Communicating
Upflow/Horizontal Left
Downflow/Horizontal Right
Direct/Non-Direct Vent
Variable Speed, Modulating
Condensing Gas Furnace
XC 95m
TUHMB060ACV3VB, TDHMB060BCV3VB
TUHMB080ACV3VB, TDHMB080ACV3VB
TUHMC100ACV4VB, TDHMC100ACV4VB
TUHMD120ACV5VB, TDHMD120BCV5VB
Direct or Non-Direct Vent with
Variable Speed Blower
Variable Speed Inducer
TDHM
UPFLOW
UPFLOW/HORIZONTAL
DOWNFLOW
DOWNFLOW/HORIZONTAL
PUB. NO. 22-1840-14
General
Features
MODULATING OPERATION
The modulating gas valves provides
longer heating cycles for more
consistent heating comfort. Modulates
from 40% (45% for the TUHMD120)
to 100% in less than 1% increments
of the furnace's heating capacity
saving energy, while at the same
time maximizing homeowner comfort.
COMMUNICATING MODE
Furnace is shipped ready to be
connected in communicating mode
using three wire hook-up using the
TZONE950 or the TCONT900 comfort
control.
ALTERNATE 24V MODE
Furnace is field configurable to 24V
non-communicating mode.
COMFORT CONTROL
Comfortlink IITM Communicating furnace
design, offers plug and play – walk away
installation. Assures the entire heating
and air conditioning system is set up
in the proper modes to optimize the
engineered performance of the matched
system installed. The furnace can also
be connected in conventional 24V mode.
NATURAL GAS MODELS
Central Heating furnace designs are certified by the American Gas Association
for both natural and L.P. gas. Limit setting
and rating data were established and approved under standard rating conditions
using American National Standards Institute standards.
SAFE OPERATION
The Integrated System Control has solid
state devices, which continuously monitor
for presence of flame, when the system
is in the heating mode of operation. Dual
solenoid combination gas valve and regulator provide additional safety.
transfers heat to provide warm conditioned air to the structure. Low energy power vent blower, to increase efficiency and provide a positive discharge of
gas fumes to the outside.
BURNERS
Multiport Inshot burners will give years of
quiet and efficient service. All models can
be converted to L.P. gas without chang-
ing burners.
INTEGRATED SYSTEM CONTROL
Exclusively designed operational program provides total control of furnace
limit sensors, blowers, gas valve, flame
control and includes self diagnostics for
ease of service. Also contains connection
points for EAC and Humidifier hookup.
AIR DELIVERY
The variable speed blower motor has
sufficient airflow for most heating and
cooling requirements and will switch from
heating to cooling speeds on demand
from room thermostat. The blower door
safety switch will prevent or terminate
furnace operation when the blower door
is removed.
SECONDARY HEAT EXCHANGER
The XC95m has a special type 29-4C™
stainless steel secondary heat exchanger to reclaim heat from flue gases which
would normally be lost.
STYLING
Heavy gauge steel and “wrap-around”
cabinet construction is used in the
cabinet with baked-on enamel finish for
strength and beauty. The heat exchanger section of the cabinet is completely
lined with foil faced fiberglass insulation.
This results in quiet and efficient operation due to the excellent acoustical and
insulating qualities of fiberglass. Built-in
bottom pan and alternate bottom, left or
right side return air connection provision.
FEATURES AND GENERAL
OPERATION
The XC95m High Efficiency Gas Furnaces utilize an Adaptive Heat Up Silicon
Nitride Hot Surface Ignition system, which
eliminates the waste of a constant burning pilot. The integrated system control
lights the main burners upon a demand
for heat from the room thermostat. Complete front service access.
a. Low energy power venter
b. Vent proving pressure switch.
Ampacity (In Amps)
Max. Overcurrent Protection (Amps)
PIPE CONN. SIZE (IN.)
DIMENSIONS
Crated (In.)
WEIGHT
Shipping (Lbs.) / Net (Lbs)
TUHMB060ACV3VB 7
Upflow/ Horizontal Left
24,000
23,352
60,000
58,380
35 - 65
97.3
DIRECT
10 x 8
1
Variable
See Fan Performance Table
1/2
Variable
115/1/60
5.2 - 6.2 8
Centrifugal
Direct - Variable
1/50 - 5000
115/3/60
1.0
Ye s
High Velocity
1 - 17x25 - 1 in.
2 Round
Aluminized Steel - Type I
20
3 — 45
3 — 56
Redundant - Three Stage
Hot Surface Igniter
Multiport Inshot
3
115/1/60
8.8
15
1/2
H x W x D
41-3/4 x 19-1/2 x 30-1/2
158 / 146
TUHMB080ACV3VB 7
Upflow/ Horizontal Left
32,000
30,944
80,000
77,360
35 - 65
96.7
DIRECT
10 x 8
1
Variable
See Fan Performance Table
1/2
Variable
115/1/60
5.2 - 6.2 8
Centrifugal
Direct - Variable
1/50 - 5000
115/3/60
1.0
Ye s
High Velocity
1 - 17x25 - 1 in.
2 Round
Aluminized Steel - Type I
20
4 — 45
4 — 56
Redundant - Three Stage
Hot Surface Igniter
Multiport Inshot
4
115/1/60
8.8
15
1/2
H x W x D
41-3/4 x 19-1/2 x 30-1/2
168 / 156
TUHMC100ACV4VB
Upflow/ Horizontal Left
40,000
38,400
100,000
96,000
35 - 65
96.0
DIRECT
10 x 10
1
Variable
See Fan Performance Table
1
Variable
115/1/60
7.4
Centrifugal
Direct - Variable
1/50 - 5000
115/3/60
1.0
Ye s
High Velocity
1 - 20x25 - 1 in.
2.5 Round
Aluminized Steel - Type I
20
5 — 45
5 — 56
Redundant - Three Stage
Hot Surface Igniter
Multiport Inshot
5
115/1/60
10.4
15
1/2
H x W x D
41-3/4 x 23 x 30-1/2
197 / 185
TUHMD120ACV5VB 7
Upflow/ Horizontal Left
54,000
52,380
120,000
116,400
40 - 70
97.0
DIRECT
10 x 10
1
Variable
See Fan Performance Table
1
Variable
115/1/60
9.9
Centrifugal
Direct - Variable
1/50 - 5000
115/3/60
1.0
Ye s
High Velocity
1 - 24x25 - 1 in.
3 Round
Aluminized Steel - Type I
20
6 — 45
6 — 56
Redundant - Three Stage
Hot Surface Igniter
Multiport Inshot
6
115/1/60
13.5
15
1/2
H x W x D
41-3/4 x 26-1/2 x 30-1/2
206 / 193
1 CentralFurnaceheatingdesignsarecertiedtoANSIZ21.47/CSA2.3.
2 For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea level.
For Canadian applications, above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above sea level.
3 Based on U.S. government standard tests.
4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.
5 Furnace ships in natural gas configuration. The LP conversion kit used with the modulating furnace is BAYLPSS220B or BAYLPKT220B.
6 45%(low)heatfor*UHM1D120ACV5VB.
7 Energy Star
8 Check motor nameplate for actual FLA
Ampacity (In Amps)
Max. Overcurrent Protection (Amps)
PIPE CONN. SIZE (IN.)
DIMENSIONS
Crated (In.)
WEIGHT
Shipping (Lbs.) / Net (Lbs)
TDHMB060BCV3VB 6
Downflow / Horizontal Right
24,000
22,800
60,000
57,000
30 - 60
95.0
DIRECT
10 x 8
1
Variable
See Fan Performance Table
1/2
Variable
115/1/60
5.2
Centrifugal
Direct - Variable
1/50 - 5000
115/3/60
1.0
Ye s
High Velocity
2 - 14x20 - 1 in.
2 Round
Aluminized Steel - Type I
20
3 — 45
3 — 56
Redundant - Three Stage
Hot Surface Igniter
Multiport Inshot
3
115/1/60
7.7
15
1/2
H x W x D
41-3/4 x 19-1/2 x 30-1/2
160/ 146
TDHMC080ACV3VB 6
Downflow / Horizontal Right
32,000
30,400
80,000
76,000
35 - 65
96.0
DIRECT
10 x 8
1
Variable
See Fan Performance Table
1/2
Variable
115/1/60
5.2 - 6.2 7
Centrifugal
Direct - Variable
1/50 - 5000
115/3/60
1.0
Ye s
High Velocity
2 - 14x20 - 1 in.
2 Round
Aluminized Steel - Type I
20
4 — 45
4 — 56
Redundant - Three Stage
Hot Surface Igniter
Multiport Inshot
4
115/1/60
8.8
15
1/2
H x W x D
41-3/4 x 19-1/2 x 30-1/2
168 / 158
TDHMC100ACV4VB
Downflow / Horizontal Right
40,000
38,400
100,000
96,000
35 - 65
96.0
DIRECT
10 x 10
1
Variable
See Fan Performance Table
3/4
Variable
115/1/60
7.4
Centrifugal
Direct - Variable
1/50 - 5000
115/3/60
1.0
Ye s
High Velocity
2 - 16x20 - 1 in.
2.5 Round
Aluminized Steel - Type I
20
5 — 45
5 — 56
Redundant - Three Stage
Hot Surface Igniter
Multiport Inshot
5
115/1/60
10.4
15
1/2
H x W x D
41-3/4 x 23 x 30-1/2
185 / 175
TDHMD120BCV5VB 6
Downflow / Horizontal Right
48,000
45,600
120,000
114,000
40 - 70
95.0
DIRECT
10 x 10
1
Variable
See Fan Performance Table
1
Variable
115/1/60
9.9
Centrifugal
Direct - Variable
1/50 - 5000
115/3/60
1.0
Ye s
High Velocity
2 - 16x20 - 1 in.
3 Round
Aluminized Steel - Type I
20
6 — 45
6 — 56
Redundant - Three Stage
Hot Surface Igniter
Multiport Inshot
6
115/1/60
13.5
15
1/2
H x W x D
41-3/4 x 26-1/2 x 30-1/2
206 / 196
1 CentralFurnaceheatingdesignsarecertiedtoANSIZ21.47/CSA2.3.
2 For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea level.
For Canadian applications, above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above sea level.
3 Based on U.S. government standard tests.
4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.
5 Furnace ships in natural gas configuration. The LP conversion kit used with the modulating furnace is BAYLPSS220B or BAYLPKT220B.
6 Energy Star
7 Check motor nameplate for actual FLA
Pub. No. 22-1840-14
7
TUHM AIRFLOW - HEATING
0.10.30.50.70.9
CFM393504512546560
Temp. Rise7357565351
Watts4381112142140
CFM435541549580593
Temp. Rise6653525049
Watts4686119150148
CFM472573580609621
Temp. Rise6150504746
Watts5090125159155
CFM545636644667676
Temp. Rise5345454343
Watts60103141177169
CFM565653660682691
Temp. Rise6859585756
Watts64107145182172
CFM622703710727734
Temp. Rise6255545353
Watts75120161199183
CFM671745752766771
Temp. Rise5852515050
Watts86133175215192
CFM769831837843846
Temp. Rise5046464646
Watts114164210250211
CFM791849856861862
Temp. Rise6561606060
Watts121171219258215
CFM867916922921920
Temp. Rise5956565656
Watts148201251290230
CFM932972979973970
Temp. Rise5553535353
Watts174229282319243
CFM10631086109210761069
Temp. Rise4847474848
Watts236295353384268
100%
(high)
Heat
Low
830
Medium Low
900
Medium**
960
High
1080
65%
(medium)
Heat
Low
623
Medium Low
675
Medium**
720
High
810
Medium Low
504
Medium**
538
High
605
Heating
*UHMB060ACV3VB^ Furnace Heating Airflow (CFM) and Power (watts) vs. External Static Pressure With Filter
Airflow
Setting
Target Airflow
(See Note 5)
External Static Pressure
40%
(low)
Heat
Low
465
0.10.30.50.70.9
CFM512564581538572
Temp. Rise7063626662
Watts4577112109146
CFM586634649606634
Temp. Rise6156555956
Watts5790129127177
CFM661704717673696
Temp. Rise5451505351
Watts71106148146207
CFM772809819774789
Temp. Rise4644444645
Watts99136184176253
CFM757794805760776
Temp. Rise6763636665
Watts95132179172246
CFM862893901855864
Temp. Rise5956565958
Watts127165217202289
CFM967992997951951
Temp. Rise5251515353
Watts165205262235332
CFM11251139114110931083
Temp. Rise4544444647
Watts233276341288395
CFM10841101110410561048
Temp. Rise6564636667
Watts214256319273379
CFM12301238123711881170
Temp. Rise5757575960
Watts286331401325437
CFM13761375137013201292
Temp. Rise5151515354
Watts369418495381496
CFM15951580157015191474
Temp. Rise4444454648
Watts398470522522529
Target Airflow
(See Note 5)
External Static Pressure
40%
(low)
Heat
Low
571
Medium Low
643
Medium**
714
High
821
65%
(medium)
Heat
Low
806
Medium Low
907
Medium**
1008
High
1159
Heating
*UHMB080ACV3VB^ Furnace Heating Airflow (CFM) and Power (Watts) vs. External Static Pressure With Filter
Airflow
Setting
100%
(high)
Heat
Low
1120
Medium Low
1260
Medium**
1400
High
1610
Notes:
1. * First letter may be "A" or "T".
3. ** Factory setting.
2. ^ Letter may be “A” through “Z”.
4. Continuous Fan Setting: Heating or cooling airflow is approximately 50% of selected
cooling value.
5. LOW 350 cfm/ton is recommended for variable speed application for COMFORT & HUMID
CLIMATE setting; NORMAL is 400 cfm/ton; HIGH 450 cfm/ton is for DRY CLIMATE setting.
6. Target airflow is field selectable for high (100%) heat. Target airflow for low and medium
heat are percentages of high heat and are not field selectable.
8
Pub. No. 22-1840-14
TUHM AIRFLOW - HEATING
0.10.30.50.70.9
CFM592617623617606
Temp. Rise6159585960
Watts78109141173233
CFM626651655649639
Temp. Rise5856555657
Watts79110142175236
CFM660684688682671
Temp. Rise5553535354
Watts81111144177241
CFM732755757751739
Temp. Rise5048484849
Watts87115149185254
CFM10481065106010521038
Temp. Rise6059596061
Watts149169208252358
CFM11071123111611081094
Temp. Rise5756565758
Watts167186226271386
CFM11651181117311651150
Temp. Rise5453545455
Watts187204245292417
CFM12911304129312841269
Temp. Rise4948494950
Watts236250293343490
CFM14661476146114511435
Temp. Rise6059606061
Watts319330374430613
CFM15481556154015291512
Temp. Rise5756575758
Watts364373419476679
CFM16291637161816081590
Temp. Rise5454545455
Watts413419467527750
CFM18031807178517741755
Temp. Rise4948494950
Watts529532582646864
100%
(high)
Heat
Low
1460
Medium Low
1540
Medium**
1620
High
1790
High
1289
672
High
743
639
Medium**
Low
1051
Medium Low
1109
606
Medium**
1166
40%
(low)
Heat
Low
Heating
*UHMC100ACV4VB^ Furnace Heating Airflow (CFM) and Power (Watts) vs. External Static Pressure With Filter
Airflow
Setting
Target Airflow
(See Note 5)
External Static Pressure
Medium Low
65%
(medium)
Heat
0.10.30.50.70.9
CFM728758785805819
Temp. Rise6259575655
Watts11910710294108
CFM769797822840853
Temp. Rise5856545353
Watts113107111113133
CFM813841864880890
Temp. Rise5553525150
Watts108107122135160
CFM863889910923930
Temp. Rise5250494948
Watts104108135160191
CFM12131232123712321220
Temp. Rise6060596060
Watts131160253345405
CFM12791297129912901274
Temp. Rise5757565758
Watts147178281382445
CFM13531369136713551335
Temp. Rise5454545455
Watts168201313423489
CFM14341448144314261402
Temp. Rise5151515152
Watts197229352469538
CFM16991707169016591621
Temp. Rise6060606163
Watts325349495628698
CFM17901797177517401696
Temp. Rise5757575960
Watts382400551685752
CFM18921896187018301781
Temp. Rise5454545657
Watts453462616750813
CFM20042006197519291873
Temp. Rise5151525354
Watts540538694822880
100%
(high)
Heat
Low
1700
Medium Low
1790
Medium**
1890
High
2000
High
1440
832
High
880
788
Medium**
Low
1224
Medium Low
1289
748
Medium**
1361
45%
(low)
Heat
Low
Heating
*UHMD120ACV5VB^ Furnace Heating Airflow (CFM) and Power (Watts) vs. External Static Pressure With Filter
Airflow
Setting
Target Airflow
(See Note 5)
External Static Pressure
Medium Low
65%
(medium)
Heat
Notes:
1. * First letter may be "A" or "T".
3. ** Factory setting.
2. ^ Letter may be “A” through “Z”.
4. Continuous Fan Setting: Heating or cooling airflow is approximately 50% of selected
cooling value.
5. LOW 350 cfm/ton is recommended for variable speed application for COMFORT & HUMID
CLIMATE setting; NORMAL is 400 cfm/ton; HIGH 450 cfm/ton is for DRY CLIMATE setting.
6. Target airflow is field selectable for high (100%) heat. Target airflow for low and medium
heat are percentages of high heat and are not field selectable.
Pub. No. 22-1840-14
9
TUHM AIRFLOW - COOLING
0.10.30.50.70.9
CFM
356476488511519
Watts
296797132167
CFM
389504516538545
Watts
3271102138174
CFM
422533544565572
Watts
3675107144181
CFM
455561566589592
Watts
3979111150187
CFM
487589600619624
Watts
4384119158197
CFM
537631655669673
Watts
5092130171212
CFM
586674684700702
Watts
57101139182223
CFM
619695717727733
Watts
63106150193236
CFM
515613623641646
Watts
4788124164204
CFM
559650660677681
Watts
5396133175215
CFM
602688698713716
Watts
60104143186228
CFM
646707737748752
Watts
68112156200243
CFM
690763772785785
Watts
76123165211255
CFM
764816778847844
Watts
86137180231275
CFM
821876884892890
Watts
108159206256303
CFM
937968977985984
Watts
136193241295343
CFM
673749758771772
Watts
73119161206250
CFM
732791756766818
Watts
79129160203268
CFM
783843852861860
Watts
98147193242288
CFM
848894908917917
Watts
110163212262308
CFM
892937945951947
Watts
129182232284333
CFM
97210159729571036
Watts
160213262312374
CFM
10571078108510851078
Watts
191249306360415
CFM
11151137114211401139
Watts
214275333388447
CFM
832885894901899
Watts
111162210260308
CFM
898942950955951
Watts
131184234286336
CFM
964998100610091004
Watts
154209262314366
CFM
10391065107310741075
Watts
181237292344402
CFM
10951111111811161108
Watts
208268326380436
CFM
11891212121411491207
Watts
257320380435500
CFM
12921280128512781201
Watts
317383448501508
CFM
13261317136112421166
Watts
366433495510509
Notes:
1. * First letter may be "A" or "T".
2. ^ Letter may be "A" through "Z"
3. ** Factory setting.
4. Continuous Fan Setting: Heating or cooling airflow is approximately 50% of selected
cooling value.
5. LOW 350 cfm/ton is recommended for variable speed application for COMFORT & HUMID
CLIMATE setting; NORMAL is 400 cfm/ton; HIGH 450 cfm/ton is for DRY CLIMATE setting.
Cooling
Unit
Outdoor
Airflow
Setting
External Static Pressure
1.5
290 CFM/ton
310 CFM/ton
330 CFM/ton
350 CFM/ton
370 CFM/ton
400 CFM/ton
430 CFM/ton
450 CFM/ton
2
290 CFM/ton
310 CFM/ton
330 CFM/ton
350 CFM/ton
370 CFM/ton
400 CFM/ton
310 CFM/ton
330 CFM/ton
350 CFM/ton
370 CFM/ton
400 CFM/ton
430 CFM/ton
430 CFM/ton
450 CFM/ton
*UHMB060ACV3VB^ Furnace Cooling Airflow (CFM) and Power (Watts) vs. External Static
Pressure With Filter
450 CFM/ton
3
290 CFM/ton
310 CFM/ton
2.5
290 CFM/ton
330 CFM/ton
350 CFM/ton
370 CFM/ton
400 CFM/ton
430 CFM/ton
450 CFM/ton
10
NOTE:
CONTINUOUS fan mode during
COOLING operation may not be
appropriate in humid climates. If the
indoor air exceeds 60% relative humidity
or simply feels uncomfortably humid,
it is recommended that the fan only be
used in the AUTO mode.