Through the years, Trane has designed
and developed the most complete line of
Packaged Rooftop products available in
the market today. Trane was the first to
introduce the Micro—microelectronic unit
controls—and has continued to improve
and revolutionalize this design concept.
The ReliaTel control platform offers the
same great features and functionality as
the original Micro, with additional benefits
for greater application flexibility.
Voyager continues to provide the highest
standards in quality and reliability,
comfort, ease of service, and the
performance of Trane light commercial
products.
Trane customers demand products that
provide exceptional reliability, meet
stringent performance requirements, and
are competitively priced. Trane delivers
with Voyager.
Voyager features cutting edge
technologies: reliable compressors, Trane
engineered ReliaTel controls, computeraided run testing, and Integrated
Comfort™ Systems. So, whether you’re
the contractor, the engineer, or the owner
you can be certain Voyager Products are
built to meet your needs.
• Through the Base Electrical with Circuit
Breaker
• Through the Base Electrical With
Disconnect Switch
• Through the Base Utilities Access
• Two-Inch Pleated Filters
Factory or Field Installed Options
• Clogged Filter/Fan Failure Switch
• Differential Pressure Switches
• Discharge Air Sensing Kit
• Downflow – Economizer
• Electric Heaters
• Frostat
• LonTalk® Communications Interface
• Oversized Motors
• Reference or Comparative Enthalpy
• Tool-less Hail Guards
• Trane Communications Interface (TCI)
Field Installed Options
• CO
Sensing
2
• Digital Display Zone Sensor
• Dual Thermistor Remote Zone Sensor
• Low Static Drive
• High Static Drive
• Manual Outside Air Damper
• Motorized Outside Air Dampers
• Powered Exhaust
• Downflow – Roof Curb
• Horizontal – Economizer
• Remote Potentiometer
• Ventilation Override Accessory
• Zone Sensors
4
RT-PRC002-EN
Features and
Benefits
Easy to Install, Service and
Maintain
Because today’s owners are very costconscious when it comes to service and
maintenance, the Trane Voyager was
designed with direct input from service
contractors. This valuable information
helped to design a product that would get
the serviceman off the job quicker and
save the owner money. Voyager does
this by offering:
Quality and Reliability
ReliaTel™ Controls (LCI-R)
ReliaTel controls provide unit control for
heating, cooling and ventilating utilizing
input from sensors that measure outdoor
and indoor temperature.
ReliaTel™
Quality and Reliability are enhanced
through ReliaTel control and logic:
—prevents the unit from short cycling,
considerably improving
compressor life.
—ensures that the compressor will run
for a specific amount of time which
allows oil to return for better
lubrication, enhancing the reliability of
the compressor.
Voyager with ReliaTel reduces the
number of components required to
operate the unit, thereby reducing
possibilities for component failure.
ReliaTel Makes Installing and
Servicing Easy
ReliaTel eliminates the need for field
installed anti-shortcycle timer and time
delay relays. ReliaTel controls provide
these functions as an integral part of the
unit. The contractor no longer has to
purchase these controls as options and
pay to install them.
The wiring of the low voltage connections
to the unit and the zone sensors is as
easy as 1-1, 2-2, and 3-3. This simplified
system makes wiring easier for the
installer.
ReliaTel Makes Testing Easy
ReliaTel requires no special tools to run
the Voyager unit through its paces.
Simply place a jumper between Test 1
and Test 2 terminals on the Low Voltage
Terminal Board and the unit will walk
through its operational steps
automatically.
— The unit automatically returns
control to the zone sensor after
stepping through the test mode a
single time, even if the jumper is
left on the unit.
As long as the unit has power and the
“system on” LED is lit, ReliaTel is
operational. The light indicates that the
controls are functioning properly.
ReliaTel features expanded diagnostic
capabilities when utilized with Trane
Integrated Comfort™ Systems.
Some zone sensor options have central
control panel lights which indicate the
mode the unit is in and possible
diagnostic information (dirty filters for
example).
Other ReliaTel Benefits
The ReliaTel built-in anti-shortcycle timer,
time delay relay and minimum “on” time
control functions are factory tested to
assure proper operation.
ReliaTel softens electrical “spikes” by
staging on fans, compressors and
heaters.
Intelligent Fallback is a benefit to the
building occupant. If a component goes
astray, the unit will continue to operate at
predetermined temperature setpoint.
Intelligent Anticipation is a standard
ReliaTel feature. It functions continuously
as ReliaTel and zone sensor(s) work
together in harmony to provide much
tighter comfort control than conventional
electro-mechanical thermostats.
The same ReliaTel Board fits all Voyager
Packaged Gas/Electrics, Cooling with
Electric Heat, and Heat Pump models.
This provides standardization of parts for
contractors. Less money is tied up in
inventory with ReliaTel.
RT-PRC002-EN
5
Features and
Benefits
Outstanding Standard and
Optional Components
Black Epoxy Pre-Coated Coils
The pre-coated coils are an economical
option for protection in mildly corrosive
environments.
Cabinet Integrity
For added water integrity, Voyager has a
raised 1
return of the downflow units to prevent
water from blowing into the ductwork.
Clogged Filter/Fan Failure Switch
A dedicated differential pressure switch is
available to achieve active fan failure
indication and/or clogged filter indication.
CO
The CO2 sensor has the ability to monitor
space occupancy levels within the
building by measuring the parts per
million of CO
As the CO
damper modulates to meet the CO
space ventilation requirements. The CO
sensor kit is available as a field installed
accessory.
Colored And Numbered Wiring
Save time and money tracing wires and
diagnosing the unit.
Compressors
Voyager contains the best compressor
technology available to achieve the
highest possible performance. Dual
compressors are outstanding for
humidity control, light load cooling
conditions and system back-up
applications. Dual compressors are
available on all models.
Refrigerant Circuits
All Voyager 12½-25 ton units shall have
crankcase heaters, low and high pressure
controls as standard.
1
/8" lip around the supply and
Sensing
2
(Carbon Dioxide) in the air.
2
levels increase, the outside air
2
2
2
Condenser Coil
Voyager boasts a patent-pending 1+1+1
condenser coil, permanently gapped for
easy cleaning.
Digital Display Zone Sensor
The Digital LCD (Liquid Crystal Display)
zone sensor has the look and functionality
of standard zone sensors. This sensor
should be utilized with ReliaTel™ controls.
Discharge Air Sensing Kit
Provides true discharge air sensing in
heating models. The kit is functional only
with the ReliaTel Options Module.
Downflow And Horizontal Economizers
The economizers come with three control
options — dry bulb is standard, enthalpy
and differential enthalpy are optional.
Dual Thermistor Remote Zone Sensor
This sensor will reduce the total number
of remote sensors to obtain space
temperature averaging. This sensor
should be utilized with ReliaTel controls.
Factory Built Roof Curbs
Available for downflow units. Only two
roof curbs for the entire Voyager line
simplifies curb selection.
Fresh Air
0 - 25% manual or 0 - 50% motorized
outside air hoods are available.
High Static Drive Accessory
Available on many models, this high
static drive accessory extends the
capability of the standard motor. Avoid
expensive motors and operating costs by
installing this optimized sheave
accessory.
Hinged Access Doors
These doors permit easy access to the
filter, fan/heat, and compressor/control
sections. They reduce the potential roof
damage from screws or sharp access
door corners.
LonTalk® Communications Interface
The LonTalk communications interface
allows the unit to communicate as a
Tracer™LCI-V device or directly with
generic LonTalk Network Building
Automation System Controls.
Power Exhaust Option
This option is available on downflow units
and provides exhaust of the return air,
when using a downflow economizer, to
maintain proper building pressurization.
Great for relieving most building
overpressurization problems.
Quick-Access Panels
Remove three or fewer screws for
access to the standardized internal
components and wiring.
Quick-Adjust Idler Arm
With the Quick-Adjust Idler Arm, the belt
and sheaves can be quickly adjusted
without moving the mounted fan motor.
The result is a major savings in time and
money.
6
RT-PRC002-EN
Features and
Benefits
Reference or Comparative Enthalpy
Measures and communicates humidity
while maximizing comfort control.
Sloped Drain Pans
Standard on every unit.
Standardized Components
Components are placed in the same
location on all Voyager units. Familiarize
yourself with one Voyager and you are
familiar with every Voyager.
Due to standardized components
throughout the Voyager line, contractors/
owners can stock fewer parts.
Supply and/or Return Air Smoke
Detector
With this option installed, if smoke is
detected, all unit
operation will be shut
down. Reset will be
manual at the unit.
Return Air Smoke
Detectors require
minimum allowable
airflow when used
with certain models.
Tool-less Hail Guards
Tool-less, hail
protection quality coil
guards shall be either
factory or field-installed for condenser
coil protection. This option protects the
condenser coil from vandalism and/or
hail damage.
Va riTra c
When Trane’s changeover VAV System
for light commercial applications is
coupled with Voyager, it provides the
latest in technological advances for
comfort management systems and can
allow thermostat control in every zone
served by VariTrac.
Ventilation Override Accessory
With the Ventilation Override Accessory
installed, the unit can be set to transition
to up to 3 different pre-programmed
sequences for Smoke Purge,
Pressurization, and Exhaust. The
transition occurs when a binary input on
the RTOM is closed (shorted). This would
typically be a hard wired relay output
from a smoke detector or fire control
panel. The ventilation override kit is
available as a field installed accessory.
Zone Sensors
Available in programmable, automatic
and manual styles.
Rigorous Testing
The fan and idler arm assembly designs
have been tested to over 300,000 cycles
each. Our combined cycle testing is now
over 7,000,000 cycles.
All of Voyager’s designs were rigorously
rain tested at the factory to ensure water
integrity.
Actual shipping tests were performed to
determine packaging requirements. Units
were test shipped around the country to
determine the best packaging. Factory
shake and drop tests were used as part
of the package design process to help
assure that the unit arrives at the job site
in top condition.
Rigging tests include lifting a unit into the
air and letting it drop one foot, assuring
that the lifting lugs and rails hold up under
stress.
We perform a 100% coil leak test at the
factory. The evaporator and condenser
coils are leak tested at 200 psig and
pressure tested to 450 psig.
All parts are inspected at the point of final
assembly. Sub-standard parts are
identified and rejected immediately.
Every unit receives a 100% unit run test
before leaving the production line to
make sure it lives up to rigorous Trane
requirements.
Voyager units incorporate either a one
piece top or the Trane-Tite-Top (T
part of the top (either two or three pieces)
overlaps in such a way that water cannot
leak into the unit. These overlapped edges
are gasketed and sealed to ensure
superior water integrity.
3
). Each
Trane Communication Interface (TCI)
Available factory or field installed. This
module when applied with the ReliaTel™
easily interfaces with Trane’s Integrated
Comfort
TM
RT-PRC002-EN
System.
VariTrac™
7
Features and
Benefits
Easy to Install and Service
Conversionless Units
The dedicated design units (either
downflow or horizontal) require no panel
removal or alteration time to convert in
the field — a major cost savings during
installation.
Horizontal units come complete with duct
flanges so the contractor doesn’t have to
field fabricate them. These duct flanges
are a time and cost saver.
Easy Access Low Voltage Terminal Board
Voyager’s Low Voltage Terminal Board is
external to the electrical control cabinet. It
is extremely easy to locate and attach the
thermostat wire. This is another cost and
time saving installation feature.
Low Voltage Connections
The wiring of the low voltage connections
to the unit and the zone sensors is as
simple as 1-1, 2-2, and 3-3. This simplified
system makes it easy for the installer to
wire.
Electric Heaters
Electric heat modules are available within
the basic unit. If ordering the Through the
Base Electrical option with an Electrical
Heater, the heater must be factory
installed.
Powered or Unpowered Convenience
Outlet
This option is a GFCI, 120v/15amp, 2 plug,
convenience outlet, either powered or
unpowered. This option can only be
ordered when the Through the Base
Electrical with either the Disconnect
Switch, or Circuit Breaker, option is
ordered. This option is available on all
downflow models.
Single Point Power
A single electrical connection powers the
unit.
Single Side Service
Single side service is standard on all
units.
Through the Base Electrical with Circuit
Breaker
This option is a factory installed thermal
magnetic, molded case, HACR Circuit
Breaker with provisions for through the
base electrical connections. This option is
available on all downflow models.
Through the Base Electrical with
Disconnect Switch
Factory installed 3-pole, molded case,
disconnect switch with provisions for
through the base electrical connections
are available. This option is available on
all downflow models.
Through the Base Utilities Access
An electrical service entrance shall be
provided allowing electrical access for
both control and main power connections
inside the curb and through the base of
the unit. Option will allow for field
installation of liquid-tight conduit and an
external field installed disconnect switch.
Factory Installed Options
A wide variety of Factory Installed
Options (FIOPs) are available.
Added Efficiency
Airflow
Airflow is outstanding. The Voyager can
replace an older machine with old
ductwork and, in many cases, improve
the comfort through better air
distribution.
High Efficiency Motors
This option is available with efficiency
ratings from 86.5 up to 91.0. It is not
available for all models.
U-shaped Airflow
U-shaped airflow allows for improved
static capabilities.
Low Ambient Cooling
Cooling capabilities down to 0°F as
standard.
Oversized Motors
Factory or field installed oversized
motors available for high static
applications.
One of our Finest Assets:
Trane Sales Representatives are a
Support group that can assist you with:
— Product
— Application
— Service
— Training
— Special Applications
— Specifications
— Computer Programs and much more
Voyager has the features and benefits
that make it first class in the light
commercial rooftop market. Designed
with input from field contractors and
engineers, its U-shaped airflow
performance is outstanding.
8
RT-PRC002-EN
Application
Considerations
Application of this product should be
within the cataloged airflow and cooling
considerations.
Low Ambient Cooling
This Voyager line features, as standard,
low ambient cooling down to 0°F. The
following options need to be included/
considered when low ambient
applications are required: continuous fan
operation, crankcase heaters, thermal
expansion valves, frostat. Contact your
local Trane Representative for more
assistance with low ambient cooling
applications.
Barometric Relief
This product line offers an optional
barometric relief damper included in the
downflow economizer accessory. This
accessory consists of gravity dampers
which open with increased pressure. As
the building air pressure increases, the
pressure in the unit return air section
also increases, opening the dampers and
relieving the conditioned space.
NOTE: THE EFFECTIVENESS OF
BAROMETRIC RELIEF DAMPER DURING
ECONOMIZING OPERATION IS SYSTEM
RELATED.
PRESSURE DROP OF THE RETURN AIR
SYSTEM SHOULD BE CONSIDERED TO
CONTROL BUILDING PRESSURIZATION.
Power Exhaust Accessory
The power exhaust accessory is available
on all 12½-25 ton downflow units. This
accessory can be field installed and will
assist in relieving building pressurization.
Condensate Trap
The evaporator is a draw-thru
configuration. A trap must be field
provided prior to start-up on the cooling
cycle.
Clearance Requirements
The recommended clearances identified
with unit dimensions should be
maintained to assure adequate
serviceability, maximum capacity and
peak operating efficiency. Actual
clearances which appear inadequate
should be reviewed with the local Trane
sales personnel.
Unit Pitch
These units have sloped condensate
drain pans. Units must be installed level,
any unit slope must be toward access
side of unit.
RT-PRC002-EN
9
Selection
Procedures
Cooling Capacity
Step 1
Calculate the building’s total and sensible
cooling loads at design conditions. Use
the Trane calculation methods or any
other standard accepted method.
As a starting point, a rough determination
must be made of the size of the unit. The
final selection will be made after
examining the performance at the given
conditions. Divide the total cooling load by
nominal BTUH per ton (12 MBh per ton);
then round up to the nearest unit size.
180 MBh / 12 MBh = 15.0 Tons
Step 3
Table PD - 2 shows that a TCD180B4 has a
gross cooling capacity of 184 MBh and
130 MBh sensible capacity at 6000 cfm
and 95 DB outdoor ambient with 80 DB,
67 WB air entering the evaporator.
To Find Capacity at Intermediate
Conditions Not in the Table
When the design conditions are between
two numbers that are in the capacity
table, interpolation is required to
approximate the capacity. Note:
Extrapolation outside of the table
conditions is not recommended.
Step 4
In order to select the correct unit which
meets the building’s requirements, the
fan motor heat must be deducted from
the gross cooling capacity. The amount of
heat that the fan motor generates is
dependent on the effort by the motor cfm and static pressure. To determine the
total unit static pressure you add the
external static pressure to the additional
static related by the added features:
External Static (duct system)
0.49 wg
Standard Filter 1 in.0.10 wg
from Table PD-35
Economizer0.04 wg
(100% Return Air) from Table PD-35
Electric Heater Size 36 kw 0.07 wg
from Table PD-35
Total Static Pressure0.60 wg
Note: The Evaporator Fan Performance
Table PD-18 has already accounted for
the pressure drop for standard filters and
wet coils (see note below Table PD-18).
Therefore, the actual total static pressure
is 0.60 -0.10 (from Table PD-35) = 0.50 wg.
With 6000 cfm and 0.50 wg.
Table PD-18 shows 2.56 bhp for this unit.
Note below the table gives a formula to
calculate Fan Motor Heat,
3.15 x bhp = MBH.
3.15 x 2.56 = 8.06 MBH.
Now subtract the fan motor heat from
the gross cooling capacity of the unit:
Net Total Cooling Capacity
= 184 MBH - 8.06 = 175.9 MBH.
If the performance will not meet the
required load of the building -total or
sensible cooling load, try a selection at
the next higher size unit.
Heating Capacity
Step 1
Calculate the building heating load using
the Trane calculation form or other
standard accepted method.
Step 2
Size the system heating capacity to
match the calculated building heating
load. The following are building heating
requirements:
A
Total heating load of 115.0 MBH
B
6000 cfm
C
460 volt/3 phase Power Supply
The electric heat accessory capacities are
listed in Table PD-36. From the table, a 36
kw heater will deliver 122.94 MBH at 480
volts. In order to determine capacity at
460 volts, the heater voltage correction
factor from Table PD-37 must be used.
Therefore, 122.94 MBH x .94 (voltage
correction factor) = 115.6 MBH.
Air Delivery Selection
External static pressure drop through the
air distribution system has been
calculated to be 0.50 inches of water.
From Table PD-35 static pressure drop
through the economizer is 0.04 and the
36 kw heater is 0.07 inches of water (0.49
+ 0.04 + 0.07). Enter Table PD-18 for a
TCD180B4 at 6000 cfm and 0.50 static
pressure. The standard motor at 777 rpm
will give the desired airflow at a rated bhp
of 2.71.
10
RT-PRC002-EN
Selection
Procedure
Dehumidification Selection
Determine normal unit cooling and
heating capacities as previously
described in the selection procedures on
prior page.
Typical 20 ton TFD241C
6400 cfm Total Supply airflow
2560 cfm Outside Air (40%)
3840 cfm Return Air
0.41” External Static Pressure
OA Conditions
Part load day and raining
68°F db
67°F wb
66.5 dp
95% RH
RA’ conditions
75°F db
63°F wb
52% RH
55.9 dp
Step 1: Determine the mixed/
entering air condition (MA’)
MA’ = (% outside air*outside air dry-bulb
temperature) + (% return air*return air
dry-bulb temperature)
MA’ = (0.40*68°F) + (0.60*75°F)
MA’ = 72.20°F db
Note: Repeat for wet-bulb
temperature (wb).
Plot on psychrometric chart.
MA’
72.2°F db
64.7°F wb
Step 2: Determine static pressure
drop add for reheat
Table PD-35 shows a static pressure drop
of 0.35” for the reheat coil and an
additional .04 for the mandatory 2”
pleated filters required when ordering the
dehumidification option. Total static
pressure =
1.0+0.035+0.04=1.075
(
≅1.1 for manual calculations)
Do not forget to also add any additional
static from other accessories.
Table PD-29 (airflow table for 20 ton
dehumidification units) indicates that a
standard motor and drive is needed for
this airflow and static pressure range.
68°F DB,
OA
67°F WB
75°F DB,
RA'
52% RH
MA' 7 2.2°F DB
SA'
SA
Chart C-1
65°F WB
47°F DB
73°F DB
SA'
SA'
REHEAT
OAOAOA
Step 3a: Determine leaving
evaporator temperature SA’
Leaving Unit Temperature = SA’
Utilizing the manual selection method as
previously described and the formula
∆Temp =cooling capacity in Bth
(cfm)(1.085)
or using the TOPSS™ program
determine the leaving evaporator
temperature (temperature without the
addition of fan heat).
517.74 db
51.03 wb
Step 3b: Determine leaving
unit
temperature in standard cooling
mode
Find the leaving unit temperature
including fan heat as discussed in prior
selection procedures and using the
temperature formula from Step 3a or
refer to your TOPSS selection.
53.6 db
51 wb
84% RH
49% dp
Step 4: Determine reheat
temperature rise
Using the leaving
evaporator temp, go to
PD-39 and find the reheat temperature
rise for that particular cfm: 17.55°F db
Note: Reheat temperature rise is based
on supply airflow and leaving
evaporator coil temperature.
MA'
MA'
RA'
RA'
SA
SA
Step 5: Determine leaving unit
temperature with reheat active (SA)
Reheat temperature (obtained in step 3)
+ SA’ = SA
17.55°F db + 53.6°F = 71.2°F db
SA’=71.2°F
51 wb
20.8 RH
29.4 dp
Consider Chart C-1. If the space relative
humidity is equal to or above the space
relative humidity setpoint, the
Dehumidification option will:
• Energize compressor or both
compressors (2 stage compressor units).
• Hot gas reheat valve is energized and
hot gas is diverted to the reheat coil.
• Dehumidification/reheat is terminated
when space humidity is reduced to 5%
below relative humidity setpoint.
At MA’, air enters the RTU. The RTU filters,
cools, and dehumidifies the air as it
moves through the evaporator coil. Air
leaves the evaporator coil saturated at
the preset dew point condition (SA’) and
is reheated by the hot gas reheat coil to
deliver 71°F (SA) supply air to the space.
RT-PRC002-EN
11
Model
Number
Description
Packaged Cooling with Electric Heat Unit Typical Model Nomenclature
TC D150C30 0AA
12 3456789 1011 12
Digits 1, 2 - Product Type
TC = Packaged Cooling, Electric
Heat
TF = With Factory Installed
Options
150 =12½ Tons Standard Efficiency
151 =12½ Tons High Efficiency
180 =15 Tons Standard Efficiency
181 =15 Tons High Efficiency
210 =17½ Tons Standard Efficiency
211 =17½ Tons High Efficiency
240 =20 Tons Standard Efficiency
241 =20 Tons High Efficiency
300 =25 Tons Standard Efficiency
301 =25 Tons High Efficiency
Digit 7- Major Development Sequence
Digit 8 - Electrical Characteristics
3 = 208-230/60/3
4 = 460/60/3
W = 575/60/3
K = 380/60/3
Digit 9, 10 - Factory-Installed Options
00 = No Factory-installed Options
0A = Factory-installed Economizer
0B = Oversized Motor
0C = Downflow Economizer and
Oversized Motor
0F = Trane Communications Interface
(TCI)
0G = Downflow Economizer and TCI
0H = TXV/Face-Split Evaporator
0J = Oversized Motor and TXV/Face-Split
Evaporator
0K = Downflow Economizer, Oversized
Motor, and TXV/Face-Split Evaporator
0L = Downflow Economizer with TXV/Face-
No. Used11
Diameter x Width (in.)15 x 1515 x 15
Drive Type/No. SpeedsBelt/1Belt/1
No. Motors11
Motor HP (Standard/Oversized)3.0/5.03.0/5.0
Motor RPM (Standard/Oversized)1,740/3,4501,740/3,450
Motor Frame Size (Standard/Oversized)145T/145T145T/145T
Filters — Type Furnished
(No.) Size Recommended (in.)
Downflow(2) 20 x 20 x 2, (4) 20 x 25 x 2(2) 20 x 20 x 2, (4) 20 x 25 x 2
Horizontal(2) 20 x 20 x 2, (4) 20 x 25 x 2(2) 20 x 20 x 2, (4) 20 x 25 x 2
Refrigerant Charge (Lbs of R-22)
Notes:
1. Cooling Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net
and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the Unitary Large Equipment certification
program, which is based on ARI Standard 340/360-93.
2. EER is rated at ARI conditions and in accordance with ARI Standard 210/240 or 360.
3. Integrated Part Load Value is based in accordance with ARI Standard 210/240 or 360. Units are rated at 80°F ambient, 80°F entering dry bulb, and 67°F entering wet bulb at ARI
rated cfm.
4. Sound Rating shown is tested in accordance with ARI Standard 270 or 370.
5. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
6. Optional 2 inch pleated filters are also available.
7. For 380V/60Hz units, the oversized motor is used as the standard motor. Refer to oversized motor data.
1
3
4
6
5
TC*150D3, D4, DW, DKTC*180B3, B4, BW, BK
9.89.9
10.510.2
9.29.2
ThrowawayThrowaway
9.3/9.4/Circuit17.5/9.5/Circuit
*Indicates both downflow and horizontal units.
RT-PRC002-EN
13
General
(17½, 20, 25 Ton)
Data
Standard Efficiency
Table GD - 2 — General Data
Downflow and Horizontal UnitsDownflow and Horizontal UnitsDownflow and Horizontal Units
Cooling Performance
Gross Cooling Capacity210,000242,000290,000
2
EER
Nominal CFM / ARI Rated CFM7,000/5,80 08,000/7,00 010,000/8,750
ARI Net Cooling Capacity196,000232,000272,000
Integrated Part Load Value
System Power (KW)20.023.9128.05
Indoor Fan — TypeFC CentrifugalFC CentrifugalFC Centrifugal
No. Used111
Diameter x Width (in.)15 x 1518 x 1818 x 18
Drive Type/No. SpeedsBelt / 1Belt / 1Belt / 1
No. Motors111
Motor HP (Standard/Oversized)5.0/7.55.0/7.57.5/NA
Motor RPM (Standard/Oversized)3,450/3,4703,450/3,4703,470/NA
Motor Frame Size (Standard/Oversized)145T/184T145T/184T184T/NA
Filters — Type Furnished
(No.) Size Recommended (in.)
Downflow(2) 20 x 20 x 2, (4) 20 x 25 x 2(4) 20 x 20 x 2, (4) 20 x 25 x 2(4) 20 x 20 x 2, (4) 20 x 25 x 2
Horizontal(2) 20 x 20 x 2, (4) 20 x 25 x 2(8) 20 x 25 x 2(8) 20 x 25 x 2
Refrigerant Charge (Lbs of R-22)
Notes:
1. Cooling Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net
and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. 17½ - 20 ton models are certified in accordance with the Unitary Large
Equipment certification program, which is based on ARI Standard 340/360-93. 25 ton model ratings shown are tested in accordance with ARI Standard 340/360-93.
2. EER is rated at ARI conditions and in accordance with ARI Standard 210/240 or 360.
3. Integrated Part Load Value is based in accordance with ARI Standard 210/240 or 360. Units are rated at 80°F ambient, 80°F entering dry bulb, and 67°F entering wet bulb at ARI
rated cfm.
4. Sound Rating shown is tested in accordance with ARI Standard 270 or 370.
5. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
6. Refrigerant charge for horizontal models is 21.5/14.5 per circuit.
7. Optional two inch pleated filters are also available.
8. For 380V/60Hz units, the oversized motor is used as the standard motor. Refer to oversized motor data.
1
3
4
7
5
17½ Ton20 Ton25 Ton
TC*210C3, C4, CW, CKTC*240B3, B4, BW, BKTC*300B3, B4, BW, BK
9.89.79.7
10.010.09.8
9.49.49.4
ThrowawayThrowawayThrowaway
21.0/14.3/Circuit
6
18.9/21.0/Circuit17.0/Circuit
*Indicates both downflow and horizontal units.
14
RT-PRC002-EN
General
(12½, 15 Ton)
Data
High Efficiency
Table GD - 3 — General Data
12½ Ton15 Ton
Downflow and HorizontalDownflow and Horizontal
Cooling Performance
Gross Cooling Capacity154,000189,000
2
EER
Nominal CFM / ARI Rated CFM5,000/4,4006,000/5,300
ARI Net Cooling Capacity146,000180,000
Integrated Part Load Value
System Power KW12.9215.65
No. Used11
Diameter x Width (in.)15 x 1518 x 18
Drive Type/No. SpeedsBELT/1BELT/1
No. Motors11
Motor HP (Standard/Oversized)3.0/5.03.0/5.0
Motor RPM (Standard/Oversized)1740/34501740/3450
Motor Frame Size (Standard/Oversized)145T/145T145T/145T
Filters — Type/Furnished?Throwaway/Yes
(No.) Size Recommended (in.)(2)20 x 20 x 2(4) 20 x 20 x 2
Optional Hot Gas Reheat Coil — TypeHi-PerformanceHi-Performance
Tube Size (in.) OD0.3750.375
Face Area (sq. ft.)17.526
Rows/FPI1/161/16
Refrigerant Charge (Lbs of R-22) 5/Circuit
Standard15.0/13.8
Optional Hot Gas Reheat Coil15.3/14.327.8/11.4
Notes:
1. Cooling Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net
and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the Unitary Large Equipment certification
program, which is based on ARI Standard 340/360-93.
2. EER is rated at ARI conditions and in accordance with DOE test procedures.
3. Integrated Part Load Value is based in accordance with ARI Standard 210/240 or 360. Units are rated at 80°F ambient, 80°F entering dry bulb, and 67°F entering wet bulb at ARI
rated cfm.
4. Sound Rating shown is tested in accordance with ARI Standard 270 or 370.
5. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
6. Face area for Indoor Coil on horizontal models is 12.36.
7. Horizontal models have 4 - 20 x 25 x 2 filters.
8. Optional two inch pleated filters are also available for 12½ ton models.
Indoor Fan — TypeFC CentrifugalFC CentrifugalFC Centrifugal
No. Used111
Diameter x Width (in.)18 x 1818 x 1818 x 18
Drive Type/No. SpeedsBELT/1BELT/1BELT/1
No. Motors111
Motor HP (Standard/Oversized)5.0/7.55.0/7.57.5/NA
Motor RPM(Standard/Oversized)3450/34703450/34703470/NA
Motor Frame Size (Standard/Oversized)145T/184T145T/184T184T/NA
Filters — Type Furnished
7
(No.) Size Recommended (in.)(4/4)20 x 20 x 2/20 x 25 x 26(4/4)20 x 20 x 2/20 x 25 x 26(4/4)20 x 20 x 2/20 x 25 x 2
Optional Hot Gas Reheat Coil — Type—Hi-Performance—
Tube Size (in.) OD—0.375—
Face Area—26—
Rows/FPI—1/16—
Refrigerant Charge (Lbs of R-22)
5
/ Circuit
Standard2 5.7/12.5
Optional Hot Gas Reheat Coil—21.3/21.0—
Notes:
1. Cooling Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net
and includes the effect of fan motor heat. 15 - 20 ton models are certified in accordance with the Unitary Large Equipment certification program, which is based on ARI
Standard 340/360-93. 25 ton model ratings shown are tested in accordance with ARI Standard 340/360-93.
2. EER is rated at ARI conditions and in accordance with DOE test procedures.
3. Integrated Part Load Value is based in accordance with ARI Standard 210/240 or 360. Units are rated at 80°F ambient, 80°F entering dry bulb, and 67°F entering wet bulb at ARI
rated cfm.
4. Sound Rating shown is tested in accordance with ARI Standard 270 or 370.
5. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
6. Horizontal models have 8 - 20 x 25 x 2 filters.
7. Optional two inch pleated filters are also available.
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to
appropriate airflow table notes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
4. Table is for 460 volt capacity. For capacity at 230 volt, multiply table capacity by 101%.
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to
appropriate airflow table notes.
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate
airflow table notes.
2. MBH = Total Gross Cooling Capacity
3. SHC = Sensible Heat Capacity
*Unit applications below 4000 CFM
• Electric heaters restricted on applications below 4000 CFM.
• Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters are required on applications below 4000 CFM.
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to
appropriate airflow table notes.
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate
airflow table notes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
*Unit applications below 4800 CFM
• Electric heaters restricted on applications below 4800 CFM.
• Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters are required on applications below 4800 CFM.
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to
appropriate airflow table notes.
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to
appropriate airflow table notes.
2. MBH = Total Gross Cooling Capacity
3. SHC = Sensible Heat Capacity
*Unit applications below 5600 CFM
• Electric heaters restricted on applications below 5600 CFM.
• Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters are required on applications below 5600 CFM.
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to
appropriate airflow table notes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
*Unit applications below 6400 CFM
• Electric heaters restricted on applications below 6400 CFM.
• Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters are required on applications below 6400 CFM.
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to
appropriate airflow table notes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
*Unit applications below 6400 CFM
• Electric heaters restricted on applications below 6400 CFM.
• Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters are required on applications below 6400 CFM.
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to
appropriate airflow table notes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
*Unit applications below 8000 CFM
• Electric heaters restricted on applications below 8000 CFM.
• Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters are required on applications below 8000 CFM.
For Standard Evaporator Fan Speed (RPM), reference Table PD-31.
For Oversized Evaporator Fan Speed (RPM), reference Table PD-33.
Fan motor heat (MBH) = 3.15 x Fan BHP
Data includes pressure drop due to wet coils and filters.
No accessories or options are included in pressure drop data.
Refer to Table PD-35 to determine add’l static pressure drop due to other options/accessories.
Notes:
1. Field Supplied Fan Sheave BK90 Required. Field Supplied Belt may be necessary.
2. 5 HP Oversized Motor with Field Supplied Motor Sheave IVL40 Required. Field Supplied Belt
may be necessary.
3. For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to “Motor &
Sheave/Fan Speed” tables to determine operating range.
1.101.201.301.401.501.601.701.801.902.00
3 HP Standard Motor & Sheaves3 HP Standard Motor & High Static Drive Accessory
External Static Pressure (Inches of Water)
5 HP Oversize Motor & Sheaves
5 HP Oversize Motor & Field Supplied Drive
Factory supplied motors, in commercial equipment, are definite
purpose motors, specifically designed and tested to operate
reliably and continuously at all cataloged conditions. Using the
full horsepower range of our fan motors as shown in our
tabular data will not result in nuisance tripping or premature
motor failure. Our product’s warranty will not be affected.
RT-PRC002-EN
31
Performance
(15 Ton)
Data
Standard Efficiency
Table PD-18 — Evaporator Fan Performance — 15 Ton — TC*180B
3 HP Standard Motor & Sheaves3 HP Standard Motor & High Static Drive Accessory
5 HP Oversized Motor & Sheaves
External Static Pressure (Inches of Water)
5 HP Oversized Motor & Field Supplied Drive (3)
For Standard Evaporator Fan Speed (RPM), reference Table PD-31.
For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-32.
For Oversized Evaporator Fan Speed (RPM), reference Table PD-33.
Fan motor heat (MBH) = 3.15 x Fan BHP
Data includes pressure drop due to wet coils and filters.
No accessories or options are included in pressure drop data.
Refer to Table PD-35 to determine add’l static pressure drop due to other options/accessories.
Notes:
1. Field Supplied Fan Sheave BK105 Required. Field Supplied Belt may be necessary.
2. 5 HP Oversized Motor with Field Supplied Fan Sheave BK160 Required. Field Supplied Belt may
be necessary.
3. 5 HP Oversized Motor with Field Supplied Motor Sheave IVP50 Required. Field Supplied Belt
may be necessary.
4. For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to “Motor &
Sheave/Fan Speed” tables to determine operating range.
Factory supplied motors, in commercial equipment, are
definite purpose motors, specifically designed and tested
to operate reliably and continuously at all cataloged
conditions. Using the full horsepower range of our fan
motors as shown in our tabular data will not result in
nuisance tripping or premature motor failure. Our
product’s warranty will not be affected.
32
RT-PRC002-EN
Performance
(17½Ton)
Data
Standard Efficiency
Table PD-19 — Evaporator Fan Performance — 17½ Ton — TC*210C
For Standard Evaporator Fan Speed (RPM), reference Table PD-31.
For Oversized Evaporator Fan Speed (RPM), reference Table PD-33.
For Standard Motor & Low Static Drive Accessory Fan Speed (RPM), reference Table PD-34.
Fan motor heat (MBH) = 3.15 x Fan BHP
Data includes pressure drop due to wet coils and filters.
No accessories or options are included in pressure drop data.
Refer to Table PD-35 to determine add’l static pressure drop due to other options/accessories.
Notes:
1. For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to “Motor & Sheave/
Fan Speed” tables to determine operating range.
1.101.201.301.401.501.601.701.801.902.00
External Static Pressure (Inches of Water)
5 HP Standard Motor & Sheaves
7.5 HP Oversive Motor & Sheaves
Factory supplied motors, in commercial equipment, are
definite purpose motors, specifically designed and tested to
operate reliably and continuously at all cataloged conditions.
Using the full horsepower range of our fan motors as shown
in our tabular data will not result in nuisance tripping or
premature motor failure. Our product’s warranty will not be
affected.
*Indicates both downflow and horizontal units.
RT-PRC002-EN
33
Performance
(20 Ton)
Data
Standard Efficiency
Table PD-20 — Evaporator Fan Performance — 20 Ton — TC*240B
For Standard Evaporator Fan Speed (RPM), reference Table PD-31.
For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-32.
For Oversized Evaporator Fan Speed (RPM), reference Table PD-33.
Fan motor heat (MBH) = 3.15 x Fan BHP
Data includes pressure drop due to wet coils and filters.
No accessories or options are included in pressure drop data.
Refer to Table PD-35 to determine add’l static pressure drop due to other options/accessories.
Notes:
1. Field Supplied Fan Sheave BK190 Required. Field Supplied Belt may be necessary.
2. 7.5 HP Standard Motor with Field Supplied Motor Sheave IVP50 Required. Field Supplied Belt
may be necessary.
3. For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to “Motor &
Sheave/Fan Speed” tables to determine operating range.
1.101.201.301.401.501.601.701.801.902.00
5 HP Standard Motor & Sheaves5 HP Standard Motor & High Static Drive Accessory
7.5 HP Oversized Motor & Sheaves
External Static Pressure (Inches of Water)
Factory supplied motors, in commercial equipment, are
definite purpose motors, specifically designed and tested to
operate reliably and continuously at all cataloged conditions.
Using the full horsepower range of our fan motors as shown
in our tabular data will not result in nuisance tripping or
premature motor failure. Our product’s warranty will not be
affected.
*Indicates both downflow and horizontal units.
34
RT-PRC002-EN
Performance
(25 Ton)
Data
Standard Efficiency
Table PD-21 — Evaporator Fan Performance — 25 Ton — TC*300B
For Standard Evaporator Fan Speed (RPM), reference Table PD-31.
For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-32.
For Standard Motor & Low Static Drive Accessory Fan Speed (RPM), reference Table PD-34.
Fan motor heat (MBH) = 3.15 x Fan BHP
Data includes pressure drop due to wet coils and filters.
No accessories or options are included in pressure drop
data. Refer to Table PD-35 to determine add’l static pressure drop due to other options/accessories.
Note:
1. For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to “Motor & Sheave/Fan
Speed” tables to determine operating range.
1.101.201.301.401.50
7.5 HP Standard Motor & High Static Drive Accessory
External Static Pressure (Inches of Water)
7.5 HP Standard Motor & Sheaves
Factory supplied motors, in commercial equipment, are
definite purpose motors, specifically designed and tested
to operate reliably and continuously at all cataloged
conditions. Using the full horsepower range of our fan
motors as shown in our tabular data will not result in
nuisance tripping or premature motor failure. Our
product’s warranty will not be affected.
*Indicates both downflow and horizontal units.
RT-PRC002-EN
35
Performance
(12½ Ton)
Data
High Efficiency
Table PD-22 — Evaporator Fan Performance — 12½Ton — TCD151C — Standard or TXV Refrigeration System
For Standard Evaporator Fan Speed (RPM), reference Table PD-31.
For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-32.
For Oversized Evaporator Fan Speed (RPM), reference Table PD-33.
*Unit applications below 4000 CFM
• Electric heaters restricted on applications below 4000 CFM.
• Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters
are required on applications below 4000 CFM.
Fan motor heat (MBH) = 3.15 x Fan BHP
Data includes pressure drop due to wet coils and filters.
No accessories or options are included in pressure drop data.
Refer to Table PD-35 to determine add’l static pressure drop due to other options/accessories.
Note:
1. Field Supplied Fan Sheave BK115 Required. Field Supplied Belt may be necessary.
1.101.201.301.401.501.601.701.801.902.00
3 HP Standard Motor & Drive3 HP Standard Motor & High Static Drive Accessory
External Static Pressure (Inches of Water)
5 HP Oversized Motor & Drive
Factory supplied motors, in commercial equipment, are
definite purpose motors, specifically designed and tested to
operate reliably and continuously at all cataloged conditions.
Using the full horsepower range of our fan motors as shown
in our tabular data will not result in nuisance tripping or
premature motor failure. Our product’s warranty will not be
affected.
36
RT-PRC002-EN
Performance
(12½ Ton)
Data
High Efficiency
Table PD-23 — Evaporator Fan Performance — 12½Ton — T*D151C — Dehumidification (Hot Gas Reheat) Option
For Standard Evaporator Fan Speed (RPM), reference Table PD-31.
For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-32.
For Oversized Evaporator Fan Speed (RPM), reference Table PD-33.
Table includes Dehumidification (Hot Gas Reheat Option).
*Unit applications below 4000 CFM
• Electric heaters restricted on applications below 4000 CFM.
• Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters
are required on applications below 4000 CFM.
Fan motor heat (MBH) = 3.15 x Fan BHP
Data includes pressure drop due to wet coils and filters.
No accessories or options are included in pressure drop data.
Refer to Table PD-35 to determine add’l static pressure drop due to other options/accessories.
Note:
1. Field Supplied Fan Sheave BK115 Required. Field Supplied Belt may be necessary.
1.101.201.301.401.501.601.701.801.902.00
3 HP Standard Motor3 HP Standard Motor & High Static Drive Accessory
& Drive
External Static Pressure (Inches of Water)
5 HP Oversized Motor & Drive w/Field Supplied Fan Sheave
Factory supplied motors, in commercial equipment, are
definite purpose motors, specifically designed and tested to
operate reliably and continuously at all cataloged conditions.
Using the full horsepower range of our fan motors as shown
in our tabular data will not result in nuisance tripping or
premature motor failure. Our product’s warranty will not be
affected.
RT-PRC002-EN
37
Performance
(12½ Ton)
Data
High Efficiency
Table PD-24 — Evaporator Fan Performance — 12½Ton — TCH151C — Standard Refrigeration System
For Standard Evaporator Fan Speed (RPM), reference Table PD-31.
For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-32.
For Oversized Evaporator Fan Speed (RPM), reference Table PD-33.
Fan motor heat (MBH) = 3.15 x Fan BHP
Data includes pressure drop due to wet coils and filters.
No accessories or options are included in pressure drop data.
Refer to Table PD-35 to determine add’l static pressure drop
due to other options/accessories.
Note:
1. Field Supplied Fan Sheave BK115 Required. Field Supplied Belt may be necessary.
1.101.201.301.401.501.601.701.801.902.00
3 HP Standard Motor & Drive3 HP Standard Motor & High Static
External Static Pressure (Inches of Water)
5 HP Oversized Motor & Drive
Drive Accessory
Factory supplied motors, in commercial equipment, are
definite purpose motors, specifically designed and tested to
operate reliably and continuously at all cataloged conditions.
Using the full horsepower range of our fan motors as shown
in our tabular data will not result in nuisance tripping or
premature motor failure. Our product’s warranty will not be
affected.
38
RT-PRC002-EN
Performance
(15 Ton)
Data
High Efficiency
Table PD-25 — Evaporator Fan Performance — 15 Ton — TC*181C — Standard or TXV Refrigeration System
For Standard Evaporator Fan Speed (RPM), reference Table PD-31.
For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-32.
For Oversized Evaporator Fan Speed (RPM), reference Table PD-33.
*Unit applications below 4000 CFM
• Electric heaters restricted on applications below 4000 CFM.
• Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase
Heaters
are required on applications below 4000 CFM.
Fan motor heat (MBH) = 3.15 x Fan BHP
Data includes pressure drop due to wet coils and filters.
No accessories or options are included in pressure drop data.
Refer to Table PD-35 to determine add’l static pressure drop due to other options/ccessories.
Note:
1. Field Supplied Fan Sheave BK120 Required. Field Supplied Belt may be necessary. Field
Supplied Belt may be necessary.
1.101.201.301.401.501.601.701.801.902.00
3 HP Standard Motor & Drive3 HP Standard Motor & High
External Static Pressure (Inches of Water)
Static Drive Accessory
5 HP Oversized Motor & Drive
Factory supplied motors, in commercial equipment, are
definite purpose motors, specifically designed and tested to
operate reliably and continuously at all cataloged conditions.
Using the full horsepower range of our fan motors as shown
in our tabular data will not result in nuisance tripping or
premature motor failure. Our product’s warranty will not be
affected.
*Indicates both downflow and horizontal units.
RT-PRC002-EN
39
Performance
(15 Ton)
Data
High Efficiency
Table PD-26 — Evaporator Fan Performance — 15 Ton — T*D181C — Dehumidification (Hot Gas Reheat) Option
For Standard Evaporator Fan Speed (RPM), reference Table PD-31.
For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-32.
For Oversized Evaporator Fan Speed (RPM), reference Table PD-33.
Table includes Dehumidification (Hot Gas Reheat Option).
*Unit applications below 4800 CFM
• Electric heaters restricted on applications below 4800 CFM.
• Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters
are required on applications below 4800 CFM.
Fan motor heat (MBH) = 3.15 x Fan BHP
Data includes pressure drop due to wet coils and filters.
No accessories or options are included in pressure drop data.
Refer to Table PD-35 to determine add’l static pressure drop due to other options accessories.
Note:
1. Field Supplied Fan Sheave BK120 Required. Field Supplied Belt may be necessary. Field
Supplied Belt may be necessary.
2. Field Supplied Fan Sheave BK160 Required. Field Supplied Belt may be necessary. Field
Supplied Belt may be necessary.
Factory supplied motors, in commercial equipment, are
definite purpose motors, specifically designed and tested to
operate reliably and continuously at all cataloged conditions.
Using the full horsepower range of our fan motors as shown
in our tabular data will not result in nuisance tripping or
premature motor failure. Our product’s warranty will not be
affected.
40
RT-PRC002-EN
Performance
(17½ Ton)
Data
High Efficiency
Table PD-27 — Evaporator Fan Performance — 17½ Ton — TC*211C — Standard or TXV Refrigeration System
For Standard Evaporator Fan Speed (RPM), reference Table PD-31.
For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-32.
For Oversized Evaporator Fan Speed (RPM), reference Table PD-33.
*Unit applications below 5600 CFM
• Electric heaters restricted on applications below 5600 CFM.
• Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters
are required on applications below 5600 CFM.
Fan motor heat (MBH) = 3.15 x Fan BHP
Data includes pressure drop due to wet coils and filters.
No accessories or options are included in pressure drop data.
Refer to Table PD-35 to determine add’l static pressure drop due to other options/accessories.
Note:
1. Field Supplied Fan Sheave BK190 Required. Field Supplied Belt may be necessary.
1.101.201.301.401.501.601.701.801.902.00
5 HP Standard Motor & Drive5 HP Standard Motor & High
External Static Pressure (Inches of Water)
7.5 Oversize Motor & Drive
Static Drive Accessory
Factory supplied motors, in commercial equipment, are
definite purpose motors, specifically designed and tested to
operate reliably and continuously at all cataloged conditions.
Using the full horsepower range of our fan motors as shown
in our tabular data will not result in nuisance tripping or
premature motor failure. Our product’s warranty will not be
affected.
*Indicates both downflow and horizontal units.
RT-PRC002-EN
41
Performance
(20 Ton)
Data
High Efficiency
Table PD-28 — Evaporator Fan Performance — 20 Ton — TC*241C — Standard or TXV Refrigeration System
For Standard Evaporator Fan Speed (RPM), reference Table PD-31.
For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-32.
For Oversized Evaporator Fan Speed (RPM), reference Table PD-33.
*Unit applications below 6400 CFM
• Electric heaters restricted on applications below 6400 CFM.
• Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters
are required on applications below 6400 CFM.
Fan motor heat (MBH) = 3.15 x Fan BHP
Data includes pressure drop due to wet coils and filters.
No accessories or options are included in pressure drop data.
Refer to Table PD-35 to determine add’l static pressure drop due to other options/accessories.
Notes:
1. Field Supplied Fan Sheave BK190 Required. Field Supplied Belt may be necessary.
2. 7.5 HP Standard Motor with Field Supplied Motor Sheave 1VP50 Required. Field Supplied Belt
may be necessary.
3. Field Supplied Fan Sheave B5V200 and Motor Sheave IVP34 required. Field Supplied Belt may
be necessary.
1.101.201.301.401.501.601.701.801.902.00
5 HP Standard Motor & Drive5 HP Standard Motor
7.5 HP Oversized Motor & Drive
External Static Pressure (Inches of Water)
& High Static Drive Accessory
Factory supplied motors, in commercial equipment, are
definite purpose motors, specifically designed and tested to
operate reliably and continuously at all cataloged conditions.
Using the full horsepower range of our fan motors as shown
in our tabular data will not result in nuisance tripping or
premature motor failure. Our product’s warranty will not be
affected.
*Indicates both downflow and horizontal units.
42
RT-PRC002-EN
Performance
(20 Ton)
Data
High Efficiency
Table PD-29 — Evaporator Fan Performance — 20 Ton — T*D241C — Dehumidification (Hot Gas Reheat) Option
For Standard Evaporator Fan Speed (RPM), reference Table PD-31.
For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-32.
For Oversized Evaporator Fan Speed (RPM), reference Table PD-33.
Table includes Dehumidification (Hot Gas Reheat Option).
*Unit applications below 6400 CFM
• Electric heaters restricted on applications below 6400 CFM.
• Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters
are required on applications below 6400 CFM.
Fan motor heat (MBH) = 3.15 x Fan BHP
Data includes pressure drop due to wet coils and filters.
No accessories or options are included in pressure drop data.
Refer to Table PD-35 to determine add’l static pressure drop due to other options/accessories.
Notes:
1. Field Supplied Motor Sheave IVP34 Required. Field Supplied Belt may be necessary.
2. Field Supplied Fan Sheave BK190 Required. Field Supplied Belt may be necessary.
3. 7.5 HP Standard Motor with Field Supplied Motor Sheave 1VP50 Required. Field Supplied Belt
may be necessary.
1.101.201.301.401.501.601.701.801.902.00
5 HP Standard Motor & Drive5 HP Standard Motor
7.5 HP Oversized Motor & Drive
External Static Pressure (Inches of Water)
& High Static Drive
Factory supplied motors, in commercial equipment, are
definite purpose motors, specifically designed and tested to
operate reliably and continuously at all cataloged conditions.
Using the full horsepower range of our fan motors as shown
in our tabular data will not result in nuisance tripping or
premature motor failure. Our product’s warranty will not be
affected.
RT-PRC002-EN
43
Performance
(25 Ton)
Data
High Efficiency
Table PD-30 — Evaporator Fan Performance — 25 Ton — TC*301C — Standard Refrigeraton System
For Standard Evaporator Fan Speed (RPM), reference Table PD-31.
For Standard Motor & High Static Drive Accessory Fan Speed (RPM),
reference Table PD-32.
For Standard Motor & Low Static Drive Accessory Fan Speed (RPM),
reference Table PD-34.
Fan motor heat (MBH) = 3.15 x Fan BHP
*Unit applications below 8000 CFM
• Electric heaters restricted on applications below 8000
CFM.
• Dehumidification (Hot Gas Reheat) or TXV with Frostat
and Crankcase Heaters are required on applications
below 8000 CFM.
Notes:
Data includes pressure drop due to wet coils and filters.
No accessories or options are included in pressure drop data.
Refer to Table PD-35 to determine add’l static pressure drop due to
other options/accessories.
1.101.201.301.401.50
7.5 HP Standard Motor & High Static Drive Accessory
External Static Pressure (Inches of Water)
7.5 HP Standard Motor & Drive
Factory supplied motors, in commercial
equipment, are definite purpose motors,
specifically designed and tested to operate
reliably and continuously at all cataloged
conditions. Using the full horsepower range
of our fan motors as shown in our tabular
data will not result in nuisance tripping or
premature motor failure. Our product’s
warranty will not be affected.
*Indicates both downflow and horizontal units.
44
RT-PRC002-EN
Performance
Data
(12½-25 Ton)
Table PD-31— Standard Motor & Drive/Fan Speed (Rpm)
Zone sensors are the building occupant’s
comfort control devices. They replace the
conventional electro-mechanical
thermostats. The following zone sensor
options are available for Voyager units
with the ReliaTel™ control:
Manual Changeover
Heat, Cool or Off
System Switch. Fan
Auto or Off Switch.
One temperature
setpoint lever.
Manual/Automatic Changeover
Auto, Heat, Cool or Off System Switch.
Fan Auto or Off
Switch. Two
temperature
setpoint levers.
Optional Status
Indication LED lights,
System On, Heat,
Cool, or Service.
Remote Sensor
Sensor(s) available
for all zone sensors to
provide remote
sensing capabilities.
Dual Thermistor Remote Zone Sensor
This sensor will allow the customer to
reduce the total number of remote
sensors to obtain space temperature
averaging. This sensor should be utilized
with ReliaTel controls.
RT-PRC002-EN
Digital Display Zone Sensor
The Digital LCD (Liquid Crystal Display)
zone sensor has the look and functionality
of standard zone
sensors. This
sensor includes a
digital display of
set point
adjustment and
space temperature
in F (Fahrenheit) or
C (Celsius).
Includes FAN and
SYSTEM buttons
(supports the
service functions of
the standard
sensor). E-squared memory stores last
programmed set points. Requires 24 VAC
(Volts AC). This sensor should be utilized
with ReliaTel controls.
Programmable Night Setback
Auto or manual changeover with sevenday programming. Keyboard selection
of Heat, Cool, Fan, Auto, or On. All
programmable sensors have System On,
Heat, Cool, Service LED/indicators as
standard. Night Setback Sensors have
one (1) Occupied, one (1) Un-occupied,
and two (2) Override programs per day.
Integrated
Comfort
TM
System
Sensor(s)
available with
optional
temperature
adjustment and
override buttons
to provide central
control through a
Trane Integrated
Comfort system.
CO
Sensing The CO2 sensor has the
2
ability to monitor space occupancy levels
within the
building by
measuring the
parts per million
of CO
(Carbon
2
Dioxide) in the air.
As the CO
levels
2
increase, the
outside air
damper
modulates to
meet the CO
requirements. The CO
space ventilation
2
sensor kit is
2
available as a field installed accessory.
Economizer Controls
The standard equipment offering is a
fixed dry bulb changeover control. In
addition, there are two optional controls,
Enthalpy and Differential Enthalpy
Control.
Enthalpy Control
Replaces the dry bulb control with a wet
bulb changeover controller which has a
fully adjustable set point. Enthalpy control
offers a higher level of comfort control,
along with energy savings potential, than
the standard dry bulb control. This is due
to the additional wet bulb sensing
capability.
Differential Enthalpy
Replaces the standard dry bulb control
with two enthalpy sensors that compare
total heat content of the indoor air and
outdoor air to determine the most
efficient air source. This control option
offers the highest level of comfort control,
plus energy efficiency, available.
Remote Potentiometer
Minimum position setting of economizer
can be remotely adjusted with this
accessory.
Differential Pressure Switches
This factory or field-installed option
allows individual fan failure and dirty filter
indication. The fan failure switch will
disable all unit functions and “flash” the
Service LED on the zone sensor. The dirty
filter switch will light the Service LED on
the zone sensor and will allow continued
unit operation.
Trane Communication Interface (TCI)
This factory or field-installed microprocessor interface allows the unit to
communicate to Trane’s Integrated
Comfort system.
Standard Evaporator Fan MotorOversized Evaporator Fan Motor
*Indicates both downflow and horizontal units.
RT-PRC002-EN
63
Electrical
Data
Table ED-15 — Electrical Characteristics — Power Exhaust Accessory
TonsVoltagePhaseHPRPMFLALRA
1, 2
12½
15, 17½46013/410403.28.4
20, 2557513/410402.15.2
Notes:
1. 12½ Ton Standard Unit.
2. 12½ Ton High Efficiency Unit.
Accessory
Operating\Amps
208-23013/410406.613.5
64
RT-PRC002-EN
Jobsite
Connections
DISCONNECT
SWITCH
(BY OTHERS)
ZONE SENSORS
ROOFTOP
UNIT
For specific wiring information, see the installation instructions.
All wiring except power wires is low voltage.
All customer supplied wiring to be copper and must conform to NEC or CEC and local electrical codes. Wiring shown dotted is to be furnished and installed by the customer.
Status Indication LED’s ........................... 10
Programmable Night Setback with
Status Indication LED’s ............................. 7
B— 3 Power Wires + 1 Ground Wire (three phase)
2 Power Wires + 1 Ground Wire (single phase)
RT-PRC002-EN
65
Typical
Wiring
(12½-25 Ton)
66
RT-PRC002-EN
Typical
Wiring
(12½-25 Ton)
Typical wiring diagram. For specific
wiring, see individual Service Facts.
RT-PRC002-EN
67
Typical
Wiring
(12½-25 Ton)
68
RT-PRC002-EN
Typical
Wiring
(12½-25 Ton)
RT-PRC002-EN
69
Dimensional
(12½ Ton)
High Efficiency
All dimensions are in inches.
Data
(12½, 15, 17½ Ton)
Standard Efficiency
Note: Duct flanges mount 7-7/16" down
inside the curb on the 1½" curb flanges.
See recommended duct dimensions on
the next page.
Roofcurb is intended for downflow use
only.
Downflow Unit Clearance
70
RT-PRC002-EN
Dimensional
(12½ Ton) High Efficiency
All dimensions are in inches.
Downflow Duct Connections — Field Fabricated
7 7/16"
Data
14 1/16"
59 7/16"
RETURN
(12½, 15, 17½ Ton)
Standard Efficiency
1"
17 7/8"
52 1/2"
26 5/16"
SUPPLY
1"
1 1\2"
PERIMETER
CURB FLANGE
Note:
Duct flanges mount 7-7/16" down inside
the curb on the 1½" curb flanges.
Roofcurb is intended for downflow use
only.
Horizontal Unit Supply/Return and Unit Clearance
RT-PRC002-EN
71
Dimensional
(15-25 Ton) High Efficiency
All dimensions are in inches.
Data
(20, 25 Ton)
Standard Efficiency
Note:
Duct flanges mount 7-7/16" down inside
the curb on the 1½" curb flanges. See
recommended duct dimensions on the
next page.
Roofcurb is intended for downflow use
only.
72
Downflow Unit Clearance
RT-PRC002-EN
Dimensional
RETURN
SUPPLY
1 1\2"
PERIMETER
CURB FLANGE
73 7/16"
19 5/16"
26 5/16"
66 1/2"
1"
14 1/16"
7 7/16"
1"
(15-25 Ton) High Efficiency
All dimensions are in inches.
Downflow Duct Connections — Field Fabricated
Data
(20, 25 Ton)
Standard Efficiency
Note: Duct flanges mount 7-7/16" down
inside the curb on the 1½" curb flanges.
Roofcurb is intended for downflow use
only.
Horizontal Unit Supply/Return and Unit Clearance
RT-PRC002-EN
73
Dimensional
(12½-25 Ton)
All dimensions are in inches.
Data
Accessories
Note:
When applying economizer to horizontal units,
connecting ductwork must be run full size to
allow proper operation of Economizer Damper.
1. Horizontal dimension only. Downflow economizer is width
of end panel.
2. Power exhaust is applied on downflow economizer only.
1
2
C
RT-PRC002-EN
Dimensional
Factory Installed
All dimensions are in inches.
Data
Options (FIOPS)
Table DD-2
Unit
Model #ABC
TCD150, 151, 180, 21042
TCD181, 211-301291/256381/2
3/
3/
8
8
48
31
RT-PRC002-EN
75
Dimensional
Factory Installed
Hinged Access Door
Data
Fan Failure Switch
Clogged Filter Switch
Options (FIOPS)
Disconnect Switch
or Circuit Breaker
Powered or Unpowered
Convenience Outlet
Trane Communication Interface
Black Epoxy Coated
Outdoor Coils
Through the Base Electrical
Hinged Access Door
High Pressure Cut Out
76
Supply and/or Return Smoke Detectors
RT-PRC002-EN
Dimensional
Data
(12½-25 Ton)
Table DD-3 — Standard Efficiency Units
CondensateCondensate Drain Location
TonsDownflow OnlyDrain SizeDownflowHorizontal
ABCDF G HEJ EK
12½, 15, 17½26
20, 2526
7/
16
7/
16
1/
11/
2
22
18
3/
15/
4
28
19
1/
16
4
16
4
1/
4
4
4
1/
1/
4
4
4
7/
16
62
5/
16
76
11/
16
54
11/
16
68
1 NPT—25
1 NPT—26
5/
8
3/
4
Table DD-4 — High Efficiency Units
CondensateCondensate Drain Location
TonsDownflow OnlyDrain SizeDownflowHorizontal
ABCDF G HEJ EK
12½26
15-2526
RT-PRC002-EN
7/
16
7/
16
1/
22
28
11/
18
2
3/
15/
19
4
1/
4
16
4
16
1/
4
4
1/
4
1/
4
4
4
7/
62
16
5/
76
16
11/
54
16
11/
68
16
1 NPT—25
1 NPT—26
5/
8
3/
4
—6
3/
8
—5
—6
3/
—5
8
77
Weights
(12½-25 Ton)
Table W-1 — Accessory Net Weights (Lbs)
1, 7
OversizedHigh5Low
Model No. NetManualMotorizedExhaust
EconomizerOutside Air DamperPowerRoofMotorStaticStatic
4
Curb
4
AdderDriveDrive
TCD150D, 180B
TCD121,151C, TCD210C65326095205522
TCD240B
TCD181,211,241C8032759523552—
TCD300B.301C80327595235N/AN/A2
TCH150D, 180B, 210C
TCH121,151C503260——522
TCH240B
TCH181,211,241C653275——52—
TCH300B,301C653275——N/AN/A2
Table W-1 Continued
UnitAll Zone6-23 KW27-36 KW54 KW72 KW
Model No.Sensors240/480V
TCD150D, 180B, 210C128/21
23
6
TCD121,151,181C
TCD240B1—33/2740/3243/34
TCD211,241C
TCD300B,301C1—33/2740/3243/34
TCH150D, 180B, 210C128/21
6
TCH121,151,181C
TCH240B1—33/2740/3243/34
TCH211, 241C
TCH300B, 301C1—33/2740/3243/34
Notes:
1. Net weight should be added to unit weight when ordering factory installed accessories.
2. For 600V heaters net weights are same as 480V heaters.
3. To estimate shipping weight add 5 lbs to net weight.
4. Downflow only.
5. Not available on all models (See Fan Performance tables for specific models).
6. 9 - 23 KW Heaters not available for TC*210C.
7. TC*150-300 factory installed options for economizers, multiply net capacity x .99, EER x .97. For oversized motors, multiply net capacity x .98, EER x .93.
This is provided in compliance with ARI certification program.
Electric Heaters
240/480V
23
240/480V
23
31/2738/32—
31/2738/32—
240/480V
5
23
78
RT-PRC002-EN
Weights
Table W-2 — Maximum Unit And Corner Weights (Lbs) And Center Of Gravity Dimensions (In.)
1. Corner weights are given for information only. 12½-25 ton models must be supported continuously by a curb or equivalent frame support.
2. Weights are approximate. Horizontal and downflow unit and corner weights may vary slightly.
UnitMaximum Weights (Lbs)Corner Weights (Lbs)
2
NetABCDLengthWidth
1
Center of Gravity (In.)
*Indicates both downflow and horizontal units.
RT-PRC002-EN
79
Weights
Table W-3 — Factory Installed Options (FIOPS) Net Weights (Lbs)
AccessoryWeightUnit Model Number
High Efficiency Motors
Hinged Doors27All TC* units
Powered Convenience Outlet38All TC* units
Through the Base Electrical23All TC* units
Unit Mounted Circuit Breaker5All TC* units except those with 54&72 kW heaters
Unit Mounted Disconnect5All TC* units except those with 54&72 kW heaters
Smoke Detectors
Supply/Return5All TC* units
Tool-less Hail Guard38TC*150,151,180,210
Novar 20247All TC* units
Novar 30515All TC* units
Notes:
1. Weights for FIOP accessories not listed are >5 lbs.
2. Net weight should be added to unit weight when ordering factory installed accessories.
3. See Table W-1 for standard factory installed economizer and oversized motors.
4. Standard factory installed motors are already included in unit net and shipping weights. Values shown for high
efficiency motors are in addition to the standard motor weight.
4
49TC*150-181 standard size motor
36
0
10All TC* units with 54&72 kW heaters & 208/230V
10All TC* units with 54&72 kW heaters & 208/230V
43TC*181,211,240,241,300,301
TC*210-241 standard size motor
TC*150-181 oversize motor
TC*210-241 oversize motor
TC*300-301 standard size motor
& 208/230V
& 208/230V
1,2,3
80
RT-PRC002-EN
Mechanical
Specifications
General
The units shall be dedicated downflow or
horizontal airflow. The operating range
shall be between 115°F and 0°F in cooling
as standard from the factory for all units.
Cooling performance shall be rated in
accordance with ARI testing procedures.
All units shall be factory assembled,
internally wired, fully charged with R-22,
and 100 percent run tested to check
cooling operation, fan and blower rotation
and control sequence, before leaving the
factory. Wiring internal to the unit shall be
colored and numbered for simplified
identification. Units shall be UL listed and
labeled, classified in accordance to UL
1995/CAN/CSA No. 236-M90 for Heat
Pumps. Canadian units shall be CSA
Certified.
Casing
Unit casing shall be constructed of zinc
coated, heavy gauge, galvanized steel.
Exterior surfaces shall be cleaned,
phosphatized, and finished with a
weather-resistant baked enamel finish.
Unit’s surface shall be tested 500 hours in
a salt spray test in compliance with ASTM
B117. Cabinet construction shall allow for
all maintenance on one side of the unit. In
order to ensure a water and air tight seal,
service panels shall have lifting handels
and no more thatn three screws to
remove. All exposed vertical panels and
top covers in the indoor air section shall
be insulated with a 1/2 inch, 1 pound
density foil-faced, fire-resistant,
permanent, odorless, glass fiber material.
The base of the downflow unit shall be
insulated with 1/2 inch, 1 pound density
foil-faced, closed-cell material. The
downflow unit’s base pan shall have no
penetrations within the perimeter of the
curb other than the raised 1
supply/return openings to provide an
added water integrity precaution, if the
condensate drain backs up. The base of
the unit shall have provisions for forklift
and crane lifting.
1
/8 inch high
Unit Top
The top cover shall be one piece, or
where seams exist, double hemmed and
gasket sealed to prevent water leakage.
Filters
Two inch standard filters shall be factory
supplied on all units. Optional two inch
pleated media filters shall be available.
Compressors
All units shall have direct-drive, hermetic,
scroll type compressors with centrifugal
type oil pumps. Motor shall be suction
gas-cooled and shall have a voltage
utilization range of plus or minus 10
percent of nameplate voltage. Internal
overloads shall be provided with the
scroll compressors. All models shall have
crankcase heaters, low and high pressure
controls as standard.
Refrigerant Circuits
Each refrigerant circuit shall have
independent fixed orifice or thermostatic
expansion devices, service pressure
ports, and refrigerant line filter driers
factory installed as standard. An area
shall be provided for replacement suction
line driers.
Evaporator and Condenser Coils
Internally finned, 3/8" copper tubes
mechanically bonded to a configured
aluminum plate fin shall be standard.
Coils shall be leak tested at the factory to
ensure the pressure integrity. The
evaporator coil and condenser coil shall
be leak tested to 200 psig and pressure
tested to 450 psig. All dual compressor
units shall have intermingled evaporator
coils. Sloped condensate drain pans are
standard. Patent-pending 1+1+1
condenser coil, permanently gapped for
easy cleaning is available.
Gas Heating Section
The heating section shall have a drum
and tube heat exchanger design using
corrosion resistant steel components. A
forced combustion blower shall supply
premixed fuel to a single burner ignited
by a pilotless hot surface ignition system.
In order to provide reliable operation, a
negative pressure gas valve shall be
used that requires blower operation to
initiate gas flow. On an initial call for heat,
the combustion blower shall purge the
heat exchanger 45 seconds before
ignition. After three unsuccessful ignition
attempts, the entire heating system shall
be locked out until manually reset at the
thermostat. Units shall be suitable for use
with natural gas or propane (field
installed kit) and shall also comply with
California requirements for low NOx
emissions. The 12½-25 tons shall have
two stage heating.
Outdoor Fans
The outdoor fan shall be direct-drive,
statically and dynamically balanced,
draw-through in the vertical discharge
position. The fan motor(s) shall be
permanently lubricated and shall have
built-in thermal overload protection.
Indoor Fan
Units above shall have belt driven, FC
centrifugal fans with adjustable motor
sheaves. Units with standard motors
shall have an adjustable idler-arm
assembly for quick-adjustment of fan
belts and motor sheaves. All motors shall
be thermally protected. Oversized motors
shall be available for high static
application. All indoor fan motors meet
the U.S. Energy Policy Act of 1992
(EPACT).
RT-PRC002-EN
81
Mechanical
Specifications
Controls
Unit shall be completely factory wired
with necessary controls and contactor
pressure lugs or terminal block for power
wiring. Unit shall provide an external
location for mounting a fused disconnect
device. ReliaTel controls shall be provided
for all 24 volt control functions. The
resident control algorithms shall make all
heating, cooling, and/or ventilating
decisions in response to electronic signals
from sensors measuring indoor and
outdoor temperatures. The control
algorithm maintains accurate
temperature control, minimizes drift from
set point, and provides better building
comfort. A centralized control shall
provide anti-short cycle timing and time
delay between compressors to provide a
higher level of machine protection.
Defrost Controls
Adaptive demand defrost shall be
provided to permit defrost wherever coil
icing conditions begin to significantly
reduce unit capacity.
Factory Installed Options
Black Epoxy Coated Pre-Coated Coils
The black epoxy coils have a thermoset
vinyl coating that is bonded to the
aluminum fin stock prior to the finstamping process. The pre-coated coils
are an economical option for protection in
mildly corrosive environments.
Dehumidification Option
The dehumidification (hot gas reheat)
option shall provide increased
dehumidification. The option shall consist
of a hot-gas reheat coil located on the
leaving air side of the evaporator coil
prepiped and circuited. Low pressure
switch(es) and thermostatic expansion
valve(s) TXV are standard. Frostat™,
ReliaTel options module, and 2”pleated
filters are required but not standard. They
must be ordered and configured
separately.
Hinged Access Doors
Sheet metal hinges are available on the
Filter/Evaporator Access Door and the
Compressor/Control Access Door. This
option is available on all downflow
models.
High Efficiency Motors
This option is available with efficiency
ratings from 86.5 up to 91.0. It is not
available for all models.
High Pressure Cutout
This option is offered for units that do not
have High Pressure cutout as standard.
Powered or Unpowered Convenience
Outlet
This option is a GFCI, 120v/15amp, 2 plug,
convenience outlet, either powered or
unpowered. When the convenience outlet
is powered, a service receptacle
disconnect will be available. The
convenience outlet is powered from the
line side of the disconnect or circuit
breaker, and therefore will not be
affected by the position of the disconnect
or circuit breaker. This option can only be
ordered when the Through the Base
Electrical with either the Disconnect
Switch, or Circuit Breaker, option is
ordered. This option is available on all
downflow models.
Supply and/or Return Air Smoke
Detector
With this option installed, if smoke is
detected, all unit operation will be shut
down. Reset will be manual at the unit.
Return Air Smoke Detectors require
minimum allowable airflow when used
with certain models. See the Installation,
Operation, and Maintenance (IOM)
manual for the models affected and the
minimum allowable airflow required. This
option is available on all downflow
models.
Through the Base Electrical with Circuit
Breaker
This option is a thermal magnetic, molded
case, HACR Circuit Breaker with
provisions for through the base electrical
connections. The circuit breaker will be
installed in a water tight enclosure in the
unit with access through a swinging door.
Factory wiring will be provided from the
switch to the unit high voltage terminal
block. The circuit breaker will provide
overcurrent protection, be sized per NEC
and UL guidelines, and be agency
recognized by UL/CSA. This option is
available on all downflow models.
Through the Base Electrical With
Disconnect Switch
Three-pole, molded case, disconnect
switch with provisions for through the
base electrical connections are available.
The disconnect switch will be installed in
the unit in a water tight enclosure with
access through a swinging door. Factory
wiring will be provided from the switch to
the unit high voltage terminal block. The
switch will be UL/CSA agency recognized.
Note: The disconnect switch will be sized
per NEC and UL guidelines but will not be
used in place of unit overcurrent
protection. This option is available on all
downflow models.
Through the Base Utilities Access
An electrical service entrance shall be
provided allowing electrical access for
both control and main power connections
inside the curb and through the base of
the unit. Option will allow for field
installation of liquid-tight conduit and an
external field installed disconnect switch.
Two-Inch Pleated Filters
Two inch pleated media filters shall be
available on all models.
82
RT-PRC002-EN
Mechanical
Specifications
Factory or Field Installed
Options
Clogged Filter/Fan Failure Switch
A dedicated differential pressure switch is
available to achieve active fan failure
indication and/or clogged filter indication.
These indications will be registered with
either a zone sensor with status indication
lights or an Integrated Comfort™ System.
Differential Pressure Switches
These options allow for individual fan
failure and dirty filter indication. The fan
failure switch will disable all unit functions
and “flash” the Service LED on the zone
sensor. The dirty filter switch will light the
Service LED on the zone sensor and will
allow continued unit operation.
Discharge Air Sensing Kit
This kit provides true discharge air
sensing in heating models. This sensor is
a status indicator readable through
Tracer™or Tracker™. The kit is functional
only with the ReliaTel Options Module.
Economizer - Downflow
The assembly includes fully modulating
0-100 percent motor and dampers,
barometric relief, minimum position
setting, preset linkage, wiring harness
with plug, fixed dry bulb and spring return
actuator. The barometric relief damper
shall be standard with the downflow
economizer and shall provide a pressure
operated damper that shall be gravity
closing and shall prohibit entrance of
outside air during the equipment “off”
cycle. Solid state enthalpy and differential
enthalpy control shall be field-installed
Electric Heaters
Electric heat modules shall be available
for installation within the basic unit.
Electric heater elements shall be
constructed of heavy-duty nickel
chromium elements internally delta
connected for 240 volt, wye connected
for 480 and 600 volt. Staging shall be
achieved through ReliaTel. Each heater
package shall have automatically reset
high limit control operating through
heating element contactors. All heaters
shall be individually fused from the
factory, where required, and shall meet
all NEC and CEC requirements when
properly installed. Power assemblies
shall provide single-point connection.
Electric heat modules shall be UL listed or
CSA certified. If ordering the Through the
Base Electrical option with an Electric
Heater, the heater must be factory
installed.
Frostat
This option is to be utilized as a safety
device. The Frostat opens when
temperatures on the evaporator coil fall
below 10°F. The temperature will need to
rise to 50°F before closing. This option
should be utilized in low airflow or high
outside air applications.
LonTalk® Communications Interface
The LonTalk communications interface,
when installed in a Voyager unit, allows
the unit to communicate as a Tracer™LCIV device or directly with generic LonTalk
Network Building Automation System
Controls.
Oversized Motors
Oversized motors shall be available for
high static applications.
Reference or Comparative Enthalpy
Reference Enthalpy is used to measure
and communicate outdoor humidity. The
unit receives and uses this information to
provide improved comfort cooling while
using the economizer. Comparative
Enthalpy measures and communicates
humidity for both outdoor and return air
conditions, and return air temperature.
The unit receives and uses this
information to maximize use of
economizer cooling, and to provide
maximum occupant comfort control.
Reference or Comparative Enthalpy
option shall be available when a factory
or field installed Downflow Economizer is
ordered. This option is available on all
downflow models.
Tool-less Hail Guards
Tool-less, hail protection quality coil
guards are available for condenser coil
protection.
Trane Communication Interface
This factory or field-installed option shall
be provided to interface ReliaTel™
controlled units with the Trane Integrated
Comfort
TM
systems.
RT-PRC002-EN
83
Mechanical
Specifications
Field Installed Options
CO2 Sensing
The CO2 sensor has the ability to monitor
space occupancy levels within the
building by measuring the parts per
million of CO
As the CO
damper modulates to meet the CO
space ventilation requirements.
Digital Display Zone Sensor
The Digital LCD (Liquid Crystal Display)
zone sensor has the look and functionality
of standard zone sensors. This sensor
includes a digital display of set point
adjustment and space temperature in F
(Fahrenheit) or C (Celsius). Includes FAN
and SYSTEM buttons (supports the
service functions of the standard sensor).
E-squared memory stores last
programmed set points. Requires 24 VAC
(Volts AC). This sensor should be utilized
with ReliaTel™ controls.
Dual Thermistor Remote Zone Sensor
This sensor will allow the customer to
reduce the total number of remote
sensors to obtain space temperature
averaging. This sensor should be utilized
with ReliaTel controls.
High Static Drive
The high static drive option shall allow the
standard motor on the 12½ and 20 ton
units to operate with improved external
static capabilities.
Manual Outside Air Damper
The rain hood and screen shall provide
up to 25 percent outside air.
Motorized Outside Air Dampers
Manually set outdoor air dampers shall
provide up to 50 percent outside air. Once
set, outdoor air dampers shall open to set
position when indoor fan starts. The
damper shall close to the full closed
position when indoor fan shuts down.
(Carbon Dioxide) in the air.
2
levels increase, the outside air
2
2
Powered Exhaust
The powered exhaust shall provide
exhaust of return air, when using an
economizer, to maintain better building
pressurization.
Roof Curb - Downflow
The roof curb shall be designed to mate
with the downflow unit and provide
support and a water tight installation
when installed properly. The roof curb
design shall allow field-fabricated
rectangular supply/return ductwork to be
connected directly to the curb. Curb
design shall comply with NRCA
requirements. Curb shall be shipped
knocked down for field assembly and
shall include wood nailer strips.
Economizer - Horizontal
The horizontal economizer shall contain
the same features as the downflow
economizer with the exception of
barometric relief.
Remote Potentiometer
The minimum position setting of the
economizer shall be adjusted with this
accessory.
Ventilation Override Accessory
With the Ventilation Override Accessory
installed, the unit can be set to transition
up to 3 different pre-programmed
sequences for Smoke Purge,
Pressurization, and Exhaust. The
transition occurs when a binary input on
the RTOM is closed (shorted). This would
typically be a hard wired relay output
from a smoke detector or fire control
panel.
Zone Sensors
This option shall be provided to interface
with the Micro equipped Voyagers and
shall be available in either manual,
automatic, programmable with night
setback, with system malfunction lights or
remote sensor options.
84
RT-PRC002-EN
RT-PRC002-EN
85
86
RT-PRC002-EN
RT-PRC002-EN
87
Trane
A business of American Standard Companies
www.trane.com
For more information contact your local dealer
(distributor), local district office, or e-mail us at
comfort@trane.com
Literature Order Number
File Number
Supersedes
Stocking Location
RT-PRC002-EN
PL-UN-RT-TCD/TCH12½-25TONS-PRC002-EN-10-04
PL-UN-RT-TCD/TCH12½-25TONS-PRC002-EN-09-04
09-04 Webb/Mason 10-04 Electronic Only
Trane has a policy of continuous product and product data improvement and reserves the right to change design
and specifications without notice.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.