Trane VPCF, VPWF, VPEF, VSCF, VSWF Catalogue

...
Product Catalog
VariTrane™ Products
Parallel and Series Fan-Powered
VPCF, VPWF, VPEF, VSCF, VSWF, VSEF,
LPCF, LPWF, LPEF, LSCF, LSWF, LSEF
Variable-Air-Volume (VAV) System
OA
cooling
coil
variable-
speed drive
supply
fan
thermostat
PA
RA
VAV
box
SA
July 2013
VAV-PRC012-EN
Introduction
Fan-powered units offer energy savings due to intermittent fan control.The fan energizes only in heating mode when the space needs heat. Additional energy savings are obtained by using warm plenum air forfree reheat. Motor heat is never wasted in parallel units.Theyare an excellent choice when minimal zone heating is needed.
Figure 1. Parallel fan-powered terminal unit (L) & series fan-powered terminal units (R)
Figure 2. Low height series: LSCF (L) & low height series: LSWF (R)
Figure 3. Low height series: LSEF (L) & low height parallel: LPCF (R)
Figure 4. Low height parallel: LPWF (L) & low height parallel: LPEF (R)
Revision Summary
VAV-PRC012-EN (16 Jul 2013). Updated proportional water valve design.
VAV-PRC012-EN (27 June 2013). Updated controls information. Updated dimensions for units
with attenuators.
Trademarks
Earthwise, VariTrane, VariTrac,Trane and theTrane logo are trademarks of Trane in the United States and other countries. All trademarks referenced in this document are the trademarks of their respective owners.
BACnet is a registered trademark of American Society of Heating, Refrigerating and Air­Conditioning Engineers (ASHRAE); LONMARK and LonTalk are registered trademarks of Echelon Corporation.
© 2013Trane All rights reserved VAV-PRC012-EN
Table of Contents
Features and Benefits ..............................................5
Agency Certifications ..............................................13
Model Number Descriptions ........................................15
Selection Procedure ...............................................17
Performance Data ................................................24
Parallel Fan-Powered Terminal Units .............................. 24
Series Fan-Powered Terminal Units ............................... 35
Low Height Parallel Fan-Powered Terminal Units .................... 47
Low Height Series Fan-Powered Terminal Units ..................... 53
Electrical Data ....................................................59
Parallel Fan-Powered Terminal Units .............................. 59
Series Fan-Powered Terminal Units ............................... 63
Low Height Parallel Fan-Powered Terminal Units .................... 68
Low Height Series Fan-Powered Terminal Units ..................... 70
Acoustics Data ...................................................76
Parallel Fan-Powered Terminal Units .............................. 76
Series Fan-Powered Terminal Units ............................... 85
Low Height Parallel Fan-Powered Terminal Units .................... 92
Low Height Series Fan-Powered Terminal Units ..................... 98
Dimensional Data ................................................103
Parallel Fan-Powered Terminal Units ............................. 103
Series Fan-Powered Terminal Units .............................. 109
Low Height Parallel Fan-Powered Terminal Units ................... 123
Low Height Series Fan-Powered Terminal Units .................... 134
Mechanical Specifications: Fan-Powered ............................142
DDC Controls ...................................................147
Control Logic ................................................. 147
DDC Remote Heat Control Options ............................... 148
Tracer™ UC400 and UC210 Programmable BACnet Controllers ....... 152
Trane DDC VAV Controller Logic ................................. 154
Flow Tracking Control .......................................... 157
Tracer™ Programmable BACnet Controller — Unit Control Module .... 158
Trane LonMark DDC VAV Controller .............................. 160
Trane DDC VAV Controller Logic ................................. 162
VAV-PRC012-EN 3
Flow Tracking Control .......................................... 165
LonMark™ Direct Digital Controller—Unit Control Module ........... 166
Direct Digital Controller—Unit Control Module ..................... 169
Wireless Comm Interface (WCI) .................................. 170
Wireless Receiver/Wireless Zone Sensor .......................... 172
DDC Zone Sensor ............................................. 173
CO
Wall Sensor and Duct CO2Sensor ............................ 174
2
DDC Zone Sensor with LCD ..................................... 176
Zone Occupancy Sensor ........................................ 177
Factory or Field Wired Auxiliary Temperature Sensor ............... 178
Control Relay ................................................. 178
Two-Position Water Valve ...................................... 179
Proportional Water Valve ....................................... 180
Differential Pressure Transducer ................................. 181
Transformers ................................................. 182
Trane Actuator – 90 Second at 60 Hz Drive Time .................... 183
Belimo Actuator – 95 Second Drive Time .......................... 184
Trane Spring Return Actuator ................................... 185
VariTrane DDC Retrofit Kit ...................................... 186
Retrofit Kit Actuator ........................................... 186
Silicon-Controlled Rectifier (SCR) ................................ 187
Pneumatic Controls ............................................ 188
Controls Specifications ......................................... 203
Application Considerations ........................................208
VAV System .................................................. 208
Parallel vs. Series ............................................. 211
Low-Temperature Air .......................................... 213
Energy Savings & System Controls ............................... 216
Control Types ................................................ 218
Flow Measurement and Control ................................. 221
Reheat Options ............................................... 224
Insulation .................................................... 226
Acoustics .................................................... 226
Duct Design .................................................. 230
Best Practices ................................................. 231
Unit Conversions .............................................. 232
Additional VAV System and Product References .................... 233
4 VAV-PRC012-EN

Features and Benefits

VariTrane™– VAV Leadership
VariTrane variable-air-volume (VAV) units lead the industry in quality and reliability and are
designed to meet the specific needs of today’s applications.This generation of VariTrane units builds upon the history of quality and reliability and expands the products into the most complete
VAV offering in the industry.
Parallel Fan-powered units offer energy savings due to intermittent fan control.The fan energizes only inheating mode when the space needsheat. Additional energysavings are obtained by using warm plenum air for free reheat. Motor heat is never wasted in parallel units.They are an excellent choice when minimal zone heating is needed.
Series fan-powered units have fans which are always energized in occupied mode.They are common in applications such as conference rooms, cafeterias, etc., that desire constant airflow rates at all conditions.
Low-height parallel units provide the energy savings of an intermittent fan with the flexibility of an 11"–11.5” casing height.This is a good choice for tight plenum spaces.
Low-height series units have been used for years in projects with strict plenum height requirements. Units are available in 11.0" height.
Energy Efficient Earthwise™ Systems
Figure 5. Rooftop VAV (office building)
A significant consumer of energy in commercial buildings is heating and air conditioning. One of the most energy-efficient HVAC solutions is theVAV system.This inherent system efficiency, along with high-quality, affordable DDC controls, has steadily increased demand forVAV systems over the years. VAV systems save significant energy, are able to deliver the required amount of ventilation air, and provide reliable occupant comfort.
Energy saving featuresmust go beyond a simple VAV unit to incorporate VAV unit level and system level control strategies like:
Ventilation Optimization-Combines demand-controlled ventilation (using either a time-of-day schedule, an occupancy sensor, or a carbon dioxide sensor) at the zone level with ventilation reset at the system level to deliver the required amount of outdoor air to each zone, while minimizing costly over-ventilation.
VAV-PRC012-EN 5
Features and Benefits
S Q s r
y u
g
l
Fan Pressure Optimization- reduces supply fan energy by as much as 40% by intelligently
Night setback reduces energy consumption during unoccupied periods by raising or lowering
Supply AirTemperature Reset-reduces overall system energy use (balancing reduced cooling
Electrically Commutated Motors (ECM) improve the efficiency of fan-powered VAV units.
LowTemperatureAir Distribution can decrease overall system energy use by reducing airflows
To determine the potential energy savings a VAV system can bring to your applications,Trane
offers energy-modeling software like System Analyzer™ andTRACE 700 introduced into the HVAC industry in 1972, the HVAC design and analysis program was the first of its kind and quickly became a defacto industry standard. It continues to grow with the industry meeting requirements for ASHRAE Standard 140, ASHRAE 90.1, and the LEED® Green Building Rating System and has now been approved by the IRS to certify energy savings for building owners. Contact your localTrane Sales Engineer for additional information.
reducing the pressure in the air distribution system to the lowest possible level without impacting occupant comfort.
space temperature setpoints.
and reheat energy with increasedfan energy)by raising thesupply airtemperature at part load, while avoiding elevated space humidity levels.
and the fan energy needed to move that air through the system.
®
. WhenTRACE™ was
Control Flexibility—Trane factory installs more VAV controllers than any other manufacturer in the industry. In addition to Trane DDC controls and simple factory-mounting of non-Trane VAV controllers, Trane now offers a LonMark™ controller that is completely factory-commissioned to maximize installation quality and system reliability. Labor savings are maximized with Trane factory-commissioned controllers.
Service Friendly: * Internal shaft visible through control box cover sight hole for blade orientation verification. * Same-side NEC jumpback clearance— provides all high- and low-voltage components on the same side to minimize field labor. * SQ fan-powered units have improved accessability to internal components. Sliding panels are standard which improve safety and allow servicing with a single technician.
Accurate Flow Ring—Housed and recessed within the air valve to provide flow ring handling/shipping protection. The patented flow ring provides unmatched airflow measurement accuracy.
Optional Narrow Corridor unit configuration — designed to minimize building material expenses by squeezing more into less space. Meets all NEC jumpback clearance requirements for these extra-tight areas. Narrow Corridor Configuration not pictured here. Refer to Series Fan-Powered dimensional data for reference drawings.
Rugged Air Valve—Trane air valves are heavy gage steel with a continuously welded seam to limit inlet deformation. This provides consistent and repeatable airflow across the flow ring with performance you can count on.
Full Range of Insulation—Whether seeking optimal acoustical perf or cleanability, Trane has a complete line of insulation options, inc double-wall, matte-faced, foil-faced, closed cell, etc.
Technologically Advanced " Units— New super-quiet (S fan/motor/wheel assemblie engineered as an air delive system to provide the most efficient design available in industry. For quiet comfort can trust, rely on Trane SQ
Tough Interlocking Panels— Ru and rigidity are assured with Tra patent-pending interlocking pan
Superior Metal Encapsulated VariTrane Units are complete encapsulated edges to arrest fibers and prevent erosion in
6 VAV-PRC012-EN
Construction
Features and Benefits
UL-listed products—
Safety and reliability are vital in commercial construction. AllVariTrane units are completely listed in accordance with UL -1995 as terminal units.This listing includes the VAV terminal with electric heaters. Additionally, all insulation materials pass UL 25/50 smoke and flame safety standards.
AHRI Certified Performance—
All VariTrane units are AHRI certified. AHRI 880 guarantees the pressure drop, flow performance, and acoustical performance provided is reliable and has been tested in accordance with industry accepted standards. AHRI 885 uses AHRI 880 performance and applies accepted industry methods to estimate expected “NC” sound levels within the occupied space.
Casing Design—
Interlocking Panels—VariTrane products are manufactured in the most state-of-the-art VAV facility in the world.The patent-pending interlocking panels are designed using integral I-beam construction technology.This limits deformation and creates tremendous product rigidity. An additional benefit is a smooth unit exterior with few exposed screws—ideal for exposed ceiling applications. VariTrane units are designed for use in systems that operate up to 5" w.c. of inlet pressure.
Metal Encapsulated Edges—AllVariTrane unitsare complete with encapsulated edges to arrest cut fibers and prevent insulation erosion into the airstream.This is the standard of care in applications concerned with fiberglass erosion or projects with either double-wall or externally wrapped duct work.
TheTrane Air Valve—is at the heart of VariTrane terminal units.This is where airflow is measured and controlled. Repeatability and ruggedness is vital.VariTrane products are the most rugged and reliable available.
18-gage Cylinder—limits deformation or damage during shipment and job site handling, and provides even airflow distribution across the flow ring for unmatched airflow measurement accuracy.
Continuously Welded Seam — an automated weld process creates the highest quality continuous seam, which is “right” every time.The welded seam improves air valve rigidity and creates consistent and repeatable airflow across the flow measurement device.The result is a truly round cylinder every time, with no flat spots caused by lower quality crimping and riviting technologies.
Flow Ring—TheTrane flow ring is time tested to perform under the most demanding conditions. Additionally,Trane’s patented flow ring is recessed within the air valve cylinder to reduce the potential for damage during job site handling and installation.
VAV-PRC012-EN 7
Features and Benefits
External Shaft—The simple design provides controller flexibility and is designed to facilitate actuator field replacement.
Position Indicator—The position indicator shows current air valve position to aid in system commissioning. Many times this can be seen from the floor without climbing a ladder.
ExternalActuator—This feature increases serviceability,control system compatibility,and actuator clutch access for simplified commissioning.
Indoor Air Quality (IAQ) Features
The oil embargo ofthe early1970s created an energy crisis,which resulted in tighter buildings,and
reduced ventilation rates. A fallout issue of tighter building construction was poor indoor air quality.This heightened IAQ awareness. IAQ issues have been featured in publications from the smallest towns to the largest cities. System design should consider applicable ventilation and IAQ standards.(See your localTrane Sales Engineer or visit Good indoor air quality results from units and systems which:
Provide the required amount of ventilation air to each zone during all operating conditions
Limit particulates from entering occupied spaces
Allow proper access for periodic cleaning.
www.trane.com for additional information).
Note: Access made easy on new VariTrane units, as shown on this Series Fan-Powered unit.
VariTrane units are designed with simplified access and a full line of insulation options including:
Matte-faced—Typical industry standard with reduced first cost.
Closed-cell—This insulation has anR-value andperformance equivalent to matte-faced insulation.
The main difference is the reduction of water vapor transmission. Closed-cell is designed for use
in installations with a high chance of waterformation. (It has been usedto coat the exterior of chiller evaporator barrels for many years.)
Foil-faced—A fiberglass insulation with a thin aluminum coating on the air stream side to prevent fibers frombecoming airborne.The aluminum lining is acceptable for many applications, however it is not as rugged as double-wall
Double-wall—Premium insulation often used in many health care applications with insulation locked between metal liners.This eliminates the possibility for insulation entering the airstream and allows for unit interior wipe-down as needed.
VariTrane VAV units are the most prepared IAQ units in the industry.
The end result is areliable product designed for peak performance, regardless of jobsite conditions
or handling.
8 VAV-PRC012-EN
Tracer™ Building Automation System
Tracer Building Automation System assures comfort within your building. Building controls have
a bigger job descriptionthan theydid afew years ago. It’s no longer enough tocontrol heatingand cooling systems and equipment. Sophisticated buildings require smarter technology that will carry into the future. Tracer™ controls provide the technology platform – mobile, easy-to-use, cloud-based, scalable and open - for the next generation of data-driven, technology-enabled services that are creating high performance buildings. With aTraneTracer Building Automation System, you’ll:
Reduce operating costs through energy management strategies
Consistently provide occupant comfort
Enjoy reliable operation with standard, pre-engineered and pretested applications
Easily troubleshoot and monitor either on site or from a remote location
Reduce installation time and simplify troubleshooting
Whether factory-mounted or field-installed,Trane offers a wide range of controllers to suit virtually
any application.These unitsare compatible witha variety of building typesand can be usedfor new construction or renovation.Through extensive usability testing internally and with building operators, we’ve designed our controls for real world ease of use.
(Additional control options and sequence-of-operations are located in the “Controls” section.)
Trane VAV UCM DDC Controller
Features and Benefits
DDC (communicating electronic)—DDC controllers are today’s industrystandard. DDC controllers provide system-level data used to optimize overall SYSTEM performance.
Variables such as occupied/unoccupied,
minimum and maximum cfm and temperature, valve position, ventilation fraction, etc. are available on a simple twisted­shielded wire pair. For additional information, see “Industry Issues: Energy Efficiency”.
Note: One of many Trane DDC Control Options which are factory-installed, wired, calibrated, and fully tested before shipment.
Trane DDC controllers provideTrane-designed solid-state electronics intended specifically forVAV
temperature control in space comfort applications. DDC control capabilities include:
Pressure-independent (PI) operation—Provides airflow required by the room thermostat to maintain occupant comfort.The controller automatically adjusts valve position to maintain required airflow. Minimum and maximum airflow is factory-set and field-adjustable.
Factory-set airflow and temperature setpoints
Most advanced system integration in the industry.
Tracer VV550 LonTalk™ Controllers
LonTalk™ Controller
Trane now offers a full line of LonTalk™ controllers designed for simple integration into ANY system which can communicate via the LonMark Space Comfort Control (SCC) protocol.These controllers are also completely factory-commissioned.
VAV-PRC012-EN 9
Features and Benefits
Tracer BACnet™ Controllers
Trane now offers a full line of BACnet controllers designed for simple integration into any system
which can communicate via the BACnet protocol.These controllers are factory-commissioned and shipped ready to be installed.
UC210 BACnet Controller
Trane Wireless Comm Interface (WCI)
WCI controller
Provides wireless communication between theTracer SC,
Tracer Unit Controllers, and BACnet™ Communication
Interface (BCI) modules.
TheTrane WCI is the perfect alternative to Trane’s BACnet
wired communication links (for example – Comm links between aTracer SC andTracer UC400).
Eliminating communication wire used between terminal products, zone sensors, and system controllers has substantial benefits.
Installation time and associated risks are reduced.
Projects are completed with fewer disruptions.
Future re-configurations, expansions, and upgrades are easier and more cost effective.
UC400 BACnet Controller
Trane Wireless Zone Sensor
Wireless Zone Sensor
Provides wireless communication between theUnit Controller and the zone sensor.This is an alterntive to the wired zone sensor when access and routing of communicaiton cable is an issue. It also allows very flexible mounting and relocation of zone sensors
10 VAV-PRC012-EN
Pneumatic Controller
Pneumatic Controller
Binary Input Controller
Features and Benefits
Pneumatic—Pneumatic controllers provide
proven reliability and performance. A full line of options provide:
Highest quality PVR available, which maximizes zone temperature control.
Pressure-independent operation
AllVariTrane pneumatic controllers use the patented flow sensor input to provide the most accurate performance available.
Integration Options (Interfacing with other control systems) - Trane offers three ways to interface with other control systems.
1. UseTrane LonMark, factory-commissioned VAV controllers
2. UseTrane Binary Input Controller (BIC). BIC allows system control through binary logic.This means that a control system on an existing campus, or those seeking “Analog non­communicating control” can control aTrane DDCVAV unit viabasic binarycontact closures, like relays, etc.This can be a cost effective interface option where a fullTrane DDC VAV System is not available.
3. UseTrane BACnet™ factory-commissioned VAV controllers.
Factory-installed vs. Factory-commissioned:
The terms factory-installedand factory-commissioned are often used interchangeably.Trane takes
great pride in being the industry leader in factory-commissioned DDC controllers. Table differentiates these concepts.
Factory-commissioned controllers provide thehighest quality and most reliable units for your VAV system. Additional testing verifies proper unit operation including occupied/unoccupied airflow, temperature setpoints, communication link functionality, and output device functionality.The benefits of factory-commissioning are standard on VariTrane terminal units withTrane DDC controls.This means that factory-commissioned quality on VariTrane VAV units is now available on ANY manufacturer’s control system that can communicate using the LonMark Space Comfort Control (SCC) protocol. (See Controls section for complete listing of variables which are communicated.
Table 1. Factory-installed vs. factory-commissioned
Factory-installed Factory-commissioned
Transformer installed (option) X X
Wires terminated in reliable/consistent setting X X
Controller mounted XX
Electric heat contactors and fan relay wired X X
VAV-PRC012-EN 11
Features and Benefits
Table 1. Factory-installed vs. factory-commissioned
Factory-installed Factory-commissioned
Testing of electric heat contactors and fan relay X
Controller addressing and associated testing X
Minimum & Maximum airflows settings (occupied/unoccupied) X
Minimum & Maximum temperature setpoints (occupied/unoccupied) X
Minimum ventilation requirements X
Thumbwheel enable/disable X
Heating offset X
Wireless communications modules (WCI) X X
Wireless zone sensor X
Indoor Air Quality Management During Construction
LEED wrap option is a pressure sensitive covering that prevents contamination of the
VAV box during the construction phase. It is
utilized to seal all openings without constraining the installation process.
Trane VAV Systems - Proven Performance
Trane is the industry leader in VAV systems, including factory-commissioned controls and
integration with other control systems.This leadership began with customers seeking the most reliable VAV products in the industry.The solution was factory-commissioned controls (see Factory-installed vs. Factory-commissioned). Since then, it has blossomed to include optimized system control strategies.
Control strategies are often made more complicated than necessary. VariTrane DDC controls simplify control strategies by pre-engineeringcontrol logic and sequencinginto the controller.This information is available via a twisted-shielded wire pair, and accessible via aTraneTracer™ SC building automation system. Data is easily accessed via a computer workstation.
Optimized system control strategies, such as ventilation optimization, fan-pressure optimization, and optimal start/stop, are pre-engineered in VariTrane™ unit-level DDC controllers and theTracer SC building automation system.
This allows aTrane VAV system to meet or exceed the latest ASHRAE 90.1 Energy Efficiency
standards. Pre-engineered controls allow consistent, high quality installations which are very repeatable.The end result is PROVEN control strategies you can rely on to perform. For more information on these and other control strategies, contact your localTrane Sales Office, or visit www.trane.com.
PurchasingVAV controllers and VAV hardware from a single manufacturer provides a single contact for all HVAC system related questions.
12 VAV-PRC012-EN

Agency Certifications

There are numerous regulationsand standardsin theindustry thatdetermine theconstruction and
performance parameters for VAV terminal units. Some of the more important of those standards and regulations are listed below, along with a brief description of what each one addresses.
American Society of Heating, Refrigerating and Air-conditioning Engineers
(ASHRAE) - 41.1
ASHRAE - 41.2
ASHRAE - 41.3
These standards specify methods for temperature measurement (41.1), laboratory airflow
measurement (41.2), and pressure measurement (41.3).While none of these standards specifically discusses VAV air terminals, they discuss topics that are aspects of terminal box systems.
Therefore, some engineers will include these standards in their specifications as a primer on
accepted measurement techniques.
ASHRAE - 62
This standard specifies theminimum ventilationrates andindoor air qualitythat areacceptable for
occupied spaces.
ASHRAE - 111
This standard calls out procedures to be followed for testing and balancing HVAC systems. It
includes descriptions of the equipment used, procedures followed, and field changes that must be made when a system is balanced.
Air-Conditioning, Heating and Refrigeration Institute (AHRI)
AHRI 880
This standard sets forth classifications, performance testing requirements, and test results
reporting requirements for air terminal units.The standard contains very detailed procedures that are to be followed for the testing and certification program associated with this standard.This is one of the most commonly referenced standards in the VAV terminal unit industry.The AHRI-880 certification program is designed to police the accuracy of documented performance for terminal units.The certification program requires a sampling of at least four units be tested annually.The tested units are chosen at random by AHRI and sent to an independent laboratory for the testing.
The performance is tested at one specific operating condition.The operating characteristics tested
include discharge and radiated sound power (for the damper and, in the case of fan-powered boxes, the fan), wide-open damper pressure drop, and fan motor amp draw. VariTrane terminal
units are certified according to AHRI-880.
AHRI 885
This document provides a procedure to estimate sound pressure levels in an occupied space.The
standard accounts for the amount of sound pressure in the space due to the VAV air terminal, diffusers and their connecting low pressure ductwork. While sound generated from the central system fan andductwork may be a significant factor in determining thesound pressure level in the room, this standarddoes not address those factors. It focusessolely onthe VAVterminal and items downstream of it.This standard is related to AHRI-880 by using sound power determined using AHRI-880 methodology as a starting point for the AHRI-885 procedure.
Underwriter’s Laboratory (UL) 1995
Underwriter’s Laboratory is an independent testing agency that examines products and determines if those products meet safety requirements. Equipment manufacturers strive to meet UL guidelines and obtain listing and classifications for their products because customers recognize UL approval as a measure of a safely designed product. VariTrane VAV air terminals are listed per UL-1995, Heating and Cooling Equipment.The terminals are listed as an entire assembly.
VAV-PRC012-EN 13
Agency Certifications
National Fire Protection Association
NFPA 70
This standard is also known as the National Electrical Code (NEC).The Code gives standards for
installation of wiring and electrical equipment for most types of commercial and residential buildings. It is often referred to inVAV air terminal specifications when fan-powered boxes, electric heat or electric controls are included.
NFPA 90A
This standard does not speak directly to VAV air terminals but does discuss central system
considerations pertaining to a fire and/or smoke condition.The standard discusses safety requirements in design and construction that should be followed to keep the air-handling system from spreading a fire or smoke.The standard specifies practices that are intended to stop fire and smoke from spreading through a duct system, keep the fire-resistive properties of certain building structures (fire walls, etc.) intact, and minimize fire ignition sources and combustible materials.
14 VAV-PRC012-EN

Model Number Descriptions

Digit 1, 2—Unit Type
VP = VariTrane™ Fan-Powered Parallel VS = VariTrane Fan-Powered Series
LP = VariTrane Fan-Powered
Low-Height Parallel
LS = VariTrane Fan-Powered
Low-Height Series
Digit 3—Reheat
C = Cooling Only E = Electric Heat
W = Hot Water Heat
Digit 4—Development Sequence
F = Sixth
Digit 5, 6—Primary Air Valve
05 = 5" inlet (350 max cfm) 06 = 6" inlet (500 max cfm) 08 = 8" inlet (900 max cfm) 10 = 10" inlet (1400 max cfm) 12 = 12" inlet (2000 max cfm) 14 = 14" inlet (3000 max cfm) 16 = 16" inlet (4000 max cfm) RT = 8" x 14" inlet (1800 max CFM)
Note: 10, 12, 14, 16 Not Available on Low-
Height
Digit 7, 8—Secondary Air Valve
00 = N/A
Digit 9—Fan
P = 02SQ fan (500 nominal cfm) Q = 03SQ fan (1100 nominal cfm) R = 04SQ fan (1350 nominal cfm) S = 05SQ fan (1550 nominal cfm)
T = 06SQ fan (1850 nominal cfm)
U = 07SQ fan (2000 nominal cfm) V = 08SQ Fan (500 nominal cfm) W = 09SQ Fan (900 nominal cfm)
X = 10SQ Fan (1800 nominal cfm)
Digit 10, 11—Design Sequence
** = Factory assigned
Digit 12, 13, 14, 15—Controls
DD01= Cooling Only Control
DD02= N.C. On/Off Hot Water
DD03= Prop. Hot Water
DD04= Staged On/Off E-Heat
DD05= Pulse Width Mod of E-Heat
DD07= N.O. On/Off Hot Water
DD11= VV550 DDC Controller - Cooling
Only
DD12= VV550 DDC Ctrl w/N.C. On/Off
HW Valve
DD13= VV550 DDC Ctrl w/Prop. HW
Valve
DD14= VV550 DDC Ctrl - On/Off
Electric Heat
DD15= VV550 DDC Ctrl w/Pulse Width
Modulation
DD17= VV550 DDC Ctrl w/N.O. On/Off
HW Valve
DD23= VV550 DDC- Basic plus- Local
(Electric heat- PWM) Remote (Staged EH)
DD28= VV550 DDC-Basic plus- Local
(Water heat- N.O. 2-position) Remote (Water- N.O. 2-position)
DD29= VV550 DDC-Basic plus- Local
(Water heat- N.C. 2-position) Remote (Water- N.C. 2-position)
DD30= VV550 DDC-Basic plus- Local
(Water heat- N.O. 2-position) Remote (Water- N.C. 2-position)
DD31= VV550 DDC-Basic plus- Local
(Water heat- N.C. 2-position) Remote (Water- N.O. 2-position)
DD32= VV550 DDC-Basic plus- Local
(Electric heat- Staged) Remote (Staged EH)
DD41= UC400 DDC-Basic (No water or
electric heat)
DD42= UC400 DDC-Basic (Water heat-
Normally Closed- 2 position)
DD43= UC400 DDC-Basic (Water heat-
Modulating)
DD44= UC400 DDC-Basic (Electric heat-
staged)
DD45= UC400 DDC-Basic (Electric heat-
PWM)
DD47= UC400 DDC-Basic (Water heat-
Normally Opened- 2 position)
DD53= UC400 DDC-Basic plus- Local
(Electric heat- PWM) Remote (Staged EH)
DD58= UC400 DDC-Basic plus- Local
(Water heat- N.O. 2-position) Remote (Water- N.O. 2-position)
DD59= UC400 DDC-Basic plus- Local
(Water heat- N.C. 2-position) Remote (Water- N.C. 2-position)
DD60= UC400 DDC-Basic plus- Local
(Water heat- N.O. 2-position) Remote (Water- N.C. 2-position)
DD61= UC400 DDC-Basic plus- Local
(Water heat- N.C. 2-position) Remote (Water- N.O. 2-position)
DD62= UC400 DDC-Basic plus- Local
(Electric heat- Staged) Remote (Staged EH)
DD65= Basic (Electric Heat- Modulating
SCR)
DD66= Basic plus – Local (Electric heat –
Modulating SCR) Remote (Staged EH)
DD71= UC210 DDC-Basic
(Cooling only)
DD72= UC210 DDC-Basic
(Water heat-nc 2pos)
DD73= UC210 DDC-Basic
(Water heat-Modulating)
DD74= UC210 DDC-Basic
(Electric heat-staged) DD75= UC210 DDC-Basic (Electric heat-pwm)
DD77= UC210 DDC-Basic
(Water heat-NO 2pos) DD83= UC210 DDC-Basic+ Local
(Electric heat-pwm)
Remote (Staged)
DD84= UC210 DDC-Basic+ Local
(Water heat Modulating) Remote (Water-NC 2pos)
DD85= UC210 DDC-Basic+ Local
(Water heat Modulating) Remote (Water-NO 2pos)
DD86= UC210 DDC-Basic+ Local
(Water heat NO 2pos)
Remote (Water-Modulating)
DD87= UC210 DDC-Basic+ Local
(Water heat NC 2pos) Remote (Water-Modulating)
DD88= UC210 DDC-Basic+ Local
(Water heat NO 2pos) Remote (Water-NO 2pos)
DD89= UC210 DDC-Basic+ Local
(Water heat NC 2pos) Remote (Water-NC 2pos)
DD90= UC210 DDC-Basic+ Local
(Water heat NO 2pos) Remote (Water-NC 2pos)
DD91= UC210 DDC-Basic+ Local
(Water heat NC 2pos) Remote (Water-NO 2pos)
DD92= UC210 DDC-Basic+ Local
(Electric heat-staged) Remote (Staged)
DD95= UC210 DDC-Ctrl w/Modulating
SCR
DD96= UC210 DDC-SpaceTemp Ctrl w/
Local SCR & Remote Stge Elec
Heat DD00= Trane Actuator Only ENCL= Shaft Only in Enclosure ENON= Shaft Out Side for Electric Units FM00= Other Actuator and Control FM01= Trane supplied actuator,
other control PN00= N.O. Actuator and Linkage Only PN05= N.O. 3000 Series, RA Stat PN51= Pneumatic normally open
w/3011,DPS fan PN52= Pneumatic normally open
w/3011, DPM fan PNON= Shaft Out Side for Pneumatic
Units N.C. = Normally-closed N.O. = Normally-opened DA Stat = Direct-acting pneumatic t-stat
(by others)
RA Stat = Reverse-acting pneumatic
t-stat (by others) PN = Pneumatic FM = Factory installation of customer-
supplied controller PVR = Pneumatic Volume Regulator
Digit 16—Insulation
A = 1/2” Matte-faced B = 1" Matte-faced D = 1" Foil-faced F = 1" Double-wall G = 3/8” Closed-cell
Digit 17—MotorType
D = PSC Motor E = High-efficiency motor (ECM)
VAV-PRC012-EN 15
Model Number Descriptions
Digit 18—Motor Voltage
1 = 115/60/1 2 = 277/60/1 3 = 347/60/1 4 = 208/60/1 5 = 230/50/1
Digit 19—Outlet Connection
1 = Flanged 2 = Slip & Drive
Digit 20—Attenuator
0 = No Attenuator
W = With Attenuator
Digit 21—Water Coil
0 = None 1 = 1-Row–Plenum inlet installed RH 2 = 2-Row–Plenum inlet installed RH 3 = 1-Row–Discharge installed, LH 4 = 1-Row–Discharge installed, RH 5 = 2-Row–Discharge installed, LH 6 = 2-Row–Discharge installed, RH1
A = 1-Row–Premium water coil inlet
B = 2-Row–Premium water coil inlet C = 1-Row–Premium hot coil
on discharge, LH
D = 1-Row–Premium hot coil
on discharge, RH
E = 2-Row–Premium hot coil
on discharge, LH
F = 2-Row–Premium hot coil
on discharge, RH
Note: 1- and 2-row not available with
Low-Height
Digit 22—Electrical Connections
L = Left (Airflow hitting you in the
face)
R = Right (Airflow hitting you in the
face)
W = Narrow Corridor LH, Hi-Volt Inlet
Facing
X = Narrow Corridor RH, Hi-Volt Inlet
Facing
Note: (W & X) Fan Powered Series Only
Digit 23—Transformer
0 = N/A (provided as standard)
Digit 24—Disconnect Switch
0 = None
W = With
Electric Reheat w/ door interlocking power disconnect, Cooling Only and
Water Reheat w/ toggle disconnect
Digit 25—Power Fuse
0 = None
W = With
Digit 26—Electric Heat Voltage
0 = None A = 208/60/1 B = 208/60/3 C = 240/60/1 D = 277/60/1 E = 480/60/1 F = 480/60/3 G = 347/60/1 H = 575/60/3 J = 380/50/3 K = 120/60/1
Note: K not available with Low Height
Digit 27, 28, 29—Electric Heat kW
000 = None 050 = 0.5 kW 010 = 1.0 kW 015 = 1.5 kW 260 = 26.0 kW
Note: Electric Heat Voltage -
0.5 to 8.0 kW–½ kW increments
8.0 to 18.0 kW –1 kW increments
18.0 to 46.0 kW–2 kW increments
Digit 30—Electric Heat Stages
0 = None 1 = 1 Stage 2 = 2 Stages Equal 3 = 3 Stages Equal
Note: 3 not available with Low Height
Digit 31—Contactors
0 = None 1 = 24-volt magnetic 2 = 24-volt mercury 3 = PE with magnetic 4 = PE with mercury 5 = SCR heat UC400 6 = SCR heat FMTD/ENCL/DD00
Note: SCR cannot be selected with the
following configuration:
KW > 10, 208 volt 3 phase, Low
Height
KW > 22, 480 volt 3 phase, Low
Height
Voltage = 575 volt
Digit 32—Airflow Switch
0 = None W = With
Digit 33—Not Used
0 = N/A
Digit 34—Actuator
0 = Standard A = Belimo actuator
Digit 35—Wireless Sensors
0 = None 1 = Factory Mounted Wireless
Receiver (Sensor Assembly)
2 = Wireless Comm Interface
Modular FM
Note: All sensors selected in accessories
Digit 36—Pre-Wired Factory Solutions
0 = None 1 = Factory Mounted DTS 2 = HW Valve Harness 3 = Both DTS & HW Valve Harness
16 VAV-PRC012-EN

Selection Procedure

This section describes elements and process required to properly select fan-powered VAV
terminals, and includes a specificexamples. Selection procedure is iterativein naturewhich makes computer selection desirable. Selection of fan-powered VAV terminals involves four elements:
Air valve selection
Heating coil selection
Fan size and selection
Acoustics Note: Use the same procedures for selecting Low-Height Fan-Powered Units.

Air Valve Selection

Provided in the Performance Data—Air Pressure Requirements section of the catalog is the unit air pressure drop at varying airflows.To select an air valve, determine the airflow required at design cooling. Next, select an air valve diameter that will allow proper airflow modulation, (a velocity of 1600 – 2000 FPM is recommended). Keep in mind that modulation below 300 FPM is not recommended. Proper selection requires defining the minimum valve airflow (in either heating or cooling) and maintaining at least 300 FPM through the air valve.The minimum is typically set based on ventilation requirements. If zone ventilation does not come through the VAV unit, a minimum valve position can also be zero.

Heating Coil Selection

Supply Air Temperature
The first step required when selecting a heating coil is to determine the heating supply air
temperature to the space, calculated using the heat transfer equation. A recommended value is 90°F, although values between 85°F and 95°F are common. Discharge air temperatures that exceed 20 degrees above space temperature are not recommended for proper diffuser operation. Air temperature difference is defined as the heating supply air temperature to the space minus the winter room design temperature.The zone design heat loss rate is denoted by the letter Q. Supply air temperature to the space equals the leaving air temperature (LAT) for the terminal unit.
Coil Leaving Air Temperature
Once the terminal unit LAT is determined, the heating requirements for the coil can be calculated.
The leaving air temperature for the coil of a parallel fan-powered terminal unit varies based on the
type of unit installed heat being selected. Series unit leaving air temperatures do not vary because in each case the coil is located on the unit discharge.
Electric coil LAT equals terminal unitLATbecause the coil is located on the unit discharge.Hot water coils can be located on either the discharge or, for maximum system efficiency, the plenum inlet when located on the entering air side of the fan. Coil LAT is calculated using a mixing equation. Given the unitheating airflow and LAT, minimum primary airflow atits supplyair temperature,and the volume of heated plenum air, the leaving air temperature for the hot water coil can be determined (see the unit selection example that follows for more details).
Coil Entering Air Temperature
The entering air temperature (EAT) to the coil also varies based on the coil position on the unit for
parallel units.The unit heat is mounted on the discharge of a series unit.Therefore the EAT equals the temperature of blended primary and plenum air.
Parallel electric coils are mounted on the unit discharge. Hot water coils can be mounted on the discharge or on the plenum inlet. Plenum inlet mounting creates a more efficientVAV system.This is because the parallel fan is energized only when in heating mode, and thus, when in cooling mode, the water coil is not in the airstream.
The EAT for discharge mounted coils equals the temperature of blended primary air and plenum
air. For plenum inlet mounted water coils, the EAT equals the plenum air temperature.
VAV-PRC012-EN 17
Selection Procedure
Capacity Requirement
Once both coil EAT and LAT are determined, the heat transfer (Q) for the coil must be calculated using the heat transfer equation. For electric heat units, the Q value must be converted from Btu to kW for heater selection.The required kW should be compared to availability charts in the performance data section for the unit selected. For hot water heat units, reference the capacity charts in the performance data section for the required heat transfer Q and airflow to pick the appropriate coil.

Fan Size and Selection

Fan Airflow
Fan airflow is determined by calculating thedifference between the unitdesign heating airflowand minimum primary airflow.
Fan External Static Pressure
Fan external static pressure is the total resistance experienced by the fan, which may include downstream ductwork and diffusers, heating coils, and sound attenuators. As total airflow varies so will static pressure, making calculation of external static pressure dependent on unit type.
In many applications of parallel terminals,a minimumprimary airflow mustbe maintainedto meet ventilation requirements.This primary airflow contributes to the total resistance experienced by the fan and should be accounted for in all components downstream of the fan itself, including electric coils. Hot water coils positioned on the fan inlet are not affected by the additional primary airflow.The static pressure resistance experienced by the fan due to the hot water coil is based on fan airflow only, not the total heating airflow.
With series fan-powered terminal units, all airflowpasses through the fan. External static pressure
requirements are the sum of the individual component pressure retirements at the design airflow of the unit.

Acoustics

Fan Motor Type
The fan motor type that will be used for the unit will need to be known before fan selection can
begin.The ECM motor offers more efficient operation than the standard single-speed PSC motor and will use different fan curves. Because series fans operate in both heating and cooling mode, payback is typically 2–3 years for the premium ECM option. Refer to the Features and Benefits section to determine which motor is more appropriate for the unit
Selection
Once fan airflow and external static pressure are determined, reference the fan curves in the performance data section. Cross plot both airflow and external static pressure on each applicable graph. A selection between the minimum and maximum airflow ranges for the fan is required.
It is common to identify more than one fan that can meet the design requirements.Typically, selection begins with the smallest fan available to meet capacity. If this selection does not meet acoustical requirements, upsizing the fan andoperating it at aslower speed can be donefor quieter operation.
Air Valve Generated Noise
To determine the noise generated by the air valve, two pieces of information are required; design
airflow and design air pressure drop.The design air pressure drop is determined by taking the difference between design inlet and static pressure (the valve’s most over-pressurized condition) and external static pressure at design cooling flow.This represents a worst-case operating condition for the valve.
18 VAV-PRC012-EN
Fan Generated Noise
To determine fan noise levels, fan airflow, external static pressure and speed information is
required.
Evaluation Elements
For parallel fan-powered terminal units, the air valve and fan operation must be evaluated separately because these operations are not simultaneous. For Series fan-powered units, the air valve and fan are evaluated together because they have simultaneous operation. Access the appropriate acoustics table(s)of the catalog and determine the sound power and NC predictionfor both the discharge and radiated paths. It is important to understand that discharge air noise is generally not a concern with fan-powered terminals. Radiated noise from the unit casing typically dictates the noise level of the space. If the entire unit or any element of it is generating noise in excess of the NoiseCriteria requirements, thesize of theappropriate portion of theterminal should be increased. Because the selection procedure is iterative, care should be taken by the designer to confirm that the change in selection does not affect other elements of the unit or system design.

Selection Example—ParallelWith Hot Water Heat

Air Valve Selection
Design Cooling Airflow:1000 cfm Minimum Ventilation Airflow: 200 cfm Maximum Unit APD: 0.25 in. wg Choose 10" air valve Check – Is minimum airflow above 300 FPM? Guidelines, FPP 8) A 10" air valve is selected with unit pressure drop = 0.01 in. wg
Selection Procedure
Heating Coil Selection
Required Information: Zone design heat loss: 20000 Btu Unit heating airflow: 600 cfm
Winter room design temp.: 68ºF
Coil entering water temp.: 180ºF Minimum primary airflow: 200 cfm Fan Airflow: 400 cfm Plenum temperature: 70ºF Coil flow rate: 2 gpm Primary air temperature: 55ºF
Heat Transfer Equation (Btu)
Q = 1.085 x Cfm x DTemperature
For the heating zone, the temperature difference is the zone supply air temperature (SAT) minus the winter room design temperature.
18000 Btu = 1.085 x 600 x (SAT - 68ºF) SAT = 95.6ºF
Because the designer chose to maximize system efficiency by having the hot water coil on the plenum inlet, the unit supply air temperature is equal to the mix of the heated plenum air from the fan and the minimum primary airflow.
600 cfm x 95.6ºF = 200 cfm x 55ºF + (600 cfm - 200 cfm) x Coil LAT
Coil LAT = 116ºF
VAV-PRC012-EN 19
Selection Procedure
For the heating coil, the temperature difference is the calculated coil LAT minus the coil EAT (Plenum AirTemperature). CoilQ=1.085 x 400 x (116-70) = 19,964 Btu = 19.96 Mbh
Coil Performance Table
Selection: Size 02SQ fan, 1-row coil with 2 gpm =20.53 Mbh (at 400 cfm)
1-row coil with 2 gpm = 2.57 ftWPD
Fan Selection
Required Information:
Design airflow: 400 cfm Downstream static pressure at design airflow: 0.25 in. wg
Fan external static pressure equals downstream static pressure (ductwork and diffusers) plus coil static pressure.The coil static pressure that the fan experiences is at the fan airflow (400 cfm).The downstream static pressure the fan experiences is at fan airflow plus minimum primary airflow.
The sum of fan airflow and minimum primary airflow (600 cfm) is less than design airflow (1000
cfm) and therefore the 0.25 in. wg downstream static pressure at design airflow must be adjusted for the lower heating airflow.
Parallel Fan-Powered Unit with Water Coil (2 Options)
Plenum Inlet Mounted
Using Fan LawTwo:
Heating Downstream Static Pressure = (600/1000)2 x 0.25 = .09 in. wg
A size 02SQ fan has the capability to deliver approximately 650 cfm at 0.09 downstream static pressure. If an attenuator is required, use the attenuator air pressure drop tables to define additional fan static pressure.
Acoustics
Required Information:
Design inlet static press.: 1.0 in. wg NC criteria: NC-35
The selection is a VPWF Parallel Fan-poweredTerminal Unit, 10" primary, parallel fan size 02SQ,
with a 1-row hot water coil.
Determine the casing radiated noise level because it typically dictates the sound level (NC) of the space. With a parallel unit, two operating conditions must be considered, design cooling and design heating.
Discharge Mounted
20 VAV-PRC012-EN
Selection Procedure
Design Cooling (1000 cfm). Radiated valve typically sets the NC for parallel units incooling mode.
The closest tabulated condition (1100 cfm at 1.0 in. wg ISP) has an NC=31. (A more accurate
selection can be done viaTOPSS electronic selection program.):
Table 2. Selection Program Output (Radiated Valve):
Octave Band 2 3 4 5 6 7 NC
Sound Power 65 60 53 48 41 32 30
Design Heating (200 cfm valve, 400 cfm fan, 0.25 in. wg DSP). Radiated fan typically sets the NC for parallel units in heating mode.The closest cataloged condition (430 fan cfm , 0.25 in. wg DSP) has an NC=32. (A more accurate selection can be done viaTOPSS electronic selection program.)
Table 3. Selection Program Output (Radiated Fan):
Octave Band 2 3 4 5 6 7 NC
Sound Power 66 58 56 52 48 41 31
The predicted NC level for design cooling is NC-30 and for design heating is NC-31. If the catalog
path attenuation assumptions are acceptable, this unit meets all of the design requirements and the selection process is complete.
Computer Selection
The advent of personal computers has served to automate many processes that were previously
repetitive and time-consuming. One of those tasks is the proper scheduling, sizing, and selection of VAV terminal units.Trane has developed a computer program to perform these tasks.The software is called theTrane Official Product Selection System (TOPSS).
TheTOPSS program will take the input specifications and output the properly sizedVariTrane VAV
terminal unit along with the specific performance for that size unit.
The program has several required fields, denoted by red shading in theTOPSS screen, and many
other optional fields to meet the criteria you have. Required values include maximum and minimum airflows, control type, and model. If selecting models with reheat, you will be required to enter information to make that selection also.The user is given the option to look at all the information for one selection on one screen or as a schedule with the other VAV units on the job.
The user can select single-duct, dual-duct, and fan-poweredVAV boxes with the program, as well
as most otherTrane products, allowing you to select all yourTrane equipment with one software program.
The program will also calculate sound power datafor the selected terminal unit.The usercan enter
a maximum individual sound level for each octave bandor a maximum NC value.The program will calculate acoustical data subject to default or user supplied sound attenuation data.
Schedule View
The program has many time-saving features such as:
Copy/Paste from spreadsheets like Microsoft® Excel
Easily arranged fields to match your schedule
Time-saving templates to store default settings
The user can also export the Schedule View to Excel to modify and put into a CAD drawing as a
schedule.
Specific details regarding the program, its operation, and how to obtain a copy of it are available from your localTrane sales office.
VAV-PRC012-EN 21
Selection Procedure

Selection Example—Series With Hot Water Heat and ECM

Air Valve Selection
Required Information: Design cooling airflow: 1000 cfm
Minimum ventilation airflow: 200 cfm Maximum unit APD: 0.40 in. wg
A 10" air valve is selected.
Check–is minimum airflow above 300 FPM?
Answer–Yes. Minimum cfm allowable = 165 cfm. (See General Data—Valve/Controller Guidelines pp FPS 8).
The 03SQ fan will be used in this instance. By interpolating,
you can choose a 10" air valve with wide-open air pressure drop of 0.32 in. wg.
Heating Coil Selection
Required Information: Zone design heat loss: 30000 Btu
Design heating airflow: 1000 cfm
Winter room design temp.: 68ºF
Coil entering water temp.: 180ºF Minimum primary airflow: 200 cfm Plenum temperature: 70ºF Primary air temperature: 55ºF Coil flow rate: 2 gpm HeatTransfer Equation (Btu)Q=1.085 x Cfm x Temperature
For the heating zone, the temperature difference is the zone supply air temperature (SAT) minus the winter room design temperature.
30000 Btu = 1.085 x 1000 x (SAT-68°F) SAT = 96ºF
Because the hot water coil is on the unit discharge of a series fan-powered unit, the unit supply air temperature is equal to the coil LAT. Coil entering air temperature (EAT) is a mix of plenum air and the minimum primary airflow.
1000 cfm x Coil EAT = 200 cfm x 55ºF + (1000 cfm - 200 cfm) x 70ºF
Coil EAT = 67ºF
For the heating coil, the temperature difference is the calculated coil LAT minus the coil EAT (Plenum AirTemperature).
Coil Q =1.085 x 1000 x (96-70) = 31,465 Btu
On a series unitthe hot water coilis locatedon thedischarge, so the totalheating airflow, 1000 cfm, passes through the coil.
Coil Performance Table
Selection: Performance: Size 03SQ fan, 1-row coil at 2 gpm = 32.23 MBh 1-row Coil at 2 gpm= 0.83 ftWPD
Fan Selection
Required Information. Fan airflow: 1000 cfm
Downstream static pressure at design airflow: 0.25 in. wg
A size 03SQ fan can operateat upto 1150 cfm (1-row coil) or 1100 (2-row coil) and 0.25" downstream static pressure. Inlet and coil selections should be verified withTOPSS electronic selections.
22 VAV-PRC012-EN
Selection Procedure
If an attenuator is required, use attenuator air pressure drop tables to define additional fan static pressure.
Acoustics
Required Information. Design inlet static press: 0.75 in. wg
NC criteria (general office space): NC-40
The selection is aVSWF Series Fan-PoweredTerminal Unit, 10" primary, series fan size 03SQ, with
a 1-row hot water coil.
Determine the casing radiated noise level because it typically dictates the sound level (NC) of the space. With a series unit, the air valve and fan operate simultaneously, so the chart
for air valve and fan sound data must be consulted.
The results in the below table are for the acoustics value of a size 10" air valve with a size 03SQ fan.
The predicted NC level for design conditions is NC-38.
Octave Band 2 3 4 5 6 7 NC
Sound Power 70 65 63 61 59 59 38
Note: Ensure water coil acoustical impact is considered. For this example, the appurtenance effect
adds one (1) NC to fan-only radiated sound. Because this does not set NC for this selection, it can be overlooked.The addition of an attenuator (see same appurtenance effect tables reduces the NC four (4) points, resulting in a final selection NC = 30 (if required).
Note: Do not overlook the water coil impact on acoustics. A good rule of thumb is that it will add
1 to 2 NC to “fan only” radiated sound for most applications.
Computer Selection
The advent of personal computers has served to automate many processes that were previously
repetitive and time-consuming. One of those tasks is the proper scheduling, sizing, and selection of VAV terminal units.Trane has developed a computer program to perform these tasks.The software is called theTrane Official Product Selection System (TOPSS).
TheTOPSS program will take the input specifications and output the properly sizedVariTrane VAV
terminal unit along with the specific performance for that size unit.
The program has several required fields, denoted by red shading in theTOPSS screen, and many
other optional fields to meet the criteria you have. Required values include maximum and minimum airflows, control type, and model. If selecting models with reheat, you will be required to enter information to make that selection also.The user is given the option to look at all the information for one selection on one screen or as a schedule with the other VAV units on the job.
User can select single-duct, dual-duct, and fan-powered VAV boxes with the program, as well as most otherTrane products, allowing selection of allTrane equipment with one software program.
The program will also calculate sound power datafor the selected terminal unit.The usercan enter
a maximum individual sound level for each octave bandor a maximum NC value.The program will calculate acoustical data subject to default or user supplied sound attenuation data.
Schedule View
The program has many time-saving features such as:
Copy/Paste from spreadsheets like Microsoft® Excel
Easily arranged fields to match your schedule
Time-saving templates to store default settings User can also export Schedule View to Excel to modify and put into a CAD drawing as a schedule.
Specific details regarding program, its operation, and how to obtain a copy of it are available from your localTrane sales office.
VAV-PRC012-EN 23

Performance Data

Parallel Fan-PoweredTerminal Units

Table 4. Primary airflow control factory setting-I-P
Control Type
Direct Digital Control/ UCM
Pneumatic with
Volume
Regulator
Note: Maximum airflow must be greater than or equal to minimum airflow.
Size (in.)
5 6 8
10 12 14 16
5 6 8
10 12 14 16
Table 5. Primary airflow control factory settings – SI
Air Valve
Control Type
Direct Digital Control/ UCM
Pneumatic with
Volume
Regulator
Note: Maximum airflow must be greater than or equal to minimum airflow.
Air Valve Size (in.)
5 6 8
10 12 14 16
5 6 8
10 12 14 16
Maximum
Valve Cfm
350 500 900
1400 2000 3000 4000
350 500 900
1400 2000 2885 3785
Maximum Valve L/s
165 236 425
661
944 1416 1888
165
236
425
661
944 1362 1787
Maximum
Controller Cfm
40-350 60-500
105-900
165-1400 240-2000 320-3000 420-4000
63-350 73-500
134-900
215-1400 300-2000 408-2887 536-3789
Maximum
Controller L/s
19-165 28-236 50-425
77-661
111-944 151-1416 198-1888
30-165 35-236 63-425
102-661
141-944 193-1363 253-1788
Minimum
Controller Cfm
0, 40-350 0, 60-500
0, 105-900
0, 165-1400 0, 240-2000 0, 320-3000 0, 420-4000
0, 63-350 0, 73-500
0, 134-900
0, 215-1400 0, 300-2000 0, 408-2887 0, 536-3789
Minimum
Controller L/s
0, 19-350 0, 28-236 0, 50-425
0, 77-661
0, 111-944 0, 151-1416 0, 198-1888
0, 30-165 0, 35-236 0, 63-425
0, 102-661
0, 141-944 0, 193-1363 0, 253-1788
Constant Volume
Cfm
40-350 60-500
105-900
165-1400 240-2000 320-3000 420-4000
63-350 73-500
134-900
215-1400 300-2000 408-2887 536-3789
Constant
Volume L/s
19-350 28-236 50-425
77-661
111-944 151-1416 198-1888
30-165 35-236 63-425
102-661
141-944 193-1363 253-1788
Table 6. Unit air pressure drop – in. wg (I-P)
Fan/Inlet Size Airflow Cfm Cooling Only Fan/Inlet Size Airflow Cfm Cooling Only
02SQ-05
02SQ-06
Note: Unit pressure drops do not include hot water coil or attenuator pressure drops.
02SQ-08
40 150 250 350
60 200 350 500
105 350 600 900
0.01
0.03
0.08
0.17
0.01
0.05
0.17
0.35
0.01
0.03
0.09
0.21
04SQ-14
05SQ-10
05SQ-12
320 1200 2100 3000
165
550
950 1400
240
750 1350 2000
24 VAV-PRC012-EN
0.01
0.01
0.01
0.01
0.01
0.01
0.02
0.05
0.01
0.01
0.01
0.01
Performance Data
Table 6. Unit air pressure drop – in. wg (I-P) (continued)
Fan/Inlet Size Airflow Cfm Cooling Only Fan/Inlet Size Airflow Cfm Cooling Only
02SQ-10
03SQ-06
03SQ-08
03SQ-10
03SQ-12
04SQ-08
04SQ-10
04SQ-12
Note: Unit pressure drops do not include hot water coil or attenuator pressure drops.
165 550 950
1400
60 200 350 500
105 350 600 900
165 550 950
1400
240 750
1350 2000
105 350 600 900
165 550 950
1400
240 750
1350 2000
0.01
0.01
0.01
0.01
0.01
0.06
0.19
0.40
0.01
0.03
0.08
0.20
0.01
0.01
0.02
0.05
0.01
0.01
0.01
0.01
0.01
0.03
0.08
0.20
0.01
0.01
0.02
0.05
0.01
0.01
0.01
0.01
05SQ-14
06SQ-10
06SQ-12
06SQ-14
06SQ-16
07SQ-10
07SQ-12
07SQ-14
07SQ-16
320 1200 2100 3000
165
550
950 1400
240
750 1350 2000
320 1200 2100 3000
420 1600 2800 4000
165
550
950 1400
240
750 1350 2000
320 1200 2100 3000
420 1600 2800 4000
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
Table 7. Coil air pressure drop – in. wg (I-P)
Fan Size Airflow Cfm 1-Row HW (in. wg) 2-Row HW (in. wg)
02SQ
03SQ 04SQ 05SQ
06SQ 07SQ
Note: HW Coil Only pressure drops do not include unit pressure drop.
100 200 300 400 500
250 500
750 1000 1250 1400
600
900 1200 1500 1800 2000
0.00
0.01
0.01
0.02
0.02
0.01
0.02
0.04
0.07
0.10
0.12
0.02
0.04
0.06
0.09
0.12
0.15
VAV-PRC012-EN 25
0.00
0.01
0.02
0.03
0.05
0.02
0.04
0.08
0.13
0.19
0.23
0.04
0.07
0.11
0.16
0.22
0.27
Performance Data
Table 8. Attenuator air pressure drop (I-P)
Fan Size Plenum Cfm Attenuator Fan Size Plenum Cfm Attenuator
02SQ
03SQ
04SQ
Note: Plenum cfm = (Fan cfm)
50 200 350 500 650 750
50 250 500 750
1000 1200
50 300 600 900
1200 1450
0.00
0.00
0.01
0.02
0.04
0.06
0.00
0.00
0.00
0.00
0.01
0.06
0.00
0.01
0.02
0.03
0.05
0.06
05SQ
06SQ
07SQ
50 300 600 900
1200 1550
50 500 900
1300 1650 1900
50 500
1000 1500 2000 2500
0.00
0.00
0.02
0.06
0.13
0.24
0.00
0.01
0.03
0.06
0.10
0.14
0.00
0.01
0.04
0.08
0.15
0.25
Table 9. Attenuator air pressure drop (SI)
Fan Size Plenum L/s Attenuator Fan Size Plenum L/s Attenuator
02SQ
03SQ
04SQ
Note: Plenum cfm = (Fan cfm)
24
94 165 236 307 354
24 118 236 354 472 566
24 142 283 425 566 684
10 14
14
11 14
0 0 2 5
0 0 0 0 2
0 3 5 8
05SQ
06SQ
07SQ
24 142 283 425 566 731
24 236 425 613 779 897
24 236 472 708 944
1180
0 1
5 15 32 61
0
2
7 15 26 35
0
2
9 21 38 62
Table 10. Coil air pressure drop – Pa (SI)
Fan Size Airflow L/s 1-Row HW (Pa) 2-Row HW (Pa)
02SQ
03SQ 04SQ 05SQ
200 300 400 500 600
118 236 354 472 590 661
0 1 2 4 6
2
5 10 17 25 31
26 VAV-PRC012-EN
1 3 5 8
12
4 11 21 33 47 57
Performance Data
Table 10. Coil air pressure drop – Pa (SI)
06SQ 07SQ
Note: HW Coil Only pressure drops do not include unit pressure drop.
900 1200 1500 1800 2150 2500
5
9 15 22 30 36
Table 11. Unit air pressure drop-Pa (SI)
Fan/Inlet Size Airflow L/s Cooling Only Fan/Inlet Size Airflow L/s Cooling Only
19
02SQ-05
02SQ-06
02SQ-08
02SQ-10
03SQ-06
03SQ-08
03SQ-10
03SQ-12
04SQ-08
04SQ-10
04SQ-12
Note: Unit pressure drops do not include hot water coil or attenuator pressure drops.
71 118 165
28
94 165 236
50 165 283 425
78 260 448 661
28
94 165 236
50 165 283 425
78 260 448 661
113 354 637 944
50 165 283 425
78 260 448 661
113 354 637 944
2
7 20 41
2 13 41 86
2
8 23 51
2
2
2
3
2 15 48 99
2
6 21 49
2
2
6 13
2
2
2
2
2
6 21 49
2
2
6 13
2
2
2
2
04SQ-14
05SQ-10
05SQ-12
05SQ-14
06SQ-10
06SQ-12
06SQ-14
06SQ-16
07SQ-10
07SQ-12
07SQ-14
07SQ-16
151 566 991
1416
78 260 448 661
113 354 637 944
151 566 991
1416
78 260 448 661
113 354 637 944
151 566 991
1416
198 755
1321 1888
78 260 448 661
113 354 637 944
151 566 991
1416
198 755
1321 1888
10 18 28 41 56 67
2 2 2 2
2 2 6
13
2 2 2 2
2 2 2 2
2 2 2 2
2 2 2 2
2 2 2 2
2 2 2 2
2 2 2 2
2 2 2 2
2 2 2 2
2 2 2 2
VAV-PRC012-EN 27
Performance Data
VPCF and VPEF maximum
Minimum
1-row coil maximum
2-row coil maximum
Note: When attenuator is required, add inlet
attenuator pressure to discharge static pressure for final fan performance.
Pa In. wg
0.60
150
0.50
125
0.40
100
0.30
75
Discharge Static Pressure
0.20
50
0.10
25
Pa In. wg
0.80
199
0.70
174
0.60
150
0.50
125
0.40
100
0.30
75
0.20
50
Discharge Static Pressure
0.10
25
200 300 400 500
94 142 189 236
100
47
(57 L/s)
120 cfm min
(118 L/s)
250 cfm min
Parallel 02SQ—PSC
200 300 400
94
142
189 236
Airflow
Parallel Fan Size 03SQ—PSC
700
600
330
283
Airflow
800
378
900
425
500
1000
472
1100
519
1200
566
700600
Cfm
330283
L/s
1300
Cfm
614
L/s
Pa
In. wg
199
0.80
174
0.70
150
0.60
125
0.50
0.40
100
0.30
75
Discharge Static Pressure
0.20
50
0.10
25
200 400 600 800 1000 1200 1400 1600
300 cfm min
94
(142 L/s)
189
Parallel 04SQ—PSC
283
378 472 566
661
755
Cfm
L/s
Airflow
28 VAV-PRC012-EN
Performance Data
VPCF and VPEF maximum
Minimum
1-row coil maximum
2-row coil maximum
Note: When attenuator is required, add inlet
attenuator pressure to discharge static pressure for final fan performance.
Pa In. wg
0.80
199
174
0.70
0.60
150
125
0.50
0.40
100
75
0.30
Discharge Static Pressure
50
0.20
0.10
25
Pa In. wg
199
0.80
0.70
174
150
0.60
0.50
125
0.40
100
0.30
75
Discharge Static Pressure
50
0.20
(165 L/s)
350 cfm min
300 500 700 900 1100 1300 1500 1700
142
236 330
(250 L/s)
530 cfm min
Parallel 05SQ—PSC
425
519
Airflow
Parallel 06SQ—PSC
614
708
802
Cfm
L/s
25
0.10 400
600 800 1000
283
189
378
1200
566 850
1600 1800 2000 2200
1400
755661472
944
1038
Cfm
L/s
Airflow
Pa In. wg
0.80
199
0.70
174
0.60
150
(276 L/s)
0.50
125
0.40
100
0.30
75
Discharge Static Pressure
0.20
50
25
0.10
585 cfm min
500 700 900 1100
236
425330
Parallel 07SQ—PSC
1300
519
1500 1700
708 897 1086
1900 2100
2300
991802614
Cfm
L/s
Airflow
VAV-PRC012-EN 29
Performance Data
VPCF and VPEF maximum
Minimum
1-row coil maximum
2-row coil maximum
Notes:
1. ECMs (Electrically Commutated Motors) are ideal for systems seeking maximum motor efficiency.
2. When attenuator is required, add inlet attenuator pressure to discharge static pressure for final fan performance.
Pa In. wg
125
0.50
0.40
100
(76 L/s)
0.30
75
0.20
50
Discharge Static Pressure
25
0.10
Pa In. wg
0.50
125
0.40
100
0.30
75
0.20
50
Discharge Static Pressure
0.10
25
160 cfm min
100 200 300 400 500 600 700 800 900 1000 1100
47
220 cfm min
200 400 600 800 1000 1200 1400 1600
94 189 283
142
(104 L/s)
VPxF 03SQ—ECM
236 330 425 47294 189
283 378 519
Airflow
VPxF 04SQ—ECM
Airflow
Cfm
L/s
661566472378
755
Cfm
L/s
Pa In. wg
0.50
125
0.40
100
0.30
75
50
0.20
Discharge Static Pressure
25
0.10
(132 L/s)
280 cfm min
200 400 600 800 1000 1200 1400 1800 2000
94 189
283 850
VPxF 05SQ—ECM
1600
661566472378
755
944
Cfm
L/s
Airflow
30 VAV-PRC012-EN
Performance Data
VPCF and VPEF maximum
Minimum
1-row coil maximum
2-row coil maximum
Notes:
1. ECMs (Electrically Commutated Motors) are ideal for systems seeking maximum motor efficiency.
2. When attenuator is required, add inlet attenuator pressure to discharge static pressure for final fan performance.
Table 12. Heating capacity (MBh) - fan size 02SQ (I-P)
Rows Gpm
0.5
1-Row
Capacity
MBH
2-Row
Capacity
MBH
Notes:
1. Fouling Factor = 0.0005 °F ft² h/Btu.
2. Capacity based on 70°F entering air temperature and 180°F entering water temperature.
1.0
2.0
3.0
4.0
5.0
1.0
2.0
3.0
4.0
5.0
Pa In. wg
125
0.50
0.40
100
75
0.30
Discharge Static Pressure
0.20
50
25
0.10 400 600 800 1000 1200 1400 1600 1800 2000 2200
189
189
Water Pressure Drop (ft)
100 150 200 250 300 350 400 450 500 550 600
0.22
0.76
2.65
5.54
9.39
14.17
1.30
4.41
9.08
15.18
22.66
9.20
9.79
10.01
10.12
10.19
9.97
10.29
10.40
10.45
10.48
-
(250 L/s)
530 cfm min
-
11.49
12.50
12.87
13.07
13.19
13.83
14.58
14.83
14.95
15.03
-
13.14
14.52
15.04
15.32
15.49
17.07
18.39
18.83
19.05
19.18
VPxF 06SQ—ECM
Airflow
Airflow (Cfm)
-
-
15.56
14.45
17.60
16.17
18.39
16.84
18.82
17.19
19.09
17.41
22.13
19.81
24.82
21.78
25.76
22.46
26.23
22.80
26.52
23.00
-
16.52
18.87
19.79
20.29
20.60
24.13
27.56
28.77
29.40
29.78
850755661566472378283
-
17.38
20.02
21.07
21.64
22.00
25.85
30.03
31.54
32.32
32.80
944 1038
-
18.16
21.09
22.26
22.90
23.30
27.35
32.27
34.09
35.04
35.62
-
18.93
22.08
23.38
24.09
24.54
28.67
34.31
36.45
37.56
38.25
Cfm
L/s
-
19.64
23.02
24.44
25.22
25.71
29.83
36.18
38.63
39.92
40.72
-
20.30
23.90
25.44
26.29
26.83
30.86
37.90
40.67
42.13
43.03
VAV-PRC012-EN 31
Performance Data
Table 13. Heating capacity (MBh) - fan sizes 03SQ–05SQ (I-P)
Water
Airflow (Cfm)
Pressure
Rows Gpm
1-Row
Capacity
MBH
2-Row
Capacity
MBH
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
Drop (ft)
0.28
1.02
2.22
3.85
5.92
8.41
11.32
14.65
18.40
22.57
0.35
1.28
2.74
4.72
7.20
10.18
13.64
17.59
22.03
26.94
150 300 450 600 750 900 1050 1200 1350 1500 1650
-
-
-
-
-
13.14
13.62
13.88
14.04
14.14
14.22
14.28
14.33
14.37
-
15.08
15.36
15.50
15.59
15.64
15.68
15.71
15.74
15.76
18.63
19.69
20.27
20.64
20.89
21.08
21.22
21.33
21.42
-
25.87
27.00
27.57
27.92
28.15
28.31
28.44
28.54
28.62
22.21
23.78
24.65
25.21
25.59
25.88
26.10
26.28
26.42
-
33.70
35.94
37.11
37.83
38.31
38.66
38.93
39.13
39.30
25.01
27.05
28.20
28.95
29.46
29.85
30.15
30.38
30.57
-
39.58
42.99
44.82
45.97
46.74
47.31
47.74
48.08
48.35
27.36
29.86
31.28
32.21
32.85
33.34
33.71
34.01
34.25
44.13
48.69
51.20
52.78
53.87
54.67
55.28
55.76
56.15
-
29.41
32.34
34.03
35.14
35.92
36.50
36.95
37.31
37.60
-
-
47.77
53.40
56.57
58.59
59.99
61.02
61.81
62.44
62.95
Table 14. Heating capacity (MBh) - fan sizes 06SQ & 07SQ (I-P)
Rows Gpm
1-Row
Capacity
MBH
2-Row
Capacity
MBH
0.5
1.0
2.0
3.0
4.0
5.0
6.0
7.0
1.0
2.0
3.0
4.0
5.0
6.0
7.0
Water Pressure Drop (ft)
0.11
0.36
1.24
2.57
4.32
6.49
9.04
11.99
0.68
2.24
4.57
7.59
11.29
15.64
20.61
900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900
-
-
-
-
32.17
35.12
36.78
37.86
38.61
39.17
-
51.03
56.65
59.73
61.67
63.00
63.97
33.60
36.76
38.60
39.79
40.63
41.25
53.38
59.74
63.27
65.51
67.05
68.18
-
-
-
34.93
38.31
40.32
41.63
42.55
43.23
-
55.46
62.53
66.50
69.04
70.79
72.07
36.17
39.77
41.95
43.38
44.38
45.13
57.32
65.06
69.46
72.28
74.24
75.69
-
-
37.34
41.16
43.51
45.05
46.14
46.95
-
58.98
67.37
72.18
75.29
77.45
79.05
Airflow (Cfm)
-
-
-
-
38.43
42.50
45.01
46.66
47.83
48.70
-
-
60.47
69.48
74.69
78.08
80.44
82.19
-
31.30
34.58
36.54
37.82
38.73
39.41
39.94
40.36
40.71
-
50.73
57.36
61.15
63.60
65.32
66.58
67.55
68.32
68.95
-
-
39.47
43.81
46.44
48.21
49.46
50.40
-
61.83
71.42
77.02
80.67
83.24
85.14
-
33.00
36.63
38.84
40.31
41.35
42.13
42.73
43.22
43.62
-
53.20
60.74
65.13
67.99
70.00
71.49
72.64
73.55
74.30
-
-
40.45
45.07
47.82
49.70
51.04
52.04
-
63.07
73.20
79.18
83.09
85.86
87.90
-
34.54
38.52
40.98
42.62
43.80
44.67
45.36
45.91
46.36
-
55.29
63.66
68.60
71.85
74.15
75.86
77.19
78.24
79.10
-
-
41.38
46.27
49.14
51.14
52.56
53.62
-
64.20
74.86
81.19
85.36
88.31
90.51
-
35.94
40.31
42.99
44.80
46.10
47.08
47.85
48.46
48.97
-
57.08
66.21
71.68
75.30
77.87
79.80
81.29
82.48
83.45
-
-
42.27
47.42
50.42
52.53
54.04
55.16
-
65.24
76.40
83.08
87.50
90.63
92.96
-
37.23
41.99
44.86
46.85
48.28
49.36
50.21
50.89
51.45
-
58.63
68.46
74.42
78.39
81.23
83.36
85.01
86.33
87.42
-
-
43.12
48.53
51.68
53.88
55.47
56.66
-
66.20
77.83
84.84
89.50
92.81
95.28

Water Coil Performance Notes (I-P)

1. Fouling Factor = 0.0005.
2. The off-coil temperature of the hot water coil on parallel fan-powered units must not exceed 140°F when mounted on plenum inlet.
3. The following equations may be used in calculating Leaving AirTemperature (LAT) and Water
Temperature Difference (WTD).
MB H 921.7
AT EAT
WTD EWT LWT
32 VAV-PRC012-EN

------------------------------------- -
+=

Cfm
2MBH

------------------------
==

Gpm
Performance Data
4. Capacity based on 70°F entering air temperature and 180°F entering water temperature. Refer to correction factors for different entering conditions.
5. For premium coils (.020” wall), water side pressure drop increases 17% and water velocity increases 7% for fixed GPM.
Table 15. Temperature correction factors for water pressure drop (ft)
Average Water Temperature Correction Factor
Table 16. Temperature correction factors for coil capacity (MBH)
Entering Water Minus Entering Air Correction Factor
Table 17. Heating capacity (kW) - fan size 02SQ (SI)
Water
Pressure
Rows L/s
1-Row
Capacity
kW
2-Row
Capacity
kW
0.03
0.06
0.13
0.19
0.25
0.32
0.06
0.13
0.19
0.25
0.32
Drop
(kPa)
0.66
2.26
7.91
16.57
28.08
42.34
3.89
13.19
27.13
45.38
67.73
200
0.970
190
180
170
160
0.985
1.000
1.020
1.030
40
0.355500.446600.537700.629800.722900.814
150
1.050
140
1.080
100
0.907
130
1.100
110
1.000
120
1.130
120
1.093
110
1.150
1.187
Airflow (L/s)
47 71 94 118 142 165 189 212 236 260 283
-
-
-
-
-
-
-
-
-
-
2.69
2.87
2.93
2.97
2.99
2.92
3.02
3.05
3.06
3.07
3.37
3.66
3.77
3.83
3.87
4.05
4.27
4.35
4.38
4.40
3.85
4.26
4.41
4.49
4.54
5.00
5.39
5.52
5.58
5.62
4.24
4.74
4.93
5.04
5.10
5.80
6.38
6.58
6.68
6.74
4.56
5.16
5.39
5.52
5.59
6.49
7.27
7.55
7.69
7.77
4.84
5.53
5.80
5.95
6.04
7.07
8.08
8.43
8.62
8.73
5.09
5.87
6.18
6.34
6.45
7.58
8.80
9.24
9.47
9.61
5.32
6.18
6.52
6.71
6.83
8.02
9.46
9.99
10.27
10.44
5.55
6.47
6.85
7.06
7.19
8.40
10.06
10.68
11.01
11.21
10.60
11.32
11.70
11.93
5.76
6.75
7.16
7.39
7.53
8.74
5.76
6.75
7.16
7.39
7.53
8.74
10.60
11.32
11.70
11.93
130
-
Table 18. Heating capacity (kW) - fan sizes 03SQ–05SQ (SI)
Water
Pressure
Rows L/s
1-Row
Capacity
kW
2-Row
Capacity
kW
0.06
0.13
0.19
0.25
0.32
0.38
0.44
0.50
0.57
0.63
0.06
0.13
0.19
0.25
0.32
0.38
0.44
0.50
0.57
0.63
Drop (kPa)
0.82
3.06
6.63
11.51
17.68
25.13
33.83
43.79
55.00
67.45
1.06
3.83
8.20
14.11
21.52
30.42
40.78
52.59
65.84
80.52
71 142 212 283 354 425 495 566 637 708 779
-
-
-
-
3.85
3.99
4.07
4.11
4.15
4.17
4.19
4.20
4.21
-
4.42
4.50
4.54
4.57
4.58
4.60
4.61
4.61
4.62
5.46
5.77
5.94
6.05
6.12
6.18
6.22
6.25
6.28
-
7.58
7.91
8.08
8.18
8.25
8.30
8.33
8.36
8.39
6.51
6.97
7.22
7.39
7.50
7.58
7.65
7.70
7.74
-
9.88
10.53
10.88
11.09
11.23
11.33
11.41
11.47
11.52
7.33
7.93
8.27
8.48
8.64
8.75
8.83
8.90
8.96
-
11.60
12.60
13.14
13.47
13.70
13.87
13.99
14.09
14.17
VAV-PRC012-EN 33
Airflow (L/s)
-
8.62
8.02
9.48
8.75
9.97
9.17
10.30
9.44
10.53
9.63
10.70
9.77
10.83
9.88
10.93
9.97
11.02
10.04
-
14.00
12.93
15.65
14.27
16.58
15.01
17.17
15.47
17.58
15.79
17.88
16.02
18.12
16.20
18.30
16.34
18.45
16.45
-
9.17
10.14
10.71
11.08
11.35
11.55
11.71
11.83
11.93
-
-
14.87
16.81
17.92
18.64
19.14
19.51
19.80
20.02
20.21
9.67
10.74
11.38
11.81
12.12
12.35
12.52
12.67
12.78
-
15.59
17.80
19.09
19.92
20.51
20.95
21.29
21.56
21.77
10.12
11.29
12.01
12.49
12.84
13.09
13.29
13.46
13.59
-
16.20
18.66
20.11
21.06
21.73
22.23
22.62
22.93
23.18
10.53
11.81
12.60
13.13
13.51
13.80
14.02
14.20
14.35
-
16.73
19.40
21.01
22.07
22.82
23.39
23.82
24.17
24.46
10.53
11.81
12.60
13.13
13.51
13.80
14.02
14.20
14.35
-
16.73
19.40
21.01
22.07
22.82
23.39
23.82
24.17
24.46
-
-
-
-
-
Performance Data
Table 19. Heating capacity (kW) - fan sizes 06SQ & 07SQ (SI)
Water
Pressure
Rows L/s
0.03
0.06
kW
kW
0.13
0.19
0.25
0.32
0.38
0.44
0.06
0.13
0.19
0.25
0.32
0.38
0.44
1-Row
Capacity
2-Row
Capacity
Drop
(kPa)
0.33
1.09
3.71
7.68
12.92
19.39
27.04
35.84
2.02
6.70
13.65
22.70
33.76
46.74
61.61

Water Coil Performance Notes (SI)

1. Fouling Factor = 0.0005.
2. The off-coil temperature of the hot water coil on parallel fan-powered units must not exceed 60°C when mounted on plenum inlet.
3. The following equations may be used in calculating Leaving AirTemperature (LAT) and Water
Temperature Difference (WTD).
kW 0.83
AT EAT
WTD=EWT-LWT=kW/(4.19) L/s
4. Capacity based on 21°C entering air temperature and 82°C entering water temperature. Refer to correction factors for different entering conditions.
5. For premium coils (.020” wall), water side pressure drop increases 17% and water velocity increases 7% for fixed GPM.

-----------------------------
+=

Ls
Airflow (L/s)
425 472 519 566 613 661 708 755 802 849 897
-
-
-
9.43
10.29
10.78
11.10
11.32
11.48
-
14.96
16.60
17.51
18.07
18.46
18.75
-
-
9.85
10.77
11.31
11.66
11.91
12.09
-
15.64
17.51
18.54
19.20
19.65
19.98
10.24
11.23
11.82
12.20
12.47
12.67
16.25
18.33
19.49
20.23
20.75
21.12
-
-
-
-
-
-
-
-
-
-
-
10.60
10.94
11.26
11.66
12.06
12.30
12.75
12.71
13.20
13.01
13.52
13.23
13.76
-
-
-
16.80
19.07
20.36
21.18
21.76
22.18
17.28
19.74
21.15
22.06
22.70
23.17
12.46
13.19
13.67
14.02
14.27
-
17.72
20.36
21.89
22.88
23.58
24.09
11.57
12.84
13.61
14.13
14.50
14.77
18.12
20.93
22.57
23.64
24.39
24.95
-
11.86
12.13
13.21
13.56
14.01
14.40
14.57
14.99
14.96
15.40
15.25
15.72
-
-
18.48
21.45
23.20
24.35
25.16
25.76
18.82
21.94
23.80
25.02
25.88
26.52
-
-
-
12.39
12.39
13.90
13.90
14.78
14.78
15.40
15.40
15.84
15.84
16.17
16.17
-
-
19.12
22.39
24.35
25.64
26.56
27.24
19.12
22.39
24.35
25.64
26.56
27.24
-
-
-
Table 20. Temperature correction factors for water pressure drop (kPa)
Average Water Temperature Correction Factor
93
0.970880.985821.000771.020711.030661.050601.080541.100491.130431.150
Table 21. Temperature correction factors for coil capacity (kW)
Entering Water Minus Entering Air Correction Factor
34 VAV-PRC012-EN
22
0.355270.446330.537380.629440.722500.814550.907611.000671.093721.187

Series Fan-PoweredTerminal Units

Table 22. Primary airflow control factory settings – I-P
Control Type
Direct Digital Control/UCM
Pneumatic with
Volume Regulator
Note: Maximum airflow must be greater than or equal to minimum airflow.
(in.)
4 5 6 8
10 12 14 16
4 5 6 8
10 12 14 16
Air Valve Size
Maximum Valve Cfm
225 350 500 900
1400 2000 3000 4000
225 350 500 900
1400 2000 2885 3785
Maximum
Controller Cfm
25-225 40-350 60-500
105-900
165-1400 240-2000 320-3000 420-4000
38-225 63-350 73-500
134-900
215-1400 300-2000 408-2887 536-3789
Performance Data
Minimum
Controller Cfm
0, 25-225 0, 40-350 0, 60-500
0, 105-900
0, 165-1400 0, 240-2000 0, 320-3000 0, 420-4000
0, 38-225 0, 63-350 0, 73-500
0, 134-900
0, 215-1400 0, 300-2000 0, 408-2887 0, 536-3789
Constant
Volume Cfm
25-225 40-350 60-500
105-900
165-1400 240-2000 320-3000 420-4000
38-225 63-350 73-500
134-900
215-1400 300-2000 408-2887 536-3789
Table 23. Primary airflow control factory settings – SI
Control Type
Direct Digital
Control/UCM
Pneumatic with
Volume
Regulator
Note: Maximum airflow must be greater than or equal to minimum airflow.
(in.)
4 5 6 8
10 12 14 16
4 5 6 8
10 12 14 16
Air Valve Size
Maximum
Valve L/s
106 165 236 425
661
944 1416 1888
106
165
236
425
661
944 1362 1787
Maximum
Controller L/s
12-106 19-165 28-236 50-425
77-661
111-944 151-1416 198-1888
18-106 30-165 35-236 63-425
102-661
141-944 193-1363 253-1788
Minimum
Controller L/s
0, 12-106 0, 19-165 0, 28-236 0, 50-425
0, 77-661
0, 111-944 0, 151-1416 0, 198-1888
0, 18-106 0, 30-165 0, 35-236 0, 63-425
0, 102-661
0, 141-944 0, 193-1363 0, 253-1788
Constant
Volume L/s
12-106 19-165 28-236 50-425
77-661
111-944 151-1416 198-1888
18-106 30-165 35-236 63-425
102-661
141-944 193-1363 253-1788
VAV-PRC012-EN 35
Performance Data
Table 24. Unit air pressure drop – in. wg (I-P)
Fan/Inlet Size Airflow Cfm Unit Fan/Inlet Size Airflow Cfm Unit
2SQ-04
2SQ-05
2SQ-06
2SQ-08
2SQ-10
03SQ-06
03SQ-08
03SQ-10
03SQ-12
04SQ-06
200 225
200 250 300 350
200 300 400 500
200 400 550 700
200 400 550 700
250 300 400 500
250 500 700 900
250 550 850
1200
250 550 850
1200
330 400 450 500
0.03
0.03
0.03
0.04
0.06
0.09
0.03
0.06
0.12
0.19
0.01
0.05
0.10
0.16
0.01
0.02
0.06
0.11
0.10
0.15
0.34
0.45
0.05
0.16
0.31
0.49
0.03
0.11
0.24
0.44
0.01
0.07
0.16
0.32
0.16
0.29
0.35
0.48
04SQ-12
04SQ-14
05SQ-10
05SQ-12
05SQ-14
6SQ-10
6SQ-12
6SQ-14
6SQ-16
7SQ-10
330
750 1150 1550
330
750 1150 1550
400
750 1100 1400
400
900 1400 1900
400
900 1400 1900
700
950 1200 1400
700 1150 1600 2000
700 1350 2000 2600
700 1350 2000 2600
850 1000 1200 1400
0.02
0.11
0.28
0.51
0.02
0.11
0.26
0.48
0.01
0.08
0.22
0.39
0.01
0.09
0.28
0.58
0.01
0.09
0.26
0.53
0.01
0.03
0.12
0.22
0.01
0.01
0.12
0.27
0.01
0.04
0.19
0.41
0.01
0.04
0.19
0.41
0.01
0.05
0.12
0.22
Note: Unit pressure drops do not include hot water coil or attenuator pressure drops.
36 VAV-PRC012-EN
Performance Data
Table 24. Unit air pressure drop – in. wg (I-P) (continued)
Fan/Inlet Size Airflow Cfm Unit Fan/Inlet Size Airflow Cfm Unit
330
04SQ-08
500 700 900
330
04SQ-10
700 1050 1400
Note: Unit pressure drops do not include hot water coil or attenuator pressure drops.
0.04
0.12
0.25
0.44
0.02
0.12
0.29
0.54
Table 25. Coil air pressure drop – in. wg (I-P)
Fan
Airflow
Size
02SQ
03SQ 04SQ
Note: HW Coil Only pressure drops do not include unit pressure drop.
Cfm
200 300 400 500 600
250 500
750 1000 1250 1500
1-Row HW
(in. wg)
0.01
0.02
0.04
0.06
0.08
0.01
0.02
0.05
0.08
0.12
0.16
2-Row HW
(in. wg) Fan Size Airflow Cfm
0.03
0.05
0.08
0.11
0.15
0.02
0.05
0.10
0.15
0.22
0.30
7SQ-12
7SQ-14
7SQ-16
05SQ
06SQ 07SQ
400
700 1000 1250 1500 1750
600 1000 1500 2000 2500 3000
850 1200 1600 2000
850 1550 2250 3000
850 1550 2250 3000
1-Row HW
(in. wg)
0.01
0.04
0.07
0.10
0.14
0.19
0.02
0.04
0.08
0.13
0.19
0.27
0.01
0.02
0.12
0.27
0.01
0.07
0.27
0.59
0.01
0.07
0.27
0.59
2-Row HW
(in. wg)
0.03
0.08
0.13
0.19
0.26
0.34
0.04
0.08
0.15
0.23
0.34
0.47
Table 26. Attenuator air pressure drop (I-P)
Fan Size Plenum Cfm Attenuator Fan Size Plenum Cfm Attenuator
50
150
02SQ
03SQ
04SQ
Note: Plenum cfm = (Fan cfm) – (Min. valve cfm)
350 550 750 950
50 250 500 750
1000 1200
50 300 600 900
1200 1500
VAV-PRC012-EN 37
0.00
0.00
0.02
0.05
0.10
0.16
0.00
0.00
0.02
0.06
0.13
0.21
0.00
0.02
0.07
0.14
0.24
0.35
05SQ
06SQ
07SQ
50 300 650
1000 1300 1650
50 500 900
1300 1700 2100
50 800
1200 1600 2000 2400
0.00
0.01
0.05
0.14
0.28
0.52
0.00
0.00
0.02
0.07
0.17
0.36
0.00
0.01
0.05
0.14
0.30
0.58
Performance Data
Table 27. Attenuator air pressure drop (SI)
Fan Size Plenum L/s Attenuator Fan Size Plenum L/s Attenuator
24 71
02SQ
03SQ
04SQ
Note: Plenum cfm = (Fan cfm) – (Min. valve cfm)
165 260 354 448
24 118 236 354 472 566
24 142 283 425 566 708
0 1
4 12 24 40
0
1
5 15 32 52
0
5 18 36 59 88
05SQ
06SQ
07SQ
24 142 307 472 613 779
24 236 425 613 802 991
24 378 566 755 944
1133
0
2 12 36 70
129
0
1
4 16 42 90
0
3 12 34 75
144
Table 28. Coil air pressure drop – Pa (SI)
Fan
Size
02SQ
03SQ 04SQ
Note: HW coil only pressure drops do not include unit pressure drop.
Airflow
L/s
250 400 500 600 700
118 236 354 472 590 708
1-Row HW
(Pa)
3
6 10 14 20
2
6 12 19 29 40
2-Row HW
(Pa) Fan Size
7 12 19 28 38
5 13 24 38 55 75
Airflow L/s1-Row HW
189 330
05SQ
06SQ 07SQ
472 590 708 826
850 1300 1700 2150 2550 3000
(Pa)
4
9 17 25 35 47
4
9 19 31 47 66
2-Row HW
(Pa)
8 19 33 48 65 85
9 19 36 58 85
117
38 VAV-PRC012-EN
Performance Data
Table 29. Unit air pressure drop-Pa (SI)
Fan/Inlet Size Airflow Cfm Unit Fan/Inlet Size Airflow Cfm Unit
2SQ-04
2SQ-05
2SQ-06
2SQ-08
2SQ-10
03SQ-06
03SQ-08
03SQ-10
03SQ-12
04SQ-06
04SQ-08
04SQ-10
04SQ-12
Note: Unit pressure drops do not include hot water coil or attenuator pressure drops.
94
106
94 118 142 165
94 142 189 236
94 189 260 330
94 189 260 330
118 142 189 236
118 236 330 425
118 260 401 566
118 260 401 566
156 189 212 236
156 236 330 425
156 330 495 661
156 354 543 731
7 9
7 11 16 22
7 16 29 46
2 12 24 39
2
5 14 39
25 38 85
112
12 41 76
123
8 28 59
110
4 17 40 79
40 73 88
119
10 29 63
109
5 30 73
135
5 28 69
127
04SQ-14
05SQ-10
05SQ-12
05SQ-14
6SQ-10
6SQ-12
6SQ-14
6SQ-16
7SQ-10
7SQ-12
7SQ-14
7SQ-16
156 354 543 731
189 354 519 661
189 425 661 897
189 425 661 897
330 448 566 661
330 543 755 944
330 637 944
1227
330 637 944
1227
401 472 566 661
401 566 755 944
401
731 1062 1416
401
731 1062 1416
5 27 65
120
1 20 55 98
2 23 71
144
2 21 65
131
2
8 31 55
2
3 31 68
2
9 47
101
2
9 47
101
2 12
55
2
5 31 68
2 18 67
147
2 18 67
147
VAV-PRC012-EN 39
Performance Data
VSCF and VSEF maximum
Minimum
1-row coil maximum
2-row coil maximum
Note: When attenuator is required, add inlet
attenuator pressure to discharge static pressure for final fan performance.
Pa In. wg
0.60
150
0.50
125
0.40
100
0.30
75
0.20
50
Discharge Static Pressure
0.10
25
0.00
0
100 200 300 400 500 600 700 800
47 94 142 189 236
In. wg
Pa
199
0.80
0.70
174
0.60
150
125
0.50
100
0.40
250 cfm min
0.30
75
0.20
Discharge Static Pressure
50
0.10
25
0.00
0
200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400
94
142
(90 L/s)
190 cfm min
(118 L/s)
189
Series 02SQ—PSC
Airflow
Series 03SQ—PSC
236 283 330 378
Airflow
425
472
519
330283
566 614
661
378
Cfm
L/s
Cfm
L/s
Pa In. wg
0.80
199
0.70
174
150
0.60
125
0.50
100
75
Discharge Static Pressure
50
25
0
(156 L/s)
0.40
330 cfm min
0.30
0.20
0.10
0.00
300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700
142 189
236
283
Series 04SQ—PSC
330 378 425
472
Airflow
519
566
614
661
708
755
802
Cfm
L/s
40 VAV-PRC012-EN
Performance Data
VSCF and VSEF maximum
Minimum
1-row coil maximum
2-row coil maximum
Note: When attenuator is required, add inlet
attenuator pressure to discharge static pressure for final fan performance.
Pa
In. wg
0.80
199
174
0.70
0.60
150
0.50
125
(189 L/s)
100
75
50
Discharge Static Pressure
25
0
400 cfm min
0.40
0.30
0.20
0.10
0.00
300 500 700 900 1100 1300 1500 1700 1900 2100
236
142
330
Series 05SQ—PSC
425 519 614 708 802 897 991
Airflow
Pa In. wg
0.80
199
0.70
174
150
0.60
0.50
125
(330 L/s)
0.40
100
0.30
75
Discharge Static Pressure
0.20
50
0.10
25
0
0.00 400 600 800 1000 1200 1400 1600 1800 2000 2200 2400 2600 2800
189
700 cfm min
283 378 850 1322
Series 06SQ—PSC
944755661566472 122711331038
Airflow
Cfm
L/s
Cfm
L/s
Pa In. wg
0.80
199
0.70
174
0.60
150
125
0.50
100
75
50
Discharge Static Pressure
25
0.00
0
(401 L/s)
0.40
850 cfm min
0.30
0.20
0.10
800 1000 1200 1400 1600 1800 2000 2200 2400 2600 2800 3000 3200 3400
378
Series 07SQ—PSC
11331038944850755661566472
1227
1322
1605
Cfm
L/s
15101416
Airflow
VAV-PRC012-EN 41
Performance Data
VSCF and VSEF maximum
Minimum
1-row coil maximum
2-row coil maximum
Notes:
1. ECMs (Electrically Commutated Motors) are ideal for systems seeking maximum motor efficiency.
2. When attenuator is required, add inlet attenuator pressure to discharge static pressure for final fan performance.
Pa In. wg
0.50
125
100
0.40
0.30
75
50
Discharge Static Pressure
25
0
(94 L/s)
200 cfm min
0.20
0.10
0.00 100 200 300 400 500 600 700 800 900 1000 1100 1200
47 94
142
VSxF Size 03SQ—ECM
189 236
Airflow
Pa In. wg
0.50
125
100
0.40
0.30
75
(113 L/s)
240 cfm min
0.20
50
Discharge Static Pressure
0.10
25
0.00
0
200 400 600 800 1000 1200 1400 1600
94 189
VSxF 04SQ—ECM
566472378283
Airflow
661
Cfm
566519472425378330283
L/s
Cfm
755
L/s
Pa In. wg
125
0.50
0.40
100
0.30
75
(165 L/s)
350 cfm min
0.20
50
Discharge Static Pressure
0.10
25
0.00
0
300 500 700 900 1100 1300 1500 1700 1900 2100
142 236
VSxF 05SQ—ECM
614519425330
708
802
Cfm
991897
L/s
Airflow
42 VAV-PRC012-EN
Performance Data
Pa In. wg
125
0.50
0.40
VSCF and VSEF maximum
100
Minimum
0.30
1-row coil maximum
75
2-row coil maximum
0.20
Notes:
1. ECMs (Electrically Commutated Motors) are ideal for systems seeking maximum motor efficiency.
2. When attenuator is required, add inlet attenuator pressure to discharge static pressure for final fan performance.
50
Discharge Static Pressure
0.10
25
0.00
0
600 800 1,000 1,200 1,400 1,800 2,000 2,200 2,400 2,600
283 472
Table 30. Heating capacity (MBh) - fan size 02SQ (I-P)
Water
Pressure
Rows Gpm
1-Row
Capacity
MBH
2-Row
Capacity
MBH
0.50
1.0
2.0
3.0
4.0
5.0
1.0
2.0
3.0
4.0
5.0
Drop (ft)
0.16
0.53
1.85
3.85
6.51
9.79
1.00
3.42
7.05
11.82
17.68
150 200 250 300 350 400 450 500 550 600 700
-
9.14
9.94
10.25
10.41
10.51
12.59
13.42
13.71
13.86
13.94
-
10.34
11.40
11.80
12.02
12.15
15.23
16.60
17.08
17.33
17.48
-
11.34
12.63
13.14
13.41
13.58
17.40
19.34
20.04
20.40
20.62
-
12.20
13.73
14.34
14.66
14.87
19.21
21.73
22.66
23.14
23.44
Table 31. Heating capacity (MBh) - fan sizes 03SQ 04SQ (I-P)
Water
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
Pressure
Drop (ft)
0.27
1.01
2.19
3.81
5.85
8.32
11.20
14.50
18.22
22.35
0.39
1.41
3.01
5.16
7.84
11.06
14.81
19.07
200 300 400 550 700 850 1000 1150 1300 1450 1600
-
15.03
15.70
16.06
16.29
16.45
16.56
16.65
16.72
16.78
-
18.93
19.46
19.72
19.88
19.98
20.06
20.12
-
18.19
19.23
19.80
20.16
20.41
20.59
20.73
20.84
20.93
-
25.58
26.72
27.30
27.65
27.88
28.05
28.18
-
20.63
22.00
22.76
23.24
23.58
23.82
24.01
24.17
24.29
-
30.93
32.79
33.75
34.34
34.74
35.02
35.24
-
23.57
25.41
26.44
27.11
27.57
27.91
28.18
28.39
28.56
-
37.20
40.20
41.80
42.79
43.47
43.96
44.34
Rows Gpm
1-Row
Capacity
MBH
2-Row
Capacity
MBH
(330 L/s)
700 cfm min
Airflow (Cfm)
-
12.97
14.73
15.43
15.81
16.05
20.74
23.84
25.00
25.62
25.99
Airflow (Cfm)
-
26.00
28.29
29.59
30.43
31.02
31.46
31.80
32.08
32.30
-
41.99
46.12
48.38
49.81
50.79
51.50
52.05
-
13.67
15.66
16.45
16.89
17.17
22.06
25.71
27.12
27.86
28.32
-
28.09
30.81
32.38
33.40
34.12
34.66
35.07
35.41
35.68
-
45.78
50.97
53.88
55.73
57.01
57.96
58.68
VSxF 06SQ—ECM
1,600
661 944
566 1038850755 12271133378
Airflow
-
14.32
16.52
17.41
17.90
18.21
23.19
27.39
29.03
29.90
30.44
-
29.99
33.08
34.91
36.11
36.96
37.59
38.08
38.48
38.80
-
48.85
55.02
58.54
60.81
62.40
63.57
64.46
-
14.93
17.33
18.32
18.87
19.21
24.19
28.90
30.77
31.77
32.40
-
31.71
35.15
37.23
38.60
39.58
40.31
40.88
41.34
41.71
-
51.38
58.45
62.56
65.23
67.10
68.49
69.57
-
15.51
18.10
19.18
19.78
20.17
25.07
30.27
32.37
33.50
34.21
-
33.27
37.05
39.38
40.93
42.03
42.86
43.51
44.03
44.46
-
53.52
61.41
66.05
69.11
71.26
72.87
74.11
-
16.05
18.82
20.01
20.66
21.08
25.85
31.52
33.84
35.10
35.89
-
34.68
38.83
41.38
43.10
44.34
45.26
45.99
46.57
47.05
-
55.34
63.98
69.14
72.55
74.98
76.79
78.19
Cfm
L/s
-
17.02
20.18
21.56
22.32
22.81
27.19
33.72
36.46
37.96
38.92
-
35.97
40.51
43.26
45.15
46.51
47.54
48.34
48.99
49.52
-
56.92
66.24
71.88
75.63
78.31
80.32
81.88
VAV-PRC012-EN 43
Performance Data
Table 32. Heating capacity (MBh) - fan size 05SQ (I-P)
Water
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
0.5
1.0
2.0
3.0
4.0
5.0
6.0
1.0
2.0
3.0
4.0
5.0
6.0
Pressure Drop (ft)
0.29
1.08
2.33
4.03
6.18
8.76
11.79
15.24
0.39
1.39
2.96
5.08
7.72
10.90
14.59
18.79
Water Pressure Drop (ft)
0.12
0.40
1.37
2.83
4.76
7.13
9.93
0.77
2.58
5.27
8.78
13.07
18.13
350 500 650 800 1000 1200 1400 1600 1800 2000 2150
-
21.67
23.02
23.76
24.23
24.55
24.79
24.97
-
29.95
31.40
32.14
32.58
32.87
33.08
33.24
-
25.25
27.14
28.20
28.87
29.34
29.69
29.95
-
37.69
40.36
41.74
42.59
43.16
43.57
43.88
-
28.09
30.49
31.85
32.72
33.34
33.79
34.14
-
43.62
47.58
49.69
51.00
51.88
52.53
53.02
-
30.49
33.38
35.03
36.10
36.86
37.42
37.85
-
48.30
53.51
56.37
58.16
59.39
60.28
60.96
700 900 1100 1300 1500 1700 1900 2100 2300 2500 2700
-
-
31.21
33.81
35.27
36.20
36.85
-
47.79
52.10
54.37
55.77
56.71
-
-
34.50
37.76
39.61
40.80
41.64
-
54.01
60.08
63.38
65.44
66.85
-
-
37.47
41.19
43.42
44.87
45.90
-
58.79
66.51
70.82
73.55
75.43
-
-
40.06
44.25
46.86
48.57
49.78
-
62.56
71.79
77.06
80.45
82.80
Rows Gpm
1-Row
Capacity
MBH
2-Row
Capacity
MBH
Table 33. Heating capacity (MBh) - fan size 06SQ & 07SQ (I-P)
Rows Gpm
1-Row
Capacity
MBH
2-Row
Capacity
MBH
Airflow (Cfm)
-
33.30
36.75
38.78
40.11
41.05
41.75
42.29
-
53.17
59.95
63.77
66.21
67.90
69.14
70.09
Airflow (Cfm)
-
-
42.33
47.10
50.00
51.97
53.36
-
65.61
76.21
82.39
86.40
89.22
35.79
39.71
42.12
43.71
44.83
45.67
46.33
56.95
65.16
69.90
72.97
75.11
76.69
77.91
-
-
44.37
49.74
52.91
55.12
56.70
-
68.13
79.96
86.98
91.60
94.86
-
-
-
37.96
42.39
45.14
46.98
48.29
49.28
50.05
-
59.97
69.45
75.05
78.72
81.30
83.22
84.70
-
-
46.21
52.17
55.63
58.07
59.83
-
70.25
83.19
91.00
96.18
99.86
-
39.88
44.89
47.92
50.01
51.50
52.63
53.51
-
62.43
73.07
79.45
83.68
86.69
88.93
90.66
-
-
47.89
54.40
58.24
60.84
62.79
-
72.05
86.00
94.54
100.26
104.34
-
41.61
47.17
50.48
52.81
54.50
55.76
56.76
-
64.49
76.15
83.26
88.02
91.42
93.97
95.95
-
-
49.43
56.49
60.68
63.46
65.59
-
73.60
88.47
97.69
103.91
108.37
-
43.17
49.26
52.91
55.44
57.30
58.71
59.82
-
66.24
78.82
86.60
91.85
95.63
98.47
100.69
-
-
50.85
58.43
62.97
66.00
68.24
-
74.95
90.65
100.51
107.20
112.03
-
44.25
50.73
54.64
57.30
59.30
60.82
62.01
-
67.38
80.59
88.84
94.45
98.49
101.54
103.93
-
-
52.16
60.24
65.14
68.41
70.77
-
76.14
92.61
103.06
110.19
115.36

Water Coil Notes (I-P)

1. Fouling Factor = 0.0005.
2. The following equations may be used in calculating Leaving AirTemperature (LAT) and Water Temperature Difference (WTD):
MB H x921.7
AT EAT
WTD EWT LWT
3. Capacity based on 70°F entering air temperature and 180°F entering water temperature. Refer
to correction factors for different entering conditions.
Table 34. Temperature correction factors for water pressure drop (ft)
Average Water Temperature Correction Factor
44 VAV-PRC012-EN
------------------------------------
+=
Cfm
2MBH

------------------------
==

Gpm
200
0.970
190
0.985
180
1.000
170
1.020
160
1.030
150
1.050
140
1.080
130
1.100
120
1.130
110
1.150
Table 35. Temperature correction factors for coil capacity (MBH)
Entering Water Minus Entering Air Correction Factor
0.355500.446600.537700.629800.722900.814
Table 36. Heating capacity (kW) - fan size 02SQ (SI)
Water
Pressure
Rows L/s
1-Row
Capacity kW
2-Row
Capacity kW
0.03
0.06
0.13
0.19
0.25
0.32
0.06
0.13
0.19
0.25
0.32
Drop (kPa)
0.47
1.59
5.52
11.51
19.45
29.27
3.00
10.21
21.07
35.33
52.84
71 94 118 142 165 189 212 236 260 283 330
-
2.68
2.91
3.00
3.05
3.08
3.69
3.93
4.02
4.06
4.09
-
3.03
3.34
3.46
3.52
3.56
4.46
4.86
5.01
5.08
5.12
-
3.32
3.70
3.85
3.93
3.98
5.10
5.67
5.87
5.98
6.04
Table 37. Heating capacity (kW) - fan sizes 03SQ 04SQ(SI)
Water
Rows L/s
1-Row
Capacity kW
2-Row
Capacity kW
0.06
0.13
0.19
0.25
0.32
0.38
0.44
0.50
0.57
0.63
0.06
0.13
0.19
0.25
0.32
0.38
0.44
0.50
Pressure
Drop (kPa)
0.81
3.02
6.56
11.39
17.49
24.86
33.49
43.36
54.46
66.80
1.18
4.22
8.99
15.41
23.45
33.07
44.26
57.00
94 142 189 260 330 401 472 543 613 684 755
-
4.40
4.60
4.71
4.77
4.82
4.85
4.88
4.90
4.92
-
5.55
5.70
5.78
5.83
5.86
5.88
5.90
-
5.33
5.64
5.80
5.91
5.98
6.03
6.08
6.11
6.13
-
7.50
7.83
8.00
8.10
8.17
8.22
8.26
-
6.04
6.45
6.67
6.81
6.91
6.98
7.04
7.08
7.12
-
9.07
9.61
9.89
10.06
10.18
10.26
10.33
6.91
7.45
7.75
7.94
8.08
8.18
8.26
8.32
8.37
10.90
11.78
12.25
12.54
12.74
12.88
12.99
40
-
3.58
4.02
4.20
4.30
4.36
5.63
6.37
6.64
6.78
6.87
-
-
-
3.80
4.32
4.52
4.63
4.71
6.08
6.99
7.33
7.51
7.62
Airflow (L/s)
-
7.62
8.29
8.67
8.92
9.09
9.22
9.32
9.40
9.47
-
12.31
13.52
14.18
14.60
14.88
15.09
15.25
Airflow (L/s)
-
4.01
4.59
4.82
4.95
5.03
6.46
7.54
7.95
8.16
8.30
8.23
9.03
9.49
9.79
10.00
10.16
10.28
10.38
10.46
13.42
14.94
15.79
16.33
16.71
16.99
17.20
4.20
4.84
5.10
5.25
5.34
6.80
8.03
8.51
8.76
8.92
-
8.79
9.70
10.23
10.58
10.83
11.02
11.16
11.28
11.37
-
14.32
16.12
17.16
17.82
18.29
18.63
18.89
Performance Data
100
110
120
0.907
1.000
1.093
-
-
4.38
5.08
5.37
5.53
5.63
7.09
8.47
9.02
9.31
9.50
-
9.29
10.30
10.91
11.31
11.60
11.81
11.98
12.12
12.22
-
15.06
17.13
18.33
19.12
19.67
20.07
20.39
-
4.55
5.30
5.62
5.80
5.91
7.35
8.87
9.49
9.82
10.03
-
-
-
9.75
10.86
11.54
11.99
12.32
12.56
12.75
12.90
13.03
-
15.68
18.00
19.36
20.25
20.89
21.36
21.72
-
4.70
5.52
5.86
6.06
6.18
7.58
9.24
9.92
10.29
10.52
-
10.16
11.38
12.13
12.63
12.99
13.27
13.48
13.65
13.79
-
16.22
18.75
20.26
21.26
21.97
22.50
22.92
130
1.187
-
4.70
5.52
5.86
6.06
6.18
7.58
9.24
9.92
10.29
10.52
-
10.16
11.38
12.13
12.63
12.99
13.27
13.48
13.65
13.79
-
16.22
18.75
20.26
21.26
21.97
22.50
22.92
VAV-PRC012-EN 45
Performance Data
Table 38. Heating capacity (kW) - fan size 05SQ(SI)
Water
Rows L/s
0.06
0.13
0.19
1-Row
Capacity kW
2-Row
Capacity kW
0.25
0.32
0.38
0.44
0.50
0.06
0.13
0.19
0.25
0.32
0.38
0.44
0.50
Table 39. Heating capacity (kW) - fan sizes 06SQ & 07SQ (SI)
Rows L/s
0.03
0.06
1-Row
Capacity kW
2-Row
Capacity kW
0.13
0.19
0.25
0.32
0.38
0.06
0.13
0.19
0.25
0.32
0.38
Pressure
Drop (kPa)
0.87
3.22
6.95
12.04
18.46
26.20
35.23
45.57
1.16
4.16
8.85
15.17
23.09
32.57
43.60
56.16
Water
Pressure
Drop (kPa)
0.36
1.20
4.10
8.46
14.22
21.30
29.68
2.31
7.71
15.74
26.24
39.08
54.19
165 236 307 378 472 566 661 755 849 944 1015
-
6.35
6.75
6.96
7.10
7.19
7.26
7.32
-
8.78
9.20
9.42
9.55
9.63
9.70
9.74
-
7.40
7.95
8.26
8.46
8.60
8.70
8.78
-
11.05
11.83
12.23
12.48
12.65
12.77
12.86
-
8.23
8.94
9.33
9.59
9.77
9.90
10.01
-
12.78
13.94
14.56
14.95
15.21
15.39
15.54
-
8.94
9.78
10.27
10.58
10.80
10.97
11.09
-
14.16
15.68
16.52
17.04
17.40
17.67
17.87
330 425 519 613 708 802 897 991 1085 1180 1274
-
-
9.15
9.91
10.34
10.61
10.80
-
14.01
15.27
15.94
16.34
16.62
-
-
10.11
11.07
11.61
11.96
12.20
-
15.83
17.61
18.58
19.18
19.59
-
-
10.98
12.07
12.73
13.15
13.45
-
17.23
19.49
20.75
21.55
22.11
-
-
11.74
12.97
13.73
14.23
14.59
-
18.33
21.04
22.58
23.58
24.27
Airflow (L/s)
-
9.76
10.77
11.37
11.76
12.03
12.24
12.40
-
15.58
17.57
18.69
19.41
19.90
20.26
20.54
Airflow (L/s)
-
-
12.41
13.80
14.66
15.23
15.64
-
19.23
22.33
24.14
25.32
26.15
-
10.49
11.64
12.34
12.81
13.14
13.39
13.58
-
16.69
19.10
20.48
21.38
22.01
22.48
22.83
-
-
13.00
14.58
15.51
16.15
16.62
-
19.97
23.43
25.49
26.85
27.80
-
11.12
12.42
13.23
13.77
14.15
14.44
14.67
-
17.57
20.35
21.99
23.07
23.83
24.39
24.82
-
-
13.54
15.29
16.30
17.02
17.54
-
20.59
24.38
26.67
28.19
29.27
-
11.69
13.16
14.04
14.66
15.09
15.42
15.68
-
18.30
21.41
23.28
24.52
25.41
26.06
26.57
-
-
14.03
15.94
17.07
17.83
18.40
-
21.11
25.20
27.71
29.38
30.58
-
12.19
13.82
14.79
15.48
15.97
16.34
16.63
-
18.90
22.32
24.40
25.80
26.79
27.54
28.12
-
-
14.49
16.55
17.78
18.60
19.22
-
21.57
25.93
28.63
30.45
31.76
-
12.65
14.44
15.51
16.25
16.79
17.21
17.53
-
19.41
23.10
25.38
26.92
28.03
28.86
29.51
-
-
14.90
17.12
18.46
19.34
20.00
-
21.97
26.57
29.46
31.42
32.83
-
12.65
14.44
15.51
16.25
16.79
17.21
17.53
-
19.41
23.10
25.38
26.92
28.03
28.86
29.51
-
-
14.90
17.12
18.46
19.34
20.00
-
21.97
26.57
29.46
31.42
32.83

Water Coil Notes (SI)

1. Fouling Factor = 0.0005.
2. The following equations may be used in calculating Leaving Air Temperature (LAT) and Water Temperature Difference (WTD).
kW 0.83
AT EAT
TD EWT LWT
3. Capacity based on 21°C entering air temperature and 82°Centering water temperature. Refer to
correction factors for different entering conditions.
Table 40. Temperature correction factors for water pressure drop (kPa)
Average Water Temperature Correction Factor
Table 41. Temperature correction factors for coil capacity (kW)
Entering Water Minus Entering Air Correction Factor
46 VAV-PRC012-EN

-----------------------------
+=

Ls
kW
==
-----------------------------
4.19 L s
93
0.970880.985821.000771.020711.030661.050601.080541.100491.130431.150
22
0.355270.446330.537380.629440.722500.814550.907611.000671.093721.187

Low Height Parallel Fan-PoweredTerminal Units

Table 42. Primary airflow control factory settings – I-P
Performance Data
Control Type
Direct Digital Control/
UCM
Pneumatic with
Volume Regulator
Analog Electronic
Air Valve Size
(in.)
5 6 8
8x14
5 6 8
8x14
5 6 8
8x14
Maximum Valve
Cfm
350 500 900
2200
350 500 900
2100
350 500 900
2200
Table 43. Primary airflow control factory settings – SI
Control Type
Direct Digital Control/
UCM
Pneumatic with Volume
Regulator
Analog Electronic
Note: Maximum airflow must be greater than or equal to minimum airflow.
(in.)
5 6 8
8x14
5 6 8
8x14
5 6 8
8x14
Air Valve Size
Maximum Valve
L/s
165 236 425
1038
165 236 425 991
165 236 425
1038
Maximum
Controller Cfm
40-350 60-500
105-900
200-2200
63-350 73-500
134-900
297-2100
82-350 120-500 210-900
440-2200
Maximum
Controller L/s
19-165 28-236 50-425
104-1038
30-165 35-236 63-425
140-991
39-165 57-236
100-425
208-1038
Minimum Controller
Cfm
0, 40-350 0, 60-500
0, 105-900
0, 220-2200
0, 63-350 0, 73-500
0, 134-900
0, 297-2100
0, 82-310 0, 120-360 0, 210-660
0, 440-1475
Minimum Controller
L/s
0, 19-165
0, 28-236
0, 50-425
0, 104-1038
0, 30-165
0, 35-236
0, 63-425 0, 140-991
0, 39-146
0, 57-170 0, 100-311 0, 208-696
Constant Volume
Cfm
40-350 60-500
105-900
220-2200
63-350 73-500
134-900
297-2100
82-310 120-360 210-660
440-1475
Constant Volume
L/s
19-165 28-236 50-425
104-1038
30-165 35-236 63-425
140-991
39-146
57-170 100-311 208-696
Table 44. Unit air pressure drop – in. wg (I-P)
Fan/Inlet Size Airflow Cfm Cooling Only Unit
(in. wg)
150
08SQ-05
08SQ-06
08SQ-08
09SQ-06
Notes:
1. Units with Electric Coils per fan size add 0.01" (3 Pa) to cooling only value.
2. HW Coil only pressure drops are just for the heating coil.
200 250 350
200 300 400 500
400 600 800 900
200 300 400 500
0.01
0.02
0.03
0.05
0.01
0.04
0.06
0.09
0.01
0.09
0.16
0.20
0.01
0.04
0.06
0.09
VAV-PRC012-EN 47
Fan/Inlet Size Airflow Cfm Cooling Only Unit
(in. wg)
0.01
0.09
0.16
0.20
0.10
0.25
0.47
0.75
0.01
0.09
0.18
0.24
0.18
0.36
0.53
0.78
09SQ-08
09SQ-8x14
10SQ-08
10SQ-8x14
400 600 800 900
700 1100 1500 1900
400
600
800
900
725 1000 1200 1450
Performance Data
Table 45. Unit air pressure drop – Pa (SI)
Inlet/Fan Size Airflow L/s
71
08SQ-05
08SQ-06
08SQ-08
09SQ-06
Notes:
1. Units with Electric Coils per fan size add 0.01" (3 Pa) to cooling only value.
2. HW Coil only pressure drops are just for the heating coil.
94 118 165
200 142 189 236
189 283 378 425
94 142 189 236
Cooling Only
Unit (Pa) Inlet/Fan Size Airflow L/s
2 5 7
13
0.01 10 16 24
2 21 40 51
2 10 16 24
09SQ-08
09SQ-8x14
10SQ-08
10SQ-8x14
189 283 378 425
330 519 708 897
189 283 378 425
345 475 565 685
Cooling Only
Unit (Pa)
2 21 40 51
26 63
116 185
2 23 45 59
47 91
131 195
Table 46. Coil air pressure drop
in. wg (I-P) Pa (SI)
Fan Size Airflow Cfm 1-Row HW
(in. wg)
100 200
08SQ
09SQ
10SQ
Note: HW Coil Only pressure drops do not include unit pressure drop.
300 400 450
250 400 550 700 850
725 800
900 1000 1100 1150
0.00
0.01
0.02
0.03
0.04
0.01
0.03
0.05
0.08
0.11
0.09
0.11
0.13
0.16
0.19
0.20
2-Row HW
(in. wg)
0.01
0.02
0.04
0.06
0.07
0.03
0.06
0.10
0.15
0.20
0.17
0.20
0.24
0.29
0.33
0.35
Fan Size Airflow L/s 1-Row HW
(Pa)
1 2 4 7 9
3
7 12 19 27
22 26 33 40 46 49
08SQ
09SQ
10SQ
47
94 142 189 212
118 189 260 330 401
342 375 425 475 520 543
Table 47. Attenuator air pressure drop
(I-P) (SI)
Fan Size Plenum Cfm Attenuator Fan Size Plenum L/s Attenuator
150
08SQ
09SQ
10SQ not available 10SQ not available
250 350 450
350 500 650 800
0.01
0.03
0.05
0.07
0.05
0.08
0.13
0.18
08SQ
09SQ
71 118 165 212
165 236 307 378
2-Row HW (Pa)
2
5 10 15 18
7 15 25 36 51
43 49 60 72 82 87
0.01
0.01
0.02
0.02
0.02
0.03
0.04
0.05
48 VAV-PRC012-EN

Performance Data Fan Curves

Performance Data
LPCF and LPEF maximum
Minimum
1-row coil maximum
2-row coil maximum
Notes:
1. When attenuator is required, add inlet attenuator pressure to discharge static pressure for final fan performance.
2. When attenuator is required, add inlet attenuator pressure to discharge static pressure for final fan performance.
Pa In. wg
0.60
150
0.50
125
0.40
100
75
0.30
0.20
50
Discharge Static Pressure
0.10
25
150 200 250 300 350 400 450 500 550
(83 L/s)
175 cfm min
Low-Height Parallel 08SQ—PSC
11894 142
165 189 23671
212 260
Airflow
Pa In. wg
0.80
199
174
0.70
0.60
150
0.50
125
(193 L/s)
410 cfm min
0.40
100
0.30
75
Discharge Static Pressure
50
0.20
25
0.10 400
189 236 273 330 378
Low-Height Parallel 09SQ—PSC
500
600 700
800
Airflow
Cfm
L/s
900
425
1000
472
Cfm
L/s
Pa In. wg
0.80
199
0.70
174
0.60
150
0.50
125
0.40
100
75
0.30
0.20
50
Discharge Static Pressure
0.10
25
300 500 700 900 1100
142 236 330 425 519
Low-Height Parallel 10SQ—PSC
1300
614
1500
708
Cfm
L/s
Airflow
VAV-PRC012-EN 49
Performance Data
LPCF and LPEF maximum
Minimum
1-row coil maximum
2-row coil maximum
Notes:
1. ECMs (Electrically Commutated Motors) are ideal for systems seeking maximum motor efficiency.
2. When attenuator is required, add inlet attenuator pressure to discharge static pressure for final fan performance.
Pa In. wg
0.50
125
0.40
100
0.30
75
0.20
50
Discharge Static Pressure
0.10
25
50 150 250 350 450
24
(47 L/s)
100 cfm min
71 118 165 212
LPxF 08SQ—ECM
Airflow
Pa In. wg
125
0.50
0.40
100
(118 L/s)
250 cfm min
LPxF 09SQ—ECM
Cfm
L/s
0.30
75
50
0.20
Discharge Static Pressure
25
0.10 200 300 400 500 600 700 800 900
94 142 189 236
283 519472
Airflow
330
1100
1000
425378
Cfm
L/s
50 VAV-PRC012-EN
Table 48. Heating capacity (MBh) - fan sizes 08SQ & 09SQ (I-P)
Water
Pressure
Rows Gpm
1-Row
Capacity MBH
2-Row
Capacity MBH
0.5
1.0
1.5
2.0
2.5
1.0
2.0
3.0
4.0
5.0
Drop (ft)
0.80
2.67
5.43
9.02
13.39
0.89
3.02
6.24
10.47
15.66
100 200 300 400 500 600 700 800 900
7.73
8.58
8.90
9.06
9.17
9.36
9.74
9.86
9.92
9.96
10.43
12.15
12.83
13.20
13.43
15.49
16.83
17.29
17.53
17.67
12.20
14.51
15.52
16.07
16.43
19.69
22.20
23.11
23.59
23.88
Table 49. Heating capacity (MBh) - fan size 10SQ (I-P)
Water
Rows Gpm
1-Row Capacity
MBH
2-Row Capacity
MBH
0.7
1.0
1.5
2.0
2.5
1.5
2.0
3.0
4.0
5.0
Pressure Drop (ft)
1.51
2.80
5.69
9.45
14.03
1.85
3.07
6.32
10.58
15.80
700 800 900 1000 1100 1200 1240
18.46
20.69
22.72
23.97
24.79
32.51
35.03
37.85
39.39
40.36
19.31
21.82
24.15
25.51
26.45
34.20
37.06
40.32
42.11
43.24
13.50
16.37
17.69
18.42
18.89
22.72
26.42
27.82
28.56
29.01
20.07
22.85
25.46
26.95
28.00
35.65
38.83
42.49
44.52
45.81
Airflow (Cfm)
14.51
17.98
19.56
20.47
21.06
25.00
29.83
31.72
32.73
33.36
15.33
19.42
21.21
22.30
23.00
26.79
32.65
35.02
36.29
37.10
Airflow (Cfm)
20.75
23.78
26.67
28.32
29.46
36.90
40.38
44.42
46.68
48.13
21.37
24.64
27.79
29.62
30.83
38.01
41.76
46.15
48.62
50.22
Performance Data
16.03
20.69
22.72
23.97
24.79
28.23
35.03
37.85
39.39
40.36
16.63
21.82
24.15
25.51
26.45
29.41
37.06
40.32
42.11
43.24
21.93
25.43
28.84
30.84
32.14
38.98
42.99
47.71
50.39
52.13
17.15
22.85
25.46
26.95
28.00
30.41
38.83
42.49
44.52
45.81
22.14
25.72
29.24
31.30
32.66
39.34
43.44
48.29
51.06
52.84
Water Coil Notes (I-P)
Note: Fouling Factor = 0.0005.
Note: The off-coil temperature of the hot water coil on parallel fan-powered units must not exceed
140°F when mounted on plenum inlet.
Note: The following equations may be used in calculating Leaving AirTemperature (LAT) and
WaterTemperature Difference (WTD).
MB H 921.7
AT EAT
WTD EWT LWT
Note: Capacity based on 70°F entering air temperature and 180°F entering water temperature.
Refer to correction factors for different entering conditions.
Table 50.
Temperature correction factors for water pressure drop (WPD)
Average Water Temperature 200 190 180 170 160 150 140 130 120 110
Correction Factor 0.970 0.985 1.000 1.020 1.030 1.050 1.080 1.100 1.130 1.150
Temperature correction factors for coil capacity (MBH)
Entering Water Minus Entering Air 40 50 60 70 80 90 100 110 120 130
Correction Factor 0.355 0.446 0.537 0.629 0.722 0.814 0.907 1.000 1.093 1.187
VAV-PRC012-EN 51

------------------------------------- -
+=

Cfm
2MBH

==
------------------------

Gpm
Performance Data
Table 51. Heating capacity (kW) - fan sizes 08SQ & 09SQ (SI)
Rows L/s Water Pressure
0.03
1-Row Capacity
kW
2-Row Capacity
kW
0.06
0.09
0.13
0.16
0.06
0.13
0.19
0.25
0.32
Table 52. Heating capacity (kW) - fan size 10SQ (SI)
Rows L/s
0.04
1-Row Capacity
kW
2-Row Capacity
kW
0.06
0.09
0.13
0.16
0.09
0.13
0.19
0.25
0.32
Drop (kPa)
2.39
7.98
16.24
26.97
40.04
2.65
9.03
18.65
31.29
46.82
Water Pressure
Drop (kPa)
4.51
8.37
17.02
28.25
41.94
5.53
9.19
18.89
31.61
47.22
47 94 142 189 236 283 330 378 425
2.27
2.51
2.61
2.66
2.69
2.74
2.85
2.89
2.91
2.92
3.06
3.56
3.76
3.87
3.94
4.54
4.93
5.07
5.14
5.18
330 378 425 472 519 566 585
5.41
6.06
6.66
7.03
7.27
9.53
10.27
11.09
11.54
11.83
5.66
6.40
7.08
7.48
7.75
10.02
10.86
11.82
12.34
12.67
3.58
4.25
4.55
4.71
4.81
5.77
6.51
6.77
6.91
7.00
3.96
4.80
5.18
5.40
5.54
6.66
7.74
8.15
8.37
8.50
5.88
6.70
7.46
7.90
8.21
10.45
11.38
12.45
13.05
13.43
Airflow (L/s)
4.25
5.27
5.73
6.00
6.17
7.33
8.74
9.30
9.59
9.78
4.49
5.69
6.22
6.54
6.74
7.85
9.57
10.26
10.64
10.87
Airflow (L/s)
6.08
6.97
7.81
8.30
8.63
10.82
11.84
13.02
13.68
14.10
6.26
7.22
8.14
8.68
9.03
11.14
12.24
13.52
14.25
14.72
4.70
6.06
6.66
7.03
7.27
8.27
10.27
11.09
11.54
11.83
10.86
11.82
12.34
12.67
6.43
7.45
8.45
9.04
9.42
11.42
12.60
13.98
14.77
15.28
4.87
6.40
7.08
7.48
7.75
8.62
5.03
6.70
7.46
7.90
8.21
8.91
11.38
12.45
13.05
13.43
6.49
7.54
8.57
9.17
9.57
11.53
12.73
14.15
14.96
15.49
Water Coil Notes (SI)
1. Fouling Factor = 0.0005.
2. The off-coil temperature of the hot water coil on parallel fan-powered units must not exceed 60°C when mounted on plenum inlet.
3. The following equations may be used in calculating Leaving Air Temperature (LAT) and Water
emperature Difference (WTD).
T
kW 0.83
AT EAT
TD EWT LWT
4. Capacity based on 21°C entering air temperature and 82°C entering water temperature. Refer to correction factors for different entering conditions.
Table 53.
Temperature correction factors for water pressure drop (kPa)
Average Water Temperature 93 88 82 77 71 66 60 54 49 43
Correction Factor 0.970 0.985 1.000 1.020 1.030 1.050 1.080 1.100 1.130 1.150
Temperature correction factors for coil capacity (kW)
Entering Water Minus Entering Air 22 27 33 38 44 50 55 61 67 72
Correction Factor 0.355 0.446 0.537 0.629 0.722 0.814 0.907 1.000 1.093 1.187

-----------------------------
+=

Ls
kW
==
--------------------------------- -
4.19Ls
52 VAV-PRC012-EN

Low Height Series Fan-PoweredTerminal Units

Table 54. Primary airflow control factory settings-I-P
Control Type Air Valve Size
(in.)
5
Direct Digital Control/UCM
Pneumatic with Volume
Regulator
Analog Electronic
6 8
8x14
5 6 8
8x14
5 6 8
8x14
Table 55. Primary airflow control factory settings-SI
Control Type
Direct Digital Control/ UCM
Pneumatic with Volume Regulator
Analog Electronic
Note: Maximum airflow must be greater than or equal to minimum airflow.
Air Valve Size
Maximum Valve
Cfm
2200
2100
2200
(in.)
5 6 8
8x14
5 6 8
8x14
5 6 8
8x14
350 500 900
350 500 900
350 500 900
Maximum
Valve L/s
165 236 425
1038
165 236 425 991
165 236 425
1038
Maximum Controller
Cfm
40-350 60-500
105-900
200-2200
63-350 73-500
134-900
297-2100
82-350 120-500 210-900
440-2200
Maximum Controller
L/s
19-165 28-236 50-425
104-1038
30-165 35-236 63-425
140-991
39-165 57-236
100-425
208-1038
Minimum Controller
Cfm
0, 40-350 0, 60-500
0, 105-900
0, 220-2200
0, 63-350 0, 73-500
0, 134-900
0, 297-2100
0, 82-310 0, 120-360 0, 210-660
0, 440-1475
Minimum Controller L/
s
0, 19-165 0, 28-236 0, 50-425
0, 104-1038
0, 30-165 0, 35-236 0, 63-425
0, 140-991
0, 39-146
0, 57-170 0, 100-311 0, 208-696
Performance Data
Constant Volume
Cfm
40-350 60-500
105-900
220-2200
63-350 73-500
134-900
297-2100
82-310 120-360 210-660
440-1475
19-165 28-236 50-425
104-1038
30-165 35-236 63-425
140-991
39-146
57-170 100-311 208-696
Table 56. Unit air pressure drop
in. wg (I-P) Pa (SI
Fan/Inlet Size Airflow Cfm Cooling Only Fan/Inlet Size Airflow L/s Cooling Only
08SQ-05
08SQ-06
08SQ-08
09SQ-06
150 250 350
150 275 400 500
150 275 400 500
350 400 450 500
0.01
0.03
0.11
0.02
0.14
0.35
0.58
0.01
0.05
0.13
0.21
0.17
0.26
0.37
0.50
08SQ-05
08SQ-06
08SQ-08
09SQ-06
71 118 165
71 130 189 236
71 130 189 236
165 189 212 236
VAV-PRC012-EN 53
2 9
28
5 34 86
143
3 14 32 52
43 66 93
124
Performance Data
Table 56. Unit air pressure drop (continued)
in. wg (I-P) Pa (SI
400
09SQ-08
09SQ-8x14
10SQ-08
10SQ-8x14
600 750 900
600 700 900
1050
400 600 800
600
900 1100 1500
Table 57. Coil air pressure drop
in.wg (I-P) Pa (SI)
Fan
Size Airflow Cfm
100 200
08SQ
09SQ
10SQ
Note: HW Coil Only pressure drops do not include unit pressure drop.
300 400 500
400 550 700 850
1000
400
800 1200 1600 2000
1-Row HW (in.
wg)
0.00
0.01
0.02
0.03
0.05
0.03
0.06
0.09
0.13
0.18
0.01
0.03
0.06
0.11
0.16
0.08
0.24
0.40
0.61
0.18
0.27
0.51
0.73
0.08
0.38
0.84
0.21
0.50
0.77
1.47
2-Row HW (in.
wg) Fan Size Airflow L/s 1-Row HW (Pa) 2-Row HW (Pa)
0.01
0.03
0.05
0.07
0.10
0.07
0.12
0.17
0.24
0.32
0.02
0.07
0.12
0.20
0.29
08SQ
09SQ
10SQ
09SQ-08
8x14-09SQ
10SQ-08
10SQ-8x14
47
94 142 189 236
189 260 330 401 472
189 378 566 755 944
13
15 23 33 44
16 27 40
1 3 5 9
9
3 8
189 283 354 425
283 330 425 495
189 283 378
283 425 519 708
21
59 100 151
44
66 126 182
20
94 209
51 124 191 367
3
6 11 18 25
18 29 43
0 80
6 16 31 50 72
Table 58. Attenuator air pressure drop
(I-P) (SI)
Fan Size Plenum Cfm Attenuator Fan Size Plenum L/s Attenuator
71 118 165 212
165 236 307 378
189 330 472 614 755
08SQ
09SQ
10SQ
150 250 350 450
350 500 650 800
400
700 1000 1300 1600
0.02
0.04
0.06
0.09
0.06
0.10
0.15
0.22
0.02
0.05
0.09
0.14
0.20
08SQ
09SQ
10SQ
54 VAV-PRC012-EN
0.01
0.01
0.02
0.03
0.02
0.03
0.05
0.06
0.01
0.02
0.03
0.04
0.06
Performance Data
LSCF and LSEF maximum
Minimum
1-row coil maximum
2-row coil maximum
Note: When attenuator is required, add inlet
attenuator pressure to discharge static pressure for final fan performance.
Pa In. wg
199
0.80
0.70
174
0.60
150
0.50
125
0.40
100
0.30
75
0.20
50
Discharge Static Pressure
0.10
25
0.00
0
Pa In. wg
199
174
150
125
100
75
Discharge Static Pressure
50
25
(80 L/s)
170 cfm min
150
200 250 300 350 400 450 500
94 142 189 236
71
0.80
0.70
0.60
0.50
0.40
0.30
0.20
0.10
350 cfm min
Low-Height Series 08SQ—PSC
Low-Height Series 09SQ—PSC
(165 L/s)
Airflow
600
550
212 260165118 283
Cfm
L/s
0
0.00 300 400 500 600
142 189 236
700 800 900
1000
472425378330283
1100
519
Cfm
L/s
Airflow
Pa In. wg
0.80
199
0.70
174
0.60
150
0.50
125
405 cfm min
142
(191 L/s)
236
0.40
100
0.30
75
Discharge Static Pressure
0.20
50
0.10
25
0
0.00 300 500 700
Low-Height Series 10SQ—PSC
519425330
1300 1500
614
900 1100
1700 1900 2100
2300
1086991897802708
Cfm
L/s
Airflow
VAV-PRC012-EN 55
Performance Data
LSCF and LSEF maximum
Minimum
1-row coil maximum
2-row coil maximum
Notes:
1. ECMs (Electrically Commutated Motors) are ideal for systems seeking maximum motor efficiency.
2. When attenuator is required, add inlet attenuator pressure to discharge static pressure for final fan performance.
Pa In. wg
125
0.50
100
0.40
0.30
75
(47 L/s)
0.20
50
Discharge Static Pressure
25
0.10
0.00
0
50 100 150 200 250 300 350 400 450 500
24
100 cfm min
LSxF 08SQ—ECM
94
118
Airflow
Pa In. wg
0.50
125
0.40
100
0.30
75
(113 L/s)
50
Discharge Static Pressure
25
0
240 cfm min
0.20
0.10
0.00 200 300 400 500 600 700 800 900 1000
94 142
189
LSxF 09SQ—ECM
236
283 472
330
Airflow
189
236
Cfm
L/s
Cfm
L/s
2121651427147
425378
Pa In. wg
0.50
125
0.40
100
0.30
75
0.20
50
Discharge Static Pressure
0.10
25
0.00
0
(189 L/s)
400 cfm min
300 500 700 900 1100 1300 1500 1700 1900
142
330236 425 897
LSxF 10SQ—ECM
519 614 708 802
Cfm
L/s
Airflow
56 VAV-PRC012-EN
Table 59. Heating capacity (MBh) - fan sizes 08SQ & 09SQ (I-P)
Water
Pressure
Rows Gpm
1-Row Capacity
MBH
2-Row Capacity
MBH
1.0
2.0
3.0
4.0
5.0
6.0
1.0
2.0
3.0
4.0
5.0
Drop (ft)
0.15
0.58
1.27
2.24
3.48
4.98
0.76
2.60
5.39
9.06
13.57
100 200 300 400 500 600 700 800 900 1000
-
-
7.92
8.08
8.17
8.24
9.04
9.45
9.59
9.66
9.70
-
-
11.16
11.48
11.69
11.83
14.59
15.95
16.43
16.68
16.83
-
-
13.45
13.94
14.25
14.47
18.26
20.70
21.60
22.08
22.37
Table 60. Heating capacity (MBh) - fan size 10SQ (I-P)
Water
Rows Gpm
1-Row Capacity
MBH
2-Row Capacity
MBH
1.0
2.0
4.0
6.0
8.0
10.0
1.0
2.0
3.0
4.0
5.0
Pressure Drop (ft)
0.16
0.61
2.32
5.09
8.91
13.77
1.29
4.31
8.84
14.77
22.03
450 600 750 900 1050 1200 1350 1500 1650 1800 1950
-
-
25.05
26.10
26.66
27.02
28.40
33.46
35.30
36.25
36.83
-
-
28.61
30.00
30.76
31.23
32.18
39.56
42.41
43.91
44.83
-
-
31.67
33.40
34.34
34.95
34.87
44.37
48.23
50.30
51.58
34.39
36.45
37.59
38.32
36.88
48.27
53.10
55.72
57.37
-
-
15.34
15.98
16.39
16.69
20.87
24.34
25.68
26.40
26.85
-
-
Airflow (Cfm)
-
-
16.97
17.76
18.28
18.65
22.83
27.24
29.01
29.96
30.56
Airflow (Cfm)
-
-
36.86
39.26
40.59
41.44
38.43
51.49
57.23
60.40
62.41
39.12
41.85
43.38
44.36
39.66
54.19
60.78
64.48
66.84
-
-
-
-
18.42
19.36
19.99
20.43
24.35
29.61
31.78
32.96
33.71
-
-
41.23
44.28
46.00
47.11
40.66
56.50
63.88
68.08
70.78
-
-
19.73
20.82
21.54
22.06
25.57
31.59
34.14
35.54
36.43
Performance Data
-
-
20.92
22.16
22.98
23.58
26.58
33.28
36.17
37.78
38.80
-
-
43.18
46.57
48.48
49.72
41.49
58.49
66.61
71.28
74.30
22.01
23.39
24.32
24.99
27.42
34.74
37.95
39.75
40.90
-
-
45.02
48.73
50.83
52.20
42.19
60.23
69.03
74.15
77.48
-
-
-
-
46.75
50.77
53.07
54.56
42.79
61.76
71.20
76.74
80.36
-
-
23.02
24.54
25.57
26.31
28.14
36.02
39.53
41.51
42.78
-
-
48.41
52.71
55.20
56.83
43.30
63.13
73.16
79.09
82.99
Water Coil Notes
1. Fouling Factor = 0.0005.
2. The following equations may be used in calculating Leaving Air Temperature (LAT) and Water Temperature Difference (WTD).
MB H 921.7
LAT EAT
WTD EWT LWT
3. Capacity based on 70°F entering air temperature and 180°F entering water temperature. Refer
to correction factors for different entering conditions.
Table 61. Temperature correction factors for water pressure drop (ft)
Average Water Temperature 200 190 180 170 160 150 140 130 120 110
Correction Factor 0.970 0.985 1.000 1.020 1.030 1.050 1.080 1.100 1.130 1.150
Table 62. Temperature correction factors for coil capacity (MBH)
Entering Water Minus Entering Air 40 50 60 70 80 90 100 110 120 130
Correction Factor 0.355 0.446 0.537 0.629 0.722 0.814 0.907 1.000 1.093 1.187
VAV-PRC012-EN 57

------------------------------------- -
+=

Cfm
2MBH

------------------------
==

Gpm
Performance Data
Table 63. Heating capacity (kW) - fan size 08SQ & 09SQ (SI)
Rows L/s
0.06
0.13
1-Row Capacity
kW
2-Row Capacity
kW
0.19
0.25
0.32
0.38
0.06
0.13
0.19
0.25
0.32
Table 64. Heating capacity (kW) - fan size 10SQ (SI)
Rows L/s
0.06
0.13
1-Row Capacity kW
2-Row Capacity kW
0.25
0.38
0.50
0.63
0.06
0.13
0.19
0.25
0.32
Water Pressure
Drop (kPa)
0.44
1.72
3.81
6.71
10.40
14.90
2.27
7.78
16.11
27.08
40.58
Water
Pressure Drop
(kPa)
0.48
1.82
6.93
15.22
26.64
41.16
3.84
12.90
26.43
44.15
65.84
47 94 142 189 236 283 330 378 425 472
-
-
2.32
2.37
2.39
2.41
2.65
2.77
2.81
2.83
2.84
-
-
3.27
3.36
3.42
3.47
4.28
4.67
4.82
4.89
4.93
212 283 354 425 495 566 637 708 779 849 920
-
-
7.34
7.65
7.81
7.92
8.32
9.81
10.35
10.62
10.79
-
-
8.38
8.79
9.01
9.15
9.43
11.59
12.43
12.87
13.14
-
-
9.28
9.79
10.07
10.24
10.22
13.00
14.14
14.74
15.12
-
-
3.94
4.08
4.18
4.24
5.35
6.07
6.33
6.47
6.56
-
-
10.08
10.68
11.02
11.23
10.81
14.15
15.56
16.33
16.81
-
-
4.50
4.68
4.80
4.89
6.12
7.13
7.53
7.74
7.87
10.80
11.50
11.90
12.15
11.26
15.09
16.77
17.70
18.29
Airflow (L/s)
-
-
4.97
5.21
5.36
5.47
6.69
7.98
8.50
8.78
8.96
5.40
5.67
5.86
5.99
7.14
8.68
9.31
9.66
9.88
Airflow (L/s)
-
-
-
-
11.47
12.27
12.71
13.00
11.62
15.88
17.81
18.90
19.59
-
-
-
-
12.08
12.98
13.48
13.81
11.92
16.56
18.72
19.95
20.74
-
-
5.78
6.10
6.31
6.47
7.49
9.26
10.00
10.41
10.68
-
-
12.66
13.65
14.21
14.57
12.16
17.14
19.52
20.89
21.78
-
-
6.13
6.49
6.74
6.91
7.79
9.75
10.60
11.07
11.37
-
-
13.19
14.28
14.90
15.30
12.36
17.65
20.23
21.73
22.71
-
-
6.45
6.86
7.13
7.32
8.04
10.18
11.12
11.65
11.99
13.70
14.88
15.55
15.99
12.54
18.10
20.87
22.49
23.55
-
-
6.75
7.19
7.49
7.71
8.25
10.56
11.58
12.16
12.54
-
-
-
-
13.70
14.88
15.55
15.99
12.54
18.10
20.87
22.49
23.55
Water Coil Notes
1. Fouling Factor = 0.0005.|
2. The following equations may be used in calculating Leaving Air Temperature (LAT) and Water Temperature Difference (WTD).
kW 0.83
LAT EAT
WTD EWT LWT
3. Capacity based on 21°C entering air temperature and 82°C entering water temperature. Refer
to correction factors for different entering conditions.
Table 65. Temperature correction factors for water pressure drop (kPa)
Average Water Temperature 93 88 82 77 71 66 60 54 49 43
Correction Factor 0.970 0.985 1.000 1.020 1.030 1.050 1.080 1.100 1.130 1.150
Table 66. Temperature correction factors for coil capacity (kW)
Entering Water Minus Entering Air 22 27 33 38 44 50 55 61 67 72
Correction Factor 0.355 0.446 0.537 0.629 0.722 0.814 0.907 1.000 1.093 1.187
58 VAV-PRC012-EN

-----------------------------
+=

Lls
kW

--------------------------- -
==

4.19Lls

Electrical Data

Parallel Fan-PoweredTerminal Units

Table 67. PSC motor units—electric coil kW guidelines – minimum to maximum (VPEF)
Single-Phase Voltage Three-Phase Voltage
Fan Size Stages
02SQ
03SQ
04SQ
05SQ
06SQ
07SQ
Table 68. ECM units—electric coil kW guidelines – minimum to maximum (VPEF)
Fan Size Stages
03SQ
04SQ
05SQ
06SQ
Notes:
1. Coils available with 24-VAC magnetic or mercury contactors, load carrying P.E. switches, and P.E. switch with magnetic or mercury contactors.
2. Available kW increments are by 0.5 from 0.5 kW to 8.0 kW, by 1.0 kW from 9.0 to 18.0 kW, and by 2.0 kW from 18.0 to 20.0 kW.
3. Each stage will be equal in kW output.
4. All heaters contain an auto reset thermal cutout and a manual reset cutout.
5. See section “Formulas,” p. 73 for formulas used to calculate the current amp draw for the heater elements.
6. Recommended coil temperature rise = 20° to 30°F (-7° to -1°C). Maximum temperature rise = 55°F (12°C).
7. Heaters should not operate at cfms below the nameplate minimum.
120V 208V 240V 277V 347V 480V 208V 480V 600V
1
0.5-5.0
2
0.5-5.0
1
0.5-5.0
2
0.5-5.0
1
0.5-4.5
2
0.5-4.5
1
0.5-4.5
2
0.5-4.5
1 2
1 2
0.5-6.0
0.5-6.0
0.5-9.0
0.5-9.0
0.5-8.0
0.5-8.0
0.5-8.0
0.5-8.0
-
0.5-9.0
-
0.5-9.0
-
0.5-8.0
-
0.5-8.0
0.5-6.0
0.5-6.0
0.5-10.0
0.5-10.0
0.5-10.0
0.5-10.0
0.5-9.0
0.5-9.0
-
-
-
-
0.5-6.0
1.0-6.0
0.5-11.0
1.0-11.0
0.5-12.0
1.0-12.0
0.5-12.0
1.0-12.
0.5-12.0
1.0-12.0
0.5-11.0
1.0-11.0
0.5-6.0
1.0-6.0
0.5-11.0
1.0-11.0
0.5-14.0
1.0-14.0
0.5-15.0
1.0-15.0
0.5-15.0
1.0-15.0
0.5-15.0
1.0-15.0
0.5-6.0
1.0-6.0
0.5-11.0
1.0-11.0
0.5-14.0
1.0-14.0
0.5-18.0
1.0-18.0
0.5-16.0
1.0-16.0
0.5-20.0
1.0-20.0
0.5-6.0
1.0-6.0
0.5-11.0
1.0-11.0
0.5-14.0
1.0-14.0
0.5-14.0
1.0-14.0
0.5-15.0
1.0-15.0
0.5-14.0
1.0-14.0
1.0-6.0
2.0-6.0
1.0-11.0
2.0-11.0
1.0-14.0
2.0-14.0
1.0-18.0
2.0-18.0
1.0-16.0
2.0-16.0
1.0-20.0
2.0-20.0
Single-Phase Voltage Three-Phase Voltage
120V 208V 240V 277V 347V 480V 208V 480V 600V
1
0.5-4.5
2
0.5-4.5
1
0.5-4.5
2
0.5-4.5
1
0.5-4.0
2
0.5-4.0
1
0.5-4.0
2
0.5-4.0
0.5-8.0
0.5-8.0
0.5-8.0
0.5-8.0
0.5-7.0
0.5-7.0
0.5-7.0
0.5-7.0
0.5-10.0
0.5-10.0
0.5-9.0
0.5-9.0
0.5-8.0
0.5-8.0
0.5-8.0
0.5-8.0
0.5-11.0
1.0-11.0
0.5-12.0
1.0-12.0
0.5-11.0
1.0-11.0
0.5-11.0
1.0-11.0
-
0.5-11.0
-
1.0-11.0
-
0.5-14.0
-
1.0-14.0
-
0.5-18.0
-
1.0-18.0
-
0.5-16.0
-
1.0-16.0
0.5-11.0
1.0-11.0
0.5-14.0
1.0-14.0
0.5-12.0
1.0-12.0
0.5-12.0
1.0-12.0
1.0-11.0
2.0-11.0
1.0-14.0
2.0-14.0
1.0-18.0
2.0-18.0
1.0-16.0
2.0-16.0
1.5-6.0
3.0-6.0
1.5-11.0
3.0-11.0
1.5-14.0
3.0-14.0
1.5-18.0
3.0-18.0
1.5-16.0
3.0-16.0
1.5-20.0
3.0-20.0
-
-
-
-
-
-
-
-
380V/
50Hz
1.0-6.0
1.5-6.0
1.0-11.0
1.5-11.0
1.0-14.0
1.5-14.0
1.0-18.0
1.5-18.0
1.0-16.0
1.5-16.0
1.0-20.0
1.5-20.0
380V/
50Hz
-
-
-
-
-
-
-
-
Table 69. Fan electrical performance (PSC)
Maximum Fan Motor Amperage (FLA)
Fan Size HP
02SQ 1/8 1.6 - 0.7
03SQ 1/3 4.3 - 1.6
04SQ 1/3 5.5 - 2.0
05SQ 1/2 6.7 - 2.4
06SQ 1/2 - 4.6 3.8
07SQ 1 - 6.6 4.7
VAV-PRC012-EN 59
115 VAC 208 VAC 277 VAC
Electrical Data
Table 69. Fan electrical performance (PSC)
Notes:
1. Electric Heat Units - Units with fan sizes 02SQ to 05SQ and a primary voltage of 208/60/1, 208/60/3, or 240/60/1 have 115/60/1 VAC fan motors. Fan sizes 06SQ and 07SQ with the same voltages, have 208/60/1 VAC motors.
2. Electric Heat Units - Units with primary voltage of 277/60/1, 480/60/1 or 480/60/3 use 277 VAC fan motors.
3. Electric Heat Units - Units with primary voltage of 347/60/1 or 575/60/3 use 347 VAC fan motors.
4. With 380/50/3 and 230/50/1, use 230/50 motors.
Table 70. Fan electrical performance (ECM)
Maximum Fan Motor Amperage (FLA)
Fan Size HP
03SQ 1/3 4.5 2.4
04SQ 1/2 6.5 3.5
05SQ 1 10.1 5.4
06SQ 1 9.5 5.1
Notes:
1. Electric heat units—units with primary voltages of 208/60/1, 208/60/3, or 240/60/1 have 115-VAC fan motors.
2. Electric heat units—units with primary voltages of 277/60/1, 480/60/1, or 480/60/3 have 277-VAC fan motors.
3. 347/60/1 and 230/50/1 voltage motors not available with ECMs.
Table 71. Minimum unit electric heat Cfm guidelines (PSC)
Unit kW
0.5 1
1.5
2
2.5 3
3.5 4
4.5
5
5.5 6
6.5 7
7.5
8 9
10
11 12 13
14 15 16
17 18 20
02SQ 03SQ 04SQ 05SQ 06SQ 07SQ
118 118 118
118 146 174
201 229 257
285 312 340
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
200 200 200
200 200 200
200 230 260
290 315 350
375 400 430
460 515 575
630
-
-
-
-
-
-
-
-
115 VAC 277 VAC
Cfm
315 315 315
315 315 315
315 315 315
315 315 350
375 400 430
460 515 575
630 690 745
810
-
-
-
-
-
350 350 350
350 350 350
350 350 350
350 350 350
375 400 430
460 515 575
630 690 745
810 860 920
973
1030
-
533 533 533
533 533 533
533 533 533
533 533 533
533 533 533
533 589 645
701 758 814
870 926 982
-
-
-
585 585 585
585 585 585
585 585 585
585 585 585
585 585 585
585 633 682
730 779 827
876 924 972
1021 1069 1166
60 VAV-PRC012-EN
Table 72. Minimum unit electric heat L/s guidelines (PSC)
Unit kW
0.5 1
1.5
2
2.5 3
3.5 4
4.5
5
5.5 6
6.5 7
7.5
8 9
10
11 12 13
14 15 16
17 18 20
02SQ 03SQ 04SQ 05SQ 06SQ 07SQ
56 56 56
56 69 82
95 108 121
134 147 160
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
94 94 94
94 94 94
94 109 123
137 149 165
177 189 203
217 243 271
297
-
-
-
-
-
-
-
-
149 149 149
149 149 149
149 149 149
149 149 165
177 189 203
217 243 271
297 326 352
382
-
-
-
-
-
L/s
165 165 165
165 165 165
165 165 165
165 165 165
177 189 203
217 243 271
297 326 352
382 406 434
459 486
Electrical Data
252 252 252
252 252 252
252 252 252
252 252 252
252 252 252
252 278 305
331 358 384
410 437 463
-
-
-
-
276 276 276
276 276 276
276 276 276
276 276 276
276 276 276
276 299 322
345 367 390
413 436 459
482 505 550
Table 73. Minimum unit electric heat Cfm guidelines (ECM)
Cfm
Unit kW
0.5 1
1.5
2
2.5 3
3.5 4
4.5
5
5.5 6
6.5 7
7.5
8 9
10
VAV-PRC012-EN 61
03SQ 04SQ 05SQ 06SQ
200 200 200
200 200 200
200 230 260
290 315 350
375 400 430
460 515 575
315 315 315
315 315 315
315 315 315
315 315 350
375 400 430
460 515 575
350 350 350
350 350 350
350 350 350
350 350 350
375 400 430
460 515 575
560 560 560
560 560 560
560 560 560
560 560 560
560 560 560
560 604 649
Electrical Data
Table 73. Minimum unit electric heat Cfm guidelines (ECM) (continued)
Cfm
Unit kW
11 12 13
14 15 16
17 18
Table 74. Minimum unit electric heat L/s guidelines (ECM)
Unit kW 03SQ 04SQ 05SQ 06SQ
0.5 1
1.5
2
2.5 3
3.5 4
4.5
5
5.5 6
6.5 7
7.5
8 9
10
11 12 13
14 15 16
17 18
03SQ 04SQ 05SQ 06SQ
630
-
-
-
-
-
-
-
630 690 745
810
-
-
-
-
L/s
94 94 94
94 94 94
94 109 123
137 149 165
177 189 203
217 243 271
297
-
-
-
-
-
-
-
149 149 149
149 149 149
149 149 149
149 149 165
177 189 203
217 243 271
297 326 352
382
-
-
-
-
165 165 165
165 165 165
165 165 165
165 165 165
177 189 203
217 243 271
297 326 352
382 406 434
459 486
630 690 745
810 860 920
973
1030
693 738 782
826 871 915
-
-
264 264 264
264 264 264
264 264 264
264 264 264
264 264 264
264 285 306
327 348 369
390 411 432
-
-
62 VAV-PRC012-EN

Series Fan-PoweredTerminal Units

Table 75. VSEF—electric coil kW guidelines – minimum to maximum (PSC motor units)
Fan
Size Stages
02SQ
03SQ
04SQ
05SQ
06SQ
07SQ
(a) 4.5, 5.5, 6.5, 9, 11, 13 kW not available (b) 12 kW not available (c) 10, 13 kW not available (d) 16, 17 kW not available (e) 18 kW not available
120V 208V 240V 277V 347V 480V 208V 480V 600V 380V/50Hz
1
0.5-5.0
2
0.5-5.0
1
0.5-5.0
2
0.5-5.0
1
0.5-4.5
2
0.5-4.5
1
0.5-4.5
2
0.5-4.5
1 2
1 2
0.5-7.0
0.5-7.0
0.5-9.0
0.5-9.0
0.5-8.0
0.5-8.0
0.5-8.0
0.5-8.0
-
0.5-9.0
-
0.5-9.0
-
0.5-8.0
-
0.5-8.0
Single-Phase Voltage Three-Phase Voltage
0.5-7.0
0.5-7.0
0.5-10.0
0.5-10.0
0.5-10.0
0.5-10.0
0.5-9.0
0.5-9.0
-
-
-
-
0.5-7.0
1.0-7.0
0.5-12.0
1.0-12.0
0.5-12.0
1.0-12.0
0.5-12.0
1.0-12.0
0.5-12.0
1.0-12.0
0.5-11.0
1.0-11.0
0.5-7.0
1.0-7.0
0.5-14.0
1.0-14.0
0.5-16.0
1.0-16.0
0.5-15.0
1.0-15.0
0.5-15.0
1.0-15.0
0.5-15.0
1.0-15.0
1.0-7.0
1.5-7.0
1.0-13.0
1.5-13.0
0.5-18.0
1.0-18.0
0.5-20.0
1.0-20.0
0.5-22.0
1.0-22.0
0.5-20.0
1.0-20.0
(b)
(b)
0.5-7.0
1.0-7.0
0.5-14.0
1.0-14.0
0.5-15.0
1.0-15.0
0.5-14.0
1.0-14.0
0.5-15.0
1.0-15.0
0.5-14.0
1.0-14.0
1.0-7.0
3.5-7.0
1.0-12.0
3.5-12.0
1.0-18.0
2.5-18.0
1.0-20.0
2.5-20.0
1.0-22.0
2.0-22.0
1.0-24.0
2.0-24.0
(a)
(a)
Electrical Data
1.5-7.0
-
1.5-13.0
-
4.0-15.0
1.5-22.0
1.5-22.0
3.0-22.0
1.5-24.0
3.0-24.0
(d)
(e)
1.5-18.0
4.0-20.0
1.5-7.0
2.5-7.0
1.0-14
2.5-13
1.0-18
1.5-18
1.0-22.0
1.5-22.0
1.0-22
1.5-22
-
-
(c)
(c)
Table 76. VSEF—electric coil kW guidelines – minimum to maximum (ECM units)
Single-Phase Voltage Three-Phase Voltage
Fan
Size Stages
03SQ
04SQ
05SQ
06SQ
Notes:
1. Coils available with electric, 24 VAC magnetic or contactors, load carrying P.E. switches, and P.E. switches with magnetic or mercury contactors.
2. Available kW increments are by 0.5 from 0.5 to 8.0 kW, by 1.0 kW from 9.0 to 17.0 kW, and by 2.0 kW from 18.0 to 24.0 kW.
3. Each stage will be equal in kW output.
4. All heaters contain an auto reset thermal cutout and a manual reset cutout.
5. See section “Formulas,” p. 73 for formulas used to calculate the current amp draw for the heater elements.
6. Recommended coil temperature rise = 20°-30°F (-7° to -1°C). Maximum temperature rise = 55°F (12°C).
7. Heaters should not operate at cfms below the nameplate minimum.
(a) 12 kW not available (b) 4.5, 5,5, 6.5, 9, 11 kW not available (c) 16, 17 kW not available
1 2
1 2
1 2
1 2
120V 208V 240V 277V 347V 480V 208V 480V 600V
0.5-18.0
1.0-18.0
0.5-18.0
1.0-18.0
0.5-22.0
1.0-22.0
(a)
(a)
0.5-14.0
1.0-14.0
0.5-14.0
1.0-14.0
0.5-12.0
1.0-12.0
0.5-12.0
1.0-12.0
1.0-12.0
3.5-12.0
1.0-18.0
2.5-15.0
1.0-22.0
2.5-20.0
1.0-22.0
2.0-22.0
(b)
(c)
0.5-4.5
0.5-4.5
0.5-4.5
0.5-4.5
0.5-4.0
0.5-4.0
0.5-4.0
0.5-4.0
0.5-8.0
0.5-8.0
0.5-8.0
0.5-8.0
0.5-7.0
0.5-7.0
0.5-7.0
0.5-7.0
0.5-10.0
0.5-10.0
0.5-9.0
0.5-9.0
0.5-8.0
0.5-8.0
0.5-8.0
0.5-8.0
0.5-12.0
1.0-12.0
0.5-12.0
1.0-12.0
0.5-11.0
1.0-11.0
0.5-11.0
1.0-11.0
-
1.0-13.0
-
1.5-13.0
-
-
-
-
-
-
380V/
50Hz
-
-
-
-
-
-
-
-
Table 77. Fan electrical performance (PSC)
Maximum Fan Motor Amperage (FLA)
Fan Size HP
02SQ 1/8 1.6 - 0.7
03SQ 1/3 4.3 - 1.6
04SQ 1/3 5.5 - 2.0
05SQ 1/2 6.7 - 2.4
06SQ 1/2 - 4.6 3.8
115 VAC 208 VAC 277 VAC
-
-
-
-
-
-
-
-
VAV-PRC012-EN 63
Electrical Data
Table 77. Fan electrical performance (PSC)
07SQ 1 - 6.6 4.7
Notes:
1. Electric Heat Units—Units with fan sizes 02SQ to 05SQ and a primary voltage of 208/60/1, 208/60/3 or 0/60/1 use 115/60/1 VAC fan motors. Fan sizes 06SQ and 07SQ in these same voltages, have 208/60/1 VAC fan motors.
2. Electric Heat Units—Units with primary voltage of 277/60/1, 480/60/1 or 480/60/3 use 277 VAC fan motors.
3. Electric Heat Units—Units with primary voltage of 347/60/1 or 575/60/3 use 347 VAC fan motors.
4. With 380/50/3 and 230/50/1 use 230/50 motors.
Table 78. Fan electrical performance (ECM)
Maximum Fan Motor Amperage (FLA)
Fan Size HP
03SQ 1/3 4.5 2.4
04SQ ½ 6.5 3.5
05SQ 1 10.1 5.4
06SQ 1 9.5 5.1
Notes:
1. Acceptable selections are any point within the shaded area. The ECM will operate on a vertical performance line using the solid state speed controller provided.
2. The ECM motor provides constant volume with changing static pressure conditions. Therefore, the fan curves for the ECM are different compared to fan curves with PSC motors.
3. By using an ECM motor, less fan sizes are used because of the wider turn-down ratios.
120 VAC 277 VAC
Table 79. Minimum unit electric
Unit kW
0.5 1
1.5
2
2.5 3
3.5 4
4.5
5
5.5 6
6.5 7
7.5
8 9
10
11 12 13
14 15 16
17 18 20
22 24
02SQ 03SQ 04SQ 05SQ 06SQ 07SQ
191 191 191
191 191 214
236 259 282
304 327 350
372 395
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
260 260 260
260 260 260
260 260 260
290 315 350
375 400 430
460 515 575
630 690 745
810
-
-
-
-
-
-
-
Heat Cfm Guidelines (PSC)
315 315 315
315 315 315
315 315 315
315 315 350
375 400 430
460 515 575
630 690 745
810 860 920
973
1030
-
-
-
400 400 400
400 400 400
400 400 400
400 400 400
400 400 430
460 515 575
630 690
745
810 860 920
973 1030 1150
1260
-
700 700 700
700 700 700
700 700 700
700 700 700
700 700 700
700 700 700
713 792 872
951 1031 1110
1190 1269 1428
1587
-
850 850 850
850 850 850
850 850 850
850 850 850
850 850 850
850 850 850
850 902 954
1006 1057 1109
1161 1213 1317
1420 1524
64 VAV-PRC012-EN
Table 80. Minimum unit electric
Unit kW
0.5 1
1.5
2
2.5 3
3.5 4
4.5
5
5.5 6
6.5 7
7.5
8 9
10
11 12 13
14 15 16
17 18 20
22 24
02SQ 03SQ 04SQ 05SQ 06SQ 07SQ
90 90 90
90 90
101
112 122 133
144 154 165
176 186
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
123 123 123
123 123 123
123 123 123
137 149 165
177 189 203
217 243 271
297 326 352
382
-
-
-
-
-
-
-
Heat L/s Guidelines (PSC)
149 149 149
149 149 149
149 149 149
149 149 165
177 189 203
217 243 271
297 326 352
382 406 434
459 486
-
-
-
189 189 189
189 189 189
189 189 189
189 189 189
189 189 203
217 243 271
297 326 352
382 406 434
459 486 543
595
-
330 330 330
330 330 330
330 330 330
330 330 330
330 330 330
330 330 330
336 374 411
449 486 524
562 599 674
749
-
Electrical Data
401 401 401
401 401 401
401 401 401
401 401 401
401 401 401
401 401 401
401 426 450
475 499 524
548 572 621
670 719
VAV-PRC012-EN 65
Electrical Data
Table 81. Minimum unit electric
Unit kW
0.5 1
1.5
2
2.5 3
3.5 4
4.5
5
5.5 6
6.5 7
7.5
8 9
10
11 12 13
14 15 16
17 18 20 22
Heat Cfm Guidelines (ECM)
03SQ 04SQ 05SQ 06SQ
260 260 260
260 260 260
260 260 260
290 315 350
375 400 430
460 515 575
630 690 745
810
-
-
-
-
-
-
315 315 315
315 315 315
315 315 315
315 315 350
375 400 430
460 515 575
630 690 745
810 860 920
973
1030
-
-
400 400 400
400 400 400
400 400 400
400 400 400
400 400 430
460 515 575
630 690 745
810 860 920
973 1030 1150 1260
943 943 943
943 943 943
943 943 943
943 943 943
943 943 943
943 943 975
1006 1038 1069
1101 1133 1164
1196 1228 1291 1354
66 VAV-PRC012-EN
Table 82. Minimum unit electric
Unit kW
0.5 1
1.5
2
2.5 3
3.5 4
4.5
5
5.5 6
6.5 7
7.5
8 9
10
11 12 13
14 15 16
17 18 20 22
03SQ 04SQ 05SQ 06SQ
123 123 123
123 123 123
123 123 123
137 149 165
177 189 203
217 243 271
297 326 352
382
Electrical Data
Heat L/s Guidelines (ECM)
149 149 149
149 149 149
149 149 149
149 149 165
177 189 203
217 243 271
297 326 352
382
-
-
-
-
-
-
406 434
459 486
-
-
189 189 189
189 189 189
189 189 189
189 189 189
189 189 203
217 243 271
297 326 352
382 406 434
459 486 543 595
445 445 445
445 445 445
445 445 445
445 445 445
445 445 445
445 445 460
475 490 505
520 535 549
564 579 609 639
VAV-PRC012-EN 67
Electrical Data

Low Height Parallel Fan-PoweredTerminal Units

Table 83. LPEF—electric coil kW guidelines – minimum to maximum (PSC motor units)
Single-Phase Voltage Three-Phase Voltage
Fan Size Stages
08SQ
09SQ
10SQ
1 2
1 2
1 2
Table 84. LPEF–electric coil kW guidelines – minimum to maximum (ECM units)
Fan Size Stages
08SQ
09SQ
Notes:
1. Coils available with 24 VAC magnetic or mercury contactors, load carrying P.E. switches, and P.E. switch with magnetic or mercury contractors.
2. Available kW increments are by 0.5 from 0.5 kW to 8.0 kW and by 1.0 kW from 9.0 to 14.0 kW.
3. Each stage will be equal in kW output.
4. All heaters contain an auto thermal cutout and a manual reset cutout.
5. The current amp draw for the heater elements is calculated by the formula below.
1 2
1 2
120V 208V 240V 277V 347V 480V 208V 480V 600V
0.5-4.5
0.5-4.5
0.5-4.5
0.5-4.5
0.5-4.0
0.5-4.0
0.5-7.0
0.5-7.0
0.5-8.0
0.5-8.0
0.5-8.0
0.5-8.0
0.5-7.0
0.5-7.0
0.5-10.0
0.5-10.0
0.5-9.0
0.5-9.0
0.5-7.0
1.0-7.0
0.5-12.0
1.0-12.0
0.5-12.0
1.0-12.0
0.5-7.0
1.0-7.0
0.5-14.0
1.0-14.0
0.5-14.0
1.0-14.0
0.5-7.0
1.0-7.0
0.5-14.0
1.0-14.0
0.5-14.0
1.0-14.0
0.5-7.0
1.0-7.0
0.5-14.0
1.0-14.0
1.0-13.0
1.0-13.0
1.0-7.0
2.0-7.0
1.0-14.0
2.0-14.0
1.0-14.0
2.0-14.0
Single-Phase Voltage Three-Phase Voltage
120V 208V 240V 277V 347V 480V 208V 480V 600V
0.5-5.0
0.5-5.0
0.5-4.5
0.5-4.5
0.5-7.0
0.5-7.0
0.5-8.0
0.5-8.0
0.5-7.0
0.5-7.0
0.5-9.0
0.5-9.0
0.5-7.0
1.0-7.0
0.5-12.0
1.0-12.0
-
-
-
-
0.5-7.0
1.0-7.0
0.5-14.0
1.0-14.0
0.5-7.0
1.0-7.0
0.5-14.0
1.0-14.0
1.0-7.0
2.0-7.0
1.0-14.0
2.0-14.0
1.5-7.0
3.0-7.0
1.5-14.0
3.0-14.0
1.5-12.0
3.0-12.0
-
-
-
-
380V/
50Hz
-
-
-
-
-
-
380V/
50Hz
-
-
-
-
Table 85. Fan electrical performance (PSC)
Maximum Fan Motor Amperage (FLA)
Fan Size HP
08SQ 1/3 5.5 2.5 1.8
09SQ 1/3 5.5 2.5 1.8
10SQ* 2 x 1/8 9.4 3.5 3.0
Notes:
1. Electric Heat Units - Units with Primary Voltage of 208/60/1, 208/60/3 or 240/60/1 use 115 VAC fan motors.
2. Electric Heat Units - Units with Primary Voltage of 277/60/1, 480/60/1 or 480/60/3 use 277 VAC fan motors.
3. Electric Heat Units - Units with Primary Voltage of 347/60/1 or 575/60/3 use 347 VAC fan motors.
4. Values are for standard, single-speed, permanent split capacitor type motors. Consult factory for non-standard motor performance.
5. Motor amps for 10SQ are total amps for two motors.
115 VAC 277 VAC 347 VAC
Table 86. Fan electrical performance (ECM)
Maximum Fan Motor Amperage (FLA)
Fan Size HP
08SQ 1/2 2.0 1.1
09SQ 1/2 6.7 3.6
68 VAV-PRC012-EN
115 VAC 277 VAC
Table 87. Minimum unit electric heat guidelines
Cfm (PSC)
Unit kW
0.5 1
1.5
2
2.5 3
3.5 4
4.5
5
5.5 6
6.5 7
7.5
8 9
10
11 12 13 14
08SQ 09SQ 10SQ 08SQ 09SQ 10SQ
173 173 173
173 173 173
202 232 261
290 319 349
378 407
440 440 440
440 440 440
440 440 440
440 440 440
440 440
-
-
-
-
-
-
-
-
468
496 552 608
664 720 776 832
720 720 720
720 720 720
720 720 720
720 720 720
720 720 720
720 720 720
720 720 720
-
Unit kW
0.5 1
1.5
2
2.5 3
3.5 4
4.5
5
5.5 6
6.5 7
7.5
8 9
10
11 12 13 14
82 82 82
82 82 82
95 109 123
137 151 164
178 192
-
-
-
-
-
-
-
-
L/s (PSC)
208 208 208
208 208 208
208 208 208
208 208 208
208 208 221
234 261 287
313 340 366 393
Electrical Data
340 340 340
340 340 340
340 340 340
340 340 340
340 340 340
340 340 340
340 340 340
-
Table 88. Minimum unit electric heat Cfm guidelines (ECM)
Cfm (ECM)
Unit kW
0.5 1
1.5
2
2.5 3
3.5 4
4.5
5
5.5 6
6.5 7
7.5
8 9
10
11 12 13 14
08SQ 09SQ 08SQ 09SQ
188 188 188
188 188 188
220 251 283
314 346 377
409 440
-
-
-
-
-
-
-
-
490 490 490
490 490 490
490 490 490
490 490 490
490 490 514
539 588 637
685 734 783 832
Unit kW
0.5 1
1.5
2
2.5 3
3.5 4
4.5
5
5.5 6
6.5 7
7.5
8 9
10
11 12 13 14
89 89 89
89 89 89
104 118 133
148 163 178
193 208
-
-
-
-
-
-
-
-
L/s (ECM)
231 231 231
231 231 231
231 231 231
231 231 231
231 231 243
254 277 300
323 347 370 393
VAV-PRC012-EN 69
Electrical Data

Low Height Series Fan-PoweredTerminal Units

Table 89. LSEF-electric coil kW guidelines-minimum to maximum (PSC motor units)
Single-Phase Voltage Three-Phase Voltage
Fan Size Stages
08SQ
09SQ
10SQ
Table 90. LSEF-electric coil kW guidelines-minimum to maximum (ECM units)
Fan Size Stages
08SQ
09SQ
10SQ
Notes:
1. Coils available with 24 VAC magnetic or mercury contactors, load carrying P.E. switches, and P.E. switch with magnetic or mercury contactors.
2. Available kW increments are by 0.5 from 0.5 kW to 8.0 kW and by 1.0 kW from 9.0 to 18.0 kW.
3. Each stage will be equal in kW output.
4. All heaters contain an auto thermal cutout and a manual reset cutout.
5. The current amp draw for the heater elements is calculated by the formula below.
1 2
1 2
1 2
120V 208V 240V 277V 347V 480V 208V 480V 600V
1
0.5-4.5
2
0.5-4.5
1
0.5-4.5
2
0.5-4.5
1
0.5-4.0
2
0.5-4.0
0.5-6.0
0.5-6.0
0.5-8.0
0.5-8.0
0.5-7.5
0.5-7.5
-
-
0.5-10.0
0.5-10.0
0.5-8.0
0.5-8.0
0.5-6.0
0.5-6.0
0.5-12.0
1.0-12.0
0.5-11.0
1.0-11.0
0.5-6.0
1.0-6.0
0.5-12.0
1.0-12.0
0.5-15.0
1.0-15.0
0.5-6.0
1.0-6.0
0.5-12.0
1.0-12.0
0.5-18.0
1.0-18.0
0.5-6.0
1.0-6.0
0.5-12.0
1.0-12.0
0.5-13.0
1.0-13.0
1.0-6.0
3.0-6.0
1.0-12.0
3.0-12.0
1.0-18.0
2.0-18.0
Single-Phase Voltage Three-Phase Voltage
120V 208V 240V 277V 347V 480V 208V 480V 600V
0.5-5.0
0.5-5.0
0.5-4.5
0.5-4.5
0.5-4.5
0.5-4.5
0.5-6.0
0.5-6.0
0.5-8.0
0.5-8.0
0.5-8.0
0.5-8.0
0.5-6.0
0.5-6.0
0.5-10.0
0.5-10.0
0.5-9.0
0.5-9.0
0.5-6.0
1.0-6.0
0.5-12.0
1.0-12.0
0.5-12.0
1.0-12.0
-
0.5-6.0
-
1.0-6.0
-
0.5-12.0
-
1.0-12.0
-
0.5-18.0
-
1.0-18.0
0.5-6.0
1.0-6.0
0.5-12.0
1.0-12.0
0.5-14.0
1.0-14.0
1.5-12.0
4.5, 5, 9, 10--
1.5-18.0
3.0-18.0
1.0-6.0
3.0-6.0
1.0-12.0
3.0-12.0
1.0-18.0
2.0-18.0
1.5-6.0
5.0-5.0
380V/
50Hz
-
-
-
-
380V/
50Hz
-
-
-
-
-
-
-
-
-
-
-
-
Table 91. Fan electrical performance (PSC)
Maximum Fan Motor Amperage (FLA)
Fan Size HP
08SQ 1/3 5.5 2.5 1.8
09SQ 1/3 5.5 2.5 1.8
10SQ* 2 x 1/3 11.0 5.0 3.5
Notes:
1. Electric Heat Units - Units with Primary Voltage of 208/60/1, 208/60/3 or 240/60/1 use 115 VAC fan motors.
2. Electric Heat Units - Units with Primary Voltage of 277/60/1, 480/60/1 or 480/60/3 use 277 VAC fan motors.
3. Electric Heat Units - Units with Primary Voltage of 347/60/1 or 575/60/3 use 347 VAC fan motors.
4. Values are for standard, single-speed, permanent split capacitor type motors. Consult factory for non-standard motor performance.
5. Motor amps for 10SQ are total amps for two motors.
115 VAC 277 VAC 347 VAC
Table 92. Fan electrical performance (ECM)
Maximum Fan Motor Amperage (FLA)
Fan Size HP
08SQ 1/2 1.3 .7
09SQ 1/2 5.0 2.7
10SQ 2 x 1/2 7.5 4.0
70 VAV-PRC012-EN
115 VAC 277 VAC
Table 93. Minimum unit electric heat guidelines (PSC)
Cfm
Unit kW
0.5 1
1.5
2
2.5 3
3.5 4
4.5
5
5.5 6
6.5 7
7.5
8 9
10
11 12 13
14 15 16
17 18
08SQ 09SQ 10SQ 08SQ 09SQ 10SQ
228 228 228
228 244 260
276 293 309
325 341 357
-
-
-
-
-
-
-
-
-
-
-
-
-
-
377 377 377
377 377 377
377 377 377
377 377 377
403 429 455
480 532 584
635 687
-
-
-
-
-
-
440 440 440
440 440 440
440 440 440
440 440 440
440 440 467
494 547 601
655 708 762
815 869 923
976
1030
Unit kW
0.5 1
1.5
2
2.5 3
3.5 4
4.5
5
5.5 6
6.5 7
7.5
8 9
10
11 12 13
14 15 16
17 18
108 108 108
108 115 123
130 138 146
153 161 168
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Electrical Data
L/s
178 178 178
178 178 178
178 178 178
178 178 178
190 202 215
227 251 275
300 324
-
-
-
-
-
-
208 208 208
208 208 208
208 208 208
208 208 208
208 208 220
233 258 284
309 334 360
385 410 435
461 486
VAV-PRC012-EN 71
Electrical Data
Table 94. Minimum unit electric heat guidelines (ECM)
Cfm
Unit kW
0.5 1
1.5
2
2.5 3
3.5 4
4.5
5
5.5 6
6.5 7
7.5
8 9
10
11 12 13
14 15 16
17 18
08SQ 09SQ 10SQ 08SQ 09SQ 10SQ
128 128 128
128 159 190
221 253 284
315 346 377
-
-
-
-
-
-
-
-
-
-
-
-
-
-
377 377 377
377 377 377
377 377 377
377 377 377
403 429 455
480 532 584
635 687
-
-
-
-
-
-
480 480 480
480 480 480
480 480 480
480 480 480
480 480 505
530 580 630
680 730 779
829 879 929
979
1029
Unit kW
0.5 1
1.5
2
2.5 3
3.5 4
4.5
5
5.5 6
6.5 7
7.5
8 9
10
11 12 13
14 15 16
17 18
60 60 60
60 75 90
104 119 134
149 163 178
-
-
-
-
-
-
-
-
-
-
-
-
-
-
L/s
178 178 178
178 178 178
178 178 178
178 178 178
190 202 215
227 251 276
300 324
-
-
-
-
-
-
227 227 227
227 227 227
227 227 227
227 227 227
227 227 238
250 274 297
321 345 368
391 415 438
462 486
72 VAV-PRC012-EN
Formulas
-
--
-

Fan-Powered Parallel

Minimum Circuit Ampacity (MCA) Equation
MCA=1.25x( Motor amps is the sum of all motor current draws if more than one is used in the unit.
Maximum Overcurrent Protection (MOP) Equation
MOP = (2.25 x motor1 amps) + motor2 amps + heater amps motor1 amps = current draw of largest motor motor2 amps = sum of current of all other motors used in unit
General Sizing Rules:
If MOP = 15, then fuse size = 15
If MOP =19, then fuse size = 15with oneexception. If heater amps x 1.25 > 15, then fuse size = 20.
If MOP is equal to or less than MCA, then choose next fuse size greater than MCA.
Control fusing not applicable.
Standard Fuse Sizes: 15, 20, 25, 30, 35, 40, 45, 50, and 60.
Example:
A modelVPEF, electric reheat unit size 10-05SQ has 480/3 phase, 12 kW electric reheat with 2 stages and 277-Volt motor.
For MOP of fan-powered unit:
12 kW-480/3 heater:12x1000/480x1.73=14.45 amps
MCA = (2.4 + 14.45) x 1.25 = 21.06, MOP = (2.25 x 2.4) + 14.45 = 19.9.
Since MOP is less than or equal to MCA, then MOP = 25.
For total current draw of unit:
12kW-480/3 heater:12x1000/480x1.73=14.45
Two heat outputs (2 stages) @0.5 amps max each=1.00
Motor amps: 277 V (Fan size 0517) =2.4
Amps Max: 18.35
Useful Formulas:
kW
Cfm ATD
--------------------------------=
3145
Electrical Data
motor amps + heater amps)
kW 3145
TD
------------------------------
TD
amps
amps
=
------------------------------- -=
1214 L s
=
=
|
Cfm
kW
kW 1000
------------------------------------------------------------
PrimaryVoltage
kW 1000
-----------------------------------------------
PrimaryVoltag
kW = 1214 x L/s x ATD
VAV-PRC012-EN 73
Electrical Data
--
-
-

Fan-Powered Series

Minimum Circuit Ampacity (MCA) Equation
MCA = 1.25 x (Smotor amps + heater amps)
Maximum Overcurrent Protection (MOP) Equation
MOP = (2.25 x motor 1amps) + motor2 amps + heater amps motor1 amps = current draw of
General Sizing Rules:
If MOP = 15, then fuse size = 15
If MOP =19, then fuse size = 15with oneexception. If heater amps x 1.25 > 15, then fuse size = 20.
If MOP is less than/equal to MCA, then choose next fuse size greater than MCA.
Control fusing not applicable.
Standard Fuse Sizes: 15, 20, 25, 30, 35, 40, 45, 50, and 60.
Example:
A modelVSEF, electric reheat unit size 10-0517 has 480/3 phase, 12 kW electric reheat with 2 stages and 277-Volt motor.
For MOP of fan-powered unit:
12 kW - 480/3 heater:12x1000/480x1.73=14.45 amps.
MCA=(2.4 + 14.45) x 1.25 = 21.06, MOP = (2.25 x 2.4) + 14.45 = 19.9.
Since MOP is less than/equal to MCA, then MOP = 25.
For total current draw of unit:
12 kW—480/3 heater:12x1000/480x1.73=14.45
Two heat outputs (2 stages)@0.5 amps max each=1.00
Motor amps: 277 V (Fan size 0517)=2.4
Total amps max: 18.35
Used Formulas:
Here motor amps is the sum of all motor current draws if more than one is used in the unit.
largest motor motor2 amps = sum of current draw of all other motors used in units
amps
kW
TD
TD
amps
Cfm ATD
--------------------------------=
=
kW 1000
------------------------------------------------------------
=
PrimaryVoltage
3145
kW 3145
------------------------------
Cfm
kW
------------------------------- -=
1214 L s
kW 1000
-----------------------------------------------
=
PrimaryVoltag
kW=1214 x L/s x ATD
74 VAV-PRC012-EN

Low Height Parallel Fan-Powered

-
--
-
Minimum Circuit Ampacity (MCA) = (motor amps + heater amps) x 1.25
Maximum Overcurrent Protection (MOP) = (2.25 x motor amps) + heater amps
General Sizing Rules:
If MOP = 15, then fuse size = 15
If MOP =19, then fuse size = 15with oneexception. If heater amps x 1.25 > 15, then fuse size = 20.
If MOP £ MCA, then choose next fuse size greater than MCA.
Control fusing not applicable.
Standard Fuse Sizes: 15, 20, 25, 30, 35, 40, 45, 50, and 60.
Useful Formulas:
Cfm ATD
kW
--------------------------------=
3145
kW 3145
TD
------------------------------
=
Cfm
Electrical Data
TD
W 1214 L s ATD=
amps
amps
kW
------------------------------- -=
1214 L s
kW 1000
------------------------------------------------------------
=
PrimaryVoltage
kW 1000
-----------------------------------------------
=
PrimaryVoltag

Low-Height Series Fan-Powered

Minimum Circuit Ampacity (MCA) = (motor amps + heater amps) x 1.25
Maximum Overcurrent Protection (MOP) = (2.25 x motor amps) + heater amps
General Sizing Rules:
If MOP = 15, then fuse size = 15
If MOP =19, then fuse size = 15with oneexception. If heater amps x 1.25 > 15, then fuse size = 20.
If MOP is less than/equal to MCA, then choose next fuse size greater than MCA.
Control fusing not applicable.
Standard Fuse Sizes: 15, 20, 25, 30, 35, 40, 45, 50, and 60.
Useful Formulas
Cfm ATD
kW
--------------------------------=
3145
3amps
ATD
kW 3145
-------------------------------=
kW 1000
----------------------------------------------------------------- -=
PrimaryVoltage 3
Cfm
kW 1214 L l s ATD=
1amps
ATD
kW 1000
--------------------------------------------------- -=
PrimaryVoltage
kW
------------------------------=
1214 Ll s
VAV-PRC012-EN 75

Acoustics Data

Parallel Fan-PoweredTerminal Units

Table 95. Discharge sound power (dB)
1, 2, 4
- valve only
Inlet
Fan
Size
Size
02SQ 5 250 118 65 57 54 53 50 47
02SQ 6
02SQ 8
02SQ 10
03SQ 6
03SQ 04SQ
03SQ 04SQ
05SQ
03SQ 04SQ
05SQ
04SQ 05SQ
Cfml/s234567234567234567234567234567
(in)
200 94 55 51 44 43 38 30 57 52 48 47 43 39 60 54 54 53 51 50 63 56 57 57 56 56
300 142 60 53 49 48 44 35 62 56 54 53 50 43 64 58 57 56 54 50 66 60 61 59 57 55
400 189 62 54 49 47 42 36 67 60 58 57 54 46 67 61 59 60 57 49 68 62 60 61 58 52 69 64 63 63 60 56
500 236 64 57 53 51 47 41 70 63 60 59 55 47 71 65 64 65 62 55 73 68 66 68 65 58
350 165 56 49 46 45 40 33 60 54 51 48 46 45 63 58 56 53 52 51 65 60 59 56 55 55
520 245 61 54 50 49 44 37 64 58 55 52 50 47 66 62 60 57 55 52 68 64 63 60 58 56
700 330 66 60 55 53 49 42 68 63 60 57 54 49 69 65 63 60 57 52 70 67 65 62 59 54 72 69 67 65 62 57
900 425 70 64 59 57 52 45 73 67 64 61 57 52 74 70 69 66 62 57 76 72 71 68 65 60
550 260 63 55 52 52 49 39 67 60 57 57 55 47 71 65 62 62 59 54 73 67 65 65 62 58
820 387 66 58 56 56 54 44 71 64 61 61 59 51 76 70 67 67 65 58 78 72 70 70 67 61
1100 519 69 61 59 59 58 48 73 67 64 65 63 55 77 70 68 68 66 58 79 72 70 70 68 60 82 75 73 74 71 64
1400 661 71 65 62 62 60 51 76 70 67 67 65 57 82 75 72 73 71 63 85 78 76 76 74 67
100 47 48 45 41 37 33 30 49 46 44 39 37 39 50 48 47 43 45 47 51 48 47 45 49 53
200 94 52 48 43 40 35 29 55 51 47 44 41 40 57 53 52 48 47 48 58 55 54 50 51 54
300 142 57 51 46 43 36 32 60 56 51 47 44 40 62 59 56 52 50 49 63 60 59 55 54 54
400 189 59 53 48 44 38 34 64 59 54 50 46 42 65 61 57 53 50 46 66 63 59 55 52 49 68 64 62 58 56 54
600 283 63 59 56 50 46 44 65 61 57 53 48 46 73 68 64 61 56 52 75 70 68 64 60 56
175 83 48 45 42 39 34 30 50 47 44 41 41 42 53 49 47 45 47 49 55 50 49 48 51 53
350 165 52 48 44 41 35 31 56 52 49 46 43 41 60 57 55 52 51 51 62 58 58 54 54 55
525 248 57 53 49 47 42 34 61 57 54 51 47 42 65 61 59 56 53 51 66 63 62 58 56 56
8
700 330 62 57 53 51 47 40 64 60 57 55 51 45 66 63 60 57 54 49 68 65 63 60 56 52 70 67 66 62 59 57
1050 496 68 64 60 59 51 46 72 68 65 63 59 53 73 70 68 67 63 57 75 72 71 69 65 60
275 130 52 48 46 44 38 32 54 51 49 47 46 47 56 54 53 51 50 49 58 56 56 54 54 53
550 260 57 52 50 47 42 35 60 57 54 51 48 43 63 62 60 57 55 54 65 64 63 60 58 56
825 389 61 56 53 50 46 39 64 61 58 56 52 46 67 66 64 60 58 53 70 69 68 64 62 59
10
1100 519 64 60 57 54 50 43 67 64 62 59 55 49 70 67 65 62 59 53 72 69 67 64 61 56 74 71 70 67 64 60
1640 774 69 66 63 59 54 48 73 70 68 64 61 55 76 74 72 69 66 60 79 77 75 73 70 64
385 182 52 48 47 41 38 34 56 52 51 46 43 41 59 57 57 52 50 48 59 59 60 55 54 53
775 366 58 53 52 49 43 37 63 59 57 54 50 47 67 65 63 59 55 52 69 67 66 61 58 55
1160 547 62 57 55 51 47 41 67 62 60 57 54 49 73 68 67 64 61 55 76 71 70 67 64 59
12
1550 732 65 60 58 54 50 44 70 65 63 60 57 51 77 71 69 67 64 58 80 75 73 71 68 62
1600 755 74 68 66 64 61 55
2350 1109 70 66 65 60 56 50 75 71 69 65 61 55 81 75 73 71 68 62 84 79 77 75 72 66
525 248 55 50 48 45 41 35 59 54 53 50 48 44 63 59 59 55 53 52 64 62 62 58 56 55
1050 496 61 56 54 51 51 40 67 62 60 57 54 49 70 68 66 62 59 56 72 70 69 65 62 58
1575 743 64 59 57 54 52 44 71 65 63 60 57 52 75 72 70 67 63 59 77 75 73 70 67 62
14
2100 991 67 62 60 57 53 47 72 68 66 62 59 56 76 72 69 66 63 59 79 74 72 70 66 61 82 78 76 73 70 65
3200 1510 72 68 67 63 59 55 77 72 71 67 64 59 83 78 76 73 70 65 87 82 79 77 74 69
0.5" Inlet Pressure
Ps
5
1.0" Inlet Pressure
Ps
5
1.5" Inlet Pressure
Ps
3
2.0" Inlet Pressure
Ps
5
3.0" Inlet Pressure
Ps
5
76 VAV-PRC012-EN
Acoustics Data
Table 95. Discharge sound power (dB)
Inlet
Fan
Size
Size
06SQ 07SQ
06SQ 07SQ
06SQ 07SQ
06SQ 07SQ
Notes:
1. All data are measured in accordance with Industry Standard AHRI 880-2011.
2. All sound power levels, dB re: 10
3. Data in this column constitute AHRI 880-2011 Standard Rating Conditions
4. Where Ps is the inlet static pressure minus discharge static.
5. Application ratings are outside the scope of the certification program.
Cfml/s234567234567234567234567234567
(in)
550 260 53 49 46 43 38 31 56 54 51 49 45 41 60 60 58 54 52 54 62 63 62 58 56 54
800 378 57 53 50 46 41 34 60 58 55 52 48 42 64 63 61 57 54 53 66 66 65 61 59 56
1000 472 60 56 53 49 44 36 63 61 58 54 50 43 67 65 63 60 56 52 69 68 67 64 61 57
10
1100 519 66 65 62 58 54 49
1200 566 62 59 56 52 46 39 66 64 61 57 52 46 70 68 66 62 58 53 72 70 69 66 62 58
1350 637 64 61 58 54 48 42 68 66 63 59 54 48 72 70 68 64 60 54 74 72 71 67 63 59
800 378 63 56 55 54 51 42 68 62 61 61 59 51 71 67 65 66 64 57 73 70 68 69 67 60
1100 519 65 57 56 54 52 43 72 65 63 63 60 53 75 71 69 70 67 60 77 74 72 73 71 64
1400 661 66 59 58 54 52 44 74 67 64 64 62 54 79 73 71 72 70 62 81 77 74 76 74 66
12
1600 755 78 72 69 69 67 60
1700 802 67 61 60 55 52 44 75 69 66 65 62 55 82 75 72 73 71 63 84 79 76 77 76 68
2000 944 69 63 61 55 52 46 76 70 67 65 63 55 84 77 74 74 71 64 86 81 78 78 77 69
1100 519 60 54 53 51 48 41 65 60 58 57 54 48 69 66 64 61 60 55 73 71 69 64 62 59
1600 755 64 58 56 55 52 45 69 64 62 61 58 52 74 70 68 66 64 59 77 73 71 69 67 62
2100 991 67 61 60 57 55 47 72 67 66 64 61 55 75 70 68 67 64 58 77 72 71 69 67 61 80 76 74 72 70 65
14
2500 1180 70 64 63 60 57 50 74 69 67 66 63 56 80 74 72 71 69 63 83 77 76 74 72 66
3000 1416 73 67 66 63 60 53 77 71 69 68 65 58 83 76 74 73 71 65 87 79 78 76 74 68
1400 661 62 57 54 54 51 43 67 63 61 60 57 52 72 70 67 65 62 57 75 75 72 67 65 61
2100 991 64 60 58 56 54 46 71 66 63 62 60 55 76 73 71 69 67 62 78 76 74 72 70 65
2700 1274 67 63 61 59 56 49 73 68 66 65 62 57 79 74 72 71 69 64 82 78 76 75 73 68
16
2800 1321 77 71 69 68 66 61
3400 1605 70 65 64 62 58 52 75 70 68 66 64 58 82 75 74 72 70 65 86 79 77 76 74 69
4000 1888 73 68 67 64 61 55 77 72 70 68 65 60 84 77 75 74 71 66 89 80 78 77 75 70
0.5" Inlet Pressure
Ps
-12
Watts.
1, 2, 4
- valve only (continued)
5
1.0" Inlet Pressure
Ps
5
1.5" Inlet Pressure
Ps
3
2.0" Inlet Pressure
Ps
5
3.0" Inlet Pressure
Ps
5
Table 96. Radiated sound power (dB)
Inlet
Fan
Size
Size
02SQ 5 250 118 50 48 46 42 38 30
02SQ 6
02SQ 8
Cfml/s234567234567234567234567234567
(in)
200 94 48 40 38 35 31 25 48 44 42 37 33 26 53 48 47 43 38 33 54 50 47 44 41 37
300 142 51 45 42 35 29 24 54 49 46 39 33 26 57 51 50 44 38 32 60 55 53 48 42 37
400 189 54 48 46 38 32 25 58 53 49 42 35 26 60 54 51 44 37 29 61 55 52 47 40 33 63 57 55 49 43 37
500 236 52 50 48 40 33 27 62 56 52 45 37 29 65 59 56 50 42 34 65 60 57 52 45 38
350 165 53 45 40 37 31 23 55 49 44 39 35 30 60 53 50 45 41 36 62 55 52 48 45 40
520 245 57 49 44 40 34 26 59 53 48 42 37 31 64 57 53 47 43 38 66 59 56 51 46 41
700 330 61 53 48 43 37 29 63 57 52 46 40 33 66 59 55 48 43 39 68 61 57 50 45 40 70 63 60 54 48 42
900 425 66 58 53 47 41 33 68 62 56 50 44 37 72 65 61 53 48 42 73 67 63 56 50 44
0.5" Inlet Pressure
Ps
1, 2, 4
- valve only
5
1.0" Inlet Pressure
Ps
5
1.5" Inlet Pressure
Ps
3
2.0" Inlet Pressure
Ps
5
3.0" Inlet Pressure
Ps
5
VAV-PRC012-EN 77
Acoustics Data
Table 96. Radiated sound power (dB)
Inlet
Fan
Size
Size
(in)
02SQ 10
03SQ 6
03SQ 04SQ
03SQ 04SQ
10
05SQ
03SQ 04SQ
12
05SQ
04SQ
14
05SQ
06SQ
10
07SQ
06SQ
12
07SQ
Cfml/s234567234567234567234567234567
550 260 57 50 44 39 32 25 61 54 48 42 36 28 65 58 52 46 40 34 67 60 56 50 43 38
"820 387 59 52 46 41 34 25 64 58 52 46 40 31 69 63 56 51 44 37 71 66 60 54 47 40
1100 519 62 56 50 44 41 26 66 61 54 49 42 33 70 64 58 52 45 36 72 66 60 54 48 39 75 68 63 57 51 42
1400 661 65 60 53 47 44 30 68 64 57 52 45 36 74 69 63 57 50 41 77 71 66 60 53 44
100 47 49 44 38 37 31 24 50 46 41 41 35 29 52 47 44 46 41 36 53 48 45 48 45 40
200 94 50 44 39 37 31 24 53 48 43 41 36 29 56 51 47 46 42 36 59 53 49 49 45 40
300 142 52 45 40 38 31 25 54 50 45 42 36 30 59 53 50 47 42 37 60 55 53 49 45 40
400 189 54 47 42 39 33 26 57 53 48 44 38 31 59 55 51 46 41 35 61 55 52 48 43 38 62 57 55 50 46 41
600 283 58 53 50 45 40 34 58 56 54 48 42 35 64 61 58 51 45 39 67 62 60 53 48 42
175 83 52 45 39 36 33 26 54 47 42 41 36 30 57 50 45 46 42 36 59 52 46 49 45 39
350 165 57 50 43 38 33 26 59 52 46 42 37 30 61 54 50 47 43 37 63 55 52 50 46 40
525 248 58 51 45 39 34 27 61 55 48 43 38 31 64 57 53 48 44 37 66 58 56 51 47 41
8
700 330 60 53 47 42 36 30 63 56 51 45 39 33 64 58 53 47 42 35 66 60 55 49 44 37 68 62 58 52 48 41
1050 496 63 59 55 49 42 35 68 62 57 51 45 38 72 65 60 54 48 41 74 67 63 56 50 43
275 130 55 49 43 38 34 27 57 51 45 42 37 30 58 53 48 47 43 36 59 54 50 50 46 40
550 260 59 54 47 40 34 28 61 56 50 45 39 34 63 58 53 51 45 41 64 60 56 54 51 44
825 389 61 55 49 42 36 29 63 58 53 46 40 35 66 61 57 51 46 41 69 64 60 54 50 44
1100 519 62 56 50 44 38 32 66 60 54 49 43 37 68 62 57 51 46 40 70 64 59 53 48 43 72 66 62 56 51 46
1640 774 65 61 55 50 43 37 70 65 58 53 46 40 76 69 64 58 51 45 79 72 67 61 55 49
385 182 52 47 42 40 36 30 55 50 45 43 40 35 59 53 48 47 44 39 61 55 50 50 47 42
775 366 59 51 45 40 35 28 63 55 48 43 38 33 66 59 52 48 44 39 69 62 56 52 48 42
1160 547 63 54 47 41 35 30 67 58 51 46 39 35 72 63 56 51 45 40 75 67 60 54 49 43
1550 732 66 58 50 43 37 31 71 62 54 48 42 36 75 66 59 53 46 41 78 70 63 56 50 44
1600 755 73 64 57 51 44 39
2350 1109 69 64 55 49 42 36 74 68 59 52 45 40 79 72 64 57 50 44 82 75 67 60 54 47
525 248 58 51 45 40 34 27 61 53 48 44 38 31 64 56 51 49 44 37 66 59 54 51 47 40
1050 496 62 56 49 42 37 30 66 59 52 46 42 34 71 63 57 51 46 39 74 66 60 54 49 42
1575 743 65 59 52 44 37 31 70 62 55 48 42 35 75 67 61 54 48 40 78 70 64 57 51 43
2100 991 67 60 54 45 38 33 72 64 58 50 43 36 75 66 60 53 46 40 78 69 63 56 49 43 83 74 68 61 54 46
3200 1510 72 66 59 51 44 38 77 70 63 55 48 42 83 75 68 60 53 47 86 78 71 63 56 50
550 260 51 44 42 40 37 32 54 49 45 44 42 38 58 55 49 49 48 45 61 58 52 52 52 49
800 378 53 48 43 41 37 32 57 52 47 45 42 38 62 58 52 50 48 45 65 61 55 53 52 49
1000 472 55 51 44 42 38 33 59 55 48 46 42 38 65 61 54 51 48 45 68 63 57 54 52 49
1100 519 63 59 53 49 46 42
1200 566 58 53 47 43 38 33 62 58 51 47 42 38 67 63 56 52 48 45 70 65 59 56 52 49
1350 637 60 55 49 44 39 34 64 60 53 48 43 39 69 65 58 53 49 45 72 67 61 57 53 49
800 378 58 50 44 40 33 26 62 55 49 45 38 31 66 60 54 50 43 36 68 63 56 52 46 39
1100 519 60 52 46 40 33 27 65 58 51 47 40 33 70 64 58 53 46 39 72 66 60 56 50 42
1400 661 62 54 46 40 34 27 67 60 53 48 41 34 73 66 60 55 48 41 75 69 64 58 52 44
1600 755 73 65 58 53 46 40
1700 802 64 56 48 42 34 28 68 62 54 48 41 35 76 68 61 56 49 42 78 72 66 60 54 46
2000 944 65 58 49 47 36 31 70 63 55 50 42 35 77 70 62 57 50 43 79 73 67 61 55 48
0.5" Inlet Pressure
Ps
5
1, 2, 4
- valve only (continued)
1.0" Inlet Pressure
Ps
5
1.5" Inlet Pressure
Ps
3
2.0" Inlet Pressure
Ps
5
3.0" Inlet Pressure
Ps
5
78 VAV-PRC012-EN
Acoustics Data
5
Watts.
1, 2, 4
- valve only (continued)
1.0" Inlet Pressure
Ps
5
Table 96. Radiated sound power (dB)
Inlet
Fan
Size
Size
06SQ 07SQ
06SQ 07SQ
Notes:
1. All data are measured in accordance with Industry Standard AHRI 880-2011.
2. All sound power levels, dB re: 10
3. Data in this column constitute AHRI 880-2011 Standard Rating Conditions
4. Where Ps is the inlet static pressure minus discharge static.
5. Application ratings are outside the scope of the certification program.
Cfml/s234567234567234567234567234567
(in)
1100 519 56 49 44 40 32 25 61 55 48 44 38 30 66 61 54 49 43 36 69 66 57 51 45 40
1600 755 59 53 47 42 35 27 65 59 52 48 41 33 70 64 58 53 46 39 74 68 61 55 49 42
2100 991 64 57 51 46 38 29 68 61 55 50 43 35 72 64 58 53 46 38 74 67 61 55 49 41 77 70 64 59 52 45
14
2500 1180 67 59 53 48 40 31 71 63 57 52 44 36 76 68 62 56 50 42 79 72 66 60 54 46
3000 1416 71 62 56 50 42 33 74 66 59 54 46 38 78 70 64 58 51 44 82 74 68 62 56 48
1400 661 63 54 48 41 36 29 67 59 53 46 42 35 70 66 58 52 48 40 72 70 61 54 50 43
2100 991 66 57 51 44 39 32 71 63 56 49 45 38 75 69 63 56 52 44 77 72 66 59 55 47
2700 1274 68 60 54 46 41 34 73 65 59 51 47 40 78 72 66 59 54 47 80 75 69 62 58 50
16
2800 1321 76 69 62 55 51 44
3400 1605 70 63 57 51 46 42 76 68 61 54 48 42 81 74 68 60 56 48 83 76 70 64 59 52
4000 1888 73 66 60 56 52 50 78 70 63 56 50 45 83 75 70 62 57 50 85 78 72 65 60 53
0.5" Inlet Pressure
Ps
-12
Table 97. Fan only sound power
Outlet
Fan CFMl/s234567234567
02SQ 0.25
03SQ 0.25
04SQ 0.25
05SQ 0.25
SP
200 94 59 51 50 46 42 35 63 55 53 50 44 37
280 132 61 53 51 48 44 38 65 57 54 52 46 40
350 165 62 54 52 50 46 40 66 58 55 52 48 42
430 203 65 56 54 52 49 43 68 60 57 54 50 45
(a)
500
1090
1100 519 69 63 64 60 56 55 72 66 64 60 57 55
1300
1350 637 72 66 66 65 60 59 75 69 67 64 61 60
1300 614 68 64 66 63 58 57 71 67 65 62 59 57
1550
236 66 57 55 53 50 46 69 61 58 56 52 48
250 118 57 50 51 45 40 39 61 55 53 49 42 35
400 189 60 52 53 46 42 41 64 56 55 51 45 40
610 288 67 59 57 53 48 47 70 62 60 56 51 48
850 401 69 60 60 56 52 51 72 63 62 59 55 53
(a)
514 74 65 65 63 58 58 77 68 66 64 60 59
300 142 59 52 52 47 41 38 61 56 54 49 43 34
530 250 60 54 55 50 45 42 63 57 56 51 47 41
790 373 66 59 59 55 50 48 69 62 60 56 52 49
(a)
614 71 65 66 64 59 58 74 68 66 63 60 59
350 165 60 53 54 46 40 37 63 57 54 48 42 35
650 307 62 56 57 50 45 42 65 60 57 51 47 43
970 458 65 61 62 57 51 50 68 63 62 57 53 51
(a)
732 70 66 67 66 61 60 74 69 68 65 62 61
1.5" Inlet Pressure
Ps
3
2.0" Inlet Pressure
Ps
5
3.0" Inlet Pressure
Discharge Lw (dB) Radiated Lw (dB)
Octave Bands Octave Bands
Ps
5
VAV-PRC012-EN 79
Acoustics Data
Table 97. Fan only sound power (continued)
Discharge Lw (dB) Radiated Lw (dB)
920 434 66 61 60 56 51 48 71 64 62 56 51 47
1200 566 69 64 61 59 54 51 73 65 63 59 53 51
06SQ 0.25
07SQ 0.25
06SQ ECM 0.25
Notes:
1. All data are measured in accordance with Industry Standard AHRI 880-2011.
2. all sound power levels, dB re: 10
3. application ratings are outside the scope of the certification program
(a) AHRI 880-2011 section 7.2 Standard Rating Conditions
1400 661 71 65 63 61 56 54 75 67 64 60 55 53
1700 802 73 68 65 63 58 57 77 69 66 63 58 56
(a)
1960
925 75 70 68 66 62 60 79 71 67 64 61 59
1050 496 62 61 61 55 49 46 67 61 62 56 50 46
1300 614 65 65 62 58 53 50 69 64 66 58 54 50
1500 708 67 67 64 61 56 53 70 65 68 60 56 52
1800 850 69 68 68 65 60 57 73 68 68 63 59 56
(a)
2020
953 70 69 69 66 62 59 74 69 69 65 61 58
800 378 68 61 60 57 51 49 71 65 63 57 52 49
1100 519 71 64 62 59 54 52 73 66 64 58 54 51
1500 708 74 67 65 63 58 56 76 70 66 62 57 55
1800 850 76 69 67 66 60 58 78 72 67 64 60 58
2100 991 78 71 69 68 63 62 80 74 69 66 63 61
-12
Watts
Table 98. Sound noise criteria (NC) - fan only
Fan-Only
0.25" Disch. Pres.
Fan Outlet SP CFM l/s Discharge Radiated
200 94 -- 27
280 132 -- 29
02SQ 0.25
03SQ 0.25
04SQ 0.25
05SQ 0.25
350 165 -- 30
430 203 17 33
(a)
500
236 19 34
250 118 -- 27
400 189 -- 30
610 288 17 35
850 401 20 38
(a)
1090
514 26 44
300 142 -- 28
530 250 -- 31
790 373 16 35
1100 519 21 39
(a)
1300
614 23 41
1350 637 24 43
350 165 -- 28
650 307 -- 32
970 458 18 37
1300 614 22 40
(a)
1550
732 24 44
80 VAV-PRC012-EN
Table 98. Sound noise criteria (NC) - fan only (continued)
Fan-Only
920 434 18 37
1200 566 21 39
06SQ 0.25
07SQ 0.25
06SQ
ECM
Notes:
1. “--” represents NC levels below NC 15.
2. NC values are calculated using modeling assumptions based on AHRI 885-2008 Appendix E.
3. application ratings are outside the scope of the certification program.
(a) AHRI 880-2011 section 7.2 Standard Rating Conditions
0.25
1400 661 23 42
1700 802 26 44
(a)
1960
1050 496 18 37
1300 614 23 41
1500 708 25 44
1800 850 26 44
(a)
2020
800 378 18 38
1100 519 22 39
1500 708 26 43
1800 850 29 45
2100 991 31 48
925 29 47
953 27 45
Acoustics Data
Table 99. AHRI 885-2008 discharge transfer function assumptions:
Octave Band
23 4 5 6 7
Small Box (<300 Cfm) -24 -28 -39 -53 -59 -40
Medium Box (300-700 Cfm) -27 -29 -40 -51 -53 -39
Large Box (>700 Cfm) -29 -30 -41 -51 -52 -39
Notes: Subtract from terminal unit sound power to determine discharge sound pressure in the space.
1. NC Values are calculated using current Industry Standard AHRI 885-2008. Radiated Transfer Function obtained from Appendix E, Type 2 Mineral Fiber Insulation.
2. Application ratings are outside the scope of the Certification Program.
Table 100. AHRI 885-2008 radiated transfer function assumptions:
Octave Band
23 4 5 6 7
Type 2- Mineral Fiber Insulation -18 -19 -20 -26 -31 -36
Total dB reduction -18 -19 -20 -26 -31 -36
Notes: Subtract from terminal unit sound power to determine discharge sound pressure in the space.
1. NC Values are calculated using current Industry Standard AHRI 885-2008. Radiated Transfer Function obtained from Appendix E, Type 2 Mineral Fiber Insulation.
2. Application ratings are outside the scope of the Certification Program.
VAV-PRC012-EN 81
Acoustics Data
Table 101. Sound noise criteria (NC) - valve only
Discharge
Fan Size
02SQ 5 250 118 21 20
02SQ 6
02SQ 8
02SQ 10
03SQ 6
03SQ 04SQ
03SQ 04SQ
03SQ 04SQ 05SQ
04SQ 05SQ
Size (in)
8
10
12
14
CFM l/s 0.5” 1.0” 1.5” 2.0” 3.0” 0.5” 1.0” 1.5” 2.0” 3.0”
200 94 -- -- -- 20 -- 15 21 21
300 142 -- -- 16 19 15 20 24 27
400 189 -- 20 20 21 23 20 23 25 26 30
500 236 16 23 25 28 22 26 31 32
350 165 -- -- 16 19 -- 18 24 26
520 245 -- 16 21 23 19 22 27 31
700 330 18 22 24 26 29 24 26 30 33 35
900 425 23 27 30 32 30 33 38 39
550 260 -- 17 23 25 19 24 29 31
820 387 16 22 29 31 21 27 34 37
1100 519 20 25 30 32 36 25 31 35 38 42
1400 661 23 29 36 40 30 34 40 44
100 47 -- -- -- 17 -- -- 18 20
200 94 -- -- -- 18 -- 16 21 23
300 142 -- -- 17 18 -- 19 24 27
400 189 -- 17 19 22 23 15 22 25 26 30
175 83 -- -- -- 17 -- 15 19 21
350 165 -- -- -- 19 19 21 24 26
525 248 -- -- 19 22 20 24 27 31
700 330 -- 18 22 24 26 22 26 27 30 33
1050 496 23 28 30 32 30 33 38 40
275 130 -- -- -- 17 17 19 22 24
550 260 -- -- 19 22 23 25 27 31
825 389 -- 18 24 28 24 27 32 35
1100 519 17 22 25 28 30 25 30 33 35 38
1640 774 24 29 34 37 31 36 43 47
385 182 -- -- -- 17 15 19 22 24
775 366 -- 16 23 25 21 26 30 34
1160 547 -- 19 26 30 26 31 38 42
1550 732 17 23 30 35 30 36 42 45
1600 755 26 39
2350 1109 24 30 35 40 34 40 47 51
525 248 -- -- 16 19 20 24 27 30
1050 496 -- 19 26 29 25 30 36 40
1575 743 16 23 31 35 29 35 42 45
2100 991 19 26 31 34 38 31 38 42 45 52
3200 1510 26 31 38 43 38 44 52 56
Inlet
Inlet Pressure (Ps)
1,2,4
3,5
Radiated
Inlet Pressure (Ps)
1,2,4
3,5
82 VAV-PRC012-EN
Table 101. Sound noise criteria (NC) - valve only (continued)
Discharge
550 260 -- -- 18 20 15 19 24 27
800 378 -- -- 20 24 16 21 27 31
06SQ 07SQ
06SQ 07SQ
06SQ 07SQ
06SQ 07SQ
Notes:
1. “--” represents NC levels below NC 15.
2. NC Values are calculated using modeling assumptions based on AHRI 885-98-02 Addendum
3. Data at 1.5” inlet pressure constitute AHRI 880-2011 Standard Rating Conditions.
4. Where Ps is the inlet static pressure minus discharge static.
5. Data at 0.5”, 1.0”, 2.0” and 3.0” are application ratings. These ratings are outside the scope of the certification program.
10
12
14
16
1000 472 -- 18 23 26 19 24 31 33
1100 519 23 28
1200 566 16 21 26 29 21 27 33 36
1350 637 18 24 29 31 24 30 36 38
800 378 -- 19 25 29 20 25 30 33
1100 519 15 24 30 33 22 29 35 38
1400 661 16 27 33 37 25 31 39 42
1600 755 32 39
1700 802 18 28 37 39 27 33 43 45
2000 944 20 29 39 42 29 35 44 47
1100 519 -- 17 24 30 18 24 31 37
1600 755 -- 21 29 32 21 29 35 40
2100 991 18 25 29 31 36 27 33 38 40 44
2500 1180 21 27 34 38 31 36 43 47
3000 1416 25 30 38 43 36 40 45 51
1400 661 -- 20 29 35 26 31 37 42
2100 991 17 24 32 36 30 36 42 44
2700 1274 20 26 33 38 33 39 45 48
2800 1321 30 43
3400 1605 23 29 37 42 35 43 49 52
4000 1888 26 31 39 46 39 45 52 54
1,2,4
Radiated
Acoustics Data
1,2,4
Table 102. Parallel inlet attenuator appurtenance effects (fan noise only)
Discharge Sound Effect* (dB) Radiated Sound Effect* (dB)
Fan
Matte-faced and foil-faced insulation, solid double-wall**
02SQ
03SQ, 04SQ, 05SQ
06SQ, 07SQ
Closed-cell insulation
02SQ
03SQ, 04SQ, 05SQ
06SQ, 07SQ
Notes:
* Add to sound power, a negative effect represents a sound reduction, a positive effect represents a sound increase. ** Note- Attenuators on double-wall units contain foil-faced insulation.
1. All data are measured in accordance with Industry Standard AHRI 880-2011.
2. All sound power levels, dB re: 10-12 Watts.
3. Application ratings are outside the scope of the Certification Program.
VAV-PRC012-EN 83
234567234567
2 2 2
1 1 1
1 1 1
1 1 1
1 1 1
1 1 1
2 2 2
1 1 1
1 1 1
1 1 1
2 2 2
1 1 1
-1
0
0
1
-1
1
-1
0
-1
1
-2
1
-8
-8
-8
-3
-3
-3
-13
-12
-12
-2
-2
-2
-15
-16
-15
-4
-4
-4
-16
-17
-18
-4
-4
-4
Acoustics Data
Table 103. Parallel cabinet lining appurtenance effects (fan noise and valve noise)
Discharge Sound Effect* (dB) Radiated Sound Effect* (dB)
Fan
Solid double-wall
02SQ
03SQ, 04SQ, 05SQ
06SQ, 07SQ
Closed-cell insulation
02SQ
03SQ, 04SQ, 05SQ
06SQ, 07SQ
Note:
* Add to sound power, a negative effect represents a sound reduction, a positive effect represents a sound increase
1. All data are measured in accordance with Industry Standard AHRI 880-2011.
2. All sound power levels, dB re: 10-12 Watts.
3. Application ratings are outside the scope of the Certification Program.
Table 104. Parallel heating coil appurtenance effects
Fan
Hot Water Coil**
02SQ
03SQ, 04SQ, 05SQ
06SQ, 07SQ
Electric Heat***
02SQ
03SQ, 04SQ, 05SQ
06SQ, 07SQ
Notes:
* Add to sound power, a negative effect represents a sound reduction, a positive effect represents a sound increase. ** Add to fan sound only, not valve sound. ***Add to both fan sound and valve sound.
Apply fan only data, not valve sound.
1. All data are measured in accordance with Industry Standard AHRI 880-2011.
2. All sound power levels, dB re: 10-12 Watts.
3. Application ratings are outside the scope of the Certification Program.
2345672 3 4567
3
3 1 3
1 1 1
1
-1 1
1 1 1
1 1 1
1 2 2
-1 3 1
0 2 1
1
5
4
5
3
4
1
3
2
4
2
1 1
-1
0 1 1
0 0
-1
0 2 0
Discharge Sound Effect* (dB) Radiated Sound Effect* (dB)
2345 6 7 2 34 5 6 7
-1
-1 2 2
0 0 3
0 2 1
0 0 4
-1 2 0
0 0 3
2
-1
-1
0 2
0 2 0
-2 0 4
-1 1 0
-1 1 4
-1 1 0
0 0 1
-1 1 0
0 0 0
0 2
-1
2 4 3
0 1 0
0 0 0
1 5 2
2 4 4
-1 1
-1
0 0 0
-1 0 0
0 0 0
8
8
5
4
7
5
5
4
6
5
-3 0
-1
0 0 0
7
4
84 VAV-PRC012-EN

Series Fan-PoweredTerminal Units

Table 105. Discharge sound power (dB)- fan and 100% primary
Acoustics Data
Fan
Inlet
Size
Size (in)
02SQ 10
03SQ 10
04SQ 12
05SQ 12
06SQ 16
07SQ 16
0.5” Inlet Pressure Ps 1.0” Inlet Pressure Ps 2.0” Inlet Pressure Ps 3.0” Inlet Pressure Ps
Cfm l/s 234567234567234567234567
200 94 71 55 54 52 49 45 72 61 56 54 52 51 74 70 66 62 59 55 74 64 63 61 59 59
300 142 71 56 55 52 49 46 72 61 57 54 52 52 74 69 65 61 58 56 75 67 66 63 60 60
500 236 71 57 56 52 49 47 72 61 58 54 52 53 74 68 64 60 57 59 76 74 73 67 63 63
600 283 72 60 59 55 52 50 74 63 60 56 54 55 75 67 64 60 58 59 76 72 69 64 61 62
700 330 73 62 61 57 55 53 75 64 61 58 56 56 75 66 63 59 58 58 76 69 64 61 59 60
250 118 57 49 47 43 38 34 57 50 48 43 39 34 58 52 48 44 40 36 59 53 48 45 41 39
480 227 61 53 52 49 45 43 62 55 53 49 46 43 63 57 53 49 46 44 64 59 53 50 47 45
720 340 66 58 58 55 53 52 68 60 59 56 54 52 68 63 58 55 53 52 70 65 59 55 53 52
960 453 71 63 63 61 59 59 72 64 63 62 59 59 74 67 64 62 60 60 74 68 64 62 60 59
1200 566 76 67 67 66 64 65 77 68 67 66 64 64 79 71 68 67 65 65 79 72 68 68 65 65
330 156 58 52 49 45 39 34 59 53 49 45 40 35 62 57 50 46 40 38 63 59 51 46 42 40
620 293 62 55 54 51 46 43 63 57 54 51 47 44 67 62 55 52 47 46 68 64 55 52 48 47
930 439 66 59 59 57 54 53 68 61 59 57 55 53 72 67 60 58 55 54 73 69 60 58 55 54
1250 590 72 64 64 63 60 60 74 66 65 64 61 61 76 69 65 65 62 62 78 72 66 65 63 62
1550 732 77 69 68 68 66 66 77 70 68 69 66 66 80 72 69 70 67 67 81 75 70 70 68 67
400 189 56 52 52 46 40 38 57 53 52 47 41 39 59 54 52 47 42 40 60 56 53 48 43 41
760 359 61 58 58 54 49 48 62 58 57 54 49 48 65 60 57 53 49 48 66 62 58 54 50 48
1140 538 67 64 64 62 59 58 67 63 63 61 58 57 71 66 63 60 57 56 73 69 64 61 58 56
1500 708 73 69 69 68 65 64 73 69 69 67 65 64 75 70 69 68 65 64 77 72 69 68 65 64
1900 897 77 74 73 74 71 71 78 74 73 74 71 70 79 74 73 73 70 70 79 75 73 73 70 70
700 330 57 53 53 49 46 41 70 59 55 52 51 50 75 71 65 62 56 56 78 71 69 65 60 58
1200 566 63 59 58 55 52 48 72 63 60 57 55 54 77 72 67 64 60 60 80 75 71 67 64 62
1600 755 69 63 62 59 56 54 74 67 64 61 59 58 79 74 69 66 62 62 82 77 73 69 66 64
2100 991 75 69 67 65 62 61 77 71 69 66 63 62 81 76 72 69 66 66 84 80 75 72 70 68
2500 1180 77 72 69 67 65 64 79 74 71 69 66 65 83 78 74 71 69 68 86 82 77 74 72 70
850 401 62 58 51 53 47 51 66 60 53 54 47 52 69 63 56 56 52 58 75 69 62 59 54 63
1400 661 65 61 59 56 52 53 69 63 61 57 55 57 74 68 64 59 57 61 77 72 67 62 59 63
1900 897 69 66 65 61 58 57 73 67 66 61 59 60 77 71 68 63 61 63 80 75 70 65 63 64
2250 1062 72 69 68 64 62 61 75 70 69 64 62 62 79 73 71 65 64 65 82 77 72 67 65 66
2500 1180 74 71 71 67 65 63 76 72 71 67 65 65 79 74 73 67 66 67 83 77 73 69 67 67
3000 1416 77 75 75 71 69 68 79 75 75 71 69 69 81 77 76 71 70 70 85 79 76 72 70 70
275 130 56 51 49 44 38 37 57 52 49 44 38 38 58 53 49 44 39 39 59 55 50 45 41 40
620 293 61 55 54 51 46 45 63 57 54 51 47 46 65 60 55 51 47 47 66 62 55 52 48 47
04SQ
ECM
12
930 439 66 59 59 57 54 53 68 61 59 57 55 53 72 67 60 58 55 54 73 69 60 58 55 54
1250 590 72 64 64 63 60 60 74 66 65 64 61 61 76 69 65 65 62 62 78 72 66 65 63 62
1550 732 77 69 68 68 66 66 77 70 68 69 66 66 80 72 69 70 67 67 81 75 70 70 68 67
1660 783 79 71 69 70 68 68 78 71 69 71 68 68 81 73 70 72 69 69 82 76 71 72 70 69
VAV-PRC012-EN 85
Acoustics Data
Table 105. Discharge sound power (dB)- fan and 100% primary (continued)
Fan
Inlet
Size
Size (in)
05SQ
ECM
06SQ
ECM
Notes:
1. All data are measured in accordance with Industry Standard AHRI 880-2011.
2. All sound power levels, dB re: 10
3. Where Ps is the inlet static pressure minus discharge static.
4. Application ratings are outside the scope of the certification program.
Cfm l/s 234567234567234567234567
350 165 57 51 50 45 39 39 57 52 50 45 40 39 57 53 49 46 40 40 59 54 50 47 42 41
760 359 62 58 57 54 49 49 62 58 57 53 49 48 64 60 56 53 49 48 66 62 57 54 50 49
1140 538 67 64 64 62 59 58 67 63 63 61 58 57 71 66 63 60 57 56 73 69 64 61 58 56
14
1500 708 73 69 69 68 65 64 73 69 69 67 65 64 75 70 69 68 65 64 77 72 69 68 65 64
1900 897 77 74 73 74 71 71 78 74 73 74 71 70 79 74 73 73 70 70 79 75 73 73 70 70
2350 1109 81 78 77 78 76 76 82 78 77 78 76 76 83 79 77 78 76 76 83 79 77 78 76 76
700 330 57 53 53 49 46 41 70 59 55 52 51 50 75 71 65 62 56 56 78 71 69 65 60 58
1200 566 63 59 58 55 52 48 72 63 60 57 55 54 77 72 67 64 60 60 80 75 71 67 64 62
1600 755 69 63 62 59 56 54 74 67 64 61 59 58 79 74 69 66 62 62 82 77 73 69 66 64
16
2100 991 75 69 67 65 62 61 77 71 69 66 63 62 81 76 72 69 66 66 84 80 75 72 70 68
2500 1180 77 72 69 67 65 64 79 74 71 69 66 65 83 78 74 71 69 68 86 82 77 74 72 70
1500 708 75 74 70 68 64 63 76 74 70 69 64 63
Table 106. Radiated sound power (dB)
Inlet
Fan
Size
Size
02SQ 10
03SQ 10
04SQ 12
05SQ 12
Cfml/s234567234567234567234567234567
(in)
200 94 65 53 53 52 49 45 66 59 55 54 52 51 68 68 65 62 59 55 68 62 62 61 59 59
300 142 65 54 54 52 49 46 66 59 56 54 52 52 68 67 64 61 58 56 69 65 65 63 60 60
500 236 65 55 55 52 49 47 66 59 57 54 52 53 68 66 63 60 57 59 70 72 72 67 63 63
600 283 66 58 58 54 52 50 68 60 58 56 54 54 69 66 63 60 58 60 71 72 70 66 62 63
700 330 67 60 60 57 55 53 69 62 60 58 56 56 69 64 61 59 57 58 70 67 63 61 59 60 72 71 68 66 62 63
250 118 53 49 47 44 40 35 56 51 49 47 44 42 58 54 53 52 49 48 59 56 56 55 52 52
480 227 58 54 52 49 45 42 61 56 53 51 48 48 63 59 57 55 52 53 65 62 60 58 55 56
720 340 63 59 57 54 51 50 66 61 58 55 53 54 69 65 61 58 56 59 71 68 64 61 58 61
960 453 68 63 61 59 57 57 71 65 63 60 58 59 73 69 65 62 59 62 74 71 68 64 61 63
1100 519 74 69 66 63 61 63
1200 566 72 67 65 63 61 62 75 69 66 64 62 63 77 72 68 66 63 65 78 74 70 67 64 66
330 156 56 51 49 44 41 37 58 54 52 47 46 47 62 58 56 53 51 53 64 60 59 57 54 56
620 293 60 55 54 49 46 44 62 58 55 51 50 51 67 63 60 56 54 57 69 65 63 60 57 60
930 439 64 60 59 54 52 51 67 62 59 55 54 56 73 68 64 59 58 62 74 71 67 63 60 65
1250 590 69 65 63 59 58 57 72 66 64 60 59 60 76 71 66 62 61 65 78 74 69 65 63 67
1500 708 77 71 68 65 64 65
1550 732 74 69 67 65 63 63 76 71 68 65 64 64 79 73 69 66 65 67 80 76 72 68 66 68
400 189 57 54 50 45 44 40 60 56 53 49 50 50 63 60 57 53 52 55 65 62 60 57 54 57
760 359 61 58 55 51 50 47 64 60 57 53 54 54 68 64 60 56 55 59 70 67 64 60 57 61
1140 538 65 63 60 57 56 54 68 65 61 58 58 58 73 69 64 60 59 63 75 73 68 63 61 65
1500 708 69 67 65 63 62 60 72 69 65 63 62 62 76 72 68 64 63 65 78 75 70 66 65 67
1900 897 74 72 69 68 67 66 76 73 70 69 67 67 76 73 70 68 67 67 79 75 71 68 67 68 81 77 72 69 68 69
0.5” Inlet Pressure Ps 1.0” Inlet Pressure Ps 2.0” Inlet Pressure Ps 3.0” Inlet Pressure Ps
-12
Watts.
1,2,4
- fan and 100% primary
0.5” Inlet Pressure
Ps
5
1.0” Inlet Pressure
Ps
5
1.5” Inlet Pressure
Ps
3
2.0” Inlet Pressure
Ps
5
3.0” Inlet Pressure
Ps
5
86 VAV-PRC012-EN
Acoustics Data
5
Watts.
1,2,4
- fan and 100% primary (continued)
1.0” Inlet Pressure
Ps
5
Table 106. Radiated sound power (dB)
Inlet
Fan
Size
Size
06SQ 16
07SQ 16
04SQ
ECM
05SQ
ECM
06SQ
ECM
Notes:
1. All data are measured in accordance with Industry Standard AHRI 880-2011.
2. All sound power levels, dB re: 10
3. Data in this column constitute AHRI 880-2011 Standard Rating Conditions.
4. Where Ps is the inlet static pressure minus discharge static.
5. Application ratings are outside the scope of the certification program.
Cfml/s234567234567234567234567234567
(in)
700 330 54 52 53 49 46 41 67 58 55 52 51 50 72 70 65 62 56 56 75 70 69 65 60 58
1200 566 60 58 58 55 52 48 69 62 60 57 55 54 74 71 67 64 60 60 77 74 71 67 64 62
1600 755 66 62 62 59 56 54 71 66 64 61 59 58 76 73 69 66 62 62 79 76 73 69 66 64
2100 991 72 68 67 65 62 61 74 70 68 66 63 62 78 74 72 69 66 66 81 79 75 72 70 68
2500 1180 74 71 69 67 65 64 76 73 70 69 66 65 78 75 72 70 68 67 80 76 74 71 69 68 83 81 77 74 72 70
850 401 59 57 51 53 47 51 63 59 53 54 47 52 66 62 56 56 52 58 72 68 62 59 54 63
1400 661 62 60 59 56 52 53 66 62 61 57 55 57 71 67 64 59 57 61 74 71 67 62 59 63
1900 897 66 65 65 61 58 57 70 66 66 61 59 60 74 70 68 63 61 63 77 74 70 65 63 64
2250 1062 69 68 68 64 62 60 72 69 69 64 62 62 75 72 71 65 64 65 79 75 72 67 65 66
2500 1180 71 70 71 67 65 63 73 71 71 67 65 65 76 73 73 67 66 67 80 76 73 69 67 67
2800 1321 76 74 74 69 68 68
3000 1416 74 74 75 71 69 68 76 74 75 71 69 69 78 76 76 71 70 70 82 78 76 72 70 70
275 130 56 52 49 44 41 38 59 54 52 47 46 47 62 58 56 53 51 52 64 60 59 56 54 56
620 293 60 56 54 49 47 45 63 58 56 51 50 52 68 63 60 56 55 57 69 66 63 60 57 61
930 439 64 60 59 54 52 51 67 62 59 55 54 56 73 68 64 59 58 62 74 71 67 63 60 65
12
1250 590 69 65 63 59 58 57 72 66 64 60 59 60 76 71 66 62 61 65 78 74 69 65 63 67
1550 732 74 69 67 65 63 63 76 71 68 65 64 64 79 73 69 66 65 67 80 76 72 68 66 68
1660 783 76 70 68 67 65 65 77 73 69 67 66 65 80 74 70 67 66 68 81 77 73 69 67 68
350 165 53 50 48 46 42 38 55 52 50 48 46 47 57 55 54 53 51 51 60 58 57 56 54 55
760 359 58 56 54 51 49 46 61 58 56 53 51 52 64 61 59 57 55 57 66 64 62 59 58 60
1140 538 63 62 60 56 55 53 66 63 61 57 56 57 71 67 63 60 59 62 72 70 66 62 61 64
14
1500 708 69 67 65 62 61 60 70 67 65 62 62 61 72 68 66 63 62 63 73 70 66 64 63 65
1900 897 73 71 69 68 66 66 74 71 69 67 66 66 76 73 69 68 67 68 77 75 71 68 67 69
2350 1109 75 74 72 72 71 71 77 75 72 72 71 71 79 77 73 72 72 72 81 78 74 73 72 73
700 330 54 52 53 49 46 41 67 58 55 52 51 50 72 70 65 62 56 56 75 70 69 65 60 58
1200 566 60 58 58 55 52 48 69 62 60 57 55 54 74 71 67 64 60 60 77 74 71 67 64 62
1600 755 66 62 62 59 56 54 71 66 64 61 59 58 76 73 69 66 62 62 79 76 73 69 66 64
16
2100 991 72 68 67 65 62 61 74 70 68 66 63 62 78 74 72 69 66 66 81 79 75 72 70 68
2500 1180 74 71 69 67 65 64 76 73 70 69 66 65 80 76 74 71 69 68 83 81 77 74 72 70
0.5” Inlet Pressure
Ps
-12
1.5” Inlet Pressure
Ps
3
2.0” Inlet Pressure
Ps
5
3.0” Inlet Pressure
Ps
5
VAV-PRC012-EN 87
Acoustics Data
Table 107. Fan only sound power (dB)
Fan
02SQ 0.25
03SQ 0.25
04SQ 0.25
05SQ 0.25
06SQ 0.25
07SQ 0.25
03SQ
ECM
Outlet
SP
0.25
CFMl/s234567234567
200 94 64 53 52 46 41 33 56 49 47 43 36 28
300 142 65 52 51 47 42 34 57 48 48 44 39 32
500 236 70 58 56 54 50 47 61 56 54 50 47 43
600 283 73 61 59 57 53 52 64 59 57 53 50 48
(a)
690
700 330 76 64 61 60 56 55 66 62 60 56 53 51
250 118 57 50 48 45 40 34 52 49 47 43 37 28
480 227 60 52 54 49 45 41 55 52 51 47 42 39
720 340 64 56 58 54 52 51 60 57 56 53 50 49
960 453 71 62 63 61 59 58 67 63 61 59 56 56
1100
1200 566 76 67 67 67 64 64 73 67 65 63 61 62
330 156 58 51 48 45 40 34 56 51 48 42 37 30
620 293 61 54 53 51 47 44 59 54 53 47 44 40
930 439 66 59 59 58 54 53 63 58 58 53 51 49
1250 590 74 66 65 65 62 61 69 64 63 59 58 56
1500
1550 732 78 71 68 69 66 66 75 69 66 64 63 62
400 189 58 54 52 48 42 39 54 52 51 44 40 33
760 359 62 57 56 54 50 48 58 56 53 49 47 43
1140 538 68 63 64 62 59 58 63 62 60 57 55 52
1500 708 73 69 69 68 65 65 69 67 64 62 60 59
1900 897 78 73 73 73 70 70 73 71 68 67 66 65
700 330 57 56 52 50 44 39 58 55 52 47 41 34
1200 566 59 58 57 55 51 49 60 58 58 51 47 44
1600 755 64 62 62 61 57 56 63 62 62 57 53 51
2100 991 69 67 67 67 64 64 68 67 66 62 60 59
2500
850 401 57 61 53 50 45 41 55 56 52 48 41 36
1400 661 63 67 59 56 54 54 59 62 58 54 50 48
1900 897 68 69 65 62 60 61 63 64 64 60 56 55
2250 1062 71 72 69 66 64 65 66 67 68 64 61 59
2500 1180 73 74 72 69 67 68 69 69 70 66 64 62
2800
3000 1416 76 76 76 73 71 72 71 72 72 70 68 67
200 94 56 49 47 44 38 37 51 48 48 42 35 34
480 227 58 51 53 48 45 43 53 50 51 46 42 40
720 340 64 56 57 54 52 51 57 55 55 51 49 47
960 453 71 63 63 62 59 59 67 62 61 59 56 56
1175 555 76 67 67 66 63 63 70 66 64 62 60 60
326 76 64 61 59 56 55 66 61 59 56 53 51
(a)
519 74 65 65 64 62 62 70 65 64 61 59 60
(a)
708 77 70 68 68 65 65 74 68 66 63 62 61
(a)
1180 73 71 71 71 69 69 72 71 69 66 64 63
(a)
1321 75 75 74 72 69 70 70 71 71 68 66 65
Discharge Lw (dB) Radiated Lw (dB)
Octave Bands Octave Bands
88 VAV-PRC012-EN
Table 107. Fan only sound power (dB)
Discharge Lw (dB) Radiated Lw (dB)
Fan
04SQ
ECM
05SQ
ECM
06SQ
ECM
Notes:
1. All data are measured in accordance with Industry Standard AHRI 880-2011.
2. all sound power levels, dB re: 10
3. application ratings are outside the scope of the certification program
(a) xAHRI 880-2011 section 7.2 Standard Rating Conditions
SP
0.25
0.25
0.25
CFMl/s234567234567
275 130 56 51 48 45 39 37 52 49 48 42 37 35
620 293 60 54 55 51 48 47 55 52 52 48 45 43
930 439 63 59 59 57 55 55 59 58 58 54 53 52
1250 590 70 65 65 65 63 63 65 64 64 61 60 59
1550 732 76 71 69 69 67 68 68 67 67 65 64 63
1660 783 78 73 70 70 68 70 69 68 68 66 65 64
350 165 57 52 50 46 40 39 52 49 47 43 38 34
760 359 60 55 55 52 49 48 56 52 51 48 46 43
1140 538 65 61 62 60 57 57 61 59 58 55 54 52
1500 708 72 67 68 66 64 64 67 65 63 61 61 60
(a)
1900
2350 1109 82 77 76 77 75 76 76 75 72 71 71 71
700 330 56 52 53 51 45 44 56 50 50 46 43 36
1200 566 60 57 57 55 50 49 57 54 55 51 48 45
1600 755 63 61 61 59 55 55 60 57 60 56 52 51
2100 991 69 67 67 66 62 63 66 63 64 62 59 58
2500
897 77 72 72 72 70 70 72 70 68 67 66 66
(a)
1180 73 71 70 70 66 67 70 67 68 66 63 62
-12
Watts
Outlet
Octave Bands Octave Bands
Acoustics Data
Table 108. Sound noise criteria (NC) fan and 100% primary
Fan
Size
02SQ 500 236 25 26 28 35 30 32 38 48
03SQ 10
04SQ 12
Size (in)
10
CFM l/s 0.5” 1.0” 2.0” 3.0” 0.5” 1.0” 1.5” 2.0” 3.0”
200 94 25 26 30 28 29 30 40 37
300 142 25 26 29 30 29 31 39 40
600 283 26 28 30 32 33 33 38 46
700 330 27 30 30 31 35 35 36 38 44
250 118 -- -- -- -- 21 23 27 31
480 227 -- -- -- 16 26 27 32 35
720 340 16 18 21 23 32 33 36 39
960 453 23 24 26 27 36 38 40 44
1100 519 41
1200 566 29 30 33 33 40 42 44 46
330 156 -- -- -- 16 23 26 31 34
620 293 -- -- 19 22 28 30 35 38
930 439 17 18 25 28 34 34 39 43
1250 590 24 26 29 31 38 39 43 46
1500 708 44
1550 732 30 30 34 35 43 44 47 49
Inlet
Discharge Radiated
Inlet Pressure (Ps) Inlet Pressure (Ps)
VAV-PRC012-EN 89
Acoustics Data
Table 108. Sound noise criteria (NC) fan and 100% primary (continued)
Fan
Size
05SQ 12
06SQ 16
07SQ 16
04SQ
ECM
05SQ
ECM
06SQ
ECM
Notes:
1. “--” represents NC levels below NC 15.
2. NC Values are calculated using modeling assumptions based on AHRI 885-98-02 Addendum
3. Data at 1.5” inlet pressure constitute AHRI 880-2011 Standard Rating Conditions.
4. Where Ps is the inlet static pressure minus discharge static.
5. Data at 0.5”, 1.0”, 2.0” and 3.0” are application ratings. These ratings are outside the scope of the certification program.
Size (in)
12
14
16
CFM l/s 0.5” 1.0” 2.0” 3.0” 0.5” 1.0” 1.5” 2.0” 3.0”
400 189 -- -- -- -- 24 27 32 35
760 359 -- -- 17 19 30 32 35 39
1140 538 22 21 24 27 35 36 40 45
1500 708 28 28 29 31 40 40 44 47
1900 897 34 33 33 35 45 46 46 47 50
700 330 -- 21 30 32 27 31 42 45
1200 566 15 24 31 34 33 35 43 47
1600 755 20 26 33 37 37 39 45 49
2100 991 28 30 36 40 43 44 48 52
2500 1180 31 33 38 43 45 46 48 50 55
850 401 -- 17 22 28 26 28 32 39
1400 661 18 21 26 31 34 36 39 43
1900 897 24 25 30 34 40 41 44 46
2250 1062 27 28 33 37 44 45 47 48
2500 1180 30 31 33 38 47 47 49 49
2800 1321 50
3000 1416 34 34 37 41 51 51 52 52
275 130 -- -- -- -- 23 26 31 34
620 293 -- -- 17 19 28 31 35 38
930 439 17 18 25 28 34 34 39 43
1250 590 24 26 29 31 38 39 43 46
1550 732 30 30 34 35 43 44 47 49
1660 783 33 31 35 36 44 45 48 50
350 165 -- -- -- -- 22 24 28 32
760 359 -- -- 17 19 28 31 34 37
1140 538 22 21 24 27 35 36 38 42
1500 708 28 28 29 31 40 40 41 42
1900 897 34 33 33 35 45 45 45 47
2350 1109 39 39 39 39 48 48 50 51
700 330 -- 21 30 32 27 31 42 45
1200 566 15 24 31 34 33 35 43 47
1600 755 20 26 33 37 37 39 45 49
2100 991 28 30 36 40 43 44 48 52
2500 1180 31 33 38 43 45 46 50 55
Inlet
Discharge Radiated
Inlet Pressure (Ps) Inlet Pressure (Ps)
Table 109. AHRI 885-2008 discharge transfer function assumptions:
Octave Band
2 3 456 7
Small Box (<300 Cfm) Medium Box (300-700 Cfm) Large Box (>700 Cfm)
Notes: Subtract from terminal unit sound power to determine discharge sound pressure in the space.
1. NC Values are calculated using modeling assumptions based on AHRI 885-2008.
2. Where DPs is inlet static pressure minus discharge static pressure.
3. Application ratings are outside the scope of the Certification Program.
-24
-27
-29
-28
-29
-30
-39
-40
-41
-53
-51
-51
-59
-53
-52
90 VAV-PRC012-EN
-40
-39
-39
Table 110. AHRI 885-2008 radiated transfer function assumptions:
Octave Band
234567
Type 2- Mineral Fiber Insulation Total dB reduction
Notes: Subtract from terminal unit sound power to determine radiated sound pressure in the space.
1. NC Values are calculated using modeling assumptions based on AHRI 885-2008.
2. Where DPs is inlet static pressure minus discharge static pressure.
3. Application ratings are outside the scope of the Certification Program.
-18
-18
-19
-19
-20
-20
-26
-26
Table 111. Series inlet attenuator appurtenance effects
Discharge Sound Effect* (dB) Radiated Sound Effect* (dB)
Fan
23456723 4 5 6 7
Matte-faced and foil-faced insulation, solid double-wall**
02SQ
03SQ, 04SQ, 05SQ
06SQ, 07SQ
2 2 2
2 2 2
2 2 2
3 3 3
3 3 3
2 2 2
-3
-1
-3
-3
1
-3
Closed-cell insulation
-2
02SQ
03SQ, 04SQ, 05SQ
06SQ, 07SQ
Notes:
* Add to sound power, a negative effect represents a sound reduction, a positive effect represents a sound increase. ** Note – Attenuators on double-wall units contain foil-faced insulation.
1. All data are measured in accordance with Industry Standard AHRI 880-2011.
2. All sound power levels, dB re: 10
3. Application ratings are outside the scope of the Certification Program.
2 2 2
-12
2 2 2
watts.
2 2 2
3 3 3
3 3 3
2 2 2
1
-2
1
-2
1
Table 112. Series cabinet lining appurtenance effects
Discharge Sound Effect* (dB) Radiated Sound Effect* (dB)
Fan
234567 2 3 4567
Solid double-wall
02SQ
03SQ, 04SQ, 05SQ
06SQ, 07SQ
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 1
0 0 3
Closed-cell insulation
02SQ
03SQ, 04SQ, 05SQ
06SQ, 07SQ
Note:
* Add to sound power, a negative effect represents a sound reduction, a positive effect represents a sound increase.
1. All data are measured in accordance with Industry Standard AHRI 880-2011.
2. All sound power levels, dB re: 10-12 watts.
3. Application ratings are outside the scope of the Certification Program.
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
-1 1 1
-1 1 5
Table 113. Series heating coil appurtenance effects
Discharge Sound Effect* (dB) Radiated Sound Effect* (dB)**
Fan
Hot Water Coil
02SQ
03SQ, 04SQ, 05SQ
06SQ, 07SQ
Electric Heat
02SQ
03SQ, 04SQ, 05SQ
06SQ, 07SQ
Notes:
* Add to sound power, a negative effect represents a sound reduction, a positive effect represents a sound increase. ** Radiated effect applies to “fan only” sound only. Do not apply to fan + valve sound.
1. All data are measured in accordance with Industry Standard AHRI 880-2011.
2. All sound power levels, dB re: 10-12 Watts.
3. Application ratings are outside the scope of the Certification Program.
2345672 3 4 567
1 1 2
-4 2 4
2 3 6
-1 1 4
2 1 4
0 2 2
1 2 4
0 1 2
2 2 4
1
-1 3
2 1 3
0
-1 1
2 0 6
-1 0 2
2 2 5
0 1 3
-9
-10
-8
-5
-5
-5
Acoustics Data
-31
-31
-10
-14
-9
-4
-4
-4
0 1 2
0 2 3
2 1 2
-1 1 3
2 2 5
1 2 4
2 2 2
0 1 4
-12
-17
-8
-6
-6
-6
-36
-36
-17
-20
-10
-6
-6
-6
3 3 8
1 2 6
3 4 8
2 2 6
2 2 2
0 1 3
2 2 3
0 1 2
VAV-PRC012-EN 91
Acoustics Data

Low Height Parallel Fan-PoweredTerminal Units

Table 114. Discharge sound power (dB)
Inlet
Fan
Size
Size
08SQ 5
08SQ 09SQ
08SQ 09SQ
09SQ8x
10SQ8x
Notes:
1. All data are measured in accordance with Industry Standard AHRI 880-2011.
2. All sound power levels, dB re: 10
3. Data in this column constitute AHRI 880-2011 Standard Rating Conditions.
4. Where Ps is the inlet static pressure minus discharge static.
5. Application ratings are outside the scope of the certification program.
Cfml/s234567234567234567234567234567
(in)
150 71 55 48 44 39 32 29 58 51 49 45 38 38 58 52 50 47 44 46 60 54 52 49 47 50
200 94 58 51 47 42 36 31 61 54 51 47 40 39 62 56 53 50 46 47 63 57 55 52 49 51
250 118 62 54 49 45 40 33 63 57 53 48 42 40 65 59 56 51 45 44 65 60 56 53 48 48 66 61 58 54 51 52
300 142 65 56 51 48 43 37 66 60 55 50 45 42 69 62 59 55 50 48 69 64 61 57 54 54
350 165 67 59 54 50 46 41 69 62 57 53 49 44 71 65 61 57 51 49 73 68 64 61 58 55
200 94 56 49 45 40 34 29 58 52 50 44 38 37 61 55 52 50 47 48 63 57 54 51 49 52
280 132 60 53 49 44 40 33 62 56 54 48 44 40 65 59 56 53 50 48 67 61 58 55 52 52
350 165 63 57 53 48 44 37 65 60 57 52 48 42 68 62 59 56 53 49 70 64 61 58 55 53
6
400 189 69 64 60 56 54 47
430 203 67 62 57 52 50 42 68 64 60 56 54 46 71 66 63 59 56 50 73 68 65 61 58 54
500 236 71 65 61 56 53 45 71 67 63 59 57 49 73 69 66 62 60 53 75 71 68 64 62 56
350 165 58 51 48 44 39 31 61 55 53 48 44 40 65 60 57 53 50 49 67 62 60 55 53 52
500 236 61 55 52 48 44 36 65 59 56 52 48 43 69 64 61 57 54 51 71 66 64 59 57 54
600 283 64 58 54 50 47 39 67 61 59 54 51 45 71 67 64 60 57 53 73 69 66 62 59 56
8
700 330 72 67 64 60 57 51
800 378 68 63 59 56 52 44 71 66 63 59 56 49 75 71 68 64 62 56 78 74 71 68 64 59
900 425 70 65 61 58 55 47 73 68 64 61 58 51 77 72 69 66 63 57 80 75 73 70 67 61
780 368 64 63 58 52 48 45 69 69 62 56 52 54 73 70 72 61 56 55 77 74 78 66 59 56
1100 519 66 64 61 54 52 48 70 69 66 59 56 55 76 72 75 64 61 58 79 76 80 68 63 59
1500 708 69 67 65 58 56 51 73 69 71 62 61 57 79 75 79 69 66 62 83 78 82 72 68 63
1560 736 75 73 74 66 63 60
14
1800 850 71 69 68 61 59 53 75 71 74 65 63 58 81 76 80 71 68 63 83 78 82 73 70 65
2200
780 368 65 60 52 48 41 34 68 66 60 57 45 42 70 68 66 65 51 50 72 69 69 69 56 54
1170 552 72 69 62 58 51 46 75 74 70 68 56 52 76 76 75 73 59 56
1560 736 76 74 70 65 59 53 78 76 72 68 60 55 79 79 76 74 63 59
14
1800 850 79 77 75 70 63 57 81 80 77 74 65 60
2000 944 80 78 78 71 65 59 82 80 78 74 67 61
0.5” Inlet Pressure
Ps
103
8
-12
Watts.
1,2,4
5
1.0” Inlet Pressure
78 73 76 68 65 61 82 77 81 73 70 65 84 79 83 75 72 67
Ps
5
1.5” Inlet Pressure
Ps
3
2.0” Inlet Pressure
Ps
5
3.0” Inlet Pressure
Ps
5
92 VAV-PRC012-EN
Acoustics Data
5
Watts.
1,2,4
1.0” Inlet Pressure
76 70 73 55 48 40 80 74 75 62 55 47 82 75 76 65 58 49
Ps
5
Table 115. Radiated sound power (dB)
Inlet
Fan
Size
Size
08SQ 5
08SQ 09SQ
08SQ 09SQ
09SQ8x
10SQ8x
Notes:
1. All data are measured in accordance with Industry Standard AHRI 880-2011.
2. All sound power levels, dB re: 10
3. Data in this column constitute AHRI 880-2011 Standard Rating Conditions.
4. Where Ps is the inlet static pressure minus discharge static.
5. Application ratings are outside the scope of the certification program.
Cfml/s234567234567234567234567234567
(in)
150 71 53 44 38 33 28 21 54 45 40 36 31 25 54 47 42 40 38 34 56 49 45 46 42 38
200 94 55 46 41 35 29 21 56 48 42 37 32 25 57 50 45 42 38 34 58 51 47 46 42 38
250 118 56 49 44 36 30 22 59 50 44 38 33 26 59 50 46 41 36 32 60 52 48 43 39 34 61 53 48 47 43 38
300 142 59 50 45 38 31 24 62 52 47 40 34 28 62 54 50 45 40 34 63 55 50 48 44 38
350 165 62 51 46 39 33 26 65 55 50 43 36 30 65 56 51 47 41 35 65 57 53 50 45 39
200 94 53 45 40 33 27 21 56 48 43 35 29 22 57 48 44 40 37 32 58 50 45 45 42 37
280 132 54 46 40 33 27 22 57 50 45 37 30 24 59 51 47 42 37 33 61 53 48 46 42 37
350 165 54 46 41 34 28 22 58 51 46 38 31 25 62 54 49 44 38 34 63 55 50 47 43 38
6
400 189 62 55 50 42 36 31
430 203 56 49 43 36 30 25 60 53 48 40 33 27 64 57 52 46 39 35 66 58 53 49 43 38
500 236 59 53 47 40 34 29 62 55 50 42 35 30 66 58 53 47 41 36 68 60 55 51 44 39
350 165 57 50 45 38 34 23 59 54 46 40 34 26 61 55 48 43 39 35 63 56 50 47 44 37
500 236 60 53 47 40 34 24 62 56 49 42 36 28 65 58 51 46 41 35 67 60 54 50 45 38
600 283 62 54 49 41 34 24 65 58 51 44 37 29 68 60 54 47 42 35 70 62 56 51 46 38
8
700 330 69 61 55 47 40 33
800 378 65 57 52 44 36 26 69 61 54 46 40 32 73 64 58 50 44 36 74 66 60 54 48 40
900 425 66 58 53 45 37 28 71 63 56 48 41 33 75 66 60 52 45 37 76 67 62 55 48 40
780 368 62 59 55 48 40 31 66 61 57 51 44 38 70 63 61 53 48 43 72 66 63 55 51 46
1100 519 64 60 56 47 40 32 68 63 60 52 45 38 72 66 65 57 52 45 74 68 66 59 54 48
1500 708 68 62 58 47 39 32 71 65 64 53 46 39 75 69 70 62 56 47 77 72 70 63 58 50
1560 736 73 68 67 58 51 43
14
1800 850 71 63 59 47 39 32 73 67 68 54 47 39 77 71 72 62 56 47 79 73 73 64 59 50
2200
780 368 60 55 47 41 32 28 63 61 55 48 38 34 66 63 60 55 45 41 69 66 64 59 50 45
1170 552 68 65 57 50 41 39 71 69 66 59 48 45 74 74 69 64 53 48
1560 736 73 71 64 56 47 46 74 72 66 59 49 47 76 74 71 65 54 50
14
1800 850 75 74 68 61 51 49 77 76 72 65 55 51
2000 944 76 75 70 62 52 50 78 77 72 65 55 52
0.5” Inlet Pressure
Ps
103
8
-12
1.5” Inlet Pressure
Ps
3
2.0” Inlet Pressure
Ps
5
3.0” Inlet Pressure
Ps
5
VAV-PRC012-EN 93
Acoustics Data
Table 116. Fan only sound power (dB)
Discharge Lw (dB) Radiated Lw (dB)
Fan
SP
CFMl/s234567234567
175 83 61 53 51 47 41 34 65 56 57 50 41 35
250 118 64 56 55 50 44 40 68 58 60 53 44 38
Outlet
08SQ 0.25
320 151 67 58 58 53 48 45 72 61 63 56 48 42
400 189 71 62 61 58 54 51 75 64 65 61 52 47
(a)
460
217 73 64 64 62 58 56 76 66 69 63 55 50
470 222 74 65 65 62 58 56 77 67 69 64 56 50
400 189 70 61 58 54 48 44 69 65 62 56 46 38
500 236 71 62 59 56 49 46 70 66 64 58 48 40
09SQ 0.25
700 330 74 65 63 61 54 53 72 69 68 64 54 46
800 378 76 67 65 64 57 56 74 71 70 67 57 49
(a)
900
425 78 70 69 67 61 61 77 74 72 69 60 53
700 330 67 59 56 51 45 40 67 61 57 54 49 44
840 396 69 60 58 53 48 43 68 63 58 55 50 46
10SQ 0.25
980 463 70 63 59 56 51 47 70 65 60 57 53 50
1200 566 74 67 64 61 56 54 73 69 64 61 57 55
1400 661 77 71 67 65 60 57 76 72 67 64 60 58
(a)
1420
670 77 71 67 65 60 57 76 72 67 64 60 58
150 71 61 55 51 46 40 34 66 58 56 50 42 36
230 109 64 57 54 49 44 39 69 60 58 52 44 40
08SQ
ECM
0.25
310 146 67 59 57 53 48 45 71 62 62 56 47 44
380 179 70 61 61 57 51 50 74 64 64 59 50 47
(a)
460
217 72 65 64 61 55 54 76 67 66 63 54 51
400 189 71 61 58 54 47 45 69 64 61 56 47 41
600 283 75 64 62 59 52 51 72 67 65 61 51 45
09SQ
ECM
0.25
700 330 77 66 64 63 56 56 75 71 68 64 55 49
(a)
900
425 81 71 70 68 62 62 79 75 72 69 61 55
1020 481 83 73 72 70 65 64 81 78 74 72 64 58
Notes:
1. All data are measured in accordance with Industry Standard AHRI 880-2011.
2. all sound power levels, dB re: 10
3. application ratings are outside the scope of the certification program
(a) AHRI 880-2011 section 7.2 Standard Rating Conditions
-12
Watts
Octave Bands Octave Bands
Table 117. AHRI 885-2008 add discharge transfer function assumptions:
Octave Band
23456 7
Small Box (< 300 CFM) Medium Box (300-700 CFM)
Large Box (> 700 CFM) -29 -30 -41 -51 -52 -39
Notes: Subtract from terminal unit sound power to determine discharge sound pressure in the space.
1. NC Values are calculated using modeling assumptions based on AHRI 885-2008.
2. Where DPs is inlet static pressure minus discharge static pressure.
3. Application ratings are outside the scope of the Certification Program.
94 VAV-PRC012-EN
-24
-27
-28
-29
-39
-40
-53
-51
-59
-53
-40
-39
Table 118. AHRI 885-2008 radiated transfer function assumptions:
Octave Band
23 4 5 6 7
Type 2- Mineral Fiber Insulation Total dB reduction
Notes: Subtract from terminal unit sound power to determine radiated sound pressure in the space.
1. NC Values are calculated using modeling assumptions based on AHRI 885-2008.
2. Where DPs is inlet static pressure minus discharge static pressure.
3. Application ratings are outside the scope of the Certification Program.
-18
-18
-19
-19
-20
-20
-26
-26
Table 119. Sound noise criteria (NC) - valve only
Fan
Size
08SQ 5
08SQ 09SQ
08SQ 09SQ
09SQ 8x14
10SQ 8x14
Notes:
1. “--” represents NC levels below NC 15.
2. NC Values are calculated using modeling assumptions based on AHRI 885-98-02 Addendum
3. Data at 1.5” inlet pressure constitute AHRI 880-2011 Standard Rating Conditions.
4. Where Ps is the inlet static pressure minus discharge static.
5. Data at 0.5”, 1.0”, 2.0” and 3.0” are application ratings. These ratings are outside the scope of the certification program.
Size (in)
6
8
CFM l/s 0.5” 1.0” 1.5” 2.0” 3.0” 0.5” 1.0” 1.5” 2.0” 3.0”
150 71 -- -- -- -- -- -- 15 19
200 94 -- 16 17 19 16 17 19 21
250 118 17 19 21 21 23 18 21 21 22 24
300 142 21 23 26 26 21 25 25 26
350 165 24 26 29 32 25 29 29 29
200 94 -- -- -- 16 -- 17 19 20
280 132 -- -- 17 20 -- 19 21 24
350 165 -- 18 21 24 -- 20 25 26
400 189 23 25
430 203 20 22 25 28 17 22 27 30
500 236 25 26 28 31 21 25 30 33
350 165 -- -- 18 20 19 23 24 26
500 236 -- 17 23 25 22 25 29 31
600 283 16 20 26 28 25 29 33 35
700 330 26 34
800 378 21 25 31 34 29 34 39 40
900 425 24 28 33 37 30 36 42 43
780 368 20 27 28 33 30 32 36 38
1100 519 21 27 31 36 31 35 40 41
1500 708 25 27 34 38 33 39 46 46
1560 736 32 43
1800 850 27 30 36 38 36 44 48 49
2200 1038 32 37 39 49 51 52
780 368 17 24 26 27 24 31 35 39
1170 552 27 33 36 36 41 46
1560 736 33 36 39 43 44 47
1800 850 37 40 46 49
2000 944 38 40 47 50
Inlet
Discharge
Inlet Pressure (Ps)
1,2,4
3,5
Radiated
Inlet Pressure (Ps)
Acoustics Data
-31
-31
1,2,4
-36
-36
3,5
VAV-PRC012-EN 95
Acoustics Data
Table 120. Sound noise criteria (NC) - fan only
Fan Outlet SP CFM l/s Discharge Radiated
175 83 -- 32
250 118 16 35
08SQ 0.25
09SQ 0.25
10SQ 0.25
08SQ
ECM
09SQ
ECM
Notes:
1. “--” represents NC levels below NC 15.
2. NC values are calculated using modeling assumptions based on AHRI 885-2008 Appendix E.
3. Application ratings are outside the scope of the certification program.
(a) AHRI 880-2011 section 7.2 Standard Rating Conditions.
0.25
0.25
320 151 20 38
400 189 25 42
(a)
460
217 28 45
470 222 29 45
400 189 21 37
500 236 23 39
700 330 26 44
800 378 29 46
(a)
900
425 32 48
700 330 17 32
840 396 20 33
980 463 21 36
1200 566 26 40
1400 661 30 44
(a)
1420
670 30 44
150 71 -- 31
230 109 -- 34
310 146 17 37
380 179 21 40
(a)
460
217 24 43
400 189 23 36
600 283 28 40
700 330 30 44
(a)
900
425 35 48
1020 481 38 51
Fan-Only
0.25” Disch. Pres.
Table 121. Discharge sound power (dB)-fan only (AHRI conditions)
Fan Size Inlet Size Cfm L/s 2 3 4 5 6 7
08SQ 5, 6, 8 460 217 68 62 63 62 58 56
09SQ 6, 8, 8x14 900 425 73 68 68 67 61 61
10SQ 8, 8x14 1420 670 72 69 66 65 60 57
Notes:
1. All sound data rated in accordance with current Industry Standard AHRI 880-2011.
2. All sound power levels, dB re: 10
96 VAV-PRC012-EN
-12
Watts.
Acoustics Data
Table 122. Radiated sound power (dB)-fan only (AHRI conditions)
Fan Size Inlet Size Cfm L/s 2 3 4 5 6 7
08SQ 5, 6, 8 460 217 76 66 69 63 55 50
09SQ 6, 8, 8x14 900 425 77 74 72 69 60 53
10SQ 8, 8x14 1420 670 76 72 67 64 60 58
Notes:
1. All sound data rated in accordance with current Industry Standard AHRI 880-2011.
2. All sound power levels, dB re: 10
Table 123. Inlet attenuator appurtenance effects (fan noise only)
Fan
Matte-faced and foil-faced insulation
08SQ, 09SQ 2 3 455620-4-8-7-7
Closed-cell insulation
08SQ, 09SQ 2 3 4545212-3-4-4
(a) Add to sound power, a negative effect represents a sound reduction, a positive effect represents a sound increase. (b) Attenuators on double-wall units contain foil-faced insulation.
All data are measured in accordance with Industry Standard AHRI 880-2011. All sound power levels, dB re: 10 Application ratings are outside the scope of the Certification Program.
-12
-12
Watts.
Discharge Sound Effect
(a)
(dB) Radiated Sound Effect
(a)
(dB)
2 34567234 5 6 7
(b)
Watts.
Table 124. Cabinet lining appurtenance effects (fan noise and valve noise)
(a)
(dB) Radiated Sound Effect
Fan
Discharge Sound Effect
2 3 4 5 6 7 2 3 4 5 6 7
Solid double-wall
08SQ, 09SQ 1 0 2 3 4 6 2 1 2 5 9 13
Closed-cell insulation
08SQ, 09SQ 2 1 3 2 2 2 2 2 4 5 5 8
(a) Add to sound power, a negative effect represents a sound reduction, a positive effect represents a sound increase.
All data are measured in accordance with Industry Standard AHRI 880-2011. All sound power lev Application ratings are outside the scope of the Certification Program.
els, dB re: 10
-12
Watts.
(a)
(dB)
Table 125. Heating coil appurtenance effects
(a)
(dB) Radiated Sound Effect
Fan
Discharge Sound Effect
2 3 4567 2 3456 7
Hot Water Coil (Fan Noise)
08SQ, 09SQ 3 3 4 5 4 5 2 2 3 3 3 4
Electric Heat
08SQ, 09SQ 0 -1 0 1 1 3 1 1 1 2 2 3
(a) Add to sound power, a negative effect represents a sound reduction, a positive effect represents a sound increase.
All data are measured in accordance with Industry Standard AHRI 880-2011. All sound power levels, dB re: 10 Application ratings are outside the scope of the Certification Program.
-12
Watts.
(a)
(dB)
VAV-PRC012-EN 97
Acoustics Data

Low Height Series Fan-PoweredTerminal Units

Table 126. Discharge sound power (dB)
Inlet
Fan
Size
Size
(in)
Cfm l/s 234567234567234567234567
170 80 61 53 54 47 44 42 60 52 49 42 38 33 61 58 50 43 39 34 61 60 52 45 41 35
250 118 64 56 57 52 49 47 63 55 54 48 44 40 64 60 55 49 45 41 64 62 55 50 46 42
08SQ 8
09SQ 8x14
10SQ 8x14
08SQ
ECM
09SQ
8x14
ECM
10SQ
8x14
ECM
Notes:
1. All data are measured in accordance with Industry Standard AHRI 880-2011.
2. All sound power levels, dB re: 10
3. Where Ps is the inlet static pressure minus discharge static.
4. Application ratings are outside the scope of the certification program.
330 156 68 60 61 56 53 52 67 59 58 53 49 47 68 63 59 54 50 48 68 65 59 55 51 49
410 193 71 63 64 61 57 57 71 63 63 59 55 55 72 65 63 60 56 55 72 67 63 60 56 56
500 227 74 67 67 65 61 62 75 67 67 65 61 62 76 68 67 65 61 62 76 69 67 65 61 63
350 165 63 59 55 51 45 41 64 60 59 52 45 41 65 62 59 53 47 42 66 63 59 54 48 44
500 236 67 64 60 57 51 49 67 65 63 57 51 49 69 67 63 58 53 49 71 68 63 59 54 51
700 330 71 70 66 64 59 59 72 71 67 64 59 59 75 73 67 65 60 59 77 75 69 66 61 61
800 378 75 73 68 67 62 62 75 73 69 67 62 62 76 74 69 67 63 62 78 76 71 68 64 64
890 420 77 75 70 69 65 64 77 75 71 69 65 64 78 76 71 69 65 64 79 77 72 70 66 66
440 208 60 58 54 50 43 37 62 59 54 51 44 39 64 60 57 51 46 40 66 63 58 53 47 41
700 330 63 60 57 53 47 43 64 61 57 54 48 44 66 63 59 55 49 45 69 64 65 56 51 46
900 425 65 64 60 56 50 47 67 65 61 58 53 50 69 66 62 59 53 51 71 67 66 60 55 51
1100 519 69 68 64 62 57 55 71 69 65 62 57 56 72 70 66 63 58 56
1300 614 73 72 68 65 61 60 74 72 68 66 61 60
1500 708 75 74 70 68 64 63 76 74 70 69 64 63
170 80 61 53 54 47 44 42 60 52 49 42 38 33 61 58 50 43 39 34 61 60 52 45 41 35
250 118 64 56 57 52 49 47 63 55 54 48 44 40 64 60 55 49 45 41 64 62 55 50 46 42
330 156 68 60 61 56 53 52 67 59 58 53 49 47 68 63 59 54 50 48 68 65 59 55 51 49
8
410 193 71 63 64 61 57 57 71 63 63 59 55 55 72 65 63 60 56 55 72 67 63 60 56 56
500 227 74 67 67 65 61 62 75 67 67 65 61 62 76 68 67 65 61 62 76 69 67 65 61 63
350 165 63 59 55 51 45 41 64 60 59 52 45 41 65 62 59 53 47 42 66 63 59 54 48 44
500 236 67 64 60 57 51 49 67 65 63 57 51 49 69 67 63 58 53 49 71 68 63 59 54 51
700 330 71 70 66 64 59 59 72 71 67 64 59 59 75 73 67 65 60 59 77 75 69 66 61 61
800 378 75 73 68 67 62 62 75 73 69 67 62 62 76 74 69 67 63 62 78 76 71 68 64 64
890 420 77 75 70 69 65 64 77 75 71 69 65 64 78 76 71 69 65 64 79 77 72 70 66 66
440 208 60 58 54 50 43 37 62 59 54 51 44 39 64 60 57 51 46 40 66 63 58 53 47 41
700 330 63 60 57 53 47 43 64 61 57 54 48 44 66 63 59 55 49 45 69 64 65 56 51 46
900 425 65 64 60 56 50 47 67 65 61 58 53 50 69 66 62 59 53 51 71 67 66 60 55 51
1100 519 69 68 64 62 57 55 71 69 65 62 57 56 72 70 66 63 58 56
1300 614 73 72 68 65 61 60 74 72 68 66 61 60
1500 708 75 74 70 68 64 63 76 74 70 69 64 63
0.5” Inlet Pressure Ps 1.0” Inlet Pressure Ps 2.0” Inlet Pressure Ps 3.0” Inlet Pressure Ps
-12
Watts.
98 VAV-PRC012-EN
Acoustics Data
5
Watts.
1,2,4
1.0” Inlet Pressure
Ps
5
Table 127. Radiated sound power (dB)
Inlet
Fan
Size
Size
08SQ
09SQ
10SQ8x
08SQ
ECM
09SQ
ECM
10SQ
ECM
Notes:
1. All data are measured in accordance with Industry Standard AHRI 880-2011.
2. All sound power levels, dB re: 10
3. Data in this column constitute AHRI 880-2011 Standard Rating Conditions.
4. Where Ps is the inlet static pressure minus discharge static.
5. Application ratings are outside the scope of the certification program.
Cfml/s234567234567234567234567234567
(in)
170 80 54 49 45 37 28 22 55 53 47 40 33 31 58 62 55 45 41 37 58 63 58 49 46 40
250 118 57 52 48 42 33 27 58 56 50 43 36 33 60 63 56 47 42 38 60 64 59 50 46 41
330 156 60 56 52 46 37 31 61 59 54 47 39 36 63 64 58 50 43 39 63 65 60 52 46 42
8
410 193 63 60 56 50 41 36 64 62 57 50 42 38 65 65 59 52 44 41 65 67 62 53 46 43
500 227 66 64 60 53 44 40 67 65 60 54 45 41 68 66 61 54 46 42 68 66 61 54 45 42 68 68 63 55 46 44
350 165 58 53 47 39 32 27 59 56 56 43 37 34 62 63 61 52 45 42 64 65 62 54 49 45
500 236 62 57 51 44 36 30 63 59 57 46 39 36 65 64 62 53 46 44 67 66 63 55 50 47
8
700 330 68 63 56 50 40 33 68 64 58 50 42 39 69 65 62 53 47 46 71 67 64 56 51 50
x
14
800 378 70 66 58 52 44 38 70 66 59 52 44 41 70 66 61 53 46 44 71 67 63 55 48 47 72 69 65 57 52 51
890 420 72 67 59 54 46 40 72 67 60 54 46 42 73 69 64 56 49 48 74 71 67 59 53 51
440 208 61 56 49 42 33 27 62 59 52 45 40 38 65 60 60 50 46 46 66 63 61 58 50 49
700 330 62 58 51 45 37 31 64 61 55 48 43 41 68 64 62 53 48 48 70 66 67 57 52 51
900 425 66 62 55 48 41 34 68 63 56 50 44 42 70 66 64 55 50 50 72 68 68 58 54 52
1100 519 71 65 58 53 46 42 72 68 65 57 52 52 73 70 69 60 55 54
14
1300 614 74 69 65 58 53 52 76 72 69 61 56 55
1500 708 76 71 64 60 54 52 78 74 70 63 58 57
170 80 54 49 44 36 29 22 57 54 48 39 36 30 57 60 54 44 41 36 58 61 56 48 45 40
250 118 57 52 47 40 32 27 59 56 50 42 37 32 59 62 56 46 42 38 60 63 58 50 46 41
330 156 60 56 51 44 36 31 62 58 53 46 39 35 62 64 58 49 44 40 63 66 61 52 47 42
8
410 193 63 59 55 48 40 36 64 60 56 49 41 38 65 66 60 52 45 42 66 68 63 54 48 44
500 227 66 62 58 52 43 40 66 62 58 52 43 40 67 67 61 54 46 43 68 70 65 56 49 45
350 165 60 53 47 40 32 25 60 56 55 43 37 34 63 63 62 52 45 42 64 63 62 54 49 47
500 236 64 57 51 44 36 29 64 59 56 46 39 36 67 64 63 53 46 44 68 65 63 55 50 48
8
700 330 71 63 56 51 41 33 71 64 58 51 42 39 71 65 63 53 47 46 73 68 64 57 51 49
x
14
800 378 73 66 58 53 44 38 73 66 59 53 44 40 73 67 63 55 48 46 75 69 64 58 52 49
890 420 75 67 59 55 46 40 75 67 60 55 46 41 75 69 63 56 49 47 77 70 65 59 53 50
440 208 61 54 47 42 37 32 62 57 49 44 38 38 64 59 60 48 44 44 68 63 68 56 48 51
700 330 64 57 50 45 37 32 66 60 54 49 43 43 69 64 60 53 47 49 71 66 68 56 51 51
8
900 425 65 62 55 48 40 35 69 63 56 52 44 43 72 67 61 55 50 51 73 68 68 58 52 52
x
1100 519 72 66 58 54 46 43 74 70 62 57 52 53 75 71 67 60 54 54
14
1300 614 76 71 63 59 53 53 77 72 67 61 56 55
1500 708 78 72 65 61 54 52 79 74 68 63 58 57
0.5” Inlet Pressure
Ps
-12
1.5” Inlet Pressure
76 70 63 59 52 48
Ps
5
2.0” Inlet Pressure
Ps
5
3.0” Inlet Pressure
Ps
5
VAV-PRC012-EN 99
Acoustics Data
Table 128. Fan only sound power (dB)
Discharge Lw (dB) Radiated Lw (dB)
Fan
08SQ 0.25
09SQ 0.25
10SQ 0.25
08SQ
ECM
09SQ
ECM
10SQ
ECM
Notes:
1. All data are measured in accordance with Industry Standard AHRI 880-2011.
2. All sound power levels, dB re: 10
3. Application ratings are outside the scope of the certification program
(a) AHRI 880-2011 section 7.2 Standard Rating Conditions
SP
0.25
0.25
0.25
CFMl/s234567234567
170 80 61 51 52 46 42 38 53 47 44 36 26 21
250 118 63 54 55 50 46 43 56 51 48 41 30 23
330 156 67 58 59 54 50 49 59 56 52 46 36 27
410 193 70 61 64 58 56 56 60 59 55 49 40 34
480 227 73 64 66 62 60 59 63 62 58 53 44 37
(a)
500
350 165 65 58 55 51 46 41 57 51 44 38 24 20
500 236 69 62 60 57 52 49 61 55 48 42 30 23
700 330 74 68 66 64 59 58 66 61 55 49 38 29
800
890 420 79 73 71 70 65 64 70 67 60 55 45 36
440 208 61 58 54 51 44 38 62 57 48 41 29 22
700 330 63 61 58 56 49 45 64 60 51 45 33 24
900 425 65 64 61 59 53 51 66 62 54 48 36 26
1100 519 68 67 64 62 57 55 68 64 57 52 40 30
1300 614 71 70 66 66 61 59 71 66 60 55 44 33
1400
1500 708 73 73 69 69 64 63 74 69 62 58 48 36
170 80 60 48 47 42 36 30 53 46 41 36 25 23
250 118 63 52 53 48 44 38 55 50 45 40 28 25
330 156 67 57 59 53 50 47 58 54 50 44 33 28
410 193 71 62 63 59 56 54 61 58 54 49 38 33
480 227 74 65 67 64 61 59 66 61 57 53 43 37
350 165 64 60 57 53 48 46 60 53 45 39 28 23
500 236 69 65 62 60 55 54 64 58 50 44 34 28
700 330 73 71 67 67 62 61 69 63 56 51 40 33
800 378 77 74 71 70 66 65 72 66 59 54 44 36
890 420 80 78 74 74 70 69 76 70 62 57 48 40
440 208 62 59 58 55 49 48 62 55 48 41 30 23
700 330 65 62 61 58 52 51 65 59 52 46 35 27
900 425 67 64 63 61 55 54 67 62 55 50 39 30
1100 519 69 67 66 64 58 58 70 66 58 54 42 33
1300 614 72 70 68 67 62 62 73 69 61 57 46 36
1500 708 75 73 70 70 65 65 75 71 63 59 49 40
236 73 65 67 63 60 60 64 62 59 54 45 38
(a)
378 77 70 69 67 62 61 68 64 58 52 42 32
(a)
661 72 71 68 68 62 61 72 68 61 56 46 35
-12
Watts
Outlet
Octave Bands Octave Bands
100 VAV-PRC012-EN
Loading...