Trane MCX512 G1, MCX512G1E, MWX512 G1, MCX518 G1, MCX518G1F Installation Manual

...
Page 1
Installation Manual
NEW STYLUS
Split System, 1-5 Tons Convertible Type MCX/MWX Series 60 Hz
Cooling Only Cooling Only
MCX512 G1 MCX512G1E MWX512 G1 MCX518 G1 MCX518G1F MWX518 G1 MCX524 G1 MCX524G1B MWX524 G1 MCX530 G1 MCX530G1H MWX530 G1 MCX536 G1 MCX536G1J MWX536 G1 MCX042 G1 MCX042G1J MWX042 G1 MCX048 G1 MCX048G1K MWX048 G1 MCX060 G1 MCX060G1L MWX060 G1
April 2009 MS-SVN15B-EN
Heat Pump with Electric Heater
Page 2
Preface
General Information
This Installation Manual is given as a guide to good practice in the installation by the installer of MCX mini-split system. Installation procedures should be performed in the sequence that they appear in this manual.
For installing the unit to operate properly and reliably, it must be installed in accordance with these instructions. Also, the services of a qualified service technician should be employed, through the maintenance contract with a reputable service company.
Read these Installation Instructions completely before installing the air conditioning system.
About this Manual
Warnings and Cautions appear at appropriate places in this Instruction Manual. Your personal safety and the proper operation of this machine depend upon the strict observance of these precautions.
The Trane Company assumes no liability for installations or servicing performed by unqualified personnel. All phases of the installation of this air conditioning system must conform to all national, provincial, state and local codes.
NOTICE: Warnings and Cautions appear at appropriate sections throughout this
literature. Read these carefully.
WAR NING: Indicates a potentially hazardous situation which, if not avoided, could
result in death or serious injury.
CAUTION: Indicates a potentially hazardous situation which, if not avoided, could
result in minor or moderate injury. It may also be used to alert against unsafe practices.
NOTICE: Indicates a situation that could result in equipment or property-damage only
accidents.
WARNI NG
Grounding Required!
Follow proper local and state electrical code on requirements for grounding. Failure to follow code could result in death or serious injury.
About the Unit
These MCX/MWX units are assembled, pressure tested, dehydrated, charged and run tested before shipment. They are charged with nitrogen, and could be used in applications with R-22 and R-410A refrigerant. For further information on refrigerant and piping connections refer to the outdoor unit manual or contact your Trane local office.
The information contained in this manual applies to MCX/MWX units are designed to operate in cooling mode only (MCX) and in cooling or heating modes (MWX).
Trane MCX/MWX series of mini-split systems offer three styles of installation: floor, low wall and under ceiling with both LCD wireless remote control or wired control. Trane MCX/MWX series provide flexibility and savings.
Note: For model MCX/MWX 042, MCX/MWX 048 and MCX/MWX 060, there are only two styles
of installation: under ceiling and low wall.
© 2009 Trane All rights reserved MS-SVN15B-EN
Page 3
Preface
Reception
On arrival, inspect the unit before signing the delivery note. Specify any damage of the unit on the delivery note, and send a registered letter of protest to the last carrier of the goods within 72 hours of delivery. Notify the dealer at the same time.
The unit should be totally inspected within 7 days of delivery. If any concealed damage is discovered, send a registered letter of protest to the carrier within 7 days of delivery and notify the dealer.
Warranty
Warranty is based on the general terms and conditions by country. The warranty is void if the equipment is modified or repaired without the written approval of The Trane Company, if the operating limits are exceeded or if the control system or the electrical wiring is modified.
Damage due to inappropriate installation, lack of knowledge or failure to comply with the manufacturer’s instructions, is not covered by the warranty obligation.
If the installation does not conform to the rules described in Installation Manual, it may entail cancellation of warranty and liabilities by The Trane Company.
Important
This document is customer property and is to remain with unit. Please place in service information pack upon completion of work. These instructions do not cover all variations in systems, nor do they provide for every possible contingency to be met in connection with installation. Should further information be desired or should particular problems arise which are not covered sufficiently in this manual, the matter should be referred to your authorized Trane dealer.
MS-SVN15B-EN 3
Page 4
Contents
Typical Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Location and Preparation of Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Unit installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Indoor Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Outdoor Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Connection of Refrigerant Tubing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Condensate Drain Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Electrical Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Remote Control Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Typical Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Dimensional Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
4 MS-SVN15B-EN
Page 5
Typical Installation
Return air grille contains air lter
Indoor unit
Supply air grille Adjustable louvers direct air
Ceiling mounted
Supply air grille Adjustable louvers direct air
Refrigerant tubing/wiring
Outdoor unit
Drain
Low wall mounted
Note: For models MCX/MWX 042, MCX/MWX 048, MCX/MWX 060 there are only two styles of
installation: under ceiling and low wall
MS-SVN15B-EN 5
Return air grille contains air lter
Floor mounted
Page 6
Location and Preparation of Units
1. Select an appropriate position that allows every corners of the room to be uniformly air conditioned and where it is easy to route the refrigerant tubing.
2. Ensure that the floor or ceiling construction is sufficient to fully support the weight of the indoor unit.
3. Consideration must be given to assure an unobstructed flow of supply and return air.
4. Refrigerant tubes between indoor and outdoor units should be as short as possible.
5. Length of the condensate drain hose should be kept as short as possible (Figure 1).
Figure 1.
6. Recommended service clearance as shown in figure 2, 3 and 4.
Figure 2.
Min.
20 cm.
Min.
20 cm.
Maintenance area (Celling mounted)
Figure 3.
Min.
20 cm.
Min.
30 cm.
30 cm.
Maintenance area (Floor mounted)
Min.
6 MS-SVN15B-EN
Page 7
Location and Preparation of Units
Min. 120 cm.
Min.
30 cm.
Min.
20 cm.
Min.
20 cm.
Maintenance area
(Low wall mounted)
Figure 4.
7. Do not install unit in direct sunlight or near other heat sources as this may affect performance. Do not allow outside air to directly enter unit or condensate may form at the unit’s discharge.
Note: For MCX/MWX 042-060, the unit should be installed over the floor at least 20 cm.
MS-SVN15B-EN 7
Page 8
Indoor Unit
Pull
Pull
Unit installation
1. Select a location to route tubing, wiring and drain pipe between the indoor and outdoor units.
2. Make a hole in the wall using a key hole saw or hole-cutting drill attachment.
The hole should be made at a slight downward slant to the outdoor side (Figure 5).
Figure 1.
Outdoor side
Indoor side
Before cutting, check that no pipes or studs are directly behind the place to be cut. Avoid areas where electrical wiring or conduits are located.
3. Place the unit on a solid and level foundation.
4. Tubing, wiring through and drain pipe of low wall and floor mounted units can be routed, rear or right side of unit when facing front. Ceiling mounted can be routed straight downward.
5. Pull air filters upward (Figure 6).
Figure 2.
6. Unscrew at the return grille (Figure 7).
Figure 3.
8 MS-SVN15B-EN
Page 9
Unit installation
0.83"(21)
0.83"(21)
8.5"(215)
B
A
7. Unscrew at the grille bottom hinges, pull out the screw, and unscrew at the side panel front (Figure 8). Then, push down on the side panel front and pull up (Figure 9).
Figure 4.
Figure 5.
Figure 6.
Note: A= 0.49" x 1.575" - 4 SLOT (Mounting hole) (12.5 mm 40.0 mm)
Unit Size B
MCX/MWX 512-518 36.2" (920)
MCX/MWX 524 46.1" (1,170) MCX/MWX 530-536 55.9" (1,420) MCX/MWX 042-048 65.7" (1,670)
MCX/MWX 060 75.6" (1,920)
MS-SVN15B-EN 9
Page 10
Unit installation
WARNING
Improper Unit Lift!
Test lift unit approximately 24 inches to verify proper center of gravity lift point. To avoid dropping of unit, reposition lifting point if unit is not level. Failure to properly lift unit could result in death or serious injury or possible equipment or property-only damage.
8. Place or hang the unit at the selected position.
9. Replace both right and left side panels, and the return grille after the installation of wiring,
Outdoor Unit
See the proper installation method provided in the Installation Manual for the outdoor unit.
tubing and piping is complete.
10 MS-SVN15B-EN
Page 11
Connection of Refrigerant Tubing
Copper tubing
Reamer
WARNING
Hazard of Explosion and Deadly Gases!
Never solder, braze or weld on refrigerant lines or any unit components that are above atmospheric pressure or where refrigerant may be present. Always remove refrigerant by following the guidelines established by the EPA Federal Clean Air Act or other state or local codes as appropriate. After refrigerant removal, use dry nitrogen to bring system back to atmospheric pressure before opening system for repairs. Mixtures of refrigerants and air under pressure may become combustible in the presence of an ignition source leading to an explosion. Excessive heat from soldering, brazing or welding with refrigerant vapors present can form highly toxic gases and extremely corrosive acids. Failure to follow all proper safe refrigerant handling practices could result in death or serious injury.
The indoor unit refrigerant line connections are flared. Installation brazing, leak testing, and evacuation of refrigerant lines are covered in the Installer Manual, packaged with the outdoor unit. Read the instructions before installing the refrigerant lines.
The indoor unit refrigerant piping connections are located on the right hand side when facing the unit (Figure 11).
Figure 1.
Connecting the unit with flaring procedure. (Only for MCX/MWX 512-536)
1. Flaring (If piping is procured or cut at the site). Cut the copper tube to the required length with a tube cutter. It is recommended to cut approx. 30-50 cm. longer than the tubing length you estimate.
2. Hold each pipe downward when cutting and remove burrs at the end of the copper tube with a tube reamer or file. This process is important and should be done carefully to make a good flare (Figure 12 and Figure 13).
Figure 2.
When reaming, hold the tube end downward and be sure that no copper scraps fall into the tube.
3. Remove the flare nut from the unit and be sure to mount it on the copper tube.
MS-SVN15B-EN 11
Page 12
Connection of Refrigerant Tubing
Befor e After
Deburring
Figure 3.
4. Make a flare at the end of copper tube with a flare tool (Figure 14, 15).
Figure 4.
Flar e nut
Copper
Flar e tool
Check if (L) is flared uniform and is not cracked or scratched. L Dimension: 1.4 to 1.7 mm (6.35 mm dia) 1.8 to 2.0 mm (9.53 mm dia) 1.9 to 2.2 mm (12.7 mm dia) 2.1 to 2.4 mm (15.88 mm dia)
tubing
Figure 5.
L
A good flare should have the following characteristics:
Inside surface is glossy and smooth.
Edge is smooth.
Tapered sides are of uniform length.
Bending
5. When bending the tube, be careful not to crush it. To prevent crushing of the tube, bend it gently and do not bend the tube at a radius curvature of less than 100 mm.
6. If the copper tube is bent or pulled too often, it will become stiff. Do not bend the pipe more than three times at one place.
Cautions before connecting tubes tightly
7. Be sure to apply a sealing cap or water-proof tape to prevent dust or water from getting into the tubes before they are used.
8. Be sure to apply refrigerant lubricant to the matching surfaces of the flare and union before connecting them together. This is effective for reducing gas leaks (Figure 16).
12 MS-SVN15B-EN
Page 13
Connection of Refrigerant Tubing
Apply r efrigerant
lubricant her e
Union Flar e nut
Figure 6.
Connection
9. For proper connection, align the union tube and flare tube straight with each other, then screw in the flare nut lightly at first to obtain a smooth match (Figure 17).
Figure 7.
10. Tighten the flare nut to the specified tightening torque with torque wrench and adjustable wrench (Figure 18).
Table 1. Flare Nut Tightening Torque
Flare Nut/Piping Size
6.35 mm(1/4") dia. 150 200 130 170
9.53 mm(3/8") dia. 350 400 300 340
12.7 mm(1/2") dia. 500 550 430 470
15.88 mm(5/8") dia. 600 650 520 570
Tightening Torque
Kgf, -cm lbf- in
Figure 8.
Indoor unit pipe
Wrench (adjustable)
To rque wrench
Flar e nut
11. Repeat the process above for the remaining line.
MS-SVN15B-EN 13
Connection pipe
Page 14
Connection of Refrigerant Tubing
Swaging
tool
Copper
tube
Tube holder
(Clamp)
Connecting the unit with brazing procedure (Only for MCX/MWX 042-060)
1. Cut the copper tube to the required length with a tube cutter. It is recommended to cut approx. 20-30 cm. longer than the tube length you estimate.
2. Remove burrs at the end of the copper tube with a tube reamer (Figure 12).
3. There are 2 ways to connect the copper tube
Use a coupling between the copper tube of indoor unit and the copper tube used for
installation (Figure 19).
Figure 9.
Copper tube of indoor unit
Braze coupling
Copper tube of outdoor unit
Expand the copper tube by using a swaging tool set as in Figure 20.
Figure 10.
4. Clean internal and external surfaces of coupling or expanded tube prior to brazing.
NOTICE
System Component Damage!
These air handlers are shipped with dry nitrogen holding charge in the coil. Cut the process tube or puncture the cap to bleed off the nitrogen prior to any brazing. Temporarily cap off tubes if the refrigerant line connections are to be made later.
WARNING
Hazard of Explosion and Deadly Gases!
Never solder, braze or weld on refrigerant lines or any unit components that are above atmospheric pressure or where refrigerant may be present. Always remove refrigerant by following the guidelines established by the EPA Federal Clean Air Act or other state or local codes as appropriate. After refrigerant removal, use dry nitrogen to bring system back to atmospheric pressure before opening system for repairs. Mixtures of refrigerants and air under pressure may become combustible in the presence of an ignition source leading to an explosion. Excessive heat from soldering, brazing or welding with refrigerant vapors present can form highly toxic gases and extremely corrosive acids. Failure to follow all proper safe refrigerant handling practices could result in death or serious injury.
14 MS-SVN15B-EN
Page 15
Connection of Refrigerant Tubing
Braze coupling
C
O
M
M
E
T
3
To r c h
Copper tube from indoor unit
Braze rod
Copper tube from outdoor unit
5. Insulate the entire gas line.
6. Do not allow uninsulated liquid line to come in direct contact with bare gas line.
7. Precautions should be taken to avoid heat damage to the pressure tap valve core during brazing. It is recommended that a wet rag be wrapped around the valve body.
8. It is recommended to use braze shield, soak pad in water and place over suction and liquid lines to protect unit finish.
9. To braze the copper tube, before brazing a copper tube to a solder coupling or a copper tube to an expanded tube, do not forget to keep them tight as shown in Figure 21, 22.
Figure 11.
C
O
M
M
E
T
To r c h
3
Copper tube from indoor unit
Braze rod
Braze coupling
Copper tube from outdoor unit
Figure 12.
10. Use a dry nitrogen purge and brazing alloy without flux when brazing the field line to the copper factory connection. Flow -dry nitrogen into either valve pressure tap port, through the tubing and out the other port while brazing.
11. Braze using accepted good brazing techniques.
MS-SVN15B-EN 15
Page 16
Condensate Drain Piping
Figur e 24
Drain hose
The drain hose should run straight down the wall to a level where the runoff will not stain
the wall.
There should be no traps. Avoid putting the end of the hose in water.
To conveniently drain the system, the drain hose must slant downward, with a slope of at
least 1: 50 to prevent leakage. Figure 23 shows the unit in the floor mounted position.
Figure 1.
Indoor unit
Slant
Drain hose
Figur e 23
When the drain hose is placed in the room, insulate the hose with foam polyethylene to
avoid damage to the ceiling or furniture.
After completing installation of refrigerant lines, wiring and drain connections, bind the
tubing, wiring and drain hose -(check if local codes permit binding) into a bundle by using tape at 100 or 200 mm (4" to 8") intervals. Make sure the drain hose is at the bottom of the bundle (Figure 24).
Figure 2.
16 MS-SVN15B-EN
Page 17
Electrical Installation
All wiring and grounding must comply with local electrical codes.
WARNING
Grounding Required!
Follow proper local and state electrical code on requirements for grounding. Failure to follow code could result in death or serious injury.
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.
Wiring
Important Safeguards:
Check the unit nameplate for electrical rating. Be sure wiring is done according to local
codes and wiring diagram.
Use a separate power line with circuit breaker for each air conditioning unit.
Connect electrical ground to all units.
Wiring should not touch refrigerant tubing, compressor, motors or moving parts.
The manufacturer will accept no responsibility for problems caused by unauthorized
changes in the internal wiring.
Connect the wiring firmly.
Electrical Connections
See Section: Wiring System Diagram
Indoor Unit
Remove the right side panel and return grille (see previous instructions), to access the terminal base.
Pass the system wiring through the PVC pipe (both power and control lines) to
interconnect indoor and outdoor units.
Connect the wire terminals to the terminal base (see connection indication on system
wiring diagram).
Make sure all connections are tight.
Outdoor unit
Outdoor Unit - Indoor Unit Electrical Interconnection should be in accordance with the applicable system wiring diagram and indoor unit diagrams.
Outdoor unit diagram are contained in the outdoor unit Installer Manual.
Note: All wiring must comply with national state and local codes.
Note: After completing the connections, re-confirm them to be in accordance with the unit and
system wiring diagrams.
MS-SVN15B-EN 17
Page 18
Remote Control Installation
Dimension
Wired remote control (MCX units only) Mounting Bracket
TEMP
MENU
MODE
FA
N
ON
ON
OFF
OFF
ECONO
SW
SLEEP ECONO
TURBO
TURBO
AU
TO
14.5
4.0 X 2 SLOT
14.5
45.0
90.0
45.0
90.0
61.0
ECONOECONO
ON
FAN COOL DRY HEAT AUTO
OFF
POWERCOOL
SW
Z
Z
MODE
LOUVER
SWEEP
FRONT BLADE
LIGHT
OFF
ON
POWER
COOL
ECONO
SLEEP
SEND
Wireless remote control
Locate and attach the wireless remote control and wired control as follows:
1. Do not place the control and the remote control near heat sources or expose to the direct rays of the sun.
2. Do not expose the control to the indoor unit’s supply air stream.
3. Do not place in a confined space.
4. Attach the remote control holder as shown in Figure 25.
Figure 1.
18 MS-SVN15B-EN
Page 19
Typical Wiring Diagram
J2
N
C1
C2
L
P20
J1
P17
P16
P19
P21
FREEZE
P22
P26
2
1
P3
LINE-C
EX-HI
P7
P6
P5
P4
LOW
MED
HI
NEUTRAL
P2
LINE
P1
BLK
BLU
RED
YL
BRW WHT
WHT
GRN/YL
WHT
RED
RED
BLK
BLU
RED
YL
INFRARED RECEIVER
GRN/YL
DESCRIPTION
COIL
BLK
RED
1. FREEZE SENSOR LOCATED ON EVAPORATOR COIL
2. TEMPERATURE SENSOR LOCATED IN RETURN AIR STREAM
SWEEP MOTOR
(OPTION)
ROOM
STEPPER TOP STEPPER FRONT
DISPLAY
WIRELESS REMOTE
CONTROLLER
POWER SUPPLY
220-240VAC/1PH/60Hz
BLOWER
MOTOR
WIRING TO GROUNDING SYSTEM
200-240 VAC CONTROL WIRING TO OUTDOOR UNIT
FIELD WIRING
FACTORY WIRING
JUNCTION
TERMINAL BOARD
CAPACITOR
FUSE 3 AMP.
COLOR CODE
BLU BLUE BLK BLACK RED RED WHT WHITE GRN GREEN YL YELLOW BR BROWN
COULD RESULT INCOULD RESULT IN
USE COPPER MAY CAUSEUSE COPPER MAY CAUSE
DEATH OR SERIOUS INJURY.DEATH OR SERIOUS INJURY.
Figure 1. MCX 512-536G1 (60Hz), Indoor Unit, Cooling only with Wireless Controller. (Residential model, 4 speed)
MS-SVN15B-EN 19
Page 20
Typical Wiring Diagram
COULD RESULT IN
USE COPPER MAY CAUSE
DEATH OR SERIOUS INJURY.
Figure 2. MCX042-060G1 (60Hz), Indoor Unit, Cooling only with Wireless Controller. (Basic model, 3 speed)
1. FREEZE SENSOR
LINE
NEUTRAL
P1
P2
LINE-C
P3
1
2
GRN/YL
P21
ROOM
P26
DISPLAY
MED
LOW
HI
P6
P5
P4
FREEZE
P16
P22
P17
LOCATED ON EVAPORATOR COIL
2. TEMPERATURE SENSOR LOCATED IN RETURN AIR STREAM
INFRARED RECEIVER
WIRELESS REMOTE
CONTROLLER
220-240VAC/1PH/60Hz
DESCRIPTION
WHT
RED
L
NC1
POWER SUPPLY
FIELD WIRING
FACTORY WIRING
COIL
JUNCTION
TERMINAL BOARD
CAPACITOR
FUSE 3 AMP.
BLK
BLU
RED
RED
J2
C2
WIRING TO GROUNDING SYSTEM
200-240 VAC CONTROL WIRING TO OUTDOOR UNIT
GRN/YL
COLOR CODE
BLU BLUE BLK BLACK RED RED WHT WHITE GRN GREEN YL YELLOW BR BROWN
RED
BLK
J1
WHT
BLK
BLU
RED
BLOWER
MOTOR
BRW WHT
DEATH OR SERIOUS INJURY.
COULD RESULT IN
20 MS-SVN15B-EN
USE COPPER MAY CAUSE
Page 21
Typical Wiring Diagram
GRN/YL
2
1
1. FREEZE SENSOR LOCATED ON EVAPORATOR COIL
2. TEMPERATURE SENSOR LOCATED IN RETURN AIR STREAM
SWEEP MOTOR
(OPTION)
GRN/YL
STEPPER TOP STEPPER FRONT
P20 P19
P21
FREEZE
P22
ROOM
DISPLAY
P31
LINE-C
EX-HI
LOW
MED
HI
NEUTRAL
LINE
P3
P7
P6
P5
P4
P2
P1
WHT
RED
RED
BLK
BLU
RED
YL
P17
P16
BLK
RED
J2
J1
WIRE DISPLAY
BLK
BLU
RED
YL
WHT
BRW WHT
BLOWER
MOTOR
NC1
C2L
POWER SUPPLY
220-240VAC/1PH/60Hz
WIRING TO GROUNDING SYSTEM
200-240 VAC CONTROL WIRING TO OUTDOOR UNIT
BLU BLUE BLK BLACK RED RED WHT WHITE GRN GREEN YL YELLOW BR BROWN
COIL
FIELD WIRING
FACTORY WIRING
JUNCTION
TERMINAL BOARD
CAPACITOR
FUSE 3 AMP.
DESCRIPTION
COLOR CODE
COULD RESULT INCOULD RESULT IN
USE COPPER MAY CAUSEUSE COPPER MAY CAUSE
DEATH OR SERIOUS INJURY.DEATH OR SERIOUS INJURY.
Figure 3. MCX 512-536G1 (60Hz), Indoor Unit, Cooling only with Wired Controller. (Residential model, 4 speed)
MS-SVN15B-EN 21
Page 22
Typical Wiring Diagram
GRN/YL
P21
FREEZE
P22
ROOM
DISPLAY
P31
J2
GRN/YL
2
1
1. FREEZE SENSOR LOCATED ON EVAPORATOR COIL
2. TEMPERATURE SENSOR LOCATED IN RETURN AIR STREAM
LINE-C
HI
LOW
MED
NEUTRAL
LINE
WIRE DISPLAY
P3P6P5
P4
P2
P1
WHT
RED
RED
BLK
BLU
RED
P17
P16
BLK
RED
J1
WHT
BRW WHT
BLK
BLU
RED
BLOWER
MOTOR
BLU BLUE BLK BLACK RED RED WHT WHITE GRN GREEN YL YELLOW BR BROWN
COIL
FIELD WIRING
FACTORY WIRING
JUNCTION
TERMINAL BOARD
CAPACITOR
FUSE 3 AMP.
NC1
C2L
POWER SUPPLY
220-240VAC/1PH/60Hz
200-240 VAC CONTROL WIRING TO OUTDOOR UNIT
COLOR CODE
DESCRIPTION
WIRING TO GROUNDING SYSTEM
COULD RESULT INCOULD RESULT IN
USE COPPER MAY CAUSEUSE COPPER MAY CAUSE
DEATH OR SERIOUS INJURY.DEATH OR SERIOUS INJURY.
Figure 4. MCX 042-060G1 (60 Hz), Indoor Unit, Cooling only with Wired Controller. (Basic model, 3 speed)
22 MS-SVN15B-EN
Page 23
Typical Wiring Diagram
Figure 5. MCX512-536G1 (60 Hz) Indoor Unit Cooling/Heater with Wireless Controller. (Basic model, 3 speed)
MS-SVN15B-EN 23
Page 24
Typical Wiring Diagram
Figure 6. MCX042-060G1 (60 Hz) Indoor Unit Cooling/Heater with Wireless Controller. (Basic model, 3 speed)
24 MS-SVN15B-EN
Page 25
Typical Wiring Diagram
SWEEP MOTOR
P20 P19
STEPPER TOP
STEPPER FRONT
Figure 7. MWX 512-536 G1 (60 Hz) Indoor Unit Heat Pump Model with Wireless Controller. (Residential model, 4 speed)
MS-SVN15B-EN 25
Page 26
Typical Wiring Diagram
Figure 8. MWX 042-060 G1 (60 Hz) Indoor Unit Heat Pump Model with Wireless Controller. (Basic model, 3 speed)
26 MS-SVN15B-EN
Page 27
Dimensional Data
Figure 1. Outline Dimensions, MCX/MWX 512-536G1
SLOT (MOUNTING HOLE)
LENS FOR WIRELESS REMOTE CONTROL
RETURN AIR
RETURN AIR
RUBBER ISOLATOR (QTY. = C)
SUCTION CONNECTION
LIQUID CONNECTION
Table 1. Dimensional Data
Connection Size Type A B C
Model
MCX/MWX 512G1 MCX/MWX 518G1
MCX/MWX 524G1 3/8 (9.5) 5/8 (15.9) Flared 51.13/1324.0 44.45/1129.0 4 MCX/MWX 530G1 3/8 (9.5) 5/8 (15.9) Flared 61.97/1574.0 54.29/1379.0 6 MCX/MWX 536G1 3/8 (9.5) 3/4 (19.0) Flared 61.97/1574.0 54.29/1379.0 6
Liquid Suction Connections IN./mm. IN./mm Each
1/4 (6.4) 1/2 (12.7) Flared 42.28/1074.0 34.61/879.0 4
Note: SUCTION AND LIQUID LINES HAVE FLARE TYPE CONNECTIONS.
Note: DIMENSIONS : MILIMETERS [INCHES] 25.4 MM. = 1 IN.
MS-SVN15B-EN 27
Page 28
Dimensional Data
Figure 2. Outline Dimensions, MCX/MWX 042-060G1
LENS FOR WIRELESS REMOTE CONTROL
RETURN AIR
RUBBER ISOLATOR (QTY.= C)
Table 2. Dimensional Data
Connection Size Type A B C D
Model
MCX/MWX 042G1 MCX/MWX 048G1
MCX/MWX 060G1 3/8 (9.5) 1-1/8 (28.6) Brazed
Liquid Suction Connections IN./mm. IN./mm Each IN./mm
3/8 (9.5) 3/8 (9.5)
7/8 (22.2)
1-1/8 (28.6)
Brazed Brazed
71.81/
1824.0
81.65/
2074.0
Note: DIMENSIONS : MILIMETERS [INCHES] 25.4 MM. = 1 IN.
RETURN AIR
SUCTION CONNECTION
LIQUID CONNECTION
64.13/
1629.0
73.98/
1879.0
8 15.76/400
8 23.64/600
28 MS-SVN15B-EN
Page 29
Page 30
Page 31
Page 32
www.trane.com
For more information, contact your local Trane office or e-mail us at comfort@trane.com
Literature Order Number MS-SVN15B-EN
Date April 2009
Supersedes MS-SVN15B-EN (February 2009)
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.
Loading...