Safety signal words are used to designate a degree or
level of seriousness associated with a particular hazard. The signal words for safety markings are WARN-ING and CAUTION.
a. WARNING indicates a potentially hazardous situa-
tion which, if not avoided, could result in death or
serious injury.
b. CAUTION indicates a potentially hazardous situa-
tion which, if not avoided, may result in minor or
moderate injury. It is also used to alert against unsafe practices and hazards involving only property
damage.
The following safety practices and precautions must be
followed during the installation, servicing, and operation of this furnace.
1. Use only with the type of gas approved for this furnace.
Refer to the furnace rating plate.
2. Install this furnace only in a location and position as
specified in “Location and Clearances” (page 4), of these
instructions.
3. Provide adequate combustion and ventilation air to the
furnace space as specified in “Air for Combustion and
Ventilation” (pages 8-9), of these instructions.
4. Combustion products must be discharged outdoors. Connect this furnace to an approved vent system only, as
specified in the “Venting” section (starting on page 15),
of these instructions.
5. Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for
the detection of leaks to check all connections, as specified in “Gas Piping” (pages 31-32), of these instructions.
6. Always install the furnace to operate within the furnace’s
intended temperature-rise range with a duct system
which has an external static pressure within the allowable range, as specified on the unit rating plate.
Airflow with temperature rise for cfm versus static is
shown in the Service Facts accompanying this furnace.
7. When a furnace is installed so that supply ducts carry
air circulated by the furnace to areas outside the space
containing the furnace, the return air shall also be
handled by a duct(s) sealed to the furnace casing and
terminating outside the space containing the furnace.
8. A gas-fired furnace for installation in a residential garage
must be installed as specified in “Location and Clearances” section (page 4), of these instructions.
9. The furnace may be used for temporary heating of buildings or structures under construction only when the
following conditions have been met:
a. The furnace venting system must be complete
and installed per manufacturers instructions.
b. The furnace is controlled only by a room ther-
mostat (no field jumpers).
c. The furnace return air duct must be complete
and sealed to the furnace and clean air filters
are in place.
d. The furnace input rate and temperature rise
must be verified to be within nameplate marking.
e. 100% of the furnace combustion air require-
ment must come from outside the structure.
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each appliance connected to the venting system being placed
into operation could result in carbon monoxide poisoning or death.
The following steps shall be followed for each appliance connected to the venting system being placed
into operation, while all other appliances connected to
the venting system are not in operation:
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and horizontal pitch, as required in the National Fuel Gas
Code, ANSI Z223.1/NFPA 54 or the CAN/CGA B149
Installation Codes and these instructions. Determine that there is no blockage or restriction, leakage, corrosion and other deficiencies which could
cause an unsafe condition.
3. As far as practical, close all building doors and
windows and all doors between the space in which
the appliance(s) connected to the venting system
are located and other deficiencies which could
cause an unsafe condition.
4. Close fireplace dampers.
5. Turn on clothes dryers and any appliance not connected to the venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they are operating at maximum speed.
Do not operate a summer exhaust fan.
6. Follow the lighting instructions. Place the appliance being inspected into operation. Adjust the
thermostat so appliance is operating continuously.
7. If improper venting is observed during any of the
above tests, the venting system must be corrected
in accordance with the National Fuel Gas Code,
ANSI Z221.1/NFPA 54 and/or CAN/CGA B149.1 Installation Codes.
8. After it has been determined that each appliance
connected to the venting system properly vents
where tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any
other gas-fired burning appliance to their previous
conditions of use.
upon substantial completion of the construction process, and verify furnace operating conditions including ignition, input rate, temperature rise and venting, according to the manufacturer's instructions.
10. This product must be gas piped by a Licensed
Plumber or Gas Fitter in the Commonwealth
of Massachusetts.
FIRE OR EXPLOSION HAZARD
Failure to follow the safety warnings exactly could
result in serious injury, death or property damage.
Improper servicing could result in dangerous operation, serious injury, death, or property damage.
GENERAL INSTALLATION INSTRUCTIONS
The manufacturer assumes no responsibility for equipment installed in violation of any code or regulation.
It is recommended that Manual J of the Air Conditioning Contractors Association (ACCA) or A.R.I. 230 be
followed in estimating heating requirements. When
estimating heating requirements for installation at
altitudes above 2000 ft., remember the gas input may
need to be reduced (See High Altitude Installation).
Material in this shipment has been inspected at
the factory and released to the transportation
agency without known damage. Inspect exterior
of carton for evidence of rough handling in shipment. Unpack carefully after moving equipment
to approximate location. If damage to contents is
found, report the damage immediately to the delivering agency.
Codes and local utility requirements governing the
installation of gas fired equipment, wiring, plumbing, and flue connections must be adhered to. In the
absence of local codes, the installation must conform
with latest edition of the National Fuel Gas Code ANSI
Z223.1 • National Installation Code, CAN/CGA B149.1.
The latest code may be obtained from the American
Gas Association Laboratories, 400 N. Capitol St. NW,
Washington D.C. 20001.
1-800-699-9277 or www.aga.org
These furnaces have been classified as CATEGORY
IV furnaces in accordance with latest edition of ANSI
Z21.47 • CAN/ CGA 2.3 standards.
Category IV furnaces operate with positive vent static pressure and with a flue loss less than 17 percent.
These conditions require special venting systems,
which must be gas tight and water tight. These Category IV Direct Vent furnaces are approved for installa-
tion in Manufactured/ Mobile housing when used with
BAYMFGH100A.
Contents
INSTALLATION INSTRUCTIONS
General Installation Instructions 3
Location and Clearances 4
Outline Drawings 5
Upflow Installation 7
Downflow Installation 7
Horizontal Installation 7
Air For Combustion and Ventilation 8
Duct Connections 10
Return Air Filters 11
General Venting Instructions 15
Venting Material 17
Venting Tables 18
Horizontal Venting 21
Venting Through The Wall 21
Venting Through The Roof 22
Downward Venting 24
Venting Through a Masonry Chimney 24
Condensate Drain Instructions 27
Electrical Connections 30
Field Wiring Diagrams 29
Gas Piping 32
Combustion Input Checks 33
Start Up and Adjustment 36
Preliminary Inspections 36
Lighting Instructions 36
Sequence Of Operation 37
Control And Safety Switch Adjustments 37
Airflow Adjustment 37
Abnormal Conditions 38
IFC Error Flash Code 40
To prevent shortening its service life, the furnace should
not be used as a “Construction Heater” during the finishing phases of construction until the requirements listed in
item 9, a-g of the safety section of this publication have
been met. Condensate in the presence of chlorides and
fluorides from paint, varnish, stains, adhesives, cleaning compounds, and cement create a corrosive condition
which may cause rapid deterioration of the heat exchanger.
18-CD29D1-11 3
Page 4
Installer’s Guide
▲
CAUTION
!
▲
WARNING
!
UPFLOW
FURNACE
CASED
COIL
SCREWS
(BOTH SIDES)
STANDOFFS
(BOTH SIDES)
STANDOFFS (4)
DRILL SCREWS (4)
▲
WARNING
!
EXPLOSION HAZARD!
PROPANE GAS IS HEAVIER THAN AIR AND MAY
COLLECT IN ANY LOW AREAS OR CONFINED SPACES. IN ADDITION, ODORANT FADE MAY MAKE THE
GAS UNDETECTABLE EXCEPT WITH A WARNING
DEVICE. IF THE GAS FURNACE IS INSTALLED IN A
BASEMENT, AN EXCAVATED AREA OR A CONFINED
SPACE, IT IS STRONGLY RECOMMENDED TO CONTACT A GAS SUPPLIER TO INSTALL A GAS DETECTING WARNING DEVICE IN CASE OF A GAS LEAK.
NOTE: The manufacturer of your furnace does NOT test
any detectors and makes no representations regarding
any brand or type of detector.
Do NOT install the furnace in a corrosive or contaminated
atmosphere.
LOCATION AND CLEARANCES
The location of the furnace is normally selected by the architect, the builder, or the installer. However, before the
furnace is moved into place, be sure to consider the following requirements:
1. Is the location selected as near the vent and as centralized for heat distribution as practical?
2. Do all clearances between the furnace and enclosure
equal or exceed the minimums shown in the Table 1.
3. Is there sufficient space for servicing the furnace and
other equipment? A minimum of 24 inches front accessibility to the furnace must be provided. Any access
door or panel must permit removal of the largest component.
4. Are there at least 3 inches of clearance between the furnace front panel and any closed panel or door provided?
5. Are the ventilation and combustion air openings large
enough and will they remain unobstructed? If outside
air is used, are the openings set 12" minimum above
the highest snow accumulation level?
6. Allow sufficient height in supply plenum above or below
the furnace to provide for cooling coil installation if the
cooling coil is not installed at the time of this furnace
installation.
7. A furnace shall be installed so electrical components are
protected from water.
8. If the furnace is installed in a residential garage, it
must be installed so that the burners and the ignition
source are located not less than 18 inches (46 cm) above
the floor and the furnace must be located or protected
to avoid physical damage from vehicles.
UPFLOW INSTALLATION
Standoffs and screws (See Figure 1) are included with
the cased coils for attachment to the furnace. There
are clearance alignment holes near the bottom of the
coil wrapper. Drill screws are used to engage the furnace top flanges. The standoff is inserted into the
cabinet alignment hole. The drill screws are inserted
through the standoffs then screwed into the furnace
flange.
The coil is always placed downstream of the furnace
airflow.
1
FOR VERTICAL
INSTALLATIONS:
DOWNFLOW INSTALLATIONS
FIRE HAZARD
Do NOT install the furnace directly on carpeting, tile
or other combustible material other than wood flooring. For vertical downflow application, subbase (BAYBASE-205) must be used between the furnace and
combustible flooring. When the downflow furnace is
installed vertically with a cased coil, a subbase is not
required.
Required floor opening:
IMPORTANT:
The furnace must be installed level. The only allowable variation would be slightly to the left and/or forward in upflow installations or slightly toward the front in horizontal installations.
This is necessary for proper condensate drainage.
NOTE:
On upflow 5 or 6 ton airflow models where the airflow requirement exceeds 1800 CFM - Models will require return
air openings and filters on: (1) both sides; or (2) one side
and the bottom; or (3) just the bottom.
4 18-CD29D1-11
2
CABINET
WIDTH
17-1/2"16-1/4"16-5/8"20-1/8"15-5/8"19-3/8"
21"19-3/4"20-1/8"20-1/8"19-1/8"19-3/8"
24-1/2"23-1/4"23-5/8"20-1/8"22-5/8"19-3/8"
SUBBASE CROSS SECTION
TABLE 1
RETURN
DUCT WIDTH
FLOOR OPENING PLENUM OPENING
"A""B""C""D"
Page 5
1. *UH1D120A9601, *UH1C080A9601, *UH1C100A9481, AND
UH1D100A9601 REQUIRE 3” DIAMETER VENT PIPE.
2. DIAMETER OF VENT PIPE MAY BE LIMITED TO 2-1/2” OR 3”
ON SOME MODELS AT DIFFERENT ALTITUDES. REFER TO THE
VENT LENGTH TABLE FOR PROPER APPLICATION.
Installer’s Guide
From Dwg. C341884 Rev. 9
(ALL DIMENSIONS ARE IN INCHES)
*UH1 OUTLINE DRAWING, UPFLOW / HORIZONTAL
18-CD29D1-11 5
Page 6
Installer’s Guide
From Dwg. C341885 Rev. 7
(ALL DIMENSIONS ARE IN INCHES)
*DH1 OUTLINE DRAWING, DOWNFLOW / HORIZONTAL
17-1/2"2-1/4"16-1/4"16"
MODELDIM "A"DIM"B"DIM "C"DIM "D"
*DH1B040A9241
*DH1B065A9421
*DH1C085A948121"2-1/2"19-3/4"19-1/2"
*DH1D110A960124-1/2"2-15/16"23-1/4"23"
* May be "A" or "T"
Part numbers can end in A-Z
6 18-CD29D1-11
Page 7
Installer’s Guide
3
A (width)
FURNACE
FRONT
HORIZONTAL INSTALLATION
The coil and furnace must be fully supported when used in
the horizontal position. It is always recommended that an
auxiliary drain pan be installed under a horizontally installed evaporator coil or 95% gas furnace. Connect the auxiliary drain line to a separate drain line (no trap is needed
in this line).
Three brackets (with screws) are included with downflow
furnaces for installation to stabilize and secure the furnace and TXC cased coil in the horizontal position. See
Figure 4.
IMPORTANT:
The 2/4TXC cased coil must be placed downstream of the
furnace. In horizontal installations, the apex of the coil
may point either toward or away from the furnace. See the
2/4TXC coil Installer's Guide for more details.
The cased coil is secured to the furnace and both the furnace and the cased coil must be properly supported. The
brackets mount using the rear screws on the coil case and
use the screws provided to secure the bracket to the furnace. The remaining bracket is placed as close to center as
possible (horizontally) between the coil case front and the
Use four of the screws provided to secure the bracket. The
upflow furnace, converted to horizontal, aligns and attaches
the TXC coil as in Figure 1. However, the coil requires additional support.
B (depth)
D
C
5
UPFLOW/
HORIZONTAL
SHOWN
The furnace may be placed horizontally in a crawl space on
a pad or other noncombustible material which will raise the
unit for sufficient protection from moisture. The furnace
must be supported at both ends and the middle when
installed horizontally.
The furnace must also be elevated a minimum of 6
inches to allow clearance for the condensate drain to
exit the cabinet in the horizontal position.
The horizontal furnace may also be suspended from the
joists using 3/8" all-thread rods with pieces of angle iron
underneath the furnace to form a hanging rack at both
ends and the midpoint. The rods need to be of sufficient
length to allow for proper clearances from combustible
materials. The angle iron needs to be at least 32" in length
to allow for access to service panels.
6
50 CU. FT. OR MORE
PER 1000 BTU/HR. INPUT
ALL EQUIP. INSTALLED
4
CASED COIL CONNECTION
BRACKET FOR DOWNFLOW
FURNACE IN HORIZONTAL
DOWNFLOW ONLY
The furnace may be installed in an attic or crawl space in
the horizontal position by placing the furnace on the left side (as viewed from the front in the vertical position). The
horizontal furnace installation in an attic should be on a
service platform large enough to allow for proper clearances
on all sides and service access to the front of the furnace
(See Figure 3 & Clearance Table 1). Line contact is only
permissible between lines formed by intersections of the
top and two sides of the furnace casing and building joists,
studs, or framing.
UNCONFINED
AIR FOR COMBUSTION AND VENTILATION
If these furnaces are installed in a nondirect vent capacity then the adequate flow of combustion and ventilating
air must not be obstructed from reaching the furnace. Air
openings provided for combustion air must be kept free of
obstructions which restrict the flow of air. Airflow restrictions affect the efficiency and safe operation of the furnace.
Keep this in mind should you choose to remodel or change
the area which contains your furnace. Furnaces must have
a free flow of air for proper performance.
Provisions for combustion and ventilation air shall be made
in accordance with latest edition of Section 5.3, Air for Combustion and Ventilation, of the National Fuel Gas Code,
ANSI Z223.1 — CAN/CGA B149.1 or applicable provisions
of the local building codes. Special conditions created by
mechanical exhausting of air and fireplaces must be considered to avoid unsatisfactory furnace operation.
18-CD29D1-11 7
Page 8
Installer’s Guide
OUTSIDE AIR IS RECOMMENDED
The use of indoor air for most applications is acceptable,
unless there is the presence of corrosive chemicals or contamination. Certain types of installation will require
the use of outside air for combustion.
The following types of installations will require use of
OUTDOOR AIR for combustion, due to chemical exposures:
* Commercial buildings
* Buildings with indoor pools
* Furnaces installed in “confined” laundry rooms
* Furnaces installed in “confined” hobby or craft rooms
* Furnaces installed near chemical storage areas.
Exposure to the following substances in the combustion air
supply will also require OUTDOOR AIR for combustion:
* Permanent wave solutions
* Chlorinated waxes and cleaners
* Chlorine based swimming pool chemicals
* Water softening chemicals
* Deicing salts or chemicals
* Carbon Tetrachloride
* Halogen type refrigerants
* Cleaning solvents (such as perchloroethylene)
* Printing inks, paint removers, varnish, etc.
* Hydrochloric acid
* Cements and glues
* Antistatic fabric softeners for clothes dryers
* Masonry acid washing materials
Furnace locations may be in a “confined space” or an “un-confined space”.
Unconfined space is defined in Figure 6. These spaces may
have adequate air by infiltration to provide air for combus-
tion and ventilation. Buildings with tight construction (for
example, weather stripping, heavily insulated, caulked, vapor barrier, etc.), may need additional air to be provided as
described for confined space.
1. All air from inside the building as in Figure 8: The confined space shall be provided with two permanent openings communicating directly with an additional room(s)
of sufficient volume so that the combined volume of all
spaces meets the criteria for an unconfined space. The
total input of all gas utilization equipment installed in
the combined space shall be considered in making this
determination. Refer to Table 2 for minimum open areas requirements.
2. All air from outdoors as in Figure 9: The confined space
shall be provided with two permanent openings, one
commencing within 12 inches of the top and one commencing within 12 inches of the bottom of the enclosure. The openings shall communicate directly, or by
ducts, with the outdoors or spaces (crawl or attic) that
freely communicate with the outdoors. Refer to Table 2,
for minimum open areas requirements.
TABLE 3
MINIMUM FREE AREA IN SQUARE INCHES
EACH OPENING (FURNACE ONLY)
Furnace
Maximum
BTUH/INPUT
Rating
40,000
60,000
80,000
97,000
110,000
Air
From
Inside
100
100
100
100
110
Air From Outside
Vertical
Duct
10
15
20
25
28
Horizontal
Duct
20
30
40
50
55
8
Confined spaces are installations with less than 50 cu. ft. of
space per 1000 BTU/hr input from all equipment installed,
as in Figure 7. Air for combustion and ventilation requirements can be supplied from inside the building as in Figure
8 or from the outdoors, as in Figure 9.
Table 2
MINIMUM AREA IN SQUARE FEET
FOR UNCONFINED SPACE INSTALLATIONS
FURNACE MAXI-
MUM BTUH INPUT
RATING
40,000
60,000
80,000
97,000
110,000
WITH 8 FT. CEILING
MINIMUM AREA IN SQUARE FEET
OF UNCONFINED SPACE
250
375
500
625
688
7
CONFINED
SPACE
8 18-CD29D1-11
Page 9
9
Installer’s Guide
On any job, flexible connections of nonflammable material may be used for return air and discharge connections to
pre vent transmission of vibration. Though these units have
been specifically designed for quiet, vibration free operation,
air ducts can act as sounding boards and could, if poorly installed, amplify the slightest vibration to the annoyance level.
When the furnace is located in a utility room adjacent to
the living area, the system should be carefully designed
with returns to minimize noise transmission through the
return air grille. Although these furnaces are designed
with large blowers operating at moderate speeds, any blower moving a high volume of air will produce audible noise
which could be objectionable when the unit is located very
close to a living area. It is often advisable to route the return air ducts under the floor or through the attic. Such design permits the installation of air return remote from the
living area (i.e. central hall).
When the furnace is installed so that the supply ducts carry
air circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by
a duct(s) sealed to the furnace and terminating outside the
space containing the furnace.
RETURN AIR DUCT CONNECTION
NOTE:
On upflow 5 or 6 ton airflow models where the airflow requirement exceeds 1800 CFM - Models will require return
air openings and filters on: (1) both sides; or (2) one side
and the bottom; or (3) just the bottom.
All return air duct systems should provide for installation
of return air filters.
1. Determine the appropriate position to set the furnace
in order to connect to the existing supply and return
ductwork.
2. For side return installations on upflow models, remove
the insulation around the opening in the blower compartment.
DUCT CONNECTIONS
Air duct systems should be installed in accordance with
standards for air conditioning systems, National Fire Protection Association Pamphlet No. 90. They should be sized
in accordance with ACCA Manual D or whichever is applicable.
Central furnaces, when used in connection with cooling
units, shall be installed in parallel or on the upstream side
of the cooling coil to avoid condensation in the heat exchanger. With a parallel flow arrangement, the dampers or
other means used to control flow of air shall be adequate to
prevent chilled air from entering the furnace, and if manually operated, must be equipped with means to prevent operation of either unit unless the damper is in full heat or
cool position.
NOTE:
Minimum return air temperature is 55° F.
3. The side panels on upflow furnaces include locating
notches which may be used as guides for cutting an
opening for return air. Refer to Figure 11 and the outline drawing on pages 5-6 for duct connection dimensions for various furnaces.
4. If a 3/4" ange is to be used for attaching the air inlet
duct, add to cut where indicated by dashed lines in
Figure 11. Cut corners diagonally and bend outward to
form flange.
5. If flanges are not required, and a filter frame is installed, cut along knockout guidelines.
6. Upflow Furnaces: Use the optional filter rack on
either side or on the bottom if the filter is to be used
within the furnace cabinet.
When the upflow furnace is installed in the horizontal
application and a return duct is attached to the top side
as shown in Figure 10, install the filter in a remote
location.
Do not install the filter in the return duct directly
above the furnace in horizontal applications.
18-CD29D1-11 9
Page 10
Installer’s Guide
▲
WARNING
!
▲
WARNING
!
When the upflow furnace is installed in the horizontal
application and a close coupled (less than 36") return
duct is attached to the bottom side of the furnace as
shown in Figure 10, securely attach a 1/2" mesh metal
hardware cloth protective screen to the inside bottom
of the filter grill to prevent personal injury from
contacting moving parts when reaching into the
return opening to replace the filter.
Close coupled (less than 36") return (filter directly
beneath bottom side return) is not recommended due to
noise considerations.
Downflow Furnaces: Brackets are factory supplied
to mount filters in the return air duct work.
FIRE OR EXPLOSION HAZARD
Do not install the filter in the return duct directly above
the furnace in horizontal applications. Install the filter remotely. Failure to follow the safety warnings exactly could
result in serious injury, death or property damage.
SAFETY HAZARD
To prevent injury or death due to contact with moving
parts, turn the power to the furnace off before servicing
filters
Failure to follow the safety warnings exactly could result
in serious injury, death or property damage.
REMOVE FILTER FROM UPFLOW
FURNACE WHEN RETURN DUCT IS
ATTACHED TO FURNACE TOP SIDE
(HORIZONTAL APPLICATIONS) AS
SHOWN.
Close coupled (less than 36")
return (filter directly beneath bottom
side return) not recommended due to
noise considerations. If used, securely
attach 1/2" mesh metal hardware cloth
protective screen to the inside bottom
of filter grill.
FILTER
0
7. Connect the duct work to the furnace. See Outline
Drawing (pages 5-6) for supply and return duct size
and location. Flexible duct connectors are recommended to connect both supply and return air ducts to the
furnace.
If only the front of the furnace is accessible, it is recommended that both supply and return air plenums are
removable.
8. When replacing a furnace, old duct work should be
cleaned out. Thin cloths should be placed over the
registers and the furnace fan should be run for 10 minutes. Don’t forget to remove the cloths before you start
the furnace.
q
LOCATING
NOTCHES
PROVIDED
FOR SIDE
RETURN
CUTOUT
*
*
*
*
CUT OUT
FOR
SIDE
FILTER
FRONT
of Furnace
*SEE OUTLINE DRAWING
RETURN AIR FILTERS
(Filter and filter rack are not supplied with unit)
TYPICAL UPFLOW RETURN AIR FILTER INSTALLATIONS
These furnaces require high velocity type air filters. The
optional filters may be located within the furnace blower
compartment for UPFLOW furnaces in either a BOTTOM
or SIDE (left side or right side) return air inlet. Some
optional filters may need to be trimmed for side or bottom
filter use.
The furnace and the blower filter rack installation can be
seen in Figure 12.
The optional furnace filter in the bottom or side configuration can be removed by simply turning the two latches on
the blower door and tilting the door forward.
The filter rails are spring loaded for automatic adjustment
to allow standard size, locally obtainable replacement
filters. The filter rack itself slides to adjust to the required
width needed for bottom or side return.
TABLE 4 - MINIMUM CLEARANCE FROM COMBUSTIBLE MATERIALS FOR
UPFLOW/HORIZONTAL LEFT AND DOWNFLOW/HORIZONTAL RIGHT FURNACES
UNIT LOCATION
FURNACE SURFACE
SIDES0"1"0"
BACK0"3"6"
TOP1"1"1"
FRONT3"3"18"
VENT0"0"0"
NOTE: CLEARANCE REQUIRED AT TOP OF PLENUM IS 1"
10 18-CD29D1-11
VERTICAL
CLOSET
HORIZONTAL
CLOSET
HORIZONTAL
ALCOVE / ATTIC
Page 11
Installer’s Guide
Filter
TABLE 5
UPFLOW FURNACE RETURN AIR FILTERS
CABINET
WIDTH
14-1/2"114" X 25" X 1"17-1/2" X 25" X 1"
17-1/2"117" X 25" X 1"17-1/2" X 25" X 1"
21"120" X 25" X 1"17-1/2" X 25" X 1"
24-1/2"124" X 25" X 1"17-1/2" X 25" X 1"
**NOTE: For upflow 5 ton airflow models where the airflow
requirement exceeds 1800 CFM - Models will require return air
openings and filters on: (1) both sides, or (2) one side and the
bottom, or (3) just on the bottom
QTY*
CABINET
BOTTOM FILTER
CABINET
SIDE FILTER
Airflow
NOTE: The narrow 14.5" width furnace cabinet prevents
use of the filter rack for right side return. Pre-drill clearance holes and then attach filter clips with the screws
provided. The filter clip with the leaf spring mounts in the
rear of the cabinet
OPTIONAL FILTER RACK INSTALLATION FOR BOTTOM
RETURN - BAYRACK960
The following checklist should be used when installing as a
bottom return filter on an upflow furnace:
a. Remove the filter.
b. Remove the bottom panel.
c. Pre-drill two engagement holes with 3/16" drill at
dimple locations. See Figure 14.
d. With the filter removed, the filter rack is compressed
and then inserted into the bottom of the furnace. The
retaining screw/pin on each side inserts into engagement holes at the bottom of the furnace cabinet side.
See Figure 15.
e. Reinstall the furnace filter in the bottom position by
inserting the chamfer end first into the filter rack.
NOTE: Remove the bottom front channel to install the
filter rack in the 14-1/2" width cabinet furnaces.
e
w
Airflow
BOTTOM FILTER RACK INSTALLATION
r
Blower Deck
Engagement
PRE-DRILL
Two clearance holes with a
3/16” drill at dimple locations
(one per side)
1. UC1B060C has 10x7 blower which requires use of alternate filter
clips for left side filter. "K1" and later use the filter rack.
2. Remove bottom front channel to install or reposition filter rack.
X - All Models
OPTIONAL FILTER RACK INSTALLATION FOR SIDE
RETURN AIR ON UPFLOW FURNACES (Left or Right) BAYRACK960
The following checklist should be used when installing a
right or left side return filter on an upflow furnace:
a. Remove the filter.
b. Leave the bottom panel in place.
c. Make side cutout by following the directions in the
“Return Air Duct Connections” section on page 9.
d. Compress the filter rack and reinstall in the side
position on the furnace. Confirm that the upper
retaining pin/screw locks into the engagement hole in
the blower deck and the lower pin/screw rests against
the side of the bottom panel. See Figures 14, 18-20.
e. Reinstall the furnace filter in the side position by
inserting the chamfer end first into the filter rack.
1
X2Use Alternate Filter Clips Only
i
Typical Upflow Left Side Return Filter Rack Installation
o
y
u
BLOWER
DECK
12 18-CD29D1-11
BOTTOM ENGAGEMENT
Furnace
Cabinet
Side
Retaining
Screw/Pin
Filter
Rack
Bottom Panel
Typical Upflow Right Side Return Filter Rack Installation
p
Airflow
Accessory filter kit
BAYFLTR203, 204, or
205 used for Upflow
Horizontal furnaces
Typical Horizontal Filter Installation
Page 13
Installer’s Guide
REAR
SIDE
CUT-OUT
ALTERNATE FILTER
CLIPS LOCATION
RETURN AIR FILTERS FOR UPFLOW FURNACE
IN HORIZONTAL CONFIGURATION
When the Upflow Furnace is installed in a horizontal
configuration, the filter must never be installed inside or
outside the cabinet directly above the blower assembly.
See Figure 10 (page 11). Remote filter grilles may be used
for homeowner convenience or the filters may be installed
in the duct work upstream of the furnace. See Figures 20
(page 13).
Optional horizontal lter conversion kits are BAYFLTR203
for 17 1/2" width cabinets, BAYFLTR204 for 21" width
cabinets, and BAYFLTR205 for 24" width cabinets. These
include filters and brackets necessary for horizontal filters.
See Figure 20.
1. Determine the location to be used. The furnace cabinet
has dimples for location of the alternate furnace clips
(Side return only). Pre-drill clearance holes with a
3/16" drill. Bottom return holes are pre-drilled.
2. Install the clips in front and rear of the desired location
using the screws provided. The filter clip with the leaf
spring mounts in the rear of the cabinet. See Figure21.
a
TYPICAL DOWNFLOW FURNACE
RETURN AIR FILTER INSTALLATIONS
Two high velocity type air filters are required for each downflow furnace. Downflow furnace filters must be located
outside the furnace cabinet. Typical installations are shown
in Figures 22 and 23. Tables 8 and 9 provide information
for installation of the filter retaining brackets shipped with
downflow furnaces.
s
Airflow
d
Airflow
INSTALLING THE OPTIONAL FILTER
The filter may need to be cut to fit the unit depending on
the location of the return air filter.
A score line and the words “CUT HERE” are located on the
end of the filter. If your application requires cutting the
filter, do so as indicted by the score mark.
* Location dimension is from end of duct to the screw holes for the bracket.
CABINET
WIDTH
14-1/2"13-1/4"12"14"
17-1/2"16-1/4"15"14"
21"19-3/4"19-1/2"14"
24-1/2"23-1/4"22"14"
Optional accessory door kit BAYFLTR206 is also available
with narrow door to avoid flue piping in downflow furnaces.
RETURN
DUCT
WIDTH
TABLE 8
FILTER
SIZE
TABLE 9
FILTER ACCESS
OPENING - DI-
MENSION "A"
FILTER BRACKET
LOCATION *
FILTER ACCESS
OPENING -
DIMENSION "B"
Page 14
Installer’s Guide
▲
WARNING
!
GENERAL VENTING
CARBON MONOXIDE POISONING HAZARD
FURNACE MUST BE VENTED PROPERLY. FAILURE TO
FOLLOW THE INSTALLATION INSTRUCTIONS FOR THE
VENTING SYSTEM COULD RESULT IN CARBON MONOXIDE
POISONING, FIRE OR SMOKE THAT CAN CAUSE SERIOUS
BODILY INJURY, DEATH OR PROPERTY DAMAGE.
IMPORTANT:
The building owner/maintenance provider must keep the
area around the vent clear from snow.
THIS FURNACE MUST BE VENTED TO THE OUTDOORS. THESE FURNACES ARE INDUCED DRAFT
VENTED AND MUST NOT BE CONNECTED TO ANY
VENT SERVING ANOTHER APPLIANCE. PLEASE
NOTE THAT THESE FURNACES USE POSITIVE-PRESSURE VENT SYSTEMS.
Proper venting is essential to obtain maximum efficiency
from a condensing furnace. Proper installation of the vent
system is necessary to assure drainage of the condensate
and prevent deterioration of the vent system.
American Gas Association has certified the design of condensing furnaces for a minimum of 0" clearance from combustible materials with a single wall plastic vent pipe.
The recommended system is assembled from 2", 2-1/2", or
3" plastic pipe and fittings (See Table 10, page 16). Where
the system is routed to the outdoors through an existing
masonry chimney containing flue products from another
gas appliance, or where required by local codes, then 3"
venting of Type 29-4C stainless steel must be used in place
of PVC material.
These furnaces have been classified as CATEGORY
IV furnaces in accordance with the latest edition of
ANSI Z21.47 • CAN/ CGA-2.3 Standards. Category IV furnaces operate with positive vent pressure and with a vent
gas temperature less than 140°F above the dewpoint. These
conditions require special venting systems, which must be
gas tight and water tight.
NOTE:
When an existing furnace is removed from a venting system serving other gas appliances, the venting system is
likely to be too large to properly vent the remaining attached appliances.
IMPORTANT
These Furnaces may be installed as Direct Vent
(sealed combustion) or as Nondirect Vent (single pipe).
The Furnaces are shipped DIRECT VENT with sealed
combustion.
!
WARNING
▲
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each
appliance connected to the venting system being
placed into operation could result in carbon monoxide
poisoning or death.
The following steps shall be followed for each appliance
connected to the venting system being placed into
operation, while all other appliances connected to the
venting system are not in operation:
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and
horizontal pitch, as required in the National Fuel Gas
Code, ANSI Z223.1/NFPA 54 or the CSA B149.1
Natural Gas and Propane Installation Code and these
instructions. Determine that there is no blockage or
restriction, leakage, corrosion and other deficiencies
which could cause an unsafe condition.
3. As far as practical, close all building doors and
windows and all doors between the space in which the
appliance(s) connected to the venting system are
located and other deficiencies which could cause an
unsafe condition.
4. Close fireplace dampers.
5. Turn on clothes dryers and any appliance not
connected to the venting system. Turn on any exhaust
fans, such as range hoods and bathroom exhausts, so
they are operating at maximum speed. Do not operate
a summer exhaust fan.
6. Follow the lighting instructions. Place the appliance
being inspected into operation. Adjust the thermostat
so appliance is operating continuously.
7. Test for spillage from draft hood equipped appliances
at the draft hood relief opening after 5 minutes of main
burner operation. Use the flame of a match or candle.
8. If improper venting is observed during any of the above
tests, the venting system must be corrected in
accordance with the National Fuel Gas Code, ANSI
Z221.1/NFPA 54 and/or CSA B149.1 Natural Gas and Propane Installation Code.
9. After it has been determined that each appliance
connected to the venting system properly vents when
tested as outlined above, return doors, windows,
exhaust fans, fireplace dampers and any other gas-fired
burning appliance to their previous conditions of use.
The following are general steps to be used to correct or resize
a remaining vent system when a furnace which may not be
common vented is removed from the system:
a. Determine the Btu per hour input of all remaining
appliances attached to the venting system.
b. Determine the diameter, rise, and lateral of the ex-
isting venting system, as well as quantity and type
of bends.
c. Use the appropriate tables in the latest edition of
the National Fuel Gas Code (ANSI Z223.1 • CAN/
CGA B149.1 Installation Codes or “Exhibit J” of
ANSI Z21.47 • CAN/ CGA-2.3 Standards. “Exhibit J”
includes examples and drawings of typical venting
systems.
IMPORTANT:
These furnaces may be installed as Direct Vent (sealed
combustion) or as Nondirect vent (single pipe). The furnaces are shipped DIRECT VENT with sealed combustion.
For DIRECT VENT APPLICATION: The furnaces must
be vented to the exterior of the house and combustion air
MUST come through the inlet air pipe FROM OUTSIDE
AIR.
For NONDIRECT VENT APPLICATION: The furnace shall
be vented to the exterior of the house, but combustion air
may enter from the surrounding area as long as combustion air requirements are met. (See AIR FOR COMBUSTION AND VENTILATION)
14 18-CD29D1-11
Page 15
Installer’s Guide
Furnace
Vent
Air
Inlet
(See Note)
Furnace
Air
Inlet
Vent
Attic
Vent
(See Note)
For DIRECT VENT APPLICATION: The Furnaces must
be vented to the exterior of the house and combustion air
MUST come through the inlet air pipe FROM OUTSIDE
AIR.
NOTE: BAYVENT200* accessories can be used for inlet
and outlet terminals when the pipes do not exit the
structure together.
For Canadian applications, venting systems must meet
ULC-S636 requirements.
For NONDIRECT VENT APPLICATION: The Furnace
shall be vented to the exterior of the house, but combustion
air may enter from the surrounding area as long as
combustion air requirements are met. (See AIR FOR
COMBUSTION AND VENTILATION)
FURNACE VENT / INLET PIPE INSTALLATION
There are many different variations of the vent / inlet air
pipe combination. The vent / inlet air combination used for
installation of these Furnaces depends on the needs of the
location. However, these guidelines must be followed:
1. The Furnace must vent outside the structure.
2. Furnace combustion air requirements must be met for
non-direct, single pipe applications.
3. For direct vent application of these Furnaces, the vent
pipe and air inlet pipe do not have to exit in the same
air space. However, the longest individual pipe will
decide the value for the longest allowable equivalent
vent/ inlet air length as shown in the vent length tables
on page 17 and 18.
NOTE: For single pressure zone applications, see Figure
27.
The following are EXAMPLES ONLY:
EX. 1 —
Example 1 shows the vent pipe exhausting through the roof
and the inlet air coming from the interior of the house. The
inlet air coming from the interior of the house must meet
combustion requirements for area, etc., as shown in the sec-
tion AIR FOR COMBUSTION AND VENTILATION in this
Installer’s Guide.
Example 1
EX. 2 —
The inlet air does not have to come from outside the
structure. Example 2 shows the inlet air, may come from
the attic if the requirements for combustion air are met as
shown in the section AIR FOR COMBUSTION AND VENTILATION.
NOTE: If only the flue gas pipe is to the outside of the
structure, a straight section of pipe (long enough to exit
the Furnace cabinet) must be attached to the inlet air side
with an elbow (which is 5 to 10 equiv. ft.) installed on the
end to prevent dust and debris from falling directly into
the Furnace.
Example 2
18-CD29D1-11 15
Page 16
Installer’s Guide
▲
WARNING
!
▲
WARNING
!
PVC VENT FITTING MATERIAL
These fittings are available from your Gas Furnace
Distributors.
Straight Pipe Sections, Couplings, 45° Elbows, 60° Elbows,
90° Elbows, Vent or Sanitary Tee, or other necessary fittings
may be 2", 2½", 3", or 4" diameter. The allowable materials are
shown in Table 10.
VENT FITTING MATERIAL – PLASTIC
Gas and liquid tight single wall vent fittings, designed for resistance to corrosive flue condensate, MUST be used throughout.
Listed in Table 10 are designations for different types of 2" and
3" size pipe and fittings that meet these requirements. The materials listed are various grades of PVC, CPVC, ABS, and DuraVent PolyPro®.
ATTACHING VENT PIPING
Important: Products installed in Canada must use vent
systems that are certified to the Standard for Type BH Gas
Venting Systems (ULC S636) for Class II-A venting systems
(up to 65°C). Components of the vent system must not be
interchanged with other vent systems or unlisted pipe or
fittings. Plastic components, specified primers, and glues must
be from a single system manufacturer and not intermixed with
other system manufacturer's vent system parts. In addition, the
first three feet of the vent pipe must be visible for inspection.
PIPE JOINTS: All joints must be fastened and sealed to
prevent escape of combustion products into the building.
MANUFACTURED MODULAR VENTING SYSTEMS
CARBON MONOXIDE POISONING HAZARD
See Table 10 for manufactured modular venting systems
that are approved for use with this product. Follow the
manufacturer's installation instructions when installing the
venting system. Failure to follow this warning may result
in property damage, severe personal injury, or death.
APPROVED VENT PIPE MATERIALS
CARBON MONOXIDE POISONING HAZARD
Do not use cement on polypropelene venting systems.
Follow the manufacturer's installation instructions when
installing the venting system. Failure to follow this
warning may result in property damage, severe personal
injury, or death.
For manufactured modular venting systems that are approved with this product see Table 10. Do not drill into
polypropelene venting pipes
BONDING OF PVC
NOTE:
It is recommended that the first joints from the furnace be
connected and sealed with high temperature RTV. This will
enable the pipes to be removed later without cutting.
Be sure to properly support these joints.
Commercially available solvent cement must be used to join
the pipe and fittings. Follow instructions on the container
carefully.
Procedure for Cementing Joints:
1. Cut pipe square, remove ragged edges and burrs.
Chamfer end of pipe, then clean fitting socket and pipe
joint area of all dirt, grease, moisture or chips.
2. After checking pipe and socket for proper fit, wipe socket and pipe with cleaner-primer. Apply a liberal coat of
primer to inside surface of socket and outside of pipe.
DO NOT ALLOW PRIMER TO DRY BEFORE APPLY-
ING CEMENT.
3. Apply a thin coat of cement evenly in the socket. Quickly apply a heavy coat of cement to the pipe end and insert pipe into fitting with a slight twisting movement
until it bottoms out.
4. Hold the pipe in the fitting for 30 seconds to prevent
tapered socket from pushing the pipe out of the fitting.
5. Wipe all excess cement from the joint with a rag. Allow
TABLE 10
PLASTIC VENT PIPE DESIGNATIONS
PVC
ASTM STANDARDPIPE TYPEALLOWABLE TEMPERATURE °FMARKING
F891CELLULAR CORE
D2665DWV PIPE
D1785SCH 40, 80, 120
D2241SDR SERIES
1 158
2 158
2 158
2 158
CPVC
ASTM STANDARDPIPE TYPEALLOWABLE TEMPERATURE MARKING
1 Allowable temperatures based on classifications covered in ASTM D4396 [Deflection Temps Under Load (264 PSI)]
2 Allowable temperatures based on classifications covered in ASTM D1784 [Deflection Temps Under Load (264 PSI)]
3 Allowable temperatures based on classifications covered in ASTM D3965 [Deflection Temps Under Load (264 PSI)]
4 This furnace family is approved for venting with DuraVent PolyPro® venting systems.
5 Canadian venting systems must be composed of materials that meet ULC-S636.
ASTM F891
ASTM D2665
ASTM D1785
ASTM D2241
ASTM D2846
ASTM F441
ASTM F442
ASTM D2661
ASTM F628
16 18-CD29D1-11
Page 17
Seal VENT PIPE
with RTV sealant
Seal INLET AIR PIPE
with RTV sealant
Front of Furnace
▲
WARNING
!
15 minutes before handling. Cure time varies according
to fit, temperature and humidity.
NOTE:
Follow venting instructions carefully when using PVC cement.
IMPORTANT:
All joints must be water tight. Flue condensate is somewhat
acidic, and leaks can cause equipment damage.
Connection of the pipe and collar of the combustion air
inlet should just be a friction fit. It is recommended that
the inlet air joint be sealed with RTV type sealant to allow
the joint to be separated for possible future service. The inlet and vent pipes must be properly supported throughout
the entire length.
Connection of the vent pipe to the vent collar should also
be accomplished using RTV type sealant. This type sealant
provides a connection which remains flexible and can be
separated in the future if service needs require the removal
of the vent pipe for service or clearance. See Figure 24.
NOTE:
To ensure proper operation at the vent lengths indicated,
the combustion air inlet and vent terminals should be in
the same pressure zone. Terminating the vent and inlet in
different pressure zones will change the maximum vent
lengths and may cause nuisance tripping of the pressure
switch(es). The amount of change can not be predicted.
The selection of the inlet and outlet terminal locations are
the responsibility of the designer/installer. If the installer
chooses separate pressure zones for the terminals, the
combustion air inlet termination must be in the higher
(more positive) pressure zone.
Installer’s Guide
CARBON MONOXIDE POISONING HAZARD
FAILURE TO FOLLOW THE DURAVENT INSTALLATION
INSTRUCTIONS IF THE POLYPROPELENE VENTING
SYSTEM IS BEING PLACED INTO OPERATION COULD
RESULT IN CARBON MONOXIDE POISONING OR DEATH.
VENT AND INLET AIR CONNECTIONS
f
Products installed in Canada must use vent systems
that are certified to the Standard for Type BH Gas Venting Systems (ULC S636) for Class II-A venting systems
(up to 65°C). Components of the vent system must not
be interchanged with other vent systems or unlisted
pipe or fittings. Plastic components, specified primers,
and glues must be from a single system manufacturer
and not intermixed with other system manufacturer's
vent system parts. In addition, the first three feet of the
vent pipe must be visible for inspection.
MAXIMUM VENT LENGHT TABLE
MAXIMUM VENT LENGTH:
*UH1B040A9241A6080100130508080130
*UH1B060A9361A6080100130508080130
*UH1B080A9421B4080100130308080130
*UH1C080A9601ANOT ALLOWED NOT ALLOWED70130NOT ALLOWED NOT ALLOWED50130
*UH1C100A9481ANOT ALLOWED NOT ALLOWED90130NOT ALLOWED NOT ALLOWED70130
*UH1D100A9601ANOT ALLOWED NOT ALLOWED90130NOT ALLOWED NOT ALLOWED70130
*UH1D120A9601ANOT ALLOWED NOT ALLOWED50130NOT ALLOWED NOT ALLOWED30130
NOTES: * - First letter may be "A" or "T"
1. FOR DURAVENT MANUFACTURED MODULAR VENTING SYSTEMS THAT ARE APPROVED IN TABLE 10, EQUIVALENT VENT LENGTHS MAY BE DIF-
FERENT FROM WHAT IS SHOWN ABOVE. REFER TO THE VENTING SYSTEM MANUFACTURER'S INSTALLATION INSTRUCTIONS FOR APPROPRIATE
VENTING DIAMETERS AND EQUIVALENT LENGTHS.
2. Minimum vent length for all models: 3' horizontal or 3' vertical.
3. DO NOT MIX PIPE DIAMETERS IN THE SAME LENGTH OF PIPE OUTSIDE THE FURNACE CABINET (Except adapters at the top of the furnace). If different
inlet and vent pipe sizes are used, the vent pipe must adhere to the maximum length limit shown in the table above (See note 6 below for exception). The inlet pipe
can be of a larger diameter, but never smaller than the vent pipe.
4. MAXIMUM PIPE LENGTHS MUST NOT BE EXCEEDED! THE LENGTH SHOWN IS NOT A COMBINED TOTAL, IT IS THE MAXIMUM LENGTH OF EACH (Vent
or Inlet air pipes).
5. One SHORT radius 90° elbow is equivalent to 10' of 4" pipe, 10' of 3" pipe, or 8’ of 2” pipe. One LONG radius elbow is equivalent to 6' of 4" pipe, 7’ of 3” pipe, 6’
of 2.5” pipe, or 5' of 2" pipe. Two 45° elbows equal one 90° LONG elbow.
6. The termination tee or bend must be included in the total number of elbows. If the BAYAIR30AVENTA termination kit is used, the equivalent length of pipe is 5
feet. BAYVENT200B equivalent length is 0 feet.
7. Pipe adapters are field supplied (except for the *UH/DH2D120 models).
8. For Canadian applications, venting systems must meet ULC-S636 requirements.
18-CD29D1-11 17
MODEL
UPFLOW/ HORIZONTAL VENTING TABLE
DIRECT VENT (2 PIPE SYSTEM) -
MAXIMUM TOTAL EQUIVALENT FEET FOR
VENT AND INLET AIR PIPES (See Notes)
2" PIPE
& FITTINGS
2-1/2" PIPE
& FITTINGS
3" PIPE
& FITTINGS
TABLE 11
4" PIPE
& FITTINGS
NONDIRECT VENT (1 PIPE SYSTEM) -MAXIMUM TOTAL
2" PIPE
& FITTINGS
EQUIVALENT FEET FOR
VENT PIPE ONLY (See Notes)
2-1/2" PIPE
& FITTINGS
3" PIPE
& FITTINGS
4" PIPE
& FITTINGS
Page 18
Installer’s Guide
Vent only
to outside
Air Inlet
B
A
A (0-2') or greater
B (0-2') or greater
A+B = 2' minimum
UPFLOW FURNACE
V
D
EE
V
G
INSIDE
CORNER DETAIL
B
L
V
V
FIXED
CLOSED
OPERABLE
F
B
C
V
FIXED
CLOSED
V
V
V
B
B
B
A
X
J
B
H
I
V
X
K
M
V
VENT TERMINAL
X
AIR SUPPLY INLET
AREA WHERE TERMINAL IS NOT PERMITTED
OPERABLE
Vent only
to outside
Air Inlet
A
A = 2' minimum
DOWNFLOW
FURNACE
DOWNFLOW/ HORIZONTAL VENTING TABLE
TABLE 12
MAXIMUM VENT LENGTH:
DIRECT VENT (2 PIPE SYSTEM) - MAXIMUM TOTAL EQUIV-
ALENT FEET FOR VENT AND INLET AIR PIPES (SEE NOTES)
MODEL
2" PIPE
& FITTINGS
2-1/2" PIPE
& FITTINGS
3" PIPE
& FITTINGS
4" PIPE
& FITTINGS
*DH1B040A9241A6080100130508080130
*DH1B065A9421A4580100130408080130
*DH1C085A9481A NOT ALLOWED80100130NOT ALLOWED8080130
*DH1D110A9601A NOT ALLOWED1560130NOT ALLOWED2570130
NOTES: * - First letter may be "A" or "T"
1. FOR DURAVENT MANUFACTURED MODULAR VENTING SYSTEMS THAT ARE APPROVED IN TABLE 10, EQUIVALENT VENT LENGTHS MAY BE DIFFER-
ENT FROM WHAT IS SHOWN ABOVE. REFER TO THE VENTING SYSTEM MANUFACTURER'S INSTALLATION INSTRUCTIONS FOR APPROPRIATE VENTING
DIAMETERS AND EQUIVALENT LENGTHS.
2. Minimum vent length for all models: 3' horizontal or 3' vertical.
3. DO NOT MIX PIPE DIAMETERS IN THE SAME LENGTH OF PIPE OUTSIDE THE FURNACE CABINET (Except adapters at the top of the furnace). If different inlet
and vent pipe sizes are used, the vent pipe must adhere to the maximum length limit shown in the table above (See note 6 below for exception). The inlet pipe can be of
a larger diameter, but never smaller than the vent pipe.
4. MAXIMUM PIPE LENGTHS MUST NOT BE EXCEEDED! THE LENGTH SHOWN IS NOT A COMBINED TOTAL, IT IS THE MAXIMUM LENGTH OF EACH (Vent or
Inlet air pipes).
5. One SHORT radius 90° elbow is equivalent to 10' of 4" pipe, 10' of 3" pipe, or 8’ of 2” pipe. One LONG radius elbow is equivalent to 6' of 4" pipe, 7’ of 3” pipe, 6’ of
2.5” pipe, or 5' of 2" pipe. Two 45° elbows equal one 90° LONG elbow.
6. The termination tee or bend must be included in the total number of elbows. If the BAYAIR30AVENTA termination kit is used, the equivalent length of pipe is 5 feet.
BAYVENT200B equivalent length is 0 feet.
7. Pipe adapters are field supplied (except for the *UH/DH2D120 models).
8. For Canadian applications, venting systems must meet ULC-S636 requirements.
NONDIRECT VENT (1 PIPE SYSTEM) - MAXIMUM TOTAL
EQUIVALENT FEET FOR VENT PIPE ONLY (SEE NOTES)
2" PIPE
& FITTINGS
2-1/2" PIPE
& FITTINGS
3" PIPE
& FITTINGS
4" PIPE
& FITTINGS
g
VENT CLEARANCES
See Tables 13 & 14
SINGLE PIPE VENTING
h
18 18-CD29D1-11
Page 19
Installer’s Guide
Table 13 - See Figure 22
Direct Vent Terminal Clearances
A=Clearance above grade, veranda, porch, deck,
B=Clearance to window or door that may be
C=Clearance to permanently closed window**
D=Vertical clearance to ventilated soffit located
E=Clearance to unventilated soffit**
F=Clearance to outside corner**
G=Clearance to inside corner**
H=Clearance to each side of center line extended
I=Clearance to service regulator vent outlet3 feet (91 cm)*
J=Clearance to nonmechanical air supply inlet
K=Clearance to a mechanical air supply inlet6 feet (1.83m)3 feet (91 cm) above if within 10 feet (3m) horizontally
L=Clearance above a paved sidewalk or paved
M=Clearance under veranda, porch, deck, or
Table 14 - See Figure 22
A=Clearance above grade, veranda, porch, deck, or
B=Clearance to window or door that may be opened6 inches (15 cm) for appliances =/< 10,000 Btuh (3 kw), 12
C=Clearance to permanently closed window**
D=Vertical clearance to ventilated soffit located above
E=Clearance to unventilated soffit**
F=Clearance to outside corner**
G=Clearance to inside corner**
H=Clearance to each side of center line extended
I=Clearance to service regulator vent outlet3 feet (91 cm)*
J=Clearance to nonmechanical air supply inlet to
K=Clearance to a mechanical air supply inlet6 feet (1.83m)3 feet (91 cm) above if within 10 feet (3m)
L=Clearance above a paved sidewalk or paved drive-
M=Clearance under veranda, porch, deck, or balcony`12 inches (30 cm) ‡*
Notes:
1. In accordance with the current CSA B149.1 Natural Gas and Propane Installation Code.
2. In accordance with the current ANSI Z223.1/NFPA 54 National Fuel Gas Code.
†. A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwelling and serves both dwellings.
‡. Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.
* Clearance in accordance with local installation codes and the requirements of the gas supplier and the manufacturer's Installation Instructions.
or balcony
opened
above the terminal within a horizontal distance
of 2 feet (61 cm) from the center line of the
terminal
above meter/regulator assembly
to building or the combustion air inlet to any
other appliance
driveway located on public property
balcony
Notes:
1. In accordance with the current CSA B149.1 Natural Gas and Propane Installation Code.
2. In accordance with the current ANSI Z223.1/NFPA 54 National Fuel Gas Code.
†. A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwelling and serves both dwellings.
‡. Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.
* Clearance in accordance with local installation codes and the requirements of the gas supplier and the manufacturer's Installation Instructions.
balcony
the terminal within a horizontal distance of 2 feet
(61 cm) from the center line of the terminal
above meter/regulator assembly
building or the combustion air inlet to any other
appliance
way located on public property
6 inches (15 cm) for appliances =/< 10,000
Btuh (3 kw), 12 inches (30 cm) for appliances
> 10,000 Btuh (3 kw) and =/< 100,000 Btuh
(30 kw), 36 inches (91 cm) for appliances >
100,000 Btuh (30 kw)
3 feet (91 cm) with a height 15 feet (4.5 m)
6 inches (15 cm) for appliances =/< 10,000
Btuh (3 kw), 12 inches (30 cm) for appliances
> 10,000 Btuh (3 kw) and =/< 100,000 Btuh
(30 kw), 36 inches (91 cm) for appliances >
100,000 Btuh (30 kw)
inches (30 cm) for appliances > 10,000 Btuh (3 kw) and =/<
100,000 Btuh (30 kw), 36 inches (91 cm) for appliances >
100,000 Btuh (30 kw)
6 inches (15 cm) for appliances =/< 10,000 Btuh (3 kw), 12
inches (30 cm) for appliances > 10,000 Btuh (3 kw) and =/<
100,000 Btuh (30 kw), 36 inches (91 cm) for appliances >
100,000 Btuh (30 kw)
18-CD29D1-11 19
Canadian InstallationsUS Installations
12 inches (30 cm)12 inches (30 cm)
6 inches (15 cm) for appliances =/< 10,000 Btuh (3 kw),
9 inches (23 cm) for appliances > 10,000 Btuh (3 kw)
and =/< 50,000 Btuh (15 kw), 12 inches (30 cm) for appliances > 50,000 Btuh (15 kw)
**
above the meter/regulator assembly
6 inches (15 cm) for appliances =/< 10,000 Btuh (3 kw),
9 inches (23 cm) for appliances > 10,000 Btuh (3 kw)
and =/< 50,000 Btuh (15 kw), 12 inches (30 cm) for appliances > 50,000 Btuh (15 kw)
7 feet (2.13 m) †*
`12 inches (30 cm) ‡*
Non-Direct Vent Terminal Clearances
Canadian InstallationsUS Installations
12 inches (30 cm)12 inches (30 cm)
4 feet (1.2m) below or to the side of opening; 1 foot (0.3m) above opening.
**
3 feet (91 cm) with a height 15 feet (4.5 m) above the
meter/regulator assembly
4 feet (1.2 m) below or to side of opening; 1
foot (300 m) above opening
7 feet (2.13 m) †7 feet (2.13 m)
*
*
horizontally
Page 20
Installer’s Guide
▲
CAUTION
!
6” Min.
24” Max.
12” Min.
15” Max
.
9” Minimum
minimum from end
of exhaust pipe to
end of inlet pipe
6” Min.
24” Max.
6” Min.
24” Max.
VENT
COMBUSTION
AIR
VENT
VENT
PLATE
VENT
CAP
12" MINIMUM
TO OVERHANG
MAINTAIN 12" MINIMUM CLEARANCE
ABOVE HIGHEST ANTICIPATED SNOW LEVEL
OR GRADE WHICHEVER IS GREATER
SCREWS
(4 req.)
ANCHORS
(4 req.)
7.2"
3.2"
▲
WARNING
!
j
6” Min.
24” Max.
12” Min.
15” Max
.
6” Min.
24” Max.
12” Min.
15” Max
.
9” Minimum
minimum from end
of exhaust pipe to
end of inlet pipe
ELBOW AND TEE MUST
BE AS CLOSE TOGETHER
AS POSSIBLE
POSSIBLE CONFIGURATIONS FOR TWO PIPE VENTING SYSTEMS WHEN
BOTH TERMINATIONS ARE LOCATED IN THE SAME PRESSURE ZONE
CARBON MONOXIDE POISONING HAZARD
Do not replace any of the factory supplied venting
components with field fabricated parts. Failure to follow this safety warning exactly could result in damaged vents, damaged components, carbon monoxide
poisoning, or death.
k
9” Minimum
minimum from end
of exhaust pipe to
end of inlet pipe
HORIZONTAL VENTING
NOTE:
Vent termination kit BAYAIR30AVENTA or BAYVENT200B
may be used instead of the horizontal and vertical termination options shown in the following figures.
For Canadian applications, venting systems must meet
ULC-S636 requirements..
When the vent pipe is exposed to temperatures below
freezing, i.e., when it passes through unheated spaces,
etc., the pipe must be insulated with 1/2 inch (22.7 mm)
thick Armaflex-type insulation or equal. If the space is
heated sufficiently to prevent freezing, then the insulation would not be required. If domestic water pipes are
not protected from freezing then it is assumed the space
meets the condition of a heated space.
20 18-CD29D1-11
For Canadian applications, horizontal vent termination kits must meet ULCS636.
DO NOT Install return air through the side of furnace cabinet on horizontal applications.
HORIZONTAL VENTING THROUGH WALL
These furnaces may be installed as direct vent (as
shipped) or as nondirect vent. Installation must conform to national, state, and local codes.
The vent & inlet terminals must be located at least 12"
minimum above normally expected snow accumulation level.
BAYVENT200B
Page 21
Avoid areas where staining or condensate drippage may be
COUPLING
(PLASTIC
VENTING)
STUD
PVC WALL
MOUNT FLANGE
(OPTIONAL)
APPROVED
TERMINATION
1” CLEARANCE
(AIR SPACE)
VENTING THROUGH COMBUSTIBLE WALLS
Pitch - 1/4 Inch Per Foot
CLEARANCE (0” ACCEPTABLE FOR PVC VENT PIPE)
(1” ACCEPTABLE FOR TYPE 29-4C STAINLESS STEEL VENT PIPE)
Location of the vent/ wind terminal should be chosen to
meet the requirements of Figure 26 for either direct or nondirect vent applications.
PITCH – Venting through the wall must maintain 1/4" per
foot pitched upward to insure that condensate drains back
to the furnace.
FLUE GAS DEGRADATION – The moisture content of
the flue gas may have a detrimental effect on some building
materials. This can be avoided by using the roof or chimney
venting option. When wall venting is used on any surface
that can be affected by this moisture, it is recommended
that a corrosion resistant shield (24 inches square) be used
behind the vent terminal. This shield can be wood, plastic,
sheet metal, etc. Also, silicone caulk all cracks, seams and
joints within 3 feet of the vent terminal.
COMBUSTIBLE MATERIAL WALL
A minimum clearance of 1" to combustible materials must
be maintained when using single wall stainless steel venting. See Figure 30.
Installer’s Guide
;
l
12" MIN TO
OVERHANG
1
1" + "
2
COMBUSTION
AIR
BAYAIR30AVENTA
(Sidewall)
For Canadian applications, horizontal vent termination kits must meet
ULC-S636.
Shield material to be a minimum of 24 gauge stainless or
aluminized sheet metal. Minimum dimensions are 12"x12".
Shield must be fastened to both inside and outside of wall.
Use screws or anchor type fasteners suited to the outside or
inside wall surfaces.
NONCOMBUSTIBLE MATERIAL WALL
The hole through the wall must be large enough to maintain pitch of vent and properly seal.
Use cement mortar seal on inside and outside of wall.
See Figure 31.
VENT
MAINTAIN 12 IN.
MINIMUM CLEARANCE
ABOVE HIGHEST
ANTICIPATED SHOW
LEVEL OR GRADE
WHICH EVER IS GREATER
z
x
SUPPORT HORIZONTAL PIPE EVERY
3' 0" WITH THE FIRST SUPPORT AS
CLOSE TO THE FURNACE AS POSSIBLE.
INDUCED DRAFT BLOWER, HOUSING,
AND FURNACE MUST NOT SUPPORT
THE WEIGHT OF THE FLUE PIPE.
18-CD29D1-11 21
Page 22
Installer’s Guide
40" UPFLOW OR
DOWNFLOW MODELS
SEE VENTING TABLE
OUTSIDE
WALL
NOTE: ANY FITTINGS PASSING
THROUGH AN UNHEATED SPACE
MUST BE INSULATED.
FIRST SUPPORT SHOULD BE AS
CLOSE TO FURNACE CONNECTION
AS POSSIBLE.
UPWARD PITCH -- 1/4" PER FOOT
STRAPS OR OTHER SUITABLE SUPPORTS
AT MAXIMUM OF 3'-0" INTERVALS
COMBUSTION
AIR INLET
USE ONLY
APPROVED
TERMINATION
RAIN CAP
COMBUSTION AIR
STRAP
(FIELD SUPPLIED)
COMBUSTION
AIR
VENT
ELBOW
(FIELD
SUPPLIED)
VENT
1" + 1/2"
3" PIPING
2", 2-1/2"
or 3" PIPING
REDUCING
COUPLING,
FIELD SUPPLIED
IF NEEDED
SEAL ALL
WALL CAVITIES
▲
CAUTION
!
c
NOTE: VENT AND INLET MUST BE SUPPORT-
ED AT A MAXIMUM OF 3' INTERVALS
TEE
The vent for this appliance shall not terminate
(1) Over public walkways; or
(2) Near soffit vents or crawl space vents or other
(3) Where condensate vapor could cause damage or
22 18-CD29D1-11
BAYAIR30AVENTA
For Canadian applications, horizontal vent termination kits must meet ULC-S636.
areas where condensate or vapor could create a
nuisance or hazard or cause property damage; or
could be detrimental to the operation of regulators, relief valves. or other equipment.
BAYVENT200B
Page 23
Installer’s Guide
MAINTAIN 12 IN.
(18 IN. FOR CANADA)
MINIMUM CLEARANCE
ABOVE HIGHEST
ANTICIPATED SNOW
LEVEL. MAXIMUM OF
24 IN. ABOVE ROOF.
VENT
COMBUSTION
AIR
REMOVE RIBS
FROM CAP
COMBUSTION
AIR
ROOF FLASHING BOOT
(FIELD SUPPLIED)
COMBUSTION
AIR
VENT
ELBOW
(FIELD SUPPLIED)
MAINTAIN 12 IN.
(18 IN. FOR CANADA)
MINIMUM CLEARANCE
ABOVE HIGHEST
ANTICIPATED SNOW
LEVEL. MAXIMUM OF
24 IN. ABOVE ROOF
SUPPORT
(FIELD SUPPLIED)
VENT
6" Min.
40 Inch
Upflow or
Downflow
Furnace
Slope 1/4" per ft.
Slope 1/4" per ft.
12 INCHES MIN. CLEARANCE MUST BE
MAINTAINED ABOVE HIGHEST
ANTICIPATED SNOW LEVEL.
MAXIMUM NOT TO EXCEED
24 INCHES ABOVE ROOF.
DOWNWARD VENTING
Furnace may be in vertical or horizontal configuration.
DOWNWARD VENT
LENGTH IS LIMITED
TO A MAXIMUM OF 15
EQUIVALENT FEET.
All horizontal pipes must be supported
at a maximum of 3 foot intervals
v
NOTES:
A) Condensate trap for vent pipe must be a minimum
of 6 inches in height.
B) Condensate trap for vent and inlet pipe must be
connected into a condensate drain pump; an open
or vented drain; or it can be connected to the outlet hose of the furnace's condensate trap. Outdoor
draining of the furnace and coil condensate is permissible if allowed by local codes. Caution should
be taken to prevent drains from freezing or causing
slippery conditions that could lead to personal injury. Excessive draining of condensate may cause
saturated ground conditions that may result in
damage to plants.
C) The condensate trap should be primed at initial
start up prior to heating season operation.
VENTING THROUGH THE ROOF
When penetrating roof with a 2" PVC vent pipe, a 2" electrical conduit flashing may be used for a weather tight
seal. Lubricate flexible seal on flashing before PVC pipe is
pushed through the seal. (Field Supplied)
All pipe joints must be fastened and sealed to prevent escape of combustion products into the building.
NOTE:
Both venting methods shown in Figure 39 & 41 must also
have the combustion air inlet installed - meeting dimension requirements of Figure 35.
b
n
For Canadian applications,
vertical vent termination kits
BAYAIR30AVENTA
must meet ULC-S636.
m
NOTE:
No vent cap as shown in Figure 35 is the preferred method for vertical vent termination in extremely cold climates.
In extreme climate conditions, insulate the exposed pipe
above the roof line with Armaflex type insulation.
VENTING ROUTED THROUGH A MASONRY CHIMNEY
VENT FITTING MATERIAL – STAINLESS STEEL
Gas and liquid tight single wall metal vent fitting, designed
for resistance to corrosive flue condensate such as Type 294C MUST be used throughout.
These fittings and fitting accessories are to be supplied locally.
DIRECTION OF STAINLESS STEEL FITTING
All stainless steel fitting must be installed with male end
towards the furnace.
All horizontal stainless steel sections must be positioned
with the seam on top.
All long horizontal sections must be supported to prevent
sagging.
18-CD29D1-11 23
For Canadian applications, vertical vent
termination kits must meet ULC-S636.
Page 24
Installer’s Guide
GALVANIZED FIRESTOP SHOULD
BE FABRICATED WITH 3-7/8" DIA.
HOLE FOR SUPPORT FLANGE
(12" x 12" PANEL OR 12" DIA MIN.)
VENTING THROUGH CEILING
CEILING
SUPPORT
FLANGE
FLUE PIPE
COUPLING
SEAL BETWEEN FLANGE, PIPE,
COUPLING AND METAL PANEL
WITH HI TEMP RTV SILICONE SEALANT
CLEARANCE ( 0" ACCEPTABLE FOR PVC VENT PIPE )
( 1" ACCEPTABLE FOR TYPE 29-4C STAINLESS STEEL VENT PIPE )
STAINLESS STEEL
▲
CAUTION
!
▲
CAUTION
!
,
TYPE 29-4C STAINLESS STEEL VENTING -
.
USED THROUGH CHIMNEY THAT VENTS
ANOTHER GAS APPLIANCE
VENT CAP (OPTIONAL)
SEE CAUTION
6 IN. MIN.
SUPPORT THE SINGLE WALL
STAINLESS STEEL GAS
VENTING AND CENTER IT IN
THE CHIMNEY OPENING WITH
ANGLES AS SHOWN OR
ANOTHER EQUIVALENT
MANNER.
/
PVC PLASTIC VENTING - ONLY
!
COUPLING TO SUPPORT
PIPE FROM ANGLES
OR OTHER SUITABLE
SUPPORT METHOD
THROUGH UNUSED CHIMNEY
STAINLESS STEEL
VENT CAP (OPTIONAL)
SEE CAUTION
FLUE PIPE
6 IN. MIN.
SUPPORT THE SINGLE
WALL FLUE PIPE AND
CENTER IT IN THE
CHIMNEY OPENING WITH
ANGLES AS SHOWN OR
ANOTHER EQUIVALENT
MANNER.
COUPLING
AS REQUIRED
NOTE:
HORIZONTAL VENTING
TO VERTICAL VENTING
Do NOT run vent through chimney for wood burning or oil furnaces or incinerators.
If remaining free area between single wall flue pipe
and masonry chimney is to be used for another gas
appliance venting area must be sufficient to vent
that appliance and that appliance must be connected to chimney with separate entry openings.
IMPORTANT –
The single wall flue pipe joints must be sealed.
The 90° elbow connection to vertical pipe must be
sealed to prevent condensate leakage to base of masonry chimney.
24 18-CD29D1-11
FLUE PIPE
NOTE:
HORIZONTAL VENTING
TO VERTICAL VENTING
Do NOT run vent through chimney for wood burning
or oil furnaces or incinerators or any other gas appliance.
IMPORTANT –
The single wall flue pipe joints must be sealed.
The 90° elbow connection to vertical pipe must be sealed
to prevent condensate leakage to base of masonry
chimney.
Page 25
Installer’s Guide
IMPORTANT:
The Commonwealth of Massachusetts requires compliance
with regulation 248 CMR 4.00 and 5.00 for installation of
through – the – wall vented gas appliances as follows:
For all side wall horizontally vented gas fueled equipment
installed in every dwelling, building or structure used in
whole or in part for residential purposes, including those
owned or operated by the Commonwealth and where the
side wall exhaust vent termination is less than seven
(7) feet above finished grade in the area of the venting,
including but not limited to decks and porches, the
following requirements shall be satisfied:
1. INSTALLATION OF CARBON MONOXIDE
DETECTORS. At the time of installation of the side wall
horizontal vented gas fueled equipment, the installing
plumber or gasfitter shall observe that a hard wired carbon
monoxide detector with an alarm and battery back-up
is installed on the floor level where the gas equipment
is to be installed. In addition, the installing plumber or
gasfitter shall observe that a battery operated or hard
wired carbon monoxide detector with an alarm is installed
on each additional level of the dwelling, building or
structure served by the side wall horizontal vented gas
fueled equipment. It shall be the responsibility of the
property owner to secure the services of qualified licensed
professionals for the installation of hard wired carbon
monoxide detectors
a. In the event that the side wall horizontally vented
gas fueled equipment is installed in a crawl space or an
attic, the hard wired carbon monoxide detector with alarm
and battery back-up may be installed on the next adjacent
floor level.
b. In the event that the requirements of this
subdivision can not be met at the time of completion of
installation, the owner shall have a period of thirty (30)
days to comply with the above requirements; provided,
however, that during said thirty (30) day period, a battery
operated carbon monoxide detector with an alarm shall be
installed.
2. APPROVED CARBON MONOXIDE
DETECTORS. Each carbon monoxide detector as required
in accordance with the above provisions shall comply with
NFPA 720 and be ANSI/UL 2034 listed and IAS certied.
3. SIGNAGE. A metal or plastic identification
plate shall be permanently mounted to the exterior of
the building at a minimum height of eight (8) feet above
grade directly in line with the exhaust vent terminal
for the horizontally vented gas fueled heating appliance
or equipment. The sign shall read, in print size no less
than one-half (1/2) inch in size, “GAS VENT DIRECTLY
BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS”.
4. INSPECTION. The state or local gas inspector
of the side wall horizontally vented gas fueled equipment
shall not approve the installation unless, upon inspection,
the inspector observes carbon monoxide detectors and
signage installed in accordance with the provisions of 248
CMR 5.08(2)(a)1 through 4.
This appliance requires a special venting system. If
BAYAIR30AVENTA or BAYVENT200B are used, a copy
of the installation instructions for the kit shall remain
with the appliance or equipment at the completion of
installation. The venting system installation instructions
can be obtained from the manufacturer by writing to the
following address:
Trane
6200 Troup Highway
Tyler, TX 75707
Attention: Manager of Field Operations Excellence
For Canadian installations, if you used a ULC-S636
approved manufactured modular venting system, a copy
of the manufacturer's instructions should remain with the
system. The installation instruction can be obtained from
the vent termination manufacturer.
18-CD29D1-11 25
Page 26
Installer’s Guide
▲
CAUTION
!
LABEL
SAYS
"TOP"
STRAIGHT SIDE MUST BE
ON BOTTOM FOR PROPER
CONDENSATE DRAINAGE.
WHEN THE FACTORY SUPPLIED "OFF-SET" (2X3
REDUCING COUPLING) IS USED FOR 3" VENT PIPE
INSTALLATION, MAKE SURE THE MARKING "TOP" IS
LOCATED ON THE TOP SIDE OF THE PIPE.
2" TO 3" COUPLING
FURNACE
VENT
OUTLET
FACTORY SUPPLIED ONLY
WITH THE FOLLOWING
MODELS: *UH1C080A9601A,
ALL 100,000 BTUH UPFLOW
MODELS, ALL 120,000 BTUH
UPFLOW MODELS, AND ALL
*DH1 DOWNFLOW MODELS
#CPL00938
HORIZONTAL INSTALLATION
Upflow/ Horizontal
NOTE:
In horizontal venting when the factory supplied “offset” (2X3 reducing coupling) is used for 3” vent pipe
installation, make sure the marking “Top” is located
on the top side of the pipe. The straight side must be
on bottom for proper condensate drainage. This coupling is only factory supplied with all 100,000 BTU upflow models, *UH1C080A9601A, all 120,000 BTU upflow
models, and all downflow models.
It is recommended that a drain pan be installed under the
furnace to prevent property damage or personal injury
from leaking condensate.
Upflow furnace - The connection tubing for left and right
side drainage is shipped in the blower compartment. Install
the connection tubing from the trap to the side of the unit
and trim all excess tubing to avoid kinks.
$
UPFLOW
(VERTICAL)
#
Right side
%
UPFLOW HORIZONTAL 17"
UNITS (Left side only)
Downflow furnace - Use RTV silicon sealant to connect
the fitting to the trap for ease of removal when cleaning the trap.
For left side drain a 1/2" slip PVC tting is needed.
See Figure 48.
To change to a right side drain, remove the drain lines
from the trap, rotate the trap 180° so it exits to the
right, then reconnect the lines. Start with a 1/2" 90°
CPVC street elbow connected to the trap using RTV
silicon sealant. Run 1/2" CPVC pipe to a CPVC elbow.
Run 1/2" CPVC pipe from the elbow out through the
right side knock-out. See Figure 49.
Use Inducer Drain
hose without
extension
26 18-CD29D1-11
Page 27
HORIZONTAL APPLICATIONS
Upflow and Downflow furnaces - All horizontal applications are left side only. It is always recommended that
the auxiliary drain pan be installed under a horizontally
installed evaporator and/or 95% gas furnace. Connect the
auxiliary drain pan to a separate drain line (no trap is
needed in this line).
The trap must be repositioned to the exterior of the cabinet.
Remove the trap from its present location and reposition
the trap outside of the unit, through the long circular hole,
Installer’s Guide
*
^
UPFLOW
(VERTICAL)
Left side
UPFLOW HORIZONTAL 21" & 24" UNITS
(Left side only)
Use exten-
sion hose
here
&
Left
side
DOWNFLOW (VERTICAL)
(
Right
side
Use CPVC tubing from Trap outlet,
over burner box to cabinet exit
DOWNFLOW (VERTICAL)
)
next to the secondary recuperated cell. Remove the larger
drain line (from the secondary cell) and trim to fit between
the secondary cell and the new trap location. On upflow
units, plug the hole in the blower deck where the tube went
through.
Remove the hose from the induced blower and reposition
into the other drain tap of the inducer, which is located 90°
clockwise around the inducer. Move the cap from that drain
tap to the unused drain tap. On upflow units, plug the hole
in the blower deck where the tube went through. On upflow
units, this tube may need to be extended, using the tubing
shipped with the furnace.
Connections must be made to an OPEN or VENTED DRAIN. Outdoor draining of the furnace and coil condensate is permissible if allowed by local codes. Caution should
be taken to prevent drains from freezing or causing slippery conditions that could lead to personal injury. Excessive
draining of condensate may cause saturated ground conditions that may result in damage to plants.
18-CD29D1-11 27
DOWNFLOW (HORIZONTAL)
Cut off curved end of
Inducer drain hose
Page 28
Installer’s Guide
SEE
NOTE 6
From drawing B341437 Rv 1
FURNACE
TWIN
SEE
NOTE 7
B/C
B/C
TO 115 V 1 PH.,
60 HZ., POWER
SUPPLY PER
LOCAL CODES
HUM SEE
NOTE 5
EAC SEE
NOTE 5
FIELD WIRING DIAGRAM FOR 1 STAGE FURNACE
1 STAGE HEATING
USING A 1 STAGE HEATING THERMOSTAT
NO COOLING
NOTE:
Use 1/2" or larger PVC or CPVC pipe and fittings as required for drain connections (fittings, pipe and solvent cement not provided).
NOTE:
A corrosion resistant condensate pump must be used if a
pump is required for a specific drain system.
IMPORTANT:
The condensate drain should be installed with provisions
to prevent winter freeze-up of the condensate drain line.
Frozen condensate will block drains, resulting in fur nace
shutdown. If the drain line cannot be installed in a conditioned space, then UL listed heat tape should be applied
as required to prevent freezing (per manufacturer’s instructions). The heat tape should be rated at 5 or 6 watts
per foot at 120 volts. Self-regulating (preferred) or thermostatically controlled heat tape is required.
Evaporator and furnace condensate drain piping may be
manifolded together as shown in Figure 51. A primary
drain vent stack must be installed and terminated below
the outlet of the secondary heat exchanger drain connection
to prevent water from damaging furnace controls if the primary drain outlet plugs up. Where the furnace is installed
above a finished ceiling, the primary drain vent stack must
be installed such that overflow from the vent stack opening
will flow into an auxiliary drain pan in order to prevent water damage to the finished ceiling below.
TWINNING FURNACES
These furnaces may be twinned. Twinning requires that
two furnaces with the same configuration, capacity, and airflow must be used. They shall have common returns with
equal pressure drops or ducts with equivalent lengths and
sizes. See Field Wiring Diagrams for proper hookup.
Q
If upflow furnace is
installed over a finished
ceiling, overflow from
the primary drain vent
stack must flow into an
auxillary drain pan to
prevent damage to the
finished ceiling below.
TO 115 V 1 PH.,
60 HZ., POWER
SUPPLY PER
LOCAL CODES
HUM SEE
NOTE 5
EAC SEE
NOTE 5
FIELD WIRING DIAGRAM FOR 1 STAGE FURNACE
1 STAGE HEATING, 1 STAGE COOLING
USING A 1 STAGE HEATING, 1 STAGE COOLING THERMOSTAT
(OUTDOOR SECTION WITHOUT TRANSFORMER)
ELECTRICAL CONNECTIONS
Make wiring connections to the unit as indicated on
enclosed wiring diagram. As with all gas appliances
using electrical power, this furnace shall be connected
into a permanently live electric circuit. It is recommended that furnace be provided with a separate “circuit protection device” in the electric circuit. The furnace must be electrically grounded in accordance with
local codes or in the absence of local codes with the
National Electrical Code, ANSI/NFPA 70 or CSA C22.1
Electrical Code, if an external electrical source is utilized.
The integrated furnace control is polarity sensitive. The hot leg of the 120V power supply must be
connected to the black power lead as indicated on the
wiring diagram. Provision for hooking up an electronic
air cleaner and or humidifier is provided on the integrated control.
Refer to the SERVICE FACTS literature and unit wiring diagram attached to furnace diagram attached to
furnace.
18-CD29D1-11 29
Page 30
Installer’s Guide
TWIN
TWIN
R1
R1
TWINNING CONNECTION DIAGRAM
FOR TWINNING 1 STAGE FURNACES WITH
SINGLE WIRE TWINNING FEATURE
1 STAGE HEATING ONLY THERMOSTAT
1 STAGE HEAT
ONLY
THERMOSTAT
(WITH FAN SWITCH)FURNACE NO. 1
FURNACE NO. 2
BLOWER OPERATION OF
UNIT NO. 2 IS SYNCRONIZED
WITH UNIT NO. 1 VIA SIGNALS
FROM TWIN CONNECTION.
SEE NOTE 4
SEE NOTE 3
ISOLATION RELAY
(FIELD SUPPLIED)
SEE NOTE 4
ISOLATION RELAY
SEE NOTE 4
B/C
B/C
B/C
From Dwg. 21B341422 Rev. 3
TWIN
TWIN
R1
R1
TWINNING CONNECTION DIAGRAM
FOR TWINNING 1 STAGE FURNAC ES WITH
SINGLE WIRE TWINNING FEATURE
1 STAGE HEAT / 1 STAGE COOL THERMOSTAT
1 STAGE
HEATING / COOLING
THERMOSTATFURNACE NO. 1
FURNACE NO. 2
BLOWER OPERATION OF
UNIT NO. 2 IS SYNCRONIZED
WITH UNIT NO. 1 VIA SIGNALS
FROM TWIN CONNECTION.
SEE NOTE 4
SEE NOTE 5
ISOLATION RELAY
(FIELD SUPPLIED)
SEE NOTE 4
ISOLATION RELAY
SEE NOTE 4
OUTDOOR UNIT
(NO TRANSFORMER)
OUTDOOR UNIT
(WITH TRANSFORMER)
RC
ISOLATION RELAY
(FIELD SUPPLIED)
SEE NOTE 3
B/C
B/C
B/C
From Dwg. 21B341423 Rev. 2
30 18-CD29D1-11
Page 31
Installer’s Guide
▲
CAUTION
!
GAS PIPING
The upow/ horizontal furnace is shipped standard for left
side installation of gas piping. A knock-out is provided on
the right side for an alternate gas piping arrangement. See
Figure 52.
The installation of piping shall be in accordance with piping codes and the regulations of the local gas company. Pipe
joint compound must be resistant to the chemical reaction
with liquefied petroleum gases.
Refer to piping Table 15, for delivery sizes. Connect gas
supply to the unit, using a ground joint union and a manual
shut-off valve as shown in Figures 52-53.
National codes require a condensation drip leg to be installed ahead of the controls as shown in Figures 52-53.
The furnace and its individual shut-off valve must be disconnected from the gas supply piping system during any
pressure testing of that system at test pressures in excess
of 1/2 psig (3.5 kPa).
The furnace must be isolated from the gas supply piping
by closing its individual manual shut-off valve during any
pressure testing of the gas supply piping system at test
pressures equal to or less than 1/2 psig (3.5 kPa).
W
MAIN MANUAL
SHUTOFF VALVE
GROUND
UNION
JOINT
AUTOMATIC GAS VALVE
WITH MANUAL SHUTOFF
NOTE:
Maximum pressure to the gas valve for natural gas is
13.8" W.C. Minimum pressure is 5.0" W.C. Maximum
pressure to the gas valve for propane is 13.8" W.C.
Minimum pressure is 11.0" W.C.
All gas fittings must be checked for leaks using a soapy
solution before lighting the furnace. DO NOT CHECK WITH
AN OPEN FLAME!
Use a backup wrench on the gas valve when installing gas
piping to prevent damage to the gas valve and manifold
assembly.
AUTOMATIC GAS VALVE
WITH MANUAL SHUTOFF
MAIN MANUAL
SHUTOFF VALVE
GROUND
UNION
JOINT
DRIP
LEG
E
DRIP
LEG
UPFLOW – LEFT HAND GAS PIPING
UPFLOW – RIGHT HAND GAS PIPING
THE DOWNFLOW (VERTICAL) MAY BE INSTALLED LEFT OR RIGHT SIDE GAS PIPING
18-CD29D1-11 31
Page 32
Installer’s Guide
R
AUTOMATIC GAS VALVE WITH
MANUAL SHUTOFF
MAIN MANUAL
SHUTOFF VALVE
GROUND
UNION JOINT
DRIP
LEG
HORIZONTAL FURNACE GAS PIPING MAY BE FROM EITHER SIDE (UPFLOW SHOWN)
TABLE 15
NATURAL GAS ONLY
TABLE OF CUBIC FEET PER HOUR OF GAS
FOR VARIOUS PIPE SIZES AND LENGTHS
PIPE
SIZE
1/2132927363565046
3/427819015213011510596
1520350285245215195180
1-1/41050730590520440400370
This table is based on pressure drop of 0.3 inch W.C. and 0.6 SP.GR. gas
4. Read the “Flow” column opposite the number of seconds clocked.
5. Use the following factors if necessary:
For 1 Cu. Ft. Dial Gas Flow CFH =
Chart Flow Reading ÷2
For 1/2 Cu Ft. Dial Gas Flow CFH =
Chart Flow Reading ÷4
For 5 Cu. Ft. Dial Gas Flow CFH =
10X Chart Flow Reading ÷4
6. Multiply the final figure by the heating value of the
gas obtained from the utility company and compare
to the nameplate rating. This must not exceed the
nameplate rating.
Gas Valve Adjustment
Changes can be made by adjusting the manifold pressure
(See Table 17, or changing orifices (orifice change
may not always be required). To adjust the manifold
pressure:
1. Turn off all electrical power to the system.
2. Attach a manifold pressure gauge with flexible tub-
ing to the outlet pressure boss marked “OUT P” on
White-Rodgers gas valve model 36G or 36J. See Figure 58 for White-Rodgers gas valve model 36J. See
Figure 57 for White-Rodgers gas valve model 36G.
3. Loosen (Do Not remove) the pressure tap test set
screw one turn with 3/32" hex wrench.
a. The pressure tap adjustment kit (KIT07611) con-
tains a 3/32" hex wrench, a 5/16" hose and a con-
nector and can be ordered through Global Parts.
4. Turn on system power and energize valve.
COMBUSTION AND INPUT CHECK
1. Make sure all gas appliances are off except the furnace.
2. Clock the gas meter with the furnace operating (determine the dial rating of the meter) for one revolution.
3. Match the “Sec” column in the gas flow (in cfh) Table 18
with the time clocked.
32 18-CD29D1-11
Page 33
Installer’s Guide
▲
CAUTION
!
▲
WARNING
!
5. Adjust gas heat by removing the adjustment regulator
cover screw.
a. To increase outlet pressure, turn the regulator ad-
just screw clockwise.
b. To decrease outlet pressure, turn the regulator ad-
just screw counterclockwise.
c. Adjust regulator until pressure shown on mano-
meter matches the pressure specified in Table 17.
1. The input of no more than nameplate rating and
no less than 93% of the nameplate rating, unless the
unit is derated for high altitude.
d. Replace and tighten the regulator cover screw se-
curely.
6. Cycle the valve several times to verify regulator set-
ting.
a. Repeat steps 5-6 if needed.
7. Turn off all electrical power to the system.
8. Remove the manometer and flexible tubing and tighten
the pressure tap screw.
9. Using a leak detection solution or soap suds, check for
leaks at the pressure outlet boss and pressure tap test
screw.
10. Turn on system power and check operation of the
unit.
SAFETY HAZARD
Replace and/ or tighten all plugs removed or loosened
when adjusting gas pressure. Leak check the fittings before placing the furnace into regular service.
Failure to follow this warning could result in fire, explosion, or property damage.
NOTE:
The manifold pressure must be referenced to the burner
box. The burner box pressure tap equalizes the gas valve
pressure regulator. Manifold pressure is checked by installing a tee (field supplied) in the tubing, between the tee
coming from the burner box tube and the gas valve, in addition to the regular gas valve pressure tap on the outlet
side of the gas valve. See Figure 55.
Replace manifold pressure tap threaded plug and leak
check after checking/ adjusting manifold gas pressure.
Table 19 lists the main burner orifices used with the furnace. If a change of orifices is required to correct the furnace input rating. Refer to Table 20.
TABLE 17
FINAL MANIFOLD PRESSURE SETTINGS
MODELFUELPRESSURE
NATURAL GASLP GAS
*UH1B040A9241A3.5" W.C.11.0" W.C.
*UH1B060A9361A3.5" W.C.11.0" W.C.
*UH1B080A9421B
*UH1C080A9601A
*UH1C100A9481A
*UH1D100A9601A
*UH1D120A9601A3.3" W.C.11.0" W.C.
*DH1B040A9241A3.5" W.C.11.0" W.C.
*DH1B065A9421A3.0" W.C.9.5" W.C.
*DH1C085A9481A3.5" W.C.11.0" W.C.
*DH1D110A9601A4.5" W.C.11.0" W.C.
3.5" W.C.11.0" W.C.
3.5" W.C.11.0" W.C.
T
18-CD29D1-11 33
Page 34
Installer’s Guide
HIGH ALTITUDE DERATE
Input ratings (BTUH) of these furnaces are based on sea
level operation and should not be changed at elevations up
to 2,000 ft.
If the installation is 2,000 ft. or above, the furnace input
rate (BTUH) shall be reduced 4% for each 1,000 ft. above
sea level. The furnace input rate shall be checked by clocking the gas flow rate (CFH) and multiplying by the heating
value obtained from the local utility supplier for the gas being delivered at the installed altitude. Input rate changes
can be made by adjusting the manifold pressure (min 3.0
- max 3.7 in. W.C. - Natural Gas for upflow models and min
3.0 - max 4.5 in. W.C. - Natural Gas for downflow models)
or changing orifices (orifice change may not always be required). If the desired input rate can not be achieved with
a change in manifold pressure, then the orifices must be
changed. LP installations will require an orifice change.
Installation of this furnace at altitudes above 2,000 ft.
(610m) shall be in accordance with the local codes, or in the
absence of local codes, the National Fuel Gas Code, ANSI
Z223.1/ NFPA 54 or National Standard of Canada, Natural Gas and Propane Installation Code, CSA 149.1. Instal-
lation of this furnace at altitudes above 2,000 ft. (610m)
shall be made in accordance with the listed high Altitude
Conversion Kit available with this furnace.
IMPORTANT:
Re-install the propane orifices to the same depth as the
orifices supplied with the equipment.
Y
ROTATE THE FRONT
COVER AS SHOWN
INSERT THE TOP
FLANGE OF THE
FRONT COVER UNDER
THE LIP INSIDE THE
BOX
ALL SIDE FLANGES
MUST BE OUTSIDE
OF THE BOX
ROTATE THE FRONT
COVER INWARD
MAKING SURE THAT
ALL SIDE FLANGES
ARE OUTSIDE OF THE
BOX.
See Table 19 & 20 for help in selecting orifices if orifice
change is required. Furnace input rate and temperature
rise should be checked again after changing orifices to confirm the proper rate for the altitude.
Installations above 4,000 feet may require a pressure
switch change. If required, use the BAYHALT*** Kit (High
Altitude Accessory Kit) listed in PRODUCT DATA.
Figure 56 shows the correct way to reinstall the burner box
cover if adjustment or replacement of the flame sensor, hot
surface igniter, or main burner orifices have required removal of the cover.
TABLE 20
Orifice
Twist
Drill
Size If
Installed
At Sea
Level
42
43
44
45
46
47
48
54
55
56
57
58
From National Fuel Gas Code - Table F-4
ALTITUDE ABOVE SEA LEVEL and Orifice Required
2000 3000 4000 5000 6000 7000 8000 9000 10000
42
43
44
44
45
45
46
47
47
47
48
48
49
49
54
55
55
55
56
56
58
59
59
60
At Other Elevations
43
43
44
45
45
46
47
47
47
48
49
49
49
50
55
55
55
56
57
57
59
60
60
61
44
45
47
48
48
49
50
55
56
57
60
62
44
46
47
48
49
50
50
55
56
58
61
62
45
47
48
49
49
50
51
56
56
59
62
63
46
47
48
49
50
51
51
56
56
59
63
63
47
48
50
50
51
52
52
56
57
60
63
64
Check all gas connections for leaks with a soapy solution
— DO NOT CHECK WITH AN OPEN FLAME. Allow 5
minutes for any gas that might have escaped to dissipate.
LP Gas being heavier than air may require forced ventilation. Flip the switch on the gas valve in the unit to the
“ON” position.
U
White-Rodgers 36G gas valve
I
Inlet Pressure
Boss (opt.)
Outlet Pressure Boss
White-Rodgers 36J gas valve
On/Off Switch
LIGHTING INSTRUCTIONS
SAFETY HAZARD
DO NOT attempt to manually light the burner.
Failure to follow this warning could result in property
damage, personal injury or death.
Regulator
Adjustment
Lighting instructions appear on each unit. Each instal-
CARBON MONOXIDE POISONING HAZARD
Failure to follow the installation instructions for the venting system being placed into operation could result in
carbon monoxide poisoning or death.
START UP AND ADJUSTMENT
PRELIMINARY INSPECTIONS
With gas and electrical power “OFF”
1. Duct connections are properly sealed
2. Filters are in place
3. Venting is properly assembled
lation must be checked out at the time of initial start up
to insure proper operation of all components. Check out
should include putting the unit through one complete cycle
as outlined below.
Turn on the main electrical supply and set the thermostat
above the indicated temperature. The ignitor will automatically heat, then the gas valve is energized to permit
the flow of gas to the burners. After ignition and flame is
established, the flame control module monitors the flame
and supplies power to the gas valve until the thermostat is
satisfied.
4. Blower door is in place
Flip the switch on main gas valve within the unit to the
“OFF” position. Turn the external gas valve to “ON”. Purge
the air from the gas lines. After purging,
18-CD29D1-11 35
Page 36
Installer’s Guide
▲
WARNING
!
▲
WARNING
!
▲
CAUTION
!
To shut off.
For complete shut-down: Flip the switch on the main gas
valve to the “OFF” position, (See Figure 57 & 58). Disconnect the electrical supply to the unit.
If this is done during the cold weather months, provisions
must be taken to prevent freeze-up of all water pipes and
water receptacles.
Failure to follow this warning could result in property
damage.
Whenever your house is to be vacant, arrange to
have someone inspect your house for proper temperature. This is very important during freezing weather. If for any reason your furnace should fail to operate damage could result, such as frozen water pipes.
SEQUENCE OF OPERATION
Thermostat call for heat
R and W thermostat contacts close signaling the control
module to run its self-check routine. After the control module has verified that the pressure switch contacts are open
and the limit switch(es) contacts are closed, the draft blower will be energized.
As the induced draft blower comes up to speed, the pressure
switch contacts will close and the ignitor warm up period
will begin. The ignitor will heat for approximately 20 seconds, then the gas valve is energized to permit gas flow to
the burners. The flame sensor confirms that ignition has
been achieved.
After the flame sensor confirms within a 4 second trial period that ignition has been achieved, the delay to fan ON
period begins timing. After approximately 45 seconds the
indoor blower motor will be energized and continue to run
during the heating cycle (downflow models have a 10 second
blower ON delay).
When the thermostat is satisfied, R and W thermostat contacts open, the gas valve will close, the flames will extinguish, and the induced draft blower will be de-energized.
The indoor blower motor will continue to run for the fan
off period (Field selectable at 60, 100, 140 or 180 seconds),
then be de-energized by the control module.
CONTROL AND SAFETY SWITCH ADJUSTMENTS
LIMIT SWITCH CHECK OUT
The limit switch is a safety device designed to close the gas
valve should the furnace become overheated. Since proper
operation of this switch is important to the safety of the
unit, it must be checked out on initial start up by the installer.
To check for proper operation of the limit switches, set the
thermostat to a temperature higher than the indicated temperature to bring on the gas valve. Restrict the airflow by
blocking the return air (disconnecting the indoor blower
may trip the inducer limit).
When the furnace reaches the maximum outlet temperature as shown on the rating plate, the burners must shut
off. If they do not shut off after a reason able time and overheating is evident, a faulty limit switch is probable and the
limit switch must be replaced. After checking the operation
of the limit control, be sure to remove the paper or cardboard from the return air inlet. Refer to Service Facts for
additional instructions.
NOTE TO INSTALLER
Review the following warnings with the owner. Review contents of USER’S INFORMATION MANUAL with the owner.
AIRFLOW ADJUSTMENT
Check inlet and outlet air temperatures to make sure they
are within the ranges specified on the furnace rating nameplate. If the airflow needs to be increased or decreased, see
the wiring diagram for information on changing the speed
of the blower motor.
ELECTRICAL SHOCK HAZARD
Disconnect power to the unit before removing the blower
door.
Failure to follow this warning could result in property
damage, personal injury or death.
This unit is equipped with a blower door switch which cuts
power to the blower and gas valve causing shutdown when
the door is removed. Operation with the door removed or
ajar can permit the escape of dangerous fumes. All panels
must be securely closed at all times for safe operation of the
furnace.
INDOOR BLOWER TIMING
Heating: The integrated furnace control module controls
the indoor blower. The blower start is fixed at 45 seconds
after ignition (10 seconds for downflow models). The FANOFF period is field selectable by dip switches at 60, 100,
140, or 180 seconds. The factory setting is 100 seconds (See
wiring diagram).
Cooling: The fan delay off period is factory set at 0 seconds. The option for 80 second delay off is field selectable
(See wiring diagram).
ROOM AIR THERMOSTAT
HEAT ANTICIPATOR ADJUSTMENT
Set the thermostat heat anticipator according to the current flow measured, or the settings found in the notes on
the furnace wiring diagram (found in the SERVICE FACTS
or inside the furnace casing).
INSTRUCTIONS TO THE OWNERS
EXPLOSION HAZARD
In the event that electrical, fuel, or mechanical failures occur, shut off the gas supply off at the manual
gas valve, located on the supply gas piping coming
into the furnace, before turning off the electrical
power to the furnace. Contact the service agency
designated by your dealer.
BURNER BOX TEMPERATURE LIMIT DEVICE
All models are equipped with a manual reset temperature
limit located on the burner box. In case of excessive temperature, the limit will open and cause the circuit to open
which shuts off all flow of gas.
36 18-CD29D1-11
Page 37
Installer’s Guide
ABNORMAL CONDITIONS
1. EXCESSIVE COMBUSTION PRESSURE (WIND IN
EXCESS OF 40 M.P.H.) VENT OR FLUE BLOCKAGE
If pressure against induced draft blower outlet becomes
excessive, the pressure switch will open and shut off
the gas valve until acceptable combustion pressure is
again available.
2. LOSS OF FLAME
If loss of flame occurs during a heating cycle, or flame
is not present at the sensor, the flame control module
will close the gas valve. The flame control module will
then recycle the ignition sequence, then if ignition is
not achieved, it will shut off the gas valve and lock out
the system.
3. POWER FAILURE
If there is a power failure during a heating cycle, the
system will restart the ignition sequence automatically
when power is restored if the thermostat still calls for
heat.
4. GAS SUPPLY FAILURE
If loss of flame occurs during a heating cycle, the sys-
tem integrated control module will recycle the ignition
sequence, then if ignition is not achieved, the integrated control module will shut off the gas valve and lock
out the system.
5. INDUCED DRAFT BLOWER FAILURE
If pressure is not sensed by the pressure switch, the
contacts will remain open and not allow the gas valve
to open, therefore the unit will not start. If failure occurs during a running cycle, the pressure switch contacts will open and the gas valve will close to shut the
unit down.
6. CONDENSATE DRAIN BLOCKAGE
If the condensate drain is blocked, either by debris, im-
proper draining, or by freezing condensate, the pressure switch will receive a signal warning of the accumulation of condensate in the heat exchanger assembly. The pressure switch contacts will open and remain
open, not allowing unit operation. The unit will not operate until the condensate drain has been cleared, and
the condensate flows freely.
7. RESET AFTER LOCKOUT
When the integrated control module has shut the sys-
tem down and gone into lockout, the system must be
manually reset before the unit will restart. To reset,
turn the system power off, then on, then off and then
on again within 30 seconds. This may be done at the
unit’s power source or at the thermostat. The system
will not reset unless the procedure off-on-off-on is completed within 30 seconds.
8. RESET AFTER BURNER BOX LIMIT SHUTDOWN
If the furnace shuts down, one thing that can be
checked is the burner box temperature limit switch.
It is located on the bottom of the burner box. The
vent and combustion air inlet terminations should be
checked for blockage. If blockage exists, clear the problem and then the reset button may be depressed. If
there is no blockage of the terminations, the limit
switch must be reset by a qualified servicer.
Carbon monoxide, fire or smoke can cause serious bodily in-
jury, death, and/or property damage.
A variety of potential sources of carbon monoxide can be
found in a building or dwelling such as gas-fired clothes
dryers, gas cooking stoves, water heaters, furnaces and
fireplaces. The U.S. Consumer Product Safety Commission recommends that users of gas-burning appliances install carbon monoxide detectors as well as fire and smoke
detectors per the manufacturers installation instructions to
help alert dwelling occupants of the presence of fire, smoke
or unsafe levels of carbon monoxide. These devises should
be listed by Underwriters Laboratories, Inc. Standards for
Single and Multiple Station Carbon Monoxide Alarms, UL
2034 or CSA International Standard, Residential Carbon
Monoxide Alarming Devices, CSA 6.19
NOTE:
The manufacturer of your furnace does not test any detectors and makes no representations regarding any brand or
type of detector.
18-CD29D1-11 37
Page 38
Installer’s Guide
38 18-CD29D1-11
Page 39
TABLE 21
INTEGRATED FURNACE CONTROL ERROR FLASH CODES
Flashing Slow ---Normal - No call for Heat
Flashing Fast ---Normal - Call for Heat
Continuous ON ---Replace IFC
Continuous OFF ---Check Power
2 Flashes ---System Lockout (Retries or Recycles exceeded)
Draft Pressure Error - Possible problems
3 Flashes ---
4 Flashes ---Open High Limit Device
5 Flashes ---Flame sensed when no flame should be present
6 Flashes ---115 Volt AC power reversed or Poor Grounding
a) Venting problem
b) Pressure switch problem
c) Inducer problem
Installer’s Guide
7 Flashes ---Gas valve circuit error
8 Flashes ---Low flame sense signal
Check Ignitor circuit and Line "N" to 24VAC "Com-
9 Flashes ---
mon" voltage (< 2volts)
(possible grounding problem)
18-CD29D1-11 39
Page 40
Trane
6200 Troup Highway
Tyler, TX 75707
Literature Order Number 18-CD29D1-11
File Number 18-CD29D1-11
Supersedes 18-CD29D1-10
Date 03/14
For more information contact
your local dealer (distributor)
The manufacturer has a policy of continuous product and product data improvement and reserves the right to
change design and specifications without notice.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.