Traulsen RBC400RT, RBC200, RBC200RT, RBC400 User Manual

Page 1
Quality Refrigeration
OWNER’S MANUAL
Instructions for the installation, operation,
and maintenance of Blast Chiller Models:
RBC50 (50 lb. capacity undercounter model) RBC100 (100 lb. capacity reach-in model) RBC200 (200 lb. capacity roll-in model) RBC200RT (200 lb. capacity roll-thru model) RBC400 (400 lb. capacity roll-in model) RBC400RT (400 lb. capacity roll-thru model)
All Traulsen units are placed on a permanent record file with the service department. In the event of any future questions you may have, please refer to the model and serial number found on the name tag affixed to the unit. Should you need service, however, call us on our toll free number, 800-825­8220 between 7:30 am and 4:30 pm CST, Monday thru Friday. It is our pleasure to help and assist you in every possible way.
IMPORTANT WARRANTY NOTES
RBC50 & RBC100 Owner/Operators
Please Contact (800) 825-8220 ext. #6115 upon start-up to register your warranty
RB200/RBC200RT & RBC400/RBC400RT Owner/Operators
Please Contact (800) 825-8220 ext. #6112 after installation but before start-up in order to register
your warranty and arrange for a mandatory free Installation Validation & Service Check
(allow at least 72 hours from time of call for this to be performed)
Contact your local Hobart/Traulsen sales representative to arrange for a free on-site
demonstration (after warranty registration and/or installation validation)
FORM NUMBER TR35850 REV. 4/07 P/N 375-60217-00
Page 2
I. INTRODUCTION
Thank you for your decision to purchase a Traulsen Blast Chiller. This important piece of food safety equipment is built to our highest standards and will provide you with years of dependable service. However, it is important to note that although this product is designed to chill product from 135°F down to below 41°F within FDA/HACCP guidelines, several operational factors, such as product temperature, density, loading, etc. will all effect actual chilling performance. As a result, although easy to use, the operation of blast chilling requires diligent attention on the part of the operator(s) in order to insure proper results.
It is also important to note many perceived service problems can actually be attributed to operational issues, resulting in lost product and/or service down time. Please review the instructions contained in this manual completely, and make certain that all operators are well trained in the equipments proper use.
TABLE OF CONTENTS
GETTING STARTED: QUICK START CHECK-LISTS & GUIDELINES
Blast Chiller Installation Checklist Page 2 Blast Chiller Quick Start Checklist Page 3 Basic Operating Guidelines Page 4
SECTION 1: RECEIPT, INSTALLATION, CARE & MAINTENANCE
I. Introduction Page 1 II. Receipt Inspection Page 5 III. Installation
a-Location Page 5 b-Packaging Page 5 c-Wiring Diagram Page 5 d-Installing Legs or Casters Page 5 e-Assembly Of Models RBC400 & RBC400RT Page 5 f-Cord & Plug Page 6 g-Electrical Requirements Page 6 h-Proper Clearances Page 6 i-Condensate Removal Page 7 j-Remote Unit BTU Requirements Page 7 k-Remote Unit Cut-Out Settings Page 7 l-Sealing Roll-In/Roll-Thru Units Page 7 m-ON/OFF Power Switch Page 7. n-Installing RBC50 Control Panel Page 8
IV. Care & Maintenance
a-Cleaning The Condenser Page 8 b-Printer Supplies Page 8 c-Installing Printer Paper Page 8/9 d-Cleaning The Exterior Page 9 e-Cleaning The Interior Page 9 f-The Serial Tag Page 9
V. Other
a-Service Agency Check & Start-Up Page 9 b-On-Site Blast Chill Training Page 9 c-Service Information Page 9 d-Demonstrations Page 9 e-Blast Chill Video Page 9 f-Blast Chill Data Communications Kit Page 9
SECTION 2: CONTROL OPERATION DETAILS
VI. The SmartChill® Control
a-The SmartChill Control - Overview Page 10 b-Printing Capability Page 10 c-Control Basics Page 10 d-Start-Up Page 10 e-Over Temperature Page 10 f-In The Event Of A Power Interruption Page 10 g-Getting Started Page 10 h-EZ Start Page 10
VII. Operating The Blast Chill Control
a-Starting A Chill Cycle By Temp Page 11-12 b-Starting A Chill Cycle By Time Page 13 c-Starting A Chill Cycle By Product Page 14 d-Chill By Product Feature - Product List Page 15 e-Refrigerated Hold Mode Page 16 f-Staring A Manual Defrost Page 16 g-Printing Batch/Chill Cycle Data Page 17 h-Set-Up Products Page 18 i-Set-Up Users Page 19 j-Accessing The SYSPAR Page 20 k-SYS PAR Page 21
SECTION 3: OTHER/MISC.
VIII. SmartChill® Communications
a-Introduction Page 22 b-System Requirements Page 22 c-Operation Page 22 d-Communicating With SmartChill Page 22
e-Hardware Connection Page 22 IX. Glossary Page 23 X. Replacement Parts List Page 24 XI. Summary of Error Messages Page 25 XII. Warranty Information Page 26 XIII. Mechanical Trouble Shooting Guide Back Cover
-1-
Page 3
Blast Chiller Installation Checklist
Model RBC50
1) Insure proper clearances, no obstruction to either front louver for at least 24 from cabinet face.
2) Install all eight legs or casters, insuring that the unit is level for proper operation (see section III d. for more details).
3) Install the control panel (see section III n. for more details). Before doing so be sure to perform a visual inspection of the control to insure that no connections have come loose during shipment.
4) Plug both power cords into separate, dedicated 115 volt/20 amp outlets (see section III f. for more details).
5) Insure that paper supply for both printers are properly installed and that the printers themselves are operational (see section IV c. for more details).
Model RBC100
1) Insure proper clearances, no obstruction to either front louver for at least 24 from cabinet face, 6 along left side, 4 along the right side, and 6 behind the unit
2) Install the legs or casters, insuring that the unit is level for proper operation (see section III d. for more details).
3) Make condensate removal provisions (see section III h. for more details).
4) Hardwire the cord to a dedicated 220/60/1 volt, 4 wire, 20 amp circuit (see section III g. for more details).
5) Insure that paper supply for both printers are properly installed and that the printers themselves are operational (see section IV c. for more details).
Models RBC200 & RBC200RT (same for models RBC400 & RBC400RT but please see section III e. for additional installation/assembly instructions)
1) Insure proper clearances, no obstruction to either front louver for at least 12 above the cabinet and 4” along the right side (for the drain tube). Unit must be located on a level surface.
2) Seal the unit to the floor (see section III l for more details).
3) Install the door ramp(s), (see section III l. for more details).
4) Make condensate removal provisions (see section III h. for more details). Note that two drain outlets are provided. Please insure that the unused drain line is properly plugged to prevent leaks.
5) Plug the power cord into a dedicated 115 volt/20 amp outlets (see section III g. for more details).
IMPORTANT NOTE In order to accomplish blast chilling, models RBC200 and RBC200RT require one, and models RBC400 and RBC400RT require two properly sized remote condensing units (see section III j. for more details). After this installation has been completed by a qualified refrigeration technician, please call Traulsen Service at (800) 825-8220 in order to arrange for your free on-site installation validation.
6) In order to properly charge the system, at the completion of installation
this must be run in blast chill mode for at least 90-minutes. To do so...
`1-Select: BY TIME from the main menu.
2- Then select the default setting CHILL (default) or scroll up or down
to select this mode.
3- Next select the default cycle time 01:30 (1 hour & 30 minutes) or
scroll up or down to select this time.
4- Finish by selecting START to initiate the test cycle.
MAIN MENU AIR 35°F
BY TEMP BY PROD
BY TIME
08:05:01 MORE
BY TIME
TYPE: CHILL
↓↓
CYCLE TIME: 01:30
↓↓
MAIN START
↑↑
↑↑
7) Insure that paper supply for both printers are properly installed and
that the printers themselves are operational (see section IV d. for more details).
GENERAL NOTE:
In the event that the owners manual is not available, please visit www. traulsen.com in order to view/print the latest version.
-2-
BY TIME
TYPE: CHILL
↓↓
CYCLE TIME: 01:30
↓↓
MAIN START
BY TIME
TYPE: CHILL
↓↓
CYCLE TIME: 01:30
↓↓
MAIN START
↑↑
↑↑
↑↑
↑↑
Page 4
Blast Chiller Quick Start Checklist
Starting a Chill Cycle - All Models
1) Load product into the blast chiller. Both full and partial loads are OK, but for best results evenly distribute product throughout the interior tray slides or roll-in rack.
2) Insert a food probe into the top, bottom and middle level pans. The probe should be located in the center of the food pan, at about the halfway point of the product depth.
3) Close the door.
4) Press the EZ Start button.
The Blast Chill Process - All Models
1) While in a blast chill cycle, cold air is rapidly being circulated around the food pans in order to remove heat as rapidly as possible.
2) Actual chill times will vary depending on many product related factors such as starting temperature, product density, cycle load, content, etc.
3) To insure food safety, the probes constantly monitor product core temperature(s) throughout each chill cycle, as well as during any holding period afterwards. Reports available at the end of each chill cycle can then be used by the operator to confirm that both FDA critical control points were met in accordance with the current food code.
Concluding a Chill Cycle - All Models
1) Upon each probe reaching target temperature (37°F) an audible alarm will sound for 30-seconds, and the probe number on the control display will continuously flash “DONE.”
2) Press the button alongside the probe flashing “DONE” in order to conclude that probes batch.
3) The control will now display the print menu. 3a. Press BOTH to receive both record and label printouts 3b. Press RECORD to receive only the record printout 3c. Press LABEL to receive only the label printout 3d. Press NONE if no printouts are desired.
NOTE: After printing has completed for either the RECORD, LABEL or BOTH, the control will continue to display the print menu until NONE is selected. This allows for multiple copies of each to be printed as needed.
4) Repeat for any remaining probes as they complete in turn. Pressing NONE after the final probe has completed returns the display to the MAIN MENU.
5) Any probes used should be properly sanitized prior to use in another batch.
For more details and/or to make use of other
control features please refer to pages 12 - 23 of this manual.
-3-
Page 5
Basic Operating Guidelines
Chilling Within HACCP Guidelines
1) The current FDA Food Code allows much more time for safe chilling than 90-minutes. This actually requires two critical control points of:
a) From 135°F to 70°F within two hours, then... b) From 70°F to below 41°F within four hours, for a total chill time
from 135°F to below 41°F of no more than six hours.
2) Total chill times can exceed six hours in duration and still be safe. This safety threshhold does not include:
a) Any time needed for product to chill from any start temp down to
135°F, or...
b) Any time elapsed to chill to below 41°F.
Loading
1) To achieve quickest chill times product should be loaded into pans to a depth of no greater than 2”.
2) Products should always be loaded into the shallowest pan possible.
3) Chilling of products of greater than 2 depth is often possible within FDA guidelines. However please note that actual chill times are a function of: Start Temperature, Product Density, Product Depth, and Total Load.
4) Chilling of products, such as whole cooked chickens or meatloaf can be accomplished. However these should be positioned inside the chiller to allow the air-flow to contact the greatest surface area of the product.
Covering
1) Product does not always need to be covered. However before doing so
please consider the following potential scenarios...
a) If large loads of especially hot product are chilled there is the
potential to freeze the coil.
b) Loads of uncovered product that require especially long chilling
times may have the potential to experience surface drying.
c) Loads that are left uncovered in the chiller for long periods after
completion of a chill cycle may also experience surface drying of the product if left uncovered.
d) Loads of especially liquid product, such as soup, are highly
recommended to be covered in order to prevent accidental spillage.
e) Some foods, such as rice and pasta, are particularly vulnerable
to drying and so should always be covered.
Use of Food Probes
1) For most accurate results food probes should be used. These need to be properly placed in the center of the thickest part of the product to insure an accurate temperature reading.
2) Some products are not suitable for use of food probes. These products...
a) Should be chilled BY TIME. b) The correct chill time should be established by the operator based
upon actual product testing.
c) The end cycle temperature should be verified manually with an
clean, accurate thermometer as soon as the pre-established chill time elapses.
For details about using your Traulsen blast chiller within a cook/chill operation please refer to form number TR99999.
-4-
Page 6
II. RECEIPT INSPECTION
III. INSTALLATION (continued)
All Traulsen products are factory tested for performance and are free from defects when shipped. The utmost care has been taken in crating this product to protect against damage in transit. All interior fittings have been carefully secured and the legs or casters are boxed and strapped inside to prevent damage. Door keys will be attached to the handle with a nylon strip. The handle is protected by an easily removable nylon netting.
You should carefully inspect your Traulsen unit for dam­age during delivery. If damage is detected, you should save all the crating materials and make note on the carriers Bill Of Lading describing this. A freight claim should be filed immediately. If damage is subsequently noted during or immediately after installation, contact the respective carrier and file a freight claim. Under no condition may a damaged unit be returned to Traulsen without first obtaining written permission (return autho­rization).
III. INSTALLATION
III. a - LOCATION: Select a proper location for your Traulsen unit, away from extreme heat or cold. Allow enough clearance between the unit and the side wall so that the door (s) may open a minimum of 90°.
III. b - PACKAGING: All Traulsen units are shipped from the factory bolted to a sturdy wooden pallet and packaged in a durable card­board container. The carton is attached to the wooden skid with the use of large staples. These should first be removed to avoid scratching the unit when lifting off the crate.
To remove the wooden pallet, first if at all possible, we suggest that the cabinet remain bolted to the pallet dur­ing all transportation to the point of final installation. The bolts can then be removed with a 3/4” socket wrench. Avoid laying the unit on its front, side or back for removal of the pallet.
NOTE: Traulsen does not recommend laying the unit down on its front, side or back. However, if you must please be certain to allow the unit to remain in an up­right position afterwards for 24 hours before plugging it in so that the compressor oils and refrigerant may settle.
III. c - WIRING DIAGRAM: Refer to the wiring diagram for any service work per­formed on the unit. Should you require a wiring dia­gram, please contact Traulsen Service at (800) 825-8220, and provide the model and serial number of the unit in­volved.
III. d - INSTALLING LEGS OR CASTERS: 6 high stainless steel legs are supplied standard for models RBC50 and RBC100. Casters in lieu of legs are available as an optional accessory for the same mod­els. These are shipped from the factory packed inside a cardboard box which is strapped to one of the shelves (two boxes for model RBC50 which requires either eight legs or casters). Remove the nylon strap and open the
III. d - INSTALLING LEGS OR CASTERS (cont’d): box(es), it should contain either four (4) legs or casters (RBC50 x 8 or RBC100 x 4 and four bolts for each caster).
WARNING: THE CABINET MUST BE BLOCKED AND STABLE BEFORE INSTALLING LEGS OR CASTERS.
To install the legs or casters, first raise and block the unit a minimum of 7from the floor. For installing legs, thread the legs into the threaded holes on the bottom of the cabinet (see figure 1). Be certain that all legs are tightened securely. When the unit is set in its final posi­tion, it is important for proper operation that the unit be level. The legs are adjustable for this purpose, turn the bottom of the leg counter-clockwise to raise it, clock­wise to lower it. Level the unit from front to back as well as side to side in this manner, using a level placed in the bottom of the cabinet.
Fig. 1
Fig. 2
Please note that Traulsen units are not designed to be moved while on legs. If the unit requires moving, a pal­let jack or forklift should be used to prevent damage. For installing casters, the casters are “plate” type, and require the use of four (4) bolts each to secure them firmly to the cabinet bottom at each corner (see figure
2). The caster bolts are tightened using a 1/2” socket wrench.
II. e - ASSEMBLY OF MODELS RBC400 & RBC400RT: Double depth roll-in/roll-thru units are shipped as two separate components which must be attached together at the jobsite. To accomplish this, first, place the front and rear cabinets in close proximity to each other being careful to align the drain from the front of the rear unit to the drain of the front unit. It will be necessary to level both units together at this time.
Next, using two pipe clamps, pull the units together (see figure 3). Install the covers over the gap formed between the units From inside the cabinets, using the screws provided, install the breaker strips using the strip as a template.
Fig. 3 - Using two pipe clamps, pull the two units together and using the screws provided. Align the breaker strips as a template for the screw pattern inside and outside the cabinet.
-5-
Page 7
III. INSTALLATION (continued)
III. f - CORD & PLUG: All Traulsen Blast Chill models (except model RBC100 which is supplied with a cord set but no plug) are supplied with a cord & plug attached (for models RBC200 and RBC200RT, the cord and plug supplied is for the self-con­tained maintenance compressor only, the 4HP remote con­densing unit requires a separate electrical connection of its own). It is shipped coiled at the top of the cabinet, se­cured by a nylon strip. For your safety and protection, all units supplied with a cord and plug include a special three­prong grounding plug on the service cord. Select only a certified electrical outlet with grounding plug for power source. NOTE: Do not under any circumstances, cut or remove the round grounding prong from the plug, or use an extension cord.
6 Clearance In Rear
Fig. 5
III. g - ELECTRICAL REQUIREMENTS: Model RBC50 is normally provided with two (2) grounding type cords with plugs (NEMA 5-15P). Two (2) separate 115/ 60/1 volt, 20 amp, grounded circuits with receptacle must be provided by a certified electrician to assure proper op­eration of the equipment
115/60/1
Outlet #1
Model RBC100 is normally provided with a grounding type cord without a plug. A dedicated 220/60/1 volt, 4 wire, 20 amp grounded circuit with receptacle should be provided by a certified electrician to assure that the computerized control is not adversely affected by the operation of other equipment.
Models RBC200/RBC200RT are normally provided with one (RBC400/RBC400RT are provided with two) grounded cordset (NEMA 5-20P). A dedicated 115/60/1 volt, 20 amp, grounded circuit should be provided by a certified electrician to assure that the computerized control is not adversely affected by the operation of other equipment.
(see figure 43).
Fig. 4
115/60/1
Outlet #2
Air
Intake
↓↓
↓↓
6 Clearance On Left
4 Clearance On Right
12 Clearance On Top
↓↓
↓↓
↑↑
↑↑
III. h - PROPER CLEARANCES: Model RBC50: Make certain that there are no obstructions in front of the louver panels on the left and right front sides of the unit. This will allow for sufficient air flow to the re­frigeration system and maintenance access.
Model RBC100: A minimum of 4clearance on the right side, 6” on the left side and 6” clearance in the rear (see figure 5). This will allow for sufficient air flow to the refrigeration system and maintenance access.
Models RBC200/RBC200RT & RBC400/RBC400RT: Insure an overhead clearance of 12” and a rear clearance of 4(see figure 6). This will allow for sufficient air flow to the refrigeration system and maintenance access.
-6-
4 Clearance In Rear
↑↑
↑↑
↑↑
↑↑
Fig. 6
↑↑
↑↑
4 Clearance On Right Side For Drain Tube
↑↑
↑↑
Page 8
III. INSTALLATION (continued)
III. i - CONDENSATE REMOVAL: All Traulsen Blast Chill models (except model RBC50) require the use of a floor drain or floor mounted electric condensate evaporator.
Model RBC100 requires either a floor drain or the use of an optional bottom mounted electric condensate evapo­rative pan kit (BCACC-BMCE) for condensate removal. The standard drain port location is at the rear of the unit (see figure 7).
Front
↑↑
↑↑
Of Unit
Evaporative Pan Kit
Front
↑↑
↑↑
Of Unit
Floor Drain
Fig. 7
Models RBC200 and RBC200RT require either a floor drain or the use of an optional floor mounted electric condensate evaporative pan kit (BCACC-FMCE) for con­densate removal. Two drain ports are provided, located at the right side and rear of the unit. Plug the unused drain port with the male pipe thread plug supplied (see figure 8).
III. j - REMOTE CONDENSING UNIT REQUIREMENTS: This section applies only to models RBC200/200RT and RBC400/400RT. A remote condensing unit, operating on R-404A refrigerant, is required for Blast Chill operation on these models. The remote condensing unit should be capable of providing 18,700 BTU/hr @ -10°F evapora­tor temperature in a 90°F ambient environment.
4 HP air-cooled and 3 HP water-cooled remote condens­ing units are available from Traulsen as an optional ac­cessory. Increased capacity of the remote condensing unit and line sizing will depend on the length and layout of the connecting piping from the remote condensing unit to the Blast Chill unit. Proper line sizing should be defined by a qualified refrigeration engineer or techni­cian.
III. k - REMOTE UNIT CUT-OUT SETTINGS: This section applies only to models RBC200/200RT and RBC400/400RTRT. The low pressure cut-out of the re­mote condensing unit should be adjusted to obtain an evaporator coil temperature NO LOWER THAN -15°F. I f the length of the connecting piping is 40 feet or less, the condensing unit low pressure cut-out settings will be approximately 15 +/- 2 PSIG cut-out and 25+/- 3 PSIG cut-in.
III. l - SEALING ROLL-IN/ROLL-THRU UNITS: This section applies only to models RBC200/200RT and RBC400/400RTRT Roll-In and Roll-Thru cabinets set on the floor require the floor area to be flat and level. In addition, after the cabinet is set in place, sealant should be used around the perimeter of the base to comply with NSF International requirements. After sealing the unit, the enclosed ramp should then be installed.
III. m - ON/OFF SWITCH: The Traulsen Blast Chiller models are all equipped with a power ON/OFF switch intended to cut power to the control as needed. In the event of routine maintenance and/or service is needed, be certain to disconnect the electrical power to the machine and follow lockout/tagout Procedures.
Front
↑↑
↑↑
Of Unit
Pipe Thread Plug
Fig. 8
NOTE: Local code should be consulted when plumbing to drain port.
Evaporative Pan Kit
This is located on top of models RBC100, RBC200, RBC200RT, RBC400 and RBC400RT behind the louver panel assembly. On model RBC50, this switch is located on the right side of the control tower.
-7-
Page 9
III. INSTALLATION (continued)
IV. CARE & MAINTENANCE
III. n - INSTALLING RBC50 CONTROL PANEL: Model RBC50 is shipped with the control panel detached, and laid flat, taped to the cabinet top (see figure 9). This must be installed before use. To install:
Fig. 9
Remove the packing material and tape holding the con­trol to the top. Remove and retain the six (6) Phillips head screws attaching the control cover to the frame. Also, re­move and retain the 1/4- 20 x 1/2screws found in the cabinet top. Next, position the control frame over the hole in the unit top and attach using 1/2-20x1/2screws (see figure 10).
WARNING: DISCONNECT ELECTRICAL POWER SUPPLY BEFORE CLEANING ANY PARTS OF THE UNIT.
IV. a - CLEANING THE CONDENSER: The most important thing you can do to insure a long, reliable service life for your Traulsen is to regularly clean the condenser coil. The self-contained condens­ing unit requires regularly scheduled cleaning to keep the finned condenser clean of lint and dust accumula­tion. Keeping the condenser clean allows the cabinet to operate more efficiently and use less energy.
To clean the self-contained condenser, first discon­nect electrical power to the cabinet and lift up the front louver assembly. To lift this, remove the two screws located on both sides at the bottom of the louver as­sembly. Once the screws are removed, the panel can be pivoted upwards allowing full access to the front facing condenser (for model RBC50, remove the four Phillips head screws from the front louver panel, and lift-off). Vacuum or brush any dirt, lint or dust from the finned condenser coil, the compressor and other cooling system parts. If significant dirt is clogging the condenser fins, use compressed air to blow this clear. Lower louver assembly and replace screws to hold it in place. For care of the remote condensing unit(s) used for models RBC200 & RBC200RT, consult the manufacturers product literature.
Fig. 10
NOTE: Extreme care needs to be taken to insure that: a- all wires connecting the control cover to the RBC50 are not damaged in any way, nor mistakenly mounted between the cover and cabinet during installation, which could re­sult in a short circuit, or... b- that no connections are pulled off the control.
NOTE: Ensure that grommet is firmly in place, aligning round hole in bottom of control housing with round hole in unit top.
IV. b - PRINTER SUPPLIES: Supplies to support the both standard SmartChill control printers are available directly from our Parts Department, or from your local Hobart Sales and Service Office. In addition it may also be possible to obtain one of these locally. The record printer paper is standard thermal paper which is readily available at most office supply outlets. Specifications are 2-1/2" wide by 85" long:
Traulsen P/N 400-60003-00 Office Depot #302-224 Staples #PMF-5233
The label printer uses a special peel-off label stock, Traulsen part number 400-60004-00. Each roll contains 225 labels.
IV. c - INSTALLING PRINTER PAPER: To load the record printer paper, place a roll on the roll shaft. Position the paper such that the paper feeds from the back of the roll. This allows the thermal sen­sitive side of the paper to be on the upper surface as it feeds through the printer. The ends of the roll shaft are installed in the two roll holders.
®
Inspect paper roll, label roll, and spindles from rear of con­trol panel before installing panel. Reattach the control cover to the frame using the six (6) Phillips head screws previously removed.
Gently pull the feed door down and slightly forward. It is located on the bottom of the printer and will open about 90 degrees. Feed the paper into the loading slot directly behind the door and push it up until the paper
-8-
Page 10
IV. CARE & MAINTENANCE (contd)
V. OTHER
IV. c - INSTALLING PRINTER PAPER (cont’d): extends about 1/4" in front of the printer. Then return the feed door to its original position. If the feed door is not closed, the printer will not operate. Labels are loaded in the same manner. The label printer is located to the right of the record printer as you look at the unit. After turning the unit on, the label printer will automatically orient itself for the next label.
IV. d - CLEANING THE EXTERIOR: Exterior stainless steel should be cleaned with warm wa­ter, mild soap and a soft cloth. Apply with a dampened cloth and wipe in the direction of the metal grain. Avoid the use of strong detergents and gritty, abrasive cleaners as they may tend to mar and scratch the surface. Do NOT use cleansers containing chlorine, this may pro­mote corrosion of the stainless steel.
Care should also be taken to avoid splashing the unit with water, containing chlorinated cleansers, when mopping the floor around the unit. For stubborn odor spills, use baking soda and water (mixed to a 1 TBSP baking soda to 1 pint water ratio).
IV. e - CLEANING THE INTERIOR: For cleaning stainless steel interiors, the use of baking soda as described in section IV. bis recommended. Use on breaker strips as well as door gaskets. All interior fit­tings are removable without tools to facilitate cleaning. A defrost cycle is the ideal time for performing interior clean­ing. For more information on the care of stainless steel finishes, please refer to section XV.
V. c - SERVICE INFORMATION (cont’d): If after checking the above items and the unit is still not operating properly, please contact Traulsen (if under warranty) or an authorized Traulsen service agent. A complete list of authorized service agents was provided along with your Traulsen unit. If you cannot locate this, you may also obtain the name of a service agent from the Service/Contact page of our website: www.traulsen.com.
If service is not satisfactory, please contact our in­house service department at:
Traulsen 4401 Blue Mound Road Fort Worth, TX 76106 (800) 825-8220
Traulsen reserves the right to change specifications or discontinue models without notice.
V. d - DEMONSTRATIONS: Traulsen sales representatives perform in-service op­erational training for the end-user. Contact your local Traulsen Sales Representative (after completion of the service agency start-up, on required models) to arrange this.
V. e - SMARTCHILL DATA COMMUNICATIONS KIT: Each Traulsen blast chiller is communications capable. To make use of the optional communications feature, please refer to section "X." of this manual.
V. OTHER
V. a - RBC200/RT SERVICE AGENCY CHECK & START-UP: After installation and start-up of models RBC200 or RBC200RT, please contact the Service Department at (800) 825-8220 to arrange for a Mechanical Installation and Operation Inspection,” which is required by Traulsen in order to validate the warranty. On-site inspection not required for models RBC50 and RBC100.
V. b - ON-SITE BLAST CHILL TRAINING: Traulsen offers the operator comprehensive one and two day, on-site training in the proper operation of your Blast Chiller. Contact your authorized Traulsen equipment dealer for pricing information.
V. c - SERVICE INFORMATION: Before calling for service, please check the following:
Is the electrical cord plugged in?
Is the fuse OK or circuit breaker on?
Is the ON/OFF Power Switch in the ON position?
V. f - THE SERIAL TAG: The serial tag is a permanently affixed sticker on which is recorded vital electrical and refrigeration data about your Traulsen product, as well as the model and serial number. This tag is located inside the door on the right interior wall of the cabinet.
READING THE SERIAL TAG
Serial = The permanent ID# of your Traulsen
Model = The model # of your Traulsen
Volts = Voltage
Hz = Cycle
PH = Phase
Total Current = Maximum amp draw
Minimum Circuit = Minimum circuit ampacity
Lights = Light wattage
Heaters
Refrigerant = Refrigerant type used
Design Pressure = High & low side operating
pressures and refrigerant charge
Agency Labels = Designates agency listings
-9-
Page 11
VI. THE SMARTCHILL® CONTROL
VI. a - THE SMARTCHILL CONTROL - OVERVIEW: This unit is equipped with our exclusive SmartChill microprocessor control (Traulsen Blast Chill units manufactured prior to 6/03 were equipped with the DIGITRAUL II control, please refer to owner's manual part number 375-60180-00 for more information).
MAIN MENU AIR 41°F
BY TEMP BY PROD
BY TIME
08:05:01 MORE
The SmartChill® Controller
EZ START
The SmartChill® controller provides the ability to:
Select the chill mode: By Product, By Time or By
Temperature (chill or freeze)
Display the current air and product temperatures
and time.
Monitor product temperatures with three smart
probes to reduce chances of freezing.
Select Soft Chill to reduce the chances of
freezing in the final phase of chilling.
Provide service diagnostics to quickly check
machine functions and control circuitry.
Send Chill
SmartChill® computer software, providing state of the art HACCP data management.
VI. b - PRINTING CAPABILITY: The standard printer provides the ability to:
®
Cycle data via an RS232 port to
Print data from the last chill cycle with time,
date, and temperature information.
Charts chill temperatures vs. time at intervals
that can be set by the supervisor.
The label printer can print a condensed "LABEL" type of report with both PRODUCT and USER information.
VI. d - START-UP:
®
When power is turned ON to the blast chiller the start­up screen below appears.
SmartChill
RBC100
VERSION X.XX
VI. e - OVER TEMPERATURE: An OVER TEMPERATURE situation occurs if interior cabinet air temperature rises to 160°F or above. The unit will shut down and a service technician should be notified.
VI. f - IN THE EVENT OF A POWER INTERRUPTION: Following a power interruption, the system resumes at the previous activity. A report will also be printed containing the time of the power loss and the time of power return.
VI. g - GETTING STARTED: The Traulsen Blast Chiller is designed to chill its respective capacity of hot product from 135°F down to 40°F in approximately 90 minutes if loaded in pans no more than 2” deep. However, it is important to follow all the preceding guidelines for product loading and batching in order to duplicate this performance on-site.
Once you have insured that product is properly loaded into the pans and batched correctly, proceed to the next section in order to correctly operate the SmartChill controls chill feature modes.
VI. h - EZ START FEATURE: All Traulsen Blast Chillers built after June 1, 2006 include an EZ-Startfeature which allows a blast chill batch to be initiated with the touch of a single button located on the main menu.
VI. c - CONTROL BASICS: Begin by choosing a selection from the menu that appears on the control's display by pressing the button graphically connected to the display prompt. Four buttons are arranged on the left and four on the right. For example, to select BY TEMP, press the second button on the left.
Please note that in order to use this feature, one or more of the food probes must first be placed into hot product which is at least 40°F warmer than the interior cabinet temperature
When using this feature the factory preset chill cycle parameters are: Blast Chill, By Temperature, with a product end-point of 37°F, and are not adjustable by the operator.
-10-
Page 12
VII. OPERATING THE BLAST CHILL CONTROL - STARTING A CHILL CYCLE
MAIN MENU AIR 35°F
BY TEMP BY PROD BY TIME
08:05:01 MORE
Main Menu Display
MAIN MENU AIR 35°F
BY TEMP BY PROD
BY TIME
08:05:01 MORE
BY TEMPERATURE
TYPE: CHILL
↓↓
TARGET TEMP: 37
↓↓
°F
MAIN START
BY TEMPERATURE
TYPE: CHILL
↓↓
TARGET TEMP: 0
↓↓
°F
MAIN START
VII. a - STARTING A CHILL CYCLE - BY TEMP: Use of the chilling mode BY TEMPERATURE means that product will be constantly chilled until the food probe(s) temperature reaches the preset target temperature, at which time the cycle is complete and operation reverts to normal refrigerated holding mode.
The main menu should be displayed on the control. To begin a chill cycle BY TEMPERATURE follow the below instructions:
STEP ONE: Press the button to the left of where BY TEMPERATURE is
shown on the display. The menu will then change to show TYPE : CHILL.
STEP TWO: Select the TYPE by pressing the button to the left of where by
TYPE is shown on the display. The display will change between
↑↑
↑↑
STEP THREE: Adjust the TARGET TEMPERATURE if you wish to deviate from
↑↑
↑↑
CHILL (blast chill mode), SOFT (soft chill mode) and FREEZE (freeze chill mode).
the factory preset temperatures (see chart below). This is done by pressing the buttons to the left and right of the UP and DOWN arrows.
MODELS BY TEMP RANGE
All Models Blast Chill 37°F 33-40°F
All Models Soft Chill* 37
All Models Freeze* 0
*Soft Chill and Freeze modes are not available on GC units.
FACTORY PRESET
TARGET RANGE
°F 33-40°F
°F -22-28°F
STEP FOUR: Insert the food probes into the food product as shown in
section VI. a.
NOTE: The SmartProbes sense the product temperature and are automatically selected (if product temperature is 75°F or higher). If probes are not sensed, probes have to be enabled using the SELECT PROBE menu.
BY TEMPERATURE
TYPE: CHILL
↓↓
TARGET TEMP: 37
↓↓
°F
MAIN START
BY TEMPERATURE
TYPE: CHILL
↓↓
TARGET TEMP: 37
↓↓
°F
MAIN START
CHILLING AIR: 14°F
STEP FIVE: Close the door. You are now ready to begin chilling. If you are
satisfied with the selections made in steps 1 thru 3, press the
↑↑
↑↑
NOTE: You can return to the MAIN MENU at any time by pushing the button to the left of where MAIN is shown on the display.
↑↑
↑↑
When a programmed batch has reached completion the alarm will activate, providing an audible notification (buzzer). This can be turned OFF by p the button to the right of where MUTE is shown on the display. (This step is repeated as each probe reaches the target temperatures; see page 14).
button to the right of where START is shown on the display. The chill time will display in the lower left corner of the display: Hr: Min: Sec: (hours:minutes:seconds).
ressing
1 41°F DONE 3 2 44°F
1:16:01 MUTE
NOTE: After completion of all batches the unit will return to normal refrigerated holding temperatures (37°F). Product which was either BLAST or SOFT chilled may remain in the blast chiller. However, if a FREEZE CHILL cycle was completed product must be removed immediately upon batch completion.
-11-
Page 13
VII. OPERATING THE BLAST CHILL CONTROL - STARTING A CHILL CYCLE
VII. a - STARTING A CHILL CYCLE - BY TEMP (contd):
STEP SIX: Select the doneprobe(s) by pressing the button(s) to the left
or right of where that number probe(s) is displayed. Remove all product associated with the doneprobe(s) from the chiller. If all probes have completed their respective batches, the display changes to the HOLDING screen menu.
To remove a product before it is completed press the button to the right of where ADD/REMOVE is shown on the display.Select any other probes number to stop cycle and remove it. Answer, by pressing the button to the left/right of where NO/YES is shown on the display.
STEP SEVEN: The display will ask if you want to print a chill cycle data report
and/or label for that particular probe.
1) RECORD = Print probe report on standard printer only
2) LABEL = Print probe report on label printer only
3) BOTH = Print probe report on both standard and label printers.
To continue chilling without printing either, press the button to the left of where NONE is shown on the display.
To print a chill report for this probe, press the button to the right of where RECORD is shown on the display.
HOLDING AIR 37°F
1 DONE DONE 3 2 DONE
1:16:01 ADD/REMOVE
CHILLING AIR 14°F
1 41°F DONE 3 2 44°F
1:16:08 CONTINUE
SELECT PROBE:
1 39°F REMOVE 3 2 44°F
1:16:28 CONTINUE
STOP CYCLE ON #2
REMOVE PRODUCT?
NO YES
PRINT PROBE #
RECORD
LABEL
NONE BOTH
PRINTING
PLEASE WAIT...
To print a label for this probe, press the button to the right of where LABEL is shown on the display.
To print a both chill report and label for this probe, press the button to the right of where BOTH is shown on the display.
Multiple records and/or labels may be printed by pressing the appropriate button after previous printing is completed. When finished printing press NONE and the display will return to the MAIN MENU or PROBE MENU if there are still active probes.
Repeat as necessary when each probe reaches completion. When all probes are DONE, return to the MAIN MENU.
-12-
Page 14
VII. OPERATING THE BLAST CHILL CONTROL - STARTING A CHILL CYCLE
MAIN MENU AIR 35°F
BY TEMP BY PROD BY TIME
08:05:01 MORE
Main Menu Display
MAIN MENU AIR 35°F
BY TEMP BY PROD
BY TIME
08:05:01 MORE
BY TIME
TYPE: CHILL
↓↓
CYCLE TIME: 01:30
↓↓
↑↑
↑↑
MAIN START
BY TIME
TYPE: CHILL
↓↓
CYCLE TIME: 01:30
↓↓
↑↑
↑↑
MAIN START
NOTE: If desired you may insert the food probes into the food product as shown in section VI. a., however please be aware that these will only display the product temperatures and have no effect on the chilling process in this mode.
BY TIME
TYPE: CHILL
↓↓
CYCLE TIME: 01:30
↓↓
↑↑
↑↑
MAIN START
VII. b - STARTING A CHILL CYCLE - BY TIME: Use of the chilling mode BY TIME means that product will be constantly chilled until the set chill time, as determined by the operator, has elapsed, at which time the cycle is complete and operation reverts to normal refrigerated holding mode.
The main menu should be displayed on the control. To begin a chill cycle BY TIME follow the below instructions:
STEP ONE: Press the button to the left of where BY TIME is shown on the
display. The menu will then change to show TYPE : CHILL.
STEP TWO: Select the TYPE by pressing the button to the left of where by
TYPE is shown on the display. The display will toggle between CHILL (blast chill mode), SOFT (soft chill mode) and FREEZE (flash chill mode) each time you press this button.
STEP THREE: Adjust the CYCLE TIME (not required) if you wish to deviate
from the factory preset times (see chart below). This is done by pressing the buttons to the left and right of the UP and DOWN arrows.
MODELS BY TEMP TIME RANGE
All Models Blast Chill 01:30 00:01 To 09:00
All Models Soft Chill 01:30 00:01 To 09:00
All Models Freeze 01:30 00:01 To 09:00
STEP FOUR: Close the door. You are now ready to begin chilling. If you are
satisfied with the selections made in steps 1 thru 3, press the button to the right of where START is shown on the display. The chill time remaining will display in the lower left corner of the display: Hr: Min: Sec: (hours:minutes:seconds).
INITIAL TIME
SETTING
BY TIME
TYPE: CHILL
↓↓
CYCLE TIME: 01:30
↓↓
MAIN START
HOLDING AIR: 14°F
1 41°F 43°F 3 2 44°F
1:16:01 MUTE
HOLDING AIR 35°F 1 159
°F 156°F 3
2 154°FBY TIME 1:30:00 STOP/RESET
BY TIME
ADD 30 MINUTES
RESET TIMER
STOP CONTINUE
NOTE: Prior to selecting START you can return to the MAIN MENU at any time by pushing the button to the left of where MAIN is shown on the display.
↑↑
↑↑
When a programmed batch has reached completion (i.e. the timer has counted down to 0:00:00) the alarm will activate, providing an audible notification (buzzer). This can be turned OFF by p is shown on the display.
NOTE: After completion of a batch the unit will return to normal refrigerated holding temperatures (37°F). Product which was either BLAST or SOFT chilled may remain in the blast chiller. However, if a FREEZE CHILL cycle was completed product must be removed immediately upon batch completion.
OTHER BY TIME CONTROL FUNCTIONS During a chill cycle BY TIME, the control has several preset functions that can be accessed by pressing the button to the left of where STOP/RESET is shown on the display.
ADD 30 MINUTES: adds 30 additional minutes to the timer.
RESET TIMER: re-starts the timer at the original time setting.
CONTINUE: resumes the cycle at the time remaining.
STOP: control returns to the MAIN MENU.
ressing the button to the right of where MUTE
-13-
Page 15
VII. OPERATING THE BLAST CHILL CONTROL - STARTING A CHILL CYCLE
VII. c - STARTING A CHILL CYCLE - BY PRODUCT: Use of the chilling mode BY PRODUCT allows the operator to select from a listing of chill parameters for various previously programmed products. These products will then be chilled either BY TEMPERATURE or BY TIME, depending upon their individual settings. When the chill cycle is completed operation reverts to normal refrigerated holding mode.
The main menu should be displayed on the control. To begin a chill cycle BY PRODUCT follow the below instructions:
STEP ONE: Insert the food probes into the food product as shown in
section VI. a and close the door.
STEP TWO: Press the button to the right of where BY PRODUCT is shown
on the display. The menu will then change to show TYPE: CHILL.
STEP THREE: Select the USER (if more than one user has been previously
entered) by pressing the buttons to the left and right of the UP and DOWN arrows.
STEP FOUR: Select the PRODUCT to be chilled. The display will show the
two most recently chilled products. You can scroll through the listing of products by pressing the buttons to the left of the UP and DOWN arrows. See page 16 for more information.
MAIN MENU AIR 35°F
BY TEMP BY PROD BY TIME
08:05:01 MORE
Main Menu Display
MAIN MENU AIR 35°F
BY TEMP BY PROD BY TIME
08:05:01 MORE
BY PRODUCT
TYPE: CHILL
↓↓
TARGET TEMP: 37
↓↓
°F
MAIN START
SELECT USER:
↓↓
TIM SMITH
↓↓
BACK SELECT
SELECT PRODUCT:
↑↑
CHICKEN PARTS
↑↑
↓↓
SOUP VEGETABLE
↓↓
MAIN MENU
↑↑
↑↑
↑↑
↑↑
STEP FIVE: Once the product you wish to chill is shown on the display,
press the button to the right of where this is shown to recall that products chill paramaters and begin chilling.
If the product selected is being chilled BY TEMPERATURE, the chill cycle time will be shown in the lower left corner of the display: Hr: Min: Sec: (hours:minutes:seconds).
If the product selected is being chilled BY TIME, the time remaining will be shown in the lower left corner of the display: Hr: Min: Sec: (hours:minutes:seconds).
NOTE: You can return to the MAIN MENU at any time by pushing the button to the left of where MAIN is shown on the display.
When a programmed batch has reached completion the alarm will activate, providing an audible notification (buzzer). This can be turned OFF by p the button to the right of where MUTE is shown on the display.
(This step is repeated as each probe reaches the target temperatures; see page 14).
NOTE: After completion of all batches the unit will return to normal refrigerated holding temperatures (37°F). Product which was either BLAST or SOFT chilled may remain in the blast chiller. However, if a FREEZE CHILL cycle was completed product must be removed immediately upon batch completion.
ressing
SELECT PRODUCT:
↑↑
CHICKEN PARTS
↑↑
↓↓
SOUP VEGETABLE
↓↓
MAIN MENU
NOTE: If the product you wish to se­lect is on the Product List shown on page 20 but is not available from the SELECT PRODUCT menu of the con­trol display, it first needs to be enabled. The Supervisor should refer to Set-Up Products on page 23.
Refer to page 14 or 19 for printing procedures and information.
-14-
Page 16
VII. OPERATING THE BLAST CHILL CONTROL - STARTING A CHILL CYCLE
VII. d - THE CHILL BY PRODUCT FEATURE - PRODUCT LIST: Any product from the PRODUCT LIST can be chilled using the BY PROD mode, once it has been enabled in Setup Products (page 22). Only CHICKEN PARTS and SOUP VEGETABLE are initially enabled as preset at the factory.
NOTE: All products are initially set in the BY TEMP - CHILL mode with a Target Temperature of 37°F and Holding
Temperature of 37°F.
ASPARAGUS LAMB SALAD POTATO
BEANS LASAGNA SANDWICHES
BEANS BAKED LIVER SAUCE
BEEF MACARONI & CHEESE SAUCE CHEESE
BEEF CREAMED MACARONI & GROUND BEEF SAUCE MEAT
BEEF ROAST MEAT SAUCE TOMATO
BEEF TIPS MEAT GROUND SAUSAGE
BROCCOLI MEAT LOAF SOUP BEAN
CABBAGE STUFFED MEAT SLICED SOUP CREAM OF CELERY
CARROTS MEAT WITH SAUCE SOUP POTATO
CASSEROLE OATMEAL SOUP TOMATO
CEREAL COOKED PASTA SOUP VEGETABLE
CHICKEN & DUMPLINGS PEAS SPAGHETTI
CHICKEN PARTS PEPPERS STUFFED STARCH DISH
CHICKEN POT PIE PORK STEAK
CHOWDER CORN PORK CHOPS STEAK CHOPPED
COLE SLAW POTATO MASHED STEAK SALISBURY
COMBINATION DISHES POTATO SLICED STEAK SWISS
CORN POTATOES STEW
DRESSING CORNBREAD POTATOES SCALLOPED STEW BEEF
FISH BAKED POULTRY TACO MEAT
FISH BREADED POULTRY SLICED TUNA SALAD
GRAVY POULTRY WITH SAUCE TURKEY BREAST
GRITS PRE PLATES TURKEY ROAST
HAM RICE VEAL CHOPS
JELLO ROAST WHOLE VEGETABLES
NOTE: A list of the products can be printed by holding the button by MAIN MENU then pressing
BY PRODUCT.
-15-
Page 17
VII. OPERATING THE BLAST CHILL CONTROL - HOLD MODE & DEFROST
VII. e - REFRIGERATED HOLD MODE: At the completion of a chill cycle, regardless of the mode used, the Traulsen blast chiller reverts to normal refrigerated holding mode of 37°F. Hold mode can also be manually selected at any time (i.e. interrupting the chill cycle) by using the HOLD MODE feature. When in the holding mode both the mainteance and blast chill compressors will operate during cooling portions of the cycle.
The main menu should be displayed on the control. To initiate a HOLD MODE follow the below instructions:
STEP ONE: From the MAIN MENU, select MORE by pressing the button to
the right of where this is shown on the display. The menu shown will then change to display additional menu options.
STEP TWO: Press the button to the left of where HOLD PROD (hold product)
is shown on the display.
HOLDING will show on the display. The timer will indicate run time in the lower left corner of the display: Hr: Min: Sec: (hours:minutes:seconds).
NOTE: HOLD mode does not retain temperature vs. time data in memory; as a result printed reports are not available.
MAIN MENU AIR 35°F
BY TEMP BY PROD BY TIME
08:05:01 MORE
Main Menu Display
MAIN MENU AIR 35°F
BY TEMP BY PROD BY TIME
08:05:01 MORE
HOLDING AIR: 34°F
1 37
2 37
°F 37°F 3 °F
0:00:04 EXIT
VII. f - DEFROST: When not in a chill cycle, the Traulsen blast chiller will automatically start a defrost cycle every three hours while in refrigerated HOLD mode. However, a defrost can also be manually initiated by following the below procedure.
STEP ONE: From the MAIN MENU, select MORE by pressing the button to
the right of where this is shown on the display. The menu shown will then change to display additional menu options.
STEP TWO: Press the button to the left of where DEFROST is shown on the
display. The menu will then change slightly to show REMOVE FOOD, CANCEL and START.
NOTE: Remove food from the blast chiller before proceeding.
STEP THREE: Press the button to the right of where START is shown on the
display to initiate a manual defrost cycle. The defrost cycle will run for 40 minutes or until both the maintenance and blast chill coil temperatures reach 50°F. Once initiated, the defrost cycle will only terminate on time or temperature, and cannot be manually terminated.
For model RBC100, a common evaporator coil is used for the both the blast chill and maintenance compressors.
MAIN MENU AIR 35°F
BY TEMP BY PROD BY TIME
08:05:01 MORE
Main Menu Display
MAIN MENU AIR 35°F
BY TEMP BY PROD BY TIME
08:05:01 MORE
MAIN MENU 08:06:01
HOLD PROD PRINT
DEFROST SETUP
BACK
READY TO DEFROST REQUIRED IN XX MIN.
REMOVE FOOD
CANCEL START
XX = Number of minutes until next scheduled defrost.
-16-
DEFROSTING
MAINT 50 BLAST 49
00:10:05
°F °F
Page 18
VII. OPERATING THE BLAST CHILL CONTROL - PRINTING
VII. g - PRINTING BATCH/CHILL CYCLE DATA: Once a chill cycle is complete, data can be printed.
MAIN MENU AIR 35°F
BY TEMP BY PROD BY TIME
08:05:01 MORE
MAIN MENU 08:06:01
HOLD PROD PRINT DEFROST SETUP BACK
Press to select DATA. Press to change to a previous date. Press to change to a future date. For multi-batching, press to select probe. Press to select LABEL or BOTH. Press to return to MAIN MENU. Press to print selection.
PRINT: CYCLE
4/03 08:40
PRB#1 RECORD MAIN MENU PRINT
However, the following information can always be printed.
Press to select LIST. Press to change to a previous date. Press to change to a future date.
PRINT: DATA
4/03 08:00
12 HOUR LOG
Press to return to MAIN MENU. Press to print selection.
MAIN MENU PRINT
Optional Label Printer SampleStandard On-Board Printer Sample
CHILL CYCLE REPORT
MODE: FREEZE FOOD PRODUCT:SOUP VEGETABLE
USER: BOB SMITH
PROBE #2
STARTED: 04/11/03 13:08
0 40 70 140 13:09 13:10 13:11 13:12 13:13 13:14 13:15 13:16 13:17 13:18 13:19 13:20 13:21 13:22 13:23 13:24 13:25 13:26 13:27 13:28 13:29 13:30
REMOVED: 04/11/03 13:08 CYCLE TIME: 358 MINUTES HIGHEST: 140°F LOWEST -7°F TIME TO 70°F: 45 MINUTES TIME TO 40°F: 75 MINUTES
112 106
96 89 84 79 75 70 66 63 60 57 54 51 49 49 47 46 44 42 40 38
NOTE:
When printing at the end of a BY TEMP cycle, the controller will print an abbreviated Chill Cycle Report. Only the data from when the cycle started until the desired target temperature was reached will be printed. If for any reason after reaching the set temperature the temperature increased above 40F during the HOLD cycle, that information will be printed at the bottom of the Chill Cycle Report,
CHILL CYCLE REPORT
MODE: FREEZE FOOD PRODUCT:SOUP VEGETABLE
USER: BOB SMITH
PROBE #2
STARTED: 04/11/03 13:08 REMOVED: 04/11/03 13:08 CYCLE TIME: 358 MINUTES HIGHEST: 140°F LOWEST -7°F TIME TO 70°F: 45 MINUTES TIME TO 40°F: 75 MINUTES
-17-
Page 19
VII. OPERATING THE BLAST CHILL CONTROL - SET UP PRODUCTS
VII. h- SET-UP PRODUCTS: Pages 15 and 16 describe the chill BY PRODUCT mode, where the operator can choose from a preprogrammed list of product chill parameters. As shipped from the factory, only two products on the list are enabled and ready from immediate use (chicken parts and vegetable soup). To enable any of the other food products which appear on the list please follow the below procedure.
STEP ONE: From the MAIN MENU, select MORE by pressing the button to
the right of where this is shown on the display. The menu shown will then change to display additional menu options.
STEP TWO: Press the button to the right of where SETUP is shown on the
display. Note when you first enter SETUP, only Preset Supervisor is available. On the PASSWORD (PIN) line, use the UP or DOWN keys until 57 is displayed as the Preset Supervisors Personal Identification Number. Press ENTER. The menu shown will then change back to display the SETUP menu options.
If users have already been setup, select the supervisors name using the UP or DOWN keys. On the next line, use the UP or DOWN keys to enter their Password (or Personal Identification Number). Press ENTER. The menu shown will then change back to display the SETUP menu options.
STEP THREE: Press the button to the left of where PRODUCTS is shown on
the display.
MAIN MENU AIR 35°F
BY TEMP BY PROD BY TIME
08:05:01 MORE
MAIN MENU AIR 35°F
BY TEMP BY PROD BY TIME
08:05:01 MORE
MAIN MENU 08:06:01
HOLD PROD PRINT DEFROST SETUP BACK
SELECT SUPERVISOR:
↓↓
PRESET SUPERVISOR
↓↓
↓↓
PASSWORD (PIN): 00
↓↓
CANCEL ENTER
SELECT SUPERVISOR:
↓↓
TIM SMITH
↓↓ ↓↓
PASSWORD (PIN): 57
↓↓
CANCEL ENTER
↑↑
↑↑ ↑↑
↑↑
↑↑
↑↑
↑↑
↑↑
STEP FOUR: Press the button to the left of where ENABLE / DISABLE is
shown on the display to choose what products are enabled on the product list (only an enabled product is available to chill BY PRODUCT).
STEP FIVE: Press the button to the right of where BACK is shown on the
display in order to save the revised BY PRODUCT listing.
NOTE: If it is necessary to edit the settings (BY TEMPERATURE or BY TIME and their associated endpoints) please proceed by using the below procedure.
STEP ONE: Select ENABLE / DISABLE to choose what products are enabled
from the Product List. Only an enabled product is available to chill BY PRODUCT.
STEP TWO: Select EDIT SETTINGS to adjust chill parameters for any product
that has already been enabled (BACK returns to SETUP).
STEP THREE: After selecting ENABLE / DISABLE, use the UP or DOWN keys
to select a product from the list. Press to change ENABLED: NO to YES to enable the product or to change YES to NO to disable it. The two most recently chilled products cannot be disabled. BACK saves the enabled and returns to SETUP PRODUCTS.
STEP FOUR: After selecting EDIT SETTINGS, use the UP or DOWN keys to
select a product. Finish all the below steps to change any setting(s).
Select the Type: CHILL, SOFT CHILL or FREEZE.
Select BY TEMP or BY TIME. Use the TEMP if BY TEMP is displayed, or to adjust the CYCLE TIME if BY TIME is displayed.
Select MORE and use the
Press SAVE to keep the changes and return to SETUP PRODUCTS.
(CANCEL returns to SETUP PRODUCTS without saving the changes. BACK returns to the previous screen).
↑↑
or
keys to adjust the HOLD TEMP.
↑↑
↑↑
or
keys to adjust the TARGET
↑↑
-18-
SETUP 09:04:11
PRODUCTS SYS PAR
USERS MAIN MENU
SETUP PRODUCTS:
ENABLE/DISABLE
EDIT SETTINGS
BACK
PRODUCT SELECTION:
↓↓
ASPARAGUS
↓↓
ENABLED: NO
EDIT
BACK
SETUP PRODUCTS:
ENABLE/DISABLE EDIT SETTINGS
BACK
↓↓
ASPARAGUS
↓↓
TYPE: CHILL
↓↓
TARGET TEMP: 37
↓↓
°F
BY TEMP MORE
↓↓
ASPARAGUS
↓↓
↓↓
HOLD TEMP: 37
↓↓
°F
CANCEL
BACK SAVE
↓↓
ASPARAGUS
↓↓ ↓↓
HOLD TEMP: 37
↓↓
°F
CANCEL
BACK SAVE
↑↑
↑↑
↑↑
↑↑
↑↑
↑↑
↑↑
↑↑
↑↑
↑↑
↑↑
↑↑ ↑↑
↑↑
Page 20
VII. OPERATING THE BLAST CHILL CONTROL - SET UP USERS
MAIN MENU AIR 35°F
BY TEMP BY PROD BY TIME
08:05:01 MORE
MAIN MENU AIR 35°F
BY TEMP BY PROD BY TIME
08:05:01 MORE
MAIN MENU 08:06:01
HOLD PROD PRINT DEFROST SETUP BACK
SETUP 09:04:11
PRODUCTS SYS PAR
USERS
MAIN MENU
VII. h - SET-UP USERS: The SmartChill® control offers the convenience of having individual operators have their own unique BY PRODUCT and SYSPAR settings already programmed, facilitating the changing chilling needs of different production shifts. To add new user settings please follow the below procedure.
STEP ONE: From the MAIN MENU, select MORE by pressing the button to
the right of where this is shown on the display. The menu shown will then change to display additional menu options.
STEP TWO: Press the button to the right of where SETUP is shown on the
display. Note when you first enter SETUP, only Preset Supervisor is available. On the PASSWORD (PIN) line, use the UP or DOWN keys until 57 is displayed as the Preset Supervisors Personal Identification Number. Press ENTER. The menu shown will then change back to display the SETUP menu options.
If users have already been setup, select the supervisors name using the UP or DOWN keys. On the next line, use the UP or DOWN keys to enter their Password (or Personal Identification Number). Press ENTER. The menu shown will then change back to display the SETUP menu options.
STEP THREE: Press the button to the left of where USERS is shown on the
display.
SETUP USERS:
ADD DELETE ALL
EDIT/DELETE
BACK
SELECT SUPERVISOR:
↓↓
TIM SMITH
↓↓
↓↓
PASSWORD (PIN): 07
↓↓
CANCEL ENTER
ENTER NAME:
↓↓
_
↓↓
BACK NEXT CANCEL ENTER
ENTER NAME:
↓↓
TIM SMIT
↓↓
H
↑↑
↑↑
BACK NEXT CANCEL ENTER
SETUP USER:
SECURITY LEVEL:0PER
↓↓
PASSWORD (PIN): 00
↓↓
ENTER
SETUP USER: SECURITY LEVEL:0PER
↓↓
PASSWORD (PIN): 23
↓↓
ENTER
SETUP USER: SECURITY LEVEL:0PER
↓↓
PASSWORD (PIN): 23
↓↓
ENTER
STEP FOUR: Press the button to the left of where ADD is shown on the
display to add new users to the roster.
NOTE: The first user entered is automatically given Supervisor access. This can be changed by using the EDIT/DELETE selection to change a given users security level or PIN number,
↑↑
↑↑
↑↑
↑↑
STEP FIVE: To enter the name of a new user, press the buttons to the left
↑↑
↑↑
STEP SIX: Select the new users security level by pressing the button to
↑↑
↑↑
↑↑
↑↑
↑↑
↑↑
STEP SEVEN: To enter the new use’s two-digit PASSWORD, press the buttons
or delete an entire user from the roster. DELETE ALL removes all users from the roster.
and right of the UP and DOWN arrows to scroll through the alphabet, one character at a time. Press the button to the right of where NEXT is shown on the display to set this character and move on to the next letter, repeating this until the new users name is complete.
NOTE: BACK moves the cursor one space to the left to allow for editing. Press the button to the right of where ENTER is shown on the display to save the new users name (CANCEL aborts this process).
the right of where SECURITY LEVEL is shown on the display (pressing this button toggles between OPER (operator level) and SUPV (supervisor). Please note that at least one user must already be set-up as a supervisor before an operator access level can be selected.
to the left and right of the UP and DOWN arrows to scroll through the numbers 00-99. Press the button to the right of where ENTER is shown on the display to set this users access level and pin number. The display will return to the SET­UP USERS menu. Press the button to the right of where BACK is shown on the display to return to the SETUP menu. Press the button to the left of where MAIN is shown on the display to return to the main menu.
-19-
Page 21
VII. OPERATING THE BLAST CHILL CONTROL - SYSPAR
VII. i - ACCESSING SYS PAR SETTING LEVEL:
SYS PAR represents the supervisor level of access to the SmartChill® controller, allowing on-site adjustment to the factory preset operating parameters.
To enter the SYSPAR access level please follow the below procedure.
STEP ONE: From the MAIN MENU, select MORE by pressing the button to
the right of where this is shown on the display. The menu shown will then change to display additional menu options.
STEP TWO: Press the button to the right of where SETUP is shown on the
display. Note when you first enter SETUP, only Preset Supervisor is available (as delivered, only the factory preset supervisor’s PIN access or ID is set-up).
Press the buttons to the left and right of where PASSWORD is shown on the display to scroll to the factory preset PIN of 57. Press the button to the right of where ENTER appears on the control to enter this PIN number. The SETUP display menu
is displayed.
NOTE: If users have already been setup, select the supervisor’s name
using the UP or DOWN keys. On the next line, use the UP or DOWN keys to enter their Password (or Personal Identification Number). Press the button to the right of where ENTER appears on the control to enter this selection. The SETUP display menu is displayed.
STEP THREE: From the SETUP display menu , select the button to the right of
where SYS PAR is shown on the display. Refer to the diagram on page 21 in order to access the various Sys Par settings
MAIN MENU AIR 35°F
BY TEMP BY PROD BY TIME
08:05:01 MORE
MAIN MENU 08:06:01
HOLD PROD PRINT DEFROST SETUP BACK
SELECT SUPERVISOR:
↓↓
PRESET SUPERVISOR
↓↓
↓↓
PASSWORD (PIN): 00
↓↓
CANCEL ENTER
SELECT SUPERVISOR:
↓↓
PRESET SUPERVISOR
↓↓
↓↓
PASSWORD (PIN): 57
↓↓
CANCEL ENTER
MAIN MENU 08:06:01
HOLD PROD PRINT DEFROST SETUP BACK
SETUP 09:04:11
PRODUCTS SYS PAR USERS MAIN MENU
SYS PAR: SET CLOCK
ITEM: MONTH
VALUE:APRIL
CANCEL ENTER
↑↑
↑↑
↑↑
↑↑
↑↑
↑↑
↑↑
↑↑
SYS PAR Menu Display
-20-
Page 22
VII. OPERATING THE BLAST CHILL CONTROL - SYSPAR
VII. j - SYSPAR - SETTING THE VARIOUS CONTROL FEATURES:
By accessing SYSPAR (system parameters), the operator can adjust many control features to better suit their operational needs, such as: Clock Settings, Probes, Temperature Scale (F or C), Alarm Settings and Chill Parameters. It also provides for an easy return to the original factory default settings with a RESET feature.
From the SETUP screen, select SYS PAR to get:
Press to select SYS PAR. Press to select SYS PAR.
Press to decrease ITEM. Press to increase ITEM.
Press to decrease VALUE. Press to increase VALUE.
Press to return to MAIN MENU* Press to return to SETUP with saving.
*without saving.
1) SET CLOCK a) MONTH (JANUARY – DECEMBER) b) DATE (1 – 311) c) YEAR (2003 – 2079) d) DAY OF WEEK (SUNDAY – SATURDAY) e) HOUR (0 – 23) f) MINUTE (0 – 59) g) DLS TIME (ENABLED – DISABLED)
2) PROBES a) 1 (ON – OFF) b) 2 (ON – OFF) c) 3 (ON – OFF)
3) DISPLAY a) TEMPERATURES (IN DEG C – IN DEG F)
4) LOGGING a) TIME (5-MINUTES – 30-MINUTES)
5) ALARM a) CYCLE RUNNING (NO – yes) b) CYCLE ENDS (NO – yes) c) PRINTER ERROR (NO – yes) d) HIGH/LOW TEMP (no – YES) e) POWER FAILURE (no – YES)
6) REMINDERS a) DOOR OPEN (0 – 2 MINUTES)
7) BLAST a) TARGET (33 – 40) b) AIR (10 – 40) c) HOLD (10 – 40) d) HIGH ALARM (35 – 60) e) LOW ALARM (-30 – 34)
8) SOFT CHILL a) BY TEMP (5 – 20) b) BY TIME (10 – 90) c) 2ND TEMP (10 – 40)
9) FREEZE CHILL a) TARGET (-22 – 28) b) AIR (-32 – 20) c) HOLD (10 – 40) d) HIGH ALARM (20 – 45) e) LOW ALARM (-30 – 0)
10) RESET a) PARAMETERS (YES – NO)
SYS PAR: SET CLOCK
ITEM:MONTH
VALUE:APRIL
CANCEL ENTER
SYS PAR Menu Display
SYS PAR: SET CLOCK
ITEM:MONTH
VALUE:APRIL
CANCEL ENTER
SYS PAR: SET CLOCK
ITEM:DATE
VALUE:04/XX/00
CANCEL ENTER
SYS PAR: SET CLOCK
ITEM:YEAR
VALUE:04/14/XX
CANCEL ENTER
SYS PAR: SET CLOCK
ITEM:HOUR
VALUE:XX:00
CANCEL ENTER
SYS PAR: SET CLOCK
ITEM:MINUTE
VALUE:10:XX
CANCEL ENTER
1
Last day is corrected for month and leap year.
-21-
Page 23
VIII. SMARTCHILLTM COMMUNICATIONS
VIII. a - INTRODUCTION: All Traulsen SmartChill cations. However, an optional software/hardware kit is required to make this compatible with your PC. Use of this provides many user advantages, such as:
Retrieving Batch/Chill Cycle Data
Viewing Users and Their Status
Exporting Data To A Spreadsheet
Adding Additional Products To The BY PRODUCT Mode
VIII. b ­IBM PC, Pentium II 300mhz or greater, Windows 95, 98, 2000, ME or NT operating system, 10 x CD ROM Drive, 64 MB RAM, 800 x 600 display, 24 bit color support.
VIII. c - OPERATION: For more information and operation detail, please refer to the SmartChill® Communications User’s Guide, form number TR35853.
VIII. d - COMMUNICATION WITH SMARTCHILL®: During communication with the SmartChill® program on a PC, the screen below displays.
SYSTEM REQUIREMENTS:
®
equipped blast chiller models are supplied from the factory capable of on-line communi-
COMMUNICATING WITH COMPUTER
PLEASE WAIT...
VIII. e - HARDWARE CONNECTION: To utilize the communication features of the SmartChill® control, it is necessary to connect this to a PC using its RS232 data port. See form number TR35853 for more information.
-22-
Page 24
IX. GLOSSARY
Alarms: Sets buzzer intervals after Door is Open or when to be notified that the Compressor needs to be Cleaned. By Temp: Chill cycle that terminates when the probes reach the Target Temperature. By Time: Chill cycle that terminates after a set amount of time has lapsed. By Prod: Chill cycle that terminates after a particular product’s specified chill parameters are met (the parameters
can be set either By Temp or By Time with specific cut-offs for a particular product. Chill: Chilling Cycle that may end with either Time or Temperature controlled events. (Also see Soft Chill or Freeze).
Clock: Allows the Date and Time to be entered so the system’s clock correctly records chilling events. Cycle #: The system assigns a consecutive number to each Chill Cycle. Defrost: System Controlled Defrost occurs after three hours of chilling (this can also be set to occur at between
2 - 6 hours). The defrost will not begin during a chill cycle. The system waits until it is in Holding mode before starting the defrost cycle. The Defrost from the Main Menu is a manual defrost that will not run if selected and unneeded. The Defrost cycle requires about 30 minutes (this can also be set from 20 - 60 minutes in duration as needed). Fac Presets: Factory Presets are system parameters that are set at the factory but can be changed by the supervisor. Freeze: This mode allows the product to be frozen down to a target temperature. The target temperature range available for freeze mode varies from -22°F to 28°F. Hold Prod: After completed chill cycle or when selected from the Main Menu, the chiller will act like a regular refrigerator.
Label: A condensed Chill Cycle Report that can be printed on adhesive-backed label stock by the label printer. Logging: The time interval at which Chill Cycle data (temperature vs. time) is logged into memory for record
purposes. The factory setting is 5 minutes.
Main Menu: The two initial menus available from the controller after the chiller is turned on. Mode: Basic chiller operating parameters are available from Sys Par in Setup mode.
Chill mode parameters allow adjustment of the target temperature, the air temperature during chill mode, the hold mode temperature, the high alarm temperature, the low alarm temperature and the maximum chill mode target temperature. Soft Chill mode parameters apply a modification of some of the Chill settings during the final portion of the chill cycle if Soft Chill is selected. Soft Chill provides additional protection against freezing of surfaces.
Oper: An Operator is a user who is allowed to operate the chiller and make reports of chill cycles performed. Print: Allows a report of any Chill Cycle and probe to be printed. Chillers equipped with the optional second printer
can print the condensed ‘Label’ type of report. All Chillers can print the ‘Record’ type of report. Probe #: Each probe is numbered and its temperature vs. time is recorded for each probe # during every BY TEMP chill cycle and the record can be printed, either at the end of the chill cycle or subsequently. Product List: A list of products in system memory which can have individual chill parameters specifically set for each product (assuming that the product is already enabled). Refer to Setup Products. Record: Type of report that can be printed by all chillers. This report provides a record of time vs. temperature for a specific Probe and Chill Cycle. Remote Alarm: The chiller can be wired to a remote alarm which will close the remote alarm circuit in the event of one or more of the following situations: Printer Error, Cycle End, Door Open, High or Low Temperatures or Power Failure. If Cycle Running is chosen, the remote alarm circuit will close when a chill cycle is running and all other remote alarm settings are overridden (reset to NO). The supervisor can determine which events the remote alarm will signal by adjusting the settings in the Sys Par (System Parameters) section.
Setup: Specific control settings that can be set by the supervisor which determine how the chiller will operate. Soft Chill: Type of chill process that moderates the temperatures and fan speed near the end of the chill cycle to
provide less risk of freezing at the product’s surface. Supv: A Supervisor is a user who is allowed to identify the users and limit their access to system parameters, enable products to be selected, set specific product chill parameters and change system parameters. Sys Par: System Parameters are control settings that determine how the chiller will operate. These settings can be adjusted by the supervisor in Setup mode.
Temps in Temps in °F: If so displayed on the Sys Par 1 screen, all temperatures will be recorded in °F (Fahrenheit).
°
C: If so displayed on the Sys Par 1 screen, all temperatures will be recorded in °C (Celsius).
-23-
Page 25
X. REPLACEMENT PARTS LIST
MODEL NUMBER PART/DESCRIPTION PART # RBC50 CORDSET - 115V 333-13013-01 RBC50 POWER PACK ASSEMBLY 900-60233-00 RBC50/RBC100 6” HIGH STAINLESS STEEL LEGS 344-13168-01 RBC50 STAINLESS STEEL SIDE PANEL 401-60027-01 RBC50 UNIVERSAL TRAY SLIDE 701-60115-00 RBC100 LOUVER ASSEMBLY 500-60154-00 RBC100 DRAINPAN 701-60105-00 RBC100 PROBE CABLE HOOK 344-60081-00 ALL MODELS HINGE BODY 344-28482-00 ALL MODELS HINGE COVER 344-28486-00 ALL MODELS HINGE CAM 344-28488-00 ALL MODELS HINGE BRACKET 344-28487-00 RBC100 HORIZONTAL BREAKER CAP 345-60011-04 RBC100 VERTICAL BREAKER CAP 345-60011-05 RBC100/200/400 LOCK KEEPER 346-60018-00 RBC100/200/400 LOCK KEEPER BRACKET 346-60019-00 RBC100/200/400 SMARTCHILL® CONTROL KIT SER-60461-00 RBC100 DOOR - HINGED RIGHT 200-60059-00 RBC100 TRAY SLIDE 342-60014-00 RBC100 PRINTER COVER 701-60741-00 ALL MODELS STANDARD PRINTER PAPER 400-60003-00 ALL MODELS LABEL PAPER 400-60004-00 ALL MODELS SMART PROBE 333-60331-00 RBC200/200RT LOUVER ASSEMBLY 500-60138-00 RBC200/200RT ROLL-IN RAMP 501-60409-00 RBC200/200RT RECORD/LABEL PRINTER 950-60355-00 RBC200/200RT PRINTER COVER 701-60724-01 RBC200/200RT DOOR - HINGED LEFT 200-36064-00 RBC400/400RT LOUVER ASSEMBLY 500-60138-00 RBC400/400RT ROLL-IN RAMP 501-60409-00 RBC400/400RT RECORD/LABEL PRINTER 950-60355-00 RBC400/400RT PRINTER COVER 701-60724-01 RBC400/400RT DOOR - HINGED LEFT 200-36064-00
-24-
Page 26
XI. SUMMARY OF ERROR MESSAGES
SYSTEM/CONTROL ERROR CURRENT PROBE IS BAD CHECK FOOD PROBES PLUGGED IN EXIT
CHILLING AIR: 10°F
°
41
°
2 37
F
F 3
STOP/RESET
FAILED PROBE (#1)
SYSTEM/CONTROL ERROR CHILL TIME EXCEEDED CONTACT SERVICE! EXIT
SYSTEM/CONTROL ERROR DEFROST FAILURE CONTACT SERVICE! EXIT
XI. a - FOOD PROBE ERROR DURING CHILL CYCLE BY TEMP: In the event of a food probe error during a BY TEMP chill cycle, the control automatically switches to a BY TIME chill cycle. The timer will begin to countdown from 90 minutes, at which time the chill cycle will be complete.
XI. b - FOOD PROBE ERROR DURING CHILL CYCLE BY TIME: In the event of a food probe error during a BY TIME chill cycle, or during a refrigerated holding cycle, the control will no longer display a temperature for that probe.
XI. c - CHILL TIME EXCEEDED: In the event a chill cycle does not complete within six hours, the control automatically switches operation to a refrigerated holding cycle. This cycle will continue until the operate selects EXIT and returns to the main menu to choose another cycle option.
XI. d - DEFROST FAILURE: Occurs when either a coil probe temperature falls below 25°F after a de­frost cycle, or in the event of a probe short circuit. Unit automatically switches to IDLE mode.
SYSTEM/CONTROL ERROR NO PRODUCT PROBES CHECK FOOD PROBES USE BY TIME EXIT
SYSTEM/CONTROL ERROR OVER TEMPERATURE CONTACT SERVICE! TURN OFF/UNPLUG UNIT
PRODUCT DETECTED! STARTING HOLD MODE CHECK FOOD PROBES EXIT
AIR TEMP SENSOR NOT READING CONTACT SERVICE TURN OFF/UNPLUG UNIT
XI. e - NO PRODUCT PROBES: Occurs when either a BY TEMP or BY PRODUCT chill cycle has been at­tempted, but no food probes are connected. Unit automatically switches to IDLE mode.
XI. f - OVER TEMPERATURE: Occurs when cabinet air temperature rises above 160°F. Unit automati­cally turns off all compressors, fans and defrost heaters. NOTE: To reset control after an OVER TEMPERATURE alarm it is necessary to either turn OFF or unplug the unit.
XI. g - PRODUCT DETECTED W/O CYCLE STARTED: Occurs when cabinet air temperature rises above 40F for ten minutes (with product in the unit but no chill cycle started). Unit automatically switches to a refrigerated holding cycle.
XI. h - CABINET AIR TEMPERATURE SENSOR: Occurs when the cabinet air sensor has shorted or is open. Unit automati­cally turns off compressors, fans and defrost heaters.
NOTE: To reset the control after an air temperature sensor failure, it is necessary to turn off or unplug the unit and replace the faulty air tempera­ture sensor.
-25-
Page 27
XII. WARRANTY INFORMATION
STANDARD DOMESTIC WARRANTY
TRAULSEN warrants new equipment to the original purchaser, when installed within the United States against defective material and workmanship for one (1) year from the date of original installation. Under this warranty, TRAULSEN will repair or replace, at its option, including service and labor, all parts found to be defective and subject to this warranty. The compressor part (self­contained only) is warranted for an additional four (4) years. During this period TRAULSEN will supply replacement compressor(s) if deemed defective, however, all installation, recharging and repair costs will remain the responsibility of the owner.
This warranty does not apply to damage resulting from fire, water, burglary, accident, abuse, misuse, transit, acts of God, terrorism, attempted repairs, improper installation by unauthorized persons, and will not apply to food loss.
The remote compressor used on models RBC200 and RBC200RT, when purchased from Traulsen, is warranted for a period of five (5) years from the date of original installation. During this period TRAULSEN will supply replacement compressor if deemed defective, however, after the first year, all installation, recharging and repair costs will remain the responsibility of the owner.
THERE ARE NO ORAL, STATUTORY OR IMPLIED WARRANTIES APPLICABLE TO TRAULSEN, INCLUDING BUT NOT LIMITED TO, ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR ANY PARTICULAR PURPOSE WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE HEREOF. TRAULSEN SHALL HAVE NO OBLIGATION OR LIABILITY FOR CONSEQUENTIAL OR SPECIAL DAMAGES, GROWING OUT OF OR WITH RESPECT TO THE EQUIPMENT OR ITS SALE, OPERATION OR USE, AND TRAULSEN NEITHER ASSUMES NOR AUTHORIZES ANYONE ELSE TO ASSUME FOR IT ANY OBLIGATION OR LIABILITY IN CONNECTION WITH THE EQUIPMENT OR ITS SALE, OPERATION OR USE OTHER THAN AS STATED HEREIN.
INTERNATIONAL COMMERCIAL WARRANTY
(for Canadian warranties see domestic US warranty)
TRAULSEN warrants to the original purchaser the Refrigeration Equipment manufactured and sold by it
to be free from defects in material and workmanship under normal use and service for a period of one (1) year from date of shipment. Under this warranty, TRAULSEN will reimburse the purchaser for the replacement of any part of said equipment (excluding dryers & refrigerant gas) which then proves to be defective. This warranty does not apply to damage resulting from fire, water, burglary, accident,
abuse, misuse, transit, acts of God, terrorism, attempted repairs, improper installation by unauthorized persons, and will not apply to food loss.
TRAULSENS standard warranty does not apply to Export Sales. Rather, for a period of one (1) year from date of original installation not to exceed Fifteen (15) months from date of shipment from factory, TRAULSEN:
will replace, F.O.B. factory, any defective parts normally subject to warranty.
will not cover the cost of packing, freight or labor such costs being the sole responsibility of the
dealer.
THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES EITHER EXPRESSED OR IMPLIED AND CONSTITUTES TRAULSEN’S FULL OBLIGATION AND LIABILITY. WARRANTIES NOT AVAILABLE ON REMOTE MODELS.
-26-
Page 28
XIII. MECHANICAL TROUBLE SHOOTING GUIDE
1. Condensing unit fails to start when programming a new batch.
2. Batch requires too much time to chill product down to 40° F. Chill Cycle Batch Over 6-Hours will ALARM and a printout will note the chill cycle has exceeded maximum safe time.
3. Food Probe Failure - ALARM will occur during a chill cycle batch with printout noting the Food Probe Failure Warning.
4. Refrigeration Failure - ALARM with a printout noting the warning will occur when the interior temperature exceeds 100° F for more than 20-minutes. Blast Chill refrigeration system will shut down as a safety default. The compressors and blower fans are shut off and the control key pad is locked out.
a. Check power supply to condensing unit. b. Batch was not programmed properly. Select chill method, press START, and if
required select probes.
c. System problem. Call for service.
a. Is the door closed properly? If not, close door completely. b. Too much product loaded. Adjust the load to not exceed capacity of the unit. c. Product depth in pan exceeds 2. Reduce pan load per guidelines on page 7. d. Has pan been covered with a lid, plastic wrap or foil, and is this not in direct contact
with the product? Cover product correctly as per guidelines on page 7. e. Perhaps the product loaded is of a high density. Allow additional chilling time. f. Dirty condenser coil. Clean condenser as per instructions on page 6. g. Evaporator coil iced. Allow to defrost (press DEFROST to initiate a manual defrost).
a. Food Probe Failure - printer will notify the operator that it is converting to chilling BY
TIME.
b. When starting a BY TEMP cycle, if food probe is not available, there is an open circuit.
Check the probe plug connection. c. Food probe was placed in excessively hot product. Product temperatures exceeding
210° F can result in the probe reporting false temperatures. Cool food probe and test
again. d. Food probe fails and will then operate correctly at a later time. Program a BY
TEMP batch using the suspect probe. Wiggle the food probe wire. If a second Food
Probe Failure occurs the food probe is defective. Replace with new food probe. g. Damaged or defective food probe. Replace with new food probe.
Refrigeration Failure CORRECTION - Remove power from the unit. Unplug and then replug the unit or reset the circuit breaker (OFF and back ON). The Blast Chiller will reset and turn ON. Power Loss Failure will printout when reset.
a. Batch programming was incomplete or incorrect and chill cycle did not start. Try
programming batch again. b. Too much product loaded. Adjust the load to not exceed capacity of the unit. c. Dirty condenser coil. Clean condenser as per instructions on page 6. d. Refrigeration system failure, unit will not cool after having been reset. Call service for
repair.
5. Power Loss Notification - Printout notes the time power was lost and the time in which it was restored.
6. Cannot program a new batch.
7. Printer not printing.
8. No display on control.
9. Condensation on exterior surface.
Traulsen
4401 Blue Mound Road Fort Worth, TX 76106 Phone: (800) 825-8220 Fax-Svce: (817) 740-6757 Website: www.traulsen.com
Quality Refrigeration
a. Power was lost to the Blast Chill unit. If product was inside the unit see the printout
to determine if product temperature was compromised. The printout will show the temperature before and after the interruption.
a. Unit may be in a defrost cycle. Batch programming cannot be done while in a
defrost cycle.
b. If during a BY TEMP chill cycle, a new batch can be added by using the ADD/REMOVE
option.
a. Printer is out of paper. Replace printer paper roll as per instructions on page 6. b. Printer paper may be installed incorrectly. Verify that the thermal sensitive side
of the paper is on the top and feed door closed, see instructions on page 6 or label in the printer cavity.
c. Paper does not feed or jams behind the paper feed slot in the cover. Remove paper
and reinstall as per instructions on page 6 or label in the printer cavity.
a. Check power supply and circuit breaker. b. Confirm unit is correctly plugged into a working power outlet. c. System problem. Call for service.
Condensation on the exterior surface of the unit is perfectly normal during periods of high humidity, otherwise refer below for other possible causes.
a. Check door alignment and gasket for proper seal. b. On Roll-In/Roll-Thru models, check bottom door sweep for proper adjustment. c. Electric door heater malfunction. Call for service.
HOURS OF OPERATION:
© 2006 Traulsen - All Rights Reserved
Monday thru Friday 7:30 am - 4:30 pm CST
Loading...