WARNING: If the information in these instructions is not followed exactly, a fire
or explosion may result causing property damage, personal injury or
loss of life.
-Do not store or use gasoline or other flammable vapors and liquids in the
vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call gas supplier from a neighbor's phone. Follow the gas
supplier's instructions.
• If you cannot reach your gas supplier, call the fire department.
-Insta lla tion and service must be pe rforme d by a qua lified installe r, service
age ncy or the ga s supplier.
This appliance may be installed in an aftermarket permanently located, manufactured home (USA only)
or mobile home, where not prohibited by local codes.
This appliance is only for use with the type(s) of gas indicated on the rating plate. A conversion kit is
supplied with the appliance.
Installation Manual
Installer:After installation give this manual to the home-
owner and explain operation of this heater.
Copyright 2008, T.I. $10.00 100-01185_000 4080207
4800 Harbour Pointe Blvd. SW
Mukilteo, WA 98275
Page 2
2Introduction
Overview
This manual details the installation requirements for
the 21 TRV fireplace. For operating and
maintenance instructions, refer to the 21 TRV
Owner's Manual (part # 100-01186).
Listing Details
This appliance was listed by OMNI Test Labs to
ANSI Z21.88a-2007/CSA 2.33a-2007 - report #
028-F-85-5 – for US and Canadian installations.
The listing label is attached to the appliance near
the gas control valve. A copy is shown to the right.
ICBO Approval
This appliance was listed by OMNI Test Labs - ICBO
# TL130.
Massachusetts Approval
This manual has been submitted to the
Massachusetts Board of State Examiners of
Plumbers and Gas Fitters
• Failure to follow all of the requirements may result in property damage, bodily injury, or even death.
• This unit must be installed by a qualified installer to prevent the possibility of an explosion.
• This appliance must be installed in accordance with all local codes, if any; if not, in U.S.A. follow ANSI
Z223.1 and NFPA 54(88).
•A manufactured home (USA only) or mobile home OEM installation must conform with the
Manufactured Home Construction and Safety Standard, Title 24 CFR, Part 3280, or, when such a
standard is not applicable, the Standard for Manufactured Home Installations, ANSI/NCSBCS A225.1,
or Standard for Gas Equipped Recational Vehicles and Mobile Housing, CSA Z240.4. This appliance
may be installed in Manufactured Housing only after the home is site located.
•All exhaust gases must be vented outside the structure of the living-area. Combustion air is drawn
from outside the living-area structure. The venting must not be connected to a chimney flue serving a
separate solid-fuel burning appliance.
• Notify your insurance company before hooking up this fireplace.
• The room heater should be inspected before use and at least annually by a qualified service person.
More frequent cleaning may be required due to excessive lint from carpeting, bedding material, etc.
•The instructions in this manual must be strictly adhered to. Do not use makeshift methods or
compromise in the installation. Improper installation will void the warranty and safety listing.
•This heater is approved for use with natural gas (NG) or propane (LP). Burning the incorrect fuel will
void the warranty and safety listing and may cause an extreme safety hazard. Direct questions about
the type of fuel used to your dealer. Check the label and flame adjust knob on the gas control valve.
•Contact your local building officials to obtain a permit and information on any installation restrictions or
inspection requirements in your area.
•If the flame becomes sooty, dark orange in color, or extremely tall, do not operate the heater. Call your
dealer and arrange for proper servicing.
•It is imperative that control compartments, screens, or circulating air passageways of the heater be
kept clean and free of obstructions. These areas provide the air necessary for safe operation.
•Do not operate the heater if it is not operating properly in any fashion or if you are uncertain. Call your
dealer for a full explanation of your heater and what to expect.
• Do not store or use gasoline or other flammable liquids in the vicinity of this heater.
• Do not operate if any portion of the heater was submerged in water or if any corrosion occurs.
• Do not place clothing or other flammable items on or near the heater. Because this heater can be
controlled by a thermostat there is a possibility of the heater turning on and igniting any items placed
on or near it.
•Light the heater using the built-in piezo igniter. Do not use matches or any other external device to
light your heater.
•Never remove, replace, modify or substitute any part of the heater unless instructions are given in this
manual. All other work must be done by a trained technician. Don't modify or replace orifices.
• The viewing glass should be opened only for lighting the pilot or conducting service.
• Any safety screen or guard removed for servicing must be replaced prior to operating the heater.
• Allow the heater to cool before carrying out any maintenance or cleaning.
• Operate the heater according to the instructions included in this manual.
• If the main burners do not start correctly turn the gas off at the gas control valve and call your dealer for
service.
•The pilot flame must contact the thermopile and thermocouple. If it does not, turn the gas control
valve to "OFF" and call your dealer.
• This unit is not for use with solid fuel.
• Do not place anything inside the firebox (except the included fiber logs).
• If the fiber logs become damaged, replace with Travis Industries log set.
• Do not throw this manual away. This manual has important operating and maintenance instructions
that you will need at a later time. Always follow the instructions in this manual.
•Do not touch the hot surfaces of the heater. Educate all children of the danger of a high-temperature
heater. Young children should be supervised when they are in the same room as the heater.
•Due to the high temperature, the heater should be located out of traffic and away from furniture and
draperies.
•Instruct everyone in the house how to shut gas off to the appliance and at the gas main shutoff valve.
The gas main shutoff valve is usually next to the gas meter or propane tank and requires a wrench to
shut off.
•Travis Industries, Inc. grants no warranty, implied or stated, for the installation or
maintenance of your heater, and assumes no responsibility of any consequential
damage(s).
1 Install the optional equipment (do not install the logs) – we recommend the following order:
a)LP Conversion (if applicable) – NOTE: leave the burner removed until after the liner and
accent light are installed (if applicable). If using the Omega remote, install the modulating
regulator during LP conversion.
b) Liner (if applicable)
c) Accent Light (if applicable)
NOTE: Do not install the accent light wiring harness or rheostat if using the omega remote.
NOTE: Leave the control cover removed if using the blower
d) Blower
NOTE: Do not install the rheostat if using the omega remote.
e) Remote
2 Frame the opening for the fireplace. Make sure to allow for vent installation.
3 This fireplace is designed to accommodate 1/2" drywall or 1/2” drywall with 3/8” tile (see "Nailing
Brackets" on page 17 for details). Secure the fireplace to the framing.
NOTE: If the facing is not 1/2" or 7/8" thick, follow the directions below:
Place a strip of facing material to both sides of the fireplace opening (NOTE: the strips will
be removed after the fireplace is secured). The facing thickness must represent the total
thickness of the finished facing (e.g.: If tile is to be used, include the thickness of the
backboard, tile, and tile adhesive). Insert the fireplace into the framing. Slide it back until
the front edge of the fireplace is flush with the facing material. Secure the fireplace using
the plates located along the base of the fireplace.
4 Complete the gas line installation. Complete the electrical hook-up.
5 Complete the vent installation.
6 Install the hearth (if applicable).
7 Install the drywall and facing (if applicable).
8 Install the mantel (if applicable).
9 Finalize the installation (see page 39) and install the grill or face.
NOTE: The following requirements reference various Massachusetts and national codes not contained in this document.
Requirements for the Commonwealth of Massachusetts
For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in
part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent
termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and
porches, the following requirements shall be satisfied:
Installation of Carbon Monoxide Detectors
At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gasfitter shall
observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the
gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery operated or hard
wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served
by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the
services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors.
In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired
carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.
In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall
have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day
period, a battery operated carbon monoxide detector with an alarm shall be installed.
Approved Carbon Monoxide Detectors
Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be
ANSI/UL 2034 listed and IAS certified.
Signage
A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight
(8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or
equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, “GAS VENT DIRECTLY BELOW. KEEP
CLEAR OF ALL OBSTRUCTIONS”.
Inspection
The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation
unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the
provisions of 248 CMR 5.08(2)(a)1 through 4.
Exemptions
The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:
• The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current edition of NFPA 54 as
adopted by the Board; and
• Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the
dwelling, building or structure used in whole or in part for residential purposes.
MANUFACTURER REQUIREMENTS
Gas Equipment Venting System Provided
When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or
venting system components with the equipment, the instructions provided by the manufacturer for installation of the
equipment and the venting system shall include:
• Detailed instructions for the installation of the venting system design or the venting system components; and
• A complete parts list for the venting system design or venting system.
Gas Equipment Venting System NOT Provided
When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts
for venting the flue gases, but identifies “special venting systems”, the following requirements shall be satisfied by the
manufacturer:
• The referenced “special venting system” instructions shall be included with the appliance or equipment installation
instructions; and
• The “special venting systems” shall be Product Approved by the Board, and the instructions for that system shall include a
parts list and detailed installation instructions.
A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting
instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or
equipment at the completion of the installation.
See Gas Connection section for additional Commonwealth of Massachusetts requirements.
This appliance is shipped in the top vent configuration. To change to the rear vent configuration, follow
the directions below.
NOTE : top or rear vent configuration affects several aspects of installation (framing, maximum vent rise,
maximum vent run). Make sure the vent configuration is correct prior to installation.
HINT : the diffuser is easiest to modify when converting the vent to rear-vent configuration. Refer to the
vent configuration charts to determine if the vent diffuser requires adjustment to position # 2.
Converting the Fireplace to Rear Vent Configuration
Remove the outer flue
assembly. Place the screws
and components aside (for
all subsequent steps).
Remove the cover
plate, and heat shield.
NOTE: Use a magnetic-tipped
nutdriver on these screws - take
care to prevent the screws from
falling into the fireplace.
Cover Plate
Heat Shield
Remove the inner flue assembly
and exhaust cover plate.
•The fireplace requires a 1/2" clearance from the angled sides and back of the fireplace to the framing
members. No material (insulation, framing, etc.) may be placed into this area. The stand-offs (and
nailing brackets) may contact the framing members but no material may be placed into this
area.
• Fireplace must be installed on a level surface capable of supporting the fireplace and vent.
• Fireplace must be placed directly on wood or non-combustible surface (not on linoleum or carpet).
• This heater may be placed in a bedroom.
Clearances
• Walls in front of the fireplace must be a minimum 1" to the side of the face.
• Due to the high temperature, the heater should be located out of traffic and away from furniture and
draperies.
•Fireplace must be placed so the vents below and above the glass do not become blocked.
Raised Fireplaces
NOTE: Looking Glass and Wilmington Faces require a raised fireplace - see "Dimensions" for
details.
•The fireplace (and hearth, if desired) may be placed on a platform designed to support the fireplace
(95 Lbs.) and vent.
Minimum Framing Dimensions - Top Vent Configuration
Vent Clearances:
1" to the sides, 1" below, and 3" above
48" Min.
the vent to combustibles.
The fireplace enclosure must
be a minimum 48" above the
base of the fireplace.
NOTE: Do not build into the
area above the fireplace
(except for the required
framing members).
HINT: We recommend
installing the shaded
framing after the fireplace
is in place.
Firestop
(required)
36"
13-1/2"
If using an elbow directly off the
fireplace, the vent will be centered
41-3/4" above the base of the
fireplace.
HINT: we recommend reinforcing the
upper corners of the fireplace opening.
6"
1"
5"
Route the electrical line to a position
to the right rear of the fireplace.
20-1/4"
WARNING: A cut-out for the gas line may be
required on the framing.
NOTE: The rear vent may require extra
clearance - make sure to accommodate the
vent when determining the framing.
Page 17
Nailing Brackets
There are four nailing brackets on
the sides of the fireplace. Follow
the directions below to prepare the
nailing brackets. Once in place,
nail or screw the nailing brackets to
the framing.
NOTE: There are alternative
nailing brackets on the back
corners of the fireplace if the
front brackets can not be used.
Installation(for qualified installers only)17
1/2” Facing
For installations using
1/2” facing (1/2” drywall
or other facing) fold the
lower tab out 90°.
7/8” to 1” Facing
For installations using 1”
facing (1/2” drywall with
3/8” tile, 7/8” tile, etc.)
fold the upper tab out
90°.
THIS PRODUCT MUST BE INSTALLED BY A LICENSED PLUMBER OR GAS FITTER WHEN INSTALLED WITHIN THE
COMMONWEALTH OF MASSACHUSETTS.
OTHER MASSACHUSETTS CODE REQUIREMENTS:
• Flexible connector must not be longer than 36 inches.
• Shutoff valve must be a “T” handle gas cock.
• Only direct vent sealed combustion products are approved for bedrooms or bathrooms.
• Fireplace dampers must be removed or welded in the open position prior to the installation of a fireplace insert or gas log.
• A carbon monoxide (CO) detector is required in the same room as the appliance.
• The gas line must be installed in accordance with all local codes, if any; if not, follow ANSI 223.1 and
the requirements listed below.
•The fireplace and gas control valve must be disconnected from the gas supply piping during any
pressure testing of that system at test pressures in excess of 1/2 psig. For pressures under 1/2 psig,
isolate the gas supply piping by closing the manual shutoff valve.
•Leak test all gas line joints and the gas control valve prior to and after starting the fireplace.
Fuel
•This fireplace is designed either for natural gas or for propane (but not for both). Check the sticker on the top of
the gas control valve to make sure the correct fuel is used.
Gas Line Connection
•Installation must be performed by a qualified installer, service agency or the gas supplier (In Massachusetts a
licensed plumber/gasfitter).
•If the pressure is not sufficient, make sure the piping used is large enough, the supply regulator is adequately
adjusted, and the total gas load for the residence does not exceed the amount supplied.
•The supply regulator (the regulator that attaches directly to the residence inlet or to the propane tank) should
supply gas at the suggested input pressure listed above. Contact the local gas supplier if the regulator is at an
improper pressure.
Secure the romex connector to the cover plate. Route
d
the electrical line through the cover plate and attach to
the three electrical leads. Replace the cover plate plate.
Page 22
22Installation (for qualified installers only)
Wall Switch or Thermostat Installation
Wiring Diagram (Millivolt System)
Do not connect 110-120 VAC to the gas control valve or wiring system of this fireplace. The switch must
be installed by a qualified installer.
Caution : Label all wires prior to disconnection when servicing controls. Wiring errors can cause
improper and dangerous operation.
Thermopile
Piezo Igniter
On/Off Switch (on fireplace)
Red
Brown
Thermocouple
Copper Co-Axial
Wire
Orange
Red
White
Optional Wall Switch,
Thermostat, or
Remote Control
Spark Electrode
Pilot Hood
Installation
1. Attach the included wire to the gas control valve.
Attach the two wires to the top and
bottom posts on the gas control
valve (orientation does not matter).
2. Determine a location for the wall switch or thermostat (maximum 25' long). Route the wire through the
grommet on the right side of the fireplace (next to the electrical junction box).
3. If using a thermostat, attach it following the manufacturer’s instructions. If using a wall switch, attach
following the directions below.
NOTE : Set the on/off switch on the appliance to "OFF" to control the appliance with the wall switch or thermostat.
Insert the wire
a
through the back of
the mounted
junction box (your
junction box may
look different).
Expose 1/2" of
each wire. Secure
the wires to the
posts on the side of
the on/off switch
(orientation does
not matter).
From
Appliance
Standard
Screwdriver
Carefully pack the wires into the
b
junction box. Attach the switch
to the junction box. Attach the
switchplate to the switch.
•The gas appliance and vent system must be vented directly to the outside of the building, and never
be attached to a chimney serving a separate solid fuel or gas-burning appliance. Each direct vent gas
appliance must use it's own separate vent system.
• In addition to the requirements listed here, follow the requirements provided with the vent.
• A firestop is required whenever the vent penetrates a wall, floor, or ceiling (passes through framing
members). Use the included firestop. It incorporates a 3" clearance above, 1" clearance below and to
the sides of the vent.
•Always use the high-wind termination.
Vent Clearances
•The vent must maintain the required clearance to combustible materials to prevent a fire. Do not fill air
spaces with insulation.
Sides1"
Above3"
Below Horizontal or 45° Section1"
Use a firestop when
passing through any
Min. 3" Clearance
Above the Vent
wall (WARNING: some
firestops provide a 1"
clearance above the
vent -- 3" is required for
this heater).
Min. 1" Clearance to
the side of vent
1" Clearance to the sides
after the first firestop.
Use a firestop whenever
passing through a
ceiling, enclosure or
floor penetration.
Altitude Considerations
•This heater has been tested at altitudes ranging from sea level to 6,000 feet. In this testing we have found that
the heater, with its standard orifice, burns correctly with just an air shutter adjustment.
•Failure to adjust the air shutter properly may lead to improper combustion which can create a safety hazard.
Consult your dealer or installer if you suspect an improperly adjusted air shutter.
• Rear vent configurations use 8" diameter Simpson Dura-Vent Model GS or Pro vent.
• Top vent configurations use 8" or 6-5/8" diameter Simpson Dura-Vent Model GS or Pro vent. If using
6-5/8" diameter vent, attach the 8" to 6-5/8" reducer (Travis part # 98900165) directly to the fireplace
(see the illustration below).
•Installation instructions for Simpson Dura-Vent may be found at www.duravent.com
6-5/8" Diameter Vent
(minimum 12" vertical rise)
Reducer - # 98900165
Vent Installation
• Slide the vent sections together and turn 1/4 turn until the sections lock in place.
• Screws are not required to secure the vent. However, three screws may be used to secure vent
sections together if desired.
•High temperature sealant is recommended at the appliance starter section connection (use hightemperature silicone or Mill-Pac®).
•If disassembly is required, at time of re-assembly check to see if the vent creates a tight fit. If it does
not, apply high temperature sealant to the joints of the affected sections.
• Horizontal sections require a 1/4" rise every 12" of travel
• Horizontal sections require non-combustible support every three feet (e.g.: plumbing tape)
•An exhaust restrictor and diffuser are built into the appliance to adjust the flow rate of intake air and
exhaust gases. Depending upon the vent configuration, you may be required to adjust the restrictor
and/or diffuser . The charts for acceptable vent configurations detail the correct vent restrictor and
diffuser positions.
Exhaust Restrictor Adjustment
Adjustment
Plate
Adjustment Bracket
This restrictor is in position 1
(factory setting).
Restrictor Position
To adjust, lift the adjustment plate and
pull it forward
To Access the Restrictor:
Remove the face (with the stove
cool).
This restrictor is in position 3.
To Adjust the Restrictor:
1
Determine the correct restrictor position (see the charts under "Approved
Vent Configurations" - the factory position is #1).
2
Lift up the adjustment plate and move it so the correct notch falls into the
slot on the adjustment bracket.
Certain vent configurations require the diffuser plate to be adjusted (refer to the approved vent
configuration charts for details). Position # 1 is stock (flat). Position # 2 is bent. See the directions below
to change the diffuser to position #2.
If the diffuser is required to be in position # 2, you may wish to adjust the diffuser while converting the
appliance to rear-vent configuration.
Firebox Roof
NOTE: To better
access the diffuser,
DIFFUSER SIDE VIEW
Before (Stock - Position # 1)
Back Wall of Firebox
you may wish to move
the restrictor to the # 1
postion.
Remove the diffuser.
Bend the round portion of the
diffuser 90° (position # 1).
Horizontal length is calculated by adding
both lengths of horizontal run
(Horizontal Length = H1 + H2).
This is considered a
vertical elbow
Page 28
28Installation (for qualified installers only)
Top Vent Configuration with Vertical Termination
•The termination must fall within the shaded area shown in the chart. Use the indicated restrictor and
diffuser positions.
• Up to four elbows (45° or 90°) may be used.
• Only one horizontal elbow may be used (see illustration at the bottom of the page).
• May use 8" or 6-5/8" diameter vent (see page for 24 details).
40' (max)
Restrictor Position # 3
Diffuser Position # 1 (stock)
NOTE:
Two 45° elbows
may be used.
30 feet
25 feet
20 feet
15 feet
10 feet
0 feet
Restrictor Position # 2
Diffuser Position # 1 (stock)
Restrictor Position # 1 (stock)
Diffuser Position # 1 (stock)
5 feet
NOTE:
Restrictor positions are
based upon lab tests.
The ideal restrictor
position may vary
slightly, especially when
the termination is near a
demarkation line.
10 feet
14' (max)
40' (max)
35 feet35 feet
30 feet
25 feet
20 feet
15 feet
10 feet
NOTE:
One 45° or 90° elbow may
be used between horizontal
sections. Horizontal length
is caculated by adding each
horizontal run together.
NOTE:
Horizontal sections require a
1/4" rise every 12" of travel.
6' (min)6' (min)
0 feet
5 feet
0 feet
5 feet
10 feet
5 feet
0 feet
14' (max)
H2
This is considered a horizontal
elbow (it does not matter
whether it turns right or left).
Horizontal length is calculated by adding
both lengths of horizontal run
(Horizontal Length = H1 + H2).
Horizontal sections require a 1/4" rise
every 12" of travel.
H2
Horizontal length is calculated by adding
both lengths of horizontal run
(Horizontal Length = H1 + H2).
This is considered a
vertical elbow
Page 30
30Installation (for qualified installers only)
Rear Vent Configuration with Vertical Termination
•The termination must fall
within the shaded area
shown in the chart. Use the
indicated restrictor and
diffuser positions.
•Up to four elbows (45° or
90°) may be used.
•Only one horizontal elbow
may be used (see
illustration at the bottom of
the page).
• Use 8" diameter vent.
40' (max)
Restrictor Position # 3
Diffuser Position # 1 (stock)
30 feet
0 feet
5 feet
NOTE:
Restrictor positions are
based upon lab tests.
The ideal restrictor
position may vary
slightly, especially when
the termination is near a
demarkation line.
Restrictor Position # 2
Diffuser Position # 1 (stock)
10 feet
14' (max)
40' (max)
35 feet35 feet
30 feet
NOTE:
Two 45° elbows
may be used.
NOTE:
One 45° or 90° elbow may
be used between horizontal
sections. Horizontal length
is caculated by adding each
horizontal run together.
NOTE:
Horizontal sections require a
1/4" rise every 12" of travel.
25 feet
20 feet
15 feet
Restrictor Position # 1 (stock)
Diffuser Position # 1 (stock)
10 feet
6' (min)6' (min)
5 feet
0 feet
0 feet
5 feet
10 feet
25 feet
20 feet
15 feet
10 feet
5 feet
0 feet
14' (max)
This is considered a horizontal
elbow (it does not matter
whether it turns right or left).
It may be a 90° or 45° elbow.
NOTE: Vinyl surfaces require 24"
NOTE: Clearance in accordance with local installation codes and the requirements of the gas supplier.
FMinimum 12" clearance below a veranda, porch, deck or balcony
NOTE: Permitted only if veranda, porch, deck, or balcony is fully open on a minumum of two sides beneath the floor.
NOTE: Clearance in accordance with local installation codes and the requirements of the gas supplier.
GMinimum 48" clearance from any adjacent building
HMinimum 84" clearance above any grade when adjacent to public walkways or driveways
NOTE: may not be used over a walkway or driveway shared by an adjacent building
IMinimum 9" clearance to any nonmechanical air supply inlet to the building or the combustion air inlet to any other
appliance.
JMinimum 36" clearance above any mechanical air supply inlet if within 10’ horizontally
KMinimum 36" from the area above the meter/regulator (vent outlet) - this extends 15’ above the regulator
NOTE: Clearance in accordance with local installation codes and the requirements of the gas supplier.
LMinimum 36" from the meter/regulator (vent outlet)
NOTE: Clearance in accordance with local installation codes and the requirements of the gas supplier.
MMinimum 12” above the roof line (for vertical terminations)
NMinimum 24” horizontal clearance to any surface (such as an exterior wall) – for vertical terminations
Roof
Surface
11” Min.
6” Min.
Roof
Eaves
E
N
M
E
K
G
NOTE: Measure clearances to the nearest edge of the exhaust hood.
•Use the vinyl siding standoff when installing on an exterior with vinyl siding.
•Vent termination must not be located where it will become plugged by snow or other material
NOTE: Looking Glass and Wilmington Faces require a raised fireplace – see Face Dimensions on page 33
for details.
Floor Mounted
Fireplaces
Do not build a hearth or other
item above the baseplate (this
area must remain clear for the
access door).
If installed in front of carpet or
other flooring, the fireplace must
be raised so the base of the unit is
above the carpet surface or
flooring material.
Raised
Fireplaces
WARNING:
A non-combustible hearth is not required. However, if
the heater is installed next to the floor, we recommend
a hearth to protect the flooring surface from
discoloration or other negative impact from the heater.
A hearth is not required
when the fireplace is
raised above the flooring
surface.
NOTE: The combustible area above the facing must not protrude more than 3/4" from the facing. If it
does, it is considered a mantel and must meet the mantel requirements listed in this manual.
Face Dimensions
FaceHeightWidthBottom of FaceInstallation Notes
Arched Faces35-1/2”21-1/8”Flush w base of fireplaceArched top is 25-3/4” radius
Bungalow, T. of L.35-3/8”21-1/8”Flush w base of fireplace
Vict. Lace35-1/2”21-1/8”Flush w base of fireplace
Looking Glass36-3/4”23-1/2”1-1/4” BELOW base of fireplaceCast face is approx. 2” thick
Wilmington36-3/4”22-1/8”1-1/4” BELOW base of fireplace
Facing Under 1” Thick
Any material that protrudes
more than 3/4” in front of the
facing is considered a mantel
and must meet the mantel
requirements in this manual.
NOTE: The facing tucks
behind the flanges.
Recommended Order of Installation We
recommend installing the facing (drywall, tile)
under the notch at the front of the fireplace
(“a”) - then install the sides and top (“b” and
“c”)
4-7/8”
3-1/4”
30-1/2”
(approx.)
c
The wall trim comes off,
allowing the installer to cover
b
3/8”
a
NOTE The facing tucks under the notch at the front
of the fireplace (3/8” above the base of the fireplace).
the drywall edge below the
front edge of the fireplace.
Facing Over 1” Thick
•Facing that protrudes in front of the face above the face (or within 1/2” of each side) must be
made of non-combustible materials.
NOTE A 3/8" gap above the face is required for face installation and removal.
Recommended Order of Installation We
recommend installing the facing (drywall, tile)
under the notch at the front of the fireplace
(“a”) - then install the sides and top (“b” and
“c”)
c
b
NOTE The facing tucks under the
notch at the front of the fireplace
(3/8” above the base of the
fireplace).
Top View - Drywall Facing
Side View - Drywall Facing
Fireplace
Nailing Bracket
Face
White Tape Gasket
(attached to fireplace)
Fireplace
a
Drywall, paneling, or other
facing (combustible or noncombustible).
NOTE: The facing should tuck
behind the wall trim, thus
concealing the top of the facing
and the base of the fireplace.
NOTE: The fireplace is shifted back
on the shelf to accommodate the
facing thickness.
Facing (drywall, paneling, or other
material - combustible or noncombustible).
Page 36
36Installation (for qualified installers only)
Facing Detail – Tile Facing
Top View - Tile Facing
Side View - Tile Facing
NOTE: The fireplace is shifted back
on the shelf to accommodate the
facing thickness.
Fireplace
Framing
Fireplace
NOTE: Make sure to use the correct nailing bracket for this type
of facing (see “Nailing Bracket” for details). For this example the
facing is 7/8" thick (3/8" tile plus 1/2" drywall). The framing is
positioned 1" behind the front of the fireplace.
Drywall
Tile
NOTE: The facing should tuck
behind the wall trim, thus
concealing the top of the facing
and the base of the fireplace.
Tile
Drywall
3-d View - Tile Facing
The wall trim is removed for
installation and replaced to cover the
top edge of the facing.
Recommended Order of Installation We
recommend installing the tile under the notch at
the front of the fireplace then working your way
up.
The facing contacts
the side of the
fireplace.
Note how the facing
tucks underneath the
wall trim.
The side facing should be spaced 1/8"
from the face (3/8” from the side of the
fireplace).
Page 38
38Installation (for qualified installers only)
Mantel Requirements
• The illustration below details mantel clearances and maximum mantel depth.
• Any material that protrudes more than 3/4” from the non-combustible facing is considered a mantel
and must meet the mantel requirements.
Maximum Mantel Depth (b)
0” 1” 2” 3” 4” 5” 6” 7” 8” 9” 10” 11” 12”
Mantel
Height
Above
Face (a)
9”
8”
7”
6”
5”
4”
3”
2”
1”
0”
Mantel
(combustible or non-combustible)
a
See “Face Dimensions”
If you have a tapered mantel, measure the
mantel height at the point where it
protrudes 3/4” in front of the face.
b
Combustible mantel columns (legs) that
protrude more than 3/4” from the glass
frame must meet the sidewall clearance (1”
from the face). If they protrude 3/4” or less,
they do not have a minimum clearance.
Non-combustible mantel columns do not
have a minimum clearance.
Finalizing the Installation (for qualified installers only)39
Steps for Finalizing the Installation
1. Remove the glass (see page 41).
NOTE :If using propane (LP) convert the appliance prior to installing the logs.
2. We recommend you purge the gas line at this time (with the glass removed). This allows gas to be
detected once it enters the firebox, ensuring gas does not build up.
3. Install the logs (see page 43).
4. Turn on the gas to the fireplace. Turn on gas to the heater. Leak test all gas joints prior to starting the
appliance. Start the pilot.
Starting the Pilot Flame
WARNING :When lighting or re-lighting the pilot, the glass must be removed (see
page 41).
aRemove the glass (see page 41 for details).
bPush the gas control knob in slightly and turn it to the "OFF" position. The knob will not turn from
"ON" to "OFF" unless the knob is depressed slightly. Wait five minutes to let any gas that may have
accumulated inside the firebox escape. If you smell leaking gas, follow the directions on the cover "IF
YOU SMELL GAS".
cTurn the gas control knob to the "PILOT" position and press the knob in, this will allow gas to flow to
the pilot light. Press the button on the pilot igniter repeatedly until you see the pilot light.
WARNING: If the pilot does not light after 15 seconds, release the knob and call
your dealer for service. Do not attempt to light pilot until service has
been performed.
NOTE:
You may wish to remove the log set to gain a better view of the pilot (see page 43).
dKeep the gas control knob depressed for 30 seconds once it is lit.
eRelease the gas control knob. If the pilot goes out, repeat step C. If the pilot refuses to stay lit, call
your dealer for service. With the pilot lit, proceed to step “f”.
fReplace the glass.
gTurn the gas control knob counter-clockwise to "ON". The pilot is now lit and the heater can be turned
on and off.
5. Check the pilot flame following the directions below.
Pilot Flame Inspection
The pilot flame should look like the illustration below. Adjust the pilot flame if necessary.
To adjust the pilot flame, turn this screw. Clockwise
lowers the flame while counter-clockwise raises it.
6. Start the main burner (the main burner circuit is detailed on page 22). Leak test all gas joints again.
The pilot flame must contact the thermocouple and
thermopile (see the illustration below). Adjust the pilot up or
down as necessary.
Page 40
40Finalizing the Installation (for qualified installers only)
7. Check the air shutter following the directions below.
Air Shutter Adjustment
Let the heater burn for fifteen minutes (make sure the logs and glass are in place). The flames should be
yellow with no sooting. Adjust the air shutter, if necessary, to achieve the correct looking flame.
ADJUSTING THE AIR SHUTTER
Moving the air shutter control to the right
gives the flame less air (closed) - making it
more orange. Moving it to the left gives the
flame more air (open), making it more blue.
For fine adjustments use a screwdriver to
tap the air shutter.
NOTE: If the air shutter is all the way
open, yet the flames remain sooty, shut
off gas to the fireplace and contact a
qualified gas service technician.
Correct
Flames should be blue at the
base, yellow-orange on the top.
Air Shutter
Control
Phillips
Screwdriver
NOTE: The logs must be installed correctly to
monitor the flame while adjusting the air shutter.
Not Enough Air
If the flames are too tall or sooty on the
ends, open the air shutter.
More Air
Too Much Air
If the flames are all blue and
short, close the air shutter.
Less Air
8. Turn the flame adjust knob to its highest position - the flames should not contact the top of the
firebox. Check the flame on low position. The flames should burn off of each burner hole. If the
heater does not work correctly, contact your Travis dealer for a remedy.
9. Give this manual to the home owner for future reference and fully explain operation of this heater. For
comprehensive operating and maintenance instructions, refer to the Owner's Manual (part # 100-
01186).
ACID WASH WARNING: Before installing the faceplate, make sure any masonry that has been treated
with acid wash has been properly neutralized (this is used primarily with brick faces). Acid wash (muriatic
acid) is used to remove excess mortar. If not properly neutralized with an ammonia solution, the plated
face may develop a permanent tarnish when the acid evaporates over time. Contact your dealer if
uncertain your facing has been properly neutralized.
42Finalizing the Installation (for qualified installers only)
Glass Frame Removal and Installation (continued)
The latch can come loose from glass frame anchor. This occurs when it is turned 1/4 turn when it is
disengaged. Follow the directions below to re-install the latch if it becomes loose.
Hold the latch at an angle and insert it into the slot on the glass frame anchor.
Latch
NOTE: this slot may be at a
different angle than illustrated.
Top of
Firebox
Glass Frame
Anchor
Note how the washer on the latch fits behind the flange on the
glass frame anchor.
Once fully inserted, turn the latch until it is upright.
Finalizing the Installation (for qualified installers only)43
Log Set Installation
Rear Log Installation
Place the rear log with the left side flush to the edge of the burner and the right side flush to the metal
deflector on the back edge of the burner. The bottom edge of the log should be located behind the
burner ports (see the illustration below).
CROSS-SECTIONAL VIEW
Burner
Rear Log
Make sure the ledge on the burner
lines up with stepped-down portion of
the rear log.
Right Rear Log Installation
Place the right rear log on top of the rear log. When placed correctly there is a minimal gap between the
two logs. Make sure the bottom is placed so no burner ports are blocked.
NOTE: Make sure the
right rear log does not
rest against the back
of the firebox (or liner).
If it does, it will block
the light from the
optional accent light,
creating a large
shadow.
44Finalizing the Installation (for qualified installers only)
Right Front Twig Installation
Place the right front twig as shown below. The bottom of the twig is placed one inch to the right of the
center screw on the burner. The top of the twig rests in the groove on the right rear log.
Left Front Twig Installation
Place the left front twig as shown below. Note how both ends of the twig are directly over the center and
left hand screw on the burner
These two projections
on the bottom of the
twig insert into screw
holes on the burner.
Finalizing the Installation (for qualified installers only)45
Left Front Twig Installation (continued)
Double check that the front twigs are not blocking any burner ports.
Place an ember
over this screw.
Log Installation Overview
Correct view of complete log installation.
Place embers in the
firebox corners and
along the front edge
of the burner. Do not
place embers over
burner holes or allow
the embers to block
airflow.
Install the conversion kit prior to installing the gas line to ensure proper gas use.
1Remove the glass (see page 41). Remove the logs and coals (if installed - page 43)
2Remove the burner (see illustration below).
Lift the pilot hood off the pilot
a
assembly (you may need to
pull hard to remove).
b
Lift up on the left
side of the burner,
then slide the
burner to the left
and up to remove.
Burner Replacement:
Make sure the orifice on the firebox
floor inserts into the fitting on the
bottom of the burner.
The mixing tube slides
After replacing the burner
re-attach the pilot hood.
onto the orifice.
Make sure the burner is fully seated and pilot hood lines up with the
burner holes at the rear edge of theburner.
7Make the gas line connection, bleed the gas line (if applicable), start the heater and thoroughly leak-
test all gas connections and the gas control valve. Check the pilot. Adjust if necessary.
WARNING :When lighting or re-lighting the pilot, the glass must be removed (see page 41).
To adjust the pilot flame, turn this screw (NOTE: if totally
unscrewed gas will come out of this port). Clockwise
lowers the flame while counter-clockwise raises it.
Aromatherapy Modification
If you are using the aromatherapy option with the 21 TRV, you will need to bend up the mounting
flange on the front of the fireplace (see the illustration below). The aromatherapy extension assembly
attaches to this flange.
Standard
Screwdriver
The pilot flame must contact the thermocouple and
thermopile (see the illustration below). Adjust the pilot up or
down as necessary.
If you are using the Omega remote option with the 21 TRV, follow the directions below for installing the
receiver and attaching the accent light leads (if applicable – see the following page).
Receiver Installation
Attach the two wires labeled "SOLENOID
OPTIONAL" to the modulating regulator
e
(orientation does not matter).
SOLENOID
(OPTIONAL)
Control Cover
Make sure the power
is disconnected!
a
Disconnect the control cover and
pull it forward (leave the wires
attached). Remove and discard
the regulator knock-out (use tin
snips or wire cutters).
d
Replace the control cover.
b
Remove the jumper connector on
the wiring harness and place it near
the gas control valve (it is required if
you wish to remove the remote).
Attach the molex connector from the
receiver to the molex connector on
the appliance.
c
Place the receiver to the right of the gas control valve (it is a
very tight fit). Make sure the wires do not contact the
burner or any moving parts (use lock ties if necessary).
NOTE: When installing the receiver, make sure to place the
receiver with the "Learn" button in a forward position. Before
replacing the control cover, make sure to verify the remote
works correctly. Once the control cover is installed, the
"Learn" button can not be readily accessed.
IF USING AN ACCENT LIGHT
Follow the directions listed under
“Accent Light Receiver Connection”.
IF NOT USING AN ACCENT LIGHT
Secure the two white wires, making
sure they do not contact the burner or
any moving parts.
If using the accent light with an Omega remote, you will want to remove and discard the accent light
rheostat and wiring harness. Plug the wiring harness (included with the blower) into the junction box
on the fireplace. The leads from the accent light are connected to the leads from the Omega remote.
The molex connector on the blower wiring harness
plugs into the molex connector on the junction box.
Accent Light Leads
Remote Accent Light Leads
(orientation does not matter)
The accent light rheostat and wiring harness are not
needed when using the Omega remote.