Trane Installation, Operation And Maintenance Manual
Specifications and Main Features
Frequently Asked Questions
User Manual
Installation, Operation,
and Maintenance
Packaged Rooftop Air Conditioners
Precedent™ — Gas/Electric
5–10Tons–50Hz
Model Numbers
Only qualified personnel should install and service the equipment. The installation, starting up, and
servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific
knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could
result in death or serious injury.When working on the equipment, observe all precautions in the literature
and on the tags, stickers, and labels that are attached to the equipment.
September 2012RT-SVX38B-EN
YSC060ED - YSC120ED
SAFETY WARNING
Warnings, Cautions and Notices
Warnings, Cautions and Notices. Note that warnings,
cautions and notices appear at appropriate intervals
throughout this manual. Warnings are provide to alert
installing contractors to potential hazards that could result
in death or personal injury. Cautions are designed to alert
personnel to hazardous situations that could result in
personal injury, while notices indicate a situation that
could result in equipment or property-damage-only
accidents.
Your personal safety and the proper operation of this
machine depend upon the strict observance of these
precautions.
Read this manual thoroughly before operating or servicing
this unit.
ATTENTION: Warnings, Cautions and Notices appear at
appropriate sections throughout this literature. Read
these carefully:
WARNING
CAUTIONs
NOTICE:
Indicates a potentially hazardous
situation which, if not avoided, could
result in death or serious injury.
Indicates a potentially hazardous
situation which, if not avoided, could
result in minor or moderate injury. It
could also be used to alert against
unsafe practices.
Indicates a situationthat could result in
equipment or property-damage only
Important
Environmental Concerns!
Scientific research has shown that certain man-made
chemicals can affect the earth’s naturally occurring
stratospheric ozone layer when released to the
atmosphere. In particular, several of the identified
chemicals that may affect the ozone layer are refrigerants
that contain Chlorine, Fluorine and Carbon (CFCs) and
those containing Hydrogen, Chlorine, Fluorine and
Carbon (HCFCs). Not all refrigerants containing these
compounds have the same potential impact to the
environment.Trane advocates the responsible handling of
all refrigerants-including industry replacements for CFCs
such as HCFCs and HFCs.
Responsible Refrigerant Practices!
Trane believes that responsible refrigerant practices are
important to the environment, our customers, and the air
conditioning industry. All technicians who handle
refrigerants must be certified.The Federal Clean Air Act
(Section 608) sets forth the requirements for handling,
reclaiming, recovering and recycling of certain
refrigerants and the equipment that is used in these
service procedures. In addition, some states or
municipalities may have additional requirements that
must also be adhered to for responsible management of
refrigerants. Know the applicable laws and follow them.
WARNING
Proper Field Wiring and Grounding
Required!
All field wiring MUST be performed by qualified
personnel. Improperly installed and grounded field
wiring poses FIRE and ELECTROCUTION hazards. To
avoid these hazards, you MUST follow requirements for
field wiring installation and grounding as described in
NEC and your local/state electrical codes. Failure to
follow code could result in death or serious injury.
WARNING
Personal Protective Equipment (PPE)
Required!
Installing/servicing this unit could result in exposure to
electrical, mechanical and chemical hazards.
•Before installing/servicing this unit, technicians
MUST put on all Personal Protective Equipment (PPE)
recommended for the work being undertaken.
ALWAYS refer to appropriateMSDS sheets and OSHA
guidelines for proper PPE.
•When working with or around hazardous chemicals,
ALWAYS refer to the appropriate MSDS sheets and
OSHA guidelines for information on allowable
personal exposure levels, proper respiratory
protection and handling recommendations.
•If there is a risk of arc or flash, technicians MUST put
on all Personal Protective Equipment (PPE) in
accordance with NFPA 70E or other country-specific
requirements for arc flash protection, PRIOR to
servicing the unit.
Failure to follow recommendations could result in death
or serious injury.
A Unpowered Convenience Outlet
B Powered Convenience Outlet
(three-phase only)
9
Digit 21 - Communications
Sensor
30
DCV
3
30
Options
0No Communications Interface
1 Trane Communications Interface
2LonTalk® Communications Interface
3Novar 2024 Controls
4Novar 3051 Controls without Zone
5Novar 3051Controls Interface with
6BACnet™ Communications Interface
Digit 22 - Refrigeration System
Option
0Standard Refrigeration System
B Dehumidification Option
Digit 23 - Refrigeration Controls
Note: Applicable to Digit7=E,F
0No Refrigeration Control
1Frostat
2Crankcase Heater
3Frostat
11 ,29
11 ,29
2
and Crankcase Heater
Digit 24 - Smoke Detector
0No Smoke Detector
A Return Air Smoke Detector
B Supply Air Smoke Detector
C Supply and Return Air Smoke
Detectors
12,13
D Plenum Smoke Detector
Digit 25 - System Monitoring
Controls
0No Monitoring Control
1Clogged Filter Switch
2Fan Failure Switch
3Discharge Air Sensing Tube
4Clogged Filter Switch and Fan
Failure Switch
5Clogged Filter Switch and Discharge
Air SensingTube
6Fan Failure Switch and Discharge Air
SensingTube
7Clogged Filter Switch, Fan Failure
Switch and Discharge Air
SensingTube
8Novar Return Air Sensor
(NOVAR 2024)
9Novar ZoneTemp Sensor
(NOVAR 3051)
A Condensate Drain Pan Overflow
Switch
B Clogged Filter Switch14and
Condensate Drain Pan Overflow
Switch
C Fan Failure Switch14and Condensate
Drain Pan Overflow Switch
D Discharge Air Sensing14and
Condensate Drain Pan Overflow
Switch
14
14
14
14
14
15,30
19,30
30
10
22,23
5
17
12,13
14
14
14
2
4RT-SVX38B-EN
Model Number Description
14
E Clogged Filter Switch
Switch14and Condensate Drain Pan
Overflow Switch
FClogged Filter Switch14, Discharge
Air SensingTube14and Condensate
Drain Pan Overflow Switch
G Fan Failure Switch, Discharge Air
SensingTube14and Condensate
Drain Pan Overflow Switch
H Clogged Filter Switch14, Fan Failure
Switch14, Discharge Air Sensing
and Condensate Drain Pan Overflow
Switch
, Fan Failure
14
Digit 26 - System Monitoring
Controls
0No Monitoring Controls
A Demand Control Ventilation
31,32
(CO2)
Digit 27 - Unit Hardware
Enhancements
0No Enhancements
1Stainless Steel Drain Pan
Model Number Notes
1. Available on 3-5 ton models.
2. Standard on 4-5Ton E3,4,W and
6-10Ton Heat Pumps and all High
Efficiency models.
3. Not available with
electromechanical controls.
4. Manual outside air damper will
ship factory supplied within the
unit, but must be field installed.
5. High pressure controlis standard
on all units.
6. On 3-5 ton, multispeed direct
drive is standard on single phase
and 15 SEER. On 6-10 ton,
multispeed direct drive is
standard on all 10 ton and 7.5-8.5
ton high efficiency. Belt drive is
standard on all other units.
Digit 15 = 0
Standard Efficiency
1 Phase = High Efficiency Multispeed Direct
Drive Motor
3 Phase (3-8½ Ton) = Belt Drive
3 Phase (10 T on) = Ultra High Efficiency Direct
Drive Plenum Fan
High Efficiency
1 Phase = High Efficiency Multispeed Direct
Drive Motor
3 Phase (3-5 ton) = High Efficiency Multispeed
Direct Drive Motor
3 Phase (3-5 ton w/Dehumidification) = Belt
Drive Motor
3 Phase (7½-10 ton) = Ultra High Efficiency
Direct Drive Plenum Fan
7. Economizer with Barometric
Relief is for downflow configured
units only. Order Economizer
without Barometric Relief for
horizontal configuration.
Barometric Relief for horizontal
configured units must beordered
as field installed accessory.
8. Through the base electric
required when ordering
disconnect/circuit breaker
options.
9. Requires use of Disconnect or
Circuit Breaker.
Not Available
Standard Efficiency
10 Ton w/575V
High Efficiency
3-5 ton w/Standard Indoor Motor w/460V
10. Standard metering devices are
TXVs.
11. Frostat cannot be field installedin
electro-mechanical units.
12. The return air smoke detector
may not fitup or workproperly on
the Precedent units when used in
conjunction with 3rd party
accessories such as bolt on heat
wheels, economizers and power
exhaust. Do not order the return
air smoke detectors when using
this type of accessory.
13. Return Air Smoke Detector
cannot be ordered with Novar
Controls.
14. These options are standard when
ordering Novar Controls.
15. This option is used when
ordering Novar Controls.
16. Includes gas piping and shutoff
(field assembly required).
17. Not available with high
temperature duct sensor
accessory.
18. Digit 15 = 2
Standard Efficiency
1 Phase = Not Available
3 Phase = Not Available
High Efficiency
1 Phase = Not Available
3 Phase (3-5 ton) = May be Ordered
3 Phase (3-5 ton w/Dehumidification) = Not
Available
3 Phase (6-10 ton) = Not Available
19. Novar Sensor utilized with
Digit 21 = (4)Novar 3051 Controls
without Zone Sensor.
20. Available for 10 ton standard
efficiency models only.
21. Available for 3, 4, 5, 6, 7½, 8½ ton
standard/high efficiency models
only.
22. Requires selection of 2” Pleated
Filters (option B or C) for Digit 16.
23. Not available on 6 ton units and
all single phase or standard
efficiency.
24. Standard onYSC 6, 7½ (single
and dual systems), 8½, 10 ton
standard efficiency models and
YHC 4, 5, 6, 7½ ton highefficiency
models (except for
dehumidification models).
25. Epoxy coil and epoxy with
hailguard options are not
available for units with
microchannel condenser coil.
26. Single ZoneVAV is only available
on 7.5-10 ton high efficiency and
10 ton standard efficiency
products with ReliaTel™ controls.
27. Multi-speed indoor fan available
only on 7.5 & 8.5 ton high
efficiency, and 10 ton products
with ReliaTel™ controls.
28. Motorized Outside Air Damper is
not available on Multi-Speed or
SZVAV (Single Zone Variable Air
Volume) products.
29. Frostat standard on Multi-Speed
and SZVAV (Single ZoneVariable
Air Volume) products.
30. Novar is not available with SZVAV
products.
31. Demand Control Ventilation not
available with electromechanical
controls.
32. Demand Control Ventilation
Option includes wiring only.The
C0
sensor is afield-installed only
2
option.
RT-SVX38B-EN5
General Information
Unit Inspection
As soon as the unit arrives at the job site
•Verify that the nameplate data matches the data on the
sales order and bill of lading (including electrical data).
•Verify that the power supply complies with the unit
nameplate specifications.
•Visually inspect the exterior of the unit, including the
roof, for signs of shipping damage.
If the job site inspection of the unit reveals damage or
material shortages, file a claim with the carrier
immediately.Specify the typeand extent ofthe damage on
the “bill of lading” before signing.
•Visually inspect the internal components for shipping
damage as soon as possible after delivery and before
it is stored. Do not walk on the sheet metal base pans.
•If concealed damage is discovered, notify the carrier’s
terminal of damage immediately by phone and by
mail. Concealed damage must be reported within 15
days.
•Request an immediate joint inspection of the damage
by the carrier and the consignee. Do not remove
damaged material from the receiving location.Take
photos of the damage, if possible.The owner must
provide reasonable evidence that the damage did not
occur after delivery.
•Notify the appropriate sales representative before
installing or repairing a damaged unit.
Compressor Nameplate
The nameplate forthe compressors are located onthe side
of the compressor.
Unit Description
Before shipment, each unit is leak tested, dehydrated,
charged with refrigerant and compressor oil, and run
tested for proper control operation.
The condenser coilsare either aluminum fin, mechanically
bonded to copper tubing or all aluminum microchannel.
Direct-drive, vertical discharge condenser fans are
provided with built-in thermal overload protection.
There are two control systems offered for these units.The
electromechanical control option uses a thermostat to
perform unit functions.The ReliaTel™ Control Module is a
microelectronic control system that is referred to as
“Refrigeration Module” (RTRM). The acronym RTRM is
used extensively throughout this document when
referring to the control system network.
These modules through Proportional/Integral control
algorithms perform specific unit functions that governs
unit operation inresponse to; zone temperature, supply air
temperature, and/or humidity conditions depending on
the application.The stages of capacity control for these
units are achieved by starting and stopping the
compressors.
The RTRM is mounted in the control panel and is factory
wired to the respective internal components.The RTRM
receives and interprets information from other unit
modules, sensors, remote panels, and customer binary
contacts to satisfy the applicable request for cooling.
Storage
Take precautions to prevent condensate from forming
inside the unit’s electrical compartments and motors if:
1. The unit is stored before it is installed; or,
2. The unit is set on the roof curb, and temporary heat is
provided in the building. Isolate all side panel service
entrances and base pan openings (e.g., conduit holes,
Supply Air and Return Air openings, and flue
openings) from the ambient air until the unit is ready
for start-up.
Note: Do not use the unit’s heater for temporary heat
without first completing the start-up procedure
detailed under “Unit Start-Up,” p. 32.
The manufacturer will not assume any responsibility for
equipment damage resulting from condensate
accumulation on the unit’s electrical and/or mechanical
components.
Unit Nameplate
A Mylar unit nameplate is located on the unit’s corner
support next to the filter access panel. It includes the unit
model number, serial number, electrical characteristics,
refrigerant charge, as well as other pertinent unit data.
Economizer Control Actuator (Optional)
ReliaTel™ Control
The ECA monitors the mixed air temperature, return air
temperature, minimum position setpoint (local or
remote), power exhaust setpoint, CO
ambient dry bulb/enthalpy sensor or comparative
humidity (return air humidity against ambient humidity)
sensors, if selected, to control dampers to an accuracy of
+/- 5% of stroke.The actuator is spring returned to the
closed position any time that power is lost to the unit. It is
capable of delivering up to 25 inch pounds of torque and
is powered by 24 VAC.
RTCI - ReliaTel™ Trane Communication
Interface (Optional)
This module is used when the application calls for an
ICSTM building management type control system. It
allows the control and monitoring of the system through
an ICS panel.The module can be ordered from the factory
or ordered as a kit to be field installed. Follow the
installation instruction that ships with each kit when field
installation is necessary.
setpoint, CO2, and
2
6RT-SVX38B-EN
General Information
RLCI - ReliaTel™ LonTalk® Communication
Interface (Optional)
This module is used when the application calls for an
ICSTM building management type control system that is
LonTalk. Itallows the control and monitoringof the system
through an ICS panel.The module can be ordered from the
factory or ordered as a kit to be field installed. Follow the
installation instruction that ships with each kit when field
installation is necessary.
This module is used when the application calls for anopen
BACnet protocol. It allows the control and monitoring of
the system through an ICS panel.The module can be
ordered from the factory or as a kit to be field installed.
Follow the installation instructions that ships with each kit
when field installation is necessary.
RTOM - ReliaTel™ Options Module (Optional)
The RTOMmonitors the supply fan proving, cloggedfilter,
supply air temperature, exhaust fan setpoint, supply air
tempering, Frostat™ and smoke detector. Refer to system
input devices and functions for operation.
System Input Devices & Functions
The RTRM must have a zone sensor or thermostat input in
order to operate the unit.The flexibility of having several
mode capabilities dependsupon the type of zone sensor or
thermostat selected to interface with the RTRM.
The descriptions of the following basic InputDevices used
within the RTRM network are to acquaint the operator with
their function as they interface with the various modules.
Refer to the unit’s electrical schematic for the specific
module connections.
The following controls are available from the factory for
field installation.
Supply Fan Failure Input (Optional)
The Fan Failure Switch can be connected to sense indoor
fan operation:
FFS (Fan Failure Switch) If air flow through the unit is not
proven by the differential pressure switch connected to the
RTOM (factory set point 0.07 “w.c.) within 40 seconds
nominally, the RTRM will shut off all mechanical
operations, lock the system out, send a diagnostic to ICS,
and the SERVICE output will flash.The system will remain
locked out until a reset is initiated either manually or
through ICS.
Clogged Filter Switch (Optional)
The unit mounted clogged filter switch monitors the
pressure differential across the return air filters. It is
mounted in the filter section and is connected to the
RTOM. A diagnostic SERVICE signal is sent to the remote
panel if the pressure differential across the filters is at least
0.5" w.c.The contacts will automatically open when the
pressure differential across the filters decreases to
approximately 0.4" w.c.The clogged filter output is
energized when the supply fan is operating and the
clogged filter switch has been closedfor at least 2 minutes.
The system will continue to operate regardless of the
status of the filter switch.
Note: On units equipped with factory installed MERV 13
filters, a clogged filter switch with different
pressure settings will be installed. This switch will
close when the differential pressure is
approximately 0.8' w.c. and open when the
differential falls to 0.7" w.c.
Condensate Drain Pan Overflow Switch
(Optional)
ReliaTel Option
This input incorporates the Condensate Overflow Switch
(COF) mounted on the drain pan and the ReliaTel Options
Module (RTOM).When the condensate level reaches the
trip point for 6 continuous seconds, the RTOM will shut
down all unit functions until the overflow condition has
cleared.The unit will return to normal operation after 6
continuous seconds with the COF in a non-tripped
condition. If the condensate level causes unit shutdown
more than 2 times in a 3 days period, the unit will be
locked-out of operation requiring manual reset of
diagnostic system through Zone Sensor or Building
Automation System (BAS). Cycling unit power will also
clear the fault.
Compressor Disable (CPR1/2)
This input incorporates the low pressure control (LPC) of
each refrigeration circuit and can be activated by opening
a field supplied contact installed on the LTB.
If this circuit is open before the compressor is started, the
compressor will not be allowed to operate. Anytime this
circuit is opened for 1 continuous second during
compressor operation, the compressor for that circuit is
immediately turned “Off”. The compressor will not be
allowed to restart for a minimum of 3 minutes should the
contacts close.
If four consecutive open conditions occur during the first
three minutes of operation,the compressor for that circuit
will be locked out, a diagnostic communicated to the
remote panel (if installed), and a manual reset will be
required to restart the compressor.
Low Pressure Control
ReliaTel Control
When the LPC is opened for 1 continuous second, the
compressor for that circuit is turned off immediately.The
compressor will not be allowed to restart for a minimum
of 3 minutes.
If four consecutive open conditions occur during an active
call for cooling, the compressor will be locked out, a
diagnostic communicated to ICS™, if applicable, and a
RT-SVX38B-EN7
General Information
manual reset required to restart the compressor. On dual
compressor units only the affected compressor circuit is
locked out.
High Pressure Control
ReliaTel Control
The high pressure controls are wiredin series between the
compressor outputs on the RTRM and the compressor
contactor coils. If the high pressure control switch opens,
the RTRM senses a lack of current while calling for cooling
and locks the compressor out.
If four consecutive open conditions occur during an active
call for cooling, the compressor will be locked out, a
diagnostic communicated to ICS™, if applicable, and a
manual reset required to restart the compressor. On dual
compressor units only the affected compressor circuit is
locked out.
Lead/Lag Control (Dual Circuit Only)
ReliaTel Control Only
Lead/Lag is a selectable input located on the RTRM.The
RTRM is configured from the factory with the Lead/Lag
control disabled.To activate the Lead/Lag function, simply
cut the wire connected to J3-8 at the RTRM. When it is
activated, each time the designated lead compressor is
shut off due to the load being satisfied, the lead
compressor or refrigeration circuit switches. When the
RTRM is powered up, i.e. after a power failure, the control
will default to the number one circuit compressor.
Zone Sensor Module (ZSM) (BAYSENS106*)
This electronic sensor features three system switch
settings (Heat, Cool, and Off) and two fan settings (On and
Auto). It is a manual changeover control with single
setpoint. (Cooling Setpoint Only)
Zone Sensor Module (ZSM) (BAYSENS108*)
This electronic sensorfeatures four system switch settings
(Heat, Cool, Auto, and Off) and two fan settings (On and
Auto). It is a manual or auto changeover control with dual
setpoint capability. It can be used with a remote zone
temperature sensor BAYSENS077*.
Zone Sensor (BAYSENS110*)
This electronic sensorfeatures four system switch settings
(Heat, Cool, Auto, and Off) and two fan settings (On and
Auto) with four system status LED’s. It is a manual or auto
changeover control with dual setpoint capability. It can be
used with a remote zone temperature sensor
BAYSENS077*.
Programmable Zone Sensor - (BAYSENS119*)
This 7 day programmable sensor features 2, 3 or 4 periods
for Occupied or Unoccupied programming per day. If the
power is interrupted, the program is retained in
permanent memory. If power is off for an extended period
of time, only the clock and day may have to be reset.
The Zone Sensor allows selection of 2, 3 or 4 system
modes (Heat, Cool,Auto, and Off), two fan modes (On and
Auto). It has dual temperature selection with
programmable start time capability.
The occupied cooling set point ranges between 45 and 98
º F. The heating set point ranges between 43 and 96ºF.
A liquid crystal display (LCD) displays zone temperature,
temperature set points, day of the week, time, and
operational mode symbols.
The Option Menu is used to enable or disable applicable
functions, i.e.; Morning Warm-up, Economizer minimum
position override during unoccupied status, Fahrenheit or
Centigrade, Supply air tempering, Remote zone
temperature sensor, 12/24 hour time display, Smart fan,
and Computed recovery.
During an occupied period, an auxiliary relay ratedfor 1.25
amps @ 30 volts AC with one set of single pole double
throw contacts is activated.
Status Inputs (4 Wires Optional)
The ZSM can be wired to receive four (4) operating status
signals from the RTRM (HEAT, COOL, SYSTEM “ON”,
SERVICE).
Four (4) wires from the RTRM should be connected to the
appropriate terminals (7, 8,9&10)ontheZSM.
Remote Zone Sensor (BAYSENS073*)
This electronic sensor features remote zone sensing and
timed override with override cancellation. It is used with a
Trane Integrated Comfort™ building management
system.
Remote Zone Sensor (BAYSENS074*)
This electronic sensor features single setpoint capability
and timed override with override cancellation. It is used
with aTrane Integrated Comfort™ building management
system.
Remote Zone Sensor (BAYSENS016*)
This bullet type temperature sensor can be used for
outside air (ambient) sensing, return air temperature
sensing, supply air temperature sensing, remote
temperature sensing (uncovered). Wiring proceduresvary
according to the particular application and equipment
involved. Refer to the unit’s wiring diagrams for proper
connections.
Remote Zone Sensor (BAYSENS077*)
This electronic sensor can be used with BAYSENS106*,
108*, 110*, 119* Remote Panels.When this sensor is wired
to a BAYSENS119* Remote Panel, wiring must be 18 AWG
ShieldedTwisted Pair (Belden 8760 or equivalent). Refer to
the specific Remote Panel for wiring details.
Wireless Zone Sensor (BAYSENS050)
This electronic sensor features five system settings (Auto,
Off, Cool, Heat, and Emergency Heat) and with On and
8RT-SVX38B-EN
Auto fan settings. It is amanual or auto changeover control
with dual setpoint capability. Other features include a
timed override function, lockable system settings, and
Fahrenheit or Celsius temperature display. Included with
the wireless zone sensor will be a receiver that is to be
mounted inside the unit, a mounting bracket, and a wire
harness.
High Temperature Sensor (BAYFRST001*)
This sensor connects to the RTRM Emergency Stop Input
on the LTB andprovides high limit “shutdown” of the unit.
The sensor is used to detect high temperatures due to a
high thermal event in the air conditioning or ventilation
ducts.The sensor is designed to mount directly to the
sheet metal duct. Each kit contains two sensors.The return
air duct sensor (X1310004001) is set to open at 135ºF. The
supply air duct sensor (X1310004002) is set to open at
240ºF. The control can be reset after the temperature has
been lowered approximately 25ºF below the cutout
setpoint.
Evaporator Frost Control
ReliaTel™ Option
This input incorporates the Frostat™ control (FOS)
mounted in the indoor coil circuit and can be activated by
closing a field supplied contact installed in parallel with
the FOS.
If this circuit is open before the compressor is started, the
compressor will not be allowed to operate. Anytime this
circuit is opened for 1 continuous second during
compressor operation, the compressor for that circuit is
immediately turned “Off”. The compressor will not be
allowed to restart for a minimum of 3 minutes should the
FOS close.
General Information
Discharge LineTemp Switch (DLTS)
The DLTS is looped in series with HPC and LPC. It prevents
compressor from overheating (over 300 Fº dome temp) in
case of indoor fan failure (cooling) or outdoor fan failure
(heating).
Phase Monitor
This sensor monitors voltage between the 3 conductors of
the 3 phase power supply.Two LED lights are provided:
• The green light indicates that a balanced 3 phase
supply circuit is properly connected.
• The red light indicates that unit operation has been
prevented.There are two conditions that will prevent
unit operation:
• The power supply circuit is not balanced with the
proper phase sequence of L1, L2, L3 for the 3
conductors of a 3 phase circuit.
• The line to line voltage is not between 180 volts and
633 volts.
RT-SVX38B-EN9
Unit Dimensions
Figure 1 illustrates the minimum operating and service
clearances for either a single or multiple unit installation.
These clearances are the minimum distancesnecessary to
assure adequate serviceability, cataloged unit capacity,
and peak operating efficiency.
Figure 1.Typical installation clearances for single & multiple unit applications
Providing less than the recommended clearances may
result in condenser coil starvation, “short-circuiting” of
exhaust and economizer airflows, or recirculation of hot
condenser air.
YSC060ED
10RT-SVX38B-EN
YSC072-120ED
Figure 2.5 tons standard efficiency
44MMMM
44MMMM
1038MMMM
1053MMMM
Notes:
1. All dimensions are in inches/millimeters.
2. ½ NPT Gas Connection
Unit Dimensions
Figure 3.5 tons standard efficiency - roof curb
Note: All dimensions are in inches/millimeters.
44
44
7
1038
1053
RT-SVX38B-EN11
Unit Dimensions
Figure 4.5 tons standard efficiency - unit clearance and roof opening
Note: All dimensions are in inches/millimeters.
CLEARANCE 36” (914 MM)
Figure 5.6, 7½ tons standard efficiency
Note: All dimensions are in inches/millimeters.
12RT-SVX38B-EN
Figure 6.6, 7½ tons standard efficiency - roof curb
Note: All dimensions are in inches/millimeters.
Unit Dimensions
(356 MM)
Figure 7.6, 7½ tons standard efficiency - unit clearance and roof opening
Note: All dimensions are in inches/millimeters.
(2130 MM)
RT-SVX38B-EN13
Unit Dimensions
Figure 8.8½ - 10 tons standard efficiency
Note: All dimensions are in inches/millimeters.
1/2 NPT GAS CONNECTION
Figure 9.8½ - 10 tons standard efficiency - roof curb
Note: All dimensions are in inches/millimeters.
(356 MM)
(2130 MM)
14RT-SVX38B-EN
Figure 10. 8½ - 10 tons standard efficiency - unit clearance and roof opening
Note: All dimensions are in inches/millimeters.
Unit Dimensions
RT-SVX38B-EN15
Loading...
+ 33 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.