Only qualified personnel should install and service the equipment.The installation, starting up, and servicing
of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and
training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or
serious injury.When working on the equipment, observe all precautions in the literature and on the tags,
stickers, and labels that are attached to the equipment.
This document and the information in it are the property ofTrane and may not be used
or reproduced in whole or in part, without the written permission ofTrane.Trane reserves
the right to revise this publication at any time and to make changes to its content without
obligation to notify any person of such revision or change.
Trademarks
Trane and its logo are trademarks ofTrane in the United States and other countries. All
trademarks referenced in this document are the trademarks of their respective owners.
Warnings, Cautions, and Notices
Warnings, cautions, and notices are provided in appropriate places throughout this
document:
WARNING: Indicates a potentially hazardous situation which, if not avoided,
could result in death or serious injury.
CAUTION: Indicates a potentially hazardous situation which, if not avoided,
could result in minor or moderate injury. It could also be used to alert against
unsafe practices.
NOTICE: Indicates a situation that could result in equipment or property-
damage-only accidents.
Note: To identify thethermostat type, locate theTrane PLM# and theTrane PLM#/TraneClarksville
The information contained in this document applies to either one or two models or to all.
Differences are noted where appropriate. If no difference between models is noted, assume that
all thermostat models share the information.
– Trane PLM # X13511537-01
– Trane Clarksville part # BAYSTAT150A
– Service parts #THT02774
– Trane PLM # X13511536-01
– Trane Clarksville part # BAYSTAT155A
– Service parts #THT02773
– Trane PLM # X13511535-01
– Trane Clarksville part # BAYSTAT151A
– Service parts #THT02772
# on the thermostat circuit board.
BAS-SVX36C-EN5
Introduction
Product Features and Capabilities
The table below shows the functional differences between the three thermostat models.
Thermostat Function or Feature
A liquid crystal display (LCD) with symbols for temperature, setpoints, and system operating
modes. The programmable thermostat also has day of the week, time of day, and occupancy
settings.
System modes: Heat, Cool, Auto, Off. Both types of 3-Heat/2-Cool thermostat also have
Emergency Heat mode.
System Configuration Options. See
• 1-heat/1-cool, conventional
• 1-heat/1-cool, heat pump without auxiliary heat
• 1-heat only, conventional without fan
• 1-heat only, conventional with fan
• 1-cool, conventional
• 2-heat/1-cool, heat pump with auxiliary heat
• 2-heat/2-cool, conventional
• 2-heat/1-cool, conventional
• 1-heat/2-cool, conventional
• 2-heat/2-cool, heat pump without auxiliary heat
• 3-heat/2-cool, heat pump with auxiliary heat
A heating and cooling setpoint range of 40ºF to 90ºF (4.5ºC to 32ºC)
Two fan modes: On, Auto
Additional configurable options (See
Terminals and configuration options for a remote temperature sensor. Options include:
• Displaying the remote/outdoor temperature on the LCD
• Using the remote/outdoor temperature to lockout the compressor or auxiliary heat
• Using the remote/outdoor temperature instead of the built-in sensor
Scheduling function with two or four periods per day and the following day/week options:
• 5/2 day schedule: weekdays share a schedule; Saturday and Sunday share a schedule
• 5/1/1 day schedule: weekdays share a schedule; Saturday and Sunday have their own,
independent schedules
• 1 day schedule: Every day shares the same schedule
• 7 day schedule: Each day has its own, independent schedule
Temporary override function with configurable override time limit
“Configuration,” p. 26 for more information:
“Configuration,” p. 26)
1H/1C Thermostat
(p/n X13511535-01)
3H/2C Thermostat
(p/n X13511536-01)
Programmable
Thermostat
(p/n X13511537-01)
6BAS-SVX36C-EN
Dimensions
Introduction
Figure 1 and Figure 2 provide dimensions for each type of thermostat.The two non-programmable
thermostats have the same dimensions; the programmable thermostat has slightly different
dimensions.
Figure 1. ProgrammableThermostat Dimensions
0.3 in.
(8 mm)
1.08 in.
3.25 in.
(83 mm)
Typ. Radius
0.08 in.
(2 mm)
(27.5 mm)
4.7 in.
(119 mm)
3.4 in.
(86 mm)
Typ.P Radius 0.08 in. (2 mm)
Note: Drawing not to scale. Dimensions within ± 0.02 in. (± 0.5 mm)
BAS-SVX36C-EN7
Introduction
Figure 2. 1-Heat/1-Cool or 3-Heat/2-Cool (non-programmable)Thermostat Dimensions
0.3 in.
(8 mm)
1.1 in.
(28 mm)
4.7 in.
(119 mm)
3.4 in.
(86 mm)
3.07 in.
(78 mm)
Typ. Radius
0.08 in.
(2 mm)
Typ.P Radius 0.08 in. (2 mm)
Note: Drawing not to scale. Dimensions within ± 0.02 in. (± 0.5 mm)
8BAS-SVX36C-EN
Pre-Installation
This section provides the following pre-installation information:
•Location considerations
•Height requirements
•Mounting surfaces
•Maximum wire length
Location Considerations
When selecting a location, avoid the following:
•Areas of direct sunlight
•Areas in the direct airstream of air diffusers
•Exterior walls and other walls that have a temperature differential between the two sides
•Areas that are close to heat sources such as sunlight, appliances, concealed pipes, chimneys,
or other heat-generating equipment
•Drafty areas
•Dead spots behind doors, projection screens, or corners
• Walls that are subject to high vibration
•Areas with high humidity
•High traffic areas (to reduce accidental damage or tampering)
Height Requirements
It is recommended that you mount the back plate a maximum distance of 54 in. (137 cm) above the
floor. If a parallel approach by a person in a wheelchair is required, reduce the maximum height
to 48 inches.
Note: Consult section4.27.3 of the 2002 Americans withDisabilityAct guideline, and local building
codes, for further details regarding wheelchair requirements.
Mounting Surfaces
The thermostat can be mounted to any sturdy, vertical surface. Plastic threaded anchors and
M3.5 x 20 mm screws are provided for mounting to plaster or wallboard; 6-32 x 3/4 inch machine
screws are provided for mounting directly to a standard electrical device box. Other fastener
varieties may be required for other surface types.
When replacing a horizontally mounted thermostat and there is an adapter kit available to cover
any opening in the wall. Contact your localTrane office for more information.
BAS-SVX36C-EN9
Pre-Installation
Maximum Wire Lengths
Thermostat to HVAC Equipment
The thermostat may not function properly if the total resistance of any of the thermostat to HVAC
equipment wires exceeds 2.5 ohms.To ensure that wire length does not cause excess resistance,
refer to
long.
Table 1.MaximumThermostat to HVAC Equipment Wire Lengths
Remote Sensor to ProgrammableThermostat
Because remote temperature sensors measure resistance, very long cable runs can cause slight
errors in the measurement. For the highest temperature reading accuracy, avoid exceeding the
maximum recommended wire lengths shown in
Table 1 and ensure that the wires from the thermostat to the HVAC equipment are not too
Copper wire sizeMaximum recommended wire length
22 AWG (0.33 mm2)150 ft (46 m)
20 AWG (0.50 mm2)240 ft (73 m)
18 AWG (0.75 mm2)385 ft (117 m)
Maximum recommended remote
Copper wire size
22 AWG (0.33 mm2)1000 ft (300 m)
20 AWG (0.50 mm2)1500 ft (450 m)
18 AWG (0.75 mm2)2500 ft (750 m)
sensor wire length
Table 2.
Note: For 22 AWG (0.33 mm2) copper wires, the rate of error can be up to 0.5 °F (0.3 °C) per 100 ,
which typically requires wire lengths in excess of 5000 ft (1500 m).
10BAS-SVX36C-EN
Installation
This section provides installation instructions.
Before you begin, read through the pre-installation information, beginning on
the following conditions are met:
•A wire access hole is available at the thermostat location.
• The wires are accessible through the hole.
• The wires are attached to the appropriate terminals on the HVAC equipment.
• There is continuity (and not more than 2.5 ohms resistance) between the thermostat location
the HVAC equipment.
and
• The wires are accurately labeled or identified by color.
Mounting the Back Plate
WARNING
Hazardous voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper
lockout/tagout procedures to ensure the power cannot be inadvertently energized. Failure to
disconnect power before servicing could result in death or serious injury.
NOTICE
Equipment damage!
Applying excessive voltage to the thermostat will permanently damage it.
p. 9, and also verify
To mount the back plate:
1. Shut off power to the HVAC equipment.
Note: If the security screw is installed, remove it before attempting to remove the cover.
See
Figure 3.
Figure 3.
2. Remove the cover by firmly pressing the thumb tab at the bottom of the cover and pulling the
3. Feed the wires through the opening in the back plate.
Security Screw Location (if used)
ver away from the back plate.
co
Security screw
BAS-SVX36C-EN11
Installation
Wiring
Figure 4. Feeding Wires through Back Plate
4. If you are mounting the back plate directly to a wall surface, hold the back plate against the
surface and mark the fastener locations.
5. Secure the back plate using appropriate fasteners. (See
thermostat must be level and plumb for accurate temperature control and to ensure proper air
movement through the thermostat enclosure.
“Mounting Surfaces,” p. 9.)The
WARNING
Hazardous voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper
lockout/tagout procedures to ensure the power cannot be inadvertently energized. Failure to
disconnect power before servicing could result in death or serious injury.
NOTICE
Equipment damage!
Applying excessive voltage to the thermostat will permanently damage it.
General Practice
To wire the thermostat:
1. Connect the wires to the terminal block(s) packaged in the box with the thermostat. (The
programmable
only one):
• R
emove approximately 1/4 inch (6 mm) of insulation from the wires.
• Use the terminal block screws to securely fasten each wire into the terminal block.
• Refer to the section,
that follow to determine the correct terminal for each wire.
Note: In
color wire to which they are connected. However, you must verify which equipment
terminals are connected at the other ends of the wires before connecting the wires to
the thermostat.
12BAS-SVX36C-EN
thermostat has two terminal blocks, the non-programmable thermostats have
“Terminal Identification,” p. 13 and the wiring diagrams on the pages
some cases the terminal labels (Y, G, R, etc.) correctly correspond to first letter of the
Installation
2. Align the pins on the circuit board with the holes on the bottom of theterminal blocks and gently
push the wired terminal blocks into place on the circuit board. See
Figure 5.
Figure 5. Attaching the wired terminal blocks to the pins on the circuit board
3. Push the excess wire through the hole in the wall cavity or into the junction box.
Important: Do
4. Use nonflammable insulation to prevent air movement between the wall cavity and the
thermostat.
Terminal Identification
The table below defines the terminals for each of the thermostat types.
1. Hook the cover over the top of the back plate. Apply light pressure to the bottom of the cover
it snaps in place.
until
2. If desired, install the security screw into the bottom of the cover. See
Figure 32.
24BAS-SVX36C-EN
Close cover - insert security screw
Security screw
Figure 32.
Applying Power
Applying power to the thermostat will initiate a power up sequence.
1. The full screen appears for 1.5 seconds.
2. The firmware version appears for 1.5 seconds:
3. Power up tests are performed.
Figure 33. Home screens
Installation
the programmable thermostat, the firmware version shows in the HH:MM digits.
• On
• On the non-programmable thermostats, the digits are split between the top and bottom
regions of the screen: the most significant digits are at the top.
an error is detected, an error code appears (see
• If
• If no errors are detected, the home screen appears (see
Mo
.
AM
.
“Error Codes,” p. 43).
Figure 33).
Programmable
thermostat
Non-programmable
thermostats
BAS-SVX36C-EN25
Configuration
NOTICE
Adverse Control System Behavior!
Improper configuration could cause unwanted, possibly adverse control system behavior. Be
sure to configure the thermostat according to your system type.
To change the installation configuration:
1. Apply electrical power to the thermostat.
2. See the appropriate table for your thermostat type to determine the configuration options you
need:
•
•
•
3. Write down your selections or other notes on the table.
4. Enter installer configuration mode:
WARNING
Live Electrical Components!
The circuit board is energized. Have a qualified licensed electrician or other individual who has
been properly trained in handling live electrical components perform this step. Failure to follow
all electrical safety precautions when exposed to live electrical components could result in death
or serious injury.
a. Remove the thermostat cover.
b. Press and hold the configuration button for at least 3 sec.
able 6, p. 27
T
for 3-Heat/2-Cool programmable thermostats
Table 7, p. 31 for 3-Heat/2-Cool non-programmable thermostats
Table 8, p. 32 for 1-Heat/1-Cool, non-programmable thermostats
Figure 34. Pressing the Configuration Button
Programmable 3H/
2C configuration
button
The configuration wrench icon
appears, along with the option number and value:
Thermostat Non-Prog XH/XC
X########-## Rev X
BAYSTAT15#X
####XXX
Non-programmable
thermostats
configuration button
Figure 35. Configuration Mode
Value
Option
Number
Non-Programmable
Programmable
Thermostat
Thermostat
Note: Configuration mode automatically ends if no buttons are pressed for 10 min.
26BAS-SVX36C-EN
Configuration
5. Press,,orto scroll through the options, identified by their numbers, until you reach
the option you want to change:
scrolls to a lower-numbered option.
orscrolls to a higher-numbered option.
6. Use
7. Repeat
8. Do one of the following to exit configuration mode:
Table 6.Installation Options for 3-Heat/2-Cool ProgrammableThermostat
No. NameDefaultOpts. Descriptions
0100 Temperature
0110 Clock format121212 hour clock
0120 Year0909-99 2009 - 2099
0121 Month11-12 Months of the year
0122 Day11-31 Days of the month
0125 Daylight savings20Disabled
0126 Spring month
0127 Spring day0801-31 The day on which the Spring daylight savings change occurs
0128 Fall month1101-12 The month in which the Fall daylight savings change occurs
0129 Fall day0801-31 The day on which the Fall daylight savings change occurs
0130 System selection811H/1C (conv) 1st Stage Heat (W), 1st Stage Comp (Y), Fan (G)
orto change the value of the option:
decreases the value.
increases the value.
Step 5 and Step 6 until you have made all necessary changes.
Note: V
alues are saved in permanent memory after setting a value and moving to next
configuration parameter, and also when you exit configuration mode.
• Remove the thermostat cover, if necessary, and then press and immediately release the
configuration button.
• Do not press any buttons for 10 min.
• Press and holdfor 2 sec.
indication/
resolution
00°F, 1 degree resolution
(1)
0301-12 The month in which the Spring daylight savings change occurs
1°F, 0.5 degree resolution
2°C, 1 degree resolution
3°C with 0.5 degree resolution
4°C with 0.1 degree resolution
2424 hour clock
1US (1987), changeover at 2:00am
2US (2007), changeover at 2:00am
3Europe, changeover at 1:00am
4Manual, changeover at 2:00am
21H/1C (HP) 1st Stage Comp (Y), Changeover (O/B), Fan (G)
31H (Conv) 1st Stage Heat (W), without fan
41H (Conv) 1st Stage Heat (W), Fan (G)
51C (Conv) 1st Stage Comp (Y), Fan (G)
62H/1C (HP) 1st Stage Comp (Y), Changeover (O/B), Auxiliary Heat (W1),
Table 6.Installation Options for 3-Heat/2-Cool Programmable Thermostat (continued)
No. NameDefaultOpts. Descriptions
0233 Scheduling mode
day options
0240 Heat
temperature
range stops
0241 Cool temperature
range stops
0260 Temperature
display offset
0270 Extended fan-on
time heat
0271 Extended fan-on
time cool
0300 Restore factory
defaults
(1) Only available if option #0125 is set to 4.
“Heat and Cool Cycling Rate,” p. 41.
(2) See
“Deadband,” p. 41.
(3) See
(4) If an external sensor is attached to the S1 and S2 terminals, it must be 10Knegative temperature coefficient.
(5) Only available for heat pump systems with more heat than cool stages and remote outdoor sensor. A 5 °F (2.5 °C) dead
band between options #0220 and #0221 will be enforced automatically.
(6) Only applies to systems with heat stages.
(7) Only applies to systems with cool stages.
(8) Only applies to control temperature and display temperature for internal and indoor remote sensor. Does not apply to out-
door temperature for display.
(9) See
“Extended Fan-on Time (Heat or Cool),” p. 42.
(10)Only available when option #0151 is set to 1.
(6)
(7)
(8)
(9)(10)
(9)(7)
001 day - Mo-Su share the same schedule
9040 - 90 40° F to 90° F
5050 - 99 50° F to 99° F
0-3–3° F (–1.5° C)
00Off
00Off
00No - do not restore
15+1+1 days - Mo-Fr share a schedule; Sa and Su each have an independent
schedule
25+2 days - Mo-Fr share a schedule; Sa-Su share a schedule
37 days - Each day has an independent schedule
4 - 32 4° C to 32° C
10 - 37 4° C to 32° C
-2–2° F (–1.0° C)
-1–1° F (–0.5° C)
0None
11° F (0.5° C)
22° F (1.0° C)
33° F (1.5° C)
9090 sec
4040 sec
1Yes - reset all installer options to default except calendar, and system
selection - options 0120-0122 and 0125-0130 do not reset.
30BAS-SVX36C-EN
Table 7.Installation Options for 3-Heat/2-Cool Non-ProgrammableThermostat
1Yes - reset all installation configurations (all settings in this table) to default
settings, except System selection
32BAS-SVX36C-EN
Operation
This section provides general descriptive and procedural information intended for typical daily
operators of the thermostat.
Icon Descriptions
Figure 36 describes the icons visible on the front of the thermostat.
Note: Except when the thermostat is powering up, when all of the icons are shown for 2 sec, only
Figure 36. Thermostat Icons
some of the icons will be visible at once.
Large numeric display - Shows current temperature but
can indicate other information.
Setpoint indicator - upper arrow
indicates cooling setpoint; lower arrow
indicates heating setpoint.
Heating mode indicator - heating, cooling,
automatic heating/cooling, or off.
Time of day - 12 hour clock with AM and PM
indicator or 24 hour clock.
Configuration/test indicator - solid for
configuration mode; flashing for test mode.
Space unoccupied indicator.
Timed override indicator
Space occupied indicator
Button lock indicator
Overview of Operation
If configured properly, bothprogrammable and non-programmable thermostats will control HVAC
equipment to maintain room temperature automatically.
.
Mo Tu We Th Fr Sat Su
DAYS
HOURS
Temperature units - F or C.
Fan mode indicator - auto or on.
Period indicator - morning, day,
evening, night.
.
AM
PM
Icons on the nonprogrammable thermostats
have the same function, but
no programming/
scheduling-related buttons
appear.
BAS-SVX36C-EN33
Operation
Non-ProgrammableThermostats
Non-programmable thermostats do not have timekeeping or scheduling capabilities.They will
continue to maintain heating and/or cooling setpoints until an operator makes changes to the
setup.Therefore, only the following tasks may be required performed:
•Change the system mode.
•Show or change the heating or cooling temperature setpoint.
•Change the fan mode.
Note: The
Changing the System Mode
Note: If you are unable to change the system mode, check thesystem typesetting and the manual/
Depending upon the model and system type, the thermostat can be set to one of five modes:
Cooling, Heating, Emergency Heat, Auto, or Off.
system mode, temperature setpoints, and fan mode can each be individually locked to
prevent users from changing them. If you see a
the setting before you change it (see
auto changeover setting (see
configured with heat and cool modes, and that it permits manually changing them.
Cooling mode cools the room to bring it down to the cooling setpoint.
Heating mode heats the room to bring it up to the heating setpoint.
Emergency Heat mode heats the room according to the heating unit’s emergency heat mode
settings.
Auto mode switches automatically between heating and cooling modes as required.
Off mode prevents the thermostat from requesting any heating or cooling regardless of the
room temperature. Off mode also disables fan selection and prevents the user from changing
the setpoint.
on the display, you may need to unlock
“Locking or Unlocking Modes,” p. 40).
“Configuration,” p. 26) to verify that the thermostat is
Note: The 1-Heat/1-Cool thermostat does not have Emergency Heat mode.
To change the system mode:
1. Press>.The current mode flashes.
2. Pressorto select a mode.
3. Tapor wait 5 sec to save and exit.
Showing or Changing the Heating or CoolingTemperature Setpoint
To change the heating or cooling setpoint:
1. Pressoronce. This shows the active setpoint.
2. Within 5 sec:
ressorto increase or decrease the setpoint.
• P
• Pressorto change between heat and cool setpoints if both are enabled.
3. Tapor wait 5 sec to save and exit.
34BAS-SVX36C-EN
Changing the Fan Mode
Note: If you are unable to see the fan mode, check the system type setting in the installation
configuration options to make sure that it is specified as a system with a fan.
There are two fan modes. Each are indicated by an icon on the display:
Auto mode turns the fan on and off as needed according to equipment configuration.
On runs the fan continuously.
o change the fan mode:
T
1. Press>>.The current mode flashes.
2. Pressorto change the mode.The selected mode flashes.
Note: If
3. Tapor wait 5 sec to save and exit.
you are unable to change the mode and
or Unlocking Modes,” p. 40
ProgrammableThermostats
Programmable thermostats contain all of the functionality of the non-programmable thermostats,
but they also keep track of the date, day of week, and time of day for scheduling purposes.
Operation
flashes, the mode is locked. See “Locking
.
Programming
This section describes how to program the thermostat after it has been installed and configured.
Setting theTime
The time must be set in the thermostat to ensure operation of the schedule.
Note: The date is set during configuration and the day of the week is calculated automatically
according to the date.
To set the time:
1. Press>>>>>.The hour flashes to indicate that it can be changed.
Mo
Note: The thermostat automatically returns to normal operating mode if no buttons are
2. Make changes to the hour and minute, as needed:
• P
• Pressorto change the value of the option.
3. Press and holdfor 2 sec or wait 10 sec to apply the change and exit.
AM
pressed for 10 sec.
ressorto switch between hours and minutes.The changeable option flashes to
indicate that it can be changed.
BAS-SVX36C-EN35
Operation
Scheduling
The thermostat can be configured for two periods (day and night) or four periods (morning, day,
evening, and night).The chosen number of periods are applied to each day of the week when you
program the thermostat. Each period canhave a unique start time, heat setpoint, cool setpoint, and
fan setting.
The groups of days can be one of the following:
•1 day = all 7 days of the week follow the same schedule.
•5+1+1 days = Monday - Friday all follow the same schedule; Saturday and Sunday each follow
their own schedules.
•5+2 days = Monday - Fridayall follow the same schedule;Saturday and Sunday follow thesame
schedule, which is different than the Monday - Friday schedule.
•7 days = Each day follows its own schedule.
Note: See “Configuration,” p. 26 tochange the number of periods in a day or the grouping ofdays
in the schedule.
If needed, you can use Table 9 to write down your schedule settings before you begin setting up
the schedule.The default schedule is also shown in the table. Unless you program your own
schedule settings, the thermostat follows the default schedule for all days of the week.
36BAS-SVX36C-EN
Operation
Table 9.Weekly Operating Schedule Worksheet
Heating
DayPeriodStart time
Four period
default settings
Two period
default settings
MondayMorning :°°Auto On
TuesdayMorning :°°Auto On
WednesdayMorning :°°Auto On
ThursdayMorning :°°Auto On
FridayMorning :°°Auto On
SaturdayMorning :°°Auto On
SundayMorning :°°Auto On
Morning 6:00 am70° F (21.0° C)78° F (25.5° C)Auto
Day 8:00 am62° F (16.5° C)85° F (29.5° C)Auto
Evening 6:00 pm70° F (21.0° C)78° F (25.5° C)Auto
Night 10:00 pm62° F (16.5° C)82° F (28.0° C)Auto
Day 6:00 am70° F (21.0° C)78° F (25.5° C)Auto
Night 10:00 pm55° F (13.0° C)85° F (29.5° C)Auto
Day :°°Auto On
Evening :°°Auto On
Night :°°Auto On
Day :°°Auto On
Evening :°°Auto On
Night :°°Auto On
Day :°°Auto On
Evening :°°Auto On
Night :°°Auto On
Day :°°Auto On
Evening :°°Auto On
Night :°°Auto On
Day :°°Auto On
Evening :°°Auto On
Night :°°Auto On
Day :°°Auto On
Evening :°°Auto On
Night :°°Auto On
Day :°°Auto On
Evening :°°Auto On
Night :°°Auto On
setpoint
Cooling
setpoint
Fan Setting
BAS-SVX36C-EN37
Operation
To set the schedule:
1. Press>>>.The display shows only the following elements:
MoTu We Th Fr Sa Su
2. Press .
Note: At
this point the thermostat is in schedule change mode. It returns to normal operating
mode if no buttons are pressed for 45 sec.To manually exit schedule change mode, press
and hold
for 2 sec.
Note: Ifflashes and you are unable toenter schedule change mode, the mode is locked. See
“Locking or Unlocking Modes,” p. 40.
3. Pressorto select the day or days for which you want to set the schedule.The selected day
or days flash.
4. Pressto accept the selection.,,,or starts flashing.
5. Pressorto select the period.The selected period starts flashing.
6. Pressto accept the selection. The start time starts flashing.
Mo
AM
7. Pressorto select the start time. Time is increased or decreased in 10 min steps.
8. Pressto accept the selection. If there is a heat mode configured, the heat setpoint appears
and its icons start flashing.
9. Pressorto select the heating setpoint.
Note: The
heating and cooling setpoints cannot be closer together than the deadband, which
is specified in installer configuration option #0181 (see
“Configuration,” p. 26). If you
raise the heating setpoint or reduce the cooling setpoint to a value that would violate
the
deadband setting, the opposing setpoint will also adjust to maintain the deadband.
10. Pressto accept the selection. If there is a cool mode configured, the cooling setpoint
appears and its icons start flashing.
11. Pressorto select the cool setpoint.
12. Pressto accept the selection.orstarts flashing.
13. Pressorto select the fan setting.
•to
turn it on and off automatically
•to keep the fan on continuously
14. Pressto accept the selection. This completes the schedule settings for one period of one
day of the week.
15. Repeat
Step 3 through Step 14 once for each day and period you need to set.
38BAS-SVX36C-EN
Day-to-Day Operation
After a programmable thermostat is configured and the schedule is programmed, the thermostat
automatically changes the setpoints and fan settings accordingto theschedule.However,there are
some operator tasks that you may need or want to perform:
•Show setpoint or current temperature.You can temporarily or permanently switch the main
display from current temperature to temperature setpoint. See
Temperature on Display,” p. 39
•Set the system mode, which includes turning the system on or off, and switching between
heating,
•Override the schedule. If an unexpected, one-time temperature setpoint or fan mode change is
needed you can temporarily override the schedule. See “Timed Override (TOV) Mode,” p. 40.
•Lock or unlock.You can lock the thermostat buttons to prevent changes to the thermostat
set
Note: It is possible for a programmable thermostat to be configured to be a non-programmable
Showing the Setpoint orTemperature on Display
Depending upon the value of configuration option #210, the large numeric display could show any
of the following:
Figure 37. Display Options
Operation
“Showing the Setpoint or
.
cooling, and automatic heating and cooling. See
tings. See
“Locking or Unlocking Modes,” p. 40.
thermostat. If installation configuration option #140 is set to 0, schedule programming
capabilities will be absent.
“Changing the System Mode,” p. 34.
“o dr” indicates outdoor
Arrow indicates
setpoint
Mo
.
AM
.
Current temperatureCurrent (or most
Value of configuration
option #210
0The current local temperature, or the current or most recent temperature setpoint
1 or 2The current local or remote indoor temperature or the current or most recent temperature
3The current indoor temperature, the current or most recent temperature setpoint, or the
Numeric display options
(press and for 3 sec to change)
setpoint
current remote outdoor temperature, which only appears for 8 sec before reverting to
current indoor temperature or setpoint
recent) setpoint
temperature (after 8 sec,
returns to previous mode)
Current outdoor
temperature
To switch between the current temperature, “o dr” temperature, and the setpoint temperature,
press and hold theandbuttons for 3 sec.The display will toggle as shown in
Figure 37.
BAS-SVX36C-EN39
Operation
Timed Override (TOV) Mode
During normal operation, the thermostat controls the HVAC equipment according to the schedule
that is programmed into it.To permanently change the temperature setpoint or fan setting, make
the change in the programmed schedule (see “Scheduling,” p. 36). However, a timed override can
be used to temporarily change the current settings without making any change to the schedule.
To start a temperature setpoint override:
1. Pressor. The current temperature setpoint appears.
2. Within 5 sec of
thermostat enters timed override mode, giving you the opportunity to specify the other
parameter
3. Press and releaseor(or, which has the same function as ) to scroll to heating or
cooling temperature setpoints, fan mode, override duration, or occupancy setting.
4. When youreach the functionyou want tochangeas part of theoverride,pressandmake
the changes.
5. Once you have specified all needed changes, press and holdfor 2 sec or wait 15 sec to save
and exit.
6. Press and holdandfor 2 sec from the home screen or when inTOV setup mode to exit
without enteringTOV mode.
Step 1, pressto raise the setpoint orto lower the setpoint.The
s of the override.
Locking or Unlocking Modes
You can independently lock and unlock the system, fan, and schedule change modes.When a lock
is activated, users cannot change the current mode or schedule settings. If you attempt to make a
change,flashes on the display.
2. Simultaneously press and holdandfor 4 sec.When the mode is unlocked,disappears.
> for system mode
> for system mode
40BAS-SVX36C-EN
Operational and Programming Reference Information
This section provides additional information that may be useful for understanding thermostat
operation or programming.
Deadband
The thermostat automatically maintains a temperature deadband between the heating setpoint
and the cooling setpoint whenever automatic changeover (heat-to-cool or cool-to-heat mode) is
enabled.The temperature range of the deadband is 2–9 °F (1.0–4.5°C) and is specified in the
installation configuration options (see
temperature setpoint to within the deadband of its opposing setpoint, the opposing setpoint will
automatically be pushed to the next value that satisfies the deadband. (See
Heat and Cool Cycling Rate
The heat and cool cycling rate, expressed in cycles per hour (CPH) indicates how often heating or
cooling system is turned on when temperature is within the temperature differential from the
setpoint, which is 1°F (0.5°C).There are ten options (1–10) for heat stages and five options (1–5) for
cool stages.The number selected is the maximum number of times the stage is cycled in 1 hr.
For example, when the system is set to 5 CPH, it runs at 12 min cycles with variable duty cycle.
Depending on the heating or cooling load, which is measured by feedback from the sensor
thermistor and/or temperature error, the system could run at 50% duty cycle (6 min ON and 6 min
OFF), 80% duty cycle (9.6 min ON and 2.4 min OFF), or other variations of the duty cycle.
Note: The
cycling rate described above is only active when the temperature is within the
temperature differential. If the temperature is outside of the temperature, the heating and
cooling equipment will either be fully on or fully off accordingly. (See
“Configuration,” p. 26). If you attempt to change a
Figure 38.)
Figure 38.)
Figure 38. General Heat and Cool Cycling Rate Diagram
Output
100 %
0 %
All heat
stages on
All heat stages
cycling dependent
on load
TDTDTD
Heat set point
temperature differential
(TD) is ±1°F (0.5°C)
centered on set point
There is one cycling rate setting for each of the thermostat’s available heat and cool stages,
including auxiliary and emergency heat stages.You can specify them during installation
configuration. See
“Configuration,” p. 26.
Minimum Compressor OffTime
To protect the compressor from cycling too frequently, there is an automatic 5 min gap between
cycles.You cannot reduce the gap, but you can add up to 5 min if needed. See
p. 26
.
All heat and cool
stages off
Adjustable deadband
2–9°F (1–4.5°C)
All cool stages
cycling dependent
on load
TD
Cool set point
temperature differential
(TD) is ±1°F (0.5°C)
centered on set point
“Configuration,”
All cool
stages on
Temperature
BAS-SVX36C-EN41
Operational and Programming Reference Information
Configuration and Programming Retention
The thermostat retains the time and date for a minimum of 5 days with no electricity. If power is
lost for more than 5 days, you will need to reset the time and date when power is restored.
All configuration parameters, system settings, and scheduling are stored in non-volatile memory,
which will retain the data indefinitely with or without power.
Note: You canmanually revert todefault settings bysetting the appropriateinstallation parameter
(#300 for programmable thermostats or #18for non-programmable thermostats)to avalue
of 1, and exiting configuration mode.
Extended Fan-onTime (Heat or Cool)
Note: This feature applies only to the programmable thermostat.
When the thermostat fan is in Auto mode, the fan on time can be extended.
•Configuration option #270 extends the fan on time by 90 sec after heat turns off.
•Configuration option #271extends the fan on time by 40 sec after cool turns off.
These options may not be available for some system configurations. See
Compressor and Auxiliary Heat Lockout
Note: This feature applies only to the programmable thermostat.
Compressor and auxiliary heat is used for heat pump systems with more heat stages than cool
stages. When the temperature from an outdoor sensor is
•above the auxiliary lockout point, only the compressor will operate on a call for heat.
•below the compressor lockout point, only the auxiliary heat will operate on a call for heat.
•between the compressor and auxiliary lockout point, the compressor and auxiliary heat will
operate on a call for heat.
There is a minimum 5°F (2.5°C) deadband between compressor and auxiliary heat lockout
temperatures. Configuration option #220 sets the compressor lockoutpoint; #221 sets the auxiliary
lockout point. See
“Configuration,” p. 26.
“Configuration,” p. 26.
Auxiliary Heat Control
Note: This feature applies only to the non-programmable 3-Heat/2-Cool thermostat.
You can set the auxiliary heat control using configuration option #17 to one of two settings:
•Comfort - prioritizes comfort over economy. Raising the temperature just a few degrees often
will activate the auxiliary heat.
•Economy - attempts to reach the temperature setting without activating the auxiliary heat.
Economizer/TOD
Note: This feature applies only to the programmable thermostat.
You can set the Economizer orTOD mode using configuration option #150 to one of two settings:
•Economizer Mode - “A” terminal is energized with the thermostat in Occupied mode,
Unoccupied mode with a call for cool, or aTimed Override mode (TOV) active.
• TOD Mode - “A” terminal is energized with thermostat in Occupied mode or aTimed Override
mode (TOV) active.
42BAS-SVX36C-EN
Troubleshooting
This section describes troubleshooting for the thermostat.
Error Codes
An error code indicates that technical assistance may be required.
Try cycling the power to the thermostat as a first method to clear the error. See
Table 12, p. 47 for additional information.
Note: On
Note: On
Table 10. Error Codes
CodeDescription
E0Thermistor Error; occurs when the configured thermistor reading is out of range (less
E3Permanent data error. Access error or checksum error is detected.
E4Input voltage out of range - too low or too high. Input voltage is lower than 18Vac or
E5RTC Error (this error can only appear on the programmable thermostat).
E7Memory error (write and read 0x55 and 0xAA failed). Only checked during power up test.
Table 10 below and
the display, error codes appear at the bottom of the display.
the programmable thermostat, the error code alternates with the time on the display.
than 14°F (-9.9°C) or greater than 122°F (50°C). If this error occurs:
• All Heat/Cool outputs turn off.
• If the fan mode is Auto, the thermostat turns off the fan.
• If the fan mode is On, the thermostat leaves the fan on.
higher than 34V
of out of range input voltage.
ac. The error code display will remain on for 30 sec after the detection
SystemTest Mode
You can run diagnostic tests on the thermostat to verify that thethermostat is functioning properly
and that the devices in the system are wired properly.
To enter system test mode:
1. Apply electrical power to the thermostat.
2. Enter installer configuration mode:
BAS-SVX36C-EN43
Troubleshooting
WARNING
Live Electrical Components!
The circuit board is energized. Have a qualified licensed electrician or other individual who has
been properly trained in handling live electrical components perform this step. Failure to follow
all electrical safety precautions when exposed to live electrical components could result in death
or serious injury.
a. Remove the thermostat cover.
b. Press and hold the configuration button for at least 3 sec, then release it.
Figure 39. Pressing the Configuration Button
Programmable 3H/
2C configuration
button
Thermostat Non-Prog XH/XC
X########-## Rev X
BAYSTAT15#X
####XXX
Non-programmable
thermostats
configuration button
The configuration wrench iconappears, along with the option number and value.
3. Press and hold the configuration button again for at least 3 sec, then release it.The thermostat
into system test mode:
goes
wrench iconflashes.
• The
• The system test number appears in small digits at the lower part of the display.
• The test setting value appears in large digits at the top part of the display.
Figure 40. System Test Mode
Value
System
Test
Number
Programmable
Thermostat
Non-Programmable
Thermostat
Note: System test mode automatically ends if no buttons are pressed for 10 min.
While in system test mode, you can scroll from one test to the next, change the value for the
then test or observe thesystem for the expected result.The numbers and values are shown
test,
Table 11 , p . 46. Some values are retained when you scroll to the next number; others are
in
deactivated when you scroll to the next number, as indicated in the table.
4. Press,,orto scroll through the options, identified by their numbers, until you reach
the option you want to change:
orscrolls to the next larger numbered option.
scrolls to the next lower-numbered option.
44BAS-SVX36C-EN
Troubleshooting
5. Useorto change the value of the option:
decreases the value.
increases the value.
6. Repeat
7. Change the value of the power up test (test number 8 for the 1-Heat/1-Cool thermostat; test
8. Do one of the following to exit test mode:
Step 4 and Step 5 until you have conducted all needed tests.
number
you exit test mode.
• R
• Do not press any buttons for 10 min.
• Press and holdfor 2 sec.
11 for the 3-Heat/2-Cool or programmable thermostat) to 1 to run a power up test after
emove the thermostat cover, if necessary, and then press and immediately release the
configuration button.
BAS-SVX36C-EN45
Troubleshooting
Table 11. System Test Descriptions
Test Number
1H/1C Thermostat
(p/n X13511535-01)
3H/2C Thermostat
(1)
1
1
(1)
2
22Cooling system0 = all cooling stages off
333Fan system0 = fan off
NA44O/B changeover valve0 = changeover valve off
NANA5TOD/Economizer system 0 = TOD/Economizer off
NA5NAAuxiliary Heat0 = Auxiliary heat and fan turns off
NA6NAEmergency Heat0 = Emergency relay, fan, and terminal L output turn off
586LCD segments0 = full segment on
NANA7Remote thermistor (S1 & S2)
478Internal thermistor
699Major software versionShow major software revision number.
71010Minor software versionShow minor software version.
81111Power up test0 = do not run power up test on self-test exit
(1) Only values 0 and 1 are available because there are only one heat and one cool stage.
DescriptionValues
(p/n X13511536-01)
Programmable
Thermostat
1Heating system0 = all heating stages off
temperature reading
temperature reading
1 = heat stage 1 on; heat stage 2 off
2 = heat stage 2 on; heat stage 1 off
3 = heat stage 1 and 2 on
This setting remains active when you scroll to the next setting.
1 = cool stage 1 on; cool stage 2 off
2 = cool stage 2 on; cool stage 1 off
3 = cool stage 1 and 2 turn on
This setting remains active when you scroll to the next setting.
1 = fan on
This setting remains active when you scroll to the next setting.
1 = changeover valve on
This setting remains active when you scroll to the next setting.
1 = TOD/Economizer on
This setting remains active when you scroll to the next setting.
1 = Auxiliary heat and fan turns off
This setting remains active when you scroll to the next setting.
1 = Emergency relay, fan, and terminal L output turn on
This setting remains active when you scroll to the next setting.
1 = odd segments on; even segments off
2 = even segments on; odd segments off
This setting is deactivated when you scroll to the next setting.
0 = show temperature reading in Fahrenheit
1 = show temperature reading in Celsius
This setting is deactivated when you scroll to the next setting.
0 = show temperature reading in Fahrenheit
1 = show temperature reading in Celsius
This setting is deactivated when you scroll to the next setting for
the 3H/2C and programmable thermostats, but it remains active
when you scroll to the next setting for the 1H/1C thermostat.
This setting is deactivated when you scroll to the next setting.
This setting is deactivated when you scroll to the next setting.
1 = run power up test on self-test exit
This setting retained (and applied) upon exit from self-test mode.
46BAS-SVX36C-EN
Troubleshooting Table
Table 12 to diagnose and solve problems you may encounter.
Use
Table 12. Troubleshooting
ProblemSolution
Error code E0 Thermistor error.
Error code E4 - Input
voltage out of range
Error codes E3, E5, or E7 • Cycle the power to the thermostat.
Blank display• Check the power supply.
Erratic display
appearance or contrast
Buttons do not respond • Make sure the thermostat modes are not locked. See
“--F” or “--C” flashes• Temperature is outside of the measurable range. The temperature reading should be
Fan settings are not
visible
Troubleshooting
• For non-programmable thermostats and programmable thermostats set to use internal
temperature sensor (configuration option #210 set to 0, 1, or 2):
Thermistor is defective or local temperature is out of range. Replace or repair
thermostat through a qualified Trane supplier.
• For programmable thermostats with configuration option #210 set to 3:
Check the sensor terminals S1 and S2 for secure connection. If wires are securely
connected, try replacing the sensor.
• Check the input voltage to the thermostat. It must be within the range of 18Vac to 32
Vac rms.
• If it does not recover to normal operation, have it serviced or replaced by a qualified
Trane supplier.
• If the power supply is ok, have the thermostat serviced or replaced by a qualified Trane
supplier.
• Check the power supply.
• Check the frequency configuration (Configuration option #210 for the programmable
thermostat or #11 for non-programmable thermostats) to make sure that you are using
the correct frequency setting for your power supply.
• If the power supply and frequency setting are ok, have the thermostat serviced or
replaced by a qualified Trane supplier.
p. 40
.
• Cycle the power to the thermostat.
• If the modes are not locked and cycling the power do not solve the problem, have the
thermostat serviced or replaced by a qualified Trane supplier.
correct when the temperature is within the measurable range.
• Check the system status. If the status is Off, the fan settings will not appear.
• Check the configuration options to verify that the fan is enabled:
For programmable thermostats, check options 0130 and 0151;
For non-programmable thermostats, check options 01 and 03.
(18Vac to 32Vac)
(Power supply frequency selected using
installation configuration option #190)
+15 to +122°F (–9.5 to +50°C)+32 to +99°F (0 to +37°C)
–31 to +122°F (–35 to +50°C)
–40 to +158°F (–40 to +70°C)–40 to +158°F (–40 to +70°C)
50 to 90 °F (10 to 32.2°C)
0.1°C
< 1VA< 1VA
Polycarbonate/ABS blend, UV protected,
UL 94-5VA flammability rating, suitable for
application in a plenum.
3.24 in (8.26 cm) for two mounting screws
(supplied)
24Vac, 50Hz or 60Hz
(18Vac to 32Vac)
(Power supply frequency selected using
installation configuration option #11)
NA
±1.4°F (±0.8°C) over a range of 50 to 90 °F
(10 to 32.2°C)
Configurable: 1.0°F, 0.5°F, 1°C, 0.5°C, 0.1°C
Polycarbonate/ABS blend, UV protected, UL 945VA flammability rating, suitable for application in
a plenum.
3.24 in (8.26 cm) for two mounting screws
(supplied)
Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the
leader in creating and sustaining safe, comfortable and energy efficient environments, Trane offers a broad
portfolio of advanced controls and HVAC systems, comprehensive building services, and parts. For more
information, visit www.Trane.com.
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.