Traulsen RBC50, RBC100, RBC200, RBC400, RBC200RT User Manual

...
Quality Refrigeration
OWNER’S MANUAL
Instructions for the installation, operation,
and maintenance of all Blast Chill Models:
Undercounter Model: RBC50 Reach-In Model: RBC100 Roll-In Models: RBC200 & RBC400 Roll-Thru Models: RBC200RT & RBC400RT
This Traulsen unit is built to our highest quality standards. We build our refrigerators, freezers and heated cabinets this way as a matter of pride. This philosophy has made T raulsen the leader in commercial refrig­eration since 1938. We thank you for your choice and confidence in T raulsen equipment and we know you will receive many years of utility from this equipment.
All Traulsen units are placed on a permanent record file with the service department. In the event of any future questions you may have, please refer to the model and serial number found on the name tag affixed to the unit. Should you need service, however, call us on our toll free number, 800-825-8220 between 7:30 am and 4:30 pm CST, Monday thru Friday. It is our pleasure to help and assist you in every possible way.
INSTALLER
COMPLETE THE FOLLOWING INFORMATION PRIOR TO UNIT INSTALLATION
INITIAL START DATE: SERIAL NO. MODEL TYPE: COMPANY/INDIVIDUAL NAME: INSTALLER:
RBC DOC REV. 12/02 P/N 375-60180-00
TABLE OF CONTENTS
I. The Serial Tag Page 1 II. Receipt Inspection Page 2 III. Installation
a-Location Page 2 b-Packaging Page 2 c-Wiring Diagram Page 2 d-Installing Legs or Casters Page 2 e-Cord & Plug Page 3 f-Electrical Requirements Page 3 g-Proper Clearances Page 3 h-Condensate Removal Page 4 i-Remote Unit BTU Requirements Page 4 j-Remote Unit Cut-Out Settings Page 4 k. Sealing Roll-In/Roll-Thru Units Page 4 l. Installing RBC50 Control Panel Page 5 m. Attaching RBC400 Units Together Page 5
IV. Care & Maintenance
a-Cleaning The Condenser Page 6 b-Cleaning The Exterior Page 6 c-Cleaning The Interior Page 6 d-Installing Printer Paper Page 6
V. Other
a-Service Agency Check & Start-Up Page 6 b-On-Site Blast Chill Training Page 6 c-Service Information Page 6/7 d-Demonstrations Page 7 e-Blast Chill Video Page 7 f-Blast Chill Data Communications Kit Page 7
VI. Blast Chill Operation
a-Loading Food Into Pans Page 7 b-Covering Foods Page 7
VI. Blast Chill Operation (cont’d)
c-Grouping Foods To Form Batches Page 7 d-Maximum Load Per Batch Page 8 e-Pan Placement In Unit Page 8 f-Food Probe Placement Page 9 g-Example Batches For RBC50 Page 9 h-Example Batches For RBC100 Page 10 i-Example Batches For Roll-In/Roll-Thru Models Page 11
VII. Operating The Blast Chill Control
a-Operating Modes Page 12 b-Continuous Batching Page 13 c-Probe Temperatures Page 13 d-Lock Function Page 13 e-Unlock Function Page 13 f-Defrost Function Page 13 g-Printout Data Page 13 h-Resetting Date & Time Page 13 i-Programming A New Batch Page 13/14 j-Control Panel Configuration Page 15 k-Probe Temperature & Alarm Warnings Page 16
VIII. Understanding Printouts
a-Current Data Printout Page 16 b-Constant Chill Cycle - Batch Data Page 16 c-Blast Chill Cycle - Batch Data Page 17 d-72-Hour Data Log Page 18
e-Food Probe Failure Warnings Page 19 IX. Trouble Shooting Guide Page 20 X. Wiring Diagrams Page 21-24 XI. Warranty Information Page 25 XII. Parts List Page 26 XIII. Index Page 26
FORT WORTH, TX.
SERIAL MODEL VOLTS Hz PH
TOTAL CURRENT AMPS MINIMUM CIRCUIT AMPS MAXIMUM OVERCURRENT PROTECTION AMPS LIGHTS WATTS HEATERS AMPS
REFRIGERANT TYPE OZ DESIGN PRESSURE HIGH LOW
REFRIGERANT TYPE OZ DESIGN PRESSURE HIGH LOW
370-60294-00 REV (A)
R
R
I. THE SERIAL TAG
The serial tag is a permanently affixed sticker on which is recorded vital electrical and refrigeration data about your Traulsen product, as well as the model and serial number. This tag is located inside the door on the right interior wall of the cabinet.
READING THE SERIAL TAG
Serial = The permanent ID# of your Traulsen
Model = The model # of your Traulsen
Volts = Voltage
Hz = Cycle
PH = Phase
Total Current = Maximum amp draw
Minimum Circuit = Minimum circuit ampacity
Lights = Light wattage
Heaters
Refrigerant = Refrigerant type used
Design Pressure = High & low side operating
pressures and refrigerant charge
Agency Labels = Designates agency listings
AW-03118
-1-
II. RECEIPT INSPECTION
III. INSTALLATION (continued)
All Traulsen products are factory tested for perfor­mance and are free from defects when shipped. The utmost care has been taken in crating this product to protect against damage in transit. All interior fittings have been carefully secured and the legs or casters are boxed and strapped inside to prevent damage. Door keys will be attached to the handle with a nylon strip. The handle is protected by an easily removable nylon netting.
You should carefully inspect your Traulsen unit for damage during delivery. If damage is detected, you should save all the crating materials and make note on the carriers Bill Of Lading describing this. A freight claim should be filed immediately. If damage is sub­sequently noted during or immediately after installa­tion, contact the respective carrier and file a freight claim. Under no condition may a damaged unit be re­turned to Traulsen & Co. without first obtaining writ­ten permission (return authorization).
III. INSTALLATION
III. a -
LOCATION: Select a proper location for your Traulsen unit, away from extreme heat or cold. Allow enough clearance between the unit and the side wall so that the door (s) may open a minimum of 90°.
III. d - INSTALLING LEGS OR CASTERS: 6 high stainless steel legs are supplied standard for models RBC50 and RBC100. Casters in lieu of legs are available as an optional accessory for the same models. These are shipped from the factory packed inside a cardboard box which is strapped to one of the shelves (two boxes for model RBC50 which re­quires either eight legs or casters). Remove the nylon strap and open the box(es), it should contain either four (4) legs or four (4) casters and sixteen (16) bolts.
WARNING: THE CABINET MUST BE BLOCKED AND STABLE BEFORE INSTALLING LEGS OR CASTERS.
To install the legs or casters, first raise and block the unit a minimum of 7from the floor. For installing legs, thread the legs into the threaded holes on the bottom of the cabinet (see figure 1). Be certain that all legs are tightly secured (legs and casters should be tightened to 300 inch/pounds, max). When the unit is set in its final position, it is important for proper op­eration that the unit be level. The legs are adjustable for this purpose, turn the bottom of the leg counter­clockwise to raise it, clockwise to lower it. Level the unit from front to back as well as side to side in this manner, using a level placed in the bottom of the cabi­net.
III. b - PACKAGING: All Traulsen units are shipped from the factory bolted to a sturdy wooden pallet and packaged in a durable cardboard container. The carton is attached to the wooden skid with the use of large staples. These should first be removed to avoid scratching the unit when lifting off the crate.
To remove the wooden pallet, first if at all possible, we suggest that the cabinet remain bolted to the pallet during all transportation to the point of final installa­tion. The bolts can then be removed with a 3/4” socket wrench. Avoid laying the unit on its front, side or back for removal of the pallet.
NOTE: Traulsen does not recommend laying the unit down on its front, side or back. However, if you must please be certain to allow the unit to remain in an up­right position afterwards for 24 hours before plugging it in so that the compressor oils and refrigerant may settle.
III. c - WIRING DIAGRAM: Refer to the wiring diagram for any service work per­formed on the unit. These are located on pages 21 thru 24 of this manual. Should you require a wiring diagram for a non-standard configuration unit, please contact Traulsen Service at (800) 825-8220, and pro­vide the model and serial number of the unit involved.
Fig. 1
Please note that Traulsen units are not designed to be moved while on legs. If the unit requires moving, a pallet jack or forklift should be used to prevent dam­age. For installing casters, the casters are “plate” type, and require the use of four (4) bolts each to se­cure them firmly to the cabinet bottom at each corner (see figure 2). The caster bolts are tightened using a 1/2 socket wrench.
Fig. 2
-2-
III. INSTALLATION (continued)
CORD & PLUG:
III. e ­All Traulsen Blast Chill models (except model RBC100 which is supplied with a cord set but no plug) are sup­plied with a cord & plug attached. It is shipped coiled at the top of the cabinet, secured by a nylon strip. For your safety and protection, all units supplied with a cord and plug include a special three-prong ground­ing plug on the service cord. Select only a certified electrical outlet with grounding plug for power source. NOTE: Do not under any circumstances, cut or remove the round grounding prong from the plug, or use an extension cord.
III. f -
ELECTRICAL REQUIREMENTS: Model RBC50 is normally provided with two (2) ground­ing type cords with plugs (NEMA 5-15P). T wo (2) sepa­rate 115/60/1 volt, 20 amp, grounded circuits with re­ceptacle must be provided by a certified electrician to assure proper operation of the equipment.
Model RBC100 is normally provided with a grounding type cord without a plug. A 220/60/1 volt, 4 wire, 20 amp grounded circuit with receptacle should be pro­vided by a certified electrician to assure that the com­puterized control is not adversely affected by the op­eration of other equipment.
6 Clearance In Rear
Air Intake
4
Models RBC200 and RBC200RT are normally provided with a grounded cordset (NEMA 5-20P). A separate 115/60/1 volt, 20 amp, grounded circuit should be pro­vided by a certified electrician to assure that the com­puterized control is not adversely affected by the op­eration of other equipment.
Models RBC400 and RBC400RT are normally provided with two (2) grounded cordsets (NEMA 5-20P). T wo (2) separate 115/60/1 volt, 20 amp, grounded circuits should be provided by a certified electrician to assure that the computerized control is not adversely affected by the operation of other equipment.
III. g - PROPER CLEARANCES: Model RBC50: Make certain that there are no obstruc­tions in front of the louver panels on the left and right front sides of the unit. This will allow for sufficient air flow to the refrigeration system and maintenance ac­cess.
Model RBC100: A minimum of 4” clearance on the right side, 6on the left side and 6clearance in the rear (see figure 3). This will allow for sufficient air flow to the refrigeration system and maintenance access.
4 Clearance In Rear
Fig. 3
6
12 Clearance On T op
Models RBC200, RBC200RT, RBC400 & RBC400RT: Insure an overhead clearance of 12 and a rear clear­ance of 4(see figure 4). This will allow for sufficient air flow to the refrigeration system and maintenance access.
-3-
Fig. 4
4 Clearance On Right Side For Drain Tube
III. INSTALLATION (continued)
III. h - CONDENSATE REMOVAL: All Traulsen Blast Chill models (except model RBC50) require the use of a floor drain or floor mounted elec­tric condensate evaporator.
Model RBC100 requires a floor drain for condensate removal or the use of a condensate evaporative pan kit (p/n 329-60018-00). The drain port is located at the rear of the unit (see figure 5).
Front
Of Unit
Evaporative Pan Kit
Front
Of Unit
Floor Drain
Models RBC200 and RBC200RT require a floor drain for condensate removal or the use of a condensate evaporative pan kit (p/n 329-60018-00). T wo drain ports are provided, located at the right side and rear of the unit. Plug the unused drain port with the male pipe thread plug supplied (see figure 6).
III. h - CONDENSATE REMOVAL (cont’d): plug supplied (see figure 7).
For Unit 1 of either 400 lb. capac­ity model, location of the evapora­tive pan kit is required at the side drain port location.
For unit 2, on model RBC400 the second pan kit can be placed ei­ther at the side or rear drain ports. For model RBC400RT this second pan kit must be placed at the side drain port.
Unit 1 Evaporative Pan Kit for RBC 400 & RBC400RT (REQUIRED)
Fig. 7
Front
Of Unit
Unit 2 Evaporative Pan Kit for RBC400 & RBC400RT
NOTE: Local code should be consulted when plumb­ing to drain port.
III. i -
REMOTE CONDENSING UNIT REQUIREMENTS: This section applies only to models RBC200, RBC200RT, RBC400 and RBC400RT. A remote con­densing unit, operating on R-404A refrigerant, is re­quired for Blast Chill operation on these models (two for RBC400 and RBC400RT). The remote condensing unit(s) should be capable of providing 18,700 BTU/hr @ -10°F suction and 90°F ambient at the evaporator coils of the Blast Chill section.
4 HP air-cooled and 3 HP water-cooled remote con­densing units are available from Traulsen as an op­tional accessory, but please note that these are rated for use only within a 25 foot radius of the cabinet. In­creased capacity of the remote condensing unit and line sizing will depend on the length and layout of the connecting piping from the remote condensing unit to the Blast Chill unit. Proper line sizing should be defined by a qualified refrigeration engineer or techni­cian.
Unit 2 Evapora­tive Pan Kit for RBC400
Front
Of Unit
Pipe Thread Plug
Fig. 6
Evaporative Pan Kit
Models RBC400 and RBC400RT require a floor drain for condensate removal or the use of a two (2) con­densate evaporative pan kits (p/n 329-60018-00). T wo drain ports are provided, located at the right side and rear of the unit. Plug the unused drain port with the
III. j - REMOTE UNIT CUT-OUT SETTINGS: This section applies only to models RBC200, RBC200RT , RBC400 and RBC400RT. The low pressure cut-out of the remote condensing unit should be ad­justed to obtain an evaporator coil temperature NO LOWER THAN -15°F. If the length of the connecting piping is 40 feet or less, the condensing unit low pres­sure cut-out settings will be approximately 15 +/- 2 PSIG cut-out and 25+/- 3 PSIG cut-in.
III. k - SEALING ROLL-IN/ROLL-THRU UNITS: This section applies only to models RBC200, RBC200RT , RBC400 and RBC400RT. Roll-In and Roll­Thru cabinets set on the floor require the floor area to be flat and level. In addition, after the cabinet is set in place, sealant should be used around the perimeter of the base to comply with National Sanitation Founda­tion requirements. After sealing the unit, the enclosed ramp should then be installed.
-4-
III. INSTALLATION (continued)
III. l - INSTALLING RBC50 CONTROL PANEL: Model RBC50 is shipped with the control panel de­tached, and laid flat, taped to the cabinet top (see fig­ure 8). This must be installed before use. To install:
Remove the packing material and tape holding the control to the top. Remove and retain the six (6) Phillips head screws attaching the control cover to the frame. Also, remove and retain the 14- 20x1/2” screws found in the cabinet top. Next, position the control frame over the hole in the unit top and attach using 1/4-20x1/ 2 screws (see figure 9).
NOTE: Ensure that grommet is firmly in place, align­ing round hole in bottom of control housing with round hole in unit top.
Inspect paper roll and spindle from rear of control panel before installing panel. Reattach the control cover to the frame using the six (6) Phillips head screws previ­ously removed.
III. m - ATTACHING RBC400 UNITS TOGETHER: This section applies only to models RBC400 and RBC400RT. First, place the front and rear cabinets in close proximity to each other being careful to align the drain from the front of the rear unit to the drain of the front unit. It will be necessary to level both units together at this time.
The liquid line solenoid and TXV are provided. The tem­perature control and defrost functions are performed by the blast chill digital control.
Next, using two pipe clamps, pull the units together(see figure 10). Install the covers over the gap formed be­tween the units From inside the cabinets, using the screws provided, install the breaker strips using the strip as a template.
Connect both the probe harness and control harness from unit two (the rear unit) to their dedicated connectors on unit one (see figure 10a). Set #4 DIP switch to the ON position as shown (see figure 10b).
CONTROL BOX
LOCATION
Fig. 8
Fig. 9
Fig. 10
USING TWO PIPE CLAMPS, PULL THE TWO UNITS TOGETHER AND USING THE SCREWS PROVIDED. ALIGN THE BREAKER STRIPS AS A TEMPLATE FOR THE SCREW PATTERN INSIDE AND OUTSIDE THE CABINET.
CONTROL BOX - RBC400
(wiring connections)
Fig. 10b
SET #4 DIP SWITCH
TO ON POSITION
AS SHOWN FOR RBC400
AND RBC400RT.
UNIT 2
PROBE HARNESS
CONNECTOR
UNIT 2 CONTROL
HARNESS
CONNECTOR
Fig. 10a
-5-
IV. CARE & MAINTENANCE
CLEANING THE CONDENSER:
IV. a ­The most important thing you can do to insure a long, reliable service life for your Traulsen is to regularly clean the condenser coil. The self-contained condens­ing unit requires regularly scheduled cleaning to keep the finned condenser clean of lint and dust accumula­tion. Keeping the condenser clean allows the cabinet to operate more efficiently and use less energy.
To clean the self-contained condenser, first discon­nect electrical power to the cabinet and lift up the front louver assembly. To lift this, remove the two thumb screws located on both sides at the bottom of the lou­ver assembly . Once the screws are removed, the panel can be pivoted upwards allowing full access to the front facing condenser (for model RBC50, remove the four Phillips head screws from the front louver panel, and lift-off). Vacuum or brush any dirt, lint or dust from the finned condenser coil, the compressor and other cooling system parts. If significant dirt is clog­ging the condenser fins, use compressed air to blow this clear. Lower louver assembly and replace thumb screws to hold it in place. For care of the remote con­densing unit(s) used for models RBC200, RBC200RT, RBC400 and RBC400RT, consult the manufacturer’s product literature.
IV. b -
CLEANING THE EXTERIOR: Exterior stainless steel should be cleaned with warm water, mild soap and a soft cloth. Apply with a damp­ened cloth and wipe in the direction of the metal grain. Avoid the use of strong detergents and gritty, abra­sive cleaners as they may tend to mar and scratch the surface. Do NOT use cleansers containing chlorine, this may promote corrosion of the stainless steel.
IV. d - INSTALLING PRINTER PAPER (cont’d): the paper opening with the spindle in the paper roll. Position the paper so it is fed out from the bottom of the roll. Feed the paper into the bottom of the printer enough to start the edge of the paper and press the print button on the key pad (this will draw the paper up through the printer and feed the paper out through the front of the printer).
Feed the printer paper through the slot in the printer cover and position the printer cover in place. Secure the printer cover with the original screws (see figure
11).
Test the printer by pressing the print button and make sure the paper feeds normally and the text is clear.
Printer paper is standard 2-1/4” wide x 100’ long small diameter,Office Depot #451 - 310. Printer ribbon Traulsen service part number SPR-00001-00 is Epson #ERC-09, or Office Depot #626-602.
Fig. 11
2-14 wide x 100’ long “small diameter” paper roll
V. OTHER
Care should also be taken to avoid splashing the unit with water, containing chlorinated cleansers, when mopping the floor around the unit. For stubborn odor spills, use baking soda and water (mixed to a 1 TBSP baking soda to 1 pint water ratio).
WARNING: DISCONNECT ELECTRICAL POWER SUPPLY BEFORE CLEANING ANY PARTS OF THE UNIT.
IV. c - CLEANING THE INTERIOR: For cleaning stainless steel interiors, the use of bak­ing soda as described in section IV. bis recom­mended. Use on breaker strips as well as door gas­kets. All interior fittings are removable without tools to facilitate cleaning. A defrost cycle is the ideal time for performing interior cleaning.
IV. d - INSTALLING PRINTER PAPER: Remove the two (2) thumb screws on either side of the printer cover. Pull the printer cover out and up to expose the printer. Cut a clean edge on the end of a roll of printer paper. Install the printer paper in through
V. a - SERVICE AGENCY CHECK & START-UP: After installation and start-up, contact Traulsen’ s Ser­vice Department at (800) 825-8220 to arrange for a Mechanical Installation and Operation Inspection, which is required by Traulsen to validate the warranty . On-site inspection not required for model RBC50.
V. b - ON-SITE BLAST CHILL TRAINING: Traulsen offers the operator comprehensive one and two day, on-site training in the proper operation of your Blast Chiller. Contact your authorized Traulsen equipment dealer for more information.
V. c - SERVICE INFORMATION: Before calling for service, please check the follow­ing:
Is the electrical cord plugged in?
Is the fuse OK or circuit breaker on?
If after checking the above items and the unit is still not operating properly, please contact an authorized
-6-
V. OTHER
SERVICE INFORMATION (cont’d):
V. c ­Traulsen service agent. A complete list of authorized service agents was provided along with your Traulsen unit. If you cannot locate this, you may also obtain the name of a service agent from the Service/Contact page of our website: www.traulsen.com.
If service is not satisfactory, please contact our in­house service department at:
VI. BLAST CHILL OPERATION
VI. b - COVERING FOODS (cont’d): cess. NOTE: The plastic wrap or foil should be placed directly onto the food surface. DO NOT place a lid over the pan, or stretch the plastic wrap tightly across the rim of the pan. This will create an insulating layer of air above the food surface which will slow the cool­ing of the center of the food, while the outside edges are cooling rapidly due to being in contact with the pan surfaces (see figure 13).
Traulsen 4401 Blue Mound Road Fort Worth, TX 76106 (800) 825-8220
Traulsen & Co., Inc. reserves the right to change speci­fications or discontinue models without notice.
V. d -
DEMONSTRATIONS: Traulsen sales representatives perform in-service op­erational training for the end-user. Contact the T raulsen Service Department (after completion of the service agency start-up) to arrange this at (800) 825-8220.
V. e - BLAST CHILL VIDEO: Traulsen supplies each Blast Chiller sold with an op­erational video (VHS format).
V. f - BLAST CHILL DATA COMMUNICATIONS KIT: To obtain information about downloading batch data to a PC, please contact the factory.
VI. BLAST CHILL OPERATION
VI. a - LOADING FOOD INTO PANS: The food product to be blast chilled should be placed into metal pans (generally 12x 20x 2-1/2) to a DEPTH NOT TO EXCEED 2. This will assure the fast­est blast chilling cycle. NOTE: Use of deeper pans and/or plastic containers can cause freezing and if product is too thick or deep, the surface will freeze and the center of the product will be insulated, pre­venting proper chilling (see figure 12).
NOT RECOMMENDEDRECOMMENDED
2” Maximum
Food Depth
More Than
2” Depth
RECOMMENDED NOT RECOMMENDED
Solid Lid Over Pan
Plastic Wrap In Contact With Food
Plastic Wrap Stretched Across Food
Fig. 13
AIR
AIR
VI. c - GROUPING FOODS TO FORM BATCHES: In order to achieve the best utilization of the Blast Chiller Unit, it is possible to group foods with similar cooling properties to form “Batches”. This will allow one of the food probes to be inserted into one pan of food product within the “batch” and represent the cooling rate of the entire batch.
Based on our testing, we have found that foods with higher levels of water content will cool much faster than foods that have lower water content. If more than three (3) types of foods are to be blast chilled at the same time, it will be necessary to form one or more batches to make best utilization of the three (3) probes available. Below is a list of guidelines to follow when forming batches.
1) Do not combine hot food and room temperature foods within the same batch, even though they may be similar (i.e. hot tuna casserole and cool tuna salad). This is because it will take longer to cool from cook­ing temperatures to 40°F (5°C) than it will take from 70
°F to 40°F (21°C to 5°C). CAUTION: Coupling hot foods
with cold foods run the risk of the cold food remain­ing at dangerous temperatures too long as hot foods cool.
2) The chart on page 8 shows the relative cooling times of various foods compared to water (generally the fast­est to cool). It can also be used as an approximate guideline when forming batches.
VI. b - COVERING FOODS: It is recommended that all food product be covered with plastic wrap or foil for hot foods to minimize mois­ture loss from product during the blast chilling pro
3) Sliced meats placed in layers will cool more rapidly than whole meats due to the ratio of surface area to content (volume) allowing for greater heat dissipation.
-7-
VI. BLAST CHILL OPERATION (contd)
VI. c - GROUPING FOODS TO FORM BA TCHES (contd):
AVG. COOLING TIME
FOOD RELATIVE TO WATER
LASAGNA +89%
SLOWER
CHILI +64% MASHED POTATOES +64% MEAT LOAF (WHOLE) +61% RICE +61% CREAM OF WHEAT +60% KERNEL CORN +58% SOUP (THICK TYPES) +49% BAKED POTATOES +47% CHOPPED STEAKS/GRAVY +43% REFRIED BEANS +43% SPAGHETTI/MEAT SAUCE +39% GREEN BEANS +39% SCRAMBLED EGGS +36% MACARONI & CHEESE +33% CHICKEN BREASTS +12% WATER 0%
FASTER
VI. e - PAN PLACEMENT IN THE UNIT (cont’d): Bottom). This will facilitate easier removal from the unit if more than one batch is being blast chilled at the same time, but have different completion times.
In the RBC50 model, air flows through the unit in a horizontal plane from right to left, and left to right, there­fore, there is no significant difference if the pans are placed toward the rear of the unit or toward the door.
In the RBC100 model, air flows through the unit in a horizontal plane from right to left, therefore, there is no significant difference if the pans are placed toward the rear of the unit or toward the door (see figure 14).
AIR FLOW
VI. d -
MAXIMUM LOAD PER BATCH: Model RBC50 has a maximum recommended capacity of 50 lbs. of food. This would be approximately five (5) 12 x 20 x 2-1/2 pans with 2 thick product.
Model RBC100 has a maximum recommended capac­ity of 100 lbs. of food. This would be approximately ten (10) 12x 20x 2-1/2pans with 2” thick product.
Models RBC200 and RBC200RT have a maximum rec­ommended capacity of 200 lbs. of food. This would be approximately twenty (20) 12” x 20” x 2-1/2” pans (one cart) with 2 thick product.
Models RBC400 and RBC400RT have a maximum rec­ommended capacity of 400 lbs. of food. This would be approximately forty (40) 12x 20x 2-1/2pans (two carts) with 2 thick product.
All Blast Chiller units will provide more uniform cool­ing of the food if they are setup close to their capacity of food with each blast chill cycle. This is due to the fact that the heat being removed from the food tends to moderate the temperature of the air being circulated. Lightly loaded blast chill cycles tend to run with colder air temperatures, which can cause the food to freeze near the outside surfaces of the pans. The soft chill cycle should be used if the chiller is loaded less than 50% of capacity.
Fig. 14
On the Roll-In and Roll-Thru models, it is recommended that the slower cooling foods within the batch be placed in the area of the cart which will be toward the rear of the Blast Chill interior (away from the door). This area of the unit receives the incoming air from the blowers and is slightly cooler than the air passing over the pans nearest the doors (see figure 15).
Rear Of
Door
Faster Cooling Food
BATCH
#1
BATCH
#2
Interior
Slower Cooling Food
VI. e - PAN PLACEMENT IN THE UNIT: All pans of food with a batch should be grouped to­gether in the same area of the unit (i.e. T op, Middle, or
-8-
Fig. 15