Note:
One copy of this document ships inside
the control panel of each unit and is
customer property. It must be retained
by the unit’s maintenance personnel.
This booklet describes proper installation, operation, and maintenance procedures for air cooled systems. By
carefully reviewing the information
within this manual and following the instructions, the risk of improper operation and/or component damage will be
minimized.
It is important that periodic maintenance be performed to help assure
trouble free operation. A maintenance
schedule is provided at the end of this
manual. Should equipment failure occur, contact a qualified service organization with qualified, experienced
HVAC technicians to properly diagnose
and repair this equipment.
Note:
Do Not release refrigerant to the
atmosphere! If adding or removing
refrigerant is required, the service
technician must comply with all federal,
state, and local laws.
Model Number Description
All products are identified by a multiplecharacter model number that precisely
identifies a particular type of unit. An
explanation of the alphanumeric identification code is provided below. Its use
will enable the owner/operator, installing contractors, and service engineers
to define the operation, specific components, and other options for any specific unit.
When ordering replacement parts or requesting service, be sure to refer to the
specific model number and serial number printed on the unit nameplate.
CAUTION
Equipment Damage From
Ultraviolet (UV) Lights!
The manufacturer does not recommend field installation of ultraviolet
lights in its equipment for the intended purpose of improving indoor
air quality. High intensity C-band
ultraviolet light is known to severely
damage polymer (plastic) materials
and poses a personal safety risk to
anyone exposed to the light without
proper personal protective equipment. Polymer materials commonly
found in HVAC equipment that may be
susceptible include insulation on
electrical wiring, fan belts, thermal
insulation, various fasteners and
bushings. Degradation of these
materials can result in serious
damage to the equipment.
The manufacturer accepts no
responsibility for the performance or
operation of our equipment in which
ultraviolet devices were installed
outside of the manufacturer’s factory
or its approved suppliers.
RT-SVX31A-EN
Page 3
Contents
Introduction
Literature Change History ................. 2
Overview of Manual .......................... 2
Model Number Description ............... 2
Unit Nomenclature ............................ 4
General Information
Unit Nameplate ................................. 5
Compressor Nameplate .................... 5
Unit Description................................. 5
0 = No Fresh Air
A = Manual OA, 0 - 25%
B = Motorized OA, 0 - 50%
C = Economizer Dry Bulb
D = Economizer with
Barometric Relief
E = Economizer, Reference Enthalpy
F = Economizer, Reference Enthalpy,
with Barometric Relief
G = Economizer Comparative Enthalpy
H = Economizer, Comparative Enthalpy,
with Barometric Relief
0 = Without Monitoring Controls
1 = Clogged Filter Switch
2 = Fan Failure Switch
3 = Discharge Air Sensing Tube
4 = Clogged Filter Switch and Fan
Failure Switch
5 = Clogged Filter Switch and
Discharge Air Sensing Tube
6 = Fan Failure Switch and
Discharge Air Sensing Tube
7 = Clogged Filter Switch, Fan Failure
Switch and
Discharge Air Sensing Tube
RT-SVX31A-EN4
Page 5
General Information
Unit Nameplate
A Mylar unit nameplate is located on
the unit’s corner support next to the filter access panel. It includes the unit
model number, serial number, electrical
characteristics, refrigerant charge, as
well as other pertinent unit data.
Compressor Nameplate
The nameplate for the compressors are
located on the side of the compressor.
Hazard Identification
Warnings are provided throughout
this manual to indicate to installing
contractors, operators, and service
personnel of potentially hazardous
situations which, if not avoided,
COULD result in death or serious injury.
Cautions are provided throughout
this manual to indicate to installing
contractors, operators, and service
personnel of potentially hazardous
situations which, if not avoided, MAY
result in minor or moderate injury.
Unit Description
Before shipment, each unit is leak
tested, dehydrated, charged with refrigerant and compressor oil, and run
tested for proper control operation.
The condenser coils are aluminum fin,
mechanically bonded to copper tubing.
Direct-drive, vertical discharge condenser fans are provided with built-in
thermal overload protection.
The ReliaTel™ Control Module is a microelectronic control system that is referred to as “Refrigeration Module”
(RTRM). The acronym RTRM is used
extensively throughout this document
when referring to the control system
network.
These modules through Proportional/Integral control algorithms perform specific unit functions that governs unit operation in response to; zone temperature, supply air temperature, and/or humidity conditions depending on the application. The stages of capacity control
for these units are achieved by starting
and stopping the compressors.
The RTRM is mounted in the control
panel and is factory wired to the respective internal components. The
RTRM receives and interprets information from other unit modules, sensors,
remote panels, and customer binary
contacts to satisfy the applicable request for cooling.
Economizer Control Actuator
(Optional)
ReliaTel™ Control
The ECA monitors the mixed air temperature, return air temperature, minimum position setpoint (local or remote),
power exhaust setpoint, CO2 setpoint,
CO2, and ambient dry bulb/enthalpy
sensor or comparative humidity (return
air humidity against ambient humidity)
sensors, if selected, to control dampers
to an accuracy of +/- 5% of stroke. The
actuator is spring returned to the closed
position any time that power is lost to
the unit. It is capable of delivering up to
25 inch pounds (2.82 N-m) of torque
and is powered by 24 VAC.
RTCI - ReliaTel™ Trane
Communication Interface
(Optional)
This module is used when the application calls for an ICS
ment type control system. It allows the
control and monitoring of the system
through an ICS panel. The module can
be ordered from the factory or ordered
as a kit to be field installed. Follow the
installation instruction that ships with
each kit when field installation is necessary.
TM
building manage-
RLCI - ReliaTel™ LonTalk
Communication Interface
(Optional)
This module is used when the application calls for an ICS
ment type control system that is
LonTalk. It allows the control and monitoring of the system through an ICS
panel. The module can be ordered from
the factory or ordered as a kit to be field
installed. Follow the installation instruction that ships with each kit when field
installation is necessary.
TM
building manage-
RTOM - ReliaTel™ Options
Module (Optional)
The RTOM monitors the supply fan
proving, clogged filter, supply air temperature, exhaust fan setpoint, supply
air tempering, Frostat™ and smoke detector. Refer to system input devices
and functions for operation.
5RT-SVX31A-EN
Page 6
General Information
System Input Devices &
Functions
The RTRM must have a zone sensor or
thermostat input in order to operate the
unit. The flexibility of having several
mode capabilities depends upon the
type of zone sensor or thermostat selected to interface with the RTRM.
The descriptions of the following basic
Input Devices used within the RTRM
network are to acquaint the operator
with their function as they interface with
the various modules. Refer to the unit’s
electrical schematic for the specific
module connections.
The following controls are available
from the factory for field installation.
Supply Fan Failure Input (Optional)
The Fan Failure Switch can be connected to sense indoor fan operation:
FFS (Fan Failure Switch) If air flow
through the unit is not proven by the differential pressure switch connected to
the RTOM (factory set point 0.07 “
w.c.(17.4 Pa)) within 40 seconds nominally, the RTRM will shut off all mechanical operations, lock the system
out, send a diagnostic to ICS, and the
SERVICE output will flash. The system
will remain locked out until a reset is initiated either manually or through ICS.
Clogged Filter Switch (Optional)
The unit mounted clogged filter switch
monitors the pressure differential
across the return air filters. It is
mounted in the filter section and is connected to the RTOM. A diagnostic SERVICE signal is sent to the remote panel
if the pressure differential across the filters is at least 0.5" w.c. (124.5 Pa). The
contacts will automatically open when
the pressure differential across the filters decreases to approximately 0.4"
w.c. (99.6 Pa). The clogged filter output
is energized when the supply fan is operating and the clogged filter switch has
been closed for at least 2 minutes. The
system will continue to operate regardless of the status of the filter switch.
Compressor Disable (CPR1/2)
This input incorporates the low pressure
control (LPC) of each refrigeration circuit
and can be activated by opening a field
supplied contact installed on the LTB.
If this circuit is open before the compressor is started, the compressor will
not be allowed to operate. Anytime
this circuit is opened for 1 continuous
second during compressor operation,
the compressor for that circuit is immediately turned “Off”. The compressor will not be allowed to restart for a
minimum of 3 minutes should the contacts close.
If four consecutive open conditions
occur during the first three minutes of
operation, the compressor for that circuit will be locked out, a diagnostic
communicated to the remote panel (if
installed), and a manual reset will be
required to restart the compressor.
Low Pressure Control
ReliaTel Control
When the LPC is opened for 1 continuous second, the compressor for
that circuit is turned off immediately.
The compressor will not be allowed to
restart for a minimum of 3 minutes.
If four consecutive open conditions
occur during the first three minutes of
operation, the compressor will be
locked out, a diagnostic communicated to ICS
manual reset will be required to restart
the compressor.
High Pressure Control (Optional)
ReliaTel Control
The high pressure controls are wired
in series between the compressor outputs on the RTRM and the compressor contactor coils. If the high pressure control switch opens, the RTRM
senses a lack of current while calling
for cooling and locks the compressor
out.
On dual circuit units, if the high pressure
control opens, the compressor on the
TM
if applicable, and a
affected circuit is locked out. A manual reset for the affected circuit is required.
ReliaTel Control
The power exhaust fan is started whenever the position of the economizer
dampers meets or exceed the power
exhaust setpoint when the indoor fan is
on.
The setpoint panel is located in the return air section and is factory set at
25%.
Lead/Lag Control (Dual Circuit Only)
ReliaTel Control Only
Lead/Lag is a selectable input located
on the RTRM. The RTRM is configured
from the factory with the Lead/Lag
control disabled. To activate the Lead/
Lag function, simply cut the wire
connected to J3-8 at the RTRM. When it
is activated, each time the designated
lead compressor is shut off due to the
load being satisfied, the lead compressor or refrigeration circuit switches.
When the RTRM is powered up, i.e.
after a power failure, the control will
default to the number one circuit
compressor.
Zone Sensor Module (ZSM)
(BAYSENS006B)
This electronic sensor features three
system switch settings (Heat, Cool, and
Off) and two fan settings (On
and Auto). It is a manual changeover
control with single setpoint. (Cooling
Setpoint Only)
Zone Sensor Module (ZSM)
(BAYSENS008B)
This electronic sensor features four
system switch settings (Heat, Cool,
Auto, and Off) and two fan settings (On
and Auto). It is a manual or auto
changeover control with dual setpoint
capability. It can be used with a remote
zone temperature sensor
BAYSENS017B.
RT-SVX31A-EN6
Page 7
General Information
Zone Sensor (BAYSENS010B)
This electronic sensor features four system switch settings (Heat, Cool, Auto,
and Off) and two fan settings (On and
Auto) with four system status LED’s. It is
a manual or auto changeover control with
dual setpoint capability. It can be used
with a remote zone temperature sensor
BAYSENS017B.
Programmable Zone Sensor (BAYSENS019B)
This 7 day programmable sensor features 2, 3 or 4 periods for Occupied or
Unoccupied programming per day. If
the power is interrupted, the program is
retained in permanent memory. If power
is off for an extended period of time,
only the clock and day may have to be
reset.
The Zone Sensor allows selection of 2,
3 or 4 system modes (Heat, Cool, Auto,
and Off), two fan modes (On and Auto).
It has dual temperature selection with
programmable start time capability.
The occupied cooling set point ranges
between 45 F (7.2 C)and 98 F (35.6 C)
degrees. The heating set point ranges
between 43 F (6.1 C) and 96 F ( 35.6
C) degrees.
A liquid crystal display (LCD) displays
zone temperature, temperature set
points, day of the week, time, and operational mode symbols.
The Option Menu is used to enable or
disable applicable functions, i.e.; Morning Warm-up, Economizer minimum position override during unoccupied status, Fahrenheit or Centigrade, Supply
air tempering, Remote zone temperature sensor, 12/24 hour time display,
Smart fan, and Computed recovery.
During an occupied period, an auxiliary
relay rated for 1.25 amps @ 30 volts
AC with one set of single pole double
throw contacts is activated.
Status Inputs (4 Wires Optional)
The ZSM can be wired to receive four
(4) operating status
signals from the RTRM (HEAT, COOL,
SYSTEM “ON”, SER-VICE).
Four (4) wires from the RTRM should be
connected to
the appropriate terminals (7, 8, 9 & 10)
on the ZSM.
Remote Zone Sensor
(BAYSENS013B)
This electronic sensor features remote
zone sensing and timed override with
override cancellation. It is used with a
Trane Integrated Comfort
management system.
TM
building
Remote Zone Sensor
(BAYSENS014B)
This electronic sensor features single
setpoint capability and timed override
with override cancellation. It is used
with a Trane Integrated ComfortTM building management system.
Remote Zone Sensor
(BAYSENS016A)
This bullet type temperature sensor can
be used for; outside air (ambient) sensing, return air temperature sensing,
supply air temperature sensing, remote
temperature sensing (uncovered. Wiring procedures vary according to the
particular application and equipment involved. Refer to the unit’s wiring diagrams for proper connections.
Remote Zone Sensor
(BAYSENS017B)
This electronic sensor can be used with
BAYSENS006B, 008B, 010B, 019B Remote Panels. When this sensor is wired
to a BAYSENS019B Remote Panel,
wiring must be 18 AWG (.75mm
Shielded Twisted Pair (Belden 8760 or
2
)
equivalent). Refer to The specific Remote Panel for wiring details.
BAYSTAT036A
Single Stage - 1 Heat/1 Cool
BAYSTAT037A
Multi Stage - 2 Heat/2 Cool - Can be
Used for Economizer Operation
BAYSENS025A
Remote sensor for BAYSTAT036A and
BAYSTAT037A
Phase Monitor (Optional)
ReliaTel Control Only
This sensor monitors voltage between
the 3 conductors of the 3 phase power
supply. Two LED lights are provided.
The green light indicates that a balanced 3 phase supply circuit is properly connected. The red light indicates
that unit operation has been prevented. There are two conditions that
will prevent unit operation.The power
supply circuit is not balanced with the
proper phase sequence of L1,L2,L3 for
the 3 conductors of a 3 phase circuit.
The line to line voltage is not between
180 volts and 633 volts.
Unit Inspection
7RT-SVX31A-EN
Page 8
General Information
As soon as the unit arrives at the job
site
[ ] Verify that the nameplate data
matches the data on the sales order
and bill of lading (including electrical
data).
[ ] Verify that the power supply complies
with the unit nameplate specifications.
[ ] Visually inspect the exterior of the
unit, including the roof, for signs of
shipping damage.
If the job site inspection of the unit reveals damage or material shortages,
file a claim with the carrier immediately.
Specify the type and extent of the damage on the “bill of lading” before signing.
[ ] Visually inspect the internal compo-
nents for shipping damage as soon
as possible after delivery and before
it is stored. Do
metal base pans.
not walk on the sheet
Take precautions to prevent condensate from forming inside the unit’s
electrical compartments and motors if:
a. the unit is stored before it is in-
stalled; or,
b. the unit is set on the roof curb, and
temporary heat is provided in the
building. Isolate all side panel service entrances and base pan openings (e.g., conduit holes, S/A and R/
A openings, and flue openings) from
the ambient air until the unit is
ready for start-up.
Note:
Do not use the unit’s heater for
temporary heat without first completing
the start-up procedure detailed under
“Starting the Unit”.
The manufacturer will not assume any
responsibility for equipment damage
resulting from condensate accumulation on the unit’s electrical and/or mechanical components.
Unit Clearances
Figure 1 illustrates the minimum operating and service clearances for either a single or multiple unit installation. These clearances are the minimum distances necessary to assure
adequate serviceability, cataloged
unit capacity, and peak operating efficiency.
Providing less than the recommended clearances may result in
condenser coil starvation, “short-circuiting” of exhaust and economizer
airflows, or recirculation of hot condenser air.
[ ] If concealed damage is discovered,
notify the carrier’s terminal of damage immediately by phone and by
mail. Concealed damage must be reported within 15 days.
Request an immediate joint inspection of the damage by the carrier and
the consignee. Do not remove damaged material from the receiving location. Take photos of the damage, if
possible. The owner must provide
reasonable evidence that the damage did not occur after delivery.
[ ] Notify the appropriate sales repre-
sentative before installing or repairing a damaged unit.
Storage
RT-SVX31A-EN8
Page 9
Pre - Installation
Figure 1
Typical Installation Clearances for Single & Multiple Unit Applications
Economizer2636Economizer1216
Barometric Relief710Barometric Relief35
Motorized Outside Air Damper2030Motorized Outside Air Damper914
Manual Outside Air Damper1626Manual Outside Air Damper712
Roof Curb70115Roof Curb3252
Oversized Motor58Oversized Motor24
Coil Guards1220Coil Guards59
Hinged Doors1012Hinged Doors55
NOTES:
(1) Net weight should be added to unit weight when ordering factory-installed accessories.
1
Net Weights (kg)
Figure 3
LIFTING AND MOVING INSTRUCTIONS!
DO NOT USE CABLES (CHAINS OR SLINGS) EXCEPT AS SHOWN. OTHER LIFTING ARRANGEMENTS MAY CAUSE EQUIPMENT DAMAGE OR SERIOUS PERSONAL INJURY.
EACH OF THE CABLES (CHAINS OR SLINGS) USED
TO LIFT UNIT MUST BE CAPABLE OF SUPPORTING
THE ENTIRE WEIGHT OF THE UNIT.
LIFTING CHAINS (CABLES OR SLINGS) MAY NOT
BE THE SAME LENGTH. ADJUST AS NECESSARY
FOR EVEN LEVEL LIFT.
Rigging and Center-of-Gravity Data
1
USE SPREADER BARS AS SHOWN IN DIAGRAM. REFER TO TABLE 1 FOR UNIT WEIGHT.
RT-SVX31A-EN12
Page 13
Installation
Foundation
Horizontal Units
If the unit is installed at ground level, elevate it above the snow line. Provide
concrete footings at each support location with a “full perimeter” support structure or a slab foundation for support. Refer to Table 1 for the unit’s operating
and point loading weights when constructing a footing foundation.
If anchoring is required, anchor the unit to the slab using hold down bolts or isolators. Isolators should be installed to minimize the transmission of vibrations
into the building.
For rooftop applications, ensure the roof is strong enough to support the combined unit and support structural weight. Refer to Table 1 for the unit operating
weights. If anchoring is required, anchor the unit to the roof with hold-down bolts
or isolators.
Check with a roofing contractor for proper waterproofing procedures.
13RT-SVX31A-EN
Page 14
Installation
Figure 4-1
YSC060AD
Horizontal Unit Supply & Return Air Opening
YSC072AD - 120AD
Horizontal Unit Supply & Return Air Opening
Figure 4-1
YSC060AD
Downflow Unit Supply & Return Air Openings
YSC072AD - 120AD
Downflow Unit Supply & Return Air Openings
Supply
Return
RT-SVX31A-EN14
Page 15
Installation
Ductwork
Figure 4-1 illustrates the supply and return air openings as viewed from the
rear of the unit.
Elbows with turning vanes or splitters
are recommended to minimize air noise
due to turbulence and to reduce static
pressure.
When attaching the ductwork to the
unit, provide a water tight flexible connector at the unit to prevent operating
sounds from transmitting through the
ductwork.
All outdoor ductwork between the unit
and the structure should be weather
proofed after installation is completed.
Roof Curb
Note:
All Gas/Electric units shall be installed
on a roof curb that is a minimum height
of 5.0 inches ( 127 mm ), or in any other
manner such that the distance between
the bottom of the intake vents of the gas
section and grade of the surface that the
unit is installed on is no less than 19.7
inches ( 500 mm ).
Downflow
The roof curbs for these units consists
of a “full perimeter” enclosure to support the unit.
Before installing any roof curb, verify;
1. That it is the correct curb for the unit,
2. That it includes the necessary gaskets and hardware,
3. That the purposed installation location provides the required clearance
for proper operation.
4. Insure that the curb is level and
square. The top surface of the curb
must be true to assure an adequate
curb-to-unit seal.
Step-by-step curb assembly and installation instructions ship with each accessory roof curb kit. Follow the instructions carefully to assure proper fit-up
when the unit is set into place.
Note:
To assure proper condensate flow
during operation, the unit (and curb)
must be level.
If the unit is elevated, a field constructed catwalk around the unit is
strongly recommended to provide easy
access for unit maintenance and service.
Recommendations for installing the
Supply Air and Return Air ductwork joining the roof curb are included in the
curb instruction booklet. Curb ductwork
must be fabricated and installed by the
installing contractor before the unit is
set into place.
Note:
For sound consideration, cut only the
holes in the roof deck for the ductwork
penetrations. Do not cut out the entire
roof deck within the curb perimeter.
If a Curb Accessory Kit is not used:
a. The ductwork can be attached
directly to the factory-provided
flanges around the unit’s supply
and return air openings. Be sure
to use flexible duct connections
at the unit.
b. For “built-up” curbs supplied by
others, gaskets must be installed
around the curb perimeter flange
and the supply and return air
opening flanges.
15RT-SVX31A-EN
Page 16
Installation
Rigging
A Rigging illustration and Center-ofGravity dimensional data table is shown
in Figure 3. Refer to the typical unit operating weights table before proceeding.
1. The wooden top is secured to the
unit by a plastic strap. The plastic
strap is secured to the right front corner post of the unit with one screw.
Remove this screw to release the
strap. Remove the wooden top and
plastic strap. Replace the screw in
the right front corner post.
2. Remove protective covering from
around the unit.
DO NOT USE CABLES (CHAINS OR
SLINGS) EXCEPT AS SHOWN. OTHER
LIFTING ARRANGEMENTS MAY CAUSE
EQUIPMENT DAMAGE OR SERIOUS
PERSONAL INJURY.
EACH OF THE CABLES (CHAINS OR
SLINGS) USED TO LIFT UNIT MUST BE
CAPABLE OF SUPPORTING THE ENTIRE
WEIGHT OF THE UNIT.
LIFTING CHAINS (CABLES OR SLINGS)
MAY NOT BE THE SAME LENGTH. ADJUST AS NECESSARY FOR EVEN LEVEL
LIFT.
3. Rig the unit as shown in Figure 3. Attach adequate strength lifting slings
to all four lifting brackets in the unit
base rail. Do not use cables, chains,
or slings except as shown.
4. Install a lifting bar, as shown in Figure 3, to protect the unit and to facilitate a uniform lift. The minimum
disbetween the lifting hook and the
top of the unit should be 7 feet
(21m).
5. Test-lift the unit to ensure it is properly rigged and balanced, make any
necessary rigging adjustments.
6. Lift the unit enough to allow the removal of two Fork Lift brackets and
hardware. Remove the two Fork Lift
brackets, two metal runners and
three wooden boards as shown.
7. Downflow units; align the base rail of
the unit with the curb rail while lowering the unit onto the curb. Make sure
that the gasket on the curb is not
damaged while positioning the unit.
General Unit Requirements
Note:
Before installation check that local
distribution conditions, nature of gas
and pressure. and the current state
adjustment of the appliance are
compatible.
The checklist listed below is a summary
of the steps required to successfully install a commercial unit. This checklist is
intended to acquaint the installing personnel with what is required in the installation process. It does not replace
the detailed instructions called out in
the applicable sections of this manual.
[ ] Check the unit for shipping damage
and material shortage; file a freight
claim and notify appropriate sales
representative.
[ ] Verfiy correct model, options and
voltage from unit nameplate.
[ ] Verify that the installation location of
the unit will provide the required
clearance for proper operation.
[ ] Assemble and install the roof curb (if
applicable). Refer to the latest edition of the curb installers guide that
ships with each curb kit.
[ ] Fabricate and install ductwork; se-
cure ductwork to curb.
[ ] Install pitch pocket for power supply
through building roof. (If applicable)
[ ] Rigging the unit.
[ ] Set the unit onto the curb; check for
levelness.
[ ] Ensure unit-to-curb seal is tight and
without buckles or cracks.
[ ] Install and connect a condensate
drain line to the evaporator drain
connection.
Factory Installed Economizer
[ ] Ensure the economizer has been
pulled out into the operating position.
Refer to the economizer installers
guide for proper position and setup.
[ ] Install all access panels.
RT-SVX31A-EN16
Page 17
Installation
pping
Temperature Limit Switch Usage for
Gas Heat Units
Units are factory shipped in the
downflow discharge confriguration but
can be field converted to a horizontal
discharge confriguration. Some, but not
all units require a different TC01 limit
switch, which is attached to the combustion blower motor if horizontal discharge confriguration is used.
Note:
The following units require a limit switch
change out for horizontal discharge. The
additional limit switch is shipped
attached to the blower housing. Refer to
the Horizontal Discharge Conversion,
Step 5 for the following models "ONLY"
YSC060A**H, YSC072A**H, YSC090**H,
YSC102A**H, YSC120A**H.
If any of the above units are installed in
the downflow discharge configuration,
remove the additional TC01 limit switch
from the combustion blower motor and
discard.
Unit Model
TCO1 Tri
Downflow / Horizontal
Values
YSC060 A **H 170F / 200F 77C / 93C
YSC072 A **H 180F / 220F 82C / 104C
YSC090 A **H 180F / 220F 82C / 104C
YSC102 A **H 190F / 260F 88C / 127C
YSC120 A **H 190F / 260F 88C / 127C
Gas Heat Technical Data
GENERAL DATA
HEAT E R S IZEG80G120G120G200G150G250
INP UT (M BH)(K W)(67)( 19 .6)(100)(29.3)(100)(29. 3)(167)( 48.9)(125)(36.7)(208)(60.9)
HI LI M IT TRIP T E M P ( Down F low / Horz )
HI LI M IT TRIP T E M P ( Down F low / Horz )
NO. OF INJECTORS233435
INLE T P IPE SIZE ( NP T) 1/2 1/2 1/2 1/2 1/2 1/2
Gas G20
INPUT m
INLE T P RE S S URE S ( MIN, NO M ,MAX ) m bar17|20| 2517|20| 2517|20| 2517|20| 2517|20|2617|20| 25
MANIFOLD PRESSURE ( m b ar )3.0" w. c .(7.5) 3.0" w.c.(7.5 )3.0" w.c.(7. 5)3.0" w.c .(7.5)3.0" w.c .(7.5) 3.0" w. c .(7.5)
INJ ECTO R SIZ E (DRILL)( m m )(33)( 2.87)(33) (2.87)(33)( 2.87)(1/8") ( 3.175)(1/ 8")(3.175) ( 1/8") ( 3.175)
Gas G25
INPUT m
INLE T P RE S S URE S ( MIN, NO M ,MAX ) m bar20|25| 3020|25| 3020|25| 3020|25| 3020|25|3120|25| 30
MANI FO LD PRE S S URE (m bar )4.2" w. c .(10.5) 4.2" w. c . ( 10.5) 4.2" w. c .(10. 5) 4.2" w.c. ( 10.5) 4.2" w. c . (10.5)4.2" w.c. ( 10. 5 )
INJ ECTO R SIZ E (DRILL)( m m )(33)( 2.87)(33) (2.87)(33)( 2.87)(1/8") ( 3.175)(1/ 8")(3.175) ( 1/8") ( 3.175)
Gas G31
INPUT m
INLE T P RE S S URE S ( MIN, NO M ,MAX ) m bar25|37| 4525|37| 4525|37| 4525|37| 4525|37|4625|37| 45
MANIFOLD PRE S SURE ( mb ar )10"w.c.(24. 9) 10"w.c .(24.9)10"w.c.(24.9)10"w.c.(24. 9) 10"w.c .(24.9) 10"w.c.(24.9)
INJ ECTO R SIZ E (DRILL)( m m )51(1.70)51(1.70)51(1.70 )51(1.7 0)51(1.70)5 1(1.70)
MODEL #YSC060**LYSC060**H
o
F170170/200200180/220200190/260
o
C7777/939382/939388/126
3
/ h 1.92.82.84.73.55.9
3
/ h 2.23.33.35.54.16.9
3
/ h 1.42.12.13.52.64.4
YSC072**L
YSC090**L
YSC072**H
YSC090**H
YSC102**L
YSC120**L
YSC102**H
YSC120**H
17RT-SVX31A-EN
Page 18
Installation
Horizontal Discharge Conversion
YSC060
Supplies Needed by Installer for Conversion: 3 oz. tube of
High Temperature RTV sealant. ( 500°F / 260°C : Similar to
Dow Corning 736 )
Note: Failure to use recommended sealant could result in unit
performance loss.
If a unit is to be converted to a Horizontal discharge, the following conversion must be performed:
1. Remove RETURN and SUPPLY duct covers.
2. Locate supply cover. Apply ¼ in. (6mm.) continuous bead
of 500°F RTV sealant to the flange as shown.
RTV Sealant
Note: Certain unit/electric heater combinations require a
limit switch change out for horizontal airflow applications.
Refer to the following instructions to determine if this
process is required for the unit undergoing installation.
6. After completing installation of the duct covers for
horizontal discharge, proceed to TCO-1 instructions.
3. Position duct cover as shown, rotate 90 degrees to allow
entrance into supply opening.
4. Slide duct covers into duct openings until inward edge of
duct cover engages with the 2 retaining clips on the duct
flanges. Secure the outward edge of each duct cover with 2
screws.
5. Slide RETURN DUCT COVER (insulation side up) into
supply opening until inward edge of duct cover engages
with the 2 retaining clips on the duct flange. Secure outward
edge of the duct cover with two screws.
Supply duct cover with
RTV installed
RT-SVX31A-EN18
Page 19
Installation
Horizontal Discharge Conversion
YSC072 - 120
Supplies Needed by Installer for Conversion: 3 oz. tube of
high Temperature RTV sealant. ( 500°F / 260°C : Similar to
Dow Corning 736 )
Note: Failure to use recommended sealant could result in unit
performance loss.
If a unit is to be converted to a Horizontal discharge, the following conversion must be performed:
1. Remove RETURN and SUPPLY duct covers.
2. Place SUPPLY DUCT COVER over down-flow return
opening. (Insulation side down)
3. Using self-drilling screws, (or screws removed from duct
cover), screw through dimples to attach duct cover to base.
Supply Duct Cover
Note: The following units require a limit switch change
out. The additional limit switch is shipped attached to
the blower housing for these models. Proceed to Step
5 for the following models "ONLY". YSC060A**H,
YSC072A**H, YSC090A**H, YSC102A**H,
YSC120A**H.
5. After completing installation of the duct covers for horizontal discharge, proceed to TCO-1 instructions.
TCO1 Instructions:
If the unit being installed is listed in the following table the
limit control TCO1 must be replaced with the extra limit control shipped in the heater compartment. Replace TCO1 following the instructions in steps 1through 4 below. If the unit
being installed does not correspond to any in the following
table, skip steps1 through 4 and go on to next step in the installation process.
Unit Model Number
Y*C036A* *H, Y * C048A** H, Y *C060A **H, YHC060A**M
Y*C072A* *H, Y SC090A**M , Y* C092A** M, Y HC092A**H,
Y*C102A* *M , Y*C102A** H, Y *C120A **M , Y *C120A* *H.
1. Remove the heat section access panel.
2. Remove TC01 from shipping location, attached to the
combustion blower.
Screw into 4
dimples on top
edge
4. On original RETURN DUCT COVER, apply ¼” (6mm.)
continuous bead of 500°F RTV sealant around flange (opposite insulation side), as shown.
RTV Sealant
5. Slide RETURN DUCT COVER (insulation side up) into
supply opening until inward edge of duct cover engages
with the 2 retaining clips on the duct flange. Secure outward
edge of the duct cover with two screws.
Note: If Unit is equipped with Return Air Smoke Detector, refer
to field conversion instructions for horizontal discharge before
installing return air duct.
3. Replace and discard the existing TC01 originally installed
at the factory for downflow operation with the TC01
shipped attached to the combustion blower for horizontal
operation.
4. Replace heat section access panel.
19RT-SVX31A-EN
Page 20
Installation
Through the Base Gas Installation
To convert the unit to through the base gas, complete the
following procedure. The gas supply line must extend 120
mm (4-5/8 in) above the base-pan. The parts listed in the
procedure are all field-supplied, and need to be purchased
separately in order to make this conversion. All joints in the
assembly should be made using a pipe sealant approved
for gas applications.
Note:
All field-installed gas piping must comply with
applicable state and local codes.
1. Remove the insulation and metal plug from the through
the base gas penetration. Route the gas supply pipe so
that it extends 120 mm (4-5/8 in) above the base pan.
2. Remove the plastic plug from the upper hole in the center
post. Insert a grommet (similar to the one located at the
bottom of the center post) in place of the plastic plug.
3. Using pipe sealant attach a 90° street elbow to the outlet
side of the gas shut-off valve and a 165 mm (6-1/2 inch)
pipe nipple to the inlet side.
4. Using pipe sealant, attach a 90° elbow to the gas supply
line that has been routed through the base.
12. Using pipe sealant, assemble the two measured
nipples, 90° elbow, and the other side of the union.
13.Using pipe sealant, attach the assembly from step 12 to
the 90° street elbow on the gas shut-off valve, and tighten
the union.
5. Install 2 grommets in the pipe access holes in the center
post.
6. Install the gas shut-off valve/nipple assembly through the
upper grommet in the center post.
7. Using pipe sealant, attach the 165 mm (6-1/2 in) pipe
nipple, from the assembly completed in step 3, to the 90
elbow on the gas supply line.
8. Attach one side of a union, using pipe sealant, to a 125
mm (5 in) pipe nipple.
9. Install the union/nipple assembly through the lower grommet in the center post.
10. Using pipe sealant, attach the 125 mm (5 in) pipe nipple
assembly from step 8 to the 90° elbow on the gas valve located inside the unit.
11. To assemble the remainder of the gas piping, two more
nipples and a 90° elbow will be needed. The lengths of
the two nipples will vary depending on the unit and installation. Measure the two lengths of pipe that will be needed
to connect the union to the 90° street elbow on the gas
shut-off valve using a 90° elbow. The lengths of pipe will
be approximately 70 mm (2-3/4 in).
RT-SVX31A-EN20
Page 21
Installation
Main Electrical Power Requirements
[ ] Verify that the power supply complies
with the unit nameplate specifications.
[ ] Inspect all control panel components;
tighten any loose connections.
[ ] Connect properly sized and pro-
tected power supply wiring to a fieldsupplied/installed disconnect switch
and to the main power terminal block
(HTB1) in the unit control panel.
[ ] Install proper grounding wires to an
earth ground.
Note:
All field-installed wiring must comply
with applicable State and Local codes.
Requirements for Gas Heat
[ ] Gas supply line properly sized and
connected to the unitgas train.
[ ] All gas piping joints properly sealed.
[ ] Drip leg Installed in the gas piping
near the unit.
[ ] Gas piping leak checked with a soap
solution. If piping connections to the
unit are complete, do not pressurize
piping in excess of 0.50 psig or 14 "
W.C. (3.5 kPa) to prevent compo-
nent failure.
[ ] Minimum gas supply pressure should
be 4.5" W.C. (1.1 kPa).
[ ] Maximum gas supply pressure must
not exceed 14.0" W.C.(3.5 kPa).
Condensate Drain Configuration
An evaporator condensate drain connection is provided on each unit. Refer
to Figure 4-1 for the appropriate drain
location.
The condensate drain pan is factory installed to drain condensate to the back
side of the unit. See Figure 4-1. It can
be converted to drain condensate out
the front side of the unit or through the
base.
To convert drain condensate out the
front of unit:
1. Remove evaporator access panel
and supply air access panels.
2. Remove the support panel that the
condensate drain pan exits through.
3. Slide the condensate drain pan out of
the unit and rotate 180°.
4. Slide the condensate drain pan back
into the unit, align the drain with the
grommeted opening in the rear support panel and push until the coupling is seated in the grommet.
5. Replace the front support panel by
aligning the panel with tabs in the
raceway. Align the condensate drain
pan support in the grommeted hole
as the panel is put in place.
6. Replace evaporator access panel
and supply air access panels.
To convert drain condensate through
the base of unit:
1. Remove evaporator access panel
and supply air access panels.
6. Plug the original condensate drain
opening with a field supplied 3/4"
NPT plug.
7. Slide the condensate drain pan back
into the unit, align the drain support
with the grommeted opening in the
rear support panel and push until the
support is seated in the grommet.
8. Replace the front support panel by
aligning the panel with tabs in the
raceway. Align the plugged condensate drain pan coupling in the
grommeted hole as the panel is put
in place.
9. Replace evaporator access panel
and supply air access panels.
A condensate trap must be installed at
the unit due to the drain connection being on the “negative pressure” side of
the fan. Install the P-Trap using the
guidelines in Figure 5.
A condensate drain line must be connected to the P-Trap. Pitch the drain
lines at least 1/2 inch (13 mm) for every
10 feet (3.0 m) of horizontal run to assure proper condensate flow. Do not allow the horizontal run to sag causing a
possible double-trap condition which
could result in condensate backup due
to “air lock”.
Figure 5
Condensate Trap Installation
[ ] Manifold pressure for single stage
heaters should be set to 3.3" W.C.
(.8 kPa).
[ ] Manifold pressure for two stage heat-
ers should be set to 3.5" W.C. (.9
kPa) on HIGH FIRE. The low fire setting is not field adjustable.
[ ] Flue Exhaust clear of any obstruc-
tion.
2. Remove the support panel that the
condensate drain pan exits through.
3. Slide the condensate drain pan out
of the unit.
4. Place on a level surface in the position it was removed from the unit.
5. Remove the plug knockout in the
bottom of the drainpan to convert it
to through the base drainage.
21RT-SVX31A-EN
Page 22
Installation
Filter Installation
YSC060AD unit ships with one inch (25
mm) filters. The quantity of filters is determined by unit size. Access to the filters is obtained by removing the indoor
fan access panel. To modify the unit’s
filter rack to accept two inch (50 mm)
filters, remove the L-shaped angle attachment screws and rotate the angles
90 degrees.
Reinstall the screws and insert new filters. Refer to the unit Service Facts
(shipped with each unit) for filter requirements.
Note:
Do not operate the unit without filters.
Field Installed Power Wiring
An overall dimensional layout for the
field installed wiring entrance into the
unit is illustrated in Figure 2. To insure
that the unit’s supply power wiring is
properly sized and installed, follow the
guidelines outline d below.
Note:
All field installed wiring must conform to
State and Local codes.
Verify that the power supply available is
compatible with the unit’s nameplate
ratings. The available supply power
must be within 10% of the rated voltage
stamped on the nameplate. Use only
copper conductors to connect the
power supply to the unit.
USE COPPER CONDUCTORS ONL Y!
UNIT TERMINALS ARE NOT DESIGNED TO ACCEPT OTHER TYPES
OF CONDUCTORS.
Failure to do so may cause damage
to the equipment.
Main Unit Power Wiring
1. The unit is
tional factory installed nonfused disconnect switch or circuit breaker. A
field supplied disconnect switch must
be installed at or near the unit in accordance with the State and Local
codes.
2. Location of the applicable electrical
service entrance is illustrated in Figure 2. Complete the unit’s power wiring connections onto either; the main
terminal wire connectors inside the
unit control panel, the field supplied
nonfused disconnect switch (UCD)
or circuit breaker (UCB). Refer to the
customer connection diagram that is
shipped with the unit for specific termination points.
3. Provide proper grounding for the unit
in accordance with local and national
codes.
Field Installed Control Wiring
An overall layout of the various control
options available with the required
number of conductors for each control
device is illustrated in Figure 6.
not equipped with an op-
Note:
All field wiring must conform to state
and local codes.
Control Power Transformer
The 24 volt control power transformers
are to be used only with the accessories called out in this manual. Transformers rated greater than 50 VA are
equipped with internal circuit breakers.
If a circuit breaker trips, turn “Off” all
power to the unit before attempting to
reset it.
The transformer is located in the control panel. The circuit breaker is located on the left side of the transformer and can be reset by pressing in
on the black reset button.
Controls using 24 VAC
Before installing any connecting wiring,
refer to Figure 2-1 for the electrical access locations provided on the unit and
Table 2 for AC conductor sizing guidelines, and;
a. Use copper conductors unless other-
wise specified.
b. Ensure that the AC control wiring be-
tween the controls and the unit’s
termination point does not exceed
three (3) ohms/conductor for the
length of the run.
Note: Resistance in excess of 3 ohms
per conductor may cause component
failure due to insufficient AC voltage
supply.
c. Be sure to check all loads and con-
ductors for grounds, shorts, and miswiring.
d. Do not run the AC low voltage wiring
in the same conduit with the high
voltage power wiring.
e. Route low voltage wiring per illustra-
tions on page 24.
HAZARDOUS VOLT AGE
DISCONNECT ALL ELECTRIC
POWER INCLUDING REMOTE DISCONNECTS BEFORE SERVICING.
Failure to disconnect power before
servicing can cause severe personal
injury or death.
RT-SVX31A-EN22
Page 23
t
Area
m
Installation
Table 2A
24V AC Conductors with Reliatel
Distance from UnitRecommended
to ControlWire Size
000 - 460 feet18 gauge
000 - 140 m.75 mm
2
461 - 732 feet16 gauge
141 - 223 m1.3 mm
2
733 - 10 00 feet14 gauge
224 - 305 m2.0 mm
2
Controls using DC Analog Input/
Outputs
(Standard Low Voltage
Multiconductor Wire)
Before installing any connecting wiring
between the unit and components utilizing a DC analog input\output signal, refer to Figure 2 for the electrical access
locations provided on the unit.
a. Table 3 lists the conductor sizing
guidelines that must be followed
when interconnecting the DC binary
output devices and the system components utilizing a DC analog
input\output signal to the unit.
DC Conductors
Table 3
Distance fro
Unit to Control
Fee
0 - 1500 - 4622 gauge0.33 mm
151 - 24047 - 7320 gauge0.50 mm
241 - 38574 - 11718 gauge0.75 mm
386 - 610118 - 18516 gauge1.30 mm
611 - 970186 - 29614 gauge2.00 mm
Met er s
Rec ommended
Wir e Si ze
2
2
2
2
2
Note:
Resistance in excess of 2.5 ohms per
conductor can cause deviations in the
accuracy of the controls.
b. Ensure that the wiring between con-
trols and the unit’s termination point
does not exceed two and a half (2.5)
ohms/conductor for the length of the
run.
c. Do not run the electrical wires trans-
porting DC signals in or around
conduit housing high voltage wires.
d. Route low voltage wiring per illustra-
tions on page 25.
23RT-SVX31A-EN
Page 24
Installation
Reliatel Conventional Thermostat Field Wiring
Diagrams
Reliatel Control
Customer Low Voltage Routing-
Reliatel Refrigeration Module
RT-SVX31A-EN24
Page 25
Installation
Figure 6
Typical Field Wiring Diagrams for Optional Controls (ReliaTel™ only)
25RT-SVX31A-EN
Page 26
Installation
Space Temperature Averaging
ReliaTel™
Space temperature averaging is accomplished by wiring a number of remote sensors in a series/parallel circuit.
Using the BAYSENS016* or BAYSENS017*, at least four sensors are required to accomplish space temperature averaging.
Example #1 illustrates two series circuits with two sensors in each circiut wired in parallel. The square of any number of remote sensors required. Example #2 illustrates three sensors squared in a series/parallel circuit. Using BAYSENS032*, two
sensors are required to accomplish space temperature averaging. Example #3 illustrates the circuit required for this senor.
Table 4 lists the temperature versus resistance coefficient for all sensing.
Use the checklist provided below in conjunction with the “General Unit Requirements” checklist to ensure that the unit is
properly installed and ready for operation.
RT-SVX31A-EN26
Page 27
p
Installation
Table 4
Temperature versus Resistance
(temperature vs resistance)
Tem
erature
Degrees F°Degrees C°Nominal
-20°- 28.9°170.1 K - Ohms
-15°- 26.1° 143.5 K - O hms
-10°- 23.3°121.4 K - Ohms
-5° -20. 6°103. 0 K - Ohms
0° -17. 8°87.56 K - Ohms
5° -15. 0°74.65 K - Ohms
10° -12.2°63.80 K - Ohms
15° -9. 4°54.66 K - Ohms
20°-6.7°46.94 K - Ohms
25°-3.8°40.40 K - Ohms
30°-1.1°34.85 K - Ohms
35°1.7°30.18 K - Ohms
40°4.4°26.22 K - Ohms
45°7.2°22.85 K - Ohms
50°10.0°19.9 6 K - Ohms
55°12.8°17.4 7 K - Ohms
60°15.6°15.3 3 K - Ohms
65°18.3°13.4 9 K - Ohms
70°21.1°11.8 9 K - Ohms
75°23.9°10.5 0 K - Ohms
80°26.7°9.29 7 K - Ohms
85°29.4°8.24 7 K - Ohms
90°32.2°7.33 0 K - Ohms
95°35.0°6.52 8 K - Ohms
7577155345545
Capacity of Pip e of Diffe r ent Diameter s and
Lengths in Cu. Ft. Per Hr. with Pressure
Drop of 0.3" and Specific Gravit y of 0.60
Iron Pipe Size (SI) Millimeters
Length of15 mm 20 mm 25 mm 32 mm 40 mm
Pipe (Meters) PipePipePipePipePipe
4.62.154.989.7621.2334.54
9.11.473.396.8215.1424.06
13.71.212.805.6312.3119.82
18.31.072.434.8910.7617.27
22.9--2.184.389.7615.40
Capacity of Pip e of Diffe r ent Diameter s and
Length s in C u. Meter Per Hr. with Press ur e
Drop of 74.6 Pa and S pe c ific Gra v ity of 0.60
Spec ific Gravity Multiplier s
Specific
Gravity
0.50
0.55
0.60
0.65
Multiplier
1.10
1.04
1.00
0.96
Figure 8
Typical Unit Gas Train Configuration
27RT-SVX31A-EN
Page 28
Installation
Use the checklist provided below in conjunction with the
“General Unit Requirements” checklist to ensure that the
unit is properly installed and ready for operation.
HAZARDOUS VOLTAGE!
HIGH VOLTAGE IS PRESENT AT THE TERMINAL BLOCK
OR UNIT MOUNTED DISCONNECT SWITCH.
[ ] Check all electrical connections for tightness and “point
of termination” accuracy.
[ ] Verify that the condenser airflow will be unobstructed.
[ ] Verify that the condenser fan and indoor blower turn freely
without rubbing and are properly tightened on the shafts.
[ ] Check the supply fan belts for proper tension and the fan
bearings for sufficient lubrication. If the belts require ad-
justment, or if the bearings need lubricating, refer to the
maintenance section of this manual for instructions.
[ ] Verify that a condensate trap is installed and the piping is
properly sized and pitched.
[ ] Verify that the correct size and number of filters are in
place.
[ ] Inspect the interior of the unit for tools and debris and in-
stall all panels in preparation for starting the unit.
Voltage Imbalance
Three phase electrical power to the unit must meet stringent requirements for the unit to operate properly. Measure
each leg (phase-to-phase) of the power supply. Each reading must fall within the utilization range stamped on the unit
nameplate. If any of the readings do not fall within the
proper tolerances, notify the power company to correct this
situation before operating the unit.
Excessive three phase voltage imbalance between phases
will cause motors to overheat and eventually fail. The maximum allowable voltage imbalance is 2%. Measure and
record the voltage between phases 1, 2, and 3 and calculate the amount of imbalance as follows:
% Voltage Imbalance =100 X AV - VD where;
AV
VD = Line Voltage reading that deviates the farthest from
the average voltage.
Example: If the voltage readings of the supply power
measured 403, 402, and 389, the average volts would be:
VD (reading farthest from average) = 389
The percentage of Imbalance equals:
The 2.2% imbalance in this example exceeds the maximum
allowable imbalance of 2.0%. This much imbalance between phases can equal as much as a 20% current imbalance with a resulting increase in motor winding temperatures that will decrease motor life. If the voltage imbalance
is over 2%, notify the proper agencies to correct the voltage
problem before operating this equipment.
Electrical Phasing
(Three Phase Motors)
The compressor motor(s) and the supply fan motor are internally connected for the proper rotation when the incoming
power supply is phased as A, B, C.
Proper electrical supply phasing can be quickly determined
and corrected before starting the unit by using an instrument such as an Associated Research Model 45 Phase Sequence Indicator and following the steps below:
[ ] Turn the field supplied disconnect switch that provides
[ ] Connect the phase sequence indicator leads to the termi-
Black (phase A) toL1
Red (phase B)toL2
Yellow (phase C) toL3
[ ] Close the field supplied main power disconnect switch or
403 + 402 + 389 = 398 Avg.
100 X
power to the main power terminal block or to the “Line”
side of the optional factory mounted disconnect switch to
the “Off” position.
nal block or to the “Line” side of the optional factory
mounted disconnect switch as follows;
circuit protector switch that provides the supply power to
the unit.
3
398 - 389 = 2.2%
398
AV (Average Voltage) =
V1, V2, V3 = Line Voltage Readings
Volt 1 + Volt 2 + Volt 3
3
RT-SVX31A-EN28
Page 29
Installation
HAZARDOUS VOLTAGE!
HIGH VOLTAGE IS PRESENT AT THE TERMINAL BLOCK
OR UNIT MOUNTED DISCONNECT SWITCH.
To prevent injury or death from electrocution, it is the responsibility of the technician to recognize this hazard and
use extreme care when performing service procedures with
the electrical power energized.
[ ] Observe the ABC and CBA phase indicator lights on the
face of the sequencer. The ABC indicator light will glow if
the phase is ABC. If the CBA indicator light glows, open
the disconnect switch or circuit protection switch and reverse any two power wires.
[ ] Restore the main electrical power and recheck the phas-
ing. If the phasing is correct, open the disconnect switch or
circuit protection switch and remove the phase sequence
indicator.
29RT-SVX31A-EN
Page 30
Pre - Start
HAZARDOUS VOLTAGE!
HIGH VOLTAGE IS PRESENT AT THE
TERMINAL BLOCK OR UNIT
MOUNTED DISCONNECT SWITCH.
To prevent injury or death from electrocution, it is the responsibility of the
technician to recognize this hazard
and use extreme care when performing service procedures with the electrical power energized.
ReliaTel Controls
Upon power initialization, the RTRM
performs self-diagnostic checks to insure that all internal controls are functional. It also checks the configuration
parameters against the components
connected to the system. The Liteport
LED located on the RTRM module is
turned “On” within one second of
power-up if internal operation is okay.
Use one of the following “Test” procedure to bypass some time delays and
to start the unit at the control panel.
Each step of unit operation can be ac-
tivated individually by temporarily shorting across the “Test” terminals for two
to three seconds. The Liteport LED located on the RTRM module will blink
when the test mode has been initiated. The unit can be left in any “Test”
step for up to one hour before it will
automatically terminate, or it can be
terminated by opening the main power
disconnect switch. Once the test mode
has been terminated, the Liteport LED
will glow continuously and the unit will
revert to the “System” control.
Test Modes
There are three methods in which the
“Test” mode can be cycled at LTB-Test
1 and LTB-Test 2.
1. Step Test Mode - This method initiates the different components of
the unit, one at a time, by temporarily shorting across the two test
terminals for two to three seconds.
For the initial start-up of the unit, this
method allows the technician to cycle
a component “On” and have up to one
hour to complete the check.
2. Resistance Test Mode - This
method can be used for start-up
providing a decade box for variable
resistance outputs is available. This
method initiates the different components of the unit, one at a time,
when a specific resistance value is
placed across the two test terminals. The unit will remain in the
specific test mode for approximately
one hour even though the resistance is left on the test terminals.
3. Auto Test Mode - This method is not
recommended for start-up due to
the short timing between individual
component steps. This method initiates the different components of
the unit, one at a time, when a
jumper is installed across the test
terminals. The unit will start the first
test step and change to the next
step every 30 seconds. At the end of
the test mode, control of the unit will
automatically revert to the applied
“System” control method.
For unit test steps, test modes, and
step resistance values to cycle the various components, refer to Table 6.
Table 6
Service Test Guide for Component Operation
TESTMODEFanEconCompCom pHe atH ea tOhms
STEP(Note 2)1212
1Setpoint2.2K
2Economizer
3CoolMinim u m (Not e 1)
4CoolMinim u m (Note 1) (Note 1)
(Note 3)Stage 2OnPosit ionOnOnOffOff6.8K
5
(Note 3)
6Heat
(Note 3)Stage 1OnMinimumOf fOffOnOff10K
7Heat
(Note 3)Stage 2OnMinimumOf fOffOnOn15K
Notes:
1 - The condenser f ans will operat e any t im e a com pres sor is "On"
providing the outdoor air t emper at ur es are wit hin t he operating values.
2 - The exhaust fan will turn on anytim e t he economizer damper posit ion is equal
to or greater than the exhaust fan setpoint.
3 - Steps for optional accessories and non-applicable modes in unit will be skipped.
FanOnPositionOffOffOffOff
Minimum
VentilationOnSelectableOffOffOffOff
Test OpenOnOpenOffOffOffOff3.3K
Stage 1OnPositionOnOffOffOff4.7K
ReheatOnMinimumOnOnOffOff3 3K
Minimum
0%
RT-SVX31A-EN30
Page 31
Pre - Start
Verifying Proper Air Flow
(Units with Belt Drive Indoor Fan)
Much of the systems performance and reliability is closely
associated with, and dependent upon having the proper airflow supplied both to the space that is being conditioned
and across the evaporator coil.
The indoor fan speed is changed by opening or closing the
adjustable motor sheave.
Before starting the SERVICE TEST, set the minimum position setpoint for the economizer to 0 percent using the
setpoint potentiometer located on the Economizer Control
(ECA), if applicable.
ReliaTel Control
Using the Service Test Guide in Table 6, momentarily jump
across the Test 1 & Test 2 terminals on LTB1 one time to
start the Minimum Ventilation Test.
Once the supply fan has started, check for proper rotation.
The direction of rotation is indicated by an arrow on the fan
housing.
Use the following procedure to determine the proper adjustment of the evaporator fan for a specific application.
1. With the fan operating properly, determine the total system airflow CFM (m
3
/h) by;
3. If the required CFM is too high, (external static pressure
is low causing motor HP output to be above table value),
perform one or both of the following:
a. Relieve supply and/or return duct static.
b. Change indoor fan speed and repeat step 1.
To Increase Fan RPM; Loosen the pulley adjustment set
screw and close the sheave by moving the two halves
closer together.
To Decrease Fan RPM; Loosen the pulley adjustment set
screw and open the sheave by moving the two halves farther apart..
4. To stop the SERVICE TEST, turn the main power disconnect switch to the “Off” position or proceed to the next
component start-up procedure.
a. Measuring the actual RPM,
b. Measure the amperage at the supply fan contactor
and compare it with the full load amp (FLA) rating
stamped on the motor nameplate.
c. Calculate the theoretical BHP (KW)
Actual Motor Amps X Motor HP (KW)
Motor Nameplate Amps
d. Using the fan performance tables in the unit Service
Facts, plot the actual RPM (step 1) and the theoretical
BHP (KW) (step 2c) to obtain the operating Air Flow.
2. If the required Air Flow is too low, (external static pressure
is high causing motor HP (KW) output to be below table
value), perform one or both of the following.
a. Relieve supply and/or return duct static.
b. Change indoor fan speed and repeat step 1.
31RT-SVX31A-EN
Page 32
Start Up
Economizer Start-Up
ReliaTel Control
Using the Service Test Guide in Table
6, momentarily jump across the Test 1
& Test 2 terminals on LTB1 one time to
start the Minimum Ventilation Test.
ROTATING PARTS!
UNIT STARTS AUTOMATICALLY
Verify that the dampers stroked to the
minimum position.
ReliaTel Control
Momentarily jump across the Test 1 &
Test 2 terminals on LTB1 one additional time if continuing from previous
component start-up or until the desired
start-up component Test is started.
Verify that the dampers stroked to the
full open position.
To stop the SERVICE TEST, turn the
main power disconnect switch to the
“Off” position or proceed to the next
component start-up procedure. Remove electro mechanical test mode
connections (if applicable).
Compressor Start-Up
1. Attach a set of service gauges onto
the suction and discharge gauge
ports for each circuit. Refer to the refrigerant circuit illustration in the
Service Facts.
ReliaTel Control
Momentarily jump across the Test 1 &
Test 2 terminals on LTB1 one additional
time if continuing from previous component start-up or until the desired startup component Test is started.
Scroll Compressors
a. Once each compressor has started,
verify that the rotation is correct. If a
scroll compressor is rotating backwards, it will not pump and a loud
rattling sound can be observed.
b. If the electrical phasing is correct,
before condemning a compressor,
interchange any two leads (at the
compressor Terminal block) to check
the internal phasing. Refer to the illustration in Figure 5-1 for the compressor terminal/phase identification. If the compressor runs backward for an extended period (15 to
30 minutes), the motor winding can
overheat and cause the motor winding thermostat to open.
c. Check the compressor oil levels.
The oil level in each compressor
sight glass should be 1/2 to 3/4 full
when they are “Off”.
Note:
The scroll compressor uses
Trane OIL42 without substitution. The appropriate
oil charge for a 9 and 10 Ton scroll
compressor is 8 pints ( 3.8 liters). For a
14 and 15 Ton scroll compressor, use 14
pints ( 6.6 liters).
2. After the compressor and condenser
fan have started and operated for
approximately 30 minutes, observe
the operating pressures. Compare
the operating pressures to the operating pressure curve in the Service
Facts.
3. Check system superheat. Follow the
instruction listed on the superheat
charging curve in the Service Facts.
Superheat should be within ±5 F (15C) of the superheat chart value.
4. Repeat steps 1 through 4 for each
refrigerant circuit.
Gas Heat Units
Open the main disconnect switch to
shut the unit off and to reset the RTRM.
Follow the Test Guide in Table 6 to
start the unit in the heating mode.
ReliaTel Control Momentarily jump
across the Test 1 & Test 2 terminals
on LTB1 one additional time if continuing from previous component start-up
or until the desired start-up component Test is started.
5. To stop the SERVICE TEST, turn the
main power disconnect switch to
the “Off” position or proceed to the
next component start-up procedure.
Remove electro mechanical test
mode connections (if applicable).
RT-SVX31A-EN32
Page 33
Final System Setup
Final System Setup
After completing all of the pre-start and
start-up procedures outlined in the
previous sections (i.e., operating the
unit in each of its Modes through all
available stages of cooling & heating),
perform these final checks before leaving the unit:
[ ] Program the Night Setback (NSB)
panel (if applicable) for proper unoccupied operation. Refer to the
programming instructions for the
specific panel.
[ ] Verify that the Remote panel “Sys-
tem” selection switch, “Fan” selection switch, and “Zone Temperature”
settings for automatic operation are
correct.
[ ] Inspect the unit for misplaced tools,
hardware, and debris.
[ ] Verify that all exterior panels includ-
ing the control panel doors and condenser grilles are secured in place.
[ ] Close the main disconnect switch or
circuit protector switch that provides
the supply power to the unit’s terminal block or the unit mounted disconnect switch.
33RT-SVX31A-EN
Page 34
Maintenace
ROTATING PARTS!
UNIT STARTS AUTOMATICALLY
Make sure all personnel are standing
clear of the unit before proceeding.
The system components will start
when the power is applied.
Fan Belt Adjustment
The fan belts must be inspected periodically to assure proper unit operation.
Replacement is necessary if the belts
appear frayed or worn. Units with dual
belts require a matched set of belts to
ensure equal belt length.
When removing or installing the new
belts, do not stretch them over the
sheaves. Loosen the belts using the
belt tension adjustment bolts on the
motor mounting base.
Once the new belts are installed, using
a Browning or Gates tension gauge (or
equivalent) illustrated in Figure 9; adjust the belt tension as follows;
1. To determine the appropriate belt de-
flection;
4. Place the large end of the gauge at
the center of the belt span; then depress the gauge plunger until the
large O-ring is even with the top of
the next belt or even with a straightedge placed across the fan and
motor sheaves. Refer to Figure 9.
5. Remove the belt tension gauge.
The small O-ring now indicates a
number other than zero on the
plunger’s force scale. This number
represents the force in pounds or
newtons required to give the
needed deflection.
6. Compare the “force” scale reading
(Step 5) with the appropriate “force”
value listed in Table 7. If the “force”
reading is outside the range, readjust the belt tension.
Note:
Actual belt deflection “force” must
not
exceed the maximum “force” value
shown in Table 7.
7. Recheck the belt tension at least
twice during the first 2 to 3 days of
operation. Belt tension may decrease until the new belts are “run
in”.
a. Measure the center-to-center
shaft distance in inches or
millimeters between the fan and
motor sheaves.
b. Divide the distance measured in
Step 1a by 64 inches or 152
millimeters; the resulting value
represents the amount of belt
deflection that corresponds to
the proper belt tension.
2. Set the large O-ring on the belt tension gauge at the deflection value
determined in Step 1b.
3. Set the small O-ring at zero on the
force scale of the gauge plunger.
RT-SVX31A-EN34
Page 35
Maintenace
Figure 9
Belt Tension Gauge
Table 7
Belt Tension Measurement and Deflection
Deflection Force (Lbs.)
BeltsSuper Steel Cable
CrossSmall P.DGripbeltsGripnotchGripbelts
SectionRange
(in)
3.0 - 3 .634 1 /2 3 7/8 5 1/ 2 3 1/44
A
B
BeltsSuper Steel Cable
CrossSmall P.DGripbeltsGripnotchGripbelts
SectionRange
3.8 - 4 .83 1/254 1/2 6 1/4 3 3/4 4 3/4
5.0 - 7 .045 1 /256 7/8 4 1/ 4 5 1/ 4
3.4 - 4 .245 1 /2 5 3/484 1/2 5 1/2
4.4 - 5 .65 1/8 7 1/8 6 1/ 2 9 1/8 5 3/4 7 1/ 4
5.8 - 8 .86 3/8 8 3/4 7 3/ 8 10 1/878 3/ 4
(mm)
13.3 - 1 6.013.3 20.0 17.2 24.5 14.5 17.8
16.9 - 2 1.415.6 22.2 20.0 27.8 16.7 21.1
A
22.0 - 3 1.117.8 24.5 22.2 30.6 18.9 23.4
15.1 - 1 8.717.8 24.5 25.6 35.6 20.0 24.5
19.6 - 2 4.922.8 31.7 28.9 40.6 25.6 32.3
B
25.8 - 3 9.128.4 38.9 32.8 45.0 31.1 38.9
(in)(in)(in)
Min. Max. Min. Max. Min. Max
Deflection Force (N.)
(mm)(mm)(mm)
Min. Max. Min. Max. Min. Max
35RT-SVX31A-EN
Page 36
Maintenance
Monthly Maintenance
Before completing the following
checks, turn the unit OFF and lock the
main power disconnect switch open.
HAZARDOUS VOLTAGE!
DISCONNECT ALL ELECTRIC
POWER INCLUDING REMOTE DISCONNECTS BEFORE SERVICING.
Failure to disconnect power before
servicing can cause severe personal
injury or death.
Filters
[ ] Inspect the return air filters. Clean or
replace them if necessary. Refer to
the unit Service Facts for filter information.
Cooling Season
[ ] Check the unit’s drain pans and con-
densate piping to ensure that there
are no blockages.
[ ] Inspect the evaporator and con-
denser coils for dirt, bent fins, etc. If
the coils appear dirty, clean them
according to the instructions described in “Coil Cleaning” later in
this section.
[ ] Manually rotate the condenser fan(s)
to ensure free movement and check
motor bearings for wear. Verify that
all of the fan mounting hardware is
tight.
[ ] Inspect the F/A-R/A damper hinges
and pins to ensure that all moving
parts are securely mounted. Keep
the blades clean as necessary.
[ ] Verify that all damper linkages move
freely; lubricate with white grease, if
necessary.
[ ] Check supply fan motor bearings; re-
pair or replace the motor as necessary.
[ ] Check the fan shaft bearings for
wear. Replace the bearings as necessary.
[ ] Check the supply fan belt. If the belt
is frayed or worn, replace it. Refer to
the “Fan Belt Adjustment” section for
belt replacement and adjustments.
[ ] Verify that all wire terminal connec-
tions are tight.
[ ] Remove any corrosion present on
the exterior surfaces of the unit and
repaint these areas.
are reinstalled in the unit access
panels once these checks are complete.
[ ] With the unit running, check and
record the: ambient temperature;
compressor suction and discharge
pressures (each circuit); superheat
(each circuit);
Record this data on an “operator’s
maintenance log” like the one shown in
Table 8. If the operating pressures indicate a refrigerant shortage, measure
the system superheat. For guidelines,
refer to the “Compressor Start-Up” section.
Note:
Do Not release refrigerant to the
atmosphere! If adding or removing
refrigerant is required, the service
technician must comply with all federal,
state and local laws.
Heating Season
[ ] Inspect the unit’s air filters. If neces-
sary, clean or replace them.
[ ] Check supply fan motor bearings; re-
pair or replace the motor as necessary.
[ ] Inspect both the main unit control
panel and heat section control box
for loose electrical components and
terminal connections, as well as
damaged wire insulation. Make any
necessary repairs.
[ ] Clean burner area, verify gas heat
system operates properly.
Coil Cleaning
Regular coil maintenance, including
annual cleaning, enhances the unit’s
operating efficiency by minimizing:
compressor head pressure and amperage draw; evaporator water
carryover; fan brake horsepower, due
to increase static pressure losses; airflow reduction.
At least once each year, or more often
if the unit is located in a “dirty” environment, clean the evaporator and condenser coils using the instructions
outlined below. Be sure to follow these
instructions as closely as possible to
avoid damaging the coils.
To clean refrigerant coils, use a soft
brush and a sprayer (either a garden
pump-up type or a high-pressure
sprayer). A high-quality detergent is
also required; suggested brands include “SPREX A.C.”, “OAKITE 161”,
“OAKITE 166” and “COILOX”. If the detergent selected is strongly alkaline
(ph value exceeds 8.5), add an inhibitor.
1. Remove enough panels from the
unit to gain access to the coil.
2. Protect all electrical devices such as
motors and controllers from any
over spray.
3. Straighten any bent coil fins with a
fin comb.
4. Mix the detergent with water according to the manufacturer’s instructions. If desired, heat the solution to
RT-SVX31A-EN36
Page 37
Maintenance
150o F 65.6o C maximum to improve
its cleansing capability.
CONTAINS REFRIGERANT! SYSTEM
CONTAINS OIL AND REFRIGERANT
Do not heat the detergent-and-water
solution above 150
uids sprayed on the exterior of the coil
will raise the coil’s internal pressure
and may cause it to burst. Failure to
follow proper procedures can result in
personal illness or injury or severe
equipment damage.
5. Pour the cleaning solution into the
sprayer. If a high-pressure sprayer
is used:
a. do not allow sprayer pressure
to exceed 600 psi (41.4 bar).
b. the minimum nozzle spray
angle is 15 degrees.
c. maintain a minimum clearance
of 6" (152.4 mm) between the
sprayer nozzle and the coil.
d. spray the solution
perpendicular (at 90 degrees) to
the coil face.
o
F (-9.4C). Hot liq-
[ ] Clean and repaint any corroded sur-
face.
Final Process
For future reference, you may find it
helpful to record the unit data requested below in the blanks provided.
(1) Com plete Unit Model Num ber :
(2) Unit Serial Number:
(3) Wiring Diagram Numbers (from unit control panel):
— schematic(s)
— connection(s)
6. Spray the leaving-airflow side of the
coil first; then spray the opposite
side of the coil. Allow the cleaning
solution to stand on the coil for five
minutes.
7. Rinse both sides of the coil with
cool, clean water.
8. Inspect both sides of the coil; if it
still appears to be dirty, repeat
Steps 6 and 7.
9. Reinstall all of the components and
panels removed in Step 1 and any
protective covers installed in step 2.
10. Restore the unit to it’s operational
status and check system operation.
Check and record the data request ed a bov e ea c h m on th during the c o oling season with the unit running.
Note:
ReliaTel Control
The RTRM has the ability to provide the service personnel with some unit diagnostics and system status information.
RT-SVX31A-EN38
Page 39
Trouble Shooting
Before turning the main power disconnect switch “Off”, follow the steps below to check the ReliaTel Refrigeration
Module (RTRM). All diagnostics & system status information stored in the
RTRM will be lost when the main
power is turned “Off”.
HAZARDOUS VOLTAGE!
HIGH VOLTAGE IS PRESENT AT THE
TERMINAL BLOCK OR UNIT
MOUNTED DISCONNECT SWITCH.
To prevent injury or death from electrocution, it is the responsibility of the
technician to recognize this hazard
and use extreme care when performing service procedures with the electrical power energized.
1. Verify that the Liteport LED on the
RTRM is burning continuously. If the
LED is lit, go to Step 3.
2. If the LED is not lit, verify that 24 VAC
is presence between J1-1 and J1-2.
If 24 VAC is present, proceed to Step
3. If 24 VAC is not present, check the
unit main power supply, check transformer (TNS1). Proceed to Step 3 if
necessary.
3. Utilizing “Method 1” or “Method 2” in
the “System Status Diagnostic” section, check the following:
System status
Heating status
Cooling status
If a System failure is indicated, proceed to Step 4. If no failures are indicated, proceed to Step 5.
4. If a System failure is indicated, recheck Steps 1 and 2. If the LED is
not lit in Step 1, and 24 VAC is
present in Step 2, the RTRM has
failed. Replace the RTRM.
5. If no failures are indicated, use one
of the TEST mode procedures described in the “Unit Start-Up” section
to start the unit. This procedure will
allow you to check all of the RTRM
outputs, and all of the external controls (relays, contactors, etc.) that
the RTRM outputs energize, for
each respective mode. Proceed to
Step 6.
6. Step the system through all of the
available modes, and verify operation of all outputs, controls, and
modes. If a problem in operation is
noted in any mode, you may leave
the system in that mode for up to
one hour while troubleshooting. Refer to the sequence of operations for
each mode, to assist in verifying
proper operation. Make the necessary repairs and proceed to Steps 7
and 8.
7. If no abnormal operating conditions
appear in the test mode, exit the test
mode by turning the power “Off” at
the main power disconnect switch.
8. Refer to the individual component
test procedures if other microelectronic components are suspect.
System Status Checkout Procedure
“System Status” is checked by using
one of the following two methods:
Method 1
If the Zone Sensor Module (ZSM) is
equipped with a remote panel with LED
status indication, you can check the
unit within the space. If the ZSM does
not have LED’s, use Method 2.
BAYSENS010B, BAYSENS011B,
BAYSENS019A, BAYSENS020A,
BAYSENS021A & BAYSENS023A all
have the remote panel indication feature. The LED descriptions are listed
below.
LED 2 (Heat)
“On” when the heat cycle is operating.
“Off” when the heat cycle terminates or
the LED fails.
“Flashing” indicates a heating failure.
LED 3 (Cool)
“On” when the cooling cycle is operating.
“Off” when the cooling cycle terminates
or the LED fails.
“Flashing” indicates a cooling failure.
LED 4 (Service)
“On” indicates a clogged filter.
“Off” during normal operation.
“Flashing” indicates an evaporator fan
failure
Below is the complete listing of failure
indication causes.
System failure
Check the voltage between terminals 6
and 9 on J6, it should read approximately 32 VDC. If no voltage is present,
a System failure has occurred. Refer to
Step 4 in the previous section for the
recommended troubleshooting procedure.
Heating Failure
Verify Heat Failure by Ignition Module
(IGN) LED indicator:
OFF:No Power or Failure
ON:Normal
Slow Flash:Normal, Heat Call
Fast Flash:Error Code:
1 Flash:Communication
Failure
2 Flashes:System Lockout
3 Flashes:Pressure Switch Fail
4 FlashesTC01 or TC02 Open
5 Flashes:Flame w/o Gas
Valve
6 Flashes:Flame Rollout Open
LED 1 (System)
“On” during normal operation.
“Off” if a system failure occurs or the
LED fails.
“Flashing” indicates test mode.
39RT-SVX31A-EN
Page 40
Trouble Shooting
Cooling Failure
1. Cooling and heating set point (slide
pot) on the zone sensor has failed.
Refer to the “Zone Sensor Test Procedure” section.
2. Zone temperature thermistor ZTEMP
on ZTS failed. Refer to the “Zone
Sensor Test Procedure” section.
3. CC1 or CC2 24 VAC control circuit
has opened, check CC1 & CC2
coils, and any of the controls below
that apply to the unit (HPC1, HPC2).
4. LPC1 has opened during the 3
minute minimum “on time” during 4
consecutive compressor starts,
check LPC1 or LPC2 by testing voltage between the J1-1 & J3-2 terminals on the RTRM and ground. If 24
VAC is present, the LPC’s has not
tripped. If no voltage is present,
LPC’s has tripped.
Service Failure
1. If the supply fan proving switch has
closed, the unit will not operate
(when connected to RTOM), check
the fan motor, belts, and proving
switch.
2. Clogged filter switch has closed,
check the filters.
Simultaneous Heat and Cool Failure
1. Emergency Stop is activated
Method 2
The second method for determining
system status is done by checking voltage readings at the RTRM (J6). The
system indication descriptions and the
approximate voltages are listed below.
System Failure
Measure the voltage between terminals
J6-9 & J6-6.
Normal Operation = approximately 32
VDC
System Failure = less than 1 VDC, approximately 0.75 VDC
Test Mode = voltage alternates between 32 VDC & 0.75 VDC
Heat Failure
Measure the voltage between terminals
J6-7 & J6-6.
Heat Operating = approximately 32
VDC
Heat Off = less than 1 VDC, approximately 0.75 VDC
Heating Failure = voltage alternates between 32 VDC & 0.75 VDC
Cool Failure
Measure the voltage between terminals
J6-8 & J6-6.
Cool Operating = approximately 32
VDC
Cool Off = less than 1 VDC, approximately 0.75 VDC
Cooling Failure = voltage alternates between 32 VDC & 0.75 VDC
Service Failure
Measure the voltage between terminals
J6-10 & J6-6.
Clogged Filter = Approximately 32
VDC.
Normal = Less than 1 VDC, approximately 0.75 VDC Fan Failure = voltage
alternates between 32 VDC & 0.75
VDC.
To use LED’s for quick status information at the unit, purchase a
BAYSENS010B ZSM and connect wires
with alligator clamps to terminals 6
through 10. Connected each respective
terminal wire (6 through 10) from the
Zone Sensor to the unit J6 terminals 6
through 10.
Note:
If the system is equipped with a
programmable zone sensor,
BAYSENS019B the LED indicators will
not function while the BAYSENS010A is
connected.
Resetting Cooling and Ignition
Lockouts
Cooling Failures and Ignition Lockouts
are reset in an identical manner.
Method 1 explains resetting the system
from the space; Method 2 explains resetting the system at the unit.
Note:
Before resetting Cooling Failures and
Ignition Lockouts check the Failure
Status Diagnostics by the methods
previously explained. Diagnostics will be
lost when the power to the unit is
disconnected.
Method 1
To reset the system from the space,
turn the “Mode” selection switch at the
zone sensor to the “Off” position. After
approximately 30 seconds, turn the
“Mode” selection switch to the desired
mode, i.e. Heat, Cool or Auto.
Method 2
To reset the system at the unit, cycle
the unit power by turning the disconnect switch “Off” and then “On”.
Lockouts can be cleared through the
building management system. Refer to
the building management system instructions for more information.
Zone Temperature Sensor (ZTS)
Service Indicator
The ZSM SERVICE LED is a generic
indicator, that will signal the closing of a
Normally Open switch at any time, providing the Indoor Motor (IDM) is operating. This indicator is usually used to indicate a clogged filter, or an air side fan
failure.
The RTRM will ignore the closing of this
Normally Open switch for 2 (±1) minutes. This helps prevent nuisance SERVICE LED indications. The exception is
the LED will flash 40 seconds after the
fan is turned “On” if the Fan Proving
Switch is not made.
Clogged Filter Switch
This LED will remain lit the entire time
that the Normally Open switch is
closed. The LED will be turned off immediately after resetting the switch (to
the Normally Open position), or any
time that the IDM is turned “Off”.
RT-SVX31A-EN40
Page 41
p
Trouble Shooting
If the switch remains closed, and the
IDM is turned “On”, the SERVICE LED
will be turned “On” again after the 2
(±1) minute ignore delay.
This LED being turned “On”, will have
no other affect on unit operation. It is an
indicator only.
Fan Failure Switch
When the “Fan Failure” switch is wired
to the RTOM, the LED will remain flashing the entire time the fan proving
switch is closed, indicating a fan failure, and it will shut the unit operations
down.
Zone Temperature Sensor (ZTS) Test
Note:
These procedures are not for
programmable or digital models and are
conducted with the Zone Sensor Module
electrically removed from the system.
Test 1
Zone Temperature Thermistor
(ZTEMP)
This component is tested by measuring
the resistance between terminals 1 and
2 on the Zone Temperature Sensor. Below are some typical indoor temperatures, and corresponding resistive values.
Test 2
Cooling Set Point (CSP) and Heating
Set Point (HSP)
The resistance of these potentiometers
are measured between the following
ZSM terminals. Refer to the chart
above for approximate resistances at
the given setpoints.
Cool SP= Terminals 2 and 3
Range = 100 to 900 Ohms approximate
Heat SP = Terminals 2 and 5
Range = 100 to 900 Ohms approximate
Test 3
System Mode and Fan Selection
The combined resistance of the Mode
selection switch and the Fan selection
switch can be measured between terminals 2 and 4 on the Zone Sensor. The
possible switch combinations are
listed below with their corresponding
resistance values.
Test 4
LED Indicator Test, (SYS ON, HEAT,
COOL & SERVICE)
Method 1
Testing the LED using a meter with diode test function. Test both forward and
reverse bias. Forward bias should measure a voltage drop of 1.5 to 2.5 volts,
depending on your meter. Reverse bias
will show an Over Load, or open circuit
indication if LED is functional.
Method 2
Testing the LED with an analog Ohmmeter. Connect Ohmmeter across LED
in one direction, then reverse the leads
for the opposite direction. The LED
should have at least 100 times more
resistance in reverse direction, as compared with the forward direction. If high
resistance in both directions, LED is
open. If low in both directions, LED is
shorted.
Method 3
To test LED’s with ZSM connected to
unit, test voltages at LED terminals on
ZSM. A measurement of 32 VDC,
across an unlit LED, means the LED
has failed.
Note:
Measurements should be made from
LED common (ZSM terminal 6 to
respective LED terminal). Refer to the
Zone Sensor Module (ZSM) Terminal
Identification table at the beginning of
this section.
Programmable & Digital Zone Sensor
Test
Testing serial communication
voltage
1. Verify 24 VAC is present between
terminals J6-14 & J6-11.
2. Disconnect wires from J6-11 and
J6-12. Measure the voltage between
J6-11 and J6-12, should be about
32 VDC.
3. Reconnect wires to terminals J6-11
and J6-12. Measure voltage again
between J6-11 and J6-12, voltage
should flash high and low every 0.5
seconds. The voltage on the low end
will measure about 19 VDC, while
the voltage on the high end will measure from approximately 24 to 38
VDC.
4. Verify all modes of operation, by running the unit through all of the steps
in the “Test Modes” section discussed in “Unit Start-Up”.
5. After verifying proper unit operation,
exit the test mode. Turn the fan on
continuously at the ZSM, by pressing
the button with the fan symbol. If the
fan comes on and runs continuously,
the ZSM is good. If you are not able
to turn the fan on, the ZSM is defective.
If the RTCI loses input from the building management system, the RTRM
will control in the default mode after
approximately 15 minutes. If the RTRM
loses the Heating and Cooling setpoint
input, the RTRM will control in the default mode instantaneously. The temperature sensing thermistor in the Zone
41RT-SVX31A-EN
Page 42
Trouble Shooting
Sensor Module is the only component
required for the “Default Mode” to operate.
Unit Operation without a Zone Sensor
This procedure is for temporary operation only. The economizer and condenser fan cycling functions are disabled.
1. Open and Lock the unit disconnect
switch.
2. Remove the Outside Air Sensor
(OAS) from the condenser section of
unit.
3. Use two (2) wire nuts, to individually
cap the wires.
4. Locate the RTRM (J6). Connect two
(2) wires to terminals J6-1 and 2.
5. Connect the sensor (OAS) using two
wire nuts to the two (2) field supplied
wires that were connected to terminals 1 and 2 on J6.
Unit Economizer Control (ECA)
Troubleshooting
ReliaTel Control
Verify Economizer Status by Economizer Actuator (ECA) LED indicator:
OFF:No Power or Failure
ON:Normal, OK to
Economize
Slow Flash:Normal, Not OK to
Economize
Fast Flash:Communications
Failure
Pulse Flash:Error Code:
1 Flash:Actuator Fault
2 Flashes:CO2 Sensor
3 Flashes:RA Humidity Sensor
4 FlashesRA Temp Sensor
5 Flashes:OA Quality Sensor
6 Flashes:OA Humidity Sensor
7 Flashes:OA Temp Sensor
8 Flashes:MA Temp Sensor
9 Flashes:RAM Fault
10 Flashes:ROM Fault
11 Flashes:EEPROM Fault
Before turning the main power disconnect switch “Off”, follow the steps below to check the Ignition Module (IGN).
HAZARDOUS VOLTAGE!
HIGH VOLTAGE IS PRESENT AT THE
TERMINAL BLOCK OR UNIT
MOUNTED DISCONNECT SWITCH.
To prevent injury or death from electrocution, it is the responsibility of the
technician to recognize this hazard
and use extreme care when performing service procedures with the electrical power energized.
1. Verify that the LED on the IGN is
burning continuously. If the LED is lit,
go to Step 3.
2. If the LED is not lit, verify that 24 VAC
is present between R and B. If the
LED is not lit and 24 VAC is present
replace the IGN. If 24 VAC is not
present, check transformer (TNS1).
Proceed to Step 3 if necessary.
3. If no failures are indicated, use the
TEST mode procedures described in
the “Unit Start-Up” section or thermostat to start the unit. This procedure
will allow you to check all of the external controls (relays, contactors,
etc) and the IGN.
4. Test the system through all of the
available modes, and verify operation of all outputs, controls, and
modes. Refer to the sequence of operations for each mode, to assist in
verifying proper operation. Make the
necessary repairs and proceed to
Steps 5 and 6.
7. If no abnormal operating conditions
appear in the test mode, exit the test
mode by turning the power “Off” at
the main power disconnect switch
and removing the test mode connections.
8. Refer to the individual component
test procedures if other components
are suspect.
Verify Heat Failure by Ignition Module
(IGN) LED indicator:
OFF:No Power or Failure
ON:Normal
Slow Flash:Normal, Heat Call
Fast Flash:Error Code:
2 Flashes:System Lockout
3 Flashes:Pressure Switch Fail
4 FlashesTC01 or TC02 Open
5 Flashes:Flame w/o Gas
Valve
6 Flashes:Flame Rollout Open
Cooling Failure
1. Cooling and heating set point (slide
pot) on the thermostat has failed.
2. CC1 or CC2 24 VAC control circuit
has opened, check CC1 & CC2 coils,
and any of the controls below that
apply to the unit (HPC1, HPC2,
LPC1, LPC2, Frostat™).
Resetting Cooling and Ignition
Lockouts
Cooling Failures and Ignition Lockouts
are reset in an identical manner.
Method 1 explains resetting the system
from the space; Method 2 explains resetting the system at the unit.
Method 1
To reset the system from the space,
turn the “Mode” selection switch at the
thermostat to the “Off” position. After
approximately 30 seconds, turn the
“Mode” selection switch to the desired
mode, i.e. Heat, Cool or Auto.
Method 2
To reset the system at the unit, cycle
the unit power by turning the disconnect switch “Off” and then “On”.
Heating Failure
RT-SVX31A-EN42
Page 43
Control Wiring Schematic
43RT-SVX31A-EN
Page 44
Power Wiring Schematic
RT-SVX31A-EN44
Page 45
45RT-SVX31A-EN
Page 46
RT-SVX31A-EN46
Page 47
47RT-SVX31A-EN
Page 48
®
The Trane Company
Worldwide Applied Systems Group
3600 Pammel Creek Road
La Crosse, WI 54601-7599
www.trane.com
An American Standard Company
Literature Order Number
Date
Supersedes
RT-SVX31A-EN
08/07
Y_C-IOM-2A
Since The Trane Company has a policy of continuous product improvement, it reserves the right to change design
and specifications without notice.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.