Trane TTD 524 AB0E, TTD 518 AB0E, TTD 521 AB0E, TTD 524 AB00, TTT 521 AB0E Installation Manual

...
Page 1
Installation Manual
Multi-Split System Condensing Unit 18,000-36,000 Btuh Models 50/60 Hz
MS-SVN005-EN
TTD/TTT
60 Hz Models Cooling Only
TTD 518 A10E TTD 521 A10E TTD 524 A10E TTD 524 A100 TTT 527 A10E TTT 530 A10E TTT 533 A10E
50 Hz Models Cooling Only
TTD 518 AB0E TTD 521 AB0E TTD 524 AB0E TTD 524 AB00 TTT 521 AB0E TTT 527 AB0E TTT 530 AB0E TTT 533 AB0E
TTD 536 AB0E TTD 536 AB00 TTT 536 AB0E TTT 536 AB00 TTD 536 DB00 TTD 536 DB0E TTT 536 DB0E
TTD 536 A10E TTD 536 A100 TTT 536 A10E TTT 536 A100 TTD 536 D100 TTD 536 D10E TTT 536 D10E
Page 2
2
MS-SVN005-EN
General Information
© American Standard Inc. 2000
General Information
This Installation Manual is given as a guide to good practice in the installation by the installer of TTD/TTT mini-split system. Installation procedures should be performed in the sequence that they appear in this manual.
For installing the unit to operate properly and reliably, it must be installed in accordance with these instructions. Also, the services of a qualified service technician should be employed, through the maintenance contract with a reputable service company.
Read this Installation Manual completely before installing and operating the system.
About this Manual
Cautions appear at appropriate places in this Instruction Manual. Your personal safety and the proper operation of this machine require that you follow them carefully. The Trane Company assumes no liability for installations or servicing performed by unqualified personnel. All phases of the installation of this air conditioning system must conform to all national, provincial, state and local codes.
About the Unit
These TTD/TTT units are assembled, pressure tested, dehydrated, charged and run tested before shipment.
Reception
On arrival, inspect the unit before signing the delivery note. Specify any damage of the unit on the delivery note, and send a registered letter of protest to the last carrier of the goods within 72 hours of delivery. Notify the dealer at the same time.
The unit should be totally inspected within 7 days of delivery. If any concealed damage is discovered, send a registered letter of protest to the carrier within 7 days of delivery and notify the dealer.
Warning
Warnings are provided at appropriate places in this manual to indicate to installers, operators and service personnel of potentially hazardous situations which, if not avoided, COULD result in death or serious injury.
Caution
Cautions are provided at appropriate places in this manual to indicate to installers, operators, and service personnel of potentially hazardous situations which, if not avoided, MAY result in minor or moderate injury or malfunction of the unit.
Your personal safety and the proper operation of this unit require that you follow them carefully. The Trane Company assumes no liability for installations or servicing performed by unqualified personnel.
Warranty
Warranty is based on the general terms and conditions by country. The warranty is void if the equipment is modified or repaired without the written approval of The Trane Company, if the operating limits are exceeded or if the control system or the electrical wiring is modified.
Damage due to inappropriate installation, lack of knowledge or failure to comply with the manufacturer’s instructions, is not covered by the warranty obligation. If the installation does not conform to the rules described in Installation Manual, it may entail cancellation of warranty and liabilities by The Trane Company.
Important
This document is customer property and is to remain with unit. Please place in service information pack upon completion of work. These instructions do not cover all variations in systems, nor do they provide for every possible contingency to be met in connection with installation. Should further information be desired or should particular problems arise which are not covered sufficiently in this manual, the matter should be referred to your authorized Trane dealer.
Page 3
MS-SVN005-EN
3
Contents
General Information 2
Valid System Combinations 4
Installation Requirements 6
Location and Preparation of Units 7
Connection of Refrigerant Tubing 8
Condensate Drain Piping 9
System Evacuation and Purging 10
Electrical Installation 11
Wiring Diagram 12
Dimensional Data 17
Page 4
4
MS-SVN005-EN
Valid System Combinations
Table 1 : TTT/TTD Multi-Split Condensing Unit with Convertible,
Concealed and Frio Hi-Wall (For Domestic Only) Indoor Unit
Model Model Nominal 50 Hz 60 Hz
Outdoor Unit Indoor Unit Capacity
Btuh
MCW509H 9,000 Yes Yes MCW509H 9,000
MCW509H 9,000 Yes Yes MCW512H 12,000
MCW512H 12,000 Yes Yes MCW512H 12,000
MCX512 or MCD512 12,000 Yes Yes MCX512 or MCD512 12,000
MCW509H 7,500 Yes No
TTT521AB0E MCW509H 7,500
MCW509H 7,500
MCW509H 9,000 Yes Yes
TTT527AB0E/A10E MCW509H 9,000
MCW509H 9,000
MCW509H 9,000 Yes Yes
TTT530AB0E/A10E MCW509H 9,000
MCW512H 12,000
MCW509H 9,000 Yes Yes
TTT533AB0E/A10E MCW512H 12,000
MCW512H 12,000
MCW518H 18,000 Yes Yes MCW518H 18,000
MCX518 or MCD518 18,000 Yes Yes MCX518 or MCD518 18,000
MCW512H 12,000 Yes Yes
TTT536AB0E/A10E MCW512H 12,000
MCW512H 12,000
MCX512 or MCD512 12,000 Yes Yes
TTT536AB00/A100 MCX512 or MCD512 12,000
MCX512 or MCD512 12,000
MCX512 or MCD512 12,000 Yes Yes MCX524 or MCD524 24,000
MCW512H 12,000 Yes Yes MCW524H 24,000
MCW509H 9,000 Yes Yes
TTT536DB0E/D10E MCW509H 9,000
MCW518H 18,000
TTD518AB0E/A10E
TTD521AB0E/A10E
TTD524AB0E/A10E
TTD524AB00/A100
TTD536AB0E/A10E
TTD536AB00/A100
TTD536DB00/D100
TTD536DB0E/D10E
Page 5
MS-SVN005-EN
5
Table 1.1 : TTT/TTD Multi-Split Condensing Unit with
Contura 3G Hi-Wall Indoor Unit
Model Model Nominal 50 Hz 60 Hz
Outdoor Unit Indoor Unit Capacity
Btuh
MCW509K 8,600 Yes Yes MCW509K 8,600
MCW509K 8,600 Yes Yes MCW512K 11,000
MCW512K 11,000 Yes Yes MCW512K 11,000
MCW507K 7,000 Yes No
TTT521AB0E MCW507K 7,000
MCW507K 7,000
MCW509K 8,600 Yes Yes
TTT527AB0E/A10E MCW509K 8,600
MCW509K 8,600
MCW509K 8,600 Yes Yes
TTT530AB0E/A10E MCW509K 8,600
MCW512K 11,000
MCW509K 8,600 Yes Yes
TTT533AB0E/A10E MCW512K 11,000
MCW512K 11,000
MCW518K 17,000 Yes Yes MCW518K 17,000
MCW512K 11,000 Yes Yes
TTT536AB0E/A10E MCW512K 11,000
MCW512K 11,000
MCW512K 11,000 Yes Yes MCW524K 21,000
MCW512K 11,000 Yes Yes MCW526K 24,000
MCW509K 8,600 Yes Yes
TTT536DB0E/D10E MCW509K 8,600
MCW518K 17,000
TTD518AB0E/A10E
TTD524AB0E/A10E
TTD521AB0E/A10E
TTD536DB0E/D10E
TTD536AB0E/A10E
Page 6
6
MS-SVN005-EN
Indoor Unit 507 509 512 518 524/526
Item O.D. O.D. O.D. O.D. O.D.
mm (in) mm (in) mm (in) mm (in) mm (in)
Deoxidized Annealed (L*) 6.35 (1/4) 6.35 (1/4) 6.35 (1/4) 6.35 (1/4) 9.52 (3/8)
Copper Tube (S*) 9.52 (3/8) 9.52 (3/8) 12.7 (1/2) 12.7 (1/2) 15.88 (5/8)
Installation Requirements
Table 2 : For Convertible (MCX), Concealed (MCD) and Hi-Wall (MCW, Frio) Indoor units
1. Copper Tubing
Copper tubing, fittings and insulation to interconnect the suction (S) (wide tube) and liquid (L) (narrow tube) refrigerant lines between the indoor and outdoor units can be purchased locally. It is necessary to purchase the following items:
- Purchase equal lengths of both tubes and insulation required. Cut the appropriate tube lengths, 30 to 40 cm (12 to 16 in.) longer on each one to deepen vibration between units. Wall thickness of copper tube should be 0.8 mm (0.0314 in.). Both tubes must be well insulated with proper insulation materials.
- The length of wiring will determine the wire size. See local codes, refer to section of electrical installation.
2. Additional Materials
- Saddles or clamps to hold refrigerant tubing.
- Insulated clamps or staples for connecting wire. See local codes.
- Refrigeration oil and tape (armored).
- Putty or similar filter.
*On Cooling Mode
Indoor Unit 509 512 518 524
Item O.D. O.D. O.D. O.D.
mm (in) mm (in) mm (in) mm (in)
Deoxidized Annealed (L*) 6.35 (1/4) 6.35 (1/4) 6.35 (1/4) 9.52 (3/8)
Copper Tube (S*) 9.52 (3/8) 12.7 (1/2) 12.7 (1/2) 15.88 (5/8)
Foamed Polyethylene Diameter : According to O.D. of copper tube
Insulation Thickness : No less than 8 mm (0.3 in)
Insulated Copper Wire Length required to make electrical wiring
Table 3 : For Hi-Wall (MCW, Contura 3G) Indoor units
*On Cooling Mode
Page 7
MS-SVN005-EN
7
Location and Preparation of Units
1. Choose a place as cool as possible. The place should be well ventilated and the inlet air should not hotter than the outside temperature (max 45OC or 113OF).
2. Avoid the vicinity of heat sources, exhaust fan, etc.
3. Avoid direct sunlight, provide awnings if necessary.
4. The unit should be set on a level reinforced concrete pad to avoid the effect humidity. The minimum height of the concrete pad should be 100 mm. (4"). Unit shall be fixed securely to the concrete pad with bolts (not supplied) to prevent abnormal noise and vibration.
5. The concrete pad must be positioned a minimum of 200 mm. (8") from any well and surrounding shrubbery.
6. Minimum clearance on the inlet air side of the unit must be 250 mm. (10") : 1200 mm. (48") on the discharge air side of the unit and 250 mm. (10") on the tubing side of the unit (Figure 1).
7. When the unit is mounted on a roof, be sure the roof will carry the unit’s weight. Vibration isolation is recommended to prevent transmission to the building structure.
Note
The Multi-Split System (Outdoor) Unit should be installed as close to the indoor units as possible.
Figure 1
Air Discharge Air Inlet
200 mm (10")1,200 mm (48")
250 mm (10")250 mm (10")
Page 8
8
MS-SVN005-EN
Connection of Refrigerant Tubing
Table 4
Tube Diameter Tightening Torque
mm. in. kg - cm lbs - in.
6.35 (1/4) 150 - 200 (130 - 170)
9.52 (3/8) 350 - 400 (300 - 340)
12.70 (1/2) 500 - 550 (430 - 470)
15.88 (5/8) 600 - 650 (520 - 570)
1. The principal concerns in refrigeration tubing are:
- Uniform oil return to the compressor.
- Pressure drops and their effect on system capacity.
- Tube routing and isolation to avoid line breakage, vibration and sound transmission. Regarding this, the interconnecting refrigerant lines should be simple and shorter as much as possible.
2. Flare Connections
The units reported in this manual employ the flare method to interconnect refrigerant tubes between indoor and outdoor units (Figure 2).
- The tube end of all refrigerant tubes should be flared, the tube should be cut and deburred. Be sure no copper scraps fall in to the tube.
- Be sure to fit a cap to the open end of the tube to keep it free of dust and moisture.
- Avoid bending the tube. If it is necessary, bend it gently, with a radius of more than 3 or 4 cm. (1 1/2 in. or 1 5/8 in.)
- Cut approximately 30 to 50 cm. (12 in. to 20 in.) longer than estimated tubing length.
- Before flaring remember to fit the nut.
- Ream with tube end downward to avoid copper scraps inside the tube.
- Remove the flare caps on the tube end.
- Connect the tubes by aligning the centers of both flares and turn the flare nuts by hand 3 or 4 turns (Figure 3).
3. Insulate both lines, liquid (narrow tube) and suction (wide tube), to prevent heat loss and wet floor due to dripping of chilled condensation. Apply proper insulation material, minimum thickness should be 8 mm (1/3 in.) (Figure 4).
Note
Do not try to bend the tube after installation.
4. Finish with armoring tape. Also see section of condensate drain piping.
Note
Apply refrigeration oil on flare and union surfaces before connecting them. This will reduce refrigerant leakage.
- Check the tubing connections and refrigerant lines before applying specified torque. Fasten flare nuts as recommended below.
Figure 4
Figure 3
Figure 2
Electrical Connection
Service Port
Valve Cap
Tube Connection (Flare)
Liquid Line System # 1 Gas Line System # 1
Liquid Line System # 2 Gas Line System # 2 Liquid Line System # 3 Gas Line System # 3
Union
Flare nut
Insulation Thickness
Min. 8 mm Min. 8 mm (1/3 in.)
Page 9
MS-SVN005-EN
9
Condensate Drain Piping
Figure 5
Drain
1. The drain hose should come straight down the wall to a level where runoff will not stain the wall.
2. There should be no traps and avoid putting the end of the hose in water.
3. To avoid damage to the floor or furniture when the drain hose is placed in the room, insulate the hose with foamed polyethylene or equivalent.
4. After completing refrigerant lines, wining and drain connection, bind the tubing, wining and drain pipe (check if local codes permit it) into a bundle by using tape at 100 or 200 mm (4 in. or 8 in.) intervals. Make sure the drain tube is at the bottom of the bundle (Figure 5).
Page 10
10
MS-SVN005-EN
System Evacuation and Purping
The outdoor unit is factory charged. Unit nameplate charge is the total required system charge with 7.5 meters of interconnecting lines. Since the outdoor unit will not have to be evacuated unless charge has been completely lost, leave the suction and liquid shut-off valves closed.
1. Upon completion of installation, evacuate the refrigerant lines and indoor coil (Figure 6).
2. Evacuate unit until the gauge reads 350 microns or evacuate at least one hour for one system.
3. Close off valve to vacuum pump and observe the micron gauge. If gauge pressure rised above 500 microns in one (1) minute, then evacuation is incompleted or system is leaking.
- Attach appropriate hose from manifold gauge to suction and liquid line valves service ports.
- Attached center hose of mainfold gauges to vacuum pump.
Note
Unnecessary switching of hoses and complete evacuation of all lines leading to sealed system can be accomplished by placing a “T” in manifold center hose and connecting branch hose to cylinder of R-22.
Note
Evacuate unit 2 and 3 in the same manner explained above. This completes system evacuation with a vacuum pump and the air conditioner is ready for actual operation.
Figure 6
Indoor Unit 3
Indoor Unit 2
Indoor Unit 1
System # 3 System # 2 System # 1
Service Port System #3
Suction Line System #3
Liquid Line System #3
Suction Pressure
Liquid Pressure
Vacuum Pump
Cylinder of R-22
Page 11
MS-SVN005-EN
11
Electrical Installation
Wiring and grounding must comply with national and local codes.
Wiring Important Safeguards:
- Check the unit nameplate for electrical rating. Be sure wiring is according to local codes and wiring system diagram.
- A power supply disconnect and a circuit breaker for overcurrent protection should be provided in the exclusive line.
- Connect all units electrically with ground.
- Wiring should not touch refrigerant tubing, compressor or moving parts.
- The manufacturer will have no responsibility for the problems caused by unauthorized change in the internal wiring.
- Connect wiring firmly.
- Use recommended wire length and size.
Note
- Each country has their own field wiring rules and regulations. Be sure the installation complies with local electrical codes.
- Nameplate ratings on indoor units are for “one-to-one” system installations only.
Checking the system before start up
Once the unit is installed, a check of the system is recommended before starting the units.
- Check that field connections are correctly made.
- Check that units are correctly installed and there is no tool or debris near or on top of the unit.
- Check the tubing and the connections for leaks.
- Check that unit has a proper ground wiring.
- Check for proper voltage and fuse size.
- Check electrical wire size used is as specified.
- Check all field wiring for tight connection.
- Make sure that electrical wires inside the unit do not contact with refrigerant pipes.
- Start the system and carefully observe operation.
Page 12
12
MS-SVN005-EN
Wiring Diagram
220-240/1/50 Hz 200-240/1/60 Hz
Page 13
MS-SVN005-EN
13
220-240/1/50 Hz 200-240/1/60 Hz
Page 14
14
MS-SVN005-EN
Page 15
MS-SVN005-EN
15
Page 16
16
MS-SVN005-EN
Page 17
MS-SVN005-EN
17
Dimensional Data
Models
50Hz TTT521AB0EA
Page 18
18
MS-SVN005-EN
Models
50Hz 60Hz TTT527AB0EA TTT527A10EA TTT530AB0EA TTT530A10EA TTT533AB0EA TTT533A10EA TTD536AB0EA TTD536A10EA TTD536AB00A TTD536A100A TTT536AB0EA TTT536A10EA TTT536AB00A TTT536A100A TTD536DB00A TTD536D100A TTD536DB0EA TTD536D10EA TTT536DB0EA TTT536D10EA
Page 19
MS-SVN005-EN
19
Models
50Hz 60Hz TTD518AB0EA TTD518A10EA TTD521AB0EA TTD521A10EA TTD524AB0EA TTD524A10EA TTD524AB00A TTD524A100A
Page 20
Since The Trane Company has a policy of continuous product and product data improvement, it reserves the right to change design and specifications without notice.
Literature Order Number MS-SVN005-EN 0601
Supersedes MS-SVN005-EN 0300
Stocking Location Bangkok, Thailand
Trane Thailand
7th Floor, Ploenchit Center Building 2 Sukhumvit Road, Klongtoey Bangkok 10110
Amair Limited
35 Mu 8, Poochaosamingprai Road Samrong Tai, Samutprakarn 10130
http://www.trane.com An American Standard Company
Loading...