Trane MCC 518 ZB, MCC 524 ZB, MCC 530 ZB, MCC 536 ZB, MCC 048 ZB Installation Manual

MCC-SVN02A-EN
Models Cooling Only
MCC 518 ZB MCC 524 ZB MCC 530 ZB MCC 536 ZB MCC 048 ZB
October 2007
Installation Manual
Split System, 18,000 - 48,000 Btu/h Under ceiling T ype MCC Series 50 Hz
CASSETTE
MCC-SVN02A-EN
General Information
General Information
This Installation Manual is given as a guide to good practice in the installation by the installer of MCC mini-split system. Installation procedur es should be performed in the sequence that they appear in this manual.
For installing the unit to operate properly and r eliably, it must be installed in accor dance with these instructions. Also, the services of a qualied service technician should be employed, thr ough the maintenance contract with a r eputable ser vice company .
Read this Installation Manual completely befor e installing the air conditioning system.
About this Manual
Cautions appear at appr opriate places in this Installation Manual. Your personal safety and the pr oper operation of this machine r equire that you follow them car efully. The T rane Company assumes no liability for installations or servicing performed by unqualied personnel. All phases of the installation of this air conditioning system must conform to all national, pr ovincial, state and local codes.
About the Unit
These MCC units ar e assembled, pressur e tested, dehydrated, char ged and run tested befor e shipment. The information contained in this manual applies to MCC units ar e designed to operate in cooling mode only .
Trane MCC series of fer ceiling mounted installation to leave the oor space unclutter ed, and equipped with LCD wir eless r emote contr ol.
Reception
On ar rival, inspect the unit befor e signing the delivery note. Specify any damage of the unit on the delivery note, and send a r egister ed letter of protest to the last carrier of the goods within 72 hours of delivery . Notify the dealer at the same time.
The unit should be totally inspected within 7 days of delivery . If any concealed damage is discover ed, send a r egister ed letter of pr otest to the carrier within 7 days of delivery and notify the dealer .
Wa rning
Warnings ar e pr ovided at appr opriate places in this manual to indicate to installers, operators and service personnel of potentially hazar dous situations which, if not avoided, COULD r esult in death or serious injury.
Caution
Cautions ar e provided at appr opriate places in this manual to indicate to installers, operators, and service personnel of potentially hazar dous situations which, if not avoided, MA Y result in minor or moderate injury or malfunction of the unit.
Your personal safety and the pr oper operation of this unit r equire that you follow them car efully. The T rane Company assumes no liability for installations or servicing performed by unqualied personnel.
Wa rranty
Warranty is based on the general terms and conditions by country . The warranty is void if the equipment is modied or r epair ed without the written appr oval of The T rane Company , if the operating limits ar e exceeded or if the contr ol system or the electrical wiring is modied.
Damage due to inappr opriate installation, lack of knowledge or failure to comply with the manufactur er’s instructions, is not cover ed by the warranty obligation. If the installation does not conform to the rules described in Installation Manual, it may entail cancellation of warranty and liabilities by The T rane Company .
Important
This document is customer pr operty and is to r emain with unit. Please place in service information pack upon completion of work. These instructions do not cover all variations in systems, nor do they provide for every possible contingency to be met in connection with installation. Should further information be desir ed or should par ticular pr oblems arise which ar e not cover ed suf ciently in this manual, the matter should be referred to your authorized T rane dealer.
MCC-SVN02A-EN
3
Contents
4
MCC-SVN02A-EN
Figure 1
Figure 2
Figure 3
Figure 4
Figure 5
more than
100 cm.
more than
100 cm.
Lock Nut
Washers
Suspension
Bracket
Cross Section
of Air Outlet
Indoor Unit Installation
Where to install Indoor Unit
• There should not be any heat source or steam near the unit.
• There should not be any obstacles to prevent the air circulation.
• A place where air circulation in the room will be good.
• A place where drainage can be easily obtained.
• A place where noise prevention is taken into consideration.
• Do not install the unit near the door way.
Indoor Unit Installation
• Select the location where a space is more than 100 cm. as shown in gure 1 also ensure that the position dose not interfere with light tting, sprinkle head, etc.
• Determine the ceiling hole by using the paper pattern.
- Determine the mounting position
• Hang the four mounting rods to the positions marked as picture shown in gure 3 (using twelve nuts and eight washers to support the suspension brackets). Suspend the unit to the mounting rods. Lock the nuts, ensure for good drainage, and check whether the unit is on horizontal level by using leveling guage.
• Install the leveling metal plate to adjust the gap between the unit and a ceiling, xing the screws
paper pattern.
• Remove four screws (M8). Fix the front panel with the units by tighten up four screws (M8).
Caution: Over tightening the screws will distort the front panel.
MCC-SVN02A-EN
5
Figur e 6
Figur e 7
more than 10 cm.
more than 10 cm.
more than 10 cm.
more than 70 cm.
more than 35 cm.
more than 30 cm.
more than 10 cm.
more than 30 cm.
more than 120 cm.
more than 35 cm.
Wir eless Remote Control
Figur e 8
Outdoor Unit Installation
Wher e to install Outdoor Unit
• The foundation must be solid enough to bear the weight and vibration of the unit.
• The space ar ound the unit is adequate for ventilation.
• The location is not close to any amable gases.
• The location is sufciently isolated so that the running noise and the hot exhaust air do not disturb the users or their neighbors.
• Easy access to check and to maintain.
• Ensur e the spaces indicated by arrows fr om the wall, ceiling, fence, or other obstacles.
Caution
Installation in the following places may cause pr oblems. If it is unavoidable to use such places, consult with your distributor or dealer .
• A place with machine oil.
• A saline place such as a place very close to a seashore.
• A place with sulphur gas.
• A place where high-fr equency waves are generated by radio equipment, welder and medical equipment.
Remote Contr ol Installation
Locate and attach the wireless remote contr ol as follows:
• Do not place the remote control near heat sources or expose to the direct rays of the sun.
• Do not expose the remote control to the indoor unit’s supply air stream.
• Do not place in a conned space.
• Attach the remote control holder as shown in gure 8.
6
MCC-SVN02A-EN
Figure 15
Figure 10
Figure 9
Figure 11
Figure 12
Figure 13
Copper
tubing
Reamer
Before
After
Flare nut
Flare tool
Copper
tubing
Apply refrigerant
lubricant here
Flare nut
Union
epols a eviG
Figure 14
Drain hose
Connection of Refrigerant Tubing and Condensate Drain Piping
Deburring
Connecting the unit with aring procedure
1. Flaring (If piping is procured or cut at the site). Cut the copper tube to the required length with a tube cutter. It is recommended to cut approx. 30-50 cm. longer than the tubing length you estimate.
2. Hold each pipe downward when cutting and remove burrs at the end of the copper tube with a tube reamer or le. This process is important and should be done carefully to make a good are (Figure 9 and Figure 10).
A good are should have the following characteristics:
- Inside surface is glossy and smooth.
- Edge is smooth.
- Tapered sides are of uniform length.
Bending
5. When bending the tube, be careful not to crush it. To prevent crushing of the tube, bend it gently and do not bend the tube at a radius curvature of less than 100 mm.
6. If the copper tube is bent or pulled too often, it will become sti. Do not bend the pipe more than three times at one place.
Cautions before Connecting Tubes Tightly
7. Be sure to apply a sealing cap or water-proof tape to prevent dust or water from getting into the tubes before they are used.
8. Be sure to apply refrigerant lubricant to the matching surfaces of the are and union before connecting them together. This is eective for reducing gas leaks (Figure 12).
10. Tighten the are nut to the specied tightening torque with torque wrench and adjustable wrench.
Condensate Drain Piping
- The drain hose should run straight down the wall to a level where the runo will not stain the wall.
- There should be no traps. Avoid putting the end of the hose in water.
- To conveniently drain the system, the drain hose must slant downward, with a slope of at least 1 : 50 to prevent leakage as shown in gure 14.
When reaming, hold the tube end downward and be sure that no copper scraps fall into the tube.
3. Remove the are nut from the unit and be sure to mount it on the copper tube.
4. Make a are at the end of copper tube with a are tool (Figure 11).
Connection
9. For proper connection, align the union tube and are tube straight with each other, then screw in the are nut lightly at rst to obtain a smooth match (Figure 13).
- When the drain hose is placed in the room, insulate the hose with foam polyethylene to avoid damage to the ceiling or furniture.
- After completing installation of refrigerant lines, wiring and drain connections, bind the tubing, wiring and drain hose (check if local codes permit binding) into a bundle by using tape at 100 or 200 mm (4" to 8") intervals. Make sure the drain hose is at the bottom of the bundle (Figure 15).
MCC-SVN02A-EN
7
Leak Check and System Evacuation
Leak Check
After the connection operation of refrigerant lines to both the outdoor and indoor unit is completed, the eld brazed connections must be checked for leaks. Pressurize the system through the service valve with dry nitrogen to 250 psi. Use soap bubbles or other leak-checking methods to ensure that all eld joints are leak free. If not, release pressure, repair and repeat leak test.
System Evacuation
1. After completion of leak check, evacuate the system.
2. Attach appropriate hoses from manifold gauge to gas and liquid line pressure taps. Note: Unnecessary switching of hoses can be avoided and complete evacuation of all lines leading to sealed system can be accomplished with manifold center hose and connecting branch hose to a cylinder of R-22 and vacuum pump.
3. Attach center hose of manifold gauges to vacuum pump.
4. Evacuate the system to hold a 350 micron vacuum.
5. Close o valve to vacuum pump and observe the micron gauge. If gauge pressure rised above 500 microns in one (1) minute, then evacuation is incomplete or the system has a leak.
6. If vacuum gauge does not rise above 500 microns in one (1) minute, the evacuation should be complete.
7. With vacuum pump and micron gauge blanked o, open valve on R-22 cylinder and allow refrigerant pressure to build up to about 40 psig.
8. Close valve on the R-22 supply cylinder. Close valves on manifold gauge set and remove refrigerant charging hoses from liquid and gas gauge ports.
9. Leak test the entire system. Using proper procedures and caution, repair any leaks found and repeat the leak test.
Refrigerant Charging Procedure
Charge refrigerant through the gauge port on the liquid line until pressure at gauge is up to 120-150 psi. Once the charge enters the system, backseat (open) the liquid line service valve and disconnect the charging line and replace the cap on the gauge port.
Gaseous Charging
This procedure is accomplished with the unit operating. Electrical connections must be complete. Do not proceed until the system is ready to operate.
Procedure
1. Connect R-22 drum with gauge manifold to the Schrader valves (pressure taps) on the compressor discharge and suction lines.
2. Turn on power to the unit. Allow the system to run for ve to ten minutes to stabilize operating conditions.
3. Once proper airow is established, observe the suction and head pressure gauges on the gauge manifold. Pressure reading should fall approximately at the normal points. Add or remove refrigerant (gas only) as required to obtain correct head and suction pressures. Check suction line superheat and condenser sub-cooling to ensure the unit is operating properly.
4. Disconnect all power to the unit.
5. Remove the charging system from the unit and close the opening in the bottom of the control box with the pivotal cover before attempting to replace access panel.
Liquid pressure
Suction pressure
Vacuum pump
R-22
Service hose
Liquid line
Suction
line
Electrical connection
Figure 16
MCC-SVN02A-EN
9
Wiring Diagram
OUTDOOR CASSETTE 18000 Btu/h & 24000 Btu/h
220-240/1/50 Hz 380-420/3/50 Hz MCC518-048ZB
MCC-SVN02A-EN
10
Wiring Diagram
OUTDOOR CASSETTE 30000 Btu/h
MCC-SVN02A-EN
11
Wiring Diagram
OUTDOOR CASSETTE 36,000 Btu/h & 48,000 Btu/h
36,000 48,000
12
MCC-SVN02A-EN
MCC518ZB MCC524ZB MCC530ZB MCC536ZB MCC048ZB
A. Height above ceiling B. Height above suspension brackets C. Height of condensate drain above ceiling D. Pipe exit position
Model
950
390
340
512
330
370
350
CEILING HOLES 860-890
418
785
drainpipe outlet
850
60
main cable entry
B
C
D
22
refrigerant pipe
Dimensional Data
A
230 230 230 290 290 100 100 100 150 150 200 200 200 200 200
150 150 150 150 150
MCC-SVN02A-EN
13
Notes
Trane has a policy of continuous product and product data implement and reserves the right to change design and specications without notice.
New
Loading...