearances ........................... 36
Mantel Requirements ....................................... 36
Massachusetts Approval .................................... 3
Massachusetts Requirements ............................ 8
Minimum Framing Dimensions – Rear Vent .... 10
Minimum Framing Dimensions – Top Vent ..... 11
Nailing Brackets ............................................... 12
National Fireplace Institute ................................ 3
Optional Faceplates – Sizing Chart ................. 29
Optional Wall Switch or Thermostat Installation
..................................................................... 17
Overview ............................................................ 3
Packing List ........................................................ 7
Power Heat Duct Installation ........................... 57
Raised Fireplaces .............................................. 9
Recommended Installation Procedure .............. 7
Restrictor Position ............................................ 20
Safety Warnings ................................................. 4
Special Instructions for Louvered Grills / Rosario
Faces ............................................................ 30
Special Instructions for Metropolitan and
Victorian Lace Faces .................................... 29
Special Instructions for Wilmington Faces ....... 29
Steps for Finalizing the Installation .................. 37
Termination Requirements .............................. 25
Thick Facing Installation .................................. 33
Thick Facing Installation - Side View ............... 35
Thick Facing with Fireplace Xtrordinair (FPX)
Arched Faces ............................................... 34
Thin Facing Installation .................................... 31
Vent Clearances .............................................. 18
Vent Configuration: Horizontal Termination (no
vertical rise) .................................................. 22
Vent Configuration: Horizontal Termination (with
vertical rise) .................................................. 23
Vent Configuration: Vertical Termination ......... 24
Vent Firestop .................................................... 18
Vent Installation ............................................... 18
Vent Location and Vent Shield Position .......... 19
Vent Requirements .......................................... 18
© Travis Industries 4120327 100-01290_000
Loading...