IMPORTANT — This Document is customer property and is to remain with this unit. Please return to service information pack upon completion of work.
Single Package Two Stage
Gas/Electric 16 SEER
Convertible 3, 4, 5 Ton
Service Literature
Unitary
Packaged Gas/Electric
YCZ
1F
December 2002
New
WARNING:
All phases of this installation must comply with the NATIONAL, STATE & LOCAL CODES. In the absence of local codes, the
installation must conform with National Electric Code -- ANSI/NFPA 70 or "LATEST REVISION."
Since Trane has a policy of continuous product and product data improvement,
it reserves the right to change design and specification without notice.
HAZARDOUS VOLTAGE - DISCONNECT POWER BEFORE SERVICING
12/02
GENERAL INFORMATION
IMPORTANT: Read this entire manual before
beginning installation procedures.
▲
WARNING:
HIGH VOLTAGE ELECTRICAL COMPONENTS, FAST MOVING FANS,
AND COMBUSTIBLE GAS. FOR PROTECTION FROM THESE
INHERENT HAZARDS DURING INSTALLATION AND SERVICING,
THE ELECTRICAL SUPPLY MUST BE DISCONNECTED AND THE
MAIN GAS VALVE MUST BE TURNED OFF. IF OPERATING CHECKS
MUST BE PERFORMED WITH THE UNIT OPERATING, IT IS THE
TECHNICIANS RESPONSIBILTY TO RECOGNIZE THESE HAZARDS
AND PROCEED SAFELY.
Read this manual carefully before attempting to install, operate,
or perform maintenance on this unit. Installation and maintenance should be performed by qualified service technicians
only.
As shipped from the factory, this unit is for use with natural gas
only, and is listed by Underwriters Laboratory.
Model YCY-F heating/cooling units are designed for outdoor
mounting with a vertical condenser discharge. They can be
located either at ground level or on a roof, in accordance with
local codes or National Fuel Gas Code (ANSI-Z223.1A) Latest
Revision. Since these units are designed exclusively for outdoor
operation, additional flue venting systems are not required.
Each unit contains an operating charge of Refrigerant-22 as
shipped.
BODILY INJURY CAN RESULT FROM
IMPORTANT: DO NOT CONNECT GAS PIPING TO THE UNIT
UNTIL A LINE PRESSURE TEST HAS BEEN COMPLETED.
DAMAGE TO THE GAS VALVE MAY RESULT IN AN UNSAFE
CONDITION. THIS UNIT SHOULD NEVER BE EXPOSED TO
GAS LINE PRESSURE IN EXCESS OF 14 INCHES WATER
COLUMN. (1/2 PSIG)
IMPORTANT: RECONNECT ALL GROUNDING DEVICES.
ALL PARTS OF THIS PRODUCT CAPABLE OF CONDUCTING
ELECTRICAL CURRENT ARE GROUNDED. IF GROUNDING
WIRES, SCREWS, STRAPS, CLIPS NUTS OR WASHERS
USED TO COMPLETE A PATH TO GROUND ARE REMOVED
FOR SERVICE, THEY MUST BE RETURNED TO THEIR ORIGINAL POSITION AND PROPERLY FASTENED.
IMPORTANT: ALL POWER LEGS MAY NOT BE BROKEN BY
CONTACTORS. SEE WIRING DIAGRAM ON UNIT CONTROL
BOX COVER.
THIS UNIT, AS SHIPPED FROM THE FACTORY, IS DESIGNED FOR NATURAL GAS ONLY.
BEFORE STARTING THE COMPRESSOR, THE CRANKCASE
HEATER SHOULD BE ENERGIZED FOR EIGHT HOURS
INSPECTION
1. Check for damage after the unit is unloaded. Report promptly,
to the carrier, any damage found to the unit. Do not drop the
unit.
IMPORTANT: The use of “spreader bars” is required
when hoisting the unit (to prevent damage to sides and
top).
2. Check the unit’s nameplate to determine if the unit is correct
for the intended application. The power supply must be
adequate for both the unit and all accessories.
3. Check to be sure the refrigerant charge has been retained
during shipment. Access to 1/4" flare pressure taps may be
gained by removing the furnace compartment access panel.
NOTICE
Warnings and Cautions appear at appropriate locations throughout this manual.
Read these carefully.
WARNING:
Indicates a potentially hazardous situation which, if not avoided, could
▲
result in death or serious injury.
The following warning complies with State of California law, Proposition 65.
▲
WARNING:
Exposure to fuel substances or by-products of incomplete
fuel combustion is believed by the state of California to
cause cancer, birth defects, or other reproductive harm.
Hazardous Gasses!
Page 2
CAUTION: Indicates a potentially hazardous situation which, if not avoided, may
▲
result in minor or moderate injury. It may also be used to alert against unsafe practices
and where property-damage-only accidents could occur.
1
D
D
TYPICAL ROOFTOP INSTALLATION WITH FULL PERIMETER CURBS
(YCZ036,050,060F Models)
FIELD SUPPLIE
AT EACH END
ROOF INSULATION
ROOF DECK
FIELD SUPPLIED
RIGID INSULATION
ROOF MOUNTING
CURB
ROOFING
FIELD SUPPLIED
CANT STRIP
SUPPORTS
OF CURB
2
NOTES:
1. The YCZ036F models extend out past this end of the
curb ONLY.
2. The YCZ050F, YCZ060F models extend past both the
end and the side of the curb as illustrated.
TYPICAL ROOFTOP INSTALLATION WITH BAYCURB030A,038A
* 18" WITH FRESH AIR ACCESSORY
* 30" WITH EC ONOMI ZE R
MODEL
YCZ036F-M643629-3/1627-1/2
YCZ050F-M
YCZ060F-M
ABCD
65-1/84533-3/8 27-15/1
CLEARANCE TO
COMBUSTIBLE MATERIAL
BOTTOM0.0"
BACK1.0"
LEFT SIDE6.0"
RIGHT SIDE6.0"
FRONT SIDE12.0"
TOP36.0"
Page 5
5
"
"
NOTE
SUPPLY OPENING
1. REMOVE SCREW NEAREST TO THE
OPENING AND PULL THE PANEL FIRMLY
TOWARD THE OUTSIDE OF THE UNIT TO
DISENGAGE THE BACK ATTACHMENT.
RETURN OPENING
2. REMOVE RIGHT HAND SCREW AND
MOVE PANEL TO THE RIGHT OR REMOVE BOTH SCREWS.
CONVERTING HORIZONTAL TO DOWNFLOW
HEATER EXCHANGER
TUBES
6
HORIZONTAL SUPPLY
AIR COVER
SHEET METAL
SCREWS
HORIZONTAL RETURN
REQUIRED CLEARANCE FOR UNIT INSTALLATION
AND ROOF PENETRATION HOLE SIZE REQUIRED
D
SERVICE
CLEARANCE
LINES
SIDE RAIL
WOOD NAILER
SUPPLY AIR
C
RETURN AIR
AIR COVER
A
SERVICE
CLEARANCE
LINES
B
SERVICE CLEARANCE & PENETRATION DIMENSIONS
MODEL NO.ABCDEF
YCZ036F30" 30" *12" 30" 44" 25
YCZ050F
YCZ060F
* 18" WITH FRESH AIR ACCESSORY
* 30" WITH ECONOMIZER
Page 6
42" 30" *12" 36" 50" 25
HOLE IN ROOF
E
F
LOCATIONS AND RECOMMENDATIONS
HORIZONTAL AIRFLOW APPLICATION
1. These units are design certified for outdoor installations. These
units may be installed directly on wood flooring or on Class A,
Class B, or Class C roof covering material. The discharge air
from the condenser fans must be unrestricted for a minimum of
3 feet above the unit.
NOTE: The unit is shipped for horizontal installation.
The Air Inlet Hood in the combustion blower access panel must
have adequate clearance around the air opening into the
combustion area. See Outline Drawing, Figure 3.
Examine all flue product-carrying areas of the furnace, its vent
system, and the main burner for safe operation. A periodic
inspection of the furnace should be made by a qualified service
agency at the start of each heating season.
Replacement parts list for this Gas/Electric Air Conditioner , may be
obtained by contacting your local manufacturer representative.
NOTE: If any internal accessories are to be added to the unit,
install them at the shop if at all practical.
2. Location of the unit must allow service clearance around it.
Clearance of the unit must be given careful consideration. See
Figures 2, 3, and 4.
IMPORTANT: Air outlet duct must have 1" clearance to
combustible material downstream from the unit.
3. Check the handling facilities to ensure the safety of personnel
and the unit(s).
4. CAUTION MUST BE TAKEN AT ALL TIMES TO AVOID
PERSONAL INJURIES AND/OR DAMAGE TO EQUIPMENT
5. The unit must be mounted level for proper drainage of water
through the holes in the base pan.
6. The unit must not be exposed to direct roof water runoff.
7. Flexible duct connectors must be of a flame retardant material.
All duct work outside of the structure must be insulated and
weatherproofed in accordance with local codes.
3. See the unit’s nameplate for the absolute minimum clearance
between the unit and any combustible surface(s).
IMPORTANT:
1. Remove the Flue and Air Inlet Hood with gasket from the return
air section of the unit.
The screws that attach the flue and air inlet hood will be installed
in their proper location at the factory. Therefore, they must be
removed and then used to attach the flue and the air inlet hood.
2. Remove the packaging material from the components and
secure the Flue and Air Inlet Hood with the gasket to the unit
with sheet metal screws as illustrated in Figure 5. See “Firing
Rate Selection” section for additional information.
NOTE: Outdoor air or other requirements during heating
operation that result in supply air temperatures below 80
degrees F or return air temperatures below 50 degrees F may
cause flue gas condensate to form and is to be avoided.
DOWNFLOW APPLICATION -- CURB MOUNTING
1.The Roof Mounting Curb, (field assembled
BAYCURB030,038,033,034A), or a field fabricated curb must
be in place before the unit is hoisted to the roof top.
2. The Roof Mounting Curb (frame) must be installed on a flat,
level section of the roof (maximum of 1/4" per foot pitch)
and provide a level mounting surface for the unit. In
addition, be sure to provide sufficient height above the roof
to prevent water from entering the unit.
NOTE: This unit was shipped for horizontal installation. Con-
vert to downflow per instructions:
Remove covers from the downflow supply and return air openings and place them over the horizontal supply return air
openings (painted side out) and secure with sheet metal screws.
See Figure 6.
3. Be sure the mounting curb spans structural members (trusses)
of the roof, thereby providing sufficient support for the weight of
the unit, the curb, the duct(s), and any factory or field installed
accessories. See Figures 1, 7, 8, 9, 10, and 11.
8. Holes through exterior walls must be sealed in accordance with
local codes.
9. All fabricated outdoor ducts should be as short as possible.
CLEARANCES
1. The recommended clearances for single-unit installations are
illustrated in Figure 4. These minimum requirements are not
only an important consideration when determining unit placement, but they are also essential to ensure adequate serviceability, maximum capacity, and peak operating efficiency.
2. Any reduction of the unit clearances indicated in these illustrations may result in condenser coil starvation or the recirculation
of warm condenser air. Actual clearances which appear to be
inadequate should be reviewed with a local engineer.
4. Be sure the hole in the structure for the ducts is large enough
to accommodate the fabricated ducts and the insulation surrounding them. See Figure 4.
Note: If any internal accessories are to be added to the unit,
install them at the shop if at all practical.
5. These units are design certified for outdoor installation. These
units may be installed directly on wood flooring or on Class A,
Class B, or Class C roof covering material. The discharge air
from the condenser fans must be unrestricted for a minimum of
3 feet above the unit.
The air inlet hood in the combustion blower access panel must
have adequate clearance around air openings into the combustion area. See Outline Drawing, Figure 3.
continued on next page
Page 7
LOCATIONS AND RECOMMENDATIONS
continued from page 7
Examine all flue product-carrying areas of the furnace, its vent
system, and the main burner for safe operation. A periodic
inspection of the furnace should be made at the start of each
heating season.
Replacement parts list for this Gas/Electric Air Conditioner may
be obtained by contacting your local manufacturer representative.
6. Location of the unit must allow for service clearance around it.
Clearance of the unit must be given careful consideration. See
Figure 4.
7. IMPORTANT: The air outlet duct must have one (1) inch
clearance to combustible material downstream from the
unit.
8. Exhaust vents or other sources of contaminated air should not
be near the unit’s air inlet, if outside air is to be introduced as
makeup air or a ventilation feature is to be used.
9. Check the handling facilities to ensure the safety of personnel
and the unit(s).
10. Caution must be taken at all times to avoid personal
injuries and/or damage to the equipment.
15. Access and service clearances for the unit must be given
careful consideration when locating the duct entrance openings. Figure 4 provides unit dimensions.
16. All fabricated outdoor ducts should be as short as possible.
CLEARANCES
1. The recommended clearances for single-unit installations are
illustrated in Figure 4. These minimum requirements are not
only an important consideration when determining unit placement, but they are also essential to ensure adequate serviceability, maximum capacity, and peak operating efficiency.
2. Any reduction of the unit clearances indicated in these illustrations may result in condenser coil starvation or the recirculation
of warm condenser air. Actual clearances which appear to be
inadequate should be reviewed with a local sales engineer.
IMPORTANT:
1. Remove the Flue and Air Inlet Hood with the gasket from the
return air section of the unit.
The screws that attach the flue and air inlet hood will be installed
in their proper location at the factory. Therefore, they must be
removed and then used to attach the flue and air inlet hood.
11. The unit must be mounted level for proper drainage of water
through the holes in the base pan.
12. The unit must not be exposed to direct roof water runoff.
13. Flexible duct connectors must be of a flame retardant material.
All duct work outside of the structure must be insulated and
weatherproofed in accordance with local codes.
14. Roof flashing must be installed to seal the roof curb cavity and
must conform to local building codes.
INSTALLATION
UNIT SUPPORT
If the unit is to be roof mounted, check the appropriate building
codes for weight distribution requirements. Refer to the applicable
roof curb mounting instruction. Check the unit’s nameplate for
supply voltage required. Determine if adequate electrical power is
available. The furnace may be installed on Class A, B, or C roofing
material.
LOCATION AND CLEARANCES
Installation of the unit should conform to local building codes or, in
the absence of local codes, to the National Fuel Gas Code,
ANSIZ223.1, Latest Revision, and the National Electrical Code.
Canadian installations must conform to CSA and local codes.
Select a location that will permit adequate combustion and ventilation air in accordance with Section 5.3, Air For Combustion and
Ventilation, of the National Fuel Gas Code, ANSIZ223.1, Latest
Revision, or applicable provisions of the local building code.
Page 8
2. Remove the packaging material from the components and
secure the Flue and Air Inlet Hood with the gasket to the unit
with sheet metal screws as illustrated in Figure 16 on page 14.
NOTE: Outdoor air or other requirements during heating
operation that result in supply air temperatures below 80
degrees F or return air temperatures below 50 degrees F may
cause flue gas condensate to form and is to be avoided.
PLACING AND RIGGING
1. Before preparing the unit for lifting, check the outline drawing for
center of gravity for lifting safety. Because of placement of
internal components, the unit’s weight may be unevenly distributed. Approximate unit weights are given in Figure 2, page 3.
NOTE: Accessory BAYLIFT002AA, a kit of four (4) lifting lugs, is
required for rigging the unit for hoisting. See Figure 7, insert B.
2. Insert the four lifting lugs in the openings provided in the drip lip
on the perimeter of the unit. See Figure 7, insert B. A tap or jerk
to the lug will overcome the interference that arises due to the
nipple on the lug.
3. Before hoisting the unit, be sure that the proper method of
rigging is used, with straps or slings and spreader bars for
protection during lifting. Always test-lift the unit to determine the
exact unit balance and stability before hoisting it to the installation location.
Loading...
+ 16 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.