Trane AUH1D100A9601A, AUH1C080A9601A, AUH1D120A9601A, AUH1C100A9481A, ADH1B065A9421A Installer's Manual

...
Page 1
18-CD29D1-11
Installer’s Guide
Upflow/ Horizontal, Downflow/ Horizontal, Gas-Fired, Direct Vent Condensing Furnaces
*UH1B040A9241A *UH1B060A9361A *UH1B080A9421B *UH1C080A9601A
*__First letter may be “A” or “T”
ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES
IMPORTANT — This Document is customer property and is to remain with this unit.
Please return to service information pack upon completion of work.
*UH1
*UH1C100A9481A *UH1D100A9601A *UH1D120A9601A
*DH1B040A9241A *DH1B065A9421A *DH1C085A9481A *DH1D110A9601A
*DH1
DOWNFLOW
*UH1
UPFLOW/HORIZONTAL
*DH1
DOWNFLOW/HORIZONTAL
A341624P13
Page 2
Installer’s Guide
WARNING
!
SAFETY SECTION
Safety signal words are used to designate a degree or level of seriousness associated with a particular haz­ard. The signal words for safety markings are WARN- ING and CAUTION. a. WARNING indicates a potentially hazardous situa-
tion which, if not avoided, could result in death or serious injury.
b. CAUTION indicates a potentially hazardous situa-
tion which, if not avoided, may result in minor or moderate injury. It is also used to alert against un­safe practices and hazards involving only property damage.
The following safety practices and precautions must be followed during the installation, servicing, and opera­tion of this furnace.
1. Use only with the type of gas approved for this furnace. Refer to the furnace rating plate.
2. Install this furnace only in a location and position as specified in “Location and Clearances” (page 4), of these instructions.
3. Provide adequate combustion and ventilation air to the furnace space as specified in “Air for Combustion and Ventilation” (pages 8-9), of these instructions.
4. Combustion products must be discharged outdoors. Con­nect this furnace to an approved vent system only, as specified in the “Venting” section (starting on page 15), of these instructions.
5. Never test for gas leaks with an open flame. Use a com­mercially available soap solution made specifically for the detection of leaks to check all connections, as speci­fied in “Gas Piping” (pages 31-32), of these instructions.
6. Always install the furnace to operate within the furnace’s intended temperature-rise range with a duct system which has an external static pressure within the al­lowable range, as specified on the unit rating plate. Airflow with temperature rise for cfm versus static is shown in the Service Facts accompanying this furnace.
7. When a furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by a duct(s) sealed to the furnace casing and terminating outside the space containing the furnace.
8. A gas-fired furnace for installation in a residential garage must be installed as specified in “Location and Clear­ances” section (page 4), of these instructions.
9. The furnace may be used for temporary heating of build­ings or structures under construction only when the following conditions have been met:
a. The furnace venting system must be complete
and installed per manufacturers instructions.
b. The furnace is controlled only by a room ther-
mostat (no field jumpers).
c. The furnace return air duct must be complete
and sealed to the furnace and clean air filters are in place.
d. The furnace input rate and temperature rise
must be verified to be within nameplate mark­ing.
e. 100% of the furnace combustion air require-
ment must come from outside the structure.
CARBON MONOXIDE POISONING HAZARD Failure to follow the steps outlined below for each ap­pliance connected to the venting system being placed into operation could result in carbon monoxide poi­soning or death. The following steps shall be followed for each appli­ance connected to the venting system being placed into operation, while all other appliances connected to the venting system are not in operation:
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and hor­izontal pitch, as required in the National Fuel Gas Code, ANSI Z223.1/NFPA 54 or the CAN/CGA B149 Installation Codes and these instructions. Deter­mine that there is no blockage or restriction, leak­age, corrosion and other deficiencies which could cause an unsafe condition.
3. As far as practical, close all building doors and windows and all doors between the space in which the appliance(s) connected to the venting system are located and other deficiencies which could cause an unsafe condition.
4. Close fireplace dampers.
5. Turn on clothes dryers and any appliance not con­nected to the venting system. Turn on any ex­haust fans, such as range hoods and bathroom ex­hausts, so they are operating at maximum speed. Do not operate a summer exhaust fan.
6. Follow the lighting instructions. Place the appli­ance being inspected into operation. Adjust the thermostat so appliance is operating continuously.
7. If improper venting is observed during any of the above tests, the venting system must be corrected in accordance with the National Fuel Gas Code, ANSI Z221.1/NFPA 54 and/or CAN/CGA B149.1 In­stallation Codes.
8. After it has been determined that each appliance connected to the venting system properly vents where tested as outlined above, return doors, win­dows, exhaust fans, fireplace dampers and any other gas-fired burning appliance to their previous conditions of use.
© 2014 Trane All Rights Reserved 18-CD29D1-11
Page 3
Installer’s Guide
WARNING
!
CAUTION
!
f. The furnace return air temperature range is
between 55 and 80 degrees Fahrenheit.
g. Clean the furnace, duct work, and components
upon substantial completion of the construc­tion process, and verify furnace operating con­ditions including ignition, input rate, tempera­ture rise and venting, according to the manu­facturer's instructions.
10. This product must be gas piped by a Licensed Plumber or Gas Fitter in the Commonwealth of Massachusetts.
FIRE OR EXPLOSION HAZARD Failure to follow the safety warnings exactly could result in serious injury, death or property damage. Improper servicing could result in dangerous opera­tion, serious injury, death, or property damage.
GENERAL INSTALLATION INSTRUCTIONS
The manufacturer assumes no responsibility for equip­ment installed in violation of any code or regulation. It is recommended that Manual J of the Air Condition­ing Contractors Association (ACCA) or A.R.I. 230 be followed in estimating heating requirements. When estimating heating requirements for installation at altitudes above 2000 ft., remember the gas input may need to be reduced (See High Altitude Installation).
Material in this shipment has been inspected at the factory and released to the transportation agency without known damage. Inspect exterior of carton for evidence of rough handling in ship­ment. Unpack carefully after moving equipment to approximate location. If damage to contents is found, report the damage immediately to the de­livering agency.
Codes and local utility requirements governing the installation of gas fired equipment, wiring, plumb­ing, and flue connections must be adhered to. In the absence of local codes, the installation must conform with latest edition of the National Fuel Gas Code ANSI
Z223.1 • National Installation Code, CAN/CGA B149.1.  
The latest code may be obtained from the American Gas Association Laboratories, 400 N. Capitol St. NW, Washington D.C. 20001. 1-800-699-9277 or www.aga.org These furnaces have been classified as CATEGORY IV furnaces in accordance with latest edition of ANSI
Z21.47 • CAN/ CGA 2.3 standards.
Category IV furnaces operate with positive vent stat­ic pressure and with a flue loss less than 17 percent. These conditions require special venting systems, which must be gas tight and water tight. These Cate­gory IV Direct Vent furnaces are approved for installa-
tion in  Manufactured/ Mobile housing when used with  BAYMFGH100A.
Contents
INSTALLATION INSTRUCTIONS
General Installation Instructions 3 Location and Clearances 4 Outline Drawings 5 Upflow Installation 7 Downflow Installation 7 Horizontal Installation 7 Air For Combustion and Ventilation 8 Duct Connections 10 Return Air Filters 11 General Venting Instructions 15 Venting Material 17 Venting Tables 18 Horizontal Venting 21 Venting Through The Wall 21 Venting Through The Roof 22 Downward Venting 24 Venting Through a Masonry Chimney 24 Condensate Drain Instructions 27 Electrical Connections 30 Field Wiring Diagrams 29 Gas Piping 32 Combustion Input Checks 33
Start Up and Adjustment 36
Preliminary Inspections 36 Lighting Instructions 36 Sequence Of Operation 37 Control And Safety Switch Adjustments 37 Airflow Adjustment 37
Abnormal Conditions 38
IFC Error Flash Code 40
To prevent shortening its service life, the furnace should not be used as a “Construction Heater” during the finish­ing phases of construction until the requirements listed in item 9, a-g of the safety section of this publication have been met. Condensate in the presence of chlorides and fluorides from paint, varnish, stains, adhesives, clean­ing compounds, and cement create a corrosive condition which may cause rapid deterioration of the heat exchang­er.
18-CD29D1-11 3
Page 4
Installer’s Guide
CAUTION
!
WARNING
!
UPFLOW
FURNACE
CASED
COIL
SCREWS
(BOTH SIDES)
STANDOFFS
(BOTH SIDES)
STANDOFFS (4)
DRILL SCREWS (4)
WARNING
!
EXPLOSION HAZARD! PROPANE GAS IS HEAVIER THAN AIR AND MAY COLLECT IN ANY LOW AREAS OR CONFINED SPAC­ES. IN ADDITION, ODORANT FADE MAY MAKE THE GAS UNDETECTABLE EXCEPT WITH A WARNING DEVICE. IF THE GAS FURNACE IS INSTALLED IN A BASEMENT, AN EXCAVATED AREA OR A CONFINED SPACE, IT IS STRONGLY RECOMMENDED TO CON­TACT A GAS SUPPLIER TO INSTALL A GAS DETECT­ING WARNING DEVICE IN CASE OF A GAS LEAK.
NOTE: The manufacturer of your furnace does NOT test any detectors and makes no representations regarding any brand or type of detector.
Do NOT install the furnace in a corrosive or contaminated atmosphere.
LOCATION AND CLEARANCES
The location of the furnace is normally selected by the ar­chitect, the builder, or the installer. However, before the furnace is moved into place, be sure to consider the follow­ing requirements:
1. Is the location selected as near the vent and as central­ized for heat distribution as practical?
2. Do all clearances between the furnace and enclosure equal or exceed the minimums shown in the Table 1.
3. Is there sufficient space for servicing the furnace and other equipment? A minimum of 24 inches front ac­cessibility to the furnace must be provided. Any access door or panel must permit removal of the largest com­ponent.
4. Are there at least 3 inches of clearance between the fur­nace front panel and any closed panel or door provided?
5. Are the ventilation and combustion air openings large enough and will they remain unobstructed? If outside air is used, are the openings set 12" minimum above the highest snow accumulation level?
6. Allow sufficient height in supply plenum above or below the furnace to provide for cooling coil installation if the cooling coil is not installed at the time of this furnace installation.
7. A furnace shall be installed so electrical components are protected from water.
8. If the furnace is installed in a residential garage, it must be installed so that the burners and the ignition source are located not less than 18 inches (46 cm) above the floor and the furnace must be located or protected to avoid physical damage from vehicles.
UPFLOW INSTALLATION
Standoffs and screws (See Figure 1) are included with the cased coils for attachment to the furnace. There are clearance alignment holes near the bottom of the coil wrapper. Drill screws are used to engage the fur­nace top flanges. The standoff is inserted into the cabinet alignment hole. The drill screws are inserted through the standoffs then screwed into the furnace flange.
The coil is always placed downstream of the furnace airflow.
1
FOR VERTICAL
INSTALLATIONS:
DOWNFLOW INSTALLATIONS
FIRE HAZARD Do NOT install the furnace directly on carpeting, tile or other combustible material other than wood floor­ing. For vertical downflow application, subbase (BAY­BASE-205) must be used between the furnace and combustible flooring. When the downflow furnace is installed vertically with a cased coil, a subbase is not required.
Required floor opening:
IMPORTANT:
The furnace must be installed level. The only allowable varia­tion would be slightly to the left and/or forward in upflow instal­lations or slightly toward the front in horizontal installations. This is necessary for proper condensate drainage.
NOTE: On upflow 5 or 6 ton airflow models where the airflow re­quirement exceeds 1800 CFM - Models will require return air openings and filters on: (1) both sides; or (2) one side and the bottom; or (3) just the bottom.
4 18-CD29D1-11
2
CABINET
WIDTH
17-1/2" 16-1/4" 16-5/8" 20-1/8" 15-5/8" 19-3/8"
21" 19-3/4" 20-1/8" 20-1/8" 19-1/8" 19-3/8"
24-1/2" 23-1/4" 23-5/8" 20-1/8" 22-5/8" 19-3/8"
SUBBASE CROSS SECTION
TABLE 1
RETURN
DUCT WIDTH
FLOOR OPENING PLENUM OPENING
"A" "B" "C" "D"
Page 5
1. *UH1D120A9601, *UH1C080A9601, *UH1C100A9481, AND
UH1D100A9601 REQUIRE 3” DIAMETER VENT PIPE.
2. DIAMETER OF VENT PIPE MAY BE LIMITED TO 2-1/2” OR 3”
ON SOME MODELS AT DIFFERENT ALTITUDES. REFER TO THE
VENT LENGTH TABLE FOR PROPER APPLICATION.
Installer’s Guide
From Dwg. C341884 Rev. 9
(ALL DIMENSIONS ARE IN INCHES)
*UH1 OUTLINE DRAWING, UPFLOW / HORIZONTAL
18-CD29D1-11 5
Page 6
Installer’s Guide
From Dwg. C341885 Rev. 7
(ALL DIMENSIONS ARE IN INCHES)
*DH1 OUTLINE DRAWING, DOWNFLOW / HORIZONTAL
17-1/2" 2-1/4" 16-1/4" 16"
MODEL DIM "A" DIM"B" DIM "C" DIM "D"
*DH1B040A9241
*DH1B065A9421
*DH1C085A9481 21" 2-1/2" 19-3/4" 19-1/2"
*DH1D110A9601 24-1/2" 2-15/16" 23-1/4" 23"
* May be "A" or "T"
Part numbers can end in A-Z
6 18-CD29D1-11
Page 7
Installer’s Guide
3
A (width)
FURNACE
FRONT
HORIZONTAL INSTALLATION
The coil and furnace must be fully supported when used in the horizontal position. It is always recommended that an auxiliary drain pan be installed under a horizontally in­stalled evaporator coil or 95% gas furnace. Connect the aux­iliary drain line to a separate drain line (no trap is needed in this line). Three brackets (with screws) are included with downflow furnaces for installation to stabilize and secure the fur­nace and TXC cased coil in the horizontal position. See Figure 4.
IMPORTANT: The 2/4TXC cased coil must be placed downstream of the furnace. In horizontal installations, the apex of the coil may point either toward or away from the furnace. See the 2/4TXC coil Installer's Guide for more details.
The cased coil is secured to the furnace and both the fur­nace and the cased coil must be properly supported. The brackets mount using the rear screws on the coil case and use the screws provided to secure the bracket to the fur­nace. The remaining bracket is placed as close to center as possible (horizontally) between the coil case front and the
furnace  bottom  channel  (for  downow/horizontal  furnace). 
Use four of the screws provided to secure the bracket. The upflow furnace, converted to horizontal, aligns and attaches the TXC coil as in Figure 1. However, the coil requires ad­ditional support.
B (depth)
D
C
5
UPFLOW/ HORIZONTAL SHOWN
The furnace may be placed horizontally in a crawl space on a pad or other noncombustible material which will raise the unit for sufficient protection from moisture. The furnace
must be supported at both ends and the middle when installed horizontally. The furnace must also be elevated a minimum of 6 inches to allow clearance for the condensate drain to exit the cabinet in the horizontal position.
The horizontal furnace may also be suspended from the
joists  using  3/8"  all-thread  rods  with  pieces  of  angle  iron 
underneath the furnace to form a hanging rack at both ends and the midpoint. The rods need to be of sufficient length to allow for proper clearances from combustible materials. The angle iron needs to be at least 32" in length to allow for access to service panels.
6
50 CU. FT. OR MORE PER 1000 BTU/HR. INPUT ALL EQUIP. INSTALLED
4
CASED COIL CONNECTION
BRACKET FOR DOWNFLOW 
FURNACE IN HORIZONTAL
DOWNFLOW ONLY
The furnace may be installed in an attic or crawl space in the horizontal position by placing the furnace on the left side (as viewed from the front in the vertical position). The horizontal furnace installation in an attic should be on a service platform large enough to allow for proper clearances on all sides and service access to the front of the furnace (See Figure 3 & Clearance Table 1). Line contact is only permissible between lines formed by intersections of the top and two sides of the furnace casing and building joists, studs, or framing.
UNCONFINED
AIR FOR COMBUSTION AND VENTILATION
If these furnaces are installed in a nondirect vent capac­ity then the adequate flow of combustion and ventilating air must not be obstructed from reaching the furnace. Air openings provided for combustion air must be kept free of obstructions which restrict the flow of air. Airflow restric­tions affect the efficiency and safe operation of the furnace.
Keep this in  mind  should  you choose to  remodel  or  change 
the area which contains your furnace. Furnaces must have a free flow of air for proper performance. Provisions for combustion and ventilation air shall be made in accordance with latest edition of Section 5.3, Air for Com­bustion and Ventilation, of the National Fuel Gas Code,
ANSI Z223.1  —  CAN/CGA B149.1  or  applicable provisions 
of the local building codes. Special conditions created by mechanical exhausting of air and fireplaces must be con­sidered to avoid unsatisfactory furnace operation.
18-CD29D1-11 7
Page 8
Installer’s Guide
OUTSIDE AIR IS RECOMMENDED
The use of indoor air for most applications is acceptable, unless there is the presence of corrosive chemicals or contamination. Certain types of installation will require the use of outside air for combustion. The following types of installations will require use of OUTDOOR AIR for combustion, due to chemical exposures: * Commercial buildings
* Buildings with indoor pools
* Furnaces installed in “confined” laundry rooms * Furnaces installed in “confined” hobby or craft rooms * Furnaces installed near chemical storage areas. Exposure to the following substances in the combustion air supply will also require OUTDOOR AIR for combustion: * Permanent wave solutions * Chlorinated waxes and cleaners * Chlorine based swimming pool chemicals * Water softening chemicals * Deicing salts or chemicals * Carbon Tetrachloride * Halogen type refrigerants * Cleaning solvents (such as perchloroethylene) * Printing inks, paint removers, varnish, etc. * Hydrochloric acid * Cements and glues * Antistatic fabric softeners for clothes dryers * Masonry acid washing materials
Furnace locations may be in a “confined space” or an “un- confined space”.
Unconfined space is defined in Figure 6. These spaces may have adequate air by infiltration to provide air for combus-
tion and  ventilation.  Buildings  with  tight   construction  (for 
example, weather stripping, heavily insulated, caulked, va­por barrier, etc.), may need additional air to be provided as described for confined space.
1. All air from inside the building as in Figure 8: The con­fined space shall be provided with two permanent open­ings communicating directly with an additional room(s) of sufficient volume so that the combined volume of all spaces meets the criteria for an unconfined space. The total input of all gas utilization equipment installed in the combined space shall be considered in making this determination. Refer to Table 2 for minimum open ar­eas requirements.
2. All air from outdoors as in Figure 9: The confined space shall be provided with two permanent openings, one commencing within 12 inches of the top and one com­mencing within 12 inches of the bottom of the enclo­sure. The openings shall communicate directly, or by ducts, with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors. Refer to Table 2, for minimum open areas requirements.
TABLE 3
MINIMUM FREE AREA IN SQUARE INCHES
EACH OPENING (FURNACE ONLY)
Furnace
Maximum
BTUH/INPUT
Rating
40,000 60,000 80,000 97,000
110,000
Air
From
Inside
100 100 100 100 110
Air From Outside
Vertical
Duct
10 15 20 25 28
Horizontal
Duct
20 30 40 50 55
8
Confined spaces are installations with less than 50 cu. ft. of
space per 1000  BTU/hr  input  from  all  equipment  installed, 
as in Figure 7. Air for combustion and ventilation require­ments can be supplied from inside the building as in Figure 8 or from the outdoors, as in Figure 9.
Table 2
MINIMUM AREA IN SQUARE FEET
FOR UNCONFINED SPACE INSTALLATIONS
FURNACE MAXI-
MUM BTUH INPUT
RATING
40,000 60,000 80,000 97,000
110,000
WITH 8 FT. CEILING
MINIMUM AREA IN SQUARE FEET
OF UNCONFINED SPACE
250 375 500 625 688
7
CONFINED
SPACE
8 18-CD29D1-11
Page 9
9
Installer’s Guide
On any job, flexible connections of nonflammable materi­al may be used for return air and discharge connections to pre vent transmission of vibration. Though these units have been specifically designed for quiet, vibration free operation, air ducts can act as sounding boards and could, if poorly in­stalled, amplify the slightest vibration to the annoyance lev­el. When the furnace is located in a utility room adjacent to the living area, the system should be carefully designed with returns to minimize noise transmission through the return air grille. Although these furnaces are designed with large blowers operating at moderate speeds, any blow­er moving a high volume of air will produce audible noise which could be objectionable when the unit is located very close to a living area. It is often advisable to route the re­turn air ducts under the floor or through the attic. Such de­sign permits the installation of air return remote from the living area (i.e. central hall). When the furnace is installed so that the supply ducts carry air circulated by the furnace to areas outside the space con­taining the furnace, the return air shall also be handled by a duct(s) sealed to the furnace and terminating outside the space containing the furnace.
RETURN AIR DUCT CONNECTION
NOTE: On upflow 5 or 6 ton airflow models where the airflow re­quirement exceeds 1800 CFM - Models will require return air openings and filters on: (1) both sides; or (2) one side and the bottom; or (3) just the bottom.
All return air duct systems should provide for installation of return air filters.
1. Determine the appropriate position to set the furnace in order to connect to the existing supply and return ductwork.
2. For side return installations on upflow models, remove the insulation around the opening in the blower com­partment.
DUCT CONNECTIONS
Air duct systems should be installed in accordance with standards for air conditioning systems, National Fire Pro­tection Association Pamphlet No. 90. They should be sized in accordance with ACCA Manual D or whichever is appli­cable. Central furnaces, when used in connection with cooling units, shall be installed in parallel or on the upstream side of the cooling coil to avoid condensation in the heat ex­changer. With a parallel flow arrangement, the dampers or other means used to control flow of air shall be adequate to prevent chilled air from entering the furnace, and if manu­ally operated, must be equipped with means to prevent op­eration of either unit unless the damper is in full heat or cool position.
NOTE: Minimum return air temperature is 55° F.
3. The side panels on upflow furnaces include locating notches which may be used as guides for cutting an opening for return air. Refer to Figure 11 and the out­line drawing on pages 5-6 for duct connection dimen­sions for various furnaces.
  4.  If a 3/4" ange is to be used for attaching the air inlet 
duct, add to cut where indicated by dashed lines in Figure 11. Cut corners diagonally and bend outward to form flange.
5. If flanges are not required, and a filter frame is in­stalled, cut along knockout guidelines.
6. Upflow Furnaces: Use the optional filter rack on either side or on the bottom if the filter is to be used within the furnace cabinet.
When the upflow furnace is installed in the horizontal
application and a return duct is attached to the top side as shown in Figure 10, install the filter in a remote location.
Do not install the filter in the return duct directly
above the furnace in horizontal applications.
18-CD29D1-11 9
Page 10
Installer’s Guide
WARNING
!
WARNING
!
When the upflow furnace is installed in the horizontal
application and a close coupled (less than 36") return duct is attached to the bottom side of the furnace as
shown in Figure 10, securely attach a 1/2" mesh metal 
hardware cloth protective screen to the inside bottom of the filter grill to prevent personal injury from
contacting moving parts when reaching into the return opening to replace the filter.
Close coupled (less than 36") return (filter directly
beneath bottom side return) is not recommended due to noise considerations.
Downflow Furnaces:  Brackets are factory supplied 
to mount filters in the return air duct work.
FIRE OR EXPLOSION HAZARD
Do not install the filter in the return duct directly above the furnace in horizontal applications. Install the filter re­motely. Failure to follow the safety warnings exactly could result in serious injury, death or property damage.
SAFETY HAZARD
To prevent injury or death due to contact with moving parts, turn the power to the furnace off before servicing filters
Failure to follow the safety warnings exactly could result in serious injury, death or property damage.
REMOVE FILTER FROM UPFLOW FURNACE WHEN RETURN DUCT IS ATTACHED TO FURNACE TOP SIDE (HORIZONTAL APPLICATIONS) AS SHOWN.
Close coupled (less than 36") return (filter directly beneath bottom side return) not recommended due to noise considerations. If used, securely
attach 1/2" mesh metal hardware cloth 
protective screen to the inside bottom of filter grill.
FILTER
0
7. Connect the duct work to the furnace. See Outline Drawing (pages 5-6) for supply and return duct size and location. Flexible duct connectors are recommend­ed to connect both supply and return air ducts to the furnace. If only the front of the furnace is accessible, it is recom­mended that both supply and return air plenums are removable.
8. When replacing a furnace, old duct work should be cleaned out. Thin cloths should be placed over the registers and the furnace fan should be run for 10 min­utes. Don’t forget to remove the cloths before you start the furnace.
q
LOCATING NOTCHES PROVIDED FOR SIDE RETURN CUTOUT
*
*
*
*
CUT OUT
FOR
SIDE
FILTER
FRONT
of Furnace
*SEE OUTLINE DRAWING
RETURN AIR FILTERS (Filter and filter rack are not supplied with unit)
TYPICAL UPFLOW RETURN AIR FILTER INSTALLATIONS
These furnaces require high velocity type air filters. The optional filters may be located within the furnace blower
compartment for UPFLOW furnaces in either a BOTTOM 
or SIDE (left side or right side) return air inlet. Some optional filters may need to be trimmed for side or bottom filter use.
The furnace and the blower filter rack installation can be seen in Figure 12.
The optional furnace filter in the bottom or side configura­tion can be removed by simply turning the two latches on the blower door and tilting the door forward.
The filter rails are spring loaded for automatic adjustment to allow standard size, locally obtainable replacement filters. The filter rack itself slides to adjust to the required width needed for bottom or side return.
TABLE 4 - MINIMUM CLEARANCE FROM COMBUSTIBLE MATERIALS FOR
UPFLOW/HORIZONTAL LEFT AND DOWNFLOW/HORIZONTAL RIGHT FURNACES
UNIT LOCATION
FURNACE SURFACE
SIDES 0" 1" 0"
BACK 0" 3" 6"
TOP 1" 1" 1"
FRONT 3" 3" 18"
VENT 0" 0" 0"
NOTE: CLEARANCE REQUIRED AT TOP OF PLENUM IS 1"
10 18-CD29D1-11
VERTICAL
CLOSET
HORIZONTAL
CLOSET
HORIZONTAL
ALCOVE / ATTIC
Page 11
Installer’s Guide
Filter
TABLE 5
UPFLOW FURNACE RETURN AIR FILTERS
CABINET
WIDTH
14-1/2" 1 14" X 25" X 1" 17-1/2" X 25" X 1"
17-1/2" 1 17" X 25" X 1" 17-1/2" X 25" X 1"
21" 1 20" X 25" X 1" 17-1/2" X 25" X 1"
24-1/2" 1 24" X 25" X 1" 17-1/2" X 25" X 1"
**NOTE: For upflow 5 ton airflow models where the airflow requirement exceeds 1800 CFM - Models will require return air openings and filters on: (1) both sides, or (2) one side and the bottom, or (3) just on the bottom
QTY*
CABINET
BOTTOM FILTER
CABINET
SIDE FILTER
Airflow
NOTE: The narrow 14.5" width furnace cabinet prevents use of the filter rack for right side return. Pre-drill clear­ance holes and then attach filter clips with the screws provided. The filter clip with the leaf spring mounts in the rear of the cabinet
OPTIONAL FILTER RACK INSTALLATION FOR BOTTOM RETURN - BAYRACK960
The following checklist should be used when installing as a bottom return filter on an upflow furnace:
a. Remove the filter.
b. Remove the bottom panel.
c. Pre-drill two engagement holes with 3/16" drill at
dimple locations. See Figure 14.
d. With the filter removed, the filter rack is compressed
and then inserted into the bottom of the furnace. The retaining screw/pin on each side inserts into engage­ment holes at the bottom of the furnace cabinet side. See Figure 15.
e. Reinstall the furnace filter in the bottom position by
inserting the chamfer end first into the filter rack.
NOTE: Remove the bottom front channel to install the filter rack in the 14-1/2" width cabinet furnaces.
e
w
Airflow
BOTTOM FILTER RACK INSTALLATION
r
Blower Deck Engagement
PRE-DRILL
Two clearance holes with a 3/16” drill at dimple locations (one per side)
t
Furnace
Cabinet
Side
Hole
VIEW
Rack
Filter Rack Retaining
Optional Filter Rack Accessory Kit
Engagement Hole For
Filter Rack Installation With Bottom Return (Pre-drill 3/16” diameter clearance holes)
Screw/Pin
BAYRACK960A
18-CD29D1-11 11
Page 12
Installer’s Guide
Filter Rack Assembly
Furnace Blower Deck
Filter Rack Retaining Screw/Pin
Engagement Hole For
Return
Filter Rack Installation With Side
Furnace
Cabinet
Side
Filter Rack
RETAINING
PIN
(Both Sides)
SPRINGS
SIDE
CUTOUT
FILTER
RACK
RAILS
BOTTOM
PANEL
INSTALLED
Airflow
RETAINING
PIN
(Both Sides)
SPRINGS
SIDE
CUTOUT
FILTER
RACK
RAILS
BOTTOM
PANEL
INSTALLED
Airflow
TABLE 6
Cabinet Width Left Side Bottom Right Side
14.5 X
17.5 X X X
21 X X X
24.5 X X X
1. UC1B060C has 10x7 blower which requires use of alternate filter clips for left side filter. "K1" and later use the filter rack.
2. Remove bottom front channel to install or reposition filter rack.
X - All Models
OPTIONAL FILTER RACK INSTALLATION FOR SIDE RETURN AIR ON UPFLOW FURNACES (Left or Right) ­BAYRACK960
The following checklist should be used when installing a right or left side return filter on an upflow furnace:
a. Remove the filter.
b. Leave the bottom panel in place.
c. Make side cutout by following the directions in the
“Return Air Duct Connections” section on page 9.
d. Compress the filter rack and reinstall in the side
position on the furnace. Confirm that the upper retaining pin/screw locks into the engagement hole in the blower deck and the lower pin/screw rests against the side of the bottom panel. See Figures 14, 18-20.
e. Reinstall the furnace filter in the side position by
inserting the chamfer end first into the filter rack.
1
X2Use Alternate Filter Clips Only
i
Typical Upflow Left Side Return Filter Rack Installation
o
y
u
BLOWER DECK
12 18-CD29D1-11
BOTTOM ENGAGEMENT
Furnace
Cabinet
Side
Retaining Screw/Pin
Filter Rack
Bottom Panel
Typical Upflow Right Side Return Filter Rack Installation
p
Airflow
Accessory filter kit
BAYFLTR203, 204, or 
205 used for Upflow Horizontal furnaces
Typical Horizontal Filter Installation
Page 13
Installer’s Guide
REAR
SIDE
CUT-OUT
ALTERNATE FILTER CLIPS LOCATION
RETURN AIR FILTERS FOR UPFLOW FURNACE IN HORIZONTAL CONFIGURATION
When the Upflow Furnace is installed in a horizontal configuration, the filter must never be installed inside or outside the cabinet directly above the blower assembly. See Figure 10 (page 11). Remote filter grilles may be used for homeowner convenience or the filters may be installed in the duct work upstream of the furnace. See Figures 20 (page 13).
Optional horizontal lter conversion kits are BAYFLTR203  for 17 1/2"  width cabinets, BAYFLTR204 for 21" width  cabinets, and BAYFLTR205 for 24" width cabinets.  These 
include filters and brackets necessary for horizontal filters. See Figure 20.
ALTERNATE UPFLOW FILTER CLIP / BRACKET INSTALLATION - KIT09224
1. Determine the location to be used. The furnace cabinet has dimples for location of the alternate furnace clips (Side return only). Pre-drill clearance holes with a
3/16" drill.  Bottom return holes are pre-drilled.
2. Install the clips in front and rear of the desired location using the screws provided. The filter clip with the leaf spring mounts in the rear of the cabinet. See Figure21.
a
TYPICAL DOWNFLOW FURNACE RETURN AIR FILTER INSTALLATIONS
Two high velocity type air filters are required for each down­flow furnace. Downflow furnace filters must be located outside the furnace cabinet. Typical installations are shown in Figures 22 and 23. Tables 8 and 9 provide information for installation of the filter retaining brackets shipped with downflow furnaces.
s
Airflow
d
Airflow
INSTALLING THE OPTIONAL FILTER
The filter may need to be cut to fit the unit depending on the location of the return air filter.
A score line and the words “CUT HERE” are located on the end of the filter. If your application requires cutting the filter, do so as indicted by the score mark.
TABLE 7
UNIT SIZE
RETURN AIR
BOTTOM SIDE
14-1/2" CUT ON LINE DO NOT CUT
17-1/2" DO NOT CUT DO NOT CUT
21" DO NOT CUT CUT ON LINE
24-1/2" DO NOT CUT CUT ON LINE
18-CD29D1-11 13
CABINET
WIDTH
14-1/2" 2 - 14X20X1 12-7/8" 17-1/2" 2 - 16X20X1 14-3/8"
21" 2 - 16X20X1 13-1/8"
24-1/2" 2 - 16X20X1 11-5/8"
* Location dimension is from end of duct to the screw holes for the bracket.
CABINET
WIDTH
14-1/2" 13-1/4" 12" 14" 17-1/2" 16-1/4" 15" 14"
21" 19-3/4" 19-1/2" 14"
24-1/2" 23-1/4" 22" 14"
Optional accessory door kit BAYFLTR206 is also available 
with narrow door to avoid flue piping in downflow furnaces.
RETURN
DUCT
WIDTH
TABLE 8
FILTER
SIZE
TABLE 9
FILTER ACCESS
OPENING - DI-
MENSION "A"
FILTER BRACKET
LOCATION *
FILTER ACCESS
OPENING -
DIMENSION "B"
Page 14
Installer’s Guide
WARNING
!
GENERAL VENTING
CARBON MONOXIDE POISONING HAZARD FURNACE MUST BE VENTED PROPERLY. FAILURE TO FOLLOW THE INSTALLATION INSTRUCTIONS FOR THE VENTING SYSTEM COULD RESULT IN CARBON MONOXIDE POISONING, FIRE OR SMOKE THAT CAN CAUSE SERIOUS BODILY INJURY, DEATH OR PROPERTY DAMAGE.
IMPORTANT: The building owner/maintenance provider must keep the area around the vent clear from snow.
THIS  FURNACE  MUST  BE  VENTED  TO  THE  OUT­DOORS. THESE FURNACES ARE INDUCED DRAFT VENTED AND MUST NOT  BE  CONNECTED  TO  ANY  VENT SERVING ANOTHER APPLIANCE. PLEASE NOTE THAT THESE FURNACES USE POSITIVE- PRESSURE VENT SYSTEMS. Proper venting is essential to obtain maximum efficiency from a condensing furnace. Proper installation of the vent system is necessary to assure drainage of the condensate and prevent deterioration of the vent system. American Gas Association has certified the design of con­densing furnaces for a minimum of 0" clearance from com­bustible materials with a single wall plastic vent pipe.
The  recommended  system  is  assembled  from  2",  2-1/2",  or 
3" plastic pipe and fittings (See Table 10, page 16). Where the system is routed to the outdoors through an existing masonry chimney containing flue products from another gas appliance, or where required by local codes, then 3" venting of Type 29-4C stainless steel must be used in place of PVC material. These furnaces have been classified as CATEGORY IV furnaces in accordance with the latest edition of ANSI  Z21.47 • CAN/  CGA-2.3  Standards.  Category  IV  fur­naces operate with positive vent pressure and with a vent gas temperature less than 140°F above the dewpoint. These conditions require special venting systems, which must be gas tight and water tight.
NOTE: When an existing furnace is removed from a venting sys­tem serving other gas appliances, the venting system is likely to be too large to properly vent the remaining at­tached appliances.
IMPORTANT These Furnaces may be installed as Direct Vent (sealed combustion) or as Nondirect Vent (single pipe). The Furnaces are shipped DIRECT VENT with sealed combustion.
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon monoxide poisoning or death.
The following steps shall be followed for each appliance connected to the venting system being placed into operation, while all other appliances connected to the venting system are not in operation:
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and horizontal pitch, as required in the National Fuel Gas Code, ANSI Z223.1/NFPA 54 or the CSA B149.1 Natural Gas and Propane Installation Code and these instructions. Determine that there is no blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition.
3. As far as practical, close all building doors and windows and all doors between the space in which the appliance(s) connected to the venting system are located and other deficiencies which could cause an unsafe condition.
4. Close fireplace dampers.
5. Turn on clothes dryers and any appliance not connected to the venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they are operating at maximum speed. Do not operate a summer exhaust fan.
6. Follow the lighting instructions. Place the appliance being inspected into operation. Adjust the thermostat so appliance is operating continuously.
7. Test for spillage from draft hood equipped appliances at the draft hood relief opening after 5 minutes of main burner operation. Use the flame of a match or candle.
8. If improper venting is observed during any of the above tests, the venting system must be corrected in accordance with the National Fuel Gas Code, ANSI Z221.1/NFPA 54 and/or CSA B149.1 Natural Gas and Propane Installation Code.
9. After it has been determined that each appliance connected to the venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas-fired burning appliance to their previous conditions of use.
The following are general steps to be used to correct or resize a remaining vent system when a furnace which may not be common vented is removed from the system:
a.  Determine  the  Btu  per  hour  input  of  all  remaining 
appliances attached to the venting system.
b. Determine the diameter, rise, and lateral of the ex-
isting venting system, as well as quantity and type of bends.
c. Use the appropriate tables in the latest edition of
the  National  Fuel  Gas  Code  (ANSI  Z223.1  •  CAN/  CGA  B149.1  Installation  Codes  or  “Exhibit  J”  of  ANSI Z21.47 • CAN/  CGA-2.3 Standards. “Exhibit  J” 
includes examples and drawings of typical venting systems.
IMPORTANT:
These furnaces may be installed as Direct Vent (sealed combustion) or as Nondirect vent (single pipe). The furnac­es are shipped DIRECT VENT with sealed combustion.
For DIRECT VENT APPLICATION: The furnaces must be vented to the exterior of the house and combustion air MUST come through the inlet air pipe FROM OUTSIDE AIR.
For NONDIRECT VENT APPLICATION: The furnace shall be vented to the exterior of the house, but combustion air may enter from the surrounding area as long as combus­tion air requirements are met. (See AIR FOR COMBUS­TION AND VENTILATION)
14 18-CD29D1-11
Page 15
Installer’s Guide
Furnace
Vent
Air
Inlet
(See Note)
Furnace
Air
Inlet
Vent
Attic Vent
(See Note)
For DIRECT VENT APPLICATION: The Furnaces must be vented to the exterior of the house and combustion air MUST come through the inlet air pipe FROM OUTSIDE AIR.
NOTE: BAYVENT200* accessories can be used for inlet and outlet terminals when the pipes do not exit the structure together. For Canadian applications, venting systems must meet ULC-S636 requirements.
For NONDIRECT VENT APPLICATION: The Furnace shall be vented to the exterior of the house, but combustion air may enter from the surrounding area as long as combustion air requirements are met. (See AIR FOR
COMBUSTION AND VENTILATION)
FURNACE VENT / INLET PIPE INSTALLATION
There are many different variations of the vent / inlet air  pipe combination. The vent / inlet air combination used for 
installation of these Furnaces depends on the needs of the location. However, these guidelines must be followed:
1. The Furnace must vent outside the structure.
2. Furnace combustion air requirements must be met for non-direct, single pipe applications.
3. For direct vent application of these Furnaces, the vent pipe and air inlet pipe do not have to exit in the same air space. However, the longest individual pipe will
decide the value for the longest allowable equivalent vent/ inlet air length as shown in the vent length tables on page 17 and 18.
NOTE: For single pressure zone applications, see Figure
27.
The following are EXAMPLES ONLY:
EX. 1 —
Example 1 shows the vent pipe exhausting through the roof and the inlet air coming from the interior of the house. The inlet air coming from the interior of the house must meet combustion requirements for area, etc., as shown in the sec-
tion AIR FOR COMBUSTION AND VENTILATION in this 
Installer’s Guide.
Example 1
EX. 2 —
The inlet air does not have to come from outside the structure. Example 2 shows the inlet air, may come from the attic if the requirements for combustion air are met as shown in the section AIR FOR COMBUSTION AND VENTI­LATION.
NOTE: If only the flue gas pipe is to the outside of the structure, a straight section of pipe (long enough to exit the Furnace cabinet) must be attached to the inlet air side with an elbow (which is 5 to 10 equiv. ft.) installed on the end to prevent dust and debris from falling directly into the Furnace.
Example 2
18-CD29D1-11 15
Page 16
Installer’s Guide
WARNING
!
WARNING
!
PVC VENT FITTING MATERIAL
These fittings are available from your Gas Furnace Distributors. Straight Pipe Sections, Couplings, 45° Elbows, 60° Elbows, 90° Elbows, Vent or Sanitary Tee, or other necessary fittings may be 2", 2½", 3", or 4" diameter. The allowable materials are shown in Table 10.
VENT FITTING MATERIAL – PLASTIC
Gas and liquid tight single wall vent fittings, designed for resis­tance to corrosive flue condensate, MUST be used throughout. Listed in Table 10 are designations for different types of 2" and 3" size pipe and fittings that meet these requirements. The ma­terials listed  are  various  grades  of  PVC,  CPVC, ABS,  and  Du­raVent PolyPro®.
ATTACHING VENT PIPING
Important: Products installed in Canada must use vent systems that are certified to the Standard for Type BH Gas Venting Systems (ULC S636) for Class II-A venting systems (up to 65°C). Components of the vent system must not be interchanged with other vent systems or unlisted pipe or fittings. Plastic components, specified primers, and glues must be from a single system manufacturer and not intermixed with other system manufacturer's vent system parts. In addition, the first three feet of the vent pipe must be visible for inspection.
PIPE JOINTS: All joints must be fastened and sealed to prevent escape of combustion products into the building.
MANUFACTURED MODULAR VENTING SYSTEMS
CARBON MONOXIDE POISONING HAZARD See Table 10 for manufactured modular venting systems that are approved for use with this product. Follow the manufacturer's installation instructions when installing the venting system. Failure to follow this warning may result in property damage, severe personal injury, or death.
APPROVED VENT PIPE MATERIALS
CARBON MONOXIDE POISONING HAZARD Do not use cement on polypropelene venting systems. Follow the manufacturer's installation instructions when installing the venting system. Failure to follow this warning may result in property damage, severe personal injury, or death.
For manufactured modular venting systems that are ap­proved with this product see Table 10. Do not drill into polypropelene venting pipes
BONDING OF PVC NOTE: It is recommended that the first joints from the furnace be connected and sealed with high temperature RTV. This will enable the pipes to be removed later without cutting. Be sure to properly support these joints.
Commercially available solvent cement must be used to join the pipe and fittings. Follow instructions on the container carefully. Procedure for Cementing Joints:
1. Cut pipe square, remove ragged edges and burrs. Chamfer end of pipe, then clean fitting socket and pipe joint area of all dirt, grease, moisture or chips.
2. After checking pipe and socket for proper fit, wipe sock­et and pipe with cleaner-primer. Apply a liberal coat of primer to inside surface of socket and outside of pipe.
    DO NOT ALLOW PRIMER TO  DRY BEFORE APPLY-
ING CEMENT.
3. Apply a thin coat of cement evenly in the socket. Quick­ly apply a heavy coat of cement to the pipe end and in­sert pipe into fitting with a slight twisting movement until it bottoms out.
4. Hold the pipe in the fitting for 30 seconds to prevent tapered socket from pushing the pipe out of the fitting.
5. Wipe all excess cement from the joint with a rag. Allow
TABLE 10
PLASTIC VENT PIPE DESIGNATIONS
PVC
ASTM STANDARD PIPE TYPE ALLOWABLE TEMPERATURE °F MARKING
F891 CELLULAR CORE D2665 DWV PIPE D1785 SCH 40, 80, 120 D2241 SDR SERIES
1 158 2 158 2 158 2 158
CPVC
ASTM STANDARD PIPE TYPE ALLOWABLE TEMPERATURE MARKING
D2846 CPVC 41
F441 SCH 40, 80
F442 SDR SERIES
2 212 2 212 2 212
ABS
ASTM STANDARD PIPE TYPE ALLOWABLE TEMPERATURE MARKING
D2661 SCH 40 DWV
F628 SCH 40 DWV CELLULAR CORE
3 180 3 180
DuraVent PolyPro® 45
ASTM STANDARD PIPE TYPE ALLOWABLE TEMPERATURE MARKING
NA NA 230 ULC-S636
1 Allowable temperatures based on classifications covered in ASTM D4396 [Deflection Temps Under Load (264 PSI)] 2 Allowable temperatures based on classifications covered in ASTM D1784 [Deflection Temps Under Load (264 PSI)] 3 Allowable temperatures based on classifications covered in ASTM D3965 [Deflection Temps Under Load (264 PSI)] 4 This furnace family is approved for venting with DuraVent PolyPro® venting systems. 5 Canadian venting systems must be composed of materials that meet ULC-S636.
ASTM F891 ASTM D2665 ASTM D1785 ASTM D2241
ASTM D2846
ASTM F441
ASTM F442
ASTM D2661
ASTM F628
16 18-CD29D1-11
Page 17
Seal VENT PIPE with RTV sealant
Seal INLET AIR PIPE
with RTV sealant
Front of Furnace
WARNING
!
15 minutes before handling. Cure time varies according to fit, temperature and humidity.
NOTE: Follow venting instructions carefully when using PVC cement.
IMPORTANT:
All joints must be water tight. Flue condensate is somewhat acidic, and leaks can cause equipment damage.
Connection of the pipe and collar of the combustion air inlet should just be a friction fit. It is recommended that
the inlet air joint be sealed with RTV type sealant to allow the joint to be separated for possible future service. The in­let and vent pipes must be properly supported throughout the entire length. Connection of the vent pipe to the vent collar should also be accomplished using RTV type sealant. This type sealant provides a connection which remains flexible and can be separated in the future if service needs require the removal of the vent pipe for service or clearance. See Figure 24.
NOTE: To ensure proper operation at the vent lengths indicated, the combustion air inlet and vent terminals should be in the same pressure zone. Terminating the vent and inlet in different pressure zones will change the maximum vent lengths and may cause nuisance tripping of the pressure switch(es). The amount of change can not be predicted. The selection of the inlet and outlet terminal locations are the responsibility of the designer/installer. If the installer chooses separate pressure zones for the terminals, the combustion air inlet termination must be in the higher (more positive) pressure zone.
Installer’s Guide
CARBON MONOXIDE POISONING HAZARD FAILURE TO FOLLOW THE DURAVENT INSTALLATION INSTRUCTIONS IF THE POLYPROPELENE VENTING SYSTEM IS BEING PLACED INTO OPERATION COULD RESULT IN CARBON MONOXIDE POISONING OR DEATH.
VENT AND INLET AIR CONNECTIONS
f
Products installed in Canada must use vent systems that are certified to the Standard for Type BH Gas Vent­ing Systems (ULC S636) for Class II-A venting systems (up to 65°C). Components of the vent system must not be interchanged with other vent systems or unlisted pipe or fittings. Plastic components, specified primers, and glues must be from a single system manufacturer and not intermixed with other system manufacturer's vent system parts. In addition, the first three feet of the vent pipe must be visible for inspection.
MAXIMUM VENT LENGHT TABLE
MAXIMUM VENT LENGTH:
*UH1B040A9241A 60 80 100 130 50 80 80 130
*UH1B060A9361A 60 80 100 130 50 80 80 130
*UH1B080A9421B 40 80 100 130 30 80 80 130
*UH1C080A9601A NOT ALLOWED NOT ALLOWED 70 130 NOT ALLOWED NOT ALLOWED 50 130
*UH1C100A9481A NOT ALLOWED NOT ALLOWED 90 130 NOT ALLOWED NOT ALLOWED 70 130
*UH1D100A9601A NOT ALLOWED NOT ALLOWED 90 130 NOT ALLOWED NOT ALLOWED 70 130
*UH1D120A9601A NOT ALLOWED NOT ALLOWED 50 130 NOT ALLOWED NOT ALLOWED 30 130
NOTES: * - First letter may be "A" or "T"
1. FOR DURAVENT MANUFACTURED MODULAR VENTING SYSTEMS THAT ARE APPROVED IN TABLE 10, EQUIVALENT VENT LENGTHS MAY BE DIF-
FERENT FROM WHAT IS SHOWN ABOVE. REFER TO THE VENTING SYSTEM MANUFACTURER'S INSTALLATION INSTRUCTIONS FOR APPROPRIATE VENTING DIAMETERS AND EQUIVALENT LENGTHS.
2. Minimum vent length for all models: 3' horizontal or 3' vertical.
3. DO NOT MIX PIPE DIAMETERS IN THE SAME LENGTH OF PIPE OUTSIDE THE FURNACE CABINET (Except adapters at the top of the furnace). If different inlet and vent pipe sizes are used, the vent pipe must adhere to the maximum length limit shown in the table above (See note 6 below for exception). The inlet pipe can be of a larger diameter, but never smaller than the vent pipe.
4. MAXIMUM PIPE LENGTHS MUST NOT BE EXCEEDED! THE LENGTH SHOWN IS NOT A COMBINED TOTAL, IT IS THE MAXIMUM LENGTH OF EACH (Vent or Inlet air pipes).
5. One SHORT radius 90° elbow is equivalent to 10' of 4" pipe, 10' of 3" pipe, or 8’ of 2” pipe. One LONG radius elbow is equivalent to 6' of 4" pipe, 7’ of 3” pipe, 6’ of 2.5” pipe, or 5' of 2" pipe. Two 45° elbows equal one 90° LONG elbow.
6. The termination tee or bend must be included in the total number of elbows. If the BAYAIR30AVENTA termination kit is used, the equivalent length of pipe is 5 feet. BAYVENT200B equivalent length is 0 feet.
7. Pipe adapters are field supplied (except for the *UH/DH2D120 models).
8. For Canadian applications, venting systems must meet ULC-S636 requirements.
18-CD29D1-11 17
MODEL
UPFLOW/ HORIZONTAL VENTING TABLE
DIRECT VENT (2 PIPE SYSTEM) -
MAXIMUM TOTAL EQUIVALENT FEET FOR
VENT AND INLET AIR PIPES (See Notes)
2" PIPE
& FITTINGS
2-1/2" PIPE
& FITTINGS
3" PIPE
& FITTINGS
TABLE 11
4" PIPE
& FITTINGS
NONDIRECT VENT (1 PIPE SYSTEM) -MAXIMUM TOTAL
2" PIPE
& FITTINGS
EQUIVALENT FEET FOR
VENT PIPE ONLY (See Notes)
2-1/2" PIPE
& FITTINGS
3" PIPE
& FITTINGS
4" PIPE
& FITTINGS
Page 18
Installer’s Guide
Vent only to outside
Air Inlet
B
A
A (0-2') or greater B (0-2') or greater A+B = 2' minimum
UPFLOW FURNACE
V
D
EE
V
G
INSIDE
CORNER DETAIL
B
L
V
V
FIXED
CLOSED
OPERABLE
F
B
C
V
FIXED
CLOSED
V
V
V
B
B
B
A
X
J
B
H
I
V
X
K
M
V
VENT TERMINAL
X
AIR SUPPLY INLET
AREA WHERE TERMINAL IS NOT PERMITTED
OPERABLE
Vent only to outside
Air Inlet
A
A = 2' minimum
DOWNFLOW
FURNACE
DOWNFLOW/ HORIZONTAL VENTING TABLE
TABLE 12
MAXIMUM VENT LENGTH:
DIRECT VENT (2 PIPE SYSTEM) - MAXIMUM TOTAL EQUIV-
ALENT FEET FOR VENT AND INLET AIR PIPES (SEE NOTES)
MODEL
2" PIPE
& FITTINGS
2-1/2" PIPE
& FITTINGS
3" PIPE
& FITTINGS
4" PIPE
& FITTINGS
*DH1B040A9241A 60 80 100 130 50 80 80 130
*DH1B065A9421A 45 80 100 130 40 80 80 130
*DH1C085A9481A NOT ALLOWED 80 100 130 NOT ALLOWED 80 80 130
*DH1D110A9601A NOT ALLOWED 15 60 130 NOT ALLOWED 25 70 130
NOTES: * - First letter may be "A" or "T"
1. FOR DURAVENT MANUFACTURED MODULAR VENTING SYSTEMS THAT ARE APPROVED IN TABLE 10, EQUIVALENT VENT LENGTHS MAY BE DIFFER-
ENT FROM WHAT IS SHOWN ABOVE. REFER TO THE VENTING SYSTEM MANUFACTURER'S INSTALLATION INSTRUCTIONS FOR APPROPRIATE VENTING DIAMETERS AND EQUIVALENT LENGTHS.
2. Minimum vent length for all models: 3' horizontal or 3' vertical.
3. DO NOT MIX PIPE DIAMETERS IN THE SAME LENGTH OF PIPE OUTSIDE THE FURNACE CABINET (Except adapters at the top of the furnace). If different inlet and vent pipe sizes are used, the vent pipe must adhere to the maximum length limit shown in the table above (See note 6 below for exception). The inlet pipe can be of a larger diameter, but never smaller than the vent pipe.
4. MAXIMUM PIPE LENGTHS MUST NOT BE EXCEEDED! THE LENGTH SHOWN IS NOT A COMBINED TOTAL, IT IS THE MAXIMUM LENGTH OF EACH (Vent or Inlet air pipes).
5. One SHORT radius 90° elbow is equivalent to 10' of 4" pipe, 10' of 3" pipe, or 8’ of 2” pipe. One LONG radius elbow is equivalent to 6' of 4" pipe, 7’ of 3” pipe, 6’ of
2.5” pipe, or 5' of 2" pipe. Two 45° elbows equal one 90° LONG elbow.
6. The termination tee or bend must be included in the total number of elbows. If the BAYAIR30AVENTA termination kit is used, the equivalent length of pipe is 5 feet. BAYVENT200B equivalent length is 0 feet.
7. Pipe adapters are field supplied (except for the *UH/DH2D120 models).
8. For Canadian applications, venting systems must meet ULC-S636 requirements.
NONDIRECT VENT (1 PIPE SYSTEM) - MAXIMUM TOTAL
EQUIVALENT FEET FOR VENT PIPE ONLY (SEE NOTES)
2" PIPE
& FITTINGS
2-1/2" PIPE
& FITTINGS
3" PIPE
& FITTINGS
4" PIPE
& FITTINGS
g
VENT CLEARANCES
See Tables 13 & 14
SINGLE PIPE VENTING
h
18 18-CD29D1-11
Page 19
Installer’s Guide
Table 13 - See Figure 22
Direct Vent Terminal Clearances
A= Clearance above grade, veranda, porch, deck,
B= Clearance to window or door that may be
C= Clearance to permanently closed window * * D= Vertical clearance to ventilated soffit located
E= Clearance to unventilated soffit * * F= Clearance to outside corner * * G= Clearance to inside corner * * H= Clearance to each side of center line extended
I= Clearance to service regulator vent outlet 3 feet (91 cm) * J= Clearance to nonmechanical air supply inlet
K= Clearance to a mechanical air supply inlet 6 feet (1.83m) 3 feet (91 cm) above if within 10 feet (3m) horizontally L= Clearance above a paved sidewalk or paved
M= Clearance under veranda, porch, deck, or
Table 14 - See Figure 22
A= Clearance above grade, veranda, porch, deck, or
B= Clearance to window or door that may be opened 6 inches (15 cm) for appliances =/< 10,000 Btuh (3 kw), 12
C= Clearance to permanently closed window * * D= Vertical clearance to ventilated soffit located above
E= Clearance to unventilated soffit * * F= Clearance to outside corner * * G= Clearance to inside corner * * H= Clearance to each side of center line extended
I= Clearance to service regulator vent outlet 3 feet (91 cm) * J= Clearance to nonmechanical air supply inlet to
K= Clearance to a mechanical air supply inlet 6 feet (1.83m) 3 feet (91 cm) above if within 10 feet (3m)
L= Clearance above a paved sidewalk or paved drive-
M= Clearance under veranda, porch, deck, or balcony `12 inches (30 cm) ‡ * Notes:
1. In accordance with the current CSA B149.1 Natural Gas and Propane Installation Code.
2. In accordance with the current ANSI Z223.1/NFPA 54 National Fuel Gas Code. †. A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwelling and serves both dwellings. ‡. Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor. * Clearance in accordance with local installation codes and the requirements of the gas supplier and the manufacturer's Installation Instructions.
or balcony
opened
above the terminal within a horizontal distance of 2 feet (61 cm) from the center line of the terminal
above meter/regulator assembly
to building or the combustion air inlet to any other appliance
driveway located on public property
balcony
Notes:
1. In accordance with the current CSA B149.1 Natural Gas and Propane Installation Code.
2. In accordance with the current ANSI Z223.1/NFPA 54 National Fuel Gas Code. †. A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwelling and serves both dwellings. ‡. Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor. * Clearance in accordance with local installation codes and the requirements of the gas supplier and the manufacturer's Installation Instructions.
balcony
the terminal within a horizontal distance of 2 feet (61 cm) from the center line of the terminal
above meter/regulator assembly
building or the combustion air inlet to any other appliance
way located on public property
6 inches (15 cm) for appliances =/< 10,000 Btuh (3 kw), 12 inches (30 cm) for appliances > 10,000 Btuh (3 kw) and =/< 100,000 Btuh (30 kw), 36 inches (91 cm) for appliances > 100,000 Btuh (30 kw)
3 feet (91 cm) with a height 15 feet (4.5 m)
6 inches (15 cm) for appliances =/< 10,000 Btuh (3 kw), 12 inches (30 cm) for appliances > 10,000 Btuh (3 kw) and =/< 100,000 Btuh (30 kw), 36 inches (91 cm) for appliances > 100,000 Btuh (30 kw)
inches (30 cm) for appliances > 10,000 Btuh (3 kw) and =/< 100,000 Btuh (30 kw), 36 inches (91 cm) for appliances > 100,000 Btuh (30 kw)
6 inches (15 cm) for appliances =/< 10,000 Btuh (3 kw), 12 inches (30 cm) for appliances > 10,000 Btuh (3 kw) and =/< 100,000 Btuh (30 kw), 36 inches (91 cm) for appliances > 100,000 Btuh (30 kw)
18-CD29D1-11 19
Canadian Installations US Installations
12 inches (30 cm) 12 inches (30 cm)
6 inches (15 cm) for appliances =/< 10,000 Btuh (3 kw), 9 inches (23 cm) for appliances > 10,000 Btuh (3 kw) and =/< 50,000 Btuh (15 kw), 12 inches (30 cm) for ap­pliances > 50,000 Btuh (15 kw)
* *
above the meter/regulator assembly
6 inches (15 cm) for appliances =/< 10,000 Btuh (3 kw), 9 inches (23 cm) for appliances > 10,000 Btuh (3 kw) and =/< 50,000 Btuh (15 kw), 12 inches (30 cm) for ap­pliances > 50,000 Btuh (15 kw)
7 feet (2.13 m) † *
`12 inches (30 cm) ‡ *
Non-Direct Vent Terminal Clearances
Canadian Installations US Installations
12 inches (30 cm) 12 inches (30 cm)
4 feet (1.2m) below or to the side of open­ing; 1 foot (0.3m) above opening.
* *
3 feet (91 cm) with a height 15 feet (4.5 m) above the
meter/regulator assembly
4 feet (1.2 m) below or to side of opening; 1 foot (300 m) above opening
7 feet (2.13 m) † 7 feet (2.13 m)
*
*
horizontally
Page 20
Installer’s Guide
CAUTION
!
6” Min. 24” Max.
12” Min. 15” Max
.
9” Minimum minimum from end of exhaust pipe to end of inlet pipe
6” Min. 24” Max.
6” Min. 24” Max.
VENT
COMBUSTION AIR
VENT
VENT PLATE
VENT CAP
12" MINIMUM TO OVERHANG
MAINTAIN 12" MINIMUM CLEARANCE
ABOVE HIGHEST ANTICIPATED SNOW LEVEL
OR GRADE WHICHEVER IS GREATER
SCREWS (4 req.)
ANCHORS (4 req.)
7.2"
3.2"
WARNING
!
j
6” Min. 24” Max.
12” Min. 15” Max
.
6” Min. 24” Max.
12” Min.
15” Max
.
9” Minimum minimum from end of exhaust pipe to end of inlet pipe
ELBOW AND TEE MUST BE AS CLOSE TOGETHER AS POSSIBLE
POSSIBLE CONFIGURATIONS FOR TWO PIPE VENTING SYSTEMS WHEN
BOTH TERMINATIONS ARE LOCATED IN THE SAME PRESSURE ZONE
CARBON MONOXIDE POISONING HAZARD Do not replace any of the factory supplied venting components with field fabricated parts. Failure to fol­low this safety warning exactly could result in dam­aged vents, damaged components, carbon monoxide poisoning, or death.
k
9” Minimum minimum from end of exhaust pipe to end of inlet pipe
HORIZONTAL VENTING
NOTE: Vent termination kit BAYAIR30AVENTA or BAYVENT200B may be used instead of the horizontal and vertical termi­nation options shown in the following figures. For Canadian applications, venting systems must meet ULC-S636 requirements..
When the vent pipe is exposed to temperatures below freezing, i.e., when it passes through unheated spaces, etc., the pipe must be insulated with 1/2 inch (22.7 mm) thick Armaflex-type insulation or equal. If the space is heated sufficiently to prevent freezing, then the insula­tion would not be required. If domestic water pipes are not protected from freezing then it is assumed the space meets the condition of a heated space.
20 18-CD29D1-11
For Canadian applications, horizontal vent termination kits must meet ULC­S636.
DO NOT Install return air through the side of furnace cabi­net on horizontal applications.
HORIZONTAL VENTING THROUGH WALL
These furnaces may be installed as direct vent (as shipped) or as nondirect vent. Installation must con­form to national, state, and local codes.
The vent & inlet terminals must be located at least 12" minimum above normally expected snow accumulation lev­el.
BAYVENT200B
Page 21
Avoid areas where staining or condensate drippage may be
COUPLING (PLASTIC VENTING)
STUD
PVC WALL MOUNT FLANGE (OPTIONAL)
APPROVED TERMINATION
1” CLEARANCE (AIR SPACE)
VENTING THROUGH COMBUSTIBLE WALLS Pitch - 1/4 Inch Per Foot
CLEARANCE (0” ACCEPTABLE FOR PVC VENT PIPE) (1” ACCEPTABLE FOR TYPE 29-4C STAINLESS STEEL VENT PIPE)
12” MINIMUM ABOVE NORMALLY EXPECTED SNOW ACCUMULATION LEVEL
6 IN. MIN. (TO JOINT)
COUPLING (PLASTIC VENTING)
PVC WALL MOUNT FLANGE (OPTIONAL)
APPROVED TERMINATION
CEMENT MORTAR SEAL INSIDE & OUTSIDE
VENTING THROUGH NON-COMBUSTIBLE WALLS Pitch - 1/4 Inch Per Foot
12” MINIMUM ABOVE NORMALLY EXPECTED SNOW ACCUMULATION LEVEL
6 IN. MIN. (TO JOINT)
a problem.
Location  of  the  vent/  wind  terminal  should  be  chosen  to 
meet the requirements of Figure 26 for either direct or non­direct vent applications.
PITCH – Venting through the wall must maintain 1/4"  per 
foot pitched upward to insure that condensate drains back to the furnace. FLUE GAS DEGRADATION – The moisture content of the flue gas may have a detrimental effect on some building materials. This can be avoided by using the roof or chimney venting option. When wall venting is used on any surface that can be affected by this moisture, it is recommended that a corrosion resistant shield (24 inches square) be used behind the vent terminal. This shield can be wood, plastic, sheet metal, etc. Also, silicone caulk all cracks, seams and joints within 3 feet of the vent terminal.
COMBUSTIBLE MATERIAL WALL
A minimum clearance of 1" to combustible materials must be maintained when using single wall stainless steel vent­ing. See Figure 30.
Installer’s Guide
;
l
12" MIN TO OVERHANG
1
1" + "
2
COMBUSTION AIR
BAYAIR30AVENTA
(Sidewall)
For Canadian applications, horizontal vent termination kits must meet ULC-S636.
Shield material to be a minimum of 24 gauge stainless or aluminized sheet metal. Minimum dimensions are 12"x12". Shield must be fastened to both inside and outside of wall. Use screws or anchor type fasteners suited to the outside or inside wall surfaces.
NONCOMBUSTIBLE MATERIAL WALL
The hole through the wall must be large enough to main­tain pitch of vent and properly seal. Use cement mortar seal on inside and outside of wall. See Figure 31.
VENT
MAINTAIN 12 IN. MINIMUM CLEARANCE ABOVE HIGHEST ANTICIPATED SHOW LEVEL OR GRADE WHICH EVER IS GREATER
z
x
SUPPORT HORIZONTAL PIPE EVERY 3' 0" WITH THE FIRST SUPPORT AS CLOSE TO THE FURNACE AS POSSIBLE. INDUCED DRAFT BLOWER, HOUSING, AND FURNACE MUST NOT SUPPORT THE WEIGHT OF THE FLUE PIPE.
18-CD29D1-11 21
Page 22
Installer’s Guide
40" UPFLOW OR DOWNFLOW MODELS
SEE VENTING TABLE
OUTSIDE
WALL
NOTE: ANY FITTINGS PASSING THROUGH AN UNHEATED SPACE MUST BE INSULATED.
FIRST SUPPORT SHOULD BE AS CLOSE TO FURNACE CONNECTION AS POSSIBLE.
UPWARD PITCH -- 1/4" PER FOOT
STRAPS OR OTHER SUITABLE SUPPORTS AT MAXIMUM OF 3'-0" INTERVALS
COMBUSTION AIR INLET
USE ONLY
APPROVED
TERMINATION
RAIN CAP
COMBUSTION AIR
STRAP (FIELD SUPPLIED)
COMBUSTION AIR
VENT
ELBOW (FIELD SUPPLIED)
VENT
1" + 1/2"
3" PIPING
2", 2-1/2"
or 3" PIPING
REDUCING COUPLING, FIELD SUPPLIED IF NEEDED
SEAL ALL
WALL CAVITIES
CAUTION
!
c
NOTE: VENT AND INLET MUST BE SUPPORT-
ED AT A MAXIMUM OF 3' INTERVALS
TEE
The vent for this appliance shall not terminate
(1) Over public walkways; or
(2) Near soffit vents or crawl space vents or other
(3) Where condensate vapor could cause damage or
22 18-CD29D1-11
BAYAIR30AVENTA
For Canadian applications, horizontal vent termination kits must meet ULC-S636.
areas where condensate or vapor could create a nuisance or hazard or cause property damage; or
could be detrimental to the operation of regula­tors, relief valves. or other equipment.
BAYVENT200B
Page 23
Installer’s Guide
MAINTAIN 12 IN. (18 IN. FOR CANADA) MINIMUM CLEARANCE ABOVE HIGHEST ANTICIPATED SNOW LEVEL. MAXIMUM OF 24 IN. ABOVE ROOF.
VENT
COMBUSTION AIR
REMOVE RIBS FROM CAP
COMBUSTION AIR
ROOF FLASHING BOOT (FIELD SUPPLIED)
COMBUSTION AIR
VENT
ELBOW (FIELD SUPPLIED)
MAINTAIN 12 IN. (18 IN. FOR CANADA) MINIMUM CLEARANCE ABOVE HIGHEST ANTICIPATED SNOW LEVEL. MAXIMUM OF 24 IN. ABOVE ROOF
SUPPORT (FIELD SUPPLIED)
VENT
6" Min.
40 Inch
Upflow or
Downflow
Furnace
Slope 1/4" per ft.
Slope 1/4" per ft.
12 INCHES MIN. CLEARANCE MUST BE MAINTAINED ABOVE HIGHEST ANTICIPATED SNOW LEVEL. MAXIMUM NOT TO EXCEED 24 INCHES ABOVE ROOF.
DOWNWARD VENTING
Furnace may be in vertical or horizontal configuration.
DOWNWARD VENT
LENGTH IS LIMITED
TO A MAXIMUM OF 15
EQUIVALENT FEET.
All horizontal pipes must be supported
at a maximum of 3 foot intervals
v
NOTES: A) Condensate trap for vent pipe must be a minimum
of 6 inches in height.
B) Condensate trap for vent and inlet pipe must be
connected into a condensate drain pump; an open or vented drain; or it can be connected to the out­let hose of the furnace's condensate trap. Outdoor draining of the furnace and coil condensate is per­missible if allowed by local codes. Caution should be taken to prevent drains from freezing or causing slippery conditions that could lead to personal in­jury. Excessive draining of condensate may cause saturated ground conditions that may result in damage to plants.
C) The condensate trap should be primed at initial
start up prior to heating season operation.
VENTING THROUGH THE ROOF
When penetrating roof with a 2" PVC vent pipe, a 2" elec­trical conduit flashing may be used for a weather tight seal. Lubricate flexible seal on flashing before PVC pipe is pushed through the seal. (Field Supplied)
All pipe joints must be fastened and sealed to prevent es­cape of combustion products into the building.
NOTE: Both venting methods shown in Figure 39 & 41 must also have the combustion air inlet installed - meeting dimen­sion requirements of Figure 35.
b
n
For Canadian applications, vertical vent termination kits
BAYAIR30AVENTA
must meet ULC-S636.
m
NOTE:
No vent cap as shown in Figure 35 is the preferred meth­od for vertical vent termination in extremely cold climates. In extreme climate conditions, insulate the exposed pipe above the roof line with Armaflex type insulation.
VENTING ROUTED THROUGH A MASONRY CHIMNEY VENT FITTING MATERIAL – STAINLESS STEEL
Gas and liquid tight single wall metal vent fitting, designed for resistance to corrosive flue condensate such as Type 29­4C MUST be used throughout. These fittings and fitting accessories are to be supplied lo­cally.
DIRECTION OF STAINLESS STEEL FITTING
All stainless steel fitting must be installed with male end towards the furnace. All horizontal stainless steel sections must be positioned with the seam on top. All long horizontal sections must be supported to prevent sagging.
18-CD29D1-11 23
For Canadian applications, vertical vent termination kits must meet ULC-S636.
Page 24
Installer’s Guide
GALVANIZED FIRESTOP SHOULD BE FABRICATED WITH 3-7/8" DIA. HOLE FOR SUPPORT FLANGE (12" x 12" PANEL OR 12" DIA MIN.)
VENTING THROUGH CEILING
CEILING
SUPPORT
FLANGE
FLUE PIPE
COUPLING
SEAL BETWEEN FLANGE, PIPE, COUPLING AND METAL PANEL WITH HI TEMP RTV SILICONE SEALANT
CLEARANCE ( 0" ACCEPTABLE FOR PVC VENT PIPE )
( 1" ACCEPTABLE FOR TYPE 29-4C STAINLESS STEEL VENT PIPE )
STAINLESS STEEL
CAUTION
!
CAUTION
!
,
TYPE 29-4C STAINLESS STEEL VENTING -
.
USED THROUGH CHIMNEY THAT VENTS
ANOTHER GAS APPLIANCE
VENT CAP (OPTIONAL)
SEE CAUTION
6 IN. MIN.
SUPPORT THE SINGLE WALL STAINLESS STEEL GAS VENTING AND CENTER IT IN THE CHIMNEY OPENING WITH ANGLES AS SHOWN OR ANOTHER EQUIVALENT MANNER.
/
PVC PLASTIC VENTING - ONLY
!
COUPLING TO SUPPORT PIPE FROM ANGLES OR OTHER SUITABLE SUPPORT METHOD
THROUGH UNUSED CHIMNEY
STAINLESS STEEL VENT CAP (OPTIONAL)
SEE CAUTION
FLUE PIPE
6 IN. MIN.
SUPPORT THE SINGLE WALL FLUE PIPE AND CENTER IT IN THE CHIMNEY OPENING WITH ANGLES AS SHOWN OR ANOTHER EQUIVALENT MANNER.
COUPLING AS REQUIRED
NOTE: HORIZONTAL VENTING TO VERTICAL VENTING
Do NOT run vent through chimney for wood burn­ing or oil furnaces or incinerators. If remaining free area between single wall flue pipe and masonry chimney is to be used for another gas appliance venting area must be sufficient to vent that appliance and that appliance must be connect­ed to chimney with separate entry openings.
IMPORTANT – The single wall flue pipe joints must be sealed. The 90° elbow connection to vertical pipe must be sealed to prevent condensate leakage to base of ma­sonry chimney.
24 18-CD29D1-11
FLUE PIPE
NOTE: HORIZONTAL VENTING TO VERTICAL VENTING
Do NOT run vent through chimney for wood burning or oil furnaces or incinerators or any other gas appli­ance.
IMPORTANT – The single wall flue pipe joints must be sealed.
The 90° elbow connection to vertical pipe must be sealed to prevent condensate leakage to base of masonry chimney.
Page 25
Installer’s Guide
IMPORTANT:
The Commonwealth of Massachusetts requires compliance with regulation 248 CMR 4.00 and 5.00 for installation of through – the – wall vented gas appliances as follows:
For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:
1.  INSTALLATION OF CARBON MONOXIDE 
DETECTORS. At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level. b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.
2.  APPROVED CARBON MONOXIDE 
DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions shall comply with
NFPA 720 and be ANSI/UL 2034 listed and IAS certied.
3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less
than one-half (1/2) inch in size, “GAS VENT DIRECTLY  BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS”.
4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4. This appliance requires a special venting system. If
BAYAIR30AVENTA or BAYVENT200B are used, a copy 
of the installation instructions for the kit shall remain with the appliance or equipment at the completion of installation. The venting system installation instructions can be obtained from the manufacturer by writing to the following address: Trane 6200 Troup Highway Tyler, TX 75707 Attention: Manager of Field Operations Excellence
For Canadian installations, if you used a ULC-S636 approved manufactured modular venting system, a copy of the manufacturer's instructions should remain with the system. The installation instruction can be obtained from the vent termination manufacturer.
18-CD29D1-11 25
Page 26
Installer’s Guide
CAUTION
!
LABEL SAYS "TOP"
STRAIGHT SIDE MUST BE ON BOTTOM FOR PROPER CONDENSATE DRAINAGE.
WHEN THE FACTORY SUPPLIED "OFF-SET" (2X3 REDUCING COUPLING) IS USED FOR 3" VENT PIPE INSTALLATION, MAKE SURE THE MARKING "TOP" IS LOCATED ON THE TOP SIDE OF THE PIPE.
2" TO 3" COUPLING
FURNACE VENT OUTLET
FACTORY SUPPLIED ONLY WITH THE FOLLOWING MODELS: *UH1C080A9601A, ALL 100,000 BTUH UPFLOW MODELS, ALL 120,000 BTUH UPFLOW MODELS, AND ALL *DH1 DOWNFLOW MODELS
#CPL00938
HORIZONTAL INSTALLATION Upflow/ Horizontal
NOTE: In horizontal venting when the factory supplied “off­set” (2X3 reducing coupling) is used for 3” vent pipe installation, make sure the marking “Top” is located on the top side of the pipe. The straight side must be on bottom for proper condensate drainage. This cou­pling is only factory supplied with all 100,000 BTU up­flow models, *UH1C080A9601A, all 120,000 BTU upflow models, and all downflow models.
@
CONDENSATE DRAIN INSTRUCTIONS VERTICAL APPLICATIONS
It is recommended that a drain pan be installed under the furnace to prevent property damage or personal injury from leaking condensate.
Upflow furnace - The connection tubing for left and right side drainage is shipped in the blower compartment. Install the connection tubing from the trap to the side of the unit and trim all excess tubing to avoid kinks.
$
UPFLOW
(VERTICAL)
#
Right side
%
UPFLOW HORIZONTAL 17"
UNITS (Left side only)
Downflow furnace - Use RTV silicon sealant to connect the fitting to the trap for ease of removal when clean­ing the trap.
For  left  side  drain  a  1/2"  slip  PVC  tting  is  needed.  
See Figure 48. To change to a right side drain, remove the drain lines from the trap, rotate the trap 180° so it exits to the
right,  then  reconnect  the  lines.    Start  with  a  1/2"  90° 
CPVC street elbow connected to the trap using RTV
silicon sealant.  Run 1/2" CPVC pipe to a CPVC elbow.   Run  1/2"  CPVC  pipe  from  the  elbow  out  through  the 
right side knock-out. See Figure 49.
Use Inducer Drain
hose without
extension
26 18-CD29D1-11
Page 27
HORIZONTAL APPLICATIONS
Upflow and Downflow furnaces - All horizontal appli­cations are left side only. It is always recommended that the auxiliary drain pan be installed under a horizontally
installed  evaporator  and/or  95%  gas  furnace.  Connect  the 
auxiliary drain pan to a separate drain line (no trap is needed in this line). The trap must be repositioned to the exterior of the cabinet. Remove the trap from its present location and reposition the trap outside of the unit, through the long circular hole,
Installer’s Guide
*
^
UPFLOW
(VERTICAL)
Left side
UPFLOW HORIZONTAL 21" & 24" UNITS
(Left side only)
Use exten-
sion hose
here
&
Left
side
DOWNFLOW (VERTICAL)
(
Right
side
Use CPVC tubing from Trap outlet,
over burner box to cabinet exit
DOWNFLOW (VERTICAL)
)
next to the secondary recuperated cell. Remove the larger drain line (from the secondary cell) and trim to fit between the secondary cell and the new trap location. On upflow units, plug the hole in the blower deck where the tube went through. Remove the hose from the induced blower and reposition into the other drain tap of the inducer, which is located 90° clockwise around the inducer. Move the cap from that drain tap to the unused drain tap. On upflow units, plug the hole in the blower deck where the tube went through. On upflow units, this tube may need to be extended, using the tubing shipped with the furnace.
Connections must be made to an OPEN or VENTED DRAIN. Outdoor draining of the furnace and coil conden­sate is permissible if allowed by local codes. Caution should be taken to prevent drains from freezing or causing slip­pery conditions that could lead to personal injury. Excessive draining of condensate may cause saturated ground condi­tions that may result in damage to plants.
18-CD29D1-11 27
DOWNFLOW (HORIZONTAL)
Cut off curved end of
Inducer drain hose
Page 28
Installer’s Guide
SEE
NOTE 6
From drawing B341437 Rv 1
FURNACE
TWIN
SEE
NOTE 7
B/C
B/C
TO 115 V 1 PH., 60 HZ., POWER SUPPLY PER LOCAL CODES
HUM SEE NOTE 5
EAC SEE NOTE 5
FIELD WIRING DIAGRAM FOR 1 STAGE FURNACE
1 STAGE HEATING
USING A 1 STAGE HEATING THERMOSTAT
NO COOLING
NOTE: Use 1/2" or larger PVC or CPVC pipe and fittings as re­quired for drain connections (fittings, pipe and solvent ce­ment not provided).
NOTE: A corrosion resistant condensate pump must be used if a pump is required for a specific drain system.
IMPORTANT: The condensate drain should be installed with provisions to prevent winter freeze-up of the condensate drain line. Frozen condensate will block drains, resulting in fur nace shutdown. If the drain line cannot be installed in a condi­tioned space, then UL listed heat tape should be applied as required to prevent freezing (per manufacturer’s in­structions). The heat tape should be rated at 5 or 6 watts per foot at 120 volts. Self-regulating (preferred) or thermo­statically controlled heat tape is required.
Evaporator and furnace condensate drain piping may be manifolded together as shown in Figure 51. A primary drain vent stack must be installed and terminated below the outlet of the secondary heat exchanger drain connection
to prevent water from damaging furnace controls if the pri­mary drain outlet plugs up. Where the furnace is installed above a finished ceiling, the primary drain vent stack must be installed such that overflow from the vent stack opening will flow into an auxiliary drain pan in order to prevent wa­ter damage to the finished ceiling below.
TWINNING FURNACES
These furnaces may be twinned. Twinning requires that two furnaces with the same configuration, capacity, and air­flow must be used. They shall have common returns with equal pressure drops or ducts with equivalent lengths and sizes. See Field Wiring Diagrams for proper hookup.
Q
If upflow furnace is installed over a finished ceiling, overflow from the primary drain vent stack must flow into an auxillary drain pan to prevent damage to the finished ceiling below.
Primary drain vent stack must terminate below secondary heat exchanger condensate drain outlet.
To drain opening
28 18-CD29D1-11
Page 29
Installer’s Guide
OUTDOOR UNIT
(NO TRANSFORMER)
SEE
NOTE 6
From drawing B340388 Rv 2
SEE
NOTE 8
FURNACE
B/C
B/C
TO 115 V 1 PH., 60 HZ., POWER SUPPLY PER LOCAL CODES
HUM SEE NOTE 5
EAC SEE NOTE 5
FIELD WIRING DIAGRAM FOR 1 STAGE FURNACE
1 STAGE HEATING, 1 STAGE COOLING
USING A 1 STAGE HEATING, 1 STAGE COOLING THERMOSTAT
(OUTDOOR SECTION WITHOUT TRANSFORMER)
ELECTRICAL CONNECTIONS
Make wiring connections to the unit as indicated on enclosed wiring diagram. As with all gas appliances using electrical power, this furnace shall be connected into a permanently live electric circuit. It is recom­mended that furnace be provided with a separate “cir­cuit protection device” in the electric circuit. The fur­nace must be electrically grounded in accordance with local codes or in the absence of local codes with the
National Electrical Code, ANSI/NFPA 70 or CSA C22.1 
Electrical Code, if an external electrical source is uti­lized.
The integrated furnace control is polarity sensi­tive. The hot leg of the 120V power supply must be
connected to the black power lead as indicated on the wiring diagram. Provision for hooking up an electronic air cleaner and or humidifier is provided on the inte­grated control. Refer to the SERVICE FACTS literature and unit wir­ing diagram attached to furnace diagram attached to furnace.
18-CD29D1-11 29
Page 30
Installer’s Guide
TWIN
TWIN
R1
R1
TWINNING CONNECTION DIAGRAM
FOR TWINNING 1 STAGE FURNACES WITH
SINGLE WIRE TWINNING FEATURE
1 STAGE HEATING ONLY THERMOSTAT
1 STAGE HEAT
ONLY
THERMOSTAT
(WITH FAN SWITCH) FURNACE NO. 1
FURNACE NO. 2
BLOWER OPERATION OF
UNIT NO. 2 IS SYNCRONIZED
WITH UNIT NO. 1 VIA SIGNALS
FROM TWIN CONNECTION.
SEE NOTE 4
SEE NOTE 3
ISOLATION RELAY (FIELD SUPPLIED)
SEE NOTE 4
ISOLATION RELAY
SEE NOTE 4
B/C
B/C
B/C
From Dwg. 21B341422 Rev. 3
TWIN
TWIN
R1
R1
TWINNING CONNECTION DIAGRAM
FOR TWINNING 1 STAGE FURNAC ES WITH
SINGLE WIRE TWINNING FEATURE
1 STAGE HEAT / 1 STAGE COOL THERMOSTAT
1 STAGE
HEATING / COOLING
THERMOSTAT FURNACE NO. 1
FURNACE NO. 2
BLOWER OPERATION OF
UNIT NO. 2 IS SYNCRONIZED
WITH UNIT NO. 1 VIA SIGNALS
FROM TWIN CONNECTION.
SEE NOTE 4
SEE NOTE 5
ISOLATION RELAY
(FIELD SUPPLIED)
SEE NOTE 4
ISOLATION RELAY
SEE NOTE 4
OUTDOOR UNIT
(NO TRANSFORMER)
OUTDOOR UNIT
(WITH TRANSFORMER)
RC
ISOLATION RELAY (FIELD SUPPLIED)
SEE NOTE 3
B/C
B/C
B/C
From Dwg. 21B341423 Rev. 2
30 18-CD29D1-11
Page 31
Installer’s Guide
CAUTION
!
GAS PIPING
The upow/  horizontal  furnace  is shipped  standard  for  left 
side installation of gas piping. A knock-out is provided on the right side for an alternate gas piping arrangement. See Figure 52. The installation of piping shall be in accordance with pip­ing codes and the regulations of the local gas company. Pipe joint compound must be resistant to the chemical reaction with liquefied petroleum gases. Refer to piping Table 15, for delivery sizes. Connect gas supply to the unit, using a ground joint union and a manual shut-off valve as shown in Figures 52-53. National codes require a condensation drip leg to be in­stalled ahead of the controls as shown in Figures 52-53. The furnace and its individual shut-off valve must be dis­connected from the gas supply piping system during any pressure testing of that system at test pressures in excess
of 1/2 psig (3.5 kPa).
The furnace must be isolated from the gas supply piping by closing its individual manual shut-off valve during any pressure testing of the gas supply piping system at test
pressures equal to or less than 1/2 psig (3.5 kPa).
W
MAIN MANUAL
SHUTOFF VALVE
GROUND
UNION
JOINT
AUTOMATIC GAS VALVE
WITH MANUAL SHUTOFF
NOTE: Maximum pressure to the gas valve for natural gas is
13.8" W.C. Minimum pressure is 5.0" W.C. Maximum pressure to the gas valve for propane is 13.8" W.C. Minimum pressure is 11.0" W.C. All gas fittings must be checked for leaks using a soapy solution before lighting the furnace. DO NOT CHECK WITH AN OPEN FLAME!
Use a backup wrench on the gas valve when installing gas piping to prevent damage to the gas valve and manifold assembly.
AUTOMATIC GAS VALVE
WITH MANUAL SHUTOFF
MAIN MANUAL
SHUTOFF VALVE
GROUND
UNION
JOINT
DRIP
LEG
E
DRIP
LEG
UPFLOW – LEFT HAND GAS PIPING
UPFLOW – RIGHT HAND GAS PIPING
THE DOWNFLOW (VERTICAL) MAY BE INSTALLED LEFT OR RIGHT SIDE GAS PIPING
18-CD29D1-11 31
Page 32
Installer’s Guide
R
AUTOMATIC GAS VALVE WITH
MANUAL SHUTOFF
MAIN MANUAL
SHUTOFF VALVE
GROUND
UNION JOINT
DRIP LEG
HORIZONTAL FURNACE GAS PIPING MAY BE FROM EITHER SIDE (UPFLOW SHOWN)
TABLE 15
NATURAL GAS ONLY
TABLE OF CUBIC FEET PER HOUR OF GAS
FOR VARIOUS PIPE SIZES AND LENGTHS
PIPE
SIZE
1/2 132 92 73 63 56 50 46
3/4 278 190 152 130 115 105 96
1 520 350 285 245 215 195 180
1-1/4 1050 730 590 520 440 400 370
This table is based on pressure drop of 0.3 inch W.C. and 0.6 SP.GR. gas
10 20 30 40 50 60 70
MODEL
*UH1B040A9241A 40,000 2 45 56 *UH1B060A9361A 60,000 3 45 56
*UH1B080A9421B 77,000 4 45 56 *UH1C080A9601A 80,000 4 45 56 *UH1C100A9481A
*UH1D100A9601A *UH1D120A9601A 110,000 6 45 56
*DH1B040A9241A 40,000 2 45 56
*DH1B065A9421A 60,000 4 48 56 *DH1C085A9481A 80,000 5 48 56 *DH1D110A9601A 110,000 6 48 56
LENGTH OF PIPE
TABLE 16
ORIFICE SIZES
INPUT
RATING
BTUH
NUMBER
OF
BURNERS
MAIN BURNER
ORIFICE
DRILL SIZE
NAT. GAS LP GAS
100,000 5 45 56
MAIN MANUAL
SHUTOFF VALVE
AUTOMATIC GAS VALVE
WITH MANUAL SHUTOFF
GROUND UNION JOINT
DRIP LEG
4. Read the “Flow” column opposite the number of sec­onds clocked.
5. Use the following factors if necessary:
For 1 Cu. Ft. Dial Gas Flow CFH = Chart Flow Reading ÷2
    For 1/2 Cu Ft. Dial Gas Flow CFH = 
Chart Flow Reading ÷4 For 5 Cu. Ft. Dial Gas Flow CFH = 10X Chart Flow Reading ÷4
6. Multiply the final figure by the heating value of the gas obtained from the utility company and compare to the nameplate rating. This must not exceed the nameplate rating.
Gas Valve Adjustment
Changes can be made by adjusting the manifold pressure
(See Table 17, or changing orifices (orifice change may not always be required). To adjust the manifold pressure:
1. Turn off all electrical power to the system.
2. Attach a manifold pressure gauge with flexible tub-
ing to the outlet pressure boss marked “OUT P” on White-Rodgers gas valve model 36G or 36J. See Fig­ure 58 for White-Rodgers gas valve model 36J. See Figure 57 for White-Rodgers gas valve model 36G.
3. Loosen (Do Not remove) the pressure tap test set
screw one turn with 3/32" hex wrench.
a.  The pressure tap adjustment kit (KIT07611) con-
tains a 3/32" hex wrench, a 5/16" hose and a con-
nector and can be ordered through Global Parts.
4. Turn on system power and energize valve.
COMBUSTION AND INPUT CHECK
1. Make sure all gas appliances are off except the furnace.
2. Clock the gas meter with the furnace operating (deter­mine the dial rating of the meter) for one revolution.
3. Match the “Sec” column in the gas flow (in cfh) Table 18 with the time clocked.
32 18-CD29D1-11
Page 33
Installer’s Guide
CAUTION
!
WARNING
!
5. Adjust gas heat by removing the adjustment regulator cover screw.
a. To increase outlet pressure, turn the regulator ad-
just screw clockwise.
b. To decrease outlet pressure, turn the regulator ad-
just screw counterclockwise.
c. Adjust regulator until pressure shown on mano-
meter matches the pressure specified in Table 17.
1. The input of no more than nameplate rating and no less than 93% of the nameplate rating, unless the unit is derated for high altitude.
d. Replace and tighten the regulator cover screw se-
curely.
6. Cycle the valve several times to verify regulator set-
ting.
a. Repeat steps 5-6 if needed.
7. Turn off all electrical power to the system.
8. Remove the manometer and flexible tubing and tighten
the pressure tap screw.
9. Using a leak detection solution or soap suds, check for
leaks at the pressure outlet boss and pressure tap test screw.
10. Turn on system power and check operation of the
unit.
SAFETY HAZARD Replace and/ or tighten all plugs removed or loosened when adjusting gas pressure. Leak check the fittings be­fore placing the furnace into regular service. Failure to follow this warning could result in fire, explo­sion, or property damage.
NOTE: The manifold pressure must be referenced to the burner box. The burner box pressure tap equalizes the gas valve pressure regulator. Manifold pressure is checked by in­stalling a tee (field supplied) in the tubing, between the tee coming from the burner box tube and the gas valve, in ad­dition to the regular gas valve pressure tap on the outlet side of the gas valve. See Figure 55.
Replace manifold pressure tap threaded plug and leak check after checking/ adjusting manifold gas pressure.
Table 19 lists the main burner orifices used with the fur­nace. If a change of orifices is required to correct the fur­nace input rating. Refer to Table 20.
TABLE 17
FINAL MANIFOLD PRESSURE SETTINGS
MODEL FUEL PRESSURE
NATURAL GAS LP GAS
*UH1B040A9241A 3.5" W.C. 11.0" W.C.
*UH1B060A9361A 3.5" W.C. 11.0" W.C.
*UH1B080A9421B
*UH1C080A9601A *UH1C100A9481A
*UH1D100A9601A
*UH1D120A9601A 3.3" W.C. 11.0" W.C.
*DH1B040A9241A 3.5" W.C. 11.0" W.C.
*DH1B065A9421A 3.0" W.C. 9.5" W.C.
*DH1C085A9481A 3.5" W.C. 11.0" W.C.
*DH1D110A9601A 4.5" W.C. 11.0" W.C.
3.5" W.C. 11.0" W.C.
3.5" W.C. 11.0" W.C.
T
18-CD29D1-11 33
Page 34
Installer’s Guide
HIGH ALTITUDE DERATE
Input  ratings  (BTUH)  of  these  furnaces  are  based  on  sea 
level operation and should not be changed at elevations up to 2,000 ft. If the installation is 2,000 ft. or above, the furnace input
rate  (BTUH)  shall  be  reduced  4%  for  each  1,000  ft.  above 
sea level. The furnace input rate shall be checked by clock­ing the gas flow rate (CFH) and multiplying by the heating value obtained from the local utility supplier for the gas be­ing delivered at the installed altitude. Input rate changes can be made by adjusting the manifold pressure (min 3.0
- max 3.7 in. W.C. - Natural Gas for upflow models and min
3.0 - max 4.5 in. W.C. - Natural Gas for downflow models) or changing orifices (orifice change may not always be re­quired). If the desired input rate can not be achieved with a change in manifold pressure, then the orifices must be changed. LP installations will require an orifice change. Installation of this furnace at altitudes above 2,000 ft. (610m) shall be in accordance with the local codes, or in the absence of local codes, the National Fuel Gas Code, ANSI
Z223.1/ NFPA 54 or National Standard of Canada, Natu­ral Gas and Propane Installation Code, CSA 149.1. Instal-
lation of this furnace at altitudes above 2,000 ft. (610m) shall be made in accordance with the listed high Altitude
Conversion Kit available with this furnace.
IMPORTANT: Re-install the propane orifices to the same depth as the orifices supplied with the equipment.
Y
ROTATE THE FRONT COVER AS SHOWN
INSERT THE TOP FLANGE OF THE FRONT COVER UNDER THE LIP INSIDE THE BOX
ALL SIDE FLANGES MUST BE OUTSIDE OF THE BOX
ROTATE THE FRONT COVER INWARD MAKING SURE THAT ALL SIDE FLANGES ARE OUTSIDE OF THE BOX.
TABLE 18
GAS FLOW IN CUBIC FEET PER HOUR
2 CUBIC FOOT DIAL
SEC. FLOW SEC. FLOW SEC. FLOW SEC. FLOW
8 900 29 248 50 144 82 88
9 800 30 240 51 141 84 86 10 720 31 232 52 138 86 84 11 655 32 225 53 136 88 82 12 600 33 218 54 133 90 80 13 555 34 212 55 131 92 78 14 514 35 206 56 129 94 76 15 480 36 200 57 126 96 75 16 450 37 195 58 124 98 73 17 424 38 189 59 122 100 72 18 400 39 185 60 120 104 69 19 379 40 180 62 116 108 67 20 360 41 176 64 112 112 64 21 343 42 172 66 109 116 62 22 327 43 167 68 106 120 60 23 313 44 164 70 103 124 58 24 300 45 160 72 100 128 56 25 288 46 157 74 97 132 54 26 277 47 153 76 95 136 53 27 267 48 150 78 92 140 51 28 257 49 147 80 90 144 50
34 18-CD29D1-11
Page 35
Installer’s Guide
WARNING
!
WARNING
!
Outlet Pressure Boss
On/Off Switch
Inlet Pressure
Boss (opt.)
Regulator
Adjust
See Table 19 & 20 for help in selecting orifices if orifice change is required. Furnace input rate and temperature rise should be checked again after changing orifices to con­firm the proper rate for the altitude. Installations above 4,000 feet may require a pressure
switch change. If required, use  the BAYHALT*** Kit (High  Altitude Accessory Kit) listed in PRODUCT DATA.
TABLE 19
PART NUMBERS FOR REPLACEMENT ORIFICES
DRILL
SIZE
44 45 46 47 48 49 50
PART
NUMBER
ORF00501 ORF00644 ORF00909 ORF00910 ORF01099 ORF00503 ORF00493
DRILL
SIZE
54 55 56 57 58 59
PART
NUMBER
ORF00555 ORF00693 ORF00907 ORF00908 ORF01338 ORF01339
REINSTALLATION OF THE BURNER BOX COVER
Figure 56 shows the correct way to reinstall the burner box cover if adjustment or replacement of the flame sensor, hot surface igniter, or main burner orifices have required re­moval of the cover.
TABLE 20
Orifice
Twist
Drill
Size If
Installed
At Sea
Level
42 43 44 45 46 47 48
54 55 56 57 58
From National Fuel Gas Code - Table F-4
ALTITUDE ABOVE SEA LEVEL and Orifice Required
2000 3000 4000 5000 6000 7000 8000 9000 10000
42
43
44
44
45
45
46
47
47
47
48
48
49
49
54
55
55
55
56
56
58
59
59
60
At Other Elevations
43
43
44
45
45
46
47
47
47
48
49
49
49
50
55
55
55
56
57
57
59
60
60
61
44 45 47 48 48 49 50
55 56 57 60 62
44 46 47 48 49 50 50
55 56 58 61 62
45 47 48 49 49 50 51
56 56 59 62 63
46 47 48 49 50 51 51
56 56 59 63 63
47 48 50 50 51 52 52
56 57 60 63 64
Check all gas connections for leaks with a soapy solution — DO NOT CHECK WITH AN OPEN FLAME. Allow 5 minutes for any gas that might have escaped to dissipate. LP Gas being heavier than air may require forced venti­lation. Flip the switch on the gas valve in the unit to the “ON” position.
U
White-Rodgers 36G gas valve
I
Inlet Pressure Boss (opt.)
Outlet Pressure Boss
White-Rodgers 36J gas valve
On/Off Switch
LIGHTING INSTRUCTIONS
SAFETY HAZARD DO NOT attempt to manually light the burner. Failure to follow this warning could result in property damage, personal injury or death.
Regulator Adjustment
Lighting instructions appear on each unit. Each instal-
CARBON MONOXIDE POISONING HAZARD Failure to follow the installation instructions for the vent­ing system being placed into operation could result in carbon monoxide poisoning or death.
START UP AND ADJUSTMENT PRELIMINARY INSPECTIONS
With gas and electrical power “OFF”
1. Duct connections are properly sealed
2. Filters are in place
3. Venting is properly assembled
lation must be checked out at the time of initial start up to insure proper operation of all components. Check out should include putting the unit through one complete cycle as outlined below. Turn on the main electrical supply and set the thermostat above the indicated temperature. The ignitor will auto­matically heat, then the gas valve is energized to permit the flow of gas to the burners. After ignition and flame is established, the flame control module monitors the flame and supplies power to the gas valve until the thermostat is satisfied.
  4.  Blower door is in place
Flip the switch on main gas valve within the unit to the “OFF” position. Turn the external gas valve to “ON”. Purge the air from the gas lines. After purging,
18-CD29D1-11 35
Page 36
Installer’s Guide
WARNING
!
WARNING
!
CAUTION
!
To shut off.
For complete shut-down: Flip the switch on the main gas valve to the “OFF” position, (See Figure 57 & 58). Discon­nect the electrical supply to the unit.
If this is done during the cold weather months, provisions must be taken to prevent freeze-up of all water pipes and water receptacles. Failure to follow this warning could result in property damage.
Whenever your house is to be vacant, arrange to have someone inspect your house for proper temper­ature. This is very important during freezing weath­er. If for any reason your furnace should fail to oper­ate damage could result, such as frozen water pipes.
SEQUENCE OF OPERATION Thermostat call for heat
R and W thermostat contacts close signaling the control module to run its self-check routine. After the control mod­ule has verified that the pressure switch contacts are open and the limit switch(es) contacts are closed, the draft blow­er will be energized. As the induced draft blower comes up to speed, the pressure switch contacts will close and the ignitor warm up period will begin. The ignitor will heat for approximately 20 sec­onds, then the gas valve is energized to permit gas flow to the burners. The flame sensor confirms that ignition has been achieved. After the flame sensor confirms within a 4 second trial pe­riod that ignition has been achieved, the delay to fan ON period begins timing. After approximately 45 seconds the indoor blower motor will be energized and continue to run during the heating cycle (downflow models have a 10 second blower ON delay). When the thermostat is satisfied, R and W thermostat con­tacts open, the gas valve will close, the flames will extin­guish, and the induced draft blower will be de-energized. The indoor blower motor will continue to run for the fan off period (Field selectable at 60, 100, 140 or 180 seconds), then be de-energized by the control module.
CONTROL AND SAFETY SWITCH ADJUSTMENTS LIMIT SWITCH CHECK OUT
The limit switch is a safety device designed to close the gas valve should the furnace become overheated. Since proper operation of this switch is important to the safety of the unit, it must be checked out on initial start up by the installer. To check for proper operation of the limit switches, set the thermostat to a temperature higher than the indicated tem­perature to bring on the gas valve. Restrict the airflow by blocking the return air (disconnecting the indoor blower may trip the inducer limit). When the furnace reaches the maximum outlet tempera­ture as shown on the rating plate, the burners must shut off. If they do not shut off after a reason able time and over­heating is evident, a faulty limit switch is probable and the limit switch must be replaced. After checking the operation of the limit control, be sure to remove the paper or card­board from the return air inlet. Refer to Service Facts for additional instructions.
NOTE TO INSTALLER
Review the following warnings with the owner. Review con­tents of USER’S INFORMATION MANUAL with the own­er.
AIRFLOW ADJUSTMENT
Check inlet and outlet air temperatures to make sure they are within the ranges specified on the furnace rating name­plate. If the airflow needs to be increased or decreased, see the wiring diagram for information on changing the speed of the blower motor.
ELECTRICAL SHOCK HAZARD Disconnect power to the unit before removing the blower door. Failure to follow this warning could result in property damage, personal injury or death.
This unit is equipped with a blower door switch which cuts power to the blower and gas valve causing shutdown when the door is removed. Operation with the door removed or ajar can permit the escape of dangerous fumes. All panels must be securely closed at all times for safe operation of the furnace.
INDOOR BLOWER TIMING
Heating: The integrated furnace control module controls the indoor blower. The blower start is fixed at 45 seconds after ignition (10 seconds for downflow models). The FAN­OFF period is field selectable by dip switches at 60, 100, 140, or 180 seconds. The factory setting is 100 seconds (See wiring diagram). Cooling: The fan delay off period is factory set at 0 sec­onds. The option for 80 second delay off is field selectable (See wiring diagram).
ROOM AIR THERMOSTAT HEAT ANTICIPATOR ADJUSTMENT
Set the thermostat heat anticipator according to the cur­rent flow measured, or the settings found in the notes on the furnace wiring diagram (found in the SERVICE FACTS or inside the furnace casing).
INSTRUCTIONS TO THE OWNERS
EXPLOSION HAZARD
In the event that electrical, fuel, or mechanical fail­ures occur, shut off the gas supply off at the manual gas valve, located on the supply gas piping coming into the furnace, before turning off the electrical power to the furnace. Contact the service agency designated by your dealer.
BURNER BOX TEMPERATURE LIMIT DEVICE
All models are equipped with a manual reset temperature limit located on the burner box. In case of excessive tem­perature, the limit will open and cause the circuit to open which shuts off all flow of gas.
36 18-CD29D1-11
Page 37
Installer’s Guide
ABNORMAL CONDITIONS
  1.  EXCESSIVE  COMBUSTION  PRESSURE  (WIND  IN  EXCESS OF 40 M.P.H.) VENT OR FLUE BLOCKAGE
If pressure against induced draft blower outlet becomes
excessive, the pressure switch will open and shut off the gas valve until acceptable combustion pressure is again available.
2. LOSS OF FLAME
If loss of flame occurs during a heating cycle, or flame
is not present at the sensor, the flame control module will close the gas valve. The flame control module will then recycle the ignition sequence, then if ignition is not achieved, it will shut off the gas valve and lock out the system.
3. POWER FAILURE
If there is a power failure during a heating cycle, the
system will restart the ignition sequence automatically when power is restored if the thermostat still calls for heat.
4. GAS SUPPLY FAILURE
If loss of flame occurs during a heating cycle, the sys-
tem integrated control module will recycle the ignition sequence, then if ignition is not achieved, the integrat­ed control module will shut off the gas valve and lock out the system.
  5.  INDUCED DRAFT BLOWER FAILURE
If pressure is not sensed by the pressure switch, the
contacts will remain open and not allow the gas valve to open, therefore the unit will not start. If failure oc­curs during a running cycle, the pressure switch con­tacts will open and the gas valve will close to shut the unit down.
  6.  CONDENSATE DRAIN BLOCKAGE
If the condensate drain is blocked, either by debris, im-
proper draining, or by freezing condensate, the pres­sure switch will receive a signal warning of the accu­mulation of condensate in the heat exchanger assem­bly. The pressure switch contacts will open and remain open, not allowing unit operation. The unit will not op­erate until the condensate drain has been cleared, and the condensate flows freely.
  7.  RESET AFTER LOCKOUT
When the integrated control module has shut the sys-
tem down and gone into lockout, the system must be manually reset before the unit will restart. To reset, turn the system power off, then on, then off and then on again within 30 seconds. This may be done at the unit’s power source or at the thermostat. The system
will not reset unless the procedure off-on-off-on is com­pleted within 30 seconds.
  8.  RESET AFTER BURNER BOX LIMIT SHUTDOWN
If the furnace shuts down, one thing that can be
checked is the burner box temperature limit switch. It is located on the bottom of the burner box. The vent and combustion air inlet terminations should be checked for blockage. If blockage exists, clear the prob­lem and then the reset button may be depressed. If
there is no blockage of the terminations, the limit switch must be reset by a qualified servicer.
Carbon monoxide, fire or smoke can cause serious bodily in-
jury, death, and/or property damage. 
A variety of potential sources of carbon monoxide can be found in a building or dwelling such as gas-fired clothes dryers, gas cooking stoves, water heaters, furnaces and fireplaces. The U.S. Consumer Product Safety Commis­sion recommends that users of gas-burning appliances in­stall carbon monoxide detectors as well as fire and smoke detectors per the manufacturers installation instructions to help alert dwelling occupants of the presence of fire, smoke or unsafe levels of carbon monoxide. These devises should be listed by Underwriters Laboratories, Inc. Standards for
Single and Multiple Station Carbon Monoxide Alarms, UL 2034 or CSA International Standard, Residential Carbon Monoxide Alarming Devices, CSA 6.19
NOTE: The manufacturer of your furnace does not test any detec­tors and makes no representations regarding any brand or type of detector.
18-CD29D1-11 37
Page 38
Installer’s Guide
38 18-CD29D1-11
Page 39
TABLE 21
INTEGRATED FURNACE CONTROL ERROR FLASH CODES
Flashing Slow --- Normal - No call for Heat
Flashing Fast --- Normal - Call for Heat
Continuous ON --- Replace IFC
Continuous OFF --- Check Power
2 Flashes --- System Lockout (Retries or Recycles exceeded)
Draft Pressure Error - Possible problems
3 Flashes ---
4 Flashes --- Open High Limit Device
5 Flashes --- Flame sensed when no flame should be present
6 Flashes --- 115 Volt AC power reversed or Poor Grounding
a) Venting problem b) Pressure switch problem c) Inducer problem
Installer’s Guide
7 Flashes --- Gas valve circuit error
8 Flashes --- Low flame sense signal
Check Ignitor circuit and Line "N" to 24VAC "Com-
9 Flashes ---
mon" voltage (< 2volts) (possible grounding problem)
18-CD29D1-11 39
Page 40
Trane 6200 Troup Highway Tyler, TX 75707
Literature Order Number 18-CD29D1-11
File Number 18-CD29D1-11
Supersedes 18-CD29D1-10
Date 03/14
For more information contact your local dealer (distributor)
The manufacturer has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.
Loading...