Trane MCV 036 BB, MCV 048 BB, MCV 060 BB, MCV 090 BB, MCV 120 BB Installation Manual

...
Page 1
YUKON
Tall Floor Split Systems 36,000 - 120,000 Btu/h Cooling Only MCV Series 50/60 Hz
MS-SVN007-EN
Installation Manual
50 Hz Models Cooling Only
MCV 036 BB MCV 048 BB MCV 060 BB MCV 090 BB MCV 120 BB
60 Hz Models Cooling Only
MCV 036 B1 MCV 048 B1 MCV 060 B1 MCV 090 B1 MCV 120 B1
MS_SVN007_EN.p65 6/7/06, 10:30 AM1
Black
Page 2
MS-SVN007-EN
General Information
General Information
This Installation Manual is provided as a guide to good practice in the installation by the installer of the Trane MCV vertical floor mounted split system. Installation procedures should be performed in the sequence that they appear in this manual.
To install the system for proper and to operate reliable operation, it must be installed in accordance with these instructions. Also, the services of a qualified service technician should be employed, through a maintenance contract with a reputable service company.
Please read these Installation Manual completely before installing the air conditioning system.
About this Manual
Cautions appear at appropriate places in this Installation Manual. Your personal safety and the proper operation of this machine require that you follow them carefully. The Trane Company assumes no liability for installations or servicing performed by unqualified personnel. All phases of the installation of this air conditioning system must conform to all national, provincial, state and local codes.
About the Unit
These MCV units are assembled, pressure tested, dehydrated, charged and run-tested prior to shipment from the factory. The information contained in this manual applies to MCV units designed to operate in the cooling mode only.
The Trane MCV series, is equipped with a microprocessor control to provide flexibility and energy savings.
Reception
On arrival, please inspect the unit before signing the delivery note. Specify any damage of the unit on the delivery note, and send a registered letter of protest to the last carrier of the goods within 72 hours of delivery.
The unit should be totally inspected within 7 days of delivery. If any concealed damage is discovered, send a registered letter of protest to the carrier within 7 days of delivery.
Warning
Warnings are provided at appropriate places in this manual to indicate to installers, operators and service personnel of potentially hazardous situations which, if not avoided, COULD result in death or serious injury.
Caution
Cautions are provided at appropriate places in this manual to indicate to installers, operators, and service personnel of potentially hazardous situations which, if not avoided, MAY result in minor or moderate injury or malfunction of the unit.
Your personal safety and the proper operation of this unit require that you follow them carefully. The Trane Company assumes no liability for installations or servicing performed by unqualified personnel.
Warranty
Warranty is based on the general terms and conditions in each country. The warranty is void if the equipment is modified or repaired without the written approval of The Trane Company, if the operating limits are exceeded or if the control system or the electrical wiring is modified.
Damage due to inappropriate installation, lack of knowledge or failure to comply with the manufacturer s instructions, is not covered by the warranty obligation. If the installation does not conform to the rules described in Installation Manual, it may entail cancellation of warranty and liabilities by The Trane Company.
Important
This document is customer property and is to remain with the unit. Please place it in the service information pack upon completion of work.
These instructions do not cover all variations in systems, nor do they provide for every possible contingency to be met in connection with installation. Should further information be desired or should particular problems arise which are not covered sufficiently in this manual, the matter should be referred to your Trane sales representative
MS_SVN007_EN.p65 10/7/06, 8:54 AM2
Black
Page 3
MS-SVN007-EN
3
Contents
2
4
5
6
8
9
10
11
General Information
Typical Installation
Location and Preparation of Unit
Unit Installation
Condensate Drain Piping
Electrical Installation
Typical Wiring Diagram
Dimensional Data
MS_SVN007_EN.p65 6/7/06, 10:21 AM3
Black
Page 4
4
MS-SVN007-EN
Typical Installation
Indoor Unit
Outdoor Unit
Control Display
Bottom Panel
Drain
Front Panel
Supply Air Grille
Refrigerant Tubing
& Wiring
Return Air Grille
with Air Filter
MS_SVN007_EN.p65 6/7/06, 10:21 AM4
Black
Page 5
MS-SVN007-EN
5
Location and Preparation of Unit
Figure 1
Figure 2
1. Select an appropriate position that allows every corner of the room to be uniformly air conditioned and where it is easy to route the refrigerant tubing (Figure 1).
2. Ensure that the floor construction is sufficient to fully support the weight of the indoor unit.
3. Consideration must be given to ensure an unobstructed flow of supply and return air.
4. Refrigerant tubes between indoor and outdoor units should be kept as short as possible.
5. Length of the condensate drain hose should be kept as short as possible.
6. Do not install unit in direct sunlight or near other heat sources as this may affect performance. Do not allow outside air to directly enter unit or condensate may form at the unit s discharge.
7. Recommended service clearance as shown in (Figure 2).
300mm
300mm
200mm
500mm
MS_SVN007_EN.p65 6/7/06, 10:21 AM5
Black
Page 6
6
MS-SVN007-EN
Unit Installation
Indoor side
Outdoor side
Figure 3
Figure 4
Indoor Unit
1. Select a location to route tubing, wiring and drain pipe between the indoor and outdoor units.
2. Make a hole in the wall using a key hole saw or hole-cutting drill attachment.
The hole should be made at a slight downward slant to the outdoor side (Figure 3).
Before cutting, check that no pipes or studs are directly behind the place to be cut. Avoid areas where electrical wiring or conduits are located.
3. Place the unit on a solid and level foundation.
4. Tubing, wiring and the drain pipe can be routed to rear or left and right side of the unit.
5. To gain access to the electrical terminals, the drain and the refrigerant lines, remove the return air grille and bottom panel.
5.1 Remove a screw at return air grille
(Figure 4).
5.2 Pull the return air grille forward
and lift up to remove it (Figure 5).
5.3 Unscrew at the bottom panel, pull
forward and lift up to remove the panel. The electrical box will be on the left hand side, the drain and refrigerant lines will be on the right hand side when facing front (Figure 6).
5.4 Unscrew at the electrical box to
remove the cover, the electrical terminal will be placed inside the box (Figure 7).
6. Replace the cover of electrical box, bottom panel and the return air grille after the installation of wiring, tubing and piping is completed.
Figure 5
Figure 6 Figure 7
MS_SVN007_EN.p65 6/7/06, 10:21 AM6
Black
Page 7
MS-SVN007-EN
7
C
O
M
M
E
T
3
Copper tube of outdoor unit
Solder rod
Copper tube of indoor unit
Figure 9
Figure 10
Solder coupling
Torch
Copper tube from outdoor unit
Solder coupling
Figure 11
C
O
M
M
E
T
3
Solder rod
Torch
Copper tube from outdoor unit
Solder coupling
Figure 12
Figure 8
Copper tubing
Reamer
Connecting the Unit with Brazing Procedure
1. Cut the copper tube to the required length with a tube cutter. It is recommened to cut approx. 20-30 cm. longer than the tube length you estimate.
2. Remove burrs at the end of the copper tube with a tube reamer (Figure 8).
3. There are 2 ways to connect the copper tube.
- Use a coupling between the copper tube of indoor unit and the copper tube used for installation (Figure 9).
- Expand the copper tube by using a swaging tool set (Figure 10).
4. Clean internal and extenal surfaces of coupling or expanded tube prior to brazing.
5. Insulate the entire suction line.
6. Do not allow uninsulated liquid line to come in direct contact with bare suction line.
7. Precautions should be taken to avoid heat damage to the pressure tap valve core during brazing. It is recommended that a wet rag be wrapped around the valve body.
8. It is recommended to use braze shield, soak pad in water and place over suction and liquid lines to protect unit finish.
9. To braze the copper tube, before brazing a copper tube to a solder coupling or a copper tube to an expanded tube, do not forget to keep them tight as shown in (Figure 11, 12).
10. Use a dry nitrogen purge and brazing alloy without flux when brazing the field line to the copper factory connection. Flow dry nitrogen into either valve pressure tap port, through the tubing and out the other port while brazing.
11. Braze using accepted good brazing techniques.
Swaging
tool
Tube holder
(Clamp)
Copper
tube
Unit Installation
MS_SVN007_EN.p65 10/7/06, 8:54 AM7
Black
Page 8
8
MS-SVN007-EN
Condensate Drain Piping
Figure 12
P.V.C. Conduit
Control Wiring
Suction Line Tube
Insulation Tube
P.V.C. Tape
Liquid Line Tube
Water Condensated Drain Tube (P.V.C. Tube)
Power Wiring
- The drain hose should run straight down the wall to a level where the run off will not stain the wall.
- There should be no traps. Avoid putting the end of the hose in water.
- To conveniently drain the system, the drain hose must slant downward, with a slope of at least 1 : 50 to prevent leakage.
- When the drain hose is placed in the room, insulate the hose with foam polyethylene to avoid damage to the ceiling or furniture.
- After completing installation of refrigerant lines, wiring and drain connections, bind the tubing, wiring and drain hose (check if local codes permit binding) into a bundle by using tape at 100 or 200 mm. (4" to 8") intervals. Make sure the drain hose is at the bottom of the bundle (Figure 12).
MS_SVN007_EN.p65 6/7/06, 10:22 AM8
Black
Page 9
MS-SVN007-EN
9
Electrical Installation
All wiring and grounding must comply with local electrical codes.
1. Wiring
Important Safeguards:
- Check the unit nameplate for electrical rating. Be sure wiring is done according to local codes and wiring diagram.
- Use a separate power line with circuit breaker for each air conditioning unit.
- Connect electrical ground to all units.
- Wiring should not touch refrigerant tubing, compressor, motors or moving parts.
- The manufacturer will accept no responsibility for problems caused by unauthorized changes in the internal wiring.
- Connect the wiring firmly.
2. Electrical Connections
See Section: Typical Wiring Diagram
Indoor Unit
Remove the return air grille and cover of electrical box (see previous instructions) to access the terminal base.
- Connect the wire terminals to the terminal base. (See connection indication on system wiring diagram).
- Make sure all connections are tight.
Outdoor Unit
Outdoor unit - indoor unit electrical interconnection should be in accordance with the applicable system wiring diagram and indoor unit diagrams.
Outdoor unit diagram is contained in the outdoor unit Installation Manual
Note:
- All wiring must comply with national state and local codes.
- After completing the connections, re-confirm them to be in accordance with the unit and system wiring diagrams.
MS_SVN007_EN.p65 6/7/06, 10:22 AM9
Black
Page 10
10
MS-SVN007-EN
Typical Wiring Diagram
LEGEND
MCV036/048/060
FREEZE SENSOR
L NC1C2 -
CF
WH
#3
#2
#1
BR
WH
GRN/YL
MS
035-0977
MCV036
YL
RD
BL
RD
BLK
BL
MCV048
MCV060
WIRE #
WH
BLK
GRN/YL
BL
RD
YL
SWP
LINE-C
COMP
HI
MED
LINE
LOW
BLK
BLK
BLK
ROOM SENSOR
CONTROL PANEL
TERMINAL
JUNCTION CF FAN CAPACITOR FAN MTR FAN MOTOR
IDENTIFIED TERMINAL
CONTACTOR COIL
TERMINAL BOARD BY FACTORY
FIELD WIRING
FACTORY WIRING
RELAY CONTACT N.O.
CAPACITOR
COLOR CODE
BL BLUE BLK BLACK BR BROWN GR GRAY GRN GREEN RD RED WH WHITE YL YELLOW
NEUTRAL
SWEEP MOTOR
FAN MTR
CONDENSING UNIT
POWER SUPPLY 220-240V/1Ph/50Hz 220-240V/1Ph/60Hz
1. POWER WIRING AND GROUNDING OF EQUIPMENT MUST COMPLY WITH LOCAL CODES.
2. USE COPPER CONDUCTORS ONLY.
3. ENSURE THAT POWER SUPPLY AGREE WITH EQUIPMENT NAME PLATE.
NOTES:
REV. -
COLOR
#3 (LOW)
#2 (MID)
#1 (HIGH)
035-0978
3M
2M
1M
3M
2M
1M
SWP
MED
LINE-C
HI
LINE
BLK
BLK
BLK
FREEZE SENSOR
ROOM SENSOR
MS
CONDENSING UNIT
WH
NL
GRN/YL
C2C1 -
#1
GRN/YL
WH
WH
BLK
BR
#3
#2
CF
GRN/YL
#1
#2
#3
CF
WH
WH
BR
MCV090/120
CONTROL PANEL
LEGEND
TERMINAL
JUNCTION CF FAN CAPACITOR FAN MTR FAN MOTOR
IDENTIFIED TERMINAL
CONTACTOR COIL
TERMINAL BOARD BY FACTORY
FIELD WIRING
FACTORY WIRING
RELAY CONTACT N.O.
CAPACITOR
COLOR CODE
BL BLUE BLK BLACK BR BROWN GR GRAY GRN GREEN RD RED WH WHITE YL YELLOW
MCV090
YL
RD
BL#1 (HIGH)
#3 (LOW)
#2 (MED)
WIRE #
COLOR
BLK
RD
BL
MCV120
NEUTRAL
LOW
COMP
SWEEP MOTOR
POWER SUPPLY 220-240V/1Ph/50Hz 220-240V/1Ph/60Hz
1. POWER WIRING AND GROUNDING OF EQUIPMENT MUST COMPLY WITH LOCAL CODES.
2. USE COPPER CONDUCTORS ONLY.
3. ENSURE THAT POWER SUPPLY AGREE WITH EQUIPMENT NAME PLATE.
NOTES:
REV. -
FAN MTR
FAN MTR
MS_SVN007_EN.p65 6/7/06, 10:22 AM10
Black
Page 11
MS-SVN007-EN
11
Dimensional Data
MCV036/048/060
FOR EXPORT MODEL (50/60Hz)
LIQUID SIZE
3/8"
3/8"
1/2"
1/2"
3/8"
A
1196
848
600
1196
600
3/4"
1-1/8"
1-3/8"
1-1/8"
1-1/8"
SUCTION SIZE
BRAZE
BRAZE
BRAZE
BRAZE
BRAZE
MCV090/120
MCV120
MCV048
MCV060
MCV090
MCV036
MODEL
989
494
742
989
B
494
400
370
400
400
C
370
370
340
370
370
D
340
954
462
710
954
E
462
ø27 KNOCK-OUT(2) FOR ELEC.
ø75 KNOCK-OUT(2)
FOR SUCTION & LIQUID
ø30 KNOCK-OUT(2) FOR DRAIN
ø27 KNOCK-OUT(2) FOR ELEC.
ø75 KNOCK-OUT(2)
FOR SUCTION & LIQUID
ø30 KNOCK-OUT(2) FOR DRAIN
1900
668
52
117
268
A
E
B
1900
E
117
668
B
A
268
52
180
135.5
70.5
30
D
80
C
100
80
80
100
100
135.5
70.5
180
30
D
80
100
80
C
80
SLOT ø70X110 KNOCK-OUT(2)
FOR SUCTION+LIQUID+DRAIN+ELEC.
SLOT ø70X110 KNOCK-OUT(2)
FOR SUCTION+LIQUID+DRAIN+ELEC.
NOTE : ALL DIMENSIONS ARE IN MILLIMETER.
CONNECTION TYPE
MS_SVN007_EN.p65 6/7/06, 10:22 AM11
Black
Page 12
Trane A business of American Standard Companies
http://www.trane.com
For more information, contact your local district office
File Number
Stocking Location Thailand
Literature Order Number MS-SVN007-EN (June 2006)
MS-SVN007-EN.pdf
Supersedes New
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice. Only qualified technicians should perform the installation and servicing of equipment referred to in this publication.
MS_SVN007_EN.p65 6/7/06, 10:22 AM12
Black