Traulsen RET232NUT-HHS Service Manual

Traulsen Refrigeration
SERVICE MANUAL #05
Instructions For The Troubleshooting And
Repair Of Traulsen R-Series
Even-Thaw Refrigerator Models
RET232NUT-FHS & RET232NUT-HHS
-NOTICE-
Reproduction or other use of this Manual, without the express written consent of Traulsen, is prohibited.
FORM NUMBER TR35845 - REVISED. 12/04
TABLE OF CONTENTS
I. THE SERIAL TAG 1
II. GENERAL INFORMATION
a. Introduction 2 b. Model Designations 2 c. Wiring Diagrams 2 d. Installation - See Owner’s Manual 2 e. Cleaning 2 f. Tools 2 g. Refrigeration System Theory Of Operation 2 h. Air Flow Requirements 3 i. Control Location 3 j. Specifications 3 k. Operating Data Chart 3
III. REMOVAL & REPLACEMENT OF PARTS
a. Standard Incandecent Lights 3 b. Louver Assembly 3 c. Evaporator Housing Cover 4 d. Removing The Door 4 e. Door Hinge 4 f. Snap-In Door Gaskets 5 g. Condensate Drain Pan 5 h. Door Breaker Caps 5
IV. REPLACING THE...
a. CONDENSER FAN MOTOR AND/OR BLADE 6 b. CONDENSER COIL 6 c. COMPRESSOR 7 d. DOOR BREAKER CAPS 7
V. SERVICE PROCEDURES & ADJUSTMENTS
a. System Access 8 b. Sweat On Piercing Valves 8 c. Refrigerant Leak Check 8 d. Evacuating System 8-9 e. Charging System 9 f. System Clean-up 9-10 g. Heater Test/Door Perimeter Heater 10 h. Heater Test/Defrost Heater 10
VI. ELECTRICAL OPERATION
a. Sequence Of Operation/Normal Operation 11 b. Sequence Of Operation/Defrost Mode 11 c. Component Function 11
VII. WIRING DIAGRAMS 12
VIII. PARTS LISTING 13
IX. TROUBLESHOOTING 14
For Questions Please Contact Traulsen Service At:
(800) 825-8220
FORT WORTH, TX.
SERIAL MODEL VOLTS Hz PH
TOTAL CURRENT AMPS MINIMUM CIRCUIT AMPS MAXIMUM OVERCURRENT PROTECTION AMPS LIGHTS WATTS HEATERS AMPS
REFRIGERANT TYPE OZ DESIGN PRESSURE HIGH LOW
REFRIGERANT TYPE OZ DESIGN PRESSURE HIGH LOW
370-60294-00 REV (A)
I. THE SERIAL TAG
The serial tag is a permanently affixed sticker on which is recorded vital electrical and refrigeration data about your Traulsen product, as well as the model and serial number. This tag is located in the upper right interior compartment on all reach-in/pass-thru and roll-in/roll-thru refrigerator, freezer and dual-temp models.
READING THE SERIAL TAG
Serial = The permanent ID# of your Traulsen
Model = The model # of your Traulsen
Volts = Voltage
Hz = Cycle
PH = Phase
Total Current = Maximum amp draw
Minimum Circuit = Minimum circuit required
Lights = Light wattage
Heaters = Heater amperage
Refrigerant = Refrigerant type used
Design Pressure = High & low side operating
pressures and refrigerant charge
Agency Labels = Designates agency listings
-1-
II. GENERAL INFORMATION
II. a - INTRODUCTION: This manual applies to the following Traulsen product types:
R-Series Reach-In Even-Thaw Models
II. b - MODEL DESIGNATIONS: The first letter indicates the series, “R”
R = Stainless Steel Exterior & Interior
The next two letters indicate the product type
ET = Even-Thaw Refrigerator
The first number indicates the number of sections
2 = Two Section
The next two numbers indicates the product depth
32 = 32 Deep Over Body (not including hardware)
The next letter indicates the product width
N = 2 Section: 52-1/8
If UT is present the product is self-contained. If UT is not present the product is remote.
II. c - WIRING DIAGRAM: Refer to the wiring diagram for any service work per­formed on this unit. The copy contained in this book­let is for standard 115/60/1 voltage, self-contained, incandescent light equipped models only. Other volt­ages and feature/options sets are not necessarily covered by the diagrams contained within. Should you require a wiring diagram for a specific unit, please contact Traulsen Service at (800) 825-8220, and provide the model and serial number of the unit involved.
II. d - INSTALLATION: Generally R-Series refrigeration products are in­stalled by the dealer or others contracted by the dealer or owner. Detailed installation instructions are included with each unit.
TOOL REQUIREMENTS:
II. f ­For most jobs a standard set of hand tools, a VOM and AC current tester, along with a temperature tester or thermometer are adequate. However in some cases the following additional tools may be required as well:
Refrigeration Guage Manifold
Refrigeration Reclaiming Equipment
Acetylene Torch
Anti-Static Grounding Kit (TL 84919)
Nitrogen Bottle With Gauges
Thin 5/16 Open End Wrench
Refrigerant Reclaim Unit
II. g -
REFN SYSTEM - THEORY OF OPERATION:
The refrigeration system is the mechanism whereby heat is transferred from the cabinet to the outside air. It works under the principle that the heat moves from hot to cold as it tries to establish equilibrium.
The temperature control control signals a need for heat to be removed from the cabinet. The compressor be­gins by compressing the refrigerant gas as it is dis­charged. The high pressure refrigerant now circulates through the condenser, removing heat from the refrig­erant and condensing it into a liquid. From there the refrigerant flows to the filter drier which removes all traces of moisture and particles from the system.
After the filter drier, the refrigerant passes through a “metering device.” Traulsen uses a thermostatic ex­pansion valve to regulate the flow of refrigerant into the evaporator coil.
In the evaporator coil, heat is transfered from the cabi­net to the refrigerant, which changes from a cold liq­uid to a warm low pressure gas. When the desired cabinet air temperature has been reached, the tem­perature control shuts off the compressor.
II. e - CLEANING: Detailed cleaning instructions are included with each unit, however special care MUST be given to the con­denser coil. The condenser coil must be cleaned at a minumum of every six months. Your particular application may require more frequent intervals. This can be done with a vacuum cleaners using a brush attachment, or a stiff brush or wisk broom. For more information please refer to
the Owners Manual sup-
plied with the unit.
Your Traulsen unit may incorporate a washable, re­usable wire mesh filter on the condensing unit. Clean it with soap and water or in a dishwasher.
Fig. 1 - The Traulsen Refrigeration System
-2-
II. GENERAL INFORMATION (cont’d)
II. h - AIR FLOW REQUIREMENTS: In order to assure optimum performance, the condens­ing unit of your Traulsen unit MUST have an adequate supply of air for cooling purposes. Therefore, the op­erating location must either have a minimum of 12 clearance overhead of the condensing unit or allow for unrestricted air flow at the back of the unit. The louver panel must remain free and clear of obstruc­tion. The condenser coil must be kept clean (see II. e).
Please note that clearance of at least 12above is re­quired in order to perform certain maintenance tasks.
III. REMOVAL & REPLACEMENT OF
BASIC PARTS
WARNING: DISCONNECT THE ELECTRICAL POWER
TO THE MACHINE AT THE MAIN CIRCUIT BOX.
PLACE A TAG ON THE CIRCUIT BOX INDICATING
THE CIRCUIT IS BEING SERVICED.
III. a - STANDARD INCANDESCENT LIGHTS: Lights are usually located in the front center of the unit, mounted on the interior top. To replace the light bulb, first remove the light cover by squeezing the sides to­gether, which releases the tabs from the holding slots. Replace the burned out light bulb with a similar type appliance bulb.
II. i - CONTROL LOCATION: On all Even-Thaw refrigerator models, the temperature control is located on the evaoprator housing behind the louvers.
II. j - SPECIFICATIONS:
R-Series Even-Thaw Refrigerator
ET232N
Horsepower 1/2 HP
Condensing Unit - BTU/HR 4750
Condensing Unit Amp Draw 10.0
Fan, Lights, Etc. Amp Draw 5.0
Refrigerant R-404A
Refrigerant Charge (oz.) 20
II. k - OPERATING DATA CHART:
Even-Thaw Models (Cabinet Temperature Set at 38°F) AMBIENT 70°F 100°F
SUCTION PRESSURE 45 PSIG 50 PSIG
SUCTION TEMPERATURE 11°F15°F
DISCHARGE PRESSURE 240 PSIG 360 PSIG
DISCHARGE TEMPERATURE 100°F 130°F
To replace the light cover, squeeze the sides together and reinsert tabs in to the holding slots and release to lock in place.
III. b -
LOUVER ASSEMBLY: To remove the louver assembly, first remove the two screws located on both sides at the bottom of the lou­ver assembly (see figure 2). Once the screws are re­moved, the panel can be pivoted upwards allowing full access to the front facing condenser (see figure 3).
Fig. 2
Remove Screws
Fig. 3
Lift-Up Louvers
When finished, lower the louver assembly and replace the screws to hold it in place.
-3-
III. REMOVAL & REPLACEMENT OF BASIC PARTS (cont’d)
WARNING: DISCONNECT THE ELECTRICAL POWER TO THE MACHINE
AND FOLLOW LOCKOUT/TAGOUT PROCEDURES.
EVAPORATOR HOUSING COVER:
III. c ­Remove the screws on top of the evaporator housing. Lift-off the housing cover to complete removal (see figure 4).
Fig. 4
Lift-Off Cover
Reverse the procedure when done to reinstall, mak­ing sure that the gasket forms a tight seal.
III. d -
REMOVING THE DOOR: The door can be easily removed from the cabinet. To remove the door, remove the plug at the bottom of the top hinge. Inside the hinge there is a small screw which secures the door in place. Remove this with a flat head screwdriver and the door can then be lifted off the hinge (see figure 5).
III. e - DOOR HINGE: The hinge can be easily removed from the cabinet. To remove the door, follow the instructions listed in sec­tion III. d.
To remove the door portion of the hinge from the door, lift off the hinge cover and then remove the three Phillips head screws which secure the hinge in place on the door (see figure 6). To remove the cabinet por­tion of the hinge, remove the three Phillips head screws which hold it in place. On solid door units, the top hinge(s) contains a microswitch for controlling the interior lighting.
Fig. 6
To reassemble the hinge reverse the previous proce­dure.
Fig. 5
-4-
Loading...
+ 10 hidden pages