Trane LPC Install And Operation Instructions

Installation, Operation, and Maintenance
Packaged Climate Changer Air Handler
Model LPC “FO” and later design sequence
1,500 to 15,000 cfm
LPC-SVX01C-EN
general information
About This Manual Literature Change History
Use this manual for Packaged Climate Changer air handlers, model LPC. This is the first revision of this manual. It provides specific installation, operation, and maintenance instructions for “DO” and later design sequences. For previous design sequence information, contact your local Trane representative.
Warnings and Cautions
Warnings and cautions appear at appropriate sections throughout this manual. Read these carefully.
WARNING
Indicates a potentially hazardous situation, which could result in death or serious injury if not avoided.
CAUTION
Indicates a potentially hazardous situation, which may result in minor or moderate injury if not avoided. Also, it may alert against unsafe practices.
CAUTION
Indicates a situation that may result in equipment or property-damage­only accidents.
Sample Warnings and Cautions
WARNING
Hazardous Voltage w/Capacitors!
Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized. Verify with an appropriate voltmeter that all capacitors have discharged. Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury.
CAUTION
Use Copper Conductors Only!
Unit terminals are not designed to accept other types of conductors. Failure to use copper conductors may result in equipment damage.
Special Note on Refrigeration Emissions
World environmental scientists have concluded that ozone in our upper atmosphere is being reduced due to the release of CFC fully halogenated compounds.
Trane urges all HVAC service personnel to make every effort to prevent any refrigerant emissions while installing, operating, or servicing equipment. Always conserve refrigerants for continued use.
Additional specific information on refrigerant handling is included in this manual where applicable.
Common HVAC Acronyms
For convenience, a number of acronyms and abbreviations are used throughout this manual. These acronyms are alphabetically listed and defined below.
BAS = Building automation systems cfm = Cubic-feet-per-minute ewt = entering water temperature F/A = Fresh air HVAC = Heating, ventilation and air conditioning I/O = Inputs/outputs IOM= Installation, operation, and maintenace manual LH = Left-hand O/A = Outside air R/A = Return air RH = Right-hand rpm = Revolutions-per-minute S/A = Supply air w.c. = Water column ZSM = Zone sensor module
© 2006 American Standard All rights reserved LPC-SVX01C-EN
contents
Cross reference to related publications/information for model LPC units with Tracer AH540 controls:
• Installation, Operation, and Programming Guide for Tracer AH540 Unit Controller, CNT-SVX05B-EN
• Packaged Climate Changer Air Handler Catalog, CLCH-PRC007-EN
Installation ……………………………………………………………2
general information ……………………………………………2 dimensions & weights ………………………………………14 pre-installation considerations ………………………………27 mechanical requirements …………………………………29 electrical requirements ………………………………………33 installation procedure ………………………………………36 pre-startup requirements ……………………………………40
Operation ……………………………………………………………43
general information …………………………………………43 sequence of operation ………………………………………59
Maintenance…………………………………………………………86
diagnostics ……………………………………………………86 troubleshooting ………………………………………………89 maintenance procedures ……………………………………96 appendix ………………………………………………………99
LPC-SVX01C-EN 3
general information
General
Packaged Climate Changer units are draw-through air handlers that are designed for cooling and/or heating conditions of 1,500 to 15,000 nominal cfm.
Basic unit components consist of coil(s), condensate drain pan, filter, one fan wheel, motor and drive.
Unit control options range from the simple control interface for field-mounted controllers to the sophisticated Tracer AH540. For more information on the Tracer AH540 controls, see the Operation section of this manual.
Refrigerant Handling Procedures
Environmental Accountability Policy
Trane urges that all HVAC servicers to make every effort to eliminate, if possible, or vigorously reduce the emission of CFC, HCFC, and HFC refrigerants to the atmosphere. Always act in a responsible manner to conserve refrigerants for continued usage even when acceptable alternatives are available.
Recover and Recycle Refrigerants
Never release refrigerant to the atmosphere! Always recover and/or recycle refrigerant for reuse, reprocessing (reclaimed), or properly dispose if removing from equipment. Always determine the recycle or reclaim requirements of the refrigerant before beginning the recovery procedure. Obtain a chemical analysis of the refrigerant if necessary. Questions about recovered refrigerant and acceptable refrigerant quality standards are addressed in ARI Standard 700.
Refrigerant Handling and Safety
Consult the manufacturer’s material safety data sheet (MSDS) for information on refrigerant handling to fully understand health, safety, storage, handling, and disposal requirements. Use the approved containment vessels and refer to appropriate safety standards. Comply with all applicable transportation standards when shipping refrigerant containers.
Service Equipment and Procedures
To minimize refrigerant emissions while recovering refrigerant, use the manufacturer’s recommended recycling equipment per the MSDS. Use equipment and methods which will pull the lowest possible system vacuum while recovering and condensing refrigerant. Equipment capable of pulling a vacuum of less than 1,000 microns of mercury is recommended.
Do not open the unit to the atmosphere for service work until refrigerant is fully removed/recovered. When leak-testing with trace refrigerant and nitrogen, use HCFC-22 (R-22) rather than CFC-12 (R-
12) or any other fully-halogenated refrigerant . Be aware of any new leak test methods which may eliminate refrigerants as a trace gas. Perform evacuation prior to charging with a vacuum pump capable of pulling a vacuum of 1,000 microns of mercury or less. Let the unit stand for 12 hours and with the vacuum not rising above 2,500 microns of mercury.
A rise above 2,500 microns of mercury indicates a leak test is required to locate and repair any leaks. A leak test is required on any repaired area.
Charge refrigerant into the equipment only after equipment does not leak or contain moisture. Reference proper refrigerant charge requirements in the maintenance section of this manual to ensure efficient machine operation. When charging is complete, purge or drain charging lines into an approved refriger­ant container. Seal all used refrigerant containers with approved closure devices to prevent unused refrigerant from escaping to the atmosphere. Take extra care to properly maintain all service equipment directly supporting refrigerant service work such as gauges, hoses, vacuum pumps, and recycling equipment .
When cleaning system components or parts, avoid using CFC-11 (R-11) or CFC­113 (R-113). Use only cleaning-solvents that do not have ozone depletion factors. Properly dispose of used materials. Refrigeration system cleanup methods using filters and driers are preferred. Check for leaks when excessive purge operation is observed.
Keep abreast of unit enhancements, conversion refrigerants, compatible parts, and manufacturer’s recommenda­tions that will reduce refrigerant emis­sions and increase equipment operating efficiencies.
4 LPC-SVX01C-EN
general
Access section option
• with or without preheat coil
• one or two-row hot water (9, 12, or 14 fpi) or
• one-row steam distributing coil (6 fpi)
Installation
Internal filter frame accommodates two-inch filters
information
Galvanized steel cabinet
• matt-faced insulation
• foil face insulation optional
• double wall insulation optional
• 2-inch flat filter option on main section
Sizes: 03, 06, 09, 10, 12, 14, 17, 21, 25
or 30 square feet
• 1,500 to 15,000 cfm (708 to 4956 l/s)
• UL/CUL listing
• ARI 410 and 430 listed
• Meets ARI 260 acoustic ratings
Face & bypass option
helps control preheat
Filter section option
• 2-inch, MERV 7, angle filters
• 4-inch, MERV 7, flat filters
• 4-inch, MERV 12, flat filters
Other options include:
• electric heat with single-point power connections, reheat position
• factory mounted and wired disconnect with motor overloads
• variable frequency drive factory mounted and wired
Figure I-GI-1. Packaged Climate Changer air handler unit components. Horizontal unit is shown.
LPC-SVX01C-EN 5
Up to 8 rows of coil
• 4 or 6 row DX coil with 9, 12, or 14 fpi
• 4, 6, or 8-row chilled water with 9, 12, or 14 fpi
• 1 or 2-row hot water coil, reheat or preheat with 9, 12, or 14 fpi
• 1-row steam coil, 6 fpi, reheat or preheat
Belt-driven motor
• Internal spring isolation optional
1
/2 to 20 hp
• 650 to 1900 rpm
Forward-curved fan
• fixed pitch or variable pitch sheaves
• constant volume or variable air volume
Control options
• control interface
• Tracer AH540 DDC controller
general
Installation
Ultraviolet (UV) Germicidal Irradiation Lights
The United States Environmental Protection Agency (EPA) believes that molds and bacteria inside buildings have the potential to cause health problems in sensitive individuals Trane provides ultraviolet lights (UV-C) as a factory-engineered and installed option in select commercial air handling products for the purpose of reducing microbiological growth (mold and bacteria) within the equipment. When factory provided, polymer materials that are susceptible to deterioration by the UV-C light will be substituted or shielded from direct exposure to the light. In addition, UV-C radiation can damage human tissue, namely eyes and skin. To reduce the potential for inadvertent exposure to the lights by operating and maintenance personnel, electrical interlocks that automatically disconnect power to the lights are provided at all unit entry points to equipment where lights are located
Note:
1. United States Environmental Protec­tion Agency;
Moisture and your Home;
402-K-02-003. It’s available online, at www.epa.gov. Enter “guide to mold” in the search box to view.
A Brief Guide to Mold,
(Note 1). If specified,
Brochure EPA
information
WARNING
Equipment Damage From Ultraviolet (UV) Lights!
Trane does not recommend field installation of ultraviolet lights in its air handling equipment for the intended purpose of improving indoor air quality. High intensity C-band ultraviolet light is known to severely damage polymer (plastic) materials and poses a personal safety risk to anyone exposed to the light without proper personal protective equipment (can cause damage to eyes and skin). Polymer materials commonly found in HVAC equipment that may be susceptible include insulation on electrical wiring, fan belts, thermal insulation, various fasteners and bushings. Degradation of these materials can result in serious damage to the equipment. Trane accepts no responsibility for the performance or operation of our air handling equipment in which ultraviolet devices were installed outside of the Trane factory.
6 LPC-SVX01C-EN
general
Installation
Packaged Climate Changer Unit Configurations and Optional Sections
Vertical Unit Fan Discharge Options
Top Front Top Back
Angle Filter Section OR
OR
Mixing Section
Flat Filter Section
Optional Sections
Face & Bypass
Section
Coil Access Section
Vertical Unit, Front Top Discharge
Main Unit Section Configurations
information
Back Top
Horizontal Unit Fan Discharge Option
Horizontal Unit, Front Top Discharge
Top Front
Electric Heat Section
Optional Section
Available Fan Discharge Configurations Detail
Horizontal Unit, Top Front Fan Discharge
Horizontal Unit, Front Top Fan Discharge
LPC-SVX01C-EN 7
Vertical Unit, Front Top Fan Discharge
Vertical Unit, Back Top Fan Discharge
Vertical Unit, Top Back Fan Discharge
Vertical Unit, Top Front Fan Discharge
general
Installation
information
Table I-GI-1. Packaged Climate Changer General Data
Unit size 3 6 8 10 12 14 17 21 25 30 Unit nominal airflow, cfm 1500 3000 4000 5000 6000 7000 8500 10500 12500 15000
Hydronic & DX coil
coil area, ft width, in. 17.5 22.5 27.5 27.5 35.0 35.0 45.0 45.0 51.2 51.2 length, in. 23.0 36.0 39.0 51.0 51.0 59.0 54.0 66.0 68.0 81.0 velocity, ft./min. 536.7 533.3 537.1 513.3 484.0 488.1 503.7 509.1 516.5 520.3 dry weight, lbs. 1-row 23.5 35.0 41.8 51.5 66.2 72.1 82.8 93.2 109.7 122.5 2-row 29.5 46.3 56.8 70.8 91.0 100.5 116.6 134.2 168.5 190.2 4-row 46.6 75.8 94.7 120.5 152.8 170.7 207.3 240.7 276.3 317.0 6-row 58.6 98.5 124.7 159.3 202.4 227.8 274.9 322.8 372.7 431.2 8-row 73.6 125.4 159.5 204.7 259.4 292.9 351.3 414.5 479.5 556.8 wet weight, lbs. 1-row 29.2 43.6 52.5 64.0 85.8 93.2 108.2 121.5 141.9 158.2 2-row 37.7 59.0 73.0 90.5 119.9 132.4 161.1 184.4 226.6 255.4 4-row 59.8 97.6 123.1 155.7 201.6 225.4 279.1 323.9 373.1 427.8 6-row 76.9 129.4 165.2 210.0 271.2 305.3 374.0 438.9 508.2 587.7 8-row 96.9 165.5 212.2 271.0 348.2 393.3 477.6 563.5 653.7 759.0 waterflow limits 1-row min. gpm max. gpm 2, 4, 6, & 8-row min. gpm max. gpm volume, gallons 1-row 0.7 1.0 1.3 1.5 2.3 2.5 3.1 3.4 3.9 4.3 2-row 1.0 1.5 2.0 2.4 3.5 3.8 5.3 6.0 7.0 7.8 4-row 1.6 2.6 3.4 4.2 5.9 6.6 8.6 10.0 11.6 13.3 6-row 2.2 3.7 4.9 6.1 8.3 9.3 11.9 13.9 16.3 18.8 8-row 2.8 4.8 6.3 7.9 10.6 12.0 15.2 17.9 20.9 24.3
Steam coil
area, ft width, in. length, in. area, ft width, in. length, in. weight, lbs. 31.7 54.8 74.8 86.0 114.1 123.3 157.6 179.9 200.0 224.2
Fan/motor data
fan wheel size, in. 9x7 12x9 12x12 15x15 18x15 18x18 20x15 20x20 20x18 22x20 max rpm 2000 1500 1700 1400 1200 1200 110 0 1000 1300 1150 motor HP min. design cfm max. design cfm
2 and 4-in. Flat filter data
quantity - size in. 1 - 20x25 2 - 20x25 2 - 20x25 1 - 16x25 2 - 16x20 2 - 16x20 2 - 16x20 2 - 16x20 2 - 16x25 6 - 16x25
area, ft nominal air velocity, ft./min. 432.0 432.0 576.0 514.3 369.2 430.8 377.8 466.7 473.5 490.2
2-in. Angle filter section data
quantity - size in. 2 - 16x25 4 - 20x20 4 - 20x20 4 - 20x20 9 - 20x20 9 - 20x20 6 - 16x25 6 - 16x25 4 - 16x20 12 - 16x20
area, ft velocity, ft./min. 270.0 270.0 360.0 321.3 240.0 280.0 226.7 280.0 296.2 306.7
Mixing section
nominal air velocity, ft./min. 966.4 1066.3 1123.4 1120.4 1184.1 1161.7 1171.1 1120.1 1218.5 1247.1
2
2 Note 7
2
2
2
Note 5
Note 6
Notes 5 & 7
Notes 6 & 7
Note 10
Note 10
Note 3
Note 4
Note 3
Note 4
Note 8
Note 9
2.8 5.6 7.5 9.7 12.4 14.3 16.9 20.6 24.2 28.8
6.1 7.9 9.6 9.6 12.2 12.2 15.7 15.7 17.5 17.5
32.6 42.0 51.3 51.3 65.3 65.3 83.9 83.9 93.3 93.6
6.1 14.9 18.4 18.4 23.6 23.6 30.6 30.6 35.0 35.0
32.6 79.3 51.3 51.3 65.3 125.9 163.2 163.2 186.6 186.6
1.9 4.5 6.5 8.5 11.7 13.5 6.8 8.4 11.0 13.2
12.0 18.0 24.0 24.0 33.0 33.0 18.0 18.0 24.0 24.0
23.0 36.0 39.0 51.0 51.0 59.0 54.0 67.0 66.0 79.0 – 9.0 11.2 11.0 13.2 – 24.0 24.0 24.0 24.0 – 54.0 67.0 66.0 79.0
1
/2 - 2 1050 2100 2800 3500 4200 4900 5950 7350 8750 10500
1
/2 - 3
3
/4 - 5 1 - 5 1 - 7 1/
1 - 7 1/
2
1 -10 2 - 15 3 - 20 3 - 20
2
1800 3600 4800 6000 7200 8400 10200 12600 15000 18000
2 - 20x25 1 - 16x25 1 - 16x25 2 - 16x25 2 - 16x25 6 - 20x25 4 - 20x25
2 - 20x20 2 - 20x20 2 - 20x20 2 - 20x20 1 - 20x25 1 - 20x25 2 - 20x25 2 - 20x25
3.5 6.9 6.9 9.7 16.3 16.3 22.5 22.5 26.4 30.6
2 - 16x20 6 - 20x25 6 - 20x25 12 - 20x20 8 - 20x20
5.6 11.1 11.1 15.6 25.0 25.0 37.5 37.5 42.2 48.9
Notes: 1. Coil width = length in the direction of a coil header, typically vertical. 2. Coil length = length of coil in direction of the coil tubes, typically horizontal and perpendicular to airflow.
3. Unit sizes 17-30 have two stacked steam coils. 4. To prevent erosion/noise problems. 5. Coil width = length in the direction of a coil header, typically vertical. 6 . Coil length = length of coil in direction of the coil tubes, typically horizontal and perpendicular to airflow. 7. The minimum waterflow is to assure self venting of the coil. There is no minimum water flow limit for coils that do not require self venting. 8. Minimum airflow limit is for units with hot water, steam, or electric heat. There is no minimum airflow for cooling only units. 9. Due to moisture carryover limits. 10. Coil weight based on 12 fpi coil.
8 LPC-SVX01C-EN
general
Installation
information
Table I-GI-2. Available motor horsepower and unit voltage
unit voltage
1
/
2
3
/
4
11
1
/
2
208/60/1 zzz
230/60/1 zzz
277/60/1 zzz
208/60/3 z zzzz z zzz zz
230/60/3 z zzzz z zzz zz
460/60/3 z zzzz z zzz zz
575/60/3 zzz z zzz zz
380/50/3 zzz z zzz z
415/50/3 zzz z zzz z
motor horsepower
2357
1
/
2
10 15 20
Table I-GI-3. Available motor horsepower by unit size
unit size
1
/
2
3
/
4
11
1
/
2
3 z zzzz
6 z zzzz z
8 zzzz z z
10 zzzzz
12 zzzzzz
14 zzzzzz
17 zzz z zzz
21 z z zzz
25 z zzz zz
30 z zzz zz
motor horsepower
2357
1
/
2
10 15 20
LPC-SVX01C-EN 9
general
Dx Coil Options
Figure I-GI-1. Single Circuit DX Coil
Installation
Figure I-GI-2. Intertwined DX Coil
information
Figure I-GI-3. Horizontal Face Split DX Coil
Table I-GI-5. Packaged Climate Changer DX Coil Configuration Options
Coil Configuration Single Horizontal Face Split Intertwined
Unit # # Coil Fin # # Coil Fin # # Coil Fin Size Dist. Circuits Width Length Dist. Circuits Width Length Dist. Circuits Width Length
3 1 3 17.5 23.0 – 6 1 5 22.5 36.0 – 8 1 7 27.5 39.0 2 7 27.5 39.0 2 7 27.5 39.0 10 1 10 27.5 51.0 2 10 27.5 51.0 2 10 27.5 51.0 12 2 13 35.0 51.0 2 13 35.0 51.0 14 2 13 35.0 59.0 2 13 35.0 59.0 17 2 17 45.0 54.0 4 17 45.0 54.0 21 2 17 45.0 66.0 4 17 45.0 66.0 25 2 20 51.3 68.0 4 20 51.5 68.0 30 4 40 51.3 81.0 4 40 51.3 81.0
Note: 4-row coils have a 3/16" distributor. 6-row coils have a 1/4" distributor.
10 LPC-SVX01C-EN
general
Installation
information
Packaged Climate Changer Model Number Description
Following is a complete description of the Packaged Climate Changer model number. Each digit in the model number has a corresponding code that identifies specific unit options.
LPC A A 08 F 2 F0 L L B 0 0 000 0 0 A F B H B 0 0 0 0 0 0 0 0 0 0 0
1,2,3 4 5 6,7 8 9 10,11 12 13 14 15 16 17,18,19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37
Digit 1, 2, 3 - Unit model
LPC = Packaged Climate Changer
Digit 4 - Development sequence
A = “A” development sequence
Digit 5 - Configuration
A = horizontal/front top B = horizontal/top front C = vertical/front top D = vertical/top front E = vertical/back top F = vertical/top back
Digit 6, 7 - Unit size
03 = 3 square feet of coil 06 = 6 square feet of coil 08 = 8 square feet of coil 10 = 10 square feet of coil 12 = 12 square feet of coil 14 = 14 square feet of coil 17 = 17 square feet of coil 21 = 21 square feet of coil 25 = 25 square feet of coil 30 = 30 square feet of coil
Digit 8 - Unit voltage
0 = no motor, controls, electric heat A = 208/60/1 B = 230/60/1 C = 277/60/1 D = 208/60/3 E = 230/60 /3 F = 460/60/3 G = 575/60/3 H = 380/50/3 J = 415/50/3
Digit 9 - Insulation & Isolation
1 = 1 inch, m att faced 2 = 1 in ch, foil faced 3 = 1 inch, double-wall with field provided
external isolaiton
4 = 1 inch, double-wall with internal
isolation
Digit 10,11 - Design sequence
Digit 12 - Drain pan type, coil & motor connection location
R = polymer drain pan, RH coil & motor L = polymer drain pan, LH coil & motor C = polymer drain pan, RH coil & LH motor D = polymer drain pan, LH coil & RH motor E = SS drain pan, RH coil & motor F = SS drain pan, LH coil & motor G = SS drain pan, RH coil & LH motor H = SS drain pan, LH coil & RH motor
LPC-SVX01C-EN 11
Digit 13 - Unit Coil #1 Type (1st in Air Stream)
0 = no unit coil #1
hydronic heat coils
A = 1-row, 9 fpi B = 1-row, 12 fpi C = 1-row, 14 fpi D = 2-row, 9 fpi E = 2-row, 12 fpi F = 2-row, 14 fpi
chilled hydronic coils
G = 4-row, 9 fpi H = 4-row,12 fpi J = 4-row, 14 fpi K = 6-row, 9 fpi L = 6-row, 12 fpi M = 6-row, 14 fpi N = 8-row, 9 fpi P = 8-row, 12 fpi R = 8-row, 14 fpi
DX coils, 3/16” distributor
T = 4-row, 9 fpi U = 4-row, 12 fpi V = 4-row, 14 fpi
Steam Coil
1 = 1-row, 6 fpi
DX coils, 1/4” distributor
5 = 6-row, 9 fpi 6 = 6-row DX, 12 fpi 7 = 6-row DX, 14 fpi
Digit 14 - Unit coil #2 type (2nd in air stream)
0 = no unit coil #1
hydronic reheat coils
A = 1-row, 9 fpi B = 1-row, 12 fpi C = 1-row, 14 fpi D = 2-row, 9 fpi E = 2-row, 12 fpi F = 2-row, 14 fpi
chilled hydronic coils
G = 4-row, 9 fpi H = 4-row,12 fpi J = 4-row, 14 fpi K = 6-row, 9 fpi L = 6-row, 12 fpi M = 6-row, 14 fpi
DX coils, 3/16” distributor
N = 4-row, 9 fpi P = 4-row, 12 fpi R = 4-row, 14 fpi
steam coil
W = 1-row, 6 fpi
DX coils, 1/4” distributor
2 = 6-row, 9 fpi 3 = 6-row, 12 fpi 4 = 6-row, 14 fpi
Digit 15 - Access section (preheat)
0 = none
hydronic coils
A = 1-row, 9 fpi B = 1-row, 12 fpi C = 1-row, 14 fpi D = 2-row, 9 fpi E = 2-row, 12 fpi F = 2-row, 14 fpi G = 1-row steam coil, type NS, 6 fpi R = no coil, matt face insulation
Digit 16 - Electric heat, factory mounted only
0 = none 1 = electric heat with 1 stage 2 = electric heat with 2 stages 4 = electric heat with 4 stages
Digit 17, 18, 19 - Electric heater kW
006 - 018 = 1 kW increments 020 - 038 = 2 kW increments 041 - 059 = 3 kW increments 063 - 095 = 4 kW increments 95 and < = 5 kW increments Digit 17, 18, 19 - Electric heater kW
Digit 20 - Control type
0 = none 1 = control interface 2 = Tracer AH540 zone temp. control 3 = Tracer AH540 discharge temp. control
Digit 21 = Electric heater options
0 = none A = line fuse B = door interlocking disconnect switch C = air flow switch
combined options
D = A and B E = A and C F = B and C G = A, B, and C
Digit 22 – Refrigerant circuit options
0 = none 1 = single circuit with one stage DX 2 = face split circuit with 2 stage DX 3 = intertwined circuit with 2 stage DX 5 = single circuit with 2 stage DX 6 = face split circuit with 4 stage DX 7 = intertwined circuit with 4 stage DX
general
Digit 23 - Motor horsepower (hp)
0 = none A = 1/2 hp B = 3/4 hp C = 1 hp D = 1 1/2 hp E = 2 hp F = 3 hp G = 5 hp H = 7 1/2 hp J = 10 hp K = 15 hp L = 20 hp
Digit 24 - Volume control
A = CV with variable pitch sheaves B = CV with fixed pitch sheaves C = VFD with fixed pitch sheaves
Digit 25 – Drives, fixed/variable
0 = none A = 650 rpm/600 – 700 rpm B = 700 rpm/650 – 750 rpm C = 750 rpm/700 – 800 rpm D = 800 rpm/750 – 850 rpm E = 850 rpm/800 – 900 rpm F = 900 rpm/850 – 950 rpm G = 950 rpm/900 – 1000 rpm H = 1000 rpm/950 – 1050 rpm J = 1050 rpm/1000 – 1100 rpm K = 1100 rpm/1050 – 1150 rpm L = 1150 rpm/1100 – 1200 rpm M = 1200 rpm/1150 – 1250 rpm N = 1250 rpm/ 1200 – 1300 rpm P = 1300 rpm/1250 – 1350 rpm R = 1350 rpm/1300 – 1400 rpm T = 1400 rpm/1350 – 1450 rpm U = 1450 rpm/1400 – 1500 rpm V = 1500 rpm/1450 – 1550 rpm W = 1550 rpm/1500 – 1600 rpm Y = 1600 rpm/1550 – 1650 rpm Z = 1650 rpm/1600 – 1700 rpm 1 = 1700 rpm/1650 – 1750 rpm 2 = 1750 rpm/1700 – 1800 rpm 3 = 1800 rpm/1750 – 1850 rpm 4 = 1850 rpm/1800 – 1900 rpm 5 = 1900 rpm/1850 – 1950 rpm 6 = 1950 rpm/1900 – 2000 rpm 7 = 2000 rpm/1950 – 2050 rpm
Digit 26 - Filter type/filter/mixing section
0 = none A = flat unit filter B = flat unit filter & mixing section C = angle filter section D = flat filter section E = angle filter section & mixing section F = flat filter section & mixing section
Installation
Digit 27 – Face & bypass section (F & B, preheat position)
0 = none A = F & B w/ NC actuator B = F & B w/ NO actuator C = F & B w/ field-supplied NO actuator D = F & B w/ field-supplied NC actuator
Digit 28 - Control option
0 = none 1 = dehumidification w/RH sensor 2 = dehumidification w/comm.RH 3 = 2-pipe changeover w/EWT sensor 4 = 2-pipe changeover w/comm. EWT 5 = CO2 sensor 6 = 1 & 4
Digit 29 - Control options 1, factory mounted
0 = none A = low limit switch B = condensate overflow switch C = dirty filter switch D = fan status switch
combined options
E = A and B F = A and C G = A and D H = B and C J = B and D K = C and D L = A, B, and, C M = A, B, and D N = A, C, and D P = B, C, and D R = A, B, C, and D
Digit 30 - Control options 2
0 = none A = discharge air sensor (DAS) B = mixed air sensor (MAS) D = NO mixing box act. E = NC mixing box act.
combined options
F = A and B H = A and D J = A and E L = B and D M = B and E R = A, B, and D T = A, B, and E 1 = field mounted, NO, mixing box act. 2 = field mounted, NC, mixing box act. 3 = DAS & field sup. NO mixing box act. 4 = DAS & field sup. NC, mixing box act. 5 = MAS & field sup. NO mixing box act. 6 = MAS & field sup. NC mixing box act. 7 = DAS, MAS field sup. NO mix. box act. 8 = DAS, MAS field sup. NC mix. box act.
information
Digit 31 - Control function
0 = none 1 = mixed air ctrl. 2 = mixed air preheat ctrl. 3 = economizing with mixed air ctrl. 4 = economizing with mixed air preheat ctrl.
Digit 32 - Control options 3, factory provided, field installed
0 = none A = outdoor air temperature sensor B = duct static pressure sensor C = A & B D = outdoor air temperature communicated E = duct static pressure communicated F = D & E
Digit 33 – Preheat control valve options
0 = none A = 3/4” 2-way, NO 7.3 Cv B = 3/4” 2-way, NC 7.3 Cv C = 3/4” 3-way, NO 7.3 Cv D = 3/4” 3-way, NC 7.3 Cv E = 1” 2-way, NO 11.6 Cv F = 1” 2-way, NC 11.6 Cv G = 1” 3-way, NO 11.6 Cv H = 1” 3-way, NC 11.6 Cv J = 1 1/4” 2-way, NO 18.5 Cv K = 1 1/4” 2-way, NC 18.5 Cv L = 1 1/4” 3-way, NO 18.5 Cv M = 1 1/4” 3-way, NC 18.5 Cv N = 1 1/2” 2-way, NO 28.9 Cv P =1 1/2” 2-way, NC 28.9 Cv Q = 1 1/2” 3-way, NO 28.9 Cv R =1 1/2” 3-way, NC 28.9 Cv T = 2” 2-way, NO 46.2 Cv U = 2” 2-way, NC 46.2 Cv V = 2” 3-way, NO 46.2 Cv W = 2” 3-way, NC 46.2 Cv X = 2 1/2” 2-way, NO 54 Cv Y = 2 1/2” 2-way, NC 54 Cv Z = 2 1/2” 3-way, NO 54 Cv 1 = 2 1/2” 3-way, NC 54 Cv 2 = field supplied 2-way NO 3 = field supplied 2-way NC 6 = field supplied 3-way NO 7 = field supplied 3-way NC
Note: NO = Normally open & NC = Normally closed in the
valve’s de-energized state
12 LPC-SVX01C-EN
general
Installation
Digit 34 – Cooling control valve options
0 = none A = 3/4” 2-way, NO 7.3 Cv B = 3/4” 2-way, NC 7.3 Cv C = 3/4” 3-way, NO 7.3 Cv D = 3/4” 3-way, NC 7.3 Cv E = 1” 2-way, NO 11.6 Cv F = 1” 2-way, NC 11.6 Cv G = 1” 3-way, NO 11.6 Cv H = 1” 3-way, NC 11.6 Cv J = 1 1/4” 2-way, NO 18.5 Cv K = 1 1/4” 2-way, NC 18.5 Cv L = 1 1/4” 3-way, NO 18.5 Cv M = 1 1/4” 3-way, NC 18.5 Cv N = 1 1/2” 2-way, NO 28.9 Cv P = 1 1/2” 2-way, NC 28.9 Cv Q = 1 1/2” 3-way, NO 28.9 Cv R =1 1/2” 3-way, NC 28.9 Cv T = 2” 2-way, NO 46.2 Cv U = 2” 2-way, NC 46.2 Cv V = 2” 3-way, NO 46.2 Cv W = 2” 3-way, NC 46.2 Cv X = 2 1/2” 2-way, NO 54 Cv Y = 2 1/2” 2-way, NC 54 Cv Z = 2 1/2” 3-way, NO 54 Cv 1 = 2 1/2” 3-way, NC 54 Cv 2 = field supplied, 2-way NO 3 = field supplied, 2-way NC 6 = field supplied, 3-way NC 7 = field supplied, 3-way NC
Note: NO = Normally open & NC = Normally closed in the
valve’s de-energized state
information
Digit 35 – Reheat control valve options
0 = none A = 3/4” 2-way, NO 7.3 Cv B = 3/4” 2-way, NC 7.3 Cv C = 3/4” 3-way, NO 7.3 Cv D = 3/4” 3-way, NC 7.3 Cv E = 1” 2-way, NO 11.6 Cv F = 1” 2-way, NC 11.6 Cv G = 1” 3-way, NO 11.6 Cv H = 1” 3-way, NC 11.6 Cv J = 1 1/4” 2-way, NO 18.5 Cv K = 1 1/4” 2-way, NC 18.5 Cv L = 1 1/4” 3-way, NO 18.5 Cv M = 1 1/4” 3-way, NC 18.5 Cv N = 1 1/2” 2-way, NO 28.9 Cv P = 1 1/2” 2-way, NC 28.9 Cv Q = 1 1/2”3-way, NO 28.9 Cv R = 1 1/2” 3-way, NC 28.9 Cv T = 2” 2-way, NO 46.2 Cv U = 2” 2-way, NC 46.2 Cv V = 2” 3-way, NO 46.2 Cv W = 2” 3-way, NC 46.2 Cv X = 2 1/2” 2-way, NO 54 Cv Y = 2 1/2” 2-way, NC 54 Cv Z = 2 1/2” 3-way, NO 54 Cv 1 = 2 1/2” 3-way, NC 54 Cv 2 = field supplied, 2-way NO 3 = field supplied, 2-way NC 6 = field supplied 3-way NO 7 = field supplied 3-way NC
Note: NO = Normally open & NC = Normally closed in the
valve’s de-energized state
Digit 36 – External exhaust fan support
0 = none 1 = configure for control 2 = configure for exhaust fan start/stop &
status support
3 = generic temperature thermistor
Digit 37 – Zone sensor options
0 = none 1 = sensor w/off, auto, Fahrenheit knob,
on/cancel and comm jack
2 = sensor w/Fahrenheit knob, on/cancel
and comm jack 4 = sensor only 5 = field supplied zone sensor F = standalone operator display G = 1 & F H = 2 & F J = 4 & F K = 5 & F
LPC-SVX01C-EN 13
dimensions
Horizontal Unit, in.
Installation
& weights
HorizontalPackagedClimateChangerdimensions&weights,in-lbs.
unit weights size H W L A B C D E F G J K(RH) K(LH) M N P R S T SW DW 3 24.5 31.2 54.0 20.5 27.2 10.6 9.4 3.0 2.3 10.9 10.9 12.6 17.6 33.0 1.0 1.6 0.8 2.7 15.1 164 231 6 30.5 44.2 57.0 26.5 40.2 13.8 12.5 3.0 3.3 15.9 15.9 12.6 17.6 46.0 1.0 1.6 0.8 2.0 15.1 232 323 8 34.5 48.2 48.0 30.0 44.2 13.8 15.9 3.5 8.7 18.6 13.6 --- --- 50.0 1.0 1.6 1.0 2.4 15.1 240 337 10 34.5 60.2 52.0 30.0 56.2 16.2 18.9 3.5 3.8 20.6 20.6 --- --- 62.0 1.0 1.6 1.0 2.0 15.1 277 398 12 42.0 68.2 56.0 37.5 64.2 19.2 19.2 3.5 5.4 24.5 24.5 --- --- 70.0 1.0 1.6 1.0 2.1 15.1 462 607 14 42.0 68.2 56.0 37.5 64.2 19.2 22.2 3.5 5.4 23.0 23.0 --- --- 70.0 1.0 1.6 1.0 2.1 15.1 476 619 17 52.0 76.2 62.0 47.5 72.2 25.1 20.1 3.5 8.9 28.1 28.1 --- --- 78.0 1.0 1.6 1.0 2.1 15.1 594 775 21 52.0 76.2 62.0 47.5 72.2 25.1 25.1 3.5 8.9 25.6 25.6 --- --- 78.0 1.0 1.6 1.0 2.1 15.1 636 819 25 59.5 78.2 67.0 53.0 74.2 25.5 23.5 4.5 15.7 27.4 27.4 --- --- 80.0 2.0 2.8 1.3 2.0 18.1 771 1000 30 59.5 91.2 72.0 53.0 87.2 28.5 26.5 4.5 11.3 32.4 32.4 --- --- 93.0 2.0 2.8 1.3 2.0 18.1 967 1233
Notes: 1. Weight of basic unit includes: cabinet, fan, average drive and filter. Add 9 pounds to basic weight for control box, if applicable
2. For units with factory installed VFD, an additional 11.26 inches needs to be added to the width of the unit to accomadote VFD
3. SW = Single Wall
4. DW = Double Wall
14 LPC-SVX01C-EN
dimensions
Vertical Unit, in.
Installation
& weights
Vertical Packaged Climate Changer dimensions & weights, in-lbs.
unit K N Weights size H W L A B C D E F G J LH RH M SW DW P R S T SW DW
3 47.0 31.2 40.0 20.5 27.2 10.6 9.4 3.0 2.3 10.9 10.9 17.6 12.6 33.0 6.0 6.0 1.6 .75 2.67 21.0 189 287
6 59.0 44.2 46.0 26.5 40.2 13.8 12.5 3.0 2.3 15.9 15.9 17.6 12.6 46.0 6.0 6.0 1.6 .75 2.03 24.4 275 419
8 66.5 48.2 34.0 30.0 44.2 13.8 15.9 3.5 8.7 18.6 13.6 --- --- 50.0 6.0 6.0 1.7 1.0 2.38 12.1 286 428
10 66.5 60.2 38.0 30.0 56.2 16.2 18.9 3.5 3.8 20.6 20.6 --- --- 62.0 6.0 6.0 1.7 1.0 1.96 14.0 316 493
12 82.0 68.2 42.0 37.5 64.2 19.2 19.2 3.5 5.4 24.5 24.5 --- --- 70.0 6.0 6.0 1.7 1.0 2.07 15.0 526 751
14 82.0 68.2 42.0 37.5 64.2 19.2 22.2 3.5 5.4 23.0 23.0 --- --- 70.0 6.0 6.0 1.7 1.0 2.07 13.0 539 769
17 102.5 76.2 45.0 47.5 72.2 25.1 20.1 3.5 8.9 28.1 28.1 --- --- 78.0 6.0 5.0 1.7 1.0 2.06 13.0 709 998
21 102.5 76.2 45.0 47.5 72.2 25.1 25.1 3.5 8.9 25.6 25.6 --- --- 78.0 6.0 5.0 1.7 1.0 2.06 13.0 750 1041
Notes: 1. Vertical units are only available in sizes 3 – 21.
2. For units with factory installed VFD, an additional 11.26 inches needs to be added to the width of the unit to accomadote VFD
3. SW = Single Wall
4. DW = Double Wall
LPC-SVX01C-EN 15
dimensions
Access Section, in.
Note: This is a flanged edge to secure section to either the main unit or another section.
Installation
Airflow
& weights
Note: Access section is only available with a 1 or 2-row heating coil and ships seperate from main unit.
Access section dimensions & weights, in-lbs.
unit weight size H L W SW DW
3 24.5 24.3 31.2 69 97 6 30.5 24.3 44.2 100 137 8 34.5 24.3 48.2 106 148 10 34.5 24.3 60.2 119 169 12 42.0 24.3 68.2 162 218 14 42.0 24.3 68.2 157 213 17 52.0 24.3 76.2 204 267 21 52.0 24.3 76.2 196 259 25 59.5 28.3 78.2 248 336 30 59.5 28.3 91.2 271 370
Notes: 1. SW = Single Wall
2. DW = Double Wall
16 LPC-SVX01C-EN
dimensions
Angle Filter Section in.
Note: This is a flanged edge to secure section to either the main unit or another section.
Installation
Airflow
(5.6)
& weights
(5.6)
Note: Angle filter section ships seperate from main unit.
Flat Filter Section in.
Airflow
Angle & flat filter section dimensions & weights, in-lbs.
unit flat filter angle filter size H L W SW DW SW DW
3 24.5 21.5 31.2 46 60 50 64 6 30.5 24.0 44.2 64 86 68 90 8 34.5 27.3 48.2 78 107 82 111 10 34.5 25.5 60.2 83 115 89 121 12 42.0 27.3 68.2 112 151 126 165 14 42.0 27.3 68.2 112 151 126 165 17 52.0 29.3 76.2 164 209 179 224 21 52.0 29.3 76.2 164 209 179 224 25 59.5 35.0 78.2 184 250 200 266 30 59.5 35.0 91.2 201 275 217 291
Notes: 1. SW = Single Wall
2. DW = Double Wall
LPC-SVX01C-EN 17
dimensions
Damper Section, in.
Note: This is a flanged edge to secure section to either the main unit or another section.
Installation
OPENING OPENING
Airflow
(6.1)
Notes: All dimensions are in inches. Damper section ships seperate from main unit. Linkage between dampers factory installed inside mixing box on drive side.
& weights
(6.1)
18 LPC-SVX01C-EN
Damper section dimensions & weights, in-lbs.
unit damper weights size H L W A B C D qty. - size SW DW
3 24.5 21.5 31.2 14.0 16.0 7.6 5.8 2 - 14.0 x 16.0 80 98
6 30.5 24.0 44.2 14.0 29.0 7.6 5.8 2 - 14.0 x 29.0 119 147
8 34.5 27.3 48.2 19.7 26.0 11.1 5.8 2 - 19.7 x 26.0 135 170
10 34.5 25.5 60.2 14.0 46.0 7.1 5.8 2 - 14.0 x 46.0 168 208
12 42.0 27.3 68.2 19.7 37.0 15.6 5.8 2 - 19.7 x 37.0 186 237
14 42.0 27.3 68.2 19.7 44.0 12.1 5.8 2 - 19.7 x 44.0 199 248
17 52.0 29.3 76.2 19.7 53.0 11.6 5.8 2 - 19.7 x 53.0 274 340
21 52.0 34.0 76.2 25.5 53.0 11.6 5.8 2 - 25.7 x 53.0 309 376
25 59.5 35.0 78.2 25.5 58.0 10.1 6.0 2 - 25.7 x 58.0 318 399
30 59.5 35.0 91.2 25.5 68.0 11.6 6.0 2 - 25.7 x 68.0 355 447
Notes: 1. SW = Single Wall
2. DW = Double Wall
dimensions
Face & Bypass Section, in.
Note: This is a flanged edge to secure section to either the main unit or another section.
Installation
OPENING
Airflow
& weights
OPENING
Notes: All dimensions are in inches. Damper section ships seperate from main unit. Linkage between dampers factory installed inside mixing box on drive side.
Face & bypass section dimensions & weights, in-lbs.
unit face bypass weights size H L W A B C D E F G J K M damper damper SW DW
3 24.5 23.5 31.2 14.0 16.0 14.0 26.0 22.5 28.7 7.6 5.6 5.3 1.0 14.0 x 27.0 14.0 x 16.0 94 111
6 30.5 26.0 44.2 14.0 29.0 19.7 39.0 28.5 41.7 7.6 7.4 4.6 1.0 19.7 x 40.0 14.0 x 29.0 140 165
8 34.5 28.3 48.2 19.7 26.0 25.5 43.0 32.5 45.6 11.1 4.6 3.8 1.0 25.5 x 44.0 19.7 x 26.0 159 188
10 34.5 26.5 60.2 14.0 46.0 25.5 55.0 32.5 57.6 7.1 7.6 3.8 1.0 25.5 x 56.0 14.0 x 49.0 198 231
12 42.0 28.3 68.2 19.7 37.0 31.2 63.0 40.0 65.7 15.6 4.6 4.6 1.0 31.2 x 64.0 19.7 x 37.0 220 260
14 42.0 28.3 68.2 19.7 44.0 31.3 63.0 40.0 65.7 12.1 4.6 4.6 1.0 31.2 x 64.0 19.7 x 44.0 235 274
17 52.0 32.3 76.2 19.7 53.0 42.7 71.0 50.0 73.6 11.6 7.6 3.9 1.0 42 x 72.0 19.7 x 53.0 323 371
21 52.0 35.0 76.2 25.5 53.0 42.7 71.0 50.0 73.6 11.6 4.6 3.9 1.0 42.72 x 72.0 25.5 x 53.0 365 417
25 59.5 37.0 78.2 25.5 58.0 48.5 74.0 53.0 74.0 10.1 5.2 6.4 4.5 48.47 x 74.0 25.5 x 58.0 375 437
30 59.5 37.0 91.2 25.5 68.0 48.5 87.0 53.0 87.0 11.6 5.2 6.4 4.5 48.47 x 87.0 25.5 x 68.0 419 489
Notes: 1. SW = Single Wall
2. DW = Double Wall
LPC-SVX01C-EN 19
dimensions
Installation
Electric Heat Section
Electric Heat Section Dimensions & Weights, in-lbs.
Unit Size H W A B C D Weight
3 24.5 18.0 12.0 10.4 9.3 12.1 34.0
6 30.5 21.0 16.0 13.6 12.3 8.9 38.0
8 34.5 24.5 16.0 13.6 15.8 9.9 44.0
10 34.5 27.5 20.0 16.0 18.8 11.5 62.0
12 42.0 27.8 20.0 19.0 19.0 13.5 66.0
14 42.0 30.8 20.0 19.0 22.0 13.5 69.0
17 52.0 28.6 20.0 24.9 19.9 7.6 73.0
21 52.0 33.6 20.0 24.9 24.9 7.6 77.0
25 59.5 32.0 20.0 25.3 23.3 7.3 79.0
30 59.5 35.1 20.0 28.3 26.4 4.2 82.0
CUSTOMER ELECTRICAL CONNECTION LOCATION & SIZE TO BE DETERMINED BY TUTCO
& weights
20 LPC-SVX01C-EN
dimensions
Water Coil Connections
Installation
left hand
AIR FLOW
& weights
right hand
Note: J = 3.1” on unit sizes 3 and 6
K = 6.1” on unit sizes 3–21
= 3.6” on unit sizes 8–21 = 4.6” on unit sizes 25 & 30
= 8.1” on unit sizes 25 & 30
AIR FLOW
LPC-SVX01C-EN 21
dimensions
Installation
& weights
Water coil connections, in.
unit size A B C D A B C D E F G H
one-row coil
38
611
8, 10 13 5/
12, 14 17 5/
17, 21 22 5/
25, 30 25 3/
two-row coil
37
6 10 13/
8, 10 13 5/
12, 14 17 20 1/
17, 21 22 25 1/
25, 30 25 1/
four-row coil
37
6 10 13/
8, 10 13 5/
12, 14 17 20 1/
17, 21 22 25 1/
25, 30 25 1/
six-row coil
37
6 10 13/
8, 10 13 5/
12, 14 17 20 1/
17, 21 22 25 1/
25, 30 25 1/
eight-row coil
37
6 10 13/
8, 10 13 5/
12, 14 17 20 1/
17, 21 22 25 1/
25, 30 25 1/
left hand connections only right hand connections only
5
/
8
1
/
8
8
16
16
8
5
/
8
16
16
8
5
/
8
16
16
8
5
/
8
16
16
8
5
/
8
16
16
8
11 11/
14 3/
16 11/
20 3/
25 3/
28 5/
10 13/
13 7/
16 3/
28 3/
10 13/
13 7/
16 3/
28 3/
10 13/
13 7/
16 3/
28 3/
10 13/
13 7/
16 3/
28 5/
16
16
16
8
8
8
16
8
8
8
8
16
16
8
8
8
8
16
16
8
8
8
8
16
16
8
8
8
8
16
2 18 5/
2 23 5/
2 28 5/
2 35 13/
2 45 13/
2 5/
8
1 3/
8
16
16
16
16
16
51 3/824 13/
17 8 7/
2 22 5/810 13/
2 27 5/
2 35 1/
2 45 1/
2 51 3/
2 5/
18 5/
8
16
2 22 5/810 13/
2 27 5/
2 35 1/
2 45 1/
2 51 3/
2 5/
18 5/
8
16
2 22 5/810 13/
2 27 5/
2 35 1/
2 45 1/
2 51 3/
2 5/
18 5/
8
16
2 22 5/810 13/
2 27 5/
2 35 1/
2 45 1/
2 51 3/
7 7/
10 3/
12 7/
16 11/
21 11/
13 5/
8
8
8
8
17 20 1/
22 25 1/
25 1/
8 7/
13 5/
8
8
8
8
17 20 1/
22 25 1/
25 1/
8 7/
13 5/
8
8
8
8
17 20 1/
22 25 1/
25 1/
8 7/
13 5/
8
8
8
8
17 20 1/
22 25 1/
25 1/
11 1/
8
13 5/
8
16 1/
8
19 13/
16
24 13/
16
27 7/
16
8
13 7/
16
16 3/
16
28 5/
8
8
13 7/
16
16 3/
16
28 5/
8
8
13 7/
16
16 3/
16
28 5/
8
8
13 7/
16
16 3/
16
28 5/
8
1 3/
8
1 3/
8
1 3/
8
1 3/
16
1 3/
16
8
12 2 5/
8
8
8
8
16
12 2 5/
8
8
8
8
16
12 2 5/
8
8
8
8
16
12 2 5/
8
8
8
8
16
17 5/81 11/
8
22 5/81 11/
8
27 5/81 11/
8
35 1/
8
8
2 50 13/
8
8
45 1/
8
16
18 5/161 13/
2 22 5/81 13/
2 27 5/81 13/
2 35 1/
2 45 1/
2 51 3/
8
2 22 5/
2 27 5/
2 35 1/
2 45 1/
2 51 3/
8
8
8
8
18 5/
16
8
8
8
8
8
18 5/161 13/
2 22 5/81 13/
2 27 5/81 13/
2 35 1/81 13/
2 45 1/81 13/
2 51 3/81 13/
18 5/161 13/
8
2 22 5/81 13/
2 27 5/81 13/
2 35 1/81 13/
2 45 1/81 13/
2 51 3/81 13/
3 11/
16
3 11/
16
3 11/
16
1 1/
2
1 1/
2
24 1/
16
16
16
1 1/23 13/
1 1/23 13/
1 7/
8
47 3/
47 3/
47 3/
47 3/
47 3/
47 3/
7 3/
16
7 3/
16
7 3/
16
7 3/
16
7 3/
16
7 3/
16
16
16
16
16
16
16
3 7/
3 7/
3 5/
3 5/
3 5/
4 5/
9 3/
9 3/
9 3/
9 3/
9 3/
9 3/
5 3/
16
16
16
8
8
2
8
8
8
16
16
8
16
16
16
16
16
16
16
16
16
16
16
16
8
8
8
8
8
8
8
5 3/
8
5 3/
8
5 3/
8
5 3/
8
6 1/
2
5 3/
8
5 3/
8
5 3/
8
5 3/
8
5 3/
8
6 1/
2
91
91
91
92
92
92
91
91
91
92
92
92
11 3/
16
11 3/
16
11 3/
16
11 3/
16
11 3/
16
11 3/
16
1 1/
1 1/
1 1/
1 1/
1 1/
1 1/
2 1/
1 1/
1 1/
1 1/
2 1/
2 1/
2
2
2
2
2
2
2
2
2
2
2
2
1
/
2
1
/
2
1
/
2
1
/
2
1
/
2
1
/
2
1
/
2
1
/
2
1
/
2
1
/
2
2
2
2
2
2
2
22 LPC-SVX01C-EN
dimensions
Installation
DX Coil Connections
single circuit coils for unit sizes 3 –10 and horizontal face split coils for unit sizes 12 – 25
left hand
AIR FLOW
NOTE: DX COIL CONNECTIONS ARE SWEAT STYLE
& weights
right hand
AIR FLOW
Single circuit DX coil connections, unit sizes 3 - 10, in.
unit size A B C D (LH) D (RH) G H J K
four-row coil, 3 2 3/810 5/1645 1/87 3/161 3/8 5/83 1/86 1/
6 2 3/817 11/1645 1/87 3/161 3/8 7/83 1/86 1/
8 2 3/818 13/1645 1/87 3/161 3/8 7/83 5/86 1/
10 2 1/218 3/1645 1/87 3/161 5/8 7/83 5/86 1/
six-row coil, 1/4” distributor 3 2 3/811 1 13/162 7/851 3/8 7/83 1/86 1/
6 2 3/817 11/161 13/162 7/851 3/8 7/83 1/86 1/
8 2 3/819 5/161 13/162 7/851 3/81 1/83 5/86 1/
10 2 1/219 1 13/162 7/851 5/81 3/83 5/86 1/
Note: Single circuit DX coils on unit sizes 3 – 10 have one distributor.
3
/16” distributor
8
8
8
8
8
8
8
8
Horizontal face split circuit DX coil connections, unit sizes 8 – 25, in.
unit size A B C D (LH) D (RH) E F G G1 H H1 J K
four-row coil, 82
10 2 3/
12, 14 1 7/
17, 21 1 7/
25 1 7/
six-row coil, 1/4” distributor
82
10 2 3/
12, 14 2 3/
17, 21 2 3/
3
/16” distributor
3
/
8
8
8
8
8
3
/
8
8
8
8
8 1/
8
8 1/
8
12 5/
8
17 5/
8
18 5/
16
8 13/
16
13/
16
13 1 13/
18 3/
16
45 1/
45 1/
45 1/
45 1/
45 5/
1 13/
16
1 13/
16
16
1 13/
16
2 7/
2 7/
2 7/
2 7/
7 3/
8
7 3/
8
7 3/
8
7 3/
8
7 3/
16
8
8
8
8
17 3/
16
14 7/
16
16
16
16
19 7/
27 1/
5 17 3/
5 14 7/
519
525421
22 13/
8
22 3/81 3/81 3/
8
31 1/81 3/81 3/
8
16
1 3/81 3/
25 41 3/81 5/81 5/
43 5/
2
22 3/81 3/81 3/
8
22 3/81 3/81 5/
8
7
/
31 3/81 3/81 3/
8
16
1 5/81 5/
5
/81 5/
5/
8
7/
8
7/
8
7/
8
7/
8
7/
8
7/
8
1 1/
8
1 1/
8
5/
8
8
8
8
8
7/
8
7/
8
7/
8
1 1/
8
3 5/
8
7
/
8
7
/
8
7
/
8
7
/
8
8
8
8
8
3 5/
3 5/
3 5/
4 5/
3 5/
3 5/
3 5/
3 5/
8
8
8
8
8
8
8
8
8
6 1/
6 1/
6 1/
6 1/
8 1/
6 1/
6 1/
6 1/
6 1/
8
8
8
8
8
8
8
8
8
LPC-SVX01C-EN 23
dimensions
DX Coil Connections
horizontal face split circuit coils for unit size 30
Installation
left hand
AIR FLOW
& weights
NOTE: DX COIL CONNECTIONS ARE SWEAT STYLE
right hand
AIR FLOW
NOTE: DX COIL CONNECTIONS ARE SWEAT STYLE
Horizontal face split circuit DX coil connections, unit size 30, in.
ABCDE F G four-row coil, 3/16” distributor 3 1/84 13/1611 1/823 5/836 1/848 5/8 7/
six-row coil, 1/4” distributor 12 5/811 7/824 3/836 7/849 3/81 3/
Note: Horizontal face split circuit DX coils on unit size 30 has four distributors.
8
8
24 LPC-SVX01C-EN
dimensions
DX Coil Connections intertwined coils unit sizes 8 – 30
NOTE: DX COIL CONNECTIONS ARE SWEAT STYLE
Installation
left hand
AIR FLOW
right hand
& weights
AIR FLOW
Intertwined circuit DX coil connections, unit sizes 8 – 30, in.
unit size A B C D E F G H J J
four-row coil, 82 10 2 12,14 2 17, 21 2 25 2 3/84 7/817 1/220 3 3/164 11/165 5/167 5/16 7/81 3/81 3/81 3/8 7/8 7/8 7/8 7/827 3/829 7/842 1/245 30 2 1/23 13/1618 7/820 1/83 1/84 7/86 3/168 3/161 5/81 5/81 5/81 5/8 7/8 7/8 7/8 7/827 1/228 13/1643 7/845 1/
six-row coil, 1/4” distributor 82 10 2 12,14 2 17, 21 2 25 2 30 2 1/23 13/1619 11/1620 7/812 5/86 3/168 3/161 5/81 5/81 5/81 5/81 3/81 3/81 3/81 3/827 1/228 13/1644 11/1645 7/
Note: DX intertwined coils, on unit sizes 8 – 14 have two distributors. Unit sizes 17 – 30 have four distributors.
3
/16” distributor
3
/86 3/1618 3/1614 1/83 3/164 11/165 5/167 5/161 3/8-- 1 3/8-- 5/8-- 5/8-- -- -- -- -
3
/84 7/820 1/822 5/83 3/164 11/165 5/167 5/161 3/8-- 1 3/8-- 7/8-- 7/8-- -- -- -- --
3
/84 7/822 13/1619 11/163 3/164 11/165 5/167 5/161 3/8-- 1 3/8-- 7/8-- 7/8-- -- -- -- --
3
/84 7/817 1/214 7/83 3/164 11/165 5/167 5/161 3/81 3/81 3/81 3/8 5/8 5/8 7/8 5/824 7/827 3/836 1/838 5/
3
/86 3/1618 5/814 7/812 5/83 3/165 3/161 3/8-- 1 3/8-- 7/8-- 7/8-- -- -- -- --
3
/84 7/820 1/822 5/812 5/83 3/165 3/161 3/8-- 1 3/8-- 7/8-- 7/8-- -- -- -- --
3
/84 7/823 3/1619 13/1612 5/83 3/165 3/161 3/8-- 1 3/8-- 7/8-- 1 1/8-- -- -- -- --
3
/84 7/817 1/215 5/1612 5/83 3/165 3/161 3/81 3/81 3/81 3/8 7/8 7/8 7/8 7/824 7/827 3/836 1/239
3
/84 7/817 1/220 1 2 5/83 3/165 3/161 3/81 3/81 3/81 3/8 7/8 7/8 7/8 7/827 3/829 7/842 1/245
J2J
1
KK1K2K
3
LM N P
3
8
8
8
LPC-SVX01C-EN 25
dimensions
Steam Coil Connections
left hand
AIR FLOW
Installation
right hand
& weights
AIR FLOW
Steam coil connections, in.
unit size A B (LH) B (RH) C D E F (LH) F (RH) G G
34
6 4 13 3/
8, 10 3 3/
12, 14 2 3/
17, 21 2 3/
25, 30 2 5/
Note: Unit sizes 17 – 30 with steam coils are two stacked coils.
1
/
10 7/
2
15 7/
16
18 3/
8
14 7/
16
15 12 1 5/
16
7 7/
8
10 3/
8
12 7/
8
18 3/
16
11 7/
8
1 5/
8
1 5/
8
1 5/
8
1 5/
16
1 5/
8
2 13/
16
2 1/
16
2 1/
16
2 1/
16
2 1/
16
2 1/
16
-- -- -- 1 -- 1 1/
16
-- -- -- 1 -- 2 -- 3 1/
2
-- -- -- 1 5/
2
-- -- -- 1 5/
2
28 37 3/
2
2
27 13/1640 1/
8
2
34 3/
37 1/
8
2
1 5/
1 5/
16
16
16
16
HH1JK
1
-- 2 1/
2
2
-- 3 1/
-- 3 5/
-- 3 -- 3 5/
12
1 5/
1
/
23
2
2 1/
16
2 1/
2
4 5/
2
6 1/
8
8
8
8
5
/
8
8
6 1/
6 1/
6 1/
6 1/
8 1/
8
8
8
8
8
8
26 LPC-SVX01C-EN
pre-installation
WARNING
Hazardous Voltage w/Capacitors!
Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized. For variable frequency drives or other energy storing components provided by Trane or others, refer to the appropriate manufacturer’s literature for allowable waiting periods for discharge of capacitors. Verify with an appropriate voltmeter that all capacitors have discharged. Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury.
Receiving and Handling
Upon delivery, inspect all components for possible shipping damage. See the Receiving Checklist section for detailed instructions. Trane recommends leaving units and accessories in their shipping packages/skids for protection and ease of handling until installation.
Shipping Package
Packaged Climate Changer air handlers ship assembled on skids with protective coverings over the coil and discharge openings. Optional accessory sections ship attached to one another on a separate skid for unit sizes except 25 and
30. For those sizes, up to two accessory sections may ship on one skid.
Ship-Separate Accessories
Field-installed sensors ship separately inside the unit’s main control panel.
Receiving Checklist
Complete the following checklist immediately after receiving unit shipment to detect possible shipping damage.

Inspect individual cartons before

accepting. Check for rattles, bent carton corners, or other visible indications of shipping damage.
Installation

If a unit appears damaged, inspect it

immediately before accepting the shipment. Manually rotate the fan wheel to ensure it turns freely. Make specific notations concerning the damage on the freight bill. Do not refuse delivery.

Inspect the unit for concealed

damage before it is stored and as soon as possible after delivery. Report concealed damage to the freight line within the allotted time after delivery. Check with the carrier for their allotted time to submit a claim.

Do not move damaged material from

the receiving location. It is the receiver’s responsibility to provide reasonable evidence that concealed damage did not occur after delivery.

Do not continue unpacking the

shipment if it appears damaged. Retain all internal packing, cartons, and crate. Take photos of damaged material.

Notify the carrier’s terminal of the

damage immediately by phone and mail. Request an immediate joint inspection of the damage by the carrier and consignee.

Notify your Trane representative of

the damage and arrange for repair. Have the carrier inspect the damage before making any repairs to the unit.

Compare the electrical data on the

unit nameplate with the ordering and shipping information to verify the correct unit is received.
Table I-PC-1. Service Requirements, in. (cm)
Unit Size Dimension A
3 43 (109) 6 56 (142) 8 59 (150) 10 & 12 71 (180) 14 79 (201) 17 74 (188) 21 86 (218) 25 30
Figure I-PC-1. Top view of Packaged climate changer unit showing recommended service and code clearances.
considerations
Installation Preparation
Before installing the unit, consider the following unit location recommendations to ensure proper unit operation.
1. Verify the floor or foundation is level. Shim or repair as necessary. To ensure proper unit operation, install the unit level (zero tolerance) in both horizontal axes. Failure to level the unit properly can result in condensate management problems, such as standing water inside the unit.
2. Allow adequate service and code clearances as recommended in “Service Access” section. Position the unit and skid assembly in its final location.
3. Consider coil piping and condensate drain requirements. Allow room for proper ductwork and electrical connections. Support all piping and ductwork independently of the unit to prevent excess noise and vibration.
Service Access
See Table I-PC-1 below and Figure I-PC-1 for recommended service and code clearances.
3 Ft.
3 Ft.
3
3
LPC-SVX01C-EN 27
pre-installation
Rigging and Handling
Before preparing the unit for lifting, estimate the approximate center of gravity for lifting safety. Unit weight may be unevenly distributed with more weight in the coil area. Approximate unit weights are given in the Dimensions and Weights section and on the unit nameplate.
Before hoisting the unit into position, use a proper rigging method such as straps, slings, or spreader bars for protection and safety. Always test-lift the unit (at least 24 inches) to determine the exact unit balance and stability before hoisting it to the installation location.
WARNING
Improper Unit Lift!
Test lift unit approximately 24 inches to verify proper center of gravity lift point. To avoid dropping unit, reposition lifting point if unit is not level. Failure to properly lift unit could result in death, serious injury, or possible equipment or property-only damage.
Installation
Skid Removal
The unit ships on skids that provide forklift locations from the front or rear. The skid allows easy maneuverability of the unit during storage and transportation. Remove the skids before placing the unit in its permanent location.
Remove the skids using a forklift or jack. Lift one end of the unit off of the skids. Vibration isolators for external isolation are field supplied. See Figure I-PC-1 for installation recommendations.
Rotating Filter Door Swing
The unit ships with the fillter doors in a downstream configuration. To allow the doors to swing in an upstream configuration, follow the steps listed in the figure below.
Step 1:
Remove screws holding hinges to fixed panel near coil
considerations
Unit Location Recommendations
When selecting and preparing the installation location, follow these recommendations.
1. Consider the unit weight. Reference the unit weight on the unit nameplate or in the Dimensions and Weights section.
2. Allow sufficient space for recommended clearances, access panel removal, and maintenance access. Refer to Figure I-PC-1.
3. The installer must provide threaded suspension rods for ceiling mounted units. All units must be installed level.
4. Coil piping and condensate drain requirements must be considered. Allow room for proper ductwork and electrical connections. Support all piping and ductwork independently of unit to prevent excess noise and vibration.
28 LPC-SVX01C-EN
Step 2: Repeat Step 1
on opposite side of unit
Figure I-PC-2. Rotating Filter Door Swing
Swap doors to their opposite
Step 3:
sides. Hinges will now be located on the upstream side of the fan
Step 4:
Use self drilling screws removed in steps 1 & 2 to secure hinges to adjacent upstream panel
pre-installation
Fan Discharge Conversion
The LPC Vertical Unit can be ordered in four discharge configurations: Top/Front, Front/Top, Top/Back, and Back/ Top Figure I-PC-4. Discharge Configurations. Field conversions from one configuration to another can be made for sizes 8 through 21 by modifying certain parts of the cabinet and by rotating the fan. Also, if changing from a front or back discharge to a top discharge configuration, a duct extension will need to be added. For sizes 3 and 6 a new fan assembly will be needed. There are some differences between single-wall construction cabinets with fiberglass insulation and double-wall construction cabinets with foam insulation that will drive some minor differences in some of the steps required for a field conversion. But overall the basic steps are the same for both.
1. Disconnect power from the unit
2. Remove access doors.
3. Remove the screws inside the cabinet along the top of the coil that secure the coil to the cabinet roof
4a. If top discharge and no internal
isolation remove screws securing duct that connects the fan to the roof
b. If top discharge with internal isolation,
duct is not mechanically secured to the fan so roof & duct can be removed as one piece.
c. Remove roof 5a. If horizontal (front or back) discharge
and no internal isolation, remove screws securing fan housing to cabinet
b. If horizontal (front or back) discharge
with internal isolation loosen and remove j-bolt securing fan housing to cabinet.
c. Remove front and back panel.
6. Loosen nuts/bolts securing sliding motor base in place and loosen nuts on belt tensioning bolt.
7. Remove v-belt(s)
8. Detach fan from the base and rotate to the desired discharge position.
Installation
Figure I-PC-4. Discharge Configurations
9. It may be necessary to remove and reinstall the fan shaft on the opposite side depending on the new discharge position. Loosen set screws on the fan bearings that hold the shaft in place. Loosen set screw holding fan in place. Remove shaft from the fan and reinstall so that the driven end is on the opposite side.
10. Reattach fan to the base
considerations
11. Reattach v-belt, tighten, and secure sliding motor base in place. Because the distance between the motor shaft and the fan shaft may change, it may be necessary to purchase a new v­belt.
12. Cut a hole in the discharge panel for the air discharge. For double wall units cover the exposed foam insulation at the inside edges of the hole using the insulation cover channels installed on the other discharge panel.
LPC-SVX01C-EN 29
pre-installation
13a. If changing from horizontal discharge
to vertical (such as front/top to top/ front) then a duct extension will need to be added to join the fan to the roof.
b. On units without internal isolation the
duct extension is secured to the fan housing with screws. The duct can be purchased from Service Parts or can be fabricated in the field.
c. On units with internal isolation the
duct extension is wider at the bottom to form a gap between and the fan housing, which is bridged by a flexible foam gasket. Contact Service Parts for a duct extension kit. (See Fig. 1)
14a. If changing from vertical to horizontal
(such as top/front to front/top) then the duct extension will need to be replaced by mounting angles to join the fan to the cabinet.
Installation
b. On units without internal isolation the
mounting angles can be secured to the fan and to the cabinet with screws. The angles can be purchased from Service Parts or can be fabricated in the field.
c. On units with internal isolation the
mounting angles do not extend as far and do not reach the cabinet panel. The gap is bridged by a flexible foam gasket. Also the gasket stays compressed using a thrust restraint assembly. Contact Service parts for angle/gasket kit. (See Fig. 2)
15. Reattach roof
16. Reattach coil to roof support.
17. Reattach front/back panels
18. Reattach access doors.
considerations
Pre-Installation Checklist
Complete the following checklist before beginning unit installation.

Verify the unit size and tagging with

the unit nameplate.

Make certain the floor or foundation

is level, solid, and sufficient to support the unit and accessory weights. See the Dimensions and Weights section. Level or repair the floor before positioning the unit if necessary.

Allow minimum recommended

clearances for routine maintenance and service. Refer to unit submittals for dimensions.

Allow one and one half fan diameters

above the unit for the discharge ductwork.
Figure I-PC-5. Contact Service Parts for a Duct Extension Kit
Figure I-PC-6 Service PArts for Angle/Access Kits
30 LPC-SVX01C-EN
Loading...
+ 80 hidden pages