Travis Industries 564 HO GS Installation Manual

Page 1
564 HO GS
Fireplace
Listed by
AS 4553-2008
GMK10022
Built-In Direct Vent Fireplace Natural Gas or Propane
Residential or Mobile Home
WARNING: If the information in these instructions is not followed exactly, a fire or
explosion may result causing property damage, personal injury or loss of life.
- Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call gas supplier from a neighbor's phone. Follow the gas supplier's
instructions.
• If you cannot reach your gas supplier, call the fire department.
- Installation and service must be performed by a qualified installer, service agency or the gas supplier.
This appliance may be installed in an aftermarket permanently located, manufactured home (USA only) or mobile home, where not prohibited by local codes.
This appliance is only for use with the type(s) of gas indicated on the rating plate. A conversion kit is supplied with the appliance.
Installation Manual
Installer: After installation give this manual to the home-
owner and explain operation of this heater.
Copyright 2011, T.I. $10.00 100-01267_000 4110505
Dragon Wholesaling Pty. Ltd.
Unit 2, 16 Lexington Drive
Bella Vista NSW 2153
Australia
Page 2
2 Introduction
Overview
This manual details the installation requirements for the 564 HO GS fireplace. For operating and maintenance instructions, refer to the 564 HO GS Owner's Manual.
0965
N.G.
1.37
1.74
.87
2.74
3.24
2.49
L.P.
Back: DMS #44
Back: DMS #55
Front: DMS #50
Min i mum I nlet Press ure (k Pa)
N.G.
35.0
L.P.
FAN TYPE VENTE D CI RCULATO R
35.0
Minimum Clearances to Com bus t i bles
Blower Electrical Rating: 240V., 1.5 Amps, 50 Hz, 150 Watts
Input Rate on “HI” (MJ/h)
Front: 1.10 mm
Maximum Inlet Pressure (kPa)
Man i fol d Pre s sure o n “HI ” (kPa )
11.0
8.5
Orifice sizes for NG equipped appliances
Orifice sizes for LG equipped appliances
Input Rate on “LO” (MJ/h)
This appliance is equipped for installation 0-610 m. For altitudes above 600m, the vent configuration, orifice, or
Manufac tured by:Certificate Holder:
Oct.
Jul .
Apr.
Jan.
MANUFA CTURE DATE :
2011
combination of both may need to be changed. See owner’s manual for information on making these changes.
Mukilteo, WA 98275
4800 Harbour Pointe Blvd. SW
Nov.
Dec.
Aug.
Sep.
May
Jun.
www.lopi.com.au
Feb.
Mar.
2012
2013
© Travis Industries 4110505 100-01263_000
564 HO GS
Vented Gas Fireplace Heater
TM
OCEANA
Gas Mark
IAPMO-R&T
GMK10022_02
Tested to the combustion performance and construction requirements of AS 4553-2008 Gas Space Heating
Appliances. This appliance must be installed in accordance with all local codes.
This 564 appliance is equipped from the factory only for use with Natural Gas and is only for use with the
type of gas indicated on the rating plate. For conversion to LP (Propane) use a certified kit supplied by the
manufacturer. See owner’s manual for information on making these changes.
This appliance may be installed in an aftermarket, permanently located, manufactured (mobile) home where
not prohibited by local codes.
This vented gas fireplace heater is not for use with air filters. This appliance must be properly connected to
Improper installation, adjustment, alteration, service or maintenance can cause injury or
property damage. Refer to the owner’s information manual provided with this appliance. For assistance or
a venting system in accordance with the manufacturer’s installation instructions. Use only approved
coaxial direct vent syst e ms t o ven t t his appliance to the exterior. See owner’s manual for approved brands
additional information consult a qualified installer, service agency or the gas supplier.
of venting.
WARNING:
This appliance is a Vented Gas Fireplace Heater. Not for use with Solid Fuel.
Young children s hould be c arefully s upervised at all times w hen they are in t he s am e r oom
as t he appliance.
Page 3
Table of Contents 3
Overview ........................................................... 2
Installation Options .......................................... 6
Heating Specifications ..................................... 6
Dimensions ....................................................... 6
Packing List ...................................................... 6
Additional Items Required Direct Vent .......... 7
Installation Overview ....................................... 8
Recommended Installation Procedure .......... 8
Fireplace Placement Requirements ............... 9
Clearances ..................................................... 9
Raised Fireplaces ........................................... 9
Minimum Framing Dimensions ..................... 10
Nailing Brackets ............................................ 11
Corner Installations ....................................... 12
Gas Line Requirements ................................. 13
Fuel ............................................................... 13
Gas Line Connection .................................... 13
Gas Inlet Pressure ........................................ 13
Gas Line Location ......................................... 14
Electrical Connection (required) .................. 15
Optional Wall Switch or Thermostat
Installation ...................................................... 16
Parallel ConnectionSeries Connection 16
Vent Requirements ........................................ 17
Vent Clearances ........................................... 17
Altitude Considerations ................................. 17
Approved Vent .............................................. 18
Vent Installation ............................................ 18
Approved Vent Configurations ..................... 19
Restrictor Position ........................................ 19
Exhaust Restrictor Adjustment ..................... 19
Intake Restrictor Adjustment ........................ 20
Diffuser Plate Adjustment ............................. 21
Vent Configurations with Horizontal
Termination (EmberFyre Burner only) ......... 22
Vent Configurations with Vertical
Termination (EmberFyre Burner only) ......... 23
Termination Requirements ........................... 24
Hearth Requirements .................................... 25
Facing Requirements .................................... 26
Drywall Installation ....................................... 26
Facing Overview........................................... 27
Optional Faceplates – Sizing Chart.............. 27
Thin Facing Installation (tile, marble, or other
non-combustible under 1" (25mm) thick) ..... 28
Thin Facing Installation (tile, marble, under 1"
(25mm) thick) — Side View .......................... 29
Thick Facing Installation (stone, brick, or other
non-combustible over 1" (25mm) thick) ....... 30
Thick Facing with Fireplace Xtrordinair (FPX)
Arched Faces ............................................... 31
Thick Facing Installation — Side View ......... 32
Mantel Requirements .................................... 33
Combustible Mantels .................................... 33
Steps for Finalizing the Installation ............. 34
Air Shutter Adjustment ................................. 35
Glass Frame Removal and Installation ........ 36
Glass Frame Removal and Installation
(continued) ..................................................... 37
LP Conversion Instructions .......................... 38
Installation .................................................. 38
Index ............................................................. 42
© Travis Industries 4110505 100-01263_000
Page 4
4 Safety Precautions
Safety Warnings:
Failure to follow all of the requirements may result in property damage, bodily injury, or even death.  This unit must be installed by a qualified installer to prevent the possibility of an explosion.  This appliance must be installed in accordance with all local codes, if any; if not, in U.S.A. follow ANSI
Z223.1 and NFPA 54(88), in Canada follow CSA B149.1.
A manufactured home (USA only) or mobile home OEM installation must conform with the
Manufactured Home Construction and Safety Standard, Title 24 CFR, Part 3280, or, when such a standard is not applicable, the Standard for Manufactured Home Installations, ANSI/NCSBCS A225.1, or Standard for Gas Equipped Recreational Vehicles and Mobile Housing, CSA Z240.4. This appliance may be installed in Manufactured Housing only after the home is site located.
All exhaust gases must be vented outside the structure of the living-area. Combustion air is drawn
from outside the living-area structure. The venting must not be connected to a chimney flue serving a separate solid-fuel burning appliance.
Notify your insurance company before hooking up this fireplace.  The room heater should be inspected before use and at least annually by a qualified service person.
More frequent cleaning may be required due to excessive lint from carpeting, bedding material, etc.
The instructions in this manual must be strictly adhered to. Do not use makeshift methods or
compromise in the installation. Improper installation will void the warranty and safety listing.
This heater is approved for use with natural gas (NG) or propane (LP). Burning the incorrect fuel will
void the warranty and safety listing and may cause an extreme safety hazard. Direct questions about the type of fuel used to your dealer.
Contact your local building officials to obtain a permit and information on any installation restrictions
or inspection requirements in your area.
If the flame becomes sooty, dark orange in color, or extremely tall, do not operate the heater. Call
your dealer and arrange for proper servicing.
It is imperative that control compartments, screens, or circulating air passageways of the heater be
kept clean and free of obstructions. These areas provide the air necessary for safe operation.
Do not operate the heater if it is not operating properly in any fashion or if you are uncertain. Call
your dealer for a full explanation of your heater and what to expect.
Do not store or use gasoline or other flammable liquids in the vicinity of this heater.  Do not operate if any portion of the heater was submerged in water or if any corrosion occurs.
Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
Do not place clothing or other flammable items on or near the heater. Because this heate r ca n be
controlled by a thermostat there is a possibility of the heater turning on and igniting any items placed on or near it.
Light the heater using the built-in igniter. Do not use matches or any other external device to light
your heater.
Never remove, replace, modify or substitute any part of the heater unless instructions are given in this
manual. All other work must be done by a trained technician. Don't modify or replace orifices.
The viewing glass should be opened only for conducting service.  Any safety screen or guard removed for servicing must be replaced prior to operating the heater.
© Travis Industries 4110505 100-01263_000
Page 5
Safety Precautions 5
Safety Warnings (continued):
Allow the heater to cool before carrying out any maintenance or cleaning.  Operate the heater according to the instructions included in this manual.  If the main burners do not start correctly turn the gas off and call your dealer for service.  This unit is not for use with solid fuel.  Do not place anything inside the firebox (except the optional artwork).  Warning: Do not operate appliance with the glass front removed, cracked or broken. Replacement
of the glass should be done by a licensed or qualified service person.
Do not throw this manual away. This manual has important operating and maintenance instructions
that you will need at a later time. Always follow the instructions in this manual.
Young children should be carefully supervised when they are in the same room as the appliance.
Toddlers, young children and others may be susceptible to accidental contact burns. A physical barrier is recommended if there are at risk individuals in the house. To restrict access to a fireplace or stove, install an adjustable safety gate to keep toddlers, young children and other at risk individuals out of the room and away from hot surfaces.
Children and adults should be alerted to the hazards of high surface temperature and should stay
away to avoid burns or clothing ignition. Do not touch the hot surfaces of the heater. Educate all children of the danger of a high-temperature heater.
Due to the high temperature, the heater should be located out of traffic and away from furniture and
draperies.
Instruct everyone in the house how to shut gas off to the appliance and at the gas main shutoff valve.
The gas main shutoff valve is usually next to the gas meter or propane tank and requires a wrench to shut off.
Travis Industries, Inc. grants no warranty, implied or stated, for the installation or
maintenance of your heater, and assumes no responsibility of any consequential damage(s).
© Travis Industries 4110505 100-01263_000
Page 6
6 Installation (for qualified installers only) 6
Installation Options
Residential or Mobile Home  Straight or Corner Placement  Flush or Recessed Face
Raised or Floor Placement  Internal or External Chase Bedroom Approved
Heating Specifications
Approximate Heating Capacity (in square meters)* Up to 158 Up to 158 Maximum MJ Input Per Hour 35.0 35.0
* Heating capacity will vary with floor plan, insulation, and outside temperature.
Natural Gas Propane
Dimensions
b
a
31-3/4” 807mm
6-1/4” 159mm
33-1/4" 845mm
36-1/2” 928mm
18.75"
476mm
32.5" 826mm
30" 762mm
Rear
16-1/2”
426mm
36.25"
921mm
arrie're
Left
a' gauche
Right
droit
Front
avant
(a) Center Location of Vent (b) Heat Shield (must be bent vertically after fireplace is in location)
28-3/4" 730mm
1” 25mm
30-1/4" 768mm
Packing List
Propane Conversion Kit
© Travis Industries 4110505 100-01263_000
Page 7
564 HO Thimble (250-02318)
Installation
(
for qualified installers only)
Additional Items Required Direct Vent
Gas Line Equipment  Electrical Equipment
This Fireplace Requires a Burner Kit, Firebacks, Logs/Media, and Face/Grill
Burner Style EmberFyre™ Burner
96900116
Firebacks
Logs/Media Face/Grill
Requires 564 Ceramic Firebacks:
96100179 96100181 96100182 96100183 96100270 96100271
Included w Burner Use any 564 Face or Grill
7
© Travis Industries 4110505 100-01263_000
Page 8
8 Installation (for qualified installers only) 8
Installation Overview
All requirements below must be met.
See the section
See the section “Mantel Requirements”
Drywall
Drywall
Side Wall
12” min. 305mm
“Vent Requirements”
See the section “Approved Vent Configurations”
Nailing brackets
See the section “Minimum Framing Dimensions”
See “Optional Non­Combustible Facing”
See “Optional Non­Combustible Hearth”
See the section “Electrical Connection”
Recommended Installation Procedure
Frame the opening for the fireplace. Make sure to allow for vent installation.  This fireplace is designed to accommodate 1/2" (13mm) or 5/8" (16mm) drywall (see "Nailing
Brackets" on page 11 for details). Secure the fireplace to the framing.
Install the vent, gas line and electrical hook-up.  Install the drywall.  Install the hearth (if applicable).  Install the facing (if applicable).  Install the mantel (if applicable).  Finalize the installation (see page 33) and install the grill or face.
See the section “Gas Line Installation”
© Travis Industries 4110505 100-01263_000
Page 9
Installation (for qualified installers only) 9
Fireplace Placement Requirements
The fireplace requires a 1/2" (13mm) clearance from the angled sides of the fireplace to the framing
members. No material (insulation, framing, etc.) may be placed into this area.
Fireplace must be installed on a level surface capable of supporting the fireplace and vent  Fireplace must be placed directly on wood or non-combustible surface (not on linoleum or carpet)  This heater may be placed in a bedroom. Please be aware of the large amount of heat this appliance
produces when determining a location.
Clearances
When installed, walls in front of the fireplace must be a minimum 12" (305mm) to the side of the
fireplace.
Due to the high temperature, the heater should be located out of traffic and away from furniture and
draperies.
Fireplace must be placed so the vents below and above the glass do not become blocked.
Raised Fireplaces
The fireplace (and hearth, if desired) may be placed on a platform designed to support the fireplace
(155 lbs., 70Kg) and vent.
© Travis Industries 4110505 100-01263_000
Page 10
10 Installation (for qualified installers only) 10
Minimum Framing Dimensions
Minimum enclosure height = 56” (1422.4 mm)
Route the electrical line to a position to the left rear of the fireplace.
36.75”
936mm
The on/off switch/thermostat wire (if used) should be routed to a location near the left front of the fireplace.
36.5” 928mm
16.5”
419mm
WARNING: A cut-out for the gas line may be required on the framing. See the dimensions under “Gas Line Connection” for details.
© Travis Industries 4110505 100-01263_000
Page 11
Installation (for qualified installers only) 11
Nailing Brackets
There are 4 nailing brackets on the front of the fireplace. Follow the directions below to prepare the nailing brackets. Once in place, nail or screw the nailing brackets to the framing.
NOTE: Additional nailing brackets are provided along the base of the fireplace. Use these brackets if not using the front brackets.
WARNING: Make sure the fireplace is square and plumb when placed in the framing. Measured corner-to-corner, the fireplace should be square (approx. 47-1/8” / 1197mm) for each dimension. Use shims to ensure the fireplace is square.
1/2” (13mm) Drywall
For installations using 1/2” (13mm) facing, fold the larger tab out 90 degrees. Use a screwdriver if necessary.
5/8” (16mm) Drywall
For installations using 5/8” (625mm) facing, fold the shorter tab out 90 degrees. Use a screwdriver if necessary.
TOP VIEW
Fireplace
TOP VIEW
Fireplace
Framing
Nailing Bracket
Drywall
Framing
Nailing Bracket
Drywall
© Travis Industries 4110505 100-01263_000
Page 12
12 Installation (for qualified installers only) 12
Corner Installations
A typical 45° installation uses the framing dimensions shown in the illustration below (NOTE: all clearances still apply).
Minimum 1/2" (13mm)
Clearance
14-1/4"
362mm
44-1/2" Min. 1130mm
© Travis Industries 4110505 100-01263_000
Page 13
Installation (for qualified installers only) 13
Gas Line Requirements
The gas line must be installed in accordance with all local codes, if any; if not, follow ANSI 223.1 and
NFPA 54(88), in Canada follow CSA B149.1 and the requirements listed below.
The fireplace and gas control valve must be disconnected from the gas supply piping during any
pressure testing of that system at test pressures in excess of 1/2 psig (3.5 kPA). For pressures under 1/2 psig (kPA), isolate the gas supply piping by closing the manual shutoff valve.
Leak test all gas line joints and the gas control valve prior to and after starting the fireplace.
Fuel
This fireplace is designed either for natural gas or for propane (but not for both). Check the sticker on the top of
the gas control valve to make sure the correct fuel is used.
Gas Line Connection
Installation must be performed by a qualified installer, service agency or the gas supplier (In Massachusetts a
licensed plumber/gasfitter).
Gas Inlet Pressure
Standard Input Pressure
If the pressure is not sufficient, make sure the piping used is large enough, the supply regulator is adequately
adjusted, and the total gas load for the residence does not exceed the amount supplied.
The supply regulator (the regulator that attaches directly to the residence inlet or to the propane tank) should
supply gas at the suggested input pressure listed above. Contact the local gas supplier if the regulator is at an improper pressure.
Natural Gas 7" W.C. (1.74 kPA) Propane 13" W.C. (2.73 kPA)
© Travis Industries 4110505 100-01263_000
Page 14
14 Installation (for qualified installers only) 14
Gas Line Location
A 6” (152mm) flex tube and shutoff valve are included with the fireplace. The shutoff valve accepts a ½” MPT.
8-3/4” 222mm
The gas valve inlet is located 2-½” above the base of the fireplace.
Right Side Gas Inlet (preferred)
Left Side Gas Inlet
13-3/4” (349mm)
1-3/4”
(44mm)
7-3/4”
(197mm)
8-3/4" 222mm
© Travis Industries 4110505 100-01263_000
4-3/4”
(121mm)
13-3/4" 349mm
1-3/4”
(44mm)
Page 15
Installation (for qualified installers only) 15
Electrical Connection (required)
The electrical line to the grounded receptacle inside the fireplace must be installed by a qualified
installer and must meet all local codes.
Make sure the household breaker is shut off prior to working on any electrical lines.  The appliance, when installed, must be electrically grounded in accordance with local codes or, in the
absence of local codes, with the National Electrical Code, ANSI/NFPA 70, or the Canadian Electrical Code, CSA C22.1.
Plug the stove into a grounded receptacle supplying a minimum 2 amps (240 Volts). Caution: Label all wires prior to disconnection when servicing controls. Wiring errors can cause
improper and dangerous operation.
© Travis Industries 4110505 100-01263_000
Page 16
16 Installation (for qualified installers only) 16
Optional Wall Switch or Thermostat Installation
Do not connect 120/240 VAC to the gas control valve or wiring system of this fireplace. The switch and
wiring must be installed by a qualified installer.
This fireplace includes an optio nal wall switch (with wi re) to operate the fireplace burner without accessin g the intern al
OPTIONAL WALL SWITCH
(included with fireplace)
on/off switch. A thermostat may be used instead. Route the wire from inside the fire place, t hrough the grommet
on either side of the fireplace ne ar the g as inlet (see at ri ght) to the switch. The wall switch (o r thermo stat ) may byp ass the fireplace on/off switch or be installed in parallel or series configuration (see below).
Place "WARNING" label on switch cover.
Caution: Label all wires prior to disconnection when
servicing controls. Wiring errors can cause improper and dangerous operation.
Note: When using a GreenSmart™ remote, use the
receiver for on/off operation (do not use a wall switch or thermostat).
Warning: Make sure all wiring is secure and does not
contact hot or moving components.
Parallel Connection Series Connection
On / Off Switch
Thermostat / External
Switch ON
Thermostat / External
Switch OFF
To wire the heater in parallel, follow the directions below: To wire the heater in series, follow the directions below:
ON
Heater is ON Heater is ON Thermostat /
Heater is ON Heater is OFF Thermostat /
On / Off Switch
OFF
On / Off Switch
External Switch ON
External Switch OFF
ON
Heater is ON Heater is OFF
Heater is OFF Heater is OFF
On / Off Switch
OFF
a
On / Off Switch
b
c
© Travis Industries 4110505 100-01263_000
Thermostat
(or External Switch) Wires
a
On / Off Switch
b
Thermostat
(or External Switch) Wires
c
Page 17
Installation (for qualified installers only) 17
Vent Requirements
The gas appliance and vent system must be vented directly to the outside of the building, and never
be attached to a chimney serving a separate solid fuel or gas-burning appliance. Each direct vent gas appliance must use its own separate vent system.
In addition to the requirements listed here, follow the requirements provided with the vent.  The fireplace must use the Travis Thimble (sku 250-02318) whenever the vent penetrate s a wall.
Other penetrations only require a 1" (25mm) clearance and may use a standard firestop (make sure the required 1" (25mm) clearance is met).
Vent Clearances
The vent must maintain the required clearance to combustible materials to prevent a fire. Do not fill
air spaces with insulation.
Sides 1" (25mm) Above 4" (102mm) Below 1" (25mm)
V ertica l T ermination
Horizontal
Required Thimble
T ermina tion
Us e a roof flashing and storm colla r
whenever pas s ing through the roof
Use a restop whenever
pas sing through a c eiling
Us e a s upport box
on expos ed vent
S ee Clearances Above
S ee Clearances Above
S ee Clearances Above
S ee Clearances Above
Altitude Considerations
This heater has been tested at altitudes ranging from sea level to 6,000 feet (1800 M). In this testing we have
found that the heater, with its standard orifice, burns correctly with just an air shutter adjustment.
Failure to adjust the air shutter properly may lead to improper combustion which can create a safety hazard.
Consult your dealer or installer if you suspect an improperly adjusted air shutter.
© Travis Industries 4110505 100-01263_000
Page 18
18 Installation (for qualified installers only) 18
Approved Vent
May use 6-5/8” (168mm) if terminated vertically.  Horizontal termination configurations use 8" (203mm) diameter Simpson Dura-Vent Model Direct -
Vent Pro (or GS)*. * Other vent may be approved with this fireplace. Check with the vent manufacturer for details.
Vertical termination configurations use 8" (203mm) or 6-5/8" (168mm) diameter Simpson Dura-Vent
Direct-Vent Pro (or GS)*. If using 6-5/8" (168mm) diameter vent, attach the 8" (203mm) to 6-5/8" (168mm) reducer (Travis part # 98900165) to the fireplace.
NOTE: When using 6-5/8” (168mm) diameter vent, make sure to accommodate the 4” (102mm)
clearance above the vent. Standard firestops do not include this clearance.
Always use the high-wind cap (58DVA-HC, 58DVA-VCH, or 46DVA-VCH).  Installation instructions for Simpson Dura-Vent may be found at www.duravent.com. Other vents may be approved.
Vent Installation
Slide the vent sections together and turn 1/4 turn until the sections lock in
place.
Screws are not required to secure the vent. However, three screws may be
used to secure vent sections together if desired.
High temperature sealant is recommended at the appliance starter section
connection (use high-temperature silicone or Mill-Pac®).
If disassembly is required, at time of re-assembly check to see if the vent
creates a tight fit. If it does not, apply high temperature sealant to the joints of the affected sections.
Horizontal sections require a 1/4" (6mm) rise every 12" (305mm) of travel  Horizontal sections require non-combustible support every three feet (e.g.: plumbing tape)
© Travis Industries 4110505 100-01263_000
Page 19
Installation (for qualified installers only) 19
Approved Vent Configurations
Restrictor Position
Intake and exhaust restrictors are built into the appliance to adjust the flow rate of intake air a nd
exhaust gases. Depending upon the vent configuration, you may be required to adjust the restrictor positions. The charts for acceptable vent configurations detail the correct restrictor positions.
Exhaust Restrictor Adjustment
The exhaust restrictor is shipped in position “1”. If the restrictor is required in a different position, remove the screws, re-position the restrictor (see “A” below), and replace the screws.
In the example “B” below, the restrictor is set in position #3.
Firebox Roof
Back Wall of Firebox
Firebox Roof
Back Wall of Firebox
a
This example is Position # 3
b
# 1 (open - stock position)
# 2
# 3
# 4
# 5 (closed)
© Travis Industries 4110505 100-01263_000
Page 20
20 Installation (for qualified installers only) 20
Intake Restrictor Adjustment
The intake restrictor is shipped with the burner. See the burner installation instructions for details on installing this component.
Make sure to adjust the intake restrictor to the position indicated on the vent configuration page. To adjust the restrictor, loosen the two screws securing the restrictor to the firebox and sli de it to the correct position as shown below.
Intake Restrictor ­located on rear wall of firebox
Dancing/DiamondFyre Intake Restrictor:
6
4
3
2
Position #1 (open)
EmberFyre Intake Restrictor:
5
6
5
4
3
1
© Travis Industries 4110505 100-01263_000
2
1
Page 21
Installation (for qualified installers only) 21
Diffuser Plate Adjustment
Certain vent configurations require the diffuser plate to be adjusted (refer to the approved vent configuration charts for details). Position # 1 is stock (bent). Position # 2 is flattened.
Change the diffuser to position #2 as follows:
1. The diffuser is located above the exhaust restrictor (remove the restrictor if necessary).
2. Remove the diffuser.
3. Bend the round portion of the diffuser so it is flat (position #2).
4. Secure the flattened diffuser plate with the screws removed earlier.
5. Replace the exhaust restrictor. See “Exhaust Restrictor Adjustment” for the restrictor settings.
Firebox Roof
Back Wall of Firebox
1
1/4” Nutdriver
DIFFUSER SIDE VIEW
3
Before (Stock - Position #1)
2
After (Position #2)
4
© Travis Industries 4110505 100-01263_000
Page 22
22 Installation (for qualified installers only) 22
Vent Configurations with Horizontal Termination (EmberFyre Burner only)
The termination must fall within the shaded area shown in the chart. Use the indicated restrictor and
diffuser positions.
Up to four elbows (45° or 90°) may be used.  Only one horizontal elbow may be used.
NOTE: With no vertical rise, LP installations have a maximum run of 2 feet (0.6m); NG installations have a maximum run of 4 feet (1.2m).
0 feet
20 feet (6m) 20 feet (6m)
15 feet (4.5m)
10 feet (3m)
5 feet (1.5m)
0 feet
Exhaust Restrictor #4 Intake Restrictor #4 Diffuser Position #2 (OPEN)
Exhaust Restrictor #1 Intake Restrictor #1 Diffuser Position #1 (CLOSED)
2’ LP/4’ NG Maximum
5 feet (1.5m)
Exhaust Restrictor # 5
10 feet (3m)
Exhaust Restrictor #3 Intake Restrictor #3 Diffuser Position #2 (OPEN)
Exhaust Restrictor #2 Intake Restrictor #3 Diffuser Position #2 (OPEN)
15 feet (4.5m)
20' max (6m)
21' max (6.4m)21' max (6.4m)
15 feet (4.5m)
10 feet (3m)
5 feet (1.5m)
0 feet
This is considered a horizontal elbow (it does not matter whether it turns right or left). It may be a 90° or 45° elbow.
© Travis Industries 4110505 100-01263_000
0 feet
.
5 feet (1.5m)
H2
H1
10 feet (3m)
Horizontal length (max. 24’) is calculated by adding both lengths of horizontal run (Horizontal Length = H1 + H2).
15 feet (4.5m)
This is considered a vertical elbow.
20' max (6m)
Page 23
Installation (for qualified installers only) 23
Vent Configurations with Vertical Termination (EmberFyre Burner only)
The termination must fall
within the shaded area shown in the chart. Use the indicated restrictor and diffuser positions.
Up to four elbows (45° or
90°) may be used.
Only one horizontal elbow
may be used.
Horizontal length (max. 24’) is calculated by adding both lengths of horizontal run (Horizontal Length = H1 + H2).
This is considered a horizontal elbow (it does not matter whether it turns right or left). It may be a 90° or 45° elbow.
.
H2
H1
40' max (12m)
35 feet (10.5m)
30 feet (9m)
25 feet (7.5m)
20 feet (6m)
0 feet
Exhaust Restrictor #4 Intake Restrictor #5 Diffuser #2 (OPEN)
5 feet (1.5m)
Exhaust Restrictor #5 Intake Restrictor #6 Diffuser #2 (OPEN)
Exhaust Restrictor #2 Intake Restrictor #2 Diffuser #2 (OPEN)
)
10 feet (3m
Exhaust Restrictor #3 Intake Restrictor #3 Diffuser #2 (OPEN)
15 feet (4.5m)
20' max (6m)
40' max (12m)
35 feet (10.5m)
30 feet (9m)
25 feet (7.5m)
20 feet (6m)
This is considered a vertical elbow.
15 feet (4.5m)
10 feet (3m)
5 feet (1.5m)
0 feet
0 feet
Exhaust Restrictor #1 Intake Restrictor #2 Diffuser #2 (OPEN)
5 feet (1.5m)
Exhaust Restrictor #1 Intake Restrictor #1 Diffuser #1
10 feet (3m)
15 feet (4.5m)
15 feet (4.5m)
10 feet (3m)
5 feet (1.5m)
0 feet
20' max (6m)
© Travis Industries 4110505 100-01263_000
Page 24
24 Installation (for qualified installers only) 24
Termination Requirements
! Venting terminals shall not be recessed into a wall or siding.
A Minimum 9" (229mm) clearance from any door or window B Minimum 12" (305mm) above any grade, veranda, porch, deck or balcony C Minimum 1" (25mm) from outside corner walls
NOTE: Clearance in accordance with local installation codes and the requirements of the gas supplier.
D Minimum 1" (25mm) from inside corner walls
NOTE: Clearance in accordance with local installation codes and the requirements of the gas supplier.
E Minimum 11" (279mm) clearance below unventilated soffits or roof surfaces.
Minimum 18" (457mm) clearance below ventilated soffits. Minimum 6" (152mm) clearance below roof eaves.
NOTE: Vinyl surfaces require 24" (610mm) NOTE: Clearance in accordance with local installation codes and the requirements of the gas supplier.
F Minimum 12" (305mm) clearance below a veranda, porch, deck or balcony.
NOTE: Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor. NOTE: Clearance in accordance with local installation codes and the requirements of the gas supplier.
G Minimum 48" (1219mm) clearance from any adjacent building. H Minimum 84" (2134mm) clearance above any grade when adjacent to public walkways or driveways.
NOTE: may not be used over a walkway or driveway shared by an adjacent building.
I Minimum 9" (229mm) clearance to any non-mechanical air supply inlet to the building or the combustion air inlet
to any other appliance. J Minimum 36" (914mm) clearance above any mechanical air supply inlet if within 10’ (3M) horizontally. K Minimum 36" (914mm) from the area above the meter/regulator (vent outlet) - this extends 15’ (4.5M) above the regulator
NOTE: Clearance in accordance with local installation codes and the requirements of the gas supplier. L Minimum 36" (914mm) from the meter/regulator (vent outlet).
NOTE: Clearance in accordance with local installation codes and the requirements of the gas supplier. M Minimum 12” (305mm) above the roof line (for vertical terminations). N Minimum 24” (610mm) horizontal clearance to any surface (such as an exterior wall) – for vertical terminations.
Roof Surface
11" Min.
(279mm)
Roof Eaves
6" Min. (152mm)
E
N
M
E
K
G
NOTE: Measure clearances to the nearest edge of the exhaust hood.
Use the vinyl siding standoff when installing on an exterior with vinyl siding.
Vent termination must not be located where it will become plugged by snow or other material
F
D
A
I
C
L
B
A
E
J
H
© Travis Industries 4110505 100-01263_000
Page 25
Installation (for qualified installers only) 25
Hearth Requirements
Do not build a hearth more
than 1" (25mm) above the
Floor Mounted
Fireplaces
WARNING:
A non-combustible hearth is not required. However, if the heater is installed next to the floor, we recommend a hearth to protect the flooring surface from discoloration or other negative impact from the heater.
baseplate (this area must
remain clear for the access
door).
If installed near carpet or other
combustible flooring, the fireplace
must be raised so the base of the
unit is above the carpet surface or
flooring material.
Raised
Fireplaces
Fireplace Stand
A hearth is not required when the fireplace is raised above the flooring surface.
© Travis Industries 4110505 100-01263_000
Page 26
26 Installation (for qualified installers only) 26
Facing Requirements
The included fiber board is required and must remain attached to the fireplace (see “a” below).  Non-combustible facing must extend 3” (77mm) above the face of the fireplace (see “c” below).
Drywall or other combustible may not be place on top of this non-combustible area. Drywall (or other combustible) may be placed above the non-combustible facing (se e “b” below) and
to the sides and below the fireplace face. This combustible facing must be a minimum 3” (77mm)
above the face of the fireplace (see “b” below). Tile or other non-combustible facing may be placed along the perimeter of the fireplace face, but must
not extend over the glass/grill opening (see “d”). This area must remain open to allow for glass frame
removal and air flow.
Drywall Installation
3” (77mm)
}
a
b
b
c
d
c
a
b
b
(a) Fiber Board (included with fireplace) (c) Tile (o r other non-combustible) (b) Drywall (or other combustible) (d) Perimeter of Fireplace (may be covered)
© Travis Industries 4110505 100-01263_000
Page 27
Installation (for qualified installers only) 27
Facing Overview
Upgrade faces are available for this fireplace and may influence facing installation. Consult with your
Travis Dealer if you are using an upgraded face.
An optional non-combustible facing may be installed on the fireplace. Use the guidelines below to determine the location (also see the following pages for detailed diagrams.
Tile Line Any non-combustible facing under 1" (25mm) thick (see "Thin Facing" on page 28). Masonry Line Any non-combustible facing over 1" (25mm) thick (see "Thick Facing" on page 30). Hearth Line Non-combustible hearth/facing should be installed up to this location (1" (25mm) above the base
of the fireplace). The fireplace may be raised to accommodate thicker hearth materials.
Masonry Line
Tile Line
Drywall
Masonry Line
Tile Line
Masonry Line
Tile Line
Tile Line
Masonry Line
Hearth Line
Tile Line
Masonry Line
NOTE: The hearth or facing can extend no greater than 1" above the base of the fireplace. The fireplace may be raised to accommodate thicker hearth materials.
Optional Faceplates – Sizing Chart
Name Height Width Notes
FPX Artisan, Classic, Fr Ctry 29”
(737mm)
Wilmington 29”
(737mm)
Victorian Lace 27-1/2”
(699mm)
Bungalow, Tree of Life 27-1/2”
(699mm)
36” (914mm) 36” (914mm) 32-3/8” (822mm) 32-3/8” (822mm)
61” Radius – May fit over top of tile facing May fit over top of tile facing Optional facing will abut the edge of faceplate (tile
line) Optional facing will abut the edge of faceplate (tile line)
Drywall
Hearth Line
Tile Line
Masonry Line
© Travis Industries 4110505 100-01263_000
Page 28
28 Installation (for qualified installers only) 28
Thin Facing Installation (tile, marble, or other non-combustible under 1" (25mm) thick)
Upgrade faces are available for this fireplace and may influence facing installation. Consult with your
Travis dealer if you are using an upgraded face.
Tile Line
Tile Line
Attach the facing to this edge of the fireplace.
Do not install tile or other material in front of the glass frame, convection channel, or access panel openings. This area must remain open to access internal compo­nents and for convection air.
Hearth Line
TOP VIEW
Framing
Fireplace
NOTE FOR FPX FACES: FPX arched faces require the FPX Face Upgrade Kit (sku 98500683) and a triangular piece of facing in these upper corners. See the instructions included with the face for details.
Nailing Bracket
Drywall
Tile
7-1/2"
191mm
1-5/8"
41mm
Floor-mounted fireplaces or raised hearths: Build the hearth above the fireplace to a maximum of 1” (25mm). The fireplace may be raised to accommodate thicker hearth materials.
Raised fireplaces: Install the facing above the fireplace to a maximum of 1” (25mm).
FRONT VIEW
32-1/2"
826mm
Tile Line
1-7/8"
48mm
1-1/2"
38mm
27-3/4"
705mm
1”
© Travis Industries 4110505 100-01263_000
Page 29
Installation (for qualified installers only) 29
Thin Facing Installation (tile, marble, under 1" (25mm) thick) — Side View
Raised Fireplace (with no Hearth)
Tile or other facing under 1’’ (25mm) thick.
Face
SIDE OF FIREPLACE
Note how the facing extends 1’’ (25mm) above the base of the fireplace.
1’’ (25mm)
Fireplace Support
Floor
Floor-Mounted Fireplace (with Hearth)
SIDE OF FIREPLACE
Tile or other facing under 1’’ (25mm) thick.
Face
Hearth: note how it extends under the face ­max. 1’’ (25mm) thick. The fireplace may be raised to accommodate thicker hearth materials.
Max. 1’’ (25mm)
Floor
© Travis Industries 4110505 100-01263_000
Page 30
30 Installation (for qualified installers only) 30
Thick Facing Installation (stone, brick, or other non-combustible over 1" (25mm) thick)
If using a Fireplace Xtrordinair (FPX) arched face, see "Thick Facing with a Fireplace Xtrordinair Arched
Faces" on page 31.
Masonry Line
Masonry Line
Do not install masonry or other material in front of the fireplace. This area must remain open to install the face.
Hearth Line
TOP VIEW - Protruding Masonry
Framing
Fireplace Nailing Bracket
Drywall
Masonry
TOP VIEW - Recessed Masonry
Framing
Fireplace
Drywall
Masonry
NOTE: The nailing brackets are not used for this type of installation -- secure the fireplace to the floor with the brackets along the base of the fireplace.
Masonry Line
Floor-Mounted Fireplaces or Raised Hearths: Build the hearth 1” maximum (25mm) above the base of the fireplace. The fireplaces may be raised to accommodate thicker hearth materials.
Raised Fireplaces: Masonry is installed 1” (25mm) (maximum) above the base of the fireplace.
FRONT VIEW
29-1/4” 743mm
36-1/4” 921mm
1” 25mm
© Travis Industries 4110505 100-01263_000
Page 31
Installation (for qualified installers only) 31
Thick Facing with Fireplace Xtrordinair (FPX) Arched Faces
The following illustration shows facing considerations for those fireplaces utilizing FPX arched faces.
The facing must be non-combustible and over 1" (25mm) in depth.
Masonry Line
The Fireplace Xtrodinair 564 Masonry Template is recommended for masonry installation (sku
98500674). The template helps locate and support the masonry as it is installed.
Hearth Line
Before installing the masonry, install the FPX FaceUpgrade Kit (98500683). This kit covers the upper corners.
TOP VIEW
Framing
Fireplace
Face
Nailing Bracket
Masonry
Drywall
Floor-Mounted Fireplaces or Raised Hearths: Build the hearth above the fireplace to a maximum of 1” (25mm). The fireplace may be raised to accommodate thicker hearth materials.
Raised Fireplaces: Install the masonry above the base of the fireplace to a maximum of 1” (25mm).
FRONT VIEW
61” Radius (1549mm)
36-1/4” 921mm
2-3/4” 70mm
29” 737mm
1"
25mm
© Travis Industries 4110505 100-01263_000
Page 32
32 Installation (for qualified installers only) 32
Thick Facing Installation — Side View
Floor-Mounted Fireplace (with Hearth)
Masonry or other non-combustible over 1’’ (25mm) thick
SIDE OF FIREPLACE
Face
Hearth (note how it extends under the face - max. 1’’ (25mm) thick). The fireplace may be raised to accommodate thicker hearth materials.
Max. 1’’ (25mm)
Raised Fireplace (with no Hearth)
Floor
Masonry or other non-combustible over 1’’ (25mm) thick.
SIDE OF FIREPLACE
Face (Behind Masonry)
The masonry extends 1’’ (25mm) above the base of the fireplace.
1’’ (25mm)
© Travis Industries 4110505 100-01263_000
Fireplace Support
Floor
Page 33
Installation (for qualified installers only) 33
Mantel Requirements
Combustible Mantels
Use the table below to determine the maximum mantel depth allowed. The mantel depth (measured
from the face of the fireplace) must fall in the shaded portion of the table. Any material that protrudes more than 3/4” (19mm) from the non-combustible facing is considered a
mantel and must meet the mantel requirements.
Mantel Columns
Maximum Mantel Depth (b)
49" (1245mm)
Mantel
Height
Above
Base (a)
41" (1042mm)
48”
47”
46”
45”
44”
43”
42”
40”
39”
38”
37”
36”
35”
34" (864mm)
EXAMPLE: You may have a 4” mantel at 43”.
Combustible mantel columns (legs) that protrude more than 3/4” (19mm) from the glass frame must meet the 12” (229mm) sidewall clearance. If they protrude 3/4” (19mm) or less, they must meet the facing clearance, 2-1/4” (57mm) from the glass frame -- to the side of the fireplace, not in front of it.
Non-combustible mantel columns do not have a minimum clearance.
EXAMPLES:
You may have a 4” mantel at a minimum 43” above the base of the fireplace.
At 46”, the maximum mantel depth is 8”.
1" (25mm)
0" (0mm)
2" (51mm)
3" (76mm)
4" (102mm)
5" (127mm)
6" (152mm)
7" (178mm)
9" (229mm)
10" (254mm)
8" (203mm)
12" (305mm)
11" (279mm)
© Travis Industries 4110505 100-01263_000
Page 34
34 Installation (for qualified installers only) 34
Steps for Finalizing the Installation
1. Remove the glass (see page 36).
NOTE: If using propane (LP) convert the appliance prior to installing the logs.
2. We recommend you purge the gas line at this time (with the glass removed). This allows gas to be detected
once it enters the firebox, ensuring gas does not build up.
3. Make sure the two accent light bulbs are in place.
NOTE: Take care to not touch the bulb with your fingers (use a cloth or paper towel).
4. Install the four AA batteries (included in the owner’s pack) into battery holder (see the illustration below). The AA
batteries act as a power backup in case the household (AC) power goes out. Install the 9v battery (included in
the owner’s pack) into control panel light assembly (see the illustration below). The battery holder is held in
place with Velcro and may be removed for easier access.
Battery Holder for Control Panel Lights
9v
Battery
Lift up and swing the lower grill down to acces the area below the firebox.
Swing the concealment cover up and slide it back to expose the controls.
5. Install the Burner/Logs Kit (see the Burner instructions).
6. Replace the glass.
7. Start the heater.
8. Leak test all gas joints.
AA Battery Tray
AA Battery
AA Battery
AA Battery
AA Battery
AA Battery Holder
© Travis Industries 4110505 100-01263_000
Page 35
Installation (for qualified installers only) 35
9. Check the air shutter following the directions below.
Air Shutter Adjustment
Let the heater burn for fifteen minutes (make sure the logs and glass are in place). The flames should be yellow with no sooting. Adjust the air shutter, if necessary, to achieve the correct looking flame.
Correct
Flames should be blue at the base, yellow-orange on the top.
Air Shutter Adjustment
Rear Burner Air Shutter Control
(GOLD)
Left = Less Air
Right = More Air
Not Enough Air
If the flames are too tall or sooty on the ends, open the air shutter.
Too Much Air
If the flames are all blue and short, close the air shutter.
Front Burner Air Shutter Control
(RED)
Left = More Air
Right = Less Air
NOTE: You may wish to use pliers to adjust the front air shutter. Typically, the front air shutter is fully closed (left) on NG, and fully open (right) on LP.
10. Turn the flame adjust knob to its highest position - the flames should not contact the top of the firebox. Check the flame
on low position. The flames should burn off of each burner hole. If the heater does not work correctly, contact your Travis
dealer for a remedy.
11. Give this manual to the home owner for future reference and fully explain operation of this heater. For comprehensive
operating and maintenance instructions, refer to the Owner's Manual. ACID WASH WARNING: Before installing the faceplate, make sure any masonry that has been treated with acid wash has
been properly neutralized (this is used primarily with brick faces). Acid wash (muriatic acid) is used to remove e xcess mortar. If not properly neutralized with an ammonia solution, the plated face may develop a permanent tarnish when the acid evaporates over time. Contact your dealer if uncertain your facing has been properly neutralized.
© Travis Industries 4110505 100-01263_000
Page 36
36 Installation (for qualified installers only) 36
Glass Frame Removal and Installation
Warning: The appliance must be completely cool before removing the glass. Warning: Do not strike or slam the glass.
Depending on the face being used, either:
a
1) Swing the access door down and remove the top grill, or
2) Remove the face by unscrewing it or lifting it off -- see the instructions included with the face for details.
Open the 4 latches holding the glass frame in place, starting with the bottom. Follow the instructions shown to the right.
Latch
Top of Firebox
Glass
Lift the glass frame up and
b
pull it forward to remove.
NOTE:
You may need to lift the glass frame while re-attaching.
Re-Attaching the Glass Frame:
1) Hang the glass frame on the firebox.
2) While holding the frame in place, attach the upper latches (follow the instructions to the right in reverse).
3) Lift the glass frame slightly and attach the lower latches.
NOTE: Make sure the glass frame is fully in place -- it should be flush with the front of the fireplace when installed correctly.
Catch on glass frame
© Travis Industries 4110505 100-01263_000
Page 37
Installation (for qualified installers only) 37
Glass Frame Removal and Installation (continued)
The latch can come loose from glass frame anchor. This occurs when it is turned 1/4 turn when it is disengaged. Follow the directions below to re-install the latch if it becomes loose.
Hold the latch at an angle and insert it into the slot on the glass frame anchor.
Latch
NOTE: this slot may be at a different angle than illustrated.
Top of Firebox
Glass Frame Anchor
Note how the washer on the latch fits behind the flange on the glass frame anchor.
Once fully inserted, turn the latch until it is upright.
© Travis Industries 4110505 100-01263_000
Page 38
38 Optional Equipment (for qualified installers only) 38
LP Conversion Instructions
WARNING
This conversion kit shall be installed by a qualified service agency in accordance with the manufacturer’s instructions and all applicable codes and requirements of the authority having jurisdiction. If the information in these instructions is not followed exactly, a fire, explosion or production of carbon monoxide may result causing property damage, personal injury or loss of life. The qualified service agency is responsible for the proper installation of this kit. The installation is not proper and complete until the operation of the converted appliance is checked as specified in the manufacturer’s instructions supplied with the kit.
Install the LP conversion kit prior to installing the burner.
Remove the glass (see page 33).
Installation
1. Remove the burner bracket as shown below.
© Travis Industries 4110505 100-01263_000
Page 39
Optional Equipment (for qualified installers only) 39
2. Replace the orifices as shown below.
Rear Burner Orifice
Front Burner Orifice
1/2" Wrench
a
Orifice ID
b
Thread Sealant
c
15/16" 24mm
Orifice Front Rear
NG #50 #44
LP 1.1mm #55
3. Install the LP burner bracket and manifold seal plate as shown below. These components are
shipped with the fireplace.
© Travis Industries 4110505 100-01263_000
Page 40
40 Optional Equipment (for qualified installers only) 40
4. Remove the pilot orifice following the instructions below. Replace with the propane pilot orifice.
Lift the pilot hood
a
off the pilot assembly.
Figure1:PilotOrificeRemoval
Use a hex wrench to
b
unscrew the orifice.
5/32" Hex
Remove the orifice and replace with the LP orifice. Screw the
c
orifice all the way in and replace the pilot hood.
Orifice Identification:
35
NOTE: when re-attaching, this pin lines up with the notch in the pilot hood.
LP (Propane) Orifice
35
NG (Natural Gas) Orifice
62
5. Remove and discard the screws (see “a” below) holding the stock regulator in place (see “b” below).
Remove the stock regulator and gasket (see “c” below). Place the LP regulator in place, making sure
the pre-fitted gasket (see “c” below) is in place.
NOTE: There is a label on the base of the regulator knob indicating regulator type (NG or LP).
Secure the regulator with the screws included with the regulator – tighten to 25 lb.-in of torque (2.82
NM). Place the included label on the valve body where it can be easily seen to insure proper
identification.
NOTE: Leak test this area after the heater is installed, gas is connected, and the main burner is lit.
a
T-20 Torx or Slotted Screwdriver
b
c
d
Figure2:LPRegulatorPlacement
6. Install the burner (see the instructions included with the burner). Replace the glass and restore
the fireplace to the correct configuration.
© Travis Industries 4110505 100-01263_000
Page 41
Optional Equipment (for qualified installers only) 41
© Travis Industries 4110505 100-01263_000
Page 42
42 Index
Index
Additional Items Required .................................... 7
Air Shutter Adjustment ......................................... 35
Altitude Considerations ........................................ 17
Approved Vent Configurations ............................. 19
Approved Vent ..................................................... 18
Clearances ........................................................... 9
Corner Installations ............................................. 12
Diffuser Plate Adjustment ..................................... 21
Dimensions .......................................................... 6
Electrical Connection (required) ........................... 15
Exhaust Restrictor Adjustment ............................. 19
Facing Overview .................................................. 27
Facing Requirements ........................................... 26
Features ............................................................... 6
Fireplace Placement Requirements ..................... 9
Fuel ...................................................................... 13
Gas Inlet Pressure ............................................... 13
Gas Line Connection ............................................ 13
Gas Line Location ................................................ 13
Gas Line Requirements ....................................... 13
Glass Frame Removal and Installation ................ 36
Hearth Requirements ........................................... 25
Heating Specifications .......................................... 6
Index ..................................................................... 42
Installation Options ............................................... 6
Intake Restrictor Adjustment ................................ 20
Mantel Requirements ........................................... 33
Minimum Framing Dimensions ............................................ 10
Nailing Brackets ................................................... 11
Overview .............................................................. 2
Packing List .......................................................... 6
Raised Fireplaces ................................................ 9
Recommended Installation Procedure ................ 8
Restrictor Position ................................................ 19
Safety Precautions ............................................... 4
Thick Facing Installation with FPX Arched Face s 31
Thick Facing Installation ...................................... 30
Thin Facing Installation ........................................ 28
Vent Configurations with Horizontal Termination 22
Vent Configurations with Vertical Termination ..... 23
Vent Clearances .................................................. 17
Vent Installation ................................................... 18
Vent Requirements .............................................. 17
Optional Wall Switch or Thermostat Installation .. 16
© Travis Industries 4110505 100-01263_000
Loading...