The following safety practices and precautions must be
followed during the installation, servicing, and operation of this
furnace.
1. Use only with the type of gas approved for this furnace.
Refer to the furnace rating plate.
2. Install this furnace only in a location and position as
specified in “Location and Clearances” (page 3), of these
instructions.
3. Provide adequate combustion and ventilation air to the
furnace space as specified in “Air for Combustion and
Ventilation” (pages 8-9), of these instructions.
4. Combustion products must be discharged outdoors.
Connect this furnace to an approved vent system only, as
specified in the “Venting” section (pages 11-18), of these
instructions.
5. Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the
detection of leaks to check all connections, as specified in
“Gas Piping” (pages 22-23), of these
instructions.
6. Always install the furnace to operate within the furnace’s
intended temperature-rise range with a duct system which
has an external static pressure within the allowable range,
as specified on the unit rating plate. Airflow with temperature rise for cfm versus static is shown in the Service Facts
accompanying this furnace.
7. When a furnace is installed so that supply ducts carry air
circulated by the furnace to areas outside the space
containing the furnace, the return air shall also be handled
by a duct(s) sealed to the furnace casing and terminating
outside the space containing the furnace.
8. A gas-fired furnace for installation in a residential garage
must be installed as specified in “Location and Clearances” section (page 3), of these instructions.
9. The furnace may be used for temporary heating of buildings or structures under construction only when the
following conditions have been met:
a.The furnace venting system must be complete and
installed per manufacturers instructions.
b.The furnace is controlled only by a room thermostat
(no field jumpers).
c.The furnace return air duct must be complete and
sealed to the furnace and clean air filters are in place.
d.The furnace input rate and temperature rise must be
verified to be within nameplate marking.
e.100% of the furnace combustion air requirement must
come from outside the structure.
f.The furnace return air temperature range is between
55 and 80 degrees Farenhiet.
g.Clean the furnace, duct work, and components upon
substantial completion of the construction process, and
verify furnace operating conditions including ignition, input
rate, temperature rise and venting, according to the
manufacturer's instructions.
Safety signal words are used to designate a degree or level of
seriousness associated with a particular hazard. The signal
words for safety markings are DANGER, WARNING, and
CAUTION.
a. DANGER indicates an imminently hazardous situation
which, if not avoided, will result in death or serious injury.
This signal word is limited to the most extreme situations.
!
WARNING
▲
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each appliance
connected to the venting system being placed into operation
could result in carbon monoxide poisoning or death.
The following steps shall be followed for each appliance
connected to the venting system being placed into operation, while all other appliances connected to the venting
system are not in operation:
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and horizontal pitch, as required in the National Fuel Gas Code,
ANSI Z223.1/NFPA 54 or the CAN/CGA B149 Installation
Codes and these instructions. Determine that there is
no blockage or restriction, leakage, corrosion and other
deficiencies which could cause an unsafe condition.
3. As far as practical, close all building doors and windows
and all doors between the space in which the
appliance(s) connected to the venting system are
located and other deficiencies which could cause an
unsafe condition.
4. Close fireplace dampers.
5. Turn on clothes dryers and any appliance not connected
to the venting system. Turn on any exhaust fans, such
as range hoods and bathroom exhausts, so they are
operating at maximum speed. Do not operate a summer exhaust fan.
6. Follow the lighting instructions. Place the appliance
being inspected into operation. Adjust the thermostat
so appliance is operating continuously.
7. If improper venting is observed during any of the above
tests, the venting system must be corrected in accordance with the National Fuel Gas Code, ANSI Z221.1/
NFPA 54 and/or CAN/CGA B149 Installation Codes.
8. After it has been determined that each appliance
connected to the venting system properly vents where
tested as outlined above, return doors, windows,
exhaust fans, fireplace dampers and any other gasfired burning appliance to their previous conditions of
use.
b. WARNING indicates a potentially hazardous situation
which, if not avoided, could result in death or serious injury.
c. CAUTION indicates a potentially hazardous situation
which, if not avoided, may result in minor or moderate
injury. It is also used to alert against unsafe practices and
hazards involving only property damage.
!
WARNING
▲
FIRE OR EXPLOSION HAZARD
Failure to follow the safety warnings exactly could result in
serious injury, death or property damage.
Improper servicing could result in dangerous operation,
The manufacturer assumes no responsibility for equipment
installed in violation of any code or regulation.
It is recommended that Manual J of the Air Conditioning
Contractors Association (ACCA) or A.R.I. 230 be followed in
estimating heating requirements. When estimating heating
requirements for installation at altitudes above 2000 ft., remember the gas input may need to be reduced (See High Altitude
Installation).
Material in this shipment has been inspected at the factory
and released to the transportation agency without known
damage. Inspect exterior of carton for evidence of rough
handling in shipment. Unpack carefully after moving equipment to approximate location. If damage to contents is
found, report the damage immediately to the delivering
agency.
Codes and local utility requirements governing the installation
of gas fired equipment, wiring, plumbing, and flue connections
must be adhered to. In the absence of local codes, the installation must conform with latest edition of the National Fuel Gas
Code ANSI Z223.1 • National Installation Code, CAN/CGA
B149.1. The latest code may be obtained from the American
Gas Association Laboratories, 8501 E. Pleasant Valley Rd.,
Cleveland, Ohio 44131.
These furnaces have been classified as CATEGORY IV
furnaces in accordance with latest edition of ANSI Z21.47 •
CAN/CGA 2.3 standards.
Category IV furnaces operate with positive vent static pressure
and with a flue loss less than 17 percent. These conditions
require special venting systems, which must be gas tight and
water tight. These Category IV Direct Vent furnaces are approved for installation in Manufactured/Mobile housing when
used with BAYMFGH100A.
!
CAUTION
▲
To prevent shortening its service life, the furnace should not
be used as a “Construction Heater” during the finishing
phases of construction until the requirements listed in item
9, a-g of the safety section of this publication have been met.
Condensate in the presence of chlorides and fluorides from
paint, varnish, stains, adhesives, cleaning compounds, and
cement create a corrosive condition which may cause rapid
deterioration of the heat exchanger.
Contents
INST ALLA TION INSTRUCTIONS
General Installation Instructions3
Location and Clearances3
Outline Drawings4-5
Upflow Installation6
Downflow Installation6
Horizontal Installation6
Air For Combustion and Ventilation7- 8
Duct Connections8
Return Air Filters9-12
General Venting Instructions13
Venting Material13
Venting Tables14-17
Horizontal Venting18
Venting Through The Wall18
Venting Throught The Roof20
Downward Venting20
Venting Through a Masonry Chimney20
Condensate Drain Instructions22
Electrical Connections23
Field Wiring Diagrams24-25
Gas Piping26
Combustion Input Checks27
Start Up and Adjustment29
Preliminary Inspections29
Lighting Instructions29
Sequence Of Operation30
Control And Safety Switch Adjustments30
Airflow Adjustment3 0
Abnormal Conditions3 1
IFC Error Flash Code32
!
CAUTION
▲
Do not install the furnace in a corrosive or contaminated
atmosphere.
LOCATION AND CLEARANCES
The location of the furnace is normally selected by the architect,
the builder, or the installer. However, before the furnace is
moved into place, be sure to consider the following requirements:
1. Is the location selected as near the vent and as centralized
for heat distribution as practical?
2. Do all clearances between the furnace and enclosure
equal or exceed the minimums shown in the Table 1.
3. Is there sufficient space for servicing the furnace and other
equipment? A minimum of 24 inches front accessibility to
the furnace must be provided. Any access door or panel
must permit removal of the largest component.
4. Are there at least 3 inches of clearance between the furnace
front panel and any closed panel or door provided?
18-CD22D1-53
5. Are the vent pipe and combustion air inlet pipe within vent
table lengths? Will the pipes remain unobstructed?
6. Allow sufficient height in supply plenum above or below
the furnace to provide for cooling coil installation if the
cooling coil is not installed at the time of this furnace
installation.
7. A furnace shall be installed so electrical components are
protected from water.
8. If the furnace is installed in a residential garage, it must be
installed so that the burners and the ignition source are
located not less than 18 inches (46 cm) above the floor
and the furnace must be located or protected to avoid
physical damage from vehicles.
IMPORT ANT:
The furnace must be installed level. The only allowable
variation would be slightly to the left and/or forward in upflow
installations or slightly toward the front in horizontal installations. This is necessary for proper condensate drainage.
Page 4
418-CD22D1-5
Installer’s Guide
*UX1-H OUTLINE DRAWING
(ALL DIMENSIONS ARE IN INCHES)
From Dwg. 21C341884 Rev. 1
Page 5
18-CD22D1-55
*DX1-H DOWNFLOW / HORIZONTAL OUTLINE DRA WING
(ALL DIMENSIONS ARE IN INCHES)
From Dwg. 21C341885 Rev. 0
Installer’s Guide
Page 6
Installer’s Guide
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
UPFLOW INST ALLATION
Standoffs and screws (See Figure 1) are included with the
cased coils for attachment to the furnace. There are clearance
alignment holes near the bottom of the coil wrapper. Drill
screws are used to engage the furnace top flanges. The
standoff is inserted into the cabinet alignment hole. The drill
screws are inserted through the standoffs then screwed into the
furnace flange.
The coil is always placed downstream of the furnace airflow.
1
CASED
UPFLOW
FURNACE
STANDOFFS (4)
COIL
STANDOFFS
(BOTH SIDES)
DRILL SCREWS (4)
FOR VERTICAL
INST ALLATIONS:
SCREWS
(BOTH SIDES)
DOWNFLOW INST ALLATIONS
!
WARNING
▲
Do not install the furnace directly on carpeting, tile or other
combustible material other than wood flooring. For vertical
downflow application, subbase (BAYBASE205) must be
used between the furnace and combustible flooring. When
the downflow furnace is installed vertically with a cased coil,
a subbase is not required.
Required floor opening:
T ABLE 1
CABINET
WIDTH
RETURN
DUCT WIDTH
17-1/2"16-1/4"16-5/8" 20-1/8"15-5/8"19-3/8"
21"19-3/4"20-1/8"20-1/8"19-1/8"19-3/8"
24-1/2"23-1/4"23-5/8"20-1/8"22-5/8"19-3/8"
FLOOR OPENING PLENUM OPENING
"A""B""A""B"
HORIZONTAL INSTALLATION
The coil and furnace must be fully supported when used in the
horizontal position. It is always recommended that an auxiliary
drain pan be installed under a horizontally installed evaporator
coil or 90% gas furnace. Connect the auxiliary drain line to a
separate drain line (no trap is needed in this line).
Three brackets (with screws) are included with downflow
furnaces for installation to stabilize and secure the furnace and
TXC cased coil in the horizontal position. See Figure 4. The
coil is placed downstream of the furnace, with the apex of the
coil pointing in the direction of the airflow for horizontalinstallation. The cased coil is secured to the furnace and both
the furnace and the cased coil must be properly supported. The
brackets mount using the rear screws on the coil case and use
the screws provided to secure the bracket to the furnace. The
remaining bracket is placed as close to center as possible
(horizontally) between the coil case front and the furnace
bottom channel (for downflow/horizontal furnace). Use four of
the screws provided to secure the bracket. The upflow furnace,
converted to horizontal, aligns and attaches the TXC coil as in
Figure 1. However, the coil requires additional support.
The furnace may be installed in an attic or crawl space in the
horizontal position by placing the furnace
3
CASED COIL CONNECTION
on the left side
(as
BRACKET FOR DOWNFLOW
FURNACE IN HORIZONTAL
DOWNFLOW ONLY
viewed from the front in the vertical position). The horizontal
furnace installation in an attic should be on a service platform
large enough to allow for proper clearances on all sides and
service access to the front of the furnace (See Figure 4 &
Clearance Table). Line contact is only permissible between
lines formed by intersections of the top and two sides of the
furnace casing and building joists, studs, or framing.
The furnace may be placed horizontally in a crawl space on a
pad or other noncombustible material which will raise the unit
for sufficient protection from moisture.
The furnace must be
4
SUBBASE CROSS SECTION
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
FURNACE
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
FRONT
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
618-CD22D1-5
A (width)
B (depth)
D
C
supported at both ends and the middle when installed
horizontally.
The furnace must also be elevated a minimum of 6 inches to
allow clearance for the condensate drain to exit the cabinet
in the horizontal position.
UPFLOW/
HORIZONT AL
Page 7
Installer’s Guide
The horizontal furnace may also be suspended from the joists
using 3/8" all-thread rods with pieces of angle iron underneath
the furnace to form a hanging rack at both ends and the
midpoint. The rods need to be of sufficient length to allow for
proper clearances from combustible materials. The angle iron
needs to be at least 32" in length to allow for access to service
panels.
AIR FOR COMBUSTION AND VENTILATION
If these furnaces are installed in a nondirect vent capacity then
the adequate flow of combustion and ventilating air must not be
5
50 CU. FT. OR MORE
PER 1000 BTU/HR. INPUT
ALL EQUIP. INSTALLED
UNCONFINED
obstructed from reaching the furnace. Air openings provided for
combustion air must be kept free of obstructions which restrict
the flow of air. Airflow restrictions affect the efficiency and safe
operation of the furnace. Keep this in mind should you choose
to remodel or change the area which contains your furnace.
Furnaces must have a free flow of air for proper performance.
Provisions for combustion and ventilation air shall be made in
accordance with latest edition of Section 5.3, Air for Combustion and Ventilation, of the National Fuel Gas Code,
ANSI Z223.1 — CAN/CGA B149.1 or applicable provisions of
the local building codes. Special conditions created by
mechanical exhausting of air and fireplaces must be considered to avoid unsatisfactory furnace operation.
OUTSIDE AIR IS RECOMMENDED
The use of indoor air for most applications is acceptable,
unless there is the presence of corrosive chemicals orcontamination. Certain types of installation will require the use
of outside air for combustion.
The following types of installations will require use of
OUTDOOR AIR for combustion, due to chemical exposures:
* Commercial buildings
* Buildings with indoor pools
* Furnaces installed in “confined” laundry rooms
* Furnaces installed in “confined” hobby or craft rooms
* Furnaces installed near chemical storage areas.
Exposure to the following substances in the combustion air
supply will also require OUTDOOR AIR for combustion:
* Permanent wave solutions
* Chlorinated waxes and cleaners
* Chlorine based swimming pool chemicals
* Water softening chemicals
* Deicing salts or chemicals
* Carbon Tetrachloride
* Halogen type refrigerants
* Cleaning solvents (such as perchloroethylene)
* Printing inks, paint removers, varnish, etc.
* Hydrochloric acid
* Cements and glues
* Antistatic fabric softeners for clothes dryers
* Masonry acid washing materials
Furnace locations may be in a “confined space” or an “uncon-fined space”.
Unconfined space
have adequate air by infiltration to provide air for combustion
and ventilation. Buildings with tight construction (for example,
weather stripping, heavily insulated, caulked, vapor barrier,
etc.), may need additional air to be provided as described for
confined space
Confined spaces
space per 1000 BTU/hr input from all equipment installed. Air
for combustion and ventilation requirements can be supplied
from inside the building as in Figure 8 or from the outdoors, as
in Figure 9.
6
FOR UNCONFINED SPACE INSTALLATIONS
FURNACE
MAXIMUM BTUH
INPUT RATING
60,000
80,000
100,000
120,000
1. All air from inside the building as in Figure 8: The confined
space shall be provided with two permanent openings
communicating directly with an additional room(s) of
sufficient volume so that the combined volume of all
is defined in Figure 5. These spaces may
.
are installations with less than 50 cu. ft. of
MINIMUM AREA IN SQUARE FEET
WITH 8 FT. CEILING
MINIMUM AREA IN SQUARE FEET
OF UNCONFINE D SPACE
375
500
625
875
7
CONFINED
SPACE
spaces meets the criteria for an unconfined space. The
total input of all gas utilization equipment installed in the
combined space shall be considered in making this
determination. Refer to Table 2 for minimum open areas
requirements.
All air from outdoors as in Figure 9: The confined space
2.
shall be provided with two permanent openings, one
commencing within 12 inches of the top and one commencing within 12 inches of the bottom of the enclosure.
The openings shall communicate directly, or by ducts, with
the outdoors or spaces (crawl or attic) that freely communicate with the outdoors. Refer to Table 2, for minimum open
areas requirements.
Air
From
Inside
100
100
100
120
TABLE 2
Air From Outside
Vertical
Duct
15
20
25
30
Horizontal
Duct
30
40
50
60
MINIMUM FREE ARE A IN SQUARE INCHES
EACH OPENING (FURNACE ONLY)
Furnace
Maximum
BTUH/INPUT
Rating
60,000
80,000
100,000
120,000
DUCT CONNECTIONS
Air duct systems should be installed in accordance with
standards for air conditioning systems, National Fire Protection
18-CD22D1-57
Page 8
Installer’s Guide
8
9
Association Pamphlet No. 90. They should be sized in accordance with ACCA Manual D or whichever is applicable.
Central furnaces, when used in connection with cooling units,
shall be installed in parallel or on the upstream side of the
cooling coil to avoid condensation in the heat exchanger. With
a parallel flow arrangement, the dampers or other means used
to control flow of air shall be adequate to prevent chilled air
from entering the furnace, and if manually operated, must be
equipped with means to prevent operation of either unit unless
the damper is in full heat or cool position.
On any job, flexible connections of nonflammable material may
be used for return air and discharge connections to prevent
transmission of vibration. Though these units have been specifically designed for quiet, vibration free operation, air ducts can act
as sounding boards and could, if poorly installed, amplify the
slightest vibration to the annoyance level.
When the furnace is located in a utility room adjacent to the
living area, the system should be carefully designed with
returns to minimize noise transmission through the return air
grille. Although these furnaces are designed with large blowers
operating at moderate speeds, any blower moving a high
volume of air will produce audible noise which could be
objectionable when the unit is located very close to a living
area. It is often advisable to route the return air ducts under the
floor or through the attic. Such design permits the installation of
air return remote from the living area (i.e. central hall).
When the furnace is installed so that the supply ducts carry air
circulated by the furnace to areas outside the space containing
the furnace, the return air shall also be handled by a duct(s)
sealed to the furnace and terminating outside the space
containing the furnace.
RETURN AIR DUCT SYSTEMS
Where there is no complete return duct system, the return
connection must be run full size from the furnace to a
location outside the utility room, basement, attic, or crawl
space.
Do Not install return air through the back of the furnace cabinet
Do Not install return air through the side of the furnace cabinet
on horizontal applications.
NOTE:
Minimum return air temperature is 50° F.
All return air duct systems should provide for installation of
return air filters.
1. Set the furnace in place.
2. For upflow side return installations, remove the insulation
around the opening in the blower compartment.
3. The side panels of the upflow furnace include locating
notches that are used as guides for cutting an opening for
return air, refer to Figure 10 and the outline drawing on
page 4 for duct connection dimensions for various furnaces.
NOTE:
On upflow 5 ton airflow models, if the airflow requirement
exceeds 1800 CFM, these models will require return air
openings and filters on both sides; OR 1 side and the
bottom; OR just the bottom.
4. If a 3/4" flange is to be used for attaching the air inlet duct,
add to cut where indicated by dotted lines in Figure 10. Cut
corners diagonally and bend outward to form flange.
5. If flanges are not required, and a filter frame is installed, cut
between locating notches (See Figure 10).
818-CD22D1-5
Page 9
Installer’s Guide
6. The bottom panel of the upflow furnace must be removed
for bottom return air. Remove the filter and lay the furnace
on its back. Remove the two 1/4" hex screws securing the
bottom front channel to the cabinet. Lower the front edge of
the bottom front channel and pull forward to remove the
channel. The bottom return air panel will now easily slide
out of the cabinet. Reinstall the bottom front channel and
filter for upflow bottom return installations.
7. The filter retainer is factory supplied for upflow bottom
return. Use the filter retainer on side or bottom if filter is to
be used within the furnace cabinet on upflow only installations.
The horizontal installation of the upflow furnace requires
8.
an external filter section. Do NOT use the bottom return
filter within the furnace. Filter kits are available for
horizontal applications.
9. Connect duct work to furnace. See Outline Drawing for
supply and return duct size and location. Flexible duct
connectors are recommended to connect both supply and
return air ducts to the furnace. If only the front of the furnace
is accessible, it is recommended that both supply and
return air plenums are removable.
RETURN AIR FILTERS
TYPICAL UPFLOW RETURN AIR FILTER INSTALLATIONS
These furnaces require high velocity type air filters. The filters
may be located within the furnace blower compartment for
UPFLOW furnaces in either a BOTTOM or SIDE (left side or
right side) return air inlet. Some filters may need to be trimmed
for side or bottom filter use.
T ABLE 3
0
LOCATING
NOTCHES PROVIDED FOR SIDE
RETURN CUTOUT
SEE OUTLINE DRAWING
*
UPFLOW FURNACE ONLY
q
CUT OUT
FOR SIDE
FILTER
FRONT
of Furnace
Airflow
MODELS
NUMBERS
*UX1B040A9H21B
*UX1B060A9H31B
*UX1B080A9H31B
*UX1C100A9H41B21"1 - 20" X 25" X 1"
*UX1D120A9H51B24-1/2"1 - 24" X 25" X 1"
*First letter may be "A" or "T"
*** NOTE - On 5 ton airflow models, if the airflow requirement
exceeds 1800 CFM, these models will require filters on both sides;
OR 1 side and the bottom; OR just the bottom.
CABINET
WIDTH
17-1/2"1 - 17" X 25" X 1"
FILTER
QTY & SIZE
NOTE:
On upflow 5 ton airflow models, if the airflow requirement
exceeds 1800 CFM, these models will require return air
openings and filters on both sides; OR 1 side and the
bottom; OR just the bottom.
The upflow furnace blower door has a hinge at the bottom
which allows the door to tilt forward for filter replacement
without the door being removed (See Figure 11). The furnace
filter in the bottom or side configuration can be removed by
simply turning the two latches on the blower door and tilting the
door forward.
Blower Door Hinge and Bottom Filter Rack Installation
RETURN AIR FILTERS FOR UPFLOW FURNACE IN
HORIZONTAL CONFIGURATION
When the Upflow Furnace is installed in the horizontal configuration, the return air filters must be installed exterior to the
cabinet. Remote filter grilles may be used for homeowner
convenience or the filters may be installed in the duct work
upstream of the furnace. See Figure 12.
w
Airflow
TYPICAL RETURN AIR FILTER INSTALLA TION IN
UPFLOW MODEL IN HORIZONTAL POSITION
18-CD22D1-59
Page 10
Installer’s Guide
BLOWER DOOR/HINGE REMOVAL
If clearance or other problems create a problem in using the
tilting door, the blower door hinge may be removed without
creating any problems with the seal of the furnace. To remove
the blower door, tilt the door forward 2 to 3 inches and pull up.
To remove the tilt feature, simply remove the lower hinge as
shown in Figure 13. The bottom of the blower door will catch in
the bottom of the furnace front channel for door replacement.
1. Determine the location to be used. The furnace cabinet has
dimples for location of the alternate furnace clips (
return only
Bottom return holes are pre-drilled.
2. Install the clips in front and rear of the desired location
using the screws provided. The filter clip with the leaf
spring mounts in the rear of the cabinet.
). Pre-drill clearance holes with a 3/16" drill.
Side
TYPICAL DOWNFLOW FURNACE
RETURN AIR FILTER INSTALLATIONS
These furnaces require high velocity type air filters. Downflow
furnace filters must be located outside the furnace cabinet.
Typical installations are shown in Figure 15. Tables 4, 5 and 6
provide information for installation of the filter retaining brackets
shipped with downflow furnaces.
T ABLE 4
MODELS
NUMBERS
CABINET
WIDTH
FILTER
QTY & SIZE
*DX1B040A9H 21B
*DX1B060A9H 31B
17-1/2"2 - 14" X 20" X 1"
*DX1B080A9H 31B
*DX1C100A9H41B21"2 - 16" X 20" X 1"
*DX1D120A9H51B24-1/2"2 - 16" X 20" X 1"
*First letter may be "A" or "T"
T ABLE 5
LOCATING FILTER RETAINER BRACKETS IN DUCTWORK
CABINET
WIDTH
17-1/2"16-1/4"15"14"14-3/8"
21"19-3/4"19-1/2"14"13-1/8"
24-1/2"23-1/4"22"14"13-5/8"
* LOCATION DIMENSION IS FROM END OF DU CT AGAINST THE FURNACE TO THE
SCREW HOLES FOR THE BRACKET.
RETURN
DUCT
WIDTH
DIMENSION
"A"
DIMENSION
"B"
FILTER
BRACKET
LOCATION*
r
SIDE
CUT-OUT
1018-CD22D1-5
REAR
ALTERNATE FILTER
CLIPS LOCATION
Page 11
t
Installer’s Guide
Airflow
DOWNFLOW
TABLE 6
MINIMUM CLEARANCE FROM COMBUSTIBLE MATERIALS FOR
UPFLOW/HORIZONTAL AND DOWNFLOW/ HORIZONTAL FURNACES
UNIT LOCATION
FURNACE SURFACE
SIDES0"1"0"
BACK0"3"6"
TOP1"1"1"
FRONT3"3"18"
VENT0"0"0"
NOTE
: CLEARANCE REQUIRED AT TOP OF PLENUM IS 1"
VERTICAL
CLOSET
GENERAL VENTING
THIS FURNACE MUST BE VENTED TO THE OUTDOORS.
THESE FURNACES ARE INDUCED DRAFT VENTED AND
MUST NOT BE CONNECTED TO ANY VENT SERVING
ANOTHER A PPLIANCE. PLEASE NOTE THAT THESE FURNACES USE POSITIVE-PRESSURE VENT SYSTEMS.
Proper venting is essential to obtain maximum efficiency from a
condensing furnace. Proper installation of the vent system is
necessary to assure drainage of the condensate and prevent
deterioration of the vent system.
American Gas Association has certified the design of condensing furnaces for a minimum of 0" clearance from combustible
materials with a single wall plastic vent pipe.
The recommended system is assembled from 2", 2-1/2", or
3" plastic pipe and fittings (See Table 7, page 12). Where the
system is routed to the outdoors through an existing masonry
chimney containing flue products from another gas appliance,
or where required by local codes, then 3" venting of Type 29-4C
stainless steel must be used in place of PVC material.
These furnaces have been classified as CATEGORY IV
furnaces in accordance with the latest edition of
ANSI Z21.47 • CAN/CGA-2.3 Standards. Category IV furnaces
operate with positive vent pressure and with a vent gas
temperature less than 140° F above the dewpoint. These
conditions require special venting systems, which must be gas
tight and water tight.
Airflow
DOWNFLOW/
HORIZONT AL
HORIZONTAL
CLOSET
NOTE:
When an existing furnace is removed from a venting system
serving other gas appliances, the venting system is likely to
be too large to properly vent
attached appliances.
The following steps shall be followed with each appliance
remaining connected to the common venting system placed in
operation, while the other appliances remaining connected to
the common venting system are not in operation.
1. Seal any unused openings in the common venting system.
2. Visually inspect the venting system for proper size and
horizontal pitch and determine there is no blockage or
restriction, leakage, corrosion or other deficiencies which
could cause an unsafe condition.
3. Insofar as is practical, close all building doors and windows and all doors between the space in which the
appliances remaining connected to the common venting
system are located and other spaces of the building. Turn
on clothes dryers and any appliances not connected to the
common venting system. Turn on any exhaust fans, such
as range hoods and bathroom exhausts, so they will
operate at maximum speed. Do not operate a summer
exhaust fan, close fireplace dampers.
the remaining
HORIZONTAL
ALCOVE / ATTIC
18-CD22D1-511
Page 12
Installer’s Guide
4. Follow the lighting instructions. Place the appliance being
inspected in operation. Adjust thermostat so appliance will
operate continuously.
5. Test for spillage at the draft hood relief opening after
5 minutes of main burner operation. Use the flame of a
match or candle, or smoke from a cigarette, cigar, or pipe.
6. After it has been determined that each appliance remaining connected to the common venting system properly
vents when tested as outlined above, return door, windows, exhaust fans, fireplace dampers and any other gasburning appliance to their previous conditions of use.
a. Determine the Btu per hour input of all remaining
appliances attached to the venting system.
b. Determine the diameter, rise, and lateral of the existing
venting system, as well as quantity and type of bends.
c. Use the appropriate tables in the latest edition of
the National Fuel Gas Code (ANSI Z223.1 •
CAN/CGA B149.1 Installation Codes or “Exhibit J” of
ANSI Z21.47 • CAN/CGA-2.3 Standards. “Exhibit J”
includes examples and drawings of typical venting
systems.
If improper venting is observed during any of the above tests,
the remaining common venting system must be corrected.
Correction of the remaining common vent system should be
done by referring to the latest edition of the National Fuel Gas
Code (ANSI Z223.1) • CAN/CGA B149.1 Installation Codes or
“Exhibit J” of ANSI Z21.47• CAN/CGA-2.3 Standards. The
following are general steps to be used to correct or resize a
remaining vent system when a furnace which may not be
common vented is removed from the system:
IMPORT ANT:
These furnaces may be installed as Direct Vent (sealed combustion) or as Nondirect vent (single pipe). The furnaces are shipped
DIRECT VENT with sealed combustion.
For DIRECT VENT APPLICATION: The furnaces must be vented to the exterior of the house and combustion air MUST come
through the inlet air pipe FROM OUTSIDE AIR.
For NONDIRECT VENT APPLICATION: The furnace shall be vented to the exterior of the house, but combustion air may enter from
the surrounding area as long as combustion air requirements are met. (See AIR FOR COMBUSTION AND VENTILATION)
PVC VENT FITTING MATERIAL
These fittings are available from your Gas Furnace Distributors.
Straight Pipe Sections, Couplings, 45° Elbows, 60° Elbows, 90°
Elbows, Vent or Sanitary Tee, or other necessary fittings may be
2", 2½", 3", or 4" diameter. The allowable materials are shown in
Table 7.
VENT FITTING MA TERIAL – PLASTIC
Gas and liquid tight single wall vent fittings, designed for
resistance to corrosive flue condensate, MUST be used
throughout.
Listed in Table 8 & 9 are 2", 2½", 3", and 4" size fittings that
meet these requirements. The materials listed are various
grades of PVC and ABS plastic.
PIPE JOINTS: All joints must be fastened and sealed to prevent
escape of combustion products into the building.
* - Allowable temperatures based on c lassi ficat ions covered in ASTM D4 396 [D efle cti on Temps Under Load (264 PSI)]
** - Allowable temperatures based on cla ssific ations c overed in ASTM D1 784 [ Deflec tion Temps Under Load (264 PSI)]
*** - Allowable temperatures based on cla ssifica tion s covered in AS TM D39 65 [ Deflec tion Temps Under Load (264 PSI)]
1218-CD22D1-5
Page 13
Installer’s Guide
NOTE:
It is recommended that the first joints from the furnace be
connected and sealed with high temperature RTV. This will
enable the pipes to be removed later without cutting.
Be sure to properly support these joints.
BONDING OF PVC
Commercially available solvent cement must be used to join
the pipe and fittings. Follow instructions on the container
carefully.
Procedure for Cementing Joints:
1. Cut pipe square, remove ragged edges and burrs. Chamfer end of pipe, then clean fitting socket and pipe joint area
of all dirt, grease, moisture or chips.
2. After checking pipe and socket for proper fit, wipe socket
and pipe with cleaner-primer. Apply a liberal coat of primer
to inside surface of socket and outside of pipe.
DO NOT ALLOW PRIMER TO DRY BEFORE APPLYING
CEMENT.
3. Apply a thin coat of cement evenly in the socket. Quickly
apply a heavy coat of cement to the pipe end and insert
pipe into fitting with a slight twisting movement until it
bottoms out.
4. Hold the pipe in the fitting for 30 seconds to prevent
tapered socket from pushing the pipe out of the fitting.
5. Wipe all excess cement from the joint with a rag. Allow 15
minutes before handling. Cure time varies according to fit,
temperature and humidity.
NOTE:
To ensure proper operation at the vent lengths indicated, the
combustion air inlet and vent terminals should be in the
same pressure zone. Terminating the vent and inlet in
different pressure zones will change the maximum vent
lengths and may cause nuisance tripping of the pressure
switch(es). The amount of change can not be predicted. The
selection of the inlet and outlet terminal locations are the
responsibility of the designer/installer. If the installer
chooses separate pressure zones for the terminals, the
combustion air inlet termination must be in the higher (more
positive) pressure zone.
HORIZONTAL VENTING
NOTE:
Vent termination kit BAYAIR30AVENTA or BAYVENT200B
may be used instead of the horizontal and vertical termination options shown in the following figures.
HORIZONTAL INSTALLATION
(Upflow / Horizontal or Downflow / Horizontal)
NOTE:
In horizonal venting when the factory supplied “off-set” (2X3
reducing coupling) is used for 3” vent pipe installation, make
sure the marking “Top” is located on the top side of the pipe.
The straight side must be on bottom for proper condensate
drainage. This coupling is factory supplied only with the
following models: *UC120 & *DC120, *UX120 & *UY120
*UX100 & *UY100, *UX808C960, and all *DX & *DY models.
NOTE:
Follow venting instructions carefully when using PVC
cement.
IMPORT ANT:
All joints must be water tight. Flue condensate is somewhat
acidic, and leaks can cause equipment damage.
VENT AND INLET AIR CONNECTIONS
y
Front of Furnace
Seal INLET AIR PIPE
with RTV sealant
Connection of the pipe and collar of the combustion air inlet
should just be a friction fit. It is recommended that the inlet air
joint be sealed with RTV type sealant to allow the joint to be
separated for possible future service. The inlet and vent pipes
must be properly supported throughout the entire length.
Connection of the vent pipe to the vent collar should also be
accomplished using RTV type sealant. This type sealant
provides a connection which remains flexible and can be
separated in the future if service needs require the removal of
the vent pipe for service or clearance.
Seal VENT PIPE
with RTV sealant
WHEN THE FACTORY SUPPLIED "OFF-SET" (2X3
REDUCING COUPLING) IS USED FOR 3" VENT PIPE
INSTALLATION, MAKE SURE THE MARKING "TOP" IS
LOCATED ON THE TOP SIDE OF THE PIPE.
LABEL
SAYS
"TOP"
STRAIGHT SIDE MUST BE
ON BOTTOM FOR PROPER
CONDENSATE DRAINAGE.
2" TO 3" COUPLING
FACTORY SUPPLIED ONLY WITH
THE FOLLOWING MODELS:
UC120 & DC120
UX120 & UY120
UX100 & UY100
UX080C960
ALL DX & DY MODLES
1. The INLET AIR of one pipe systems require the installation of a 90° elbow (to prevent dust and debris from falling straight into thefurnace) and a 2 foot
horizontal or vertical straight pipe section connected before or after the elbow.
2. DO NOT MIX PIPE DIAMETERS IN THE SAME LENGTH OF PIPE OUTSIDE THE FURNACE CABINET (Except adapters at the top of the furnace).
If different inlet and vent pipe sizes are used, the vent pipe must adhere to the maximum length limit shown in the table above (See Note 7 below for exception).
The inlet pipe can be of a larger diameter, but never smaller than the vent pipe.
3. MAXIMUM PIPE LENGTHS MUST NOT BE EXCEEDED! THE LENGTH SH OWN IS NOT A COMBINED TOTAL, IT IS THE M AXIMUM L ENGTH OF EACH
(Vent or Inlet air pipes in two pipe systems).
4. One standard radius 90° elbow is equivalent to 12' of 4" pipe; one SHORT radius 90° elbow is equivalent to 10' of 3" pipe and one LONG radius elbow is
equivalent to 6' of 3" pipe. One SHORT/LONG radius 90° elbow is equivalent to 7½' of 2½" pipe, & 5' of 2" pipe. Two 45° elbows equal one 90°elbow.
5. The termination tee or bend must be included in the total number of elbows. If the BAYVENT100 termination kit is used, the equivalent length of pipe is 5 feet.
There is zero equivalent length for the BAYVENT200.
6. Pipe adapters are field supplied.
7. 4" pipe may be reduced to 3" for termination with BAYAIR30AVENTA or BAYVENT200 without additional length restriction.
2" PIPE
& FITTINGS
6080100130508080130
5080100130408080130
NOT ALLOWED40100130NOT ALLOWED4080130
NOT ALLOWED40100130NOT ALLOWED4080130
2-1/2" PIPE
& FITTINGS
3" PIPE
& FITTINGS
4" PIPE
& FITTINGS
& FITTINGS
MAXIMUM VENT LENGTH:
DIRECT VENT (2 PIPE SYSTEM) -
MAXIMUM TOTAL EQUIVALENT FEET FOR
VENT AND INLET AIR PIPES (See Notes)
MODEL
*DX1B040A9H21B
*DX1B060A9H31B
*DX1B080A9H31B
*DX1C100A9H41B
*DX1D120A9H51B
NOTES: * - First letter may be "A" or "T"
1. The INLET AIR of one pipe systems require the installation of a 90° elbow (to prevent dust and debris from falling straight into thefurnace) and a 2 foot
horizontal or vertical straight pipe section connected before or after the elbow.
2. DO N OT MIX PIPE DIAMETE R S IN TH E SAME LENGTH OF PIPE OUTSIDE THE F URNACE CA B INE T (Except adapters at the top of the furnace).
If different inlet and vent pipe sizes are used, the vent pipe must adhere to the maximum length limit shown in the table above (See Note 7 below for exception).
The inlet pipe can be of a larger diameter, but never smaller than the vent pipe.
3. MAXIMUM PIPE LENGTHS MUST NOT BE EXCEEDED! THE LENGTH SHOWN IS NOT A COMBINED TOTAL, IT IS THE MAXIMUM LENGTH OF EACH
(Vent or Inlet air pipes in two pipe systems).
4. One standard radius 90° elbow is equivalent to 12' of 4" pipe; one SHORT radius 90° elbow is equivalent to 10' of 3" pipe and one LONG radius elbow is
equivalent to 6' of 3" pipe. One SHORT/LONG radius 90° elbow is equivalent to 7½' of 2½" pipe, & 5' of 2" pipe. Tw o 45° elbows equal one 90°elbow.
5. The termination tee or bend must be included in the total number of elbows. If the BA YAIR30VENTA termination kit is used, the equivalent length of pipe is 5 feet.
There is zero equivalent length for the BAYVENT200.
6. Pipe adapters are field supplied.
7. 4" pipe may be reduced to 3" for termination with BA YAIR30AV ENT A or BAYVENT 200 w ithout additional length restriction.
2" PIPE
& FITTINGS
6080100130508080130
5080100130508080130
4580100130408080130
NOT ALLOWED80100130NOT ALLOWED8080130
NOT A LLOWED1560130NO T A LLOWED2570130
2-1/2" PIPE
& FITTINGS
3" PIPE
& FITTINGS
4" PIPE
& FITTINGS
& FITTINGS
NONDIRECT VENT (1 PIPE SYSTEM) -
MAXIMUM TOTAL EQUIVALENT FEET FOR
VENT PIPE ONLY (See Notes)
2" PIPE
MAXIMUM TOTAL EQUIVA LENT FEET FOR
2" PIPE
2-1/2" PIPE
& FITTINGS
NONDIRECT VENT (1 PIPE SYSTEM) -
VENT PIPE ONLY (See Notes)
2-1/2" PIPE
& FITTINGS
3" PIPE
& FITTINGS
3" PIPE
& FITTINGS
4" PIPE
& FITTINGS
4" PIPE
& FITTINGS
u
SINGLE PIPE VENTING
UPFLOW FURNACE
Air Inlet
B
Air Inlet
1418-CD22D1-5
A
A (0-2') or greater
B (0-2') or greater
A+B = 2' minimum
A
Vent only
to outside
DOWNFLOW
FURNACE
Vent only
to outside
A = 2' minimum
Page 15
i
INSIDE
CORNER DETAIL
G
V
Installer’s Guide
D
EE
V
FIXED
CLOSED
J
B
V
X
V
B
L
V
VENT TERMINAL
Clearance above grad e, veran da , p or ch, deck, or
A=
balcony
B=C le aran c e to wi n dow or door that may be op en ed
C=Clearance to permanently closed window**
Vertical clearance to ven ti la te d so ffit l oc ate d ab ove the
D=
terminal within a horizontal distance of 2 feet (61 cm)
from the center l in e of t he terminal
E=Clearance to unventilated soffit**
F=Clearance to outside corner**
G=Clearance to insi de corner**
Clearance to each side of center line extended above
H=
meter/regulator assembly
I=Clear an ce to s e rvice regulato r vent ou tl et3 feet (91 cm)*
Clearance to n on me cha ni c al air s u pply i nl e t to build i ng
J=
or the combustion air inlet to any othe r appl iance
K=C le aran c e to a m ec ha ni cal a ir supply inlet6 feet (1.83m)3 feet (91 cm) above if wi thin 10 feet (3m) hor iz ont al ly
Clearance above a p aved si dewalk or p aved dr i veway
L=
located on public proper ty
M=Clearance under veranda , p orc h, de ck, or b al c ony`12 inches (30 cm ) ‡*
Notes:
1. In accordance with the cur ren t C SA B149.1 Natural Gas a nd P rop ane Installatio n C ode.
2. In accordance with the current ANSI Z223.1/NFPA 54 National Fuel Gas Code.
†. A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwelling and serves both dwellings.
‡. Pemitted only if veranda, po rch , d eck, o r ba lco ny is fu l ly o pe n on a mi ni mu m of two si de s be ne ath th e flo or.
* Clearance in ac c ord an ce with local instal lati on c od es a nd th e re qu irem ents of the gas supplier and t he ma nufactur er' s In s tal lati on In s tr u ctio ns .
C
FIXED
V
CLOSED
OPERABLE
V
F
B
X
AIR SUPPLY INLET
6 inches (15 cm) for appliances =/< 10,000 Btuh (3 kw), 12
inches (30 cm) for appliances > 10,000 Btuh (3 kw) and =/<
100,000 Btuh (3 0 k w ), 36 i nc he s (91 c m) for ap pl i an ce s >
100,000 Btuh (3 0 k w )
6 inches (15 cm) for appliances =/< 10,000 Btuh (3 kw), 12
inches (30 cm) for appliances > 10,000 Btuh (3 kw) and =/<
100,000 Btuh (3 0 k w ), 36 i nc he s (91 c m) for ap pl i an ce s >
100,000 Btuh (3 0 k w )
B
B
3 feet (91 cm) with a height 15 feet (4.5 m) above the
OPERABLE
V
V
B
A
AREA WHERE TERMINAL IS NOT PERMITTED
Direct Vent Terminal Clearances
Canadian Instal l ation sUS Installations
12 inches (30 c m )12 inches (3 0 c m )
**
meter/ reg ul at or a ss em bly
7 feet (2.13 m) †*
H
I
M
6 inches (15 cm) for appliances =/< 10,000 Btuh (3 kw), 9
inches (23 cm ) for app li a nces > 1 0,0 00 B tu h ( 3 kw ) an d =/<
50,000 Btuh (15 kw ), 12 i nch es ( 30 cm ) for appl i an c es > 5 0,0 00
Btuh (15 kw)
*
6 inches (15 cm) for appliances =/< 10,000 Btuh (3 kw), 9
inches (23 cm ) for app li a nces > 1 0,0 00 B tu h ( 3 kw ) an d =/<
50,000 Btuh (15 kw ), 12 i nch es ( 30 cm ) for appl i an c es > 5 0,0 00
Btuh (15 kw)
Vertical clearance to ventilated soffit located above the
D=
terminal within a horizontal distance of 2 feet (61 cm)
from the center line of the terminal
E= Clearance to unventilated soffit**
F= Clearance to outside corner**
G= Clearance to inside corner**
Clearance to each side of center line extended above
H=
meter/regulator assembly
I=Clearance to service regulator vent outlet3 feet (91 cm)*
Clearance to nonmechanical air supply inlet to building
J=
or the combustion air inlet to any other appliance
K= Clearance to a mechanical air supply inlet6 feet (1.83m)3 feet (91 cm) above if within 10 feet (3m) horizontally
Clearance above a paved sidewalk or paved driveway
L=
located on public property
M= Clearance under veranda, porch, deck, or balcony`12 inches (30 cm) ‡*
Notes:
1. In accordance with the current CSA B149.1 Natural Gas and Propane Installation Code.
2. In accordance with the current ANSI Z223.1/NFPA 54 National Fuel Gas Code.
†. A vent shall not term inate directly above a sidewalk or paved driveway that is located between two single family dwelling and serves both dwellings.
‡. Pemitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.
* Clearance in accordance with local installation codes and the requirements of the gas supplier and the manufacturer's Installation Instructions.
inches (30 cm) for appliances > 10,000 Btuh (3 kw) and =/<
100,000 Btuh (30 kw), 36 inches (91 cm) for appliances >
100,000 Btuh (30 kw)
3 feet (91 cm) with a height 15 feet (4.5 m) above the
6 inches (15 cm) for appliances =/< 10,000 Btuh (3 kw), 12
inches (30 cm) for appliances > 10,000 Btuh (3 kw) and =/<
100,000 Btuh (30 kw), 36 inches (91 cm) for appliances >
100,000 Btuh (30 kw)
12 inches (30 cm)12 inches (30 cm)
4 feet (1.2m) below or to the side of opening; 1 foot (0.3m)
above opening.
**
meter/regulator assembly
4 feet (1.2 m) below or to side of opening; 1 foot (300 m) above
opening
7 feet (2.13 m) †7 feet (2.13 m)
*
o
ELBOW AND TEE MUST
BE AS CLOSE TOGETHER
AS POSSIBLE
POSSIBLE CONFIGURA TIONS FOR TWO PIPE VENTING SYSTEMS
1618-CD22D1-5
Page 17
Installer’s Guide
!
▲
When the vent pipe is exposed to temperatures below freezing, i.e., when it passes through unheated spaces, etc., the pipe
must be insulated with 1/2 inch (22.7 mm) thick Armaflex-type insulation or equal. If the space is heated sufficiently to
prevent freezing, then the insulation would not be required. If domestic water pipes are not protected from freezing then it is
assumed the space meets the condition of a heated space.
HORIZONT AL VENTING THROUGH W ALL
These furnaces may be installed as direct vent (as shipped) or as nondirect vent. Installation must conform to national,
state, and local codes.
The vent & inlet terminals must be located at least 12" minimum above normally expected snow accumulation level.
Avoid areas where staining or condensate drippage may be a problem.
Location of the vent/wind terminal should be chosen to meet
the requirements of Figure 20 or 21 for either direct or nondirect vent applications.
PITCH – Venting through the wall must maintain 1/4" per foot
pitched upward to insure that condensate drains back to the
furnace.
FLUE GAS DEGRADA TION – The moisture content of the flue
gas may have a detrimental effect on some building materials.
This can be avoided by using the roof or chimney venting
option. When wall venting is used on any surface that can be
affected by this moisture, it is recommended that a corrosion
resistant shield (24 inches square) be used behind the vent
CAUTION
a
p
ANCHORS
"
.2
7
3.2"
COMBUSTION
AIR
terminal. This shield can be wood, plastic, sheet metal, etc.
Also, silicone caulk all cracks, seams and joints within 3 feet of
the vent terminal.
COMBUSTIBLE MA TERIAL WALL
A minimum clearance of 1" to combustible materials must be
maintained when using single wall stainless steel venting. See
Figure 22.
Shield material to be a minimum of 24 gauge stainless or
aluminized sheet metal. Minimum dimensions are 12"x12".
Shield must be fastened to both inside and outside of wall. Use
screws or anchor type fasteners suited to the outside or inside
wall surfaces.
NONCOMBUSTIBLE MATERIAL WALL
The hole through the wall must be large enough to maintain
pitch of vent and properly seal.
Use cement mortar seal on inside and outside of wall.
See Figure 23.
VENTING THROUGH THE ROOF
When penetrating roof with a 2" PVC vent pipe, a 2" electrical
conduit flashing may be used for a weather tight seal. Lubricate
(4 req.)
VENT
VENT
VENT
CAP
PLATE
VENT
MAINTAIN 12" (18" FOR CANADA) MINIMUM
CLEARANCE ABOVE HIGHEST ANTICIPATED
SNOW LEVEL OR GRADE WHICHEVER IS GREATER
BA YVENT200B
12" MINIMUM
TO OVERHANG
SCREWS
(4 req.)
BA YAIR30A VENTA
(Sidewall)
flexible seal on flashing before PVC pipe is pushed through the
seal. (Field Supplied)
NOTE:
No vent cap as shown in Figure 27 is the preferred method
for vertical vent termination in extremely cold climates.
In extreme climate conditions, insulate the exposed pipe
s
18-CD22D1-517
Page 18
Installer’s Guide
N
d
g
SEE VENTING TABLE
STRAPS OR OTHER SUITABLE SUPPORTS
AT MAXIMUM OF 3'-0" INTERVALS
f
USE ONLY
APPROVED
TERMINATIO
SUPPORT HORIZONTAL PIPE EVERY 3'
0" WITH THE FIRST SUPPORT AS CLOSE
TO THE FURNACE AS POSSIBLE.
INDUCED DRAFT BLOWER, HOUSING,
AND FURNACE MUST NOT SUPPORT
THE WEIGHT OF THE FLUE PIPE.
NOTE: VENT AND INLET MUST BE SUPPORTED
A T A MAXIMUM OF 3' INTERVALS
COMBUSTION
AIR INLET
0" UPFLOW OR
DOWNFLOW MODELS
VENT
COMBUSTION AIR
STRAP
(FIELD SUPPLIED)
ELBOW
(FIELD
SUPPLIED)
UPWARD PITCH -- 1/4" PER FOOT
FIRST SUPPORT SHOULD BE AS
CLOSE TO FURNACE CONNECTION
AS POSSIBLE.
NOTE: ANY FITTINGS PASSING
THROUGH AN UNHEATED SPACE
MUST BE INSULATED.
COMBUSTION
AIR
RAIN CAP
VENT
1" + 1/2"
OUTSIDE
WALL
TEE
REDUCING
COUPLING,
FIELD SUPPLIED
IF NEEDED
2", 2-1/2"
or 3" PIPING
3" PIPING
BAYAIR30AVENTA
BA YVENT200B
SEAL ALL
WALL CAVITIES
1818-CD22D1-5
Page 19
Installer’s Guide
REMOVE RIBS
FROM CAP
COMBUSTION
AIR
ROOF BOOT
(FIELD SUPPLIED)
COMBUSTION
AIR
VENT
ELBOW
(FIELD SUPPLIED)
MAINTAIN 12 IN.
(18 IN. FOR CANADA)
MINIMUM CLEARANCE
ABOVE HIGHEST
ANTICIPATED SNOW
LEVEL. MAXIMUM OF
24 IN. ABOVE ROOF
SUPPORT
(FIELD SUPPLIED)
VENT
DOWNWARD VENTING
Furnace may be in vertical or horizontal configuration.
DOWNWARD VENT
LENGTH IS LIMITED
TO A MAXIMUM OF
EQUIVALENT FEET.
Slope 1/4" per ft.
Slope 1/4" per ft.
All horizontal pipes must be supported at a maximum of 3 foot
NOTES:
A) Condensate trap for vent pipe must be a minimum of 6
inches in height.
B) Condensate trap for vent and inlet pipe must be connected
into a condensate drain pump; an open or vented drain; or
it can be connected to the outlet hose of the furnace's
condensate trap. Outdoor draining of the furnace and coil
condensate is permissible if allowed by local codes.
Caution should be taken to prevent drains from freezing or
causing slippery conditions that could lead to personal
injury. Excessive draining of condensate may cause
saturated ground conditions that may result in damage to
plants.
C) The condensate trap should be primed at initial start up
prior to heating season operation.
15
Upflow or
Downflow
6" Min.
intervals
h
40 Inch
Furnace
above the roof line with Armaflex type insulation.
j
k
MAINTAIN 12 IN.
(18 IN. FOR CANADA)
MINIMUM CLEARANCE
ABOVE HIGHEST
ANTICIPATED SNOW
LEVEL. MAXIMUM OF
24 IN. ABOVE ROOF.
BAYAIR30AVENTA
l
VENT
COMBUSTION
AIR
CONCENTRIC VENT
ROOF TOP APPLICATION
VENTING ROUTED THROUGH A MASONRY CHIMNEY
VENT FITTING MATERIAL – STAINLESS STEEL
Gas and liquid tight single wall metal vent fitting, designed for
resistance to corrosive flue condensate such as Type 29-4C
MUST be used throughout.
These fittings and fitting accessories are to be supplied locally.
DIRECTION OF ST AINLESS STEEL FITTING
All stainless steel fitting must be installed with male end
towards the furnace.
All horizontal stainless steel sections must be positioned with
the seam on top.
All long horizontal sections must be supported to prevent
sagging.
All pipe joints must be fastened and sealed to prevent escape
of combustion products into the building.
NOTE:
Both venting methods shown in Figure 27 & 28 must also
have the combustion air inlet installed - meeting dimension
requirements of Figure 22.
18-CD22D1-519
CONCENTRIC VENT
ROOF INSTALLATION
GAS PIPING
The upflow /horizontal furnace is shipped standard for left side
installation of gas piping. A knock-out is provided on the right
side for an alternate gas piping arrangement. See Figure 34.
Page 20
Installer’s Guide
L
N
T
STAINLESS
E
S
SS
;
x
TYPE 29-4C ST AINLESS STEEL VENTING -
USED THROUGH CHIMNEY THA T VENTS
ANOTHER GAS APPLIANCE
STAINLESS STEEL
STEEL
VENT CAP
VENT CAP
(OPTIONAL)
E CAUTION
6 IN. MIN.
z
SEAL BETWEEN FLANGE, PIPE,
COUPLING AND METAL PANEL
WITH HI TEMP RTV SILICONE SEALANT
FLUE PIPE
COUPLING
SUPPORT
FLANGE
GALVANIZED FIRESTOP SHOULD
BE FABRICATED WITH 3-7/8" DIA.
HOLE FOR SUPPORT FLANGE
(12" x 12" PANEL OR 12" DIA MIN.)
CLEARANCE ( 0" ACCEPTABLE FOR PVC VENT PIPE )
( 1" ACCEPTABLE FOR TYPE 29-4C STAINLESS STEEL VENT PIPE )
VENTING THROUGH CEILING
PVC PLASTIC VENTING - ONLY
c
FLUE PIPE
THROUGH UNUSED CHIMNEY
STAINLESS STEEL
TAINLE
VENT CAP
STEEL
(OPTIONAL)
VENT CAP
SEE CAUTION
6 IN. MIN.
CEILING
SUPPORT THE SINGLE WA
STAINLESS STEEL GAS
VENTING AND CENTER IT I
THE CHIMNEY OPENING WI
ANGLES AS SHOWN OR
ANOTHER EQUIVALENT
MANNER.
NOTE:
HORIZONTAL VENTING
TO VERTICAL VENTING
!
CAUTION
▲
Do not run vent through chimney for wood burning or oil
furnaces or incinerators.
If remaining free area between single wall flue pipe and
masonry chimney is to be used for another gas appliance venting area must be sufficient to vent that appliance and that appliance must be connected to chimney
with
separate entry openings.
IMPORTANT –
The single wall flue pipe joints must be sealed.
The 90° elbow connection to vertical pipe must be sealed to
prevent condensate leakage to base of masonry chimney.
UPLING TO SUPPORT
PE FROM ANGLES
OTHER SUITABLE
PPORT METHOD
FLUE PIPE
!
CAUTION
▲
NOTE:
HORIZONTAL VENTING
TO VERTICAL VENTING
SUPPORT THE SINGL
WALL FLUE PIPE AND
CENTER IT IN THE
CHIMNEY OPENING WI
ANGLES AS SHOWN O
ANOTHER EQUIVALEN
MANNER.
COUPLING
AS REQUIRED
Do not run vent through chimney for wood burning or oil
furnaces or incinerators or any other gas appliance.
IMPORTANT –
The single wall flue pipe joints must be sealed.
The 90° elbow connection to vertical pipe must be sealed to
prevent condensate leakage to base of masonry chimney.
The installation of piping shall be in accordance with piping
codes and the regulations of the local gas company. Pipe joint
compound must be resistant to the chemical reaction with
liquefied petroleum gases.
2018-CD22D1-5
Page 21
CONDENSATE DRAIN INSTRUCTIONS
▲
!
CAUTION
▲
It is recommended that a drain pan be installed under the
furnace to prevent property damage, personal injury or
death from leaking condensate.
Installer’s Guide
Downflow furnace - The furnace is shipped with the left
side drainage setup. To change the right side drain, remove
the drain lines from the trap, rotate the trap 180° so it exits
to the right, reconnect the lines, and run a 1/2" CPVC pipe
from the trap out through the right side knock-out. Use RTV
silicone sealant to connect the CPVC pipe to the trap for ease
of removing to clean the trap.
VERTICAL APPLICATIONS
Upflow furnace - The connection tubing for left and right
side drainage is shipped in the blower compartment. Install
the connection tubing from the trap to the side of the unit and
trim all excess tubing to avoid kinks.
HORIZONTALAPPLICATIONS
Upflow and Downflow furnaces - All horizontal applications are left side only. It is always recommended that the
auxiliary drain pan be installed under a horizontally installed evaporator and/or 90% gas furnace. Connect the
auxillary drain pan to a separate drain line (no trap is needed
in this line).
Left side
Right side
UPFLOW (VERTICAL)
Use Inducer Drain
hose without
extension
UPFLOW HORIZONTAL 17" UNITS
(Left side only)
UPFLOW (VERTICAL)
Use
extension
hose here
UPFLOW HORIZONT AL 21" & 24" UNITS
(Left side only)
18-CD22D1-521
Page 22
Installer’s Guide
The trap must be repositioned to the exterior of the cabinet.
Remove the trap from its present location and reposition the
trap outside of the unit, through the long circular hole, next to
the secondary recouperative cell. Remove the larger drain line
(from the secondary cell) and trim to fit between the secondary cell and the new trap location. On upflow units, plug the
hole in the blower deck where the tube went through.
Remove the hose from the induced blower and reposition into
the other drain tap of the inducer, which is located 90°
clockwise around the inducer. Move the cap from that drain
tap to the unused drain tap. On upflow units, plug the hole in
the blower deck where the tube went through. This tube on
downflow units will need to be cut to fit between the inducer
Left
side
Cut off curved end of
Inducer drain hose
DOWNFLOW (HORIZONT AL)
and the trap. On upflow units, this tube may need to be
extended, using the tubing shipped with the furnace.
Connections must be made to an OPEN/VENTED DRAIN.
Outdoor draining of the furnace and coil condensate is
permissible if allowed by local codes. Caution should be taken
to prevent drains from freezing or causing slippery conditions
that could lead to personal injury. Excessive draining of
condensate may cause saturated ground conditions that may
result in damage to plants.
NOTE:
Use 1/2" or larger PVC or CPVC pipe and fittings as required
for drain connections (fittings, pipe and solvent cement not
provided).
DOWNFLOW (VERTICAL)
Use CPVC tubing from Trap outlet,
over burner box to cabinet exit
DOWNFLOW (VERTICAL)
Right
side
NOTE:
A corrosion resistant condensate pump must be used if a
pump is required for a specific drain system.
IMPORT ANT:
The condensate drain should be installed with provisions to
prevent winter freeze-up of the condensate drain line. Frozen
condensate will block drains, resulting in furnace shutdown. If
the drain line cannot be installed in a conditioned space, then
UL listed heat tape should be applied as required to prevent
freezing (per manufacturer’s instructions). The heat tape should
be rated at 5 or 6 watts per foot at 120 volts. Self-regulating
(preferred) or thermostatically controlled heat tape is required.
Evaporator and furnace condensate drain piping may be
manifolded together. A primary drain vent stack must be
installed and terminated below the outlet of the secondary
heat exchanger drain connection to prevent water from
damaging furnace controls if the primary drain outlet plugs
up. Where the furnace is installed above a finished ceiling,
the primary drain vent stack must be installed such that
overflow from the vent stack opening will flow into an
auxillary drain pan in order to prevent water damage to the
finished ceiling below.
2218-CD22D1-5
Page 23
ELECTRICAL CONNECTIONS
Make wiring connections to the unit as indicated on
enclosed wiring diagram. As with all gas appliances using
electrical power, this furnace shall be connected into a
permanently live electric circuit. It is recommended that
furnace be provided with a separate “circuit protection
device” in the electric circuit. The furnace must be electrically grounded in accordance with local codes or in the
absence of local codes with the National Electrical Code,
ANSI/NFPA 70 or CSA C22.1 Electrical Code, if an
external electrical source is utilized. The integratedfurnace control is polarity sensitive. The hot leg of the
120V power supply must be connected to the black power
lead as indicated on the wiring diagram. Provision for
hooking up an electronic air cleaner and or humidifier is
provided on the integrated control.
Refer to the SERVICE FACTS literature and unit wiring
diagram attached to furnace diagram attached to furnace.
TWINNING FURNACES
These furnaces may be twinned. Twinning requires that
two furnaces with the same configuration, capacity, and
airflow must be used. They shall have common returns
with equal pressure drops or ducts with equivalent
lengths and sizes. See Field Wiring Diagrams for proper
hookup.
Installer’s Guide
If upflow furnace is installed
over a finished ceiling, overflow
from the primary drain vent
stack must flow into an auxillary
drain pan to prevent damage to
the finished ceiling below.
TO 115 V 1 PH.,
60 HZ., POWER
SUPPLY PER
LOCAL CODES
HUM SEE
NOTE 5
OUTDOOR UNIT
(NO TRANSFORMER)
EAC SEE
NOTE 5
FIELD WIRING DIAGRAM FOR 1 STAGE FURNACE
1 STAGE HEATING, 1 STAGE COOLING
USING A 1 STAGE HEATING, 1 STAGE COOLING THERMOSTAT
(OUTDOOR SECTION WITHOUT TRANSFORMER)
FURNACE
SEE
NOTE 6
SEE
B/C
NOTE 8
B/C
TO 115 V 1 PH.,
60 HZ., POWER
SUPPLY PER
LOCAL CODES
From drawing B341437 Rv 1
HUM SEE
NOTE 5
EAC SEE
NOTE 5
From drawing B340388 Rv 2
2418-CD22D1-5
Page 25
TWINNING CONNECTION DIAGRAM
FOR TWINNING 1 STAGE FURNACES WITH
1 STAGE HEAT
ONLY
THERMOSTAT
(WITH FAN SWITCH)FURNACE NO. 1
SINGLE WIRE TWINNING FEA TURE
1 STAGE HEATING ONLY THERMOSTAT
TWIN
ISOLATION RELAY
(FIELD SUPPLIED)
SEE NOTE 4
FURNACE NO. 2
BLOWER OPERATION OF
UNIT NO. 2 IS SYNCRONIZED
WITH UNIT NO. 1 VIA SIGNALS
FROM TWIN CONNECTION.
TWIN
SEE NOTE 4
Installer’s Guide
B/C
OUTDOOR UNIT
(WITH TRANSFORMER)
RC
ISOLATION RELAY
(FIELD SUPPLIED)
SEE NOTE 3
OUTDOOR UNIT
(NO TRANSFORMER)
SEE NOTE 3
R1
B/C
TWINNING CONNECTION DIAGRAM
FOR TWINNING 1 STAGE FURNACES WITH
SINGLE WIRE TWINNING FEATURE
1 STAGE
HEATING / COOLING
THERMOSTATFURNACE NO. 1
1 STAGE HEAT / 1 STAGE COOL THERMOSTAT
TWIN
B/C
R1
ISOLATION RELAY
FURNACE NO. 2
BLOWER OPERATION OF
UNIT NO. 2 IS SYNCRONIZED
WITH UNIT NO. 1 VIA SIGNALS
FROM TWIN CONNECTION.
TWIN
SEE NOTE 4
SEE NOTE 4
From Dwg. 21B341422 Rev. 3
R1
ISOLATION RELAY
SEE NOTE 4
R1
ISOLATION RELAY
(FIELD SUPPLIED)
SEE NOTE 4
B/C
From Dwg. 21B341423 Rev. 2
B/C
SEE NOTE 5
B/C
18-CD22D1-525
Page 26
Installer’s Guide
Refer to piping Table 10, for delivery sizes. Connect gas supply
to the unit, using a ground joint union and a manual shut-off
valve as shown in Figures 34-36.
National codes require a condensation drip leg to be installed
ahead of the controls as shown in Figures 34-36.
The furnace and its individual shut-off valve must be disconnected from the gas supply piping system during any pressure
testing of that system at test pressures in excess of 1/2 psig
(3.5 kPa).
The furnace must be isolated from the gas supply piping by
closing its individual manual shut-off valve during any pressure
testing of the gas supply piping system at test pressures equal
to or less than 1/2 psig (3.5 kPa).
NOTE:
Maximum pressure to the gas valve for natural gas is
13.8" W.C. Minimum pressure is 5.0" W.C. Maximum pressure to the gas valve for propane is 13.8" W.C.
Minimum pressure is 1 1.0" W.C.
v
MAIN MANUAL
SHUTOFF VALVE
GROUND
UNION
JOINT
AUTOMATIC GAS VALVE
WITH MANUAL SHUTOFF
All gas fittings must be checked for leaks using a soapy
solution before lighting the furnace.
DO NOT CHECK WITH
AN OPEN FLAME!
!
CAUTION
▲
Use a backup wrench on the gas valve when installing gas
piping to prevent damage to the gas valve and manifold
assembly.
TABLE 10
NATURAL GAS ONLY
TABLE OF CUBIC FEET PER HOUR OF GAS
FOR VARIOUS PIPE SIZES AND LENGTHS
PIPE
SIZE
1/2132927363565046
3/427819015213011510596
1-1/41050730590520440400370
This table is based on pressure drop of 0.3 inch W.C. and 0.6 SP.GR. gas
10203040506070
1520350285245215195180
AUTOMATIC GAS VALVE
WITH MANUAL SHUTOFF
LENGTH OF PIPE
MAIN MANUAL
SHUTOFF VALVE
GROUND
UNION
JOINT
DRIP
LEG
b
DRIP
LEG
UPFLOW – LEFT HAND GAS PIPING
UPFLOW – RIGHT HAND GAS PIPING
THE DOWNFLOW (VERTICAL) MAY BE INST ALLED LEFT OR RIGHT SIDE GAS PIPING
2618-CD22D1-5
Page 27
Installer’s Guide
n
AUTOMATIC GAS VALVE
WITH MANUAL SHUTOFF
MAIN MANUAL
SHUTOFF VALVE
GROUND
UNION JOINT
DRIP
LEG
HORIZONT AL FURNACE GAS PIPING MAY BE FROM EITHER SIDE (UPFLOW SHOWN)
TABLE 11
ORIFICE SIZES
INPUT
RATING
BTUH
40,000
60,000
80,000
100,000
120,000
COMBUSTION AND INPUT CHECK
1. Make sure all gas appliances are off except the furnace.
2. Clock the gas meter with the furnace operating (determine
the dial rating of the meter) for one revolution.
3. Match the “Sec” column in the gas flow (in cfh) Table 13
with the time clocked.
4. Read the “Flow” column opposite the number of seconds
clocked.
5. Use the following factors
For 1 Cu. Ft. Dial Gas Flow CFH =
For 1/2 Cu Ft. Dial Gas Flow CFH =
For 5 Cu. Ft. Dial Gas Flow CFH =
6. Multiply the final figure by the heating value of the gas
obtained from the utility company and compare to the
nameplate rating. This must not exceed the nameplate
rating.
7. Changes can be made by adjusting the manifold pressure
or changing orifices (orifice change may not always be
required). To adjust the manifold pressure:
a. Turn off all electrical power to the system.
b. Attach a manifold pressure gauge to the outlet pressure
tap marked "OUT PRESS TAP" on White-Rodgers gas
valve model 36F or boss marked "OUT P" on WhiteRodgers gas valve model 36G. (See Figure 39 for
White-Rodgers gas valve model 36F and Figure 40 for
White-Rodgers gas valve model 36G.). For the gas
valve model 36F, measurement requires removal of the
NUMBER
OF
BURNERS
2
3
4
5
6
MAIN BURNER ORIFICE
DRILL SIZE
NAT. GASLP GAS
45
45
45
45
45
if necessary:
Chart Flow Reading ÷2
Chart Flow Reading ÷4
10X Chart Flow Reading ÷4
56
56
56
56
56
MAIN MANUAL
SHUTOFF VALVE
AUTOMATIC GAS VALVE
WITH MANUAL SHUTOFF
plug and installation of a barbed fitting. Attach flexible
tubing and a manometer to the barbed fitting. For the
gas valve model 36G, do not remove the pressure tap
test screw. Using a 3/32" hex wrench, loosen the
pressure tap test screw one turn and install 5/16"
flexible tubing and a manometer directly onto the outlet
pressure boss.
c. Turn on system power and energize valve.
d. Remove the regulator adjustment screw cap on the
gas valve for manifold pressure adjustment.
e. Turn the adjustment nut clockwise to increase the gas
flow rate, and counter-clockwise to decrease the gas
flow rate using a 3/32" hex wench.
f. The final manifold pressure setting shall be as specified
in Table 12 with an input of no more than nameplate
rating and no less than 93% of the nameplate rating,
unless the unit is derated for high altitude.
g. Replace the regulator adjustment screw cap and
tighten securely.
h. Turn off all electrical power to the system.
i. Remove the manometer and flexible tubing. Remove
the barbed futting and replace the plug or tighten the
pressure test screw.
j. Turn on electrical power to the system and energize
valve.
k. Using a leak detection solution or soap suds, check for
leaks at plug or pressure boss screw.
!
▲
Replace and/or tighten all plugs removed or loosened when
adjusting gas pressure. Leak check the fittings before
placing the furnace into regular service. Failure to follow
this warning could result in fire, explosion, or property
damage.
GROUND UNION JOINT
DRIP
LEG
CAUTION
NOTE:
The manifold pressure must be referenced to the burner
box. The burner box pressure tap equalizes the gas valve
pressure regulator. Manifold pressure is checked by
installing a tee (field supplied) in the tubing, between the tee
coming from the burner box tube and the gas valve,
in
addition to the regular gas valve pressure tap on the outlet
side of the gas valve. See Figure 37.
18-CD22D1-527
Page 28
Installer’s Guide
m
!
CAUTION
▲
Replace manifold pressure tap threaded plug and leak
check after checking/adjusting manifold gas pressure.
Table 11 lists the main burner orifices used with the furnace. If a
change of orifices is required to correct the furnace input rating
refer to Table 14.
TABLE 12
FINAL MANIFOLD PRESSURE SETTINGS
FUELPRESSURE
NATURAL GAS3.5" W.C.
LP GAS11.0" W.C.
HIGH ALTITUDE DERATE
Input ratings (BTUH) of these furnaces are based on sea level
operation and should not be changed at elevations up to 2,000
ft.
If the installation is 2,000 ft. or above, the furnace input rate
(BTUH) shall be reduced 4% for each 1,000 ft. above sea level.
The furnace input rate shall be checked by clocking the gas
flow rate (CFH) and multiplying by the heating value obtained
from the local utility supplier for the gas being delivered at the
installed altitude. Input rate changes can be made by adjusting
the manifold pressure (min 3.0 - max 3.7 in. W.C. - Natural Gas)
or changing orifices (orifice change may not always be required). If the desired input rate can not be achieved with a
change in manifold pressure, then the orifices must be
changed. LP installations will require an orifice change.
IMPORT ANT:
Re-install the propane orifices to the same depth as the
orifices supplied with th equipment.
See Table 15 for help in selecting orifices if orifice change is
required. Furnace input rate and temperature rise should be
checked again after changing orifices to confirm the proper rate
for the altitude.
Installations above 4,000 feet may require a pressure switch
change. If required, use the BAYHALT*** Kit (High Altitude
Accessory Kit) listed in PRODUCT DATA.
Figure 50 shows the correct way to reinstall the burner box
cover if adjustment or replacement of the flame sensor, hot
surface igniter, or main burner orifices have required removal of
the cover.
TABLE 15
Orifice
Twist Dri ll
Size If
Installed
At Sea
Level
42
43
44
45
46
47
54
55
56
57
58
2000 3000 4000 5000 6000 7000 8000 9000 10000
42
44
45
46
47
48
54
55
56
58
59
From National Fuel Gas Code - Table F-4
ALTITUDE ABOVE SEA LEVEL
and Orifice Require d At Ot her El evations
46
45
44
44
43
43
43
44
44
45
45
47
47
47
47
49
48
55
55
55
55
57
56
59
59
60
60
!
WARNING
▲
45
46
47
48
49
55
56
57
60
61
45
47
48
48
49
55
56
57
60
62
46
47
48
49
50
55
56
58
61
62
47
48
49
49
50
56
56
59
62
63
47
48
49
50
51
56
56
59
63
63
47
48
50
50
51
52
56
57
60
63
64
CARBON MONOXIDE POISONING HAZARD
Failure to follow the installation instructions for the venting
system being placed into operation could result in carbon
monoxide poisoning or death.
START UP AND ADJUSTMENT
PRELIMINARY INSPECTIONS
With gas and electrical power “OFF”
1. Duct connections are properly sealed
2. Filters are in place
3. Venting is properly assembled
4. Blower door is in place
Flip the switch on main gas valve within the unit to the “OFF”
position. Turn the external gas valve to “ON”. Purge the air from
the gas lines. After purging, Check all gas connections for leaks
with a soapy solution — DO NOT CHECK WITH AN OPENFLAME. Allow 5 minutes for any gas that might have escaped
to dissipate. LP Gas being heavier than air may require forced
ventilation. Flip the switch on the gas valve in the unit to the
“ON” position.
LIGHTING INSTRUCTIONS
!
WARNING
▲
DO NOT attempt to manually light the burner. Failure to
follow this warning could result in property damage, personal injury or death.
Lighting instructions appear on each unit. Each installation
must be checked out at the time of initial start up to insure
proper operation of all components. Check out should include
putting the unit through one complete cycle as outlined below.
Turn on the main electrical supply and set the thermostat above
the indicated temperature. The ignitor will automatically heat,
then the gas valve is energized to permit the flow of gas to the
burners. After ignition and flame is established, the flame
control module monitors the flame and supplies power to the
gas valve until the thermostat is satisfied.
To shut off.
For complete shut-down: Flip the switch on the main gas valve
to the “OFF” position, (See Figure 39 & 40). Disconnect the
electrical supply to the unit.
!
CAUTION
▲
If this is done during the cold weather months, provisions
must be taken to prevent freeze-up of all water pipes and
water receptacles. Failure to follow this warning could result
in property damage.
Whenever your house is to be vacant, arrange to have
someone inspect your house for proper temperature. This is
very important during freezing weather. If for any reason
your furnace should fail to operate damage could result,
such as frozen water pipes.
SEQUENCE OF OPERA TION
Thermostat call for heat
R and W thermostat contacts close signaling the control
module to run its self-check routine. After the control module
has verified that the pressure switch contacts are open and the
limit switch(es) contacts are closed, the draft blower will be
energized.
As the induced draft blower comes up to speed, the pressure
switch contacts will close and the ignitor warm up period will
begin. The ignitor will heat for approximately 20 seconds, then
the gas valve is energized to permit gas flow to the burners. The
flame sensor confirms that ignition has been achieved.
After the flame sensor confirms within a 4 second trial period
that ignition has been achieved, the delay to fan ON period
begins timing. After approximately 45 seconds the indoor
blower motor will be energized and continue to run during the
18-CD22D1-529
heating cycle.
Page 30
Installer’s Guide
Swi
ch
Outlet Pressure Boss
Swi
ch
let Pressure
Boss
.)
tor
Adj
ust
.
Inlet Pressure
Boss
(opt.)
/
Outlet Pressure Boss
On/Offff Swi
White-Rodgers 36G gas valve
On/Offff Swi
tch
tch
Regululator
Adj
ust
When the thermostat is satisfied, R and W thermostat contacts
open, the gas valve will close, the flames will extinguish, and
the induced draft blower will be de-energized. The indoor
blower motor will continue to run for the fan off period (Field
selectable at 60, 100, 140 or 180 seconds), then be deenergized by the control module.
CONTROL AND SAFETY SWITCH ADJUSTMENTS
LIMIT SWITCH CHECK OUT
The limit switch is a safety device designed to close the gas
valve should the furnace become overheated. Since proper
operation of this switch is important to the safety of the unit, it
must be checked out on initial start up by the installer.
To check for proper operation of the limit switches, set the
thermostat to a temperature higher than the indicated temperature to bring on the gas valve. Restrict the airflow by blocking
the return air (disconnecting the indoor blower may trip the
inducer limit). When the furnace reaches the maximum outlet
temperature as shown on the rating plate, the burners must
shut off. If they do not shut off after a reasonable time and overheating is evident, a faulty limit switch is probable and the limit
switch must be replaced. After checking the operation of the
limit control, be sure to remove the paper or cardboard from the
return air inlet. Refer to Service Facts for additional instructions.
NOTE TO INST ALLER
Review the following warnings with the owner. Review contents
of USER’S INFORMATION MANUAL with the owner.
AIRFLOW ADJUSTMENT
Check inlet and outlet air temperatures to make sure they are
within the ranges specified on the furnace rating nameplate. If
the airflow needs to be increased or decreased, see the wiring
diagram for information on changing the speed of the blower
motor.
White-Rodgers 36F gas valve
!
CAUTION
▲
If this is done during the cold weather months, provisions
must be taken to prevent freeze-up of all water pipes and
water receptacles. Failure to follow this warning could result
in property damage.
Whenever your house is to be vacant, arrange to have
someone inspect your house for proper temperature. This is
very important during freezing weather. If for any reason
your furnace should fail to operate damage could result,
such as frozen water pipes.
SEQUENCE OF OPERATION
Thermostat call for heat
R and W thermostat contacts close signaling the control
module to run its self-check routine. After the control module
has verified that the pressure switch contacts are open and the
limit switch(es) contacts are closed, the draft blower will be
energized.
As the induced draft blower comes up to speed, the pressure
switch contacts will close and the ignitor warm up period will
begin. The ignitor will heat for approximately 20 seconds, then
the gas valve is energized to permit gas flow to the burners. The
flame sensor confirms that ignition has been achieved.
After the flame sensor confirms within a 4 second trial period
that ignition has been achieved, the delay to fan ON period
begins timing. After approximately 45 seconds the indoor
blower motor will be energized and continue to run during the
heating cycle.
!
WARNING
▲
Disconnect power to the unit before removing the blower
door. Failure to follow this warning could result in property
damage, personal injury or death.
This unit is equipped with a blower door switch which cuts
power to the blower and gas valve causing shutdown when the
door is removed. Operation with the door removed or ajar can
permit the escape of dangerous fumes. All panels must be
securely closed at all times for safe operation of the furnace.
INDOOR BLOWER TIMING
Heating: The integrated furnace control module controls the
indoor blower. The blower start is fixed at 45 seconds after
ignition. The FAN-OFF period is field selectable by dip switches
at 60, 100, 140, or 180 seconds. The factory setting is 100
seconds (See wiring diagram).
Cooling: The fan delay off period is factory set at 0 seconds.
The option for 80 second delay off is field selectable (See
wiring diagram).
ROOM AIR THERMOSTA T
HEAT ANTICIPATOR ADJUSTMENT
Set the thermostat heat anticipator according to the current flow
measured, or the settings found in the notes on the furnace
wiring diagram (found in the SERVICE FACTS or inside the
furnace casing).
3018-CD22D1-5
Page 31
Installer’s Guide
INSTRUCTIONS TO THE OWNERS
In the event that electrical, fuel, or mechanical failures
occur, the owner should immediately turn the gas supply off
at the manual gas valve, located in the burner compartment.
Also turn off electrical power to the furnace and contact the
service agency designated by your dealer.
BURNER BOX TEMPERA TURE LIMIT DEVICE
All models are equipped with a manual reset temperature limit
located on the burner box. In case of excessive temperature,
the limit will open and cause the circuit to open which shuts off
all flow of gas.
ABNORMAL CONDITIONS
1. EXCESSIVE COMBUSTION PRESSURE (WIND IN
EXCESS OF 40 M.P.H.) VENT OR FLUE BLOCKAGE
If pressure against induced draft blower outlet becomes
excessive, the pressure switch will open and shut off the
gas valve until acceptable combustion pressure is again
available.
2. LOSS OF FLAME
If loss of flame occurs during a heating cycle, or flame is
not present at the sensor, the flame control module will
close the gas valve. The flame control module will then
recycle the ignition sequence, then if ignition is not
achieved, it will shut off the gas valve and lock out the
system.
3. POWER FAILURE
If there is a power failure during a heating cycle, the
system will restart the ignition sequence automatically
when power is restored if the thermostat still calls for heat.
4. GAS SUPPLY FAILURE
If loss of flame occurs during a heating cycle, the system
integrated control module will re-cycle the ignition sequence, then if ignition is not achieved, the integrated
control module will shut off the gas valve and lock out the
system.
5. INDUCED DRAFT BLOWER FAILURE
If pressure is not sensed by the pressure switch, the
contacts will remain open and not allow the gas valve to
open, therefore the unit will not start. If failure occurs during
a running cycle, the pressure switch contacts will open and
the gas valve will close to shut the unit down.
6. CONDENSATE DRAIN BLOCKAGE
If the condensate drain is blocked, either by debris,
improper draining, or by freezing condensate, the pressure
switch will sense the accumulation of condensate in the
furnace drain pan. The pressure switch contacts will open
and remain open, not allowing unit operation. The unit will
not operate until the condensate drain has been cleared,
and the condensate flows freely.
7. RESET AFTER LOCKOUT
When the integrated control module has shut the system
down and gone into lockout, the system must be manually
reset before the unit will restart. To reset, turn the system
power off, then on, then off and then on again within
30 seconds. This may be done at the unit’s power source
or at the thermostat.
The system will not reset unless the
procedure off-on-off-on is completed within 30 seconds.
8. RESET AFTER BURNER BOX LIMIT SHUTDOWN
If the furnace shuts down, one thing that can be checked is
the burner box temperature limit switch. It is located on the
bottom of the burner box. The vent and combustion air inlet
terminations should be checked for blockage. If blockage
exists, clear the problem and then the reset button may be
depressed. If there is no blockage of the terminations,
the limit switch must be reset by a qualified servicer.
Carbon monoxide, fire or smoke can cause serious bodily
injury, death, and/or property damage.
A variety of potential sources of carbon monoxide can be found
in a building or dwelling such as gas-fired clothes dryers, gas
cooking stoves, water heaters, furnaces and fireplaces. The
U.S. Consumer Product Safety Commission recommends that
users of gas-burning appliances install carbon monoxide
detectors as well as fire and smoke detectors per the manufacturers installation instructions to help alert dwelling occupants
of the presence of fire, smoke or unsafe levels of carbon
monoxide. These devises should be listed by Underwriters
Laboratories, Inc.
Carbon Monoxide Alarms, UL 2034
Standard,
CSA 6.19
Standards for Single and Multiple Station
or CSA International
Residential Carbon Monoxide Alarming Devices,
NOTE:
The manufacturer of your furnace does not test any detectors and makes no representations regarding any brand or
type of detector.
18-CD22D1-531
Page 32
INTEGRATED FURNACE CONTROL ERROR FLASH CODES
Flashing Slow ---Normal - No call for Heat
Flashing Fast ---N or mal - Cal l for Heat
Continuous ON ---Replace I FC
Continuous OFF ---Check Power
2 Flashes ---System Lockout (Retries or Recycles exceeded)
Draft Pressure Error - Possible problems:
3 Flashes ---
a) Venting pr oblem
b) Pressure switch problem
c) Inducer problem
4 Flashes ---Open Temperature Limit Circuit
5 Flashes ---Flame sensed when no flame should be present
6 Flashes ---115 volt AC power reversed, poor grounding or system voltage too low
7 Flashes ---Gas valve circuit error
8 Flashes ---Low flame sense signal
9 Flashes ---
Check Ignitor Circuit and Line "N" to 24VAC "Common" voltage (≤ 2 volts)
[possible grounding problem]
American Standard Inc.
6200 Troup Highway
Tyler, TX 75707
For more information contact
your local dealer (distributor)
Literature Order Number*
File Number18-CD22D1-5
Supersedes18-CD22D1-4
Stocking LocationPI Louisville & Webb/Mason-Houston
Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right
to change design and specifications without notice.
P.I.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.