Built-In Direct Vent Fireplace
Natural Gas or Propane
Residential or Mobile Home
WARNING: If the information in these instructions is not followed exactly, a fire or
explosion may result causing property damage, personal injury or loss of life.
- Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or
any other appliance.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call gas supplier from a neighbor's phone. Follow the gas supplier's
instructions.
• If you cannot reach your gas supplier, call the fire department.
- Installation and service must be performed by a qualified installer, service agency or the gas
supplier.
This appliance may be installed in
an aftermarket permanently
located, manufactured home (USA
only) or mobile home, where not
prohibited by local codes.
This appliance is only for use
with the type(s) of gas indicated
on the rating plate. A conversion
kit is supplied with the appliance.
Installation Manual
Installer: After installation give this manual to the home-
owner and explain operation of this heater.
Copyright 2011, T.I. $10.00 100-01267_000 4110505
Dragon Wholesaling Pty. Ltd.
Unit 2, 16 Lexington Drive
Bella Vista NSW 2153
Australia
Page 2
2 Introduction
Overview
This manual details the installation requirements for
the 564 HO GS fireplace. For operating and
maintenance instructions, refer to the 564 HO GS
Owner's Manual.
Failure to follow all of the requirements may result in property damage, bodily injury, or even death.
This unit must be installed by a qualified installer to prevent the possibility of an explosion.
This appliance must be installed in accordance with all local codes, if any; if not, in U.S.A. follow ANSI
Z223.1 and NFPA 54(88), in Canada follow CSA B149.1.
A manufactured home (USA only) or mobile home OEM installation must conform with the
Manufactured Home Construction and Safety Standard, Title 24 CFR, Part 3280, or, when such a
standard is not applicable, the Standard for Manufactured Home Installations, ANSI/NCSBCS
A225.1, or Standard for Gas Equipped Recreational Vehicles and Mobile Housing, CSA Z240.4. This
appliance may be installed in Manufactured Housing only after the home is site located.
All exhaust gases must be vented outside the structure of the living-area. Combustion air is drawn
from outside the living-area structure. The venting must not be connected to a chimney flue serving a
separate solid-fuel burning appliance.
Notify your insurance company before hooking up this fireplace.
The room heater should be inspected before use and at least annually by a qualified service person.
More frequent cleaning may be required due to excessive lint from carpeting, bedding material, etc.
The instructions in this manual must be strictly adhered to. Do not use makeshift methods or
compromise in the installation. Improper installation will void the warranty and safety listing.
This heater is approved for use with natural gas (NG) or propane (LP). Burning the incorrect fuel will
void the warranty and safety listing and may cause an extreme safety hazard. Direct questions about
the type of fuel used to your dealer.
Contact your local building officials to obtain a permit and information on any installation restrictions
or inspection requirements in your area.
If the flame becomes sooty, dark orange in color, or extremely tall, do not operate the heater. Call
your dealer and arrange for proper servicing.
It is imperative that control compartments, screens, or circulating air passageways of the heater be
kept clean and free of obstructions. These areas provide the air necessary for safe operation.
Do not operate the heater if it is not operating properly in any fashion or if you are uncertain. Call
your dealer for a full explanation of your heater and what to expect.
Do not store or use gasoline or other flammable liquids in the vicinity of this heater.
Do not operate if any portion of the heater was submerged in water or if any corrosion occurs.
Immediately call a qualified service technician to inspect the appliance and to replace any part of the
control system and any gas control which has been under water.
Do not place clothing or other flammable items on or near the heater. Because this heate r ca n be
controlled by a thermostat there is a possibility of the heater turning on and igniting any items placed
on or near it.
Light the heater using the built-in igniter. Do not use matches or any other external device to light
your heater.
Never remove, replace, modify or substitute any part of the heater unless instructions are given in this
manual. All other work must be done by a trained technician. Don't modify or replace orifices.
The viewing glass should be opened only for conducting service.
Any safety screen or guard removed for servicing must be replaced prior to operating the heater.
Allow the heater to cool before carrying out any maintenance or cleaning.
Operate the heater according to the instructions included in this manual.
If the main burners do not start correctly turn the gas off and call your dealer for service.
This unit is not for use with solid fuel.
Do not place anything inside the firebox (except the optional artwork).
Warning: Do not operate appliance with the glass front removed, cracked or broken. Replacement
of the glass should be done by a licensed or qualified service person.
Do not throw this manual away. This manual has important operating and maintenance instructions
that you will need at a later time. Always follow the instructions in this manual.
Young children should be carefully supervised when they are in the same room as the appliance.
Toddlers, young children and others may be susceptible to accidental contact burns. A physical
barrier is recommended if there are at risk individuals in the house. To restrict access to a fireplace
or stove, install an adjustable safety gate to keep toddlers, young children and other at risk individuals
out of the room and away from hot surfaces.
Children and adults should be alerted to the hazards of high surface temperature and should stay
away to avoid burns or clothing ignition. Do not touch the hot surfaces of the heater. Educate all
children of the danger of a high-temperature heater.
Due to the high temperature, the heater should be located out of traffic and away from furniture and
draperies.
Instruct everyone in the house how to shut gas off to the appliance and at the gas main shutoff valve.
The gas main shutoff valve is usually next to the gas meter or propane tank and requires a wrench to
shut off.
Travis Industries, Inc. grants no warranty, implied or stated, for the installation or
maintenance of your heater, and assumes no responsibility of any consequential damage(s).
Frame the opening for the fireplace. Make sure to allow for vent installation.
This fireplace is designed to accommodate 1/2" (13mm) or 5/8" (16mm) drywall (see "Nailing
Brackets" on page 11 for details). Secure the fireplace to the framing.
Install the vent, gas line and electrical hook-up.
Install the drywall.
Install the hearth (if applicable).
Install the facing (if applicable).
Install the mantel (if applicable).
Finalize the installation (see page 33) and install the grill or face.
The fireplace requires a 1/2" (13mm) clearance from the angled sides of the fireplace to the framing
members. No material (insulation, framing, etc.) may be placed into this area.
Fireplace must be installed on a level surface capable of supporting the fireplace and vent
Fireplace must be placed directly on wood or non-combustible surface (not on linoleum or carpet)
This heater may be placed in a bedroom. Please be aware of the large amount of heat this appliance
produces when determining a location.
Clearances
When installed, walls in front of the fireplace must be a minimum 12" (305mm) to the side of the
fireplace.
Due to the high temperature, the heater should be located out of traffic and away from furniture and
draperies.
Fireplace must be placed so the vents below and above the glass do not become blocked.
Raised Fireplaces
The fireplace (and hearth, if desired) may be placed on a platform designed to support the fireplace
There are 4 nailing brackets
on the front of the fireplace.
Follow the directions below to
prepare the nailing brackets.
Once in place, nail or screw the
nailing brackets to the framing.
NOTE: Additional nailing
brackets are provided along
the base of the fireplace. Use
these brackets if not using
the front brackets.
WARNING:
Make sure the fireplace is
square and plumb when
placed in the framing.
Measured corner-to-corner,
the fireplace should be square
(approx. 47-1/8” / 1197mm) for
each dimension. Use shims to
ensure the fireplace is square.
1/2” (13mm) Drywall
For installations using 1/2” (13mm)
facing, fold the larger tab out
90 degrees. Use a screwdriver if
necessary.
5/8” (16mm) Drywall
For installations using 5/8” (625mm)
facing, fold the shorter tab out
90 degrees. Use a screwdriver if
necessary.
The gas line must be installed in accordance with all local codes, if any; if not, follow ANSI 223.1 and
NFPA 54(88), in Canada follow CSA B149.1 and the requirements listed below.
The fireplace and gas control valve must be disconnected from the gas supply piping during any
pressure testing of that system at test pressures in excess of 1/2 psig (3.5 kPA). For pressures under
1/2 psig (kPA), isolate the gas supply piping by closing the manual shutoff valve.
Leak test all gas line joints and the gas control valve prior to and after starting the fireplace.
Fuel
This fireplace is designed either for natural gas or for propane (but not for both). Check the sticker on the top of
the gas control valve to make sure the correct fuel is used.
Gas Line Connection
Installation must be performed by a qualified installer, service agency or the gas supplier (In Massachusetts a
licensed plumber/gasfitter).
Gas Inlet Pressure
Standard Input Pressure
If the pressure is not sufficient, make sure the piping used is large enough, the supply regulator is adequately
adjusted, and the total gas load for the residence does not exceed the amount supplied.
The supply regulator (the regulator that attaches directly to the residence inlet or to the propane tank) should
supply gas at the suggested input pressure listed above. Contact the local gas supplier if the regulator is at an
improper pressure.
The electrical line to the grounded receptacle inside the fireplace must be installed by a qualified
installer and must meet all local codes.
Make sure the household breaker is shut off prior to working on any electrical lines.
The appliance, when installed, must be electrically grounded in accordance with local codes or, in the
absence of local codes, with the National Electrical Code, ANSI/NFPA 70, or the Canadian Electrical
Code, CSA C22.1.
Plug the stove into a grounded receptacle supplying a minimum 2 amps (240 Volts). Caution: Label all wires prior to disconnection when servicing controls. Wiring errors can cause
Do not connect 120/240 VAC to the gas control valve or wiring system of this fireplace. The switch and
wiring must be installed by a qualified installer.
This fireplace includes an optio nal wall switch (with wi re) to
operate the fireplace burner without accessin g the intern al
OPTIONAL WALL SWITCH
(included with fireplace)
on/off switch. A thermostat may be used instead.
Route the wire from inside the fire place, t hrough the grommet
on either side of the fireplace ne ar the g as inlet (see at ri ght)
to the switch. The wall switch (o r thermo stat ) may byp ass the
fireplace on/off switch or be installed in parallel or series
configuration (see below).
Place "WARNING"
label on switch cover.
Caution: Label all wires prior to disconnection when
servicing controls. Wiring errors can cause
improper and dangerous operation.
Note: When using a GreenSmart™ remote, use the
receiver for on/off operation (do not use a wall
switch or thermostat).
Warning: Make sure all wiring is secure and does not
contact hot or moving components.
Parallel Connection Series Connection
On / Off Switch
Thermostat / External
Switch ON
Thermostat / External
Switch OFF
To wire the heater in parallel, follow the directions below: To wire the heater in series, follow the directions below:
The gas appliance and vent system must be vented directly to the outside of the building, and never
be attached to a chimney serving a separate solid fuel or gas-burning appliance. Each direct vent
gas appliance must use its own separate vent system.
In addition to the requirements listed here, follow the requirements provided with the vent.
The fireplace must use the Travis Thimble (sku 250-02318) whenever the vent penetrate s a wall.
Other penetrations only require a 1" (25mm) clearance and may use a standard firestop (make sure
the required 1" (25mm) clearance is met).
Vent Clearances
The vent must maintain the required clearance to combustible materials to prevent a fire. Do not fill
air spaces with insulation.
Sides 1" (25mm)
Above 4" (102mm)
Below 1" (25mm)
V ertica l T ermination
Horizontal
Required Thimble
T ermina tion
Us e a roof flashing and storm colla r
whenever pas s ing through the roof
Use a restop whenever
pas sing through a c eiling
Us e a s upport box
on expos ed vent
S ee Clearances Above
S ee Clearances Above
S ee Clearances Above
S ee Clearances Above
Altitude Considerations
This heater has been tested at altitudes ranging from sea level to 6,000 feet (1800 M). In this testing we have
found that the heater, with its standard orifice, burns correctly with just an air shutter adjustment.
Failure to adjust the air shutter properly may lead to improper combustion which can create a safety hazard.
Consult your dealer or installer if you suspect an improperly adjusted air shutter.
May use 6-5/8” (168mm) if terminated vertically.
Horizontal termination configurations use 8" (203mm) diameter Simpson Dura-Vent Model Direct -
Vent Pro (or GS)*.
* Other vent may be approved with this fireplace. Check with the vent manufacturer for details.
Vertical termination configurations use 8" (203mm) or 6-5/8" (168mm) diameter Simpson Dura-Vent
Direct-Vent Pro (or GS)*. If using 6-5/8" (168mm) diameter vent, attach the 8" (203mm) to 6-5/8"
(168mm) reducer (Travis part # 98900165) to the fireplace.
NOTE: When using 6-5/8” (168mm) diameter vent, make sure to accommodate the 4” (102mm)
clearance above the vent. Standard firestops do not include this clearance.
Always use the high-wind cap (58DVA-HC, 58DVA-VCH, or 46DVA-VCH).
Installation instructions for Simpson Dura-Vent may be found at www.duravent.com.
Other vents may be approved.
Vent Installation
Slide the vent sections together and turn 1/4 turn until the sections lock in
place.
Screws are not required to secure the vent. However, three screws may be
used to secure vent sections together if desired.
High temperature sealant is recommended at the appliance starter section
connection (use high-temperature silicone or Mill-Pac®).
If disassembly is required, at time of re-assembly check to see if the vent
creates a tight fit. If it does not, apply high temperature sealant to the joints
of the affected sections.
Horizontal sections require a 1/4" (6mm) rise every 12" (305mm) of travel
Horizontal sections require non-combustible support every three feet (e.g.: plumbing tape)
Intake and exhaust restrictors are built into the appliance to adjust the flow rate of intake air a nd
exhaust gases. Depending upon the vent configuration, you may be required to adjust the restrictor
positions. The charts for acceptable vent configurations detail the correct restrictor positions.
Exhaust Restrictor Adjustment
The exhaust restrictor is shipped in position “1”. If the restrictor is required in a different position, remove the
screws, re-position the restrictor (see “A” below), and replace the screws.
In the example “B” below, the restrictor is set in position #3.
The intake restrictor is shipped with the burner. See the burner installation instructions for details on
installing this component.
Make sure to adjust the intake restrictor to the position indicated on the vent configuration page. To
adjust the restrictor, loosen the two screws securing the restrictor to the firebox and sli de it to the correct
position as shown below.
Intake Restrictor located on rear wall of firebox
Certain vent configurations require the diffuser plate to be adjusted (refer to the approved vent
configuration charts for details). Position # 1 is stock (bent). Position # 2 is flattened.
Change the diffuser to position #2 as follows:
1. The diffuser is located above the exhaust restrictor (remove the restrictor if necessary).
2. Remove the diffuser.
3. Bend the round portion of the diffuser so it is flat (position #2).
4. Secure the flattened diffuser plate with the screws removed earlier.
5. Replace the exhaust restrictor. See “Exhaust Restrictor Adjustment” for the restrictor settings.
! Venting terminals shall not be recessed into a wall or siding.
A Minimum 9" (229mm) clearance from any door or window
B Minimum 12" (305mm) above any grade, veranda, porch, deck or balcony
C Minimum 1" (25mm) from outside corner walls
NOTE: Clearance in accordance with local installation codes and the requirements
of the gas supplier.
D Minimum 1" (25mm) from inside corner walls
NOTE: Clearance in accordance with local installation codes and the requirements
of the gas supplier.
E Minimum 11" (279mm) clearance below unventilated soffits or roof surfaces.
NOTE: Vinyl surfaces require 24" (610mm)
NOTE: Clearance in accordance with local installation codes and the requirements of the gas supplier.
F Minimum 12" (305mm) clearance below a veranda, porch, deck or balcony.
NOTE: Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.
NOTE: Clearance in accordance with local installation codes and the requirements of the gas supplier.
G Minimum 48" (1219mm) clearance from any adjacent building.
H Minimum 84" (2134mm) clearance above any grade when adjacent to public walkways or driveways.
NOTE: may not be used over a walkway or driveway shared by an adjacent building.
I Minimum 9" (229mm) clearance to any non-mechanical air supply inlet to the building or the combustion air inlet
to any other appliance.
J Minimum 36" (914mm) clearance above any mechanical air supply inlet if within 10’ (3M) horizontally.
K Minimum 36" (914mm) from the area above the meter/regulator (vent outlet) - this extends 15’ (4.5M) above the regulator
NOTE: Clearance in accordance with local installation codes and the requirements of the gas supplier.
L Minimum 36" (914mm) from the meter/regulator (vent outlet).
NOTE: Clearance in accordance with local installation codes and the requirements of the gas supplier.
M Minimum 12” (305mm) above the roof line (for vertical terminations).
N Minimum 24” (610mm) horizontal clearance to any surface (such as an exterior wall) – for vertical terminations.
Roof
Surface
11" Min.
(279mm)
Roof
Eaves
6" Min.
(152mm)
E
N
M
E
K
G
NOTE: Measure clearances to the nearest edge of the exhaust hood.
• Use the vinyl siding standoff when installing on an exterior with vinyl siding.
• Vent termination must not be located where it will become plugged by snow or other material
A non-combustible hearth is not required. However, if the
heater is installed next to the floor, we recommend a
hearth to protect the flooring surface from discoloration or
other negative impact from the heater.
baseplate (this area must
remain clear for the access
door).
If installed near carpet or other
combustible flooring, the fireplace
must be raised so the base of the
unit is above the carpet surface or
flooring material.
Raised
Fireplaces
Fireplace Stand
A hearth is not required when the
fireplace is raised above the flooring surface.
The included fiber board is required and must remain attached to the fireplace (see “a” below).
Non-combustible facing must extend 3” (77mm) above the face of the fireplace (see “c” below).
Drywall or other combustible may not be place on top of this non-combustible area.
Drywall (or other combustible) may be placed above the non-combustible facing (se e “b” below) and
to the sides and below the fireplace face. This combustible facing must be a minimum 3” (77mm)
above the face of the fireplace (see “b” below).
Tile or other non-combustible facing may be placed along the perimeter of the fireplace face, but must
not extend over the glass/grill opening (see “d”). This area must remain open to allow for glass frame
removal and air flow.
Drywall Installation
3” (77mm)
}
a
b
b
c
d
c
a
b
b
(a) Fiber Board (included with fireplace) (c) Tile (o r other non-combustible)
(b) Drywall (or other combustible) (d) Perimeter of Fireplace (may be covered)
Upgrade faces are available for this fireplace and may influence facing installation. Consult with your
Travis Dealer if you are using an upgraded face.
An optional non-combustible facing may be installed on the fireplace. Use the guidelines below to
determine the location (also see the following pages for detailed diagrams.
Tile Line Any non-combustible facing under 1" (25mm) thick (see "Thin Facing" on page 28).
Masonry Line Any non-combustible facing over 1" (25mm) thick (see "Thick Facing" on page 30).
Hearth Line Non-combustible hearth/facing should be installed up to this location (1" (25mm) above the base
of the fireplace). The fireplace may be raised to accommodate thicker hearth materials.
Masonry Line
Tile Line
Drywall
Masonry Line
Tile Line
Masonry Line
Tile Line
Tile Line
Masonry Line
Hearth Line
Tile Line
Masonry Line
NOTE: The hearth or facing can extend no
greater than 1" above the base of the fireplace.
The fireplace may be raised to accommodate
thicker hearth materials.
Thin Facing Installation (tile, marble, or other non-combustible under 1" (25mm) thick)
Upgrade faces are available for this fireplace and may influence facing installation. Consult with your
Travis dealer if you are using an upgraded face.
Tile Line
Tile Line
Attach the facing to this edge of the fireplace.
Do not install tile or other material in front
of the glass frame, convection channel,
or access panel openings. This area must
remain open to access internal components and for convection air.
Hearth Line
TOP VIEW
Framing
Fireplace
NOTE FOR FPX FACES:
FPX arched faces require the FPX Face Upgrade Kit
(sku 98500683) and a triangular piece of facing in
these upper corners. See the instructions included with
the face for details.
Nailing Bracket
Drywall
Tile
7-1/2"
191mm
1-5/8"
41mm
Floor-mounted fireplaces or raised hearths:
Build the hearth above the fireplace to a
maximum of 1” (25mm). The fireplace may
be raised to accommodate thicker hearth materials.
Raised fireplaces:
Install the facing above the fireplace
to a maximum of 1” (25mm).
Thick Facing Installation (stone, brick, or other non-combustible over 1" (25mm) thick)
If using a Fireplace Xtrordinair (FPX) arched face, see "Thick Facing with a Fireplace Xtrordinair Arched
Faces" on page 31.
Masonry Line
Masonry Line
Do not install masonry or other
material in front of the fireplace. This area
must remain open to install the face.
Hearth Line
TOP VIEW - Protruding Masonry
Framing
FireplaceNailing Bracket
Drywall
Masonry
TOP VIEW - Recessed Masonry
Framing
Fireplace
Drywall
Masonry
NOTE: The nailing brackets are not used for this type
of installation -- secure the fireplace to the floor with
the brackets along the base of the fireplace.
Masonry Line
Floor-Mounted Fireplaces or Raised Hearths:
Build the hearth 1” maximum (25mm) above the
base of the fireplace. The fireplaces may be raised
to accommodate thicker hearth materials.
Raised Fireplaces:
Masonry is installed 1” (25mm)
(maximum) above the base
of the fireplace.
Thick Facing with Fireplace Xtrordinair (FPX) Arched Faces
The following illustration shows facing considerations for those fireplaces utilizing FPX arched faces.
The facing must be non-combustible and over 1" (25mm) in depth.
Masonry Line
The Fireplace Xtrodinair 564
Masonry Template is recommended
for masonry installation (sku
98500674). The template helps
locate and support the masonry as it
is installed.
Hearth Line
Before installing the masonry,
install the FPX FaceUpgrade Kit
(98500683). This kit covers the
upper corners.
TOP VIEW
Framing
Fireplace
Face
Nailing Bracket
Masonry
Drywall
Floor-Mounted Fireplaces or Raised Hearths:
Build the hearth above the fireplace to a maximum
of 1” (25mm). The fireplace may be raised to
accommodate thicker hearth materials.
Raised Fireplaces:
Install the masonry above the base
of the fireplace to a maximum of 1” (25mm).
Use the table below to determine the maximum mantel depth allowed. The mantel depth (measured
from the face of the fireplace) must fall in the shaded portion of the table.
Any material that protrudes more than 3/4” (19mm) from the non-combustible facing is considered a
mantel and must meet the mantel requirements.
Mantel Columns
Maximum Mantel Depth (b)
49" (1245mm)
Mantel
Height
Above
Base (a)
41" (1042mm)
48”
47”
46”
45”
44”
43”
42”
40”
39”
38”
37”
36”
35”
34" (864mm)
EXAMPLE:
You may have a 4” mantel at 43”.
Combustible mantel columns (legs) that protrude more than 3/4” (19mm)
from the glass frame must meet the 12” (229mm) sidewall clearance. If they
protrude 3/4” (19mm) or less, they must meet the facing clearance, 2-1/4” (57mm)
from the glass frame -- to the side of the fireplace, not in front of it.
Non-combustible mantel columns do not have a minimum clearance.
EXAMPLES:
You may have a 4” mantel at a minimum 43” above the base of the fireplace.
9. Check the air shutter following the directions below.
Air Shutter Adjustment
Let the heater burn for fifteen minutes (make sure the logs and glass are in place). The flames should be
yellow with no sooting. Adjust the air shutter, if necessary, to achieve the correct looking flame.
Correct
Flames should be blue at the
base, yellow-orange on the top.
Air Shutter Adjustment
Rear Burner Air Shutter Control
(GOLD)
Left = Less Air
Right = More Air
Not Enough Air
If the flames are too tall or sooty on the
ends, open the air shutter.
Too Much Air
If the flames are all blue and
short, close the air shutter.
Front Burner Air Shutter Control
(RED)
Left = More Air
Right = Less Air
NOTE: You may wish to use pliers to adjust
the front air shutter. Typically, the front air
shutter is fully closed (left) on NG, and fully
open (right) on LP.
10. Turn the flame adjust knob to its highest position - the flames should not contact the top of the firebox. Check the flame
on low position. The flames should burn off of each burner hole. If the heater does not work correctly, contact your Travis
dealer for a remedy.
11. Give this manual to the home owner for future reference and fully explain operation of this heater. For comprehensive
operating and maintenance instructions, refer to the Owner's Manual.
ACID WASH WARNING: Before installing the faceplate, make sure any masonry that has been treated with acid wash has
been properly neutralized (this is used primarily with brick faces). Acid wash (muriatic acid) is used to remove e xcess mortar.
If not properly neutralized with an ammonia solution, the plated face may develop a permanent tarnish when the acid
evaporates over time. Contact your dealer if uncertain your facing has been properly neutralized.
The latch can come loose from glass frame anchor. This occurs when it is turned 1/4 turn when it is
disengaged. Follow the directions below to re-install the latch if it becomes loose.
Hold the latch at an angle and insert it into the slot on the glass frame anchor.
Latch
NOTE: this slot may be at a
different angle than illustrated.
Top of
Firebox
Glass Frame
Anchor
Note how the washer on the latch fits behind the flange on the
glass frame anchor.
Once fully inserted, turn the latch until it is upright.
This conversion kit shall be installed by a qualified service agency in accordance with the manufacturer’s
instructions and all applicable codes and requirements of the authority having jurisdiction. If the
information in these instructions is not followed exactly, a fire, explosion or production of carbon
monoxide may result causing property damage, personal injury or loss of life. The qualified service
agency is responsible for the proper installation of this kit. The installation is not proper and complete until
the operation of the converted appliance is checked as specified in the manufacturer’s instructions
supplied with the kit.
Install the LP conversion kit prior to installing the burner.