Travis Industries 21 TRV Installation Manual

Page 1
21 TR V
Fireplace
Tested and Listed by
OMNI-Test Laboratories, Inc.
Portland, Oregon
Report # 028-F-85-5
ANSI Z21.88a-2007 / CSA 2.33a-2007
Built-In Direct Vent Fireplace
Residential or Mobile Home
WARNING: If the information in these instructions is not followed exactly, a fire
or explosion may result causing property damage, personal injury or loss of life.
- Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call gas supplier from a neighbor's phone. Follow the gas
supplier's instructions.
• If you cannot reach your gas supplier, call the fire department.
- Insta lla tion and service must be pe rforme d by a qua lified installe r, service age ncy or the ga s supplier.
This appliance may be installed in an aftermarket permanently located, manufactured home (USA only) or mobile home, where not prohibited by local codes.
This appliance is only for use with the type(s) of gas indicated on the rating plate. A conversion kit is supplied with the appliance.
Installation Manual
Installer: After installation give this manual to the home-
owner and explain operation of this heater.
Copyright 2008, T.I. $10.00 100-01185_000 4080207
4800 Harbour Pointe Blvd. SW
Mukilteo, WA 98275
Page 2
2 Introduction
Overview
This manual details the installation requirements for the 21 TRV fireplace. For operating and maintenance instructions, refer to the 21 TRV Owner's Manual (part # 100-01186).
Listing Details
This appliance was listed by OMNI Test Labs to ANSI Z21.88a-2007/CSA 2.33a-2007 - report # 028-F-85-5 – for US and Canadian installations. The listing label is attached to the appliance near the gas control valve. A copy is shown to the right.
ICBO Approval
This appliance was listed by OMNI Test Labs - ICBO # TL130.
Massachusetts Approval
This manual has been submitted to the Massachusetts Board of State Examiners of Plumbers and Gas Fitters
National Fireplace Institute
© Travis Industries 4080207 100-01185_000
Page 3
Table of Contents 3
Introduction
Overview................................................................. 2
Listing Details ..........................................................2
Safety Precautions
Safety Precautions ................................................... 4
Features and Specifications
Features ................................................................. 6
Installation Options ................................................... 6
Heating Specifications ...............................................6
Dimensions.............................................................. 6
Installation
Packing List............................................................. 7
Additional Items Required........................................... 7
Recommended Installation Procedure............................... 7
Installation Overview .................................................8
Massachusetts Requirements.................................. 10
Converting the Fireplace to Rear Vent Configuration .....11
Fireplace Placement Requirements......................... 14
Clearances...........................................................14
Raised Fireplaces ..................................................14
Min. Framing Dims. - Rear Vent Configuration......................15
Min. Framing Dims. - Top Vent Configuration................16
Nailing Brackets ....................................................17
Corner Installations - Top Vent Configuration...............18
Corner Installations - Rear Vent Configuration..............18
Gas Line Requirements.............................................. 19
Fuel.....................................................................19
Gas Line Connection ..............................................19
Gas Inlet Pressure .................................................19
Gas Line Location..................................................19
Electrical Connection (required)................................... 21
Wall Switch or Thermostat Installation........................... 22
Wiring Diagram (Millivolt System)...............................22
Installation...........................................................22
Vent Requirements.................................................... 23
Vent Clearances....................................................23
Altitude Considerations ...........................................23
Approved Vent ......................................................24
Vent Installation ....................................................24
Approved Vent Configurations..................................... 25
Restrictor and Diffuser Position ................................25
Exhaust Restrictor Adjustment .................................25
Diffuser Plate Adjustment ........................................26
Top Vent Config. W Horizontal Termination..................... 27
Top Vent Config. W Vertical Termination ........................28
Rear Vent Configuration with Horizontal Termination......... 29
Rear Vent Configuration with Vertical Termination............ 30
Termination Requirements ..........................................31
Installation (continued)
Hearth Requirements................................................. 32
Facing Requirements................................................. 33
Face Dimensions..................................................33
Facing Under 1” Thick............................................33
Facing Over 1” Thick ............................................. 33
Facing – Fireplace Overview ...................................... 34
Facing Detail – Drywall Facing ................................... 35
Facing Detail – Tile Facing ........................................ 36
Facing Detail – Facing Over 1” Thick (Brick).................37
Mantel Requirements................................................. 38
Finalizing the Installation
Steps for Finalizing the Installation............................... 39
Starting the Pilot Flame........................................... 39
Pilot Flame Inspection ............................................39
Air Shutter Adjustment............................................ 40
Glass Frame Removal and Installation .......................... 41
Log Set Installation ................................................... 43
Finalizing the Installation
LP Conversion Instructions ........................................ 46
Aromatherapy Modification ........................................ 49
Omega Remote Notes.............................................. 50
Index
Index..................................................................... 52
© Travis Industries 4080207 100-01185_000
Page 4
4 Safety Precautions
Safety Warnings:
Failure to follow all of the requirements may result in property damage, bodily injury, or even death.
This unit must be installed by a qualified installer to prevent the possibility of an explosion.
This appliance must be installed in accordance with all local codes, if any; if not, in U.S.A. follow ANSI
Z223.1 and NFPA 54(88).
A manufactured home (USA only) or mobile home OEM installation must conform with the Manufactured Home Construction and Safety Standard, Title 24 CFR, Part 3280, or, when such a standard is not applicable, the Standard for Manufactured Home Installations, ANSI/NCSBCS A225.1, or Standard for Gas Equipped Recational Vehicles and Mobile Housing, CSA Z240.4. This appliance may be installed in Manufactured Housing only after the home is site located.
All exhaust gases must be vented outside the structure of the living-area. Combustion air is drawn from outside the living-area structure. The venting must not be connected to a chimney flue serving a separate solid-fuel burning appliance.
Notify your insurance company before hooking up this fireplace.
The room heater should be inspected before use and at least annually by a qualified service person.
More frequent cleaning may be required due to excessive lint from carpeting, bedding material, etc.
The instructions in this manual must be strictly adhered to. Do not use makeshift methods or compromise in the installation. Improper installation will void the warranty and safety listing.
This heater is approved for use with natural gas (NG) or propane (LP). Burning the incorrect fuel will void the warranty and safety listing and may cause an extreme safety hazard. Direct questions about the type of fuel used to your dealer. Check the label and flame adjust knob on the gas control valve.
Contact your local building officials to obtain a permit and information on any installation restrictions or inspection requirements in your area.
If the flame becomes sooty, dark orange in color, or extremely tall, do not operate the heater. Call your dealer and arrange for proper servicing.
It is imperative that control compartments, screens, or circulating air passageways of the heater be kept clean and free of obstructions. These areas provide the air necessary for safe operation.
Do not operate the heater if it is not operating properly in any fashion or if you are uncertain. Call your dealer for a full explanation of your heater and what to expect.
Do not store or use gasoline or other flammable liquids in the vicinity of this heater.
Do not operate if any portion of the heater was submerged in water or if any corrosion occurs.
Do not place clothing or other flammable items on or near the heater. Because this heater can be
controlled by a thermostat there is a possibility of the heater turning on and igniting any items placed on or near it.
Light the heater using the built-in piezo igniter. Do not use matches or any other external device to light your heater.
Never remove, replace, modify or substitute any part of the heater unless instructions are given in this manual. All other work must be done by a trained technician. Don't modify or replace orifices.
The viewing glass should be opened only for lighting the pilot or conducting service.
Any safety screen or guard removed for servicing must be replaced prior to operating the heater.
© Travis Industries 4080207 100-01185_000
Page 5
Safety Precautions 5
Safety Warnings (continued):
Allow the heater to cool before carrying out any maintenance or cleaning.
Operate the heater according to the instructions included in this manual.
If the main burners do not start correctly turn the gas off at the gas control valve and call your dealer for
service.
The pilot flame must contact the thermopile and thermocouple. If it does not, turn the gas control valve to "OFF" and call your dealer.
This unit is not for use with solid fuel.
Do not place anything inside the firebox (except the included fiber logs).
If the fiber logs become damaged, replace with Travis Industries log set.
Do not throw this manual away. This manual has important operating and maintenance instructions
that you will need at a later time. Always follow the instructions in this manual.
Do not touch the hot surfaces of the heater. Educate all children of the danger of a high-temperature heater. Young children should be supervised when they are in the same room as the heater.
Due to the high temperature, the heater should be located out of traffic and away from furniture and draperies.
Instruct everyone in the house how to shut gas off to the appliance and at the gas main shutoff valve. The gas main shutoff valve is usually next to the gas meter or propane tank and requires a wrench to shut off.
Travis Industries, Inc. grants no warranty, implied or stated, for the installation or maintenance of your heater, and assumes no responsibility of any consequential damage(s).
© Travis Industries 4080207 100-01185_000
Page 6
6 Features and Specifications
Installation Options
Residential or Mobile Home
Straight or Corner Placement
Flush or Recessed Face
Heating Specifications
Approximate Heating Capacity (in square feet)* Up to 650 Up to 650 Maximum BTU Input Per Hour 16,500 16,500
* Heating capacity will vary with floor plan, insulation, and outside temperature.
Dimensions
Top Vent Configuration
35-7/8
NOTE: 1/2” clearance is required to the angled sides and rear of the fireplace.
Raised or Floor Placement
Internal or External Chase
Horizontal or Vertical Vent
Bedroom Approved
Natural Gas Propane
Rear Vent Configuration
8-1/2
4-7/8
4
8 External Diameter
Lifting Bracket (may
be bent down)
Nailing Brackets
See Gas Line
Requirements” for
Details on the Gas Inlet
13-1/2
45°
7-1/4
20-1/8
34-1/8
27-1/4
Front of
Fireplace
12-3/4
14
© Travis Industries 4080207 100-01185_000
Page 7
Installation (for qualified installers only) 7
Packing List
• Propane Conversion Kit
Log Set
• Rear Vent Configuration Kit (insulation)
• Firestop
Additional Items Required
Direct Vent
Gas Line Equipment (shutoff valve, pipe, etc.)
Electrical Equipment (min. 14 gauge, grounded line)
Face
Recommended Installation Procedure
1 Install the optional equipment (do not install the logs) – we recommend the following order:
a) LP Conversion (if applicable) – NOTE: leave the burner removed until after the liner and
accent light are installed (if applicable). If using the Omega remote, install the modulating
regulator during LP conversion. b) Liner (if applicable) c) Accent Light (if applicable)
NOTE: Do not install the accent light wiring harness or rheostat if using the omega remote.
NOTE: Leave the control cover removed if using the blower d) Blower
NOTE: Do not install the rheostat if using the omega remote. e) Remote
2 Frame the opening for the fireplace. Make sure to allow for vent installation. 3 This fireplace is designed to accommodate 1/2" drywall or 1/2 drywall with 3/8 tile (see "Nailing
Brackets" on page 17 for details). Secure the fireplace to the framing.
NOTE: If the facing is not 1/2" or 7/8" thick, follow the directions below: Place a strip of facing material to both sides of the fireplace opening (NOTE: the strips will
be removed after the fireplace is secured). The facing thickness must represent the total thickness of the finished facing (e.g.: If tile is to be used, include the thickness of the backboard, tile, and tile adhesive). Insert the fireplace into the framing. Slide it back until the front edge of the fireplace is flush with the facing material. Secure the fireplace using the plates located along the base of the fireplace.
4 Complete the gas line installation. Complete the electrical hook-up.
5 Complete the vent installation.
6 Install the hearth (if applicable).
7 Install the drywall and facing (if applicable).
8 Install the mantel (if applicable).
9 Finalize the installation (see page 39) and install the grill or face.
© Travis Industries 4080207 100-01185_000
Page 8
8 Installation (for qualified installers only)
Installation Overview – Top Vent Configuration
All requirements below must be met.
See the section
"Termination
Requirements"
See the section "Vent Requirements"
See the section "Minimum Framing Dimensions"
See the section "Mantel Requirements"
Gas Line (left side or beneath)
See the section "Hearth Requirements"
Drywall
1" Min. Clearance from Face to Side Wall
See the section "Electrical Connection"
Insulation or drywall must not fill the 1/2" gap around
the sides of the fireplace.
© Travis Industries 4080207 100-01185_000
Page 9
Installation (for qualified installers only) 9
Installation Overview – Rear Vent Configuration
All requirements below must be met.
See the section "Minimum Framing Dimensions"
See the section "Vent Requirements"
See the section
"Termination Requirements"
See the section "Acceptable
Vent Lengths"
See the section "Mantel Requirements"
Drywall
1" Min. (from face)
See the section "Gas Line Installation"
See the section "Electrical
Connection"
See the section "Hearth Requirements"
© Travis Industries 4080207 100-01185_000
Page 10
10 Installation (for qualified installers only)
Massachusetts Requirements
NOTE: The following requirements reference various Massachusetts and national codes not contained in this document.
Requirements for the Commonwealth of Massachusetts
For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:
Installation of Carbon Monoxide Detectors
At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors.
In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.
In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.
Approved Carbon Monoxide Detectors
Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
Signage
A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS”.
Inspection
The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4.
Exemptions
The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:
The equipment listed in Chapter 10 entitled Equipment Not Required To Be Vented in the most current edition of NFPA 54 as adopted by the Board; and
Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.
MANUFACTURER REQUIREMENTS
Gas Equipment Venting System Provided
When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
Detailed instructions for the installation of the venting system design or the venting system components; and
A complete parts list for the venting system design or venting system.
Gas Equipment Venting System NOT Provided
When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies special venting systems, the following requirements shall be satisfied by the manufacturer:
The referenced special venting system instructions shall be included with the appliance or equipment installation instructions; and
The special venting systems shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions.
A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.
See Gas Connection section for additional Commonwealth of Massachusetts requirements.
© Travis Industries 4080207 100-01185_000
Page 11
Installation (for qualified installers only) 11
Top Vent or Rear Vent Configuration
This appliance is shipped in the top vent configuration. To change to the rear vent configuration, follow the directions below.
NOTE : top or rear vent configuration affects several aspects of installation (framing, maximum vent rise, maximum vent run). Make sure the vent configuration is correct prior to installation.
HINT : the diffuser is easiest to modify when converting the vent to rear-vent configuration. Refer to the vent configuration charts to determine if the vent diffuser requires adjustment to position # 2.
Converting the Fireplace to Rear Vent Configuration
Remove the outer flue assembly. Place the screws and components aside (for all subsequent steps).
Remove the cover plate, and heat shield.
NOTE: Use a magnetic-tipped nutdriver on these screws - take care to prevent the screws from falling into the fireplace.
Cover Plate
Heat Shield
Remove the inner flue assembly and exhaust cover plate.
© Travis Industries 4080207 100-01185_000
Inner Flue Assembly
Exhaust Cover Plate
Page 12
12 Installation (for qualified installers only)
Converting the Fireplace to Rear Vent (continued)
Insert the small piece of insulation into the exhaust duct. Tuck it into the cavity so it lays flat.
Attach the exhaust cover plate, making sure the attached gasket seals the exhaust duct.
Insert the large piece of insulation into the intake duct. Note how the wider portion goes to the sides. Tuck it into the cavity so it lays flat.
Remove the flue collar suport, rotate it 180°, and re-attach it to the fireplace.
© Travis Industries 4080207 100-01185_000
Page 13
Installation (for qualified installers only) 13
Converting the Fireplace to Rear Vent (continued)
Attach the cover plate to the top of the fireplace.
NOTE: You will need to tuck the front edge of the cover plate under the upper standoff.
Flatten the exhaust restrictor following the steps shown below.
Bend the heat shield as shown to the right.
Remove the 4 screws on the angled top of the fireplace and attach the heat shield with these screws.
Attach the inner flue assembly with four screws (make sure the gasket is in place while attaching).
NOTE: Install the flue assembly with the diffuser to the bottom.
Attach the outer flue assembly with four screws (make sure the gasket is in place while attaching).
© Travis Industries 4080207 100-01185_000
Page 14
14 Installation (for qualified installers only)
Fireplace Placement Requirements
The fireplace requires a 1/2" clearance from the angled sides and back of the fireplace to the framing members. No material (insulation, framing, etc.) may be placed into this area. The stand-offs (and
nailing brackets) may contact the framing members but no material may be placed into this area.
Fireplace must be installed on a level surface capable of supporting the fireplace and vent.
Fireplace must be placed directly on wood or non-combustible surface (not on linoleum or carpet).
This heater may be placed in a bedroom.
Clearances
Walls in front of the fireplace must be a minimum 1" to the side of the face.
Due to the high temperature, the heater should be located out of traffic and away from furniture and
draperies.
Fireplace must be placed so the vents below and above the glass do not become blocked.
Raised Fireplaces
NOTE: Looking Glass and Wilmington Faces require a raised fireplace - see "Dimensions" for
details.
The fireplace (and hearth, if desired) may be placed on a platform designed to support the fireplace (95 Lbs.) and vent.
Minimum
57"
Optional Hearth
Ceiling
Min. Enclosure Height Top Vent = 48"
Rear Vent = 34-1/4"
Raised Platform
© Travis Industries 4080207 100-01185_000
Page 15
Installation (for qualified installers only) 15
Minimum Framing Dimensions - Top Vent Configuration
Vent Clearances: 1" to the sides, 1" below, and 3" above
48" Min.
the vent to combustibles.
The fireplace enclosure must be a minimum 48" above the base of the fireplace. NOTE: Do not build into the area above the fireplace (except for the required framing members).
HINT: We recommend installing the shaded framing after the fireplace is in place.
Firestop (required)
36"
13-1/2"
If using an elbow directly off the fireplace, the vent will be centered 41-3/4" above the base of the fireplace.
HINT: we recommend reinforcing the upper corners of the fireplace opening.
6"
1"
5"
Route the electrical line to a position to the right rear of the fireplace.
20-1/4"
WARNING: A cut-out for the gas line may be required on the framing.
Thermostat or Remote Control Wire (right side)
© Travis Industries 4080207 100-01185_000
Page 16
16 Installation (for qualified installers only)
Minimum Framing Dimensions - Rear Vent Configuration
Vent Clearances: 1" to the sides, 1" below, and 3" above
the vent to combustibles.
Firestop
(required)
34-1/4" Minimum
Enclosure Height
Center of Rear Vent
27-1/4"
HINT: we recommend reinforcing the upper corners of
the fireplace opening.
4-3/4"
34-1/4"
3-5/8"
Route the electrical line to a position to the right rear of the fireplace.
12-3/4"
20-1/4"
WARNING: A cut-out for the gas line may be required on the framing.
© Travis Industries 4080207 100-01185_000
Thermostat or Remote Control Wire (right side)
NOTE: The rear vent may require extra clearance - make sure to accommodate the
vent when determining the framing.
Page 17
Nailing Brackets
There are four nailing brackets on the sides of the fireplace. Follow the directions below to prepare the nailing brackets. Once in place, nail or screw the nailing brackets to the framing.
NOTE: There are alternative nailing brackets on the back corners of the fireplace if the front brackets can not be used.
Installation (for qualified installers only) 17
1/2 Facing
For installations using 1/2” facing (1/2” drywall or other facing) fold the lower tab out 90°.
7/8 to 1 Facing
For installations using 1 facing (1/2 drywall with 3/8” tile, 7/8” tile, etc.) fold the upper tab out 90°.
TOP VIEW
Fireplace
TOP VIEW
Fireplace
Framing
Nailing Bracket
Framing
Nailing Bracket
7/8
Drywall
Drywall
Tile
© Travis Industries 4080207 100-01185_000
Page 18
18 Installation (for qualified installers only)
Corner Installations - Top Vent Configuration
Typical 45° installation uses the framing dimensions shown in the illustration below (NOTE: all clearances apply).
22-1/4" Min. 24-7/8" Recommended
5-1/2" Min. 6-1/2" Recommended
Min. 1/2"
Clearance
Corner Installations - Rear Vent Configuration
Typical 45° installation uses the framing dimensions shown in the illustration below (NOTE: all clearances apply).
Minimum 1" Clearance
6-1/2" Recommended
37-1/2" Recommended
6" Typical
NOTE: Typical 9" Section
37" Min.
© Travis Industries 4080207 100-01185_000
Page 19
Installation (for qualified installers only) 19
Gas Line Requirements
MASSACHUSETTS INSTALLATIONS - WARNING:
THIS PRODUCT MUST BE INSTALLED BY A LICENSED PLUMBER OR GAS FITTER WHEN INSTALLED WITHIN THE COMMONWEALTH OF MASSACHUSETTS.
OTHER MASSACHUSETTS CODE REQUIREMENTS:
Flexible connector must not be longer than 36 inches.
Shutoff valve must be a T handle gas cock.
Only direct vent sealed combustion products are approved for bedrooms or bathrooms.
Fireplace dampers must be removed or welded in the open position prior to the installation of a fireplace insert or gas log.
A carbon monoxide (CO) detector is required in the same room as the appliance.
The gas line must be installed in accordance with all local codes, if any; if not, follow ANSI 223.1 and
the requirements listed below.
The fireplace and gas control valve must be disconnected from the gas supply piping during any pressure testing of that system at test pressures in excess of 1/2 psig. For pressures under 1/2 psig, isolate the gas supply piping by closing the manual shutoff valve.
Leak test all gas line joints and the gas control valve prior to and after starting the fireplace.
Fuel
This fireplace is designed either for natural gas or for propane (but not for both). Check the sticker on the top of the gas control valve to make sure the correct fuel is used.
Gas Line Connection
Installation must be performed by a qualified installer, service agency or the gas supplier (In Massachusetts a licensed plumber/gasfitter).
Gas Inlet Pressure
Natural Gas 7" W.C. (1.74 kPA) Propane 13" W.C. (2.73 kPA)
If the pressure is not sufficient, make sure the piping used is large enough, the supply regulator is adequately adjusted, and the total gas load for the residence does not exceed the amount supplied.
The supply regulator (the regulator that attaches directly to the residence inlet or to the propane tank) should supply gas at the suggested input pressure listed above. Contact the local gas supplier if the regulator is at an improper pressure.
Standard Input Pressure
© Travis Industries 4080207 100-01185_000
Page 20
20 Installation (for qualified installers only)
Optional Gas Line Location
Remove the two screws near the
a
gas inlet (save these screws).
Secure the gas inlet assembly using
c
the screws removed in step “a”.
Remove the three knock-outs on the
b
bottom of the fireplace (one large, two small).
HINT: remove the control cover for easier access.
Gas Line Location
The left side gas inlet is located 2-3/4" above the base of the fireplace.
4"
Gas Line (1/2" M.P.T.)
1/2" F.P.T.
The base mount gas inlet is flush with the base of the fireplace.
4-1/4"
8-1/4"
NOTE: a 3" diameter hole is required to provide clearance for the gas inlet screws.
Gas Line
(1/2" M.P.T.)
1/2" F.P.T.
© Travis Industries 4080207 100-01185_000
Page 21
Installation (for qualified installers only) 21
Electrical Connection (required)
The electrical line to the grounded input wires inside the fireplace must be installed by a qualified installer and must meet all local codes.
Make sure the household breaker is shut off prior to working on any electrical lines.
The appliance, when installed, must be electrically grounded in accordance with local codes or, in the
absence of local codes, with the National Electrical Code, ANSI/NFPA 70, or the Canadian Electrical Code, CSA C22.1.
The electrical line must be a min. 14 gauge, and supply 120 Volts at 60 Hz (2 Amps)
Caution : Label all wires prior to disconnection when servicing controls. Wiring errors can cause
improper and dangerous operation.
Remove the cover from the
a
fireplace junction box.
c
The three connection wires and a romex
b
clamp are inside the junction box.
Remove the knock-out from the cover plate.
NOTE: An alternative knock-out is provided in the base of the fireplace if you wish to run the electrical line from below.
© Travis Industries 4080207 100-01185_000
Secure the romex connector to the cover plate. Route
d
the electrical line through the cover plate and attach to the three electrical leads. Replace the cover plate plate.
Page 22
22 Installation (for qualified installers only)
Wall Switch or Thermostat Installation
Wiring Diagram (Millivolt System)
Do not connect 110-120 VAC to the gas control valve or wiring system of this fireplace. The switch must
be installed by a qualified installer.
Caution : Label all wires prior to disconnection when servicing controls. Wiring errors can cause
improper and dangerous operation.
Thermopile
Piezo Igniter
On/Off Switch (on fireplace)
Red
Brown
Thermocouple
Copper Co-Axial
Wire
Orange
Red
White
Optional Wall Switch, Thermostat, or Remote Control
Spark Electrode
Pilot Hood
Installation
1. Attach the included wire to the gas control valve.
Attach the two wires to the top and bottom posts on the gas control valve (orientation does not matter).
2. Determine a location for the wall switch or thermostat (maximum 25' long). Route the wire through the grommet on the right side of the fireplace (next to the electrical junction box).
3. If using a thermostat, attach it following the manufacturers instructions. If using a wall switch, attach following the directions below.
NOTE : Set the on/off switch on the appliance to "OFF" to control the appliance with the wall switch or thermostat.
Insert the wire
a
through the back of the mounted junction box (your junction box may look different). Expose 1/2" of each wire. Secure the wires to the posts on the side of the on/off switch (orientation does not matter).
From Appliance
Standard Screwdriver
Carefully pack the wires into the
b
junction box. Attach the switch to the junction box. Attach the switchplate to the switch.
Standard Screwdriver
© Travis Industries 4080207 100-01185_000
Page 23
Installation (for qualified installers only) 23
Vent Requirements
The gas appliance and vent system must be vented directly to the outside of the building, and never be attached to a chimney serving a separate solid fuel or gas-burning appliance. Each direct vent gas appliance must use it's own separate vent system.
In addition to the requirements listed here, follow the requirements provided with the vent.
A firestop is required whenever the vent penetrates a wall, floor, or ceiling (passes through framing
members). Use the included firestop. It incorporates a 3" clearance above, 1" clearance below and to the sides of the vent.
Always use the high-wind termination.
Vent Clearances
The vent must maintain the required clearance to combustible materials to prevent a fire. Do not fill air spaces with insulation.
Sides 1" Above 3" Below Horizontal or 45° Section 1"
Use a firestop when passing through any
Min. 3" Clearance Above the Vent
wall (WARNING: some firestops provide a 1" clearance above the vent -- 3" is required for this heater).
Min. 1" Clearance to the side of vent
1" Clearance to the sides after the first firestop.
Use a firestop whenever passing through a ceiling, enclosure or floor penetration.
Altitude Considerations
This heater has been tested at altitudes ranging from sea level to 6,000 feet. In this testing we have found that the heater, with its standard orifice, burns correctly with just an air shutter adjustment.
Failure to adjust the air shutter properly may lead to improper combustion which can create a safety hazard. Consult your dealer or installer if you suspect an improperly adjusted air shutter.
© Travis Industries 4080207 100-01185_000
Page 24
24 Installation (for qualified installers only)
Approved Vent
Rear vent configurations use 8" diameter Simpson Dura-Vent Model GS or Pro vent.
Top vent configurations use 8" or 6-5/8" diameter Simpson Dura-Vent Model GS or Pro vent. If using
6-5/8" diameter vent, attach the 8" to 6-5/8" reducer (Travis part # 98900165) directly to the fireplace (see the illustration below).
Installation instructions for Simpson Dura-Vent may be found at www.duravent.com
6-5/8" Diameter Vent (minimum 12" vertical rise)
Reducer - # 98900165
Vent Installation
Slide the vent sections together and turn 1/4 turn until the sections lock in place.
Screws are not required to secure the vent. However, three screws may be used to secure vent
sections together if desired.
High temperature sealant is recommended at the appliance starter section connection (use high­temperature silicone or Mill-Pac®).
If disassembly is required, at time of re-assembly check to see if the vent creates a tight fit. If it does not, apply high temperature sealant to the joints of the affected sections.
Horizontal sections require a 1/4" rise every 12" of travel
Horizontal sections require non-combustible support every three feet (e.g.: plumbing tape)
© Travis Industries 4080207 100-01185_000
Page 25
Installation (for qualified installers only) 25
Approved Vent Configurations
Restrictor and Diffuser Position
An exhaust restrictor and diffuser are built into the appliance to adjust the flow rate of intake air and exhaust gases. Depending upon the vent configuration, you may be required to adjust the restrictor and/or diffuser . The charts for acceptable vent configurations detail the correct vent restrictor and diffuser positions.
Exhaust Restrictor Adjustment
Adjustment Plate
Adjustment Bracket
This restrictor is in position 1 (factory setting).
Restrictor Position
To adjust, lift the adjustment plate and pull it forward
To Access the Restrictor:
Remove the face (with the stove cool).
This restrictor is in position 3.
To Adjust the Restrictor:
1
Determine the correct restrictor position (see the charts under "Approved Vent Configurations" - the factory position is #1).
2
Lift up the adjustment plate and move it so the correct notch falls into the slot on the adjustment bracket.
# 7 # 6
etc...
# 2
© Travis Industries 4080207 100-01185_000
Page 26
26 Installation (for qualified installers only)
Diffuser Plate Adjustment
Certain vent configurations require the diffuser plate to be adjusted (refer to the approved vent configuration charts for details). Position # 1 is stock (flat). Position # 2 is bent. See the directions below to change the diffuser to position #2.
If the diffuser is required to be in position # 2, you may wish to adjust the diffuser while converting the
appliance to rear-vent configuration.
Firebox Roof
NOTE: To better access the diffuser,
DIFFUSER SIDE VIEW
Before (Stock - Position # 1)
Back Wall of Firebox
you may wish to move the restrictor to the # 1 postion.
Remove the diffuser.
Bend the round portion of the diffuser 90° (position # 1).
After (Position # 2)
© Travis Industries 4080207 100-01185_000
Secure the diffuser plate with the screws removed earlier.
Page 27
Installation (for qualified installers only) 27
Top Vent Configuration with Horizontal Termination
The termination must fall within the shaded area shown in the chart. Use the indicated restrictor and diffuser positions.
Only one horizontal elbow may be used (see illustration at the bottom of the page).
May use 8" or 6-5/8" diameter vent (see page for 24 details).
14 feet
(max)
10 feet
5 feet
0 feet
0 feet
5 feet
10 feet
14'
(max)
14 feet (max)
10 feet
Restrictor Position # 1 (stock)
Diffuser Position #1 (stock)
5 feet
0 feet
0 feet
NOTE:
If using 6-5/8" diameter vent, a minimum 12" vertical rise is required.
5 feet
10 feet
(max)
14 feet
NOTE:
Horizontal sections require a 1/4" rise every 12" of travel.
NOTE:
This is considered a horizontal elbow (it does not matter whether it turns right or left). It may be a 90° or 45° elbow.
© Travis Industries 4080207 100-01185_000
H1
H2
Horizontal length is calculated by adding both lengths of horizontal run (Horizontal Length = H1 + H2).
This is considered a vertical elbow
Page 28
28 Installation (for qualified installers only)
Top Vent Configuration with Vertical Termination
The termination must fall within the shaded area shown in the chart. Use the indicated restrictor and diffuser positions.
Up to four elbows (45° or 90°) may be used.
Only one horizontal elbow may be used (see illustration at the bottom of the page).
May use 8" or 6-5/8" diameter vent (see page for 24 details).
40' (max)
Restrictor Position # 3 Diffuser Position # 1 (stock)
NOTE:
Two 45° elbows may be used.
30 feet
25 feet
20 feet
15 feet
10 feet
0 feet
Restrictor Position # 2 Diffuser Position # 1 (stock)
Restrictor Position # 1 (stock) Diffuser Position # 1 (stock)
5 feet
NOTE: Restrictor positions are based upon lab tests. The ideal restrictor position may vary slightly, especially when the termination is near a demarkation line.
10 feet
14' (max)
40' (max)
35 feet35 feet
30 feet
25 feet
20 feet
15 feet
10 feet
NOTE:
One 45° or 90° elbow may be used between horizontal sections. Horizontal length is caculated by adding each horizontal run together.
NOTE:
Horizontal sections require a 1/4" rise every 12" of travel.
6' (min) 6' (min)
0 feet
5 feet
0 feet
5 feet
10 feet
5 feet
0 feet
14' (max)
H2
This is considered a horizontal elbow (it does not matter whether it turns right or left).
Horizontal length is calculated by adding both lengths of horizontal run (Horizontal Length = H1 + H2).
It may be a 90° or 45° elbow.
H1
This is considered a vertical elbow
© Travis Industries 4080207 100-01185_000
Page 29
Installation (for qualified installers only) 29
Rear Vent Configuration with Horizontal Termination
The termination must fall within the shaded area shown in the chart. Use the indicated restrictor and diffuser positions.
Up to four elbows (45° or 90°) may be used.
Only one horizontal elbow may be used (see illustration at the bottom of the page).
Use 8" diameter vent.
14'
0 feet
5 feet
10 feet
(max)
14 feet
(max)
10 feet
5 feet
0 feet
Restrictor Position # 1 (stock)
Diffuser Position # 1 (stock)
0 feet
5 feet
Restrictor Position # 1 (stock)
Diffuser Position # 2
10 feet
14 feet (max)
10 feet
0 feet
(max)
14 feet
5 feet
NOTE: Restrictor positions are based upon lab tests. The ideal restrictor position may vary slightly.
This is considered a horizontal elbow (it does not matter whether it turns right or left). It may be a 90° or 45° elbow.
© Travis Industries 4080207 100-01185_000
H1
NOTE:
Horizontal sections require a 1/4" rise every 12" of travel.
H2
Horizontal length is calculated by adding both lengths of horizontal run (Horizontal Length = H1 + H2).
This is considered a vertical elbow
Page 30
30 Installation (for qualified installers only)
Rear Vent Configuration with Vertical Termination
The termination must fall within the shaded area shown in the chart. Use the indicated restrictor and diffuser positions.
Up to four elbows (45° or 90°) may be used.
Only one horizontal elbow may be used (see illustration at the bottom of the page).
Use 8" diameter vent.
40' (max)
Restrictor Position # 3 Diffuser Position # 1 (stock)
30 feet
0 feet
5 feet
NOTE: Restrictor positions are based upon lab tests. The ideal restrictor position may vary slightly, especially when the termination is near a demarkation line.
Restrictor Position # 2 Diffuser Position # 1 (stock)
10 feet
14' (max)
40' (max)
35 feet35 feet
30 feet
NOTE:
Two 45° elbows may be used.
NOTE:
One 45° or 90° elbow may be used between horizontal sections. Horizontal length is caculated by adding each horizontal run together.
NOTE:
Horizontal sections require a 1/4" rise every 12" of travel.
25 feet
20 feet
15 feet
Restrictor Position # 1 (stock) Diffuser Position # 1 (stock)
10 feet
6' (min) 6' (min)
5 feet
0 feet
0 feet
5 feet
10 feet
25 feet
20 feet
15 feet
10 feet
5 feet
0 feet
14' (max)
This is considered a horizontal elbow (it does not matter whether it turns right or left). It may be a 90° or 45° elbow.
© Travis Industries 4080207 100-01185_000
H1
H2
Horizontal length is calculated by adding both lengths of horizontal run (Horizontal Length = H1 + H2).
This is considered a vertical elbow
Page 31
Installation (for qualified installers only) 31
Termination Requirements
! Venting terminals shall not be recessed into a wall or siding.
A Minimum 9" clearance from any door or window B Minimum 12" above any grade, veranda, porch, deck or balcony C Minimum 1" from outside corner walls
NOTE: Clearance in accordance with local installation codes and the requirements of the gas supplier.
D Minimum 1" from inside corner walls
NOTE: Clearance in accordance with local installation codes and the requirements of the gas supplier.
E Minimum 11" clearance below unventilated soffits or roof surfaces
Minimum 18" clearance below ventilated soffits Minimum 6" clearance below roof eaves
NOTE: Vinyl surfaces require 24" NOTE: Clearance in accordance with local installation codes and the requirements of the gas supplier.
F Minimum 12" clearance below a veranda, porch, deck or balcony
NOTE: Permitted only if veranda, porch, deck, or balcony is fully open on a minumum of two sides beneath the floor. NOTE: Clearance in accordance with local installation codes and the requirements of the gas supplier.
G Minimum 48" clearance from any adjacent building H Minimum 84" clearance above any grade when adjacent to public walkways or driveways
NOTE: may not be used over a walkway or driveway shared by an adjacent building
I Minimum 9" clearance to any nonmechanical air supply inlet to the building or the combustion air inlet to any other
appliance.
J Minimum 36" clearance above any mechanical air supply inlet if within 10 horizontally K Minimum 36" from the area above the meter/regulator (vent outlet) - this extends 15 above the regulator
NOTE: Clearance in accordance with local installation codes and the requirements of the gas supplier.
L Minimum 36" from the meter/regulator (vent outlet)
NOTE: Clearance in accordance with local installation codes and the requirements of the gas supplier.
M Minimum 12 above the roof line (for vertical terminations) N Minimum 24 horizontal clearance to any surface (such as an exterior wall) – for vertical terminations
Roof Surface
11 Min.
6 Min.
Roof Eaves
E
N
M
E
K
G
NOTE: Measure clearances to the nearest edge of the exhaust hood.
Use the vinyl siding standoff when installing on an exterior with vinyl siding.
Vent termination must not be located where it will become plugged by snow or other material
F
D
A
I
C
L
B
A
E
J
H
© Travis Industries 4080207 100-01185_000
Page 32
32 Installation (for qualified installers only)
Hearth Requirements
NOTE: Looking Glass and Wilmington Faces require a raised fireplace – see Face Dimensions on page 33 for details.
Floor Mounted
Fireplaces
Do not build a hearth or other item above the baseplate (this area must remain clear for the access door).
If installed in front of carpet or other flooring, the fireplace must be raised so the base of the unit is above the carpet surface or flooring material.
Raised
Fireplaces
WARNING:
A non-combustible hearth is not required. However, if the heater is installed next to the floor, we recommend a hearth to protect the flooring surface from discoloration or other negative impact from the heater.
A hearth is not required when the fireplace is raised above the flooring surface.
Fireplace Stand
© Travis Industries 4080207 100-01185_000
Page 33
Installation (for qualified installers only) 33
Facing Requirements
NOTE: The combustible area above the facing must not protrude more than 3/4" from the facing. If it
does, it is considered a mantel and must meet the mantel requirements listed in this manual.
Face Dimensions
Face Height Width Bottom of Face Installation Notes
Arched Faces 35-1/2” 21-1/8” Flush w base of fireplace Arched top is 25-3/4” radius Bungalow, T. of L. 35-3/8” 21-1/8” Flush w base of fireplace Vict. Lace 35-1/2” 21-1/8” Flush w base of fireplace Looking Glass 36-3/4” 23-1/2” 1-1/4” BELOW base of fireplace Cast face is approx. 2” thick
Wilmington 36-3/4” 22-1/8” 1-1/4” BELOW base of fireplace
Facing Under 1” Thick
Any material that protrudes more than 3/4” in front of the facing is considered a mantel and must meet the mantel requirements in this manual.
NOTE: The facing tucks behind the flanges.
Recommended Order of Installation We recommend installing the facing (drywall, tile) under the notch at the front of the fireplace (a) - then install the sides and top (b and c)
4-7/8
3-1/4
30-1/2 (approx.)
c
The wall trim comes off, allowing the installer to cover
b
3/8
a
NOTE The facing tucks under the notch at the front
of the fireplace (3/8 above the base of the fireplace).
the drywall edge below the front edge of the fireplace.
Facing Over 1” Thick
Facing that protrudes in front of the face above the face (or within 1/2” of each side) must be
made of non-combustible materials.
NOTE A 3/8" gap above the face is required for face installation and removal.
© Travis Industries 4080207 100-01185_000
Page 34
34 Installation (for qualified installers only)
Facing – Fireplace Overview
Facing - Top View
Fireplace
1/2"
Face
White Tape Gasket (attached to fireplace)
Nailing Bracket
Facing - Side View
Fireplace
3/8"
Face
Wall Trim (1/16" thick)
1"
1/8"
Wall Trim
© Travis Industries 4080207 100-01185_000
Page 35
Installation (for qualified installers only) 35
Facing Detail – Drywall Facing
Recommended Order of Installation We recommend installing the facing (drywall, tile) under the notch at the front of the fireplace (a) - then install the sides and top (b and c)
c
b
NOTE The facing tucks under the
notch at the front of the fireplace (3/8 above the base of the fireplace).
Top View - Drywall Facing
Side View - Drywall Facing
Fireplace
Nailing Bracket
Face
White Tape Gasket (attached to fireplace)
Fireplace
a
Drywall, paneling, or other facing (combustible or non­combustible).
NOTE: The facing should tuck behind the wall trim, thus concealing the top of the facing and the base of the fireplace.
NOTE: The fireplace is shifted back on the shelf to accommodate the facing thickness.
© Travis Industries 4080207 100-01185_000
Facing (drywall, paneling, or other material - combustible or non­combustible).
Page 36
36 Installation (for qualified installers only)
Facing Detail – Tile Facing
Top View - Tile Facing
Side View - Tile Facing
NOTE: The fireplace is shifted back
on the shelf to accommodate the facing thickness.
Fireplace
Framing
Fireplace
NOTE: Make sure to use the correct nailing bracket for this type of facing (see Nailing Bracket for details). For this example the facing is 7/8" thick (3/8" tile plus 1/2" drywall). The framing is positioned 1" behind the front of the fireplace.
Drywall
Tile
NOTE: The facing should tuck behind the wall trim, thus concealing the top of the facing and the base of the fireplace.
Tile
Drywall
3-d View - Tile Facing
The wall trim is removed for installation and replaced to cover the top edge of the facing.
Recommended Order of Installation We recommend installing the tile under the notch at the front of the fireplace then working your way up.
The facing contacts the side of the fireplace.
Note how the facing tucks underneath the wall trim.
Wall Trim
© Travis Industries 4080207 100-01185_000
Page 37
Installation (for qualified installers only) 37
Facing Detail – Facing Over 1” Thick (Brick)
WARNING: Any facing that extends in front of the faceplate on the sides or top must be non-
combustible.
NOTE: A 3/8” gap is required above the face for face installation.
Top View
NOTE: When installed, there must be a minimum 1/8” gap between the face and facing.
Side View
Face
Fireplace
Fireplace
Framing
3/8"
1/8"
NOTE: Make sure to leave a 1/8" gap around the sides of the face and 3/8" above (for face installation).
Drywall
Non-combustible facing material (brick, stone, marble, tile) - required if the facing extends in front of the face on the sides or top.
NOTE: Bring the facing up to the base of the fireplace.
1/8"
3-d View
Wall Trim
The facing is brought up to the wall trim.
© Travis Industries 4080207 100-01185_000
In this example brick is used.
The side facing should be spaced 1/8" from the face (3/8 from the side of the fireplace).
Page 38
38 Installation (for qualified installers only)
Mantel Requirements
The illustration below details mantel clearances and maximum mantel depth.
Any material that protrudes more than 3/4 from the non-combustible facing is considered a mantel
and must meet the mantel requirements.
Maximum Mantel Depth (b)
0123456789101112
Mantel Height Above
Face (a)
9 8 7 6 5 4 3 2 1 0
Mantel (combustible or non-combustible)
a
See Face Dimensions
If you have a tapered mantel, measure the mantel height at the point where it protrudes 3/4 in front of the face.
b
Combustible mantel columns (legs) that protrude more than 3/4” from the glass frame must meet the sidewall clearance (1 from the face). If they protrude 3/4 or less, they do not have a minimum clearance.
Non-combustible mantel columns do not have a minimum clearance.
© Travis Industries 4080207 100-01185_000
Page 39
Finalizing the Installation (for qualified installers only) 39
Steps for Finalizing the Installation
1. Remove the glass (see page 41).
NOTE : If using propane (LP) convert the appliance prior to installing the logs.
2. We recommend you purge the gas line at this time (with the glass removed). This allows gas to be detected once it enters the firebox, ensuring gas does not build up.
3. Install the logs (see page 43).
4. Turn on the gas to the fireplace. Turn on gas to the heater. Leak test all gas joints prior to starting the appliance. Start the pilot.
Starting the Pilot Flame
WARNING : When lighting or re-lighting the pilot, the glass must be removed (see page 41).
a Remove the glass (see page 41 for details). b Push the gas control knob in slightly and turn it to the "OFF" position. The knob will not turn from
"ON" to "OFF" unless the knob is depressed slightly. Wait five minutes to let any gas that may have accumulated inside the firebox escape. If you smell leaking gas, follow the directions on the cover "IF YOU SMELL GAS".
c Turn the gas control knob to the "PILOT" position and press the knob in, this will allow gas to flow to
the pilot light. Press the button on the pilot igniter repeatedly until you see the pilot light.
WARNING: If the pilot does not light after 15 seconds, release the knob and call
your dealer for service. Do not attempt to light pilot until service has been performed.
NOTE: You may wish to remove the log set to gain a better view of the pilot (see page 43).
d Keep the gas control knob depressed for 30 seconds once it is lit. e Release the gas control knob. If the pilot goes out, repeat step C. If the pilot refuses to stay lit, call
your dealer for service. With the pilot lit, proceed to step “f”.
f Replace the glass. g Turn the gas control knob counter-clockwise to "ON". The pilot is now lit and the heater can be turned
on and off.
5. Check the pilot flame following the directions below.
Pilot Flame Inspection
The pilot flame should look like the illustration below. Adjust the pilot flame if necessary.
To adjust the pilot flame, turn this screw. Clockwise lowers the flame while counter-clockwise raises it.
6. Start the main burner (the main burner circuit is detailed on page 22). Leak test all gas joints again.
© Travis Industries 4080207 100-01185_000
Standard Screwdriver
The pilot flame must contact the thermocouple and thermopile (see the illustration below). Adjust the pilot up or down as necessary.
Page 40
40 Finalizing the Installation (for qualified installers only)
7. Check the air shutter following the directions below.
Air Shutter Adjustment
Let the heater burn for fifteen minutes (make sure the logs and glass are in place). The flames should be yellow with no sooting. Adjust the air shutter, if necessary, to achieve the correct looking flame.
ADJUSTING THE AIR SHUTTER
Moving the air shutter control to the right gives the flame less air (closed) - making it more orange. Moving it to the left gives the flame more air (open), making it more blue. For fine adjustments use a screwdriver to tap the air shutter.
NOTE: If the air shutter is all the way open, yet the flames remain sooty, shut off gas to the fireplace and contact a qualified gas service technician.
Correct
Flames should be blue at the base, yellow-orange on the top.
Air Shutter
Control
Phillips Screwdriver
NOTE: The logs must be installed correctly to monitor the flame while adjusting the air shutter.
Not Enough Air
If the flames are too tall or sooty on the ends, open the air shutter.
More Air
Too Much Air
If the flames are all blue and short, close the air shutter.
Less Air
8. Turn the flame adjust knob to its highest position - the flames should not contact the top of the firebox. Check the flame on low position. The flames should burn off of each burner hole. If the heater does not work correctly, contact your Travis dealer for a remedy.
9. Give this manual to the home owner for future reference and fully explain operation of this heater. For comprehensive operating and maintenance instructions, refer to the Owner's Manual (part # 100-
01186).
ACID WASH WARNING: Before installing the faceplate, make sure any masonry that has been treated with acid wash has been properly neutralized (this is used primarily with brick faces). Acid wash (muriatic
acid) is used to remove excess mortar. If not properly neutralized with an ammonia solution, the plated face may develop a permanent tarnish when the acid evaporates over time. Contact your dealer if uncertain your facing has been properly neutralized.
© Travis Industries 4080207 100-01185_000
Page 41
Finalizing the Installation (for qualified installers only) 41
Glass Frame Removal and Installation
Warning: The appliance must be completely cool before removing the glass. Warning: Do not strike or slam the glass.
Open the two latches holding the glass
a
frame in place - follow the directions shown to the right.
Latch
Top of Firebox
Glass
Glass Frame
Glass Frame Brackets
Tilt the glass frame forward then lift it up. The tabs
b
on the glass frame will disengage from the slots on the glass frame brackets attached to the fireplace.
Re-Attaching the Glass Frame:
a) Tilt the glass frame as shown above.
b) Insert the tabs on the glass frame into the slots on the glass frame bracets (attached to the fireplace).
c) Attach the two glass latches.
NOTE: Make sure the glass frame is all the way in place - it should be flush with the front of the fireplace when installed.
Catch (on glass frame)
© Travis Industries 4080207 100-01185_000
Page 42
42 Finalizing the Installation (for qualified installers only)
Glass Frame Removal and Installation (continued)
The latch can come loose from glass frame anchor. This occurs when it is turned 1/4 turn when it is disengaged. Follow the directions below to re-install the latch if it becomes loose.
Hold the latch at an angle and insert it into the slot on the glass frame anchor.
Latch
NOTE: this slot may be at a different angle than illustrated.
Top of Firebox
Glass Frame Anchor
Note how the washer on the latch fits behind the flange on the glass frame anchor.
Once fully inserted, turn the latch until it is upright.
© Travis Industries 4080207 100-01185_000
Page 43
Finalizing the Installation (for qualified installers only) 43
Log Set Installation
Rear Log Installation
Place the rear log with the left side flush to the edge of the burner and the right side flush to the metal deflector on the back edge of the burner. The bottom edge of the log should be located behind the burner ports (see the illustration below).
CROSS-SECTIONAL VIEW
Burner
Rear Log
Make sure the ledge on the burner lines up with stepped-down portion of the rear log.
Right Rear Log Installation
Place the right rear log on top of the rear log. When placed correctly there is a minimal gap between the two logs. Make sure the bottom is placed so no burner ports are blocked.
NOTE: Make sure the right rear log does not rest against the back of the firebox (or liner). If it does, it will block the light from the optional accent light, creating a large shadow.
© Travis Industries 4080207 100-01185_000
Page 44
44 Finalizing the Installation (for qualified installers only)
Right Front Twig Installation
Place the right front twig as shown below. The bottom of the twig is placed one inch to the right of the center screw on the burner. The top of the twig rests in the groove on the right rear log.
Left Front Twig Installation
Place the left front twig as shown below. Note how both ends of the twig are directly over the center and left hand screw on the burner
These two projections on the bottom of the twig insert into screw holes on the burner.
© Travis Industries 4080207 100-01185_000
Page 45
Finalizing the Installation (for qualified installers only) 45
Left Front Twig Installation (continued)
Double check that the front twigs are not blocking any burner ports.
Place an ember over this screw.
Log Installation Overview
Correct view of complete log installation.
Place embers in the firebox corners and along the front edge of the burner. Do not place embers over burner holes or allow the embers to block airflow.
© Travis Industries 4080207 100-01185_000
Page 46
46 Optional Equipment (for qualified installers only)
LP Conversion Instructions
Install the conversion kit prior to installing the gas line to ensure proper gas use. 1 Remove the glass (see page 41). Remove the logs and coals (if installed - page 43)
2 Remove the burner (see illustration below).
Lift the pilot hood off the pilot
a
assembly (you may need to pull hard to remove).
b
Lift up on the left side of the burner, then slide the burner to the left and up to remove.
Burner Replacement:
Make sure the orifice on the firebox floor inserts into the fitting on the bottom of the burner.
The mixing tube slides
After replacing the burner re-attach the pilot hood.
onto the orifice.
Make sure the burner is fully seated and pilot hood lines up with the burner holes at the rear edge of theburner.
© Travis Industries 4080207 100-01185_000
Before replacing the burner, slide the air control all the way to the right.
Page 47
Optional Equipment (for qualified installers only) 47
3 Follow the directions below to replace the orifice.
Front Orifice
b
Remove and discard the gaskets on the two orifices.
Slide the air shutter all
a
the way to the left.
Back Orifice
c
Use a 1/2 open end wrench to unscrew both burner orifices.
Back Orifice
Front Orifice
5/16
5/16
NOTE:
Screw the LP orifice in so the orifice shoulder protrudes 5/16 (indicating full insertion).
1/2" Wrench
d
Apply thread sealant to the new orifice and install.
Look here for the orifice identification.
Front
Rear
LP #66 #65
NG #55 #55
© Travis Industries 4080207 100-01185_000
Page 48
48 Optional Equipment (for qualified installers only)
4 Remove the pilot orifice following the instructions below. Replace with the propane pilot orifice
Lift the pilot hood
a
off the pilot assembly.
5 Replace the firebox
components. Install
the logs and embers. Replace the glass.
6 Remove the regulator
from the front of the gas control valve. Replace with the propane regulator, using the new gasket and screws included with the regulator. NOTE: Leak
test this area after the heater is installed, gas is connected, and the main burner is lit.
Use a hex wrench to
b
unscrew the orifice.
5/32" Hex
Remove and discard the three screws using a Torx T-20.
Slotted Screwdriver (or T-20 Torx)
Remove the orifice and replace with the LP orifice. Screw the
c
orifice all the way in and replace the pilot hood.
Orifice Identification:
35
NOTE: when re-attaching, this pin lines up with the notch in the pilot hood.
a
Install the LP regulator. Use the screws included with the LP regulator. Tighten to approximately 25 Lbs. torque.
b
Remove and discard the regulator, diaphram, spring and center post.
LP (Propane) Orifice
35
NG (Natural Gas) Orifice
62
c
NOTE: Make sure the
regulator gasket is correctly aligned before installation.
Slotted Screwdriver (or T-20 Torx)
d
Place the LP label on top of the control cover near the gas control valve.
© Travis Industries 4080207 100-01185_000
Page 49
Optional Equipment (for qualified installers only) 49
7 Make the gas line connection, bleed the gas line (if applicable), start the heater and thoroughly leak-
test all gas connections and the gas control valve. Check the pilot. Adjust if necessary.
WARNING : When lighting or re-lighting the pilot, the glass must be removed (see page 41).
To adjust the pilot flame, turn this screw (NOTE: if totally unscrewed gas will come out of this port). Clockwise lowers the flame while counter-clockwise raises it.
Aromatherapy Modification
If you are using the aromatherapy option with the 21 TRV, you will need to bend up the mounting flange on the front of the fireplace (see the illustration below). The aromatherapy extension assembly attaches to this flange.
Standard Screwdriver
The pilot flame must contact the thermocouple and thermopile (see the illustration below). Adjust the pilot up or down as necessary.
© Travis Industries 4080207 100-01185_000
Page 50
50 Optional Equipment (for qualified installers only)
Omega Remote Notes
If you are using the Omega remote option with the 21 TRV, follow the directions below for installing the receiver and attaching the accent light leads (if applicable – see the following page).
Receiver Installation
Attach the two wires labeled "SOLENOID OPTIONAL" to the modulating regulator
e
(orientation does not matter).
SOLENOID
(OPTIONAL)
Control Cover
Make sure the power is disconnected!
a
Disconnect the control cover and pull it forward (leave the wires attached). Remove and discard the regulator knock-out (use tin snips or wire cutters).
d
Replace the control cover.
b
Remove the jumper connector on the wiring harness and place it near the gas control valve (it is required if you wish to remove the remote). Attach the molex connector from the receiver to the molex connector on the appliance.
c
Place the receiver to the right of the gas control valve (it is a very tight fit). Make sure the wires do not contact the burner or any moving parts (use lock ties if necessary). NOTE: When installing the receiver, make sure to place the receiver with the "Learn" button in a forward position. Before replacing the control cover, make sure to verify the remote works correctly. Once the control cover is installed, the "Learn" button can not be readily accessed.
IF USING AN ACCENT LIGHT
Follow the directions listed under Accent Light Receiver Connection.
IF NOT USING AN ACCENT LIGHT
Secure the two white wires, making sure they do not contact the burner or any moving parts.
© Travis Industries 4080207 100-01185_000
Page 51
Optional Equipment (for qualified installers only) 51
Accent Light Connection to Omega Remote
If using the accent light with an Omega remote, you will want to remove and discard the accent light rheostat and wiring harness. Plug the wiring harness (included with the blower) into the junction box on the fireplace. The leads from the accent light are connected to the leads from the Omega remote.
The molex connector on the blower wiring harness plugs into the molex connector on the junction box.
Accent Light Leads
Remote Accent Light Leads (orientation does not matter)
The accent light rheostat and wiring harness are not needed when using the Omega remote.
© Travis Industries 4080207 100-01185_000
Page 52
52 Index
Index
Additional Items Required .....................................7
Air Shutter Adjustment .........................................40
Altitude Considerations ........................................23
Approved Vent Configurations ...............................25
Approved Vent....................................................24
Aromatherapy Modification...................................49
Clearances ........................................................14
Converting the Fireplace to Rear Vent Configuration...11
Corner Installations - Top Vent Configuration ............18
Corner Installations - Rear Vent Configuration...........18
Diffuser Plate Adjustment .....................................26
Dimensions........................................................6
Electrical Connection (required) .............................21
Exhaust Restrictor Adjustment ..............................25
Facing Requirements ...........................................33
Features............................................................6
Fuel..................................................................19
Gas Inlet Pressure ..............................................19
Gas Line Connection............................................19
Gas Line Location ...............................................19
Gas Line Requirements ........................................19
Glass Frame Removal and Installation.....................41
Hearth Requirements ...........................................32
Heating Specifications .........................................6
Index ................................................................52
Installation Options.............................................6
Installation Overview ...........................................8
Listing Details.....................................................2
Log Set Installation..............................................43
Mantel Requirements ...........................................38
M ini mu m F ra mi ng D im en sion s - T op V ent C on figu rati on.........................1 5
M ini mu m F ra mi ng D im en sion s - R ear Ven t Co nfig ura tion.......................16
Nailing Brackets..................................................17
Overview...........................................................2
Packing List .......................................................7
Pilot Flame Inspection..........................................39
Raised Fireplaces................................................14
T o p V e n t C o n f i g u r a t i o n w i t h H o r i z o n ta l Te r mi n a t i o n.....................27
T o p V e n t C o n f i g u r a t i o n w i t h V e r ti c a l T e r mi n a t i o n ........................28
Rear Vent Configuration with Horizontal Termination...29
Recommended Installation Procedure .....................7
Restrictor and Diffuser Position..............................25
Safety Precautions..............................................4
Starting the Pilot Flame.........................................39
Steps for Finalizing the Installation .........................39
Termination Requirements.....................................31
Thick Facing Installation with FPX Arched Faces .......
Thick Facing Installation .......................................
Thin Facing Installation.........................................
Rear Vent Configuration with Vertical Termination ......30
Vent Clearances .................................................23
Vent Installation..................................................24
Vent Requirements..............................................23
Installation.........................................................22
Wall Switch or Thermostat Installation .....................22
Wiring Diagram (Millivolt System)............................22
© Travis Industries 4080207 100-01185_000
Loading...