ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES
IMPORTANT — This Document is customer property and is to remain with this unit.
Please return to service information pack upon completion of work.
*UX2*DX2
UPFLOW
UPFLOW / HORIZONTAL LEFT
DOWNFLOW
DOWNFLOW / HORIZONTAL RIGHT
A341624P03
Installer’s Guide
▲
▲
▲
SAFETY SECTION
The following safety practices and precautions must be
followed during the installation, servicing, and operation of
this furnace.
1. Use only with the type of gas approved for this furnace.
Refer to the furnace rating plate.
2. Install this furnace only in a location and position as
specified in “Location and Clearances” (page 3), of these
instructions.
3. Provide adequate combustion and ventilation air to the
furnace space as specified in “Air for Combustion and
Ventilation” (pages 7-8), of these instructions.
4. Combustion products must be discharged outdoors.
Connect this furnace to an approved vent system only, as
specified in the “Venting” section (pages 13-23), of these
instructions.
5. Never test for gas leaks with an open flame. Use a
commercially available soap solution made specifically
for the detection of leaks to check all connections, as
specified in “Gas Piping” (page 31), of these instructions.
6. Always install the furnace to operate within the furnace’s
intended temperature-rise range with a duct system
which has an external static pressure within the allowable range, as specified on the unit rating plate. Airflow
with temperature rise for cfm versus static is shown in
the Service Facts accompanying this furnace.
7. When a furnace is installed so that supply ducts carry air
circulated by the furnace to areas outside the space
containing the furnace, the return air shall also be
handled by a duct(s) sealed to the furnace casing and
terminating outside the space containing the furnace.
8. A gas-fired furnace for installation in a residential
garage must be installed as specified in “Location and
Clearances” section (page 3), of these instructions.
9. The furnace may be used for temporary heating of
buildings or structures under construction only when the
following conditions have been met:
a. The furnace venting system must be complete and
installed per manufacturer’s instructions.
b. The furnace is controlled only by a room thermostat
(no field jumpers).
c. The furnace return air duct must be complete and
sealed to the furnace and clean air filters are in place.
d. The furnace input rate and temperature rise must be
verified to be within nameplate marking.
e. 100% of the furnace combustion air requirement must
come from outside the structure.
f. The furnace return air temperature range is between
55 and 80 degrees Fahrenheit.
g. Clean the furnace, duct work, and components upon
substantial completion of the construction process,
and verify furnace operating conditions including
ignition, input rate, temperature rise and venting,
according to the manufacturer’s instructions.
10. This product must be gas piped by a Licensed Plumber or
Gas Fitter in the Commonwealth of Massachusetts.
!
CAUTION
To prevent shortening its service life, the furnace should
not be used as a “Construction Heater” during the finishing
phases of construction until the requirements listed in item
9, a-g of the safety section of this publication have been
met. Condensate in the presence of chlorides and fluorides from paint, varnish, stains, adhesives, cleaning
compounds, and cement create a corrosive condition which
may cause rapid deterioration of the heat exchanger.
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each
appliance connected to the venting system being
placed into operation could result in carbon monoxide
poisoning or death.
The following steps shall be followed for each appliance
connected to the venting system being placed into
operation, while all other appliances connected to the
venting system are not in operation:
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and
horizontal pitch, as required in the National Fuel Gas
Code, ANSI Z223.1/NFPA 54 or the CAN/CGA B149
Installation Codes and these instructions. Determine
that there is no blockage or restriction, leakage,
corrosion and other deficiencies which could cause an
unsafe condition.
3. As far as practical, close all building doors and
windows and all doors between the space in which the
appliance(s) connected to the venting system are
located and other deficiencies which could cause an
unsafe condition.
4. Close fireplace dampers.
5. Turn on clothes dryers and any appliance not
connected to the venting system. Turn on any exhaust
fans, such as range hoods and bathroom exhausts, so
they are operating at maximum speed. Do not operate
a summer exhaust fan.
6. Follow the lighting instructions. Place the appliance
being inspected into operation. Adjust the thermostat
so appliance is operating continuously.
7. If improper venting is observed during any of the above
tests, the venting system must be corrected in
accordance with the National Fuel Gas Code,
ANSI Z221.1/NFPA 54 and/or CAN/CGA B149
Installation Codes.
8. After it has been determined that each appliance
connected to the venting system properly vents where
tested as outlined above, return doors, windows,
exhaust fans, fireplace dampers and any other gas-fired
burning appliance to their previous conditions of use.
Safety signal words are used to designate a degree or level
of seriousness associated with a particular hazard. The
signal words for safety markings are DANGER, WARNING,
and CAUTION.
a. DANGER indicates an imminently hazardous situation
which, if not avoided, will result in death or serious injury.
This signal word is limited to the most extreme situations.
b. WARNING indicates a potentially hazardous situation
which, if not avoided, could result in death or serious injury.
c. CAUTION indicates a potentially hazardous situation
which, if not avoided, may result in minor or moderate
!
WARNING
FIRE OR EXPLOSION HAZARD
Failure to follow the safety warnings exactly could result in
serious injury, death or property damage.
Improper servicing could result in dangerous operation,
serious injury, death, or property damage.
The manufacturer assumes no responsibility for equipment
installed in violation of any code or regulation.
It is recommended that Manual J of the Air Conditioning
Contractors Association (ACCA) or A.R.I. 230 be followed in
estimating heating requirements. When estimating heating
requirements for installation at Altitudes above 2000 ft.,
remember the gas input must be reduced (See GAS INPUT
ADJUSTMENT).
Material in this shipment has been inspected at the
factory and released to the transportation agency
without known damage. Inspect exterior of carton for
evidence of rough handling in shipment. Unpack
carefully after moving equipment to approximate
location. If damage to contents is found, report the
damage immediately to the delivering agency.
Codes and local utility requirements governing the installation of gas fired equipment, wiring, plumbing, and flue
connections must be adhered to. In the absence of local codes,
the installation must conform with latest edition of the
National Fuel Gas Code ANSI Z223.1 • National Installation
Code, CAN/CGA B149.1. The latest code may be obtained
from the American Gas Association Laboratories, 400 N.
Capitol St. NW, Washington D.C. 20001. 1-800-699-9277 or
www.aga.org
These furnaces have been classified as CATEGORY IV
furnaces in accordance with latest edition of ANSI Z21.47
standards • CAN/CGA 2.3. Category IV furnaces operate
with positive vent static pressure and with a flue loss less
than 17 percent. These conditions require special venting
systems, which must be gas tight and water tight. These
Category IV Direct Vent furnaces are approved for installation in Manufactured/Mobile housing when used with
BAYMFGH001A.
LOCATION AND CLEARANCES
The location of the furnace is normally selected by the
architect, the builder, or the installer. However, before the
furnace is moved into place, be sure to consider the following
requirements:
1. Is the location selected as near the chimney or vent and
as centralized for heat distribution as practical?
2. Do all clearances between the furnace and enclosure
equal or exceed the minimums stated in Clearance Table
on the Outline Drawings.
3. Is there sufficient space for servicing the furnace and
other equipment? A minimum of 24 inches front accessibility to the furnace must be provided. Any access door
or panel must permit removal of the largest component.
4. Are there at least 3 inches of clearance between the
furnace combustion air openings in the front panel and
any closed panel or door provided?
5. Are the ventilation and combustion air openings large
enough and will they remain unobstructed? If outside
air is used, are the openings set above the highest snow
accumulation level? (See the Air for Combustion and
Ventilation section.)
6. Allow sufficient height in supply plenum above the
furnace to provide for cooling coil installation, if the
cooling coil is not installed at the time of this furnace
installation.
7. A furnace shall be installed so electrical components are
protected from water.
8. If the furnace is installed in a residential garage, it
must be installed so that the burners, and the ignition
Contents
Installation Instructions3
General3
Location and Clearances3
Outline Drawings4-5
Upflow Installation6
Downflow Installations6
Air For Combustion and Ventilation7
Duct Connections8
Return Air Filters9
General Venting13
Venting Materials14
Vent Tables16-22
Horizontal Venting Through Wall18
Venting Through the Roof20
Venting Routed Through a Masonry Chimney20
Downward Venting22
Condensate Drain Instructions24
Field Wiring Diagrams26-29
Electrical Connections29
Gas Piping31
Combustion and Input Check31
High Altitude Derate33
Start-up and Adjustment34
Preliminary Inspections34
Lighting Instructions34
Sequence of Operation34
Control and Safety Switch Adjustments35
Abnormal Conditions36
IFC Error Flash Codes37
Fault Code Recovery37
source are located not less than 18 inches above the floor
and the furnace must be located or protected to avoid
physical damage from vehicles.
IMPORTANT:
The furnace must be installed level. The only allowable variation
would be slightly to the left and/or forward in upflow installations
or slightly toward the front in horizontal installations. This is
necessary for proper condensate drainage.
!
CAUTION
Do not install the furnace in a corrosive or contaminated
atmosphere. Failure to follow this warning could result in
early equipment failure.
!
WARNING
Do not install the furnace directly on carpeting, tile or other
combustible material other than wood flooring. For vertical
downflow application, subbase (BAYBASE205) must be
used between the furnace and combustible flooring. When
the downflow furnace is installed vertically with a cased
coil, a subbase is not required.
2. Diameter of Vent PIpe may be limited to 2-1/2" or 3" on some
models at different altitudes. Refer to the Vent Length Table for
proper application.
18-CD19D8-185
Installer’s Guide
From Dwg. 21C341885 Rev. 1
*DX2 DOWNFLOW / HORIZONTAL OUTLINE DRAWING
(ALL DIMENSIONS ARE IN INCHES)
Model
(See Note 1)
DIM "A" DIM "B" DIM "C" DIM "D"
*DX2B060A9362A
*DX2B080A9422A
17-1/2"2-1/4"16-1/4"16"
*DX2C100A9482A21"2-1/2"19-3/4"19-1/2"
*DX2D120A9602A24-1/2" 2-15/16" 23-1/4"23"
* Prefix May Be "A" or "T"Notes:
1. Diameter of Vent Pipe may be limited
to 2-1/2" or 3" on some models at
different altitudes. Refer to the Vent
Length Table for proper application.
Installer’s Guide
▲
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
UPFLOW INSTALLATION
Standoffs and screws (See Figure 1) are included with the
cased coils for attachment to the furnace. There are clearance alignment holes near the bottom of the coil wrapper.
Drill screws are used to engage the furnace top flanges. The
standoff is inserted into the cabinet alignment hole. The drill
screws are inserted through the standoffs then screwed into
the furnace flange. The coil is always placed downstream of
the furnace airflow.
1
CASED
UPFLOW
FURNACE
COIL
STANDOFFS (4)
STANDOFFS
(BOTH SIDES)
SCREWS
(BOTH SIDES)
DOWNFLOW INSTALLATIONS
2
!
WARNING
Do not install the furnace directly on carpeting, tile or other
combustible material other than wood flooring. For
vertical downflow application, subbase (BAYBASE205)
must be used between the furnace and combustible
flooring. When the downflow furnace is installed vertically
with a cased coil, a subbase is not required.
The coil and furnace must be fully supported when used in
the horizontal position. It is always recommended that an
auxiliary drain pan be installed under a horizontally installed evaporator coil or 90% gas furnace. Connect the
auxiliary drain line to a separate drain line (no trap is
needed in this line).
Three brackets (with screws) are included with downflow
furnaces for installation to stabilize and secure the furnace
and TXC cased coil in the horizontal position. See Figure 4.
4
CASED COIL CONNECTION
BRACKET FOR DOWNFLOW
FURNACE IN HORIZONTAL
DOWNFLOW ONLY
IMPORTANT:
The 2/4TXC cased coil must be placed downstream of the
furnace. In horizontal installations, the apex of the coil
may point either toward or away from the furnace. See
the 2/4TXC coil Installer's Guide for more details.
The cased coil is secured to the furnace and both the furnace
and the cased coil must be properly supported. The brackets
mount using the rear screws on the coil case and use the
screws provided to secure the bracket to the furnace. The
remaining bracket is placed as close to center as possible
(horizontally) between the coil case front and the furnace
bottom channel (for downflow/horizontal furnace). Use four of
the screws provided to secure the bracket. The upflow furnace,
converted to horizontal, aligns and attaches the TXC coil as in
Figure 1. However, the coil requires additional support.
The furnace may be installed in an attic or crawl space in the
horizontal position by placing the furnace on the left side (as
viewed from the front in the vertical position). The horizontal
furnace installation in an attic should be on a service platform large enough to allow for proper clearances on all sides
and service access to the front of the furnace (See Figure 5 &
Clearance Tables, pages 4-5). Line contact is only permissible between lines formed by intersections of the top and two
sides of the furnace casing and building joists, studs, or
framing.
The furnace may be placed horizontally in a crawl space on a
pad or other noncombustible material which will raise the
unit for sufficient protection from moisture.
5
UPFLOW/
HORIZONTAL
SHOWN WITH
DIRECT VENT
6
50 CU. FT. OR MORE
UNCONFINED
The furnace must be supported at both ends and the
middle when installed horizontally. The furnace must
also be elevated approximately 4-6 inches to allow
clearance for the condensate drain to exit the cabinet in
the horizontal position.
The horizontal furnace may also be suspended from the joists
using 3/8" all-thread rods with pieces of angle iron underneath the furnace to form a hanging rack at both ends and
the midpoint. The rods need to be of sufficient length to
allow for proper clearances from combustible materials. The
angle iron needs to be at least 32" in length to allow for
access to service panels.
AIR FOR COMBUSTION AND VENTILATION
If these furnaces are installed in a nondirect vent capacity
then the adequate flow of combustion and ventilating air
must not be obstructed from reaching the furnace. Air
openings provided for combustion air must be kept free of
obstructions which restrict the flow of air. Airflow restrictions affect the efficiency and safe operation of the furnace.
Keep this in mind should you choose to remodel or change
the area which contains your furnace. Furnaces must have a
free flow of air for proper performance.
Provisions for combustion and ventilation air shall be made
in accordance with latest edition of Section 5.3, Air for
Combustion and Ventilation, of the National Fuel Gas Code,
ANSI Z223.1 — CAN/CGA B149.1 or applicable provisions of
the local building codes. Special conditions created by
mechanical exhausting of air and fireplaces must be considered to avoid unsatisfactory furnace operation.
OUTSIDE AIR IS RECOMMENDED
The use of indoor air for most applications is acceptable,
unless there is the presence of corrosive chemicals orcontamination. Certain types of installation will require
the use of outside air for combustion.
The following types of installations will require use of
OUTDOOR AIR for combustion, due to chemical exposures:
* Commercial buildings
* Buildings with indoor pools
* Furnaces installed in “confined” laundry rooms
* Furnaces installed in “confined” hobby or craft rooms
* Furnaces installed near chemical storage areas.
Exposure to the following substances in the combustion air
supply will also require OUTDOOR AIR for combustion:
* Permanent wave solutions
* Chlorinated waxes and cleaners
* Chlorine based swimming pool chemicals
* Water softening chemicals
* Deicing salts or chemicals
* Carbon Tetrachloride
* Halogen type refrigerants
* Cleaning solvents (such as perchloroethylene)
* Printing inks, paint removers, varnish, etc.
* Hydrochloric acid
* Cements and glues
* Antistatic fabric softeners for clothes dryers
* Masonry acid washing materials
Installer’s Guide
Furnace locations may be in a “confined space” or an
“unconfined space”.
Unconfined space is defined in Figure 6. These spaces may
have adequate air by infiltration to provide air for combustion
and ventilation. Buildings with tight construction (for
example, weather stripping, heavily insulated, caulked, vapor
barrier, etc.), may need additional air to be provided as
described for confined space.
Confined spaces are installations with less than 50 cu. ft. of
space per 1000 BTU/hr input from all equipment installed.
Air for combustion and ventilation requirements can be
supplied from inside the building as in Figure 8 or from the
outdoors, as in Figure 9.
TABLE 2
MINIMUM AREA IN SQUARE FEET
FOR UNCONFINED SPACE INSTALLATIONS
FURNACE
MAXIMUM BTUH
INPUT RATING
60,000
80,000
100,000
120,000
7
CONFINED
SPACE
1. All air from inside the building as in Figure 8: The
confined space shall be provided with two permanent
openings communicating directly with an additional
room(s) of sufficient volume so that the combined volume
of all spaces meets the criteria for an unconfined space.
The total input of all gas utilization equipment installed
in the combined space shall be considered in making this
determination. Refer to Table 2 for minimum open areas
requirements.
2.
All air from outdoors as in Figure 9: The confined space
shall be provided with two permanent openings, one
commencing within 12 inches of the top and one commencing within 12 inches of the bottom of the enclosure.
The openings shall communicate directly, or by ducts,
with the outdoors or spaces (crawl or attic) that freely
communicate with the outdoors. Refer to Table 3, for
minimum open areas requirements.
MINIMUM FREE AREA IN SQUARE INCHES
EACH OPENING (FURNACE ONLY)
Furnace
Maximum
BTUH/INPUT
Rating
60,000
80,000
100,000
120,000
WITH 8 FT. CEILING
MINIMUM AREA IN SQUARE FEET
OF UNCONFINED SPACE
375
500
625
875
TABLE 3
Air
From
Inside
100
100
100
120
Air From Outside
Vertical
Duct
15
20
25
30
Horizontal
Duct
30
40
50
60
18-CD19D8-187
Installer’s Guide
8
9
DUCT CONNECTIONS
Air duct systems should be installed in accordance with
standards for air conditioning systems, National Fire Protection Association Pamphlet No. 90. They should be sized in
accordance with ACCA Manual D or whichever is applicable.
Central furnaces, when used in connection with cooling units,
shall be installed in parallel or on the upstream side of the
cooling coil to avoid condensation in the heat exchanger. With
a parallel flow arrangement, the dampers or other means used
to control flow of air shall be adequate to prevent chilled air
from entering the furnace, and if manually operated, must be
equipped with means to prevent operation of either unit
unless the damper is in full heat or cool position.
On any job, flexible connections of nonflammable material may
be used for return air and discharge connections to prevent
transmission of vibration. Though these units have been
specifically designed for quiet, vibration free operation, air ducts
can act as sounding boards and could, if poorly installed,
amplify the slightest vibration to the annoyance level.
When the furnace is located in a utility room adjacent to the
living area, the system should be carefully designed with
returns to minimize noise transmission through the return
air grille. Although these furnaces are designed with large
blowers operating at moderate speeds, any blower moving a
high volume of air will produce audible noise which could be
objectionable when the unit is located very close to a living
area. It is often advisable to route the return air ducts under
the floor or through the attic. Such design permits the
installation of air return remote from the living area (i.e.
central hall).
When the furnace is installed so that the supply ducts carry
air circulated by the furnace to areas outside the space
containing the furnace, the return air shall also be handled
by a duct(s) sealed to the furnace and terminating outside
the space containing the furnace.
RETURN AIR DUCT CONNECTION
NOTE:
On upflow 5 or 6 ton airflow models where the airflow
requirement exceeds 1800 CFM - Models will require
return air openings and filters on: (1) both sides; or (2)
one side and the bottom; or (3) just the bottom.
818-CD19D8-18
All return air duct systems should provide for installation of
return air filters.
1. Determine the appropriate position to set the furnace in
order to connect to the existing supply and return
ductwork.
2. For side return installations on upflow models, remove
the insulation around the opening in the blower
compartment.
3. The side panels of the upflow furnace include locating
notches that are used as guides for cutting an opening
for return air, refer to Figure 10 and the outline
drawing on page 4 for duct connection dimensions for
various furnaces.
Installer’s Guide
▲
▲
4. If a 3/4" flange is to be used for attaching the air inlet
duct, add to cut where indicated by dashed lines in
Figure 11. Cut corners diagonally and bend outward to
form flange.
5. If flanges are not required, and a filter frame is installed,
cut along knockout guidelines.
6. Upflow Furnaces: Use the optional filter rack on either
side or on the bottom if the filter is to be used within the
furnace cabinet.
When the upflow furnace is installed in the horizontal
right or left application and a return duct is attached to
the top side as shown in Figure 10, install the filter in a
remote location.
!
WARNING
Do not install the filter in the return duct directly above the
furnace in horizontal applications. Install the filter remotely.
Installing the filter directly above the furnace in horizontal
applications may cause property damage, serious injury or
death.
!
WARNING
TO PREVENT INJURY OR DEATH DUE TO CONTACT
WITH MOVING PARTS, TURN THE POWER TO THE
FURNACE OFF BEFORE SERVICING FILTERS.
Do not install the filter in the return duct directly above
the furnace in horizontal applications.
When the upflow furnace is installed in the horizontal
right or left application and a close coupled (less than
36") return duct is attached to the bottom side of the
furnace as shown in Figure 10, securely attach a 1/2"
mesh metal hardware cloth protective screen to the
inside bottom of the filter grill to prevent personal
injury from contacting moving parts when reaching
into the return opening to replace the filter.
REMOVE FILTER FROM UPFLOW
FURNACE WHEN RETURN DUCT IS
ATTACHED TO FURNACE TOP SIDE
(HORIZONTAL LEFT OR RIGHT
APPLICATIONS) AS SHOWN.
FILTER
0
Close coupled (less than 36") return (filter directly
beneath bottom side return) is not recommended due to
noise considerations.
Downflow Furnaces: Brackets are factory supplied to
mount filters in the return air duct work.
7. Connect the duct work to the furnace. See Outline
Drawing (pages 4&5) for supply and return duct size and
location. Flexible duct connectors are recommended to
connect both supply and return air ducts to the furnace.
If only the front of the furnace is accessible, it is
recommended that both supply and return air plenums
are removable.
8. When replacing a furnace, old duct work should be
cleaned out. Thin cloths should be placed over the
registers and the furnace fan should be run for 10 minutes. Don’t forget to remove the cloths before you start
the furnace.
Return Air Filters
(Filter and filter rack are not supplied with
unit)
TYPICAL UPFLOW RETURN AIR FILTER INSTALLATIONS
These furnaces require high velocity type air filters. The
optional filters may be located within the furnace blower
compartment for UPFLOW furnaces in either a BOTTOM or
SIDE (left side or right side) return air inlet. Some optional
filters may need to be trimmed for side or bottom filter use.
NOTE:
On upflow 5 or 6 ton airflow models where the airflow
requirement exceeds 1800 CFM - Models will require
return air openings and filters on: (1) both sides; or (2)
one side and the bottom; or (3) just the bottom.
q
LOCATING
NOTCHES
PROVIDED
FOR SIDE
RETURN
CUTOUT
SEE OUTLINE DRAWING
*
*
*
*
*
CUT OUT
FOR
SIDE
FILTER
FRONT
of Furnace
Close coupled (less than 36")
return (filter directly beneath bottom
side return) not recommended due to
noise considerations. If used, securely
attach 1/2" mesh metal hardware cloth
protective screen to the inside bottom of
filter grill.
18-CD19D8-189
The furnace and the blower filter rack installation can be seen
in Figures 12 & 13.
The optional furnace filter in the bottom or side configuration
can be removed by simply turning the two latches on the
blower door and tilting the door forward.
The filter rails are spring loaded for automatic adjustment to
allow standard size, locally obtainable replacement filters.
The filter rack itself slides to adjust to the required width
needed for bottom or side return.
Installer’s Guide
TABLE 4
UPFLOW FURNACE RETURN AIR FILTERS
CABINET
WIDTH
14-1/2"114" X 25" X 1"17-1/2" X 25" X 1"
17-1/2"117" X 25" X 1"17-1/2" X 25" X 1"
21"120" X 25" X 1"17-1/2" X 25" X 1"
24-1/2"124" X 25" X 1"17-1/2" X 25" X 1"
**NOTE: For upflow 5 ton airflow models where the airflow
requirement exceeds 1800 CFM - Models will require return air
openings and filters on: (1) both sides, or (2) one side and the
bottom, or (3) just on the bottom
QTY*
CABINET
BOTTOM FILTER
CABINET
SIDE FILTER
w
Airflow
NOTE: The narrow 14.5" width furnace cabinet prevents use
of the filter rack for right side return. Pre-drill clearance
holes and then attach filter clips with the screws provided.
The filter clip with the leaf spring mounts in the rear of the
cabinet
OPTIONAL FILTER RACK INSTALLATION FOR BOTTOM
RETURN
With the filter removed, the filter rack is compressed and
then inserted into the bottom of the furnace. The retaining
screw/pin on each side inserts into engagement holes at the
bottom of the furnace cabinet side. See Figures 13, 14 & 16.
NOTE: Remove the bottom front channel to install the filter
rack in the 14-1/2" width cabinet furnaces.
t
Blower Deck
Engagement
Hole
r
e
Airflow
BOTTOM FILTER RACK INSTALLATION
ENGAGEMENT
HOLE DETAIL
(Typical both sides
and blower deck)
y
Furnace
Cabinet
Side
Engagement Hole
For
Filter Rack
Installation With
Bottom Return
VIEW
Filter
Rack
Filter Rack
Retaining
Screw/Pin
Optional Filter Rack Accessory Kit
BAYRACK960A
1018-CD19D8-18
Installer’s Guide
Airflow
Airflow
TABLE 5
Cabinet Width Left Side BottomRight Side
14.5X
17.5XXX
21XXX
24.5XXX
1. UD060C/R936K0 has 10x7 blower which requires use of alternate
filter clips for left side filter. "K1" and later use the filter rack.
2. Remove bottom front channel to install or reposition filter rack.
X - All Models
OPTIONAL FILTER RACK INSTALLATION FOR SIDE
RETURN AIR ON UPFLOW FURNACES (Left or Right)
If side air return is desired, the following instructions should
be used:
a. Open or remove the blower door.
b. Leave the bottom panel in place. (Some models
require field supplied bottom panels.)
c. After the side cutout is made following the directions
in the “Return Air Duct Connections” section on
pages 8 and 9; compress the filter rack and reinstall in
the side of the furnace. Confirm that the upper
retaining pin/screw locks into the engagement hole in
the blower deck and the lower pin/screw rests against
the side of the bottom panel. See Figures 14, 15, &
17-20.
d. Install the furnace filter on the side. See Figures 14,
15, & 17-20.
u
Furnace
Cabinet
Side
1
BOTTOM ENGAGEMENT
X2Use Alternate Filter Clips Only
Filter Rack
Retaining
Screw/Pin
Filter
Rack
o
Typical Upflow Left Side Return Filter Rack Installation
p
SIDE
CUTOUT
RETAINING
PIN
(Both Sides)
SPRINGS
Airflow
FILTER
RACK
RAILS
Airflow
BOTTOM
PANEL
INSTALLED
SIDE
CUTOUT
RETAINING
PIN
(Both Sides)
SPRINGS
Engagement Hole
For
Installation With
Bottom Return
i
BLOWER
DECK
Furnace
Cabinet
Side
Filter Rack
Engagement Hole
For
Filter Rack
Installation With
Side
Return
Filter Rack
Retaining
Screw/Pin
Bottom Panel
Furnace
Blower
Deck
Filter
Rack
Assembly
BOTTOM
PAN EL
INSTALLED
Typical Upflow Right Side Return Filter Rack Installation
FILTER
RACK
RAILS
a
Airflow
Optional door kit
BAYFLTR206
Typical Horizontal Filter Installation
18-CD19D8-1811
Installer’s Guide
RETURN AIR FILTERS FOR UPFLOW FURNACE
IN HORIZONTAL CONFIGURATION
When the Upflow Furnace is installed in a horizontal configuration, the filter must never be installed inside or outside the
cabinet directly above the blower assembly. See Figure 11
(page 9). Remote filter grilles may be used for homeowner
convenience or the filters may be installed in the duct work
upstream of the furnace. See Figures 11 (page 9) and 21 (page
1. Determine the location to be used. The furnace cabinet
has dimples for location of the alternate furnace clips
(Side return only). Pre-drill clearance holes with a
3/16" drill. Bottom return holes are pre-drilled.
2. Install the clips in front and rear of the desired location
using the screws provided. The filter clip with the leaf
spring mounts in the rear of the cabinet. See Figure 22.
s
REAR
SIDE
CUT-OUT
TYPICAL DOWNFLOW FURNACE
RETURN AIR FILTER INSTALLATIONS
d
Airflow
f
ALTERNATE FILTER
CLIPS LOCATION
Optional horizontal filter conversion kits are BAYFLTR203
for 17 1/2" width cabinets, BAYFLTR204 for 21" width
cabinets, and BAYFLTR205 for 24" width cabinets. These
include filters and brackets necessary for horizontal filters.
In addition, optional door kit BAYFLTR206 is also available.
See Figures 21 and 24.
INSTALLING THE OPTIONAL FILTER
The filter may need to be cut to fit the unit depending on the
location of the return air filter.
A score line and the words “CUT HERE” are located on the
end of the filter. If your application requires cutting the filter,
do so as indicted by the score mark.
TABLE 6
UNIT
SIZE
RETURN AIR
BOTTOMSIDE
14-1/2"CUT ON LINE DO NOT CUT
17-1/2"DO NOT CUT DO NOT CUT
21"DO NOT CUT CUT ON LINE
24-1/2"DO NOT CUT CUT ON LINE
Airflow
Optional door kit
BAYFLTR206
Two high velocity type air filters are required for each downflow furnace. Downflow furnace filters must be located
outside the furnace cabinet. Typical installations are shown
in Figures 23 and 24. Tables 7 and 8 provide information for
installation of the filter retaining brackets shipped with
downflow furnaces.