Communicating
Upflow/Horizontal Left
Downflow/Horizontal Right
Direct/Non-Direct Vent
Variable Speed, Modulating
Condensing Gas Furnace
XC 95m
TUHMB060ACV3VB, TDHMB060BCV3VB
TUHMB080ACV3VB, TDHMB080ACV3VB
TUHMC100ACV4VB, TDHMC100ACV4VB
TUHMD120ACV5VB, TDHMD120BCV5VB
Direct or Non-Direct Vent with
Variable Speed Blower
Variable Speed Inducer
TDHM
UPFLOW
UPFLOW/HORIZONTAL
DOWNFLOW
DOWNFLOW/HORIZONTAL
PUB. NO. 22-1840-14
Page 2
General
Features
MODULATING OPERATION
The modulating gas valves provides
longer heating cycles for more
consistent heating comfort. Modulates
from 40% (45% for the TUHMD120)
to 100% in less than 1% increments
of the furnace's heating capacity
saving energy, while at the same
time maximizing homeowner comfort.
COMMUNICATING MODE
Furnace is shipped ready to be
connected in communicating mode
using three wire hook-up using the
TZONE950 or the TCONT900 comfort
control.
ALTERNATE 24V MODE
Furnace is field configurable to 24V
non-communicating mode.
COMFORT CONTROL
Comfortlink IITM Communicating furnace
design, offers plug and play – walk away
installation. Assures the entire heating
and air conditioning system is set up
in the proper modes to optimize the
engineered performance of the matched
system installed. The furnace can also
be connected in conventional 24V mode.
NATURAL GAS MODELS
Central Heating furnace designs are certified by the American Gas Association
for both natural and L.P. gas. Limit setting
and rating data were established and approved under standard rating conditions
using American National Standards Institute standards.
SAFE OPERATION
The Integrated System Control has solid
state devices, which continuously monitor
for presence of flame, when the system
is in the heating mode of operation. Dual
solenoid combination gas valve and regulator provide additional safety.
transfers heat to provide warm conditioned air to the structure. Low energy power vent blower, to increase efficiency and provide a positive discharge of
gas fumes to the outside.
BURNERS
Multiport Inshot burners will give years of
quiet and efficient service. All models can
be converted to L.P. gas without chang-
ing burners.
INTEGRATED SYSTEM CONTROL
Exclusively designed operational program provides total control of furnace
limit sensors, blowers, gas valve, flame
control and includes self diagnostics for
ease of service. Also contains connection
points for EAC and Humidifier hookup.
AIR DELIVERY
The variable speed blower motor has
sufficient airflow for most heating and
cooling requirements and will switch from
heating to cooling speeds on demand
from room thermostat. The blower door
safety switch will prevent or terminate
furnace operation when the blower door
is removed.
SECONDARY HEAT EXCHANGER
The XC95m has a special type 29-4C™
stainless steel secondary heat exchanger to reclaim heat from flue gases which
would normally be lost.
STYLING
Heavy gauge steel and “wrap-around”
cabinet construction is used in the
cabinet with baked-on enamel finish for
strength and beauty. The heat exchanger section of the cabinet is completely
lined with foil faced fiberglass insulation.
This results in quiet and efficient operation due to the excellent acoustical and
insulating qualities of fiberglass. Built-in
bottom pan and alternate bottom, left or
right side return air connection provision.
FEATURES AND GENERAL
OPERATION
The XC95m High Efficiency Gas Furnaces utilize an Adaptive Heat Up Silicon
Nitride Hot Surface Ignition system, which
eliminates the waste of a constant burning pilot. The integrated system control
lights the main burners upon a demand
for heat from the room thermostat. Complete front service access.
a. Low energy power venter
b. Vent proving pressure switch.
Ampacity (In Amps)
Max. Overcurrent Protection (Amps)
PIPE CONN. SIZE (IN.)
DIMENSIONS
Crated (In.)
WEIGHT
Shipping (Lbs.) / Net (Lbs)
TUHMB060ACV3VB 7
Upflow/ Horizontal Left
24,000
23,352
60,000
58,380
35 - 65
97.3
DIRECT
10 x 8
1
Variable
See Fan Performance Table
1/2
Variable
115/1/60
5.2 - 6.2 8
Centrifugal
Direct - Variable
1/50 - 5000
115/3/60
1.0
Ye s
High Velocity
1 - 17x25 - 1 in.
2 Round
Aluminized Steel - Type I
20
3 — 45
3 — 56
Redundant - Three Stage
Hot Surface Igniter
Multiport Inshot
3
115/1/60
8.8
15
1/2
H x W x D
41-3/4 x 19-1/2 x 30-1/2
158 / 146
TUHMB080ACV3VB 7
Upflow/ Horizontal Left
32,000
30,944
80,000
77,360
35 - 65
96.7
DIRECT
10 x 8
1
Variable
See Fan Performance Table
1/2
Variable
115/1/60
5.2 - 6.2 8
Centrifugal
Direct - Variable
1/50 - 5000
115/3/60
1.0
Ye s
High Velocity
1 - 17x25 - 1 in.
2 Round
Aluminized Steel - Type I
20
4 — 45
4 — 56
Redundant - Three Stage
Hot Surface Igniter
Multiport Inshot
4
115/1/60
8.8
15
1/2
H x W x D
41-3/4 x 19-1/2 x 30-1/2
168 / 156
TUHMC100ACV4VB
Upflow/ Horizontal Left
40,000
38,400
100,000
96,000
35 - 65
96.0
DIRECT
10 x 10
1
Variable
See Fan Performance Table
1
Variable
115/1/60
7.4
Centrifugal
Direct - Variable
1/50 - 5000
115/3/60
1.0
Ye s
High Velocity
1 - 20x25 - 1 in.
2.5 Round
Aluminized Steel - Type I
20
5 — 45
5 — 56
Redundant - Three Stage
Hot Surface Igniter
Multiport Inshot
5
115/1/60
10.4
15
1/2
H x W x D
41-3/4 x 23 x 30-1/2
197 / 185
TUHMD120ACV5VB 7
Upflow/ Horizontal Left
54,000
52,380
120,000
116,400
40 - 70
97.0
DIRECT
10 x 10
1
Variable
See Fan Performance Table
1
Variable
115/1/60
9.9
Centrifugal
Direct - Variable
1/50 - 5000
115/3/60
1.0
Ye s
High Velocity
1 - 24x25 - 1 in.
3 Round
Aluminized Steel - Type I
20
6 — 45
6 — 56
Redundant - Three Stage
Hot Surface Igniter
Multiport Inshot
6
115/1/60
13.5
15
1/2
H x W x D
41-3/4 x 26-1/2 x 30-1/2
206 / 193
1 CentralFurnaceheatingdesignsarecertiedtoANSIZ21.47/CSA2.3.
2 For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea level.
For Canadian applications, above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above sea level.
3 Based on U.S. government standard tests.
4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.
5 Furnace ships in natural gas configuration. The LP conversion kit used with the modulating furnace is BAYLPSS220B or BAYLPKT220B.
6 45%(low)heatfor*UHM1D120ACV5VB.
7 Energy Star
8 Check motor nameplate for actual FLA
Ampacity (In Amps)
Max. Overcurrent Protection (Amps)
PIPE CONN. SIZE (IN.)
DIMENSIONS
Crated (In.)
WEIGHT
Shipping (Lbs.) / Net (Lbs)
TDHMB060BCV3VB 6
Downflow / Horizontal Right
24,000
22,800
60,000
57,000
30 - 60
95.0
DIRECT
10 x 8
1
Variable
See Fan Performance Table
1/2
Variable
115/1/60
5.2
Centrifugal
Direct - Variable
1/50 - 5000
115/3/60
1.0
Ye s
High Velocity
2 - 14x20 - 1 in.
2 Round
Aluminized Steel - Type I
20
3 — 45
3 — 56
Redundant - Three Stage
Hot Surface Igniter
Multiport Inshot
3
115/1/60
7.7
15
1/2
H x W x D
41-3/4 x 19-1/2 x 30-1/2
160/ 146
TDHMC080ACV3VB 6
Downflow / Horizontal Right
32,000
30,400
80,000
76,000
35 - 65
96.0
DIRECT
10 x 8
1
Variable
See Fan Performance Table
1/2
Variable
115/1/60
5.2 - 6.2 7
Centrifugal
Direct - Variable
1/50 - 5000
115/3/60
1.0
Ye s
High Velocity
2 - 14x20 - 1 in.
2 Round
Aluminized Steel - Type I
20
4 — 45
4 — 56
Redundant - Three Stage
Hot Surface Igniter
Multiport Inshot
4
115/1/60
8.8
15
1/2
H x W x D
41-3/4 x 19-1/2 x 30-1/2
168 / 158
TDHMC100ACV4VB
Downflow / Horizontal Right
40,000
38,400
100,000
96,000
35 - 65
96.0
DIRECT
10 x 10
1
Variable
See Fan Performance Table
3/4
Variable
115/1/60
7.4
Centrifugal
Direct - Variable
1/50 - 5000
115/3/60
1.0
Ye s
High Velocity
2 - 16x20 - 1 in.
2.5 Round
Aluminized Steel - Type I
20
5 — 45
5 — 56
Redundant - Three Stage
Hot Surface Igniter
Multiport Inshot
5
115/1/60
10.4
15
1/2
H x W x D
41-3/4 x 23 x 30-1/2
185 / 175
TDHMD120BCV5VB 6
Downflow / Horizontal Right
48,000
45,600
120,000
114,000
40 - 70
95.0
DIRECT
10 x 10
1
Variable
See Fan Performance Table
1
Variable
115/1/60
9.9
Centrifugal
Direct - Variable
1/50 - 5000
115/3/60
1.0
Ye s
High Velocity
2 - 16x20 - 1 in.
3 Round
Aluminized Steel - Type I
20
6 — 45
6 — 56
Redundant - Three Stage
Hot Surface Igniter
Multiport Inshot
6
115/1/60
13.5
15
1/2
H x W x D
41-3/4 x 26-1/2 x 30-1/2
206 / 196
1 CentralFurnaceheatingdesignsarecertiedtoANSIZ21.47/CSA2.3.
2 For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea level.
For Canadian applications, above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above sea level.
3 Based on U.S. government standard tests.
4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.
5 Furnace ships in natural gas configuration. The LP conversion kit used with the modulating furnace is BAYLPSS220B or BAYLPKT220B.
6 Energy Star
7 Check motor nameplate for actual FLA
Pub. No. 22-1840-14
7
Page 8
TUHM AIRFLOW - HEATING
0.10.30.50.70.9
CFM393504512546560
Temp. Rise7357565351
Watts4381112142140
CFM435541549580593
Temp. Rise6653525049
Watts4686119150148
CFM472573580609621
Temp. Rise6150504746
Watts5090125159155
CFM545636644667676
Temp. Rise5345454343
Watts60103141177169
CFM565653660682691
Temp. Rise6859585756
Watts64107145182172
CFM622703710727734
Temp. Rise6255545353
Watts75120161199183
CFM671745752766771
Temp. Rise5852515050
Watts86133175215192
CFM769831837843846
Temp. Rise5046464646
Watts114164210250211
CFM791849856861862
Temp. Rise6561606060
Watts121171219258215
CFM867916922921920
Temp. Rise5956565656
Watts148201251290230
CFM932972979973970
Temp. Rise5553535353
Watts174229282319243
CFM10631086109210761069
Temp. Rise4847474848
Watts236295353384268
100%
(high)
Heat
Low
830
Medium Low
900
Medium**
960
High
1080
65%
(medium)
Heat
Low
623
Medium Low
675
Medium**
720
High
810
Medium Low
504
Medium**
538
High
605
Heating
*UHMB060ACV3VB^ Furnace Heating Airflow (CFM) and Power (watts) vs. External Static Pressure With Filter
Airflow
Setting
Target Airflow
(See Note 5)
External Static Pressure
40%
(low)
Heat
Low
465
0.10.30.50.70.9
CFM512564581538572
Temp. Rise7063626662
Watts4577112109146
CFM586634649606634
Temp. Rise6156555956
Watts5790129127177
CFM661704717673696
Temp. Rise5451505351
Watts71106148146207
CFM772809819774789
Temp. Rise4644444645
Watts99136184176253
CFM757794805760776
Temp. Rise6763636665
Watts95132179172246
CFM862893901855864
Temp. Rise5956565958
Watts127165217202289
CFM967992997951951
Temp. Rise5251515353
Watts165205262235332
CFM11251139114110931083
Temp. Rise4544444647
Watts233276341288395
CFM10841101110410561048
Temp. Rise6564636667
Watts214256319273379
CFM12301238123711881170
Temp. Rise5757575960
Watts286331401325437
CFM13761375137013201292
Temp. Rise5151515354
Watts369418495381496
CFM15951580157015191474
Temp. Rise4444454648
Watts398470522522529
Target Airflow
(See Note 5)
External Static Pressure
40%
(low)
Heat
Low
571
Medium Low
643
Medium**
714
High
821
65%
(medium)
Heat
Low
806
Medium Low
907
Medium**
1008
High
1159
Heating
*UHMB080ACV3VB^ Furnace Heating Airflow (CFM) and Power (Watts) vs. External Static Pressure With Filter
Airflow
Setting
100%
(high)
Heat
Low
1120
Medium Low
1260
Medium**
1400
High
1610
Notes:
1. * First letter may be "A" or "T".
3. ** Factory setting.
2. ^ Letter may be “A” through “Z”.
4. Continuous Fan Setting: Heating or cooling airflow is approximately 50% of selected
cooling value.
5. LOW 350 cfm/ton is recommended for variable speed application for COMFORT & HUMID
CLIMATE setting; NORMAL is 400 cfm/ton; HIGH 450 cfm/ton is for DRY CLIMATE setting.
6. Target airflow is field selectable for high (100%) heat. Target airflow for low and medium
heat are percentages of high heat and are not field selectable.
8
Pub. No. 22-1840-14
Page 9
TUHM AIRFLOW - HEATING
0.10.30.50.70.9
CFM592617623617606
Temp. Rise6159585960
Watts78109141173233
CFM626651655649639
Temp. Rise5856555657
Watts79110142175236
CFM660684688682671
Temp. Rise5553535354
Watts81111144177241
CFM732755757751739
Temp. Rise5048484849
Watts87115149185254
CFM10481065106010521038
Temp. Rise6059596061
Watts149169208252358
CFM11071123111611081094
Temp. Rise5756565758
Watts167186226271386
CFM11651181117311651150
Temp. Rise5453545455
Watts187204245292417
CFM12911304129312841269
Temp. Rise4948494950
Watts236250293343490
CFM14661476146114511435
Temp. Rise6059606061
Watts319330374430613
CFM15481556154015291512
Temp. Rise5756575758
Watts364373419476679
CFM16291637161816081590
Temp. Rise5454545455
Watts413419467527750
CFM18031807178517741755
Temp. Rise4948494950
Watts529532582646864
100%
(high)
Heat
Low
1460
Medium Low
1540
Medium**
1620
High
1790
High
1289
672
High
743
639
Medium**
Low
1051
Medium Low
1109
606
Medium**
1166
40%
(low)
Heat
Low
Heating
*UHMC100ACV4VB^ Furnace Heating Airflow (CFM) and Power (Watts) vs. External Static Pressure With Filter
Airflow
Setting
Target Airflow
(See Note 5)
External Static Pressure
Medium Low
65%
(medium)
Heat
0.10.30.50.70.9
CFM728758785805819
Temp. Rise6259575655
Watts11910710294108
CFM769797822840853
Temp. Rise5856545353
Watts113107111113133
CFM813841864880890
Temp. Rise5553525150
Watts108107122135160
CFM863889910923930
Temp. Rise5250494948
Watts104108135160191
CFM12131232123712321220
Temp. Rise6060596060
Watts131160253345405
CFM12791297129912901274
Temp. Rise5757565758
Watts147178281382445
CFM13531369136713551335
Temp. Rise5454545455
Watts168201313423489
CFM14341448144314261402
Temp. Rise5151515152
Watts197229352469538
CFM16991707169016591621
Temp. Rise6060606163
Watts325349495628698
CFM17901797177517401696
Temp. Rise5757575960
Watts382400551685752
CFM18921896187018301781
Temp. Rise5454545657
Watts453462616750813
CFM20042006197519291873
Temp. Rise5151525354
Watts540538694822880
100%
(high)
Heat
Low
1700
Medium Low
1790
Medium**
1890
High
2000
High
1440
832
High
880
788
Medium**
Low
1224
Medium Low
1289
748
Medium**
1361
45%
(low)
Heat
Low
Heating
*UHMD120ACV5VB^ Furnace Heating Airflow (CFM) and Power (Watts) vs. External Static Pressure With Filter
Airflow
Setting
Target Airflow
(See Note 5)
External Static Pressure
Medium Low
65%
(medium)
Heat
Notes:
1. * First letter may be "A" or "T".
3. ** Factory setting.
2. ^ Letter may be “A” through “Z”.
4. Continuous Fan Setting: Heating or cooling airflow is approximately 50% of selected
cooling value.
5. LOW 350 cfm/ton is recommended for variable speed application for COMFORT & HUMID
CLIMATE setting; NORMAL is 400 cfm/ton; HIGH 450 cfm/ton is for DRY CLIMATE setting.
6. Target airflow is field selectable for high (100%) heat. Target airflow for low and medium
heat are percentages of high heat and are not field selectable.
Pub. No. 22-1840-14
9
Page 10
TUHM AIRFLOW - COOLING
0.10.30.50.70.9
CFM
356476488511519
Watts
296797132167
CFM
389504516538545
Watts
3271102138174
CFM
422533544565572
Watts
3675107144181
CFM
455561566589592
Watts
3979111150187
CFM
487589600619624
Watts
4384119158197
CFM
537631655669673
Watts
5092130171212
CFM
586674684700702
Watts
57101139182223
CFM
619695717727733
Watts
63106150193236
CFM
515613623641646
Watts
4788124164204
CFM
559650660677681
Watts
5396133175215
CFM
602688698713716
Watts
60104143186228
CFM
646707737748752
Watts
68112156200243
CFM
690763772785785
Watts
76123165211255
CFM
764816778847844
Watts
86137180231275
CFM
821876884892890
Watts
108159206256303
CFM
937968977985984
Watts
136193241295343
CFM
673749758771772
Watts
73119161206250
CFM
732791756766818
Watts
79129160203268
CFM
783843852861860
Watts
98147193242288
CFM
848894908917917
Watts
110163212262308
CFM
892937945951947
Watts
129182232284333
CFM
97210159729571036
Watts
160213262312374
CFM
10571078108510851078
Watts
191249306360415
CFM
11151137114211401139
Watts
214275333388447
CFM
832885894901899
Watts
111162210260308
CFM
898942950955951
Watts
131184234286336
CFM
964998100610091004
Watts
154209262314366
CFM
10391065107310741075
Watts
181237292344402
CFM
10951111111811161108
Watts
208268326380436
CFM
11891212121411491207
Watts
257320380435500
CFM
12921280128512781201
Watts
317383448501508
CFM
13261317136112421166
Watts
366433495510509
Notes:
1. * First letter may be "A" or "T".
2. ^ Letter may be "A" through "Z"
3. ** Factory setting.
4. Continuous Fan Setting: Heating or cooling airflow is approximately 50% of selected
cooling value.
5. LOW 350 cfm/ton is recommended for variable speed application for COMFORT & HUMID
CLIMATE setting; NORMAL is 400 cfm/ton; HIGH 450 cfm/ton is for DRY CLIMATE setting.
Cooling
Unit
Outdoor
Airflow
Setting
External Static Pressure
1.5
290 CFM/ton
310 CFM/ton
330 CFM/ton
350 CFM/ton
370 CFM/ton
400 CFM/ton
430 CFM/ton
450 CFM/ton
2
290 CFM/ton
310 CFM/ton
330 CFM/ton
350 CFM/ton
370 CFM/ton
400 CFM/ton
310 CFM/ton
330 CFM/ton
350 CFM/ton
370 CFM/ton
400 CFM/ton
430 CFM/ton
430 CFM/ton
450 CFM/ton
*UHMB060ACV3VB^ Furnace Cooling Airflow (CFM) and Power (Watts) vs. External Static
Pressure With Filter
450 CFM/ton
3
290 CFM/ton
310 CFM/ton
2.5
290 CFM/ton
330 CFM/ton
350 CFM/ton
370 CFM/ton
400 CFM/ton
430 CFM/ton
450 CFM/ton
10
NOTE:
CONTINUOUS fan mode during
COOLING operation may not be
appropriate in humid climates. If the
indoor air exceeds 60% relative humidity
or simply feels uncomfortably humid,
it is recommended that the fan only be
used in the AUTO mode.
Pub. No. 22-1840-14
Page 11
TUHM AIRFLOW - COOLING
0.10.30.50.70.9
CFM
504565586521540
Watts
3470104138172
CFM
547604624559579
Watts
4077112147182
CFM
590644663597617
Watts
4785121157193
CFM
656695701703694
Watts
5493130167204
CFM
676724740674694
Watts
62102140179217
CFM
764792801795789
Watts
75116157197238
CFM
806844856788810
Watts
89133175216259
CFM
877899901895886
Watts
102145188230275
CFM
660709726659680
Watts
5999136174212
CFM
740768772769764
Watts
70109149189229
CFM
768809822755776
Watts
81123164205246
CFM
848869871868858
Watts
94138179220265
CFM
875909918850872
Watts
107153197240284
CFM
978994992989980
Watts
130179224270316
CFM
1037105810639941017
Watts
157209258305354
CFM
10931096108210651051
Watts
174227276324378
CFM
816854865798819
Watts
92136178220262
CFM
881914923855877
Watts
108155199242286
CFM
945974981912935
Watts
127176222266313
CFM
10291043104310351028
Watts
148199246292340
CFM
10741093109710271050
Watts
170224274322372
CFM
11701181118411801174
Watts
206262317370423
CFM
12681276127011991224
Watts
254314372430484
CFM
13211321130612951251
Watts
287351415477518
CFM
9729981005936959
Watts
135185232277324
CFM
10471068107310031026
Watts
161213262310359
CFM
11231138114010701094
Watts
189244296347398
CFM
11951204120812051195
Watts
215275329383437
CFM
12731278127512041228
Watts
257317376433488
CFM
13751385138413831305
Watts
316383444513513
CFM
14991487149113921303
Watts
389457513513513
CFM
15131512150814181341
Watts
398470529524522
Notes:
1. * First letter may be "A" or "T".
2. ^ Letter may be "A" through "Z"
3. ** Factory setting.
4. Continuous Fan Setting: Heating or cooling airflow is approximately 50% of selected
cooling value.
5. LOW 350 cfm/ton is recommended for variable speed application for COMFORT & HUMID
CLIMATE setting; NORMAL is 400 cfm/ton; HIGH 450 cfm/ton is for DRY CLIMATE setting.
350 CFM/ton
3.5
290 CFM/ton
310 CFM/ton
330 CFM/ton
370 CFM/ton
400 CFM/ton
430 CFM/ton
450 CFM/ton
3
290 CFM/ton
310 CFM/ton
330 CFM/ton
350 CFM/ton
370 CFM/ton
400 CFM/ton
430 CFM/ton
450 CFM/ton
2.5
290 CFM/ton
310 CFM/ton
330 CFM/ton
350 CFM/ton
370 CFM/ton
400 CFM/ton
430 CFM/ton
450 CFM/ton
290 CFM/ton
310 CFM/ton
330 CFM/ton
2
350 CFM/ton
370 CFM/ton
400 CFM/ton
430 CFM/ton
450 CFM/ton
Unit
Outdoor
Airflow
Setting
External Static Pressure
*UHMB080ACV3VB^ Furnace Cooling Airflow (CFM) and Power (Watts) vs. External Static
Pressure With Filter
Cooling
Pub. No. 22-1840-14
NOTE:
CONTINUOUS fan mode during
COOLING operation may not be
appropriate in humid climates. If the
indoor air exceeds 60% relative humidity
or simply feels uncomfortably humid,
it is recommended that the fan only be
used in the AUTO mode.
11
Page 12
TUHM AIRFLOW - COOLING
Watts
171220271322368
Watts
258314373432488
CLIMATE setting; NORMAL is 400 cfm/ton; HIGH 450 cfm/ton is for DRY CLIMATE setting.
*UHMC100ACV4VB^ Furnace Cooling Airflow (CFM) and Power (Watts) vs. External Static
External Static Pressure
Pressure With Filter
Unit
Outdoor
2.5
Cooling
3.5
Notes:
1. * First letter may be "A" or "T".
2. ^ Letter may be "A" through "Z"
3. ** Factory setting.
4. Continuous Fan Setting: Heating or cooling airflow is approximately 50% of selected
cooling value.
5. LOW 350 cfm/ton is recommended for variable speed application for COMFORT & HUMID
NOTE:
CONTINUOUS fan mode during
COOLING operation may not be
appropriate in humid climates. If the
indoor air exceeds 60% relative humidity
or simply feels uncomfortably humid,
it is recommended that the fan only be
used in the AUTO mode.
12
Pub. No. 22-1840-14
Page 13
TUHM AIRFLOW - COOLING
0.10.30.50.70.9
CFM
10001024102810221011
Watts
122168209251300
CFM
10721094109710891076
Watts
140188234281331
CFM
11431164116511571141
Watts
160211261313364
CFM
12141233123412241207
Watts
182236291347400
CFM
12861303130212911272
Watts
207264323384438
CFM
13931408140513921370
Watts
250311377444500
CFM
15001513150814921468
Watts
300365437509565
CFM
15711582157615591533
337406481555611
CFM
11481169117011611146
Watts
161213263315367
CFM
12301248124812381221
Watts
187242297355408
CFM
13111328132713151295
Watts
217274335398452
CFM
13931408140513921370
Watts
250311377444500
CFM
14741488148314681445
Watts
287352422493549
CFM
15971607160115831556
Watts
352421497572628
CFM
17191727171816991668
Watts
427503581655711
CFM
18011807179717751743
483563642712768
CFM
14441458145414401417
Watts
273336405475530
CFM
15461557155215351510
Watts
324391465538594
CFM
16481657165016311603
Watts
381454531606662
CFM
17501757174817271696
Watts
447525603676732
CFM
18521857184518231790
Watts
522604682749804
CFM
20042006199219671947
Watts
651742811863966
CFM
21572156214020501947
Watts
803902966966966
CFM
22592255214020501947
Notes:
1. * First letter may be "A" or "T".
2. ^ Letter may be "A" through "Z"
3. ** Factory setting.
4. Continuous Fan Setting: Heating or cooling airflow is approximately 50% of selected
cooling value.
5. LOW 350 cfm/ton is recommended for variable speed application for COMFORT & HUMID
CLIMATE setting; NORMAL is 400 cfm/ton; HIGH 450 cfm/ton is for DRY CLIMATE setting.
*UHMD120ACV5VB^
Pressure With Filter
Furnace Cooling Airflow (CFM) and Power (Watts) vs. External Static
Outdoor
Cooling
Unit
3.5
4
Airflow
Setting
290 CFM/ton
310 CFM/ton
330 CFM/ton
350 CFM/ton
370 CFM/ton
400 CFM/ton
430 CFM/ton
450 CFM/ton
290 CFM/ton
310 CFM/ton
330 CFM/ton
350 CFM/ton
370 CFM/ton
400 CFM/ton
430 CFM/ton
External Static Pressure
Watts
5
450 CFM/ton
290 CFM/ton
310 CFM/ton
330 CFM/ton
350 CFM/ton
370 CFM/ton
400 CFM/ton
430 CFM/ton
450 CFM/ton
Watts
Watts
966966966966966
NOTE:
CONTINUOUS fan mode during
COOLING operation may not be
appropriate in humid climates. If the
indoor air exceeds 60% relative humidity
or simply feels uncomfortably humid,
it is recommended that the fan only be
used in the AUTO mode.
Pub. No. 22-1840-14
13
Page 14
TDHM AIRFLOW - HEATING
0.10.30.50.70.9
Watts129119207206291
Watts286240382348460
(See Note 5)
External Static Pressure
Setting
Notes:
1. * First letter may be "A" or "T".
3. ** Factory setting.
2. ^ Letter may be “A” through “Z”.
4. Continuous Fan Setting: Heating or cooling airflow is approximately 50% of selected
cooling value.
5. LOW 350 cfm/ton is recommended for variable speed application for COMFORT & HUMID
CLIMATE setting; NORMAL is 400 cfm/ton; HIGH 450 cfm/ton is for DRY CLIMATE setting.
6. Target airflow is field selectable for high (100%) heat. Target airflow for low and medium
heat are percentages of high heat and are not field selectable.
CFM438436458462474
CFM460458479483493
Temp. Rise4646444443
Watts28527392118
CFM499497516518526
Temp. Rise4242414140
Temp. Rise3838373737
Watts426890114144
Temp. Rise4848484848
Watts76106140176217
CFM753751755749740
Temp. Rise4646454646
Watts87117154194237
Watts108140183228275
CFM911909904892873
Temp. Rise3838383839
Watts142177226276326
CFM906904900888869
Temp. Rise5858595961
Watts140175223274323
CFM954952945931910
Temp. Rise5555565758
Temp. Rise5151515254
Watts202243295347393
CFM11571155113611151080
Temp. Rise4646464749
Watts269317361405439
*DHMB060BCV3VB^
40% (low) Heat
65% (medium)
Heating
100% (high)
Heat
Heat
Furnace Heating Airflow (CFM) and Power (Watts) vs. External Static Pressure With Filter
Airflow Setting
Low
Medium Low
Medium**
High
Low
Medium Low
Medium**
High
Low
Medium Low
Medium**
High
Target Airflow
(See Note 5)
414
437
478
534
702
741
811
905
900
950
1040
1160
0.10.30.50.70.9
Temp. Rise4848464645
Watts26497090115
Watts335879100127
CFM553551567567571
CFM715713720714708
CFM820818819810797
Temp. Rise4242424243
Watts160197248300350
CFM1041103910271010983
External Static Pressure
*DHMB080ACV3VB^ Furnace Heating Airflow (CFM) and Power (Watts) vs. External Static Pressure With Filter
Target Airflow
1400
CFM648670681685687
Temp. Rise5755545454
Watts7979148155219
CFM676698708711712
Temp. Rise5453525252
Watts8585156163230
CFM705725735737736
Temp. Rise5251505050
Watts9390165170241
CFM824841849846838
Temp. Rise4544434344
CFM923937943936923
Temp. Rise5554545455
Watts166148249241336
CFM962974980972956
Temp. Rise5252515253
Watts183161268256355
CFM1001101210171008990
Temp. Rise5050505051
Watts201174288272374
CFM11651171117311581130
Temp. Rise4343434445
CFM13181319131912971261
Temp. Rise5353535456
Watts382314485431549
CFM13721372137013471307
Temp. Rise5151515254
Watts420343526463582
CFM14261424142213961354
Temp. Rise4949495052
Watts460373569497617
CFM16541645163916051549
Temp. Rise4243434445
Watts650518770655772
40%
(low)
Heat
65%
(medium)
Heating
Heat
100%
(high)
Heat
Airflow
Low683
Medium Low709
Medium**735
High845
Low936
Medium Low972
Medium**1008
High1159
Low1300
Medium Low1350
Medium**
High1610
14
Pub. No. 22-1840-14
Page 15
TDHM AIRFLOW - HEATING
0.10.30.50.70.9
Watts40118140235247
Watts180304288441466
Watts413583483726726
*DHMC100ACV4VB^ Furnace Heating Airflow (CFM) and Power (Watts) vs. External Static Pressure With Filter
Setting
(See Note 5)
Notes:
1. * First letter may be "A" or "T".
3. ** Factory setting.
2. ^ Letter may be “A” through “Z”.
4. Continuous Fan Setting: Heating or cooling airflow is approximately 50% of selected
cooling value.
5. LOW 350 cfm/ton is recommended for variable speed application for COMFORT & HUMID
CLIMATE setting; NORMAL is 400 cfm/ton; HIGH 450 cfm/ton is for DRY CLIMATE setting.
6. Target airflow is field selectable for high (100%) heat. Target airflow for low and medium
heat are percentages of high heat and are not field selectable.
*DHMD120BCV5VB^ Furnace Heating Airflow (CFM) and Power (Watts) v s. External Static Pressure With Filter
40%
(low)
Heat
65%
(medium)
Heating
Heat
100%
(high)
Heat
Airflow
Target Airflow
Low668
Medium Low712
Medium**734
High757
Low1080
Medium Low
Medium**
1152
1188
High1224
Low
1500
Medium Low1600
Medium**1650
High1700
External Static Pressure
CFM666657643628609
Temp. Rise5959616264
Watts2492116206206
CFM710701686670650
Temp. Rise5556575860
Watts32105128220227
CFM732723708690670
Temp. Rise5354555658
Watts36111134227237
CFM755744729711690
Temp. Rise5252535556
CFM1077106310411016985
Temp. Rise5959616264
Watts128237237368398
CFM11491134111010831051
Temp. Rise5556575860
Watts153270262404432
CFM11851169114511171084
Temp. Rise5354555658
Watts166286275422449
CFM12211205118011511117
Temp. Rise5252535556
CFM14961476144614101368
Temp. Rise5959616264
Watts304455396604596
CFM15961575154215041460
Temp. Rise5556575860
Watts356517438670643
CFM16461624159015511505
Temp. Rise5354555658
Watts384550461705667
CFM16961673163915981551
Temp. Rise5252535556
40% (low) Heat
65% (medium)
Heating
Heat
100% (high) Heat
Airflow Setting
Low
Medium Low
Medium**
High
Low
Medium Low
Medium**1469
High
Low
Medium Low
Medium**
High
Target Airflow
(See Note 5)
780
827
870
959
1195
1267
1685
1660
1760
1850
2040
CFM827870800779785
Temp. Rise5755596160
Watts7698142175212
CFM871917846827834
Temp. Rise5552565757
Watts85108153188226
CFM911959889872878
Temp. Rise5250535454
Watts94117165201240
CFM9941047977964969
Temp. Rise4845494949
Watts116140191230272
CFM12141282121112091212
Temp. Rise5754575757
Watts193223285334385
CFM12811353128212831286
Temp. Rise5451545353
Watts224255322375431
CFM14701553148214931493
Temp. Rise4744464646
Watts329366449517592
CFM16711767169617171715
Temp. Rise4139404040
Watts479519633722831
CFM16481743167116911690
Temp. Rise6461636262
Watts459499609695799
CFM17411842177017951792
Temp. Rise6157605959
Watts541582709808932
CFM18251931185918881885
Temp. Rise5855575656
Watts6246638119221068
CFM20021983197719021853
Temp. Rise5353535557
Watts827925925925925
0.10.30.50.70.9
External Static Pressure
Pub. No. 22-1840-14
15
Page 16
TDHM AIRFLOW - COOLING
Watts7099130164203
Watts140175223274323
*DHMB060BCV3VB^ Furnace Cooling Airflow (CFM) and Power (Watts) vs. External Static Pressure With Filter
External Static Pressure
Unit Outdoor
Size (tons)
1.5
2
Cooling
2.5
3
Notes:
1. * First letter may be "A" or "T".
2. ^ Letter may be "A" through "Z"
3. ** Factory setting.
4. Continuous Fan Setting: Heating or cooling airflow is approximately 50% of selected cooling value.
5. LOW 350 cfm/ton is recommended for variable speed application for COMFORT & HUMID CLIMATE setting;
NORMAL is 400 cfm/ton; HIGH 450 cfm/ton is for DRY CLIMATE setting.
Airflow Setting
290 CFM/ton
310 CFM/ton
330 CFM/ton
350 CFM/ton
370 CFM/ton
400 CFM/ton
430 CFM/ton
450 CFM/ton
290 CFM/ton
310 CFM/ton
330 CFM/ton
350 CFM/ton
370 CFM/ton
400 CFM/ton
430 CFM/ton
450 CFM/ton
290 CFM/ton
310 CFM/ton
330 CFM/ton
350 CFM/ton
370 CFM/ton
400 CFM/ton
430 CFM/ton
450 CFM/ton
290 CFM/ton
310 CFM/ton
330 CFM/ton
350 CFM/ton
370 CFM/ton
400 CFM/ton
430 CFM/ton
450 CFM/ton
CFM458456477481491
Watts28527392118
CFM487485504507515
Watts32567797124
CFM516514532533540
Watts366182104132
CFM545543559560564
Watts406688111141
CFM574572586586589
Watts457295120151
CFM617615627625625
Watts5481107135169
CFM660658668665662
Watts6391120152189
CFM689687695691686
CFM598596609608609
Watts5077101128161
CFM636634645643641
Watts5885113142177
CFM675673682678674
Watts6695125158196
CFM713711718713706
Watts76105139175216
CFM752750754748739
Watts87117154193236
CFM810808809800788
Watts104136178222269
CFM868866863853836
Watts125159205253301
CFM906904900888869
CFM738735741735727
Watts82113148186228
CFM786784786778767
Watts97128168210255
CFM834832831822808
Watts112145189235282
CFM882880877866849
Watts130164212261310
CFM930928922909889
Watts150186236287337
CFM10031000990975950
Watts183222274326375
CFM10751073105910411011
Watts220263314364408
CFM11231121110410841052
Watts248294341389427
CFM877875872861845
Watts128162209258307
CFM935933927914893
Watts152188238289339
CFM993991981966942
Watts178217268321370
CFM1051104910361019991
Watts207249300352398
CFM11091106109010711040
Watts239284333381422
CFM11951193117211501113
Watts294345384422449
CFM12821280125412291186
Watts357414436456463
CFM13341351127212011125
Watts405466463459455
0.10.30.50.70.9
NOTE:
CONTINUOUS fan
mode during COOLING
operation may not be
appropriate in humid
climates. If the indoor
air exceeds 60% relative
humidity or simply feels
uncomfortably humid,
it is recommended that
the fan only be used in
the AUTO mode.
16
Pub. No. 22-1840-14
Page 17
TDHM AIRFLOW - COOLING
125168208248287
Watts
221272319366411
Watts
360415473502502
CLIMATE setting; NORMAL is 400 cfm/ton; HIGH 450 cfm/ton is for DRY CLIMATE setting.
*DHMB080ACV3VB^ Furnace Cooling Airflow (CFM) and Power (Watts) vs. External Static
Pressure With Filter
Unit
Outdoor
2
2.5
Cooling
3
Notes:
1. * First letter may be "A" or "T".
2. ^ Letter may be "A" through "Z"
3. ** Factory setting.
4. Continuous Fan Setting: Heating or cooling airflow is approximately 50% of selected
cooling value.
5. LOW 350 cfm/ton is recommended for variable speed application for COMFORT & HUMID
NOTE:
CONTINUOUS fan
mode during COOLING
operation may not be
appropriate in humid
climates. If the indoor
air exceeds 60% relative
humidity or simply feels
uncomfortably humid,
it is recommended that
the fan only be used in
the AUTO mode.
Pub. No. 22-1840-14
17
Page 18
TDHM AIRFLOW - COOLING
0.10.30.50.70.9
CFM
723713699682661
Watts
58109157204234
CFM
773763747729707
Watts
72125174222256
CFM
823812795776753
Watts
87141182241279
CFM
873861842823798
Watts
103158210260302
CFM
923910892870844
Watts
120177229279325
CFM
998984964940912
Watts
148206258309360
CFM
1072105810361011981
Watts
179238290341396
CFM
11221107108410581026
Watts
201260312362420
CFM
868856839818794
Watts
101157208258299
CFM
928915896874849
Watts
122179231281327
CFM
988974954931903
Watts
144202254305356
CFM
104710331012987958
Watts
169227279330384
CFM
11071092107010441013
Watts
195253305356413
CFM
11971181115711281095
Watts
237296346395455
CFM
12871269124312131177
Watts
284341390436498
CFM
13471329130112691232
Watts
317373420465526
CFM
1013999978954926
Watts
154212265315367
CFM
1082106810481020990
Watts
184242294345401
CFM
11521137111310861054
Watts
215274325375434
CFM
12221206118111521118
Watts
250308358406467
CFM
12921274124812181182
Watts
286344392439500
CFM
13971378134913161277
Watts
346401446489548
CFM
15011481145114151373
Watts
411463503541595
CFM
15711550151814811437
Watts
457507543577625
CFM
11571142111810911058
Watts
218276328377436
CFM
12371220119511661131
Watts
257315365413474
CFM
13171299127212411204
Watts
300357405450512
CFM
13971378134913161277
Watts
346401446489548
CFM
14761456142613921350
Watts
395448489529584
CFM
15961575154215041460
Watts
474523558591636
CFM
17161693165816171569
Watts
560604631726726
CFM
17961771173516931642
Watts
622661682726726
Notes:
1. * First letter may be "A" or "T".
2. ^ Letter may be "A" through "Z"
3. ** Factory setting.
4. Continuous Fan Setting: Heating or cooling airflow is approximately 50% of selected
cooling value.
5. LOW 350 cfm/ton is recommended for variable speed application for COMFORT & HUMID
CLIMATE setting; NORMAL is 400 cfm/ton; HIGH 450 cfm/ton is for DRY CLIMATE setting.
External Static Pressure
290 CFM/ton
*DHMC100ACV4VB^ Furnace Cooling Airflow (CFM) and Power (Watts) vs. External Static
Pressure With Filter
310 CFM/ton
330 CFM/ton
Unit
Outdoor
Airflow
Setting
450 CFM/ton
3
290 CFM/ton
310 CFM/ton
330 CFM/ton
2.5
350 CFM/ton
370 CFM/ton
400 CFM/ton
430 CFM/ton
430 CFM/ton
450 CFM/ton
350 CFM/ton
370 CFM/ton
400 CFM/ton
3.5
290 CFM/ton
310 CFM/ton
330 CFM/ton
350 CFM/ton
370 CFM/ton
400 CFM/ton
430 CFM/ton
450 CFM/ton
Cooling
4
290 CFM/ton
310 CFM/ton
430 CFM/ton
450 CFM/ton
370 CFM/ton
400 CFM/ton
330 CFM/ton
350 CFM/ton
18
NOTE:
CONTINUOUS fan mode during
COOLING operation may not be
appropriate in humid climates. If the
indoor air exceeds 60% relative humidity
or simply feels uncomfortably humid,
it is recommended that the fan only be
used in the AUTO mode.
Pub. No. 22-1840-14
Page 19
TDHM AIRFLOW - COOLING
*DHMD120BCV5VB^ Furnace Cooling Airflow (CFM) & Power (Watts) vs. External Static Pressure w/Filter
0.10.30.50.70.9
CFM10461103103210271022
Watts131157210251295
CFM11111172110210991095
Watts153180237280326
CFM11771242117111711167
Watts178207266313363
CFM12421311124012431240
Watts205236300350404
CFM13071381131013151312
Watts236269337392450
CFM14051485141414221421
Watts289325401464531
CFM15031589151815301530
Watts351389476547627
CFM15691658158716021603
Watts397436533610700
CFM11811247117611761172
Watts180209269316365
CFM12561326125512581255
Watts212243308359413
CFM13311405133513401338
Watts248282352408468
CFM14051485141414221421
Watts289325401464531
CFM14801564149315051504
Watts336373457526602
CFM15921683161216281629
Watts415454554634728
CFM17041802173117511753
Watts507548667761877
CFM17781882181018331836
Watts577617753857991
CFM14521534146314741473
Watts318354436502574
CFM15451634156215771577
Watts380419512587673
CFM16391733166116791681
Watts452492599685787
CFM17321832176017821784
Watts533573699796918
CFM18251931185918851888
Watts624663811922925
CFM19652080197719021853
Watts781925925925925
CFM20642229197719021853
Watts925925925925925
CFM20642250197719021853
Watts925925925925925
Notes:
1. * First letter may be "A" or "T".
2. ^ Letter may be "A" through "Z"
3. ** Factory setting.
4. Continuous Fan Setting: Heating or cooling airflow is approximately 50% of selected cooling value.
5. LOW 350 cfm/ton is recommended for variable speed application for COMFORT & HUMID CLIMATE setting;
NORMAL is 400 cfm/ton; HIGH 450 cfm/ton is for DRY CLIMATE setting.
Cooling
290 CFM/ton
310 CFM/ton
330 CFM/ton
350 CFM/ton
External Static Pressure
Airflow Setting
Unit Outdoor Size
(tons)
310 CFM/ton
330 CFM/ton
290 CFM/ton
290 CFM/ton
370 CFM/ton
400 CFM/ton
430 CFM/ton
450 CFM/ton
310 CFM/ton
330 CFM/ton
350 CFM/ton
370 CFM/ton
400 CFM/ton
430 CFM/ton
450 CFM/ton
3.5
4
5
350 CFM/ton
370 CFM/ton
400 CFM/ton
430 CFM/ton
450 CFM/ton
Pub. No. 22-1840-14
NOTE:
CONTINUOUS fan mode during COOLING operation
may not be appropriate in humid climates. If the
indoor air exceeds 60% relative humidity or simply
feels uncomfortably humid, it is recommended that
the fan only be used in the AUTO mode.
Notes: * - First letter may be "A" or "T", ** - Last two digits may be "A" thru "Z"
1. Minimum vent length for all models: 3' horizontal or 3' vertical
2. DO NOT MIX PIPE DIAMETERS IN THE SAME LENGTH OF PIPE OUTSIDE THE FURNACE CABINET, (Except
adapters at the top of the furnace). If different inlet and vent pipe sizes are used, the vent pipe must adhere to the
maximum length limit shown in the table above (See note 6 below for exception). The inlet pipe can be of a larger
diameter, but never smaller than the vent pipe.
3. MAXIMUM PIPE LENGTHS MUST NOT BE EXCEEDED! THE LENGTH SHOWN IS NOT A
COMBINED TOTAL, IT IS THE MAXIMUM LENGTH OF EACH (Vent or Inlet air pipes).
4. One SHORT radius 90° elbow is equivalent to 10' of 3" pipe and one LONG radius elbow is equivalent to 6' of 3"
pipe. One 90° elbow is equivalent to 7½' of 2½" pipe or 5' of 2" pipe. Two 45° elbows equal one 90° elbow.
5. The termination tee or bend must be included in the total number of elbows. If the BAYAIR30AVENTA termination
kit is used, the equivalent length of pipe is 5 feet. BAYVENT200B equivalent length is 0 feet.
6. Pipe adapters are field supplied. Downflow models, UHM 100 and UHM 120 models include
the 2" x 3" adapter.
3 or 4 INCH PIPE
3 or 4 INCH PIPE2.5 INCH PIPE2 INCH PIPE
VENT LENGTH TABLE - MODULATING FURNACE
0-7000 Feet
7000-9500 Feet
9500-12000 Feet
3 or 4 INCH PIPE2.5 INCH PIPE2 INCH PIPE
2 INCH PIPE2.5 INCH PIPE
MAXIMUM TOTAL EQUIVALENT LENGTH IN FEET FOR VENT AND INLET
AIR (SEE NOTES)
7. For Canadian applications ONLY, IPEX 196006 may be used for horizontal and vertical terminations. IPEX 081216,
IPEX 081218, and IPEX 081219 may only be used for horizontal vent terminations. Equivalent lengths are
IPEX 196009 = 5 feet, IPEX 081216 = 11 feet, IPEX 081218 = 16 feet, and IPEX 081219 = 21 feet
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing.
21
Page 22
Electrical
▲
CAUTION
!
Data
TUHM Schematic Diagram
Label all wires prior to disconnection when servicing
controls. Wiring errors can cause improper and dangerous
operation. Verify proper operation after servicing.
22
Pub. No. 22-1840-14
Page 23
Electrical
▲
CAUTION
!
Data
TDHM Wiring Diagram
Pub. No. 22-1840-14
Label all wires prior to disconnection when servicing controls.
Wiring errors can cause improper and dangerous operation.
Verify proper operation after servicing.
23
Page 24
Electrical
▲
CAUTION
!
Data
TDHM Schematic Diagram
Label all wires prior to disconnection when servicing
controls. Wiring errors can cause improper and dangerous
operation. Verify proper operation after servicing.
24
Pub. No. 22-1840-14
Page 25
NOTE:
The maximum total cable length for the entire Comfort
Control communicating system is 500 ft. 18 AWG. The
maximum distance of any single cable from a transformer is 250 ft. 18 AWG.
NOTE:
When connecting an TFD whole house air cleaner with
this furnace, order BAYACCECOMM101.
NOTE:
The BAYACCECOMM101 must be used when
connecting an TFD whole house air cleaner to a
furnace in communicating mode. For 24 volt mode,
see the installation in the whole house air cleaner
Installer's Guide.
NOTE:
The BAYACCECOMM101 can be ordered through the
sales channels.
NOTE:
The B/C terminal will require three wires to be
connected. Rather than connecting the three wires to
the low voltage terminal strip, create a pigtail using a
short length of thermostat wire and a wire nut (field
supplied) to attach to the B/C terminal.
Communicating Indoor Unit with Communicating Comfort Control and Communicating Outdoor Unit
Pub. No. 22-1840-14
25
Page 26
Communicating Indoor Unit with Communicating Comfort Control and 24VAC Single Stage Cooling
24 VAC Mode Indoor Unit with 24 VAC Comfort Control and 24VAC Single Stage Cooling
26
Pub. No. 22-1840-14
Page 27
24 VAC Mode Indoor Unit with 24 VAC Comfort Control and 24VAC 2-Stage or 2-Step Cooling
24 VAC Mode Indoor Unit with 24 VAC Comfort Control and 24VAC Single Stage Heat Pump
Pub. No. 22-1840-14
27
Page 28
24 VAC Mode Indoor Unit with 24 VAC Comfort Control and 24VAC 2-Stage or 2-Step Heat Pump
BK Jumper
Humidistat Hookup - 24 V Mode ONLY
The factory installed jumper between "R"
and "BK" on the circuit board must be
cut if an optional humidistat is installed.
HUMIDISTAT HOOKUP - 24 V ONLY
If an optional humidistat for humidity control in cooling
is used, the factory installed "BK Jumper" must be cut.
The BK Jumper must also be cut if a multi-zone control-