Trane AFD260CLAH000D, AFD145CLFR000D, AFD210CLFR000D, AFD175CLFR000D, AFD245CLFR000D Service Facts

...
Service Facts
EAC- SF- 1 3
Whole House Electronic Air Cleaner
Upflow Furnace Models
*FD145CLFR000D *FD175CLFR000D *FD210CLFR000D *FD245CLFR000D
ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES
IMPORTANT — This Document is customer property and is to remain with this unit.
Please return to service information pack upon completion of work.
44
4
1
99
9
99
33
3
33
44
Downflow Furnace Models
*FD14DCLFR000D *FD17DCLFR000D *FD21DCLFR000D *FD24DCLFR000D
Air Handler Models
*FD175CLAH000D *FD215CLAH000D *FD235CLAH000D *FD260CLAH000D
COMPONENTS OF THE AIR CLEANER
33
3
33
55
5
55
66
6
66
50 Hz Air Handler Models
TFD215CLAH005D TFD235CLAH005D TFD260CLAH005D
* May be "A" or "T"
11
1
11
1) PRE-FILTER - traps large particles such as hair and lint before they can enter the COLLECTION CELL section.
2) FIELD CHARGER - Charges the contaminants. Only to be serviced by a qualified technician.
3) COLLECTION CELL (2) - removes and collects very small
impurities from the air.
4) CABINET - mounts between the furnace/air handler and return air duct work and houses the COLLECTION CELLS, FIELD CHARGER and PRE-FILTER.
5) POWER DOOR - the solid state power supply components that convert the 24 Volt AC to the high-voltage, direct current required to power the FIELD CHARGER and COLLECTION
!
WARNING
This information is for use by individuals having adequate backgrounds of electrical and mechanical experience. Any attempt to repair a central air conditioning product may re­sult in personal injury and/or property damage. The manu­facturer or seller cannot be responsible for the interpreta­tion of this information, nor can it assume any liability in con­nection with its use.
88
8
88
77
7
22
2
22
6) TRANSFORMER - supplies 24 Volts to the indoor unit and Air
7) 24 VOLT POWER / CONTROL CABLE
8) GASKET, LITERATURE AND HARDWARE PACKET
9) UPFLOW AIR HANDLER BAFFLE - This baffle is only included
RECONNECT ALL GROUNDING DEVICES.
All parts of this product that are capable of conducting elec­trical current are grounded. If grounding wires, screws, straps, clips, nuts, or washers used to complete a path to ground are removed for service, they must be returned to their original position and properly fastened.
77
CELLS. Allows access to the COLLECTION CELLS, FIELD CHARGER and PRE-FILTER.
Cleaner
with Air Handler models. See note below.
NOTE: Be careful not to discard the baffle. It is located under
(not available with 50 Hz units)
the collection cells in the shipping box.
!
CAUTION
11
1
11
22
2
22
AIR
FLOW
33
3
33
© Trane 2011
Service Facts
INTRODUCTION
The whole house air cleaner can be installed either as part of a Communicating heating and air conditioning system or as part of a traditional 24 volt system.
When installed as part of a Communicating System in which the indoor unit, outdoor unit, and 900 series comfort control are equipped with our exclusive Communicating technology, this system performs a continuous loop of system diagnostics and data output. The Communicating System monitors itself and quickly identifies any operational faults, automatically issuing a service alert if needed.
The whole house air cleaner can also be installed as part of a traditional 24 volt heating and air conditioning system.
MODES OF OPERATION
The whole house air cleaner can be connected in one of two modes of operation; either a 24 V mode or a communicating mode. To know how the whole house air cleaner is set up, reference Figure 1a to find the amber light.
Power Button
Amber Light
Plug Power Cord in here
1a
A steady amber light indicates that the unit is wired in the 24 V mode. A blinking amber light indicates that the unit is wired in the communicating mode. No light present means that the unit is not connected.
!
CAUTION
SAFETY HAZARD Sharp Edge Hazard. Be careful of sharp edges on equip­ment or any cuts made on sheet metal while installing or servicing. Personal injury may result.
ELECTRICAL CONNECTIONS
The air cleaner requires 24 VAC power and indoor fan signal to operate. A transformer adequately sized to power both the system and air cleaner is provided with the air cleaner. Remove the transformer in the indoor unit and replace with the transformer provided.
N
OTE: A 50 VA transformer is required for Trane/ American Standard Heating & Air Conditioning furnace applications and 75 VA required for Trane/ American Standard Heating & Air Conditioning air handler applications. If the indoor air handler already has a properly sized transformer, no replacement is required.
NOTE: Trane/American Standard Heating & Air Conditioning dual circuited air handlers matched with heat pumps and Trane/American Standard Heating & Air Conditioning oil furnaces will require an accessory Transformer KIT# BAYTRANS12024 power the air cleaner. Do NOT replace air handler transformer with the transformer supplied with the air cleaner.
◆◆
◆◆
to
NOTE: When more than one whole house air cleaner is used, the 24 volt transformer which supplies power to the air cleaner will need to be increased by
25 VA for each additional air cleaner added.
NOTE: Provide adequate strain relief for the low voltage cable at the indoor unit.
NOTE: Wiring penetration must be sealed.
DO NOT attach the power/control cable to a 120 Volt EAC tap. The air cleaner uses 24 Volt power. Failure to use 24 VAC results in permanent damage to the air cleaner.
• Plug the air cleaner power/control cable into the air cleaner door and route the cable into the indoor unit low voltage wiring location.
• Connect the power/control wiring per Figure 2.
NOTE: For non-Trane/American Standard Heating & Air Conditioning systems order a 120 VAC to 24 VAC transformer, KIT# BAYTRANS12024 power only to the air cleaner. Access to 120 VAC outlet is required.
• Connect the power/control wiring per Figure 3.
NOTE: Trane/American Standard Heating & Air Conditioning Communicating Furnaces require KIT # BAYACCECOMM101.
NOTE: Wiring diagrams for the Communicating Air Handler, Communicating Furnaces and Oil Furnace are on pages 3, 4-5 and 6 respectively.
!
CAUTION
◆◆
to provide 24 volt
◆◆
2 Numbers in [brackets] are for 50 Hz international systems. EAC-SF-13
Wiring Diagram
22
2
22
Communicating Mode
Data Line
BROWN
D
NOTE: The Black wire must be connected to chassis ground to ensure proper operation.
BAYTRANS12024
◆◆
Transformer
◆◆
Air Handler may not have a Low Voltage Terminal board. Connect Electronic Air Cleaner wires to
the Air Handler Low Voltage Color coded wires.
Install Transformer, one is supplied with the Electronic Air Cleaner, in the Furnace or Air Handler.
• Transformer must have a grounded 120 VAC power source. Do not defeat ground plug on the transformer.
• Mount transformer to building structure with the four provided wood screws.
NOTE: BAYTRANS12024C complies with the California Code of Regulation,Title 20, Sections 1601 through 1608 dated December 2006. BAYTRANS12024A with
vendor’s manufacturing date codes after 0625 (YYWW) cannot be installed in California because the transformer does not satisfy the requirements set forth by California
Code of Regulations, Title 20, Sections 1601 through 1608 dated December 2006.
Transformer not applicable to 50 Hz units.
BLACK
GRD
RED
BLUE
Unused GREEN
BROWN
WHITE
Unused
Furnace
Heating Signal
Fan Signal
Data Line
24 V
Common
RED
BLUE
GREEN
BROWN
BLACK
WHITE
Furnace / Air Handler
RED
BLUE
WHITE
GREEN
BROWN
Indoor Unit
24 V Terminal Strip
BLUE
GREEN
BROWN
BLACK
RED
WHITE
R
BLUE
B
Unused
WHITE
W
Unused
G
GREEN
BROWN /
D
Dataline
GREEN
BROWN
BLACK
WHITE
BLUE
RED
The represents an alpha character.
Wiring Diagram
33
3
33
for 24 V Mode
NOTE: The Black wire must be connected to chassis ground to ensure proper operation.
◆◆
BAYTRANS12024
Transformer
◆◆
• Transformer must have a grounded 120 VAC power source. Do not defeat ground plug on the transformer.
• Mount transformer to building structure with the four provided wood screws.
NOTE: BAYTRANS12024C complies with the California Code of Regulation,Title 20, Sections 1601 through 1608 dated December 2006. BAYTRANS12024A with
vendor’s manufacturing date codes after 0625 (YYWW) cannot be installed in California because the transformer does not satisfy the requirements set forth by California
Code of Regulations, Title 20, Sections 1601 through 1608 dated December 2006.
Transformer not applicable to 50 Hz units.
Air Handler may not have a Low Voltage Terminal board. Connect Electronic Air Cleaner wires to
the Air Handler Low Voltage Color coded wires.
Install Transformer, one is supplied with the Electronic Air Cleaner, in the Furnace or Air Handler.
Common
Furnace
Heating Signal
Fan Signal
24 V
Indoor Unit
24 V Terminal Strip
Furnace / Air Handler
RED
BLUE
WHITE
GREEN
BLUE
GREEN
BROWN
BLACK
RED
WHITE
R
BLUE
B
WHITE
W
GREEN
G
BROWN /
Dataline
GREEN
BROWN
BLACK
WHITE
BLUE
RED
The represents an alpha character.
Service Facts
BK R
O G Y1 Y2
D
B W1 W2 W3
BK R
O G Y1 Y2
D
B W1 W2 W3
GREEN
WHITE
ELECTRICAL CONNECTIONS TO A COMMUNICATING SYSTEM AIR HANDLER
IN CONVENTIONAL 24 V MODE
!
WARNING
HAZARDOUS VOLTAGE! DISCONNECT ALL ELECTRIC POWER, INCLUDING REMOTE DISCONNECTS BEFORE SERVICING. FOLLOW PROPER LOCKOUT/TAGOUT PROCEDURES TO ENSURE THE POWER CAN NOT BE INADVERTENTLY ENERGIZED. FAILURE TO DISCONNECT POWER BEFORE SERVICING COULD RESULT IN DEATH OR SERIOUS INJURY.
PROCEDURE:
1) Remove electrical power going into the air handler.
2) On the communicating systems air handler, remove the blower access panel.
3) Remove the communicating control box cover.
4) Locate the red jumper wire which is attached from EAC to R on the Communicating Systems PCB. Confirm it is connected. If there is not a jumper wire installed, then one must be installed in this location in order for the air cleaner to function properly.
Detach female spade terminal
from white EAC wire and
crimp to green wire
5) Replace the Communicating control box cover.
6) Locate the white wire coming from the Communicating System Air Handler PCB labeled “EAC”. The wire will have a male spade terminal connected to it and a female spade terminal inserted into the male terminal. Remove the female spade terminal and crimp it to the green wire on the air cleaner harness.
7) Connect the green wire from the air cleaner harness to the white wire on the Communicating Systems Air Handler.
8) Using the wire harness supplied with the air cleaner, connect the Red and Blue wires from the air cleaner harness to “R” and “B” on the Indoor Unit 24V Terminal Strip respectively.
9) Connect the Black wire from the air cleaner wire harness to earth ground by attaching the wire to a grounded screw that is connected to the metal air handler chassis.
10) Replace the blower access panel.
11) Reconnect electrical power to the air handler.
Control box panel cover
(Shown removed)
24V RED
jumper wire
from EAC to R
BEFORE AFTER
WHITE
WHITE
GREEN
Indoor Unit
24V
Terminal
Strip Detail
4 Numbers in [brackets] are for 50 Hz international systems. EAC-SF-13
GREEN
EAC
GREEN
BLUE
RED
WHITE
Unused
BLACK
GRD
Wiring Cable and Plug
BROWN /
Future Use
For use with Whole House
Air Cleaner
Power / Control
Air Cleaner Plug
EAC
R
PCB Detail
ELECTRICAL CONNECTIONS TO A STANDARD 24 VOLT AIR HANDLER
!
WARNING
HAZARDOUS VOLTAGE! DISCONNECT ALL ELECTRIC POWER, INCLUDING REMOTE DISCONNECTS BEFORE SERVICING. FOLLOW PROPER LOCKOUT/TAGOUT PROCEDURES TO ENSURE THE POWER CAN NOT BE INADVERTENTLY ENERGIZED. FAILURE TO DISCONNECT POWER BEFORE SERVICING COULD RESULT IN DEATH OR SERIOUS INJURY.
Service Facts
Field wiring
W3 W2
W1
G
YI
O R B YO
GREEN
BLUE
RED
WHITE
Unused
GAM5 / A/TAM4
BLACK
GRD
BROWN /
Future Use
For use with Whole House
Power / Control
Wiring Cable and Plug
Air Cleaner
Air Cleaner Plug
W3 W2
W1
BK
G Y2 YI O R B
YO
GREEN
BLUE
RED
WHITE
Unused
(In)
(Out)
BLACK
GRD
Wiring Cable and Plug
BROWN /
Future Use
A/TAM7
For use with Whole House
Air Cleaner
Power / Control
Air Cleaner Plug
EAC-SF-13 Numbers in [brackets] are for 50 Hz international systems. 5
Service Facts
BK R
O G Y1 Y2
D
B W1 W2 W3
BK R
O G Y1 Y2
D
B W1 W2 W3
ELECTRICAL CONNECTIONS TO A COMMUNICATING SYSTEMS AIR HANDLER
IN COMMUNICATING MODE
!
WARNING
HAZARDOUS VOLTAGE! DISCONNECT ALL ELECTRIC POWER, INCLUDING REMOTE DISCONNECTS BEFORE SERVICING. FOLLOW PROPER LOCKOUT/TAGOUT PROCEDURES TO ENSURE THE POWER CAN NOT BE INADVERTENTLY ENERGIZED. FAILURE TO DISCONNECT POWER BEFORE SERVICING COULD RESULT IN DEATH OR SERIOUS INJURY.
1) Remove electrical power going into the air handler.
2) On the communicating systems air handler, remove the blower access panel.
3) Connect Red stripped wire to "R" terminal on the air handler terminal strip.
4) Connect Blue stripped wire to "B" terminal on the air handler terminal strip.
5) Connect the brown wire from the air cleaner harness to the "D" terminal on the Communicating Systems Air Handler.
6) Connect the Black wire from the air cleaner wire harness to earth ground by attaching the wire to a grounded screw that is connected to the metal air handler chassis or control plate assembly.
7) The Green and White wires on the air cleaner wiring harness are unused in this application and should be insulated separately.
8) Replace the blower access panel.
9) Reconnect electrical power to the air handler.
10) Check air cleaner and air handler operation.
4TEE3C A/TAM8
Control box panel cover
(Shown removed)
PROCEDURE:
Indoor Unit
24V Terminal
Strip Detail
Y2 Y1
O R
B D
RED
BROWN /
Dataline
WHITE
Unused
BLUE
BLACK
GRD
For use with Whole House
Air Cleaner
Power / Control
Wiring Cable and Plug
GREEN
Unused
Air Cleaner Plug
BLUE
RED
BROWN /
Dataline
WHITE
Unused
BLACK
GRD
Black wire to
chassis ground
6 Numbers in [brackets] are for 50 Hz international systems. EAC-SF-13
For use with Whole House
Air Cleaner
Power / Control
Wiring Cable and Plug
GREEN
Unused
Air Cleaner Plug
Service Facts
ELECTRICAL CONNECTIONS TO A COMMUNICATING FURNACE IN 24 V MODE
!
WARNING
HAZARDOUS VOLTAGE! DISCONNECT ALL ELECTRIC POWER, INCLUDING REMOTE DISCONNECTS BEFORE SERVICING. FOLLOW PROPER LOCKOUT/TAGOUT PROCEDURES TO ENSURE THE POWER CAN NOT BE INADVERTENTLY ENERGIZED. FAILURE TO DISCONNECT POWER BEFORE SERVICING COULD RESULT IN DEATH OR SERIOUS INJURY.
PROCEDURE:
1. Remove electrical power going into the furnace.
2. Remove blower door to up-flow or down-flow furnace.
3. Remove the two screws that secure the IFC platform to the underside of the blower deck on an up-flow furnace or the 3 screws that secure the IFC platform to the top panel on a down-flow furnace.
4. Carefully remove the IFC platform from the furnace.
5. On both the up-flow and down-flow furnaces, mount the 50VA transformer supplied in the packaging with the air cleaner onto the bottom of the IFC platform. Screws and pilot holes are provided. See figure.
6. Remove wiring from existing 35VA transformer and reconnect to the 50VA transformer. Note the polarity of the wires and reconnect to the appropriate terminals. See diagram
7. Remove the EAC-H 115VAC and EAC-N wires (white and black) out of the junction box and pull them through the grommet in the blower deck. Attach two supplied ¼” insulated female quick connect terminals by stripping the wires and crimping the terminals onto the wires. Attach these wires to the 115V terminals of the 35VA transformer as shown in the diagram.
8. Remove the wiring harness supplied with the air cleaner from the packaging. Attach a supplied 3/16” insulated female quick connect terminal to the blue wire and the green wire.
9. Attach the blue wire from the air cleaner wiring harness to the open tab on the piggyback terminal supplied in the BAYACCECOMM101. Attach piggyback terminal to the 35VA transformer terminal “C” (Common).
10. Insert the 12” blue stripped wire under the terminal strip screw marked “B/C” on the IFC control board. If the applica­tion also includes an outdoor unit (communicating or non­communicating), the B/C terminal will require 3 wires connected. For this connection, rather than connecting the three wires to the low voltage terminal strip on the furnace IFC, create a pigtail using a short length of thermostat wire and a wire nut (field supplied) to attach to the B/C terminal.
11. Connect the green wire from the air cleaner wiring harness to the 24V terminal on the 35VA transformer labeled “RD”. See diagram.
12. Insert the red stripped wire from the air cleaner wiring harness under the IFC control board terminal screw marked “R”. See diagram.
13. Attach the black stripped wire from the air cleaner wiring harness directly to ground with a screw on the furnace chassis. See diagram.
14. Once all of the connections have been completed, remount the IFC control platform into the furnace.
15. Secure any loose wiring with wire ties.
16. The brown and white wires from the EAC wiring harness are unused in this application and should be insulated. See diagram.
17. Replace the furnace door.
18. Reconnect electrical power to the furnace.
19. Check both furnace and air cleaner operation per the furnace and air cleaner installer guides.
BILL OF MATERIALS:
QTY: 2 Screw QTY: 1 4" Insulated Copper Wire –
QTY: 2 1/4” Insulated Female Quick
QTY: 2 3/16" x 0.020" Insulated Female
QTY: 1 3/16" x 0.020" Receptacle & Tab
EAC-SF-13 Numbers in [brackets] are for 50 Hz international systems. 7
Blue (18 AWG, AWM)
Connect Terminal
Quick Connect Terminal
These instructions and listed parts are included in KIT# BAYACCECOMM101
Service Facts
ELECTRICAL CONNECTIONS TO A COMMUNICATING SYSTEM FURNACE
!
WARNING
HAZARDOUS VOLTAGE! DISCONNECT ALL ELECTRIC POWER, INCLUDING REMOTE DISCONNECTS BEFORE SERVICING. FOLLOW PROPER LOCKOUT/TAGOUT PROCEDURES TO ENSURE THE POWER CAN NOT BE INADVERTENTLY ENERGIZED. FAILURE TO DISCONNECT POWER BEFORE SERVICING COULD RESULT IN DEATH OR SERIOUS INJURY.
PROCEDURE:
1. Remove electrical power going into the furnace.
2. Open blower door to upflow or downflow furnace.
3. Disconnect all wires on the 35VA transformer.
4. Remove the 35VA transformer from the IFC platform.
5. Mount the 50 VA transformer supplied in the packaging with the air cleaner onto the IFC platform where the 35VA transformer was previously located. Use the sheet metal screws supplied with the air cleaner to mount the 50VA transformer. Reconnect the 115V and 24V wires that were connected to the 35VA transformer onto the 50 VA transformer.
6. Connect Red stripped wire to "R" terminal on the furnace control board.
7. Connect Blue stripped wire to "B" terminal on the furnace control board.
8. Connect Brown stripped wire to "D" terminal on the furnace control board.
9. Attach the black stripped wire from the air cleaner wiring harness directly to ground with a screw in the chassis.
10. The green and white wires on the air cleaning wiring harness are unused in this application and should be insulated.
11. Replace door on furnace.
12. Reconnect electrical power to the furnace.
13. Check both furnace and air cleaner operation per the furnace and air cleaner installer guides.
8 Numbers in [brackets] are for 50 Hz international systems. EAC-SF-13
Loading...
+ 16 hidden pages