ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES
18-DE01D1-8
AVAILABLE IN FRENCH CANADIAN (FC)
IMPORTANT —This Document is
Please return to service information pack upon completion of work.
THV1
Highboy
Vertical
Flue
customer property and is to remain with this unit.
TDF1
Downflow/
Horizontal
Front Flue
TLF1
Lowboy
Front
Flue
TLR1
Lowboy
Rear
Flue
Page 2
Installer’s Guide
▲
Safety signal words are used to designate a degree o
level of seriousness associated with a particular hazard.
The signal words for safety markings are WAR NING
and CAUTION
a.WARNING indicates a potentially hazardous situa-
tion which, if not avoided, could result in death or
serious injury.
b.
CAUTION indicates a potentially hazardous situatio
which, if not avoided, may result in minor or mod
erate injury. It is also used to alert against unsafe
practices
EXPLOSION HAZARD
Do NOT store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
Improper installation, adjustment, alteration, service, or
maintenance can cause a fire or explosion resulting in
property damage, personal injury, or loss of life.
For assistance or additional information consult a
qualified installer or service agency.
Notice to theInstaller
Installation of this oil-fired furnace
by a qualified installer in accordance with all local codes
and authorities having jurisdiction. In the absence of lo-
cal governing codes, installation shall conform to thes
instructions and to the regulations of the National Fire
Protection Association’s
Oil-Burning Equipment, NFPA 31-2001, and the Na
tional Electrical Code, ANSI/NFPA
est editions thereof
A qualified installer, also referred to in this instruc-
tion manual as a “qualified heating contractor”,
individual, oragency,properlylicensed andexpe-
rienced to install and service oil-burning equip-
ment in accordance withalllocalcodes and ordi-
nances.
.
and hazards involving only property damage
!
WARNING
:
must be performe
Standard for the Installation of
70-2002, or the lat
.
is an
.
MATERIAL AND WORKMANSHIP
This furnace was built with the highest quality materials and attention to workmanship. However, omission
and defects occasionally occur. Before insta
nace, inspect the furnace thoroughly. If missing parts
defective material, or poor workmanship are evident
report the
the furnace rating label to the seller for adjustment
model and serial numbers imprinted o
lling the fur
.
PACKAGING
A complete furnace is contained within a single pack-
age. The factory completed all feasible assembly. However certain components including draft regulator and,
if supplied, door handle, air filter(s), and air filter
rack(s), must be assembled to the furnace, or the venting system, in the field
.
r
SHIPPING DAMAGE
Material inthisshipmenthasbeeninspected at
,
the factoryand released tothetransportation
agency without known damage. Inspect exterior
of carton for evidence of rough handling inship-
ment. Unpack carefully after moving equipmentto approximate location. If damage tocontents is
n
f
ound, report the damage immediately to thede-
-
livering agency.
If this furnace was damaged during transit, please immediately request the transportation company inspect
the furnace and issue a
The party receiving the furnace should file the claim for
shipping damage.
mediately.
It is absolutely essential that a damage report be ob
tained. If a concealed damage report is not obtained, we
cannot provide assistance in recovering your claim
against the transportation company
Report anyshippingdamage im-
concealed damage report
.
SAFETY CONSIDERATIONS
The following safety practices and precautions must
followed during the installation, servicing, and opera
tion of this furnace
d
1.Use only with the type of fuel oil approved for this
furnace. Refer to the furnace rating plate
2.Install this furnace only in a location and position a
e
-
-
s
-
,
,
n
specified in these instructions
3.Provide adequate combustion and ventilation air to
the furnace space as specified in “Air for Combustion and Ventilation” (page 9), of these instructions
4.Combustion products must
Connect this furnace to an approved vent system
only, as specified in Standard for the Installation
Oil-Burning Equipment, NFPA 31-2001.
5.Always install the furnace to operate within th
furnace’s intended temperature-rise range with
duct system which has an external static pressur
within the allowable range, as specified on the unit
rating plate. Airflow with temperature rise for cf
versus static is shown in the Service Facts a
panying this furnace.
6.When a furnace is installed so that supply ducts
carry air circulated
the space containing the furnace, the return ai
shall also be handled by a duct(s) sealed to the fur
nace casing and terminating outside the space containing the furnace
7.An oil-fired furnace for installation in a residential
garage must be installed as specified in “Installation
Location” section (page 3), of these instructions
8.The furnace may be used for temporary heating
buildings or structures under construction onl
when the following conditions have been met:
a.The furnace venting system must
and installed per manufacturers instructions.
b.The furnace is controlled only by a room therm
stat (no field jumpers)
c.The furnace return air duct must be complet
and sealed to the furnace and
are in place.
d.The furnace input rate and temperature rise
must be verified to be within nameplate marking
.
e
. 100% of the furnace combustion air requiremen
must come from outside the structure
f.The furnace return air temperature range is
tween 70 and 100 degrees Fahrenheit
g.Clean the furnace, duct work, and components
upon substantial completion of the constructio
process, and verify furnace operating condition
including ignition, input rate, temperature ris
and venting, a
structions.
ccording to the manufacturer's in-
!
The manufacturer of this equipment assumes no liability for any damages resulting from unauthorized modifications made to the furnace, or any components
thereof, or improper installation of the furnace in the
field. Furthermore, any such field modifications VOID
THE WARRANTY and place responsibility for safe and
reliable operation of the furnace on those who performed the modification(s).
.
WARNING
be complet
clean air filters
.
.
of
o-
be-
INSTALLATION GUIDELINES CODES
All local codes and regulations take precedence over the
instructions in this manual and shall be followed accord
ingly. In the absence of local codes, this installation
must conform to these instructions and to the regulations of the National Fire Protection Associatio
(NFPA) publications, the
Oil-Burning Equipment, NFPA 31-2001, and the Na
tional Electrical Code, ANSI/NFPA
est editions thereof
Standard for the Installation of
70-2002, or the lat
.
INSTALLATION LOCATION
!
CAUTION
To prevent shortening its service life, the furnace
should not be used as a “Construction Heater” during
the finishing phases of construction until the requirements listed in item 8, a-g of the safety section of this
publication have been met. Condensate in the presence of chlorides and fluorides from paint, varnish,
stains, adhesives, cleaning compounds, and cement
create a corrosive condition which may cause rapid
deterioration of the heat exchanger.
Contents
y
CONTENTS
e
INSTALLATION GUIDELINES2
Location2
Clearances4
e
t
n
s
e
-
n
-
-
Downflow/ Horizontal Furnace Setup4
Air for Combustion and Ventilation5
Chimney Inspection13
Chimney Sizing13
Chimney Height13
Flue/ Chimney/ Vent Connector14
Draft Regulator1 6
Power (Side-Wall) Venting16
Duct Work and Air Conditioning17
Air Filter Mounting17
Oil Burner and Oil Nozzle Installation18
Fuel System Installation19
Electrical Connections20
!
WARNING
SUPPORT FURNACE PROPERLY
DO NOT hang the downflow/ horizontal furnace from
a structure, or surface, by any integral part or fastener of the furnace. The furnace was not designed to
support itself in this manner.
In as much as practical, the furnace should be posi
tioned near a chimney or vent and should be centralized
with respect to the air distribution system
For a utility room installation, the entrance door must
be wide enough to permit the largest part of the furnace
to pass through the doorway or allow sufficient clear
ance to permit the replacement of another appliance,
e.g. a water heater, in the room
If the furnace is installed in a residential garage, it
must be installed so the burner is located higher tha
18 inches above the floor. Also, the furnace must be lo-
cated or protected to avoid physical damage from im
pacts by vehicles.
Highboy and lowboy furnace models must rest o
sturdy, stable, and level surfaces.
The downflow/ horizontal model may be mounted on
level surface, as described above, or it may be suspended from an overhead structure or surface. If thi
model is suspended from hanger rods, support the
f
urnace from the bottom casingsurface at three
(3) places, across
the casing, near the middle of the furnace
Generally, a simple support frame for the furnace can
be fabricated from structural steel angle, threaded stee
rod, and fastener hardware, refer to Figure
the height of the support angles to level the unit in posi
tion.
both ends of the casing and acro
.
.
.
1. Adjust
-
-
n
-
n
a
s
ss
l
-
18-DE01D1-83
Page 4
Installer’s Guide
CLOSET AND ALCOVE INSTALLATION
All furnace models may be installed in a closet or alcove
on combustible flooring with specified (standard) clear
ances to combustible construction
Thehorizontal/ downflow furnace model requires
an optional combustible surface-mounting base
(model # BAYSUB10ABASEAA) for verticalinstal-
lation (i.e., downflow configuration) directly on
combustible materials, refer to Figure 2.
.
1
Recommended Support Frame for Downflow/
Horizontal Furnaces
2
DownflowFurnace Combustible
Surface-Mounting Base
Note: See Illustration on page 24 for the
dimensions of the mounting base.
STANDARD CLEARANCES
Standard clearances are mandatory minimum clear
ances from heated surfaces of the furnace to combus
tible materials to assure protection from fire hazar
during furnace operation. (Refer to the
Installation of Oil-Burning Equipment, NFPA 31-2001,
for definitions of combustible and non
terials.)
Accessib
may exceed fire protection clearances. Therefore, consider providing at least 24 inches of clearance from th
front (and the rear, for lowboy furnaces) of the furnace
to obstructions and surfaces for adequate service an
maintenance access.
ility clearances, which are typically greater
Standard for the
-combustible ma
Theminimumclearances from furnace casing
surfaces to combustible materials are
-3 inches from casing sides and rear
-
-8 inches from front casing of furnace to the close
door, with exception
*The lowboy rear flue model only requires
from front casing of the furnace to the closet door
*The downflow/ horizontal furnace requires 22
inches from front casing of the furnace to the close
door
.
-9 inches from flue pipe/ vent connector
-3 inches from casing top.
-3 inches from any side of supply air plenum.
-3 inches above supply air ducts, within
nace.
- For the downflow/ horizontal furnace only, whe
the optional combustible surface-mounting
used with the furnace in the downflow configuration,
adequate clearances from the supply end surface
the furnace casing to combustible surfaces are pro-
vided by the design of the mounting base.
Though these are approved clearances for these furnaces, space must be provided at the front (18 inches
minimum
the furnace for access, service, and replacement of the
oil burner, air filter(s), circulating air
motor
, 24 inches recommended) and at the rear
.
of:
:
3 inches
.
6 feet of fur-
blower, and fa
DOWNFLOW/ HORIZONTAL FURNACE
SETUP
The downflow/ horizontal furnace is shipped from the
factory upright for vertical installation (downflow configuration). If the furnace is to be installed lying dow
on the right-hand or left-hand side (horizontal configu-
ration), the positions of the oil burner and the fan an
limit control thermostat may have to be changed. See
Figure 3.
The horizontal furnace may be turned end for end, or
rotated, making the top into the
Figure 3. Refer to the following instructions for install-
-
ing the oil burner and thermostat
-
d
-
,
e
d
bottom, as shown in
.
t
.
t
n
base is
of
of
n
n
d
418-DE01D1-8
Page 5
Installer’s Guide
▲
▲
1
) When the furnace isinstalled in thehorizon-
tal configuration, the oil burner must
mounted in an upright position. It will be necessar
to remove the
threaded burner-mounting studs before attempting
to reposition the burner in the upright position. See
Figure 3. Trial fit the burner to the burner mount
ing plate to determine which stud to remove
tary tool with a cutting (abrasive) disk or a hacksaw
should work well to remove the stud.
A machine
w
ill substitute for the removed stud and provide
third point to secure the
burner mounting plate. Thread the bolt through the
burner-mounting flange and into the open hol
within the burner mounting plate. See Figure 3.
2)Install the flange gasket and the burner on the
mounting plate threaded studs. Using fastener
supplied in the parts bag with each furnace [use two
(2) or three (3) 5/
ers, as required], secure the
ing studs on the burner mounting plate.
3)Secure the electrical conduit of the wiring harne
to the oil
provided.
burner then cut
bolt (furnished with the parts package
16 in
. brass hex nuts and flat wash-
burner junction box with the hardware
off one (1) of the
)
burner flange to th
burner to the mount-
b
. (A ro-
ss
AIR FOR COMBUSTION AND VENTILATION
e
y
VENTILATION REQUIRED!
Relief openings in the front or top of the furnace casing should not be obstructed or blocked. These openings supply combustion and ventilation air to the fur-
-
nace.
Chloride, fluoride, iodide, and bromide
pounds when present, even in low concentrations, in air
supplied for combustion to the furnace, can result in ac-
)
celerated and severe corrosion of the heat exchanger
a
and/or the venting system. This condition can
e
with less efficient furnaces, but is more likely to happe
on furnaces with efficiencies of 80% or greater
e
s
!
CAUTION
bearing com-
occur
n
.
!
WARNING
POSSIBLE OVERHEATING!
When converting to horizontal, the high limit and fan
control may have to be moved.
Failure to do so may result in an overheating condition
leading to property damage, or loss of life.
4
) When the furnace isinstalled in thehorizon-
tal configuration, the high limit and fan control
must also
casing when the furnace is placed in the final in
stalled position, refer to Figure
If the control must be relocated, remove the cover
of the control to gain access to the mountin
screws. Remove the mounting screws and the con
trol. Insert the control into the alternate mounting
hole in the casing and mark the screw locations.
Drill pilot holes for the new screws. Install the control in the new mounting location and secure it
with the mounting screws. Replace the cover of th
control. A metal, snap-in cap is furnished with th
furnace to close the
the cabinet
be located in the upper position on the
4.
unused hole, for the control, i
.
-
g
-
e
e
n
18-DE01D1-85
Page 6
Installer’s Guide
N
here
N
AIR
RETUR
AIR
RETUR
or end) to
f
lipped end
f
0° (or
8
urnace rotated 1
f
ontal
z
iguration
f
ontal con
z
stud for
Cut mounting
Horizontal right
stud for
Cut mounting
Horizontal left
lowdirection in thehori
f
SUPPLY
SUPPLY
AIR
AIR
Insert burner
mounting bolt
Insert burner
mounting bolt
here
iguration
f
urnace con
f
t/right
f
ontal le
z
FAN/LIMIT
or hori
f
TURNED END FOR END
RELOCATE FAN/LIMIT
an/limit control
f
CONTROL AS SHIPPED
CONTROL HERE
SUPPLY
SUPPLY
AIR
AIR
low/hori
f
reverse air
A down
Horizontal leftHorizontal right
34
618-DE01D1-8
AIR
ETURN
or the
f
Horizontal leftHorizontal right
Correctlocations
AIR
ETURN
Page 7
Installer’s Guide
Highboy VerticalHighboy Vertical
16.13
14.16
25.00
24.04
47.13
58.00
31.03
20.0
0.10
0.07
4.45
6.50
1.18
22.13
20.03
4.59
10.06
L
C
6.
50
34.25
26.00
19.00
1
.
0
0
0
.8
8
6
.
0
0
1.00
4.54
3.75
* NOTE: Filter Frame
Shipped unassembled & packed in blower
compartment
(ALL DIMENSIONS ARE IN INCHES)
MINIMUM CLEARANCE TO COMBUSTIBLE MATERIALS
Furnace casing sides and rear3"
Front furnace casing to closet door18"
Furnace flue pipe / vent connector9"
THV1MO87A936, 48, V3, V5SA OUTLINE DRAWING
0.10
0.07
6.50
25.00
24.04
47.13
31.03
20.0
22.13
4.45
20.03
16.13
14.16
Supply air plenum (any side)3"
Supply air ducts within 6 feet of the furnace.3"
Furnace casing top3"
34.25
4.59
10.06
18-DE01D1-87
1.18
6.50
26.00
0.88
58.00
1.00
6.00
19.00
1.00
3.75
4.54
Page 8
Installer’s Guide
61.25
11.12
29.82
16.13
16.13
16.13
22.25
Downflow / Horizontal - Front FlueDownflow / Horizontal - Front Flue
0.75
0.75
16.13
22.25
3.23
AI
RF
L
W
O
(ALL DIMENSIONS ARE IN INCHES)
MINIMUM CLEARANCE TO COMBUSTIBLE MATERIALS
TDF1MO87A936, 48, V3, V5SA OUTLINE DRAWING
Furnace casing sides and rear3"
Front furnace casing to closet door18"
Furnace flue pipe / vent connector9"
Furnace casing top3"
0.75
Supply air plenum (any side)3"
Supply air ducts within 6 feet of the furnace.3"
closet door.
Notes:
1 The Horizontal / Downflow model requires 22" from the front casing of the furnace to the
3.23
61.25
2 Adequate clearance from the supply end surface of the furnace casing to combustible
materials are provided by the design of the accessory mounting base when used with the
Horizontal / Downflow furnace model applied in the Downflow configuration.
22.25
0.75
11.12
29.82
818-DE01D1-8
16.13
16.13
16.13
22.25
16.13
Page 9
4.54
1
.
0
0
1
0
.
8
8
6
.
0
0
Lowboy - Front Flue
0.63
10.06
10.13
47.00
20.03
12.53
2.38
2.38
2.00
4.50
40.75
0.72
22.06
20.03
17.00
1.00
3.13
3.75
6.50
L
C
Installer’s Guide
(ALL DIMENSIONS ARE IN INCHES)
TLF1MO 87A936, 4 8, V3, V5SA OUTLINE DRAWING
47.00
12.53
20.03
0.72
22.06
2.00
10.06
20.03
4.50
40.75
6.00
10.13
0.63
Lowboy - Front Flue
MINIMUM CLEARANCE TO COMBUSTIBLE MATERIALS
Furnace casing sides and rear3"
Front furnace casing to closet door18"
Furnace flue pipe / vent connector9"
Furnace casing top3"
Supply air plenum (any side)3"
Supply air ducts within 6 feet of the furnace.3"
6.50
17.00
4.54
10.88
3.13
1.00
3.75
1.00
18-DE01D1-89
Page 10
Installer’s Guide
2.05
Lowboy Rear FlueLowboy Rear Flue
1.
00
0.
88
6
.
0
0
0.63
10.06
10.13
47.00
20.03
12.53
2.38
2.00
4.50
40.75
0.72
22.06
20.03
17.00
1.00
3.13
3.75
29.845
MINIMUM CLEARANCE TO COMBUSTIBLE MATERIALS
Furnace casing sides and rear3"
Front furnace casing to closet door18"
(ALL DIMENSIONS ARE IN INCHES)
2.38
Furnace flue pipe / vent connector9"
Furnace casing top3"
Supply air plenum (any side)3"
Supply air ducts within 6 feet of the furnace.3"
Notes:
1 Lowboy Rear Flue model requires 3" from the furnace front casing to the closet door.
compounds. There are many compounds representative
of this classification of chemicals. A few common ex-
amples are listed below
-Cleaning solvent
- Varnish and paint remover
-Bleaches
-Fabric softener
-Water softener salt
-Tile adhesive
Avoid storing or using these chemicals within close
proximity to the furnace. In addition, avoid storing o
using any chemicals, of an unknown and possibly flammable nature, in close proximity to the furnace. If it is
necessary to store or use chemicals in the same spac
as the furnace, the area should be well-ventilated an
all containers should be sealed when not in use. If pos
sible, keep chemicals in a separate, well ventilated
room closed
The furnace shall be installed in a location within the
building that permits a satisfactory supply of air fo
combustion, ventilation, and proper operation of the
venting system. While all forms of building constructio
cannot be covered in detail in this installer's guide, this
requirement may usually be met by application of on
of the following methods in ordinary
tion. However, applicable local installation codes always take precedence and shall be followed
The content of certain pertinent passages of NFPA 31
2001 on methods to obtain and ensure adequate airflow
to the furnace has been excerpted and, in some cases
paraphrased
Standard for the Installation of Oil-Burning Equipment,
NFPA
31-2001, for special cases and further details.
1.Ut
ility Room (example of a confined space)
a.In buildings of conventional construction with
normal air infiltration, two (2) permanent open
ings connecting to a well-ventilated crawl space,
attic, or another large, well-ventilated interna
area shall be provided. Each opening shall have a
minimum free area of one (1) square inch pe
1000 BTUH of total input rate (sum of the individual appliance input rates) of all appliances t
be installed in the ut
should be located near, or in, the ce
room and the other should be located near, or in,
the floor.
s
off from the furnace with a door
below for reference purposes. Consult the
.
s
s
s
d
.
n
building construc-
.
ility room. One opening
iling of the
b.In
buildings of
those having continuous water vapor
tightly-fitting, or weather-stripped, doors and
windows; and gasketed, caulked, or sealed outer
wall joints and penetrations), wherein infiltratio
and air exchange with the outdoors is very limited (0.35 air changes per hour, or less), provision
must be made to provide sufficient air for combustion. The following method will usually be ad
equate to ensure sufficient airflow into the space
Provide two (2) permanent openings, one (1) located
within 12 inches of the floor and one (1) within
r
inches of the ce
ings shall allow for direct exchange of air
room and outdoors. If required, ducting
e
room and the outdoors shall be provided
-For horizontally -oriented ducts, each opening shall
-
have a minimum free area of one (1) square inch per
,
2000 BTUH of the total input rate (sum of the individual appliance input rates) of all appliances to be in
stalled in the room
r
-For vertically -oriented ducts, the minimum free are
may
be reduced to one (1) square inch per
BTUH of the total input rate (sum of the individual
appliance input rates) of all appliances to be installe
e
in the room.
-The minimum dimension of any air opening shall not
be less than 3-inches
- When an opening in the outside wall must
-
vided, it should
metal sleeves.
,
2.Full Basement (example of an unconfined space)
a.Where a furnace is installed in a full basement,
in a building of conventional construction wit
normal air infiltration, infiltration is normally adequate to provide air for combustion and ventila
-
l
r
o
tion.
b.In buildings of unusually tight construction (suc
as those where weather stripping and storm sas
windows are used, and where basement window
are also weather-stripped), one (1) permanent
opening connecting to a well-ventilated attic, or
with the outdoors shall be provided, using a duct
if necessary. This opening shall have a minimu
free area of one (1) square inch per 5000 BTUH
of total input rate (sum of the individual appli-
ance input rates) of all appliances to be installed
in the basement.
When an opening in the outside wall must
vided, it should be furnished with properly screened
metal sleeves.
unusually tight construction (e.g
barriers
iling, or roof, of the room. These open-
between th
between th
.
.
.
be furnished with properly screene
12
4000
be pr
be pr
.
;
n
-
.
e
e
-
a
d
o-
d
h
-
h
h
s
,
m
o-
1218-DE01D1-8
Page 13
Installer’s Guide
P
for pitched roofs
If an exhaust fan, additional air consuming machines
(e.g. an air compressor), or a return air grill is presen
in the furnace room, there should
about providing adequate airflow to the furnace. Addi
tional efforts may be required to assure an adequat
supply of combustion and ventilation air is available to
the furnace under all conditions
CHIMNEY INSPECTION
The chimney, vent, or any passageway for the stac
gases to flow to the outdoor atmosphere is a very im
portant part of the heating system. No furnace, regard
less of the efficiency of the design, can perform satisfa
torily when the chimney to which it is connected is in
adequate or in poor condition
Any of the following symptoms may indicate a chimney
has severe structural damage and is unsuitable for use:
-Chimney appears to be leaning to the side.
-Chimney appears to have structural damage, i.e
loose or missing blocks or bricks, or excessive deteri
ration at mortar joints
-Tile liner damaged or missing
-Flue gas leakage along the length of the chimney be-
tween the chimney connector and discharge termination.
-Excessive corrosion at the cleanout port or at th
chimney connector entrance into the chimney
-Structural debris, i.e. mortar or tile liner flakes, in
base of the flue way
A qualified person shall inspect the chimney to confirm
it is correctly sized for the application, properly constructed, and in sound condition
for the Installation of Oil-Burning Equipment, NFPA
2001, for details on proper chimney sizing and construction. If needed, the chimney should be cleaned before
insta
lling the furnace
bris at the bottom of the flue should be removed.
CHIMNEY SIZING:
The furnace must be connected to an adequate chimney
or an approved vent in a
tions. An adequate chimney is one that is sealed and
lined with the capab
draft and having the capacity to handle the amount of
stack gases that are introduced into it. A chimney wit
an internal construction of corrosion resistant tile
stainless steel, or some other material that w
stand flue gas temperatures up to
The following are common chimney requirements necessary for the furnace to operate correctly
A masonry chimney serving an oil fired furnace mus
comply with local codes and NFPA
neys, Fireplaces, Vents, and Solid Fuel Burning Appli
ances (NFPA211-1996 or latest edition)
All installations and services must be
performed byqualified service personnel.
.
.
. Any accumulation of dirt or de
ccordance with these instru
ility of producing a (-)
be increased concern
.
.
.
. Refer to the
.04" WC flu
900°F is required
Standard for Chim-
.
.
Standar
ill with-
.
k
c-
o-
31
c-
h
The inside area of thechimneyliner should
t
equal
the furnace
-
EXAMPLE: π x r2 = Area of Pipe (s
e
-
NOTE: This formula calculates the minimum inside
-
area of the chimney. If more than one appliance vent
connector pipe is connected to the chimney, the mini-
-
mum inside area of the chimney should be equal to the
area of the largest vent pipe plus one half the area of
any additional vent pipes. If the chimney is too large or
condensation has been a problem in the past refer to
the NFPA Standard for the Installation of Oil Burning
Equipment (NFPA31-1997 or latest edition) Appendix E
.
for proper liner sizing.
CHIMNEY HEIGHT:
The chimney shall terminate at least
highest point where it passes through the roof of a
building and at least 2 feet higher than any portion
a building within a horizontal distance of
Fig
e
If the chimney penetrates a r
from a ridge, wall or parapet, a minimum of
above r
Figure 5b.
d
5
-
-
e
,
:
t
-
at minimum, the area of the vent pipe exiting
,
-
q. in.)
r = radius of pipe
π
= 3.1417
Flue Pipe Diameter = 6" [Radius of pipe =
diameter of pipe =
π
x 32 = 28 sq. in
. 5a)
.
oof or exit point must be maintained. S
( (6 in.) =
.
3 feet above th
oof more than
3in.]
10 feet. (S
roper chimney termination height
10 fee
3 fee
e
of
ee
t
t
ee
18-DE01D1-813
Page 14
Installer’s Guide
▲
P
s.
Proper insertion of the vent connector in chimney.
Suggested method to improve chimney draft.
If the roof is flat rather than the normal residentia
Pitched r
oof, refer to Figure
6 for proper clearances
.
FLUE/ CHIMNEY/ VENT CONNECTOR
!
CAUTION
PROPER VENTING REQUIRED!
DO NOT install a manual damper in the chimney or
vent connector.
Thermally-activated type vent dampers are NOT ALLOWED for use on these furnaces.
It is desirable to install the shortest vent connector
(also referred to as a flue or chimney connector) pos-
sible with the fewest number of fittings, i.e. transitions
and elbows.
6
l
7
venting system must be supported at least every five (5
feet with metal straps to prevent sagging of the ven
piping.
Secure all joints in the vent connector with sheet meta
screws or equivalent fasteners.
The vent connector pipe should extend only to (an
not
beyond) the inside wall of the chimney (See Fig.
8).
A thimble should be used to connect the vent
connector pipe to the chimney so that the ven
connector pipe may be readily removed in case of
inspection or replacement
.
)
t
l
d
t
roper chimney termination height for flat roof
Generally, 6-inch diameter
wall, lock seam-type, galvanized steel vent pipe and fit
tings are satisfactory materials for the fabrication of a
vent connector.
However, always consult local codes and authorities fo
specific minimum requirements
For some installations, it may be prudent to turn th
furnace flue elbow 90 degrees clockwise, with respect t
the front of the furnace, such that the elbow is open t
the right-hand side of the unit, rather than upward.
Turning the flue elbow may better fac
of the vent connector piping to the flue elbow on th
highboy. See Figure
and limit control and the wiring harness, the elbow
may not be rotated 90 degrees counterclockwise.
The installer must remove the upper right hand knock
out to allow the vent connector to pass through the
cabinet
If desired, with the furnace flue elbow turned to th
right, the standard furnace top front panel may b
replaced with a BAYTRM10AVENTAA. It includes to
front panel and a vent trim ring. Contact your
distributor to purchase this part
All horizontal sections of the vent connector must slop
upward not less than
the vent termination. Long horizontal sections of the
.
7. Due to the presence of the fa
inch per foot from the furnace t
, 24 Ga. or heavier, single
.
ilitate connectio
.
-
r
e
In cases where the chimney extends to the
o
floor, the draft can usually be improved by filling the
o
base of the chimney with sand to within 12 inches of
the vent connector pipe after relocating the clean-ou
n
door. (See Fig
e
n
-
e
e
p
All joints of the chimney must be tightly sealed. The
e
inside of the chimney should
o
obstructions, such as loose
tile, or corroded metal
. 9).
be free of an
brick
, broken pieces of
.
basemen
8
t
t
9
y
1418-DE01D1-8
Page 15
All chimney clean-out doors and flue connections
nt
composed of combustible material.
A
d
clearances to combustible materials.
must fit tightly so they will seal to avoid air leaks
.
If chimney flues are divided or there are multipl
flues within one chimney, make sure there are no
openings in the partition separating the divided or
individual flues.
The vent connector pipe must not pass through
combustible wall or partition unless adequate
protection is provided at the passageway. A
n
acceptable passageway could be either an approved,
ventilated metal thimble which is at least
12 inches
larger in diameter than the vent connector pipe, o
brick work which is at least 8 inches thick
constructed into the wall and surrounding the ven
connector pipe. (See Fig. 10).
Installer’s Guide
e
a
r
t
q
0
Suggested method to acommodate ve
connector passage through a wall
The vent connector pipe
chimney shall be of equal diameter as the flue outle
of the furnace
.
The vent connectorpipemustbemadeof 24
gauge (orthicker) corrosion-resistan t steel.
The vent connector pipe should be as short a
possible and installed so that it has a continuous rise
from the furnace to the chimney. The horizonta
length of a connector to a natural draft chimney o
vent serving a single appliance shall not be more
than 75 percent of the height of the vertical portio
of the chimney or vent above the connector. Elbow
should be minimized and the pipe should be joined
with metal screws and supported by straps. A
horizontal runs of vent connector pipe should
pitched upward a minimum of 1/4 inch per foot
run.
A thimble should be used to connect the vent
connector pipe to the chimney so the pipe may
readily removed in case of inspection or replacement.
See Fig. 10.
between the furnace an
b
of
b
lternate construction that allows reduce
Reduction of Clearances with Specified Forms of Protection
Typ e o f P rotect ionAl lowab le Cle arance wit h
Applied to and covering all
surfaces of combustible material
within the distance specified as
the required clearance with no
protection. See Figure 11.
d
a. 3 -1/2" thick masonry wall
t
without ventilation air space.....
b. 1/2" insulation board over 1"
glass fiber or mineral wool
batts.....
s
c. 0.024 (24 gauge) sheet metal
over 1" glass fiber or mineral wool
l
batts reinforced with wire on rear
face with ventilated air space.....
r
d. 3 - 1/2" thick masonry wall with
n
ventilation air space.....
s
e. 0.024 (24 gauge) sheet metal
with ventilated air space.....
ll
f. /2" insulation board with
e
ventilated air space....
g. 0.024 (24 gauge) sheet metal
with ventilated air space over
0.024 (24 gauge) sheet metal with
e
ventilated air space.....
h. 1" glass fiber or mineral wool
batts sandwiched between two
sheets 0.024 (24 gauge) sheet
metal with ventilated air space
A. Equal the required clearance with no protection.
B. Equals the reduced clearance permitted in accordance with the
preceeding clearance chart.
C. The protect ion applied to the constr uction that covers the
combustible material should extend far enough in each direction
to make C equal to A.
Specified Protection (in.)
Where the required clearance
with no protection from the
appliance or chimney
connector is: 9 inches
AboveSides & Rear
---6
65
53
---6
53
53
53
53
18-DE01D1-815
Page 16
Installer’s Guide
▲
▲
PREVENTION OF CHIMNEY CONDENSING:
!
WARNING
PROPER VENTING REQUIRED!
Improper venting may lead to condensation in the
chimney. This may result in property damage, injury,
or loss of life. To prevent condensation refer to NFPA
31 Section 6 and Appendix E.
Stack gas may do one of two things as it escapes u
the chimney
A. Remain entirely in a gaseous state if the interna
chimney wall temperature is above the dew point, or
B. Condense water vapor on the chimney walls if the
are chilled below the dew point.
Condensing will always
temperatures are below the dew point
condensate may evaporate when the walls war
above the dew point. If the chimney wall temperatur
does not exceed the dew point during the heating
cycle of the furnace, the moisture may accumulate in
large enough quantities to cause problems such a
corrosion of a metal chimney (especially plain steel o
galvanized steel), erosion and break up of a tile liner
in a masonry chimney and, in severe cases, corrosio
of the heat exchanger. Condensate also could enter
the home through cracks or joints in the chimney in
a worse case situation.
Condensation most likely w
of the chimney
chimney walls as it rises and the bottom w
heated first. This heating of the walls will cause the
stack gas temperature to drop, which in turn may
reduce the stack gas temperature below dew point
causing condensation to appear on the upper part of
the chimney first. This condensation may then r
down inside the chimney and drip back as far as th
flue pipe and heat exchanger, where corrosion ma
occur, if not treated.
:
occur on chimney walls whose
, but the
ill not occur at the bottom
because the stack gas heats the
ill
m
n
b
un
To prevent condensation, it is necessary that th
internal chimney wall temperature always
above the dew point. If the chimney is a masonry
type, it may have to
the temperature loss is too great for the furnace. If
the chimney is a metal type, then an “all fuel”
chimney must be used, such as a Class “A” triple wall
or insulated metal chimney. A liner w
p
insulator and reduce the stack gas temperature loss.
Insulation may be added around the liner for further
l
temperature stability. If the chimney is on th
home’s exterior or passes through a sizable,
y
unheated area of the
ceiling attic, etc., and condensing
chimney must be insulated around its exterior t
help the flue hold its temperature. Also, check to see
if the chimney is too large for the furnace and other
e
appliances connected to it. If so, reduce to proper siz
(see Appendix E of NFPA31) by lining. Be sure to us
stainless steel liners, such as stainless types 430, 304,
s
or for the toughest corrosion problems, type 316. If
r
the chimney is the correct size for the unit an
condensing still occurs, then insulating the vent
connector and/or reducing the efficiency of th
furnace may have to
temperature
More detailed information may
latest edition of the
Equipment Handbook
e
Should the previous reco
information obtained from the ASHRAE Handbook
fail to resolve a condensation problem, anothe
,
alternative to consider is power side wall venting.
.
be fitted with a flue liner, whe
building, such as a porch, hig
be done to raise the chimne
be obtained from th
ASHRAE HVAC Systems an
.
mmendations and th
be kept
ill act as an
occurs, th
DRAFT REGULATOR
A
barometric-type, draft regulator is supplied with the
e
furnace. Installation or operating conditions that pro-
y
duce excess amounts of draft can reduce the heating ef-
ficiency of the furnace. The purpose of the regulator is
to adjust and control the flow of flue gases from the fur
nace by stab
which the furnace is subjected.
Generally, install the
vent connector as close as possible to the flue outlet collar of the furnace. However, always refer to the draft
regulator manufacturer’s installation instructions for
application specific recommendations.
ilizing the amount of chimney draft t
barometric draft regulator in the
POWER (SIDE-WALL) VENTING
!
CAUTION
The manufacturer will NOT assume responsibility for
damage to, and deterioration of, exterior building materials, e.g. brick, siding, clapboards, and etc., in close
proximity to the vent terminal due to operation of a
power vented, oil furnace. This policy is applicable regardless of the cause of sooting.
e
n
e
h
e
o
e
e
d
e
y
e
d
e
r
-
o
1618-DE01D1-8
Page 17
Installer’s Guide
▲
▲
Two (2) problems typically arise when power ventin
any oil fired appliance:
1)Soot
2)Severe damage may occur to external surfaces
NOTICE: The manufacturer recommends the use of a
chimney to vent residential oil furnaces. If a power venter must be used, it is the responsibility of the installer
and power venter manufacturer to design, assemble,
and demonstrate proper operation of the power venting system with the furnace.
buildup may
critical components of the furnace oil
the primary control flame sensor (“cad cell”), the
burner head, and oil nozzle.
the structure in the event the furnace continually
produces a high level of smoke in the flue gases
Excess smoke and soot can
reasons, some of which cannot be successfully con
trolled by the installer and the appliance manufa
turer
.
occur at an accelerated rate o
burner, e.g.
be produced for many
n
of
c-
DUCT WORK AND AIR CONDITIONING
Air duct systems should
with standards for air conditioning systems, Nationa
Fire Protection Association Pamphlet No
should be sized in a
or whichever is applicable.
All furnaces are tested over a range of external static
pressure that simulates the airflow resistance of the
ductwork, fittings, and diffusers connected to the furnace for a typical (average) duct system. The furnace
blower and blower motor have
successfully against the following range of duct system
resistance.
Reco
mmended range of duct system resistance for all
models:
Due to the need to maintain an adequate supply of com
bustion and ventilation air, the furnace shall not be installed in a
tem
A duct the full size of the furnace return air openin
shall extend to a location outside the furnace room.
If the furnace is used in connection with cooling/ hea
pump systems, a 3 " minimum long transition must
installed between the furnace supply air outlet and the
evaporator coil supply air inlet to prevent overheatin
of the evaporator coil drain pan. See page
layout and dimensions
.
0.2 to
0.5 in. W.G. external static pressure
small room without a return air duct sys
!
OVERHEATING HAZARD!
Failure to maintain a minimum of 3" separation from
the furnace heat exchanger and the evaporator coil
drain pan may cause drain pan damage.
be installed in accordance
. 90. They
ccordance with ACCA Manual
been selected to wor
.
10 for specifi
.
WARNING
D
b
g
If the furnace is used in connection with summer air
conditioning (cooling), the furnace should be installed i
parallel with, or on the upstream side of, the evaporator
coil to avoid water vapor condensation in the furnac
heat exchanger.
If the
cooling unit is installed in a parallel flow arrange
ment, dampers (or other means used to control airflow)
should be provided to prevent ch
.
the furnace. If such a damper is manually operated, i
must be equipped with a means to prevent operation
-
either unit, unless the damper is placed in either th
full heat or full cool position
NOTICE: Return air grilles and supply registers in the
air distribution system should never be obstructed.
illed air from entering
.
AIR FILTER MOUNTING
!
CAUTION
POSSIBLE CASING DAMAGE!
If cutting openings in the furnace casing is required,
DO NOT cut any supporting clips or angles. Cut as
close to the scribed line as possible, but DO NOT cut
the base clip or blower pan support angle.
l
Lowboy furnaces are factory-equipped with cleanabletype, air filters located above the blower compartment
in the rear of the furnaces. Highboy furnaces ship with
an external filter rack & cleanable-type filter
NOTICE: Downflow/ horizontal furnaces are not factoryequipped with an air filter or filter rack.
Furthermore, the furnace
k
not contain enough free space to permit an air filter to
be mounted within the furnace casing. The installe
should supply, or fabricate, a filter rack and mount a
air filter in the return air plenum above, or upstream
of, the furnace blower compartment.
-
w
-
g
t
e
g
c
Cutaway view of fan section o
a typical highboy furnace.
On the highboy furnace, it is necessary to cut the re
turn air opening in the lower side, or rear, of the casing
depending upon the needs of the specific installation, re
fer to Figure
12.
blower compartment doe
.
f
n
e
-
t
of
e
,
s
r
n
-
-
18-DE01D1-817
Page 18
Installer’s Guide
▲
The side casings have each been pre-punched with four
(4), square, knockout openings for use in locating the
proper position for the return air filter rack. On the
side of the furnace, where the return air duct will attach, scribe a line connecting the outside edges of th
knockout openings to form a rectangle
Using a punch, or a large screwdriver, and a hammer
remove the knockouts and cut the return air openin
in the casing
Sheet metal shears, or a power metal cutting tool, w
be required to cut the casing
Position the open end of the filter rack to the front of
the furnace to permit access for filter replacement
Align the filter rack with the rectangular hole and
mark the locations on the casing of the pre-punche
mounting holes in the filter rack flange. Dr
holes in the casing and permanently attach the filter
rack to the furnace with screws, or pop-rivets (thes
fasteners are not included). Connect the return air ple
num to the filter rack and slide the air filter into posi
tion.
.
.
.
ill
ill pilo
OIL BURNER AND NOZZLE INSTALLATION
!
CAUTION
FUEL REQUIREMENT!
This oil furnace is designed to use No. 2 distillate
fuel (home heating) oil only.
This furnace is designed to utilize the following spe
cially modified, oil burner
-R.W. Beckett Corp. model AF
#EFL-
101.
NOTICE: NO other burners may be used in this application.
The heat output from the furnace is fixed
size of nozzle installed in the oil
input rates are permissible:
and
140,000 BTUH
Nozzle selection (i.e. heating capacity of the furnace
shall be based on a rate of heat loss (heating load) cal
culation for the
made according to the manuals provided
Conditioning Contractors of America (ACCA) or the
American Society of Heating, Refrigeration and Air
Conditioning Engineers, Inc. (ASHRAE)
Refer to the
from the ACCA, and the ASHRAE Handbook Funda-
mentals volume, from ASHRAE, for the recommended
procedure to compute the design heating load of a resi
dence
.
building. These calculations should
Residential Load Calculation, Manual J,
:
burner, specificatio
, based on th
burner. Four (4) hea
84,000, 105,000, 119,000,
.
b
by the Ai
.
The oil burner was installed in the furnace at the factory. In the field, if it is necessary to adjust the heating
capacity of the furnace by changing the oil burne
nozzle, refer to the following instructions. Also, consult
e
the oil burner manufacturer’s operating instructions
(included with the burner) for detailed instructions o
,
this procedure
g
1)The oil nozzle is factory installed in the oil
The gun/electrode assembly with nozzle may
moved from the rear of the
out removing the oil burner from the furnace.
To access the gun/ electrode assembly, loosen two
.
d
t
e
-
-
-
n
e
t
(2) machine screws and clamps holding the
ignition transformer in position. Rotate the trans-
former forward and out of the way.
2)Install an appropriate replacement nozzle of the cor
rect size, spray angle, and spray type.
3)The furnace may have
in transit. Under some conditions, the combustion
chamber can shift out of position. Check for prope
alignment of the burner air tube with the circular
opening in the combustion chamber and trial fit th
burner to check the insertion depth of the o
burner into the combustion chamber
The end of the
no farther than
face of the combustion chamber, refer to Figure 13 .
Do not allow the
cally touch or protrude into the chamber
High temperatures in the combustion chamber ca
result in damage to the tube, the end cone, or both
A distance greater than
side chamber wall may cause flame impingemen
on the combustion chamber wall and subsequent
sooting or carbon char buildup
.
burner assembly with
been handled roughly whil
.
burner air tube should be inserted
1/4 inch
burner tube/ end cone to physi
back from the inside sur-
.
1/4 inch
back from the in-
.
e
)
-
e
r
Side view of correct burnerinsertion into
-
The oil burner provided with this furnace requires initial inspection, set-up, and proper adjustment. Refer to
this manual and the oil
ing instructions for detailed information on the following items
-Initial firing of burner
- Adjusting the burner combustion air
combustion chamber.
burner manufacturer’s operat
:
burner.
be re
burne
r
n
-
-
r
-
e
r
e
il
-
n
.
t
-
1818-DE01D1-8
Page 19
Installer’s Guide
▲
- Adjusting the fuel pump pressure
-Setting the draft contro
NOTICE: This oil furnace must be installed and adjusted by qualified oil heating dealers using calibrated
combustion test instruments to ensure safe and reliable operation of the furnace.
l
FUEL SYSTEM INSTALLATION
In situations where the oil storage tank is installed a
the same level with, or above, the burner, a single o
supply line run from the oil tank to the burner will usu
ally be adequate. No return line will be required. If the
oil tank is installed
ceeds approximately
return line are necessary. See Figure
Refer to the
Equipment, NFPA
instructions for detailed information on oil storage tank
& oil supply/ return line installation.
NOTICE: Werecommend installing ahighefficiency oilfilter, inthe oilsupplyline, capable of fil-
tering 10 to 20 microndiameter (orpreferably
smaller) particles fromthe fuel.
If available, theuseof ultra-low or low sulfur (less
than 0.0015%
spectively), no.2 fuel oilishighly recommended.
Low sulfur fuel oil can help to significantly reduce instances of
delivery system (especially the nozzle), the furnace heat
exchanger, and the flue gas venting system. Air pollut
ants emitted by the furnace and the typical malodorou
smell of oil combustion w
Connect fuel lines
Carefully follow the fuel unit manufacturer’s literatur
and the latest edition of NFPA 31 for oil supply system
specifications.
Fuel units with automatic bypass do not require a bypass plug. The burner fuel unit is shipped without the
bypass plug installed. You must install this plug on tw
pipe oil systems
Standard for the Installation of Oil-Burnin
blockage and corrosion of the oil burner fuel
below the
8-ft
31-2001, and the oil burner operating
Sand 0.0015 - 0.05%
.
burner and the lift ex
., an oil supply line and an o
14 and 15.
S,byweight, re-
ill be reduced
.
il
il
o-
Manual venting of the fuel unit is required on initial
start-up. If connecting a two-pipe fuel supply, install th
fuel unit bypass plug.
The oil supply inlet pressure to the fuel unit canno
exceed
3 psi. Install a pressure-limiting device in
a
ccordance with NFPA 31. Example: Burner is at same
level or below the level of the oil tank. WARNING
Fuel supply below thelevelof theburner –
t
When the fuel supply is below the level of the burner, a
two-pipe fuel supply system is required. See Figure
-
Depending on the fuel line diameter and horizontal and
vertical length, the installation may also require a tw
-
stage pump. Consult the fuel unit literature for lift an
vacuum capab
Fuel line installation –
g
• Continuous lengths of heavy wall copper tubing ar
reco
mmended.
use compression fittings.
• Always install fittings in accessible locations. Fuel
lines should not run against the appliance or the ceil
ing joists (to avoid vibration noise)
Never use Teflon tape on any fuel fitting. Tap
fragments can lodge in fuel line components and fue
unit, damaging the equipment and preventing prope
operation. WARNING
Fuel line valve andfilter –
• Install two high quality shutoff valves in accessibl
locations on the oil supply line. Locate one close to
the tank and the other close to the burner, upstrea
of the filter
-
Some states require these valves to
s
design for protection in the event of fire. We
reco
mmend this as good industry practice for a
installations.
e
ility
.
Always use flare fittings. Never
.
.
be fusible-handle
r
e
t
15.
o-
d
e
-
e
l
r
e
m
ll
!
WARNING
DO NOT install the bypass plug in the fuel unit if connected to a one-pipe oil system.
Failure to comply could cause fuel unit seal failure, oil
leakage and potential fire and injury hazard.
Fuel supply level with oraboveburner –
The
burner is factory equipped with a single-stage fue
unit. Connect the fuel supply to the burner with a
single supply line if you want a one-pipe syste
(making sure the bypassplug is NOT installed in
the fuel unit.)
18-DE01D1-819
l
m
Page 20
Installer’s Guide
t
SEE TABLE 1
0N PAGE 18
TWO-PIPE SYSTEM
•Install a generous capacity f
ing
between the fuel tank shutoff valve and the
burner, locating both the filter and the valve close to
the
burner for ease of servicing. Filter should
rated for 50 microns or less
TABL E 1
SINGLE STAGE, TWO PIPE
MAXIMUM LINE LENGTH
( H + R )
Lift
"H"
3/8" Tubing1/2" Tubing
3 GPH7 GPH3 GPH7 GPH
0'84'71'100'100'
1'78'66'100'100'
2'73'62'100'100'
3'68'57'100'100'
4'63'53'100'100'
557'48'100'100'
6'52'44'100'100'
7'47'39'100'100'
8'42'35'100'100'
9'36'31'100'100'
10'31'27'100'100'
11'26'22'100'87'
12'21'18'83'70'
13'--62'52'
14'--41'35'
ELECTRICAL CONNECTIONS
NOTICE: All field wiring must conform to local, state,
and national installation codes.
ilter inside the
.
3450 RPM
build-
A disconnect switch equipped with overcurrent prote
tion (e.g. a time delay-type fuse or inverse time, circui
breaker) should be installed in the service line for shutting down and protecting the furnace and electrical sys
tem
.
Since the furnace is entirely pre-wired at the factory, i
is only necessary to connect the
building electrical ser-
vice lines to the two (2) pigtail wires extending from th
fan center junction box. The fan center is mounted in
side the furnace burner compartment or mounted o
the front exterior of the furnace, in the case of th
downflow / horizontal
furnace should be no smaller than
model. The service lines to th
14 Ga
., insulated cop
per wire with a temperature rating of 60ºC, or greater.
Connect an equipment ground wire to the furnace a
the fan center junction box. If wiring is run through
metal electrical conduit, it may not be necessary to run
a separate equipment ground wire. Consult local codes
b
e
and authorities for specific minimum requirements.
VARIABL E SPE ED DI P SWIT CH SE TTING FOR C OOLIN G
The following table and graph explain the delay
COOLING OFF - DELAY OPTIONS
SWITCH SETTINGSSELECTION
5 - OFF6 - OFFNONESAME
5 - ON6 - OFF1.5 MINUTES100% *
5 - OFF6 - ON3 MINUTES50%
5 - ON6 - ON**50 - 100%
* - This setting is equivalent to BAY24X045 relay ben-
efit.
** - This selection provides ENHANCED MODE, which
is a ramping up and ramping down of the blower
speed to provide improved comfort, quietness, and
potential energy savings. See Service Facts for
cooling and heating air flow dip switch settings
1,2,3,4,7,8. The graph which follows, shows the
ramping process.
100% if necessary
80%
Dehumidify
50%
Fast Cooling
OFF
1
minute
See Service Facts for dip switch setting
for complete setup for Enhanced Mode.
7.5
minutes
Efficiency
minutes
-off settings
NOMINAL
AIRFLOW
50%
OFF
3
c-
t
-
t
e
-
n
e
e
-
t
:
2018-DE01D1-8
Page 21
Using
T
AIR
R
R
C
T
AIR
R
18 gauge control wire, connect control wiring to
thermostat as shown in the following
the thermostat does not have an isolated heating circui
(RH), then install a pilot duty rated, 24 volt, relay
(RLY00975, field supplied). This relay is shown as R1 i
the illustrations
ANSI/NFPA 70-2002, for guidelines for proper wirin
methods and materials for this circuit
. Consult the
National Electrical Code,
illustrations. I
n
.
LOW VOLTAGE HOOK UP DIAGRAMS FOR OIL FURNACE WITH PSC MOTOR
(SINGLE STAGE COOLING)
Installer’s Guide
f
t
g
SINGLE STAGE HEAT/ COOL WITH RH/ RC CIRCUIT
y
HERMOSTAT
R
C
FURNACE
FAN CENTER
CONDITIONE
B/C
OIL BURNER PRIMARY
NOTE:
Thermostat "R" terminal may be labeled as "RC" or
"RH".
SINGLE STAGE HEAT/ COOL WITH 24V RELAY
u
HERMOSTAT
FURNACE
FAN CENTER
R
1
CONDITIONE
B/C
OIL BURNER PRIMARY
R
1
NOTE:
Thermostat "R" terminal may be labeled as "RC" or
"RH".
18-DE01D1-821
Page 22
Installer’s Guide
rs
VARIA BLE SPEED OIL FURNACE CO NNECTIO N LO CATIO NS AN D LO W VOLTA GE
HOOK UP DIAGRAMS (SINGLE STAGE COOLING) WITH 24V RELAY
VARIABLE SPEE D V3, V5 L OW V OL TAG E WIRING
CONNECTIONS LOCATIONS
Route electrical power circuit through outside
furnace wall and into junction box and make high
voltage connections inside box according to the
NEC and local codes.
Low Voltage
Terminal Board
MAKE LOW VOLTAGE
CONNECTIONS HERE
Oil Burner
Primary Control
DO NOT MAKE ANY
CONNECTIONS HERE
VARIABLE SPEED OIL FURNACE SINGLE STAGE COOLING
THERMOSTAT
R
Y/
Y1
G
B
W1
ONE STAGE VS
OIL FURNACE
R1
OIL BURNER PRIMARY
R1
Y1/
Y
W3
R
W2
W1
Y/
Y2
O
B
BK
LO
G
C
SINGLE STAGE
AIR CONDITIONER
R1
Y
B
"R" to "O" and "R" to "BK" are Factory Installed Jumpe
2218-DE01D1-8
Page 23
LOW VOLTAGE HOOK UP DIAGRAMS FOR VARIABLE SPEED OIL FURNACE
V
W
R
R
G
Y/
Y1
W1
B
THERMOSTAT
VARIABLE SPEED OIL FURNACE TWO STEP COOLING
WITH 24V RELAY
R
G
W1
W2
Y1/
Y
LO
B
TWO STEP
AIR CONDITIONER
ONE STAGE VS
OIL FURNACE
B
C
Y2
BK
Y/
Y2
Y1
O
Y2
Note A - Cut/remove the factory installed "R" to "BK" jumper at the indoor unit.
W3
R1
Note A
"R" to "O" and "R" to "BK" are Factory Installed Jumpers
R1
OIL BURNER PRIMARY
(TWO STAGE/ STEP COOLING)
ARIABLE SPEED OIL FURNACE TWO STAGE COOLING
ITH 24V RELAY
THERMOSTAT
ONE STAGE VS
OIL FURNACE
TWO STAGE
AIR CONDITIONE
Installer’s Guide
Y2
Y/
Y2
W3
R
R
W2
W1
Y/
Y1
G
Y1/
Y
G
LO
O
B
R1
W1
B
C
BK
OIL BURNER PRIMARY
R1
Y2
R
Y1
B
"R" to "O" and "R" to "BK" are Factory Installed Jumpers
18-DE01D1-823
Page 24
BAYSUB10ABASEAA DIMENSIONS
DownflowFurnace Combustible
Surface-Mounting Base
Trane
6200 Troup Highway
Tyler, TX 75707
For more information contact
your local dealer (distributor)
02/09
Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right
to change design and specifications without notice.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.