Trane OA B D 000, OA G D 000, OA B E 000, OA G E 000, OA B D 036 Installation, Operation And Maintenance Manual

...
Installation, Operation, and Maintenance
Horizon™ Outdoor Air Unit
Direct Gas-Fired Model: OAB, OAG
Important: Proper execution of the tasks outlined in this Installation, Operation, and Maintenance manual
require and assume the technician has been certified as a start up technician for the Horizon Outdoor Air unit. This includes working knowledge of the Tracer TU program.
SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.
AVERTISSEMENT DE SÉCURITÉ
November 2019
OAU-SVX005C-EN
Introduction
Read this manual thoroughly before operating or servicing this unit.
Warnings, Cautions, and Notices
Safety advisories appear throughout this manual as required. Your personal safety and the proper operation of this machine depend upon the strict observance of these precautions.
The three types of advisories are defined as follows:
WARNING
Proper Field Wiring and Grounding Required!
Failure to follow code could result in death or serious injury. All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state electrical codes.
WARNING
CAUTIONs
NOTICE:
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
Indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury. It could also be used to alert against unsafe practices.
Indicates a situation that could result in equipment or property-damage only accidents.
Important Environmental Concerns
Scientific research has shown that certain man-made chemicals can affect the earth’s naturally occurring stratospheric ozone layer when released to the atmosphere. In particular, several of the identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact to the environment. Trane advocates the responsible handli ng of all refrigerants-including industry replacements for CFCs and HCFCs such as saturated or unsaturated HFCs and HCFCs.
AVERTISSEMENT
Câblage sur site et mise à la terre corrects nécessaires!
Le non-respect de la réglementation peut entraîner des blessures graves, voire mortelles. Il est IMPÉRATIF de confier l’ensemble du câblage sur site à un électricien qualifié. Un câblage sur site mal installé ou mal mis à la terre constitue des risques D’INCENDIE et D’ÉLECTROCUTION. Pour éviter ces risques, il est IMPÉRATIF de respecter les obligations en matière de pose de câblage sur site et de mise à la terre tel que stipulé dans les règles du NEC et dans les réglementations électriques locales/nationales.
Important Responsible Refrigerant Practices
Trane believes that responsible refrigerant practices are important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified according to local rules. For the USA, the Federal Clean Air Act (Section 608) sets forth the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these service procedures. In addition, some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them.
© 2019 Ingersoll Rand OAU-SVX005C-EN
Introduction
WARNING
Personal Protective Equipment (PPE) Required!
Failure to wear proper PPE for the job being undertaken could result in death or serious injury. Technicians, in order to protect themselves from potential electrical, mechanical, and chemical hazards, MUST follow precautions in this manual and on the tags, stickers, and labels, as well as the instructions below:
Before installing/servicing this unit, technicians MUST put on all PPE required for the work being undertaken (Examples; cut resistant gloves/sleeves, butyl gloves, safety glasses, hard hat/bump cap, fall protection, electrical PPE and arc flash clothing). ALWAYS refer to appropriate Material Safety Data Sheets (MSDS)/Safety Data Sheets (SDS) and OSHA guidelines for proper PPE.
When working with or around hazardous chemicals, ALWAYS refer to the appropriate MSDS/SDS and OSHA/GHS (Global Harmonized System of Classification and Labelling of Chemicals) guidelines for information on allowable personal exposure levels, proper respiratory protection and handling instructions.
If there is a risk of energized electrical contact, arc, or flash, technicians MUST put on all PPE in accordance with OSHA, NFPA 70E, or other country-specific requirements for arc flash protection, PRIOR to servicing the unit. NEVER PERFORM ANY SWITCHING, DISCONNECTING, OR VOLTAGE TESTING WITHOUT PROPER ELECTRICAL PPE AND ARC FLASH CLOTHING. ENSURE ELECTRICAL METERS AND EQUIPMENT ARE PROPERLY RATED FOR INTENDED VOLTAGE.
AVERTISSEMENT
Équipements de protection individuelle (EPI) obligatoires!
En cas d’équipement de protection individuelle inadapté au travail entrepris, les techniciens s’exposent à des risques de blessures graves voire mortelles. Afin de se prémunir d’éventuels risques électriques, mécaniques et chimiques, les techniciens DOIVENT respecter les consignes préconisées dans le présent manuel, sur les étiquettes et les autocollants, ainsi que les instructions suivantes :
Avant d’installer/réparer cette unité, les techniciens doivent IMPÉRATIVEMENT porter tout l’équipement de protection individuelle (EPI) recommandé pour le travail entrepris (exemples: gants/manchons résistants aux coupures, gants en caoutchouc butyl, lunettes de protection, casque de chantier/antichoc, protection contre les chutes, EPI pour travaux électriques et vêtements de protection contre les arcs électriques). Consulter SYSTÉMATIQUEMENT les fiches de données de sécurité et les directives de l’OSHA pour connaître la liste des EPI adaptés.
Lors d’une intervention avec ou à proximité de produits chimiques dangereux, consulter SYSTÉMATIQUEMENT les fiches de données de sécurité appropriées et les directives de l’OSHA/du SGH (système général harmonisé de classification et d’étiquetage des produits chimiques) afin d’obtenir des renseignements sur les niveaux admissibles d’exposition personnelle, la protection respiratoire adaptée et les recommandations de manipulation.
En cas de risque d’éclair, d’arc électrique ou de contact électrique avec un équipement électrique sous tension, et AVANT de réparer l’unité, les techniciens doivent IMPÉRATIVEMENT porter tout l’équipement de protection individuelle (EPI) conformément à l’OSHA, à la norme NFPA 70E ou à toute autre exigence propre au pays pour la protection contre les arcs électriques. NE JAMAIS COMMUTER, DÉBRANCHER ou EFFECTUER DE TEST DE TENSION SANS PORTER UN EPI POUR TRAVAUX ÉLECTRIQUES OU UN VÊTEMENT DE PROTECTION APPROPRIÉ CONTRE LES ARCS ÉLECTRIQUES. IL CONVIENT DE S’ASSURER QUE LES COMPTEURS ET ÉQUIPEMENTS ÉLECTRIQUES CORRESPONDENT À LA TENSION NOMINALE PRÉVUE.
OAU-SVX005C-EN 3
Introduction
WARNING
Follow EHS Policies!
Failure to follow instructions below could result in death or serious injury.
All Ingersoll Rand personnel must follow Ingersoll Rand Environmental, Health and Safety (EHS) policies when performing work such as hot work, electrical, fall protection, lockout/tagout, refrigerant handling, etc. All policies can be found on the BOS
site. Where local regulations are more stringent than
these policies, those regulations supersede these policies.
Non-Ingersoll Rand personnel should always follow local regulations.
AVERTISSEMENT
Respecter les politiques EHS!
Le non-respect des consignes suivantes peut être à l’origine de blessures graves, voire mortelles.
Tous les membres du personnel du groupe Ingersoll Rand sont tenus de respecter les règles établies par Ingersoll Rand en matière d’environnement, d’hygiène et de sécurité (EHS) lors d’une intervention, notamment en cas de travaux à chaud, de risque d’électrocution et de chute, de procédures de verrouillage/mise hors service, de manipulation de fluide frigorigène, etc. Toutes les politiques sont disponibles sur le site BOS. Si les réglementations locales sont plus strictes que les règles imposées par le groupe, elles deviennent prioritaires.
Le personnel extérieur au groupe Ingersoll Rand est, quant à lui, systématiquement tenu d’observer les réglementations en vigueur à l’échelle locale.
WARNING
Refrigerant under High Pressure!
Failure to follow instructions below could result in an explosion which could result in death or serious injury or equipment damage. System contains oil and refrigerant under high pressure. Recover refrigerant to relieve pressure before opening the system. See unit nameplate for refrigerant type. Do not use non­approved refrigerants, refrigerant substitutes, or refrigerant additives.
AVERTISSEMENT
Fluide frigorigène sous haute pression!
Tout manquement aux instructions indiquées ci­dessous peut provoquer une explosion pouvant causer des blessures graves voire mortelles ou des dommages matériels. Le système contient de l’huile et du fluide frigorigène sous haute pression. Avant d’ouvrir le circuit, récupérez le fluide frigorigène pour éliminer toute pression dans le circuit. Consultez la plaque constructeur de l’unité pour connaître le type de fluide frigorigène employé. Utilisez uniquement des fluides frigorigènes, substituts et additifs agréés.
WARNING
Hazard of Explosion and Deadly Gases!
Failure to follow all proper safe refrigerant handling practices could result in death or serious injury. Never solder, braze or weld on refrigerant lines or any unit components that are above atmospheric pressure or where refrigerant may be present. Always remove refrigerant by following the guidelines established by the EPA Federal Clean Air Act or other state or local codes as appropriate. After refrigerant removal, use dry nitrogen to bring system back to atmospheric pressure before opening system for repairs. Mixtures of refrigerants and air under pressure may become combustible in the presence of an ignition source leading to an explosion. Excessive heat from soldering, brazing or welding with refrigerant vapors present can form highly toxic gases and extremely corrosive acids.
AVERTISSEMENT
Risque d’explosion et gaz mortels!
Le non-respect de toutes les consignes de manipulation des fluides frigorigènes peut entraîner la mort ou des blessures graves. N’effectuez en aucune circonstance des opérations de brasage ou de soudage sur des conduites de fluide frigorigène ou des composants de l’unité sous pression ou pouvant contenir du fluide frigorigène. Récupérez systématiquement le fluide frigorigène en respectant les directives de la loi américaine sur la propreté de l’air (Agence fédérale pour l’environnement) ou toute autre réglementation nationale ou locale en vigueur. Après la récupération du fluide frigorigène, utilisez de l’azote déshydraté pour ramener le système à la pression atmosphérique avant de l’ouvrir pour procéder aux réparations. Les mélanges de fluide frigorigène et d’air sous pression peuvent devenir combustibles en présence d’une source d’inflammation et provoquer une explosion. La chaleur excessive découlant de travaux de soudage ou de brasage associée à la présence de vapeurs de fluide frigorigène peut entraîner la formation de gaz hautement toxiques et d’acides extrêmement corrosifs.
4 OAU-SVX005C-EN
Introduction
WARNING
Hazard of Explosion and Deadly Gases!
Failure to follow instructions could result in death or serious injury.
If you smell gas:
1. Open windows.
2. Don’t touch electrical switches.
3. Extinguish any open flame.
4. Immediately call your gas supplier.
AVERTISSEMENT
Risque d’explosion et gaz mortels!
Le non-respect de toutes les consignes de sécurité ci­dessous peut entraîner la mort ou des blessures graves.
Si vous sentez une odeur de gaz:
1. Ouvrez les fenêtres.
2. Ne touches à aucun interrupteur.
3. Éteignez toute flamme nue.
4. Avertissez immédiatement votre fournisseur de gaz.
AVERTISSEMENT
Risque d’explosion et gaz mortels!
Le non-respect de toutes les consignes de sécurité ci­dessous peut entraîner la mort ou des blessures graves.
Il est dangereux d’utiliser ou d’entreposer de l’essence ou autres liquides ou vapeurs inflammables dans des récipients ouverts à proximité de cet appareil.
Copyright
This document and the information in it are the property of Trane, and may not be used or reproduced in whole or in part without written permission. Trane reserves the right to revise this publication at any time, and to make changes to its content without obligation to notify any person of such revision or change.
Trademarks
All trademarks referenced in this document are the trademarks of their respective owners.
Revision History
Added French language translations of warnings.
WARNING
Hazardous Service Procedures!
Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury or death. Read the installation, operating and maintenance instructions thoroughly before installing or servicing this equipment.
AVERTISSEMENT
Procédures d’entretien dangereuses!
Une installation, un réglage, une modification, une réparation ou un entretien incorrect peut entraîner des dommages matériels, des blessures ou la mort. Lisez attentivement les instructions d’installation, de fonctionnement et d’entretien avant de procéder à l’installation ou à l’entretien de cet équipement.
WARNING
Hazard of Explosion and Deadly Gases!
Failure to follow instructions could result in death or serious injury.
The use and storage of gasoline or other flammable vapors and liquids in open containers in the vicinity of this appliance is hazardous.
OAU-SVX005C-EN 5
Table of Contents
Model Number Descriptions . . . . . . . . . . . . . . 8
Horizon Outdoor Air Unit . . . . . . . . . . . . . . . 8
General Information . . . . . . . . . . . . . . . . . . . . 11
Overview of Manual . . . . . . . . . . . . . . . . . 11
Model Number Description . . . . . . . . . . . 11
Unit Nameplate . . . . . . . . . . . . . . . . . . . . 11
Compressor Nameplate . . . . . . . . . . . . . . 11
Unit Description . . . . . . . . . . . . . . . . . . . . 11
Indoor Fan Failure Input . . . . . . . . . . . . . 11
Low Pressure Control ReliaTel Control . 11
Refrigerant Circuits . . . . . . . . . . . . . . . . . 11
High Pressure Control ReliaTel Control . 11
Space Temperature / RH Sensor (Optional) 12
High Temperature Sensor . . . . . . . . . . . . 12
Outdoor Air Temperature and Relative Hu-
midity Sensor . . . . . . . . . . . . . . . . . . . . . . 12
Control Input (Occupied / Unoccupied) . 12
Hot Gas Reheat . . . . . . . . . . . . . . . . . . . . . 12
100 Percent Outdoor Air Hood with Damper
and Filters . . . . . . . . . . . . . . . . . . . . . . . . . 12
Through the Base Electrical with Disconnect
Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Hinged Access Doors . . . . . . . . . . . . . . . . 12
Unit Inspection . . . . . . . . . . . . . . . . . . . . . . . 12
First Aid Measures . . . . . . . . . . . . . . . . . . 13
Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Unit Clearances . . . . . . . . . . . . . . . . . . . . 13
Filter Installation . . . . . . . . . . . . . . . . . . . . .19
Field Installed Power Wiring . . . . . . . . . . .20
Main Unit Power . . . . . . . . . . . . . . . . . . . . . .21
Standard Wiring . . . . . . . . . . . . . . . . . . . . .21
Voltage Imbalance . . . . . . . . . . . . . . . . . . .21
Electrical Phasing (Three-Phase Motors) .22
Compressor Crankcase Heaters . . . . . . . .23
Main Unit Display and ReliaTel Controls .23
Field-Installed Control Wiring . . . . . . . . . .23
Control Power Transformer . . . . . . . . . . .23
Controls Using 24 Vac . . . . . . . . . . . . . . . . 24
Controls Using DC Analog Input/Output (Standard Low Voltage Multiconductor Wire) 24
DC Conductors . . . . . . . . . . . . . . . . . . . . . . . .25
System Configuration and Pre-Start . . . . . . .26
Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
Direct Heating Startup . . . . . . . . . . . . . . . . .29
Direct Gas-Fired Heating Start-Up Procedure
30
Initiate . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
Standby . . . . . . . . . . . . . . . . . . . . . . . . . . . .33
Normal Start-up Pre-purge . . . . . . . . . . . .33
Ignition Trials . . . . . . . . . . . . . . . . . . . . . . .33
Run . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33
Settings and Adjustments . . . . . . . . . . . . .34
Operation of the Direct Spark Ignition Control
Gas Valve . . . . . . . . . . . . . . . . . . . . . . . . . .34
Unit Clearances, Curb Dimensions, and Dimen­sional Data
Direct-Fired OAB Units . . . . . . . . . . . . . . . 14
Direct-Fired OAG Units . . . . . . . . . . . . . . 15
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Unit Weight and Rigging . . . . . . . . . . . . . . . . 16
Unit Weight . . . . . . . . . . . . . . . . . . . . . . . . 16
Rigging . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Ductwork . . . . . . . . . . . . . . . . . . . . . . . . . . 18
General Unit Requirements . . . . . . . . . . . 18
Main Electrical Power Requirements . . . 19
Condensate Drain Configuration . . . . . . 19
6 OAU-SVX005C-EN
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . .36
Monthly Maintenance . . . . . . . . . . . . . . . . . .36
Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36
Supply/Return Air Smoke Detector Mainte-
nance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Cooling Season . . . . . . . . . . . . . . . . . . . . .36
Heating Season . . . . . . . . . . . . . . . . . . . . .36
Condenser Coil Cleaning . . . . . . . . . . . . . .36
Direct-Fired Unit Maintenance Schedule . .38
Lubrication Requirements . . . . . . . . . . . . .39
Pillow Block Bearings . . . . . . . . . . . . . . . . 40
Frequency of Lubrication . . . . . . . . . . . . . .40
Dampers . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Air Filters . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Belt Tensions and Adjustments . . . . . . . 41
Suggested Belt Tension Method . . . . . . . 41
Gaskets . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Annual Maintenance . . . . . . . . . . . . . . . . 41
Heater Maintenance . . . . . . . . . . . . . . . . . 41
Inspection and Maintenance of Gas Ports 43
Final Process . . . . . . . . . . . . . . . . . . . . . . . . . 43
Performance Data . . . . . . . . . . . . . . . . . . . . . . 45
Superheat and Refrigeration Circuit Data 49
Alarms and Troubleshooting . . . . . . . . . . . . 51
Microprocessor Control . . . . . . . . . . . . . . 51
System Alarms . . . . . . . . . . . . . . . . . . . . . 51
Sensor Failure Alarm Display . . . . . . . . . 51
RTRM Failure Modes . . . . . . . . . . . . . . . . 53
Airflow Troubleshooting . . . . . . . . . . . . . 53
Direct-Fired OAB and OAG Unit Flame Relays
£ 400 MBh . . . . . . . . . . . . . . . . . . . . . . . . . 54
Direct-Fired OAG Unit Flame Relays >
400 MBh . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Table of Contents
Appendix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
OAU Filter Guide . . . . . . . . . . . . . . . . . . . . . 59
OAU-SVX005C-EN 7

Model Number Descriptions

Horizon Outdoor Air Unit

Digit 1, 2 — Unit Type
OA = Outdoor Air
Digit 3 — Cabinet Size
B = 500 cfm–3,000 cfm G = 1,250 cfm–7,500 cfm
Digit 4 — Major Design Sequence
D = Revision 1 E = Heat Pump
Digit 5, 6, 7 — Normal Gross Cooling Capacity (MBh)
000 = No Cooling 036 = 3 Tons High Efficiency 048 = 4 Tons High Efficiency 060 = 5 Tons High Efficiency 072 = 6 Tons High Efficiency 084 = 7 Tons High Efficiency 096 = 8 Tons High Efficiency 108 = 9 Tons High Efficiency 120 = 10 Tons High Efficiency 144 = 12 Tons High Efficiency 180 = 15 Tons High Efficiency 210 = 17 Tons High Efficiency 240 = 20 Tons High Efficiency 264 = 22 Tons High Efficiency 300 = 25 Tons High Efficiency 360 = 30 Tons High Efficiency
Digit 8 — Minor Design Sequence
A = Vertical Discharge/Vertical Return B = Vertical Discharge/
C = Horizontal Discharge/
D = Horizontal Discharge/
Horizontal Return
Vertical Return
Horizontal Return
Digit 9 — Voltage Selection
1 = 115/60/1 2 = 208-230/60/1 3 = 208-230/60/3 4 = 460/60/3 5 = 575/60/3
Digit 10 — Reserved for Future Use
Digit 11 — Evaporator Type
0 = No Cooling A = DX 3-Row B = DX 4-Row C = DX 4-Row Interlaced D = DX 6-Row Interlaced E = DX 8-Row F = Glycol/Chilled Water Coil G = DX 4-Row with
MSP
®
Technology
Digit 12 — Hot Gas Reheat
0= No HGRH 1 = Fin and Tube Modulating 2 = Fin and Tube On/Off 3 = Microchannel Modulating 4 = Microchannel On/Off
Digit 13 — Compressor
0= No Compressors A = Scroll Compressors B = Digital Scroll (1 C = Digital Scroll (1 D = Variable Speed Scroll (1
E = Variable Speed Scroll (1
Circuit Only)
nd
Circuit)
2
st
Circuit Only)
st
and 2nd Circuit)
st
st
and
Digit 14 — Condenser
0 = No Condenser 1 = Air-Cooled Fin and Tube 2 = Air-Cooled Fin and Tube
3 = Water-Cooled DX Condenser
4 = Air-Cooled Fin and Tube
5 = Air-Cooled Microchannel 6 = Air-Cooled Microchannel
7 = Air-Cooled Microchannel
8 = Water-Cooled DX Condenser
w/Head Pressure On/Off Control
Copper/Steel
w/Head Pressure Variable Speed
w/Head Pressure On/Off Control
Variable Speed
Copper/Nickel
Digit 15 — Refrigerant Capacity Control
0 = No RCC Valve A = RCC Valve on 1 B = RCC Valve on 1 C = ERCC Valve on 1 D = ERCC Valve on 1 E = HGBP Valve on 1 F = HGBP Valve on 1
nd
2
Circuit
st
Circuit
st
and 2nd Circuit
st
Circuit
st
and 2nd Circuit
st
Circuit
st
and
Digit 16 — Indoor Fan Motor (IFM)
0 = ECM w/Backward Curved
1 = Direct Drive w/ VFD 2 = Belt Drive 3 = Belt Drive w/VFD 4 = Special Motor Option
Plenum Fan
Digit 17 — Indoor Fan Wheel
A = 355 B = 450 C = 450 X 2 D = 12/9 T2 (Single Fan—Belt Drive) E = 12/9 BT (Dual Fan—Belt Drive)
Digit 18 — Indoor Fan Motor Power (hp)
ECM Belt Drive
A = 1 kW 2 hp B = 2 kW 3 hp C = 3 kW 5 hp D = 4 kW 7.5 hp E = 10 hp F = 15 hp
Digit 19 — Reserved for Future Use
Digit 20 — Heat Type (PRI/SEC)
0 = No Heat A = Indirect-Fired (IF) B = No Primary Heat, Direct-Fired
(DF) Secondary C = Electric—Stage D = Electric—SCR Modulating E = Dual Fuel (PRI-IF/SEC-DF) F = Dual Fuel (PRI-ELEC/SEC-DF) G = Dual Fuel (PRI-IF/SEC-ELEC) H = Dual Fuel
(PRI-ELEC-SCR/SEC-ELEC) J = Hot Water K = Steam L = No Primary Heat,
Secondary ELEC M = Dual Fuel
(PRI-ELEC-STAGED/SEC-DF) N = Dual Fuel
(PRI-ELEC-STAGED/SEC-ELEC)
Digit 21 — Primary Fuel Type
0 = No Heat 1= Natural Gas 2 = Propane 3 = Electric—Open Coil 4 = Electric—Sheathed Coil 5 = Hot Water 6 = Steam
8 OAU-SVX005C-EN
Model Number Descriptions
Digit 22 — Heat Capacity (Primary Heat Source)
IF ELEC
0 = No Heat No Heat A = 50 MBh 5 kW B = 75 MBh 10 kW C = 100 MBh 15 kW D = 125 MBh 20 kW E = 150 MBh 24 kW F = 200 MBh 28 kW G = 250 MBh 32 kW H = 300 MBh 40 kW J = 350 MBh 48 kW K = 400 MBh 60 kW L = 500 MBh 68 kW M = 600 MBh 79 kW N = 99 kW O = 111 kW P = 119 kW X = Special Heater Option
Digit 23 — Heat Capacity (Secondary Heat Source)
ELEC DF
0 = No Heat/No Secondary Heat A = 5 kW 6-in. Burner—
Up to 300 MBh
B = 10 kW 12-in. Burner—
Up to 400 MBh
C = 15 kW 12-in. Burner—
Up to 600 MBh
D = 20 kW 18-in. Burner—
Up to 400 MBh
E = 24 kW 18-in. Burner—
Up to 900 MBh
F = 28 kW
Digit 24 — Corrosive Environment Package
0 = No Corrosive Package 1 = S/S Interior, S/S Evap Coil Casing 2 = S/S Interior, Eco Coated Coils 3 = S/S Interior,
Copper/Copper Evap Coil 4 = S/S Coil Casing 5 = S/S Interior 6 = Eco-Coated Coils 7 = S/S Coil Casing with
Eco-Coated Coils 8 = Copper/Copper Evap,
HGRH Coils
Digit 25, 26 — Unit Controls
00 = Non-DDC—Electromechanical AA = Trane—Discharge Air Control
AB = Trane—Space Control w/LON
AC = Trane—Discharge Air Control
AD = Trane—Space Control
AF = Trane—Discharge Air Control
AG = Trane—Space Control
AI = Trane—Discharge Air Control
AJ = Trane—Space Control
AK = Trane—Multi-Zone VAV Control
AL = Trane—Multi-Zone VAV Control
AM = Trane—Multi-Zone VAV Control
AN = Trane—Multi-Zone VAV Control
AO = Trane—Single-Zone VAV Control
AP = Trane—Single-Zone VAV Control
AQ = Trane—Single-Zone VAV Control
AR = Trane—Single-Zone VAV Control
XX = Control Special
w/LON Read-Write w/Display
Read-Write w/Display
®
w/BACnet
w/BACnet (No Display)
w/BACnet w/Display
w/BACnet w/Display
w/LON Read-Write (No Display)
w/LON Read-Write (No Display)
w/LON Read-Write w/Display
w/BACnet w/Display
w/LON Read-Write (No Display)
w/BACnet (No Display)
w/LON Read-Write w/Display
w/BACnet w/Display
w/LON Read-Write (No Display)
w/BACnet (No Display)
(No Display)
Digit 27 — Powered Exhaust Fan Motor (PFM) and Exhaust Dampers
0 = No Powered Exhaust 1 = Direct Drive w/VFD 2 = Direct Drive (VFD by Others) 3 = Belt Drive 4 = Belt Drive w/VFD 5 = Special Motor Option 6 = ECM w/Backward Curved
7 = ECM w/Backward Curved
8 = ECM w/Backward Curved
9 = Barometric Relief Dampers
Plenum Fan
Plenum Fan and Barometric Relief Damper
Plenum Fan and Isolation Dampers w/End Switch
(NO PFM)
Digit 28 — Powered Exhaust Fan Wheel
0 = No Powered Exhaust A = 355 B = 450 C = 450 X 2 D = 12/9 T2 (Single Fan—Belt Drive) E = 12/9 BT (Dual Fan—Belt Drive)
Digit 29 — Powered Exhaust Fan Motor Power
ECM Belt Drive
0 = No Powered Exhaust A = 1 kW 2 hp B = 2 kW 3 hp C = 3 kW 5 hp D = 4 kW 7.5 hp E = 10 hp F = 15 hp
Digit 30 — Reserved for Future Use
Digit 31 — ERV (Requires Powered Exhaust)
0= No ERV A = ERV-Composite Construction
w/Bypass
B = ERV—Composite Construction
with Frost Protection w/VFD
C = ERV—Aluminum Construction
w/Bypass
D = ERV—Aluminum Construction
with Frost Protection w/VFD
Digit 32 — ERV Size
0= No ERV 1 = 3014 2 = 3622 3 = 4136 4 = 4634 5 = 5856
Digit 33 — Damper Options
0 = 100% OA 2-Position Damper 1 = 100% OA 2-Position Damper
w/RA 2-Position Damper
2 = Modulating OA and RA Dampers
w/Economizer
OAU-SVX005C-EN 9
Model Number Descriptions
Digit 34 — Filtration Options
A = No Filters B = MERV-8,30% C = MERV-13, 80% D = MERV-14, 95% E = MERV-8 30%, MERV-13 80% F = MERV-8 30%, MERV-14 95% G = MERV-8, 30% with UVC H = MERV-13, 80% with UVC J = MERV-14, 95% with UVC K = MERV-8 30%, MERV-13 80%,
and UVC L = MERV-8 30%, MERV-14 95%,
and UVC M = MERV-8 30% and TCACS N = MERV-13 80% and TCACS P = MERV-14 95% and TCACS Q = MERV-8 30%, MERV-13 80%,
and TCACS R = MERV-8 30%, MERV-14 95%,
and TCACS X = Special Filter Options
Digit 35 — Smoke Detector (Factory-Installed)
0 = No Smoke Detector 1 = Supply Smoke Detector 2 = Return Smoke Detector 3 = Supply and Return Smoke
Detectors
Digit 36 — Electrical Options
0 = Terminal Block A = Non-Fused Disconnect Switch B = Fused Disconnect Switch C = Non-Fused Disconnect Switch
w/Convenience Outlet D = Fused Disconnect Switch
w/Convenience Outlet E = Dual Point Power F = Dual Point Power
w/Convenience Outlet G = 65 SCCR Electrical Rating
w/Non-Fused Disconnect H = 65 SCCR Electrical Rating
w/Fused Disconnect J = 65 KAIC Electrical Rating
w/Non-Fused Disconnect K = 65 KAIC Electrical Rating
w/Fused Disconnect L = 65 KAIC Non-Fused
w/Convenience Outlet M = 65 KAIC Fused
w/Convenience Outlet N = 65 SCCR Non-Fused
w/Convenience Outlet
Digit 37 — Air Flow Monitoring
0 = No Airflow Monitoring 1 = Airflow Monitoring—IFM
Piezo Ring
2 = Airflow Monitoring—PE
Piezo Ring
3 = Airflow Monitoring—Outdoor Air
with Display and IFM w/Piezo Ring
4 = Airflow Monitoring—IFM
Piezo Ring and PE Piezo Ring
5 = Airflow Monitoring—Outdoor Air
Monitoring w/Display Supply Air and Exhaust Air w/Piezo Rings
6 = Airflow Monitoring—Outdoor Air
Monitoring for Direct-Fired Heat Units
Digit 38 — Accessories
0 = No Options A = Hailguards B = Hailguards and LED Service
Light in Supply Fan Section
C = LED Service Light in Supply
Fan Section
D = Hailguards and LED Service
Light in Exhaust Fan Section
E = Hailguards and LED Service
Light in Supply and Exhaust Fan Section
F = LED Service Light in Exhaust
Fan Section
G = LED Service Light in Supply and
Exhaust Fan Section
Digit 39 — Altitude
0 = Sea Level to 1,000 Feet 1 = 1,001 to 2,000 Feet 2 = 2,001 to 3,000 Feet 3 = 3,001 to 4,000 Feet 4 = 4,001 to 5,000 Feet 5 = 5,001 to 6,000 Feet 6 = 6,001 to 7,000 Feet 7 = Above 7,000 Feet
10 OAU-SVX005C-EN

General Information

Overview of Manual

Note: One copy of this document ships inside the control
panel of each unit and is customer property. It must
be retained by the unit’s maintenance personnel.
This booklet describes proper installation, operation, and maintenance procedures for air cooled systems. By carefully reviewing the information within this manual and following the instructions, the risk of improper operation and/or component damage will be minimized.
It is important that periodic maintenance be performed to help assure trouble free operation. A maintenance schedule is provided at the end of this manual. Should equipment failure occur, contact a qualified service organization with qualified, experienced HVAC techn icians to properly diagnose and repair this equipment.

Model Number Description

All products are identified by a multiple-character model number that precisely identifies a particular type of unit. An explanation of the alphanumeric identification code is provided (see the Model Number chapter). Its use will enable the owner/operator, installing contractors, and service engineers to define the operation, specific components, and other options for any specific unit.
When ordering replacement parts or requesting service, be sure to refer to the specific model number and serial number printed on the unit nameplate.

Unit Nameplate

A Mylar® unit nameplate is located on the unit’s corner support next to the control box. It includes the unit model number, serial number, electrical characteristics, refrigerant charge, as well as other pertinent unit data.
and RTRM receive information from sensors and customer binary contacts to satisfy the applicable request for ventilation, cooling, dehumidification and heating.

Indoor Fan Failure Input

The Indoor Fan Failure Switch (IFFS) is connected to verify indoor fan operation.
When there is a call for the indoor fan to be energized, the differential pressure switch, connected to the Main Unit Display, must prove airflow within 60 seconds or the Main Unit Display will shut off all mechanical operations, lock the system out and send a diagnostic alarm to the Unit Display. The system will remain locked out until a reset is initiated through the MCM via the Alarm Reset Function on the Unit Display.

Low Pressure Control ReliaTel Control

This input incorporates the compressor low pressure control (CLP 1/2) of each refrigeration circuit and can be activated by opening a field supplied contact installed on the OAUTS.
If this circuit is open before the compressor is started, the ReliaTel™ control will not allow the affected compressor to operate. Anytime this circuit is opened for 1 continuous second during compressor operation, the compressor is immediately turned “Off.” The compressor will not be allowed to restart for a minimum of 3 minutes should the contacts close.
If four consecutive open conditions occur during the first three minutes of operation, the compressor will be locked out, and a manual reset will be required to restart the compressor.

Refrigerant Circuits

Compressor Nameplate

The nameplate for the compressors are located on the side of the compressor.

Unit Description

Before shipment, each unit is leak tested, dehydrated, charged with refrigerant and compressor oil, and run tested for proper control operation.
The condenser coils are aluminum fin, mechanically bonded to copper tubing.
Direct-drive, vertical discharge condenser fans are provided with built-in thermal overload protection.
The Outdoor Air Unit Main Unit Display and ReliaTel™ Control Module (RTRM) are microelectronic control systems. The acronym RTRM is extensively throughout this document when referring to the control system network.
The optional Main Unit Display and the RTRM are mounted in the Main Control Panel. The Main Unit Display
OAU-SVX005C-EN 11
Units shall incorporate a 4- or 6-row evaporator coil. All circuits shall have thermal expansion valves (TXVs), service pressure ports, sight glass, and refrigerant line filter drier as standard. An area will be provided for replacement suction line driers. Each refrigerant circuit is equipped with a factory installed and preset refrigerant capacity control (RCC) to prevent evaporator coil temperatures below approximately 38°F (114 lb suction). The refrigerant capacity device is not installed when the unit is equipped with a digital scroll.

High Pressure Control ReliaTel Control

The compressor high pressure controls (CHP 1/2) are wired in series between the compressor outputs on RTRM1 (CHP 1/2) and the compressor contactor coils. If one of the high pressure control switches opens, the RTRM senses a lack of current while calling for cooling and locks the compressor out.
General Information

Space Temperature / RH Sensor (Optional)

Field installed, wall mounted temperature sensor (BAYSENS036A) and humidity to control space cooling, heating and dew point.

High Temperature Sensor

The Discharge Air Temperature Sensor (DTC) supplies a continuous signal to the MCM. If the MCM does not sense a signal from the DTC, the unit will go into LOCKOUT and require a manual restart once the proper operation of the DTC has been confirmed. If DAT exceeds Discharge Air High Temperature Cutoff (DHCS) of 125°F for 10 minutes, the unit will shut down and require manual restart.

Outdoor Air Temperature and Relative Humidity Sensor

This factory installed combination outdoor air sensor located in the outdoor air hood is designed to sense both outdoor air temperature and relative humidity for use by the microprocessor controller to make required ventilation, cooling, dehumidification and heating decisions.

Control Input (Occupied / Unoccupied)

Terminals are provided on the terminal strip labeled OAUTS for a field installed dry contact or switch closure to put the unit in the Occupied or Unoccupied modes.

Hot Gas Reheat

This option shall consist of a hot-gas reheat coil located on the leaving air side of the evaporator.

100 Percent Outdoor Air Hood with Damper and Filters

Factory-installed and -integrated 100 percent outdoor air hood with damper controlled by a direct coupled actuator.

Through the Base Electrical with Disconnect Switch

Factory installed 3-pole, molded case disconnect switch with provisions for through the base electrical connections will be included. The disconnect switch, with integral overcurrent circuit breaker, will be installed in the unit in a water tight enclosure with access through a hinged door. Factory wiring will be provided from the switch to the unit high voltage terminal block. The switch will be UL/CSA agency recognized.

Hinged Access Doors

Hinged access doors with hold open brackets will be factory-installed.

Unit Inspection

WARNING
Fiberglass Wool!
Product may contain fiberglass wool. Disturbing the insulation in this product during installation, maintenance or repair will expose you to airborne particles of glass wool fibers and ceramic fibers known to the state of California to cause cancer through inhalation. Glass wool fibers may also cause respiratory, skin or eye irritation.
AVERTISSEMENT
Laine de verre!
Le produit peut contenir de la laine de verre. Des interventions inappropriées sur l’isolation de ce produit pendant les opérations d’installation, d’entretien ou de réparation vous exposent à des particules aériennes de fibres de verre ou de fibres céramiques, responsables selon la législation américaine (état de Californie) de risques de cancers par inhalation. Les fibres de verre peuvent aussi provoquer des phénomènes d’irritation au niveau du système respiratoire, de la peau ou des yeux.
As soon as the unit arrives at the job site:
Verify that the nameplate data matches the data on
the sales order and bill of lading (including electrical data).
Verify that the power supply complies with the unit
nameplate specifications.
Visually inspect the exterior of the unit, including the
roof, for signs of shipping damage.
Visually inspect the internal components for shipping
damage as soon as possible after delivery and before it is stored. Do not walk on the sheet metal base pans.
If conce aled damage is discovered, notify the carrier’s
terminal of damage immediately by phone and by mail. Concealed damage must be reported within 15 days.
Request an immediate joint inspection of the damage by the carrier and the consignee. Do not remove damaged material from the receiving location. Take photos of the damage, if possible. The owner must provide reasonable evidence that the damage did not occur after delivery.
Notify the appropriate sales representative before
installing or repairing a damaged unit.
Avoid breathing fiberglass dust.
Use a NIOSH approved dust/mist respirator.
Avoid contact with the skin or eyes. Wear long-sleeved, loose-fitting clothing, gloves, and eye protection.
12 OAU-SVX005C-EN
Wash clothes separately from other clothing: rinse washer thoroughly.
Operations such as sawing, blowing, tear-out, and spraying may generate fiber concentrations requiring additional respiratory protection. Use the appropriate NIOSH approved respiration in these situations.

First Aid Measures

Eye Contact
Flush eyes with water to remove dust. If symptoms persist, seek medical attention.
Skin Contact
Wash affected areas gently with soap and warm water after handling.

Storage

Take precautions to prevent condensate from forming inside the unit’s electrical compartments and motors if:
the unit is stored before it is installed; or,
the unit is set on the roof curb, and temporary heat is provided in the building. Isolate all side panel service entrances and base pan openings (e.g., conduit holes, S/A and R/A openings, and flue openings) from the ambient air until the unit is ready for startup.
Note: Do not use the unit’s heater for temporary heat
without first completing the startup procedure detailed in “Startup,” p. 29.
The manufacturer will not assume any responsibility for equipment damage resulting from condensate accumulation on the unit’s electrical and/or mechanical components.
General Information

Unit Clearances

Unit Clearances, Curb Dimensions, and Dimensional Data chapter contains figures that illustrate the minimum operating and service clearances for either a single or multiple unit installation. These clearances are the minimum distances necessary to assure adequate serviceability, cataloged unit capacity, and peak operating efficiency.
Providing less than the recommended clearances may result in condenser coil starvation, “short-circuiting” of exhaust or recirculation of hot condenser air.
OAU-SVX005C-EN 13
Unit Clearances, Curb Dimensions, and Dimensional
84
72
36
36
48
36
48.500
25.500
25.000
3.750
93.500
9.250
27.500
9.250
12.750
13.750
1.250
3.438
122.688
RETURN
SUPPLY
55.143
55.489
52.554
52.000
22.000
3.180
15.676
ELECTRIC DISCONNECT
FRONT VIEW
12.979
18.149
144.349
126.200
97.000 29.200
RIGHT SIDE VIEW
3.250
12.000
SUPPLY
24.000 SUPPLY
16.000
26.500
RETURN
12.750
12.750
14.500
RETURN
32.450
22.000
4.498
THROUGH BASE
ELECTRIC
BOTTOM VIEW
Data
Curb Dimensions
WARNING
Combustible Materials!
Failure to maintain proper clearance between the unit heat exchanger, vent surfaces and combustible materials could cause a fire which could result in death or serious injury or property damage. Refer to unit nameplate and installation instructions for proper clearances.
AVERTISSEMENT
Matériaux combustibles!
Tout manquement à l’obligation de maintenir une distance appropriée entre l’échangeur de chaleur de l’unité, les surfaces de ventilation et les matériaux combustibles peut provoquer un incendie pouvant résulter en des blessures corporelles graves, voire mortelles, ou des dommages matériels. Reportez-vous à la plaque signalétique de l’unité et aux instructions d’installation pour connaître les distances appropriées.
Figure 2. Unit curb data for direct-fired OAB tons (in.)
Dimensional Data
Figure 3. Unit dimensional data for direct-fired OAB
(in.)

Direct-Fired OAB Units

Unit Clearances
Figure 1. Typical installation clearances for direct-fired
OAB unit (in.)
14 OAU-SVX005C-EN
Unit Clearances, Curb Dimensions, and Dimensional Data
72
84
36
36
48
36
70.500
22.625
21.000
8.750
15.000
25.000
RETURN
SUPPLY
53.000
8.750
117.500
23.375
35.375
11.875
121.371
66.096
ELECTRIC
DISCONNECT
SWITCH
THROUGH BASE
ELECTRIC
74.000
17.323
33.751 121
3.078
GAS INLET
5.5852

Direct-Fired OAG Units

Unit Clearances
Figure 4. Typical installation clearances for direct-fired
OAG unit (in.)
Dimensional Data
Figure 6. Unit dimensional data for direct-fired OAG
(in.)
Curb Dimensions
Figure 5. Unit curb data for direct-fired OAG tons (in.)
OAU-SVX005C-EN 15

Unit Weight and Rigging

WARNING
Heavy Objects!
Failure to follow instructions below or properly lift unit could result in unit dropping and possibly crushing operator/technician which could result in death or serious injury, and equipment or property-only damage. Ensure that all the lifting equipment used is properly rated for the weight of the unit being lifted. Each of the cables (chains or slings), hooks, and shackles used to lift the unit must be capable of supporting the entire weight of the unit. Lifting cables (chains or slings) may not be of the same length. Adjust as necessary for even unit lift.
AVERTISSEMENT
Objets lourds!
Le non-respect des instructions ci-dessous ou un levage inapproprié de l’unité peut provoquer sa chute voire écraser l’opérateur/le technicien, ce qui peut occasionner des blessures graves voire mortelles, et éventuellement endommager l’équipement ou provoquer des dégâts matériels. Assurez-vous que l’équipement de levage utilisé est adapté au poids de l’unité à soulever. Chaque câble (chaîne ou élingue), crochet ou manille utilisé pour le levage de l’unité doit être assez robuste pour supporter le poids total de l’unité. Les câbles, chaînes ou élingues de levage ne doivent pas être de longueur identique. Procédez au réglage afin de soulever l’unité de manière équilibrée.

Unit Weight

Table 1. Typical unit weight
Operating Weight (lb)
Model Number
OABD036* 1655 1839 OABD048* 1655 1839 OABD060* 1655 1839 OABD072* 1695 1879 OABD084* 1695 1879 OABD096* 1695 1879 OABD108* 1736 1920 OAGD120* 2912 3198 OAGD144* 2912 3198 OAGD180* 2913 3199 OAGD210* 3062 3348 OAGD240* 3134 3439 OAGD264* 3135 3439 OAGD300* 3175 3489 OAGD360* 3186 3500
Note: Minimum and maximum weights vary widely due to the highly
configurable nature of the product.
Min Max
WARNING
Improper Unit Lift!
Failure to properly lift unit could result in unit dropping and possibly crushing operator/technician which could result in death or serious injury, and equipment or property-only damage. Test lift unit approximately 24 inches to verify proper center of gravity lift point. To avoid dropping of unit, reposition lifting point if unit is not level.
AVERTISSEMENT
Levage inapproprié de l’unité!
Le non-respect des instructions ci-dessous ou un levage inapproprié de l’unité peut provoquer sa chute voire écraser l’opérateur/le technicien, ce qui peut occasionner des blessures graves voire mortelles, et éventuellement endommager l’équipement ou provoquer des dégâts matériels. Faites un test de levage de l’unité d’environ 60 cm (24 po) afin de vérifier que le point de levage correspond au centre de gravité de l’appareil. Pour éviter une chute de celle-ci, ajustez son point de levage si elle n’est pas à l’horizontale.
16 OAU-SVX005C-EN
Unit Weight and Rigging
A
DETAIL A
SCALE 1 : 12
SCREW PIN SHACKLE
4 LOCATIONS
SPREADER BARS
6-point lift
(Model: Direct-fired OAB)
SPREADER
BARS
A
SCALE 1 : 12
DETAIL A
SCREW PIN SHACKLE
4 LOCATIONS
4-point lift
(Model: Direct-fired OAG)

Rigging

Figure 7. Rigging
3. Test-lift the unit to ensure it is properly rigged and balanced, make any necessary rigging adjustments.
4. Lift the unit and position it into place. Remove fork pockets prior to setting on the curb.
5. Downflow units; align the base rail of the unit with the curb rail while lowering the unit onto the curb. Make sure that the gasket on the curb is not damaged while positioning the unit.
Before proceeding, refer to Table 1, p. 16 for typical unit operating weights and Figure 7, p. 17 for rigging drawing.
1. Rig the unit as shown in Figure 7, p. 17. Attach adequate strength lifting slings to all four lifting brackets in the unit base rail. Do not use cables, chains, or slings except as shown.
2. Install a lifting bar, as shown in Figure 7, p. 17, to protect the unit and to facilitate a uniform lift. The minimum distance between the lifting hook and the top of the unit should be 7 feet.
OAU-SVX005C-EN 17

Installation

48" Minimum
Airflow
WARNING
Hazardous Service Procedures!
Failure to follow all precautions in this manual and on the tags, stickers, and labels could result in death or serious injury. Technicians, in order to protect themselves from potential electrical, mechanical, and chemical hazards, MUST follow precautions in this manual and on the tags, stickers, and labels, as well as the following instructions: Unless specified otherwise, disconnect all electrical power including remote disconnect and discharge all energy storing devices such as capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. When necessary to work with live electrical components, have a qualified licensed electrician or other individual who has been trained in handling live electrical components perform these tasks.
AVERTISSEMENT
Procédures d’entretien dangereuses!
Le non-respect de toutes les précautions contenues dans ce manuel ainsi que sur les étiquettes et les autocollants peut entraîner des blessures graves voire mortelles. Les techniciens, afin d’être protégés des éventuels risques électriques, mécaniques et chimiques, DOIVENT suivre les précautions contenues dans ce manuel, sur les étiquettes et les autocollants, ainsi que les instructions suivantes : Sauf indication contraire, coupez toute l’alimentation électrique y compris les disjoncteurs à distance et déchargez tous les dispositifs de stockage d’énergie comme les condensateurs avant l’entretien. Respectez les procédures de verrouillage et d’étiquetage appropriées pour éviter tout risque de remise sous tension accidentelle. S’il est nécessaire de travailler avec des composants électriques sous tension, demandez à un électricien qualifié et agréé ou à une autre personne ayant la formation nécessaire pour manipuler des composants électriques sous tension d’exécuter ces tâches.

Ductwork

Elbows with turning vanes or splitters are recommended to minimize air noise due to turbulence and to reduce static pressure.
When attaching the ductwork to the unit, provide a water­tight flexible connector at the unit to prevent operating sounds from transmitting through the ductwork.
All outdoor ductwork between the unit and the structure should be weather proofed after installation is completed.
Note: For sound consideration, cut holes in the roof deck
only for the ductwork penetrations. Do not cut out the roof deck within the entire curb perimeter. All
duct work must be installed and connected to top of roof curb before the unit is set on curb.
If a Curb Accessory Kit is not used:
1. Be sure to use flexible duct connections at the unit.
2. Gaskets must be installed around the curb perimeter flange and the supply and return air opening flanges.
Note: For units will electric heat in the primary heating
position, refer to Figure 8.
Figure 8.
Important: Bottom discharge units with open coil
electric heater in primary heat location require discharge duct with 90° elbow. This is a MANDATORY installation requirement.
Note: A minimum 48" of straight duct is required before
an elbow. This is a requirement for both vertical and horizontal discharge regardless of heat type.

General Unit Requirements

The checklist listed below is a summary of the steps required to successfully install a commercial unit. This checklist is intended to acquaint the installing personnel with what is required in the installation process. It does
not replace the detailed instructions called out in the applicable sections of this manual.
Check the unit for shipping damage and material
shortage. File a freight claim and notify appropriate sales representative if damage or shortage is discovered.
Verify that the unit nameplate model, options, and
voltage are correct.
Verify that the installation location of the unit will
provide the required clearance for proper operation.
Assemble and install the roof curb (if applicable).
Refer to the latest edition of the curb installers guide that ships with each curb kit. Check curb for level installation; if not level, shim as required.
Rigging unit (refer to “Unit Weight and Rigging,”
p. 16).
18 OAU-SVX005C-EN
Installation
D" NPT FEMALE CONNECTOR
CLEANOUT PLUG
D = PIPE DIAMETER H = INTERNAL STATIC PRESSURE (IN W.G.) + 1" J = H * 0.5 L = H + J + D
Set the unit onto the curb; check for level.
Ensure unit-to-curb seal is tight and without buckles
or cracks.
Install and connect proper condensate drain line to
the evaporator condensate pan drain connection (see
Figure 9, p. 19).

Main Electrical Power Requirements

Verify that the power supply complies with the unit
nameplate specifications.
Inspect all control panel components; tighten any
loose connections.
Connect properly sized and protected power supply
wiring to a field-supplied/-installed disconnect switch and to the main power terminal block (HTB1) in the unit control panel.
Connect properly-sized earth ground.
Note: All field-installed wiring must comply with NEC
and applicable local codes.

Condensate Drain Configuration

OAU units are selected based on dehumidification capability. As such, condensate can form at a high rate. Therefore, the OAU drain pan and condensate line are sized and designed accordingly. However, an often­overlooked element of proper condensate drainage is proper P-Trap and drain line sizing and installation. An incorrectly-designed and -installed P-Trap can restrict condensate flow or cause water in the condensate drain pan to “spit” or “geyser” which may cause condensate overflow. Carefully install and trap the drain pan to ensure adequate condensate removal under all conditions.
An evaporator condensate drain connection is provided on the unit. Refer to Figure 11, p. 20 for the drain location.
A condensate trap must be installed at the unit due to the drain connection being on the “negative pressure” side of the fan. Install the P-Trap using the guidelines in Figure 9.
Pitch drain lines connected to P-Trap at least 1/2 inch for every 10 feet of horizontal run to assure proper condensate flow. Do not allow the horizontal run to sag causing a possible double-trap condition which could result in condensate backup due to “air lock”.
Figure 9. Condensate trap installation
D = Pipe diameter (1 in.) H = Internal static pressure (in wg) +1 in. J = H x 0.5 L = H + J +D
Notes:
1. Pitch drain at least 1/2 in. per 10 ft horizontal run.
2. Condensate drain pan will not drain properly if P-trap is not primed
and of adequate height to allow for cabinet operating negative pressure.

Filter Installation

WARNING
Do Not Install Filters or Flammable Components Downstream of Direct-Fired Burner!
Installing filters or flammable components downstream of the direct-fired burner could cause a fire hazard and result in death or serious injury.
AVERTISSEMENT
N’installez pas de filtre ou de composant inflammable en aval du brûleur à feu direct!
L’installation de filtres ou de composants inflammables en aval du brûleur à feu direct peut provoquer un risque d’incendie et résulter en des blessures graves, voire mortelles..
OAU-SVX005C-EN 19
Each unit ships with 2-inch permanent filters (mist eliminators) along with the specified MERV-rated pleated filters installed in the air inlet hood. The quantity of filters is determined by unit size. Access to the filters is through the hinged filter access panel on the air intake hood. Filter type, size, and quantity are determined by selected filter option and unit size.
Note: Do not operate the unit without filters. Pleated
filters are installed in the inlet hood in the direct­fired unit.
Installation
ELECTRIC
DISCONNECT
SWITCH
GAS INLET
1.25 IN. MPT CONDENSATE
DRAIN
0.5 IN. FPT
18.051
118.701
10.672
6.854
62.203
7.024
22.002
6.901
54.179
121.371
66.096
ELECTRIC
DISCONNECT
SWITCH
THROUGH BASE
ELECTRIC
74.000
17.323
33.751 121
3.078
GAS INLET
5.5852
6.000
62.268
5.044
HEIGHT OF INLET
TO BASE

Field Installed Power Wiring

WARNING
Proper Field Wiring and Grounding Required!
Failure to follow code could result in death or serious injury. All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state electrical codes.
AVERTISSEMENT
Câblage sur site et mise à la terre corrects nécessaires!
Le non-respect de la réglementation peut entraîner des blessures graves, voire mortelles. Il est IMPÉRATIF de confier l’ensemble du câblage sur site à un électricien qualifié. Un câblage sur site mal installé ou mal mis à la terre constitue des risques D’INCENDIE et D’ÉLECTROCUTION. Pour éviter ces risques, il est IMPÉRATIF de respecter les obligations en matière de pose de câblage sur site et de mise à la terre tel que stipulé dans les règles du NEC et dans les réglementations électriques locales/nationales.
Figure 11. OAG utility connections (in.)
An overall dimensional layout for the standard field installed wiring entrance into the unit is illustrated in
Figure 10 and Figure 11. To ensure that the unit’s supply
power wiring is properly sized and installed, refer to the following guidelines.
Figure 10. OAB utility connections (in.)
Table 2. OAB/OAG unit
Maximum MBh Burner Size (in.) Pipe Connection (in.)
300 6 1 660 12 1 814 18 1-1/4
Note: All field installed wiring must conform to NEC
guidelines as well as State and Local codes.
Verify that the power supply available is compatible with the unit’s nameplate ratings. The available supply power
20 OAU-SVX005C-EN
must be within 10 percent of the rated voltage stamped on the nameplate. Use only copper conductors to connect the power supply to the unit.
Installation

Main Unit Power

WARNING
Hazardous Voltage!
Failure to disconnect power before servicing could result in death or serious injury. Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized.
AVERTISSEMENT
Risque d’électrocution!
Le non-respect de cette consigne peut entraîner des blessures graves, voire mortelles. Avant toute intervention, coupez l’alimentation électrique, y compris aux sectionneurs à distance. Suivez scrupuleusement les procédures de verrouillage/mise hors service préconisées pour empêcher tout rétablissement accidentel de l’alimentation électrique.
NOTICE:
Use Copper Conductors Only!
Failure to use copper conductors could result in equipment damage as unit terminals are not designed to accept other types of conductors.

Standard Wiring

WARNING
Proper Field Wiring and Grounding Required!
Failure to follow code could result in death or serious injury. All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state electrical codes.
The electrical service must be protected from over current and short circuit conditions in accordance with NEC requirements. Protection devices must be sized according to the electrical data on the nameplate.
1. Location of the electrical service entrance is illustrated in Figure 11. Complete the unit’s power wiring connections onto either; the main terminal block HTB1 inside the unit control panel, the factory mounted non­fused disconnect switch (UCD) or circuit breaker (UCB), or the electric heat non-fused disconnect switch. Refer to the customer connection diagram that shipped with the unit for specific termination points.
2. Provide proper grounding for the unit in accordance with local and national codes.
Use the following checklist in conjunction with the checklist in “General Unit Requirements,” p. 18 to ensure that the unit is properly installed and ready for operation.
Verify that the correct size and number of filters are in
place.
Inspect the interior of the unit for tools and debris and
install all panels in preparation for starting the unit.
Check all electrical connections for tightness and
“point of termination” accuracy.
Verify condenser airflow is unobstructed.
Verify that the condenser and indoor fans turn freely
without rubbing and are properly tightened on the shafts.
Check motor mounting bolts and inlet cone for
tightness. Free spin wheel by hand to check for proper alignment of motor, wheel, and inlet cone. Record motor nameplate amps at unit-rated voltage.
Check proper indoor fan wheel rotation. Wheel
housing will be marked to indicate direction of proper rotation.
With access doors closed and secured, operate
blower at 100 percent speed. Check amp readout of amps output to indoor fan at VFD display to confirm operation within motor amp capacity.

Voltage Imbalance

AVERTISSEMENT
Câblage sur site et mise à la terre corrects nécessaires!
Le non-respect de la réglementation peut entraîner des blessures graves, voire mortelles. Il est IMPÉRATIF de confier l’ensemble du câblage sur site à un électricien qualifié. Un câblage sur site mal installé ou mal mis à la terre constitue des risques D’INCENDIE et D’ÉLECTROCUTION. Pour éviter ces risques, il est IMPÉRATIF de respecter les obligations en matière de pose de câblage sur site et de mise à la terre tel que stipulé dans les règles du NEC et dans les réglementations électriques locales/nationales.
OAU-SVX005C-EN 21
Live Electrical Components!
Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. When necessary to work with live electrical components, have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks.
WARNING
Installation
AVERTISSEMENT
Composants électriques sous tension!
Le non-respect de toutes les consignes de sécurité lors de la manipulation de composants électriques sous tension peut entraîner des blessures graves, voire mortelles. S’il est nécessaire de travailler avec des composants électriques sous tension, demandez à un électricien qualifié et agréé ou à une autre personne ayant la formation nécessaire pour manipuler des composants électriques sous tension d’exécuter ces tâches.
Three phase electrical power to the unit must meet stringent requirements for the unit to operate properly. Measure each leg (phase-to-phase) of the power supply. Each reading must fall within the utilization range stamped on the unit nameplate. If any of the readings do not fall within the proper tolerances, notify the power company to correct this situation before operating the unit.
Excessive three phase voltage imbalance between phases will cause motors to overheat and eventually fail. The maximum allowable voltage imbalance is 2.0 percent. Measure and record the voltage between phases 1, 2, and 3 and calculate the amount of imbalance as follows:

Electrical Phasing (Three-Phase Motors)

WARNING
Live Electrical Components!
Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. When necessary to work with live electrical components, have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks.
AVERTISSEMENT
Composants électriques sous tension!
Le non-respect de toutes les consignes de sécurité lors de la manipulation de composants électriques sous tension peut entraîner des blessures graves, voire mortelles. S’il est nécessaire de travailler avec des composants électriques sous tension, demandez à un électricien qualifié et agréé ou à une autre personne ayant la formation nécessaire pour manipuler des composants électriques sous tension d’exécuter ces tâches.
% Voltage Imbalance = 100 X
AV (Average Voltage) =
V1, V2, V3 = Line Voltage Readings
VD = Line Voltage reading that deviates the farthest from the average voltage.
Example: If the voltage readings of the supply power measured 221, 230, and 227, the average volts would be:
221 + 230 + 227
3
VD (reading farthest from average) = 221
The percentage of Imbalance equals:
100 X
The 2.2 percent imbalance in this example exceeds the maximum allowable imbalance of 2.0 percent. This much imbalance between phases can equal as much as a 20 percent current imbalance with a resulting increase in motor winding temperatures that will decrease motor life. If the voltage imbalance is over 2.0 percent, notify the proper agencies to correct the voltage problem before operating this equipment.
226 - 221
226
= 226 Avg.
= 2.2%
AV - VD
AV
Volt 1 + Volt 2 + Volt 3
where;
3
The compressor motor(s) and the supply fan motor are internally connected for the proper rotation when the incoming power supply is phased as A to L1, B to L2, and C to L3.
Proper electrical supply phasing can be quickly determined and corrected before starting the unit by using an instrument such as an Associated Research Model 45 Phase Sequence Indicator and following these steps:
Turn off the main source feeding power to the unit
field-supplied or factory-installed main disconnect device (switch or circuit breaker).
Close the unit disconnect device cover, leaving
disconnect switch in the off position, and turn main source power on.
Observe the ABC and CBA phase indicator lights on
the face of the sequencer. The ABC indicator light will glow if the phase is ABC. If the CBA indicator light glows, turn main source power off and then open the unit main disconnect device cover and reverse any two power wires.
Restore the main source power and recheck the
phasing. If the phasing is correct, turn main source power off then open the unit main disconnect device cover, remove the phase sequence indicator, reinstall disconnect device cover and, leaving disconnect device in the off position, turn main power source to unit on.
22 OAU-SVX005C-EN
Installation

Compressor Crankcase Heaters

WARNING
Live Electrical Components!
Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. When necessary to work with live electrical components, have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks.
AVERTISSEMENT
Composants électriques sous tension!
Le non-respect de toutes les consignes de sécurité lors de la manipulation de composants électriques sous tension peut entraîner des blessures graves, voire mortelles. S’il est nécessaire de travailler avec des composants électriques sous tension, demandez à un électricien qualifié et agréé ou à une autre personne ayant la formation nécessaire pour manipuler des composants électriques sous tension d’exécuter ces tâches.
To prevent injury or death from electrocution, it is the responsibility of the technician to recognize this hazard and use extreme care when performing service procedures with the electrical power energized.
Each compressor shall be equipped with a crankcase heater. The proper operation of the crankcase heater is important to maintain an elevated compressor oil temperature during the “Off” cycle to reduce oil foaming during compressor starts. Oil foaming occurs when refrigerant condenses in the compressor and mixes with the oil. In lower ambient conditions, refrigerant migration to the compressor could increase.
When the compressor starts, the sudden reduction in crankcase pressure causes the liquid refrigerant to boil rapidly causing the oil to foam. This condition could damage compressor bearings due to reduced lubrication and could cause compressor mechanical failures.
Before initial start up, or if main power has been off for an extended period of time, compressor crankcase heater(s) should be operated for a minimum of 8 hours prior to compressor operation. With main power OFF, remove jumper between OAUTS terminals 9 and 10 (E-Stop). Turn main power to energize crankcase heater(s). At end of warm up period turn main power off, install 9-10 jumper, turn main power on, and resume normal operation.
Following crankcase heater warm-up, turn main power disconnect off, and install jumper on E-Stop terminals 9 and 10.
Turn Main disconnect “On”.

Main Unit Display and ReliaTel Controls

When first powered “On”, the controls perform self­diagnostic initialization to check that all internal controls are functional. The Status LED located on the Main Unit Display and the Liteport LED located on the RTRM module is turned “On” within one second of power-up if internal operation is okay.

Field-Installed Control Wiring

WARNING
Proper Field Wiring and Grounding Required!
Failure to follow code could result in death or serious injury. All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state electrical codes.
AVERTISSEMENT
Câblage sur site et mise à la terre corrects nécessaires!
Le non-respect de la réglementation peut entraîner des blessures graves, voire mortelles. Il est IMPÉRATIF de confier l’ensemble du câblage sur site à un électricien qualifié. Un câblage sur site mal installé ou mal mis à la terre constitue des risques D’INCENDIE et D’ÉLECTROCUTION. Pour éviter ces risques, il est IMPÉRATIF de respecter les obligations en matière de pose de câblage sur site et de mise à la terre tel que stipulé dans les règles du NEC et dans les réglementations électriques locales/nationales.
An overall layout of the various control options available with the required number of conductors for each control device is illustrated in Figure 12, p. 25.
Note: All field wiring must conform to NEC guidelines as
well as state and local codes.

Control Power Transformer

WARNING
Hazardous Voltage!
Failure to disconnect power before servicing could result in death or serious injury. Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized.
OAU-SVX005C-EN 23
Installation
AVERTISSEMENT
Risque d’électrocution!
Le non-respect de cette consigne peut entraîner des blessures graves, voire mortelles. Avant toute intervention, coupez l’alimentation électrique, y compris aux sectionneurs à distance. Suivez scrupuleusement les procédures de verrouillage/mise hors service préconisées pour empêcher tout rétablissement accidentel de l’alimentation électrique.
The 24-volt control power transformers are to be used only with the accessories called out in this manual. Transformers rated greater than 50 VA are equipped with internal circuit breakers. If a circuit breaker trips, turn “Off” all power to the unit before attempting to reset it.
The transformers are located in the control panel. The circuit breaker is located on the left side of the transformers and can be reset by pressing in on the black reset button.
Note: Resistance in excess of 3 ohms per conductor
may cause component failure due to insufficient AC voltage supply.
3. Be sure to check all loads and conductors for grounds, shorts, and mis-wiring.
4. Do not run the AC low-voltage wiring in the same conduit with the high-voltage power wiring.
Table 3. 24 Vac conductors
Distance from Unit to Control Recommended Wire Size
000–460 feet
000–140 m
461–732 feet
104–223 m
18 gauge
0.75 mm 16 gauge
1 mm
2
2

Controls Using DC Analog Input/Output (Standard Low Voltage Multiconductor Wire)

Controls Using 24 Vac

WARNING
Hazardous Voltage!
WARNING
Hazardous Voltage!
Failure to disconnect power before servicing could result in death or serious injury. Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized.
Failure to disconnect power before servicing could result in death or serious injury. Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized.
AVERTISSEMENT
Risque d’électrocution!
Le non-respect de cette consigne peut entraîner des
AVERTISSEMENT
Risque d’électrocution!
Le non-respect de cette consigne peut entraîner des blessures graves, voire mortelles. Avant toute intervention, coupez l’alimentation électrique, y compris aux sectionneurs à distance. Suivez scrupuleusement les procédures de verrouillage/mise hors service préconisées pour empêcher tout rétablissement accidentel de l’alimentation électrique.
NOTICE:
Use Copper Conductors Only!
Failure to use copper conductors could result in equipment damage as unit terminals are not designed to accept other types of conductors.
Before installing any connecting wiring, refer to Figure 11,
p. 20 for the electrical access locations provided on the
unit and Table 3 for AC conductor sizing guidelines, and:
1. Use copper conductors unless otherwise specified.
2. Ensure that the AC control wiring between the controls and the unit’s termination point does not exceed three (3) ohms/ conductor for the length of the run.
24 OAU-SVX005C-EN
blessures graves, voire mortelles. Avant toute intervention, coupez l’alimentation électrique, y compris aux sectionneurs à distance. Suivez scrupuleusement les procédures de verrouillage/mise hors service préconisées pour empêcher tout rétablissement accidentel de l’alimentation électrique.
Before installing any connecting wiring between the unit and components utilizing a DC analog input\output signal, refer to Figure 11, p. 20 for the electrical access locations provided on the unit.
1. Table 4 lists the conductor sizing guidelines that must be followed when interconnecting the DC binary output devices and the system components utilizing a DC analog input/output signal to the unit.
Note: Resistance in excess of 2.5 ohms per conductor
can cause deviations in the accuracy of the controls.
2. Ensure that the wiring between controls and the unit’s termination point does not exceed 2.5 ohms/ conductor for the length of the run.
3. Do not run the electrical wires transporting DC signals in or around conduit housing high voltage wires.

DC Conductors

Table 4. Zone sensor module wiring
Distance from Unit to Control Recommended Wire Size
000–150 feet
0–45.7 m
151–240 feet
46–73.1 m
241–385 feet
73.5–117.3 m 386–610 feet
117.7–185.9 m 611–970 feet
186.2–295.7 m
Figure 12. OAUTS Connection B
22 gauge
0.33 mm 20 gauge
0.50 mm 18 gauge
0.75 mm 16 gauge
1.3 mm
14 gauge
2.0 mm
2
2
2
2
2
Installation
OAU-SVX005C-EN 25

System Configuration and Pre-Start

The following procedure must be completed prior to performing the procedure in the Start-up chapter. This section describes procedures to navigate the various displays on the Unit Display and configure the Outdoor Air Unit Main Unit Display system setpoints and operating parameters.
Important: This section is intended to provide
guidelines for navigation through the
remote operator display screens. For additional control system information, refer to Integration Guide: Tracer™ UC600
Programmable Controller for Packaged Outdoor Air Unit (BAS-SVP18*-EN). The
unit is configured at the factory with the default settings.
26 OAU-SVX005C-EN
System Configuration and Pre-Start
Table 5. Menu descriptions
Screen Menu Point List Min/Inactive Default Max/Active
Alarms
Reports (continued on next page)
Active Alarms List of all active alarms All Alarms List of all previous alarms Custom Graphics *NOT USED*
Program Control Discharge Air Control Space ControlSpace ControlY Heat Cool Mode Active Heat Cool N Occupancy Status Occupied|Unoccupied|Occupied Bypass|Occupied Standby|Unknown Y Compressor 1 Command Off On N Compressor 2 Command Off On N Digital Scroll Command 0% 100% N Dehumidification Command Disabled Enabled N Discharge Air Temperature Local Analog Input Economizer Mode Disabled Enabled N Evap Leaving Temp Local Analog Input Heat Capacity 0% 100% N Heating Output Command 0% 100% N Heat 1 Command Off On N Heat 2 Command Off On N Inducer Command Off On N
System Status
Gas Valve Status Binary Input HGRH Command 0% 100% N OA Damper End Switch Binary Input Outdoor Air Damper Command Closed Open N OAD Position Local Binary Input Outdoor Air Relative Humidity Local Analog Input Outdoor Air Temperature Local Analog Input Space Dewpoint Active Analog Input Space Temperature Local Analog Input Supply Fan Start Stop Command Off Off N Filter Status Clean Dirty N System Lockout Normal Normal Lockout N UNOCC Cooling Mode Off On N UNOCC Dehumid Mode Off On N UNOCC Heating Mode Off On N Discharge Airflow Local Analog Input ERV Leaving Air Humidity Local Analog Input
BAS Point?
OAU-SVX005C-EN 27
System Configuration and Pre-Start
Table 5. Menu descriptions (continued)
Screen Menu Point List Min/Inactive Default Max/Active
DAT High Temp Cutout 100°F 125°F 150°F Y DAT Low Temp Cutout 35°F 35°F 50°F Y DAT Temp Cutout Time 10 min. 10 min. 25 min. Y Discharge Air Cooling Setpoint 55°F 55°F 75°F Y Discharge Air Heating Setpoint 65°F 85°F 90°F Y EVAP Leaving Temp Setpoint 45°F 53°F 70°F Y IVFD Signal 50% 100% 100% Y Maximum Discharge Air Temperature 70°F 90°F 100°F Y Minimum Discharge Air Cooling Setpoint 40°F 50°F 65°F Y Minimum Discharge Air Heating Setpoint 50°F 55°F 60°F Y
System Setpoints
Reports (continued from previous page)
System Setup
Override Summary List of active overrides - same as selecting Override button at top of screen All Point Report List of all points (AO/AI/BO/BI/MS/etc …) in the configuration file About Controller Name listed is the version of the program installed in the UC600 Expansion Modules Provides status of expansion modules TGP2 Programs List of all TGP2 programs loaded on the UC600
Data Graphs *NOT USED*
Schedules - Refer to UC600 IOM for scheduling functions Display Preferences
Settings
Language Date and Time Clean Touchscreen
Maximum OA Damper Position 0% 100% 100% Y Minimum OA Damper Position 0% 100% 100% Y Occupied Space Cooling Setpoint 65°F 74°F 90°F Y Occupied Space Heating Setpoint 60°F 70°F 75°F Y Outdoor Air Cooling Setpoint (OACS) 70°F 75°F 85°F Y Outdoor Air Dewpoint Setpoint (OADS) 49°F 58°F 65°F Y Outdoor Air Heating Setpoint (OAHS) 40°F 70°F 70°F Y Space Dewpoint Setpoint (SPDS) 50°F 59°F 68°F Y UNOCC Space Cooling Setpoint 60°F 80°F 90°F Y UNOCC Space Dewpoint Setpoint 49°F 65°F 68°F Y UNOCC Space Heating Setpoint 50°F 60°F 70°F Y Program Control Discharge Air Control Space ControlSpace ControlY Compressor Count 004N Heater Count 002N Split Manifold Burner Not Installed Installed Installed N Return Air Damper Option Not Installed Installed Installed N Space Temp/Humidity Sensor Installed Not Installed Installed Installed N Heat Type No Heat|Gas Heat|Electric Heat|Other N Alarm Reset Off Off On Y Supply Fan Failure Reset Off Off On Y
BAS Point?
28 OAU-SVX005C-EN

Startup

Direct Heating Startup

WARNING
Hazardous Service Procedures!
Failure to follow all precautions in this manual and on the tags, stickers, and labels could result in death or serious injury.
Technicians, in order to protect themselves from potential electrical, mechanical, and chemical hazards, MUST follow precautions in this manual and on the tags, stickers, and labels, as well as the following instructions: Unless specified otherwise, disconnect all electrical power including remote disconnect and discharge all energy storing devices such as capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. When necessary to work with live electrical components, have a qualified licensed electrician or other individual who has been trained in handling live electrical components perform these tasks.
Do not attempt the following procedures until all electrical and gas connections to the unit have been completed and the outdoor air damper and evaporator fan operation have been verified and are operating correctly.
AVERTISSEMENT
Procédures d’entretien dangereuses!
Le non-respect de toutes les précautions contenues dans ce manuel ainsi que sur les étiquettes et les autocollants peut entraîner des blessures graves voire mortelles.
Les techniciens, afin d’être protégés des éventuels risques électriques, mécaniques et chimiques, DOIVENT suivre les précautions contenues dans ce manuel, sur les étiquettes et les autocollants, ainsi que les instructions suivantes : Sauf indication contraire, coupez toute l’alimentation électrique y compris les disjoncteurs à distance et déchargez tous les dispositifs de stockage d’énergie comme les condensateurs avant l’entretien. Respectez les procédures de verrouillage et d’étiquetage appropriées pour éviter tout risque de remise sous tension accidentelle. S’il est nécessaire de travailler avec des composants électriques sous tension, demandez à un électricien qualifié et agréé ou à une autre personne ayant la formation nécessaire pour manipuler des composants électriques sous tension d’exécuter ces tâches.
N’essayez pas de réaliser les procédures suivantes avant d’avoir effectué tous les raccordements en gaz et électricité sur l’unité, d’avoir inspecté le registre d’air extérieur et le ventilateur d’évaporateur et confirmé que leur fonctionnement est approprié.
WARNING
Hazard of Explosion!
Failure to follow proper safe leak test procedures could result in death or serious injury or equipment or property-only-damage. NEVER use an open flame to detect gas leaks. You MUST use a leak test solution for leak testing.
AVERTISSEMENT
Risque d’explosion!
Le non-respect des procédures d’essai d’étanchéité sûres recommandées pourrait provoquer des accidents graves, voire mortels, ou des dommages matériels. Ne vérifiez JAMAIS la présence de fuites de gaz avec une flamme nue. Vous devez IMPÉRATIVEMENT utiliser une solution de test d’étanchéité pour vérifier l’étanchéité.
Notes:
1. BEFORE OPERATING, leak test all gas piping up to heater gas valve. Smell around the unit area for gas. If gas is smelled, do NOT attempt to place heater in operation until source of gas leak is identified and corrected.
OAU-SVX005C-EN 29
Startup
2. Use only hand force to operate the gas control lever to the “ON” position. NEVER use tools. If lever does not operate by hand, replace gas valve prior to staring the unit. Forcing or attempting to repair the gas valve may result in fire or explosion.
3. Do not attempt to operate unit, if there is indication that any part or control has been under water. Any control or component that has been under water must be replaced prior to trying to start the unit.

Direct Gas-Fired Heating Start-Up Procedure

The following procedure must be followed for the unit heating section to function properly. The following procedures are to be performed after all electrical and gas connections to the unit have been completed and the outdoor air damper and evaporator fan operation have been verified and are operating satisfactorily.
Refer to Alarms and Troubleshooting chapter for additional information.
Tools Required
Voltage Meter (A)
Amp Meter
Gas Pressure Gauge
•Tachometer
Temperature Probe
Anemometer
•Service Mirror
Small Refrigeration Screwdriver
5/16-in. Nut Driver
1/2-in. Open End Wrench
1. Confirm Unit Airflow
Important: Accurate airflow readings require clean
inlet filters. If required clean or replace filters before proceeding.
All Horizon direct gas-fired heaters are factory­adjusted to achieve design airflow pressure drop (P) of -0.625 in. wc across the burner profile opening at ordered unit SCFM airflow. The burner baffles should not be adjusted. Outdoor Air conditions will cause the measured P to vary. Refer to Table 6 to see the acceptable measured pressures that may be read at various outdoor air conditions. Measure and record burner pressure drop.
Table 6. Acceptable measured pressures
OAT (°F) Burner Pressure Drop (in. wc)
0 0.720
5 0.712 10 0.705 15 0.697 20 0.690 25 0.683 30 0.676 35 0.669 40 0.663 45 0.656 50 0.650 55 0.643 60 0.637 65 0.631
70 0.625
75 0.619 80 0.613 85 0.608 90 0.602 95 0.597
100 0.592
(a)0.625-in. design pressure drop at standard air condi-
tions.
(a)
Note: If burner pressure drop is not within the range
shown in Table 6, refer to Airflow Troubleshooting section of Alarms and Troubleshooting chapter.
2. Check Inlet Gas Pressure and Confirm Gas Flow to Unit
WARNING
Hazard of Explosion!
Failed gas components could explode or leak flammable gas which could cause a fire resulting in death or serious injury or property damage. Do NOT expose gas controls to pressures above 1/2 psi (3.5 kPa). Refer to General Safety Information.
AVERTISSEMENT
Risque d’explosion!
Des composants au gaz défectueux peuvent exploser ou entraîner des fuites de gaz inflammable pouvant provoquer un incendie résultant en des blessures graves, voire mortelles, ou des dommages matériels. N’exposez PAS les régulations de gaz à des pressions supérieures à 1/2 psi (3,5 kPa). Reportez-vous à General Safety Information.
Confirm gas flow and gas supply pressure to heater. The Manual Shut-Off valve (MSO1) can be used to bleed the supply line as needed.
30 OAU-SVX005C-EN
Startup
MSO1
PG1
GV
MGV
PG2
MSO2
After confirming gas flow to unit , verify and record gas pressure at PG1.
3. Heating Starting Sequence for Gas Input Rating 400 MBh
Important: Open shut off vales at MSO1, MSO2, and
Main Gas Valve (MGV) before proceeding.
Refer to Figure 13.
Figure 13. Burner gas train
• Starting Sequence
Note: In the event Outdoor Air Conditions or Unit
Controls are such that the unit will not automatically enter the desired operating modes, refer to Alarms and Troubleshooting chapter for Control Override Procedures. For initial heating start-up, it may be necessary to remove and repeat the call for heat until the internal gas piping system is bled.
– R1 ON—OA damper OPEN
– R2 ON—Indoor Fan ON
– R6 ON—Call for Heating ON
– R7 ON—Ignition Process begins and requires
proof of flame at burner to continue
– R8 ON—Ignition Process Proven
4. Test Operating Heating Modes
Note: Heating default control signal is 25 percent for
90 seconds following successful ignition.
Important:
This test is designed to assure adequate stable gas
pressure is available when burner is firing at maximum capacity. Refer to unit nameplate rating for “Minimum Gas Supply Pressure Required to Achieve Maximum Temperature Rise.”
Depending on outdoor temperature, it may be necessary to bypass the manual reset High Temperature Limit control during this test.
a. High Fire Test Following Normal Burner Starting
Sequence
i. At ROD override, Heating Control Signal to
100 percent.
ii. When pressure at PG2 stabilizes, confirm PG1
Burner Gas Train
• Manual Shut-off Valves (2) (MSO1 and MSO2)
• Main Gas Valve—Automatic Safety On-Off with Main Gas Regulator
• Modulating Gas Valve (MGV)
• Gas Pressure Gauges
• Main Gas Inlet Pressure (PG1)
• Burner Inlet Pressure (PG2)
and PG2 pressures are within ±5 percent of the pressures shown on Burner Data Plate.
WARNING
Hazard of Explosion!
The Main Gas Valve/Pressure Regulator (GV) and
Modulating Gas Valve (MGV) have been factory set to achieve both proper maximum and proper minimum fuel input to the direct gas-fired burner.
Gas supply train includes (2) factory installed
pressure gauges. Gauge 1 (PG1) reads the main gas supply pressure. Gauge 2 reads the outlet pressure to the burner from the MGV.
See Heater Burner Data Plate for factory pressure
settings.
Electrical control panel includes control relays with
pilot lights which, when illuminated, indicate the relay is energized. For this starting sequence relays controlling Outdoor Air Damper (R1), Indoor Fan (R2), Heating Call (R6), Burner Proving (R7) and Burner ON (R8) will be used.
OAU-SVX005C-EN 31
Failed gas components could explode or leak flammable gas which could cause a fire resulting in death or serious injury or property damage. To avoid damage to unit if PG1 or PG2 exceed data plate pressures +5 percent, disable incoming gas using the manual shutoff valves and ensure incoming pressure is within nameplate data BEFORE enabling the gas.
Startup
PGR
MSO1
GR
PGV
PG2
MGV
GV2
GV1
PG1
MSO2
PSO
AVERTISSEMENT
Figure 14. > 400 MBh Gas train
Risque d’explosion!
Des composants au gaz défectueux peuvent exploser ou entraîner des fuites de gaz inflammable pouvant provoquer un incendie résultant en des blessures graves, voire mortelles, ou des dommages matériels. Pour éviter d’endommager l’unité si PG1 ou PG2 dépasse les pressions nominales indiquées sur la plaque signalétique de plus de 5 %, désactivez l’arrivée en gaz au moyen des vannes d’arrêt manuel et assurez­vous que la pression entrante est conforme aux valeurs indiquées sur la plaque signalétique AVANT d’activer l’arrivée en gaz.
iii. Record Gas Pressures
–PG1
–PG2
iv. At ROD, read and record
–Outdoor Air Temperature
–Discharge Air Temperature
–Burner P
v. Release Heating Control Signal Override
b. Low Fire Test Following Normal Burner Starting
Sequence
i. Override Heating Control Signal to 0 percent
ii. Confirm PG1 and PG2 pressures are within
±5 percent of the pressures shown on Burner Data Plate
iii. Allow a minimum of 5 minutes of operation at
0 percent heating signal
iv. At ROD read and record
–Outdoor Air Temperature
–Discharge Air Temperature
–Burner P
v. Record Gas Pressures
–PG1
–PG2
c. Ignition Cycle Test
i. Release Heating Control Signal Override
ii. Complete at least (5) calls for heat
–At each call for heat default heating start-up,
signal is 25 percent
–Following each ignition test and before
attempting the next test monitor analogue Heating Control Signal at ROD to be sure heat signal is released at end of each 90-second warm-up period
5. Burner Gas Train, Ignition Controls and Starting Sequence for Gas Input Rating > 400 MBh
Refer to Figure 14.
32 OAU-SVX005C-EN
a. Pilot Gas Train
i. Manual Shut-Off Valve (PSO)
ii. Pilot Gas Regulator (PGR)
iii. Pilot On-Off Valve (PGV)
b. Burner Gas Train
i. Manual Shut-off Valves (2) (MSO1 and MSO2)
ii. Main Gas Regulator (1) (GR)
iii. Main Gas Valves—Automatic Safety On-Off
Control (2) (GV1 and GV2)
iv. Modulating Gas Valve (MGV)
v. Gas Pressure Gauges
–Gas Supply Pressure (PG1)
–Burner Inlet Pressure (PG2)
c. Burner Control Operation
The RM7895, EC7895, and RM7896 have the operating sequence as shown in Figure 15, p. 34 and Figure 16, p. 34. The LED provides positive visual indication of the program sequence for power, pilot, flame, main, and alarm.

Initiate

The relay module enters the initiate sequence when it is powered. The RM7895A/B/C/D, EC7895A/C and RM7896A/ B/C/D can also enter the initiate sequence if the relay module verifies voltage fluctuations of +10/-15 percent or
Startup
frequency fluctuations of ±10 percent during any part of the operating sequence. The initiate sequence lasts for 10 seconds unless the voltage or frequency tolerances are not met. When not met, a hold condition is initiated and displayed on the optional KDM for at least five seconds. When met, the initiate sequence restarts. If the condition is not corrected and the hold condition exists for 4 minutes, the flame relay module locks out.
Causes for a hold condition in the initiate sequence are as follows:
AC line dropout detection.
AC line noise that can prevent a sufficient reading of the line voltage inputs.
Low line voltage brownouts.

Standby

The flame relay module is ready to start an operating sequence when the operating control input determines a call for heat is present. The burner switch, limits, operating limit control and all microcomputer-monitored circuits must be in the correct state for the relay module to continue into the “pre-purge” sequence.

Normal Start-up Pre-purge

The module provides 30-second ”pre-purge” timing with power applied and the operating control indicating a call for heat.
The airflow interlock, burner switch, and all microcomputer-monitored circuits must also be in the correct operating state.
The pre-purge sequence begins on call for heating.
Failure to establish airflow at unit airflow proving switch within 15 seconds of indoor fan enable discontinues ignition.

Ignition Trials

The pilot flame establishing period (PFEP) begins when:
The pilot valve and ignition transformer, terminals 8 and 10, are energized. The RM7895A/B, EC7895A, and RM7896A/B modules have an intermittent pilot valve, (terminal 8). The RM7895C/D, EC7895C, and RM7896C/ D modules have an interrupted pilot valve (terminal 8).
Flame must be proven by the end of the 15-second PFEP (4 seconds if configuration jumper, JR1, is clipped) to allow the sequence to continue. If a flame is not proven by the end of PFEP, a safety shut down occurs.
With flame proven, the ignition, terminal 10, is energized. This main flame establishing period (MFEP) begins when:
After ignition trials, and with the presence of flame, the main fuel valve, terminal 9, is powered. If a flameout occurs, the relay module locks out or recycles (depending on status of jumper JR2) within 0.8 or
3 seconds, depending on the flame failure response time (FFRT) of the amplifier.
The RM7895C/D, EC7895C, and RM7896C/D modules have a 10-second MFEP. After ignition trials and with the presence of flame, the main fuel valve, terminal 9, is powered. If the flameout occurs, the relay module locks out within 0.8 or 3 seconds, depending on the amplifier FFRT.
Run
The RM7895C/D, EC7895C, RM7896C/D has a delayed main valve that is energized once the “run” period is entered.
The relay module is now in “run” and remains in “run” until the controller input, terminal 6, opens, indicating that the demand is satisfied or a limit has opened.
Run/Test Switch (RM7895C/D, EC7895C, RM7896C/ D only)
The “run/test switch” is located on the top side of the relay module. This switch allows the burner sequence to be altered as follows:
In the measured “pre-purge” sequence, the “run/test switch,” placed in the “test” position, causes the prepurge timing to stop.
In the “pilot flame establishing period” sequence, the “run/test switch,” placed in the “test” position, stops the timer during the first 8 seconds of a 10-second PFEP selection, or during the first 3 seconds of a 4-second PFEP.
It also allows for pilot turn-down test and other burner adjustments. This activates a 15-second flameout timer that permits pilot flame adjustment without nuisance safety shutdowns. The run/test/switch is ignored during PFEP for the C and D relay modules if terminals 8 and 9, or 9 and 21 are jumpered.
Note: When the relay module is switched to the “test”
mode, it stops and holds at the next run/test switch point in the operating sequence. Ensure that the run/test switch is in the “run” position before leaving the installation.
OAU-SVX005C-EN 33
Startup
Figure 15. Sequence status LEDs
Figure 16. Selectable site-configurable jumpers
Notes:
Clipping and removing a site-configurable jumper
enhances the level of safety.
Clipping and removing a jumper after 200 hours of operation causes a non-resettable fault 100. The relay module must then be replaced.
Figure 17. Relay module plug-in diagram

Settings and Adjustments

The relay module has three site-configurable jumper options.
Table 7. Jumper options
Jumper # Description Intact Clipped
JR1
JR2 Flame Failure Action Recycle Lockout JR3 Airflow Switch (1LK) Failure Recycle Lockout
If necessary, clip the site-configurable jumpers with side cutters and remove the resistors from the relay module.
Pilot Flame Establishing
Period (PFEP)
10 seconds 4 seconds
WARNING
Combustible Materials!
Failure to maintain proper clearance between the unit heat exchanger, vent surfaces and combustible materials could cause a fire which could result in death or serious injury or property damage. Refer to unit nameplate and installation instructions for proper clearances.
AVERTISSEMENT
Matériaux combustibles!
Tout manquement à l’obligation de maintenir une distance appropriée entre l’échangeur de chaleur de l’unité, les surfaces de ventilation et les matériaux combustibles peut provoquer un incendie pouvant résulter en des blessures corporelles graves, voire mortelles, ou des dommages matériels. Reportez-vous à la plaque signalétique de l’unité et aux instructions d’installation pour connaître les distances appropriées.

Operation of the Direct Spark Ignition Control Gas Valve

On a call for heat, a 30-second pre-purge is initiated. Upon completion of the pre-purge, the gas valve and 60 Hz spark are energized. When flame is detected, the control enters the steady state heating condition. Steady state heating will continue until the call for heat is satisfied.
34 OAU-SVX005C-EN
Startup
If ignition is not achieved within 10 seconds, the control valve shuts off the gas and locks out. If the trial for ignition has been accomplished without ignition, the control shuts off all outputs and enters lockout. Reset is accomplished by cycling the power off for a minimum of 5 seconds.
If flame is lost once it has been established, the control will shut off the gas valve within 0.8 seconds and locks out.
If flame is sensed during a purge period when no flame should be present, the control will remain in a purge with the gas valve off until the false flame disappears.
If the gas valve is found to be powered when it should be off, or not powered when it should be on, the control will enter lockout with all outputs off. Reset is accomplished by cycling the power off for a minimum of 5 seconds.
High Fire Test Following Normal Burner Starting Sequence
– At ROD override, Heating Control Signal to
100 percent.
– When pressure at PG2 stabilizes, confirm PG1 and
PG2 pressures are within ±5 percent of the pressures shown on Burner Data Plate.
WARNING
Hazard of Explosion!
Failed gas components could explode or leak flammable gas which could cause a fire resulting in death or serious injury or property damage. To avoid damage to unit if PG1 or PG2 exceed data plate pressures +5 percent, disable incoming gas using the manual shutoff valves and ensure incoming pressure is within nameplate data BEFORE enabling the gas.
Low Fire Test Following Normal Burner Starting Sequence
– Override Heating Control Signal to 0 percent
– Confirm PG1 and PG2 pressures are within
±5 percent of the pressures shown on Burner Data Plate
– Allow a minimum of 5 minutes of operation at
0 percent heating signal
– At ROD read and record
Outdoor Air Temperature
Discharge Air Temperature
Burner P
– Record Gas Pressures
PG1
PG2
Ignition Cycle Test
– Release Heating Control Signal Override
– Complete at least (5) calls for heat
At each call for heat default heating start-up,
signal is 25 percent
Following each ignition test and before
attempting the next test monitor, analogue Heating Control Signal at ROD to be sure heat signal is released at end of each 90-second warm-up period
WARNING
Risque d’explosion!
Des composants au gaz défectueux peuvent exploser ou entraîner des fuites de gaz inflammable pouvant provoquer un incendie résultant en des blessures graves, voire mortelles, ou des dommages matériels. Pour éviter d’endommager l’unité si PG1 ou PG2 dépasse les pressions nominales indiquées sur la plaque signalétique de plus de 5 %, désactivez l’arrivée en gaz au moyen des vannes d’arrêt manuel et assurez­vous que la pression entrante est conforme aux valeurs indiquées sur la plaque signalétique AVANT d’activer l’arrivée en gaz.
– Record Gas Pressures
PG1
PG2
– At ROD, read and record
Outdoor Air Temperature
Discharge Air Temperature
Burner P
– Release Heating Control Signal Override
OAU-SVX005C-EN 35

Maintenance

Make sure all personnel are standing clear of the unit before proceeding. The system components will start when the power is applied.

Monthly Maintenance

Before completing the following checks, turn the unit OFF and lock the main power disconnect switch open.
WARNING
Hazardous Voltage!
Failure to disconnect power before servicing could result in death or serious injury. Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized.
AVERTISSEMENT
Risque d’électrocution!
Le non-respect de cette consigne peut entraîner des blessures graves, voire mortelles. Avant toute intervention, coupez l’alimentation électrique, y compris aux sectionneurs à distance. Suivez scrupuleusement les procédures de verrouillage/mise hors service préconisées pour empêcher tout rétablissement accidentel de l’alimentation électrique.

Filters

Inspect the return air filters. Clean or replace them if necessary. Refer to the unit Service Facts for filter information.

Supply/Return Air Smoke Detector Maintenance

Airflow through the unit is affected by the amount of dirt and debris accumulated on the indoor coil and filters.
To insure that airflow through the unit is adequate for proper sampling by the return air smoke detector, complete adherence to the maintenance procedures, including recommended intervals between filter changes, and coil cleaning is required.
Periodic checks and maintenance procedures must be performed on the smoke detector to insure that it will function properly.
For detailed instructions concerning these checks and procedures, refer to the appropriate section(s) of the smoke detector Installation and Maintenance Instructions provided with the literature package for this unit.
Inspect the evaporator and condenser coils for dirt, bent fins, etc. If the coils appear dirty, clean them according to the instructions described in “Condenser
Coil Cleaning,” p. 36.
Manually rotate the condenser fan(s) to ensure free movement and check motor bearings for wear. Verify that all of the fan mounting hardware is tight.
Inspect the F/A-R/A damper hinges and pins to ensure that all moving parts are securely mounted. Keep the blades clean as necessary.
Verify that all damper linkages move freely; lubricate with white grease, if necessary.
Check supply fan motor bearings; repair or replace the motor as necessary.
Check the fan shaft bearings for wear. Replace the bearings as necessary.
Verify that all wire terminal connections are tight.
Remove any corrosion present on the exterior surfaces of the unit and repaint these areas.
Generally inspect the unit for unusual conditions (e.g., loose access panels, leaking piping connections, etc.).
Make sure that all retaining screws are reinstalled in the unit access panels once these checks are complete.
With the unit running, check and record the: ambient temperature; compressor suction and discharge pressures; superheat; Record this data on an “operator’s maintenance log” like the one shown in
Table 11, p. 44. If the operating pressures indicate a
refrigerant shortage, measure the system superheat.
Note: Do NOT release refrigerant to the atmosphere! If
adding or removing refrigerant is required, the service technician must comply with all federal, state and local laws.

Heating Season

Inspect the unit’s air filters. If necessary, clean or replace them.
Check supply fan motor bearings; repair or replace the motor as necessary.
Inspect both the main unit control panel and heat section control box for loose electrical components and terminal connections, as well as damaged wire insulation. Make any necessary repairs.
Refer to “Heater Maintenance,” p. 41 and “Inspection
and Maintenance of Gas Ports,” p. 43.

Condenser Coil Cleaning

Cooling Season

Check the unit’s drain pans and condensate piping to ensure that there are no blockages.
36 OAU-SVX005C-EN
Regular coil maintenance, including annual cleaning, enhances the unit’s operating efficiency by minimizing: compressor head pressure and amperage draw; evaporator water carryover; fan brake horsepower, due to increase static pressure losses; airflow reduction.
At least once each year, or more often if the unit is located in a “dirty” environment, clean the condenser coils using the instructions outlined below. Be sure to follow these instructions as closely as possible to avoid damaging the coils.
Microchannel (MCHE) Coils
NOTICE:
Coil Damage!
Failure to follow instructions below could result in coil damage. DO NOT use any detergents with microchannel condenser coils. Use pressurized water or air ONLY, with pressure no greater than 600psi.
For additional information regarding the proper microchannel coil cleaning procedure, refer to service bulletin RT-SVB83*-EN.
Due to the soft material and thin walls of the MCHE coils, the traditional field maintenance method recommended for Round Tube Plate Fin (RTPF) coils does not apply to microchannel coils.
Moreover, chemical cleaners are a risk factor to MCHE due to the material of the coil. The manufacturer does not recommend the use of chemical cleaners to clean microchannel coils. Using chemical cleaners could lead to warranty claims being further evaluated for validity and failure analysis.
The recommended cleaning method for microchannel condenser coils is pressurized water or air with a non­pinpoint nozzle and an ECU of at least 180 with pressure no greater than 600 psi. To minimize the risk of coil damage, approach the cleaning of the coil with the pressure washer aimed perpendicular to the face of the coil during cleaning. Optimum clearance between the sprayer nozzle and the microchannel coil is 1 in.–3 in.
Round Tube Plate Fin (RTPF) Coils
To clean refrigerant coils, use a soft brush and a sprayer (either a garden pump-up type or a high-pressure sprayer). A high-quality detergent is also required; suggested brands include “SPREX A.C.”, “OAKITE 161”, “OAKITE 166” and “COILOX”. If the detergent selected is strongly alkaline (pH value exceeds 8.5), add an inhibitor.
Maintenance
AVERTISSEMENT
Produits chimiques dangereux!
Le non-respect de toutes les consignes de sécurité indiquées ci-après pourrait entraîner des blessures graves voire mortelles. Les agents de nettoyage pour serpentin peuvent être soit acides, soit fortement alcalins et peuvent entraîner des brûlures graves au contact de la peau. Manipulez les produits chimiques avec prudence et évitez tout contact avec la peau. Portez TOUJOURS un équipement de protection individuel (EPI), y compris des lunettes ou un masque facial, des gants résistant aux produits chimiques, des bottes, un tablier ou une combinaison conformément aux exigences. Pour la sécurité personnelle, voir les fiches de données de sécurité du fabricant pour l’agent de nettoyage et suivre toutes les pratiques de manipulation préconisées.
1. Remove enough panels from the unit to gain access to the coil.
2. Protect all electrical devices such as motors and controllers from any over spray.
3. Straighten any bent coil fins with a fin comb.
WARNING
Hazardous Pressures!
Failure to follow safety precautions below could result in coil bursting, which could result in death or serious injury. Coils contain refrigerant under pressure. When cleaning coils, maintain coil cleaning solution temperature under 150°F to avoid excessive pressure in the coil.
AVERTISSEMENT
Pressions dangereuses!
Tout manquement aux consignes de sécurité préconisées ci-dessous risquerait d’entraîner un éclatement du serpentin susceptible de provoquer des blessures graves voire mortelles. Les serpentins contiennent du fluide frigorigène sous pression. Lors du nettoyage des serpentins, maintenez la température de l’agent de nettoyage pour serpentin à moins de 65,5 °C (150 °F) pour éviter toute pression excessive dans le serpentin..
WARNING
Hazardous Chemicals!
Failure to follow all safety instructions below could result in death or serious injury. Coil cleaning agents can be either acidic or highly alkaline and can burn severely if contact with skin occurs. Handle chemical carefully and avoid contact with skin. ALWAYS wear Personal Protective Equipment (PPE) including goggles or face shield, chemical resistant gloves, boots, apron or suit as required. For personal safety refer to the cleaning agent manufacturer’s Materials Safety Data Sheet and follow all recommended safe handling practices.
OAU-SVX005C-EN 37
4. Mix the detergent with water according to the manufacturer’s instructions. If desired, heat the solution BUT DO NOT EXCEED 150ºF maximum to improve its cleansing capability.
5. Pour the cleaning solution into the sprayer. If a high­pressure sprayer is used:
a. do not allow sprayer pressure to exceed 600 psi.
b. the minimum nozzle spray angle is 15°.
c. maintain a minimum clearance of 6 in. between the
sprayer nozzle and the coil.
Maintenance
d. spray the solution perpendicular (at 90°) to the coil
face.
6. Spray the leaving-airflow side of the coil first; then spray the opposite side of the coil. Allow the cleaning solution to stand on the coil for five minutes.
7. Rinse both sides of the coil with cool, clean water.
8. Inspect both sides of the coil; if it still appears to be dirty, repeat Step 6 and Step 7.
9. Reinstall all of the components and panels removed in
Step 1 and any protective covers installed in Step 2.

Direct-Fired Unit Maintenance Schedule

Periodic maintenance is essential to the efficient operation and extended service life of the direct fired equipment. Failure to provide maintenance as recommended may void the equipment warranty.
WARNING
Hazardous Service Procedures!
Failure to follow all precautions in this manual and on the tags, stickers, and labels could result in death or serious injury. Technicians, in order to protect themselves from potential electrical, mechanical, and chemical hazards, MUST follow precautions in this manual and on the tags, stickers, and labels, as well as the following instructions: Unless specified otherwise, disconnect all electrical power including remote disconnect and discharge all energy storing devices such as capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. When necessary to work with live electrical components, have a qualified licensed electrician or other individual who has been trained in handling live electrical components perform these tasks.
AVERTISSEMENT
Procédures d’entretien dangereuses!
Le non-respect de toutes les précautions contenues dans ce manuel ainsi que sur les étiquettes et les autocollants peut entraîner des blessures graves voire mortelles. Les techniciens, afin d’être protégés des éventuels risques électriques, mécaniques et chimiques, DOIVENT suivre les précautions contenues dans ce manuel, sur les étiquettes et les autocollants, ainsi que les instructions suivantes : Sauf indication contraire, coupez toute l’alimentation électrique y compris les disjoncteurs à distance et déchargez tous les dispositifs de stockage d’énergie comme les condensateurs avant l’entretien. Respectez les procédures de verrouillage et d’étiquetage appropriées pour éviter tout risque de remise sous tension accidentelle. S’il est nécessaire de travailler avec des composants électriques sous tension, demandez à un électricien qualifié et agréé ou à une autre personne ayant la formation nécessaire pour manipuler des composants électriques sous tension d’exécuter ces tâches..
WARNING
Hazardous Gases and Flammable Vapors!
Failure to observe following instructions could result in death or serious injury. Exposure to hazardous gases from fuel substances have been shown to cause cancer, birth defects or other reproductive harm. Improper installation, adjustment, alteration, service or use of this product could cause flammable mixtures or lead to excessive carbon monoxide. To avoid hazardous gases and flammable vapors follow proper installation and set up of this product and all warnings as provided in this manual.
AVERTISSEMENT
Vapeurs inflammables et gaz dangereux!
Le non-respect des instructions suivantes peut être à l’origine de blessures graves, voire mortelles. L’exposition à des gaz dangereux provenant de substances combustibles est reconnue comme pouvant causer le cancer, des anomalies congénitales ou d’autres effets néfastes sur la reproduction. Des erreurs dans l’installation, le réglage, les modifications, les réparations ou la maintenance de ce produit peuvent entraîner des mélanges inflammables ou la libération excessive de monoxyde de carbone. Pour éviter des vapeurs inflammables et gaz dangereux, installez et mettez ce produits en service de manière appropriée et respectez tous les avertissements indiqués dans le présent manuel.
1. After 8 hours of operation:
a. Check that the fan belts are tight and sheaves are
aligned. The fan belts should be checked every 30 days after the first 60 days of new belt run-in.
38 OAU-SVX005C-EN
Maintenance
b. Check set-screws and bolts on the fan, bearings,
and burner assembly.
NOTICE:
Belt Over-Tension!
Over-tensioning the belt could result in equipment damage as it reduces fan and motor bearing life, accelerates belt wear, and can cause shaft failure.
2. Monthly:
a. Check all valves, piping and connections for leaks.
b. Check the flame setting.
c. Check the fuel pressure in the fuel supply line to
each heater.
d. Check the burner manifold pressure at full fire.
e. Clean the flame sensor(s) or UV sight tube(s).
f. Inspect filters. Clean or replace as necessary.
g. Inspect the main fan bearings.
h. Check all dampers, damper actuators and linkages.
Adjust and tighten if necessary.
i. Ensure that there are no obstruction blocking the air
supply to the heater or the air discharge from the heater.
j. Inspect the area and make sure that no combustible
or hazardous material has been stored within the clearances as shown on the unit nameplate.
3. Quarterly:
a. Complete the monthly maintenance schedule.
b. Check the belt tension for the main fan(s) and adjust
if necessary.
c. Check the alignment of the sheaves and adjust if
necessary.
d. Inspect all bearings, set-screws for tightness and
lubricate bearings if necessary.
e. Check the pilot electrical system. Adjust if
necessary.
f. Check the pilot assembly. Clean and adjust if
necessary.
g. Inspect the burner carefully. clean and adjust if
necessary.
h. Check voltages and amp draw on main fan motor.
i. Check the operation of all safety controls
individually.
j. Check the operation of the automatic gas shut-off
valves and check them for leakage at the pressure test ports provided.
k. On vertical units, inspect burner drip leg and drain
if necessary.
4. Off-Season/Yearly:
a. Complete the monthly and quarterly maintenance
schedule.
b. Inspect all fan wheels and housings. Clean if
necessary.
c. Check that all fan wheels and sheaves are securely
set on the shaft.
d. Inspect all bearings and alignment. Adjust if
necessary.
e. Inspect all V-belts. Replace if necessary.
f. Inspect all electrical components, connections, and
terminals. Clean and tighten where necessary.
g. Test ignition spark. Adjust gap if necessary.
h. Clean ignition electrodes and check for cracks.
i. Test flame safeguard relay and replace components
if necessary.
j. Inspect all regulators, relief valves, motorized
valves, solenoid valves, vent valves, manual shut­off valves and safety shut-off valves. Check their operation and clean as necessary.
k. Ensure all vents to the atmosphere are clean and
free from obstruction.
l. Inspect and clean all drip legs in the fuel line.
m. Lubricate fan motor as directed by motor
manufacturer.
n. Inspect fan motor wiring for loose connections.
o. Lightly oil all door latches.
p. Check that the cabinet is weather-tight. Replace
door gaskets and re-caulk as necessary.
Note: It is important to keep screened air intakes clear of
obstructions at all times.

Lubrication Requirements

Some blower motors require lubrication while others do not. Those that require lubrication can be identified by the presence of grease plugs in the motor casing at each end. Motors that do not have grease plugs cannot be greased and are lubricated for the life of the motor bearing.
Table 8. Lubrication instructions
Item Manufacturer Bearing Type
All 3-PH Fan Motors (1
HP to 100 HP) ODP,
TEFC
All 1-PH Motors
(Fractional HP) ODP,
TEFC or TEAO
Franctional HP 1-PH
ODP or TEFC
Fan Shaft Bearings Fafnir or Equal
Dampers Applied Air™ or Equal Sleeve
U.S., Bald or™ or Equal
Century™, G.E.™, or
Equal
Century , G.E. , or Equal
Single Row Ball
Bearings
Bronze Sleeve
Bearings
Bronze Sleeve
Bearings
Self-aligning, Single
Row or Double Row
Ball Bearings, Resilient
Mounted
OAU-SVX005C-EN 39
Maintenance
Lubrication of motors should be done while the motor is warm and at a standstill. Remove and clean all grease plugs and insert a grease fitting in the upper hole in the motor casing at each end (viewed as if motor were sitting horizontally on its base). There may be one or two plugs in each end casing of the motor. Add a small amount of a clean, good grade ball bearing grease (such as Exxon Polyrex™ EM or equal, with a low pressure grease gun. Run the motor five minutes before removing the grease fittings and replacing the plugs.
®
NOTICE:
Bearing Overheating!
Excess grease could result in overheating the bearings which could result in equipment damage.
Note: On totally enclosed fan cooled (TEFC) motors, the
rear end fan housing must be removed to expose the grease plugs.

Pillow Block Bearings

Pillow block bearings are used on supply blower(s). Bearings have been pre-lubricated with a number 2 lithium based greased. Re-lubrication should be done with a similar grease using a low pressure grease gun. Wipe all grease fittings clean before adding grease. Grease should be added slowly, in small amounts at frequent intervals while the shaft is being manually rotated.
A slight showing of grease at the seals with accompanying normal bearing temperature indicates proper lubrication. Normal temperature can range from “cool” to “hot to the touch” depending on size, speed and surrounding conditions. Excessive bearing temperature indicates faulty lubrication. An insufficient amount of grease is suggested by a bearing showing no grease at the seals, and a higher than normal temperature and noise level. Excessive leakage of grease at the seals, and a high operating temperature suggest too much grease.
Important: Grease twin blower inner bearing on same
schedule as two outer bearings.

Frequency of Lubrication

Frequency of lubrication depends upon operating conditions. The bearing operating temperature is the best index for determining a re-lubrication schedule. Table 9 gives the frequency of re-lubrication based upon continuous operation for various operating temperatures and can be used as a satisfactory guide for determining when all ball and roller bearings should be lubricated.
Table 9. Frequency of lubrication
Speed (rpm)
100 Up to 125 Clean 6 Months
500 Up to 150 Clean 2 Months 1000 Up to 210 Clean 2 Weeks 1500 Over 150 Clean Weekly
Any Speed Up to 150 Dirty 1 Week Any Speed Over 150 Dirty Daily to 1 Week Any Speed Any Temp. Very Dirty Daily to 1 Week Any Speed Any Te mp. Extreme Conditions Daily to 1 Week
Temp.
(°F) Cleanliness Interval

Dampers

Dampers should be inspected monthly (daily in icy weather) for securely fastened linkages, and smooth operation. If dampers are binding or excessively noisy, then lubrication may be required. Place one drop of #20 weight machine oil on each blade bearing, and linkage ball joint. Do not over lubricate, and wipe any excess from the area. Ensure to note that dampers over 49 inches long have intermediate bearings which require lubrication.

Air Filters

WARNING
Hazardous Voltage!
Failure to disconnect power before servicing could result in death or serious injury. Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized.
AVERTISSEMENT
Risque d’électrocution!
Le non-respect de cette consigne peut entraîner des blessures graves, voire mortelles. Avant toute intervention, coupez l’alimentation électrique, y compris aux sectionneurs à distance. Suivez scrupuleusement les procédures de verrouillage/mise hors service préconisées pour empêcher tout rétablissement accidentel de l’alimentation électrique.
All filter banks should be equipped with a manometer or differential pressure switch to indicate when the filters are dirty. Filters should be replaced when the differential pressure across them reaches the manufacturer’s recommended final value. Dirty filter elements should be replaced with a clean element of the same type and size. In addition, it is strongly advised that the air filters be checked every 30 days and replaced with new filters (throw-away type) or cleaned (washable type) as required. Cleanable filters should be given new application of filter coating after washing to maintain optimum performance.
40 OAU-SVX005C-EN
Maintenance

Belt Tensions and Adjustments

Belt tension is adjusted during the initial run-in and test periods at the factory. However, belts are run as slack as possible to prevent excessive damage to the bearings, yet tight enough to prevent slippage.
If necessary, tighten all belts during the first few months of operation, and verify proper tension weekly during the first 60 days, after which, 30-day check intervals are sufficient.
NOTICE:
Motor Failure!
Tightening any belt or belts by changing the pitch of an adjustable pulley will change the speed of a driven pulley. This could cause the unit to be rendered out of air balance which could result in improper unit operation or motor failure could result.

Suggested Belt Tension Method

1. Check tension frequently during the first 24 to 48-hours of run-in operation. Ideal tension is the lowest tension at which the belt will not slip under peak load conditions. Over tensioning shortens belt and bearing life.
2. To properly tension a conventional V-belt drive, use the following method:
a. Measure the span length.
b. At the center of the span, apply a force
perpendicular to the span to deflect the belt 1/64 inch for every inch of span length. For example: for a 40-inch span, apply a force that will deflect the belt 40/64 in. or 5/8 in.
c. Compare the force applied with the values given in
Table 10. If the force is between the values for
normal tension and 1-1/2 times normal tension, the belt tension should be satisfactory. If the belt tension is not within this range, it can be adjusted by loosening the motor mounting bolts and adjusting the position of the motor along its base.
Note: A new drive can be tightened to two times the
minimum value shown to allow for normal drop in tension during the run-in period.
Table 10. Belt tension specifications
Small pulley diameter range (in.) 3.4–4.2 4.4–4.6 5.8–8.6 Belt manufacture r and belt type Gates Hi-Power Pounds of force for normal
tension Pounds of force for 1-1/2 times
normal tension
Note: For recommendations of other belt types, consult respective
manufacturers.
4.4 4.9 5.8
6.6 7.4 8.7

Gaskets

Gaskets are used on doors, inspection covers, some filter racks and some outdoor air dampers. Inspect gaskets periodically and repair or replace as required.
WARNING
Check Gas Tightness of Safety Shut-Off Valves Annually!
Gas tightness of the safety shut-off valves must be checked at least on an annual basis. Failure to ensure gas tightness of the safety shut-off valves could result in an explosion which could result in death or serious injury.
AVERTISSEMENT
Vérifiez l’étanchéité au gaz des vannes d’arrêt de sécurité tous les ans!
L’étanchéité au gaz des vannes d’arrêt de sécurité doit être vérifiée au moins une fois par an. Le non-respect de l’obligation de garantir l’étanchéité des vannes d’arrêt de sécurité peut entraîner une explosion pouvant résulter en des blessures graves, voire mortelles.

Annual Maintenance

1. Inspect the tightness of the gas safety shut-off valves for the furnace by turning off the manual valve upstream of the appliance combination control.
2. Remove the 1/8 in. pipe plug on the inlet side of the combination control and connect a manometer to the tapping.
3. Turn the manual valve ON to apply pressure to the combination control.
4. Record the pressure reading on the manometer, then turn the valve OFF.
A loss of pressure indicates a leak. If a leak is detected, use a soap solution to check all threaded connections. If no leak is found, the combination control may be faulty and must be replaced before placing the appliance back in service.

Heater Maintenance

At least a yearly inspection is recommended for heating installations and more frequently for process applications in year-round operation. Experience is the best guide in determining frequency of inspection, but as a minimum, the following procedure should be followed.
WARNING
Hazardous Voltage!
Failure to disconnect power before servicing could result in death or serious injury. Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized.
OAU-SVX005C-EN 41
Maintenance
AVERTISSEMENT
Risque d’électrocution!
Le non-respect de cette consigne peut entraîner des blessures graves, voire mortelles. Avant toute intervention, coupez l’alimentation électrique, y compris aux sectionneurs à distance. Suivez scrupuleusement les procédures de verrouillage/mise hors service préconisées pour empêcher tout rétablissement accidentel de l’alimentation électrique.
WARNING
Combustible Materials!
Failure to maintain proper clearance between the unit heat exchanger, vent surfaces and combustible materials could cause a fire which could result in death or serious injury or property damage. Refer to unit nameplate and installation instructions for proper clearances.
AVERTISSEMENT
Matériaux combustibles!
Tout manquement à l’obligation de maintenir une distance appropriée entre l’échangeur de chaleur de l’unité, les surfaces de ventilation et les matériaux combustibles peut provoquer un incendie pouvant résulter en des blessures corporelles graves, voire mortelles, ou des dommages matériels. Reportez-vous à la plaque signalétique de l’unité et aux instructions d’installation pour connaître les distances appropriées.
1. Shut the system down totally, disconnecting or locking out power supply.
2. Inspect the burner carefully, including upstream and downstream sides of mixing plates as well as burner body face.
Note: The complete burner assembly may have to be
removed for proper inspection and cleaning. Any accumulation of scale or foreign material on either side of the mixing plates should be removed with a wire brush. Visually check that no holes in the mixing plates are blocked. If burner ports are plugged (even partially) clear with a piece of wire. See maintenance of gas ports.
NOTICE:
Equipment Performance!
Do not enlarge burner ports; doing so could adversely affect equipment performance.
3. If any mixing plates are loose or missing fasteners, tighten/replace as necessary. Always use zinc plated or stainless fasteners
Note: The missing plates on the burner may display
hairline cracks. These cracks are normal and
caused by thermal stresses occurring during combustion. The presence of these hairline cracks in no significant way affects the combustion efficiency or performance of the heater. Should a large opening develop, the specific mixing plate or plates must be replaced. Otherwise, it may cause difficulties in cross ignition of flame across the face of the burner.
4. Place the system back into operation and view burner while cycling through full firing range. This will give a visual check for blocked burner spots.
5. Inspect the flame rod and ignition electrode for dirt and moisture. Wipe off if necessary. Examine for any evidence of premature arcing. If in doubt, check continuity of flame rod to be sure it is not grounding out. Replace if required.
6. The porcelain on the ignition electrode must be intact (not cracked). The spark gap should be 1/8 in.
7. Replace all access panels which have been removed and operate the unit for a test period.
8. Check for normal response and function of all controls.
9. Check all gas piping for possible leaks using a soap bubble solution.
WARNING
Hazardous Gases and Flammable Vapors!
Failure to observe following instructions could result in death or serious injury. Exposure to hazardous gases from fuel substances have been shown to cause cancer, birth defects or other reproductive harm. Improper installation, adjustment, alteration, service or use of this product could cause flammable mixtures or lead to excessive carbon monoxide. To avoid hazardous gases and flammable vapors follow proper installation and set up of this product and all warnings as provided in this manual.
AVERTISSEMENT
Vapeurs inflammables et gaz dangereux!
Le non-respect des instructions suivantes peut être à l’origine de blessures graves, voire mortelles. L’exposition à des gaz dangereux provenant de substances combustibles est reconnue comme pouvant causer le cancer, des anomalies congénitales ou d’autres effets néfastes sur la reproduction. Des erreurs dans l’installation, le réglage, les modifications, les réparations ou la maintenance de ce produit peuvent entraîner des mélanges inflammables ou la libération excessive de monoxyde de carbone. Pour éviter des vapeurs inflammables et gaz dangereux, installez et mettez ce produits en service de manière appropriée et respectez tous les avertissements indiqués dans le présent manuel..
10. Inspect the support means to be sure that everything is firmly anchored in-place.
42 OAU-SVX005C-EN
Maintenance

Inspection and Maintenance of Gas Ports

Conduct initial inspection within the first month after commissioning. Visually check the gas ports of the new burner assemblies for any piping scale or debris. Use pin vise with drill bit to remove.
Figure 18. Gas port inspection
Pin Vise
1“
Gas Manifold
Annual inspections are normally adequate once the initial debris is removed. The operating conditions of the burner will determine how frequently maintenance is actually required. Use of an electric drill motor is not recommended unless both pin vise and drill (see
Figure 18) can be chucked-up in a variable-speed drill unit.
Care should be given in this instance due to the nature of drill bits and their ability to easily snap off in a port when using a drill motor. Removal of broken bits from the gas port is difficult.
Alternate drill sizes to be used are 5/64 in. (for #47) and 1/16 in. (for #50).
#45 Drill
_____________________________________________________
_____________________________________________________
_____________________________________________________
— connection(s)
_____________________________________________________
_____________________________________________________
_____________________________________________________

Final Process

For future reference, you may find it helpful to record the unit data requested below in the blanks provided.
(1) Complete Unit Model Number:
_____________________________________________________
_____________________________________________________
_____________________________________________________
(2) Unit Serial Number:
_____________________________________________________
_____________________________________________________
_____________________________________________________
(3) Wiring Diagram Numbers (from unit control panel)
— schematic(s)
_____________________________________________________
_____________________________________________________
OAU-SVX005C-EN 43
Maintenance
Table 11. Sample maintenance log
Refrigerant Circuit #1 Refrigerant Circuit #2
Suct.
Press.
Date
Current
Ambient
Temp F/C
Compr.
Oil Level
- ok
- low
- ok
- low
- ok
- low
- ok
- low
- ok
- low
- ok
- low
- ok
- low
- ok
- low
- ok
- low
- ok
- low
- ok
- low
- ok
- low
- ok
- low
Psig/kPa
Disch.
Press
Psig/kPa
Liquid
Press
Psig/kPa
Super-
heat F/C
Sub-cool
F/C
Compr.
Oil Level
- ok
- low
- ok
- low
- ok
- low
- ok
- low
- ok
- low
- ok
- low
- ok
- low
- ok
- low
- ok
- low
- ok
- low
- ok
- low
- ok
- low
- ok
- low
Suct.
Press.
Psig/kPa
Disch.
Press
Psig/kPa
Liquid
Press
Psig/kPa
Super-
heat F/C
Sub-cool
F/C
44 OAU-SVX005C-EN

Performance Data

Table 12. OABD General Data—Cooling 3–5 Tons High Efficiency
3 Tons 4 Tons 5 Tons
OABD036A OABD048A OABD060A
Cooling Performance
Gross Cooling Capacity, Btu (kW) 41,462 (12.15) 55,709 (16.33) 66,870 (19.60) Nominal cfm (m
Compressor
Number 1 1 1 Type Scroll Scroll Scroll
Outdoor Coil
Type High Performance High Performance High Performance Tube Size—OD, in. (mm) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5) Face Area, ft Rows 2 2 2 FPI 14 14 14
Indoor Coil
Type Propeller Propeller Propeller Tube Size—OD, in. (mm) 1/2 (12.7) 1/2 (12.7) 1/2 (12.7) Face Area, ft Rows 4 4 4 FPI 12 12 12 Refrigerant Control TXV TXV TXV Drain Connection Size, in. (mm) 3/4 (20) 3/4 (20) 3/4 (20)
Outdoor Fan
Type Propeller Propeller Propeller Number Used 1 1 1 Diameter, in. (mm) 27 27 27 Drive Type Direct Direct Direct No. Speeds 1 1 1 CFM (m Number Motors 1 1 1 Motor HP (kW), per motor 1.0 (0.75) 1.0 (0.75) 1.0 (0.75) Motor RPM 1140 1140 1140
Indoor Fan
Type Backward Curved Backward Curved Backward Curved Number Used 1 1 1 Diameter Varies Varies Varies Drive Type Direct Drive Direct Drive Direct Drive Number Motors 1 1 1 Motor HP (kW), Standard–Oversized 2.68–4.0 (2–3) 2.68–4.0 (2–3) 2.68–4.0 (2–3) Motor RPM Varies Varies Varies
Filters
Type Furnished Varies Varies Varies Evap Size, in. (Qty) 20 x 24 x 2 (2) 20 x 24 x 2 (2) 20 x 24 x 2 (2) Type Furnished MERV-8 MERV-8 MERV-8 ERV Size, in. (Qty) 20 x 24 x 2 (4) 20 x 24 x 2 (4) 20 x 24 x 2 (4)
Refrigerant Charge, lb of R-410A
3
/h) 500–2000 (850–3398) 500–2000 (850–3398) 500–2000 (850–3398)
2
(m2) 11 (1.02) 11 (1.02) 11 (1.02)
2
(m2) 4.17 (0.39) 4.17 (0.39) 4.17 (0.39)
3
/h) 7,000 (11,893) 7,000 (11,893) 7,000 (11,893)
See Nameplate See Nameplate See Nameplate
OAU-SVX005C-EN 45
Performance Data
Table 13. OABD General Data—Cooling 6–9 Tons High Efficiency
6 Tons 7 Tons 8 Tons 9 Tons
OABD072A OABD084A OABD096A OABD108A
Cooling Performance
Gross Cooling Capacity, Btu (kW) 78,600 (23.04) 88,768 (26.02) 99,099 (29.04) 108,214 (31.71) Nominal cfm (m
Compressor
Number 1111 Type Scroll Scroll Scroll Scroll
Outdoor Coil
Type High Performance High Performance High Performance High Performance Tube Size—OD, in. (mm) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5) Face Area, ft Rows 2222 FPI 14141414
Indoor Coil
Type High Performance High Performance High Performance High Performance Tube Size—OD, in. (mm) 3/8 (12.7) 1/2 (12.7) 1/2 (12.7) 1/2 (12.7) Face Area, ft Rows 46 46 46 46 FPI 12121212 Refrigerant Control TXV TXV TXV TX V Drain Connection Size, in. (mm) 3/4 (20) 3/4 (20) 3/4 (20) 3/4 (20)
Outdoor Fan
Type Propeller Propeller Propeller Propeller Number Used 1 1 1 1 Diameter, in. (mm) 27 27 27 27 Drive Type Direct Direct Direct Direct No. Speeds 1111 CFM (m Number Motors 1111 Motor HP (kW), per motor 1.0 (0.75) 1.0 (0.75) 1.0 (0.75) 1.0 (0.75) Motor RPM 1140 1140 1140 1140
Indoor Fan
Type Backward Curved Backward Curved Backward Curved Backward Curved Number Used 1 1 1 1 Diameter Varies Varies Varies Varies Drive Type Direct Drive Direct Drive Direct Drive Direct Drive Number Motors 1111 Motor HP (kW), Standard–Oversized 2.68–4.0 (2–3) 2.68–4.0 (2–3) 2.68–4.0 (2–3) 2.68–4.0 (2–3) Motor RPM Varies Varies Varies Varies
Filters
Type Furnished Varies Varies Varies Varies Evap Size, in. (Qty) 20 x 24 x 2 (2) 20 x 24 x 2 (2) 20 x 24 x 2 (2) 20 x 24 x 2 (2) Type Furnished MERV-8 MERV-8 MERV-8 MERV-8 ERV Size, in. (Qty) 20 x 24 x 2 (4) 20 x 24 x 2 (4) 20 x 24 x 2 (4) 20 x 24 x 2 (4)
Refrigerant Charge, lb of R-410A
3
/h) 625–3000 (1061–5097) 625–3000 (1061–5097) 625–3000 (1061–5097) 625–3000 (1061–5097)
2
(m2) 11 (1.02) 11 (1.02) 11 (1.02) 11 (1.02)
2
(m2) 6.56 (167) 5.69 (145) 6.56 (167) 5.69 (145) 6.56 (167) 5.69 (145) 6.56 (167) 5.69 (145)
3
/h) 7,000 (11,893) 7,000 (11,893) 7,000 (11,893) 7,000 (11,893)
See Nameplate See Nameplate See Nameplate See Nameplate
46 OAU-SVX005C-EN
Performance Data
Table 14. OAGD General Data—Cooling 10–17 Tons High Efficiency
10 Tons 12 Tons 15 Tons 17 Tons
OAGD120A OAGD144A OAGD180A OAGD210A
Cooling Performance
Gross Cooling Capacity, Btu (kW) 150,692 (44.16) 165,990 (48.65) 206,544 (60.53) 230,212 (67.47)
CFM
Nominal cfm (m3/h) 1250–2500 (2124–4248) 1500–3000 (2549–5097) 1875–3750 (3186–6371) 2125–4250 (3610–7221)
Compressor
Number 2222 Type Scroll Scroll Scroll Scroll
Outdoor Coil
Type High Performance High Performance High Performance High Performance Tube Size—OD, in. (mm) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5) Face Area, ft Rows 2222 FPI 14141414
Indoor Coil
Type High Performance High Performance High Performance High Performance Tube Size—OD, in. (mm) 1/2 (12.7) 1/2 (12.7) 1/2 (12.7) 1/2 (12.7) Face Area, ft Rows 46 46 46 46 FPI 12121212 Refrigerant Control TXV TXV TXV TXV Drain Connection Size, in. (mm) 3/4 (19.1) 3/4 (19.1) 3/4 (19.1) 3/4 (19.1)
Outdoor Fan
Type Propeller Propeller Propeller Propeller Number Used 2223 Diameter, in. (mm) 27 (685.8) 27 (685.8) 27 (685.8) 27 (685.8) Drive Type Direct Direct Direct Direct No. Speeds 1111 CFM (m Number Motors 2223 Motor HP (kW), per motor 1 (0.75) 1 (0.75) 1 (0.75) 1 (0.75) Motor RPM 1,140 1,140 1,140 1,140
Indoor Fan
Type Backward Curved Backward Curved Backward Curved Backward Curved Number Used 1–2 1–2 1–2 1–2 Diameter Varies Varies Varies Varies Drive Type Direct or Belt Drive Direct or Belt Drive Direct or Belt Drive Direct or Belt Drive Number Motors 1–2 1–2 1–2 1–2 Motor HP (kW), Standard–Oversized 2–12 (1.49–8.95) 2–12 (1.49–8.95) 2–12 (1.49–8.95) 2–12 (1.49–8.95) Motor RPM, Standard–Oversized Varies Varies Varies Varies
Filters
Type Furnished Number Size Recommended
Refrigerant Charge, lb of R-410A
2
(m2) 25 (2.32) 25 (2.32) 25 (2.32) 25 (2.32)
2
(m2) 10.0 (0.93) 10.0 (0.93) 10.0 (0.93) 12.0 (1.11)
3
/h) 14,000 (23,786) 14,000 (23,786) 14,000 (23,786) 21,000 (35,679)
Refer to OAU Filter Guide
in the Aopendix
See Nameplate See Nameplate See Nameplate See Nameplate
Refer to OAU Filter Guide
in the Aopendix
Refer to OAU Filter Guide
in the Aopendix
Refer to OAU Filter Guide
in the Aopendix
OAU-SVX005C-EN 47
Performance Data
Table 15. OAGD General Data—Cooling 20–30 Tons High Efficiency
20 Tons 22 Tons 25 Tons 30 Tons
OAGD240A OAGD264A OAGD300A OAGD360A
Cooling Performance
Gross Cooling Capacity, Btu (kW) 286,302 (83.91) 319,026 (93.50) 368,012 (107.85) 395,596 (115.94)
CFM
Nominal cfm (m3/h)
2500–5000
(4248–8495)
Compressor
Number 2222 Type Scroll Scroll Scroll Scroll
Outdoor Coil
Type High Performance High Performance High Performance High Performance Tube Size—OD, in. (mm) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5) Face Area, ft Rows 2222 FPI 14141414
2
(m2) 37 (3.44) 37 (3.44) 37 (3.44) 37 (3.44)
Indoor Coil
Type High Performance High Performance High Performance High Performance Tube Size—OD, in. (mm) 1/2 (12.7) 1/2 (12.7) 1/2 (12.7) 1/2 (12.7) Face Area, ft Rows 46 46 46 46 FPI 12121212 Refrigerant Control TXV TXV TXV TXV Drain Connection Size, in. (mm) 3/4 (19.1) 3/4 (19.1) 3/4 (19.1) 3/4 (19.1)
2
(m2) 12.0 (1.11) 12.0 (1.11) 15.0 (1.39) 15.0 (1.39)
Outdoor Fan
Type Propeller Propeller Propeller Propeller Number Used 3333 Diameter, in. (mm) 27 (685.8) 27 (685.8) 27 (685.8) 27 (685.8) Drive Type Direct Direct Direct Direct No. Speeds 1111
3
CFM (m Number Motors 3333 Motor HP (kW), per motor 1 (0.75) 1 (0.75) 1 (0.75) 1 (0.75) Motor RPM 1,140 1,140 1,140 1,140
/h) 21,000 (35,679) 21,000 (35,679) 21,000 (35,679) 21,000 (35,679)
Indoor Fan
Type Backward Curved Backward Curved Backward Curved Backward Curved Number Used 1–2 1–2 1–2 1–2 Diameter Varies Varies Varies Varies Drive Type Direct or Belt Drive Direct or Belt Drive Direct or Belt Drive Direct or Belt Drive Number Motors 1–2 1–2 1–2 1–2 Motor HP (kW), Standard–Oversized 2–12 (1.49–8.95) 2–12 (1.49–8.95) 2–12 (1.49–8.95) 2–12 (1.49–8.95) Motor RPM, Standard–Oversized Varies Varies Varies Varies
Filters
Type Furnished Number Size Recommended
Refrigerant Charge, lb of R-410A
Refer to OAU Filter Guide
in the Aopendix
See Nameplate See Nameplate See Nameplate See Nameplate
2750–5500
(4672–9345)
Refer to OAU Filter Guide
in the Aopendix
3125–6250
(5309–10619)
Refer to OAU Filter Guide
in the Aopendix
3750–7500
(6371–12743)
Refer to OAU Filter Guide
in the Aopendix
48 OAU-SVX005C-EN
Performance Data

Superheat and Refrigeration Circuit Data

Figure 19. Refrigeration diagram: Single compressor
without reheat
Figure 20. Refrigeration diagram: Single compressor
with reheat
OAU-SVX005C-EN 49
Performance Data
Figure 21. Refrigeration diagram: dual compressor
without reheat
Figure 22. Refrigeration diagram: dual compressor with
reheat
50 OAU-SVX005C-EN

Alarms and Troubleshooting

Microprocessor Control

The Main Unit Display and RTRM have the ability to provide the service personnel with some unit diagnostics and system status information.
WARNING
Hazardous Service Procedures!
Failure to follow all precautions in this manual and on the tags, stickers, and labels could result in death or serious injury. Technicians, in order to protect themselves from potential electrical, mechanical, and chemical hazards, MUST follow precautions in this manual and on the tags, stickers, and labels, as well as the following instructions: Unless specified otherwise, disconnect all electrical power including remote disconnect and discharge all energy storing devices such as capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. When necessary to work with live electrical components, have a qualified licensed electrician or other individual who has been trained in handling live electrical components perform these tasks.
AVERTISSEMENT
Procédures d’entretien dangereuses!
Le non-respect de toutes les précautions contenues dans ce manuel ainsi que sur les étiquettes et les autocollants peut entraîner des blessures graves voire mortelles. Les techniciens, afin d’être protégés des éventuels risques électriques, mécaniques et chimiques, DOIVENT suivre les précautions contenues dans ce manuel, sur les étiquettes et les autocollants, ainsi que les instructions suivantes : Sauf indication contraire, coupez toute l’alimentation électrique y compris les disjoncteurs à distance et déchargez tous les dispositifs de stockage d’énergie comme les condensateurs avant l’entretien. Respectez les procédures de verrouillage et d’étiquetage appropriées pour éviter tout risque de remise sous tension accidentelle. S’il est nécessaire de travailler avec des composants électriques sous tension, demandez à un électricien qualifié et agréé ou à une autre personne ayant la formation nécessaire pour manipuler des composants électriques sous tension d’exécuter ces tâches.
System status
Cooling status
If a System failure is indicated, proceed to Step 4. If no failures are indicated, proceed to Step 5.
4. If a System failure is indicated, recheck Step 1 and Step
2. If the LED is not lit in Step 1, and 24 Vac is present in Step 2, the RTRM has failed. Replace the RTRM.
5. If no failures are indicated, use one of the override options to start the unit. Following the Override procedure will allow you to check all of the operating modes, and all of the external controls (relays, contactors, etc.) for each respective mode.
6. Refer to the sequence of operations for each mode, to assist in verifying proper operation. Make the necessary repairs and proceed to Step 7.
7. If no abnormal operating conditions appear in the Override mode, release the override and turn the power “Off” at the main power disconnect switch.

System Alarms

The Main Unit Display has built in alarms to help the operator troubleshoot system failures. This section will describe these alarms and provide a guide to troubleshooting the all unit operating modes.
Comprehensive system alarms and diagnostics are accessed through the Alarms icon at the unit display discussed later in the section, or through Tracer TU programming on connected computer. Sensor failures may be viewed through the Alarms icon.
If an alarm is present, the main indicator light on the UC600 will blink red. If the optional unit display is installed, the Alarm icon on the display will register ALARM, illuminate red and flash.
Important: The space temperature sensor (SPTC) and
space relative humidity sensor (SPHC) will read failed if they are not connected; they will Alarm as “In Fault.”

Sensor Failure Alarm Display

Press the Alarm button on the Home display of the Unit Display to display system sensor status as described in
Table 16 and Table 17, p. 52.
1. Verify that the Liteport LED on the RTRM is burning continuously. If the LED is lit, go to Step 3.
2. If the LED is not lit, verify that 24 Vac is presence between J1-1 and J1-2. If 24 Vac is present, proceed to
Step 3. If 24 Vac is not present, check the unit main
power supply, check transformer (TNS1). Proceed to
Step 3 if necessary.
3. Utilizing “Method 1” in the RTRM “System Status Checkout Procedure”, check the following:
OAU-SVX005C-EN 51
Alarms and Troubleshooting
Table 16. TOAU UC600 alarms
Point Diagnostic Possible Cause
VFD not operating Outdoor and/or Return Air Dampers not
Operating Properly
Indoor Fan
1
Failure
OAD Proving
3
Switch
Discharge Air
6
Temp Source Failure
8 Fire Shutdown BAS ONLY
Low Temp
10
Lockout
Space Temp
11
Source Failure
OA Temp Source
13
Failure
OA Humidity
14
Source Failure
High Temp
15
Lockout
17 System Lockout
Space RH Source
19
Failure
Indoor Fan Motor Failure Indoor Fan Failure Switch IFFS (pressure)
Failure IFFS Tubing damaged or not properly
connected Refer to startup procedure No voltage at actuator Failed OAD power transformer No continuity thru end switch (check at UC) Note: If unit optional RA damper is
installed, send switch on OAD is always proven
BAS communication down Failed sensor or improper sensor
installation
Heat Overridden OFF Compressor(s) Overridden ON Setpoint Failures Incorrect DAT sensor malfunction Reference Table 17, p. 52 for heat failure
issues BAS communication down Failed sensor or improper sensor
installation BAS communication down Failed sensor or improper sensor
installation BAS communication down Failed sensor or improper sensor
installation Humidity Wiring is polarity sensitive Heat Overridden ON Low discharge air volume Dirty air filters High gas heater manifold pressure OA/RA damper position incorrect High temp limit not properly installed or
wired DAT sensor malfunction Check all Alarms External safety device failed open BAS communication down Failed sensor or improper sensor
installation Humidity Wiring is polarity sensitive
Table 16. TOAU UC600 alarms (continued)
Point Diagnostic Possible Cause
Applies to 5:1 and 10:1 Gas Heaters Only T rips after heat command “ON” and no GV
status offer 1 minute Refer to unit “Service Facts” heat control
LED status legend
42 Heat Failure
No gas, low gas pressure or high gas pressure to unit
Unit Manual shutoffs closed Heater inducer failure Heat relay failure Loose or incorrect wiring
Table 17. TOAU UC600 troubleshooting
Trouble Possible Cause
No power supply to unit disconnect switch Power disconnect tripped Lockout alarm mode
Unit Not Running
No Heat
No Compressor
Wide Discharge Temp Swings
Space too Hot, Cold or Humid
IFM or PEX VFD OC Trip
EX VFD only run to Min HZ Setting
Emergency Stop condition exists Unit in Unoccupied mode Discharge air sensor failed or not installed and
connected to unit No gas supply to unit Unit manual gas valve(s) closed Heater high limit tripped Heat relay not energized Conditions do not warrant call for heat Heater control module malfunction Roll out switch trip Main gas on-off switch OFF Inducer fan failure Heater air proving switch not making or failed Compressor limit switch(es) open Compressor relay not energized or failed Conditions do not warrant call for cooling or
dehumidification Discharge air sensor position must be at least
4 ft.-0 in. away from unit outlet Min and Max gas heater manifold pressures not set
correctly Setpoints not adjusted properly Space sensors not correctly located or wired Malfunctioning space sensor Overcurrent alarm requires max Hz sett ing on VFD
be checked and set to not exceed motor nameplate amps
If supplied with RA pressure transducer and modulating damper setup is not installed or properly wired.
52 OAU-SVX005C-EN
Alarms and Troubleshooting
Table 17. TOAU UC600 troubleshooting (continued)
Trouble Possible Cause
High fire gas manifold pressure too high Supply fan speed too low
Unit Trips Heater High Limit
Protonode Not Communicating
Dirty or clogged filters Restricted discharge air duct Temperature of air entering heater too high Defective high limit
Change Baud rate on UC600 to 38,400

RTRM Failure Modes

WARNING
Live Electrical Components!
Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. When necessary to work with live electrical components, have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks.
AVERTISSEMENT
Composants électriques sous tension!
Le non-respect de toutes les consignes de sécurité lors de la manipulation de composants électriques sous tension peut entraîner des blessures graves, voire mortelles. S’il est nécessaire de travailler avec des composants électriques sous tension, demandez à un électricien qualifié et agréé ou à une autre personne ayant la formation nécessaire pour manipuler des composants électriques sous tension d’exécuter ces tâches.
Following is the listing of RTRM failure indication causes.
System Failure
Check the voltage between RTRM terminals 6 and 9 on J6, it should read approximately 32 Vdc. If no voltage is present, a System failure has occurred. Refer to Step 4 in
“Microprocessor Control,” p. 51 for the recommended
troubleshooting procedure.
Cooling Failure
CLP1 has opened during the 3 minute minimum “on time” during four consecutive compressor starts, check CLP1 by testing voltage between the J1-8 and J3-2 terminals on the RTRM and ground. If 24 Vac is present, the CLP has not tripped. If no voltage is present, CLP has tripped.
Cool Failure
Measure the voltage between terminals J6-8 and J6-6.
Cool Operating = approximately 32 Vdc
Cool Off = less than 1 Vdc, approximately 0.75 Vdc
Cooling Failure = voltage alternates between 32 Vdc and
0.75 Vdc

Airflow Troubleshooting

Table 18. Airflow troubleshooting
Profile Opening Width (in.)
Airflow
500 6.5 750 7.5 1000 9 1250 10 1500 11-1/4 1750 12-1/2 2000 13-3/4 2250 14-3/4 2500 16 14 2750 17-1/4 15 3000 18-1/2 15-3/4 14-1/4 3250 19-3/4 16-3/4 15 3500 21 17-1/2 15-1/2 3750 22 18-1/4 16-1/4 4000 23-1/4 19-1/4 17 4250 24-1/2 20 17-1/2 4500 25-3/4 21 18-1/4 4750 27 21-3/4 18-3/4 5000 22-1/2 19-1/2 5250 23-1/2 20-1/4 5500 24-1/4 20-3/4 5750 25 21-1/2 6000 26 22 6250 26-3/4 22-3/4 6500 27-3/4 23-1/2 6750 28-1/2 24 7000 29-1/4 24-3/4 7250 30-1/4 25-1/4 7500 31 26
6-in. Burner 12-in. Burner 18-in. Burner
System Failure
Measure the voltage between terminals J6-9 and J6-6.
Normal Operation = approximately 32 Vdc
System Failure = less than 1 Vdc, approximately 0.75 Vdc
OAU-SVX005C-EN 53
Alarms and Troubleshooting
Direct-Fired OAB and OAG Unit Flame Relays 400 MBh
Procédures d’entretien dangereuses!
WARNING
Hazardous Service Procedures!
Failure to follow all precautions in this manual and on the tags, stickers, and labels could result in death or serious injury. Technicians, in order to protect themselves from potential electrical, mechanical, and chemical hazards, MUST follow precautions in this manual and on the tags, stickers, and labels, as well as the following instructions: Unless specified otherwise, disconnect all electrical power including remote disconnect and discharge all energy storing devices such as capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. When necessary to work with live electrical components, have a qualified licensed electrician or other individual who has been trained in handling live electrical components perform these tasks.
Table 19. Lockout models B, H D, and J only—Green LED status codes
Le non-respect de toutes les précautions contenues dans ce manuel ainsi que sur les étiquettes et les autocollants peut entraîner des blessures graves voire mortelles. Les techniciens, afin d’être protégés des éventuels risques électriques, mécaniques et chimiques, DOIVENT suivre les précautions contenues dans ce manuel, sur les étiquettes et les autocollants, ainsi que les instructions suivantes : Sauf indication contraire, coupez toute l’alimentation électrique y compris les disjoncteurs à distance et déchargez tous les dispositifs de stockage d’énergie comme les condensateurs avant l’entretien. Respectez les procédures de verrouillage et d’étiquetage appropriées pour éviter tout risque de remise sous tension accidentelle. S’il est nécessaire de travailler avec des composants électriques sous tension, demandez à un électricien qualifié et agréé ou à une autre personne ayant la formation nécessaire pour manipuler des composants électriques sous tension d’exécuter ces tâches.
AVERTISSEMENT
Green LED Flash
(a)
Code
OFF No “Call for Heat” Not applicable None Flash Fast Power up - internal check Not applicable None Heartbeat Normal startup - ignition
4 Seconds ON then “x” flashes
2 Lockout - Failed trial for
3Recycle
4 Flame sensed out of
6 Control Internal Error Control remains in wait mode. When the fault
7 Flame rod shorted to
8 Low secondary voltage
(a)Flash Code Descriptions:
- Flash Fast: Rapid blinking.
- Heartbeat: Constant 1/2 second bright, 1/2 second dim cycles.
- 4 second solid on pulse followed by “x” 1 second flashes indicates flame current to the nearest
- A single flash code number signifies that the LED flashes X times at 2 Hz, remains off for two seconds, and then repeats the sequence.
Indicates Next System Action Recommended Service Action
sequence started (including prepurge)
Device in run mode. “x” = flame current to the nearest μA.
ignition
- Flame failed during run
sequence
ground
supply
Not applicable None
Not applicable None
Remain in lockout until “Call for Heat” is cycled. Check gas supply , pilot burner , spark and flame
Initiate new trial for ignition. Flash code will remain through the ignition trial until flame is proved.
If situation self corrects within 10 seconds, control returns to normal sequence. If flame out of sequence remains longer than 10 seconds, control will resume normal operation 1 hour after error is corrected.
corrects, control resumes normal operation. Control remains in wait mode. When the fault
corrects, control resumes normal operation.
Control remains in wait mode. When the fault corrects, control resumes normal operation.
sense wiring, flame rod contaminated or out of position, burner ground connection.
If system fails to light on next trial for ignition, check gas supply, pilot burner, flame sense wiring, contamination of flame rod, burner ground connection.
Check for pilot flame. Replace gas valve if pilot flame present. If no pilot flame, cy cle “C all for Heat.” If error repeats, replace control.
Cycle “Call for Heat”. If error repeats, replace control.
Check flame sense lead wire for damage or shorting. Check that flame rod is in proper position.Check flame rod ceramic for cracks, damage or tracking.
Check transformer and AC line for proper i nput voltage to the control. Check with full system load on the transformer.
μA. This is only available in run mode.
54 OAU-SVX005C-EN
Flame Current Measurement
Flame current of the device can be measured using a standard micro-ammeter by simply inserting the meter probes into the holes labeled FLAME CURRENT.
Flame current must be measured with pilot valve lit but no main gas flowing.
Disconnect MV leadwire from the control before measuring flame current.
Set meter to DC µAmp scale.
Ensure meter leads are positioned correctly [+/-].
Note: Trying to measure the pilot flame current in series
with the wiring will not be accurate.
Recommended Minimum Pilot Only Flame Current:
Must read steady 1 µAmp DC minimum.
Flame current should be 2 µAmp or greater for reliable appliance operation.

Direct-Fired OAG Unit Flame Relays > 400 MBh

Alarms and Troubleshooting
AVERTISSEMENT
Procédures d’entretien dangereuses!
Le non-respect de toutes les précautions contenues dans ce manuel ainsi que sur les étiquettes et les autocollants peut entraîner des blessures graves voire mortelles. Les techniciens, afin d’être protégés des éventuels risques électriques, mécaniques et chimiques, DOIVENT suivre les précautions contenues dans ce manuel, sur les étiquettes et les autocollants, ainsi que les instructions suivantes : Sauf indication contraire, coupez toute l’alimentation électrique y compris les disjoncteurs à distance et déchargez tous les dispositifs de stockage d’énergie comme les condensateurs avant l’entretien. Respectez les procédures de verrouillage et d’étiquetage appropriées pour éviter tout risque de remise sous tension accidentelle. S’il est nécessaire de travailler avec des composants électriques sous tension, demandez à un électricien qualifié et agréé ou à une autre personne ayant la formation nécessaire pour manipuler des composants électriques sous tension d’exécuter ces tâches.
WARNING
Hazardous Service Procedures!
Failure to follow all precautions in this manual and on the tags, stickers, and labels could result in death or serious injury. Technicians, in order to protect themselves from potential electrical, mechanical, and chemical hazards, MUST follow precautions in this manual and on the tags, stickers, and labels, as well as the following instructions: Unless specified otherwise, disconnect all electrical power including remote disconnect and discharge all energy storing devices such as capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. When necessary to work with live electrical components, have a qualified licensed electrician or other individual who has been trained in handling live electrical components perform these tasks.
Table 20. Troubleshooting guide for flame relays during problem of safety shutdown (lockout)
Occurs In Occurs If
Initiate Period
Standby Period
• Purge card is not installed or removed
• Purge card is bad
• Configuration jumpers have been changed (after 200 hours)
• AC line power errors occurred
• Four minute INITIATE period has been exceeded
• Airflow lockout feature is enabled and the airflow switch does not close after ten seconds or within the specified purge card timing
• Flame signal is detected after 30 seconds
• Ignition/pilot valve/intermittent pilot valve terminal is energized
• Main valve terminal is energized
• Delayed (2
• Internal system fault occurred
• Purge card is removed
• Purge card is bad
nd
stage) main valve terminal is energized (RM7895C, D/EC7895C, RM7896C/D)
OAU-SVX005C-EN 55
Alarms and Troubleshooting
Table 20. Troubleshooting guide for flame relays during problem of safety shutdown (lockout) (continued)
Occurs In Occurs If
Prepurge Period
Pilot Flame Establishing Period (PFEP)
Main Flame Establishing Period (MFEP)
-RM7895C/D, EC7895C, RM7896C/D
Run Period
• Airflow lockout feature is enabled and the airflow switch opens
• Ignition/pilot valve terminal is not energized
• No flame present at end of PFEP
• Main valve terminal is energized
• Delayed main valve terminal is energized (RM7895C/D)
• Internal system fault occurred
• Purge card is removed
• Purge card is bad
• Airflow lockout feature is enabled and the airflow switch does not close after 10 seconds or within the specified purge card timing
• Flame signal is detected after 30 seconds
• Ignition/pilot valve/intermittent pilot valve terminal is energized
• Main valve terminal is energized.
• Delayed (2
• Internal system fault occurred
• Purge card is removed
• Purge card is bad
• Airflow lockout feature is enabled and the airflow switch opens
• Ignition terminal is energized
• Ignition/pilot valve terminal is not energized
• Main valve terminal is not energized
• Delayed main valve terminal is energized
• No flame present at end of MFEP
• Internal system fault occurred
• Purge card is removed
• Purge card is bad
• No flame present
• Airflow lockout feature is enabled and the airflow switch opens
• Interrupted pilot valve terminal is energized (RM7895C/D,EC7895C, RM7896C/D)
• Main valve terminal is not energized
• Delayed (2
• Internal system fault occurred
• Purge card is removed
• Purge card is bad
nd
stage) main valve terminal is energized (RM7895C/D, EC7895C, RM7896C/D)
nd
stage) main valve terminal is not energized (RM7895C/D,EC7895C, RM7896C/D)
Figure 23. Wiring subbase and sequence chart for RM7895A/B, EC7895A, RM7896A/B
Q7800
Line Voltage Alarm
Blower Motor (Blower)
Burner Controller/Limits
Lockout Interlock
Including Airflow Sw.
Intermittent Pilot Ignition
Main Fuel Valve(s)
Ignition
Flame Detector
(See Note 4)
G
L2
3 4 5 6 7 8 9
10
F
(See Note 3)
12 13 14 15 16
L1
17 18 19 20 21 22
1. RM7895, RM7896; 120 Vac, 50/60 Hz; EC7895; 220– 240 Vac, 50/60 Hz Power Supply. Provide disconnect means and overload protection as required.
2. Do not connect any wires to unused terminals.
3. For EC7895, A 220 to 240 Vac to 120 Vac, 10 VA minimum stepdown transformer (not provided) must be used to drive the shutter.
For Direct Spark Ignition (Oil or Gas)
10
8
(See Note 2)
Ignition Transformer
Main Valve
Master
Switch
(See Note 1)
L2
L1 (Hot) L2
4. See flame detector specifications for correct wiring.
5. For RM7896A1048 (only), Ignition Terminal 1 is de­energized when flame is proven.
6. Airflow switch check feature is for the RM7895, RM7896B.
7. RM7896A,B (only).
56 OAU-SVX005C-EN
Alarms and Troubleshooting
LED Display
Initiate Standby Start Time Purge
PFEP
4-10 Sec.
Run
Post Purge
7
15 Sec.
Standby
Power Power Power Power
Pilot
Flame
Main
Alarm
Power
Pilot
Flame
Main
Alarm
Power
Pilot
Flame
Main
Alarm
Power
Pilot
Flame
Main
Alarm
Power
Pilot
Flame
Main
Alarm
Burner Start
7 etoNrotoM rewolB/renruB
Ignition
5
Ignition/Pilot
Main Valve
Operating
Controls and
Interlocks
Limits and Burner Controller Closed to
Airflow Switch Check
6
CSFA ot desolC kcolretnI tuokcoL
CSSgnivorP emalFkcehC tratS efaSlangiS emalF
4
10
8
8
L1 6
6 7
G
L2
3 4 5 6 7 8 9
10
F
10
8 9
L2
12 13 14 15 16 17 18 19 20 21 22
Q7800
Line Voltage Alarm
Blower Motor (Blower)
10-Sec. Interupt Pilot Ignition
Main Fuel Valve(s)
Ignition
Flame Detector
Master Switch
L1 (Hot) L2
(See Note 1)
Burner Controller/Limits
Lockout Interlock
Including Airflow Sw.
(See Note 4)
(See Note 3)
(See Note 2)
Ignition Transformer
Main Valve
For Direct Spark Ignition (Oil or Gas)
L1
Delayed
(2-Stage)
Main Valve
Figure 24. Wiring subbase and sequence chart for RM7895C/D, EC7895C/D, RM7896C/D
1. RM7895, RM7896; 120 Vac, 50/60 Hz; EC7895; 220–
2. Do not connect any wires to unused terminals.
3. For EC7895, A 220 to 240 Vac to 120 Vac, 10 VA
4. See flame detector specifications for correct wiring.
5. Airflow switch check feature is for the RM7895D,
6. RM7896C,D (only).
7. RM7895C1020, RM7896C1036 PFEP 10 seconds (only).
8. RM7895C1020, RM7896C1036; during first 8 seconds
OAU-SVX005C-EN 57
240 Vac, 50/60 Hz Power Supply. Provide disconnect means and overload protection as required.
minimum step down transformer (not provided) must be used to drive the shutter.
RM7896D.
of PFEP. When a flame signal is detected, Terminal 10 is de-energized. If flame signal is lost, Terminal 10 will re­energize.
Alarms and Troubleshooting
LED Display
Initiate Standby Start Time Purge
PFEP
7
4-10 Sec.
MFEP Run
Post Purge
6
15-Sec
Standby
Power Power Power Power
Pilot
Flame
Main
Alarm
Power
Pilot
Flame
Main
Alarm
Power
Pilot
Flame
Main
Alarm
Power
Pilot
Flame
Main
Alarm
Power
Pilot
Flame
Main
Alarm
Power
Pilot
Flame
Main
Alarm
Burner Start
6 etoNrotoM rewolB/renruB
Ignition
8
Ignition/Pilot
Main Valve
2nd Stage Main
Operating
Controls and
Interlocks
Limits and Burner Controller Closed to
Airflow Switch Check
5
CSFA ot desolC kcolretnI tuokcoL
CSSgnivorP emalFkcehC tratS efaSlangiS emalF
4
10
8
9
L1 6
6 7
21
58 OAU-SVX005C-EN

Appendix

OAU Filter Guide

Table 21. OAB units
Thickness MERV Qty Height Width
2 in. Mist Eliminators 2 16 25 2 in. 8, 13 2 16 25
Table 22. OAG units
Thickness MERV Qty Height Width
2 in. Mist Eliminators 6 16 24 2 in. 8, 13 6 16 24
Note: 2 in. mist eliminators and 2 in. MERV 8 filters are standard; MERV 13
filter is optional.
OAU-SVX005C-EN 59
Ingersoll Rand (NYSE:IR) advances the quality of life by creating comfortable, sustainable and efficient
ingersollrand.com
environments. Our people and our family of brands—including Club Car®, Ingersoll Rand®, Thermo King® and Trane®—work together to enhance the quality and comfort of air in homes and buildings; transport and protect food and perishables; and increase industrial productivity and efficiency. We are a global business committed to a world of sustainable progress and enduring results.
Ingersoll Rand has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice. We are committed to using environmentally conscious print practices.
OAU-SVX005C-EN 30 Nov 2019
Supersedes OAU-SVX005B-EN (Jan 2018)
©2019 Ingersoll Rand
Loading...