Trane YSC060ED, YSC120ED Installation, Operation And Maintenance Manual

Page 1
Installation, Operation, and Maintenance
Packaged Rooftop Air Conditioners Precedent™ — Gas/Electric
Model Numbers
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury.When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.
September 2012 RT-SVX38B-EN
YSC060ED - YSC120ED
SAFETY WARNING
Page 2
Warnings, Cautions and Notices
Warnings, Cautions and Notices. Note that warnings,
cautions and notices appear at appropriate intervals throughout this manual. Warnings are provide to alert installing contractors to potential hazards that could result in death or personal injury. Cautions are designed to alert personnel to hazardous situations that could result in personal injury, while notices indicate a situation that could result in equipment or property-damage-only accidents.
Your personal safety and the proper operation of this
machine depend upon the strict observance of these precautions.
Read this manual thoroughly before operating or servicing this unit.
ATTENTION: Warnings, Cautions and Notices appear at
appropriate sections throughout this literature. Read these carefully:
WARNING
CAUTIONs
NOTICE:
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
Indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury. It could also be used to alert against unsafe practices.
Indicates a situationthat could result in equipment or property-damage only
Important Environmental Concerns!
Scientific research has shown that certain man-made chemicals can affect the earth’s naturally occurring stratospheric ozone layer when released to the atmosphere. In particular, several of the identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact to the environment.Trane advocates the responsible handling of all refrigerants-including industry replacements for CFCs such as HCFCs and HFCs.
Responsible Refrigerant Practices!
Trane believes that responsible refrigerant practices are
important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified.The Federal Clean Air Act (Section 608) sets forth the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these service procedures. In addition, some states or municipalities may have additional requirements that
must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them.
WARNING
Proper Field Wiring and Grounding Required!
All field wiring MUST be performed by qualified
personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state electrical codes. Failure to follow code could result in death or serious injury.
WARNING
Personal Protective Equipment (PPE) Required!
Installing/servicing this unit could result in exposure to electrical, mechanical and chemical hazards.
Before installing/servicing this unit, technicians MUST put on all Personal Protective Equipment (PPE) recommended for the work being undertaken.
ALWAYS refer to appropriateMSDS sheets and OSHA
guidelines for proper PPE.
When working with or around hazardous chemicals,
ALWAYS refer to the appropriate MSDS sheets and
OSHA guidelines for information on allowable personal exposure levels, proper respiratory protection and handling recommendations.
If there is a risk of arc or flash, technicians MUST put on all Personal Protective Equipment (PPE) in accordance with NFPA 70E or other country-specific requirements for arc flash protection, PRIOR to servicing the unit.
Failure to follow recommendations could result in death or serious injury.
Revision Summary
RT-SVX38B-EN (10 September 2012)
MERV 8 filter with filter removal tool
Stainless steel drain pan, condensate overflow switch
Updated Model Number Description, Maintenance, Troubleshooting
© 2012Trane All rights reserved RT-SVX38B-EN
Page 3
Table of Contents
Model Number Description ............... 4
General Information ..................... 6
Unit Dimensions ........................ 10
Installation ............................. 16
Pre-Installation ....................... 16
Foundation .......................... 17
Ductwork ............................ 18
Roof Curb ........................... 18
General Unit Requirements ............ 20
Horizontal Discharge Conversion (5 Ton Units)
20
TCO-1 Instructions .................... 21
Horizontal Discharge Conversion (6 Through 10 Ton Units)
TCO1 Instructions ..................... 22
Requirements for Gas Heat ............ 22
Condensate Drain Configuration ........ 22
Filter Installation ...................... 23
Field Installed Power Wiring ........... 23
Main Unit Power ..................... 23
Space Temperature Averaging (ReliaTel™ On­ly)
.................................. 25
........................ 21
Zone Temperature Sensor (ZTS) Service Indi­cator
.................................40
Clogged Filter Switch ..................40
Fan Failure Switch .....................40
Condensate Overflow Switch ...........40
Unit Economizer Control (ECA) Troubleshoot­ing
...................................41
Resetting Cooling and Ignition Lockouts ..42
Unit Wiring Diagrams Numbers ...........43
Limited Warranty ........................44
Combination Gas Electric Air Conditioner .44
Combination Gas Electric Air Conditioner .44
Pre-Start ............................... 29
Voltage Imbalance .................... 29
Electrical Phasing (Three Phase Motors) .29
Test Modes .......................... 31
Unit Start-Up ........................... 32
Verifying Proper Air Flow .............. 32
Economizer Start-Up .................. 32
Compressor Start-Up ................. 33
Final System Setup ................... 33
Maintenance ........................... 34
Fan Belt Adjustment - Belt Drive Units ... 34
Monthly Maintenance ................. 34
Annual Maintenance .................. 36
Final Process ......................... 37
Trouble Shooting ....................... 38
ReliaTel™ Control .................... 38
System Status Checkout Procedure ..... 38
RT-SVX38B-EN 3
Page 4
Model Number Description
YSC 036 E 3 R Z B ** 123 456 7 8 9 10 11 1213
Digit 1 - Unit Type
Y DX Cooling, Gas Heat
Digit2-Efficiency
S Standard Efficiency H High Efficiency
Digit 3 - Airflow
C Convertible
Digit 4,5,6 - Nominal Gross Cooling Capacity (MBh)
036 3Ton 048 4Ton 060 5Ton 072 6Ton 090 7½Ton, Single Compressor 092 7½Ton, Dual Compressor 102 8½ Ton 120 10 Ton
Digit 7 - Major Design Sequence
E R-410A Refrigerant F MicrochannelType Condenser
24
Coils
Digit 8 - Voltage Selection
1 208/230/60/1 3 208-230/60/3 4 460/60/3
W 575/60/3
Digit 9 - Unit Controls
E Electromechanical R ReliaTel™ Microprocessor
Digit 10 - Heating Capacity
L Low Heat M Medium Heat H High Heat X Low Heat, Stainless Steel Heat
Exchanger
Y Medium Heat, Stainless Steel Heat
Exchanger
Z High Heat, Stainless Steel Heat
Exchanger
Digit 11 - Minor Design Sequence
A First Sequence B Second Sequence
21
20
Digit 12,13 - Service Sequence
** Factory Assigned
Digit 14 - Fresh Air Selection
0 No Fresh Air A Manual Outside Air Damper 0-50% B Motorized Outside Air Damper
C Economizer, Dry Bulb 0-100%
D Economizer, Dry Bulb 0-100%
E Economizer, Reference Enthalpy
F Economizer, Reference Enthalpy
28
0-50%
without Barometric Relief
with Barometric Relief
7
7
0-100% without Barometric Relief
0-100% with Barometric Relief
3,7
3,7
G Economizer, Comparative
Enthalpy 0-100% without Barometric Relief
3,7
H Economizer, Comparative
Enthalpy 0-100% with Barometric
3,7
Relief
Digit 15 - Supply Fan/Drive Type/ Motor
0 Standard Drive 1 Oversized Motor 2 Optional Belt Drive Motor 6 Single Zone VAV 7 Multi-Speed Indoor Fan
6
18
26
27
Digit 16 - Hinged Service
Access/Filters
0 Standard Panels/Standard Filters
A Hinged Access Panels/Standard
Filters B Standard Panels/2” MERV 8 Filters C Hinged Access Panels/2” MERV 8
Filters D Standard Panels/2” MERV 13 Filters E Hinged Access Panels/2” MERV 13
Filters
Digit 17 - Condenser Coil Protection
0 Standard Coil 1 Standard Coil with Hail Guard 2 Black Epoxy Pre-Coated Condenser
25
Coil 3 Black Epoxy Pre-Coated
Condenser Coil with Hail Guard
25
4 CompleteCoat™ Condenser Coil 5 CompleteCoat™ Condenser Coil
with Hail Guard
Digit 18 - Through the Base Provisions
0 NoThrough-the-Base Provisions
A Through-the-Base Electric
B Through-the-Base Gas Piping C Through-the-Base Electric and Gas
Piping
16
8
16
Digit 19 - Disconnect/Circuit Breaker (three-phase only)
0 No Disconnect/No Circuit Breaker 1 Unit Mounted Non-Fused
Disconnect 2 Unit Mounted Circuit Breaker
8
8
Digit 20 - Convenience Outlet
0 No Convenience Outlet
4
A Unpowered Convenience Outlet B Powered Convenience Outlet
(three-phase only)
9
Digit 21 - Communications
Sensor
30
DCV
3
30
Options
0 No Communications Interface 1 Trane Communications Interface 2 LonTalk® Communications Interface 3 Novar 2024 Controls 4 Novar 3051 Controls without Zone
5 Novar 3051Controls Interface with
6 BACnet™ Communications Interface
Digit 22 - Refrigeration System Option
0 Standard Refrigeration System B Dehumidification Option
Digit 23 - Refrigeration Controls
Note: Applicable to Digit7=E,F
0 No Refrigeration Control 1 Frostat 2 Crankcase Heater 3 Frostat
11 ,29
11 ,29
2
and Crankcase Heater
Digit 24 - Smoke Detector
0 No Smoke Detector A Return Air Smoke Detector B Supply Air Smoke Detector C Supply and Return Air Smoke
Detectors
12,13
D Plenum Smoke Detector
Digit 25 - System Monitoring Controls
0 No Monitoring Control 1 Clogged Filter Switch 2 Fan Failure Switch 3 Discharge Air Sensing Tube 4 Clogged Filter Switch and Fan
Failure Switch
5 Clogged Filter Switch and Discharge
Air SensingTube
6 Fan Failure Switch and Discharge Air
SensingTube
7 Clogged Filter Switch, Fan Failure
Switch and Discharge Air SensingTube
8 Novar Return Air Sensor
(NOVAR 2024)
9 Novar ZoneTemp Sensor
(NOVAR 3051)
A Condensate Drain Pan Overflow
Switch
B Clogged Filter Switch14and
Condensate Drain Pan Overflow Switch
C Fan Failure Switch14and Condensate
Drain Pan Overflow Switch
D Discharge Air Sensing14and
Condensate Drain Pan Overflow Switch
14
14
14
14
14
15,30
19,30
30
10
22,23
5
17
12,13
14
14
14
2
4 RT-SVX38B-EN
Page 5
Model Number Description
14
E Clogged Filter Switch Switch14and Condensate Drain Pan
Overflow Switch
F Clogged Filter Switch14, Discharge
Air SensingTube14and Condensate Drain Pan Overflow Switch
G Fan Failure Switch, Discharge Air
SensingTube14and Condensate Drain Pan Overflow Switch
H Clogged Filter Switch14, Fan Failure
Switch14, Discharge Air Sensing and Condensate Drain Pan Overflow
Switch
, Fan Failure
14
Digit 26 - System Monitoring Controls
0 No Monitoring Controls A Demand Control Ventilation
31,32
(CO2)
Digit 27 - Unit Hardware Enhancements
0 No Enhancements 1 Stainless Steel Drain Pan
Model Number Notes
1. Available on 3-5 ton models.
2. Standard on 4-5Ton E3,4,W and 6-10Ton Heat Pumps and all High Efficiency models.
3. Not available with electromechanical controls.
4. Manual outside air damper will ship factory supplied within the unit, but must be field installed.
5. High pressure controlis standard on all units.
6. On 3-5 ton, multispeed direct drive is standard on single phase and 15 SEER. On 6-10 ton, multispeed direct drive is standard on all 10 ton and 7.5-8.5 ton high efficiency. Belt drive is standard on all other units.
Digit 15 = 0
Standard Efficiency 1 Phase = High Efficiency Multispeed Direct Drive Motor 3 Phase (3-8½ Ton) = Belt Drive 3 Phase (10 T on) = Ultra High Efficiency Direct Drive Plenum Fan High Efficiency 1 Phase = High Efficiency Multispeed Direct Drive Motor 3 Phase (3-5 ton) = High Efficiency Multispeed Direct Drive Motor 3 Phase (3-5 ton w/Dehumidification) = Belt Drive Motor 3 Phase (7½-10 ton) = Ultra High Efficiency Direct Drive Plenum Fan
7. Economizer with Barometric Relief is for downflow configured units only. Order Economizer without Barometric Relief for
horizontal configuration. Barometric Relief for horizontal configured units must beordered as field installed accessory.
8. Through the base electric required when ordering disconnect/circuit breaker options.
9. Requires use of Disconnect or Circuit Breaker.
Not Available
Standard Efficiency 10 Ton w/575V High Efficiency 3-5 ton w/Standard Indoor Motor w/460V
10. Standard metering devices are
TXVs.
11. Frostat cannot be field installedin electro-mechanical units.
12. The return air smoke detector may not fitup or workproperly on the Precedent units when used in conjunction with 3rd party accessories such as bolt on heat wheels, economizers and power exhaust. Do not order the return air smoke detectors when using this type of accessory.
13. Return Air Smoke Detector cannot be ordered with Novar Controls.
14. These options are standard when ordering Novar Controls.
15. This option is used when ordering Novar Controls.
16. Includes gas piping and shutoff (field assembly required).
17. Not available with high temperature duct sensor accessory.
18. Digit 15 = 2
Standard Efficiency 1 Phase = Not Available 3 Phase = Not Available High Efficiency 1 Phase = Not Available 3 Phase (3-5 ton) = May be Ordered 3 Phase (3-5 ton w/Dehumidification) = Not Available 3 Phase (6-10 ton) = Not Available
19. Novar Sensor utilized with Digit 21 = (4)Novar 3051 Controls without Zone Sensor.
20. Available for 10 ton standard efficiency models only.
21. Available for 3, 4, 5, 6, 7½, 8½ ton standard/high efficiency models only.
22. Requires selection of 2” Pleated Filters (option B or C) for Digit 16.
23. Not available on 6 ton units and all single phase or standard efficiency.
24. Standard onYSC 6, 7½ (single and dual systems), 8½, 10 ton standard efficiency models and
YHC 4, 5, 6, 7½ ton highefficiency
models (except for dehumidification models).
25. Epoxy coil and epoxy with hailguard options are not available for units with microchannel condenser coil.
26. Single ZoneVAV is only available on 7.5-10 ton high efficiency and 10 ton standard efficiency products with ReliaTel™ controls.
27. Multi-speed indoor fan available only on 7.5 & 8.5 ton high efficiency, and 10 ton products with ReliaTel™ controls.
28. Motorized Outside Air Damper is not available on Multi-Speed or SZVAV (Single Zone Variable Air
Volume) products.
29. Frostat standard on Multi-Speed and SZVAV (Single ZoneVariable
Air Volume) products.
30. Novar is not available with SZVAV products.
31. Demand Control Ventilation not available with electromechanical controls.
32. Demand Control Ventilation Option includes wiring only.The C0
sensor is afield-installed only
2
option.
RT-SVX38B-EN 5
Page 6
General Information
Unit Inspection
As soon as the unit arrives at the job site
Verify that the nameplate data matches the data on the sales order and bill of lading (including electrical data).
Verify that the power supply complies with the unit nameplate specifications.
Visually inspect the exterior of the unit, including the roof, for signs of shipping damage.
If the job site inspection of the unit reveals damage or material shortages, file a claim with the carrier immediately.Specify the typeand extent ofthe damage on the “bill of lading” before signing.
Visually inspect the internal components for shipping damage as soon as possible after delivery and before it is stored. Do not walk on the sheet metal base pans.
If concealed damage is discovered, notify the carrier’s terminal of damage immediately by phone and by mail. Concealed damage must be reported within 15 days.
Request an immediate joint inspection of the damage by the carrier and the consignee. Do not remove damaged material from the receiving location.Take photos of the damage, if possible.The owner must provide reasonable evidence that the damage did not occur after delivery.
Notify the appropriate sales representative before installing or repairing a damaged unit.
Compressor Nameplate
The nameplate forthe compressors are located onthe side
of the compressor.
Unit Description
Before shipment, each unit is leak tested, dehydrated, charged with refrigerant and compressor oil, and run tested for proper control operation.
The condenser coilsare either aluminum fin, mechanically
bonded to copper tubing or all aluminum microchannel.
Direct-drive, vertical discharge condenser fans are provided with built-in thermal overload protection.
There are two control systems offered for these units.The
electromechanical control option uses a thermostat to perform unit functions.The ReliaTel™ Control Module is a microelectronic control system that is referred to as “Refrigeration Module” (RTRM). The acronym RTRM is used extensively throughout this document when referring to the control system network.
These modules through Proportional/Integral control
algorithms perform specific unit functions that governs unit operation inresponse to; zone temperature, supply air temperature, and/or humidity conditions depending on the application.The stages of capacity control for these units are achieved by starting and stopping the compressors.
The RTRM is mounted in the control panel and is factory
wired to the respective internal components.The RTRM receives and interprets information from other unit modules, sensors, remote panels, and customer binary contacts to satisfy the applicable request for cooling.
Storage
Take precautions to prevent condensate from forming
inside the unit’s electrical compartments and motors if:
1. The unit is stored before it is installed; or,
2. The unit is set on the roof curb, and temporary heat is provided in the building. Isolate all side panel service entrances and base pan openings (e.g., conduit holes, Supply Air and Return Air openings, and flue openings) from the ambient air until the unit is ready for start-up.
Note: Do not use the unit’s heater for temporary heat
without first completing the start-up procedure detailed under “Unit Start-Up,” p. 32.
The manufacturer will not assume any responsibility for
equipment damage resulting from condensate accumulation on the unit’s electrical and/or mechanical components.
Unit Nameplate
A Mylar unit nameplate is located on the unit’s corner support next to the filter access panel. It includes the unit model number, serial number, electrical characteristics, refrigerant charge, as well as other pertinent unit data.
Economizer Control Actuator (Optional)
ReliaTel™ Control
The ECA monitors the mixed air temperature, return air
temperature, minimum position setpoint (local or remote), power exhaust setpoint, CO ambient dry bulb/enthalpy sensor or comparative humidity (return air humidity against ambient humidity) sensors, if selected, to control dampers to an accuracy of +/- 5% of stroke.The actuator is spring returned to the closed position any time that power is lost to the unit. It is capable of delivering up to 25 inch pounds of torque and is powered by 24 VAC.
RTCI - ReliaTel™ Trane Communication Interface (Optional)
This module is used when the application calls for an
ICSTM building management type control system. It allows the control and monitoring of the system through an ICS panel.The module can be ordered from the factory or ordered as a kit to be field installed. Follow the installation instruction that ships with each kit when field installation is necessary.
setpoint, CO2, and
2
6 RT-SVX38B-EN
Page 7
General Information
RLCI - ReliaTel™ LonTalk® Communication Interface (Optional)
This module is used when the application calls for an
ICSTM building management type control system that is LonTalk. Itallows the control and monitoringof the system through an ICS panel.The module can be ordered from the factory or ordered as a kit to be field installed. Follow the installation instruction that ships with each kit when field installation is necessary.
RBCI - ReliaTel™ BACnet Communications Interface (Optional)
This module is used when the application calls for anopen
BACnet protocol. It allows the control and monitoring of the system through an ICS panel.The module can be ordered from the factory or as a kit to be field installed. Follow the installation instructions that ships with each kit when field installation is necessary.
RTOM - ReliaTel™ Options Module (Optional)
The RTOMmonitors the supply fan proving, cloggedfilter,
supply air temperature, exhaust fan setpoint, supply air tempering, Frostat™ and smoke detector. Refer to system input devices and functions for operation.
System Input Devices & Functions
The RTRM must have a zone sensor or thermostat input in
order to operate the unit.The flexibility of having several mode capabilities dependsupon the type of zone sensor or thermostat selected to interface with the RTRM.
The descriptions of the following basic InputDevices used
within the RTRM network are to acquaint the operator with their function as they interface with the various modules. Refer to the unit’s electrical schematic for the specific module connections.
The following controls are available from the factory for
field installation.
Supply Fan Failure Input (Optional)
The Fan Failure Switch can be connected to sense indoor
fan operation:
FFS (Fan Failure Switch) If air flow through the unit is not proven by the differential pressure switch connected to the RTOM (factory set point 0.07 “w.c.) within 40 seconds nominally, the RTRM will shut off all mechanical operations, lock the system out, send a diagnostic to ICS, and the SERVICE output will flash.The system will remain locked out until a reset is initiated either manually or through ICS.
Clogged Filter Switch (Optional)
The unit mounted clogged filter switch monitors the
pressure differential across the return air filters. It is mounted in the filter section and is connected to the RTOM. A diagnostic SERVICE signal is sent to the remote panel if the pressure differential across the filters is at least
0.5" w.c.The contacts will automatically open when the
pressure differential across the filters decreases to approximately 0.4" w.c.The clogged filter output is energized when the supply fan is operating and the clogged filter switch has been closedfor at least 2 minutes.
The system will continue to operate regardless of the
status of the filter switch.
Note: On units equipped with factory installed MERV 13
filters, a clogged filter switch with different pressure settings will be installed. This switch will close when the differential pressure is approximately 0.8' w.c. and open when the differential falls to 0.7" w.c.
Condensate Drain Pan Overflow Switch (Optional)
ReliaTel Option
This input incorporates the Condensate Overflow Switch
(COF) mounted on the drain pan and the ReliaTel Options Module (RTOM).When the condensate level reaches the trip point for 6 continuous seconds, the RTOM will shut down all unit functions until the overflow condition has cleared.The unit will return to normal operation after 6 continuous seconds with the COF in a non-tripped condition. If the condensate level causes unit shutdown more than 2 times in a 3 days period, the unit will be locked-out of operation requiring manual reset of diagnostic system through Zone Sensor or Building Automation System (BAS). Cycling unit power will also clear the fault.
Compressor Disable (CPR1/2)
This input incorporates the low pressure control (LPC) of
each refrigeration circuit and can be activated by opening a field supplied contact installed on the LTB.
If this circuit is open before the compressor is started, the compressor will not be allowed to operate. Anytime this circuit is opened for 1 continuous second during compressor operation, the compressor for that circuit is immediately turned “Off”. The compressor will not be allowed to restart for a minimum of 3 minutes should the contacts close.
If four consecutive open conditions occur during the first three minutes of operation,the compressor for that circuit will be locked out, a diagnostic communicated to the remote panel (if installed), and a manual reset will be required to restart the compressor.
Low Pressure Control
ReliaTel Control
When the LPC is opened for 1 continuous second, the
compressor for that circuit is turned off immediately.The compressor will not be allowed to restart for a minimum of 3 minutes.
If four consecutive open conditions occur during an active call for cooling, the compressor will be locked out, a diagnostic communicated to ICS™, if applicable, and a
RT-SVX38B-EN 7
Page 8
General Information
manual reset required to restart the compressor. On dual compressor units only the affected compressor circuit is locked out.
High Pressure Control
ReliaTel Control
The high pressure controls are wiredin series between the
compressor outputs on the RTRM and the compressor contactor coils. If the high pressure control switch opens, the RTRM senses a lack of current while calling for cooling and locks the compressor out.
If four consecutive open conditions occur during an active call for cooling, the compressor will be locked out, a diagnostic communicated to ICS™, if applicable, and a manual reset required to restart the compressor. On dual compressor units only the affected compressor circuit is locked out.
Lead/Lag Control (Dual Circuit Only)
ReliaTel Control Only
Lead/Lag is a selectable input located on the RTRM.The RTRM is configured from the factory with the Lead/Lag control disabled.To activate the Lead/Lag function, simply cut the wire connected to J3-8 at the RTRM. When it is activated, each time the designated lead compressor is shut off due to the load being satisfied, the lead compressor or refrigeration circuit switches. When the RTRM is powered up, i.e. after a power failure, the control will default to the number one circuit compressor.
Zone Sensor Module (ZSM) (BAYSENS106*)
This electronic sensor features three system switch
settings (Heat, Cool, and Off) and two fan settings (On and Auto). It is a manual changeover control with single setpoint. (Cooling Setpoint Only)
Zone Sensor Module (ZSM) (BAYSENS108*)
This electronic sensorfeatures four system switch settings
(Heat, Cool, Auto, and Off) and two fan settings (On and Auto). It is a manual or auto changeover control with dual setpoint capability. It can be used with a remote zone temperature sensor BAYSENS077*.
Zone Sensor (BAYSENS110*)
This electronic sensorfeatures four system switch settings
(Heat, Cool, Auto, and Off) and two fan settings (On and Auto) with four system status LED’s. It is a manual or auto changeover control with dual setpoint capability. It can be used with a remote zone temperature sensor BAYSENS077*.
Programmable Zone Sensor - (BAYSENS119*)
This 7 day programmable sensor features 2, 3 or 4 periods
for Occupied or Unoccupied programming per day. If the power is interrupted, the program is retained in permanent memory. If power is off for an extended period of time, only the clock and day may have to be reset.
The Zone Sensor allows selection of 2, 3 or 4 system
modes (Heat, Cool,Auto, and Off), two fan modes (On and
Auto). It has dual temperature selection with
programmable start time capability.
The occupied cooling set point ranges between 45 and 98
º F. The heating set point ranges between 43 and 96ºF.
A liquid crystal display (LCD) displays zone temperature,
temperature set points, day of the week, time, and operational mode symbols.
The Option Menu is used to enable or disable applicable
functions, i.e.; Morning Warm-up, Economizer minimum position override during unoccupied status, Fahrenheit or Centigrade, Supply air tempering, Remote zone temperature sensor, 12/24 hour time display, Smart fan, and Computed recovery.
During an occupied period, an auxiliary relay ratedfor 1.25 amps @ 30 volts AC with one set of single pole double throw contacts is activated.
Status Inputs (4 Wires Optional)
The ZSM can be wired to receive four (4) operating status
signals from the RTRM (HEAT, COOL, SYSTEM “ON”, SERVICE).
Four (4) wires from the RTRM should be connected to the appropriate terminals (7, 8,9&10)ontheZSM.
Remote Zone Sensor (BAYSENS073*)
This electronic sensor features remote zone sensing and
timed override with override cancellation. It is used with a
Trane Integrated Comfort™ building management
system.
Remote Zone Sensor (BAYSENS074*)
This electronic sensor features single setpoint capability
and timed override with override cancellation. It is used with aTrane Integrated Comfort™ building management system.
Remote Zone Sensor (BAYSENS016*)
This bullet type temperature sensor can be used for
outside air (ambient) sensing, return air temperature sensing, supply air temperature sensing, remote temperature sensing (uncovered). Wiring proceduresvary according to the particular application and equipment involved. Refer to the unit’s wiring diagrams for proper connections.
Remote Zone Sensor (BAYSENS077*)
This electronic sensor can be used with BAYSENS106*,
108*, 110*, 119* Remote Panels.When this sensor is wired to a BAYSENS119* Remote Panel, wiring must be 18 AWG ShieldedTwisted Pair (Belden 8760 or equivalent). Refer to the specific Remote Panel for wiring details.
Wireless Zone Sensor (BAYSENS050)
This electronic sensor features five system settings (Auto,
Off, Cool, Heat, and Emergency Heat) and with On and
8 RT-SVX38B-EN
Page 9
Auto fan settings. It is amanual or auto changeover control with dual setpoint capability. Other features include a timed override function, lockable system settings, and Fahrenheit or Celsius temperature display. Included with the wireless zone sensor will be a receiver that is to be mounted inside the unit, a mounting bracket, and a wire harness.
High Temperature Sensor (BAYFRST001*)
This sensor connects to the RTRM Emergency Stop Input
on the LTB andprovides high limit “shutdown” of the unit.
The sensor is used to detect high temperatures due to a
high thermal event in the air conditioning or ventilation ducts.The sensor is designed to mount directly to the sheet metal duct. Each kit contains two sensors.The return air duct sensor (X1310004001) is set to open at 135ºF. The supply air duct sensor (X1310004002) is set to open at 240ºF. The control can be reset after the temperature has been lowered approximately 25ºF below the cutout setpoint.
Evaporator Frost Control
ReliaTel™ Option
This input incorporates the Frostat™ control (FOS)
mounted in the indoor coil circuit and can be activated by closing a field supplied contact installed in parallel with the FOS.
If this circuit is open before the compressor is started, the compressor will not be allowed to operate. Anytime this circuit is opened for 1 continuous second during compressor operation, the compressor for that circuit is immediately turned “Off”. The compressor will not be allowed to restart for a minimum of 3 minutes should the FOS close.
General Information
Discharge LineTemp Switch (DLTS)
The DLTS is looped in series with HPC and LPC. It prevents
compressor from overheating (over 300 Fº dome temp) in case of indoor fan failure (cooling) or outdoor fan failure (heating).
Phase Monitor
This sensor monitors voltage between the 3 conductors of
the 3 phase power supply.Two LED lights are provided:
• The green light indicates that a balanced 3 phase supply circuit is properly connected.
• The red light indicates that unit operation has been prevented.There are two conditions that will prevent unit operation:
The power supply circuit is not balanced with the
proper phase sequence of L1, L2, L3 for the 3 conductors of a 3 phase circuit.
The line to line voltage is not between 180 volts and
633 volts.
RT-SVX38B-EN 9
Page 10
Unit Dimensions
Figure 1 illustrates the minimum operating and service
clearances for either a single or multiple unit installation.
These clearances are the minimum distancesnecessary to
assure adequate serviceability, cataloged unit capacity, and peak operating efficiency.
Figure 1. Typical installation clearances for single & multiple unit applications
Providing less than the recommended clearances may result in condenser coil starvation, “short-circuiting” of exhaust and economizer airflows, or recirculation of hot condenser air.
YSC060ED
10 RT-SVX38B-EN
YSC072-120ED
Page 11
Figure 2. 5 tons standard efficiency
44 MMMM
44 MMMM
1038 MMMM
1053 MMMM
Notes:
1. All dimensions are in inches/millimeters.
2. ½ NPT Gas Connection
Unit Dimensions
Figure 3. 5 tons standard efficiency - roof curb
Note: All dimensions are in inches/millimeters.
44
44
7
1038
1053
RT-SVX38B-EN 11
Page 12
Unit Dimensions
Figure 4. 5 tons standard efficiency - unit clearance and roof opening
Note: All dimensions are in inches/millimeters.
CLEARANCE 36” (914 MM)
Figure 5. 6, 7½ tons standard efficiency
Note: All dimensions are in inches/millimeters.
12 RT-SVX38B-EN
Page 13
Figure 6. 6, 7½ tons standard efficiency - roof curb
Note: All dimensions are in inches/millimeters.
Unit Dimensions
(356 MM)
Figure 7. 6, 7½ tons standard efficiency - unit clearance and roof opening
Note: All dimensions are in inches/millimeters.
(2130 MM)
RT-SVX38B-EN 13
Page 14
Unit Dimensions
Figure 8. 8½ - 10 tons standard efficiency
Note: All dimensions are in inches/millimeters.
1/2 NPT GAS CONNECTION
Figure 9. 8½ - 10 tons standard efficiency - roof curb
Note: All dimensions are in inches/millimeters.
(356 MM)
(2130 MM)
14 RT-SVX38B-EN
Page 15
Figure 10. 8½ - 10 tons standard efficiency - unit clearance and roof opening
Note: All dimensions are in inches/millimeters.
Unit Dimensions
RT-SVX38B-EN 15
Page 16
Installation
Pre-Installation
WARNING
Fiberglass Wool!
Product contains fiberglass wool. Disturbing the insulation in this product during installation, maintenance or repair will expose you to airborne particles of glass wool fibers and ceramic fibers known to the state of California to cause cancer through inhalation. Glass wool fibers may also cause respiratory, skin or eye irritation.
Precautionary Measures
Avoid breathing fiberglass dust.
Use a NIOSH approved dust/mist respirator.
Avoid contact with the skinor eyes.Wear long-sleeved, loose-fitting clothing, gloves, and eye protection.
Wash clothes separately from other clothing: rinse washer thoroughly.
Operations such as sawing, blowing, tear-out, and spraying may generate fiber concentrations requiring additional respiratory protection. Use the appropriate NIOSH approved respiration in these situations.
First Aid Measures
Eye Contact - Flush eyes with water to remove dust. If symptoms persist, seek medical attention.
Skin Contact -Wash affected areas gently with soap and warm water after handling.
Procedure
WARNING
Heavy Objects!
Ensure that all the lifting equipment used is properly rated for the weight of the unit being lifted. Each of the cables (chains or slings), hooks, and shackles used to lift the unit must be capable of supporting the entire weight of the unit. Lifting cables (chains or slings) may not be of the same length. Adjust as necessary for even unit lift. Other lifting arrangements could cause equipment or property damage. Failure to follow instructions above or properly lift unit could result in unit dropping and possibly crushing operator/ technician which could result in death or serious injury.
WARNING
Improper Unit Lift!
Test lift unit approximately 24 inches to verify proper
center of gravity lift point. To avoid dropping of unit, reposition lifting point if unit is not level. Failure to properly lift unit could result in unit dropping and possibly crushing operator/technician which could result in death or serious injury and possible equipment or property-only damage.
Figure 11. Corner weights
16 RT-SVX38B-EN
Page 17
Installation
Table 1. Maximum unit & corner weights (lbs/kgs) and center of gravity dimensions (in/mm) - gas/electric models
Unit
Tons Model No. Shipping Net A B C D Length Width
5 YSC060E 689/312 584/264 181/82 144/65 122/55 137/62 40/1025 24/600
6 YSC072E 975/443 843/383 296/134 209/95 158/72 180/82 39/980 21/542 7½ YSC090E 1016/461 884/401 346/157 198/90 159/72 181/82 36/909 20/519 8½ YSC102E 1125/510 987/447 325/147 278/126 174/79 210/95 41/1031 21/526
10 YSC120E 1149/522 1011/459 344/156 265/120 193/88 209/95 40/1020 21/538
(a) Weights are approximate. (b) Corner weights are given for information only.
Maximum Model
Weights
(a)
Corner Weights
(b)
Center of Gravity (in./
mm)
Figure 12. Rigging and center of gravity
Table 2. Factory installed options (fiops)/accessory net weights (lbs)
YSC060ED YSC072E-120ED
Net Weight Net Weight
Accessory 5 Ton 6-10 Ton
Barometric Relief 7/3 10/5 Coil Guards 12/5 20/9 Economizer 26/12 36/16 Hinged Doors 10/5 12/5 Manual Outside Air Damper 16/7 26/12 Motorized Outside Air Damper 20/9 30/14 Oversized Motor 8/4 Roof Curb 61/28 78/35
(a)Weights for options not listed are <5 lbs. (b)Net weight should be added to unit weight when ordering factory-installed accessories.
Foundation
Horizontal Units
If the unit is installed at ground level, elevate it above the snow line. Provide concrete footings at each support location with a“full perimeter” support structure or a slab
operating and point loading weights when constructing a footing foundation.
If anchoring is required, anchor the unit to the slab using hold down bolts or isolators. Isolators should be installed to minimize the transmission of vibrations into the building.
(a),(b)
foundation for support. Refer to Table 1, p. 17 for the unit’s
RT-SVX38B-EN 17
Page 18
Installation
For rooftop applications, ensure the roof is strong enough to support the combined unit and support structural weight. Refer to Table 1, p. 17 for the unit operating weights. If anchoring is required, anchor the unit to the roof with hold-down bolts or isolators.
Check with a roofing contractor for proper waterproofing procedures.
Ductwork
Figure 13, p. 18 to Figure 16, p. 18 illustrate the supply and
return air openings as viewed from the rear of the unit.
Figure 13. 5 ton unit - Horizontal supply & return air
openings
When attaching the ductwork to the unit, provide a water
tight flexible connector at the unit to prevent operating sounds from transmitting through the ductwork.
All outdoor ductwork between the unit and the structure
should be weather proofed after installation is completed.
Figure 15. 5 ton unit - Downflow supply & return air
openings w/ through the base utilities
3 5/8” 92 MM
102 MM
610 MM
4”
24”
4 3/16”
106 MM
RETURN
14”
356 MM
23 1/2”
597 MM
9 1/4”
235 MM
406 MM
TBU CONDENSATE
THE BASE GAS
15 1/2”
394 MM
SUPPLY
16”
4 9/16”
116 MM
THROUGH
27 9/16” 701 MM
THROUGH THE BASE
ELECTRICAL
4 7/8”
124 MM
9 15/16” 253 MM
5 1/16”
128 MM
2 13/16”
71 MM
3 11/16”
94 MM
6 1/2”
165 MM
Figure 16. 6-10 ton units - downflow supply & return air
openings w/ through the base utilities
Figure 14. 6-10 ton high units - horizontal supply &
return air openings
Return
Supply
Figure 15, p. 18 to Figure 16, p. 18 illustrate the supply and
return air openings in a downflow configuration.
Elbows with turning vanes or splitters are recommended to minimize air noise due to turbulence and toreduce static pressure.
Roof Curb
Downflow
The roof curbs for these unitsconsists of a“full perimeter”
enclosure to support the unit just inside of the unit base rail.
Before installing any roof curb, verify;
It is the correct curb for the unit,
It includes the necessary gaskets and hardware,
• The installation location provides the required clearance for proper operation,
• The curb is level and square. The top surface of the curb must be true to assure an adequate curb-to-unit seal.
18 RT-SVX38B-EN
Page 19
WARNING
Combustible Materials!
Maintain proper clearance between the unit heat exchanger, vent surfaces and combustible materials. Refer to unit nameplate and installation instructions for proper clearances. Improper clearances could result in combustible materials catching on fire. Failure to maintain proper clearances could result in death or serious injury or property damage.
Verify that appropriate materials were used in the
construction of roof and ductwork.Combustible materials should not be used in the construction of ductwork or roof curb that is in close proximity to heater elements or any hot surface.Any combustible material on the inside of the unit base should be removed and replaced with appropriate material.
Step-by-step curb assembly and installation instructions ship with each accessory roof curb kit. Follow the instructions carefully to assure proper fit-up whenthe unit is set into place.
Note: To assure proper condensate flow during
operation, as well as proper operation of the condensate overflow switch (if equipped), the unit and curb must be level.
If the unit is elevated, a field constructed catwalk around the unit is strongly recommended to provide easy access for unit maintenance and service.
Recommendations for installingthe Supply Air and Return Air ductwork joining the roof curb are included in the curb instruction booklet. Curb ductwork must befabricated and installed by the installing contractor before the unit is set into place.
Note: For sound consideration, cut only the holes in the
roof deck for the ductwork penetrations. Do not cut out the entire roof deck within the curb perimeter.
If a Curb Accessory Kit is not used:
• The ductwork can be attached directly to the factory­provided flanges around the unit’s supply and return air openings. Be sure to use flexible duct connections at the unit.
For “built-up” curbs supplied by others, gaskets must be installed around the curb perimeter flange and the supply and return air opening flanges.
Installation
Rigging
WARNING
Heavy Objects!
Ensure that all the lifting equipment used is properly rated for the weight of the unit being lifted. Each of the cables (chains or slings), hooks, and shackles used to lift the unit must be capable of supporting the entire weight of the unit. Lifting cables (chains or slings) may not be of the same length. Adjust as necessary for even unit lift. Other lifting arrangements could cause equipment or property damage. Failure to follow instructions above or properly lift unit could result in unit dropping and possibly crushing operator/ technician which could result in death or serious injury.
A Rigging illustration and Center-of-Gravity dimensional
data table is shown in Figure 12, p. 17. Refer to the typical unit operating weights table before proceeding.
1. Remove all drill screws fastening wood protection to metal base rail. Remove all screws securing wooden protection to wooden top crate.
On 7½-10 ton high efficiency units, remove wire ties from outdoor grill.
2. Remove wooden top crate.
3. Rig the unit as shown in Figure 12, p. 17. Attach adequate strength lifting slings to all four lifting brackets in the unit base rail. Do not use cables, chains, or slings except as shown.
4. Install a lifting bar, as shown in Figure 12, p. 17,to protect the unit and to facilitate a uniform lift.The minimum distance between the lifting hook and the top of the unit should be 7 feet.
5. Test-lift the unit to ensure it is properly rigged and balanced, make any necessary rigging adjustments.
6. Lift the unit enough to allow the removal of base fork pocket protection components as shown in the following figures.
Figure 17. Fork pockets
RT-SVX38B-EN 19
7. Downflow units; align the base rail of the unit with the curb rail while lowering the unit onto the curb. Make sure that the gasket on the curb is not damaged while positioning the unit.
Page 20
Installation
General Unit Requirements
The checklist listed below is a summary of the steps
required to successfully install a commercial unit.This checklist is intended to acquaint the installing personnel with what isrequired in the installationprocess. It does not replace the detailed instructions called out in the applicable sections of this manual.
Check the unit for shipping damage and material shortage; file a freight claim and notify appropriate sales representative.
Verify correct model, options and voltage from unit nameplate.
Verify that the installation location of the unit will provide the required clearance for proper operation.
Assembleand install the roof curb (if applicable). Refer to the latest edition of the curb installers guide that ships with each curb kit.
Fabricate and install ductwork; secure ductwork to curb.
Install pitch pocket for power supply through building roof. (If applicable)
Rigging the unit.
Set the unit onto the curb; check for levelness.
Ensure unit-to-curb seal istight and without buckles or cracks.
Install and connect a condensate drain line to the evaporator drain connection.
Note: Condensate Overflow Switch (if equipped) will not
work if unit is not level properly.
Factory Installed Economizer
Ensure the economizer has been pulled out into the operating position. Refer to the economizer installers guide for proper position and setup.
Install all access panels.
limit switch from the combustion blower motor and discard.
Table 3. TC01 tripping values
Unit Model
(Standard Efficiency)
YSC060ED*L 170F YSC060ED*H 170F/200F YSC072ED*L 200F YSC072E*H 180F/220F YSC090ED*L 200F YSC090ED*H 180F/220F YSC102ED*L 200F YSC102ED*H 190F/260F YSC120ED*L 200F YSC120ED*H 190F/260F
TCO1 Tripping Values
Downflow/ Horizontal
Horizontal Discharge Conversion (5 Ton Units)
Supplies needed by installer for conversion: 3 oz. tube of high temperature RTV sealant. (500°F / 260°C: similar to Dow Corning 736)
Important: Failure to use recommended sealant could
result in unit performance loss.
If a unit is to be converted to a horizontal discharge, the following conversion must be performed:
1. Remove RETURN and SUPPLY duct covers.
2. Locate supply cover. Apply ¼ in. (6mm.) continuous bead of 500°F RTV sealant to the flange as shown.
Figure 18. Duct cover
RTV Sealant
Temperature Limit Switch Usage for Gas
Heat Units
Units are factory shipped in the down flow discharge configuration but can be field converted to a horizontal discharge configuration. Some, but not all units require a differentTCO1 limit switch, which is attached to the combustion blower motor if horizontal discharge configuration is used.
Note: The following units require a limit switch change
out for horizontal discharge.The additional limit switch is shipped attached to the combustion blower housing:YSC060ED*H,YSC072ED*H,
YSC090ED*H,YSC102ED*H,YSC120ED*H.
If any of the aforementioned unitsare installed in thedown flow discharge configuration, remove the additionalTCO1
20 RT-SVX38B-EN
3. Position duct cover as shown, rotate 90 degrees to allow entrance into supply opening.
4. Slide duct covers into duct openings until inward edge of duct cover engages with the 2 retaining clips on the duct flanges. Secure the outward edge of each duct cover with 2 screws.
5. Slide RETURN DUCT COVER (insulation side up) into supply opening until inward edge of duct cover engages with the 2 retaining clips on the duct flange. Secure outward edge of the duct cover with two screws.
6. After completing installation of the duct covers for horizontal discharge, proceed toTCO-1 instructions.
Page 21
Installation
FLAME ROLLOUT LIMIT
LOCATION OF TCO1 LIMIT FOR THE Y(S/H)C036E, YHC037E, YSC048E, AND YSC060E UNITS
TCO-1 Instructions
If the unit being installed is listed in the following list, the limit controlTCO1 must be replaced with the extra limit control shipped in the heater compartment. ReplaceTCO1 following the instructions insteps 1through 3 below.If the unit being installed does not correspond to any in the following list, skip steps1 through 3 and go on to next step in the installation process.
Unit Model Number
YSC060ED*H
Figure 19. TCO1 location (YSC060ED*H)
LOCATION OF TCO1 LIMIT FOR THE Y(S/H)C036E, YHC037E, YSC048E, AND YSC060E UNITS
FLAME ROLLOUT LIMIT
2. Place SUPPLY DUCT COVER over down-flow return opening. (insulation side down)
3. Using self-drilling screws, (or screws removed from duct cover), screw through dimples to attach DUCT COVER to base.
Figure 20. Duct cover
Supply Duct Cover
Screw into 4 dimples on top edge
4. On original RETURN DUCT COVER, apply ¼”(6mm.) continuous bead of 500°F RTV sealant around flange (opposite insulation side), as shown.
Figure 21. Duct cover
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/ tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.
1. Remove the heat section access panel.
2. RemoveTCO1 from shipping location, attached to the combustion blower.
3. Replace and discard the existingTCO1 originally installed at the factory for down flow operation with theTCO1 shipped attached to the combustion blower for horizontal operation.
4. Replace heat section access panel.
Horizontal Discharge Conversion (6 Through 10Ton Units)
Note: 6 - 10 ton units the supply cover to return opening
& return cover to supply opening.
Supplies Needed by Installer for Conversion: 3 oz. tube of highTemperature RTV sealant (500°F / 260°C: Similar to Dow Corning 736).
Important: Failure to use recommended sealant could
result in unit performance loss.
If a unit is to be converted to a Horizontal discharge, the following conversion must be performed:
1. Remove RETURN and SUPPLY duct covers.
RTV Sealant
5. Slide RETURN DUCT COVER (insulation side up) into supply opening until inward edge of duct cover engages with the 2 retaining clips on the duct flange. Secure outward edge of the duct cover with two screws.
Note: If unit is equipped with ReturnAir Smoke Detector,
refer to field conversion instructions for horizontal discharge before installing return air duct.
Note: If unit is equipped with Discharge Air Sensing
option refer to the following figure for proper tube positioning based on unit tonnage.
6. After completing installation of the duct covers for horizontal discharge, proceed toTCO-1 instructions.
Figure 22. Supply and return covers
Supply duct cover
Insulation side down
Insulation side up
Return duct cover
RT-SVX38B-EN 21
Page 22
Installation
TCO1 Instructions
If the unit being installed is listed in the following list, the limit controlTCO1 must be replaced with the extra limit control shipped in the heater compartment. ReplaceTCO1 following the instructions insteps 1through 3 below.If the unit being installed does not correspond to any in the following list, skip steps1 through 3 and go on to next step in the installation process.
Unit Model Number
YSC072ED*H,YSC090ED*H,YSC102ED*H,YSC120ED*H
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/ tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.
1. Remove the heat section access panel.
2. RemoveTCO1 from shipping location, attached to the combustion blower.
3. Replace and discard the existingTCO1 originally installed at the factory for down flow operation with theTCO1 shipped attached to the combustion blower for horizontal operation.
4. Replace heat section access panel.
Requirements for Gas Heat
Note: The unit gas train and Optional ThroughThe Base
Gas Shut-OffValve are rated at 1/2 PSIG maximum. A pressure reducing regulator is recommended to prevent this maximum from being exceeded.
These components must be isolated during field
gas piping test that exceed 1/2 PSIG. It is recommended that the field piping be capped prior to the unit gas train or OptionalThroughThe Base Gas Shut-Off Valve if present.
Gas supply line properly sized and connected to the unit gas train.
All gas piping joints properly sealed.
Gas piping leak checked with a soap solution. If piping connections to the unitare complete, do not pressurize piping in excess of 0.50 psig or 14" W.C. to prevent component failure.
Drip leg Installed in the gas piping near the unit.
Minimum gas supply pressure should be 4.5" W.C.
Maximum gas supply pressure must not exceed 14.0"
W.C.
Manifold pressure for single stage heaters should be set to 3.3" W.C.
Manifold pressure for two stage heaters should be set to 3.5" W.C. on HIGH FIRE and 1.8" W.C. on LOW FIRE.
Flue Exhaust clear of any obstruction.
Condensate Drain Configuration
An evaporator condensate drain connection is provided
on each unit. Refer to Figure 13, p. 18 and Figure 14, p. 18 for the appropriate drain location.
The condensate drain pan is factory installed to drain
condensate to theback side of the unit. See Figure 13, p. 18 and Figure 14, p. 18. It can be converted to drain condensate out the front side of the unit or through the base.
Before drain pan removal, switch wire must be disconnected from wire tie on panel and any tape before drain pan can be removed.
Care must be taken wire does not catch on bottom of Indoor coil or any protrusions when drain pan is removed.
To Convert Drain Condensate Out the Front of
Unit:
1. Remove evaporator accesspanel and supplyair access panels.
2. Remove the support panel that the condensate drain pan exits through.
3. Slide the condensate drain pan out of the unit and rotate 180°.
4. Slide the condensate drainpan back into the unit, align the drain with the grommeted opening in the rear support panel and push until the coupling is seated in the grommet.
5. Replace the front support panel by aligning the panel with tabs in the raceway. Align the condensate drain pan support in the grommeted hole as the panel is put in place.
6. Replace evaporator access panel and supply airaccess panels.
To Convert Drain CondensateThrough the
Base of Unit:
1. Remove evaporator accesspanel and supplyair access panels.
2. Remove the support panel that the condensate drain pan exits through.
3. Slide the condensate drain pan out of the unit.
4. Place on a level surface in the position it was removed from the unit.
5. Remove the plug knockout in the bottom of the drain pan to convert it to through the base drainage.
6. Plug the original condensate drain opening with a field supplied 3/4” NPT plug.
7. Slide the condensate drainpan back into the unit, align the drain support with the grommeted opening in the rear support panel and push until the support is seated in the grommet.
22 RT-SVX38B-EN
Page 23
Installation
8. Replace the front support panel by aligning the panel with tabs inthe raceway.Align the pluggedcondensate drain pan coupling in the grommeted hole as the panel is put in place.
9. Replace evaporator access panel and supply airaccess panels.
A condensate trap must be installed at the unit due to the drain connection being on the“negative pressure” side of the fan. Install the P-Trap using the guidelines in Figure 23,
p. 23.
A condensate drain line must be connected to the P-Trap. Pitch the drain lines at least 1/2 inch for every 10 feet of horizontal run to assure proper condensate flow. Do not allow the horizontal run to sag causing a possible double­trap condition which could result in condensate backup due to “air lock”.
Figure 23. Condensate trap installation
38.1
Field Installed PowerWiring
WARNING
Proper Field Wiring and Grounding Required!
All field wiring MUST be performed by qualified
personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state electrical codes. Failure to follow code could result in death or serious injury.
An overall dimensional layout forthe field installed wiring
entrance into the unit is illustrated in “Unit Dimensions,”
p. 10.To insure that the unit’s supply power wiring is
properly sized and installed, follow the following guidelines.
Verify that the power supply available is compatible with
the unit’s nameplate ratings.The available supply power must be within 10% of the rated voltage stamped on the nameplate. Use only copper conductors to connect the power supply to the unit.
NOTICE:
Drain Pan Removal (Units with Condensate Overflow Switch Option)
Before drain pan removal, the switch wire must be disconnected from wire tie on panel and/or any tape before drain pan can be removed.
Care must be taken so the wire does not catch on the bottom of indoor coil or any protrusion.
Note: When reversing the drain pan, on some units, the
condensate overflow switch will need to be moved to the second hole in its bracket to avoid contact with headers or indoor coil.
Filter Installation
The quantity of filters is determined by unit size.Access to
the filters is obtained by removing the filter access panel. Refer to the unit Service Facts (shipped with each unit) for filter requirements.
Note: Do not operate the unit without filters.
Use Copper Conductors Only!
Unit terminals are not designed to accept other types of conductors. Failure to use copper conductors could result in equipment damage.
Note: If the unit is not equipped with an optional factory
installed non-fused disconnect switch or circuit breaker, a field supplied disconnect switch must be installed at or near the unit in accordance with the National Electrical Code (NEC latest edition).
Main Unit Power
WARNING
Proper Field Wiring and Grounding Required!
All field wiring MUST be performed by qualified
personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state electrical codes. Failure to follow code could result in death or serious injury.
RT-SVX38B-EN 23
Page 24
Installation
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/ tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.
Standard Wiring
1. Location ofthe applicableelectrical serviceentrance is illustrated in “Unit Dimensions,” p. 10. Complete the unit’s power wiring connections at Compressor Contactor # 1 (CC1) inside the unit control panel. Refer to the customer connection diagram that is shipped with the unit for specific termination points
2. Provide proper grounding for the unit in accordance with local and national codes.
Figure 24. All units
Field Installed Control Wiring
Note: All field wiring must conform to NEC guidelines as
well as state and local codes.
Control PowerTransformer
The 24 volt controlpower transformers areto be used only
with the accessories called out in this manual.
Transformers rated greater than 50VA are equipped with
internal circuit breakers. If a circuit breaker trips, turn “Off” all power to the unit before attempting to reset it.
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/ tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.
The transformer is located in the control panel.The circuit
breaker is located on the left side of the transformer and can be reset by pressing in on the black reset button.
Controls Using 24 VAC
Before installing any connecting wiring, refer to “Unit
Dimensions,” p. 10 for the electrical access locations
provided on the unit and Table 4, p. 24 for AC conductor sizing guidelines, and;
1. Use copper conductors unless otherwise specified.
2. Ensure that the AC controlwiring between the controls and the unit’s termination point does not exceed three (3) ohms/conductor for the length of the run.
Note: Resistance in excess of 3 ohms per conductor may
cause component failure due to insufficient AC voltage supply.
Note: Be sure to check all loads and conductors for
grounds, shorts, and mis-wiring.
3. Do not run the AC low voltage wiring in the same conduit with the high voltage power wiring.
4. Route low voltage wiring per illustrations per
Figure 27, p. 25.
Table 4. Electromechanical thermostat 24V AC
conductors with ReliaTel
Distance from Unit to Control Recommended Wire Size
000 - 460 feet 18 gauge 000 - 140 m .75 mm2 461 - 732 feet 16 gauge 141 - 223 m 1.3 mm2 733 - 1000 feet 14 gauge 224 - 305 m 2.0 mm2
Controls using DC Analog Input/Outputs (Standard Low Voltage Multi conductor Wire)
Before installing any connecting wiring between the unit and components utilizing a DC analog input\output signal, refer to “Unit Dimensions,” p. 10 for the electrical access locations provided on the unit.
Table 5, p. 25 lists the conductor sizing guidelines that must be followed when interconnecting the DC binary output devices and the system components utilizing a DC analog input/output signal to the unit.
Note: Resistance in excess of 2.5 ohms per conductor can
cause deviations in the accuracy of the controls.
24 RT-SVX38B-EN
Page 25
Installation
Note: Ensure that the wiring between controls and the
unit’s termination point does not exceed two and a half (2.5) ohms/conductor for the length of the run.
Do not run the electrical wires transporting DC signals in or around conduit housing high voltage wires.
Route low voltage wiring per Figure 27, p. 25.
DC Conductors
Table 5. Zone sensor module wiring
Distance from Unit to Control Recommended Wire Size
0 - 150 feet 22 gauge 0 - 45.7 m .33 mm2 151 - 240 feet 20 gauge 46 - 73.1 m .50 mm2 241 -385 feet 18 gauge
73.5 - 117.3 m .75 mm2 386 - 610 feet 16 gauge
117.7 - 185.9 m 1.3 mm2 611 - 970 feet 14 gauge
186.2 - 295.7 m 2.0 mm2
Figure 25. ReliaTel conventional thermostat field wiring
diagrams
RTRM
Figure 26. ReliaTel options module
Figure 27. ReliaTel control customer low voltage
routing
RT-SVX38B-EN 25
Space Temperature Averaging (ReliaTel™ Only)
Space temperature averaging is accomplished by wiring a number of remote sensors in a series/parallel circuit.
Using the BAYSENS016* or BAYSENS077*, at least four sensors are required to accomplish space temperature averaging. See diagram below.
Page 26
Installation
Example #1 illustrates two series circuits with two sensors in each circuit wired in parallel.The square of any number of remote sensors is required.
Example #2 illustrates three sensors squared in a series/parallel circuit. Using BAYSENS077*, two
Figure 28. Examples
sensors are required to accomplish spacetemperature averaging.
Example #3 illustrates the circuit required for this sensor. Table 6, p. 28 lists the temperature versus resistance coefficient for all sensors.
26 RT-SVX38B-EN
Page 27
Figure 29. Typical field wiring diagrams for optional controls (ReliaTel only)
Installation
BAYSENS075*
BAYSENS106*
BAYSENS073* BAYSENS074*
BAYSENS108*
BAYSENS075*
BAYSENS110*
BAYSENS119*
BAYSENS075* ASYSTAT669A OPTIONAL REMOTE SENSOR
RT-SVX38B-EN 27
Page 28
Installation
Table 6. Temperature vs. resistance
Temperature Degrees F° Degrees C° Nominal Resistance
-20° -28.9° 170.1 K - Ohms
-15° -26.1° 143.5 K - Ohms
-10° -23.3° 121.4 K - Ohms
-5° -20.6° 103.0 K - Ohms 0° -17.8° 87.56 K - Ohms 5° -15.0° 74.65 K - Ohms 10° -12.2° 63.80 K - Ohms 15° -9.4° 54.66 K - Ohms 20° -6.7° 46.94 K - Ohms 25° -3.8° 40.40 K - Ohms 30° -1.1° 34.85 K - Ohms 35° 1.7° 30.18 K - Ohms 40° 4.4° 26.22 K - Ohms 45° 7.2° 22.85 K - Ohms 50° 10.0° 19.96 K - Ohms 55° 12.8° 17.47 K - Ohms 60° 15.6° 15.33 K - Ohms 65° 18.3° 13.49 K - Ohms 70° 21.1° 11.89 K - Ohms 75° 23.9° 10.50 K - Ohms 80° 26.7° 9.297 K - Ohms 85° 29.4° 8.247 K - Ohms 90° 32.2° 7.330 K - Ohms 95° 35.0° 6.528 K - Ohms
Figure 30. Schematic diagram for field gas piping to
unit
Table 7. Sizing natural gas pipe mains and branches
Iron Pipe Size (IPS) Inches ½"
¾"
1"
Length of Pipe (Ft.)
15 76 176 345 750 1220 30 52 120 241 535 850 45 43 99 199 435 700 60 38 86 173 380 610 75 77 155 345 545
Note: Capacity of Pipe of Different Diameters and Lengths in Cu. Ft. Per Hr .
with Pressure Drop of 0.3" and Specific Gravity of 0.60
Pipe
Pipe
Pipe
Pipe
1¼"
1½" Pipe
Table 8. Iron pipe size (SI) millimeters
Iron Pipe Size (SI) Millimeters
Length of Pipe (Meters)
4.6 2.15 4.98 9.76 21.23 34.54
9.1 1.47 3.39 6.82 15.14 24.06
13.7 1.21 2.80 5.63 12.31 19.82
18.3 1.07 2.43 4.89 10.76 17.27
22.9 2.18 4.38 9.76 15.40
Note: Capacity of Pipe of Different Diameters and Lengths in Cu. Meter Per
Hr. with Pressure Drop of 74.6 Pa and Specific Gravity of 0.60.
15 mm Pipe
20 mm Pipe
25 mm Pipe
32 mm Pipe
40 mm Pipe
28 RT-SVX38B-EN
Page 29
Pre-Start
Use the checklist provided below in conjunction with the “General Unit Requirements” checklist to ensure that the unit is properly installed and ready for operation.
WARNING
Hazardous Voltage w/Capacitors!
Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/ tagout procedures to ensure the power cannot be inadvertently energized. Verify with an appropriate voltmeter that all capacitors have discharged. Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury.
For additional information regarding the safe discharge of capacitors, see PROD-SVB06A-EN
Verify that the condenser airflow will be unobstructed.
WARNING
Rotating Components!
During installation, testing, servicing and troubleshooting of this product it may be necessary to work with live and exposed rotating components. Have a qualified or licensed service individual who has been properly trained in handling exposed rotating components, perform these tasks. Failure to follow all safety precautions could result in rotating components cutting and slashing technician which could result in death or serious injury.
Verify that the condenser fan and indoor blower turn freely without rubbing and are properly tightened on the shafts.
Check the supply fan belts for proper tension and the fan bearings for sufficient lubrication. If the belts require adjustment, or if the bearingsneed lubricating, refer to the maintenance section of this manual for instructions.
Verify that acondensate trap is installed and the piping is properly sized and pitched.
Verify that the correct size and number of filters are in place.
Inspect the interior of the unit for tools and debris and install all panels in preparation for starting the unit.
Voltage Imbalance
Three phase electrical power to the unit must meet
stringent requirements for the unit to operate properly.
Measure each leg (phase-to-phase) of the power supply. Eachreading must fallwithin the utilizationrange stamped on the unit nameplate. If any of the readings do not fall
within the proper tolerances, notify the power company to correct this situation before operating the unit.
Excessive three phase voltage imbalance between phases will cause motors to overheat and eventually fail.The maximum allowable voltage imbalance is 2%. Measure and record the voltage between phases 1, 2, and 3 and calculate the amount of imbalance as follows:
% Voltage Imbalance=
AV (Average Voltage)=
V1, V2, V3 = Line Voltage Readings
VD = Line Voltage reading that deviates the farthest from
the average voltage.
100 x AV - VD
AV
Volt 1 + Volt 2 + Volt 3
where;
3
Example: If the voltage readings of the supply power
measured 221, 230, and 227, the average volts would be:
221 + 230 + 227
3
VD (reading farthest from average) = 221
The percentage of imbalance equals:
100 x 226 - 227
226
The 2.2% imbalance in this example exceeds the
maximum allowable imbalance of 2.0%.This much imbalance between phases can equal as much as a 20% current imbalance with a resulting increase in motor winding temperatures that will decrease motor life. If the voltage imbalance is over 2%, notify the proper agencies to correct the voltage problem before operating this equipment.
= 226 Avg.
= 2.2%
Electrical Phasing (Three Phase Motors)
The compressor motor(s) and the supply fan motor are
internally connected for the proper rotation when the incoming power supply is phased as A, B, C.
Proper electrical supply phasing can be quickly determined and corrected beforestarting the unit by using an instrument such as an Associated Research Model 45 Phase Sequence Indicator and following the steps below:
• Turn the field supplied disconnect switch that provides power to the main power terminal block or to the
“Line” side of the optional factory mounted disconnect switch to the “Off” position.
Connect the phase sequence indicator leads to the
terminal block or to the “Line” side of the optional factory mounted disconnect switch as follows;
Black (phase A) to L1
Red (phase B) to L2
Yellow (phase C) to L3
RT-SVX38B-EN 29
Page 30
Pre-Start
Close the field supplied main power disconnect switch or circuit protector switch that provides the supply power to the unit.
Note: Upon closing main power disconnect and the unit
mounted disconnect switch or circuit breaker, the phase monitor will verify proper phasing. If LED on face of the monitor is red, correct supply power fault.
WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
To prevent injury or death from electrocution, it is the
responsibility of the technician to recognize this hazard and use extreme care when performing service procedures with the electrical power energized.
Observe the ABC and CBA phaseindicator lights on the face of the sequencer.The ABC indicator lightwill glow if the phase is ABC. If the CBA indicator light glows, open the disconnect switch or circuit protection switch and reverse any two power wires.
Restore the main electrical power and recheck the phasing. If the phasing is correct, open the disconnect switch or circuit protection switch and remove the phase sequence indicator.
Compressor Crankcase Heaters (Optional)
Eachcompressor can be equipped with a crankcase heater (on some units the crankcase heater comes standard).The proper operation of the crankcase heater is important to maintain an elevated compressor oil temperature during the “Off” cycle to reduce oil foaming during compressor starts. Oil foaming occurs when refrigerant condenses in the compressor and mixes with the oil. In lower ambient conditions, refrigerant migration to the compressor could increase.
When the compressor starts, the sudden reduction in
crankcase pressure causes the liquid refrigerant to boil rapidly causing the oil to foam.This condition could damage compressor bearings due to reduced lubrication and could cause compressor mechanical failures.
Before starting the unit in the “Cooling” mode, set the system switch to the “Off” position and turn the main power disconnect to the “On” position and allow the crankcase heater to operate a minimum of 8 hours.
Before closing the main power disconnect switch, insure that the “System” selection switch is in the “Off” position and the “Fan” selection switch is in the “Auto” position.
Close the main power disconnect switch and the unit mounted disconnect switch, if applicable.
Note: Upon closing main power disconnect and the unit
mounted disconnect switch or circuit breaker, the phase monitor will verify proper phasing. If LED on face of the monitor is red, correct supply power fault.
WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
To prevent injury or death from electrocution, it is the
responsibility of the technician to recognize this hazard and use extreme care when performing service procedures with the electrical power energized.
ReliaTel™ Controls
Upon power initialization, the RTRM performs self­diagnostic checks to insure that all internal controls are functional. It also checks the configuration parameters against the components connected to the system.The Liteport LED located on the RTRM module is turned “On” within one second of power-up if internal operation is okay.
Use one of the following“Test” procedure to bypass some time delays and to start the unit at the control panel. Each step of unit operation can be activated individually by temporarily shorting across the“Test” terminals for two to three seconds.The Liteport LED located on the RTRM module will blink when the test mode has been initiated.
The unit can be left in any “Test” step for up to one hour
before it will automatically terminate, or it can be terminated by opening the main power disconnect switch. Once the test mode has been terminated, the Liteport LED will glow continuously and the unit will revert to the
“System” control.
30 RT-SVX38B-EN
Page 31
Table 9. Service test guide for component operation
Pre-Start
Test Step Mode Fan Econ
Fan On
1
Minimum
Ventilation
Economizer
2
Test Open
3
(e)
4
(e)
5
(e)
6
(e)
7
(e)
8
(a)The exhaust fan will turn on anytime the economizer damper position is equal to or greater than the exhaust fan setpoint. (b)The PWM Output is in reference to the user selected maximum unit fan speed. (c) Regardless of the Economizer Mode configuration, the unit will run the Supply Fan at the minimum speed during the Economizer step of the Service
Test. (d)The condenser fans will operate any time a compressor is ‘On’ providing the outdoor air temperatures are within the operating values. (e) Steps for optional accessories and non-applicable modes in unit will be skipped. (f) Units with Enhanced Dehumidification only will not perform this step during Service Test.
Cool
Stage 1
Cool
Stage 2
Cool
Stage 3
Reheat On Minimum On On Off Off 33KΩ 100%
Heat
Stage 1
Heat
Stage 2
On Selectable Off Off Off Off
On Open Off Off Off Off 3.3K
On
On
On
On Minimum Off Off On Off 10K
On Minimum Off Off On On 15K
(a)
Minimum
Position
Setpoint 0%
Minimum
Position
Minimum
Position
Minimum
Position
Comp 1 Comp 2 Heat 1 Heat 2 Resistance
Off Off Off Off
2.2KΩ 50% low
Ω 50%
(d)
On
On
On
(d)
(d)
Off Off Off 4.7KΩ 82% low
(d)
On
On
(d)
Off Off 6.8KΩ 100%
Off Off 8.2KΩ 100% High
Ω 100% High
Ω 100% High
PWM
Output
Multi-Speed Fan
(b)
(c)
(f)
Output
High (2-step cooling) Low (3-step cooling)
low
High
Test Modes
There are three methods in which the “Test” mode can be
cycled at LTB-Test 1 and LTB-Test 2.
1. Step Test Mode -This method initiates the different components of the unit, one at a time, by temporarily shorting across the two test terminals for two to three seconds. For the initial start-up of the unit, this method allows the technician to cycle a component “On” and have up to one hour to complete the check.
2. ResistanceTest Mode - This method can be used for start-up providing a decade boxfor variableresistance outputs is available.This method initiates the different components of the unit, one at a time, when a specific resistance value is placed across the two test terminals.The unit will remain inthe specific test mode for approximately one hour even though the resistance is left on the test terminals.
3. AutoTest Mode -This method is not recommended for start-up due to the short timing between individual component steps.This method initiates the different components of the unit, one at a time, when a jumper is installed across the test terminals.The unit will start the first test step and change to the next step every 30 seconds.
At the end of the test mode, control of the unit will
automatically revert to the applied “System” control method.
For unit test steps, test modes, and step resistance values to cycle the various components, refer to Table 9, p. 31.
ReliaTel Controls
Upon power initialization, the Gas Ignition Module (IGN) performs self-diagnostic checks to insure that all internal controls are functional. It also checks the configuration parameters against the components connected to the system.The System LED located on the IGN module is turned “On” within one second of power-up if internal operation is okay.
RT-SVX38B-EN 31
Page 32
Unit Start-Up
Verifying Proper Air Flow
WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
Units with Belt Drive Indoor Fan
Much of the systems performance and reliability is closely associated with, and dependent upon having the proper airflow supplied both to the space that is being conditioned and across the evaporator coil.
The indoor fan speed is changed by opening or closingthe
adjustable motor sheave.
Before starting the SERVICETEST, set the minimum position setpoint for the economizer to 0 percent using the setpoint potentiometer located onthe Economizer Control (ECA), if applicable.
ReliaTel Control: Using the ServiceTest Guide in
Table 6, p. 30, momentarily jump across the Test 1 &Test
2 terminals on LTB1 one time to start the Minimum
Ventilation Test.
With the fan operating properly, determine the total
system airflow (CFM) by:
1. Measuring the actual RPM,
2. Measure the amperage at the supply fan contactor and compare it with the fullload amp (FLA) rating stamped on the motor nameplate.
a. Calculate the theoretical BHP using (Actual Motor
Amps/ Motor Nameplate Amps) X Motor HP.
b. Using thefan performance tables inthe unit Service
Facts, plot the actual RPM (step 1) and the BHP (step 2a) to obtain the operating CFM.
3. If therequired CFM is too low, (externalstatic pressure is high causing motor HP output to be below table value),
a. Relieve supply and/or return duct static.
b. Change indoor fan speed and repeat steps 1 and 2.
• ToIncrease Fan RPM; Loosen the pulley adjustment set screw and turn sheave clockwise.
• To Decrease Fan RPM; Loosen the pulley adjustment set screw and turn sheave counterclockwise.
If the required CFM is too high, (external static pressure is low causing motor HP output to be above
table value), change indoor fan speed and repeat steps 1 and 2.
• To stop the SERVICETEST, turn the main power disconnect switch to the "Off" position or proceed to the next component start-up procedure.
Economizer Start-Up
ReliaTel Control: Using the ServiceTest Guide in
Table 6, p. 30, momentarily jump across the Test 1 &Test
2 terminals on LTB1 one time to start the Minimum
Ventilation Test.
1. Set the minimum position setpoint for the economizer to the required percentage of minimum ventilation using the setpoint potentiometer located on the Economizer Control (ECA).
The economizer will drive to its minimum position
setpoint, exhaust fans (if applicable) may start at random, and the supply fan will start when the SERVICETEST is initiated.
WARNING
Rotating Components!
During installation, testing, servicing and troubleshooting of this product it may be necessary to measure the speed of rotating components. Have a qualified or licensed service individual who has been properly trained in handling exposed rotating components, perform these tasks. Failure to follow all safety precautions when exposed to rotating components could result in death or serious injury.
The Exhaust Fan will start anytime the economizer
damper position is equal to orgreater than the exhaust fan setpoint.
2. Verify that the dampers stroked to the minimum position.
ReliaTel Control:
Momentarily jump across theTest 1 &Test 2 terminals on LTB1 one additional time if continuing from previous component start-up or until the desired start­up componentTest is started.
3. Verify that the dampers stroked to the full open position.
4. To stop the SERVICETEST, turn the main power disconnect switch to the “Off” position or proceed to the next component start-up procedure. Remove electro mechanical test mode connections (if applicable).
32 RT-SVX38B-EN
Page 33
Unit Start-Up
Compressor Start-Up
1. Attach a set of service gauges onto the suction and discharge gauge ports for each circuit. Refer to the refrigerant circuit illustration in the Service Facts.
ReliaTel Control:
Momentarily jump across theTest 1 &Test 2 terminals on LTB1 one additional time if continuing from previous component start-up or until the desired start­up componentTest is started.
Scroll Compressors
a. Once each compressor has started, verify that the
rotation is correct. If a scroll compressor is rotating backwards, it will not pump and a loud rattling sound can be observed.
b. If the electrical phasing is correct, before
condemning a compressor, interchange any two leads (at the compressorTerminal block) to check the internal phasing. If the compressor runs backwardfor an extendedperiod (15 to 30minutes), the motor winding can overheat and cause the motor winding thermostat to open.
2. After the compressor and condenser fan have started and operated for approximately 30 minutes, observe the operating pressures. Compare the operating pressures to the operating pressure curve in the Service Facts.
3. Check system superheat. Follow the instruction listed on the superheat charging curve in the Service Facts.
Superheat should be within ±5F ofthe superheatchart value.
4. Repeat steps 1 through 4 for each refrigerant circuit.
5. To stop the SERVICETEST, turn the main power disconnect switch to the “Off” position or proceed to the next component start-up procedure. Remove electro mechanical test mode connections (if applicable).
Final System Setup
After completing all of the pre-start and start-up
procedures outlined in the previous sections (i.e., operating the unit in each of its Modes through all available stages of cooling & heating), perform these final checks before leaving the unit:
Program the Night Setback (NSB) panel (if applicable) for proper unoccupied operation. Refer to the programming instructions for the specific panel.
Verify that the Remote panel “System” selection switch, “Fan” selection switch, and “Zone
Temperature” settings for automatic operation are
correct.
Inspect the unit for misplaced tools, hardware, and debris.
Verify that all exterior panels including the control panel doors and condenser grilles are secured in place.
Close the main disconnect switch or circuit protector switch that provides the supply power to the unit’s terminal block or the unit mounted disconnect switch.
WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
Make sure all personnel are standing clear of the unit before proceeding.The system components will start when the power is applied.
Gas Heat Units
Open the main disconnect switch to shut the unit off and to reset the RTRM.
ReliaTel Control: Follow theTest Guide inTable 9, p. 32
to start the unit in the heating mode. Momentarily jump across theTest 1 &Test 2 terminals on LTB1 one additional time if continuing from previous component start-up or until the desired start-up componentTest is started.
When starting the unit for the first time or servicing the
heaters, it is a good practice to start the heater with the main gas supply turned “Off”.
Once the ignition system and components have been checked, open the main power disconnect switch to reset the unit.
RT-SVX38B-EN 33
Page 34
Maintenance
Fan Belt Adjustment - Belt Drive Units
WARNING
Rotating Components!
During installation, testing, servicing and troubleshooting of this product it may be necessary to measure the speed of rotating components. Have a qualified or licensed service individual who has been properly trained in handling exposed rotating components, perform these tasks. Failure to follow all safety precautions when exposed to rotating components could result in death or serious injury.
The fan belts must be inspected periodically to assure
proper unit operation.
Replacement is necessary if the belts appear frayed or worn. Units with dual belts require a matched set of belts to ensure equal belt length.
When removing or installing the new belts, do not stretch
them over the sheaves. Loosen the belts using the belt tension adjustment bolts on the motor mounting base.
Once the new belts are installed, using a Browning or Gates tension gauge (or equivalent) illustrated in
Figure 31; adjust the belt tension as follows;
1. To determine the appropriate belt deflection;
a. Measure the center-to-center shaft distance (in
inches) between the fan and motor sheaves.
b. Divide the distance measured in Step 1a by 64; the
resulting value represents the amount of belt deflection that corresponds to the proper belt tension.
2. Set the large O-ring on the belt tension gauge at the deflection value determined in Step 1b.
3. Set the small O-ring at zero on the force scale of the gauge plunger.
4. Place the large end of thegauge at the center of the belt span; then depress the gauge plunger until thelarge O­ring is even with the top of the next belt or even with a straightedge placed across the fan and motor sheaves. Refer to Figure 9.
5. Remove the belt tension gauge.The small O-ring now indicates a number other than zero on the plunger’s force scale.This number represents the force (in pounds) required to give the needed deflection.
6. Compare the “force” scale reading (Step 5) with the appropriate “force” value listed in Table 10.Ifthe
“force” reading is outside the range, readjust the belt
tension.
Note: Actual belt deflection “force” must not exceed the
maximum “force” value shown in Table 10
7. Recheck the belt tension at least twice during the first 2 to 3 days of operation. Belt tension may decrease until the new belts are “run in”.
Figure 31. Belt tension gauge
Table 10. Belt tension measurement and deflection
Deflection Force (Lbs.)
Belts Cross Section
A 3.8 - 4.8 3 1/2 5 4 1/2 6 1/4 3 3/4 4 3/4
B 4.4 - 5.6 5 1/8 7 1/8 6 1/2 9 1/8 5 3/4 7 1/4
Small P.D Range
3.0 - 3.6 3 4 1/2 3 7/8 5 1/2 3 1/4 4
5.0 - 7.0 4 5 1/2 5 6 7/8 4 1/4 5 1/4
3.4 - 4.2 4 5 1/2 5 3/4 8 4 1/2 5 1/2
5.8 - 8.8 6 3/8 8 3/4 7 3/8 10 1/8 7 8 3/4
Super
Gripbelts Gripnotch
Min. Max. Min. Max. Min. Max
Steel Cable
Gripbelts
Monthly Maintenance
WARNING
Rotating Components!
During installation, testing, servicing and troubleshooting of this product it may be necessary to measure the speed of rotating components. Have a qualified or licensed service individual who has been properly trained in handling exposed rotating components, perform these tasks. Failure to follow all safety precautions when exposed to rotating components could result in death or serious injury.
Before completing the following checks, turn the unit OFF and lock the main power disconnect switch open.
Filters
Inspect the return air filters. Clean or replace them if necessary. Refer to the unit Service Facts for filter information.
34 RT-SVX38B-EN
Page 35
Maintenance
Condensate Overflow Switch
During maintenance, the switch float (black ring) must be checked to ensure free movement up and down.
Cooling Season
Check the unit’s drain pans and condensate piping to ensure that there are no blockages.
Inspect the evaporator and condenser coils for dirt, bent fins, etc. If the coils appear dirty, clean them according to the instructions described in “Coil Cleaning” later in this section.
Manually rotate the condenser fan(s) to ensure free movement and check motor bearings for wear. Verify that all of the fan mounting hardware is tight.
Inspect the F/A-R/A damper hinges and pins to ensure that all moving parts are securely mounted. Keep the blades clean as necessary.
Verify that all damper linkages move freely; lubricate with white grease, if necessary.
Check supply fan motor bearings; repair or replace the motor as necessary.
Check the fan shaft bearings for wear. Replace the bearings as necessary.
Check the supply fan belt. If the belt is frayed or worn, replace it. Refer to the “Fan Belt Adjustment” section for belt replacement and adjustments.
Verify that all wire terminal connections are tight.
Remove any corrosion present onthe exterior surfaces of the unit and repaint these areas.
Generally inspect the unit for unusual conditions (e.g., loose access panels, leaking piping connections, etc.)
Make sure that all retaining screws are reinstalled in the unit access panels once these checks are complete.
With the unit running, check and record the: ambient temperature; compressor suction and discharge pressures (each circuit); superheat (each circuit);
Record this data on an “operator’s maintenance log” like the one shown in Table 11, p. 37. If the operating pressures indicate a refrigerant shortage, measure the system superheat. For guidelines, refer to the
“Compressor Start-Up” section.
Note: Do not release refrigerant to the atmosphere! If
adding or removing refrigerant is required, the service technician must comply with all federal, state and local laws.
Heating Season
Inspect the unit’s air filters. If necessary, clean or replace them.
Check supply fan motor bearings; repair or replace the motor as necessary.
Inspect both the main unit control panel and heat section control box for loose electrical components and terminal connections, as well as damaged wire insulation. Make any necessary repairs.
Clean burner area, verify gas heat system operates properly.
Coil Cleaning
Regular coil maintenance, including annual cleaning, enhances the unit’s operating efficiency by minimizing: compressor head pressure and amperage draw; evaporator water carryover; fan brake horsepower, due to increase static pressure losses; airflow reduction.
At least once each year, or more often if the unit is located
in a “dirty” environment, clean the evaporator and condenser coils using the instructions outlined below. Be sure to follow these instructions as closely as possible to avoid damaging the coils.
Note: For units equipped with hail guards follow removal
procedure listed below.
Hail Guard Removal
Unlatch hail guard.
Pull the top ofthe hail guard outward until the fastener studs are free of the retaining nuts.
Lift the hail guard from the lower retaining bracket and set aside.
To clean refrigerant coils, use a soft brush and a sprayer
(either a garden pump-up typeor a high-pressure sprayer).
A high-quality detergent is also required; suggested
brands include “SPREX A.C.”, “OAKITE 161”, “OAKITE 166” and “COILOX”. If the detergent selected is stronglyalkaline (ph value exceeds 8.5), add an inhibitor.
WARNING
Hazardous Chemicals!
Coil cleaning agents can be either acidic or highly alkaline. Handle chemical carefully. Proper handling should include goggles or face shield, chemical resistant gloves, boots, apron or suit as required. For personal safety refer to the cleaning agent manufacturer’s Materials Safety Data Sheet and follow all recommended safe handling practices. Failure to follow all safety instructions could result in death or serious injury.
1. Remove enough panels from the unit to gain access to the coil.
2. Protect all electrical devices such as motors and controllers from any over spray.
3. Straighten any bent coil fins with a fin comb.
4. Mix the detergent with water according to the manufacturer’s instructions. If desired, heat the solution BUT DO NOT EXCEED 150 F maximum to improve its cleansing capability.
RT-SVX38B-EN 35
Page 36
Maintenance
WARNING
Hazardous Pressures!
Coils contain refrigerant under pressure.When cleaning coils, maintain coil cleaning solution temperature under 150°F to avoid excessive pressure in the coil. Failure to follow these safety precautions could result in coil bursting, which could result in death or serious injury.
5. Pour the cleaning solution into the sprayer. If a high­pressure sprayer is used:
a. Do not allow sprayer pressure to exceed 600 psi.
b. The minimum nozzle spray angle is 15 degrees.
c. Maintain a minimum clearance of 6" between the
sprayer nozzle and the coil.
d. Spray the solution perpendicular (at 90 degrees) to
the coil face.
6. Spray the leaving-airflow side of the coil first; then spray the opposite side of the coil. Allow the cleaning solution to stand on the coil for five minutes.
7. Rinse both sides of the coil with cool, clean water.
8. Inspect both sides of the coil; if it still appears to be dirty, repeat Steps 6 and 7.
9. Reinstall all of the components and panels removed in Step 1 and any protective covers installed in Step 2.
Note: For units equipped with hail guards follow
reinstallation procedure listed below.
Hail Guard Reinstallation
10.To reinstall the hail guard, locate the bottom of the hail guard in the lower bracket and secure it to the upper unit bracket with the attached fasteners.
Note: Secure hail guard latches.
Figure 32. Slide latch
11. Restore the unit to it’s operational status and check system operation.
Annual Maintenance
Clean and repaint any corroded surface.
36 RT-SVX38B-EN
Page 37
Maintenance
Final Process
For future reference, you may find it helpful to record the unit data requested in the blanks provided.
Wiring Diagram Numbers (from unit control panel)
Schematics
Complete Model Number
Connections
Unit Serial Number
Table 11. Sample maintenance log
Current
Date
Note: Check and record the data requested above each month during the cooling season with the unit running
Temp. F/C
Ambient
Compr. Oil Level
- ok
- low
- ok
- low
- ok
- low
- ok
- low
- ok
- low
- ok
- low
- ok
- low
- ok
- low
- ok
- low
- ok
- low
- ok
- low
Refrigerant Circuit #1 Refrigerant Circuit #2
Suct. Press. Psig/ kPa
Disch. Press. Psig/ kPa
Liquid Press. Psig/ kPa
Super
-heat F/C
Sub­cool. F/C
Compr. Oil Level
- ok
- low
- ok
- low
- ok
- low
- ok
- low
- ok
- low
- ok
- low
- ok
- low
- ok
- low
- ok
- low
- ok
- low
- ok
- low
Suct. Press. Psig/kPa
Disch. Press. Psig/ kPa
Liquid Press. Psig/ kPa
Super­heat F/C
Sub­cool. F/C
RT-SVX38B-EN 37
Page 38
Trouble Shooting
ReliaTel™ Control
The RTRM has the ability to provide the service personnel
with some unitdiagnostics and system status information.
Before turning the main power disconnect switch “Off”, follow the steps below to check the ReliaTel Refrigeration Module (RTRM). All diagnostics & system status information stored in theRTRM will be lost when the main power is turned “Off”.
operations for each mode, to assist in verifying proper operation. Make the necessary repairs and proceed to Steps 7 and 8.
7. If no abnormal operating conditions appear in the test mode, exit the test mode by turning the power “Off” at the main power disconnect switch.
8. Refer to the individual component test procedures if other microelectronic components are suspect.
System Status Checkout
WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
To prevent injury or death from electrocution, it is the
responsibility of the technician to recognize this hazard and use extreme care when performing service procedures with the electrical power energized.
1. Verify that the Liteport LED on the RTRM is burning continuously. If the LED is lit, go to Step 3.
2. If the LED is not lit, verify that 24 VAC is presence between J1-1 and J1-2. If 24 VAC is present, proceed to Step 3. If 24 VAC is not present, check the unit main power supply, check transformer (TNS1). Proceed to Step 3 if necessary.
3. Utilizing “Method 1” or “Method 2” in the “System Status Diagnostic” section, check the following:
System status
Heating status
Cooling status
If a System failure is indicated, proceed to Step 4. If no failures are indicated, proceed to Step 5.
4. If a System failure is indicated, recheck Steps 1 and 2. If the LED is not lit in Step 1, and 24 VAC is present in Step 2, the RTRM has failed. Replace the RTRM.
5. If no failures are indicated, use one of theTEST mode procedures described in the “Unit Start-Up” section to start the unit.This procedure will allow you to check all of the RTRM outputs, and all of the external controls (relays, contactors, etc.) that the RTRM outputs energize, for each respective mode. Proceed to Step 6.
6. Step the system through all of the available modes, and verify operation of all outputs, controls, and modes. If a problem inoperation is noted in any mode, you may leave the system in that mode for up to one hour while troubleshooting. Refer to the sequence of
38 RT-SVX38B-EN
Procedure
“System Status” is checked by using one of the following
two methods:
Method 1
If the Zone Sensor Module (ZSM) is equipped with a remote panel with LED status indication, you can check the unit within the space. If the ZSM does not have LED’s, use Method 2. BAYSENS110*, BAYSENS109*, BAYSENS119*, BAYSENS023A all have the remote panel indication feature.The LED descriptions are listed below.
LED 1 (System)
“On” during normal operation.
“Off” if a system failure occurs or the LED fails.
“Flashing” indicates test mode.
LED 2 (Heat)
“On” when the heat cycle is operating.
“Off” when the heat cycle terminates or the LED fails.
“Flashing” indicates a heating failure.
LED 3 (Cool)
“On” when the cooling cycle is operating.
“Off” when the cooling cycle terminates or the LED fails.
“Flashing” indicates a cooling failure.
LED 4 (Service)
“On” indicates a clogged filter.
“Off” during normal operation.
“Flashing” indicates an evaporator fan failure or
condensate overflow switch failure.
Below is the complete listing of failure indication causes.
System failure
Check the voltage between terminals 6 and 9 on J6, it should read approximately 32 VDC. If no voltage is present, a System failure has occurred. Refer to Step 4 in the previous section for the recommended troubleshooting procedure.
Page 39
Trouble Shooting
Heating Failure
Verify Heat Failure by Ignition Module (IGN) LED indicator:
OFF: No Power or Failure
ON: Normal
Slow Flash: Normal, Heat Call
Fast Flash: Error Code:
1 Flash: Communication Failure
2 Flashes: System Lockout
3 Flashes: Pressure Switch Fail
4 Flashes: TC01 orTC02 Open
5 Flashes: Flame w/o Gas Valve
6 Flashes: Flame Rollout Open
Cooling Failure
Cooling and heating set point (slide pot) on the zone sensor has failed. Refer to the “Zone SensorTest Procedure” section.
Zone temperature thermistor ZTEMP on ZTS failed. Refer to the “Zone SensorTest Procedure” section.
CC1 or CC2 24 VAC control circuit has opened, check CC1 & CC2 coils, and any of the controls below that apply to the unit (HPC1, HPC2).
LPC1 has opened during the 3 minute minimum “on time” during 4 consecutive compressor starts, check LPC1 or LPC2 by testingvoltage between theJ1-1 & J3­2 terminals on the RTRM and ground. If 24 VAC is present, the LPC’s has not tripped. If no voltage is present, LPC’s has tripped.
Service Failure
If the supply fanproving switchhas closed, the unit will not operate (when connected to RTOM), check the fan motor, belts, and proving switch.
Clogged filter switch has closed, check the filters.
If the condensate overflow switch is closed, the unit will not operate, check the float position is not in a tripped condition and verify an "open" between wires connecting to RTOM J6-1, J6-2 (ReliaTel controls).
Simultaneous Heat and Cool Failure
Emergency Stop is activated
Method 2
The second method for determining system status is done
by checking voltage readings at the RTRM (J6).The system indication descriptions and the approximate voltages are listed below.
System Failure
Measure the voltage between terminals J6-9 & J6-6.
Normal Operation = approximately 32 VDC
System Failure = less than 1 VDC, approximately 0.75 VDC
• Test Mode = voltage alternates between 32VDC & 0.75 VDC
Heat Failure
Measure the voltage between terminals J6-7 & J6-6.
Heat Operating = approximately 32 VDC
Heat Off = less than 1 VDC, approximately 0.75 VDC
Heating Failure = voltage alternates between 32 VDC &
0.75 VDC
Cool Failure
Measure the voltage between terminals J6-8 & J6-6.
Cool Operating = approximately 32 VDC
Cool Off = less than 1 VDC, approximately 0.75 VDC
Cooling Failure = voltage alternates between 32 VDC &
0.75 VDC
Service Failure
Measure the voltage between terminals J6-10 & J6-6.
Clogged Filter = Approximately 32VDC.
Normal = Less than 1 VDC, approximately 0.75 VDC Fan Failure =voltage alternates between 32VDC & 0.75 VDC.
To use LED’s for quick status information at the unit,
purchase a BAYSENS110* ZSM and connect wires with alligator clamps to terminals 6 through10.Connected each respective terminal wire (6 through 10) from the Zone Sensor to the unit J6 terminals 6 through 10.
Note: If the system is equipped with a programmable
zone sensor, (BAYSENS119*, or BAYSENS023A), the LED indicators will not function while the BAYSENS110* is connected.
Resetting Cooling and Ignition Lockouts
Cooling Failures and Heating Lockouts are reset in an identical manner. Method 1 explains resetting the system from the space; Method 2 explains resetting the system at the unit.
Note: Before resetting Cooling Failures and Ignition
Lockouts check the Failure Status Diagnostics by the methods previously explained. Diagnostics will be lost when the power to the unit is disconnected.
Method 1
To reset the system from the space, turn the “Mode”
selection switch at the zone sensor to the “Off” position.
After approximately 30 seconds, turn the “Mode”
selection switch to the desired mode, i.e. Heat, Cool or
Auto.
RT-SVX38B-EN 39
Page 40
Trouble Shooting
Method 2
To reset the system at the unit, cycle the unit power by
turning the disconnect switch “Off” and then “On”.
Lockouts can be cleared through the building management system. Refer to the building management system instructions for more information.
Zone Temperature Sensor (ZTS) Service Indicator
The ZSM SERVICE LED is a generic indicator, that will
signal the closing of a Normally Open switch at any time, providing the Indoor Motor (IDM) is operating.This indicator is usually used to indicate a clogged filter, or an air side fan failure.
The RTRM will ignore the closing of this Normally Open
switch for 2 (±1) minutes.This helps prevent nuisance SERVICE LED indications.The exception is the LED will flash 40 seconds after the fan is turned “On” if the Fan Proving Switch is not made.
Clogged Filter Switch
This LED will remain lit the entire time that the Normally
Open switch is closed.The LED will be turned off immediately after resetting the switch (to the Normally Open position), or any time that the IDM is turned “Off”.
If the switch remains closed, and the IDM is turned “On”, the SERVICE LED will be turned “On” again after the 2 (±1) minute ignore delay.
This LED being turned “On”, will have no other affect on
unit operation. It is an indicator only.
Fan Failure Switch
When the “Fan Failure” switch is wired to the RTOM, the
LED will remain flashing the entire time the fan proving switch is closed, indicating a fan failure,and itwill shutthe unit operations down.
Zone Temperature Sensor (ZTS)
Test
Note: These procedures are not for programmable or
digital models and are conducted with the Zone Sensor Module electrically removed from the system.
Test 1 - ZoneTemperatureThermistor
(ZTEMP)
This component is tested by measuring the resistance
between terminals 1 and 2 on the ZoneTemperature Sensor. Below are some typical indoor temperatures, and corresponding resistive values.
Test 2 - Cooling Set Point (CSP) and
Heating Set Point (HSP)
Table 12. Cooling setpoint and heating setpoint
Zone Temperature
50 F° 10.0 C° 19.9 K-Ohms 55 F° 12.8 C° 17.47 K-Ohms 60 F° 15.6 C° 15.3 K-Ohms 65 F° 18.3 C° 13.49 K-Ohms 70 F° 21.1 C° 11.9 K-Ohms 75 F° 23.9 C° 10.50 K-Ohms 80 F° 26.7 C° 9.3 K-Ohms 85 F° 29.4 C° 8.25 K-Ohms 90 F° 32.2 C° 7.3 K-Ohms
The resistance of these potentiometers are measured
between the following ZSM terminals. Refer to the chart above for approximate resistances at the given setpoints.
Cool SP =Terminals 2 and 3
Range = 100 to 900 Ohms approximate
Heat SP =Terminals 2 and 5
Range = 100 to 900 Ohms approximate
Nominal ZTEMP
Resistance
Condensate Overflow Switch
When the “Condensate Overflow Switch” is closed, a
drain pan overflow condition is indicated and it will shut unit operations down.
40 RT-SVX38B-EN
Test3-SystemMode and Fan Selection
The combined resistanceof the Mode selection switch and
the Fan selection switch can be measured between terminals 2 and 4 on the Zone Sensor.The possible switch combinations are listed below with their corresponding resistance values.
Page 41
Trouble Shooting
Test 4 - LED IndicatorTest, (SYS ON, HEAT,
COOL & SERVICE)
Method 1
Testing the LED usinga meter with diode test function.Test
both forward and reverse bias. Forward bias should measure a voltage drop of 1.5 to 2.5 volts, depending on your meter. Reverse bias will show an Over Load, or open circuit indication if LED is functional.
Method 2
Testing the LED with an analog Ohmmeter. Connect
Ohmmeter across LED in one direction, then reverse the leads for the opposite direction.The LED should have at least 100 times more resistance in reverse direction, as compared with the forward direction. If high resistance in both directions, LED is open. If low in both directions, LED is shorted.
Method 3
To test LED’s with ZSM connected to unit, test voltages at
LED terminals on ZSM. A measurement of 32VDC, across an unlit LED, means the LED has failed.
Programmable & Digital Zone Sensor Test
Testing serial communication voltage
1. Verify 24VAC is present between terminals J6-14 & J6-
11.
2. Disconnect wires from J6-11 and J6-12. Measure the voltage between J6-11 and J6-12, should be about 32
VDC.
3. Reconnect wires toterminals J6-11 and J6-12. Measure voltage again betweenJ6-11 and J6-12, voltage should flash high and low every 0.5 seconds.The voltage on the low end will measure about 19VDC, while the voltage on the high end will measure from approximately 24 to 38 VDC.
4. Verify all modes of operation, by running the unit through all of the steps in the “Test Modes” section discussed in “Unit Start-Up”.
5. After verifying proper unit operation, exit the test mode.Turn the fan on continuously at the ZSM, by pressing the button with the fan symbol. If the fan comes on and runs continuously, the ZSM is good. If you are not able to turn the fan on, the ZSM is defective.
ReliaTel Refrigeration Module (RTRM) Default Chart
If the RTCI loses input from the building management system, the RTRM will control in the default mode after approximately 15 minutes. If the RTRM loses the Heating and Cooling setpoint input, the RTRM will control in the default mode instantaneously.The temperature sensing
thermistor in the Zone Sensor Module is the only component required for the “Default Mode” to operate.
Unit Operation without a Zone Sensor
This procedure is for temporary operation only.The
economizer and condenser fan cycling functions are disabled.
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/ tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.
1. Open and Lock the unit disconnect switch.
2. Remove the Outside Air Sensor (OAS) from the condenser section of unit.
3. Use two (2) wire nuts, to individually cap the wires.
4. Locate the RTRM (J6). Connect two (2) wires to terminals J6-1 and 2.
5. Connect the sensor (OAS) using two wire nuts to the two (2) field supplied wires that were connected to terminals 1 and 2 on J6.
Unit Economizer Control (ECA)
Troubleshooting
ReliaTel Control
Verify Economizer Status by Economizer Actuator (ECA)
LED indicator:
OFF: No Power or Failure
ON: Normal, OK to Economize
Slow Flash: Normal, Not OK to Economize
Fast Flash - 1/2 Second On/2Seconds Off:
Error Code:
Communications Failure
Pulse Flash:2 Seconds On / 1/2 Second Off:
Error Code:
1 Flash: Actuator Fault
2 Flashes: CO
3 Flashes: RA Humidity Sensor
4 Flashes: RATemp Sensor
5 Flashes: OA Quality Sensor
6 Flashes: OA Humidity Sensor
7 Flashes: OATemp Sensor
8 Flashes: MATemp Sensor
9 Flashes:RAM Fault
Sensor
2
RT-SVX38B-EN 41
Page 42
Trouble Shooting
10 Flashes:ROM Fault
11 Flashes:EEPROM Fault
Heating Failure
Verify Heat Failure by Ignition Module (IGN) LED indicator:
OFF: No Power or Failure
ON:Normal
Slow Flash: Normal, Heat Call
Fast Flash:Error Code:
1 Flash:No Communication
2 Flashes:System Lockout
3 Flashes:Pressure Switch Fail
4 FlashesTC01 orTC02 Open
5 Flashes:Flame w/o Gas Valve
6 Flashes:Flame Rollout Open
Cooling Failure
Cooling and heating set point (slide pot) on the thermostat has failed.
CC1 or CC2 24 VAC control circuit has opened, check CC1 & CC2 coils, and any of the controls below that apply to the unit (HPC1, HPC2, LPC1, LPC2, Frostat™).
Resetting Cooling and Ignition Lockouts
Cooling Failures and Ignition Lockouts are reset in an identical manner. Method 1 explains resetting the system from the space; Method 2 explains resetting the system at the unit.
Method 1
To reset the system from the space, turn the “Mode”
selection switch at the thermostat to the “Off” position. After approximately 30 seconds, turn the “Mode” selection switch to the desired mode, i.e. Heat, Cool or Auto.
Method 2
To reset the system at the unit, cycle the unit power by
turning the disconnect switch “Off” and then “On”.
42 RT-SVX38B-EN
Page 43
Unit Wiring Diagrams Numbers
Note: Wiring diagrams can be accessed using e-Library
by entering the diagram number in the literature order number search field or by contacting technical support.
Table 13. Unit wiring diagram numbers
Schematic
Type
Control
4366-1012-0110 4366-1015-0104 4366-1005-0104 4366-1540-0110 072E 4366-1015-0104 4366-1005-0104 4366-1540-0110 090E 4366-1042-0110 4366-1034-0110 4366-1532-0110 102E 4366-1042-0110 4366-1034-0110 4366-1532-0110 120E
Schematic
Type
4366-1005-0104
Power
Schematic
Type Description
4366-1543-0110 060E
Connection
Diagram
RT-SVX38B-EN 43
Page 44
Limited Warranty
Combination Gas Electric Air Conditioner
YCC, YCD,YCH,YCP, YSC and YHC (Parts
Only)
Models LessThan 20 Tons for Residential Use*
This limited warranty is extended byTrane to the original
purchaser and to any succeeding owner of the real property to which the Combination Gas Electric Air Conditioner is originally affixed, and applies to products purchased and retained for use within the U.S.A. and Canada.
If any part of your Combination Gas Electric Air Conditioner fails becauseof a manufacturing defectwithin five years from the date of the original purchase,
Warrantor will furnish without charge the required
replacement part.Any local transportation, related service labor, diagnosis calls, air filters, refrigerant and related items are not included.
If the sealed motor-compressor fails because of a manufacturing defect within five years from the date of original purchase, Warrantor will furnish without charge the required replacement compressor. Any local transportation, related service labor, diagnosis calls, refrigerant and related items are not included.
In addition, if theoptional, factory installed, stainless steel heat exchanger fails because of a manufacturing defect within ten years from the date of start-up, Warrantor will furnish without chargea replacement heat exchanger. Any local transportation, related service labor and diagnosis calls are not included.
This limited warranty does not cover failure of your
combination gas electric air conditioner if it is damaged while in your possession, failure attributable or caused by unreasonable use of the combination gas electric air conditioner and/or failure to properly maintain the combination gas electric air conditioner as set forth in the Use and Care manual.
This limited warranty applies to product installed on or
after 10/1/2001 where product is manufactured after 1/1/
2000.This limited warranty is not retroactive to any installations prior to 10/1/2001 or on product produced prior to 2000.
THE LIMITED WARRANTY AND LIABILITY SET FORTH
HEREIN ARE IN LIEU OF ALL OTHER WARRANTIES AND LIABILITIES, WHETHER IN CONTRACT OR IN NEGLIGENCE, EXPRESS ORIMPLIED, IN LAW OR IN FACT, INCLUDING IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR PARTICULAR USE, AND IN NO EVENT SHALL WARRANTOR BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES.
Some states do not allow limitations on how long an implied limited warranty lasts or do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you.This limited warranty gives you specific legal rights, and youmay also have otherrights whichvary from state to state.
Parts will be provided by our factory organization through an authorized service organizationin your area listedin the yellow pages. If you wish further help or information concerning this limited warranty, contact:
Trane
2701 Wilma Rudolph Blvd.
Clarksville,TN 37040-1008
Attention: Manager, Product Service
GW-618-4001
*This limited warranty is for residential usage of this equipment and not applicable when this equipment is used for a commercial application. A commercial use is any application where the end purchaser uses the product for other than personal, family or household purposes.
Combination Gas Electric Air Conditioner
YCZ, YCY, YCX,YCC, YCD,YCH,YCP, YHC
and YSC (Parts Only)
Models LessThan 20 Tons for Commercial Use*
This warranty is extended byTrane to the original
purchaser and to any succeeding owner of the real property to which the Combination Gas Electric Air Conditioner is originally affixed, and applies to products purchased and retained for use within the U.S.A. and Canada.There is no warranty against corrosion, erosion or deterioration.
If any part of your Combination Gas Electric Air Conditioner fails becauseof a manufacturing defectwithin one year from the date of the original purchase, Warrantor will furnish without charge the required replacement part.
In addition, if the sealed motor-compressor fails because of a manufacturing defect within the second through fifth year from the date of original purchase, Warrantor will furnish without charge the required replacement compressor.
In addition, if theoptional, factory installed, stainless steel heat exchanger fails because of a manufacturing defect within ten years from the date of start-up, Warrantor will furnish without chargea replacement heat exchanger. Any local transportation, related service labor and diagnosis calls are not included.
44 RT-SVX38B-EN
Page 45
Page 46
Page 47
Page 48
The manufacturer optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the leader in creating and sustaining safe, comfortable and energy efficient environments,the manufacturer offers a broad portfolio of advanced controls and HVAC systems, comprehensive building services, and parts. For more information, visit www.IRCO.com.
The manufacturer has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.
© 2012Trane All rights reserved
RT-SVX38B-EN 10 Sep 2012
Supersedes RT-SVX38A-EN (01 Nov 2009)
We are committed to using environmentally
conscious print practices that reduce waste.
Loading...