Trane Thermostats Operation Manual

Installation and Operation
Thermostats
Standard and Programmable Versions
SAFETY WARNING
Only qualified personnel should install and service the equipment.The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury.When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.
March 2012 BAS-SVX36C-EN
Copyright
© 2012Trane. All rights reserved.
This document and the information in it are the property ofTrane and may not be used
or reproduced in whole or in part, without the written permission ofTrane.Trane reserves the right to revise this publication at any time and to make changes to its content without obligation to notify any person of such revision or change.
Trademarks
Trane and its logo are trademarks ofTrane in the United States and other countries. All
trademarks referenced in this document are the trademarks of their respective owners.
Warnings, Cautions, and Notices
Warnings, cautions, and notices are provided in appropriate places throughout this
document:
WARNING: Indicates a potentially hazardous situation which, if not avoided,
could result in death or serious injury.
CAUTION: Indicates a potentially hazardous situation which, if not avoided,
could result in minor or moderate injury. It could also be used to alert against unsafe practices.
NOTICE: Indicates a situation that could result in equipment or property- damage-only accidents.
2 BAS-SVX36C-EN
Table of Contents
Introduction ............................................................ 5
Product Features and Capabilities .................................... 6
Dimensions ....................................................... 7
Pre-Installation .........................................................9
Location Considerations ............................................9
Height Requirements ............................................... 9
Mounting Surfaces ................................................. 9
Maximum Wire Lengths ........................................... 10
Installation ............................................................ 11
Mounting the Back Plate ...........................................11
Wiring ........................................................... 12
Replacing the Cover ............................................... 24
Applying Power ................................................... 25
Thermostat to HVAC Equipment ................................10
Remote Sensor to Programmable Thermostat ..................... 10
General Practice .............................................. 12
Terminal Identification ........................................ 13
Wiring Diagrams ............................................. 14
1-Heat/1-Cool Thermostat ................................... 14
3-Heat/2-Cool Non-Programmable Thermostat .................. 15
Programmable Thermostat .................................. 19
Configuration ......................................................... 26
Operation ............................................................. 33
Icon Descriptions ................................................. 33
Overview of Operation ............................................. 33
Non-Programmable Thermostats ................................... 34
Changing the System Mode .................................... 34
Showing or Changing the Heating or Cooling Temperature Setpoint . . 34
Changing the Fan Mode ....................................... 35
Programmable Thermostats ........................................ 35
Programming ................................................ 35
Setting the Time ........................................... 35
Scheduling ...............................................36
Day-to-Day Operation ......................................... 39
Showing the Setpoint or Temperature on Display ............... 39
Timed Override (TOV) Mode ................................. 40
Locking or Unlocking Modes ................................ 40
Operational and Programming Reference Information ....................41
Deadband ........................................................ 41
BAS-SVX36C-EN 3
Heat and Cool Cycling Rate ......................................... 41
Minimum Compressor Off Time .................................... 41
Configuration and Programming Retention ........................... 42
Extended Fan-on Time (Heat or Cool) ................................ 42
Compressor and Auxiliary Heat Lockout ............................. 42
Auxiliary Heat Control ............................................. 42
Economizer/TOD .................................................. 42
Troubleshooting ....................................................... 43
Error Codes ...................................................... 43
System Test Mode ................................................ 43
Troubleshooting Table ............................................. 47
Thermostat Specifications .............................................. 48
4 BAS-SVX36C-EN
Introduction
This document provides installation, operation, and troubleshooting information for threeTrane
models of push-button thermostat:
• TheTrane Programmable 3-Heat/2-CoolThermostat:
• TheTrane (non-programmable) 3-Heat/2-CoolThermostat:
• TheTrane (non-programmable) 1-Heat/1-CoolThermostat:
Note: To identify thethermostat type, locate theTrane PLM# and theTrane PLM#/TraneClarksville
The information contained in this document applies to either one or two models or to all.
Differences are noted where appropriate. If no difference between models is noted, assume that all thermostat models share the information.
– Trane PLM # X13511537-01
– Trane Clarksville part # BAYSTAT150A
– Service parts #THT02774
– Trane PLM # X13511536-01
– Trane Clarksville part # BAYSTAT155A
– Service parts #THT02773
– Trane PLM # X13511535-01
– Trane Clarksville part # BAYSTAT151A
– Service parts #THT02772
# on the thermostat circuit board.
BAS-SVX36C-EN 5
Introduction
Product Features and Capabilities
The table below shows the functional differences between the three thermostat models.
Thermostat Function or Feature
A liquid crystal display (LCD) with symbols for temperature, setpoints, and system operating modes. The programmable thermostat also has day of the week, time of day, and occupancy settings.
System modes: Heat, Cool, Auto, Off. Both types of 3-Heat/2-Cool thermostat also have Emergency Heat mode.
System Configuration Options. See
• 1-heat/1-cool, conventional  
• 1-heat/1-cool, heat pump without auxiliary heat
• 1-heat only, conventional without fan
• 1-heat only, conventional with fan
• 1-cool, conventional
• 2-heat/1-cool, heat pump with auxiliary heat
• 2-heat/2-cool, conventional
• 2-heat/1-cool, conventional
• 1-heat/2-cool, conventional
• 2-heat/2-cool, heat pump without auxiliary heat
• 3-heat/2-cool, heat pump with auxiliary heat
A heating and cooling setpoint range of 40ºF to 90ºF (4.5ºC to 32ºC)
Two fan modes: On, Auto
Additional configurable options (See
Terminals and configuration options for a remote temperature sensor. Options include:
• Displaying the remote/outdoor temperature on the LCD
• Using the remote/outdoor temperature to lockout the compressor or auxiliary heat
• Using the remote/outdoor temperature instead of the built-in sensor
Scheduling function with two or four periods per day and the following day/week options:
• 5/2 day schedule: weekdays share a schedule; Saturday and Sunday share a schedule
• 5/1/1 day schedule: weekdays share a schedule; Saturday and Sunday have their own, independent schedules
• 1 day schedule: Every day shares the same schedule
• 7 day schedule: Each day has its own, independent schedule
Temporary override function with configurable override time limit
“Configuration,” p. 26 for more information:
“Configuration,” p. 26)  
1H/1C Thermostat
(p/n X13511535-01)
3H/2C Thermostat
 
 
 
 
 
 
 
 
(p/n X13511536-01)
Programmable
Thermostat
(p/n X13511537-01)
6 BAS-SVX36C-EN
Dimensions
Introduction
Figure 1 and Figure 2 provide dimensions for each type of thermostat.The two non-programmable
thermostats have the same dimensions; the programmable thermostat has slightly different dimensions.
Figure 1. ProgrammableThermostat Dimensions
0.3 in.
(8 mm)
1.08 in.
3.25 in.
(83 mm)
Typ. Radius
0.08 in. (2 mm)
(27.5 mm)
4.7 in.
(119 mm)
3.4 in.
(86 mm)
Typ.P Radius 0.08 in. (2 mm)
Note: Drawing not to scale. Dimensions within ± 0.02 in. (± 0.5 mm)
BAS-SVX36C-EN 7
Introduction
Figure 2. 1-Heat/1-Cool or 3-Heat/2-Cool (non-programmable)Thermostat Dimensions
0.3 in.
(8 mm)
1.1 in.
(28 mm)
4.7 in.
(119 mm)
3.4 in.
(86 mm)
3.07 in.
(78 mm)
Typ. Radius
0.08 in. (2 mm)
Typ.P Radius 0.08 in. (2 mm)
Note: Drawing not to scale. Dimensions within ± 0.02 in. (± 0.5 mm)
8 BAS-SVX36C-EN
Pre-Installation
This section provides the following pre-installation information:
Location considerations
Height requirements
Mounting surfaces
Maximum wire length
Location Considerations
When selecting a location, avoid the following:
Areas of direct sunlight
Areas in the direct airstream of air diffusers
Exterior walls and other walls that have a temperature differential between the two sides
Areas that are close to heat sources such as sunlight, appliances, concealed pipes, chimneys, or other heat-generating equipment
Drafty areas
Dead spots behind doors, projection screens, or corners
• Walls that are subject to high vibration
Areas with high humidity
High traffic areas (to reduce accidental damage or tampering)
Height Requirements
It is recommended that you mount the back plate a maximum distance of 54 in. (137 cm) above the floor. If a parallel approach by a person in a wheelchair is required, reduce the maximum height to 48 inches.
Note: Consult section4.27.3 of the 2002 Americans withDisabilityAct guideline, and local building
codes, for further details regarding wheelchair requirements.
Mounting Surfaces
The thermostat can be mounted to any sturdy, vertical surface. Plastic threaded anchors and
M3.5 x 20 mm screws are provided for mounting to plaster or wallboard; 6-32 x 3/4 inch machine screws are provided for mounting directly to a standard electrical device box. Other fastener varieties may be required for other surface types.
When replacing a horizontally mounted thermostat and there is an adapter kit available to cover
any opening in the wall. Contact your localTrane office for more information.
BAS-SVX36C-EN 9
Pre-Installation
Maximum Wire Lengths
Thermostat to HVAC Equipment
The thermostat may not function properly if the total resistance of any of the thermostat to HVAC
equipment wires exceeds 2.5 ohms.To ensure that wire length does not cause excess resistance, refer to long.
Table 1. MaximumThermostat to HVAC Equipment Wire Lengths
Remote Sensor to ProgrammableThermostat
Because remote temperature sensors measure resistance, very long cable runs can cause slight errors in the measurement. For the highest temperature reading accuracy, avoid exceeding the maximum recommended wire lengths shown in
Table 2. Maximum Recommended Remote SensorWire Length
Table 1 and ensure that the wires from the thermostat to the HVAC equipment are not too
Copper wire size Maximum recommended wire length
22 AWG (0.33 mm2) 150 ft (46 m)
20 AWG (0.50 mm2) 240 ft (73 m)
18 AWG (0.75 mm2) 385 ft (117 m)
Maximum recommended remote
Copper wire size
22 AWG (0.33 mm2) 1000 ft (300 m)
20 AWG (0.50 mm2) 1500 ft (450 m)
18 AWG (0.75 mm2) 2500 ft (750 m)
sensor wire length
Table 2.
Note: For 22 AWG (0.33 mm2) copper wires, the rate of error can be up to 0.5 °F (0.3 °C) per 100 ,
which typically requires wire lengths in excess of 5000 ft (1500 m).
10 BAS-SVX36C-EN
Installation
This section provides installation instructions.
Before you begin, read through the pre-installation information, beginning on the following conditions are met:
A wire access hole is available at the thermostat location.
• The wires are accessible through the hole.
• The wires are attached to the appropriate terminals on the HVAC equipment.
• There is continuity (and not more than 2.5 ohms resistance) between the thermostat location
the HVAC equipment.
and
• The wires are accurately labeled or identified by color.
Mounting the Back Plate
WARNING
Hazardous voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.
NOTICE
Equipment damage!
Applying excessive voltage to the thermostat will permanently damage it.
p. 9, and also verify
To mount the back plate:
1. Shut off power to the HVAC equipment.
Note: If the security screw is installed, remove it before attempting to remove the cover.
See
Figure 3.
Figure 3.
2. Remove the cover by firmly pressing the thumb tab at the bottom of the cover and pulling the
3. Feed the wires through the opening in the back plate.
Security Screw Location (if used)
ver away from the back plate.
co
Security screw
BAS-SVX36C-EN 11
Installation
Wiring
Figure 4. Feeding Wires through Back Plate
4. If you are mounting the back plate directly to a wall surface, hold the back plate against the surface and mark the fastener locations.
5. Secure the back plate using appropriate fasteners. (See thermostat must be level and plumb for accurate temperature control and to ensure proper air movement through the thermostat enclosure.
“Mounting Surfaces,” p. 9.)The
WARNING
Hazardous voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.
NOTICE
Equipment damage!
Applying excessive voltage to the thermostat will permanently damage it.
General Practice
To wire the thermostat:
1. Connect the wires to the terminal block(s) packaged in the box with the thermostat. (The programmable only one):
R
emove approximately 1/4 inch (6 mm) of insulation from the wires.
Use the terminal block screws to securely fasten each wire into the terminal block.
Refer to the section,
that follow to determine the correct terminal for each wire.
Note: In
color wire to which they are connected. However, you must verify which equipment terminals are connected at the other ends of the wires before connecting the wires to the thermostat.
12 BAS-SVX36C-EN
thermostat has two terminal blocks, the non-programmable thermostats have
“Terminal Identification,” p. 13 and the wiring diagrams on the pages
some cases the terminal labels (Y, G, R, etc.) correctly correspond to first letter of the
Installation
2. Align the pins on the circuit board with the holes on the bottom of theterminal blocks and gently push the wired terminal blocks into place on the circuit board. See
Figure 5.
Figure 5. Attaching the wired terminal blocks to the pins on the circuit board
3. Push the excess wire through the hole in the wall cavity or into the junction box.
Important: Do
4. Use nonflammable insulation to prevent air movement between the wall cavity and the thermostat.
Terminal Identification
The table below defines the terminals for each of the thermostat types.
s
S2
S1
A
Y2
W2
R
W Rc
Y
C G
Y
G
C
S2
S1
A
W1)
Y2
W2(
R
Rc
W(O/B)
Y2 L
AuxE
Y C O/B G
Rc R
)
uxE
L
Y2
G
W2(A
W (O/B)
C
Y
R
Rc
Rc R Y C
W G
G
W
C
Y
R
Rc
Programmable thermostat 3-Heat/2-Cool thermostat 1-Heat/1-Cool thermostat
not coil excess wire between the thermostat and the back plate.
Where present:
Terminal Label Terminal Description
1H/1C Thermostat
(p/n X13511535-01)
3H/2C Thermostat
(p/n X13511536-01)
Programmable
Thermostat
C Common  
G Fan Relay
Y Stage 1 compressor control
W (O/B) Heat relay (Changeover valve)
Rc 24Vac cooling These terminals are shipped with a jumper connected
R 24Vac heating
W2 (W1)
W2 (Aux/E)
Second stage heat (Auxiliary heat or emergency heat relay.)
or
between them. Remove the jumper if the 24Vac power supplies are separate.
(1)
(1)
Y2 Stage 2 compressor control
A Economizer
S1 External sensor
S2 External sensor
(L) (Emergency heat indicator)
(1)
 
 
 
 
 
(1) Text (in parentheses) applies to heat pump systems.
BAS-SVX36C-EN 13
(p/n X13511537-01)
Installation
Wiring Diagrams
The following diagrams show all of the common wiring scenarios you are likely to encounter.
1-Heat/1-Cool Thermostat
Table 3 and the diagrams that follow to correctly wire the thermostat for your system type.
Use
Table 3. SystemType Options for 1H/1C Non-ProgrammableThermostats
System Type
1-heat/1-cool, conventional 0
1-heat/1-cool, heat pump without auxiliary heat 1 Figure 7
1-heat only, conventional without fan 2 Figure 8
1-heat only, conventional with fan 3 Figure 9
1-cool, conventional 4 Figure 10
Figure 6. 1H/1C Thermostat, 1H/1C Conventional (option 0)
Single Transformer:
L1 (hot)
L2
24 Vac
Compressor
Heat
Fan
Value for Option 01 See Diagram
Figure 6
(jumper
Rc
installed)
R
Y
C
W
G
Two Transformers:
Cooling Transformer
L1 (hot)
L2
24 Vac
Heating Transformer
L1 (hot)
L2
24 Vac
Compressor
Heat
Fan
Rc
(jumper
R
removed)
Y
C
W
G
Figure 7. 1H/1CThermostat, 1H/1C Heat Pump Without Auxiliary Heat (Option 1)
(jumper
L1 (hot)
L2
24 Vac
Compressor
Changeover Valve
Fan
Rc
R
Y
C
O/B
G
installed)
14 BAS-SVX36C-EN
Figure 8. 1H/1C Thermostat, 1H Only, ConventionalWithout Fan (Option 2)
(jumper
Rc
installed)
L1 (hot)
L2
24 Vac
Heat
R
Y
C
W
G
Figure 9. 1H/1C Thermostat, 1H Only, ConventionalWith Fan (option 3)
(jumper
Rc
installed)
L1 (hot)
L2
24 Vac
Heat
Fan
R
Y
C
W
G
Figure 10. 1H/1C Thermostat, 1C Only, Conventional (option 4)
(jumper
Rc
installed)
L1 (hot)
L2
24 Vac
Compressor
Fan
R
Y
C
W
G
Installation
3-Heat/2-Cool Non-ProgrammableThermostat
Use
Table 4 and the diagrams that follow to correctly wire the thermostat for your system type.
Table 4. SystemType Options for 3H/2C Non-ProgrammableThermostats
System Type Value for Option 01
1-heat/1-cool, conventional 0
1-heat/1-cool, heat pump without auxiliary heat 1 Figure 12
1-heat only, conventional without fan 2 Figure 13
1-heat only, conventional with fan 3 Figure 14
1-cool, conventional 4 Figure 15
2-heat/1-cool, heat pump with auxiliary heat 5 Figure 16
2-heat/1-cool, conventional 6 Figure 17
1-heat/2-cool, conventional 7 Figure 18
2-heat/2-cool, heat pump without auxiliary heat 8 Figure 19
3-heat/2-cool, heat pump with auxiliary heat 9 Figure 20
BAS-SVX36C-EN 15
See Diagram
Figure 11
Installation
Figure 11. 3H/2C Non-Programmable Thermostat, 1H/1C, Conventional (Option 0)
Single Transformer:
(jumper
Rc
R
L1 (hot)
L2
Two Transformers:
Cooling Transformer
L1 (hot)
L2
Heating Transformer
L1 (hot)
L2
24 Vac
24 Vac
24 Vac
Compressor
Heat
Fan
Compressor
Heat
Fan
installed)
Y
C
W
G
W2
Y2
L
Rc
(jumper
R
removed)
Y
C
W
G
W2
Y2
L
Figure 12. 3H/2C Non-Programmable Thermostat, 1H/1C, Heat Pump Without Auxiliary heat
(Option 1)
L1 (hot)
L2
24 Vac
Compressor
Changeover Valve
Fan
(jumper
Rc
R
installed)
Y
C
O/B
G
Aux/E
Y2
L
Figure 13. 3H/2C Non-Programmable Thermostat, 1H Only, ConventionalWithout Fan (Option 2)
(jumper
Rc
R
L1 (hot)
L2
24 Vac
Heat
installed)
Y
C
W
G
W2
Y2
L
16 BAS-SVX36C-EN
Installation
Figure 14. 3H/2C Non-Programmable Thermostat, 1H, ConventionalWith Fan (Option 3)
(jumper
Rc
R
L1 (hot)
24 Vac
L2
Heat
Fan
Figure 15. 3H/2C Non-Programmable Thermostat, 1C, Conventional (Option 4)
L1 (hot)
24 Vac
L2
Compressor
Fan
installed)
Y
C
W
G
W2
Y2
L
(jumper
Rc
R
installed)
Y
C
W
G
W2
Y2
L
Figure 16. 3H/2C Non-Programmable Thermostat, 2H/1C, Heat Pump With Auxiliary Heat
(Option 5)
L1 (hot)
L2
24 Vac
Compressor
Changeover Valve
Fan
Auxiliary Heat
Zoning Panels
(jumper
Rc
R
installed)
Y
C
O/B
G
Aux/E
Y2
L
BAS-SVX36C-EN 17
Installation
Figure 17. 3H/2C Non-Programmable Thermostat, 2H/1C, Conventional (Option 6)
Single Transformer:
(jumper
Rc
R
L1 (hot)
L2
24 Vac
Compressor
Heat 1
Fan
Heat 2
installed)
Y
C
W
G
W2
Y2
L
Two Transformers:
Cooling Transformer
L1 (hot)
L2
24 Vac
Heating Transformer
L1 (hot)
L2
24 Vac
Heat 1
Heat 2
Compressor
Fan
Rc
(jumper
R
removed)
Y
C
W
G
W2
Y2
L
Figure 18. 3H/2C Non-Programmable Thermostat, 1H/2C, Conventional (Option 7)
Single Transformer:
(jumper
Rc
R
L1 (hot)
L2
Two Transformers:
Cooling Transformer
L1 (hot)
L2
Heating Transformer
L1 (hot)
L2
24 Vac
24 Vac
24 Vac
Compressor 1
Heat
Fan
Compressor 2
Compressor 1
Heat
Fan
Compressor 2
installed)
Y
C
W
G
W2
Y2
L
Rc
(jumper
R
removed)
Y
C
W
G
W2
Y2
L
Figure 19. 3H/2C Non-Programmable Thermostat, 2H/2C, Heat Pump Without Auxiliary Heat
(Option 8)
L1 (hot)
24 Vac
L2
Compressor 1
Changeover Valve
Fan
Compressor 2
18 BAS-SVX36C-EN
(jumper
Rc
R
installed)
Y
C
O/B
G
Aux/E
Y2
L
Installation
Figure 20. 3H/2C Non-Programmable Thermostat, 3H/2C, Heat Pump With Auxiliary Heat
(Option 9)
L1 (hot)
L2
24 Vac
Changeover Valve
Auxiliary Heat
Zoning Panels
Compressor 1
Fan
Compressor 2
(jumper
Rc
R
installed)
Y
C
O/B
G
Aux/E
Y2
L
ProgrammableThermostat
Use
Table 5 and the diagrams that follow to correctly wire the thermostat for your system type.
Table 5. SystemType Options for ProgrammableThermostats
System Type Value for Option 130
1-heat/1-cool, conventional 1
1-heat/1-cool, heat pump without auxiliary heat 2 Figure 22
1-heat only, conventional without fan 3 Figure 23
1-heat only, conventional with fan 4 Figure 24
1-cool, conventional 5 Figure 25
2-heat/1-cool, heat pump with auxiliary heat 6 Figure 26
2-heat/2-cool, conventional 7 Figure 27
2-heat/1-cool, conventional 8 Figure 28
1-heat/2-cool, conventional 9 Figure 29
2-heat/2-cool, heat pump without auxiliary heat 10 Figure 30
3-heat/2-cool, heat pump with auxiliary heat 11 Figure 31
See Diagram
Figure 21
BAS-SVX36C-EN 19
Installation
Figure 21. ProgrammableThermostat, 1H/1C, Conventional (Option 1)
Single Transformer:
L2
L1 (hot)
Two Transformers:
Cooling Transformer
L2
L1 (hot)
Heating Transformer
L2
L1 (hot)
24 Vac
24 Vac
24 Vac
Fan
Heat
Economizer/TOD
Remote Temperature Sensor
Fan
Heat
Economizer/TOD
Remote Temperature Sensor
Compressor
Compressor
C
G
Y
W
Rc
R
W2
Y2
A
S1
S2
C
G
Y
W
Rc
R
W2
Y2
A
S1
S2
(jumper installed)
(jumper removed)
Figure 22. Programmable Thermostat, 1H/1C, Heat Pump Without Auxiliary Heat (Option 2)
C
G
Y
O/B
Rc
R
W1
Y2
A
S1
S2
(jumper installed)
L2
L1 (hot)
24 Vac
Fan
Changeover Valve
Economizer/TOD
Remote Temperature Sensor
Compressor
20 BAS-SVX36C-EN
Figure 23. Programmable Thermostat, 1H Only, ConventionalWithout Fan (Option 3)
C
G
Y
L2
L1 (hot)
Heat
24 Vac
Economizer/TOD
Remote Temperature Sensor
W
Rc
R
W2
Y2
A
S1
S2
(jumper installed)
Figure 24. Programmable Thermostat, 1H, ConventionalWith Fan (Option 4)
C
G
Y
W
Rc
R
W2
Y2
A
S1
S2
(jumper installed)
L2
L1 (hot)
Fan
Heat
24 Vac
Economizer/TOD
Remote Temperature Sensor
Installation
Figure 25. Programmable Thermostat, 1C, Conventional (Option 5)
C
Fan
Compressor
L2
L1 (hot)
24 Vac
Economizer/TOD
Remote Temperature Sensor
BAS-SVX36C-EN 21
G
Y
W
Rc
R
W2
Y2
A
S1
S2
(jumper installed)
Installation
Figure 26. Programmable Thermostat, 2H/1C, Heat Pump With Auxiliary Heat (Option 6)
C
G
Y
O/B
Rc
R
W1
Y2
A
S1
S2
(jumper installed)
L2
L1 (hot)
24 Vac
Fan
Changeover Valve
Economizer/TOD
Remote Temperature Sensor
Compressor
Auxiliary Heat
Figure 27. Programmable Thermostat, 2H/2C, Conventional (Option 7)
Single Transformer:
C
G
Y
W
Rc
R
W2
Y2
A
S1
S2
(jumper installed)
L2
L1 (hot)
24 Vac
Fan
Heat 1
Heat 2
Economizer/TOD
Remote Temperature Sensor
Compressor 1
Compressor 2
Two Transformers:
Cooling Transformer
L2
L1 (hot)
24 Vac
Heating Transformer
L2
L1 (hot)
24 Vac
Fan
Compressor 1
Heat 1
Heat 2
Compressor 2
Economizer/TOD
Remote Temperature Sensor
C
G
Y
W
Rc
R
W2
Y2
A
S1
S2
(jumper removed)
22 BAS-SVX36C-EN
Figure 28. Programmable Thermostat, 2H/1C, Conventional (Option 8)
Single Transformer:
L2
L1 (hot)
Two Transformers:
Cooling Transformer
L2
L1 (hot)
Heating Transformer
L2
L1 (hot)
Fan
Heat 1
24 Vac
Heat 2
Economizer/TOD
24 Vac
Heat 1
24 Vac
Heat 2
Economizer/TOD
Compressor
Remote Temperature Sensor
Fan
Compressor
Remote Temperature Sensor
C
G
Y
W
Rc
R
W2
Y2
A
S1
S2
C
G
Y
W
Rc
R
W2
Y2
A
S1
S2
(jumper installed)
(jumper removed)
Installation
Figure 29. Programmable Thermostat, 1H/2C, Conventional (Option 9)
Single Transformer:
L2
L1 (hot)
Two Transformers:
Cooling Transformer
L2
L1 (hot)
Heating Transformer
L2
L1 (hot)
Fan
Heat
24 Vac
Economizer/TOD
24 Vac
24 Vac
Economizer/TOD
Compressor 1
Compressor 2
Remote Temperature Sensor
Fan
Compressor 1
Heat
Compressor 2
Remote Temperature Sensor
C
G
Y
W
Rc
R
W2
Y2
A
S1
S2
C
G
Y
W
Rc
R
W2
Y2
A
S1
S2
(jumper installed)
(jumper removed)
BAS-SVX36C-EN 23
Installation
Figure 30. Programmable Thermostat, 2H/2C, Heat Pump Without Auxiliary Heat (Option 10)
C
G
Y
O/B
Rc
R
W1
Y2
A
S1
S2
(jumper installed)
L2
L1 (hot)
24 Vac
Fan
Changeover Valve
Economizer/TOD
Remote Temperature Sensor
Compressor 1
Compressor 2
Figure 31. ProgrammableThermostat, 3H/2C, Heat PumpWith Auxiliary Heat (Option 11)
C
G
Y
O/B
Rc
R
W1
Y2
A
S1
S2
(jumper installed)
L2
L1 (hot)
24 Vac
Fan
Changeover Valve
Auxiliary Heat
Economizer/TOD
Remote Temperature Sensor
Compressor 1
Compressor 2
Replacing the Cover
To replace the cover:
1. Hook the cover over the top of the back plate. Apply light pressure to the bottom of the cover
it snaps in place.
until
2. If desired, install the security screw into the bottom of the cover. See
Figure 32.
24 BAS-SVX36C-EN
Close cover - insert security screw
Security screw
Figure 32.
Applying Power
Applying power to the thermostat will initiate a power up sequence.
1. The full screen appears for 1.5 seconds.
2. The firmware version appears for 1.5 seconds:
3. Power up tests are performed.
Figure 33. Home screens
Installation
the programmable thermostat, the firmware version shows in the HH:MM digits.
On
On the non-programmable thermostats, the digits are split between the top and bottom
regions of the screen: the most significant digits are at the top.
an error is detected, an error code appears (see
If
If no errors are detected, the home screen appears (see
Mo
.
AM
.
“Error Codes,” p. 43).
Figure 33).
Programmable
thermostat
Non-programmable
thermostats
BAS-SVX36C-EN 25
Configuration
NOTICE
Adverse Control System Behavior!
Improper configuration could cause unwanted, possibly adverse control system behavior. Be sure to configure the thermostat according to your system type.
To change the installation configuration:
1. Apply electrical power to the thermostat.
2. See the appropriate table for your thermostat type to determine the configuration options you need:
3. Write down your selections or other notes on the table.
4. Enter installer configuration mode:
WARNING
Live Electrical Components!
The circuit board is energized. Have a qualified licensed electrician or other individual who has
been properly trained in handling live electrical components perform this step. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
a. Remove the thermostat cover.
b. Press and hold the configuration button for at least 3 sec.
able 6, p. 27
T
for 3-Heat/2-Cool programmable thermostats
Table 7, p. 31 for 3-Heat/2-Cool non-programmable thermostats
Table 8, p. 32 for 1-Heat/1-Cool, non-programmable thermostats
Figure 34. Pressing the Configuration Button
Programmable 3H/
2C configuration
button
The configuration wrench icon
appears, along with the option number and value:
Thermostat Non-Prog XH/XC
X########-## Rev X
BAYSTAT15#X
####XXX
Non-programmable
thermostats
configuration button
Figure 35. Configuration Mode
Value
Option Number
Non-Programmable
Programmable Thermostat
Thermostat
Note: Configuration mode automatically ends if no buttons are pressed for 10 min.
26 BAS-SVX36C-EN
Configuration
5. Press , ,or to scroll through the options, identified by their numbers, until you reach the option you want to change:
scrolls to a lower-numbered option. or scrolls to a higher-numbered option.
6. Use
7. Repeat
8. Do one of the following to exit configuration mode:
Table 6. Installation Options for 3-Heat/2-Cool ProgrammableThermostat
No. Name Default Opts. Descriptions
0100 Temperature
0110 Clock format 12 12 12 hour clock
0120 Year 09 09-99 2009 - 2099 0121 Month 1 1-12 Months of the year 0122 Day 1 1-31 Days of the month 0125 Daylight savings 2 0 Disabled
0126 Spring month 0127 Spring day 08 01-31 The day on which the Spring daylight savings change occurs 0128 Fall month 11 01-12 The month in which the Fall daylight savings change occurs 0129 Fall day 08 01-31 The day on which the Fall daylight savings change occurs 0130 System selection 8 1 1H/1C (conv) 1st Stage Heat (W), 1st Stage Comp (Y), Fan (G)
or to change the value of the option:
decreases the value.
increases the value.
Step 5 and Step 6 until you have made all necessary changes.
Note: V
alues are saved in permanent memory after setting a value and moving to next
configuration parameter, and also when you exit configuration mode.
Remove the thermostat cover, if necessary, and then press and immediately release the
configuration button.
Do not press any buttons for 10 min.
Press and hold for 2 sec.
indication/ resolution
0 0 °F, 1 degree resolution
(1)
03 01-12 The month in which the Spring daylight savings change occurs
1 °F, 0.5 degree resolution 2 °C, 1 degree resolution 3 °C with 0.5 degree resolution 4 °C with 0.1 degree resolution
24 24 hour clock
1 US (1987), changeover at 2:00am 2 US (2007), changeover at 2:00am 3 Europe, changeover at 1:00am 4 Manual, changeover at 2:00am
2 1H/1C (HP) 1st Stage Comp (Y), Changeover (O/B), Fan (G) 3 1H (Conv) 1st Stage Heat (W), without fan 4 1H (Conv) 1st Stage Heat (W), Fan (G) 5 1C (Conv) 1st Stage Comp (Y), Fan (G) 6 2H/1C (HP) 1st Stage Comp (Y), Changeover (O/B), Auxiliary Heat (W1),
Fan (G)
7 2H/2C (Conv) 1st & 2nd Stage Heat (W,W2), 1st & 2nd Stage
Comp (Y,Y2), Fan (G) 8 2H/1C (Conv) 1st & 2nd Stage Heat (W,W2), 1st Stage Comp (Y), Fan (G) 9 1H/2C (Conv) 1st Stage Heat (W), 1st & 2nd Stage Comp (Y,Y2), Fan (G)
10 2H/2C (HP) 1st & 2nd Stage Comp (Y,Y2), Changeover (O/B), Fan (G) 11 3H/2C (HP) 1st & 2nd Stage Comp (Y,Y2), Changeover (O/B), Auxiliary
Heat (W1), Fan (G)
BAS-SVX36C-EN 27
Configuration
Table 6. Installation Options for 3-Heat/2-Cool Programmable Thermostat (continued)
No. Name Default Opts. Descriptions
0140 Schedule options 1 0 Non-programmable
0150 TOD/Economizer
output (terminal A)
0151 Heat fan
operation
0153 Reversing value
O/B
0160 CPH 1st stage
compressor
0161 CPH 2nd stage
compressor
0162 CPH 1st stage
conventional heat
0163 CPH 2nd stage
conventional heat
0164 CPH for auxiliary
heat
0165 CPH for
emergency heat
0170 Continuous
backlight
(2)
(2)
(2)
(2)
(2)
(2)
0 0 Unused
0 0 System controls fan
0 0 O/B terminal energized in cooling
3 1-5 Cycles per hour for 1st stage compressor - only for systems with cool or heat
3 1-5 Cycles per hour for 2nd stage compressor - only for systems with two cool or
5 1-10 Cycles per hour for 1st stage conventional heat - only for systems with heat
9 1-10 Cycles per hour for 2nd stage conventional heat - only for systems with two
9 1-10 Cycles per hour for auxiliary heat - only for heat pump systems with more
9 1-10 Cycles per hour for emergency heat - only for heat pump systems with more
0 0 Backlight “ON” time is limited
0180 Changeover 1 0 Manual changeover (heat/cool/off ) - manually changeover the thermostat
0181 Deadband
0182 Minimum
compressor off time
0190 Power supply
frequency
0210 Temperature
sensor selection
(3)
3 2 2° F (1° C)
5 0-5 Minutes for compressor off time - for systems with cool or heat pump stages
0 0 60Hz
0 0 Internal for H/C - display can show only local temperature and setpoint
1 Programmable
1 TOD energizes terminal A during occupied period, not during
unoccupied period. 2 Economizer energizes terminal A during a call for cool
1 Thermostat controls fan
1 O/B terminal energized in heating
pump stage - also changes 2nd stage cool default CPH
heat pump stages
stages - also changes 2nd stage heat default CPH
conventional heat stages
heat than cool stages
heat than cool stages
1 Backlight does not turn off
between heat, cool, and off 1 Auto changeover (heat/cool/auto/off) - manually changeover between heat,
cool, and off, or select automatic changeover
3 3° F (1.5° C) 4 4° F (2.0° C) 5 5° F (2.5° C) 6 6° F (3.0° C) 7 7° F (3.5° C) 8 8° F (4.0° C) 9 9° F (4.5° C)
- (Minutes specified here are added to the 5 min base off time.)
1 50 Hz
1 Internal for H/C - remote (connected to S1 & S2)
show local and remote temperature, and setpoint 2 Internal for H/C, remote (connected to S1 & S2)
auxiliary lockout; display can show local and remote temperature, and
setpoint - (Disabled for conventional systems.) 3 Remote (connected to S1 & S2)
remote indoor temperature and setpoint
(4)
for H/C, internal disabled; display can show
(4)
for display - display can
(4)
for compressor and
28 BAS-SVX36C-EN
Configuration
Table 6. Installation Options for 3-Heat/2-Cool Programmable Thermostat (continued)
No. Name Default Opts. Descriptions
0220 Heat pump
compressor lockout point
0221 Heat pump aux
lockout point
0230 Temp occupied
duration limit for TOV override
0231 Number of
periods
0232 Period occupied/
unoccupied definitions
(5)
0 0 None
15 15° F (–9.5° C) 20 20° F (–6.5° C) 25 25° F (–4.0° C) 30 30° F (–1.0° C) 35 35° F (1.5° C) 40 40° F (4.5° C) 45 45° F (7.0° C)
0 0 None
40 40° F (4.5° C) 45 45° F (7.0° C) 50 50° F (10.0° C) 55 55° F (13.0° C) 60 60° F (15.5° C)
3 0 0 hours (Note: TOV function is still available)
1 1 hour 2 2 hours 3 3 hours 4 4 hours
2 2 Two scheduling periods per day
4 Four scheduling periods per day
4 If Option #0231 is set to 2:
Day Night 0 Unoccupied Unoccupied 1 Unoccupied Occupied 2 Unoccupied Unoccupied 3 Unoccupied Occupied 4 Occupied Unoccupied 5 Occupied Occupied 6 Occupied Unoccupied 7 Occupied Occupied 8 Unoccupied Unoccupied 9 Unoccupied Occupied
10 Unoccupied Unoccupied 11 Unoccupied Occupied 12 Occupied Unoccupied 13 Occupied Occupied 14 Occupied Unoccupied 15 Occupied Occupied
If Option #0231 is set to 4:
Morning Day Evening Night 0 Unoccupied Unoccupied Unoccupied Unoccupied 1 Unoccupied Unoccupied Unoccupied Occupied 2 Unoccupied Unoccupied Occupied Unoccupied 3 Unoccupied Unoccupied Occupied Occupied 4 Unoccupied Occupied Unoccupied Unoccupied 5 Unoccupied Occupied Unoccupied Occupied 6 Unoccupied Occupied Occupied Unoccupied 7 Unoccupied Occupied Occupied Occupied 8 Unoccupied Unoccupied Unoccupied Unoccupied 9 Occupied Unoccupied Unoccupied Occupied
10 Occupied Unoccupied Occupied Unoccupied 11 Occupied Unoccupied Occupied Occupied 12 Occupied Occupied Unoccupied Unoccupied 13 Occupied Occupied Unoccupied Occupied 14 Occupied Occupied Occupied Unoccupied 15 Occupied Occupied Occupied Occupied
BAS-SVX36C-EN 29
Configuration
Table 6. Installation Options for 3-Heat/2-Cool Programmable Thermostat (continued)
No. Name Default Opts. Descriptions
0233 Scheduling mode
day options
0240 Heat
temperature range stops
0241 Cool temperature
range stops
0260 Temperature
display offset
0270 Extended fan-on
time heat
0271 Extended fan-on
time cool
0300 Restore factory
defaults
(1) Only available if option #0125 is set to 4.
“Heat and Cool Cycling Rate,” p. 41.
(2) See
“Deadband,” p. 41.
(3) See (4) If an external sensor is attached to the S1 and S2 terminals, it must be 10Knegative temperature coefficient. (5) Only available for heat pump systems with more heat than cool stages and remote outdoor sensor. A 5 °F (2.5 °C) dead
band between options #0220 and #0221 will be enforced automatically. (6) Only applies to systems with heat stages. (7) Only applies to systems with cool stages. (8) Only applies to control temperature and display temperature for internal and indoor remote sensor. Does not apply to out-
door temperature for display. (9) See
“Extended Fan-on Time (Heat or Cool),” p. 42.
(10)Only available when option #0151 is set to 1.
(6)
(7)
(8)
(9)(10)
(9)(7)
0 0 1 day - Mo-Su share the same schedule
90 40 - 90 40° F to 90° F
50 50 - 99 50° F to 99° F
0 -3 –3° F (–1.5° C)
0 0 Off
0 0 Off
0 0 No - do not restore
1 5+1+1 days - Mo-Fr share a schedule; Sa and Su each have an independent
schedule 2 5+2 days - Mo-Fr share a schedule; Sa-Su share a schedule 3 7 days - Each day has an independent schedule
4 - 32 4° C to 32° C
10 - 37 4° C to 32° C
-2 –2° F (–1.0° C)
-1 –1° F (–0.5° C) 0 None 1 1° F (0.5° C) 2 2° F (1.0° C) 3 3° F (1.5° C)
90 90 sec
40 40 sec
1 Yes - reset all installer options to default except calendar, and system
selection - options 0120-0122 and 0125-0130 do not reset.
30 BAS-SVX36C-EN
Table 7. Installation Options for 3-Heat/2-Cool Non-ProgrammableThermostat
No. Name Default Opts. Descriptions
01 System type 0 0 1H/1C, conventional - 1st stage heat (W), 1st stage
02 Changeover
valve
03 Fan control
04 Stage 1 heat
cycle rate
05 Stage 1
compressor cycle rate
06 Manual/Auto
changeover
07 Temperature
indication/ resolution
08 Compressor
protection
09 Heat
temperature range stop
10 Cool temperature
range stop
11 Power supply
frequency
12 Deadband
13 Stage 2 heat
cycle rate
14 Auxiliary heat
cycle rate
15 Emergency heat
cycle rate
16 Stage 2
compressor cycle rate
17 Auxiliary heat
control
18 Restore factory
defaults
(1) These options only available on systems with fans. (2) See
“Heat and Cool Cycling Rate,” p. 41.
(3) See
“Deadband,” p. 41. For auto or manual systems (see Option 01).
(1)
(2)
(2)
(3)
(2)
(2)
(2)
(2)
0 0 O/B terminal energized in cooling
0 0 Gas or oil furnace, equipment controls fan for heating
5 1-10 Cycles per hour for 1st stage conventional heat - only available on systems
3 1-5 Cycles per hour for 1st stage compressor - only available on systems with cool
0 0 Manual changeover (heat/cool/off ) - manually changeover between heat,
0 0 °F with 1 degree resolution
5 0-5 Minutes for compressor off time - only available on heat pump systems or
90 40-90 Heating high temperature range stop in °F. (4.5-32°C)
50 50-99 Cooling low temperature range stop in °F. (10-37°C)
0 0 60 Hz
3 2 2°F (1.0°C)
9 1-10 Cycles per hour for 2nd stage conventional heat - only available for
5 1-10 Cycles per hour for auxiliary heat - only for heat pump systems with more
5 1-10 Cycles per hour for emergency heat - only for heat pump systems with more
3 1-5 Cycles per hour for 2nd stage compressor - only for systems with two cool
0 0 Comfort
0 0 No - do not reset
compressor (Y)
1 1H/1C, heat pump without auxiliary heat - 1st stage compressor (Y),
changeover (O/B) 2 1H, conventional without fan - 1st stage heat (W) 3 1H, conventional with fan - 1st stage heat (W), fan (G) 4 1C, conventional - 1st stage compressor (Y) 5 2H/1C, heat pump with auxiliary heat - 1st stage compressor (Y), changeover
(O/B), auxiliary heat (Aux/E) 6 2H/1C, conventional - 1st & 2nd stage heat (W,W2), 1st stage compressor (Y) 7 1H/2C, conventional - 1st stage heat (W), 1st & 2nd stage compressor (Y, Y2) 8 2H/2C, heat pump without auxiliary heat - 1st & 2nd stage compressor (Y,
Y2), changeover (O/B) 9 3H/2C, heat pump with auxiliary heat - 1st & 2nd stage compressor (Y, Y2),
changeover (O/B), auxiliary heat (Aux/E)
1 O/B terminal energized in heating
1 Electric furnace, thermostat controls fan in heating
with conventional heat
stages
cool, and off 1 Auto changeover (heat/cool/auto/off) - manually changeover between heat,
cool, and off, or select automatic changeover 2 Auto changeover only (auto) - no manual changeover
1 °F with 0.5 degree resolution 2 °C with 1 degree resolution 3 °C with 0.5 degree resolution 4 °C with 0.1 degree resolution
systems with cool stages - (Minutes specified here are added to the 5 min
base off time.)
1 50 Hz
3 3°F (1.5°C) 4 4°F (2.0°C) 5 5°F (2.5°C) 6 6°F (3.0°C) 7 7°F (3.5°C) 8 8°F (4.0°C) 9 9°F (4.5°C)
conventional systems with at least two stages conventional heat
heat than cool stages
heat than cool stages.
stages
1 Economy
1 Yes - reset all installation configurations (all settings in this table) to default
settings, except System selection
Configuration
BAS-SVX36C-EN 31
Configuration
Table 8. Installation Options for 1-Heat/1-Cool Non-ProgrammableThermostat
No. Name Default Opts. Descriptions
01 System type 0 0 1H/1C, conventional -1st stage heat (W), 1st stage compressor (Y)
02 Changeover
valve
03 Fan control
04 Stage 1 heat
cycle rate
05 Stage 1
compressor cycle rate
06 Manual/Auto
changeover
07 Temperature
indication/ resolution
08 Compressor
protection
09 Heat
temperature range stop
10 Cool temperature
range stop
11 Power supply
frequency
12 Deadband
18 Restore factory
defaults
(1) These options only available on systems with fans. (2) See
“Heat and Cool Cycling Rate,” p. 41. “Deadband,” p. 41. For auto or manual systems (see Option 01).
(3) See
(1)
(2)
(2)
(3)
0 0 O/B terminal energized in cooling
0 0 Gas or oil furnace, equipment controls fan for heating
5 1-10 Cycles per hour for 1st stage conventional heat - only available on systems
3 1-5 Cycles per hour for 1st stage compressor - only available on systems with cool
0 0 Manual changeover (heat/cool/off ) - manually changeover between heat,
0 0 0°F with 1 degree resolution
5 0-5 Minutes for compressor off time - only available on heat pump systems or
90 40-90 Heating high temperature range stop in °F. (4.5-32°C)
50 50-99 Cooling low temperature range stop in °F. (10-37°C)
0 0 60 Hz
3 2 2°F (1.0°C)
0 0 No - do not reset
1 1H/1C, heat pump - 1st stage compressor (Y), changeover (O/B) 2 1H, conventional, without fan - 1st stage heat (W) 3 1H, conventional with fan -1st stage heat (W), fan (G) 4 1C, conventional - 1st stage compressor (Y)
1 O/B terminal energized in heating
1 Electric furnace, thermostat controls fan in heating
with conventional heat
stages
cool, and off 1 Auto changeover (heat/cool/auto/off) - manually changeover between heat,
cool, and off, or select automatic changeover 2 Auto changeover only (auto) - no manual changeover
1 °F with 0.5 degree resolution 2 °C with 1 degree resolution 3 °C with 0.5 degree resolution 4 °C with 0.1 degree resolution
systems with cool stages - (Minutes specified here are added to the 5 min base
off time.)
1 50 Hz
3 3°F (1.5°C) 4 4°F (2.0°C) 5 5°F (2.5°C) 6 6°F (3.0°C) 7 7°F (3.5°C) 8 8°F (4.0°C) 9 9°F (4.5°C)
1 Yes - reset all installation configurations (all settings in this table) to default
settings, except System selection
32 BAS-SVX36C-EN
Operation
This section provides general descriptive and procedural information intended for typical daily
operators of the thermostat.
Icon Descriptions
Figure 36 describes the icons visible on the front of the thermostat.
Note: Except when the thermostat is powering up, when all of the icons are shown for 2 sec, only
Figure 36. Thermostat Icons
some of the icons will be visible at once.
Large numeric display - Shows current temperature but
can indicate other information.
Setpoint indicator - upper arrow
indicates cooling setpoint; lower arrow
indicates heating setpoint.
Heating mode indicator - heating, cooling,
automatic heating/cooling, or off.
Time of day - 12 hour clock with AM and PM
indicator or 24 hour clock.
Configuration/test indicator - solid for
configuration mode; flashing for test mode.
Space unoccupied indicator.
Timed override indicator
Space occupied indicator
Button lock indicator
Overview of Operation
If configured properly, bothprogrammable and non-programmable thermostats will control HVAC equipment to maintain room temperature automatically.
.
Mo Tu We Th Fr Sat Su
DAYS
HOURS
Temperature units - F or C. Fan mode indicator - auto or on.
Period indicator - morning, day, evening, night.
.
AM PM
Icons on the non­programmable thermostats have the same function, but no programming/ scheduling-related buttons appear.
BAS-SVX36C-EN 33
Operation
Non-ProgrammableThermostats
Non-programmable thermostats do not have timekeeping or scheduling capabilities.They will continue to maintain heating and/or cooling setpoints until an operator makes changes to the setup.Therefore, only the following tasks may be required performed:
Change the system mode.
Show or change the heating or cooling temperature setpoint.
Change the fan mode.
Note: The
Changing the System Mode
Note: If you are unable to change the system mode, check thesystem typesetting and the manual/
Depending upon the model and system type, the thermostat can be set to one of five modes: Cooling, Heating, Emergency Heat, Auto, or Off.
system mode, temperature setpoints, and fan mode can each be individually locked to
prevent users from changing them. If you see a
the setting before you change it (see
auto changeover setting (see configured with heat and cool modes, and that it permits manually changing them.
Cooling mode cools the room to bring it down to the cooling setpoint.
Heating mode heats the room to bring it up to the heating setpoint.
Emergency Heat mode heats the room according to the heating unit’s emergency heat mode
settings.
Auto mode switches automatically between heating and cooling modes as required.
Off mode prevents the thermostat from requesting any heating or cooling regardless of the
room temperature. Off mode also disables fan selection and prevents the user from changing the setpoint.
on the display, you may need to unlock
“Locking or Unlocking Modes,” p. 40).
“Configuration,” p. 26) to verify that the thermostat is
Note: The 1-Heat/1-Cool thermostat does not have Emergency Heat mode.
To change the system mode:
1. Press > .The current mode flashes.
2. Press or to select a mode.
3. Tap or wait 5 sec to save and exit.
Showing or Changing the Heating or CoolingTemperature Setpoint
To change the heating or cooling setpoint:
1. Press or once. This shows the active setpoint.
2. Within 5 sec:
ress or to increase or decrease the setpoint.
P
Press or to change between heat and cool setpoints if both are enabled.
3. Tap or wait 5 sec to save and exit.
34 BAS-SVX36C-EN
Changing the Fan Mode
Note: If you are unable to see the fan mode, check the system type setting in the installation
configuration options to make sure that it is specified as a system with a fan.
There are two fan modes. Each are indicated by an icon on the display:
Auto mode turns the fan on and off as needed according to equipment configuration.
On runs the fan continuously.
o change the fan mode:
T
1. Press > > .The current mode flashes.
2. Press or to change the mode.The selected mode flashes.
Note: If
3. Tap or wait 5 sec to save and exit.
you are unable to change the mode and
or Unlocking Modes,” p. 40
ProgrammableThermostats
Programmable thermostats contain all of the functionality of the non-programmable thermostats, but they also keep track of the date, day of week, and time of day for scheduling purposes.
Operation
flashes, the mode is locked. See “Locking
.
Programming
This section describes how to program the thermostat after it has been installed and configured.
Setting theTime
The time must be set in the thermostat to ensure operation of the schedule.
Note: The date is set during configuration and the day of the week is calculated automatically
according to the date.
To set the time:
1. Press > > > > > .The hour flashes to indicate that it can be changed.
Mo
Note: The thermostat automatically returns to normal operating mode if no buttons are
2. Make changes to the hour and minute, as needed:
P
Press or to change the value of the option.
3. Press and hold for 2 sec or wait 10 sec to apply the change and exit.
AM
pressed for 10 sec.
ress or to switch between hours and minutes.The changeable option flashes to
indicate that it can be changed.
BAS-SVX36C-EN 35
Operation
Scheduling
The thermostat can be configured for two periods (day and night) or four periods (morning, day,
evening, and night).The chosen number of periods are applied to each day of the week when you program the thermostat. Each period canhave a unique start time, heat setpoint, cool setpoint, and fan setting.
The groups of days can be one of the following:
1 day = all 7 days of the week follow the same schedule.
5+1+1 days = Monday - Friday all follow the same schedule; Saturday and Sunday each follow their own schedules.
5+2 days = Monday - Fridayall follow the same schedule;Saturday and Sunday follow thesame schedule, which is different than the Monday - Friday schedule.
7 days = Each day follows its own schedule.
Note: See “Configuration,” p. 26 tochange the number of periods in a day or the grouping ofdays
in the schedule.
If needed, you can use Table 9 to write down your schedule settings before you begin setting up the schedule.The default schedule is also shown in the table. Unless you program your own schedule settings, the thermostat follows the default schedule for all days of the week.
36 BAS-SVX36C-EN
Operation
Table 9. Weekly Operating Schedule Worksheet
Heating
Day Period Start time
Four period
default settings
Two period
default settings
Monday Morning : ° ° Auto On
Tuesday Morning : ° ° Auto On
Wednesday Morning : ° ° Auto On
Thursday Morning : ° ° Auto On
Friday Morning : ° ° Auto On
Saturday Morning : ° ° Auto On
Sunday Morning : ° ° Auto On
Morning 6:00 am 70° F (21.0° C) 78° F (25.5° C) Auto
Day 8:00 am 62° F (16.5° C) 85° F (29.5° C) Auto
Evening 6:00 pm 70° F (21.0° C) 78° F (25.5° C) Auto
Night 10:00 pm 62° F (16.5° C) 82° F (28.0° C) Auto
Day 6:00 am 70° F (21.0° C) 78° F (25.5° C) Auto
Night 10:00 pm 55° F (13.0° C) 85° F (29.5° C) Auto
Day : ° ° Auto On
Evening : ° ° Auto On
Night : ° ° Auto On
Day : ° ° Auto On
Evening : ° ° Auto On
Night : ° ° Auto On
Day : ° ° Auto On
Evening : ° ° Auto On
Night : ° ° Auto On
Day : ° ° Auto On
Evening : ° ° Auto On
Night : ° ° Auto On
Day : ° ° Auto On
Evening : ° ° Auto On
Night : ° ° Auto On
Day : ° ° Auto On
Evening : ° ° Auto On
Night : ° ° Auto On
Day : ° ° Auto On
Evening : ° ° Auto On
Night : ° ° Auto On
setpoint
Cooling
setpoint
Fan Setting
BAS-SVX36C-EN 37
Operation
To set the schedule:
1. Press > > > .The display shows only the following elements:
MoTu We Th Fr Sa Su
2. Press .
Note: At
this point the thermostat is in schedule change mode. It returns to normal operating mode if no buttons are pressed for 45 sec.To manually exit schedule change mode, press and hold
for 2 sec.
Note: If flashes and you are unable toenter schedule change mode, the mode is locked. See
“Locking or Unlocking Modes,” p. 40.
3. Press or to select the day or days for which you want to set the schedule.The selected day or days flash.
4. Press to accept the selection. , , ,or starts flashing.
5. Press or to select the period.The selected period starts flashing.
6. Press to accept the selection. The start time starts flashing.
Mo
AM
7. Press or to select the start time. Time is increased or decreased in 10 min steps.
8. Press to accept the selection. If there is a heat mode configured, the heat setpoint appears and its icons start flashing.
9. Press or to select the heating setpoint.
Note: The
heating and cooling setpoints cannot be closer together than the deadband, which
is specified in installer configuration option #0181 (see
“Configuration,” p. 26). If you
raise the heating setpoint or reduce the cooling setpoint to a value that would violate the
deadband setting, the opposing setpoint will also adjust to maintain the deadband.
10. Press to accept the selection. If there is a cool mode configured, the cooling setpoint appears and its icons start flashing.
11. Press or to select the cool setpoint.
12. Press to accept the selection. or starts flashing.
13. Press or to select the fan setting.
to
turn it on and off automatically
to keep the fan on continuously
14. Press to accept the selection. This completes the schedule settings for one period of one day of the week.
15. Repeat
Step 3 through Step 14 once for each day and period you need to set.
38 BAS-SVX36C-EN
Day-to-Day Operation
After a programmable thermostat is configured and the schedule is programmed, the thermostat
automatically changes the setpoints and fan settings accordingto theschedule.However,there are some operator tasks that you may need or want to perform:
Show setpoint or current temperature.You can temporarily or permanently switch the main display from current temperature to temperature setpoint. See
Temperature on Display,” p. 39
Set the system mode, which includes turning the system on or off, and switching between heating,
Override the schedule. If an unexpected, one-time temperature setpoint or fan mode change is needed you can temporarily override the schedule. See “Timed Override (TOV) Mode,” p. 40.
Lock or unlock.You can lock the thermostat buttons to prevent changes to the thermostat set
Note: It is possible for a programmable thermostat to be configured to be a non-programmable
Showing the Setpoint orTemperature on Display
Depending upon the value of configuration option #210, the large numeric display could show any of the following:
Figure 37. Display Options
Operation
“Showing the Setpoint or
.
cooling, and automatic heating and cooling. See
tings. See
“Locking or Unlocking Modes,” p. 40.
thermostat. If installation configuration option #140 is set to 0, schedule programming capabilities will be absent.
“Changing the System Mode,” p. 34.
“o dr” indicates outdoor
Arrow indicates
setpoint
Mo
.
AM
.
Current temperature Current (or most
Value of configuration option #210
0 The current local temperature, or the current or most recent temperature setpoint
1 or 2 The current local or remote indoor temperature or the current or most recent temperature
3 The current indoor temperature, the current or most recent temperature setpoint, or the
Numeric display options (press and for 3 sec to change)
setpoint
current remote outdoor temperature, which only appears for 8 sec before reverting to current indoor temperature or setpoint
recent) setpoint
temperature (after 8 sec, returns to previous mode)
Current outdoor temperature
To switch between the current temperature, “o dr” temperature, and the setpoint temperature,
press and hold the and buttons for 3 sec.The display will toggle as shown in
Figure 37.
BAS-SVX36C-EN 39
Operation
Timed Override (TOV) Mode
During normal operation, the thermostat controls the HVAC equipment according to the schedule that is programmed into it.To permanently change the temperature setpoint or fan setting, make the change in the programmed schedule (see “Scheduling,” p. 36). However, a timed override can be used to temporarily change the current settings without making any change to the schedule.
To start a temperature setpoint override:
1. Press or . The current temperature setpoint appears.
2. Within 5 sec of thermostat enters timed override mode, giving you the opportunity to specify the other parameter
3. Press and release or (or , which has the same function as ) to scroll to heating or cooling temperature setpoints, fan mode, override duration, or occupancy setting.
4. When youreach the functionyou want tochangeas part of theoverride,press and make the changes.
5. Once you have specified all needed changes, press and hold for 2 sec or wait 15 sec to save and exit.
6. Press and hold and for 2 sec from the home screen or when inTOV setup mode to exit without enteringTOV mode.
Step 1, press to raise the setpoint or to lower the setpoint.The
s of the override.
Locking or Unlocking Modes
You can independently lock and unlock the system, fan, and schedule change modes.When a lock
is activated, users cannot change the current mode or schedule settings. If you attempt to make a change, flashes on the display.
To lock a mode:
1. Enter the mode you want to lock:
>
> > for fan mode
> > > for schedule mode (programmable thermostat only)
2. Make surethat the mode or schedule you enteredis correct; if not, make the necessary changes.
3. Simultaneously press and hold and for 4 sec. When the mode is locked, appears on the display.
To unlock a mode:
1. Enter the mode you want to unlock:
>
> > for fan mode
> > > for schedule mode (programmable thermostat only)
2. Simultaneously press and hold and for 4 sec.When the mode is unlocked, disappears.
> for system mode
> for system mode
40 BAS-SVX36C-EN
Operational and Programming Reference Information
This section provides additional information that may be useful for understanding thermostat
operation or programming.
Deadband
The thermostat automatically maintains a temperature deadband between the heating setpoint
and the cooling setpoint whenever automatic changeover (heat-to-cool or cool-to-heat mode) is enabled.The temperature range of the deadband is 2–9 °F (1.0–4.5°C) and is specified in the installation configuration options (see temperature setpoint to within the deadband of its opposing setpoint, the opposing setpoint will automatically be pushed to the next value that satisfies the deadband. (See
Heat and Cool Cycling Rate
The heat and cool cycling rate, expressed in cycles per hour (CPH) indicates how often heating or
cooling system is turned on when temperature is within the temperature differential from the setpoint, which is 1°F (0.5°C).There are ten options (1–10) for heat stages and five options (1–5) for cool stages.The number selected is the maximum number of times the stage is cycled in 1 hr.
For example, when the system is set to 5 CPH, it runs at 12 min cycles with variable duty cycle. Depending on the heating or cooling load, which is measured by feedback from the sensor thermistor and/or temperature error, the system could run at 50% duty cycle (6 min ON and 6 min OFF), 80% duty cycle (9.6 min ON and 2.4 min OFF), or other variations of the duty cycle.
Note: The
cycling rate described above is only active when the temperature is within the temperature differential. If the temperature is outside of the temperature, the heating and cooling equipment will either be fully on or fully off accordingly. (See
“Configuration,” p. 26). If you attempt to change a
Figure 38.)
Figure 38.)
Figure 38. General Heat and Cool Cycling Rate Diagram
Output
100 %
0 %
All heat
stages on
All heat stages
cycling dependent
on load
TD TDTD
Heat set point
temperature differential
(TD) is ±1°F (0.5°C)
centered on set point
There is one cycling rate setting for each of the thermostat’s available heat and cool stages,
including auxiliary and emergency heat stages.You can specify them during installation configuration. See
“Configuration,” p. 26.
Minimum Compressor OffTime
To protect the compressor from cycling too frequently, there is an automatic 5 min gap between
cycles.You cannot reduce the gap, but you can add up to 5 min if needed. See
p. 26
.
All heat and cool
stages off
Adjustable deadband
2–9°F (1–4.5°C)
All cool stages
cycling dependent
on load
TD
Cool set point
temperature differential
(TD) is ±1°F (0.5°C) centered on set point
“Configuration,”
All cool
stages on
Temperature
BAS-SVX36C-EN 41
Operational and Programming Reference Information
Configuration and Programming Retention
The thermostat retains the time and date for a minimum of 5 days with no electricity. If power is
lost for more than 5 days, you will need to reset the time and date when power is restored.
All configuration parameters, system settings, and scheduling are stored in non-volatile memory,
which will retain the data indefinitely with or without power.
Note: You canmanually revert todefault settings bysetting the appropriateinstallation parameter
(#300 for programmable thermostats or #18for non-programmable thermostats)to avalue of 1, and exiting configuration mode.
Extended Fan-onTime (Heat or Cool)
Note: This feature applies only to the programmable thermostat.
When the thermostat fan is in Auto mode, the fan on time can be extended.
Configuration option #270 extends the fan on time by 90 sec after heat turns off.
Configuration option #271extends the fan on time by 40 sec after cool turns off.
These options may not be available for some system configurations. See
Compressor and Auxiliary Heat Lockout
Note: This feature applies only to the programmable thermostat.
Compressor and auxiliary heat is used for heat pump systems with more heat stages than cool stages. When the temperature from an outdoor sensor is
above the auxiliary lockout point, only the compressor will operate on a call for heat.
below the compressor lockout point, only the auxiliary heat will operate on a call for heat.
between the compressor and auxiliary lockout point, the compressor and auxiliary heat will operate on a call for heat.
There is a minimum 5°F (2.5°C) deadband between compressor and auxiliary heat lockout
temperatures. Configuration option #220 sets the compressor lockoutpoint; #221 sets the auxiliary lockout point. See
“Configuration,” p. 26.
“Configuration,” p. 26.
Auxiliary Heat Control
Note: This feature applies only to the non-programmable 3-Heat/2-Cool thermostat.
You can set the auxiliary heat control using configuration option #17 to one of two settings:
Comfort - prioritizes comfort over economy. Raising the temperature just a few degrees often will activate the auxiliary heat.
Economy - attempts to reach the temperature setting without activating the auxiliary heat.
Economizer/TOD
Note: This feature applies only to the programmable thermostat.
You can set the Economizer orTOD mode using configuration option #150 to one of two settings:
Economizer Mode - “A” terminal is energized with the thermostat in Occupied mode, Unoccupied mode with a call for cool, or aTimed Override mode (TOV) active.
TOD Mode - “A” terminal is energized with thermostat in Occupied mode or aTimed Override mode (TOV) active.
42 BAS-SVX36C-EN
Troubleshooting
This section describes troubleshooting for the thermostat.
Error Codes
An error code indicates that technical assistance may be required.
Try cycling the power to the thermostat as a first method to clear the error. See
Table 12, p. 47 for additional information.
Note: On
Note: On
Table 10. Error Codes
Code Description
E0 Thermistor Error; occurs when the configured thermistor reading is out of range (less
E3 Permanent data error. Access error or checksum error is detected.
E4 Input voltage out of range - too low or too high. Input voltage is lower than 18Vac or
E5 RTC Error (this error can only appear on the programmable thermostat).
E7 Memory error (write and read 0x55 and 0xAA failed). Only checked during power up test.
Table 10 below and
the display, error codes appear at the bottom of the display.
the programmable thermostat, the error code alternates with the time on the display.
than 14°F (-9.9°C) or greater than 122°F (50°C). If this error occurs:
• All Heat/Cool outputs turn off.
• If the fan mode is Auto, the thermostat turns off the fan.
• If the fan mode is On, the thermostat leaves the fan on.
higher than 34V of out of range input voltage.
ac. The error code display will remain on for 30 sec after the detection
SystemTest Mode
You can run diagnostic tests on the thermostat to verify that thethermostat is functioning properly
and that the devices in the system are wired properly.
To enter system test mode:
1. Apply electrical power to the thermostat.
2. Enter installer configuration mode:
BAS-SVX36C-EN 43
Troubleshooting
WARNING
Live Electrical Components!
The circuit board is energized. Have a qualified licensed electrician or other individual who has
been properly trained in handling live electrical components perform this step. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
a. Remove the thermostat cover.
b. Press and hold the configuration button for at least 3 sec, then release it.
Figure 39. Pressing the Configuration Button
Programmable 3H/
2C configuration
button
Thermostat Non-Prog XH/XC
X########-## Rev X
BAYSTAT15#X
####XXX
Non-programmable
thermostats
configuration button
The configuration wrench icon appears, along with the option number and value.
3. Press and hold the configuration button again for at least 3 sec, then release it.The thermostat
into system test mode:
goes
wrench icon flashes.
The
The system test number appears in small digits at the lower part of the display.
The test setting value appears in large digits at the top part of the display.
Figure 40. System Test Mode
Value
System Test Number
Programmable Thermostat
Non-Programmable Thermostat
Note: System test mode automatically ends if no buttons are pressed for 10 min.
While in system test mode, you can scroll from one test to the next, change the value for the
then test or observe thesystem for the expected result.The numbers and values are shown
test,
Table 11 , p . 46. Some values are retained when you scroll to the next number; others are
in deactivated when you scroll to the next number, as indicated in the table.
4. Press , ,or to scroll through the options, identified by their numbers, until you reach the option you want to change:
or scrolls to the next larger numbered option. scrolls to the next lower-numbered option.
44 BAS-SVX36C-EN
Troubleshooting
5. Use or to change the value of the option:
decreases the value.
increases the value.
6. Repeat
7. Change the value of the power up test (test number 8 for the 1-Heat/1-Cool thermostat; test
8. Do one of the following to exit test mode:
Step 4 and Step 5 until you have conducted all needed tests.
number you exit test mode.
R
Do not press any buttons for 10 min.
Press and hold for 2 sec.
11 for the 3-Heat/2-Cool or programmable thermostat) to 1 to run a power up test after
emove the thermostat cover, if necessary, and then press and immediately release the
configuration button.
BAS-SVX36C-EN 45
Troubleshooting
Table 11. System Test Descriptions
Test Number
1H/1C Thermostat
(p/n X13511535-01)
3H/2C Thermostat
(1)
1
1
(1)
2
2 2 Cooling system 0 = all cooling stages off
333 Fan system 0 = fan off
NA 4 4 O/B changeover valve 0 = changeover valve off
NA NA 5 TOD/Economizer system 0 = TOD/Economizer off
NA 5 NA Auxiliary Heat 0 = Auxiliary heat and fan turns off
NA 6 NA Emergency Heat 0 = Emergency relay, fan, and terminal L output turn off
586 LCD segments 0 = full segment on
NA NA 7 Remote thermistor (S1 & S2)
478 Internal thermistor
699 Major software version Show major software revision number.
71010 Minor software version Show minor software version.
81111 Power up test 0 = do not run power up test on self-test exit
(1) Only values 0 and 1 are available because there are only one heat and one cool stage.
Description Values
(p/n X13511536-01)
Programmable
Thermostat
1 Heating system 0 = all heating stages off
temperature reading
temperature reading
1 = heat stage 1 on; heat stage 2 off 2 = heat stage 2 on; heat stage 1 off 3 = heat stage 1 and 2 on This setting remains active when you scroll to the next setting.
1 = cool stage 1 on; cool stage 2 off 2 = cool stage 2 on; cool stage 1 off 3 = cool stage 1 and 2 turn on This setting remains active when you scroll to the next setting.
1 = fan on This setting remains active when you scroll to the next setting.
1 = changeover valve on This setting remains active when you scroll to the next setting.
1 = TOD/Economizer on This setting remains active when you scroll to the next setting.
1 = Auxiliary heat and fan turns off This setting remains active when you scroll to the next setting.
1 = Emergency relay, fan, and terminal L output turn on This setting remains active when you scroll to the next setting.
1 = odd segments on; even segments off 2 = even segments on; odd segments off This setting is deactivated when you scroll to the next setting.
0 = show temperature reading in Fahrenheit 1 = show temperature reading in Celsius This setting is deactivated when you scroll to the next setting.
0 = show temperature reading in Fahrenheit 1 = show temperature reading in Celsius This setting is deactivated when you scroll to the next setting for the 3H/2C and programmable thermostats, but it remains active when you scroll to the next setting for the 1H/1C thermostat.
This setting is deactivated when you scroll to the next setting.
This setting is deactivated when you scroll to the next setting.
1 = run power up test on self-test exit This setting retained (and applied) upon exit from self-test mode.
46 BAS-SVX36C-EN
Troubleshooting Table
Table 12 to diagnose and solve problems you may encounter.
Use
Table 12. Troubleshooting
Problem Solution
Error code E0 ­Thermistor error.
Error code E4 - Input voltage out of range
Error codes E3, E5, or E7 • Cycle the power to the thermostat.
Blank display • Check the power supply.
Erratic display appearance or contrast
Buttons do not respond • Make sure the thermostat modes are not locked. See
“--F” or “--C” flashes • Temperature is outside of the measurable range. The temperature reading should be
Fan settings are not visible
Troubleshooting
• For non-programmable thermostats and programmable thermostats set to use internal temperature sensor (configuration option #210 set to 0, 1, or 2): Thermistor is defective or local temperature is out of range. Replace or repair thermostat through a qualified Trane supplier.
• For programmable thermostats with configuration option #210 set to 3: Check the sensor terminals S1 and S2 for secure connection. If wires are securely connected, try replacing the sensor.
• Check the input voltage to the thermostat. It must be within the range of 18Vac to 32 Vac rms.
• If it does not recover to normal operation, have it serviced or replaced by a qualified Trane supplier.
• If the power supply is ok, have the thermostat serviced or replaced by a qualified Trane supplier.
• Check the power supply.
• Check the frequency configuration (Configuration option #210 for the programmable thermostat or #11 for non-programmable thermostats) to make sure that you are using the correct frequency setting for your power supply.
• If the power supply and frequency setting are ok, have the thermostat serviced or replaced by a qualified Trane supplier.
p. 40
.
• Cycle the power to the thermostat.
• If the modes are not locked and cycling the power do not solve the problem, have the thermostat serviced or replaced by a qualified Trane supplier.
correct when the temperature is within the measurable range.
• Check the system status. If the status is Off, the fan settings will not appear.
• Check the configuration options to verify that the fan is enabled: For programmable thermostats, check options 0130 and 0151; For non-programmable thermostats, check options 01 and 03.
“Locking or Unlocking Modes,”
BAS-SVX36C-EN 47
Thermostat Specifications
Table 13. Specifications
Programmable Thermostat Non-Programmable Thermostats
Input power 24Vac, 50Hz or 60Hz
Wire size 18 to 22 AWG 18 to 22 AWG
Output terminal ratings 1A @ 30Vac 1A@ 30Vac
Indoor temperature display range
Outdoor (remote) temperature display range
Storage temperature
Accuracy ±1.4°F (±0.8°C) over a range of
Resolution Configurable: 1.0°F, 0.5°F, 1°C, 0.5°C,
Power consumption
Housing materials and rating information
Mounting
(18Vac to 32Vac) (Power supply frequency selected using installation configuration option #190)
+15 to +122°F (–9.5 to +50°C) +32 to +99°F (0 to +37°C)
–31 to +122°F (–35 to +50°C)
–40 to +158°F (–40 to +70°C) –40 to +158°F (–40 to +70°C)
50 to 90 °F (10 to 32.2°C)
0.1°C
< 1VA < 1VA
Polycarbonate/ABS blend, UV protected, UL 94-5VA flammability rating, suitable for application in a plenum.
3.24 in (8.26 cm) for two mounting screws (supplied)
24Vac, 50Hz or 60Hz (18Vac to 32Vac) (Power supply frequency selected using installation configuration option #11)
NA
±1.4°F (±0.8°C) over a range of 50 to 90 °F (10 to 32.2°C)
Configurable: 1.0°F, 0.5°F, 1°C, 0.5°C, 0.1°C
Polycarbonate/ABS blend, UV protected, UL 94­5VA flammability rating, suitable for application in a plenum.
3.24 in (8.26 cm) for two mounting screws (supplied)
Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the
leader in creating and sustaining safe, comfortable and energy efficient environments, Trane offers a broad portfolio of advanced controls and HVAC systems, comprehensive building services, and parts. For more information, visit www.Trane.com.
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.
© 2012 Trane. All rights reserved.
BAS-SVX36C-EN 13 Mar 2012
Supersedes BAS-SVX36B-EN 30 Sep 2010
Loading...