Trane AFD260CLAH000D, AFD145CLFR000D, AFD210CLFR000D, AFD175CLFR000D, AFD245CLFR000D Service Facts

...
Page 1
Service Facts
EAC- SF- 1 3
Whole House Electronic Air Cleaner
Upflow Furnace Models
*FD145CLFR000D *FD175CLFR000D *FD210CLFR000D *FD245CLFR000D
ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES
IMPORTANT — This Document is customer property and is to remain with this unit.
Please return to service information pack upon completion of work.
44
4
1
99
9
99
33
3
33
44
Downflow Furnace Models
*FD14DCLFR000D *FD17DCLFR000D *FD21DCLFR000D *FD24DCLFR000D
Air Handler Models
*FD175CLAH000D *FD215CLAH000D *FD235CLAH000D *FD260CLAH000D
COMPONENTS OF THE AIR CLEANER
33
3
33
55
5
55
66
6
66
50 Hz Air Handler Models
TFD215CLAH005D TFD235CLAH005D TFD260CLAH005D
* May be "A" or "T"
11
1
11
1) PRE-FILTER - traps large particles such as hair and lint before they can enter the COLLECTION CELL section.
2) FIELD CHARGER - Charges the contaminants. Only to be serviced by a qualified technician.
3) COLLECTION CELL (2) - removes and collects very small
impurities from the air.
4) CABINET - mounts between the furnace/air handler and return air duct work and houses the COLLECTION CELLS, FIELD CHARGER and PRE-FILTER.
5) POWER DOOR - the solid state power supply components that convert the 24 Volt AC to the high-voltage, direct current required to power the FIELD CHARGER and COLLECTION
!
WARNING
This information is for use by individuals having adequate backgrounds of electrical and mechanical experience. Any attempt to repair a central air conditioning product may re­sult in personal injury and/or property damage. The manu­facturer or seller cannot be responsible for the interpreta­tion of this information, nor can it assume any liability in con­nection with its use.
88
8
88
77
7
22
2
22
6) TRANSFORMER - supplies 24 Volts to the indoor unit and Air
7) 24 VOLT POWER / CONTROL CABLE
8) GASKET, LITERATURE AND HARDWARE PACKET
9) UPFLOW AIR HANDLER BAFFLE - This baffle is only included
RECONNECT ALL GROUNDING DEVICES.
All parts of this product that are capable of conducting elec­trical current are grounded. If grounding wires, screws, straps, clips, nuts, or washers used to complete a path to ground are removed for service, they must be returned to their original position and properly fastened.
77
CELLS. Allows access to the COLLECTION CELLS, FIELD CHARGER and PRE-FILTER.
Cleaner
with Air Handler models. See note below.
NOTE: Be careful not to discard the baffle. It is located under
(not available with 50 Hz units)
the collection cells in the shipping box.
!
CAUTION
11
1
11
22
2
22
AIR
FLOW
33
3
33
© Trane 2011
Page 2
Service Facts
INTRODUCTION
The whole house air cleaner can be installed either as part of a Communicating heating and air conditioning system or as part of a traditional 24 volt system.
When installed as part of a Communicating System in which the indoor unit, outdoor unit, and 900 series comfort control are equipped with our exclusive Communicating technology, this system performs a continuous loop of system diagnostics and data output. The Communicating System monitors itself and quickly identifies any operational faults, automatically issuing a service alert if needed.
The whole house air cleaner can also be installed as part of a traditional 24 volt heating and air conditioning system.
MODES OF OPERATION
The whole house air cleaner can be connected in one of two modes of operation; either a 24 V mode or a communicating mode. To know how the whole house air cleaner is set up, reference Figure 1a to find the amber light.
Power Button
Amber Light
Plug Power Cord in here
1a
A steady amber light indicates that the unit is wired in the 24 V mode. A blinking amber light indicates that the unit is wired in the communicating mode. No light present means that the unit is not connected.
!
CAUTION
SAFETY HAZARD Sharp Edge Hazard. Be careful of sharp edges on equip­ment or any cuts made on sheet metal while installing or servicing. Personal injury may result.
ELECTRICAL CONNECTIONS
The air cleaner requires 24 VAC power and indoor fan signal to operate. A transformer adequately sized to power both the system and air cleaner is provided with the air cleaner. Remove the transformer in the indoor unit and replace with the transformer provided.
N
OTE: A 50 VA transformer is required for Trane/ American Standard Heating & Air Conditioning furnace applications and 75 VA required for Trane/ American Standard Heating & Air Conditioning air handler applications. If the indoor air handler already has a properly sized transformer, no replacement is required.
NOTE: Trane/American Standard Heating & Air Conditioning dual circuited air handlers matched with heat pumps and Trane/American Standard Heating & Air Conditioning oil furnaces will require an accessory Transformer KIT# BAYTRANS12024 power the air cleaner. Do NOT replace air handler transformer with the transformer supplied with the air cleaner.
◆◆
◆◆
to
NOTE: When more than one whole house air cleaner is used, the 24 volt transformer which supplies power to the air cleaner will need to be increased by
25 VA for each additional air cleaner added.
NOTE: Provide adequate strain relief for the low voltage cable at the indoor unit.
NOTE: Wiring penetration must be sealed.
DO NOT attach the power/control cable to a 120 Volt EAC tap. The air cleaner uses 24 Volt power. Failure to use 24 VAC results in permanent damage to the air cleaner.
• Plug the air cleaner power/control cable into the air cleaner door and route the cable into the indoor unit low voltage wiring location.
• Connect the power/control wiring per Figure 2.
NOTE: For non-Trane/American Standard Heating & Air Conditioning systems order a 120 VAC to 24 VAC transformer, KIT# BAYTRANS12024 power only to the air cleaner. Access to 120 VAC outlet is required.
• Connect the power/control wiring per Figure 3.
NOTE: Trane/American Standard Heating & Air Conditioning Communicating Furnaces require KIT # BAYACCECOMM101.
NOTE: Wiring diagrams for the Communicating Air Handler, Communicating Furnaces and Oil Furnace are on pages 3, 4-5 and 6 respectively.
!
CAUTION
◆◆
to provide 24 volt
◆◆
2 Numbers in [brackets] are for 50 Hz international systems. EAC-SF-13
Page 3
Wiring Diagram
22
2
22
Communicating Mode
Data Line
BROWN
D
NOTE: The Black wire must be connected to chassis ground to ensure proper operation.
BAYTRANS12024
◆◆
Transformer
◆◆
Air Handler may not have a Low Voltage Terminal board. Connect Electronic Air Cleaner wires to
the Air Handler Low Voltage Color coded wires.
Install Transformer, one is supplied with the Electronic Air Cleaner, in the Furnace or Air Handler.
• Transformer must have a grounded 120 VAC power source. Do not defeat ground plug on the transformer.
• Mount transformer to building structure with the four provided wood screws.
NOTE: BAYTRANS12024C complies with the California Code of Regulation,Title 20, Sections 1601 through 1608 dated December 2006. BAYTRANS12024A with
vendor’s manufacturing date codes after 0625 (YYWW) cannot be installed in California because the transformer does not satisfy the requirements set forth by California
Code of Regulations, Title 20, Sections 1601 through 1608 dated December 2006.
Transformer not applicable to 50 Hz units.
BLACK
GRD
RED
BLUE
Unused GREEN
BROWN
WHITE
Unused
Furnace
Heating Signal
Fan Signal
Data Line
24 V
Common
RED
BLUE
GREEN
BROWN
BLACK
WHITE
Furnace / Air Handler
RED
BLUE
WHITE
GREEN
BROWN
Indoor Unit
24 V Terminal Strip
BLUE
GREEN
BROWN
BLACK
RED
WHITE
R
BLUE
B
Unused
WHITE
W
Unused
G
GREEN
BROWN /
D
Dataline
GREEN
BROWN
BLACK
WHITE
BLUE
RED
The represents an alpha character.
Wiring Diagram
33
3
33
for 24 V Mode
NOTE: The Black wire must be connected to chassis ground to ensure proper operation.
◆◆
BAYTRANS12024
Transformer
◆◆
• Transformer must have a grounded 120 VAC power source. Do not defeat ground plug on the transformer.
• Mount transformer to building structure with the four provided wood screws.
NOTE: BAYTRANS12024C complies with the California Code of Regulation,Title 20, Sections 1601 through 1608 dated December 2006. BAYTRANS12024A with
vendor’s manufacturing date codes after 0625 (YYWW) cannot be installed in California because the transformer does not satisfy the requirements set forth by California
Code of Regulations, Title 20, Sections 1601 through 1608 dated December 2006.
Transformer not applicable to 50 Hz units.
Air Handler may not have a Low Voltage Terminal board. Connect Electronic Air Cleaner wires to
the Air Handler Low Voltage Color coded wires.
Install Transformer, one is supplied with the Electronic Air Cleaner, in the Furnace or Air Handler.
Common
Furnace
Heating Signal
Fan Signal
24 V
Indoor Unit
24 V Terminal Strip
Furnace / Air Handler
RED
BLUE
WHITE
GREEN
BLUE
GREEN
BROWN
BLACK
RED
WHITE
R
BLUE
B
WHITE
W
GREEN
G
BROWN /
Dataline
GREEN
BROWN
BLACK
WHITE
BLUE
RED
The represents an alpha character.
Page 4
Service Facts
BK R
O G Y1 Y2
D
B W1 W2 W3
BK R
O G Y1 Y2
D
B W1 W2 W3
GREEN
WHITE
ELECTRICAL CONNECTIONS TO A COMMUNICATING SYSTEM AIR HANDLER
IN CONVENTIONAL 24 V MODE
!
WARNING
HAZARDOUS VOLTAGE! DISCONNECT ALL ELECTRIC POWER, INCLUDING REMOTE DISCONNECTS BEFORE SERVICING. FOLLOW PROPER LOCKOUT/TAGOUT PROCEDURES TO ENSURE THE POWER CAN NOT BE INADVERTENTLY ENERGIZED. FAILURE TO DISCONNECT POWER BEFORE SERVICING COULD RESULT IN DEATH OR SERIOUS INJURY.
PROCEDURE:
1) Remove electrical power going into the air handler.
2) On the communicating systems air handler, remove the blower access panel.
3) Remove the communicating control box cover.
4) Locate the red jumper wire which is attached from EAC to R on the Communicating Systems PCB. Confirm it is connected. If there is not a jumper wire installed, then one must be installed in this location in order for the air cleaner to function properly.
Detach female spade terminal
from white EAC wire and
crimp to green wire
5) Replace the Communicating control box cover.
6) Locate the white wire coming from the Communicating System Air Handler PCB labeled “EAC”. The wire will have a male spade terminal connected to it and a female spade terminal inserted into the male terminal. Remove the female spade terminal and crimp it to the green wire on the air cleaner harness.
7) Connect the green wire from the air cleaner harness to the white wire on the Communicating Systems Air Handler.
8) Using the wire harness supplied with the air cleaner, connect the Red and Blue wires from the air cleaner harness to “R” and “B” on the Indoor Unit 24V Terminal Strip respectively.
9) Connect the Black wire from the air cleaner wire harness to earth ground by attaching the wire to a grounded screw that is connected to the metal air handler chassis.
10) Replace the blower access panel.
11) Reconnect electrical power to the air handler.
Control box panel cover
(Shown removed)
24V RED
jumper wire
from EAC to R
BEFORE AFTER
WHITE
WHITE
GREEN
Indoor Unit
24V
Terminal
Strip Detail
4 Numbers in [brackets] are for 50 Hz international systems. EAC-SF-13
GREEN
EAC
GREEN
BLUE
RED
WHITE
Unused
BLACK
GRD
Wiring Cable and Plug
BROWN /
Future Use
For use with Whole House
Air Cleaner
Power / Control
Air Cleaner Plug
EAC
R
PCB Detail
Page 5
ELECTRICAL CONNECTIONS TO A STANDARD 24 VOLT AIR HANDLER
!
WARNING
HAZARDOUS VOLTAGE! DISCONNECT ALL ELECTRIC POWER, INCLUDING REMOTE DISCONNECTS BEFORE SERVICING. FOLLOW PROPER LOCKOUT/TAGOUT PROCEDURES TO ENSURE THE POWER CAN NOT BE INADVERTENTLY ENERGIZED. FAILURE TO DISCONNECT POWER BEFORE SERVICING COULD RESULT IN DEATH OR SERIOUS INJURY.
Service Facts
Field wiring
W3 W2
W1
G
YI
O R B YO
GREEN
BLUE
RED
WHITE
Unused
GAM5 / A/TAM4
BLACK
GRD
BROWN /
Future Use
For use with Whole House
Power / Control
Wiring Cable and Plug
Air Cleaner
Air Cleaner Plug
W3 W2
W1
BK
G Y2 YI O R B
YO
GREEN
BLUE
RED
WHITE
Unused
(In)
(Out)
BLACK
GRD
Wiring Cable and Plug
BROWN /
Future Use
A/TAM7
For use with Whole House
Air Cleaner
Power / Control
Air Cleaner Plug
EAC-SF-13 Numbers in [brackets] are for 50 Hz international systems. 5
Page 6
Service Facts
BK R
O G Y1 Y2
D
B W1 W2 W3
BK R
O G Y1 Y2
D
B W1 W2 W3
ELECTRICAL CONNECTIONS TO A COMMUNICATING SYSTEMS AIR HANDLER
IN COMMUNICATING MODE
!
WARNING
HAZARDOUS VOLTAGE! DISCONNECT ALL ELECTRIC POWER, INCLUDING REMOTE DISCONNECTS BEFORE SERVICING. FOLLOW PROPER LOCKOUT/TAGOUT PROCEDURES TO ENSURE THE POWER CAN NOT BE INADVERTENTLY ENERGIZED. FAILURE TO DISCONNECT POWER BEFORE SERVICING COULD RESULT IN DEATH OR SERIOUS INJURY.
1) Remove electrical power going into the air handler.
2) On the communicating systems air handler, remove the blower access panel.
3) Connect Red stripped wire to "R" terminal on the air handler terminal strip.
4) Connect Blue stripped wire to "B" terminal on the air handler terminal strip.
5) Connect the brown wire from the air cleaner harness to the "D" terminal on the Communicating Systems Air Handler.
6) Connect the Black wire from the air cleaner wire harness to earth ground by attaching the wire to a grounded screw that is connected to the metal air handler chassis or control plate assembly.
7) The Green and White wires on the air cleaner wiring harness are unused in this application and should be insulated separately.
8) Replace the blower access panel.
9) Reconnect electrical power to the air handler.
10) Check air cleaner and air handler operation.
4TEE3C A/TAM8
Control box panel cover
(Shown removed)
PROCEDURE:
Indoor Unit
24V Terminal
Strip Detail
Y2 Y1
O R
B D
RED
BROWN /
Dataline
WHITE
Unused
BLUE
BLACK
GRD
For use with Whole House
Air Cleaner
Power / Control
Wiring Cable and Plug
GREEN
Unused
Air Cleaner Plug
BLUE
RED
BROWN /
Dataline
WHITE
Unused
BLACK
GRD
Black wire to
chassis ground
6 Numbers in [brackets] are for 50 Hz international systems. EAC-SF-13
For use with Whole House
Air Cleaner
Power / Control
Wiring Cable and Plug
GREEN
Unused
Air Cleaner Plug
Page 7
Service Facts
ELECTRICAL CONNECTIONS TO A COMMUNICATING FURNACE IN 24 V MODE
!
WARNING
HAZARDOUS VOLTAGE! DISCONNECT ALL ELECTRIC POWER, INCLUDING REMOTE DISCONNECTS BEFORE SERVICING. FOLLOW PROPER LOCKOUT/TAGOUT PROCEDURES TO ENSURE THE POWER CAN NOT BE INADVERTENTLY ENERGIZED. FAILURE TO DISCONNECT POWER BEFORE SERVICING COULD RESULT IN DEATH OR SERIOUS INJURY.
PROCEDURE:
1. Remove electrical power going into the furnace.
2. Remove blower door to up-flow or down-flow furnace.
3. Remove the two screws that secure the IFC platform to the underside of the blower deck on an up-flow furnace or the 3 screws that secure the IFC platform to the top panel on a down-flow furnace.
4. Carefully remove the IFC platform from the furnace.
5. On both the up-flow and down-flow furnaces, mount the 50VA transformer supplied in the packaging with the air cleaner onto the bottom of the IFC platform. Screws and pilot holes are provided. See figure.
6. Remove wiring from existing 35VA transformer and reconnect to the 50VA transformer. Note the polarity of the wires and reconnect to the appropriate terminals. See diagram
7. Remove the EAC-H 115VAC and EAC-N wires (white and black) out of the junction box and pull them through the grommet in the blower deck. Attach two supplied ¼” insulated female quick connect terminals by stripping the wires and crimping the terminals onto the wires. Attach these wires to the 115V terminals of the 35VA transformer as shown in the diagram.
8. Remove the wiring harness supplied with the air cleaner from the packaging. Attach a supplied 3/16” insulated female quick connect terminal to the blue wire and the green wire.
9. Attach the blue wire from the air cleaner wiring harness to the open tab on the piggyback terminal supplied in the BAYACCECOMM101. Attach piggyback terminal to the 35VA transformer terminal “C” (Common).
10. Insert the 12” blue stripped wire under the terminal strip screw marked “B/C” on the IFC control board. If the applica­tion also includes an outdoor unit (communicating or non­communicating), the B/C terminal will require 3 wires connected. For this connection, rather than connecting the three wires to the low voltage terminal strip on the furnace IFC, create a pigtail using a short length of thermostat wire and a wire nut (field supplied) to attach to the B/C terminal.
11. Connect the green wire from the air cleaner wiring harness to the 24V terminal on the 35VA transformer labeled “RD”. See diagram.
12. Insert the red stripped wire from the air cleaner wiring harness under the IFC control board terminal screw marked “R”. See diagram.
13. Attach the black stripped wire from the air cleaner wiring harness directly to ground with a screw on the furnace chassis. See diagram.
14. Once all of the connections have been completed, remount the IFC control platform into the furnace.
15. Secure any loose wiring with wire ties.
16. The brown and white wires from the EAC wiring harness are unused in this application and should be insulated. See diagram.
17. Replace the furnace door.
18. Reconnect electrical power to the furnace.
19. Check both furnace and air cleaner operation per the furnace and air cleaner installer guides.
BILL OF MATERIALS:
QTY: 2 Screw QTY: 1 4" Insulated Copper Wire –
QTY: 2 1/4” Insulated Female Quick
QTY: 2 3/16" x 0.020" Insulated Female
QTY: 1 3/16" x 0.020" Receptacle & Tab
EAC-SF-13 Numbers in [brackets] are for 50 Hz international systems. 7
Blue (18 AWG, AWM)
Connect Terminal
Quick Connect Terminal
These instructions and listed parts are included in KIT# BAYACCECOMM101
Page 8
Service Facts
ELECTRICAL CONNECTIONS TO A COMMUNICATING SYSTEM FURNACE
!
WARNING
HAZARDOUS VOLTAGE! DISCONNECT ALL ELECTRIC POWER, INCLUDING REMOTE DISCONNECTS BEFORE SERVICING. FOLLOW PROPER LOCKOUT/TAGOUT PROCEDURES TO ENSURE THE POWER CAN NOT BE INADVERTENTLY ENERGIZED. FAILURE TO DISCONNECT POWER BEFORE SERVICING COULD RESULT IN DEATH OR SERIOUS INJURY.
PROCEDURE:
1. Remove electrical power going into the furnace.
2. Open blower door to upflow or downflow furnace.
3. Disconnect all wires on the 35VA transformer.
4. Remove the 35VA transformer from the IFC platform.
5. Mount the 50 VA transformer supplied in the packaging with the air cleaner onto the IFC platform where the 35VA transformer was previously located. Use the sheet metal screws supplied with the air cleaner to mount the 50VA transformer. Reconnect the 115V and 24V wires that were connected to the 35VA transformer onto the 50 VA transformer.
6. Connect Red stripped wire to "R" terminal on the furnace control board.
7. Connect Blue stripped wire to "B" terminal on the furnace control board.
8. Connect Brown stripped wire to "D" terminal on the furnace control board.
9. Attach the black stripped wire from the air cleaner wiring harness directly to ground with a screw in the chassis.
10. The green and white wires on the air cleaning wiring harness are unused in this application and should be insulated.
11. Replace door on furnace.
12. Reconnect electrical power to the furnace.
13. Check both furnace and air cleaner operation per the furnace and air cleaner installer guides.
8 Numbers in [brackets] are for 50 Hz international systems. EAC-SF-13
Page 9
Service Facts
ELECTRICAL CONNECTIONS TO AN OIL FURNACE
!
WARNING
HAZARDOUS VOLTAGE! DISCONNECT ALL ELECTRIC POWER, INCLUDING REMOTE DISCONNECTS BEFORE SERVICING. FOLLOW PROPER LOCKOUT/TAGOUT PROCEDURES TO ENSURE THE POWER CAN NOT BE INADVERTENTLY ENERGIZED. FAILURE TO DISCONNECT POWER BEFORE SERVICING COULD RESULT IN DEATH OR SERIOUS INJURY.
SINGLE STAGE OIL FURNACE TO AIR CLEANER
THERMOSTAT
R/ RC
NOTE 1
RH
Y
G
FURNACE
FAN CENTER
R
Y
G
AIR
CLEANER
R
BR
G
Refer to the diagrams below for proper connections to an oil furnace. Consult the oil furnace installer's guide for additional information.
VARIABLE SPEED OIL FURNACE TO AIR CLEANER
FURNACE
THERMOSTAT
R/ RC
NOTE 1
RH
Y/ Y1
G
LOW VOLTAGE
TERMINAL
BLOCK
R
O
Y/ Y2
G
Factory
Jumpered
AIR
CLEANER
R
BR
G
NOTE 1:
NOTE 2:
NOTE 3:
W
R1
NOTE 2
W
C
W
B
Bk
GND
OIL BURNER PRIMARY
T
R1
NOTE 2
T
If thermostat being used has separate RC and RH terminals, jumper RC and RH together.
Oil burner primary TT contacts must be isolated using field supplied relay (RLY00925) or equivalent.
The black wire (Bk) from ACCE unit must be connected to chassis ground to ensure proper operation.
NOTE 3
W1
NOTE 1:
NOTE 2:
NOTE 3:
R1
B
NOTE 2
BCC
BK
W1
W
B
Bk
GND
OIL BURNER PRIMARY
T
R1
NOTE 2
T
If thermostat being used has separate RC and RH terminals, jumper RC and RH together.
Oil burner primary TT contacts must be isolated using field supplied relay (RLY00925) or equivalent.
The black wire (Bk) from ACCE unit must be connected to chassis ground to ensure proper operation.
NOTE 3
EAC-SF-13 Numbers in [brackets] are for 50 Hz international systems. 9
Page 10
Service Facts
ELECTRICAL CONNECTIONS FOR DUAL WHOLE HOUSE AIR CLEANER
Dual Whole House Air Cleaners
In some instances, two whole house air cleaners can be utilized to manage the overall system operational static pressure. The figure below shows two whole house air cleaners installed on an upflow furnace. The 24 volt transformer which supplies power to the air cleaner will need to be increased by 25 VA for each additional air cleaner added.
See the wiring diagrams for information on how to attach the wires in a two whole house air cleaner system. The figure on the top of page 10 shows the wiring hookup for two whole house air cleaners attached to a furnace in conventional 24 V mode.
The figure on the bottom of page 10 shows the wiring hookup for two whole house air cleaners attached to a furnace in communicating mode.
Refer to the wiring diagrams on pages 3 through 8 for guidance on wiring the whole house air cleaners to the system properly. All wires will be run the same way for each of the two whole house air cleaners.
Airflow
Dual System on Furnace
10 Numbers in [brackets] are for 50 Hz international systems. EAC-SF-13
Page 11
Service Facts
ELECTRICAL CONNECTIONS FOR DUAL WHOLE HOUSE AIR CLEANERS
AND FURNACE IN CONVENTIONAL 24V MODE
FIELD SUPPLIED 50 VA TRANSFORMER
ELECTRICAL CONNECTIONS FOR DUAL WHOLE HOUSE AIR CLEANER AND
FURNACE IN COMMUNICATING MODE
FIELD SUPPLIED 75 VA TRANSFORMER
EAC-SF-13 Numbers in [brackets] are for 50 Hz international systems. 11
Page 12
Service Facts
4
DIRTY
CLEAN
LEDs
POWER
PRE-FILTER
PRE-FILTER
RESET
RESET
LED DISPLAY
DISPLAY FEATURES (Fig. 4)
The Air Cleaner display can be used for several functions.
• Provide the homeowner the operating status of the air cleaner, including an indication the PRE-FILTER or
COLLECTION CELLS need cleaning.
• The installer can access the SET-UP mode to change the time to clean settings for the PRE-FILTER and COLLECTION CELLS as well as change the Power level setting.
• The unit will display fault codes for the homeowner indicating
there is a problem with the Air Cleaner and various fault codes for the service technician to assist in troubleshooting the problem.
AIR CLEANER OPERATION
Turn the Air Cleaner on by pushing and releasing the POWER button . The backlit POWER and RESET buttons
will illuminate along with the first Green LED (G1) indicating 24 volt power is present to the Air Cleaner.
When the indoor fan is operating the first LED (G1) will slowly flash. This indicates the FIELD CHARGER and COLLECTION CELLS have power and the unit is operating normally. There is a slight time delay between the indoor fan starting and LED (G1) flashing. Time delay for "G" fan is 10 [12] seconds. Time delay for heating is 90 [108] seconds.
In normal operation, the Air Cleaner makes a slight sound as the air passes through it and is cleaned. In some applications, you may notice this sound coming from the return air vent(s). If desired, this sound level can be reduced with minimal impact on air cleaning efficiency by reducing the power setting of the FIELD CHARGER in the SET-UP mode.
NOTE: There is a 10 [12] minute delay after the indoor fan operates, before the Air Cleaner starts to operate, each time the power to the Air Cleaner is turned off/on. This can be bypassed by going into and then out of the SET-UP mode
SET-UP MODE
A combination of Red, Yellow, and Green LED's are used to indicate the following settings.
• Three Green LED's are used to indicate PRE-FILTER clean-
ing interval. This is measured in actual run time of the indoor fan. The factory setting is 2 months [10 weeks]. Figure 5.
• Four Yellow LED's indicate the COLLECTION CELL cleaning
interval. This is measured in actual run time of the indoor fan. The factory setting is 6 months [31 weeks]. See Figure 6.
• The three Red LED's indicate the power level setting. The
default setting is maximum. See Figure 7.
SET-UP MODE OF OPERATION
To enter the SET-UP mode press and hold both the POWER and RESET buttons for a minimum of 5 [6] seconds. The display will go blank and then the factory settings for each of the settings are displayed. If this is the desired setting or at any time you want to exit the SET-UP mode, press and hold BOTH the POWER and filter RESET buttons for a minimum of 5 [6] seconds to exit.
To change any of the settings, press the POWER button once. Follow the below instructions for setting the pre-filter and collection cell timers. For a Communicating Air Cleaner, be sure the Comfort Control filter timer is set to “Auto Detect” before changing the settings on the air cleaner. To determine whether or not the unit is a communicating unit, review the Amber light shown in Figure 1a on page 2.
PRE-FILTER SETTING (Fig.5 ) One or more of the Green LED’s will come on indicating the PRE-FILTER cleaning time setting. Repeatedly press the RESET button to cycle through the time options for the PRE­FILTER cleaning cycle until the desired setting is displayed. Press the POWER button once to accept that setting and
move to the COLLECTION CELLS cleaning settings.
GREEN LED PRE-FILTER SETTINGS
5
DIRTY
CLEAN
One Month
R3 R2 R1 Y4 Y3 Y2 Y1 G3 G2 G1
[5 Weeks]
DIRTY
CLEAN
R3 R2 R1 Y4 Y3 Y2 Y1 G3 G2 G1
Two Months *
[10 Weeks]
DIRTY
CLEAN
R3 R2 R1 Y4 Y3 Y2 Y1 G3 G2 G1
Three Months
[15 Weeks]
COLLECTION CELLS CLEANING SETTING (Fig.6) One or more of the Yellow LED’s will come on indicating the COLLECTION CELLS cleaning time setting. Repeatedly press the RESET button to cycle through the time options for the COLLECTION CELLS cleaning cycle until the desired setting is displayed. Press the POWER button once to
accept that setting and move to the Power level settings.
COLLECTION CELLS CLEANING SETTING
6
DIRTY
R3
R2
R1 Y4 Y3 Y2 Y1
G3 G2
CLEAN
G1
Two Months
[10 Weeks]
* Factory Setting
DIRTY
R3 R2 R1 Y4 Y3 Y2
Y1 G3 G2
CLEAN
G1
Four Months
[20 Weeks]
DIRTY
CLEAN
Six Months*
[31 Weeks]
DIRTY
CLEAN
R3 R2 R1 Y4 Y3 Y2 Y1 G3 G2 G1
R3 R2 R1 Y4 Y3 Y2
Y1
G3 G2 G1
Nine Months
[46 Weeks]
12 Numbers in [brackets] are for 50 Hz international systems. EAC-SF-13
Page 13
Service Facts
NOTE: If two air cleaners are connected on the same system, set all timers on both air cleaners to the same settings. The comfort control will only report one air cleaner timer and this methodology will allow the air cleaners to remain on the same cleaning schedule.
FIELD CHARGER Power Level
The Red LED lights are used to set the power level of the FIELD CHARGER for maximum, medium, or minimum. The
number of illuminated Red LED lights indicates the current setting. The factory setting is for maximum.
Lower settings will reduce the slight sound emitted by the unit with minimal loss of air cleaning efficiency, if desired. Lower settings will also further reduce the very low ozone produced by the Air Cleaner. The U.S. Food and Drug Administration recommends indoor ozone concentrations should not exceed 50 parts per billion. The Air Cleaner will contribute only 5 parts per billion at the factory setting and can be reduced to .3 parts per billion at the minimum setting.
FIELD CHARGER Power Level Setting (Fig. 7) One or more of the Red LED lights will illuminate. To change the power level setting, press the RESET button until the desired setting is indicated.
To save your new settings and exit the SET-UP mode, press and hold BOTH the POWER and filter RESET buttons for a minimum of 5 [6] seconds.
RED LED POWER LEVEL SETTINGS
7
Minimum Medium Maximum**
DIRTY
CLEAN
R3 R2 R1 Y4 Y3 Y2 Y1 G3 G2 G1
DIRTY
CLEAN
R3 R2 R1 Y4 Y3 Y2 Y1 G3 G2 G1
DIRTY
CLEAN
R3 R2 R1 Y4 Y3 Y2 Y1 G3 G2 G1
or the COLLECTION CELLS need to be cleaned. The Air Cleaner control has detected ten consecutive automatic High Voltage Shut Down (HVSD) cycles. An automatic HVSD cycle is normally activated by the control system when an internal electrical arc occurs.
THREE RED LEDS & THE PRE-FILTER LED FLASHING
This means service is needed. For these THREE Red LEDs to flash on and off the control must have detected the SAME FAULT (see Fault Code Table on page 5) THREE TIMES in a row. The PRE-FILTER will flash during the 3 flashing Yellow LEDs or 3 flashing Red LEDs lockout mode.
FAULT CODES RETRIEVAL
To retrieve the last three faults that the Air Cleaner Control has detected, enter the SET-UP mode of operation. Press and hold the POWER
for a minimum of five seconds. When the control enters the SET-UP mode of operation some of the Green, Yellow and Red LEDs will be on. The color and number of LEDs that are on indicates how the control is presently programmed. (See SET-UP CHARTS on previous page). To enter the Fault Codes section press and hold the RESET Button for ten seconds. After ten seconds the main LED display will go out for one second and then some of the LEDs may begin to flash on and off. If no fault has been detected then only the first Green LED will be flashing on and off. The flashing Green LED or LEDs identifies the fault number being reported out. One Green Led flashing on and off means the last fault detected is being reported out, two Green LEDs flashing means the second fault detected is being reported out and three Green LEDs flashing means the last fault stored in the control memory is being reported out. The last three faults detected will be stored in the control’s memory and the last fault detected will be the first fault reported out.
You are now in the Fault Log report section and the last fault detected is now being reported out. To step through the faults, press the POWER
button again to get the second fault and again pressing the POWER fault stored in the control’s memory. Push the POWER button again and the control will display the last fault detected.
To exit the SET-UP mode, press and hold both the POWER and Filter RESET buttons for a minimum of 5 seconds.
button and the RESET button
button will take you to the last
**Factory Setting
FAULT CODES
The Air Cleaner LEDs will display a fault indication, three yellow or three Red LEDs, when a fault has been detected. A log of the last three faults is recorded and can be accessed by going into the SET-UP mode. The unit will repetitively check the system to determine if the fault persists. The fault indication will be displayed as long as the fault condition remains.
If the fault is no longer present, the system will return to normal operation and no longer display the fault indication. Even if the fault has been corrected, a log of the last 3 faults is recorded.
THREE YELLOW LEDs FLASHING
These LEDs flashing on and off means that the PRE-FILTER
FAULT CODES
When a fault is being reported out check the position number of any of the Yellow and Red LEDs flashing on and off. Compare this combination of flashing LEDs position numbers to the Fault Code chart to see which fault has been detected. The number one Yellow LED will always be out in the Fault Code report section.
Dual Air Cleaner Faults and Filter Reset: When dual air cleaners are installed as part of a communicating system, each whole house air cleaner will retain its own faults. However, in a communicating system with dual air cleaners, the 900 series comfort control will only recognize the filter timers for one air cleaner. Both the Pre-Filter and Collection Cell timers for one air cleaner can be reset at the comfort control.
EAC-SF-13 Numbers in [brackets] are for 50 Hz international systems. 13
Page 14
Service Facts
ifD™ DISPLAY FAULT LED CODES
COMFORT
CONTROL ERROR
CODE
18
37
64
91 Communication Fault ON OFF ON OFF OFF ON Device Count
No ERR Code Communication Fault ON OFF ON OFF OFF ON Fast Flash
No ERR Code
107 Repetitive Arcing ON ON ON OFF OFF OFF Device Count
108
108
108 HV too HIGH ON OFF OFF ON ON ON Device Count
109
109 Input Current too HIGH ON ON OFF ON ON ON Device Count
125
FAULT DESCRIPTION YEL-1 YEL-2 YEL-3 YEL-4 RED-1 RED-2 RED-3
Internal control lockout
Duplicate Filter, Another filter
timer is present/ Only seen
when Air Cleaner is configured
in the communication mode and the Comfort Control filter times are not set to "E" auto-
discover on set-up 500 and
501.
One or more buttons are stuck
in the ON position on the air-
cleaner door.
Communication Fault
HV off when it should be on /
This can be caused by a
grounded field charger or shorted cells which causes an air-cleaner shuts down before
the power output reaches 5
KV.
HV too LOW
Input Current too LOW
Input A/C Voltage too LOW
ON ON ON ON OFF OFF Device Count
Not
reported to
Not reported
air-cleaner
interface
to air-
cleaner user
user
interface
ON ON ON ON ON OFF Device Count
ON OFF ON OFF OFF ON Device Count
ON OFF OFF ON OFF OFF Device Count
ON OFF OFF ON ON OFF Device Count
ON ON OFF ON ON OFF Device Count
OFF OFF OFF ON OFF OFF
Not reported to air-cleaner
user
interface
Not reported to air-cleaner
user
interface
Not reported to air-cleaner
user
interface
reported to
air-cleaner
interface
Not
user
AIR-CLEANER
Device Count
COM LED
SERVICE PROCEDURE
Repower Air Cleaner - check for normal
operation. Replace door if same fault comes
User set-ups 500 and 501 will need to be
changed back to "E" to enable the comfort
control to auto-discover the filter cleaning
timer set-up in the air-cleaner.
Check to see if buttons operate smoothly and
are not obstructed. If unable to free button
replace air-cleaner door
Air-cleaner can not generate a ERROR
CODE 91 on the comfort control, fault is with
Active communicating fault. Check for 12-13
voltage DC between Brown and Blue wires at
Like the furnace and air-handler's users
interfaces the air-cleaner stores fault codes. Check air-cleaner COM LED for device count (one blink for each communicating device on
the COM BUS) If device count is present
ensure air-cleaner green LED #1 blinks slow
with indoor blower operation. Clear fault log
Clean Collection Cells and Field Charger - If
they are clean, check for arcing through the
Check for arcing through the Collection Cells
and Field Charger cases. Check door
operation by referring to Testing the Power
Door on page 17 of the air-cleaner's Service
Remove power door and recheck high voltage-if still low replace power door, If voltage is correct, check cells and Field
Check for arcing through the Collection Cells
and Field Charger cases. Check door
operation by referring to Testing the Power
Door on page 17 of the air-cleaner's Service
Check Collection Cells and Field Charger
Clean Collection Cells and Field Charger.
Check for arcing through the Collection Cells
Check 24 volt supply to the air-cleaner. The
supply voltage should not drop below 22 volts
under full load. Ensure Transformer is rated
for at least 50VA for furnaces and 75 for air-
handlers. If two or more air-cleaners are
connected on a system, ensure the
transformer ratting is increased 25 VA for
other unit.
the air-cleaner connection plug.
plastic frame.
Facts
Charger.
Facts
connector pins.
and Field Charger cases.
each additional air-cleaner
NOTE: If more that one whole house air cleaner is installed, each unit will retain its own fault codes.
!
WARNING
High Voltage is present within the Air Cleaner for operation.
Examples: see Fig. 8
Before removing the Power Door, turn the power off and wait at least 15 seconds to allow voltage to discharge. Failure to
Ex. #1: The most recent fault condition was a High Voltage “HV
was Low”
disconnect power before servicing could result in death or serious injury.
Ex. #2: The second fault condition was “Internal Control Lock-
out”
Ex. #3: The third fault condition was “Input Current too High”
To clear all three faults codes from the control’s memory, press and hold the RESET button for 2-4 seconds when the fault codes are displayed. When the fault memory is cleared, the Yellow and Red LEDs will go out for all three fault locations. The Green LED or LEDs will remain on to mark the fault number, first, second or third fault.
8
DIRTY
CLEAN
R3 R2 R1 Y4 Y3 Y2 Y1 G3 G2 G1
DIRTY
CLEAN
R3 R2 R1 Y4 Y3 Y2 Y1 G3 G2 G1
DIRTY
CLEAN
R3 R2 R1 Y4 Y3 Y2
Y1
G3 G2 G1
Ex 1 Ex. 2 Ex. 3
14 Numbers in [brackets] are for 50 Hz international systems. EAC-SF-13
Page 15
!
Rotate Latches
WARNING
RISK OF ELECTRIC SHOCK: These servicing instructions are for use by qualified personnel only. To reduce the risk of electric shock, do not perform any servicing other than that contained in the Service Facts unless you are qualified to do so. Failure to follow all electrical safety precautions could result in death or serious injury.
SYSTEM INFORMATION
!
CAUTION
Before cleaning the coil or ducts in the air handler or furnace, remove the COLLECTION CELLS, FIELD CHARGER, and PRE-FILTER from the Air Cleaner. Chemicals used during the cleaning of the air handler, furnace, or ductwork can damage the Air Cleaner components and degrade the performance of the Air Cleaner.
CLEANING
NOTE: When the air cleaner is installed in 24 V mode, the LED's on the front of the air cleaner door will indicate when it is time to clean the filters. When the air cleaner is installed in communicating mode, the LED's on the front of the air cleaner will indicate when it is time to clean the air filters. In addition, the comfort control will also indicate when it is time to clean the filters.
Service Facts
Do not remove the door until all of the lights are off.
3. Disconnect the power /control cable.
4. Rotate the two latches and remove the door as shown in Figure 10. Place the door in a secure location.
!
CAUTION
Handle the door only by using the handles on the front of the door. Grasp the door by the handles as depicted in Figure 10 to remove and replace the door. Do not handle the door on the edges. Metal edges may be sharp and
could result in injury if the door is not handled properly.
0
5. Remove the PRE-FILTER (Figure 11) and/or the COLLEC­TION CELLS (Figure 12) from the Air Cleaner.
9
CLEAN
PRE-FILTER
RESET
Cleaning Instructions: The Air Cleaner utilizes a PRE-FILTER and COLLECTION CELLS. The purpose of the PRE-FILTER is to capture large particles before they enter the COLLECTION CELLS which allows the Collection Cells to work more efficiently.
1. Turn the air conditioning system off at the Comfort Control (thermostat).
High Voltage is present within the Air Cleaner for operation. Before removing the Power Door, turn the power off and wait at least 15 seconds to allow voltage to discharge. Failure to follow all electrical safety precautions could result in death or serious injury.
2. Turn off power to the Air Cleaner by pushing and holding the POWER button for three seconds. The LEDs will remain on until the voltage has discharged and it is safe to remove the door. This requires approximately 15 seconds.
Red light indicates that it is time to clean the COLLECTION CELLS
Red light indicates that it is time to clean the PRE-FILTER
!
WARNING
q
w
VACUUM CLEANING
Vacuuming is the preferred method to clean the PRE-FILTER and COLLECTION CELLS. It is recommended that the PRE­FILTER and the COLLECTION CELLS be vacuumed outside the home to ensure particles on the filters are not reintroduced into the air. Persons highly sensitive to the collected particles should wear appropriate respiratory protection while cleaning.
PRE-FILTER –
It is time to clean the PRE-FILTER when the red “PRE­FILTER” light is illuminated.
EAC-SF-13 Numbers in [brackets] are for 50 Hz international systems. 15
Page 16
Service Facts
The Air Cleaner is factory set to notify the homeowner to clean the PRE-FILTER every two months [10 weeks] of actual run time of the Air Cleaner. This notification can be changed by the installer/homeowner to 1 month [5 weeks] or 3 months [15 weeks] depending on the conditions in the home (pets, smokers, etc.). Please see “SET-UP MODE” (page 3) to change the factory settings.
1. Using a vacuum hose, vacuum in even strokes across the entire PRE-FILTER. Vacuum using even strokes in one direction, then repeat the process using even strokes in the opposite direction as demonstrated in Figure 13 below.
r
e
NOTE: Do NOT replace the plastic PRE-FILTER with a metal type PRE-FILTER. A metal PRE-FILTER will cause reduction in efficiency and potential failure of the electronics in the Air Cleaner.
COLLECTION CELLS
The clean/dirty LED light bar indicator will illuminate as the system cleans the air. The LED lights will progress from green to yellow and then to red. When the last red indicator is flashing, it is time to clean the COLLECTION CELLS (see Figure 12). The Air Cleaner is factory set to notify the homeowner to clean the COLLECTION CELLS every six months [31 weeks] of actual run time of the Air Cleaner. This notification can be changed by the installer/homeowner to 2 months, 4 months, 6 months, or 9 months [10, 20, 31, or 46 weeks] depending on the conditions in the home (pets, smokers, etc.). Please see “SET-UP MODE” (page 3) to change the factory settings.
1. Using a vacuum hose, vacuum in even strokes across the entire COLLECTION CELLS. Vacuum using even strokes in one direction, then repeat the process using even strokes in the opposite direction, as demonstrated in Figure 14.
2. Once vacuuming is completed on one side of the COL­LECTION CELLS, turn the COLLECTION CELLS over and repeat on the other side of the COLLECTION CELLS.
NOTE: It is normal for COLLECTION CELLS to discolor during operation. Vacuuming will not restore the COLLECTION CELLS to their original color. However, vacuuming does restore the COLLECTION CELLS to a high efficiency.
REPLACING THE PRE-FILTER AND COLLECTION CELLS INTO THE AIR CLEANER
1. Replace the PRE-FILTER into the Air Cleaner. Ensure that the “Air Flow indicator arrow” on the PRE-FILTER is pointing in the same direction as the “Air Flow indicator arrow” on the Air Cleaner cabinet.
t
2. Reinstall the COLLECTION CELLS into the Air Cleaner.
Ensure the handles on both of the COLLECTION CELLS are folded flat. Refer to Figure 16.
16 Numbers in [brackets] are for 50 Hz international systems. EAC-SF-13
Page 17
Service Facts
y
Handles Fold Flat
3. Replace the power door onto the Air Cleaner.
4. Ensure the power cord is plugged into the Air Cleaner.
A steady amber light
u
indicates that the unit is wired in the 24 V mode. A blinking amber light indicates that the unit is wired in the communicating mode. No light present means that the unit is not connected.
Power Button
i
Carefully review BOTH of the COLLECTION CELLS for the “200/200-1” mark. If the “200/200-1” mark is visible on BOTH COLLECTION CELLS, they may be washed. If the “200/200-1” mark is NOT visible, the COLLECTION CELLS
cannot be washed.
Amber Light
Plug Power Cord in here
5. Press the POWER button to turn on the Air Cleaner.
NOTE: Once you press the POWER button, the first LED will be on and it will start flashing after the first 10 [12] minutes of indoor fan operation. This is normal operation.
Alternate Cleaning Option For Homeowners with 200 or 200-1 COLLECTION CELLS ONLY
Vacuuming the PRE-FILTER and COLLECTION CELLS restores them to a high efficiency. However, some environmental conditions, like tobacco smoke, cause the COLLECTION CELLS to need to be washed with water. Washing the COLLECTION CELLS is acceptable ONLY if the COLLECTION CELLS have a “200/200-1” embossed or written on the frame in the vicinity of the manufacturing part number (Fig. 18).
NOTE: The PRE-FILTER may also be washed ONLY if the COLLECTION CELLS show a "200/200-1". Follow the same instructions to wash the PRE-FILTER - being sure to tap gently and wipe off any visible water droplets.
!
CAUTION
Washing COLLECTION CELLS that do NOT have the “200/ 200-1” mark on them can result in degradation of the Air Cleaner system. Failure to follow this instruction could result in property damages.
1. If the COLLECTION CELLS do have the “200/200-1” mark on them, they may be washed using a low pressure water spray, such as a sink sprayer or garden hose. Residue like tobacco smoke may require warm water to be removed.
• Do NOT use soap or detergent in cleaning the COLLEC­TION CELLS.
• Do NOT immerse the COLLECTION CELLS completely in water.
• Do NOT place the COLLECTION CELLS into a dishwasher to clean.
• ALLOW THE COLLECTION CELLS TO DRY THOROUGHLY BEFORE INSTALLING.
2. After washing, drain as much water as possible from the COLLECTION CELLS.
3. Holding the sides of the COLLECTION CELLS, gently tap the cells on a flat surface to dislodge any water droplets inside the COLLECTION CELLS. After tapping, wipe down the surfaces of the COLLECTION CELLS to remove any visible droplets of water.
EAC-SF-13 Numbers in [brackets] are for 50 Hz international systems. 17
Page 18
Service Facts
o
NOTE: Once you press the POWER button, the first LED will be on and it will start flashing after the first 10 [12] minutes of indoor fan operation. This is normal operation.
7. On the thermostat, reset the indoor fan operation to the desired mode. Turn the air system back on at the Comfort Control (thermostat).
Tap Gently
4. When there are no visible water droplets left in the COL­LECTION CELLS, reinstall them into the Air Cleaner cabinet. Be sure to fold the COLLECTION CELLS handles flat. Refer to Figure 20.
p
Handles Fold Flat
5. Replace the door onto the Air Cleaner cabinet.
6. Ensure that the power cord is connected to the Air Cleaner and press the POWER
a
button.
A steady amber light indicates that the unit is wired in the 24 V mode. A blinking amber light indicates that the unit is wired in the communicating mode. No light present means that the unit is not connected.
Power Button
NOTE: The field charger should never be subjected to water. The field charger should only be cleaned by a trained service professional.
NOTE: The PRE-FILTER may also be washed ONLY if the COLLECTION CELLS show a "200/200-1". Follow the same instructions to wash the PRE-FILTER - being sure to tap gently and wipe off any visible water droplets.
RESET TIMERS
To reset the PRE-FILTER timer, press and hold the RESET button until the PRE-FILTER LED turns off. (1 to 2 seconds). To reset the Collection Cell timer, press and hold the RESET button until the COLLECTION CELL LED’s turn off. (4 to 5 seconds). In a communicating system, the filter reset timers can also be reset at the communicating comfort control. If two air cleaners are connected on the same system, reset all timers on both air cleaners at the same time to the same settings. The comfort control will only report one air cleaner timer and this methodology will allow the air cleaners to remain on the same cleaning schedule.
CLEANING THE FIELD CHARGER
1. Turn off the Air Cleaner and remove the Power Door.
2. Bend the FIELD CHARGER metal locking tabs down against the case.
3. Remove the FIELD CHARGER from the case. Lay the FIELD CHARGER on a secured flat surface.
!
CAUTION
FIELD CHARGER PINS ARE SHARP. DO NOT BEND FIELD CHARGER PINS. WEAR APPROPRI­ATE GLOVES WHEN HANDLING THE FIELD CHARGER. FAILURE TO HANDLE FIELD CHARGER PINS PROPERLY MAY RESULT IN MINOR TO MODERATE INJURY.
4. Wipe down the faceplate of the FIELD CHARGER with a dry shop towel or use a vacuum cleaner. Do not disas­semble the FIELD CHARGER.
5. Push a block of styrofoam down over the FIELD CHARGER Pin.
s
Amber Light
Plug Power Cord in here
18 Numbers in [brackets] are for 50 Hz international systems. EAC-SF-13
Page 19
Service Facts
6. Rotate the styrofoam block on the FIELD CHARGER Pin.
d
7. Use the styrofoam block to clean the faceplate opening edges.
8. Repeat steps 5, 6 and 7 for each FIELD CHARGER Pin.
9. Put FIELD CHARGER back into the Air Cleaner frame and bend the locking tabs back up against the FIELD CHARGER.
TESTING THE POWER DOOR
HIGH VOLTAGE POWER SUPPLY
Tools Required: A High voltage Probe and a compatible Volt Meter or a Screwdriver, Jumper Wire with Alligator Clips on each end, tape and dry paper.
TESTING WITH A HIGH VOLTAGE PROBE
1. Turn off the Air Cleaner and remove the Power Door.
2. Form a piece of wire that will go through the interlock switch opening and depress the interlock switch blade. Tape it in place.
If all three are NOT on, press the POWER button three times and then press the RESET button until you get all three
Red LEDs on. Now press and hold both the POWER button and the RESET button for five seconds then release these buttons to leave the SET-UP mode. The first Green LED should be on and then start flashing after the time delay to 'on' has expired. The Air Cleaner has to have a call for operation for the first Green LED to flash on and off. (A call for indoor blower or heat is a call for operation.)
4. When the first Green LED is flashing on and off connect the High Voltage Probe and compatible volt/ohm meter per their manufacturers' instructions.
5. Touch the tip of the High Voltage Probe to the Power Door High Voltage terminal and read the volt meter.
6. If the voltage read during this test is 9.6 KV + or – 600 volts the Power Door is working correctly. Replace Power Door with a new Power Door if the high voltage is not correct.
7. Turn off the Air Cleaner by pushing the POWER
8. Remove the wire and tape used to defeat the interlock switch.
9. Replace Power Door.
TESTING WITH A SCREWDRIVER, A JUMPER WIRE AND A DRY PIECE OF PAPER
1. Turn off the Air Cleaner and remove the Power Door.
2. Form a piece of wire that will go through the interlock switch opening and depress the interlock switch. Tape it in place. See Figure 24.
3. Tape a piece of paper to a screwdriver blade with ½ inch of the paper sticking out in front of the blade. Do not put the tape over the end of the screwdriver blade.
button.
f
Interlock Switch Access
!
WARNING
High Voltage is present for this test.
3. Turn on the Air Cleaner, and then enter the SET-UP mode
by pushing and holding both the POWER button and the RESET button for 5 [6] seconds. The bar graph display will show the Air Cleaners current settings ( see SET-UP MODE instructions). The top three Red LEDs should be on for this test. The three Red LEDs being on indicates that the Air Cleaner Power level setting is set at the 9.6 KV position.
g
!
CAUTION
Do not expose the filter to UV light. UV light can cause the plastic materials to deteriorate which may lead to filter damage.
4. Connect the jumper wire using the alligator clips to the screwdriver and the Power Door metal frame as illustrated in Figure 26.
!
WARNING
High Voltage is present for this test.
5. Turn on the Air Cleaner, and then enter the SET-UP mode by pushing and holding both the POWER
RESET button for 5 [6] seconds. The bar graph display will show the Air Cleaners current settings ( see SET-UP MODE
button and the
EAC-SF-13 Numbers in [brackets] are for 50 Hz international systems. 19
Page 20
Service Facts
*FD145CLFR000D
0.06
0.10
0.16
0.23
0.30
*FD175CLFR000D
0.05
0.08
0.12
0.17
0.22
0.28
0.34
*FD210CLFR000D
0.04
0.06
0.09
0.12
0.15
0.20
0.24
0.29
0.34
*FD245CLFR000D
0.03
0.04
0.06
0.09
0.12
0.15
0.19
0.22
0.26
*FD14DCLFR000D
0.09
0.16
0.24
0.34
0.46
*FD17DCLFR000D
0.07
0.11
0.18
0.25
0.33
0.42
*FD21DCLFR000D
0.05
0.09
0.13
0.18
0.23
0.29
0.37
*FD24DCLFR000D
0.04
0.07
0.11
0.14
0.19
0.24
0.30
0.36
0.43
*FD175CLAH000D
0.07
0.11
0.18
0.25
0.33
TFD215CLAH005D
TFD235CLAH005D
instructions). The top three Red LEDs should be on for this test. The three Red LEDs being on indicates that the Air Cleaner Power level setting is set at the Maximum / 9.6 KV
position. If all three are NOT on, press the POWER three times and then press the RESET button until you get all three Red LEDs on. Now press and hold both the POWER
button and the RESET button for 5 [6] seconds then release these buttons to exit the SET-UP mode. The first Green LED will be on and it will start flashing after the first 10 [12] minutes of indoor fan operation. The Air Cleaner has to have a call for operation for the first Green LED to flash on and off. (A call for indoor blower or heat is a call for operation.)
6. When the first Green LED is flashing on and off, take the screwdriver by the plastic handle and move the blade end of the screwdriver near the Power Door High Voltage termi­nal. When the end of the paper touches the High Voltage terminal the High Voltage should arc across the paper. When the arc occurs, the High Voltage Supply will shut down and stay off for one minute.
7. Turn off the Air Cleaner by pushing the POWER
8. Remove the wire and tape used to defeat the interlock switch.
9. If the arc occurred when the end of the paper was near or touching the Power Door High Voltage terminal during this test, the Power Door assembly is OK. If no arc occurred replace Power Door with a new Power Door.
button
button.
h
PRESSURE DROP
PRESSURE DROP AT SPECIFIC AIRFLOW PER MODEL
400 CFM 600 CFM 800 CFM 1000 CFM 1200 CFM 1400 CFM 1600 CFM 1800 CFM 2000 CFM
*FD215CLAH000D
*FD235CLAH000D
*FD260CLAH000D TFD260CLAH005D
* May be "A" or "T"
0.04 0.08 0.12 0.17 0.24
0.06 0.09 0.13 0.18 0.23 0.29 0.35
0.04 0.07 0.10 0.14 0.18 0.23 0.28 0.34 0.39
20 Numbers in [brackets] are for 50 Hz international systems. EAC-SF-13
Page 21
/
gag
/
t
s
/
&
/
TROUBLESHOOTING
Service Indications Service Checks Indoor Blower ON Air Cleaner First Green LED OFF
Indoor Blower ON Air Cleaner First Green LED ON, Not Flashing 1. Air Cleaner is in the 10 [12] minute dry cycle.
Service Facts
1. Check that the Power Door is installed correctly and the latches closed. The actuator tab must en
e the door safety switch.
2. Check the air cleaner power/control cable.
3. Push the power button once.
4. Check for 24 Volts AC at the Air Cleaner power plug.
2. No call for Air Cleaner Operation due to no 24 Volts AC call going to G / W or request through the data line from the (Communicating System) Furnace or Air Handler.
3. There is no High Voltage being provided to the Field Charger or the Collection Cells. Inspec the Field Charger assembly and Collection Cell for any foreign material that may be lodged in them. Clean as needed, reassemble and test.
4. If the Air Cleaner still does not work, remove Power Door from the Air Cleaner housing.
!
WARNING
HIGH VOLTAGE WILL BE PRESENT FOR THE REMAINDER OF THIS TEST.
5. With the indoor blower running and the power cord plugged into the Air Cleaner, use a tool to activate the Power Door interlock switch. Push the power button once. The first Green LED should come on and after the time delay it should start to
Indoor Blower ON Three Yellow LEDs Flashing Collection Cells. Inspect for foreign material,
Indoor Blower ON Three Red LEDs Flashing See Service Facts page 11 for fault code information.
flash. If the first Green LED does not start to flash the fault
is with the Power Door.
1. Remove the Power Door, Field Charger
clean if needed.
1. This indicates service is needed.
EAC-SF-13 Numbers in [brackets] are for 50 Hz international systems. 21
Page 22
Service Facts
COMPONENT FAILURE EVALUATION
Component Failure Evaluation
This whole house air cleaner can
be installed either as part of a
communicating system or as part
of a traditional 24 volt system
Is the amber light
above the power
YES
cord connection on
continuously
NO
YES
Go to 24 Volt
troubleshooting
flow chart
GREEN
BROWN
BLACK
WHITE
BLUE
RED
24VAC Mode
Intended
Correct control
wire problem
NO
Return
COM Mode
Intended
NO
NO
YES
Is the amber light
blinking the system
device count or a fast
flash
YES
Go to
Communicating
Mode
troubleshooting
flow chart
Correct control
wire problem
Data Line
BROWN
RED
BLUE
Unused GREEN
BROWN
D
BLACK
GRD
WHITE
Unused
RED
BLUE
GREEN
BROWN
BLACK
WHITE
BLUE
GREEN
BROWN
BLACK
WHITE
RED
22 Numbers in [brackets] are for 50 Hz international systems. EAC-SF-13
Page 23
Component Failure Evaluation in 24 Volt Mode
Service Facts
Door panel has
yellow or red
flashing LEDs
Power the air
cleaner with
24VAC and
establish a “G”
call from T-Stat
Door operates
correctly
Turn power off,
Remove the power
door, install the
collection cells, and re-
install the power door
Remove the power door,
collection cells,
and field charger
Bypass the 10 minute
time delay (This is
done by entering and
exiting the set-up
Does Green Led #1 begin to flash slowly
Power the air
cleaner with
24VAC and
establish a “G”
call from T-Stat
mode)
NoYes
Bypass the 10 minute
time delay (This is
done by entering and
exiting the set-up
mode)
Reinstall power
door to air cleaner
Wait 10 seconds
Replace the
power door
Wait 10 seconds
The power door
and collection
cells operate
correctly
Turn power off,
Remove the power
door, install the field
charger, and re-install
the power door
Air cleaner is
operating
correctly
EAC-SF-13 Numbers in [brackets] are for 50 Hz international systems. 23
Yes No
Power the air
cleaner with
24VAC and
establish a “G”
call from T-Stat
Yes No
Does Green Led #1 begin to flash slowly
Bypass the 10 minute
time delay (This is
done by entering and
exiting the set-up
mode)
Does Green Led #1
begin to flash slowly
Replace both collection cells
Wait 10 seconds
Replace the field
charger
Page 24
Service Facts
Component Failure Evaluation in Communicating Mode
NO
The user inferface on
the door panel has
yellow or red flashing
LEDs other then the
COM FAULT
YES
Use 24 Volt Mode
Troubleshooting
Flow Chart
User interface on the door
panel is displaying a COM.
Yellow-2, Yellow-4 and Red-3
FAULT
LED flashing
NO
Comfort controll is
displaying a ERROR
CODE 91
Air-cleaner can not generate a ERROR
CODE 91 on the comfort
control, fault is with other
YES
unit.
YES
Is the COM LED flashing a device
count (one flash for
each unit on the COM
BUS)
YES
NO
NO
Is the COM LED
flashing fast
NO
If COM light is on
continues the unit is
wired in the 24 Volt
Mode. Rewire in
COM Mode
YES
Active communicating fault.
Check for 12-13 voltage DC
between Brown and Blue
wires at the air-cleaner
connection plug Refer to the
Interactive Troubleshoot
Guide for Communicating
Systems to identify source of
COM Fault
Does the G1 LED blink slowly with a call for indoor fan
Clear fault log
Trane 6200 Troup Highway Tyler, TX 75707
For more information contact your local dealer (distributor)
YES
Air Cleaner
operating correctly.
NO
Replace door
Like the furnace and air-handler's
users interfaces the air-cleaner stores
fault codes. Check air-cleaner COM.
light for device count (one blink for each communicating device on the
COM. bus) If device count is present
ensure air-cleaner green light blinks
slow with indoor blower operation.
Clear fault log
07/11