Transtector APEX Series, APEX II, APEX III, APEX IV Installation Manual

Installation Manual
APEX Series
Silicon and MOV Panel Protection
APEX Series
800.882.9110 | 208.772.8515 | www.transtector.com
APEX Series | Installation Guide
Table of Contents
Table One - Application Rating 3 Figure 1 - Mounting Details 4
Figure 2 - 120T Conguration 5 Figure 3 - 120S Conguration 5 Figure 4 - 240S Conguration 6 Figure 5 - 120W, 240W Conguration 6 Figure 6 - 240D Conguration 6 Figure 7 - Card Installation 9
WARNING: AC Power to the surge suppressor, at the surge suppressor, and in the vicinity of the surge suppressor MUST be disconnected prior to performing the following mechanical and electrical installation procedure.
2
WARNING: Wiring conductors utilized to attach Phases L1, L2, L3, the Neutral and Safety Ground from the AC power source to the APEX Series should be color-coded to conform with appropriate electrical codes and/or accepted wiring practices. It is very important to make no assumptions that wiring colors on existing electrical installations correspond to proper phase, neutral, or ground connections.
WARNING: The disconnect utilized in the current path from the electrical distribution and the APEX Series must be coordinated to operate properly in conjunction with all other disconnects contained within the same electrical distribution.
WARNING: Proper electrical connections must be accomplished in accordance with applicable International, National, and/or Local electrical code requirements.
APEX Series Installation
The APEX Series surge suppressor models are designed specically to operate on the following congurations:
Congurations
120V 1Ø 240V 3Ø Delta
120/240 Split 1Ø 220/380 3Ø Wye
120/208 3Ø Wye 230/400 3Ø Wye
240V 1Ø 240/415 3Ø Wye
Suppression is accomplished in parallel between phase conductors and/or between phase and the neutral conductors, depending upon the voltage conguration. Once activated, the suppressor remains operative until excess transient energy is dissipated and instantaneous peak line voltage falls below the approximate 120% overvoltage threshold. At that time the suppressor automatically deactivates, resets to a “ready” state, and awaits further transient activity.
3
Please take a moment to read and understand the installation instructions included with this product. If any questions should arise concerning the proper installation of this product, please contact us.
Mechanical Installation
Step 1:
Select a location along the electrical distribution system as physically close to critical equipment loads as practical to install the surge suppressor. The suppressor can be installed at distribution panels, at equipment AC power inputs, or at the secondary windings of isolation transformers. The suppressor must be positioned within four (4) feet (122 cm) of the AC power source. It is recommended that the suppressor be installed within two (2) feet (61 cm) of the AC power source, if possible.
CAUTION: Increasing electrical impedance values to the inputs of any transient suppressor, regardless of manufacturer, can increase the device’s voltage limiting levels. Suppressors should be installed as physically close to the protected electrical distribution panel or critical load as possible using the largest size wiring/conductors as practical.
Step 2:
Verify that the maximum current rating of the electrical service to be protected does not exceed specied amperage rating of the suppressor model to be installed.
Table One: Application Rating
APEX II 225 Amps and below
APEX III 400 Amps and below
APEX IV 1000 Amps and below
1200-185
Loading...
+ 6 hidden pages