Sintesis chillers are part of the Ingersoll Rand EcoWise™ portfolio
of products that are designed to lower their environmental
impact with next-generation, low global warming potential
(GWP) refrigerants and high effi ciency operation.
These instructions are given as a guide to good practice in
the installation, start-up, operation, and maintenance by
the user, of Trane RTAF chillers, manufactured in France. A
separate manual is available for the use and maintenance
of the unit’s control, Tracer™ UC800. They do not contain full
service procedures necessary for the continued successful
operation of this equipment. The services of a qualified
technician should be employed through the medium of a
maintenance contract with a reputable service company.
Read this manual thoroughly before unit start-up.
Units are assembled, pressure tested, dehydrated, charged
and tested in accordance with factory standard before
shipment.
Warnings and Cautions
Warnings and Cautions appear at appropriate sections
throughout this manual. Your personal safety and the
proper operation of this machine require that you follow
them carefully. The constructor assumes no liability
for installations or servicing performed by unqualified
personnel.
WARNING: Indicates a potentially hazardous situation
which, if not avoided, could result in death or serious injury.
CAUTION: Indicates a potentially hazardous situation
which, if not avoided, may result in minor or moderate
injury. It may also be used to alert against unsafe practices
or for equipment or property-damage-only accidents.
Safety Recommendations
To avoid death, injury, equipment or property damage, the
following recommendations should be observed during
maintenance and service visits:
1. The maximum allowable pressures for system leak testing
on low and high pressure side are given in the chapter
“Installation”. Insure to do not exceed test pressure by using
appropriate device.
2. Disconnect all power supplies before any servicing on
the unit.
3. Service work on the refrigeration system and the
electrical system should be carried out only by qualified and
experienced personnel.
4. To avoid any risk, it is recommended to place the unit on
an area with limited access.
Reception
On arrival, inspect the unit before signing the delivery note.
Specify any visible damage on the delivery note, and send
a registered letter of protest to the last carrier of the goods
within 7 days of delivery.
Notify the local TRANE sales office at the same time.
The delivery note must be clearly signed and countersigned
by the driver.
Any concealed damage shall be notified by a registered
letter of protest to the last carrier of the goods within
7 days of delivery. Notify the local TRANE sales office
at the same time.
Important notice: No shipping claims will be accepted by
TRANE if the above mentioned procedure is not respected.
For more information, refer to the general sales conditions
of your local TRANE sales office.
Note: Unit inspection in France. Delay to send registered
letter in case of visible and concealed damage is only
72 hours.
Loose Parts Inventory
Check all the accessories and loose parts that are shipped
with the unit against the shipping list. Included in these
items will be the water vessel drain plugs, rigging and
electrical diagrams, service literature, which are placed
inside the control panel and/or starter panel for shipment.
If optional elastomeric isolators are ordered with the unit
(model number digit 42 =1) they are shipped mounted on
the horizontal support frame of the chiller. The isolators’
location and distribution weight diagram is placed with
the service literature inside the starter/control panel.
Warranty
Warranty is based on the general terms and conditions of
the manufacturer. The warranty is void if the equipment is
repaired or modified without the written approval of the
manufacturer, if the operating limits are exceeded or if the
control system or the electrical wiring is modified. Damage
due to misuse, lack of maintenance or failure to comply
with the manufacturer’s instructions or recommendations
is not covered by the warranty obligation. If the user does
not conform to the rules of this manual, it may entail
cancellation of warranty and liabilities by the manufacturer.
Startup MUST be performed by Trane, or an authorized
agent of Trane, to VALIDATE this WARRANTY. Contractor
must provide a two-week startup notification to Trane (or an
agent of Trane specifically authorized to perform startup).
Unit Description
The Sintesis RTAF units are helical-rotary type, air-cooled
chillers designed for outdoor installation. The refrigerant
circuits are factory-piped, leak tested and dehydrated. Every
unit is electrically tested for proper control operation before
shipment.
Chilled water inlet and outlet openings are covered for
shipment. The Sintesis RTAF features Trane’s exclusive
Adaptive Control™ logic, which monitors the control
variables that govern the operation of the chiller unit.
Adaptive control logic can adjust capacity variables to avoid
chiller shutdown when necessary, and keep producing
chilled water. The units feature two independent refrigerant
circuits. On the HSE HSS version, 1 compressor per circuit
is controlled by a dedicated variable speed Adaptive
Frequency Drive. Each refrigerant circuit is provided
with filter, sight glass, electronic expansion valve, and
charging valves. The shell-and-tube CHIL™ (Compact-High
performance-Integrated design-Low charge) evaporator is
manufactured in accordance with the Pressure Equipment
Directive (PED) code. Each evaporator is fully insulated and
equipped with water drain and vent connection.
Units are shipped with full oil charge and can be ordered
with either a factory refrigerant charge or optional
refrigerant pre-charge.
4
RLC-SVX19G-GB
Page 5
Inspection
When the unit is delivered, verify that it is the correct
unit and that it is properly equipped.
Inspect all exterior components for visible damage.
Report any apparent damage or material shortage to
the carrier and make a “unit damage” notation on the
carrier’s delivery receipt. Specify the extent and type of
damage found and notify the appropriate Trane Sales
Office.
Do not proceed with installation of a damaged unit
without sales office approval.
Inspection Checklist
To protect against loss due to damage incurred in transit,
complete the following checklist upon receipt of the unit.
• Inspect the individual pieces of the shipment before
accepting the unit. Check for obvious damage to the
unit or packing material.
• Inspect the unit for concealed damage as soon as
possible after delivery and before it is stored.
Concealed damage must be reported within 10 days
after receipt.
• If concealed damage is discovered, stop unpacking
the shipment. Do not remove damaged material from
the receiving location. Take photos of the damage, if
possible. The owner must provide reasonable evidence
that the damage did not occur after delivery.
• Notify the carrier’s terminal of the damage
immediately, by phone and by mail. Request an
immediate, joint inspection of the damage with the
carrier and the consignee.
• Notify the Trane sales representative and arrange for
repair. Do not repair the unit, however, until damage is
inspected by the transportation representative.
Pre-Installation
Storage
Extended storage of the unit prior to the installation
requires the following precautions:
Store the unit in a secured area, to avoid intentional
damages.
Close the suction, discharge and liquid-line isolation
valves.
At least every three months (quarterly), check the
pressure in the refrigerant circuits to verify that the
refrigerant charge is intact. If it is not, contact a qualified
service organization and the appropriate Trane sales
office.
Note: If the unit is stored before servicing near a
construction site it is highly recommended to protect
micro-channel coils from any concrete dust. Failure to do
so may considerably reduce reliability of the unit.
RLC-SVX19G-GB
5
Page 6
Pre-Installation
Installation Requirements
A list of the contractor responsibilities typically associated with the unit installation process is provided in Table 1.
Table 1 – Installation requirements
Type
Foundation• Meet foundation requirements
Rigging
Isolation
Electrical
Water piping• Flow switch
Insulation• Insulation• Insulation
Water Piping Connection Components• Grooved pipe
Other Materials
“Sintesis Model RTAF Installation
Completion Check Sheet and Request
for Trane Service”
Chiller Start-up Commissioning
(a)
Trane Supplied
Trane Installed
• Circuit breakers
(optional)
• Unit mounted
starter
• R-134a, R-513A
or R1234ze
refrigerant
• Full factory
charge or preload charge
• Dry nitrogen
(optional)
• Trane, or an
agent of Trane
specically
authorized to
perform startup of Trane®
products
Trane Supplied
Field Installed
• Elastomeric
isolators
(optional)
Field Supplied
Field Installed
• Safety chains
• Clevis connectors
• Lifting beam
• Spreader bar
• Elastomeric isolators (optional)
• Circuit breakers (optional)
• Electrical connections to unit mounted starter
• Wiring sizes per submittal and NEC
• Terminal lugs
• Ground connection(s)
• BAS wiring (optional)
• Control voltage wiring
• Chilled water pump contactor and wiring
• Option relays and wiring
• Taps for thermometers and gauges
• Thermometers
• Water ow pressure gauges
• Isolation and balancing valves in water piping
• Vents and drain
• Waterside pressure relief valves
• Water strainer
• Glycol for Glycol free conguration
(a)
Start-up must be performed by Trane or an agent of Trane specifically authorized to perform start-up and warranty of Trane® products. Contractor
shall provide Trane (or an agent of Trane specifically authorized to perform start-up) with notice of the scheduled start-up at least two weeks prior to the
scheduled start-up.
D = 400V/50Hz/3ph
4 = 460V/60Hz/3ph
J = 380V/60Hz/3ph
Digit 9 – Manufacturing Location
E = Europe
Digit 10, 11 – Design sequence
A0 = Factory assigned
RLC-SVX19G-GB
Digit 12 - Efficiency
N = Standard Efficiency
H = High Efficiency
A = Extra Efficiency
U = High Seasonal Short (HSS)
V = High Seasonal Efficiency
Digit 13 – Agency listing
C = CE Marking
Digit 14 – Pressure vessel code
2 = PED (Pressure equipment directive)
D = Australian code
Digit 15 – Acoustic level
X = Standard noise (SN)
L = Low noise (LN)
A = AC Extra Low Noise
Q = Low Noise with Night Noise SetBack (NNSB)
E = Extra Low Noise (XLN)
Digit 16 – Operating map : airside
X = Standard ambient
L = Low ambient
H = High ambient
Digit 17 – Relief valve option
L = Single Relief Valve High Pressure side
D = Dual Relief Valve with 3 way valve High Pressure side
Digit 18 – Water connection
X = Grooved pipe connection
W = Grooved pipe with coupling and pipe stub
Digit 19 – Operating map water side
N = Comfort cooling (above 4.4°C)
P = Process cooling (below 4.4°C) (Brine application)
C = Ice Making (-7°C to 20°C)
Digit 20 – Evaporator Configurations
2 = Standard pass evaporator
T = Standard Pass Evaporator + Turbulators
Digit 21 – Thermal Insulation
N = Standard
H = High performance
X = None
Digit 22 – Condenser Coating
N = Aluminum Micro Channel
C = E-Coated Micro Channel (Free Cooling excluded)
Digit 23 - Heat Recovery
X = No Heat Recovery
P = Partial Heat Recovery
Q = Partial Heat Recovery with on site fan control (PHR +)
T = Total Heat Recovery (full equipment)
V = Total Heat Recovery (no piping connection)
Digit 24 – Hydraulic module
X = Pump signal On/Off
1 = Dual pump standard pressure
3 = Dual pump high pressure
Digit 25 - Free Cooling
X = No Free Cooling
F = Total Free-Cooling Direct
G = Partial Free-cooling Direct
H = Total Free Cooling Glycol Free
J = Partial Free Cooling Glycol Free
7
Page 8
Unit Model Number Description
Digit 26 – Disconnect switch
F = With Fuse
B = With circuit breaker
Digit 27 – Under/Over Voltage
X = None
1 = Included
2 = Included with ground fault protection
Digit 28 – Human Interface language
C = Spanish
D = German
E = English
F = French
H = Dutch
I = Italian
M = Swedish
P = Polish
R = Russian
T = Czech
U = Greek
V = Portuguese
2 = Romanian
6 = Hungarian
8 = Turkish
Digit 29 – Smart com protocol
X = None
B = Bacnet interface
M = Modbus interface
L = LonTalk interface
Digit 30 – Communication customer
X = None
A = External set point & capacity outputs
Digit 31 – Flow switch
X = None
F = Field installed flow switch
Digit 32 – Electrical Panel Protection
X = Enclosure with deadfront protection
1 = Enclosure with IP 20 internal protection
Digit 33 – Master Slave
X = Open for Future Use
Digit 34 – Unit User Interface
L = Standard, Local UI supplied (TD7)
Digit 35 – Energy meter
X = No energy meter
M = Energy meter installed
Digit 36 – Open for future use = X
Digit 37 – Variable Primary Flow
X = None
F = Constant Speed Pump -AFD Adjustment
P = Variable Speed Pump - Constant delta P
T = Variable Speed Pump - Constant delta T
Digit 38 – Open for future use = X
Digit 39 – Open for future use = X
Digit 40 – Power socket
X = None
P = Included (230V - 100W)
Digit 41 – Factory tests
X = No final performances test
B = Visual inspection with customer
E = Performance test w/o customer
Digit 42 – Installation accessory
X = None
1 = Neoprene Isolators
4 = Neoprene pads
Digit 43 – Literature language
B = Bulgarian
C = Spanish
D = German
E = English
F = French
H = Dutch
I = Italian
K = Finnish
L = Danish
M = Swedish
N = Norvegian
P = Polish
R = Russian
T = Czech
U = Greek
V = Portuguese
Z = Slovenian
2 = Romanian
3 = Serbian
4 = Slovak
5 = Croatian
6 = Hungarian
8 = Turkish
Digit 44 – Shipping package
X = Standard protection
A = Containerization package
Digit 45 – Refrigerant
0 = R134a Factory pre-charge
1 = R134a Factory full refrigerant charge
2 = R513A Factory pre-charge
3 = R513A Factory full refrigerant charge
L = Factory Nitrogen Charge for R1234ze unit
M = Factory Nitrogen Charge for R513A unit
N = Factory Nitrogen Charge for R134a unit
Y = R1234ze Factory pre-charge
Z = R1234ze Factory full refrigerant charge
Digit 46 – Open for future use = X
Digit 47 – Open for future use = X
Digit 48 – Design special
X = none
S = special
8
RLC-SVX19G-GB
Page 9
General Data
Table 2a – General Data RTAF 090-245 Standard Efficiency - Standard and Low Noise (SN&LN) - R134a - R513A
(1) Indicative performance at Evaporator water temperature: 12°C / 7°C - Condenser air temperature 35°C - for detailed performances consult
Order Write Up.
(2) Under 400V/3/50Hz.
(3) Rated Condition without Pump Package.
(4) Percent minimum load may be adjusted around 15%-20% according to operating conditions by local sales office.
(5) Electrical & system data are indicative and subject to change without notice. Please refer to unit nameplate data.
(6) Not applicable for Glycol application - see tables with Minimum Flow with Glycol.
(7) Max speed - range is 60% to 100% of max speed.
(8) Refrigerant charge may vary according to option - for instance +20% for process (digit 19 = p). For real value refer to unit nameplate.
(9) Data containing information on two circuits shown as follows: ckt1/ckt2.
(10) Size 245 not avalaible in R513A.
10
RLC-SVX19G-GB
Page 11
General Data
Table 2b – General Data RTAF 090-185 Standard Efficiency - Standard and Low Noise (SN&LN) - R1234 ze
RTAFRTAFRTAFRTAFRTAFRTAFRTAFRTAF
090100110120130145155185
Cooling Capacity (1)(kW)325357387419450502544602
Unit electrical data (2) (3) (4)
Maximum Power input in cooling(kW)162176190201212242269273
Unit rated amps (Max compressor+fan+control)(A)272295318339360409450458
Unit start up amps starting Amps of the larges compr+RLA
of 2nd compr+RLA of all fans+control)
Displacement Power Factor (DPF)0.870.870.870.880.850.860.870.87
Max power cable cross section mm
Disconnect switch size(A)400400500500500630630630
Compressor
Quantity#22222222
TypeScrewScrewScrewScrewScrewScrewScrewScrew
Model (9)45/4555/4555/5565/5565/6578/6578/7878/78
Max Compr Power input (Circuit 1 / Circuit 2)kW73/7387/7387/8798/8798/98125/98125/125125/125
Max Amps Circuit1 / Circuit 2 (3) (5)(A)119/119142/119142/142163/142163/163204/163204/204204/204
Start up Amps Circuit1 / Circuit 2 (3)(5)(A)217/217259/217259/259291/259 291/291354/291354/354354/354
Motor RPM(rpm)30003000300030003000300030003000
Oil sump heater Circuit1 / Circuit 2(W)150/150
Evaporator
Quantity#11111111
TypeFlooded shell and tube heat exchanger
Evaporator model115B115A115A165C165B200C200C200B
Evaporator Water Content volume(l)5158586474898999
(1) Indicative performance at Evaporator water temperature: 12°C / 7°C - Condenser air temperature 35°C - for detailed performances consult
Order Write Up.
(2) Under 400V/3/50Hz.
(3) Rated Condition without Pump Package.
(4) Percent minimum load may be adjusted around 15%-20% according to operating conditions by local sales office.
(5) Electrical & system data are indicative and subject to change without notice. Please refer to unit nameplate data.
(6) Not applicable for Glycol application - see tables with Minimum Flow with Glycol.
(7) Max speed - range is 60% to 100% of max speed.
(8) Refrigerant charge may vary according to option - for instance +20% for process (digit 19 = p). For real value refer to unit nameplate.
(9) Data containing information on two circuits shown as follows: ckt1/ckt2.
(10) OIL0066E or OIL0067E may have been used on early orders and there is no restriction to continue to use them but preferable oil is OIL00315 or
OIL00317.
SE SN LN SE SN LN SE SN LN SE SN LN SE SN LN SE SN LN SE SN LN SE SN LN
12
RLC-SVX19G-GB
Page 13
General Data
Table 3a – General Data RTAF 90-245 Standard Efficiency - Extra Low Noise (XLN) - R134a - R513A
(1) Indicative performance at Evaporator water temperature: 12°C / 7°C - Condenser air temperature 35°C - for detailed performances consult
Order Write Up.
(2) Under 400V/3/50Hz.
(3) Rated Condition without Pump Package.
(4) Percent minimum load may be adjusted around 15%-20% according to operating conditions by local sales office.
(5) Electrical & system data are indicative and subject to change without notice. Please refer to unit nameplate data.
(6) Not applicable for Glycol application - see tables with Minimum Flow with Glycol.
(7) Max speed - range is 60% to 100% of max speed.
(8) Refrigerant charge may vary according to option - for instance +20% for process (digit 19 = p). For real value refer to unit nameplate.
(9) Data containing information on two circuits shown as follows: ckt1/ckt2.
(10) Size 245 not avalaible in R513A.
14
RLC-SVX19G-GB
Page 15
General Data
Table 3b – General Data RTAF 090-185 Standard Efficiency - Extra Low Noise (XLN) - R1234 ze
RTAFRTAFRTAFRTAFRTAFRTAFRTAFRTAF
090100110120130145155185
Cooling Capacity (1)(kW)325357388419450502544603
Unit electrical data (2) (3) (4)
Maximum Power input in cooling(kW)163177191202213243270274
Unit rated amps (Max compressor+fan+control)(A)264287310331352399440446
Unit start up amps starting Amps of the larges compr+RLA
of 2nd compr+RLA of all fans+control)
Displacement Power Factor (DPF)0.890.890.890.880.870.880.890.89
Max power cable cross section mm
Disconnect switch size(A)400400500500500630630630
Compressor
Quantity#22222222
TypeScrewScrewScrewScrewScrewScrewScrewScrew
Model (9)45/4555/4555/5565/5565/6578/6578/7878/78
Max Compr Power input (Circuit 1 / Circuit 2)kW73/7387/7387/8798/8798/98125/98125/125125/125
Max Amps Circuit1 / Circuit 2 (3) (5)(A)119/119142/119142/142119/142119/163119/163204/204204/204
Start up Amps Circuit1 / Circuit 2 (3)(5)(A)217/217259/217259/259291/259 291/291354/291354/354354/354
Motor RPM(rpm)30003000300030003000300030003000
Oil sump heater Circuit1 / Circuit 2(W)150
Evaporator
Quantity#11111111
TypeFlooded shell and tube heat exchanger
Evaporator model115B115A115A165C165B200C200C200B
Evaporator Water Content volume(l)5158586474898999
(1) Indicative performance at Evaporator water temperature: 12°C / 7°C - Condenser air temperature 35°C - for detailed performances consult
Order Write Up.
(2) Under 400V/3/50Hz.
(3) Rated Condition without Pump Package.
(4) Percent minimum load may be adjusted around 15%-20% according to operating conditions by local sales office.
(5) Electrical & system data are indicative and subject to change without notice. Please refer to unit nameplate data.
(6) Not applicable for Glycol application - see tables with Minimum Flow with Glycol.
(7) Max speed - range is 60% to 100% of max speed.
(8) Refrigerant charge may vary according to option - for instance +20% for process (digit 19 = p). For real value refer to unit nameplate.
(9) Data containing information on two circuits shown as follows: ckt1/ckt2.
(10) OIL0066E or OIL0067E may have been used on early orders and there is no restriction to continue to use them but preferable oil is OIL00315 or
OIL00317.
SE XLNSE XLNSE XLNSE XLNSE XLNSE XLNSE XLNSE XLN
16
RLC-SVX19G-GB
Page 17
General Data
Table 4a – General Data RTAF 090-245 Standard Efficiency - AC Extra Low Noise - R134a - R513A
(1) Indicative performance at Evaporator water temperature: 12°C / 7°C - Condenser air temperature 35°C - for detailed performances consult
Order Write Up.
(2) Under 400V/3/50Hz.
(3) Rated Condition without Pump Package.
(4) Percent minimum load may be adjusted around 15%-20% according to operating conditions by local sales office.
(5) Electrical & system data are indicative and subject to change without notice. Please refer to unit nameplate data.
(6) Not applicable for Glycol application - see tables with Minimum Flow with Glycol.
(7) Max speed - range is 60% to 100% of max speed.
(8) Refrigerant charge may vary according to option - for instance +20% for process (digit 19 = p). For real value refer to unit nameplate.
(9) Data containing information on two circuits shown as follows: ckt1/ckt2.
(10) Size 245 not avalaible in R513A.
18
RLC-SVX19G-GB
Page 19
General Data
Table 4b – General Data RTAF 090-185 Standard Efficiency - AC Extra Low Noise - R1234 ze
RTAFRTAFRTAFRTAFRTAFRTAFRTAFRTAF
090100110120130145155185
Cooling Capacity (1)(kW)328359389420451503545606
Unit electrical data (2) (3) (4)
Maximum Power input in cooling(kW)158.5172.5186.5197.5208.5238.4265.4268.3
Unit rated amps (Max compressor+fan+control)(A)263.7286.7309.7330.7351.7398.6439.5445.3
Unit start up amps starting Amps of the larges compr+RLA
of 2nd compr+RLA of all fans+control)
Displacement Power Factor (DPF)0.870.870.870.870.870.870.870.87
Max power cable cross section mm
Disconnect switch size(A)400400500500500630630630
Compressor
Quantity#22222222
TypeScrewScrewScrewScrewScrewScrewScrewScrew
Model (9)45/4555/4555/5565/5565/6578/6578/7878/78
Max Compr Power input (Circuit 1 / Circuit 2)kW73/7387/7387/8798/8798/98125/98125/125125/125
Max Amps Circuit1 / Circuit 2 (3) (5)(A)119/119142/119142/142163/142163/163204/163204/204204/204
Start up Amps Circuit1 / Circuit 2 (3)(5)(A)217/217259/217259/259291/259 291/291354/291354/354354/354
Motor RPM(rpm)30003000300030003000300030003000
Oil sump heater Circuit1 / Circuit 2(W)150/150
Evaporator
Quantity#11111111
TypeFlooded shell and tube heat exchanger
Evaporator model115B115A115A165C165B200C200C200B
Evaporator Water Content volume(l)5158586474898999
(1) Indicative performance at Evaporator water temperature: 12°C / 7°C - Condenser air temperature 35°C - for detailed performances consult
Order Write Up.
(2) Under 400V/3/50Hz.
(3) Rated Condition without Pump Package.
(4) Percent minimum load may be adjusted around 15%-20% according to operating conditions by local sales office.
(5) Electrical & system data are indicative and subject to change without notice. Please refer to unit nameplate data.
(6) Not applicable for Glycol application - see tables with Minimum Flow with Glycol.
(7) Max speed - range is 60% to 100% of max speed.
(8) Refrigerant charge may vary according to option - for instance +20% for process (digit 19 = p). For real value refer to unit nameplate.
(9) Data containing information on two circuits shown as follows: ckt1/ckt2.
(10) OIL0066E or OIL0067E may have been used on early orders and there is no restriction to continue to use them but preferable oil is OIL00315 or
OIL00317.
SE AC XLN SE AC XLN SE AC XLN SE AC XLN SE AC XLN SE AC XLN SE AC XLN SE AC XLN
20
RLC-SVX19G-GB
Page 21
General Data
Table 5a – General Data RTAF 090-245 High Efficiency - Standard and Low Noise - R134a - R513A
RTAFRTAFRTAFRTAFRTAFRTAFRTAFRTAFRTAF
090105125145155175190205245 (10)
HE SN LN HE SN LNHE SN LN HE SN LNHE SN LN HE SN LN HE SN LNHE SN LN HE SN LN
(1) Indicative performance at Evaporator water temperature: 12°C / 7°C - Condenser air temperature 35°C - for detailed performances consult
Order Write Up.
(2) Under 400V/3/50Hz.
(3) Rated Condition without Pump Package.
(4) Percent minimum load may be adjusted around 15%-20% according to operating conditions by local sales office.
(5) Electrical & system data are indicative and subject to change without notice. Please refer to unit nameplate data.
(6) Not applicable for Glycol application - see tables with Minimum Flow with Glycol.
(7) Max speed - range is 60% to 100% of max speed.
(8) Refrigerant charge may vary according to option - for instance +20% for process (digit 19=P). For real value refer to unit nameplate.
(9) Data containing information on two circuits shown as follows: ckt1/ckt2.
(10) Size 245 not avalaible in R513A.
(kg)43/4142/4045/4148/4650/4460/4662/5666/6266/62
22
RLC-SVX19G-GB
Page 23
General Data
Table 5b – General Data RTAF 090-185 High Efficiency - Standard and Low Noise - R1234 ze
RTAFRTAFRTAFRTAFRTAFRTAFRTAFRTAF
090100110120130145155185
Cooling Capacity (1)(kW)331365397430463512557614
Unit electrical data (2) (3) (4)
Maximum Power input in cooling(kW)165179193204215246273277
Unit rated amps (Max compressor+fan+control)(A)280303326347368417458466
Unit start up amps starting Amps of the larges compr+RLA
of 2nd compr+RLA of all fans+control)
Displacement Power Factor (DPF)0.860.860.860.860.850.860.870.86
Max power cable cross section mm
Disconnect switch size(A)400400500500500630630630
Compressor
Quantity#22222222
TypeScrewScrewScrewScrewScrewScrewScrewScrew
Model (9)45/4555/4555/5565/5565/6578/6578/7878/78
Max Compr Power input (Circuit 1 / Circuit 2)kW73/7387/7387/8798/8798/98125/98125/125125/125
Max Amps Circuit1 / Circuit 2 (3) (5)(A)119/119142/119142/142163/142163/163204/163204/204204/204
Start up Amps Circuit1 / Circuit 2 (3)(5)(A)217/217259/217259/259291/259 291/291354/291354/354354/354
Motor RPM(rpm)30003000300030003000300030003000
Oil sump heater Circuit1 / Circuit 2(W)150/150
Evaporator
Quantity#11111111
TypeFlooded shell and tube heat exchanger
Evaporator model115B115A115A165C165B200C200C200B
Evaporator Water Content volume(l)5158586474898999
(1) Indicative performance at Evaporator water temperature: 12°C / 7°C - Condenser air temperature 35°C - for detailed performances consult
Order Write Up.
(2) Under 400V/3/50Hz.
(3) Rated Condition without Pump Package.
(4) Percent minimum load may be adjusted around 15%-20% according to operating conditions by local sales office.
(5) Electrical & system data are indicative and subject to change without notice. Please refer to unit nameplate data.
(6) Not applicable for Glycol application - see tables with Minimum Flow with Glycol.
(7) Max speed - range is 60% to 100% of max speed.
(8) Refrigerant charge may vary according to option - for instance +20% for process (digit 19 = p). For real value refer to unit nameplate.
(9) Data containing information on two circuits shown as follows: ckt1/ckt2.
(10) OIL0066E or OIL0067E may have been used on early orders and there is no restriction to continue to use them but preferable oil is OIL00315 or
OIL00317.
SE AC XLN SE AC XLN SE AC XLN SE AC XLN SE AC XLN SE AC XLN SE AC XLN SE AC XLN
24
RLC-SVX19G-GB
Page 25
General Data
Table 6a – General Data RTAF 090-205 High Efficiency- AC Extra Low Noise - R134a - R513A
RTAFRTAFRTAFRTAFRTAFRTAFRTAFRTAF
090105125145155175190205
Cooling Capacity (1)(kW)330381450529572627683744
Unit electrical data (2) (3) (5)
Maximum Power input in cooling (kW)136157185216239262287310
Unit rated amps (Max compr +Fan+Control)(A)226264314370405444485524
Unit start up amps (Starting Amps of the largest compr+RLA
of 2nd compr+RLA of all fans+ control)
Displacement Power Factor (DPF) 0.880.860.860.850.860.850.860.86
Max power cable cross section(mm2)1x2401x2401x2402x3002x3002x3002x3002x300
Disconnect switch size(A)400400500630630800800800
Compressor
Quantity#22222222
TypeScrewScrewScrewScrewScrewScrewScrewScrew
Model (9)45/4550/5070/5070/7085/70100/70100/85100/100
Max Compr Power input Circuit 1/Circuit 2kW60/6071/7199/7199/99121/99144/99144/121144/144
Max Amps Circuit 1 / Circuit 2 (3) (5)(A)97/97116/116166/116166/166201/166240/166240/201240/240
Start up Amps Circuit 1 / Circuit 2 (3) (5)(A)144/144180/180291/180291/291354/291354/291354/354354/354
(1) Indicative performance at Evaporator water temperature: 12°C / 7°C - Condenser air temperature 35°C - for detailed performances consult
Order Write Up.
(2) Under 400V/3/50Hz.
(3) Rated Condition without Pump Package.
(4) Percent minimum load may be adjusted around 15%-20% according to operating conditions by local sales office.
(5) Electrical & system data are indicative and subject to change without notice. Please refer to unit nameplate data.
(6) Not applicable for Glycol application - see tables with Minimum Flow with Glycol.
(7) Max speed - range is 60% to 100% of max speed.
(8) Refrigerant charge may vary according to option - for instance +20% for process (digit 19 = p). For real value refer to unit nameplate.
(9) Data containing information on two circuits shown as follows: ckt1/ckt2.
HE AC XLN HE AC XLN HE AC XLN HE AC XLN HE AC XLN HE AC XLN HE AC XLN HE AC XLN
26
RLC-SVX19G-GB
Page 27
General Data
Table 6b – General Data RTAF 090-185 High Efficiency- AC Extra Low Noise - R1234 ze
RTAFRTAFRTAFRTAFRTAFRTAFRTAFRTAF
090100110120130145155185
Cooling Capacity (1)(kW)328360392424457506549607
Unit electrical data (2) (3) (4)
Maximum Power input in cooling(kW)161175189200211241268271
Unit rated amps (Max compressor+fan+control)(A)269292315336357404445451
Unit start up amps starting Amps of the larges compr+RLA
of 2nd compr+RLA of all fans+control)
Displacement Power Factor (DPF)0.870.870.870.860.860.870.870.87
Max power cable cross section mm
Disconnect switch size(A)400400500500500630630630
Compressor
Quantity#22222222
TypeScrewScrewScrewScrewScrewScrewScrewScrew
Model (9)45/4555/4555/5565/5565/6578/6578/7878/78
Max Compr Power input (Circuit 1 / Circuit 2)kW73/7387/7387/8798/8798/98125/98125/125125/125
Max Amps Circuit1 / Circuit 2 (3) (5)(A)119/119142/119142/142163/142163/163204/163204/204204/204
Start up Amps Circuit1 / Circuit 2 (3)(5)(A)217/217259/217259/259291/259 291/291354/291354/354354/354
Motor RPM(rpm)30003000300030003000300030003000
Oil sump heater Circuit1 / Circuit 2(W)150/150
Evaporator
Quantity#11111111
TypeFlooded shell and tube heat exchanger
Evaporator model115B115A115A165C165B200C200C200B
Evaporator Water Content volume(l)5158586474898999
(1) Indicative performance at Evaporator water temperature: 12°C / 7°C - Condenser air temperature 35°C - for detailed performances consult
Order Write Up.
(2) Under 400V/3/50Hz.
(3) Rated Condition without Pump Package.
(4) Percent minimum load may be adjusted around 15%-20% according to operating conditions by local sales office.
(5) Electrical & system data are indicative and subject to change without notice. Please refer to unit nameplate data.
(6) Not applicable for Glycol application - see tables with Minimum Flow with Glycol.
(7) Max speed - range is 60% to 100% of max speed.
(8) Refrigerant charge may vary according to option - for instance +20% for process (digit 19 = p). For real value refer to unit nameplate.
(9) Data containing information on two circuits shown as follows: ckt1/ckt2.
(10) OIL0066E or OIL0067E may have been used on early orders and there is no restriction to continue to use them but preferable oil is OIL00315 or
OIL00317.
HE AC XLN HE AC XLN HE AC XLN HE AC XLN HE AC XLN HE AC XLN HE AC XLN HE AC XLN
28
RLC-SVX19G-GB
Page 29
General Data
Table 7a – General Data RTAF 090-205 Extra Efficiency - Standard and Low Noise - R134a - R513A
RTAFRTAFRTAFRTAFRTAFRTAFRTAFRTAF
090105125145155175190205
XE SN LNXE SN LN XE SN LNXE SN LN XE SN LNXE SN LN XE SN LNXE SN LN
Cooling Capacity (1)(kW)326380447526569633690752
Unit electrical data (2) (3) (5)
Maximum Power input in cooling(kW)141.1162.3190.5222.6245.0267.9294.2317.1
Unit rated amps (Max compr +Fan+Control) (A)227265315371406445486525
Unit start up amps (Starting Amps of the largest
compr+RLA of 2nd compr+RLA of all fans+ control)
Unit Power factor0.900.890.880.870.870.870.880.87
Max power cable cross section (mm²)2402402402*3002*3002*3002*3002*300
Disconnect switch size(A)400400500630630630800800
Compressor
Quantity#22222222
TypeScrewScrewScrewScrewScrewScrewScrewScrew
Model (9)45/4550/5070/5070/7085/70100/70100/85100/100
Max Compr Power input Circuit 1/Circuit 2kW60/6071/7199/7199/99121/99144/99144/121144/144
Max Amps Circuit 1 / Circuit 2 (3) (5)(A)97/97116/116166/116166/166201/166240/166240/201240/240
Start up Amps Circuit 1 / Circuit 2 (3) (5)(A)144/144180/180291/180291/291354/291354/291354/354354/354
(1) Indicative performance at Evaporator water temperature: 12°C / 7°C - Condenser air temperature 35°C - for detailed performances consult
Order Write Up.
(2) Under 400V/3/50Hz.
(3) Rated Condition without Pump Package.
(4) Percent minimum load may be adjusted around 15%-20% according to operating conditions by local sales office.
(5) Electrical & system data are indicative and subject to change without notice. Please refer to unit nameplate data.
(6) Not applicable for Glycol application - see tables with Minimum Flow with Glycol.
(7) Max speed - range is 60% to 100% of max speed.
(8) Refrigerant charge may vary according to option - for instance +20% for process (digit 19=P). For real value refer to unit nameplate.
(9) Data containing information on two circuits shown as follows: ckt1/ckt2.
30
RLC-SVX19G-GB
Page 31
General Data
Table 7b – General Data RTAF 090-185 Extra Efficiency - Standard and Low Noise - R1234 ze
RTAFRTAFRTAFRTAFRTAFRTAFRTAFRTAF
090100110120130145155185
Cooling Capacity (1)(kW)328360395427459509552614
Unit electrical data (2) (3) (4)
Maximum Power input in cooling(kW)166180194205216247274278
Unit rated amps (Max compressor+fan+control)(A)270293316337358405446452
Unit start up amps starting Amps of the larges compr+RLA
of 2nd compr+RLA of all fans+control)
Displacement Power Factor (DPF)0.890.890.890.880.870.880.890.89
Max power cable cross section mm
Disconnect switch size(A)400400500500500630630630
Compressor
Quantity#22222222
TypeScrewScrewScrewScrewScrewScrewScrewScrew
Model (9)45/4555/4555/5565/5565/6578/6578/7878/78
Max Compr Power input (Circuit 1 / Circuit 2)kW73/7387/7387/8798/8798/98125/98125/125125/125
Max Amps Circuit1 / Circuit 2 (3) (5)(A)119/119142/119142/142163/142163/163204/163204/204204/204
Start up Amps Circuit1 / Circuit 2 (3)(5)(A)217/217259/217259/259291/259 291/291354/291354/354354/354
Motor RPM(rpm)30003000300030003000300030003000
Oil sump heater Circuit1 / Circuit 2(W)550/550
Evaporator
Quantity#11111111
TypeFlooded shell and tube heat exchanger
Evaporator model115B115A115A165C165B200C200C200B
Evaporator Water Content volume(l)5158586474898999
(1) Indicative performance at Evaporator water temperature: 12°C / 7°C - Condenser air temperature 35°C - for detailed performances consult
Order Write Up.
(2) Under 400V/3/50Hz.
(3) Rated Condition without Pump Package.
(4) Percent minimum load may be adjusted around 15%-20% according to operating conditions by local sales office.
(5) Electrical & system data are indicative and subject to change without notice. Please refer to unit nameplate data.
(6) Not applicable for Glycol application - see tables with Minimum Flow with Glycol.
(7) Max speed - range is 60% to 100% of max speed.
(8) Refrigerant charge may vary according to option - for instance +20% for process (digit 19 = p). For real value refer to unit nameplate.
(9) Data containing information on two circuits shown as follows: ckt1/ckt2.
(10) OIL0066E or OIL0067E may have been used on early orders and there is no restriction to continue to use them but preferable oil is OIL00315 or
OIL00317.
XE SN LN XE SN LN XE SN LN XE SN LN XE SN LN XE SN LN XE SN LN XE SN LN
32
RLC-SVX19G-GB
Page 33
General Data
Table 8a – General Data RTAF 090-245 Extra Efficiency - Extra Low Noise - R134a - R513A
(1) Indicative performance at Evaporator water temperature: 12°C / 7°C - Condenser air temperature 35°C - for detailed performances consult
Order Write Up.
(2) Under 400V/3/50Hz.
(3) Rated Condition without Pump Package.
(4) Percent minimum load may be adjusted around 15%-20% according to operating conditions by local sales office.
(5) Electrical & system data are indicative and subject to change without notice. Please refer to unit nameplate data.
(6) Not applicable for Glycol application - see tables with Minimum Flow with Glycol.
(7) Max speed - range is 60% to 100% of max speed.
(8) Refrigerant charge may vary according to option - for instance +20% for process (digit 19=P). For real value refer to unit nameplate.
(9) Data containing information on two circuits shown as follows: ckt1/ckt2.
34
RLC-SVX19G-GB
Page 35
General Data
Table 8b – General Data RTAF 090-185 Extra Efficiency - Extra Low Noise - R1234 ze
RTAFRTAFRTAFRTAFRTAFRTAFRTAFRTAF
090100110120130145155185
Cooling Capacity (1)(kW)328359394426459508552614
Unit electrical data (2) (3) (4)
Maximum Power input in cooling(kW)166180194205216247274278
Unit rated amps (Max compressor+fan+control)(A)270293316337358405446452
Unit start up amps starting Amps of the larges compr+RLA
of 2nd compr+RLA of all fans+control)
Displacement Power Factor (DPF)0.890.890.890.880.870.880.890.89
Max power cable cross section mm
Disconnect switch size(A)400400500500500630630630
Compressor
Quantity#22222222
TypeScrewScrewScrewScrewScrewScrewScrewScrew
Model (9)45/4555/4555/5565/5565/6578/6578/7878/78
Max Compr Power input (Circuit 1 / Circuit 2)kW73/7387/7387/8798/8798/98125/98125/125125/125
Max Amps Circuit1 / Circuit 2 (3) (5)(A)119/119142/119142/142163/142163/163204/163204/204204/204
Start up Amps Circuit1 / Circuit 2 (3)(5)(A)217/217259/217259/259291/259 291/291354/291354/354354/354
Motor RPM(rpm)30003000300030003000300030003000
Oil sump heater Circuit1 / Circuit 2(W)150/150
Evaporator
Quantity#11111111
TypeFlooded shell and tube heat exchanger
Evaporator model115B115A115A165C165B200C200C200B
Evaporator Water Content volume(l)5158586474898999
(1) Indicative performance at Evaporator water temperature: 12°C / 7°C - Condenser air temperature 35°C - for detailed performances consult
Order Write Up.
(2) Under 400V/3/50Hz.
(3) Rated Condition without Pump Package.
(4) Percent minimum load may be adjusted around 15%-20% according to operating conditions by local sales office.
(5) Electrical & system data are indicative and subject to change without notice. Please refer to unit nameplate data.
(6) Not applicable for Glycol application - see tables with Minimum Flow with Glycol.
(7) Max speed - range is 60% to 100% of max speed.
(8) Refrigerant charge may vary according to option - for instance +20% for process (digit 19 = p). For real value refer to unit nameplate.
(9) Data containing information on two circuits shown as follows: ckt1/ckt2.
(10) OIL0066E or OIL0067E may have been used on early orders and there is no restriction to continue to use them but preferable oil is OIL00315 or
OIL00317.
XE XLNXE XLNXE XLNXE XLNXE XLNXE XLNXE XLNXE XLN
36
RLC-SVX19G-GB
Page 37
General Data
Table 9a – General data RTAF 090-245 High Seasonal Efficiency - Standard and Low Noise - R134a - R513A
RTAFRTAFRTAFRTAFRTAFRTAFRTAFRTAFRTAF
090105125145155175190205245
HSE SN LNHSE SN LNHSE SN LNHSE SN LNHSE SN LNHSE SN LNHSE SN LNHSE SN LNHSE SN
(1) Indicative performance at Evaporator water temperature: 12°C / 7°C - Condenser air temperature 35°C - for detailed performances consult
Order Write Up.
(2) Under 400V/3/50Hz.
(3) Rated Condition without Pump Package.
(4) Electrical & system data are indicative and subject to change without notice. Please refer to unit nameplate data.
(5) Not applicable for Glycol application - see tables with Minimum Flow with Glycol.
(6) Max speed - range is 60% to 100% of max speed.
(7) Refrigerant charge may vary according to option - for instance +20% for process (digit 19=P). For real value refer to unit nameplate.
(8) Data containing information on two circuits shown as follows: ckt1/ckt2.
LN
38
RLC-SVX19G-GB
Page 39
General Data
Table 9b – General data RTAF 090-225 & 101 High Seasonal Efficiency - Standard and Low Noise - R1234 ze
RTAFRTAFRTAFRTAFRTAFRTAFRTAFRTAFRTAFRTAFRTAF
090100110120130145155185200225 101 (10)
HSE SN LNHSE SN LNHSE SN LNHSE SN LNHSE SN LNHSE SN LNHSE SN LNHSE SN LNHSE SN LNHSE SN LNHSE SN
(1) Indicative performance at Evaporator water temperature: 12°C / 7°C - Condenser air temperature 35°C - for detailed performances consult
Order Write Up.
(2) Under 400V/3/50Hz.
(3) Rated Condition without Pump Package.
(4) Percent minimum load may be adjusted around 15%-20% according to operating conditions by local sales office.
(5) Electrical & system data are indicative and subject to change without notice. Please refer to unit nameplate data.
(6) Not applicable for Glycol application - see tables with Minimum Flow with Glycol.
(7) Max speed - range is 60% to 100% of max speed.
(8) Refrigerant charge may vary according to option - for instance +20% for process (digit 19 = p). For real value refer to unit nameplate.
(9) Data containing information on two circuits shown as follows: ckt1/ckt2.
(10) Not suitable for comfort application - data are indicative - consult Order Write Up.
(11) OIL0066E or OIL0067E may have been used on early orders and there is no restriction to continue to use them but preferable oil is OIL00315 or
OIL00317.
40
RLC-SVX19G-GB
Page 41
General Data
Table 10a – General data RTAF 090-245 High Seasonal Efficiency - Extra Low Noise - R134a - R513A
(1) Indicative performance at Evaporator water temperature: 12°C / 7°C - Condenser air temperature 35°C - for detailed performances consult
Order Write Up.
(2) Under 400V/3/50Hz.
(3) Rated Condition without Pump Package.
(4) Electrical & system data are indicative and subject to change without notice. Please refer to unit nameplate data.
(5) Not applicable for Glycol application - see tables with Minimum Flow with Glycol.
(6) Max speed - range is 60% to 100% of max speed.
(7) Refrigerant charge may vary according to option - for instance +20% for process (digit 19=P). For real value refer to unit nameplate.
(8) Data containing information on two circuits shown as follows: ckt1/ckt2.
42
RLC-SVX19G-GB
Page 43
General Data
Table 10b – General data RTAF 090-225 & 101 High Seasonal Efficiency - Extra Low Noise - R1234 ze
(1) Indicative performance at Evaporator water temperature: 12°C / 7°C - Condenser air temperature 35°C - for detailed performances consult
Order Write Up.
(2) Under 400V/3/50Hz.
(3) Rated Condition without Pump Package.
(4) Percent minimum load may be adjusted around 15%-20% according to operating conditions by local sales office.
(5) Electrical & system data are indicative and subject to change without notice. Please refer to unit nameplate data.
(6) Not applicable for Glycol application - see tables with Minimum Flow with Glycol.
(7) Max speed - range is 60% to 100% of max speed.
(8) Refrigerant charge may vary according to option - for instance +20% for process (digit 19 = p). For real value refer to unit nameplate.
(9) Data containing information on two circuits shown as follows: ckt1/ckt2.
(10) Not suitable for comfort application - data are indicative - consult Order Write Up.
(11) OIL0066E or OIL0067E may have been used on early orders and there is no restriction to continue to use them but preferable oil is OIL00315 or
OIL00317.
44
RLC-SVX19G-GB
Page 45
General Data
Table 11a – General Data RTAF 090-245 High Seasonal Efficiency Short - Standard and Low Noise - R134a - R513A
(1) Indicative performance at Evaporator water temperature: 12°C / 7°C - Condenser air temperature 35°C - for detailed performances consult
Order Write Up.
(2) Under 400V/3/50Hz.
(3) Rated Condition without Pump Package.
(4) Electrical & system data are indicative and subject to change without notice. Please refer to unit nameplate data.
(5) Not applicable for Glycol application - see tables with Minimum Flow with Glycol.
(6) Max speed - range is 60% to 100% of max speed.
(7) Refrigerant charge may vary according to option - for instance +20% for process (digit 19 = p). For real value refer to unit nameplate.
(8) Data containing information on two circuits shown as follows: ckt1/ckt2.
(9) 245 HSS is available in low and standard ambient (not available in high ambient).
LN
46
RLC-SVX19G-GB
Page 47
General Data
Table 11b – General data RTAF 090 225 High Seasonal Efficiency Short - Standard and Low noise - R1234ze
RTAFRTAFRTAFRTAFRTAFRTAFRTAFRTAFRTAFRTAF
090100110120130145155185200225
HSS SN LNHSS SN LNHSS SN LNHSS SN LNHSS SN LNHSS SN LNHSS SN LNHSS SN LNHSS SN LNHSS SN
(1) Indicative performance at Evaporator water temperature: 12°C / 7°C - Condenser air temperature 35°C - for detailed performances consult
Order Write Up.
(2) Under 400V/3/50Hz.
(3) Rated Condition without Pump Package.
(4) Percent minimum load may be adjusted around 15%-20% according to operating conditions by local sales office.
(5) Electrical & system data are indicative and subject to change without notice. Please refer to unit nameplate data.
(6) Not applicable for Glycol application - see tables with Minimum Flow with Glycol.
(7) Max speed - range is 60% to 100% of max speed.
(8) Refrigerant charge may vary according to option - for instance +20% for process (digit 19 = p). For real value refer to unit nameplate.
(9) Data containing information on two circuits shown as follows: ckt1/ckt2.
(10) OIL0066E or OIL0067E may have been used on early orders and there is no restriction to continue to use them but preferable oil is OIL00315 or
OIL00317.
48
RLC-SVX19G-GB
Page 49
General Data
Table 12a – General Data RTAF 090-245 High Seasonal Efficiency Short - Extra Low Noise - R134a - R513A
(1) Indicative performance at Evaporator water temperature: 12°C / 7°C - Condenser air temperature 35°C - for detailed performances consult
Order Write Up.
(2) Under 400V/3/50Hz.
(3) Rated Condition without Pump Package.
(4) Electrical & system data are indicative and subject to change without notice. Please refer to unit nameplate data.
(5) Not applicable for Glycol application - see tables with Minimum Flow with Glycol.
(6) Max speed - range is 60% to 100% of max speed.
(7) Refrigerant charge may vary according to option - for instance +20% for process (digit 19=P). For real value refer to unit nameplate.
(8) Data containing information on two circuits shown as follows: ckt1/ckt2.
(9) 245 HSS is available in low and standard ambient (not available in high ambient).
XLN
HSS
XLN
HSS
XLN
50
RLC-SVX19G-GB
Page 51
General Data
Table 12b – General data RTAF 090-225 High Seasonal Efficiency Short - Extra Low Noise - R1234 ze
(1) Indicative performance at Evaporator water temperature: 12°C / 7°C - Condenser air temperature 35°C - for detailed performances consult
Order Write Up.
(2) Under 400V/3/50Hz.
(3) Rated Condition without Pump Package.
(4) Percent minimum load may be adjusted around 15%-20% according to operating conditions by local sales office.
(5) Electrical & system data are indicative and subject to change without notice. Please refer to unit nameplate data.
(6) Not applicable for Glycol application - see tables with Minimum Flow with Glycol.
(7) Max speed - range is 60% to 100% of max speed.
(8) Refrigerant charge may vary according to option - for instance +20% for process (digit 19 = p). For real value refer to unit nameplate.
(9) Data containing information on two circuits shown as follows: ckt1/ckt2.
(10) OIL0066E or OIL0067E may have been used on early orders and there is no restriction to continue to use them but preferable oil is OIL00315 or
OIL00317.
52
RLC-SVX19G-GB
Page 53
General Data
Table 13a – General Data RTAF 250-450 Standard Efficiency - Standard and low Noise - R134a - R513A
(1) Indicative performance at Evaporator water temperature: 12°C / 7°C - Condenser air temperature 35°C - for detailed performances consult
Order Write Up.
(2) Under 400V/3/50Hz.
(3) Rated Condition without Pump Package.
(4) Percent minimum load may be adjusted around 15%-20% according to operating conditions by local sales office.
(5) Electrical & system data are indicative and subject to change without notice. Please refer to unit nameplate data.
(6) Not applicable for Glycol application - see tables with Minimum Flow with Glycol.
(7) Max speed - range is 60% to 100% of max speed.
(8) Refrigerant charge may vary according to option - for instance +20% for process (digit 19=P). For real value refer to unit nameplate.
(9) Data containing information on two circuits shown as follows: ckt1/ckt2.
(10) Sizes 355 and 450 are not available with R513A.
SE SN LNSE SN LNSE SN LNSE SN LNSE SN LNSE SN LNSE SN LNSE SN LN
(kg)93/4596/4997/5294/9197/5298/100107/104107/104
54
RLC-SVX19G-GB
Page 55
General Data
Table 13b – General Data RTAF 210-340 Standard Efficiency - Standard and low Noise - R1234 ze
RTAFRTAFRTAFRTAFRTAFRTAF
210230265285305340
Net Cooling Capacity (1)(kW)72480688699410801186
Unit electrical data (2) (3) (5)
Maximum Power input in cooling(kW)349403408481535539
Unit rated amps (Max compr+Fan+Control)(A)590672680810892900
Unit start up amps (Starting Amps of the largest compr(A)74082283096010421050
Displacement Power factor (DPF)0.880.870.870.860.870.87
(1) Indicative performance at Evaporator water temperature: 12°C / 7°C - Condenser air temperature 35°C - for detailed performances consult
Order Write Up.
(2) Under 400V/3/50Hz.
(3) Rated Condition without Pump Package.
(4) Percent minimum load may be adjusted around 15%-20% according to operating conditions by local sales office.
(5) Electrical & system data are indicative and subject to change without notice. Please refer to unit nameplate data.
(6) Not applicable for Glycol application - see tables with Minimum Flow with Glycol.
(7) Max speed - range is 60% to 100% of max speed.
(8) Refrigerant charge may vary according to option - for instance +20% for process (digit 19 = p). For real value refer to unit nameplate.
(9) Data containing information on two circuits shown as follows: ckt1/ckt2.
(10) OIL0066E or OIL0067E may have been used on early orders and there is no restriction to continue to use them but preferable oil is OIL00315 or
OIL00317.
SE SN LNSE SN LNSE SN LNSE SN LNSE SN LNSE SN LN
56
RLC-SVX19G-GB
Page 57
General Data
Table 14a – General Data RTAF 250-450 standard efficiency Extra Low Noise - R134a - R513A
(1) Indicative performance at Evaporator water temperature: 12°C / 7°C - Condenser air temperature 35°C - for detailed performances consult
Order Write Up.
(2) Under 400V/3/50Hz.
(3) Rated Condition without Pump Package.
(4) Percent minimum load may be adjusted around 15%-20% according to operating conditions by local sales office.
(5) Electrical & system data are indicative and subject to change without notice. Please refer to unit nameplate data.
(6) Not applicable for Glycol application - see tables with Minimum Flow with Glycol.
(7) Max speed - range is 60% to 100% of max speed.
(8) Refrigerant charge may vary according to option - for instance +20% for process (digit 19=P). For real value refer to unit nameplate.
(9) Data containing information on two circuits shown as follows: ckt1/ckt2.
SE XLNSE XLNSE XLNSE XLNSE XLNSE XLNSE XLNSE XLN
(kg)93/4596/4997/5294/9197/5298/100107/104107/104
58
RLC-SVX19G-GB
Page 59
General Data
Table 14b – General Data RTAF 210-340 standard efficiency Extra Low Noise - R1234 ze
RTAFRTAFRTAFRTAFRTAFRTAF
210230265285305340
Net Cooling Capacity (1)(kW)72580688699510801187
Unit electrical data (2) (3) (5)
Maximum Power input in cooling(kW)350404408483537541
Unit rated amps (Max compr+Fan+Control)(A)576658664792874880
Unit start up amps (Starting Amps of the largest compr(A)72680881494210241030
Displacement Power factor (DPF)0.880.890.890.880.890.89
(1) Indicative performance at Evaporator water temperature: 12°C / 7°C - Condenser air temperature 35°C - for detailed performances consult
Order Write Up.
(2) Under 400V/3/50Hz.
(3) Rated Condition without Pump Package.
(4) Percent minimum load may be adjusted around 15%-20% according to operating conditions by local sales office.
(5) Electrical & system data are indicative and subject to change without notice. Please refer to unit nameplate data.
(6) Not applicable for Glycol application - see tables with Minimum Flow with Glycol.
(7) Max speed - range is 60% to 100% of max speed.
(8) Refrigerant charge may vary according to option - for instance +20% for process (digit 19 = p). For real value refer to unit nameplate.
(9) Data containing information on two circuits shown as follows: ckt1/ckt2.
(10) OIL0066E or OIL0067E may have been used on early orders and there is no restriction to continue to use them but preferable oil is OIL00315 or
OIL00317.
SE XLNSE XLNSE XLNSE XLNSE XLNSE XLN
60
RLC-SVX19G-GB
Page 61
General Data
Table 15a – General Data RTAF 250-450 Standard Efficiency - AC Extra Low Noise - R134a - R513A
(1) Indicative performance at Evaporator water temperature: 12°C / 7°C - Condenser air temperature 35°C - for detailed performances consult
Order Write Up.
(2) Under 400V/3/50Hz.
(3) Rated Condition without Pump Package.
(4) Percent minimum load may be adjusted around 15%-20% according to operating conditions by local sales office.
(5) Electrical & system data are indicative and subject to change without notice. Please refer to unit nameplate data.
(6) Not applicable for Glycol application - see tables with Minimum Flow with Glycol.
(7) Max speed - range is 60% to 100% of max speed.
(8) Refrigerant charge may vary according to option - for instance +20% for process (digit 19=P). For real value refer to unit nameplate.
(9) Data containing information on two circuits shown as follows: ckt1/ckt2.
SE AC XLNSE AC XLN SE AC XLNSE AC XLN SE AC XLNSE AC XLN SE AC XLNSE AC XLN
(kg)93/4596/4997/5294/9197/5298/100107/104107/104
62
RLC-SVX19G-GB
Page 63
General Data
Table 15b – General Data RTAF 210-340 Standard Efficiency - AC Extra Low Noise - R1234 ze
RTAFRTAFRTAFRTAFRTAFRTAF
210230265285305340
Net Cooling Capacity (1)(kW)72079988298710701180
Unit electrical data (2) (3) (5)
Maximum Power input in cooling(kW)343397400474528531
Unit rated amps (Max compr+Fan+Control)(A)575657662790872878
Unit start up amps (Starting Amps of the largest compr(A)72580781294010221028
Displacement Power factor (DPF)0.860.880.870.870.880.88
(1) Indicative performance at Evaporator water temperature: 12°C / 7°C - Condenser air temperature 35°C - for detailed performances consult
Order Write Up.
(2) Under 400V/3/50Hz.
(3) Rated Condition without Pump Package.
(4) Percent minimum load may be adjusted around 15%-20% according to operating conditions by local sales office.
(5) Electrical & system data are indicative and subject to change without notice. Please refer to unit nameplate data.
(6) Not applicable for Glycol application - see tables with Minimum Flow with Glycol.
(7) Max speed - range is 60% to 100% of max speed.
(8) Refrigerant charge may vary according to option - for instance +20% for process (digit 19 = p). For real value refer to unit nameplate.
(9) Data containing information on two circuits shown as follows: ckt1/ckt2.
(10) OIL0066E or OIL0067E may have been used on early orders and there is no restriction to continue to use them but preferable oil is OIL00315 or
OIL00317.
SE AC XLN SE AC XLN SE AC XLN SE AC XLN SE AC XLN SE AC XLN
64
RLC-SVX19G-GB
Page 65
General Data
Table 16a – General Data RTAF 250-450 High Efficiency - Standard and Low Noise - R134a - R513A
(1) Indicative performance at Evaporator water temperature: 12°C / 7°C - Condenser air temperature 35°C - for detailed performances consult
Order Write Up.
(2) Under 400V/3/50Hz.
(3) Rated Condition without Pump Package.
(4) Percent minimum load may be adjusted around 15%-20% according to operating conditions by local sales office.
(5) Electrical & system data are indicative and subject to change without notice. Please refer to unit nameplate data.
(6) Not applicable for Glycol application - see tables with Minimum Flow with Glycol.
(7) Max speed - range is 60% to 100% of max speed.
(8) Refrigerant charge may vary according to option - for instance +20% for process (digit 19=P). For real value refer to unit nameplate.
(9) Data containing information on two circuits shown as follows: ckt1/ckt2.
HE SN LNHE SN LNHE SN LNHE SN LNHE SN LNHE SN LNHE SN LNHE SN LN
(1) Indicative performance at Evaporator water temperature: 12°C / 7°C - Condenser air temperature 35°C - for detailed performances consult
Order Write Up.
(2) Under 400V/3/50Hz.
(3) Rated Condition without Pump Package.
(4) Percent minimum load may be adjusted around 15%-20% according to operating conditions by local sales office.
(5) Electrical & system data are indicative and subject to change without notice. Please refer to unit nameplate data.
(6) Not applicable for Glycol application - see tables with Minimum Flow with Glycol.
(7) Max speed - range is 60% to 100% of max speed.
(8) Refrigerant charge may vary according to option - for instance +20% for process (digit 19 = p). For real value refer to unit nameplate.
(9) Data containing information on two circuits shown as follows: ckt1/ckt2.
(10) OIL0066E or OIL0067E may have been used on early orders and there is no restriction to continue to use them but preferable oil is OIL00315 or
OIL00317.
HE SN LNHE SN LNHE SN LNHE SN LNHE SN LNHE SN LN
68
RLC-SVX19G-GB
Page 69
General Data
Table 17a – General Data RTAF 250-450 High Efficiency - AC Extra Low Noise - R134a - R513A
(1) Indicative performance at Evaporator water temperature: 12°C / 7°C - Condenser air temperature 35°C - for detailed performances consult
Order Write Up.
(2) Under 400V/3/50Hz.
(3) Rated Condition without Pump Package.
(4) Percent minimum load may be adjusted around 15%-20% according to operating conditions by local sales office.
(5) Electrical & system data are indicative and subject to change without notice. Please refer to unit nameplate data.
(6) Not applicable for Glycol application - see tables with Minimum Flow with Glycol.
(7) Max speed - range is 60% to 100% of max speed.
(8) Refrigerant charge may vary according to option - for instance +20% for process (digit 19 = p). For real value refer to unit nameplate.
(9) Data containing information on two circuits shown as follows: ckt1/ckt2.
HE AC XLN HE AC XLN HE AC XLN HE AC XLN HE AC XLN HE AC XLN HE AC XLN HE AC XLN
(1) Indicative performance at Evaporator water temperature: 12°C / 7°C - Condenser air temperature 35°C - for detailed performances consult
Order Write Up.
(2) Under 400V/3/50Hz.
(3) Rated Condition without Pump Package.
(4) Percent minimum load may be adjusted around 15%-20% according to operating conditions by local sales office.
(5) Electrical & system data are indicative and subject to change without notice. Please refer to unit nameplate data.
(6) Not applicable for Glycol application - see tables with Minimum Flow with Glycol.
(7) Max speed - range is 60% to 100% of max speed.
(8) Refrigerant charge may vary according to option - for instance +20% for process (digit 19 = p). For real value refer to unit nameplate.
(9) Data containing information on two circuits shown as follows: ckt1/ckt2.
(10) OIL0066E or OIL0067E may have been used on early orders and there is no restriction to continue to use them but preferable oil is OIL00315 or
OIL00317.
HE AC XLN HE AC XLN HE AC XLN HE AC XLN HE AC XLN HE AC XLN
72
RLC-SVX19G-GB
Page 73
General Data
Table 18a – General Data RTAF 250-450 Extra Efficiency - Standard and Low Noise - R134a - R513A
(1) Indicative performance at Evaporator water temperature: 12°C / 7°C - Condenser air temperature 35°C - for detailed performances consult
Order Write Up.
(2) Under 400V/3/50Hz.
(3) Rated Condition without Pump Package.
(4) Percent minimum load may be adjusted around 15%-20% according to operating conditions by local sales office.
(5) Electrical & system data are indicative and subject to change without notice. Please refer to unit nameplate data.
(6) Not applicable for Glycol application - see tables with Minimum Flow with Glycol.
(7) Max speed - range is 60% to 100% of max speed.
(8) Refrigerant charge may vary according to option - for instance +20% for process (digit 19=P). For real value refer to unit nameplate.
(9) Data containing information on two circuits shown as follows: ckt1/ckt2.
XE SN LN XE SN LN XE SN LN XE SN LN XE SN LN XE SN LN XE SN LN XE SN LN XE SN LN
(1) Indicative performance at Evaporator water temperature: 12°C / 7°C - Condenser air temperature 35°C - for detailed performances consult
Order Write Up.
(2) Under 400V/3/50Hz.
(3) Rated Condition without Pump Package.
(4) Percent minimum load may be adjusted around 15%-20% according to operating conditions by local sales office.
(5) Electrical & system data are indicative and subject to change without notice. Please refer to unit nameplate data.
(6) Not applicable for Glycol application - see tables with Minimum Flow with Glycol.
(7) Max speed - range is 60% to 100% of max speed.
(8) Refrigerant charge may vary according to option - for instance +20% for process (digit 19 = p). For real value refer to unit nameplate.
(9) Data containing information on two circuits shown as follows: ckt1/ckt2.
(10) OIL0066E or OIL0067E may have been used on early orders and there is no restriction to continue to use them but preferable oil is OIL00315 or
OIL00317.
XE SN LNXE SN LNXE SN LNXE SN LNXE SN LNXE SN LN
76
RLC-SVX19G-GB
Page 77
General Data
Table 19a – General Data RTAF 250-450 Extra Efficiency - Extra Low Noise - R134a - R513A
(1) Indicative performance at Evaporator water temperature: 12°C / 7°C - Condenser air temperature 35°C - for detailed performances consult
Order Write Up.
(2) Under 400V/3/50Hz.
(3) Rated Condition without Pump Package.
(4) Percent minimum load may be adjusted around 15%-20% according to operating conditions by local sales office.
(5) Electrical & system data are indicative and subject to change without notice. Please refer to unit nameplate data.
(6) Not applicable for Glycol application - see tables with Minimum Flow with Glycol.
(7) Max speed - range is 60% to 100% of max speed.
(8) Refrigerant charge may vary according to option - for instance +20% for process (digit 19=P). For real value refer to unit nameplate.
(9) Data containing information on two circuits shown as follows: ckt1/ckt2.
(1) Indicative performance at Evaporator water temperature: 12°C / 7°C - Condenser air temperature 35°C - for detailed performances consult
Order Write Up.
(2) Under 400V/3/50Hz.
(3) Rated Condition without Pump Package.
(4) Percent minimum load may be adjusted around 15%-20% according to operating conditions by local sales office.
(5) Electrical & system data are indicative and subject to change without notice. Please refer to unit nameplate data.
(6) Not applicable for Glycol application - see tables with Minimum Flow with Glycol.
(7) Max speed - range is 60% to 100% of max speed.
(8) Refrigerant charge may vary according to option - for instance +20% for process (digit 19 = p). For real value refer to unit nameplate.
(9) Data containing information on two circuits shown as follows: ckt1/ckt2.
(10) OIL0066E or OIL0067E may have been used on early orders and there is no restriction to continue to use them but preferable oil is OIL00315 or
OIL00317.
XE XLNXE XLNXE XLNXE XLNXE XLNXE XLN
80
RLC-SVX19G-GB
Page 81
General Data
Table 20a – General Data RTAF 250-410 High Seasonal Efficiency Short - Standard and Low Noise - R134a - R513A
RTAFRTAFRTAFRTAFRTAFRTAF
250280310350380410
HSS SN LNHSS SN LNHSS SN LNHSS SN LNHSS SN LNHSS SN LN
Cooling Capacity (1)(kW)8629681066119513121432
Unit electrical data (2) (3) (5)
Maximum Power input in cooling(kW)375425471527577627
Unit rated amps (Max compr +Fan+Control) (A)588668739836920997
Unit start up amps (Starting Amps of the largest
compr+RLA of 2nd compr+RLA of all fans+ control)
Unit Power factor0.920.920.920.910.910.91
Max power cable cross section (mm²)4*3004*3004*3004*3004*3004*300
Disconnect switch size(A)125012501250125012501250
Compressor
Quantity#333444
TypeScrewScrewScrewScrewScrewScrew
Model (9)85-85/7085-100/85100-100/10085-85/85-85
Max Compr Power input Circuit 1/Circuit 2kW124-121/101 124-144/124147-144/147
Max Amps Circuit 1 / Circuit 2 (3) (4)(A)188-201/153 188-240/188224-240/224
(1) Indicative performance at Evaporator water temperature: 12°C / 7°C - Condenser air temperature 35°C - for detailed performances consult
Order Write Up.
(2) Under 400V/3/50Hz.
(3) Rated Condition without Pump Package.
(4) Percent minimum load may be adjusted around 15%-20% according to operating conditions by local sales office.
(5) Electrical & system data are indicative and subject to change without notice. Please refer to unit nameplate data.
(6) Not applicable for Glycol application - see tables with Minimum Flow with Glycol.
(7) Max speed - range is 60% to 100% of max speed.
(8) Refrigerant charge may vary according to option - for instance +20% for process (digit 19 = p). For real value refer to unit nameplate.
(9) Data containing information on two circuits shown as follows: ckt1/ckt2.
82
RLC-SVX19G-GB
Page 83
General Data
Table 20b – General Data RTAF 210-405 High Seasonal Efficiency Short - Standard and Low Noise - R1234 ze
RTAFRTAFRTAFRTAFRTAFRTAFRTAFRTAFRTAFRTAF
210230265275285300305340385405
HSS SN LNHSS SN LNHSS SN LNHSS SN LNHSS SN LNHSS SN LNHSS SN LNHSS SN LNHSS SN LNHSS SN
Net Cooling Capacity (1)(kW)72780988799999811051085118813101426
Unit electrical data (2) (3) (5)
Maximum Power input in cooling(kW)379421425468511515554558605652
Unit rated amps (Max compr+Fan+Control)(A)5916566627278077998728789491021
Unit start up amps (Starting Amps of the largest
compr
Displacement Power factor (DPF)0.930.930.930.930.920.930.920.920.920.92
(1) Indicative performance at Evaporator water temperature: 12°C / 7°C - Condenser air temperature 35°C - for detailed performances consult
Order Write Up.
(2) Under 400V/3/50Hz.
(3) Rated Condition without Pump Package.
(4) Percent minimum load may be adjusted around 15%-20% according to operating conditions by local sales office.
(5) Electrical & system data are indicative and subject to change without notice. Please refer to unit nameplate data.
(6) Not applicable for Glycol application - see tables with Minimum Flow with Glycol.
(7) Max speed - range is 60% to 100% of max speed.
(8) Refrigerant charge may vary according to option - for instance +20% for process (digit 19 = p). For real value refer to unit nameplate.
(9) Data containing information on two circuits shown as follows: ckt1/ckt2.
(10) OIL0066E or OIL0067E may have been used on early orders and there is no restriction to continue to use them but preferable oil is OIL00315 or
OIL00317.
LN
84
RLC-SVX19G-GB
Page 85
General Data
Table 21a – General Data RTAF 250-410 High Seasonal Efficiency Short - Extra Low Noise - R134a - R513A
RTAFRTAFRTAFRTAFRTAFRTAF
250280310350380410
HSS XLNHSS XLNHSS XLNHSS XLNHSS XLNHSS XLN
Cooling Capacity (1)(kW)8619681065119513111431
Unit electrical data (2) (3) (4)
Maximum Power input in cooling(kW)375425471527577627
Unit rated amps (Max compr +Fan+Control) (A)588668739836920997
Unit start up amps (Starting Amps of the largest
compr+RLA of 2nd compr+RLA of all fans+ control)
Unit Power factor0.920.920.920.910.910.91
Max power cable cross section (mm²)4*3004*3004*3004*3004*3004*300
Disconnect switch size(A)125012501250125012501250
Compressor
Quantity#333444
TypeScrewScrewScrewScrewScrewScrew
Model (8)85-85/7085-100/85100-100/10085-85/85-85
Max Compr Power input Circuit 1/Circuit 2kW124-121/101 124-144/124147-144/147
Max Amps Circuit 1 / Circuit 2 (3) (4)(A)188-201/153 188-240/188224-240/224
(1) Indicative performance at Evaporator water temperature: 12°C / 7°C - Condenser air temperature 35°C - for detailed performances consult
Order Write Up.
(2) Under 400V/3/50Hz.
(3) Rated Condition without Pump Package.
(4) Electrical & system data are indicative and subject to change without notice. Please refer to unit nameplate data.
(5) Not applicable for Glycol application - see tables with Minimum Flow with Glycol.
(6) Max speed - range is 60% to 100% of max speed.
(7) Refrigerant charge may vary according to option - for instance +20% for process (digit 19=P). For real value refer to unit nameplate.
(8) Data containing information on two circuits shown as follows: ckt1/ckt2.
86
RLC-SVX19G-GB
Page 87
General Data
Table 21b –General Data RTAF 210-405 High Seasonal Efficiency Short - Extra Low Noise - R1234 ze
(1) Indicative performance at Evaporator water temperature: 12°C / 7°C - Condenser air temperature 35°C - for detailed performances consult
Order Write Up.
(2) Under 400V/3/50Hz.
(3) Rated Condition without Pump Package.
(4) Percent minimum load may be adjusted around 15%-20% according to operating conditions by local sales office.
(5) Electrical & system data are indicative and subject to change without notice. Please refer to unit nameplate data.
(6) Not applicable for Glycol application - see tables with Minimum Flow with Glycol.
(7) Max speed - range is 60% to 100% of max speed.
(8) Refrigerant charge may vary according to option - for instance +20% for process (digit 19 = p). For real value refer to unit nameplate.
(9) Data containing information on two circuits shown as follows: ckt1/ckt2.
(10) OIL0066E or OIL0067E may have been used on early orders and there is no restriction to continue to use them but preferable oil is OIL00315 or
OIL00317.
88
RLC-SVX19G-GB
Page 89
General Data
Table 22a – General Data RTAF 250-550 High Seasonal Efficiency - Standard and Low Noise - R134a - R513A
(1) Indicative performance at Evaporator water temperature: 12°C / 7°C - Condenser air temperature 35°C - for detailed performances consult
Order Write Up.
(2) Under 400V/3/50Hz.
(3) Rated Condition without Pump Package.
(4) Electrical & system data are indicative and subject to change without notice. Please refer to unit nameplate data.
(5) Not applicable for Glycol application - see tables with Minimum Flow with Glycol.
(6) Max speed - range is 60% to 100% of max speed.
(7) Refrigerant charge may vary according to option - for instance +20% for process (digit 19=P). For real value refer to unit nameplate.
(8) Data containing information on two circuits shown as follows: ckt1/ckt2.
90
RLC-SVX19G-GB
Page 91
General Data
Table 22b – General Data RTAF 210-470 & 141-191 High Seasonal Efficiency - Standard and Low Noise - R1234 ze
(1) Indicative performance at Evaporator water temperature: 12°C / 7°C - Condenser air temperature 35°C - for detailed performances consult
Order Write Up.
(2) Under 400V/3/50Hz.
(3) Rated Condition without Pump Package.
(4) Percent minimum load may be adjusted around 15%-20% according to operating conditions by local sales office.
(5) Electrical & system data are indicative and subject to change without notice. Please refer to unit nameplate data.
(6) Not applicable for Glycol application - see tables with Minimum Flow with Glycol.
(7) Max speed - range is 60% to 100% of max speed.
(8) Refrigerant charge may vary according to option - for instance +20% for process (digit 19 = p). For real value refer to unit nameplate.
(9) Data containing information on two circuits shown as follows: ckt1/ckt2.
(10) OIL0066E or OIL0067E may have been used on early orders and there is no restriction to continue to use them but preferable oil is OIL00315 or
OIL00317.
92
RLC-SVX19G-GB
Page 93
General Data
Table 23a – General Data RTAF 250-550 High Seasonal Efficiency - Extra Low Noise - R134a - R513A
(1) Indicative performance at Evaporator water temperature: 12°C / 7°C - Condenser air temperature 35°C - for detailed performances consult
Order Write Up.
(2) Under 400V/3/50Hz.
(3) Rated Condition without Pump Package.
(4) Electrical & system data are indicative and subject to change without notice. Please refer to unit nameplate data.
(5) Not applicable for Glycol application - see tables with Minimum Flow with Glycol.
(6) Max speed - range is 60% to 100% of max speed.
(7) Refrigerant charge may vary according to option - for instance +20% for process (digit 19=P). For real value refer to unit nameplate.
(8) Data containing information on two circuits shown as follows: ckt1/ckt2.
94
RLC-SVX19G-GB
Page 95
General Data
Table 23b – General Data RTAF 210-470 & 141-191 High Seasonal Efficiency - Extra Low Noise - R1234 ze
(1) Indicative performance at Evaporator water temperature: 12°C / 7°C - Condenser air temperature 35°C - for detailed performances consult
Order Write Up.
(2) Under 400V/3/50Hz.
(3) Rated Condition without Pump Package.
(4) Percent minimum load may be adjusted around 15%-20% according to operating conditions by local sales office.
(5) Electrical & system data are indicative and subject to change without notice. Please refer to unit nameplate data.
(6) Not applicable for Glycol application - see tables with Minimum Flow with Glycol.
(7) Max speed - range is 60% to 100% of max speed.
(8) Refrigerant charge may vary according to option - for instance +20% for process (digit 19 = p). For real value refer to unit nameplate.
(9) Data containing information on two circuits shown as follows: ckt1/ckt2.
(10) OIL0066E or OIL0067E may have been used on early orders and there is no restriction to continue to use them but preferable oil is OIL00315 or
OIL00317.
96
RLC-SVX19G-GB
Page 97
Installation Requirements
Installation Responsibilities
Generally contractor must do the following items when
installing an RTAF unit:
1. Install the unit on a flat foundation strong enough to
support unit loading and level (within 5 mm across
the length and width of the unit).
2. Install the units as per instructions contained in this
manual.
3. Where specified, provide and install valves in
the water piping upstream and downstream of
the evaporator water connections, to isolate the
evaporator for maintenance, and to balance and trim
the system.
4. Furnish and install a water flow prove device and/or
auxiliary contacts to prove chiller water flow.
5. Furnish and install water pressure gauges in the inlet
and outlet of the evaporator water box.
6. Supply and install an air vent cock to the top of the
evaporator water box.
7. Furnish and install strainers ahead of all pumps and
automatic modulating valves.
8. Provide and install field wiring according to
schematics provided in the control panel.
9. Install heat tape and insulate the chilled water lines
and any other portion of the system, as required, to
prevent sweating under normal operating conditions
or freezing during low ambient temperature
conditions.
10. Ensure that the compressor and oil separator
heaters have been operating for a minimum of
24 hours before starting. Failure to do so may
result in equipment damage.
11. Start the unit under supervision of a qualified service
technician.
Compressor Nameplate
The compressor nameplate provides following
information:
• Compressor model number.
• Compressor serial number.
• Compressor electrical characteristics.
• Utilization range
• Recommended refrigerant
Storage
Extended storage of the unit prior to the installation
requires the following precautions:
1. Store the unit in a secured area, to avoid intentional
damages.
2. Close the suction, discharge and liquid-line isolation
valves.
3. At least every three months, connect a gauge and
manually check the pressure in the refrigerant circuit.
If the refrigerant pressure is below 13 Bar at 20°C (or
10 Bar at 10°C), call a qualified service organization
and the appropriate Trane sales office.
Note: if the unit is stored before servicing near a
construction site it is highly recommended to protect
micro channel coils from any concrete and iron element.
Failure to do so may considerably reduce reliablity of
the unit.
Lifting and Moving Instructions
A specific lifting method is recommended, which can be
described as follow:
Nameplates
The RTAF outdoor unit nameplates are applied to the
exterior of the control panel. A compressor nameplate is
located on each compressor.
Unit Nameplate
The unit nameplate provides the following information:
• Unit model and size description
• Unit serial number
• Identifies unit electrical requirements
• Lists correct operating charges of R-134a and
refrigerant oil
• Lists unit test pressures
1. Lifting points are built into the unit, see lifting
instruction label on the unit.
2. Slings and spreader bar must be provided by crane
operator and attached on the lifting points.
3. Use the 4 or 8 rigging points (according to unit size)
which are built into the unit.
4. The minimum lifting capacity of each sling as well as
the spreader bar must be higher than the tabulated
unit shipping weight.
5. CAUTION! Lift and handle with care. Avoid shocks
while handling.
RLC-SVX19G-GB
97
Page 98
Installation Requirements
Dimension and Weights
Dimensions details, dimensions of hydraulic
connections, electrical connections, isolator positioning,
specific features for heat recovery and free cooling
are included in submittals and diagrams provided in
documentation package.
Center of Gravity
See instructions on lifting drawings available on request.
WARNING! Heavy Objects!
Ensure that all the lifting equipment used is properly
rated for weight of the unit being lifted. Each of the
cables (chains or slings), hooks, and shackles used to lift
the unit must be capable of supporting the entire weight
of unit. Lifting cables (chains or slings) may not be the
same length. Adjust as necessary for even unit lift. Other
lifting arrangements could cause equipment or property
damage. Failure to follow instructions above or properly
lift unit could result in unit dropping and possibly
crushing operator/technician which could result in death
or serious injury.
WARNING! Improper Unit Lift!
Test lift unit approximately 10 cm to verify proper center
of gravity lift point. To avoid dropping of unit, reposition
lifting point if unit is not level. Failure to properly lift
unit could result in unit dropping and possibly crushing
operator/technician which could result in death or
serious injury and possible equipment or property- only
damage.
Clearances
When installing the unit, provide enough space around
the unit to allow the installation and maintenance
personnel unrestricted access to all service points.
Unobstructed flow of condenser air is essential to
maintain chiller capacity and operating efficiency. When
determining unit placement, give careful consideration
to ensuring a sufficient air flow across the condenser
coils heat-transfer surface.
Notes:
1. Area above unit required for operation, maintenance,
panel access and airflow: NO OBSTRUCTIONS ABOVE
UNIT
2. For installations with obstructions or multiple units,
refer to Trane office for Close Spacing and Restricted
Airflow advices.
3. Minimum clearance of 1990 mm on the side of the
unit is required for coil replacement. If sufficient
clearance is not available on the side of the unit, coil
replacement should be performed through top of unit.
4. Enough clearance is required in front of the control
panels. Must be measured from front of panel, not end
of unit base.
5. Clearances should be sufficient for tube pull out of
evaporator (2.5 m in the evaporator water box side of
the unit for 2 compressors units and 4.5 m for 3 and
4 compressors units)
6. Refer to submittal drawings for complementary
information.
Unit Isolation and Leveling
Provide a foundation with sufficient strength and mass
to support the unit operating weight (that is, including
completed piping, full operating charges of refrigerant
and oil, and water). Refer to unit operating weights.
The unit must be leveled within 5 mm over its length
and width. Use shims as necessary to level the unit. For
additional reduction of sound and vibration, install the
optional elastomeric isolators.
Sound consideration
The most effective form of acoustical isolation is to
locate the unit away from any sound sensitive area.
Structurally transmitted sound can be reduced by
elastomeric vibration eliminators. Spring isolators are
not recommended. Consult an acoustical engineer in
critical sound applications.
For maximum isolation effect, isolate water lines and
electrical conduit. Rubber isolated piping hangers can
be used to reduce the sound transmitted through water
piping. To reduce sound transmitted through electrical
conduit, use flexible electrical conduit.
EU and Local Regulations codes on sound emissions
should always be considered. Since the environment
in which a sound source is located affects the sound
pressure, unit placement must be carefully evaluated.
98
RLC-SVX19G-GB
Page 99
Installation Requirements
117.6
159
9.6
Elastomeric Isolators Installation
(Optional)
Isolators are ready to install. Mountings have to
be placed on a rigid and level foundation. External
equipment should not transmit additional vibration to
the chiller. The position of elastomeric isolator and
weight per point are given in the Neoprene isolators
installation drawing which is supplied with the chiller.
Wrong placement along the unit may result in excessive
deflection.
1. Secure the isolators to the mounting surface
using the mounting slots in the isolator’s base
plate. Do NOT fully tighten the isolators mounting
bolts at this time. See the isolators submittals for
isolators location, maximum weights, and isolators
diagrams.
2. Align the mounting holes in the base of the unit
with the threaded positioning pins on the top of the
isolators.
3. Install the unit on the isolators and secure the
isolators to the unit with a nut. The maximum
isolators deflection should be 13 mm.
4. Level the unit carefully. Fully tighten the isolator
mounting bolts.
Figure 1 – Elastomeric Isolator
Isolator Pads Installation (Optional)
Isolators are ready to install. Mountings have to
be placed on a rigid and level foundation. External
equipment should not transmit additional vibration to
the chiller. The position of pads isolator is given in the
pad isolators installation or selection drawing which is
supplied with the chiller.
Figure 2 – Isolator pads
90
450
8
63.5
14.2
127
16
40.6
12.7
70
RLC-SVX19G-GB
99
Page 100
Chilled Water Piping Recommendations
Water Treatment
In the evaporator the following material are in contact
with water:
• Water boxes are made of cast iron (GJL250 EN-code)
• Tube plates are made of steel (P265GH code)
• Tubes are made of copper
• Turbulators when present in evaporator tubes are
made of phosphorous brass.
When the unit is supplied with hydraulic module, the
following additional materials are in contact with water:
• Pump frame and connections are made of cast iron
• Water pipes are made of iron
• Pipe sealings are made of EPDM rubber (ethylene
propylene diene monomer rubber)
• Pump sealings are made of silicon carbide
• Strainer is made of stainless steel
Notice!
Dirt, scale, products of corrosion, and other foreign
material will adversely affect heat transfer between the
water and system components. Foreign matter in the
chilled-water system can also increase pressure drop
and consequently, reduce water flow. Proper water
treatment must be determined locally, depending on the
type of system and local water characteristics.
Neither salt nor brackish water is recommended for use
in Trane air-cooled chillers. Use of either will lead to an
unpredictably shorter life cycle. Trane encourages the
employment of a reputable water treatment specialist,
familiar with local water conditions, to assist in this
determination and in the establishment of a proper water
treatment program.
CAUTION! If using an acidic commercial flushing
solution, construct a temporary bypass around the
unit to prevent damage to internal components of
the evaporator. Trane assumes no responsibility for
equipment failures which results from untreated or
improperly treated water or saline or brackish water.
If calcium chloride is used for water treatment, an
applicable corrosion inhibitor must also be used. Failure
to do so may result in damage to system components.
Do not use untreated or improperly treated water.
Equipment damage may occur.
Notice: Coil Damage!
Failure to follow instructions below could result in
freecooling coil freeze. For units with free-cooling option,
introduction of uninhibited water into the system is not
recommended, as it could lead to internal corrosion and
risk of coil freeze. To avoid free-cooling coil damage:
• If the building loop needs to be charged with water for
testing purposes, isolate free-cooling coils by closing
free-cooling service shut-off valve and modulating
valve.
• Completely drain any water inadvertently introduced
into the system, and replace with glycol fluid as
required for the free-cooling system.
• If water was introduced for hydronic testing, and was
not immediately replaced with glycol solution, a glycol
(freeze inhibitor) solution must be introduced to the
free-cooling system/coils for any long term storage.
Evaporator Piping
Evaporator water connections are grooved.
Thoroughly flush all water piping to the unit before
making the final piping connections to the unit.
Components and layout will vary slightly, depending on
the location of connections and the water sources (see
figure Typical RTAF water piping figure).
An air vent is located on top of the evaporator at the
chiller water outlet. Be sure to provide additional air
vents at the highest points in the piping to remove air
from the chilled water system. Install necessary pressure
gauges to monitor the entering and leaving chilled water
pressure.
Provide shut off valves in lines to the gauges to isolate
them from the system when they are not in use. Use
rubber vibration eliminators to prevent vibration
transmission through the water lines.
If desired, install thermometers in the lines to monitor
entering and leaving water line to control water flow
balance. Install shutoff valves on both the entering and
leaving water lines so that the evaporator can be isolated
for service.
CAUTION! The chilled-water connections to the
evaporator are to be “grooved pipe” type connections.
Do not attempt to weld these connections, because the
heat generated from welding can cause microscopic
and macroscopic fractures on the cast iron water boxes
that can lead to premature failure of the water box. An
optional grooved pipe stub and coupling is available for
welding on flanges.
100
To prevent damage to chilled-water components, do not
allow evaporator pressure (maximum working pressure)
to exceed 10 Bar. The maximum service pressure
depends on free cooling type and potential pump
package option. The value of max service pressure is
indicated on unit nameplate.
A pipe strainer must be installed in the entering water
line. Failure to do so can allow waterborne debris to
enter the evaporator.