Trane YCZ035F1, YCZ036F1-3M0B User Manual

INSTALLATION
YCZ-IOM-1F
18-EB21D4-7
ALL phases of this installation must comply with
NATIONAL, STATE AND LOCAL CODES
Library Product Section Product Model Literature Type Sequence Date File No. Supercedes
Installation, Operation, Maintenance
SV-UN-RT-YCZ-IOM-1F 12/02
Model:
YCZ036F1/3M0B, 4MOA YCZ050F1/3HOA, 4H0A YCZ060F1/3M0B, 4M0A
BAYLIFT002A LIFTING LUG KIT
IMPORTANT — This Document is customer property and is to remain with this unit. Please return to service information pack upon completion of work.
Single Package Two Stage Gas/Electric 16 SEER Convertible 3, 4, 5 Ton
Service Literature
Unitary
Packaged Gas/Electric
YCZ
1F
December 2002
New
WARNING:
All phases of this installation must comply with the NATIONAL, STATE & LOCAL CODES. In the absence of local codes, the installation must conform with National Electric Code -- ANSI/NFPA 70 or "LATEST REVISION."
Since Trane has a policy of continuous product and product data improvement, it reserves the right to change design and specification without notice.
© 2002 American Standard Inc. All rights reserved
HAZARDOUS VOLTAGE - DISCONNECT POWER BEFORE SERVICING
12/02
GENERAL INFORMATION
IMPORTANT: Read this entire manual before
beginning installation procedures.
WARNING:
HIGH VOLTAGE ELECTRICAL COMPONENTS, FAST MOVING FANS, AND COMBUSTIBLE GAS. FOR PROTECTION FROM THESE INHERENT HAZARDS DURING INSTALLATION AND SERVICING, THE ELECTRICAL SUPPLY MUST BE DISCONNECTED AND THE MAIN GAS VALVE MUST BE TURNED OFF. IF OPERATING CHECKS MUST BE PERFORMED WITH THE UNIT OPERATING, IT IS THE TECHNICIANS RESPONSIBILTY TO RECOGNIZE THESE HAZARDS AND PROCEED SAFELY.
Read this manual carefully before attempting to install, operate, or perform maintenance on this unit. Installation and mainte­nance should be performed by qualified service technicians only.
As shipped from the factory, this unit is for use with natural gas only, and is listed by Underwriters Laboratory.
Model YCY-F heating/cooling units are designed for outdoor mounting with a vertical condenser discharge. They can be located either at ground level or on a roof, in accordance with local codes or National Fuel Gas Code (ANSI-Z223.1A) Latest Revision. Since these units are designed exclusively for outdoor operation, additional flue venting systems are not required. Each unit contains an operating charge of Refrigerant-22 as shipped.
BODILY INJURY CAN RESULT FROM
IMPORTANT: DO NOT CONNECT GAS PIPING TO THE UNIT UNTIL A LINE PRESSURE TEST HAS BEEN COMPLETED. DAMAGE TO THE GAS VALVE MAY RESULT IN AN UNSAFE CONDITION. THIS UNIT SHOULD NEVER BE EXPOSED TO GAS LINE PRESSURE IN EXCESS OF 14 INCHES WATER COLUMN. (1/2 PSIG)
IMPORTANT: RECONNECT ALL GROUNDING DEVICES. ALL PARTS OF THIS PRODUCT CAPABLE OF CONDUCTING ELECTRICAL CURRENT ARE GROUNDED. IF GROUNDING WIRES, SCREWS, STRAPS, CLIPS NUTS OR WASHERS USED TO COMPLETE A PATH TO GROUND ARE REMOVED FOR SERVICE, THEY MUST BE RETURNED TO THEIR ORIGI­NAL POSITION AND PROPERLY FASTENED.
IMPORTANT: ALL POWER LEGS MAY NOT BE BROKEN BY CONTACTORS. SEE WIRING DIAGRAM ON UNIT CONTROL BOX COVER.
THIS UNIT, AS SHIPPED FROM THE FACTORY, IS DE­SIGNED FOR NATURAL GAS ONLY.
BEFORE STARTING THE COMPRESSOR, THE CRANKCASE HEATER SHOULD BE ENERGIZED FOR EIGHT HOURS
INSPECTION
1. Check for damage after the unit is unloaded. Report promptly, to the carrier, any damage found to the unit. Do not drop the unit.
IMPORTANT: The use of “spreader bars” is required when hoisting the unit (to prevent damage to sides and top).
2. Check the unit’s nameplate to determine if the unit is correct for the intended application. The power supply must be adequate for both the unit and all accessories.
3. Check to be sure the refrigerant charge has been retained during shipment. Access to 1/4" flare pressure taps may be gained by removing the furnace compartment access panel.
NOTICE
Warnings and Cautions appear at appropriate locations throughout this manual.
Read these carefully.
WARNING:
Indicates a potentially hazardous situation which, if not avoided, could
result in death or serious injury.
The following warning complies with State of California law, Proposition 65.
WARNING:
Exposure to fuel substances or by-products of incomplete fuel combustion is believed by the state of California to cause cancer, birth defects, or other reproductive harm.
Hazardous Gasses!
Page 2
CAUTION: Indicates a potentially hazardous situation which, if not avoided, may
result in minor or moderate injury. It may also be used to alert against unsafe practices and where property-damage-only accidents could occur.
1
D
D
TYPICAL ROOFTOP INSTALLATION WITH FULL PERIMETER CURBS
(YCZ036,050,060F Models)
FIELD SUPPLIE
AT EACH END
ROOF INSULATION
ROOF DECK
FIELD SUPPLIED
RIGID INSULATION
ROOF MOUNTING
CURB
ROOFING
FIELD SUPPLIED
CANT STRIP
SUPPORTS
OF CURB
2
NOTES:
1. The YCZ036F models extend out past this end of the curb ONLY.
2. The YCZ050F, YCZ060F models extend past both the end and the side of the curb as illustrated.
TYPICAL ROOFTOP INSTALLATION WITH BAYCURB030A,038A
ROOF INSULATION
SEE NOTE 1
ROOF DECK
FIELD SUPPLIED
RIGID INSULATION
SUPPLY AIR
DUCT
RETURN AIR
DUCT
(YCZ036,050,060F Models)
SUPPLY AIR
DUCT
RETURN AIR
DUCT
SEE NOTE 2
ROOF MOUNTING
CURB
ROOFING
FIELD SUPPLIED
CANT STRIP
FIELD SUPPLIE
SUPPORTS
AT EACH END
OF CURB
Page 3
DIMENSIONAL DATA
6
3
YCZ036,050,060F OUTLINE – BACK
NET
CORNER WEIGHT (LBS)
MODEL
YCZ036F 161 106 104 157 528 64 36 29-3/16 18-9/16 11-1/16 6-9/16 11-1/8 17 18-1/2 25-1/2 17-1/2 10 3 8-3/4
YCZ050F 172 121 137 196 626
YCZ060F 195 129 132 199 656 22-3/4 25-1/2
W1 W2 W3 W4
Page 4
UNIT
WEIGHT
(LBS)
AB C D E F G H J K L MN P
65-1/8 45 33-3/8 21-1/16 15-1/16 4-15/16 9-1/8 21-15/16
24 26-1/2
20 14 3-1/2 8-5/1
DIMENSIONAL DATA
E
6
4
YCZ036,050,060F OUTLINE – FRONT
RECOMMENDED SERVICE CLEARANC
BACK * 6.0"
LEFT SIDE 30.0"
RIGHT SIDE 24.0"
FRONT 42.0"
* 18" WITH FRESH AIR ACCESSORY * 30" WITH EC ONOMI ZE R
MODEL
YCZ036F-M 64 36 29-3/16 27-1/2 YCZ050F-M
YCZ060F-M
ABCD
65-1/8 45 33-3/8 27-15/1
CLEARANCE TO
COMBUSTIBLE MATERIAL
BOTTOM 0.0"
BACK 1.0"
LEFT SIDE 6.0" RIGHT SIDE 6.0" FRONT SIDE 12.0"
TOP 36.0"
Page 5
5
" "
NOTE SUPPLY OPENING
1. REMOVE SCREW NEAREST TO THE OPENING AND PULL THE PANEL FIRMLY TOWARD THE OUTSIDE OF THE UNIT TO DISENGAGE THE BACK ATTACHMENT.
RETURN OPENING
2. REMOVE RIGHT HAND SCREW AND MOVE PANEL TO THE RIGHT OR RE­MOVE BOTH SCREWS.
CONVERTING HORIZONTAL TO DOWNFLOW
HEATER EXCHANGER
TUBES
6
HORIZONTAL SUPPLY
AIR COVER
SHEET METAL
SCREWS
HORIZONTAL RETURN
REQUIRED CLEARANCE FOR UNIT INSTALLATION
AND ROOF PENETRATION HOLE SIZE REQUIRED
D
SERVICE
CLEARANCE
LINES
SIDE RAIL
WOOD NAILER
SUPPLY AIR
C
RETURN AIR
AIR COVER
A
SERVICE
CLEARANCE
LINES
B
SERVICE CLEARANCE & PENETRATION DIMENSIONS
MODEL NO. A B C D E F
YCZ036F 30" 30" *12" 30" 44" 25
YCZ050F
YCZ060F
* 18" WITH FRESH AIR ACCESSORY * 30" WITH ECONOMIZER
Page 6
42" 30" *12" 36" 50" 25
HOLE IN ROOF
E
F
LOCATIONS AND RECOMMENDATIONS
HORIZONTAL AIRFLOW APPLICATION
1. These units are design certified for outdoor installations. These units may be installed directly on wood flooring or on Class A, Class B, or Class C roof covering material. The discharge air from the condenser fans must be unrestricted for a minimum of 3 feet above the unit.
NOTE: The unit is shipped for horizontal installation.
The Air Inlet Hood in the combustion blower access panel must have adequate clearance around the air opening into the combustion area. See Outline Drawing, Figure 3.
Examine all flue product-carrying areas of the furnace, its vent system, and the main burner for safe operation. A periodic inspection of the furnace should be made by a qualified service agency at the start of each heating season.
Replacement parts list for this Gas/Electric Air Conditioner , may be obtained by contacting your local manufacturer representative.
NOTE: If any internal accessories are to be added to the unit, install them at the shop if at all practical.
2. Location of the unit must allow service clearance around it. Clearance of the unit must be given careful consideration. See Figures 2, 3, and 4.
IMPORTANT: Air outlet duct must have 1" clearance to combustible material downstream from the unit.
3. Check the handling facilities to ensure the safety of personnel and the unit(s).
4. CAUTION MUST BE TAKEN AT ALL TIMES TO AVOID
PERSONAL INJURIES AND/OR DAMAGE TO EQUIPMENT
5. The unit must be mounted level for proper drainage of water through the holes in the base pan.
6. The unit must not be exposed to direct roof water runoff.
7. Flexible duct connectors must be of a flame retardant material. All duct work outside of the structure must be insulated and weatherproofed in accordance with local codes.
3. See the unit’s nameplate for the absolute minimum clearance between the unit and any combustible surface(s).
IMPORTANT:
1. Remove the Flue and Air Inlet Hood with gasket from the return air section of the unit.
The screws that attach the flue and air inlet hood will be installed in their proper location at the factory. Therefore, they must be removed and then used to attach the flue and the air inlet hood.
2. Remove the packaging material from the components and secure the Flue and Air Inlet Hood with the gasket to the unit with sheet metal screws as illustrated in Figure 5. See “Firing Rate Selection” section for additional information.
NOTE: Outdoor air or other requirements during heating operation that result in supply air temperatures below 80 degrees F or return air temperatures below 50 degrees F may cause flue gas condensate to form and is to be avoided.
DOWNFLOW APPLICATION -- CURB MOUNTING
1.The Roof Mounting Curb, (field assembled BAYCURB030,038,033,034A), or a field fabricated curb must be in place before the unit is hoisted to the roof top.
2. The Roof Mounting Curb (frame) must be installed on a flat,
level section of the roof (maximum of 1/4" per foot pitch) and provide a level mounting surface for the unit. In addition, be sure to provide sufficient height above the roof to prevent water from entering the unit.
NOTE: This unit was shipped for horizontal installation. Con-
vert to downflow per instructions:
Remove covers from the downflow supply and return air open­ings and place them over the horizontal supply return air openings (painted side out) and secure with sheet metal screws. See Figure 6.
3. Be sure the mounting curb spans structural members (trusses) of the roof, thereby providing sufficient support for the weight of the unit, the curb, the duct(s), and any factory or field installed accessories. See Figures 1, 7, 8, 9, 10, and 11.
8. Holes through exterior walls must be sealed in accordance with local codes.
9. All fabricated outdoor ducts should be as short as possible.
CLEARANCES
1. The recommended clearances for single-unit installations are illustrated in Figure 4. These minimum requirements are not only an important consideration when determining unit place­ment, but they are also essential to ensure adequate service­ability, maximum capacity, and peak operating efficiency.
2. Any reduction of the unit clearances indicated in these illustra­tions may result in condenser coil starvation or the recirculation of warm condenser air. Actual clearances which appear to be inadequate should be reviewed with a local engineer.
4. Be sure the hole in the structure for the ducts is large enough to accommodate the fabricated ducts and the insulation sur­rounding them. See Figure 4.
Note: If any internal accessories are to be added to the unit, install them at the shop if at all practical.
5. These units are design certified for outdoor installation. These units may be installed directly on wood flooring or on Class A, Class B, or Class C roof covering material. The discharge air from the condenser fans must be unrestricted for a minimum of 3 feet above the unit.
The air inlet hood in the combustion blower access panel must have adequate clearance around air openings into the combus­tion area. See Outline Drawing, Figure 3.
continued on next page
Page 7
LOCATIONS AND RECOMMENDATIONS
continued from page 7
Examine all flue product-carrying areas of the furnace, its vent system, and the main burner for safe operation. A periodic inspection of the furnace should be made at the start of each heating season.
Replacement parts list for this Gas/Electric Air Conditioner may be obtained by contacting your local manufacturer representa­tive.
6. Location of the unit must allow for service clearance around it. Clearance of the unit must be given careful consideration. See Figure 4.
7. IMPORTANT: The air outlet duct must have one (1) inch
clearance to combustible material downstream from the unit.
8. Exhaust vents or other sources of contaminated air should not be near the unit’s air inlet, if outside air is to be introduced as makeup air or a ventilation feature is to be used.
9. Check the handling facilities to ensure the safety of personnel and the unit(s).
10. Caution must be taken at all times to avoid personal
injuries and/or damage to the equipment.
15. Access and service clearances for the unit must be given careful consideration when locating the duct entrance open­ings. Figure 4 provides unit dimensions.
16. All fabricated outdoor ducts should be as short as possible.
CLEARANCES
1. The recommended clearances for single-unit installations are illustrated in Figure 4. These minimum requirements are not only an important consideration when determining unit place­ment, but they are also essential to ensure adequate service­ability, maximum capacity, and peak operating efficiency.
2. Any reduction of the unit clearances indicated in these illustra­tions may result in condenser coil starvation or the recirculation of warm condenser air. Actual clearances which appear to be inadequate should be reviewed with a local sales engineer.
IMPORTANT:
1. Remove the Flue and Air Inlet Hood with the gasket from the return air section of the unit.
The screws that attach the flue and air inlet hood will be installed in their proper location at the factory. Therefore, they must be removed and then used to attach the flue and air inlet hood.
11. The unit must be mounted level for proper drainage of water through the holes in the base pan.
12. The unit must not be exposed to direct roof water runoff.
13. Flexible duct connectors must be of a flame retardant material. All duct work outside of the structure must be insulated and weatherproofed in accordance with local codes.
14. Roof flashing must be installed to seal the roof curb cavity and must conform to local building codes.
INSTALLATION
UNIT SUPPORT
If the unit is to be roof mounted, check the appropriate building codes for weight distribution requirements. Refer to the applicable roof curb mounting instruction. Check the unit’s nameplate for supply voltage required. Determine if adequate electrical power is available. The furnace may be installed on Class A, B, or C roofing material.
LOCATION AND CLEARANCES
Installation of the unit should conform to local building codes or, in the absence of local codes, to the National Fuel Gas Code, ANSIZ223.1, Latest Revision, and the National Electrical Code. Canadian installations must conform to CSA and local codes.
Select a location that will permit adequate combustion and ventila­tion air in accordance with Section 5.3, Air For Combustion and Ventilation, of the National Fuel Gas Code, ANSIZ223.1, Latest Revision, or applicable provisions of the local building code.
Page 8
2. Remove the packaging material from the components and secure the Flue and Air Inlet Hood with the gasket to the unit with sheet metal screws as illustrated in Figure 16 on page 14.
NOTE: Outdoor air or other requirements during heating operation that result in supply air temperatures below 80 degrees F or return air temperatures below 50 degrees F may cause flue gas condensate to form and is to be avoided.
PLACING AND RIGGING
1. Before preparing the unit for lifting, check the outline drawing for center of gravity for lifting safety. Because of placement of internal components, the unit’s weight may be unevenly distrib­uted. Approximate unit weights are given in Figure 2, page 3.
NOTE: Accessory BAYLIFT002AA, a kit of four (4) lifting lugs, is required for rigging the unit for hoisting. See Figure 7, insert B.
2. Insert the four lifting lugs in the openings provided in the drip lip on the perimeter of the unit. See Figure 7, insert B. A tap or jerk to the lug will overcome the interference that arises due to the nipple on the lug.
3. Before hoisting the unit, be sure that the proper method of rigging is used, with straps or slings and spreader bars for protection during lifting. Always test-lift the unit to determine the exact unit balance and stability before hoisting it to the installa­tion location.
Loading...
+ 16 hidden pages