Trane MCD 530 DB, MCD 512 DB, MCD 536 DB, MCD 048 DB, MCD 060 DB Installation Manual

...
Page 1
February 2003 MS-SVN004-EN
Installation Manual
ILLUSION
Split System Concealed Type MCD Series 50/60 Hz
Cooling Only/Cooling Heating 50 Hz Models
MCD 512 DB MCD 518 DB MCD 524 DB MCD 530 DB MCD 536 DB MCD 048 DB MCD 060 DB
Cooling Only/Cooling Heating 60 Hz Models
MCD 512 D1 MCD 518 D1 MCD 524 D1 MCD 530 D1 MCD 536 D1 MCD 048 D1 MCD 060 D1
L/O- 02091985TRA 21/4/03, 2:44 PM1
Page 2
General Information
Introduction
This Installation Manual is given as a guide to good practice in the installation by the installer of MCD mini-split system. Installation procedures should be performed in the sequence that they appear in this manual.
For installing the unit to operate properly and reliably, it must be installed in accordance with these instructions. Also, the services of a qualified service technician should be employed, through the maintenance contract with a reputable service company.
Read these installation instructions completely before installing the air conditioning system.
About the Unit
These MCD units are assembled, pressure tested, dehydrated, charged and run tested before shipment. The information contained in this manual applies to MCD units are designed to operate in cooling mode only and in cooling or heating modes.
Important
This document is customer property and is to remain with unit. Please place in service information pack upon completion of work. These instructions do not cover all variations in systems, nor do they provide for every possible contingency to be met in connection with installation. Should further information be desired or should particular problems arise which are not covered sufficiently in this manual, the matter should be referred to your authorized Trane dealer.
Reception
On arrival, inspect the unit before signing the delivery note. Specify any damage of the unit on the delivery note, and send a registered letter of protest to the last carrier of the goods within 72 hours of delivery. Notify the dealer at the same time.
The unit should be totally inspected within 7 days of delivery. If any concealed damage is discovered, send a registered letter of protest to the carrier within 7 days of delivery and notify the dealer.
Warranty
Warranty is based on the general terms and conditions by country. The warranty is void if the equipment is modified or repaired without the written approval of The Trane Company, if the operating limits are exceeded or if the control system or the electrical wiring is modified.
Damage due to inappropriate installation, lack of knowledge or failure to comply with the manufacturer’s instructions, is not covered by the warranty obligation. If the installation does not conform to the rules described in Installation Manual, it may entail cancellation of warranty and liabilities by The Trane Company.
About this Manual
Cautions appear at appropriate places in this Installation Manual. Your personal safety and the proper operation of this machine require that you follow them carefully. The Trane Company assumes no liability for installations or servicing performed by unqualified personnel. All phases of the installation of this air conditioning system must conform to all national, provincial, state and local codes.
Warning
Warnings are provided at appropriate places in this manual to indicate to installers, operators and service personnel of potentially hazardous situations which, if not avoided, COULD result in death or serious injury.
Caution
Cautions are provided at appropriate places in this manual to indicate to installers, operators, and service personnel of potentially hazardous situations which, if not avoided, MAY result in minor or moderate injury or malfunction of the unit.
MS-SVN004-EN© American Standard Inc.2000
L/O- 02091985TRA 21/4/03, 2:44 PM2
Page 3
3MS-SVN004-EN
Contents
General Information 2 System Appearance 4 Location and Preparation of Units 6 Units Installation 7 Connection of Refrigerant Tubing 9 Condensate Drain Piping 10 Electrical Installation 11 Wiring Diagram 12 Dimensional Data 15 Maintenance 18
L/O- 02091985TRA 21/4/03, 2:44 PM3
Page 4
4 MS-SVN004-EN
System Appearance
MCD 512-536 DB/D1
Condensate Drain Pan
Electric Heater
(Option)
Evaporator Coil
Outlet Collar
Motor
Blower
Outdoor Unit
Indoor unit
L/O- 02091985TRA 21/4/03, 2:44 PM4
Page 5
5MS-SVN004-EN
MCD 048-060 DB/D1
Blower
Return Air Plenum
(Standard)
Outdoor Unit
Indoor Unit
Electric Heater
(Option)
Condensate Drain Pan
Motor
Evaporator Coil
Outlet Collar
L/O- 02091985TRA 21/4/03, 2:44 PM5
Page 6
6 MS-SVN004-EN
Location and Preparation of Units
Indoor Unit
1. Select a convenient location that allows the air to reach every corner of the room and where it is easy to route the refrigerant tubing, wiring and drain to the outside.
2. The ceiling construction should be strong enough to support the weight of the unit.
3. The refrigerant tubing, drain piping and wiring conduit are connected through the wall.
4. Refrigerant tubes between the indoor and the outdoor units and drain pipes should be as short as possible (Figure 1).
5. If a refrigerant charge adjustment is necessary, follow the Installation Manual for the Outdoor Unit.
Outdoor Unit
See instructions for location and preparation of the unit in the Installation Manual for the Outdoor Unit.
Installation Method:
Indoor Unit
After selecting the location to place the unit, follow these steps:
1. Make a hole in the wall to route tubing and wiring through a locally purchased PVC pipe. The hole should slope downwards slightly, towards the outside (Figure 2).
Figure 1
2. Before cutting, check that no pipes or studs are directly behind the place to be cut. Avoid areas where electrical wiring or conduits are located.
3. Hang the unit on a solid and level roof. Noise, vibration or leakage could occur on and unstable foundation (Figure 3,4). For correct installation of duct work see (Figure 6).
4. Support the unit solidly.
5. To have access to electrical terminals, remove the right side junction box (Figure 2).
6. Note that refrigerant tubing, interconnecting wiring and drain hose should go through the wall. Shape these items so that they will easily fit through the wall.
Figure 2
Outdoor Unit
See the proper installation method provided in the Installation Manual for the Outdoor Unit.
Installation Requirements
Important
- Read the Installation Manual completely before installing and operating the system.
-Turn on the mains power at least five (5) hours before operating the system.
Installation Requirements
Following is a brief outline of where and how to install the unit. Please read over the entire set of instructions for indoor and outdoor units and make sure all accessory parts list are with the unit before beginning.
1. Tools Required for Installation (not supplied)
- Level
- Hole saw or saw
- Core bits
- Hammer
- Drill
-Torque wrench
- Adjustable wrench
- Standard screwdriver
- Phillips head screwdriver
- Knife or wire stripper
-Tape measure
-4 Anchor bolts for ceiling mounting
2. Refrigerant Piping and Insulation Material
- See the Installation Manual included with the Outdoor Unit.
- The length of wiring will determine
the wire size. See local codes and refer to Section Electrical Installation.
Caution
Check local electrical codes and regulations before buying any wire. Also check for any specitic wiring instructions or limitations.
3. Additional Materials Required
for Installation
- Saddles or clamps to secure
refrigerant tubing.
- Insulated clamps or staples for
connecting wire. See local codes.
- Ceiling mount: Use nuts and bolts
as required to mount the unit on the ceiling. Use 4 (3/8) fasteners or closest standard metric with nuts and lock washers. The length will vary with application.
- Refrigerant oil and tape
(insulation).
- Putty or similar filler.
L/O- 02091985TRA 21/4/03, 2:44 PM6
Page 7
7MS-SVN004-EN
J
K
F
E
E
H
G
C
D
D
A
B
K
Min.750 Min. 800 100 150 50 200 Min. 100 Min. 50Min. 200 Min. 300 Min. 300
NOTE: FOR DUCT LENGTH PLEASE SEE PAGE 15, 16 AND 17
IJHABCDEFG
DISTANCE (M.M.)
I
CELING
WALL
DRAIN PIPE
DRAIN PIPE
RETURN PLENUM
WITH FILTER
DETAIL "X"
FLEXIBLE CONNECTER
CHAMBER
CHAMBER
FILTER
FILTER
RETURN AIR GRILLE
SLANT 1 : 50
SUPPLY
DUCT
SUPPLY DUCT
FIGURE 3 (SIDE VIEW)
FIGURE 4 (TOP VIEW)
Unit Installation
L/O- 02091985TRA 21/4/03, 2:44 PM7
Page 8
8 MS-SVN004-EN
Units Installation
6
L/O- 02091985TRA 21/4/03, 2:44 PM8
Page 9
9MS-SVN004-EN
Connection of Refrigerant Tubing
Proper installation prodecure is recommended in the Installation Manual Package, usually provided together with the outdoor unit. It is advisable to read bofore installing.
The indoor unit refrigerant connections are located on the left hand side when facing the unit (Figure 7).
Figure 7
Connecting the Units with Flaring Procedure.
1. Cut the copper tube to the required length with a tube cutter. It is recommended to cut approx. 20-30 cm. longer than the tubing length.
2. Remove burrs at the end of the copper tube with a tube reamer or file, as shown in Figure 8.
Figure 8
Copper Tubing
Reamer
When reaming, hold the tube end downward and be sure that no copper scraps fall into the tube (Figure 9).
Deburring
Before
After
Figure 9
3. Remove the flare nut from the unit and be sure to insert on the copper tube.
4. Make a flare at the end of the copper tube with a flare tool (Figure 10).
Flare Nut
Copper Tubing
Flare Tool
Figure 10
A good flare should have the following characteristics:
• Inside surface is glossy and smooth.
• Edge is smooth.
•Tapered sides are of uniform length.
Cautions Before Connecting Tightly
1. Be sure to apply a sealing cap or
water-proof tape to prevent dust or water from getting into the tubes before they are used.
2. Be sure to apply refrigerant
lubricant to the matching surfaces of the flare and union before connecting them together. This is effective for reducing gas leaks (Figure 11).
Figure 11
Apply refrigerant lubricant here
3. For proper connection, align the union tube and flare tube straight with each other, then screw in the flare nut lightly at first to obtain a smooth match (Figure 12).
Union Flare Nut
Figure 12
4. Tighten the flare nuts, using the appropriate wrench.
Connecting the Unit with Brazing Prodecure
1. Cut the copper tube to the required length with a tube cutter. It is recommended to cut approx. 20-30 cm. longer than the tube length.
2. Remove burrs at the end of the copper tube with a tube reamer (Figure 8).
3. There are 2 ways to connect the copper tube
- Use a coupling between the copper tube of Fan Coil Unit and the copper tube used for installation (Figure 13).
Copper Tube of Fan Coil Unit
Solder Coupling
Copper Tube of Condensing Unit
Figure 13
- Expand the copper tube by using a swaging tool set as in Figure 14.
Swaging Tool
Tube Holder (Clamp)
Copper Tube
Figure 14
4. To braze the copper tube, before brazing a copper tube to a solder coupling or a copper tube to an expanded tube, do not forget to keep them tight as shown in Figure 15.
COMMET 3
Torch
Solder Coupling
Copper Tube from Condensing Unit
Solder Rod
Figure 15
Copper Tube from Fan Coil Unit
L/O- 02091985TRA 21/4/03, 2:44 PM9
Page 10
10 MS-SVN004-EN
Condensate Drain Piping
Condensate Drain Piping
1. The drain hose should run straight down the wall to a level where the run off will not stain the wall.
2. These should have water traps. Avoid putting the end of the hose in water.
3. To conveniently drain the system, the drain piping must slant downward, with a slope of at least 1:50 to prevent leakage.
4. When the drain hose is placed in the room, insulate the hose with foam polyethylene to avoid damage to the ceiling or furniture.
5. After completing installation of refrigerant lines, wiring and drain connections, bind the tubing, wiring and drain piping (check if local codes permit binding) into a bundle by using tape at 100 or 200 mm (4" to 8") intervals. Make sure the drain tube is at the bottom of the bundle (Figure 16).
Figure 16
P.V.C. Conduit
Control Wiring
Power Wiring with Ground Wiring
Suction Line Tube
Insulation Tube
P.V.C. Tape
Liquid Line Tube
Water Condensated Drain Tube (P.V.C. Tube)
L/O- 02091985TRA 21/4/03, 2:44 PM10
Page 11
11MS-SVN004-EN
Electrical Installation
Electrical Installation
All wiring and grounding must comply with local electrical codes.
Wiring Important Safeguards:
- Check the unit nameplate for electrical rating. Be sure wiring is done according to local codes and wiring diagram.
- Use a separate power line with circuit breaker for each air conditioning unit.
- Connect electrical ground to all units.
- Wiring should not touch refrigerant tubing, compressor, motors or moving parts.
- The manufacturer will accept no responsibility for problems caused by unauthorized changes in the internal wiring.
- Connect the wiring firmly.
Indoor Unit
Remove the right side junction box (see previous instructions) to access the terminal base.
System Wiring Routing
- Pass the system wiring through the PVC pipe, referred to in the Section of Installation Method (both power and control lines) to interconnect indoor and outdoor units.
- Connect the wire terminals to the terminal base. See connection indication on system wiring diagram.
- Make sure all connections are tight.
Outdoor Unit
See the electrical installation instructions in the Installation Manual for the Outdoor Unit.
L/O- 02091985TRA 21/4/03, 2:44 PM11
Page 12
12 MS-SVN004-EN
Wiring Diagram
CONCEALED FAN COIL UNITS COOLING ONLY MCD 512-536 DB/D1 MCD 048-060 DB/D1
Remove HI-BR wire from TB-1 and replace with EXTRA HI-BLK wire when high speed/cfm is required in the field.
EXTRA–HI
BLK
HI MED LOW COM
BR BL RD WH
BLOWER
MOTOR
1 2 3 4
L2 L1 C1 C2
THERMOSTAT
3 SPEED SWITCH
POWER SUPPLY 200-240V/1PH/60Hz 220-240V/1PH/50Hz
200-240 VAC CONTROL WIRING TO CONDENSING UNIT.
NOTE :
1. Power wiring and grounding of equipment must comply with local codes.
2. Ensure that power supply agrees with equipment nameplate.
3. Use only copper conductors.
LEGEND :
FIELD WIRING FACTORY WIRING
LOW MEDHI
L/O- 02091985TRA 21/4/03, 2:44 PM12
Page 13
13MS-SVN004-EN
CONCEALED DX AIR HANDLER COOLING-HEATING MCD 512-524 DB/D1
EXTRA–HI
BLK
HI MED LOW COM
BR BL RD WH
BLOWER
MOTOR
BLK RD RD
1 2 3 4 5 6
REMOVE HI-BR WIRE FROM TB-1 AND REPLACE WITH EXTRA HI-BLK WIRE WHEN HI SPEED/CFM IS REQUIRED IN THE FIELD.
HEATER THERMAL OVERLOAD PROTECTOR (MANUAL RESET) (MAX.20AMP. NON-INDUCTIVE FULL LOAD CURRENT)
HEATER THERMAL OVERLOAD PROTECTOR (AUTO RESET) (MAX.20AMP. NON-INDUCTIVE FULL LOAD CURRENT)
HEATER
HC HC
10
2468
HEAT
COOL
TO HEATING
TO COOLING
THERMOSTAT
COOLING-HEATING
SWITCH
3 SPEED SWITCH
h
OFF
LOWMED HI
POWER SUPPLY 200-240V/1PH/60Hz 220-240V/1PH/50Hz
200-240 VAC CONTROL WIRING TO CONDENSING UNIT.
LEGEND:
FIELD WIRING FACTORY WIRING
1. POWER WIRING AND GROUDING OF EQUIPMENT MUST COMPLY WITH LOCAL CODE.
2. ENSURE THAT POWER SUPPLY AGREES WITH EQUIPMENT NAME PLATE.
3. USE ONLY COPPER CONDUCTORS.
NOTE:
LNC1C2
Wiring Diagram
L/O- 02091985TRA 21/4/03, 2:44 PM13
Page 14
14 MS-SVN004-EN
CONCEALED FAN COIL UNITS COOLING-HEATING MCD 530-536 DB/D1 MCD 048-060 DB/D1
Wiring Diagram
C
C
H
H
HEATER
HEATER
CH
HC
NOTES :
THERMOSTAT
3 SPEED SWITCH
1. POWER WIRING AND GROUDING OF EQUIPMENT MUST COMPLY WITH LOCAL CODES.
2. ENSURE THAT POWER SUPPLY AGREES WITH EQUIPMENT NAME PLATE.
3. USE ONLY COPPER CONDUCTORS.
HEATER THERMAL OVERLOAD PROTECTOR (MANUAL RESET) (MAX.20AMP. NON-INDUCTIVE FULL LOAD CURRENT)
HEATER THERMAL OVERLOAD PROTECTOR (AUTO RESET) (MAX.20AMP. NON-INDUCTIVE FULL LOAD CURRENT)
FIELD WIRING FACTORY WIRING
COOLING - HEATING
LEGEND :
MOTOR
BLOWER
EXTRA-HI
RD
RD
WH
LOW COM
BLK
MED
HI
RD
BL
BR
BLK
TO HEATING
TO COOLING
COOL
SWITCH
h
HEAT
OFF
LOW MED HI
LNC1
5
2 4
6 8
0 1
6
4
3
2
1
C2
POWER SUPPLY 200-240V/1pH/60Hz 220-240V/1pH/50Hz
200-240 VAC CONTROL WIRING TO CONDENSING UNIT.
Remove HI-BR wire FROM TB-1 and replace with EXTRA HI-BLK wire when high speed/cfm is required in the field.
L/O- 02091985TRA 21/4/03, 2:44 PM14
Page 15
15MS-SVN004-EN
Dimensional Data
Model
MCD 536
MCD 518 MCD 524 MCD 530
MCD 512
External Dimensions (No Plenum)
Refrig. Line Conn. Size Number OfAll External Dimensions are in inch (mm.)
AB CSuction Liquid Fan(s) Motor(s)
2 2 2 2 2
1 1 1 1 1
30"(762) 34 3/4"(882) 37 1/4"(946) 1/4"(6.35) 1/2"(12.7) 30"(762) 34 3/4"(882) 37 1/4"(946) 1/4"(6.35) 1/2"(12.7)
36"(914) 40 1/4"(1034) 43 1/4"(1098) 3/8"(9.52) 5/8"(15.87)
30"(762) 34 3/4"(882) 37 1/4"(946) 3/8"(9.52) 5/8"(15.87)
42"(1067) 34 7/8"(1087) 49 1/4"(1251) 3/8"(9.52) 3/4"(19.05)
VIEW "A"
Ø16
32
111127
63.5
HANGER HOLES - X6
SEE VIEW "A"
A B C
C
SUCTION CONNECTION
LIQUID CONNECTION
284
252
166
254
17440
DRAIN CONN. Ø22.5 MPT
210
234
Note: From the experience of our Trane technician, based on the design condition, at velocity at supply air grille of 300 ft/min for bedroom and 400
ft/min for office (based on free face area), the length of the air duct should be more than 3 meters.
L/O- 02091985TRA 21/4/03, 2:44 PM15
Page 16
16 MS-SVN004-EN
VIEW "A"
Ø16
32
E D
111127
63.5
A B C
Ø20
HANGER HOLES - X6 SEE VIEW "A"
C
SUCTION CONNECTION
LIQUID CONNECTION
625
490
300
266
17440
DRAIN CONN. Ø22.5 MPT
254
165
External Dimensions (Return Air Plenum is option)
All External Dimensions are in inch (mm.) Refrig. Line Conn. Sizes
AB CD ESuction Liquid Fan(s) Motor(s)
MCD 512
30"(762) 34 3/4"(882) 37 1/4"(946) 30"(762) 33 15/16"(862) 1/4"(6.35) 1/2"(12.7) 2 1 MCD 518 30"(762) 34 3/4"(882) 37 1/4"(946) 30"(762) 33 15/16"(862) 1/4"(6.35) 1/2"(12.7) 2 1 MCD 524 30"(762) 34 3/4"(882) 37 1/4"(946) 30"(762) 33 15/16"(862) 3/8"(9.52) 5/8"(15.87) 2 1 MCD 530 36"(914) 40 1/4"(1034) 43 1/4"(1098)
36"(914) 39 15/16"(1014) 3/8"(9.52) 5/8"(15.87) 2
1
MCD 536 42"(1067) 42 7/8"(1087) 49 1/4"(1251) 42"(1067)
45 15/16"(1167) 3/8"(9.52) 3/4"(19.05) 2 1
Number Of
Model
Note: From the experience of our Trane technician, based on the design condition, at velocity at supply air grille of 300 ft/min for bedroom and 400
ft/min for office (based on free face area), the length of the air duct should be more than 3 meters.
Dimensional Data
L/O- 02091985TRA 21/4/03, 2:44 PM16
Page 17
17MS-SVN004-EN
VIEW "A"
Ø16
32
Ø20
HANGER HOLES - X6 SEE VIEW "A"
A B C
E D
111
139
75
SUCTION CONNECTION
408
352
180
30
DRAIN CONN. Ø21 MPT
LIQUID CONNECTION
394
354
615
759
C
ABCDESuction Liquid Fan(s) Motor(s)
MCD048 36.06"(916) 40.70"(1034) 43.58"(1107) 35.70"(907) 39.88"(1013) 1-1/8"(28.57) 3/8"(9.52) 2 1
MCD060 42.08"(1069) 46.73"(1187) 49.21"(1250) 41.73"(1060) 45.90"(1166) 1-1/8"(28.57) 3/8"(9.52) 2 1
External Dimensions (Return Air Plenum is Standard)
All External Dimensions are in inch (mm.) Refrig. Line Conn. Size Number Of
Model
Note: From the experience of our Trane technician, based on the design condition, at velocity at supply air grille of 300 ft/min for bedroom and 400
ft/min for office (based on free face area), the length of the air duct should be more than 3 meters.
Dimensional Data
L/O- 02091985TRA 21/4/03, 2:44 PM17
Page 18
18 MS-SVN004-EN
Regular Maintenance
Be sure to disconnect the power before inspection or maintenance of air conditioner.
1. Cleaning the air filter Air flow is reduced and cooling efficiency impaired if the filter is clogged. Be sure to clean the filter every two weeks during the cooling season.
1.1 How to remove the air filters
- Loose screws located under the filter in return air plenum set.
- Remove air filter frame from return air plenum set.
1.2 How to clean the air filter.
-Wash away dust from the air filter with clean water or vacuum it with an electric vacuum cleaner.
Note:
Once the air filter is washed, dry it completely before returning it to its original position. After cleaning be sure to return it to its original position.
Cautions
- Do not wash the air filter in water
that is over 40ºC or it may shrink.
- Do not expose the air filter to fire.
- Do not expose the air filter to direct
sunlight for a long time.
- Clean the air filter more frequently
Figure 8
when the air is very dirty.
Maintenance
L/O- 02091985TRA 21/4/03, 2:44 PM18
Page 19
19MS-SVN004-EN
Notes
L/O- 02091985TRA 21/4/03, 2:44 PM19
Page 20
Literature Order Number MS-SVN004-EN 0200
New MCD-SV1801-EN 0698
Stocking Location Bangkok, Thailand
∫√‘…—∑ ·Õ¡·Õ√å ®”°—¥ 35 À¡Ÿà 8 ∂.ªŸÉ‡®â“¡‘ßæ√“¬ µ.”‚√ß„µâ Õ.æ√–ª√–·¥ß ®.¡ÿ∑√ª√“°“√ 10130
Since The Trane Company has a policy of continuous product and product data improvement, it reserves the right to change design and specifications without notice.
Trane Thailand
7th Floor, Ploenchit Center Building 2 Sukhumvit Road, Klongtoey Bangkok 10110
Amair Limited
35 Mu 8, Poochaosamingprai Road Samrong Tai, Samutprakarn 10130 http://www.trane.com An American Standard Company
L/O- 02091985TRA 21/4/03, 2:45 PM20
Loading...