Trane MCX 512 GB, MCX 518 GB, MCX 524 GB, MCX 530 GB, MCX 536 GB Installation Manual

...
February 2009 MS-SVN015-EN
Installation Manual
NEW STYLUS
TM
Split System, 1-5 Tons Convertible Type MCX Series 50/60 Hz
MCX 512 GB MCX 518 GB MCX 524 GB MCX 530 GB MCX 536 GB MCX 042 GB MCX 048 GB MCX 060 GB
MCX 512 G1 MCX 518 G1 MCX 524 G1 MCX 530 G1 MCX 536 G1 MCX 042 G1 MCX 048 G1 MCX 060 G1
60 Hz Models Cooling/Heating
MCX 512 G1E MCX 518 G1F MCX 524 G1B MCX 530 G1H MCX 536 G1J MCX 042 G1J MCX 048 G1K MCX 060 G1L
MCX 512 GBE MCX 518 GBF MCX 524 GBB MCX 530 GBH MCX 536 GBJ MCX 042 GBJ MCX 048 GBK MCX 060 GBL
MS-SVN015-EN.p65 2/17/09, 4:44 PM1
Black
MS-SVN015-EN
General Information
General Information
This Installation Manual is given as a guide to good practice in the installation by the installer of MCX mini-split system. Installation procedures should be performed in the sequence that they appear in this manual.
For installing the unit to operate properly and reliably, it must be installed in accordance with these instructions. Also, the services of a qualified service technician should be employed, through the maintenance contract with a reputable service company.
Read these Installation Instructions completely before installing the air conditioning system.
About this Manual
Cautions appear at appropriate places in this Instruction Manual. Your personal safety and the proper operation of this machine require that you follow them carefully. The Trane Company assumes no liability for installations or servicing performed by unqualified personnel. All phases of the installation of this air conditioning system must conform to all national, provincial, state and local codes.
About the Unit
These MCX units are assembled, pressure tested, dehydrated, charged and run tested before shipment. The information contained in this manual applies to MCX units are designed to operate in cooling mode only and in cooling or heating modes.
Trane MCX series of mini-split systems offer three styles of installation: floor, low wall and under ceiling with both LCD wireless remote control or wired control. Trane MCX series provide flexibility and savings. Note: For model MCX 042, MCX 048 and MCX 060, there are only two styles of installation: under ceiling and low wall.
Reception
On arrival, inspect the unit before signing the delivery note. Specify any damage of the unit on the delivery note, and send a registered letter of protest to the last carrier of the goods within 72 hours of delivery. Notify the dealer at the same time.
The unit should be totally inspected within 7 days of delivery. If any concealed damage is discovered, send a registered letter of protest to the carrier within 7 days of delivery and notify the dealer.
Warning
Warnings are provided at appropriate places in this manual to indicate to installers, operators and service personnel of potentially hazardous situations which, if not avoided, COULD result in death or serious injury.
Caution
Cautions are provided at appropriate places in this manual to indicate to installers, operators, and service personnel of potentially hazardous situations which, if not avoided, MAY result in minor or moderate injury or malfunction of the unit.
Warranty
Warranty is based on the general terms and conditions by country. The warranty is void if the equipment is modified or repaired without the written approval of The Trane Company, if the operating limits are exceeded or if the control system or the electrical wiring is modified.
Damage due to inappropriate installation, lack of knowledge or failure to comply with the manufacturer’s instructions, is not covered by the warranty obligation. If the installation does not conform to the rules described in Installation Manual, it may entail cancellation of warranty and liabilities by The Trane Company.
Important
This document is customer property and is to remain with unit. Please place in service information pack upon completion of work. These instructions do not cover all variations in systems, nor do they provide for every possible contingency to be met in connection with installation. Should further information be desired or should particular problems arise which are not covered sufficiently in this manual, the matter should be referred to your authorized Trane dealer.
MS-SVN015-EN.p65 2/17/09, 4:44 PM2
Black
3MS-SVN015-EN
Contents
General Information 2 Typical Installation 4 Location and Preparation of Units 5 Unit Installation 6 Connection of Refrigerant Tubing 7 Condensate Drain Piping 9 Electrical Installation 10 Remote Control Installation 11 Typical Wiring Diagram 12 Dimensional Data 21 Notes 23
MS-SVN015-EN.p65 2/17/09, 4:44 PM3
Black
4 MS-SVN015-EN
Typical Installation
Note: For models MCX 042, MCX 048, MCX 060
there are only two styles of installation: under ceiling and low wall
Ceiling mounted
Outdoor unit
Indoor unit
Floor mounted
Return air grille contains air filter
Refrigerant tubing/wiring
Drain
Return air grille contains air filter
Supply air grille Adjustable louvers direct air
Supply air grille Adjustable louvers direct air
Low wall mounted
MS-SVN015-EN.p65 2/17/09, 4:44 PM4
Black
5MS-SVN015-EN
Location and Preparation of Units
1. Select an appropriate position that allows every corners of the room to be uniformly air conditioned and where it is easy to route the refrigerant tubing.
2. Ensure that the floor or ceiling construction is sufficient to fully support the weight of the indoor unit.
3. Consideration must be given to assure an unobstructed flow of supply and return air.
4. Refrigerant tubes between indoor and outdoor units should be as short as possible.
5. Length of the condensate drain hose should be kept as short as possible (Figure 1).
6. Recommended service clearance as shown in figure 2, 3 and 4.
7. Do not install unit in direct sunlight or near other heat sources as this may affect performance. Do not allow outside air to directly enter unit or condensate may form at the unit’s discharge.
Note: For MCX042-MCX060 the unit should be installed over the floor at least 20 cm.
Figure 4
Figure 3
Figure 2
Maintenance area
(Celling mounted)
Min.
30 cm.
Min.
20 cm.
Min.
20 cm.
Min.
30 cm.
Min.
20 cm.
Maintenance area (Floor mounted)
Figure 1
Min. 120 cm.
Min.
30 cm.
Min.
20 cm.
Min.
20 cm.
Maintenance area
(Low wall mounted)
MS-SVN015-EN.p65 2/17/09, 4:44 PM5
Black
6 MS-SVN015-EN
0.83"(21)
0.83"(21)
8.5"(215)
B
A
Unit Installation
Indoor Unit
1. Select a location to route tubing, wiring and drain pipe between the indoor and outdoor units.
2. Make a hole in the wall using a key hole saw or hole-cutting drill attachment. The hole should be made at a slight downward slant to the outdoor side (Figure 5).
Before cutting, check that no pipes or studs are directly behind the place to be cut. Avoid areas where electrical wiring or conduits are located.
3. Place the unit on a solid and level foundation.
4. Tubing, wiring through and drain pipe of low wall and floor mounted units can be routed, rear or right side of unit when facing front. Ceiling mounted can be routed straight downward.
5.
Pull air filters upward (Figure 6).
Figure 5
6. Unscrew at the return grille (Figure 7).
7. Unscrew at the grille bottom hinges, pull out the screw, and unscrew at the side panel front (Figure 8). Then, push down on the side
panel front and pull up
(Figure 9).
Note: = A 0.49" x 1.575" - 4 SLOT (Mounting hole) (12.5 mm 40.0 mm)
Unit Size B MCX 512-518
36.2" (920)
MCX 512GB5 MCX 524
46.1" (1,170)
MCX 518-524GB5 MCX 530-536
55.9" (1,420)
MCX 530GB5 MCX 042-048 65.7" (1,670) MCX 536-042GB5
75.6" (1,920)
MCX 060
8. Place or hang the unit at the selected position.
9. Replace both right and left side panels, and the return grille after the installation of wiring, tubing and piping is complete.
Outdoor Unit
See the proper installation method provided in the Installation Manual for the outdoor unit.
Indoor side
Figure 6
Pull
Pull
Figure 7
Figure 8
Figure 9
Outdoor side
Figure 10
MS-SVN015-EN.p65 2/17/09, 4:45 PM6
Black
7MS-SVN015-EN
Connection of Refrigerant Tubing
The indoor unit refrigerant line connections are flared both 50 Hz and 60 Hz. Installation brazing, leak testing, and evacuation of refrigerant lines are covered in the Installer Manual, packaged with the outdoor unit. Read the instructions before installing the refrigerant lines.
The indoor unit refrigerant piping connections are located on the right hand side when facing the unit (Figure 11).
Connecting the unit with flaring procedure. (Only for MCX 512-536)
1. Flaring (If piping is procured or cut at the site). Cut the copper tube to the required length with a tube cutter. It is recommended to cut approx. 30-50 cm. longer than the tubing length you estimate.
2. Hold each pipe downward when cutting and remove burrs at the end of the copper tube with a tube reamer or file. This process is important and should be done carefully to make a good flare (Figure 12 and Figure 13).
Figure 11
Check if (L) is flared uniform and is not cracked or scratched. L Dimension:
1.4 to 1.7 mm (6.35 mm dia)
1.8 to 2.0 mm (9.53 mm dia)
1.9 to 2.2 mm (12.7 mm dia)
2.1 to 2.4 mm (15.88 mm dia)
When reaming, hold the tube end downward and be sure that no copper scraps fall into the tube.
3. Remove the flare nut from the unit and be sure to mount it on the copper tube.
4. Make a flare at the end of copper tube with a flare tool (Figure 14, 15).
Copper tubing
Reamer
Figure 12
Before After
Deburring
Figure 13
Flare tool
Flare nut
Copper tubing
Figure 14
L
Figure 15
A good flare should have the following characteristics:
- Inside surface is glossy and smooth.
- Edge is smooth.
- Tapered sides are of uniform length.
Bending
5. When bending the tube, be careful not to crush it. To prevent crushing of the tube, bend it gently and do not bend the tube at a radius curvature of less than 100 mm.
6. If the copper tube is bent or pulled too often, it will become stiff. Do not bend the pipe more than three times at one place.
Cautions before connecting tubes tightly
7. Be sure to apply a sealing cap or water-proof tape to prevent dust or water from getting into the tubes before they are used.
8. Be sure to apply refrigerant lubricant to the matching surfaces of the flare and union before connecting them together. This is effective for reducing gas leaks (Figure 16).
Apply refrigerant
lubricant here
Figure 16
MS-SVN015-EN.p65 2/17/09, 4:45 PM7
Black
8 MS-SVN015-EN
Connection
9. For proper connection, align the union tube and flare tube straight with each other, then screw in the flare nut lightly at first to obtain a smooth match (Figure 17).
10.
Tighten the flare nut to the specified tightening torque with torque wrench and adjustable wrench (Figure 18).
Flare Nut Tightening Torque
Flare Nut/Piping Size Tightening Torque
kgf, - cm lbf-in
6.35 mm (1/4") dia. 150~200 130~170
9.53 mm (3/8") dia. 350~400 300~340
12.7 mm (1/2") dia. 500~550 430~470
15.88 mm (5/8") dia. 600~650 520~570
11. Repeat the process above for the remaining line.
Connecting the unit with brazing procedure (Only for MCX 042-060)
1. Cut the copper tube to the required length with a tube cutter. It is recommended to cut approx. 20-30 cm. longer than the tube length you estimate.
2. Remove burrs at the end of the copper tube with a tube reamer (Figure 12).
3. There are 2 ways to connect the copper tube
- Use a coupling between the
copper tube of indoor unit and the copper tube used for installation (Figure 19).
- Expand the copper tube by
using a swaging tool set as in Figure 20.
4.
Clean internal and external surfaces of coupling or expanded tube prior to brazing.
Figure 17
Figure 18
Figure 20
Figure 19
5. Insulate the entire gas line.
6. Do not allow uninsulated liquid line to come in direct contact with bare gas line.
7. Precautions should be taken to avoid heat damage to the pressure tap valve core during brazing. It is recommended that a wet rag be wrapped around the valve body.
8. It is recommended to use braze shield, soak pad in water and place over suction and liquid lines to protect unit finish.
9. To braze the copper tube, before brazing a copper tube to a solder coupling or a copper tube to an expanded tube, do not forget to keep them tight as shown in Figure 21, 22.
10. Use a dry nitrogen purge and brazing alloy without flux when brazing the field line to the copper factory connection. Flow dry nitrogen into either valve pressure tap port, through the tubing and out the other port while brazing.
11.Braze using accepted good brazing techniques.
Copper tube of outdoor unit
Solder coupling
Swaging
tool
Copper
tube
Tube holder
(Clamp)
Union Flare nut
Solder coupling
C
O
M
M
E
T
3
Figure 21
To rc h
Copper tube from indoor unit
Solder rod
Copper tube from outdoor unit
Solder coupling
C
O
M
M
E
T
3
Figure 22
To rc h
Copper tube from indoor unit
Solder rod
Copper tube from outdoor unit
Copper tube of indoor unit
Indoor unit pipe
Wrench (adjustable)
Torque wrench
Flare nut
Connection pipe
Connection of Refrigerant Tubing
MS-SVN015-EN.p65 2/17/09, 4:45 PM8
Black
Loading...
+ 16 hidden pages