Trane TSC036E, TSC060E, THC036E, THC060E, TSC072F Installation And Maintenance Manual

...
Installation, Operation, and Maintenance
Packaged Rooftop Air Conditioners Precedent™- Electric/Electric
Model Numbers
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or alter ed equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.
July 2012 RT-SVX22J-EN
TSC036E - TSC060E THC036E - THC060E TSC072F - TSC1 20F THC092E - THC120E
THC048F - THC092F
SAFETY WARNING
Warnings, Cautions and Notices
Warnings, Cautions and Notices. Note that warnings,
cautions and notices appear at appropriate intervals throughout this manual. Warnings are provide to alert installing contractors to potential hazards that could result in death or personal injury . Cautions are designed to alert personnel to hazardous situations that could result in personal injury, while notices indicate a situation that could result in equipment or property-damage-only accidents.
Your personal safety and the proper operation of this machine depend upon the strict observance of these precautions.
Read this manual thoroughly before operating or servicing this unit.
ATTENTION: Warnings, Cautions and Notices appear at
appropriate sections throughout this literature. Read these carefully:
WARNING
CAUTIONs
NOTICE:
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
Indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury. It could also be used to alert against unsafe practices.
Indicates a situation that could result in equipment or property-damage only
Important Environmental Concerns!
Scientific research has shown that certain man-made chemicals can affect the earth’s naturally occurring stratospheric ozone layer when released to the atmosphere. In particular, several of the identified chemicals that may af fect the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact to the environment. T rane advocates the responsible handling of all refrigerants-including industry replacements for CFCs such as HCFCs and HFCs.
Responsible Refrigerant Practices!
Trane believes that responsible refrigerant practices are important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified. The Federal Clean Air Act (Section 608) sets forth the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these service procedures. In addition, some states or municipalities may have additional requirements that
must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them.
WARNING
Proper Field Wiring and Grounding Required!
All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, y ou MUST f ollow r equir ements for field wiring installation and grounding as described in NEC and your local/state electrical codes. Failure to follow code could result in death or serious injury.
WARNING
Personal Protective Equipment (PPE) Required!
Installing/servicing this unit could result in exposure to electrical, mechanical and chemical hazards.
Before installing/servi cin g th is un it, technicians MUST put on all P ersonal Protective Equipmen t (PPE) recommended for the work being undertaken. AL W A YS r efer to appr opriate MSDS sheets and OSHA guidelines for proper PPE.
When working with or ar ound hazar dous chemi cals, ALWAYS refer to the appropriate MSDS sheets and OSHA guidelines for information on allowable personal exposure levels, proper respiratory protection and handling recommendations.
If there is a risk of arc or flash, te chnicians MUST put on all Personal Protective Equipment (PPE) in accordance with NFPA 70E or other country-specific requirements for arc flash protection, PRIOR to servicing the unit.
Failure to f ollow recommendations could result in death or serious injury.
Revision Summary
RT-SVX22J-EN (18 July 2012)
MERV 8 filter with filter removal tool
Stainless steel drain pan, condensate overflow switch
Updated Model Number Description, Maintenance, Troubleshooting
© 2012 Trane All rights reserved RT-SVX22J-EN
Table of Contents
Model Number Description . . . . . . . . . . . . . . . 5
Model Number Notes . . . . . . . . . . . . . . . . 6
General Information . . . . . . . . . . . . . . . . . . . . . 7
Unit Inspection . . . . . . . . . . . . . . . . . . . . . . 7
Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Unit Nameplate . . . . . . . . . . . . . . . . . . . . . 7
Compressor Nameplate . . . . . . . . . . . . . . . 7
Microchannel Condenser Barcode ID . . . . 7
Unit Description . . . . . . . . . . . . . . . . . . . . . 7
Economizer Control Actuator (Optional) . 7
System Input Devices & Functions . . . . . . 8
Low Pressure Control . . . . . . . . . . . . . . . . . 9
High Pressure Control . . . . . . . . . . . . . . . . 9
Power Exhaust Control (Optional) . . . . . . 9
Lead/Lag Control (Dual Circuit Only) . . . . 9
Evaporator Frost Control . . . . . . . . . . . . . 10
Discharge Line Temp Switch (DLTS) . . . 11
Smoke Detector Sensor (Optional) . . . . . 11
Phase Monitor . . . . . . . . . . . . . . . . . . . . . 11
Single Zone Variable Air Volume / Displace-
ment Ventilation (Optional) . . . . . . . . . . . 11
Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . 12
Unit Clearances . . . . . . . . . . . . . . . . . . . . . . 12
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Pre-Installation . . . . . . . . . . . . . . . . . . . . . . . 19
Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Foundation . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Horizontal Units . . . . . . . . . . . . . . . . . . . . 21
Ductwork . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
RoofCurb . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Downflow . . . . . . . . . . . . . . . . . . . . . . . . . 23
Rigging . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
General Unit Requirements . . . . . . . . . . . . 25
Factory Installed Economizer . . . . . . . . . 25
Temperature Limit Switch Usage for Electric
Heat Units . . . . . . . . . . . . . . . . . . . . . . . . . 25
Horizontal Discharge Conversion (3 Through 5
Ton Units)
. . . . . . . . . . . . . . . . . . . . . . . . . . . .25
Horizontal Discharge Conversion (6 Through 10 Ton Units)
TCO-A Instructions . . . . . . . . . . . . . . . . . . .26
. . . . . . . . . . . . . . . . . . . . . . . . .25
Return Air Smoke Detector . . . . . . . . . . . . .27
Main Electrical Power Requirements . . . .28
Electric Heat Requirements . . . . . . . . . . . .28
Low Voltage Wiring
(AC & DC) Requirements . . . . . . . . . . . . . .28
Condensate Drain Configuration . . . . . . . . .28
Filter Installation . . . . . . . . . . . . . . . . . . . . . .29
Field Installed Power Wiring . . . . . . . . . . . .29
Main Unit Power . . . . . . . . . . . . . . . . . . . . . .30
Standard Wiring . . . . . . . . . . . . . . . . . . . . .30
Optional TBUE Wiring (Through the Base
Electrical Option) . . . . . . . . . . . . . . . . . . . .30
Field Installed Control Wiring . . . . . . . . . .30
Control Power Transformer . . . . . . . . . . .31
Controls using 24 VAC . . . . . . . . . . . . . . . .31
Controls using DC Analog Input/Outputs (Standard Low Voltage Multi
conductor Wire) . . . . . . . . . . . . . . . . . . . . .31
Smoke Detector Customer Low Voltage Wir­ing
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36
Space Temperature Averaging (ReliaTel™ on­ly)
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36
Pre-Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .40
Voltage Imbalance . . . . . . . . . . . . . . . . . . . . .40
Electrical Phasing (Three Phase Motors) . .40
Compressor Crankcase Heaters (Optional) 41
ReliaTel™ Controls . . . . . . . . . . . . . . . . . .41
Test Modes . . . . . . . . . . . . . . . . . . . . . . . . . . .42
Electromechanical Controls
Test Procedure . . . . . . . . . . . . . . . . . . . . . .42
Start-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .43
Verifying Proper Air Flow . . . . . . . . . . . . . . .43
Units with 5-Tap Direct Drive Indoor Fan .43
Units with Belt Drive Indoor Fan . . . . . . . .43
Units with Direct Drive Indoor Fan - Electro-
RT-SVX22J-EN 3
Table of Contents
mechanical Control . . . . . . . . . . . . . . . . . 44
ReliaTel units with Direct Drive Indoor Fan (7.5 - 10 Ton High Efficiency, 10 Ton Standard
Efficiency) . . . . . . . . . . . . . . . . . . . . . . . . . 44
Units with Constant CFM Direct Drive Indoor
Fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Return Air Smoke Detector . . . . . . . . . . . . . 45
Economizer Start-Up . . . . . . . . . . . . . . . . . . 46
Compressor Start-Up . . . . . . . . . . . . . . . . . 47
Dehumidification Option . . . . . . . . . . . . . . . 47
Final System Setup . . . . . . . . . . . . . . . . . . . 48
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Fan Belt Adjustment - Belt Drive Units . . . 49
Monthly Maintenance . . . . . . . . . . . . . . . . . 49
Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Return Air Smoke Detector Maintenance 50
Cooling Season . . . . . . . . . . . . . . . . . . . . 50
Heating Season . . . . . . . . . . . . . . . . . . . . 50
Coil Cleaning . . . . . . . . . . . . . . . . . . . . . . . 50
Annual Maintenance . . . . . . . . . . . . . . . . . . 51
Final Process . . . . . . . . . . . . . . . . . . . . . . . . . 52
Set Point (HSP) . . . . . . . . . . . . . . . . . . . . . .55
Test 3 - System Mode and Fan Selection .55 Test 4 - LED Indicator Test, (SYS ON, HEAT,
COOL & SERVICE) . . . . . . . . . . . . . . . . . . .55
Method 1 . . . . . . . . . . . . . . . . . . . . . . . . . . .55
Method 2 . . . . . . . . . . . . . . . . . . . . . . . . . . .55
Method 3 . . . . . . . . . . . . . . . . . . . . . . . . . . .55
Relative Humidity Sensor Test . . . . . . . . .55
Programmable & Digital Zone
Sensor Test . . . . . . . . . . . . . . . . . . . . . . . . .56
ReliaTel Refrigeration Module (RTRM) De-
fault Chart . . . . . . . . . . . . . . . . . . . . . . . . . .56
Unit Operation without a Zone Sensor . .56
Unit Economizer Control (ECA) Troubleshoot­ing
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .56
ReliaTel Control . . . . . . . . . . . . . . . . . . . . .56
Electro Mechanical Control . . . . . . . . . . . .57
Unit Economizer Control (ECA) Test Proce­dures
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .57
Electro Mechanical Control . . . . . . . . . . . .57
Troubleshooting procedures for Direct Drive Plenum Fan
. . . . . . . . . . . . . . . . . . . . . . . . . . .57
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . 53
ReliaTel™ Control . . . . . . . . . . . . . . . . . . . . 53
System Status Checkout Procedure . . . . . 53
Method 1 . . . . . . . . . . . . . . . . . . . . . . . . . . 53
System failure . . . . . . . . . . . . . . . . . . . . . . 53
Cooling Failure . . . . . . . . . . . . . . . . . . . . . 54
Service Failure . . . . . . . . . . . . . . . . . . . . . 54
Simultaneous Heat and Cool Failure . . . 54 Resetting Cooling and Ignition Lockouts 54
Method 1 . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Method 2 . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Zone Temperature Sensor (ZTS) Service Indi­cator
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Clogged Filter Switch . . . . . . . . . . . . . . . . 55
Fan Failure Switch . . . . . . . . . . . . . . . . . . 55
Condensate Overflow Switch . . . . . . . . . 55
Zone Temperature Sensor (ZTS) Test . . . 55
Test 1 - Zone Temperature Thermistor
(ZTEMP) . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Test 2 - Cooling Set Point (CSP) and Heating
Unit Wiring Diagrams Numbers . . . . . . . . . . .59
Limited Warranty . . . . . . . . . . . . . . . . . . . . . . . .61
Electric Air Conditioner . . . . . . . . . . . . . . . . .61
TCY, TCX, TCC, TCD, TCH, TCM,TCP, TSC and THC (Parts Only) Models Less Than 20 Tons
for Residential Use* . . . . . . . . . . . . . . . . . .61
Electric Air Conditioner . . . . . . . . . . . . . . . . .62
TCY, TCX, TCC, TCD, TCH, TCK, TCM, TCP, TSC and THC (Parts Only) Models Less Than
20 Tons for Commercial Use* . . . . . . . . . .62
4 RT-SVX22J-EN
Model Number Description
TSC 036 E 3 R Z B ** 123 456 7 8 9 10 11 1213
Digit 1 - Unit Type
T DX Cooling
Digit 2 - Efficiency
S Standard Efficiency HHigh Efficiency
Digit 3 - Airflow
C Convertible
Digit 4,5,6 - Nominal Gross Cooling Capacity (MBh)
036 3 Ton 048 4 Ton 060 5 Ton 072 6 Ton 090 7½ Ton, Single Compressor 092 7½ Ton, Dual Compressor 102 8½ Ton 120 10 Ton
Digit 7 - Major Design Sequence
E R-410A Refrigerant F Microchannel Type Condenser
Coils
23
Digit 8 - Voltage Selection
1 208/230/60/1 3 208-230/60/3 4 460/60/3 W 575/60/3
Digit 9 - Unit Controls
E Electromechanical R ReliaTel™ Microprocessor
Digit 10 - Heating Capacity
0=No Electric Heat F=14 kW (1 phase) A=5 kW (1 phase)1G=18 kW (1&3 phase) B=6 kW (3 phase) J=23 kW (3 phase) C=9 kW (3 phase) K= 27 kW (3 phase) D=10 kW (1 phase) E=12 kW (3 phase) P = 54 kW (3 phase)
1
N = 36 kW (3 phase)
Digit 11 - Minor Design Sequence
A First Sequence B Second Sequence
20
19
Digit 12,13 - Service Sequence
** Factory Assigned
Digit 14 - Fresh Air Selection
0No Fresh Air A Manual Outside Air Damper 0-50% B Motorized Outside Air Damper
0-50%
27
C Economizer, Dry Bulb 0-100%
without Barometric Relief
D Economizer, Dry Bulb 0-100%
with Barometric Relief
E Economizer, Reference Enthalpy
0-100% without Barometric Relief
F Economizer, Reference Enthalpy
0-100% with Barometric Relief
G Economizer, Comparative
Enthalpy 0-100% without Barometric Relief
3,7
H Economizer, Comparative
Enthalpy 0-100% with Barometric
3,7
Relief
Digit 15 - Supply Fa n/Drive Type/ Motor
0 Standard Drive 1 Oversized Motor 2 Optional Belt Drive Motor 6 Single Zone Variable Air Volume 7 Multi-Speed Indoor Fan
6
Digit 16 - Hinged Service Access/Filters
0 Standard Panels/Standard Filters A Hinged Access Panels/Standard
Filters B Standard Panels/2” MERV 8 Filters C Hinged Access Panels/2” MERV 8
1
Filters D Standard Panels/2” MERV 13 Filters E Hinged Access Panels/2” MERV 13
Filters
Digit 17 - Condenser Coil Protection
0 Standard Coil 1 Standard Coil with Hail Guard 2 Black Epoxy Pre-Coated Condenser
24
Coil 3 Black Epoxy Pre-Coated
Condenser Coil with Hail Guard 4 CompleteCoat™ Condenser Coil 5 CompleteCoat™ Condenser Coil
with Hail Guard
Digit 18 - Through the Base Provisions
0 No Through-the-Base Provisions A Through-the-Base Electric
Digit 19 - Disconnect/Circuit Breaker (three-phase only)
0 No Disconnect/No Circuit Breaker 1 Unit Mounted Non-Fused
Disconnect 2 Unit Mounted Circuit Breaker
8
Digit 20 - Convenience Outlet
0 No Convenience Outlet
4
A Unpowered Convenience Outlet B Powered Convenience Outlet
(three-phase only)
7
7
3,7
3,7
Digit 21 - Communications
Sensor
29
DCV
3
29
Options
0 No Communications Interface 1 Trane Communications Interface 2 LonTalk® Communications Interface 3 Novar 2024 Controls 4 Novar 3051 Controls without Zone
5 Novar 3051Controls Interface with
9
29
6 BACnet™ Communications Interface
Digit 22 - Refrigeration System Option
0 Standard Refrigeration System B Dehumidification Option
10
21,22
Digit 23 - Refrigeration Controls
17
25
26
Note: Applicable to Digit 7 = E, F
0 No Refrigeration Control 1Frostat 2 Crankcase Heater 3Frostat
11,28
11,28
and Crankcase Heater
5
2
Digit 24 - Smoke Detector
0 No Smoke Detector A Return Air Smoke Detector B Supply Air Smoke Detector C Supply and Return Air Smoke
Detectors
12,13
D Plenum Smoke Detector
12,13
16
Digit 25 - System Monitoring Controls
0 No Monitoring Control 1 Clogged Filter Switch 2 Fan Failure Switch 3 Discharge Air Sensing Tube 4 Clogged Filter Switch and Fan
Failure Switch
24
5 Clogged Filter Switch and Discharge
Air Sensing Tube
6 Fan Failure Switch and Discharge Air
Sensing Tube
14
14
7 Clogged Filter Switch, Fan Failure
Switch and Discharge Air Sensing Tube
8 Novar Return Air Sensor
8
(NOVAR 2024)
9 Novar Zone Temp Sensor
(NOVAR 3051)
14
15,29
18,29
A Condensate Drain Pan Overflow
Switch
B Clogged Filter Switch
Condensate Drain Pan Overflow
8
Switch
C Fan Failure Switch
Drain Pan Overflow Switch
D Discharge Air Sensing
Condensate Drain Pan Overflow
14
14
14
14
14
14
14
and
and Condensate
14
and
2
RT-SVX22J-EN 5
Model Number Description
Switch
E Clogged Filter Switch
F Clogged Filter Switch
G Fan Failure Switch, Discharge Air
H Clogged Filter Switch
14
Switch Overflow Switch
Air Sensing Tube Drain Pan Overflow Switch
Sensing Tube Drain Pan Overflow Switch
Switch and Condensate Drain Pan Overflow Switch
and Condensate Drain Pan
14
, Discharge Air Sensing
14
, Fan Failure
14
, Discharge
14
and Condensate
14
and Condensate
14
, Fan Failure
14
Digit 26 - System Monitoring Controls
0 No Monitoring Controls A Demand Control Ventilation
(CO
2
30,31
)
Digit 27 - Unit Hardware Enhancements
0 No Enhancements 1 Stainless Steel Drain Pan
Model Number Notes
1. Available on 3-5 ton models.
2. Standard on 4-5 Ton E3,4,W and 6-10 Ton Heat Pumps and all High Efficiency models.
3. Not available with electromechanical controls.
4. Manual outside air damper will ship factory supplied within the unit, but must be field installed.
5. High pressure control is standard on all units.
6. On 3-5 ton, multispeed direct drive is standard on single phase and 15 SEER. On 6-10 ton, multispeed direct drive is standard on all 10 ton and 7.5-8.5 ton high efficiency. Belt drive is standard on all other units.
Digit 15 = 0
Standard Efficiency 1 Phase = High Efficiency Multispeed Direct Drive Motor 3 Phase (3-8½ Ton) = Belt Drive 3 Phase (10 T on) = Ultra High Efficiency Direct Drive Plenum Fan High Efficiency 1 Phase = High Efficiency Multispeed Direct Drive Motor 3 Phase (3-5 ton) = High Efficiency Multispeed Direct Drive Motor 3 Phase (3-5 ton w/Dehumidification) = Belt Drive Motor 3 Phase (7½-10 ton) = Ultra High Efficiency Direct Drive Plenum Fan
7. Economizer with Barometric Relief is for downflow configured units only. Order Economizer
without Barometric Relief for horizontal configuration. Barometric Relief for horizontal configured units must be ordered as field installed accessory.
8. Through the base electric required when ordering disconnect/circuit breaker options.
9. Requires use of Disconnect or Circuit Breaker.
Not Available
Standard Efficiency 10 Ton w/575V High Efficiency 3-5 ton w/Standard Indoor Motor w/460V
10. Standard metering devices are TXVs.
1 1 . Fro stat cannot be field installed in
electro-mechanical units.
12. The return air smoke detector may not fit up or work properly on the Precedent units when used in conjunction with 3rd party accessories such as bolt on heat wheels, economizers and power exhaust. Do not order the return air smoke detectors when using this type of accessory.
13. Return Air Smoke Detector cannot be ordered with Novar Controls.
14. These options are standard when ordering Novar Controls.
15. This option is used when ordering Novar Controls.
16. Not available with high temperature duct sensor accessory.
17. Digit 15 = 2
Standard Efficiency 1 Phase = Not Available 3 Phase = Not Available High Efficiency 1 Phase = Not Available 3 Phase (3-5 ton) = May be Ordered 3 Phase (3-5 ton w/Dehumidification) = Not Available 3 Phase (6-10 ton) = Not Available
18. Novar Sensor utilized with Digit 21 = (4) Novar 3051 Controls without Zone Sensor.
19. Available for 10 ton standard efficiency models only .
20. Available for 3, 4, 5, 6, 7½, 8½ ton standard/high efficiency models only.
21. Requires selection of 2” Pleated Filters (option B or C) for Digit 16.
22. Not available on 6 ton units and all single phase or standard efficiency.
23. Standard on TSC 6, 7½ (single and dual systems), 8½, 10 ton standard efficiency mo de ls and THC 4, 5, 6, 7½ ton high efficiency models (except for dehumidification models).
24. Epoxy coil and epoxy with hailguard options are not available for units with microchannel condenser coil.
25. Single Zone VA V is only available on 7.5-10 ton high efficiency and 10 ton standard efficiency products with ReliaT el™ controls.
26. Multi-speed indoor fan ava ilable only on 7.5 & 8.5 ton high efficiency, and 10 ton products with ReliaTel™ controls.
27. Motorized Outside Air Damper is not available on Multi-Speed or SZVAV (Single Zone Variable Air Volume) products.
28. Frostat standard on Multi-Speed and SZVA V (Single Zone V ariable Air Volume)
products.
29. Novar is not available with SZVA V products.
30. Demand Control Venti latio n no t available with electromechanical controls.
31. Demand Control Ventilation Option includes wiring only. The
sensor is a field-installed only
C0
2
option.
6 RT-SVX22J-EN
General Information
Unit Inspection
As soon as the unit arrives at the job site
V erify that the nameplate data matches the data on the sales order and bill of lading (includin g electrical data).
Verify that the power supply complies with the unit nameplate specifications.
Visually inspect the exterior of the unit, including the roof, for signs of shipping damage.
If the job site inspection of the unit reveals damage or material shortages, file a claim with the carrier immediately. Specify the type and extent of the damage on the “bill of lading” before signing.
Visually inspect the internal components for shippi ng damage as soon as possible after delivery and before it is stored. Do not walk on the sheet metal base pans.
If concealed damage is discovered, notify th e carrier’s terminal of damage immediately by phone and by mail. Concealed damage must be reported within 15 days.
Request an immediate joint inspection of the damage by the carrier and the consignee. Do not remove damaged material from the receiving location. Take photos of the damage, if possible. The owner must provide reasonable evidence that the damage did not occur after delivery.
Notify the appropriate sales representative before installing or repairing a damaged unit.
Storage
Take precautions to prevent condensate from forming inside the unit’s electrical compartments and motors if:
1. the unit is stored before it is installed; or,
2. the unit is set on the roof curb, and temporary heat is provided in the building. Isolate all sid e panel service entrances and base pan openings (e.g., conduit holes, Supply Air and Return Air openings, and flue openings) from the ambient air until the unit is ready for start-up.
Note: Do not use the unit’s heater for temporary heat
without first completing the start-up procedure detailed under ““Unit Start-Up,” p. 46”.
The manufacturer will not assume any responsibility for equipment damage resulting from condensate accumulation on the unit’s electrical and/or mechanical components.
Unit Nameplate
A Mylar unit nameplate is located on the unit’s corner support next to the filter access panel. It includ es the unit model number, serial number, electrical characteristics, refrigerant charge, as well as other pertinent unit data.
Compressor Nameplate
The nameplate for the compressors are located on the side of the compressor.
Microchannel Condenser Barcode ID
Barcode decal used for condenser coil part identification can be located on the vertical header and top of coil's inlet/ outlet side.
Unit Description
Before shipment, each unit is leak tested , dehydrated, charged with re fr igerant and compressor oil, and run tested for proper control operation.
The condenser coils are either aluminum fin, mechanically bonded to copper tubing or all aluminum microchannel.
Direct-drive, vertical discharge condenser fans are provided with built-in thermal overload protection.
There are two control systems offered for these units. The electromechanical control option uses a thermostat to perform unit functions. The ReliaTel™ Control Module is a microelectronic control system that is referred to as “Refrigeration Module” (RTRM). The acronym RTRM is used extensively throughout this document when referring to the control system network.
These modules through Proportional/Integral control algorithms perform specific unit functions that governs unit operation in response to; zone temperature, supp ly air temperature, and/or humidity conditions depending on the application. The stages of capacity control for these units are achieved by starting and stopping the compressors.
The RTRM is mounted in the control panel and is factory wired to the respective internal components. The RTRM receives and interprets information from other unit modules, sensors, remote panels, and customer binary contacts to satisfy the applicable request for cooling.
Economizer Control Actuator (Optional)
Electromechanical Control
The ECA monitors the mixed air temperature, ambient dry bulb temperature and local minimum position setpoint sensors, if selected, to control dampers to an accuracy of +/- 5% of stroke. The actuator is spring returned to the closed position any time that power is lost to the unit. It is capable of delivering up to 25 inch pound s of to rque an d is powered by 24 VAC.
ReliaTel™ Control
The ECA monitors the mixed air temperature, return air temperature, minimum position setpoint (local or remote), power exhaust setpoint, CO ambient dry bulb/enthalpy sensor or comparative humidity (return air humidity against ambient humidity)
setpoint, CO2, and
2
RT-SVX22J-EN 7
General Information
sensors, if selected, to control dampers to an accuracy of +/- 5% of stroke. The actuator is spring returned to the closed position any time that power is lost to the unit. It is capable of delivering up to 25 inch pounds of torque and is powered by 24 VAC.
RTCI - ReliaTel™ Trane Communication Interface (Optional)
This module is used when the application calls for an ICSTM building management type control system. It allows the control and monitoring of the system through an ICS panel. The module can be ordered from the factory or ordered as a kit to be field installed. Follow the installation instruction that ships with each kit when field installation is necessary.
RLCI - ReliaTel™ LonTalk Communication Interface (Optional)
This module is used when the application calls for an ICSTM building management type control system that is LonT alk. It allows the control and monitoring of the system through an ICS panel. The module can be ordered from the factory or ordered as a kit to be field installed. Follow the installation instruction that ships with each kit when field installation is necessary.
RBCI - ReliaTel™ BACnet Communications Interface (Optional)
This module is used when the application calls for an open BACnet protocol. It allows the control and monitoring of the system through an ICS panel. The module can be ordered from the factory or as a kit to be field installed. Follow the installation instructions that ships with eac h kit when field installation is necessary.
RTOM - ReliaTel™ Options Module (Standard on 17 Plus, 7.5 Ton & 8.5 Ton High Efficiency with ReliaTel, 10 Ton with ReliaTel)
The RTOM monitors the supply fan proving, clogged filter, supply air temperature, exhaust fan setpoint, supply air tempering, Frostat™, smoke detector, and V ariable Speed Fan Control (17 Plus units only). Refer to system input devices and functions for operation.
System Input Devices & Functions
The RTRM must have a zone sensor or thermostat input in order to operate the unit. The flexibility of having several mode capabilities depends upon the type of zone sensor or thermostat selected to interface with the RTRM.
The descriptions of the following basic Input Devices used within the RTRM network are to acquaint the operator with their function as they interface with the various modules. Refer to the unit’s electrical schematic for the specific module connections.
The following controls are available from the factory for field installation.
Supply Fan Failure Input (Optional)
The Fan Failure Switch can be connected to sense indoor fan operation:
FFS (Fan Failure Switch) If air flow through the unit is not proven by the differential pressure switc h connected to the RTOM (factory set point 0.07 “w.c.) within 40 seconds nominally, the RTRM will shut off all mechanical operations, lock the system out, send a diagnostic to ICS, and the SERVICE output wi ll flash. The system will remain locked out until a reset is initiated either manually or through ICS.
Clogged Filter Switch (Optional)
The unit mounted clogged filter switch monitors the pressure differential across the return air filters. It is mounted in the filter section and is connected to the RTOM. A diagnostic SERVICE signal is sent to the remote panel if the pressure differential across the filters is at least
0.5" w.c. The contacts will automatically open when the pressure differential across the filters decreases to approximately 0.4" w.c. The clogged filter output is energized when the supply fan is operating and the clogged filter switch has been closed for at least 2 minutes. The system will continue to operate regardless of the status of the filter switch.
Note: On units equipped with factory installed MERV 13
filters, a clogged filter switch with different pressure settings will be installed. This switc h will close when the differential pressure is approximately 0.8' w.c. and open when the differential falls to 0.7" w.c.
Condensate Drain Pan Overflow Switch (Optional)
ReliaTel Option
This input incorporates the Condensate Overflow Switch (COF) mounted on the drain pan and the ReliaTel Options Module (RTOM). When the condensate level reaches the trip point for 6 continuous seconds, the RTOM will shut down all unit functions until the overflow condition has cleared. The unit will return to normal operation after 6 continuous seconds with the COF in a non-tripped condition. If the condensate level causes unit shutdown more than 2 times in a 3 days period, the unit will be locked-out of operation requiring manual reset of diagnostic system through Zone Sensor or Building Automation System (BAS). Cycling unit power will also clear the fault.
Electromechanical Option
This input incorporates the condensate overflow switch (COF), COF Relay , COF Time Delay . When the condensate level reaches the trip point, the COF relay energizes and opens the 24VAC control circuit which disables the unit. Once the 24VA C control circuit is opened, a delay timer will prevent unit start-up for three minutes.
8 RT-SVX22J-EN
General Information
Compressor Disable (CPR1/2)
This input incorporates the low pressure control (LPC) of each refrigeration circuit and can be activated by opening a field supplied contact installed on the LTB.
If this circuit is open before the compressor is started, the compressor will not be allowed to operate. Anytime this circuit is opened for 1 continuous second during compressor operation, the compressor for that circuit is immediately turned “Off”. The compressor will not be allowed to restart for a minimum of 3 minutes should the contacts close.
If four consecutive open conditions occur during the first three minutes of operation, the compressor for that circuit will be locked out, a diagnostic communicated to the remote panel (if installed), and a manual reset will be required to restart the compressor.
Low Pressure Control
ReliaTel Control
When the LPC is opened for 1 continuous second, the compressor for that circuit is turned off immediately . The compressor will not be allowed to restart for a minimum of 3 minutes.
If four consecutive open conditions occur during an active call for cooling, the compressor will be locked out, a diagnostic communicated to ICS™, if applicable, and a manual reset required to restart the compressor. On dual compressor units only the affected compressor circuit is locked out.
Electromechanical Control
When the LPC is opened, the compre ssor for that circuit is turned off immediately . The compressor will restart when the LPC closes.
High Pressure Control
ReliaTel Control
The high pressure controls are wired in series between the compressor outputs on the RTRM and the compress or contactor coils. If the high pressure control switc h opens, the RTRM senses a lack of current while calling for cooling and locks the compressor out.
If four consecutive open conditions occur during an active call for cooling, the compressor will be locked out, a diagnostic communicated to ICS™, if applicable, and a manual reset required to restart the compressor. On dual compressor units only the affected compressor circuit is locked out.
Electromechanical Control
When the HPC is opened, the compressor for that circuit is turned off immediately . The compressor will restart when the HPC closes.
Power Exhaust Control (Optional)
ReliaTel Control
The power exhaust fan is started whenever the position of the economizer dampers meets or exceed the power exhaust setpoint when the indoor fan is on.
With the optional ventilation override accessory, the power exhaust fan is independent of the indoor fan.
The setpoint panel is located in the return air section and is factory set at 25%.
Electromechanical Control
The power exhaust fan is started whenever the indoor fan is on and the adjustable damper limit switc h DLS is closed.
Lead/Lag Control (Dual Circuit Only)
ReliaTel Control Only
Lead/Lag is a selectable input located on the RTRM. The RTRM is configured from the factory with the Lead/Lag control disabled. T o activate the Lead/Lag function, simply cut the wire connected to J3-8 at the RTRM. When it is activated, each time the designated lead compressor is shut off due to the load being satisfied, the lead compressor or refrigeration circuit switches. When the RTRM is powered up, i.e. af ter a power failure, the control will default to the number one circuit compressor. Lead/ Lag is not available on Multi-Speed Indoor Fan, or Single Zone Variable Air Volume (SZVAV) products.
Zone Sensor Module (ZSM) (BAYSENS106*)
This electronic sensor features three system switch settings (Heat, Cool, and Off) and two fan settings (On
and Auto). It is a manual changeover control with single setpoint. (Cooling Setpoint Only)
Zone Sensor Module (ZSM) (BAYSENS108*)
This electronic sensor features four system switch settings (Heat, Cool, Auto, and Off) and two fan settings (On and Auto). It is a manual or auto changeover control with dual setpoint capability. It can be used with a remote zone temperature sensor BAYSENS077*.
Zone Sensor (BAYSENS110*)
This electronic sensor features four system switch settings (Heat, Cool, Auto, and Off) and two fan settings (On and Auto) with four system status LED’ s. It is a manual or auto changeo ver control with dual setpoint capabili ty. It can be used with a remote zone temperature sensor BAYSENS077*.
Wall Mounted Relative Humidity Sensor (BAYSENS036*)
Field installed, wall mounted humi dity sensor is used to control activation of Enhanced Dehumidification and the Hot Gas Reheat Dehumidification options. Humidity set points can be selected for relative humidity levels between
RT-SVX22J-EN 9
General Information
40% and 60% by adjusting the DEHUMID setting on the ReliaTel Options Module. See Figure 42, p. 34.
Duct Mounted Relative Humidity Sensor (BAYSENS037*)
Field installed, duct mounted humidity sensor is used to control activation of Enhanced Dehumidification and the hot gas reheat dehumidification options. Humidity set points can be selected for relative humidity levels between 40% and 60% by adjusting the DEHUMID setting on the ReliaTel Options Module. See Figure 42, p. 34.
Programmable Zone Sensor - (BAYSENS119*)
This 7 day programmable sensor features 2, 3 or 4 periods for Occupied or Unoccupied programming per d ay. If the power is interrupted, the program is retained in permanent memory. If power is off for an extended period of time, only the clock and day may have to be reset.
The Zone Sensor allows selection of 2, 3 or 4 system modes (Heat, Cool, Auto, and Off), two fan modes (On and Auto). It has dual temperature selection with programmable start time capability.
The occupied cooling set point ranges between 45 and 98 º F. The heating set point ranges between 43 and 96ºF.
A liquid crystal display (LCD) displays zone temperature, temperature set points, day of the week, time, and operational mode symbols.
The Option Menu is used to enable or disable applicable functions, i.e.; Morning Warm-up, Economizer minimum position override during unoccupied status, Fahrenheit or Centigrade, Supply air tempering, Remote zone temperature sensor, 12/24 hour time display, Smart fan, and Computed recovery.
During an occupied period, an auxiliary relay rated for 1.25 amps @ 30 volts AC with one set of single pole double throw contacts is activated.
Status Inputs (4 Wires Optional)
The ZSM can be wired to receive four (4) operating status signals from the RTRM (HEAT, COOL, SYSTEM “ON”, SERVICE).
Four (4) wires from the RTRM should be connected to the appropriate terminals (7, 8, 9 & 10) on the ZSM.
Remote Zone Sensor (BAYSENS073*)
This electronic sensor features remote zone sensing and timed override with over ride cancellation. It is used with a Trane Integrated Comfort™ building management system.
Remote Zone Sensor (BAYSENS074*)
This electronic sensor features single setpoint capability and timed override with override cancellation. It is used with a Trane Integrated Comfort™ building management system.
Remote Zone Sensor (BAYSENS016*)
This bullet type temperature sensor can be used for outside air (ambient) sensing, return air temperature sensing, supply air temperature sensing, remote temperature sensing (uncovered). Wiring procedures vary according to the particular application and equipment involved. Refer to the unit’s wiring diagrams for proper connections.
Remote Zone Sensor (BAYSENS077*)
This electronic sensor can be used with BAYSENS106*, 108*, 110*, 119* Remote P anels. When this sensor is wired to a BA YSENS119* Remote P anel, wiring must be 18 A WG Shielded Twisted P air (Belden 8760 or equivalent). Refer to the specific Remote Panel for wiring details.
Wireless Zone Sensor (BAYSENS050)
This electronic sensor features five system settings (Auto, Off, Cool, Heat, and Emerg ency Heat) and with On and Auto fan settings. It is a manual or auto c hangeover control with dual setpoint capability. Other features include a timed override function, lockable system settings, and Fahrenheit or Celsius temperature display. Included with the wireless zone sensor will be a receiver that is to be mounted inside the unit, a mounting bracket, and a wire harness.
Electromechanical Control
The unit must have a thermostat to operate.
•BAYSTAT151
Single Stage - 1 Heat/1 Cool
•BAYSTAT155
Multi Stage - 3 Heat/2 Cool - Can be Used for Economizer Operation
BAYSENS150
Multi stage - 3 Heat/2 Cool Programmable Thermostat
High Temperature Sensor (BAYFRST001*)
This sensor connects to the RTRM Emergency Stop Input on the L TB and provides high limit “sh utdown” of the unit. The sensor is used to detect high temperatures due to a high thermal event in the air conditioning or ventilation ducts. The sensor is designed to mount directly to the sheet metal duct. Each kit contains two sensors. The return air duct sensor (X1310004001) is set to open at 135ºF. The supply air duct sensor (X1310004002) is set to open at 240ºF. The control can be reset after the temperature has been lowered approximately 25ºF below the cutout setpoint.
Evaporator Frost Control
ReliaTel™ Option
This input incorporates the Frostat™ control (FOS) mounted in the indoor coil circuit and can be activated by
10 RT-SVX22J-EN
General Information
closing a field supplied contact installed in parallel with the FOS.
If this circuit is open before the compressor is started, the compressor will not be allowed to operate. Anytime this circuit is opened for 1 continuous second during compressor operation, the compressor for that circuit is immediately turned “Off”. The compressor will not be allowed to restart for a minimum of 3 minutes should the FOS close.
Frostat is standard on multi-speed indoor motors and single zone VAV products (SZVAV).
Electromechanical Option
This input incorporates the Frostat™ control (FOS) mounted in the indoor coil circuit and can be activated by opening a field supplied contact installed in series with the FOS.
If this circuit is open before the compressor is started, the compressor will not be allowed to operate. Anytime this circuit is opened during compressor operation, the compressor for that circuit is immediately turned “Of f”. The compressor will restart when the FOS closes.
Discharge Line Temp Switch (DLTS)
The DL TS is looped in series with HPC and LPC. It prevents compressor from overheating (over 300 Fº dome temp) in case of indoor fan failure (cooling) or outdoor fan failure (heating).
Smoke Detector Sensor (Optional)
This sensor provides high limit “shutdown” of the unit and requires a manual reset. The sensor is used to detect smoke in the air conditioning or ventilation ducts.
Notes:
The supply air smoke detector samples supply air. The
return and plenum air smoke detectors sample return air. The smoke detectors are designed to shut off the unit if smoke is sensed. This function is performed by sampling the airflow enteri ng the unit at the return air opening. Follow the instructions provided below to assure that the airflow through the unit is sufficient for adequate sampling. Failure to follow t hese instructions will prevent the smoke detectors from performing its design function.
Airflow through the unit is affected by the amount of dirt and debris accumulated on the indoor coil and filters. To insure that airflow through the unit is adequate for proper sampling by the return air smoke detector, complete adherence to the maintenance procedures, including recommended intervals between filter changes, and coil cleaning is required.
Periodic chec ks and maintenance procedures must be performed on the smoke detector to insure that it will function properly . For detailed instructions concerning these checks and procedures, refer to the appropriate section(s) of the smoke detector Installation and
Maintenance Instructions provided with the literature package for this unit.
In order for the supply air smoke detector or return air smoke detector to properly sense smoke in the supply air stream or return air stream, the air velocity entering the smoke detector unit must be between 500 and 4000 feet per minute. Equipment covered in this manual will develop an airflow velocity that falls within these limits over the entire airflow range specified in the evaporator fan performance tables.
Phase Monitor
This sensor monitors voltage between the 3 conductors of the 3 phase power supply. Two LED lights are provided:
The green light indicates that a balanced 3 phase supply circuit is properly connected.
The red light indicates that unit operation has been prevented. There are two conditions that will prevent unit operation:
The power supply circuit is not balanced with the
proper phase sequence of L1, L2, L3 for the 3 conductors of a 3 phase circuit.
The line to line voltage is not between 180 v olts and
633 volts.
Single Zone Variable Air Volume / Displacement Ventilation (Optional)
This sensor offers full supply fan modulation across the available airflow range. In addition to full supply fan modulation, the unit controls the discharge air temperature to a varying discharge air temperature setpoint in order to maintain Space Temperature.
RT-SVX22J-EN 11
Unit Dimensions
TSC036-060E & THC036-037E UnitsTSC036-060E & THC036-037E Units
TSC072-120F, THC047-120E, & THC048-092F UnitsTSC072-120F, THC047-120E, & THC048-092F Units
Unit Clearances
Figure 1, p. 12 illustrates the minimum operating and
service clearances for either a single or multiple unit
Figure 1. Typical installation clearances for single & multiple unit applications
installation. These clearances are th e minimum distances necessary to assure adequate serviceability, cataloged unit capacity, an d peak operating efficiency.
Providing less than the recommended clearances may result in condenser coil starvation, “short-circuiting” of exhaust and economizer airflows, or recirculation of hot condenser air.
12 RT-SVX22J-EN
Figure 2. 3-5 ton standard efficiency, 3 ton high efficiency
7
4444 MMMM
4444 MMMM
10381038 MMMM
10531053 MMMM
Note: All dimensions are in inches/millimeters.
Unit Dimensions
Figure 3. 3-5 ton standard efficiency, 3 ton high efficiency - roof curb
Note: All dimensions are in inches/millimeters.
RT-SVX22J-EN 13
Unit Dimensions
CLEARANCE 36” (914 MM)
Figure 4. 3-5 ton standard efficiency, 3 ton high efficiency - unit clearance and roof opening
Note: All dimensions are in inches/millimeters.
Figure 5. 6, 7½ (single) ton standard efficiency, 4 - 5 ton high efficiency
Note: All dimensions are in inches/millimeters.
14 RT-SVX22J-EN
Figure 6. 6, 7½ (single) ton standard efficiency, 4 - 5 ton high efficiency - roo f curb
(2130 MM)
(356 MM)
Note: All dimensions are in inches/millimeters.
Unit Dimensions
Figure 7. 6, 7½ (single) ton standard efficiency, 4 - 5 ton high efficiency - unit clearance and roof opening
Note: All dimensions are in inches/millimeters.
RT-SVX22J-EN 15
Unit Dimensions
(2130 MM)
(356 MM)
Figure 8. 7½ ton (dual) - 10 ton standard efficiency, 6 & 7½ (microchannel) ton high efficiency
Note: All dimensions are in inches/millimeters.
Figure 9. 7½ ton (dual) - 10 ton standard efficiency, 6 & 7½ (microchannel) ton high efficiency - roof curb
Note: All dimensions are in inches/millimeters.
16 RT-SVX22J-EN
Unit Dimensions
Figure 10. 7½ ton (dual) - 10 ton standard efficiency, 6 & 7½ (microchannel) ton high efficiency - unit clearance and
roof opening
Note: All dimensions are in inches/millimeters.
Figure 11. 7½ (dehumidification) - 10 ton high efficiency
Note: All dimensions are in inches/millimeters.
RT-SVX22J-EN 17
Unit Dimensions
13/4”
(
44 MM
)
2”
(
51 MM
)
84 1/2”
(2146 MM)
83 7/8”
(2130 MM)
60 3/8”
(1534 MM)
59 7/8”
(
1521 MM
)
14”
(
356 MM
)
2”
(
51 MM
)
56 3/8”
(1432 MM)
34 3/8”
(873 MM)
34 3/8”
(873 MM)
18 1/2”
(470 MM)
18 1/2”
(470 MM)
1”
(
25 MM
)
1”
(
25 MM
)
1”
(
25 MM
)
65/8”
(
168 MM
)
80 1/2”
(2045 MM)
CL
EARANCE 18” (4
57 MM
)
FO
R
H
O
RIZO
NTAL
CLEARAN
C
E36”(914 MM)
FO
R
DO
WNFLOW
99 11/16”
(2532 MM)
63 3/16”
(1605 MM)
Figure 12. 7½ (dehumidification) - 10 ton high efficiency - roof curb
Note: All dimensions are in inches/millimeters.
Figure 13. 7½ (dehumidification) - 10 ton high efficiency- unit clearance and roof opening
Note: All dimensions are in inches/millimeters.
18 RT-SVX22J-EN
Installation
Pre-Installation
WARNING
Fiberglass Wool!
Product contains fiberglass wool. Disturbing the insulation in this product during installation, maintenance or rep air will expose you to airborne particles of glass wool fibers and ceramic fibers known to the state of California to cause cancer through inhalation. You MUST wear all necessary Personal Protective Equipment (PPE) including gloves, eye protection, mask, long sleeves and pants when working with products containing fiber glass w ool. Exposition t o glass wool fibers without all necessary PPE equipment could result in cancer, respiratory, skin or eye irritation, which could result in death or serious injury.
Precautionary Measures
Avoid breathing fiberglass dust.
Use a NIOSH approved dust/mist respirator.
Avoid contact with the skin or eyes. W ear long-sleeved, loose-fitting clothing, gloves, and eye protection.
Wash clothes separately from other clothing: rinse washer thoroughly.
Operations such as sawing, blowing, tear-out, and spraying may generate fiber concentrations requiring additional respiratory protection. Use the appropriate NIOSH approved respiration in these situations.
First Aid Measures
Eye Contact - Flush eyes with water to remove dust. If symptoms persist, seek medical attention.
Skin Contact - Wash af fected areas gently with soap and warm water after handling.
If an element has detached from its ceramic insulator, carefully put it back into place.
Replace the heater elements if they present symptoms noted in item 2 or 3 above.
Procedure
WARNING
Heavy Objects!
Ensure that all the lifting equipment used is properly rated for the we ight of th e unit being lifted. Each of the cables (chains or slings), hooks, and shackles used to lift the unit must be capable of supporting the entire weight of the unit. Lifting cables (chains or slings) may not be of the same length. Adjust as necessary for even unit lift. Other lifting arrangements could cause equipment or property damage. Failure to follow instructions above or properly lift unit could result in unit dropping and possibly crushing operator/ technician whic h coul d result in death or serious injury.
WARNING
Improper Unit Lift!
Test lift unit approximately 24 inches to verify proper center of gravity lift point. To avoid dropping of unit, reposition lifting point if unit is not level. Failure to properly lift unit could result in unit dropping and possibly crushing operator/technician which could result in death or ser i ous injury and possi ble equipmen t or property-only damage.
Figure 14. Corner weights
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing . Follow proper lockout/ tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.
Remove power to the unit and gain access to the electric heat elements by removing the horizontal supply cover. Visually inspect the heater elements for the following:
Elements that are no longer secured to the white ceramic insulator.
Elements touching each other or touching metal.
Severely kinked, drooping, or broken elements.
RT-SVX22J-EN 19
Installation
Table 1. Maximum unit & corner weights (lbs) and center of gravity dimensions (in.) - cooling models
Maximum Model
Unit
Ton Shipping Net A B C D Length Width
3 TSC036E/THC036E 555 481 157 122 95 107 31 19 4 TSC048E 586 511 167 129 101 114 31 19 5 TSC060E 636 561 183 142 111 125 31 19
6 TSC072F 762 667 218 186 131 132 44 21 7½ TSC090F 781 686 222 195 136 134 44 21 7½ TSC092F 940 797 249 235 163 149 46 21 8½ TSC102F 999 856 264 239 177 175 45 22
10 TSC120F 1058 960 320 218 233 189 40 24
3 THC037E 614 544 163 144 111 125 33 19
4 THC048E/THC047E 787 692 220 178 132 163 40 23
4 THC048F 737 642 208 177 128 130 44 22
5 THC060E/THC067E 841 746 241 193 139 173 39 22
5 THC060F 774 679 219 189 135 137 43 21
6 THC072F 883 740 228 219 155 138 47 21 7½ THC092E 1445 1228 347 330 269 283 49 28 7½ THC092F 1026 928 315 209 224 180 40 24 8½ THC102E 1472 1255 359 335 271 290 48 28
10 THC120E 1462 1245 353 332 271 288 48 28
(a) Weights are approximate. (b)Corner weights are given for information only.
Model No.
Weights
(a)
Corner Weights
(b)
Center of Gravity
(in.)
Figure 15. Rigging and center of gravity
Table 2. Facto r y in sta lled options (fiops)/accessory net weights (lbs)
TSC036E-060E
THC036E/
THC037E
Net Weight Net Weight Net Weight Net Weight Net Weight
Accessory 3-5 Ton 4-5 Ton 6-8½ Ton 7½-10 Ton 7½-10 Ton
Barometric Relief 7 10 10 10 10 Belt Drive Option (3 phase only) 31 31 — Coil Guards 12 20 20 20 30
continued on next page
THC047E-067E
THC048E/F-
060E/F
(a),(b)
TSC072F-102F
THC072F
THC092F,
TSC120F
THC092E-
120E
20 RT-SVX22J-EN
Loading...
+ 44 hidden pages