ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES
IMPORTANT — This Document is customer property and is to remain with this unit.
Please return to service information pack upon completion of work.
NOTE:
This furnace can be configured for Communicating or 24 VAC modes. Using fully Communicating or 24 VAC
modes, the furnace can support single or multi-stage heat pump, AC, or heating only applications. Combined with
a communicating Comfort Control only, the furnace will support a single stage 24 VAC cooling outdoor unit only.
1. Safety signal words are used to designate a degree or level of seriousness associated with a particular hazard.
2. The signal words for safety markings are WARNING, and CAUTION.
3. a. WARNING indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
4. b. CAUTION indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It
is also used to alert against unsafe practices and hazards involving only property damage.
DOWNFLOW/HORIZONTAL
A341624P14
Page 2
Installer’s Guide
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each
appliance connected to the venting system being
placed into operation could result in carbon monoxide
poisoning or death.
The following steps shall be followed for each appliance
connected to the venting system being placed into
operation, while all other appliances connected to the
venting system are not in operation:
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and
horizontal pitch, as required in the National Fuel Gas
Code, ANSI Z223.1/NFPA 54 or the CSA B149.1
Natural Gas and Propane Installation Code and these
instructions. Determine that there is no blockage or
restriction, leakage, corrosion and other deficiencies
which could cause an unsafe condition.
3. As far as practical, close all building doors and
windows and all doors between the space in which the
appliance(s) connected to the venting system are
located and other deficiencies which could cause an
unsafe condition.
4. Close fireplace dampers.
5. Turn on clothes dryers and any appliance not
connected to the venting system. Turn on any exhaust
fans, such as range hoods and bathroom exhausts, so
they are operating at maximum speed. Do not operate
a summer exhaust fan.
6. Follow the lighting instructions. Place the appliance
being inspected into operation. Adjust the thermostat
so appliance is operating continuously.
7. Test for spillage from draft hood equipped appliances
at the draft hood relief opening after 5 minutes of main
burner operation. Use the flame of a match or candle.
8. If improper venting is observed during any of the above
tests, the venting system must be corrected in
accordance with the National Fuel Gas Code,
ANSI Z221.1/NFPA 54 and/or CSA B149.1 Natural Gas and Propane Installation Code.
9. After it has been determined that each appliance
connected to the venting system properly vents where
when tested as outlined above, return doors, windows,
exhaust fans, fireplace dampers and any other gas-fired
burning appliance to their previous condition of use.
▲
WARNING
!
Failure to follow safety warnings exactly, could result
in a fire or explosion causing property damage,
personal injury or loss of life.
— Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any
other appliance.
— WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch;
do not use any phone in your building.
• Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s
instructions.
• If you cannot reach your gas supplier,
call the fire department.
— Installation and service must be performed by
a qualified installer, service agency or the gas
supplier.
▲
WARNING
!
The following warning complies with State of California law, Proposition 65.
Hazardous Gases!
Exposure to fuel substances or by-products of incomplete
fuel combustion is believed by the state of California to
cause cancer, birth defects, or other reproductive harm.
▲
WARNING
!
▲
WARNING
!
▲
CAUTION
!
▲
WARNING
!
▲
WARNING
!
FIRE OR EXPLOSION HAZARD
FAILURE TO FOLLOW THE SAFETY WARNINGS
EXACTLY COULD RESULT IN SERIOUS PERSONAL
INJURY, PROPERTY DAMAGE, OR DEATH.
IMPROPER SERVICING COULD RESULT IN
DANGEROUS OPERATION, SERIOUS PERSONAL
INJURY, PROPERTY DAMAGE, OR DEATH.
EXPLOSION HAZARD!
PROPANE GAS IS HEAVIER THAN AIR AND MAY
COLLECT IN ANY LOW AREAS OR CONFINED SPACES. IN ADDITION, ODORANT FADE MAY MAKE THE
GAS UNDETECTABLE EXCEPT WITH A WARNING
DEVICE. IF THE GAS FURNACE IS INSTALLED IN A
BASEMENT, AN EXCAVATED AREA OR A CONFINED
SPACE, IT IS STRONGLY RECOMMENDED TO CONTACT A GAS SUPPLIER TO INSTALL A GAS DETECTING WARNING DEVICE IN CASE OF A GAS LEAK.
NOTE: The manufacturer of your furnace does NOT test
any detectors and makes no representations regarding
any brand or type of detector.
SAFETY HAZARD
THIS INFORMATION IS INTENDED FOR USE BY INDIVIDUALS POSSESSING ADEQUATE BACKGROUNDS
OF ELECTRICAL AND MECHANICAL EXPERIENCE.
ANY ATTEMPT TO REPAIR A CENTRAL AIR CONDITIONING PRODUCT MAY RESULT IN PERSONAL
INJURY AND OR PROPERTY DAMAGE. THE MANUFACTURER OR SELLER CANNOT BE RESPONSIBLE
FOR THE INTERPRETATION OF THIS INFORMATION,
NOR CAN IT ASSUME ANY LIABILITY IN CONNECTION WITH ITS USE.
Sharp Edge Hazard. Be careful of sharp edges on
equipment or any cuts made on sheet metal while
installing or servicing. Personal injury may result.
Page 3
▲
CAUTION
!
▲
WARNING
!
▲
WARNING
!
▲
CAUTION
!
▲
WARNING
!
EXPLOSION HAZARD!
NEVER USE AN OPEN FLAME TO DETECT GAS
LEAKS. EXPLOSIVE CONDITIONS MAY OCCUR. USE
A LEAK TEST SOLUTION OR OTHER APPROVED
METHODS FOR LEAK TESTING. FAILURE TO FOLLOW THIS WARNING COULD RESULT IN PROPERTY
DAMAGE, PERSONAL INJURY OR DEATH.
To prevent shortening its service life, the Furnace
should NOT be used as a “Construction Heater”
during the finishing phases of construction until the
requirements listed in item 9, a-h of the safety section of this publication have been met. Condensate
in the presence of chlorides and fluorides from paint,
varnish, stains, adhesives, cleaning compounds, and
cement create a corrosive condition which may cause
rapid deterioration of the heat exchanger
.
SAFETY HAZARD
DO NOT USE SEMI-RIGID METALLIC GAS
CONNECTORS (flexible GAS lines) within the Furnace
cabinet. Failure to follow this warning could result in
property damage, personal injury or death.
Do NOT install the furnace in a corrosive or
contaminated atmosphere. Failure to follow this
caution could result in early equipment failure.
NOTE: The furnace must be installed level. The only
allowable variation would be slightly to the left and/
or forward in upflow installations or slightly toward
the front in horizontal installations. This is necessary
for proper condensate drainage.
3. Provide adequate combustion and ventilation air to the
Furnace space as specified in “Air for Combustion
SAFETY HAZARD
DO NOT INSTALL THE FURNACE DIRECTLY ON
CARPETING, TILE OR OTHER COMBUSTIBLE MATERIAL OTHER THAN WOOD FLOORING. FOR VERTICAL DOWNFLOW APPLICATIONS, SUBBASE (BAYBASE205) MUST BE USED BETWEEN THE FURNACE
AND COMBUSTIBLE FLOORING. WHEN THE DOWNFLOW FURNACE IS INSTALLED VERTICALLY WITH A
CASED COIL, A SUBBASE IS NOT REQUIRED. FAILURE TO FOLLOW THE WARNING EXACTLY COULD
RESULT IN SERIOUS PERSONAL INJURY, PROPERTY
DAMAGE OR DEATH.
The following safety practices and precautions must be
followed during the installation, servicing, and operation
of this furnace.
1. Use only with the type of gas approved for this
Furnace. Refer to the furnace rating plate.
2. Install this furnace only in a location and position as
specified in “Location and Clearances” on page 6 of
these instructions.
18-CD30D1-12 3
and Ventilation” of these instructions.
4. Combustion products must be discharged outdoors.
Connect this furnace to an approved vent system
only, as specified in the “Venting” section (pages 15-
27), of these instructions.
5. Never test for gas leaks with an open flame. Use
a commercially available soap solution made
specifically for the detection of leaks to check all
connections, as specified in the “Gas Piping” section
starting on page 34.
6. Always install the furnace to operate within the
furnace’s intended temperature-rise range with a duct
system which has an external static pressure within
the allowable range, as specified on the unit rating
plate. Airflow with temperature rise for cfm versus
static is shown in the Service Facts accompanying
this Furnace.
continued on page 6
Page 4
Installer’s Guide
(ALL DIMENSIONS ARE IN INCHES)
*UHM-ACV OUTLINE DRAWING
DIM "A" DIM "B" DIM "C" DIM "D" DIM "E" DIM "F"
MODEL
(SEE NOTE 1)
17-1/2"2-1/4"16-1/4"16"7-1/2"2"
*UHMB060ACV3VB
*UHMB080ACV3VB
NOTES:
1. DIAMETER OF VENT PIPE MAY BE LIMITED
TO 2-1/2" OR 3" ON SOME MODELS AT DIFFERENT
ALTITUDES. REFER TO THE VENT LENGTH TABLE
FOR PROPER APPLICATION.
*UHMC100ACV4VB21"2-1/2"19-3/4"19-1/2"9"3"
*UHMD120ACV5VB24-1/2" 2-15/16" 23-1/4"23"10"3"
4 18-CD30D1-12
Page 5
Installer’s Guide
(ALL DIMENSIONS ARE IN INCHES)
*DHM-ACV DOWNFLOW/ HORIZONTAL OUTLINE DRAWING
17-1/2"2-1/4"16-1/4"16"
DIM "A"DIM "B"DIM "C"DIM "D"
MODEL
(SEE NOTE 1)
*DHMB080ACV3VB
*DHMB060BCV3VB
*DHMC100ACV4VB21"2-1/2"19-3/4"19-1/2"
*DHMD120BCV5VB24-1/2"2-15/16"23-1/4"23"
18-CD30D1-12 5
Page 6
Installer’s Guide
7. When a furnace is installed so that supply ducts carry
air circulated by the furnace to areas outside the
space containing the furnace, the return air shall also
be handled by a duct(s) sealed to the furnace casing
and terminating outside the space containing the
furnace.
8. A gas-fired furnace for installation in a residential
garage must be installed as specified in “Location
and Clearances” section of these instructions.
9. The furnace may be used for temporary heating of
buildings or structures under construction only when
the following conditions have been met:
a. The furnace venting system must be complete
and installed per manufacturers instructions.
b. The furnace is controlled only by a room Comfort
Control (no field jumpers).
c. The furnace return air duct must be complete
and sealed to the furnace.
d. The furnace input rate and temperature rise must
be verified to be within nameplate marking.
e. 100% of the furnace combustion air requirement
must come from outside the structure.
f. The Furnace return air temperature range is
between 550 and 800 Fahrenheit.
g. Clean the Furnace, duct work, and components
upon substantial completion of the construction
process, and verify Furnace operating condition
including ignition, input rate, temperature rise and
venting, according to the manufacturer's instructions.
h. An external field supplied air filter must be used
during construction.
10. This product must be gas piped by a
Licensed Plumber or Gas Fitter in the
Commonwealth of Massachusetts.
LOCATION AND CLEARANCES
The location of the furnace is normally selected by the
architect, the builder, or the installer. However, before
the furnace is moved into place, be sure to consider the
following requirements:
1. Is the location selected as near the chimney or vent
and as centralized for heat distribution as practical?
2. Do all clearances between the furnace and enclosure
equal or exceed the minimums stated in Clearance
Table on the Outline Drawings provided in this
document?
3. Is there sufficient space for servicing the furnace and
other equipment? A minimum of 24 inches front
accessibility to the furnace must be provided. Any
access door or panel must permit removal of the
largest component.
4. Are there at least 3 inches of clearance between the
furnace combustion air openings in the front panel
and any closed panel or door provided?
5. Are the ventilation and combustion air openings large
enough and will they remain unobstructed? If outside
air is used, are the openings at least 12" above the
highest expected snow accumulation level (18"
minimum for Canadian applications)?
6. Allow sufficient height in supply plenum above the
furnace to provide for cooling coil installation, if the
cooling coil is not installed at the time of this furnace
installation.
7. A furnace shall be installed so electrical components
are protected from water.
8. If the furnace is installed in a residential garage, it
must be installed so that the burners, and the ignition
source are located not less than 18 inches above the
floor and the furnace must be located or protected to
avoid physical damage from vehicles.
GENERAL INSTALLATION
INSTRUCTIONS
The manufacturer assumes no responsibility for
equipment installed in violation of any code or regulation.
It is recommended that Manual J of the Air Conditioning
Contractors Association (ACCA) or A.R.I. 230 be followed
in estimating heating requirements. When estimating
heating requirements for installation at Altitudes above
2000 ft., remember the gas input must be reduced (See
GAS INPUT ADJUSTMENT).
Material in this shipment has been inspected at the
factory and released to the transportation agency
without known damage. Inspect exterior of carton
for evidence of rough handling in shipment. Unpack
carefully after moving equipment to approximate
location. If damage to contents is found, report the
damage immediately to the delivering agency.
Codes and local utility requirements governing the
installation of gas fired equipment, wiring, plumbing,
and flue connections must be adhered to. In the
absence of local codes, the installation must conform
with latest edition of the National Fuel Gas Code ANSI
Z223.1 • National Installation Code, CAN/CGA B149.1.
The latest code may be obtained from the American
Gas Association Laboratories, 400 N. Capitol St. NW,
Washington D.C. 20001.
1-800-699-9277 or www.aga.org
These furnaces have been classified as CATEGORY IV
furnaces in accordance with latest edition of ANSI Z21.47
standards • CAN/CGA 2.3. Category IV furnaces operate
with positive vent static pressure and with a flue loss less
than 17 percent. These conditions require special venting
systems, which must be gas tight and water tight. These
Category IV Direct Vent furnaces are not approved for
installation in Manufactured/Mobile housing.
6 18-CD30D1-12
Page 7
▲
WARNING
!
SAFETY HAZARD
UPFLOW
FURNACE
CASED
COIL
SCREWS
(BOTH SIDES)
STANDOFFS
(BOTH SIDES)
STANDOFFS (4)
DRILL SCREWS (4)
DO NOT INSTALL THE FURNACE DIRECTLY ON
CARPETING, TILE OR OTHER COMBUSTIBLE
MATERIAL OTHER THAN WOOD FLOORING. FOR
VERTICAL DOWNFLOW APPLICATIONS, SUBBASE
(BAYBASE205) MUST BE USED BETWEEN THE
FURNACE AND COMBUSTIBLE FLOORING. WHEN THE
DOWNFLOW FURNACE IS INSTALLED VERTICALLY
WITH A CASED COIL, A SUBBASE IS NOT REQUIRED.
FAILURE TO FOLLOW THE WARNING EXACTLY COULD
RESULT IN SERIOUS PERSONAL INJURY, PROPERTY
DAMAGE OR DEATH.
UPFLOW INSTALLATION
Standoffs and screws (See Figure 1) are included with
the cased coils for attachment to the furnace. There are
clearance alignment holes near the bottom of the coil
wrapper. Drill screws are used to engage the furnace
top flanges. The standoff is inserted into the cabinet
alignment hole. The drill screws are inserted through the
standoffs then screwed into the furnace flange. The coil is
always placed downstream of the furnace airflow.
1
FOR VERTICAL
INSTALLATIONS:
Installer’s Guide
DOWNFLOW INSTALLATIONS
REQUIRED FLOOR OPENING: (DOWNFLOW)
SEE FIGURE 2 AND FIGURE 3, AND TABLE 1
HORIZONTAL INSTALLATION
IMPORTANT:
The 2/4TXC cased coil must be placed downstream of the
furnace. In horizontal installations, the apex of the coil
may point either toward or away from the furnace. See the
2/4TXC coil Installer's Guide for more details.
The coil and furnace must be fully supported when used
in the horizontal position. It is always recommended that
an auxiliary drain pan be installed under a horizontally
installed evaporator coil or 90% or greater Gas Furnace.
Connect the auxiliary drain line to a separate drain line
(no trap is needed in this line).
Three brackets (with screws) are included with downflow
furnaces for installation to stabilize and secure the
furnace and TXC cased coil in the horizontal position.
See Figure 4. The coil is placed downstream of the
furnace, with the apex of the coil pointing in either
direction of the airflow for horizontal installation. The
cased coil is secured to the furnace and both the furnace
and the cased coil must be properly supported.
CASED COIL CONNECTION
4
BRACKET FOR DOWNFLOW
FURNACE IN HORIZONTAL
DOWNFLOW ONLY
2
3
A (width)
FURNACE
FRONT
TABLE 1
CABINET
WIDTH
17-1/2"16-1/4"16-5/8"20-1/8"15-5/8"19-3/8"
21"19-3/4"20-1/8"20-1/8"19-1/8"19-3/8"
24-1/2"23-1/4"23-5/8"20-1/8"22-5/8"19-3/8"
RETURN
DUCT WIDTH
FLOOR OPENING PLENUM OPENING
B (depth)
"A""B"
D
C
"C""D"
The brackets mount using the rear screws on the coil
case and use the screws provided to secure the bracket
to the furnace. The remaining bracket is placed as close
to center as possible (horizontally) between the coil case
front and the furnace bottom channel (for downflow/
horizontal furnace). Use four of the screws provided to
secure the bracket. The coil requires additional support.
The furnace may be installed in an attic or crawl space
in the horizontal position by placing the furnace on the left side (as viewed from the front in the vertical position).
The horizontal furnace installation in an attic should be
on a service platform large enough to allow for proper
clearances on all sides and service access to the front
of the furnace (See Figure 5 & Clearance Tables, on
the Outline drawings on pages 4-5). Line contact is only
permissible between lines formed by intersections of
the top and two sides of the furnace casing and building
joists, studs, or framing.
The furnace may be placed horizontally in a crawl space
on a pad or other noncombustible material which will
raise the unit for sufficient protection from moisture.
18-CD30D1-12 7
Page 8
Installer’s Guide
5
UPFLOW/
HORIZONTAL
SHOWN WITH
DIRECT VENT
The furnace must be supported at both ends and the
middle when installed horizontally. The furnace must
also be elevated approximately 4-6 inches to allow
clearance for the condensate drain to exit the cabinet
in the horizontal position.
The horizontal furnace may also be suspended from
the joists using all-thread rods with a substantial metal
support frame that supports the entire length of the
furnace. The rods need to be of sufficient length to
allow for proper clearances from combustible materials.
The frame needs to be at least 32" in length to allow for
access to service panels.
If the furnace is suspended using steel strap, it must be
supported at all four corners and in the middle at the front
of the furnace.
AIR FOR COMBUSTION AND VENTILATION
If these furnaces are installed in a nondirect vent capacity
then the adequate flow of combustion and ventilating
air must not be obstructed from reaching the furnace.
Air open ings provided for combustion air must be kept
free of obstructions which restrict the flow of air. Airflow
restrictions affect the efficiency and safe operation
of the furnace. Keep this in mind should you choose
to remodel or change the area which contains your
furnace. Furnaces must have a free flow of air for proper
performance.
Provisions for combustion and ventilation air shall be
made in accordance with latest edition of Section 5.3, Air
for Combustion and Ventilation, of the National Fuel Gas
Code, ANSI Z223.1 — CAN/CGA B149.1 or applicable
provisions of the local building codes. Special conditions
created by mechanical exhausting of air and fireplaces
must be con sidered to avoid unsatisfactory furnace
operation.
6
50 CU. FT. OR MORE
PER 1000 BTU/HR. INPUT
ALL EQUIP. INSTALLED
OUTSIDE AIR IS RECOMMENDED
The use of indoor air for most applications is acceptable,
unless there is the presence of corrosive chemicals or
contamination. Certain types of installation will require
the use of outside air for combustion.
The following types of installations will require use
of OUTDOOR AIR for combustion, due to chemical
exposures:
1. * Commercial buildings
2. * Buildings with indoor pools
3. * Furnaces installed in “confined” laundry rooms
4. * Furnaces installed in “confined” hobby or craft rooms
5. * Furnaces installed near chemical storage areas.
Exposure to the following substances in the combustion
air supply will also require OUTDOOR AIR for
combustion:
1. * Permanent wave solutions
2. * Chlorinated waxes and cleaners
3. * Chlorine based swimming pool chemicals
4. * Water softening chemicals
5. * Deicing salts or chemicals
6. * Carbon Tetrachloride
7. * Halogen type refrigerants
8. * Cleaning solvents (such as perchloroethylene)
9. * Printing inks, paint removers, varnish, etc.
10. * Hydrochloric acid
11. * Cements and glues
12. * Antistatic fabric softeners for clothes dryers
13. * Masonry acid washing materials
Furnace locations may be in a “confined space” or an
“unconfined space”.
Unconfined space is defined in Figure 6. These spaces
may have adequate air by infiltration to provide air
for combustion and ventilation. Buildings with tight
construction (for example, weather stripping, heavily
insulated, caulked, vapor barrier, etc.), may need
additional air to be provided as described for confined space. See Table 2 for minimum area.
TABLE 2
MINIMUM AREA IN SQUARE FEET
FOR UNCONFINED SPACE INSTALLATIONS
FURNACE MAXI-
MUM BTUH INPUT
RATING
60,000
80,000
100,000
120,000
WITH 8 FT. CEILING
MINIMUM AREA IN SQUARE FEET
OF UNCONFINED SPACE
375
500
625
875
UNCONFINED
8 18-CD30D1-12
Page 9
Installer’s Guide
7
CONFINED
SPACE
Confined spaces are installations with less than 50 cu.
ft. of space per 1000 BTU/hr input from all equipment
installed. Air for combustion and ventilation requirements
can be supplied from inside the building as in Figure 8 or
from the outdoors, as in Figure 9.
1. All air from inside the building as in Figure 8: The
confined space shall be provided with two permanent
openings communicating directly with an additional
room(s) of sufficient volume so that the combined
volume of all spaces meets the criteria for an
unconfined space. The total input of all gas utilization
equipment installed in the combined space shall be
considered in making this determination. Refer to
Table 3 for minimum open areas requirements.
2. All air from outdoors as in Figure 9: The confined
space shall be provided with two permanent
openings, one commencing within 12 inches of
the top and one commencing within 12 inches of
the bottom of the enclosure. The openings shall
communicate directly, or by ducts, with the outdoors
or spaces (crawl or attic) that freely communicate
with the outdoors. Refer to Table 3, for minimum open
areas requirements.
TABLE 3
MINIMUM FREE AREA IN SQUARE INCHES
EACH OPENING (FURNACE ONLY)
8
9
Furnace
Maximum
BTUH/INPUT
Rating
60,000
80,000
100,000
120,000
Air
From
Inside
100
100
100
120
Vertical
Duct
DUCT CONNECTIONS
Air duct systems should be installed in accordance with
standards for air conditioning systems, National Fire
Protection Association Pamphlet No. 90. They should be
sized in accordance with ACCA Manual D or whichever is
applicable.
Central furnaces, when used in connection with cooling
units, shall be installed in parallel or on the upstream
side of the cooling coil to avoid condensation in the heat
exchanger.
18-CD30D1-12 9
Air From Outside
Horizontal
15
20
25
30
Duct
30
40
50
60
Page 10
Installer’s Guide
▲
CAUTION
!
With a parallel flow arrangement, the dampers or other
means used to control flow of air shall be adequate to
prevent chilled air from entering the Furnace, and if
manually operated, must be equipped with means to
prevent operation of either unit unless the damper is in
full heat or cool position.
On any job, flexible connections of nonflammable material
may be used for return air and discharge connections to
prevent transmission of vibration. Though these units
have been specifically designed for quiet, vibration free
operation, air ducts can act as sounding boards and could,
if poorly installed, amplify the slightest vibration to the
annoyance level.
When the furnace is located in a utility room adjacent to
the living area, the system should be carefully designed
with returns to minimize noise transmission through the
return air grille. Although these furnaces are designed
with large blowers operating at moderate speeds, any
blower moving a high volume of air will produce audible
noise which could be objectionable when the unit is
located very close to a living area. It is often advisable
to route the return air ducts under the floor or through
the attic. Such design permits the installation of air return
remote from the living area (i.e. central hall).
When the furnace is installed so that the supply ducts
carry air circulated by the furnace to areas outside
the space containing the furnace, the return air shall
also be handled by a duct(s) sealed to the furnace and
terminating outside the space containing the furnace.
RETURN AIR DUCT SYSTEMS
Safety Hazard
Sharp Edge Hazard
Be careful of sharp edges on equipment or any cuts
made on sheet metal while installing or servicing.
Personal injury may result.
Where there is no complete return duct system,
the return connection must be run full size from
the furnace to a location outside the utility room,
basement, attic, or crawl space.
Do NOT install return air through the back of the furnace
cabinet.
Do NOT install return air through the side of the furnace
cabinet on horizontal applications.
NOTE:
Minimum return air temperature is 55°F.
PREPARATION FOR UPFLOW BOTTOM AND SIDE
RETURN AIR FILTER INSTALLATION
All return air duct systems should provide for installation
of return air filters.
1. Determine the appropriate position to set the furnace
in order to connect to existing supply and return
ductwork.
2. The return air filter is shipped in either the bottom or
side location. Remove the filter by first turning the
two latches on the blower door and tilting the door
forward to remove. Remove the filter by sliding it out.
3. For upflow side return installations, remove the
insulation around the opening in the blower
compartment.
4. The side panels of the upflow furnace include
locating notches that are used as guides for cutting
an opening for return air, refer to Figure 10 and
the outline drawing on page 4 for duct connection
dimensions for various furnaces.
UPFLOW FURNACE ONLY
0
LOCATING NOTCHES PROVIDED FOR
SIDE RETURN
CUTOUT
*SEE OUTLINE DRAWING
5. If a 3/4" flange is to be used for attaching the air inlet
duct, add to cut where indicated by dotted lines in
Figure 10. Cut corners diagonally and bend outward
to form flange.
6. If flanges are not required, and a filter frame is
installed, cut between locating notches (See Figure
10).
7. The bottom panel of the upflow furnace must be
removed for bottom return air. After removing the
filter, lay the furnace on its back. Remove the two
5/16" hex screws securing the front of the bottom
channel to the cabinet.
CUT OUT FOR
SIDE FILTER
FRONT
of Furnace
10 18-CD30D1-12
Page 11
Rotate the channel downward (or remove by lowering
VIEW
ENGAGEMENT
HOLE DETAIL
(Typical both sides
and blower deck)
Blower Deck
Engagement
Hole
the front edge of the channel and pulling forward).
Slide the bottom return air panel out of the cabinet.
Rotate the front channel to its original position and
reinstall the two 5/16” screws.
8. The horizontal installation of the upflow furnace
requires an external filter section. Do NOT use
the bottom return filter within the furnace. Filter
kits are available for horizontal applications.
9. Connect duct work to furnace. See Outline Drawing for
supply and return duct size and location. Flexible duct
con nectors are recommended to connect both supply
and return air ducts to the furnace. If only the front
of the furnace is accessible, it is recommended that
both supply and return air plenums are removable.
RETURN AIR FILTERS
TYPICAL UPFLOW RETURN AIR FILTER
INSTALLATIONS
Filters are factory supplied for these furnaces. These
furnaces require high velocity type air filters. The filters
may be installed within the furnace blower compartment
for UPFLOW furnaces in either a BOTTOM or SIDE (left
side or right side) return air inlet. Some filters may need
to be trimmed for side or bottom filter use.
TABLE 4
MODELS
NUMBERS
*UHMB060BCV3VB
*UHMB080ACV3VB
*UHMC100ACV4VB21"1 - 20" X 25" X 1"
*UHMD120BCV5VB24-1/2"1 - 24" X 25" X 1"
* First letter may be "A" or "T"
CABINET
WIDTH
17-1/2"1 - 17" X 25" X 1"
FILTER
QTY & SIZE
Installer’s Guide
q
Airflow
BOTTOM FILTER RACK INSTALLATION
w
FILTER RACK ASSEMBLY
NOTE: For upflow 5 ton airflow models where the
airflow requirement exceeds 1800 CFM - Models
will require return air openings and filters on:
(1) both sides, or (2) one side and the bottom, or
(3) just the bottom. The filter rack installation is
not allowed for right side return on the following
models: *UHMB060ACV3V, *UHMB080ACV3V &
*UHMC100ACV4V.
The furnace and the bottom filter rack, BAYRACK960,
installation can be seen in Figure 11. The furnace filter
in the bottom or side configuration can be removed by
simply turning the two latches on the blower door and
tilting the door forward.
The Filter rails are spring loaded for automatic
adjustment to allow standard size, locally obtainable
replacement filters. The filter rack itself slides to adjust to
the required width needed for bottom or side return (See
Figure 12).
18-CD30D1-12 11
e
Page 12
Installer’s Guide
Bottom Panel
Filter
Rack
Furnace
Cabinet
Side
Filter Rack
Retaining
Screw/Pin
Engagement Hole
For
Bottom Return
Filter Rack
Installation With
RETAINING
PIN
(Both Sides)
SPRINGS
SIDE
CUTOUT
FILTER
RACK
RAILS
BOTTOM
PANEL
INSTALLED
Airflow
RETAINING
PIN
(Both Sides)
SPRINGS
SIDE
CUTOUT
FILTER
RACK
RAILS
BOTTOM
PANEL
INSTALLED
Airflow
Filter
Rack
Furnace
Cabinet
Side
Filter Rac
k
Retaining
Screw/Pin
Engagement Hole
For
Bottom Return
Filter Rack
Installation With
ALTERNATE FILTER RACK INSTALLATION FOR
BOTTOM RETURN - BAYRACK960
The following checklist should be used when installing a
bottom return filter on an upflow furnace:
a. Remove the filter.
b. Remove the bottom panel.
c. With the filter removed, the filter rack is
compressed and then inserted into the bottom
of the furnace. The retaining screw/pin on each
side inserts into engagement holes at the bottom
of the furnace cabinet side. See Figure 14.
d. Reinstall the furnace filter in the bottom position
by inserting the chamfer end first into the filter
rack. See Figure 19.
ALTERNATE FILTER RACK INSTALLATION FOR SIDE
RETURN AIR ON UPFLOW FURNACES (LEFT OR
RIGHT) - BAYRACK960
NOTE:
The filter rack installation is not allowed for right side
return on the following models: *UHMB060ACV3V,
*UHMB080ACV3V & *UHMC100ACV4V. See Figure 21
for alternate upflow filter clip/ bracket installation.
The following checklist should be used when installing a
right or left side return filter on an upflow furnace:
a. Remove the filter.
b. Leave the bottom panel in place.
c. Make side cutout by following the directions in the
“Return Air Duct Connections” section on page 10,
d. Compress the filter rack and reinstall in the side
position on the furnace. Confirm that the upper
retaining pin/screw locks into the engagement hole in
the blower deck and the lower pin/screw rests against
the side of the bottom panel. See Figures 13, 15-18.
e. Reinstall the furnace filter in the side position by
inserting the chamfer end first into the filter rack.
t
BOTTOM ENGAGEMENT
y
Typical Upflow Left Side Return Filter Rack Installation
u
r
12 18-CD30D1-12
SIDE ENGAGEMENT
Typical Upflow Right Side Return Filter Rack Installation
Page 13
i
Filter
Rack
Assembly
Furnace
Blower
Deck
Filter Rack
Retaining
Screw/Pin
Engagement Hole
For
Return
Filter Rack
Installation With
Side
Furnace
Cabinet
Side
CHAMFER
END OF
FILTER GOES
INTO FILTER
RACK FIRST
SIDE
CUT-OUT
ALTERNATE SIDE
FILTER CLIPS
LOCATIONS
ALTERNATE BOTTOM
FILTER CLIPS LOCATIONS
BLOWER
DECK
o
Airflow
Installer’s Guide
RETURN AIR FILTERS FOR UPFLOW FURNACE IN
HORIZONTAL CONFIGURATION
When the upflow furnace is installed in the horizontal
configuration, the return air filters must be installed
exterior to the furnace cabinet. Remote filter grilles may
be used for homeowner convenience or the filters may be
installed in the duct work upstream of the furnace. See
Figure 20. Conversion kits for horizontal filter installation
are shown in Table 4A.
Conversion kits for horizontal filters are BAYFLTR203
for 17 1/2" width cabinets, BAYFLTR204 for 21" width
cabinets, and BAYFLTR205 for 24" width cabinets. These
include filters and brackets necessary for horizontal
filters. See Figure 20.
UPFLOW FILTER CLIP/ BRACKET INSTALLATION
1. Determine the location to be used. The furnace
cabinet has dimples for location of the alternate
furnace clips (Side return only). Pre-drill clearance
holes with a 3/16" drill. Bottom return holes are predrilled. Attach clip to bottom channel and rear of unit
with screws provided for bottom return.
2. Install the clips in front and rear of the desired location
using the screws provided. The filter clip with the leaf
spring mounts in the rear of the cabinet. See Figure
21.
p
Accessory filter kit BAYFLTR203, 204, or 205 used
for Upflow Horizontal
furnaces.
Typical Horizontal Filter Installation
Table 4A CONVERSION KITS FOR
HORIZONTAL FILTERS
MODEL NUMBERS
*UHMB060ACV3VB
*UHMB080ACV3VB
*UHMC100ACV4VB
*UHMD120ACV5VB
1. *First letter may be "A" or "T"
2. Kit includes Filters and Brackets necessary for Horizontal Filters.
18-CD30D1-12 13
CABINET
WIDTH
17-1/2"BAYFLTR203
21"BAYFLTR204
24-1/2"BAYFLTR205
Airflow
a
CONVERSION
KIT NUMBER
Page 14
Installer’s Guide
INSTALLING THE FILTER
The filter may need to be cut to fit the unit depending on
the location of the return air filter.
A score line and the words “CUT HERE” are located
on the end of the filter. If your application requires
cutting the filter, do so as indicted by the score mark.
UNIT
SIZE
TABLE 5
RETURN AIR
BOTTOMSIDE
17-1/2"DO NOT CUTDO NOT CUT
21"DO NOT CUT CUT ON LINE
24-1/2"DO NOT CUT CUT ON LINE
TYPICAL DOWNFLOW FURNACE RETURN AIR
FILTER INSTALLATIONS
Two filters are factory supplied for each downflow
furnace. These furnaces require high velocity type air
filters.
Downflow furnace filters must be located outside the
furnace cabinet. Typical installations are shown in Figure
22. Tables 6 and 7 provide information for installation
of the filter retaining brackets shipped with downflow
furnaces.
TABLE 6
MODELS
NUMBERS
*DHMB060BCV3VB
*DHMB080ACV3VB
*DHMC100ACV4VB21"2 - 16" X 20" X 1"
*DHMD120BCV5VB24-1/2"2 - 16" X 20" X 1"
*First letter may be "A" or "T"
LOCATING FILTER RETAINER BRACKETS IN DUCTWORK
CABINET
WIDTH
17-1/2"16-1/4"15"14"14-3/8"
21"19-3/4"19-1/2"14"13-1/8"
24-1/2"23-1/4"22"14"13-5/8"
* LOCATION DIMENSION IS FROM END OF DUCT AGAINST THE FURNACE TO THE
SCREW HOLES FOR THE BRACKET.
RETURN
DUCT
WIDTH
CABINET
WIDTH
17-1/2"2 - 14" X 20" X 1"
TABLE 7
DIMENSION
"A"
DIMENSION
FILTER
QTY & SIZE
"B"
FILTER
BRACKET
LOCATION*
DOWNFLOW
s
Airflow
TABLE 8
MINIMUM CLEARANCE FROM COMBUSTIBLE MATERIALS FOR
UPFLOW/HORIZONTAL AND DOWNFLOW/ HORIZONTAL FURNACES
FURNACE SURFACE
SIDES0"1"0"
BACK0"3"6"
TOP1"1"1"
FRONT3"3"18"
VENT0"0"0"
NOTE: CLEARANCE REQUIRED AT TOP OF PLENUM IS 1"
VERTICAL
CLOSET
DOWNFLOW/
HORIZONTAL
Airflow
UNIT LOCATION
HORIZONTAL
CLOSET
HORIZONTAL
ALCOVE / ATTIC
14 18-CD30D1-12
Page 15
GENERAL VENTING INFORMATION
▲
WARNING
!
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each
appliance connected to the venting system being
placed into operation could result in carbon monoxide
poisoning or death.
The following steps shall be followed for each appliance
connected to the venting system being placed into
operation, while all other appliances connected to the
venting system are not in operation:
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and
horizontal pitch, as required in the National Fuel Gas
Code, ANSI Z223.1/NFPA 54 or the CSA B149.1
Natural Gas and Propane Installation Code and these
instructions. Determine that there is no blockage or
restriction, leakage, corrosion and other deficiencies
which could cause an unsafe condition.
3. As far as practical, close all building doors and
windows and all doors between the space in which the
appliance(s) connected to the venting system are
located and other deficiencies which could cause an
unsafe condition.
4. Close fireplace dampers.
5. Turn on clothes dryers and any appliance not
connected to the venting system. Turn on any exhaust
fans, such as range hoods and bathroom exhausts, so
they are operating at maximum speed. Do not operate
a summer exhaust fan.
6. Follow the lighting instructions. Place the appliance
being inspected into operation. Adjust the thermostat
so appliance is operating continuously.
7. Test for spillage from draft hood equipped appliances
at the draft hood relief opening after 5 minutes of main
burner operation. Use the flame of a match or candle.
8. If improper venting is observed during any of the above
tests, the venting system must be corrected in
accordance with the National Fuel Gas Code,
ANSI Z221.1/NFPA 54 and/or CSA B149.1 Natural Gas and Propane Installation Code.
9. After it has been determined that each appliance
connected to the venting system properly vents where
when tested as outlined above, return doors, windows,
exhaust fans, fireplace dampers and any other gas-fired
burning appliance to their previous condition of use.
▲
WARNING
!
FACTORY SUPPLIED
ONLY WITH THE
FOLLOWING MODELS:
ALL 100,000 BTUH
UPFLOW MODELS, ALL
120,000 BTUH UPFLOW
MODELS, AND ALL
DOWNFLOW MODELS
#CPL00938
LABEL
SAYS
"TOP"
STRAIGHT SIDE MUST BE
ON BOTTOM FOR PROPER
CONDENSATE DRAINAGE.
WHEN THE FACTORY SUPPLIED "OFF-SET" (2X3
REDUCING COUPLING) IS USED FOR 3" VENT PIPE
INSTALLATION, MAKE SURE THE MARKING "TOP" IS
LOCATED ON THE TOP SIDE OF THE PIPE.
THIS FURNACE MUST BE VENTED TO THE
OUTDOORS. THESE FURNACES ARE INDUCED
DRAFT VENTED AND MUST NOT BE CONNECTED TO
ANY VENT SERVING ANOTHER APPLIANCE. PLEASE
NOTE THAT THESE FURNACES USE POSITIVE-
PRESSURE VENT SYSTEMS.
CARBON MONOXIDE HAZARD
FURNACE MUST BE VENTED PROPERLY.
FAILURE TO FOLLOW THIS WARNING COULD
RESULT IN CARBON MONOXIDE, FIRE OR SMOKE
THAT CAN CAUSE SERIOUS BODILY INJURY, DEATH
OR PROPERTY DAMAGE.
IMPORTANT:
The building owner/maintenance provider must keep
the area around the vent clear from snow.
Proper venting is essential to obtain maximum efficiency
from a condensing furnace. Proper installation of the
vent system is necessary to assure drainage of the
condensate and prevent deterioration of the vent system.
American Gas Association has certified the design of
condensing Furnaces for a minimum of 0" clearance from
combustible materials with a single wall plastic vent pipe.
See Table 8.
The recommended system is assembled from 2", 2-1/2",
or 3" plastic pipe and fittings (See Table 9, page 18) for
material specifications. Where the system is routed
to the outdoors through an existing masonry chimney
containing flue products from another gas appliance, or
where required by local codes, then 3" venting of Type
29-4C stainless steel must be used in place of PVC
material.
These furnaces have been classified as CATEGORY IV
Furnaces in accordance with ANSI Z21.47 “latest edition”
standards. Category IV Furnaces operate with positive
vent pressure and with a vent gas temperature less than
140°F. above the dewpoint. These conditions require
special venting systems, which must be gas and water
tight.
NOTE: When an existing furnace is removed from a
venting system serving other gas appliances, the
venting system is likely to be too large to properly vent
the remaining attached appliances.
The following steps shall be followed with each appliance
remaining connected to the common venting system
placed in operation, while the other appliances remaining
connected to the common venting system are not in
operation.
18-CD30D1-12 15
Installer’s Guide
d
Page 16
Installer’s Guide
▲
WARNING
!
▲
WARNING
!
Furnace
Air
Inlet
Vent
2" TO 3" COUPLING
FURNACE
VENT
OUTLET
FACTORY SUPPLIED ONLY
WITH THE FOLLOWING
MODELS:
ALL 100,000 BTUH UPFLOW
MODELS, ALL 120,000 BTUH
UPFLOW MODELS, THE
UX1C080A9601 MODEL, AND
ALL DOWNFLOW MODELS
#CPL00938
f
HORIZONTAL INSTALLATION
(UPFLOW/ HORIZONTAL OR DOWNFLOW/ HORIZONTAL)
NOTE:
See Figures 23 & 24. In horizontal venting when the
factory supplied “off-set” (2X3 reducing coupling)
is used for 3” vent pipe installation, make sure the
marking “Top” is located on the top side of the pipe.
The straight side must be on bottom for proper
condensate drainage. This coupling is factory supplied
with the following models: *UHMC100, *UHMD120, & all
downflow models.
Carbon monoxide, fire or smoke can cause serious bodily
injury, death, and/ or property damage.
A variety of potential sources of carbon monoxide can
be found in a building or dwelling such as gas-fired
clothes dryers, gas cooking stoves, water heaters,
Furnaces and fireplaces. The U.S. Consumer Product
Safety Commission recommends that users of gasburning appliances install carbon monoxide detectors as
well as fire and smoke detectors per the manufacturer’s
installation instructions to help alert dwelling occupants
of the presence of fire, smoke or unsafe levels of carbon
monoxide. These devices should meet Underwriters
Laboratories, Inc. Standards for Single and Multiple Station Carbon Monoxide Alarms, UL 2034 or CSA
International Standard, Residential Carbon Monoxide
Alarming Devices, CSA 6.19
For NONDIRECT VENT APPLICATION: The furnace shall
be vented to the exterior of the house, but combustion
air may enter from the surrounding area as long as
combustion air requirements are met. (See AIR FOR
COMBUSTION AND VENTILATION).
FURNACE VENT/INLET PIPE INSTALLATION
CARBON MONOXIDE POISONING HAZARD
Failure to follow the installation instructions for the
venting system being placed into operation could
result in carbon monoxide poisoning or death.
There are many different variations of the vent/ inlet air
pipe combination. The vent/ inlet air combination used for
installation of these furnaces depends on the needs of
the location. However, these guidelines must be followed:
1. The Furnace must vent outside the structure.
2. Furnace combustion air requirements must be met
for nondirect, single pipe applications (See ex. 2 ).
3. For direct vent application of these furnaces, the vent
pipe and air inlet pipe do not have to exit in the same air
space or even on the same surface of the structure.
However, the longest individual pipe will decide the value
for the longest allowable equivalent vent/ inlet air length
as shown in the vent length table.
NOTE:
BAYVENT200B accessories can be used for inlet
and outlet terminals when the pipes do not exit
the structure together. For Canadian applications
ONLY, IPEX 196006 may be used for horizontal and
vertical terminations. IPEX 081216, IPEX 081218, and
IPEX 081219 may be only used for horizontal vent
terminations.
The following are EXAMPLES ONLY:
EX. 1 —
Example 1 shows that the vent may go vertical while the
inlet air may be on any side of the structure. The Vent
Pipe would decide the maximum equivalent length for the
pipe depending on the furnace and pipe size.
NOTE: The manufacturer of your furnace does not test
any detectors and makes no representations regarding
any brand or type of detector.
IMPORTANT: These furnaces may be installed as Direct
Vent (sealed combustion) or as Nondirect Vent (single
pipe). The furnaces are shipped DIRECT VENT with sealed
combustion.
For DIRECT VENT APPLICATION: The furnaces must
be vented to the exterior of the house and combustion air
MUST come through the inlet air pipe FROM OUTSIDE
AIR. The pipes DO NOT have to exit the exterior of the
house together or on the same side of the house.
16 18-CD30D1-12
Page 17
Installer’s Guide
Furnace
Air
Inlet
Vent
Attic
Vent
(See Note)
Furnace
Air
Inlet
Vent
Furnace
Vent
Air
Inlet
(See Note)
EX. 2 —
Example 2 shows the vent pipe exhausting through the
roof and the inlet air coming from the interior of the house
(See Note). The inlet air coming from the interior of the
house must meet combustion requirements for area, etc.,
as shown in the section AIR FOR COMBUSTION AND
VENTILATION in this Installer’s Guide.
EX. 3 —
Example 3 shows the vent exiting one side of the house
while the inlet air is on the opposite side of the structure.
Here the Vent Pipe length must be within the allowable
length for the size of Furnace and size of the Vent Pipe.
This example demonstrates that the pipes do not have to
exit on the same side of the structure.
EX. 4 —
The inlet air does not have to come from outside the
structure. Example 4 shows the inlet air (See Note), may
come from the attic if the requirements for combustion air
are met as shown in the section AIR FOR COMBUSTION
AND VENTILATION.
NOTE:
If only the flue gas pipe is to the outside of the
structure, a straight section of pipe (long enough to
exit the Furnace cabinet) must be attached to the inlet
air side with an elbow (which is 5 to 10 equivalent feet)
installed on the end to prevent dust and debris from
falling directly into the Furnace.
VENT FITTING MATERIAL – PLASTIC
Gas and liquid tight single wall vent fittings, designed for
resistance to corrosive flue condensate, MUST be used
throughout.
Listed in Table 9 are materials that meet these
requirements. The materials listed are various grades of
PVC and ABS plastic.
PIPE JOINTS: All joints must be fastened and sealed to
prevent escape of combustion products into the building.
These materials are acceptable for U.S. applications only.
All Canadian installations must conform to ULC S636.
NOTE:
It is recommended that the first joints from the furnace
be connected and sealed with high temperature RTV.
This will enable the pipes to be removed later without
cutting. Be sure to properly support these joints.
BONDING OF PVC
Commercially available solvent cement for PVC must
be used to join PVC pipe fittings. Follow instructions on
container carefully for U.S. applications only. Canadian
applications require primer and cement that are from a
single system manufacturer.
For U.S. applications only:
Pipe and Fittings – ASTM D1785, D2466, D2661, &
D2665. PVC Primer and Solvent Cement – ASTM D2564.
Procedure for Cementing Joints Ref – ASTM D2855
1. Cut pipe square, remove ragged edges and burrs.
Chamfer end of pipe, then clean fitting socket and pipe
joint area of all dirt, grease, moisture or chips.
2. After checking pipe and socket for proper fit, wipe
socket and pipe with cleaner-primer. Apply a liberal coat
of primer to inside surface of socket and outside of pipe.
DO NOT ALLOW PRIMER TO DRY BEFORE
APPLYING CEMENT.
3. Apply a thin coat of cement evenly in the socket.
Quickly apply a heavy coat of cement to the pipe end and
insert pipe into fitting with a slight twisting movement until
it bottoms out.
4. Hold the pipe in the fitting for 30 seconds to prevent
tapered socket from pushing the pipe out of the fitting.
18-CD30D1-12 17
Page 18
Installer’s Guide
KIT02281
KIT02282
Seal VENT PIPE
with RTV sealant
Seal INLET AIR PIPE
with RTV sealant
Front of Furnace
TABLE 9
PVC VENT FITTING MATERIAL These fittings are available from your Gas Furnace Distributors for U.S. appli-
* - Allowable temperatures based on classifications covered in ASTM D4396 [Deflection Temps Under Load (264 PSI)]
** - Allowable temperatures based on classifications covered in ASTM D1784 [Deflection Temps Under Load (264 PSI)]
*** - Allowable temperatures based on classifications covered in ASTM D3965 [Deflection Temps Under Load (264 PSI)]
5. Wipe all excess cement from the joint with a rag.
Allow 15 minutes before handling. Cure time varies
according to fit, temperature and humidity.
NOTE:
Follow venting instructions carefully when using PVC
cement.
IMPORTANT:
All joints must be water tight. Flue condensate is somewhat
acidic, and leaks can cause equipment damage.
IMPORTANT:
Products installed in Canada must use vent systems that
are certified to the Standard for Type BH Gas Venting
Systems (ULC S636) for Class II-A venting systems (up
to 65 degrees C). Components of the vent system must
not be interchanged with other vent systems or unlisted
pipe or fittings. Plastic components, specified primers, and
glues must be from a single system manufacturer and not
intermixed with other system manufacturer’s vent system
parts.
18 18-CD30D1-12
VENT AND INLET AIR CONNECTIONS
g
Connection of the pipe and collar of the combustion air
inlet should just be a friction fit. It is recommended that
the inlet air joint be sealed with RTV type sealant to
allow the joint to be separated for possible future service.
The inlet and vent pipes must be properly supported
throughout the entire length.
Not AllowedNot Allowed30Not Allowed5038
Not AllowedNot AllowedNot AllowedNot Allowed5038
Not AllowedNot AllowedNot AllowedNot Allowed5025
Notes: * - First letter may be "A" or "T", ** - Last two digits may be "A" thru "Z"
1. Minimum vent length for all models: 3' horizontal or 3' vertical
2. DO NOT MIX PIPE DIAMETERS IN THE SAME LENGTH OF PIPE OUTSIDE THE FURNACE CABINET, (Except
adapters at the top of the furnace). If different inlet and vent pipe sizes are used, the vent pipe must adhere to the
maximum length limit shown in the table above (See note 6 below for exception). The inlet pipe can be of a larger
diameter, but never smaller than the vent pipe.
3. MAXIMUM PIPE LENGTHS MUST NOT BE EXCEEDED! THE LENGTH SHOWN IS NOT A
COMBINED TOTAL, IT IS THE MAXIMUM LENGTH OF EACH (Vent or Inlet air pipes).
4. One SHORT radius 90° elbow is equivalent to 10' of 3" pipe and one LONG radius elbow is equivalent to 6' of 3"
pipe. One 90° elbow is equivalent to 7½' of 2½" pipe or 5' of 2" pipe. Two 45° elbows equal one 90° elbow.
5. The termination tee or bend must be included in the total number of elbows. If the BAYAIR30AVENTA termination
kit is used, the equivalent length of pipe is 5 feet. BAYVENT200B equivalent length is 0 feet.
6. Pipe adapters are field supplied. Downflow models, UHM 100 and UHM 120 models include
the 2" x 3" adapter.
3 or 4 INCH PIPE
3 or 4 INCH PIPE2.5 INCH PIPE2 INCH PIPE
VENT LENGTH TABLE - MODULATING FURNACE
0-7000 Feet
7000-9500 Feet
9500-12000 Feet
3 or 4 INCH PIPE2.5 INCH PIPE2 INCH PIPE
2 INCH PIPE2.5 INCH PIPE
MAXIMUM TOTAL EQUIVALENT LENGTH IN FEET FOR VENT AND INLET
AIR (SEE NOTES)
7. For Canadian applications ONLY, IPEX 196006 may be used for horizontal and vertical terminations. IPEX 081216,
IPEX 081218, and IPEX 081219 may only be used for horizontal vent terminations. Equivalent lengths are
IPEX 196009 = 5 feet, IPEX 081216 = 11 feet, IPEX 081218 = 16 feet, and IPEX 081219 = 21 feet
UHMD120ACV5V
UHMD120ACV5V
UHMD120ACV5V
Not AllowedNot AllowedNot AllowedNot Allowed200150
Not AllowedNot AllowedNot AllowedNot Allowed100100
Not AllowedNot AllowedNot AllowedNot Allowed5038
TABLE 10
Connection of the vent pipe to the vent collar should
also be accomplished using RTV type sealant. This type
sealant provides a connection which remains flexible and
can be separated in the future if service needs require
the removal of the Vent Pipe for service or clearance.
The vent length Table 10 above shows the required vent
lengths for installations at various altitudes. Optional high
altitude kits are available for installations above 5000
feet (Installations above 12,000 feet are not allowed) as
follows:
18-CD30D1-12 19
For *UHM/DHMB060 use BAYSWT07AHALTA.
For *UHM/DHMB080, C100 use BAYSWT09AHALTA.
For *UHM/DHMD120 use BAYSWT08AHALTA.
For Canadian applications, use the appropriate tables in
the latest edition of the National Fuel Gas Code (ANSI
Z223.1 • CAN/CGA B149.1 Installation Codes or “Exhibit
J” of ANSI Z21.47 • CAN/CGA-2.3 Standards. “Exhibit
J” includes examples and drawings of typical venting
systems.
Page 20
Installer’s Guide
▲
CAUTION
!
9" MINIMUM
9" MINIMUM
9" MINIMUM
9" MINIMUM
9" MINIMUM
▲
WARNING
!
CARBON MONOXIDE POISONING HAZARD
DO NOT REPLACE ANY OF THE FACTORY SUPPLIED
VENTING COMPONENTS WITH FIELD FABRICATED
PARTS. FAILURE TO FOLLOW THIS SAFETY WARNING EXACTLY COULD RESULT IN DAMAGED VENTS,
DAMAGED COMPONENTS, CARBON MONOXIDE POISONING, OR DEATH.
HORIZONTAL VENTING
NOTE:
Vent termination kit BAYAIR30AVENTA or
BAYVENT200B may be used in addition to the
horizontal and vertical termination options shown in
Figure 26. See Figure 31. For Canadian applications
ONLY: IPEX 196006 may be used for horizontal and
vertical terminations. IPEX 081216, IPEX 081218, and
IPEX 081219 may only be used for horizontal vent
terminations.
When the vent pipe is exposed to temperatures below
freezing, i.e., when it passes through unheated spaces,
etc., the pipe must be insulated with 1/2 inch (22.7
mm) thick Armaflex-type insulation or equal. If the
space is heated sufficiently to prevent freezing, then
the insulation would not be required. If domestic water
pipes are not protected from freezing then the space
meets the condition of a heated space.
VENTING THROUGH THE ROOF
When penetrating roof with a 2" PVC Vent Pipe, a 2"
electrical conduit flashing may be used for a weather
tight seal. Lubricate flexible seal on flashing before PVC
pipe is pushed through the seal. (Field Supplied)
NOTE:
No Vent Cap as shown in Figure 35 is the preferred
method for vertical Vent Termination in extremely cold
climates.
In extreme climate conditions, insulate the exposed
pipe above the roof line with Armaflex type insulation.
h
ELBOW AND TEE MUST BE
AS CLOSE TOGETHER
AS POSSIBLE
POSSIBLE CONFIGURATIONS FOR TWO PIPE VENTING SYSTEMS
20 18-CD30D1-12
Page 21
Installer’s Guide
6" Min.
40 Inch
Upflow or
Downflow
Furnace
Slope 1/4" per ft.
Slope 1/4" per ft.
▲
CAUTION
!
HORIZONTAL VENTING THROUGH WALL
IMPORTANT:
The building owner/maintenance provider must keep
the area around the vent clear from snow.
These furnaces may be installed as direct vent (as
shipped) or as non-direct vent. Installation must conform to national, state, and local codes.
The vent & inlet terminals must be located at least 12"
minimum above normally expected snow accumulation
level. See Figure 29.
Avoid areas where staining or condensate drippage may
be a problem.
Location of the vent/ wind terminal should be chosen to
meet the requirements of Figure 30 and Tables 11 and 12
for either direct or non-direct vent applications.
PITCH – Venting through the wall must maintain 1/4"
per foot pitched upward to insure that condensate drains
back to the Furnace.
FLUE GAS DEGRADATION – The moisture content of
the flue gas may have a detrimental effect on some building materials. This can be avoided by using the roof or
chimney venting option. When wall venting is used on
any surface that can be affected by this moisture, it is recommended that a corrosion resistant shield (24 inches
square) be used behind the Vent Terminal. This shield
can be wood, plastic, sheet metal, etc. Also, silicone
caulk all cracks, seams and joints within 3 feet of the Vent
Terminal.
The vent for this appliance shall not terminate
(1) Over public walkways; or
(2) Near soffit vents or crawl space vents or other ar-
eas where condensate or vapor could create a
nuisance or hazard or cause property damage;
or
(3) Where condensate vapor could cause damage or
could be detrimental to the operation of regulators, relief valves, or other equipment.
j
NOTES:
A) Condensate trap for Vent Pipe must be a minimum of 6 inches in height.
B) Condensate trap for Vent and Inlet Pipe must be connected into a condensate drain pump; an open or vented
C) The condensate trap should be primed at initial start up prior to heating season operation.
DOWNWARD VENTING
Furnace may be in vertical or horizontal configuration.
All horizontal pipes must be
supported at a maximum of
3 foot intervals
DOWNWARD VENT
LENGTH IS LIMITED
TO A MAXIMUM OF
15 EQUIVALENT
FEET.
drain; or it can be connected to the outlet hose of the Furnace's condensate trap. Outdoor draining of the Furnace and coil condensate is permissible if allowed by local codes. Caution should be taken to prevent drains
from freezing or causing slippery conditions that could lead to personal injury. Excessive draining of condensate may cause saturated ground conditions that may result in damage to plants.
18-CD30D1-12 21
Page 22
Installer’s Guide
IMPORTANT:
The Commonwealth of Massachusetts requires compliance
with regulation 248 CMR 4.00 and 5.00 for installation of
through – the – wall vented gas appliances as follows:
For all side wall horizontally vented gas fueled equipment
installed in every dwelling, building or structure used in whole
or in part for residential purposes, including those owned
or operated by the Commonwealth and where the side wall
exhaust vent termination is less than seven (7) feet above
finished grade in the area of the venting, including but not
limited to decks and porches, the following requirements shall
be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS.
At the time of installation of the side wall horizontal vented
gas fueled equipment, the installing plumber or gasfitter shall
observe that a hard wired carbon monoxide detector with an
alarm and battery back-up is installed on the floor level where
the gas equipment is to be installed. In addition, the installing
plumber or gasfitter shall observe that a battery operated
or hard wired carbon monoxide detector with an alarm is
installed on each additional level of the dwelling, building or
structure served by the side wall horizontal vented gas fueled
equipment. It shall be the responsibility of the property owner
to secure the services of qualified licensed professionals for
the installation of hard wired carbon monoxide detectors
a. In the event that the side wall horizontally vented gas fueled
equipment is installed in a crawl space or an attic, the hard
wired carbon monoxide detector with alarm and battery backup may be installed on the next adjacent floor level.
b. In the event that the requirements of this subdivision can
not be met at the time of completion of installation, the owner
shall have a period of thirty (30) days to comply with the above
requirements; provided, however, that during said thirty (30)
day period, a battery operated carbon monoxide detector with
an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS. Each
carbon monoxide detector as required in accordance with the
above provisions shall comply with NFPA 720 and be ANSI/UL
2034 listed and IAS certified. The manufacturer of the furnace
does not test any carbon monoxide detectors and makes
no representation regarding any brand of carbon monoxide
detector.
3. SIGNAGE. A metal or plastic identification plate shall be
permanently mounted to the exterior of the building at a
minimum height of eight (8) feet above grade directly in line
with the exhaust vent terminal for the horizontally vented
gas fueled heating appliance or equipment. The sign shall
read, in print size no less than one-half (1/2) inch in size,
“GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL
OBSTRUCTIONS”.
4. INSPECTION. The state or local gas inspector of the
side wall horizontally vented gas fueled equipment shall not
approve the installation unless, upon inspection, the inspector
observes carbon monoxide detectors and signage installed
in accordance with the provisions of 248 CMR 5.08(2)(a)1
through 4.
This appliance requires a special venting system. If
BAYAIR30AVENTA or BAYVENT200B are used, a copy of
the installation instructions for the kit shall remain with the
appliance or equipment at the completion of installation. The
venting system installation instructions can be obtained from
the manufacturer by writing to the following address:
Residential Systems
6200 Troup Highway
Tyler, TX 75707
Attention: Manager of Field Operations Excellence
IMPORTANT:
Products installed in Canada must use vent systems that
are certified to the Standard for Type BH Gas Venting
Systems (ULC S636) for Class II-A venting systems (up
to 65°C). Components of the vent system must not be
interchanged with other vent systems or unlisted pipe or
fittings. Plastic components, specified primers, and glues
must be from a single system manufacturer and not intermixed with other system manufacturer's vent system
parts. In addition, the first three feet of the vent pipe must
be visible for inspection.
22 18-CD30D1-12
Page 23
Installer’s Guide
VENT
COMBUSTION
AIR
VENT
VENT
PLATE
VENT
CAP
12" MINIMUM
TO OVERHANG
MAINTAIN 12" MINIMUM CLEARANCE
ABOVE HIGHEST ANTICIPATED SNOW LEVEL
OR GRADE WHICHEVER IS GREATER
SCREWS
(4 req.)
ANCHORS
(4 req.)
7.2"
3.2"
COMBUSTION
AIR
12" MIN TO
OVERHANG
1" + "
VENT
1
2
MAINTAIN 12 IN.
MINIMUM CLEARANCE
ABOVE HIGHEST
ANTICIPATED SHOW
LEVEL OR GRADE
WHICH EVER IS GREATER
V
D
EE
V
G
INSIDE
CORNER DETAIL
B
L
V
V
FIXED
CLOSED
OPERABLE
F
B
C
V
FIXED
CLOSED
V
V
V
B
B
B
A
X
J
B
H
I
V
X
K
M
V
VENT TERMINAL
X
AIR SUPPLY INLET
AREA WHERE TERMINAL IS NOT PERMITTED
OPERABLE
k
BAYVENT200B
For Canadian applications only, IPEX 196006, IPEX 081216, IPEX 081218,
and IPEX 081219 may be used for horizontal vent terminations.
;
HORIZONTAL VENT CLEARANCES
(See clearance tables 11 and 12 on page 24)
l
BAYAIR30AVENTA
(Side wall)
For Canadian applications only, IPEX 196006, IPEX 081216, IPEX 081218,
and IPEX 081219 may be used for horizontal vent terminations.
CONCENTRIC VENT
SIDE WALL INSTALLATION
VENT FITTING MATERIAL – STAINLESS STEEL
Gas and liquid tight single wall metal vent fitting,
designed for resistance to corrosive flue condensate such
as Type 29-4C MUST be used throughout.
These fittings and fitting accessories are to be supplied
locally.
18-CD30D1-12 23
DIRECTION OF STAINLESS STEEL FITTING
All stainless steel fitting must be installed with male
end towards the Furnace. All horizontal stainless steel
sections must be positioned with the seam on top.
All long horizontal sections must be supported to prevent
sagging.
All pipe joints must be fastened and sealed to prevent
escape of combustion products into the building.
above the terminal within a horizontal distance
of 2 feet (61 cm) from the center line of the terminal
E=Clearance to unventilated soffit**
F=Clearance to outside corner**
G=Clearance to inside corner**
Clearance to each side of center line extended above
H=
meter/regulator assembly
I=Clearance to service regulator vent outlet3 feet (91 cm)*
Clearance to nonmechanical air supply inlet to building or
J=
the combustion air inlet to any other appliance
K=Clearance to a mechanical air supply inlet6 feet (1.83m)
Clearance above a paved sidewalk or paved driveway
L=
located on public property
M=Clearance under veranda, porch, deck, or balcony12 inches (30 cm) ‡*
Notes:
1. In accordance with the current CSA B149.1 Natural Gas and Propane Installation Code.
2. In accordance with the current ANSI Z223.1/NFPA 54 National Fuel Gas Code.
†. A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwelling and serves both dwellings.
‡. Pemitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.
* Clearance in accordance with local installation codes and the requirements of the gas supplier and the manufacturer's Installation Instructions.
Table 12Direct Vent Terminal Clearances
Clearance above grade, veranda, porch, deck,
A=
or balcony
Clearance to window or door that may be
B=
opened
C=Clearance to permanently closed window**
Vertical clearance to ventilated soffit located
above the terminal within a horizontal distance
D=
of 2 feet (61 cm)
from the center line of the terminal
E=Clearance to unventilated soffit**
F=Clearance to outside corner**
G=Clearance to inside corner**
Clearance to each side of center line extended
H=
above meter/regulator assembly
I=Clearance to service regulator vent outlet3 feet (91 cm)*
Clearance to nonmechanical air supply inlet to
J=
building or the combustion
air inlet to any other appliance
Clearance to a mechanical
K=
air supply inlet
Clearance above a paved sidewalk
L=
or paved driveway located on
public property
Clearance under veranda,
M=
porch, deck, or balcony
Notes:
1. In accordance with the current CSA B149.1 Natural Gas and Propane Installation Code.
2. In accordance with the current ANSI Z223.1/NFPA 54 National Fuel Gas Code.
†. A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwelling and serves both dwellings.
‡. Pemitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.
* Clearance in accordance with local installation codes and the requirements of the gas supplier and the manufacturer's Installation Instructions.
6 inches (15 cm) for appliances =/< 10,000 Btuh (3 kw),
12 inches (30 cm) for appliances > 10,000 Btuh (3 kw)
and =/< 100,000 Btuh (30 kw),
36 inches (91 cm) for appliances > 100,000 Btuh (30 kw)
6 inches (15 cm) for appliances =/< 10,000 Btuh (3 kw),
12 inches (30 cm) for appliances > 10,000 Btuh (3 kw)
and =/< 100,000 Btuh (30 kw),
36 inches (91 cm) for appliances > 100,000 Btuh (30 kw)
12 inches (30 cm) for appliances > 10,000 Btuh (3 kw)
and =/< 100,000 Btuh (30 kw),
36 inches (91 cm) for appliances > 100,000 Btuh (30 kw)
3 feet (91 cm) with a height 15 feet (4.5 m) above
6 inches (15 cm) for appliances =/< 10,000 Btuh (3 kw),
12 inches (30 cm) for appliances > 10,000 Btuh (3 kw)
and =/< 100,000 Btuh (30 kw),
36 inches (91 cm) for appliances > 100,000 Btuh (30 kw)
Canadian InstallationsUS Installations
12 inches (30 cm)12 inches (30 cm)
3 feet (91 cm) with a height 15 feet (4.5 m) above the meter/
regulator assembly
7 feet (2.13 m) †*
12 inches (30 cm) ‡*
12 inches (30 cm)12 inches (30 cm)
4 feet (1.2m) below or to the side of opening; 1 foot
**
the meter/regulator assembly
7 feet (2.13 m) †7 feet (2.13 m)
6 inches (15 cm) for appliances =/< 10,000 Btuh (3 kw),
9 inches (23 cm) for appliances > 10,000 Btuh (3 kw)
and =/< 50,000 Btuh (15 kw),
12 inches (30 cm) for appliances > 50,000 Btuh (15 kw)
**
6 inches (15 cm) for appliances =/< 10,000 Btuh (3 kw),
9 inches (23 cm) for appliances > 10,000 Btuh (3 kw)
and =/< 50,000 Btuh (15 kw), 12 inches (30 cm) for appliances >
50,000 Btuh (15 kw)
6 feet (1.83m)3 feet (91 cm) above if within 10 feet (3m) horizontally
(0.3m) above opening.
4 feet (1.2 m) below or to side of opening;
1 foot (300 m) above opening
3 feet (91 cm) above if within
10 feet (3m) horizontally
*
*
Page 25
Installer’s Guide
COUPLING
(PLASTIC
VENTING)
STUD
PVC WALL
MOUNT FLANGE
(OPTIONAL)
APPROVED
TERMINATION
1” CLEARANCE
(AIR SPACE)
VENTING THROUGH COMBUSTIBLE WALLS
Pitch - 1/4 Inch Per Foot
CLEARANCE (0” ACCEPTABLE FOR PVC VENT PIPE)
(1” ACCEPTABLE FOR TYPE 29-4C STAINLESS STEEL VENT PIPE)
STRAPS OR OTHER SUITABLE SUPPORTS
AT A MAXIMUM OF 3' 0" INTERVALS
TEE
NOTE: VENT AND INLET MUST BE SUPPORTED
AT A MAXIMUM OF 3' INTERVALS
BAYAIR30AVENTA
CONCENTRIC VENT
SIDE WALL INSTALLATION
For Canadian applications only, IPEX
196006, IPEX 081216, IPEX 081218,
and IPEX 081219 may be used for horizontal vent terminations.
x
COMBUSTIBLE MATERIAL WALL
A minimum clearance of 1" to combustible materials must
be maintained when using single wall stainless steel
venting. See Figure 32.
Shield material to be a minimum of 24 gauge stainless
or aluminized sheet metal. Minimum dimensions are
12"x12". Shield must be fastened to both inside and outside of wall. Use screws or anchor type fasteners suited
to the outside or inside wall surfaces.
18-CD30D1-12 25
BAYVENT200B
c
NONCOMBUSTIBLE MATERIAL WALL
The hole through the wall must be large enough to maintain pitch of vent and properly seal.
Use cement mortar seal on inside and outside of wall.
See Figure 33.
Page 26
Installer’s Guide
MAINTAIN 12 IN.
MINIMUM CLEARANCE
ABOVE HIGHEST
ANTICIPATED SNOW
LEVEL. MAXIMUM OF
24 IN. ABOVE ROOF.
VENT
COMBUSTION
AIR
REMOVE RIBS
FROM CAP
REMOVE RIBS
FROM CAP
COMBUSTION
AIR
ROOF BOOT
(FIELD SUPPLIED)
COMBUSTION
AIR
VENT
ELBOW
(FIELD SUPPLIED)
MAINTAIN 12 IN.
MINIMUM CLEARANCE
ABOVE HIGHEST
ANTICIPATED SNOW
LEVEL. MAXIMUM OF
24 IN. ABOVE ROOF
SUPPORT
(FIELD SUPPLIED)
VENT
12 INCHES MIN. CLEARANCE MUST BE
MAINTAINED ABOVE HIGHEST
ANTICIPATED SNOW LEVEL.
MAXIMUM NOT TO EXCEED
24 INCHES ABOVE ROOF.
SUPPORT HORIZONTAL PIPE EVERY
v
3' 0" WITH THE FIRST SUPPORT AS
CLOSE TO THE FURNACE AS POSSIBLE.
INDUCED DRAFT BLOWER, HOUSING,
AND FURNACE MUST NOT SUPPORT
THE WEIGHT OF THE FLUE PIPE.
b
BAYAIR30AVENTA (VERTICAL)
For Canadian applications only, IPEX 196006 may be
used for vertical or horizontal vent terminations.
26 18-CD30D1-12
For Canadian applications only,
IPEX 196006 may be used
for vertical or horizontal vent
terminations.
CONCENTRIC VENT
ROOF INSTALLATION
CONCENTRIC VENT
ROOF TOP APPLICATION
mn
Page 27
,
SUPPORT THE SINGLE WALL
STAINLESS STEEL GAS
VENTING AND CENTER IT IN
THE CHIMNEY OPENING WITH
ANGLES AS SHOWN OR
ANOTHER EQUIVALENT
MANNER.
NOTE:
HORIZONTAL VENTING
TO VERTICAL VENTING
6 IN. MIN.
SEE CAUTION
STAINLESS
STEEL
VENT CAP
(OPTIONAL)
SUPPORT THE SINGLE
WALL FLUE PIPE AND
CENTER IT IN THE
CHIMNEY OPENING WITH
ANGLES AS SHOWN OR
ANOTHER EQUIVALENT
MANNER.
NOTE:
HORIZONTAL VENTING
TO VERTICAL VENTING
6 IN. MIN.
STAINLESS
STEEL
VENT CAP
(OPTIONAL)
SEE CAUTION
FLUE PIPE
COUPLING
AS REQUIRED
FLUE PIPE
COUPLING TO SUPPORT
PIPE FROM ANGLES
OR OTHER SUITABLE
SUPPORT METHOD
Installer’s Guide
.
IMPORTANT –
Refer to Section 12.6.8 of NFPA 54 / ANSI 223.1 2012
when routing vent piping through a chimney.
IMPORTANT –
The single wall flue pipe joints must be sealed.
The 90° elbow connection to vertical pipe must be
sealed to prevent condensate leakage to base of
THROUGH UNUSED CHIMNEY
masonry chimney.
PVC PLASTIC VENTING
TYPE 29-4C STAINLESS STEEL VENTING
/
IMPORTANT –
Refer to Section 12.6.8 of NFPA 54 / ANSI 223.1 2012
when routing vent piping through a chimney.
THROUGH UNUSED CHIMNEY
IMPORTANT –
The single wall flue pipe joints must be sealed.
The 90° elbow connection to vertical pipe must be sealed
to prevent condensate leakage to base of masonry
chimney.
18-CD30D1-12 27
Page 28
Installer’s Guide
▲
CAUTION
!
ELECTRICAL CONNECTIONS
Protect from Property Damage
Do NOT connect the furnace line voltage to a GFCI
protected circuit. Failure to follow this warning could
result in property damage.
Make wiring connections to the unit as indicated on the
following field wiring diagram. As with all gas appliances
using electrical power, this furnace shall be connected
into a permanently live electric circuit. It is recommended
that furnace be provided with a separate “circuit
protection device” electric circuit. The furnace must be
electrically grounded in accordance with local codes or
in the absence of local codes with the National Electrical
Code, ANSI/ NFPA 70 or CSA C22.1 Electrical Code, if
an external electrical source is utilized. The integrated
furnace control is polarity sensitive.
The hot leg of the 120V power supply must be connected
to the Black power lead as indicated on the wiring
diagram. Provision for hooking up an Electronic Air
Cleaner and/ or Humidifier is provided on the Integrated
Control.
Refer to the Service Facts literature and unit wiring
diagram attached to the furnace.
WHOLE HOUSE AIR CLEANER
CONNECTION
NOTE:
The B/C terminal will require three wires to be connected to the low voltage terminal strip. To make this
easier, create a pigtail using a short length of thermostat wire to connect the three wires to the B/C terminal.
NOTE:
*FD whole house air cleaners with "D" or later in the
14th digit of the model number must use the BAYACCECOMM101 kit when connected for 24 volt mode. *FD
whole house air cleaners with "A", "B", or "C" in the
14th digit of the model number must use the BAYACCECOMM101 kit when connected for 24 volt or communicating modes. See the BAYACCECOMM101 Installer's
Guide for field wiring.
Field Wiring Diagrams
!
41A -Communicating Indoor Unit with Communicating Comfort Control and Communicating Outdoor Unit
28 18-CD30D1-12
Page 29
Installer’s Guide
41B - Communicating Indoor Unit with Communicating Comfort Control and 24VAC Single Stage Cooling
41C - 24 VAC Mode Indoor Unit with 24 VAC Comfort Control and 24VAC Single Stage Cooling
18-CD30D1-12 29
FIELD WIRING DIAGRAMS
Page 30
Installer’s Guide
Field Wiring Diagrams continued
41D - 24 VAC Mode Indoor Unit with 24 VAC Comfort Control and 24VAC 2-Stage or 2-Step Cooling
41E - 24 VAC Mode Indoor Unit with 24 VAC Comfort Control and 24VAC Single Stage Heat Pump
30 18-CD30D1-12
Page 31
Installer’s Guide
BK Jumper
41F - 24 VAC Mode Indoor Unit with 24 VAC Comfort Control and 24VAC 2-Stage or 2-Step Heat Pump
41G - Humidistat Hookup - 24 V Mode ONLY
The factory installed jumper between "R"
and "BK" on the circuit board must be
cut if an optional humidistat is installed.
HUMIDISTAT HOOKUP - 24 V ONLY
If an optional humidistat for humidity control in cooling
is used, the factory installed "BK Jumper" must be cut.
The BK Jumper must also be cut if a multi-zone
controller is connected to *CONT402 is installed and
using the BK enabled feature.
See the 24VAC field wiring diagrams for mor
information.
If upflow furnace is installed
over a finished ceiling, overflow
from the primary drain vent
stack must flow into an auxillary
drain pan to prevent damage to
the finished ceiling below.
CONDENSATE DRAIN INSTRUCTIONS
It is recommended that an external overflow drain pan
be installed under the furnace to prevent property
damage or personal injury from leaking condensate.
Evaporator and furnace condensate drain piping may be
manifolded together. A primary drain vent stack must be
installed and terminated below the outlet of the secondary heat exchanger drain connection to prevent water
from damaging furnace controls if the primary drain outlet
plugs up. Where the furnace is installed above a finished
ceiling, the primary drain vent stack must be installed
such that overflow from the vent stack opening will flow
into an auxiliary drain pan in order to prevent water damage to the finished ceiling below. See Figure 42.
@
VERTICAL APPLICATIONS
Upflow Vertical Furnace - The connection tubing for left
and right side drainage is shipped in the blower compartment. Install the connection tubing from the trap to the
side of the unit and trim all excess tubing to avoid kinks.
See Figures 43 & 44.
#
NOTE:
The condensate trap must be primed before operation.
Condensate trap
$
Left side
Condensate
Trap
UPFLOW (VERTICAL)
Condensate
Trap
UPFLOW (VERTICAL)
Right side
32 18-CD30D1-12
Page 33
Installer’s Guide
Downflow Vertical Furnace - Downflow furnace - Use
RTV silicon sealant to connect the fitting to the trap for
ease of removal when cleaning the trap.
For left side drain a 1/2" slip PVC fitting is needed. See
Fig 45.
To change to a right side drain, remove the drain lines
from the trap, rotate the trap 180° so it exits to the right,
then reconnect the lines. Start with a 1/2" 90° CPVC
street elbow connected to the trap using RTV silicon
sealant. Run 1/2" CPVC pipe to a CPVC elbow. Run 1/2"
CPVC pipe from the elbow out through the right side
knock-out. See Figure 46.
%
Left
side
The furnace trap must be repositioned to the exterior of
the cabinet. Remove the trap from its present location
and reposition the trap outside of the unit, through the
long circular hole, next to the secondary recuperative cell.
Remove the larger drain line (from the secondary cell)
and trim to fit between the secondary cell and the new
trap location. On upflow units, plug the hole in the blower
deck where the tube went through with factory supplied
cap.
Remove the hose from the induced blower and reposition
into the other drain tap of the inducer, which is located
90° clockwise around the inducer. Move the cap from that
drain tap to the unused drain tap. On upflow units, plug
the hole in the blower deck where the tube went through
with factory supplied cap.
&
DOWNFLOW (VERTICAL)
^
Right
side
DOWNFLOW
(VERTICAL)
HORIZONTAL APPLICATIONS
Upflow and Downflow Horizontal Furnaces - See
Figures 47 and 48. All horizontal applications are left side
only. It is always recommended that the auxiliary drain
pan be installed under a horizontally installed evaporator
and/or 95% Gas Furnace. Connect the auxiliary drain pan
to a separate drain line (no trap is needed in this line).
Use CPVC tubing from Trap outlet,
over burner box to cabinet exit
Use exten-
sion hose
here
UPFLOW HORIZONTAL 21" & 24" UNITS
(LEFT SIDE ONLY)
*
Use Inducer Drain
hose without
extension
UPFLOW HORIZONTAL 17" UNITS
(LEFT SIDE ONLY)
18-CD30D1-12 33
Page 34
Installer’s Guide
▲
CAUTION
!
▲
WARNING
!
▲
CAUTION
!
(
Cut off curved end of
Inducer drain hose
DOWNFLOW (HORIZONTAL)
This tube on downflow units will need to be cut to fit between the Inducer and the trap. On upflow units, this tube
may need to be extended, using the tubing shipped with
the furnace.
Connections must be made to an OPEN / VENTED DRAIN. Outdoor draining of the furnace and coil condensate is permissible if allowed by local codes.
Caution should be taken to prevent drains from freezing or causing slippery conditions that could lead to
personal injury. Excessive draining of condensate may
cause saturated ground conditions that may result in
damage to plants.
NOTE:
Use 1/2" or larger PVC or CPVC pipe and fittings as required for drain connections (fittings, pipe and solvent
cement not provided).
NOTE:
A corrosion resistant condensate pump must be used
if a pump is required for a specific drain system.
IMPORTANT:
The condensate drain should be installed with provisions
to prevent winter freeze-up of the condensate drain line.
Frozen condensate will block drains, resulting in Fur nace
shutdown. If the drain line cannot be installed in a conditioned space, then UL listed heat tape should be applied
as required to prevent freezing (per manufacturer’s instructions). The heat tape should be rated at 5 or 6 watts per
foot at 120 volts. Self-regulating (preferred) or thermostatically controlled heat tape is required.
GAS PIPING
FIRE - EXPLOSION HAZARD
DO NOT RUN FLEXIBLE GAS LINE THROUGH THE
FURNACE CABINET WALL OR WITHIN THE FURNACE
CABINET. FAILURE TO FOLLOW THIS WARNING
COULD RESULT IN PROPERTY DAMAGE, SERIOUS
PERSONAL INJURY, OR DEATH.
Use a backup wrench on the Gas Valve when installing
Gas Piping to prevent damage to the Gas Valve and
Manifold Assembly.
The upflow/ horizontal furnace is shipped standard for left
side installation of Gas Piping. A knockout is provided on
the right side for an alternate Gas Piping arrangement.
The installation of piping shall be in accordance with
piping codes and the regulations of the local gas
company. Pipe joint compound must be resistant to the
chemical reaction with liquefied petroleum gases. Flexible
gas connections, if applied, must not be routed through
the cabinet of the furnace.
Refer to Natural Gas Piping Table 13 for delivery sizes.
NOTE: Refer to local codes and the National Fuel Gas
Code, current edition, for gas pipe requirements.
The furnace and its individual shut-off valve must be
disconnected from the Gas Supply Piping system during
any pressure testing of that system at test pressures in
excess of 1/2 psig (3.5 kPa).
The furnace must be isolated from the Gas Supply Piping
by closing its individual manual shut-off valve during any
pressure testing of the Gas Supply Piping system at test
pressures equal to or less than 1/2 psig (3.5 kPa).
NOTE:
Maximum pressure to the Gas Valve for natural gas is
13.8" W.C. Minimum pressure is 5.0" W.C. Maximum
pressure to the Gas Valve for Propane is 13.8" W.C.
Minimum pressure is 11.0" W.C.
TABLE 13
NATURAL GAS ONLY
TABLE OF CUBIC FEET PER HOUR OF GAS
FOR VARIOUS PIPE SIZES AND LENGTHS
PIPE
SIZE
1/2132927363565046
3/427819015213011510596
1-1/41050730590520440400370
This table is based on Pressure Drop of 0.3 inch W.C. and 0.6 SP.GR. Gas
10203040506070
1520350285245215195180
LENGTH OF PIPE
NOTE:
All supplied flexible condensate piping is for internal
use only. All condensate piping external to the unit
must be CPVC or PVC piping.
34 18-CD30D1-12
All Gas fittings must be checked for leaks using a soapy
solution before lighting the furnace. DO NOT CHECK
WITH AN OPEN FLAME!
Page 35
Installer’s Guide
DRIP LEG
)
Q
DRIP
LEG
AUTOMATIC GAS VALVE
WITH MANUAL SHUT-OFF
UPFLOW MAY BE LEFT OR RIGHT HAND GAS PIPING
DRIP
LEG
AUTOMATIC GAS VALVE
WITH MANUAL SHUT-OFF
DRIP
LEG
DRIP
LEG
IMPORTANT:
A sediment trap
must be installed
in the gas line before the furnace
gas valve. The sediment trap must be
located as close to
the furnace cabinet
as practical.
IMPORTANT:
A sediment trap
must be installed
in the gas line before the furnace
gas valve. The sediment trap must be
located as close to
the furnace cabinet
as practical.
THE DOWNFLOW (VERTICAL) MAY BE INSTALLED LEFT OR RIGHT SIDE GAS PIPING
AUTOMATIC GAS VALVE
W
WITH MANUAL SHUT-OFF
DRIP
LEG
DRIP
LEG
AUTOMATIC GAS VALVE
WITH MANUAL SHUT-OFF
HORIZONTAL FURNACE GAS PIPING MAY BE FROM EITHER SIDE
(TYPICAL UPFLOW FURNACE IN HORIZONTAL CONFIGURATION SHOWN)
IMPORTANT:
A sediment trap
must be installed
in the gas line before the furnace
gas valve. The sediment trap must be
located as close to
the furnace cabinet
as practical.
18-CD30D1-12 35
Page 36
Installer’s Guide
▲
CAUTION
!
COMBUSTION AND INPUT CHECK
(SEE ALSO HIGH ALTITUDE DERATE)
NOTE: Before checking or adjusting the gas pressure,
make sure the condensate trap has been primed.
1. Make sure all Gas appliances are off except the furnace.
2. Clock the Gas Meter with the furnace operating on
high heat for one revolution. Table 18 shows the flow
rate in cubic feet per hour for a measured time of
one revolution for a meter on which one revolution
indicates 2 cubic feet per hour of gas flow. For other
meters, use the following conversions:
a. For 1 Cu. Ft. Dial Gas Flow CFH = Chart Flow
Reading ÷ 2
b. For 1/2 Cu Ft. Dial Gas Flow CFH = Chart Flow
Reading ÷ 4
c. For 5 Cu. Ft. Dial Gas Flow CFH = 10X Chart Flow
Reading ÷ 4
3. Multiply the final figure by the heating value of the
gas obtained from the utility company and compare to the
nameplate rating. This must not exceed the nameplate
rating.
4. Repeat steps 2 and 3 with the furnace operating on
low heat.
5. Changes can be made by adjusting the manifold
pressure (See Table 15), or changing orifices (orifice
change may not always be required).
HIGH ALTITUDE DERATE
CAUTION
Maintain manifold pressure as specified in Table 15
in high altitude installations. Failure to do so may
result in poor ignition characteristics.
Input ratings (BTUH) of these furnaces are based on sea
level operation and should not be changed at elevations
up to 2,000 ft. (610m).
If the installation is 2,000 ft. (610m) or above, the furnace
input rate (BTUH) shall be reduced 4% for each 1,000 ft.
above sea level.
Installation of this furnace at altitudes above 2,000 ft.
(610m) shall be in accordance with local codes, or in the
absence of local codes, the National Fuel Gas Code,
ANSI Z223.1/NFPA 54 or National Standard of Canada,
Natural Gas and Propane Installation Code, CSA B149.1.
The furnace input rate shall be checked by using the
methods of Combustion and Input Check. High altitude
kits are listed in Table 15A.
For upflow 120KBTU/hr model, 1st stage is 45%
Manifold pressures apply for Propane applications ONLY
FINAL NG MANIFOLD PRESSURE SETTINGS (inches w.c.)
40%65%100%
FINAL LP MANIFOLD PRESSURE SETTINGS (inches w.c.)
40%65%100%
BAYSWT09AHALTA*UHMB080ACV3V
*DHMB080ACV3V
*UHMC100ACV4V
*DHMC100ACV4V
BAYSWT08AHALTA*UHMD120ACV5V
*DHMD120BCV5V
* May be "A" or "T"
36 18-CD30D1-12
Page 37
Installer’s Guide
If the desired input rate cannot be achieved with a
change in manifold pressure, then the orifices must be
changed. See Table 16 for replacement orifice part numbers.
LP installations will require an orifice and gas valve
change. Order kit BAYLPKT220B or BAYLPSS220B.
IMPORTANT:
Reinstall the propane orifices to the same depth as the orifices supplied with the equipment.
See Table 17 for help in selecting orifices if orifice
change is required. Furnace input rate and temperature
rise should be checked again after changing orifices to
confirm the proper rate for the altitude. The vent length
table on page 19 shows the required vent lengths
for installations at various altitudes. An optional high
altitude kit is available for installations above 4000 feet
(Installations above 12,000 feet are not allowed). Use
Table 15A to select the appropriate high altitude kit for
your furnace model.
Note:
Natural gas input rate should be clocked at gas meter in high
heat when the gas valve is replaced or gas valve pressure
adjustments are made.
Table 19 lists the main burner orifices used with the Furnace.
Table 19 ORIFICE SIZES
INPUT
RATING
BTUH
60,000
80,000
100,000
120,000
NUMBER
OF
BURNERS
3
4
5
6
MAIN BURNER ORIFICE
DRILL SIZE
NAT. GASLP GAS
45
45
45
45
56
56
56
56
Note:
The LP Conversion Kit used with the modulating furnace
is BAYLPSS220B or BAYLPKT220B.
18-CD30D1-12 37
Page 38
Installer’s Guide
Heat Exchanger (Cold Header)
Burner Box
H-Fitting
Pressure
Switch
PS-1
Tee
Tee
Tee
Pressure Switch
PS-3
Pressure
Switch
PS-2
Negative
Control
Pressure
Post
Positive Control
Pressure Post
Modulating
Gas Valve
Orifice in H fitting must
be pointing away from PS1
To Pressure
Switch PS-1
! Important !
Brass orifices located in these two legs.
H-Fitting must be installed in this orientation.
E
VACUUM HOSE
ROUTING
38 18-CD30D1-12
R
Page 39
Installer’s Guide
▲
WARNING
!
▲
WARNING
!
▲
CAUTION
!
▲
CAUTION
!
REINSTALLATION OF THE BURNER BOX COVER
Figure 55 shows the correct way to reinstall the Burner
Box cover if adjustment or replacement of the Flame
Sensor, Hot Surface Igniter, or Main Burner orifices have
required removal of the cover.
T
ROTATE THE FRONT
COVER AS SHOWN
INSERT THE TOP FLANGE
OF THE FRONT COVER
UNDER THE LIP INSIDE
THE BOX
ALL SIDE FLANGES MUST
BE OUTSIDE OF THE BOX
ROTATE THE FRONT
COVER INWARD MAKING SURE THAT ALL SIDE
FLANGES ARE OUTSIDE
OF THE BOX.
START-UP AND ADJUSTMENT
PRELIMINARY INSPECTIONS
ELECTRICAL SHOCK HAZARD
Disconnect power to the unit before removing the
blower door. Allow a minimum of 10 seconds for IFC
power supply to discharge to 0 volts.
Failure to follow this warning could result in property
damage, personal injury or death.
for any gas that might have escaped to dissipate. LP Gas
being heavier than air may require forced ventilation. Turn
the toggle switch on the Gas Valve in the unit to the “ON”
position.
All soap solution should be cleaned off gas piping after
gas leak testing is complete.
LIGHTING INSTRUCTIONS
FIRE OR EXPLOSION HAZARD
Do NOT attempt to manually light the burner.
Failure to follow this warning could result in property
damage, personal injury or death.
Whenever your house is to be vacant, arrange
to have someone inspect your house for proper
temperature. This is very important during freezing
weather. If for any reason your furnace should fail to
operate damage could result, such as frozen water
pipes.
Lighting instructions appear on each unit. Each
installation must be checked out at the time of initial start
up to insure proper operation of all components. Check
out should include putting the unit through one complete
cycle as outlined below.
Turn on the main electrical supply and set the Comfort
Control above the indicated temperature. The Ignitor will
automatically heat, then the Gas Valve is energized to
permit the flow of gas to the burners. After ignition and
flame is established, the Flame Control Module monitors
the flame and supplies power to the Gas Valve until the
Comfort Control is satisfied.
TO SHUT OFF
For complete shutdown: Turn the Gas Valve toggle switch
on the main Gas Valve to the “OFF” position (See Figures
59). Disconnect the electrical supply to the unit.
NOTE: The condensate trap must be primed before
operation.
With gas and electrical power “OFF”
1. Duct connections are properly sealed.
2. Filters are in place.
3. Venting is properly assembled.
4. Blower door is in place.
Turn the main Gas Valve toggle switch (See Figure 59)
within the unit to the “OFF” position. Turn the external
shutoff valve to the “OPEN” position (See Figures 50 and
52). Purge the air from the gas lines. After purging, check
all gas connections for leaks with a soapy solution — DO NOT CHECK WITH AN OPEN FLAME. Allow 5 minutes
18-CD30D1-12 39
If complete shutdown is done during the cold
weather months, provisions must be taken to prevent
freeze-up of all water pipes and water receptacles.
NOTE:
Natural gas units should not have any yellow tipped
flames. This condition indicates that a service call is
required. For best operation, burners must be cleaned
annually using brushes and vacuum cleaner.
Page 40
Installer’s Guide
▲
WARNING
!
▲
WARNING
!
ENTER
USER INTERFACE MENU
SERVICE PROCEDURE TO ACCESS
USER INTERFACE FOR THE MODULATING FURNACE
This procedure should only be performed by trained service
personnel.
ELECTRICAL SHOCK HAZARD
DO NOT BYPASS THE DOOR SWITCH BY ANY
PERMANENT MEANS.
FAILURE TO FOLLOW WARNING COULD RESULT IN
SERIOUS PERSONAL INJURY OR DEATH.
ELECTRICAL SHOCK HAZARD
DO NOT TOUCH ANY COMPONENTS OTHER THAN THE
DISPLAY ASSEMBLY AND THE DOOR SWITCH DURING
THIS PROCEDURE.
FAILURE TO FOLLOW WARNING COULD RESULT IN
SERIOUS PERSONAL INJURY OR DEATH.
1. Remove Blower Door panel by turning the two door
latches.
2. Lower door panel and remove from service access area.
3. Use one hand depress the door switch (there must be
power to the control system for the display assembly to
function) and keep the door switch depressed during
programming.
4. Using the other hand move through the Display Assembly
menu using the arrow buttons.
5. The User Interface menu on pages 41-42 is a guide to
the menu options.
6. When programming is complete release Door Switch
and replace the Blower Door.
NOTE:
If power is lost during programming, all changes made
will be saved.
USER INTERFACE
Y
Push left & right
Viewing Window
Push ENTER
to make selection
User Interface pictured above adjusts Variable Speed Airflow options and is used
for custom setup of Furnace operations- See menu options in User Interface on pages 45-46.
to scroll through
menu options
Push up & down
to scroll through
setup menu
40 18-CD30D1-12
Page 41
TABLE 20 - USER INTERFACE MENU
Power Up
== WAIT ==
A/TCONT900 Variable Speed
Standy ScreenSystem StatusSetup Options[ ] = Current Setting
MODEL NUMBERCMFRT CNT MODE
SERIAL NUMBERCOMM [COMM] 24VAC
3 This menu will only display when 2 STGS is chosen in previous menu.
2 Shown only when Communicating Outdoor Unit is not detected
TABLE 20 - USER INTERFACE MENU - 24VOLT MENU (CONTINUED)
42 18-CD30D1-12
Page 43
Installer’s Guide
SEQUENCE OF OPERATION
SEQUENCE OF OPERATION – COMMUNICATING
MODE
1. This furnace is fully modulating between 40% and
100% of capacity in 1% increments. The furnace
always lights at approximately 65% and will modulate
up or down; depending on the communicating
comfort control demand. Requested capacity can be
seen in the “STATUS” section of the User Interface
menu.
Note:
Pressure Switch 1 closes at approximately 40% of
capacity.
Pressure Switch 2 closes at approximately 65% of
capacity.
Pressure Switch 3 closes at approximately 95% of
capacity.
2. The communicating comfort control signals the furnace
IFC for heat.
3. The IFC then checks all safeties, thermostats, and
pressure switches PS1, PS2, and PS3.
4. The IFC signals the variable speed inducer drive to
start the vent motor at the speed needed to close
pressure switches PS1 and PS2.
5. PS1 and PS2 close.
6. The IFC receives a 24 VAC signal from PS1 and PS2
when they close. This verifies the vent motor is
moving the correct amount of combustion air through
the furnace and the vent system.
7. IFC starts the hot surface ignitor learning routine
warm-up time cycle.
8. IFC turns on the gas valve. Trial time for ignition is 5
seconds.
Note:
The furnace lights at approximately 65% of capacity.
9. The IFC verifies ignition by the flame current sensing
method. If a flame is not detected, the IFC will cycle
the furnace three times to try and verify a flame. If no
flame is detected, the IFC will lockout for one hour.
The IFC will send an alert code to the communicating
comfort control (ERR 22) and User Interface (RETRY
LO). The Red alert LED two times repeatedly.
10. If a flame is detected, the IFC will start the heat
exchanger warm-up time delay for the indoor blower.
11. “IGNITION” will now be displayed in the “STATUS”
section of the User Interface menu.
12. After 45 seconds, the IFC signals the indoor blower
motor and run at the programmed ignition sequence
speed.
13. Depending on the communicating comfort control
demand, the IFC will then signal the variable speed
inducer motor drive board and the indoor blower
motor to ramp up or down.
14. With a heat demand less than 65% from the
communicating comfort control, the IFC signals the
variable speed inducer motor drive board to ramp
down to that corresponding demand speed. The
reduction of the vent motor speed in steps allows the
gas flow through the gas valve to also be reduced
in steps, decreasing the chance of burner flame out.
The minimum capacity change is 1%.
15. The minimum capacity of all furnaces is 40%, with the
exception of the *UHMC120. The minimum capacity
for this furnace is 45%.
16. The communicating comfort control will continue
to call for the requested capacity demand until the
indoor temperature is back at the set point OR,
17. If the communicating comfort control does not detect
that the indoor temperature is moving back towards
its set point or the indoor temperature is still moving
away from the set point, it will signal the IFC to go to
a higher capacity of heat.
18. The IFC then signals the variable speed inducer drive
to ramp up the vent motor in steps. As the vent motor
speed increases the amount of gas coming through
the gas valve will increase. The IFC will also increase
the indoor blower motor speed.
19. The communicating comfort control will continue to
monitor the indoor temperature and send signals to
the IFC to modulate the heating capacity or turn off to
maintain the homeowner's set point.
20. Once the communicating comfort control senses
that the heating requirements have been satisfied,
the gas valve will be de-energized and gas flow
will cease. The variable speed vent motor will deenergize approximately after a 5 second post purge.
All pressure switches will open and the indoor blower
motor will then run the heat off delay that is selected
in the User Interface menu.
Indoor Blower motor operation thermostat fan switch
“ON” (Communicating Mode)
The communicating comfort control signals a continuous fan call. The factory setting is 50% of the cooling cfm
selected but can be adjusted from 25% - 100% through
the Installer Setup menu on the communicating comfort
control. If the outdoor unit is a 2 stage system, the factory
setting is 50% of the 2nd stage cooling cfm. If the outdoor
unit is a 24 volt single stage cooling system, the factory
setting is 50% of the cooling cfm.
NOTE: If the actual relative humidity (RH) is at or
below the set-point, the fan will run until the continuous fan call is removed or the actual RH exceeds the
set-point. If the actual RH is above the set-point, the
fan will not turn on.
See the communicating comfort control Installer's Guide
for additional information.
18-CD30D1-12 43
Page 44
Installer’s Guide
SEQUENCE OF OPERATION – 24VAC Mode
1. This furnace modulates between 40% and 100% of
capacity, in 3% increments, every 1 minute. The
furnace always lights at approximately 65% and
will modulate up or down; depending on the 24VAC
thermostat signal. Requested capacity can be seen
in the “STATUS” section of the User Interface menu.
Note:
Pressure Switch 1 closes at approximately 40% of
capacity.
Pressure Switch 2 closes at approximately 65% of
capacity.
Pressure Switch 3 closes at approximately 95% of
capacity.
Thermostat call for W1 (2 stage heating thermostat)
2. R and W1 contacts close signaling the control board
(IFC) to run its self- check routine. After the control
has verified that all safeties are closed and PS1,
PS2, and PS3 pressure switch contacts are open, the
IFC signals the variable speed inducer drive to start
the vent motor at the speed needed to close pressure
switches PS1 and PS2.
Note:
The furnace lights at approximately 65% of capacity.
3. PS1 and PS2 close.
4. The IFC receives a 24 VAC signal from PS1 and PS2
when they close. This verifies the vent motor is
moving the correct amount of combustion air through
the furnace and the vent system.
5. IFC starts the hot surface ignitor learning routine
warm-up time cycle.
6. IFC turns on the gas valve. Trial time for ignition is 5
seconds.
7. The IFC verifies ignition by the flame current sensing
method. If a flame is not detected, the IFC will cycle
the furnace three times to try and verify a flame. If no
flame is detected, the IFC will lockout for one hour.
The IFC will send an alert code to the communicating
comfort control (ERR 22) and User Interface (RETRY
LO) as well as flash its Red alert LED two times
repeatedly.
8. If a flame is detected, the IFC will start the heat
exchanger warm-up time delay for the indoor blower.
9. “IGNITION” will now be displayed in the “STATUS”
section of the User Interface menu.
10. After 45 seconds, the IFC signals the indoor blower
motor to run at the programmed ignition sequence
speed.
11. The IFC then signals the variable speed inducer
motor drive board to ramp down to the corresponding
speed to keep PS1 closed. The reduction of the vent
motor speed in steps allows the gas flow through the
gas valve to also be reduced in steps, decreasing the
chance of burner flame out. The W1 heating capacity
is 40%. The IFC will also decrease the indoor blower
motor speed.
Thermostat call for W2 after W1
12. R and W2 thermostat contacts close signaling a call
for W2 heat. The IFC then signals the variable speed
inducer drive to ramp up the vent motor allowing flow
through the gas valve to also be increased in 3%
steps.
13. If the call for W2 remains, this 3% increase will be
repeated every 1 minute until the capacity requested
is 100%. The IFC will also increase the indoor blower
motor speed in appropriate steps.
W2 satisfied, W1 still called for
14. R and W2 thermostat contacts open signaling that W2
heating requirements have been satisfied. The IFC
will signal the variable speed vent motor to slow down
to its learned W1 speed. The gas valve will reduce
the gas flow to 40% capacity and the indoor blower
motor speed will be reduced.
W1 satisfied
15. R and W1 thermostat contacts open signaling that W1
heating requirements have been satisfied. The gas
valve will be de-energized and gas flow will cease.
The variable speed vent motor will de-energize
approximately after a 5 second post purge. The
indoor blower motor will be de-energized after the fan
off delay period has ended. (The indoor blower heat
fan off delay is field selectable and can be adjusted
using the User Interface menu. It is factory set at 100
seconds but can be set to 60, 140, or 180 seconds)
Thermostat call for heat (1 stage heating thermostat)
Note: The inter-stage delay is field selectable and can
be adjusted through the User interface menu. It is factory set at 0 minutes but can be adjusted to 5, 10, or
15 minutes. This option can help optimize the furnace
to try to satisfy the heating requirement during low
heating load conditions.
16. W1 and W2 must be jumpered at the IFC. R and
W1 contacts close signaling the control board (IFC)
to run its self- check routine. After the control has
verified that all safeties are closed and PS1, PS2,
and PS3 pressure switch contacts are open, the IFC
signals the variable speed inducer drive to start the
vent motor at the speed needed to close pressure
switches PS1 and PS2.
Note:
The furnace lights at approximately 65% of capacity.
17. PS1 and PS2 close.
18. The IFC receives a 24 VAC signal from PS1 and
PS2 when they close. This verifies the vent motor is
moving the correct amount of combustion air through
the furnace and the vent system.
19. IFC starts the hot surface ignitor learning routine
warm-up time cycle.
20. IFC turns on the gas valve. Trial time for ignition is 5
seconds.
21. The IFC verifies ignition by the flame current sensing
method. If a flame is not detected, the IFC will cycle
44 18-CD30D1-12
Page 45
Installer’s Guide
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
Communicating
Comfort Control
the furnace three times to try and verify a flame. If no
flame is detected, the IFC will lockout for one hour.
The IFC will send an alert code to the communicating
comfort control (ERR 22) and User Interface (RETRY
LO) as well as flash its Red alert LED two times
repeatedly.
22. If a flame is detected, the IFC will start the heat
exchanger warm-up time delay for the indoor blower.
23. “IGNITION” will now be displayed in the “STATUS”
section of the User Interface menu.
24. After 45 seconds, the IFC signals the indoor blower
motor to run at the programmed ignition sequence
speed.
25. Every 1 minute, the IFC will signal the vent motor
to ramp up. The increase of the vent motor speed
allows the gas flow through the gas valve to also
be increased in 3% steps. This 3% increase will be
repeated every 1 minute until the capacity requested
is 100%. Pressure switch 3 closes at approximately
95% of capacity.
26. The IFC will also increase the indoor blower motor
speed in appropriate steps.
Indoor Blower motor operation thermostat fan switch
“CONTINUOUS” (24V Mode)
R and G comfort control contacts close signaling a continuous fan call. The continuous fan cfm is field selectable
and can be adjusted through the User Interface menu.
The factory setting is 50% of the cooling cfm selected
but can be set at 25%, 50%, 75%, or 100%. If the system
has a 2 stage outdoor unit, the setting is 50% of the 2nd
stage cooling cfm.
A qualified technician can cycle the Variable Speed
Indoor Blower and the Modulating Gas Furnace
through its operation at the User Interface.
• The unit test cycle is entered at the user interface.
• The test cycle can only be entered when the comfort
control has no demand and thefurnace IFC is not
reporting a fault. Turn the comfort control to the Off
position and turn the fan control to Auto. This will
ensure the unit test cycle will not be interrupted.
• Scroll down using the button at the user interface until
the display reads:
• UNIT TEST. Press the Enter button.
• UNIT TEST and NO (NO) will now be displayed. Use
the or arrow button to change the NO to a YES and
then press ENTER.
• ARE YOU SURE and NO (NO) will now be displayed. Use
the or arrow button to change the NO to a YES and
then press ENTER.
• UNIT TEST and Y1 ON FAN ON will now be displayed.
The variable speed indoor blower will then be turned
on by the IFC for 10 seconds and then off.
• Furnace will then transition to the ignition sequence.
STAGE OFF will now be displayed. After a 45 second
heat fan on delay, Stage 1 will be displayed and 40%
(low) heat inducer speed will be energized for 10
seconds.
•Stage 2 will be displayed and 100% (high) heat inducer
speed will be energized for 10 seconds.
• The control transitions to off.
• The Model and Serial Number will be displayed.
• The variable speed indoor blower will now operate for the
heat exchanger cool down cycle and then shut off at the
end of the cycle.
• The comfort control can now be returned to the
homeowner’s desired settings.
B) GAS VALVE SETUP (MANIFOLD PRESSURE
ADJUSTMENT)
NOTE: To obtain an accurate manifold pressure measurement ,the manifold pressure must be referenced
to the burner box, since the burner box pressure tap
equalizes the gas valve pressure regulator. To do so,
install a tee and section of tube (field supplied) in the
tubing between the tee coming from the burner box
tube and the gas valve manifold pressure measurement fitting. This tube and tee is in addition to the
tube attached to the gas valve pressure tap on the
outlet side of the gas valve. See Figure 58.
NOTE: In order to properly set the manifold gas
pressure, the incoming line gas pressure should be
tested with the unit off and again with the unit operating at the high heat setting to ensure adequate fuel
supply to the furnace. The incoming gas pressure
should be 5" W.C. minimum and 13.8" W.C. maximum
for natural gas.
1) Before Setting Manifold Gas Pressure
Setting the manifold gas pressures is critical for the cor-
rect operation of this furnace.
Before entering the Gas Valve Setup mode:
a. Turn comfort control system switch to the OFF position
and fan switch to the AUTO position.
b. Prime the furnace condensate trap.
Any call for heat or fan by the comfort control will abort
or cancel the Gas Valve Setup mode. The unit will
stay in Gas Valve Setup mode for a maximum of 20
minutes.
c. Connect dual port manometer & field tubing per Figure
58 on page 47.
Note: MIN = 40% (low) heat, MAX = 100% (high) heat
Setting Manifold Gas Pressure
2) Setting “MIN” manifold gas pressure
To enter the Gas Valve Setup mode:
a. Scroll down on the user interface to Unit Test.
b. Scroll to the right and select “Gas Val Setup”.
c. Push the Enter button.
d. Select “MIN” and push the Enter button.
e. When asked “Are You Sure”, select Yes, and push the
Enter button.
f. The furnace will now begin the ignition sequence.
g. If pressure switch 1 & 2 learning routines have not
been performed; after successful ignition, the inducer
will go through this operation. (see Inducer Learning
Routine section).
46 18-CD30D1-12
Page 47
Installer’s Guide
I
Manifold
Pressure
Measurement
Fitting
CORRECT METHOD OF CHECKING DIRECT VENT MANIFOLD PRESSURE
WITH BURNER BOX REFERENCED
!
WARNING
▲
EXPLOSION HAZARD
REPLACE AND/OR TIGHTEN
ALL PLUGS REMOVED
OR LOOSENED WHEN
ADJUSTING GAS PRESSURE.
LEAK CHECK THE FITTINGS
Slope
Gauge
BEFORE PLACING INTO
REGULAR SERVICE.
FAILURE TO FOLLOW THIS
WARNING COULD RESULT IN
SERIOUS PERSONAL INJURY,
PROPERTY DAMAGE, OR
Connects to
Burner Box
Pressure Hose
Field Supplied
DEATH
A Field Supplied barb fitting must be used
on the gas valve to attach the hose
For upflow 120KBTU/hr model, 1st stage is 45%
Manifold pressures apply for Natural Gas applications ONLY
Furnace Input
rate (KBTU/hr)
602.1 ± 0.5Not Adjustable10.0 ± 0.5
802.1 ± 0.5Not Adjustable10.0 ± 0.5
1002.1 ± 0.5Not Adjustable10.0 ± 0.5
Downflow 1202.1 ± 0.5Not Adjustable10.0 ± 0.5
Upflow 1202.9 ± 0.5Not Adjustable10.0 ± 0.5
For upflow 120KBTU/hr model, 1st stage is 45%
Manifold pressures apply for Propane applications ONLY
FINAL NG MANIFOLD PRESSURE SETTINGS
(inches w.c.)
40%65%100%
FINAL LP MANIFOLD PRESSURE SETTINGS
(inches w.c.)
40%65%100%
O
Negative Control
Pressure Post
Gas Valve
On/ Off
Toggle
Switch
Inlet Pressure
Measurement Fitting
Low Heat Manifold
Pressure
(Adjustment under
cover)
Positive Control
Pressure Post
High Heat
Manifold
Pressure
(Adjustment
under cover)
Flow
Manifold
Pressure
Measurement
Fitting
18-CD30D1-12 47
Page 48
Installer’s Guide
▲
WARNING
!
h. Allow 5 minutes to pass before attempting to adjust
the 40% manifold pressure. This will insure that the
learning routine is complete and that the heat rise is
stable.
j. Read the 40% manifold pressure.
k. If needed, remove the low heat manifold adjustment
cover and adjust to obtain the correct manifold pressure. See Figure 59.
40% (LOW) HEAT ADJUSTMENT: TURN CLOCKWISE
TO DECREASE MANIFOLD PRESSURE OR COUNTERCLOCKWISE TO INCREASE MANIFOLD PRESSURE.
l. Use Manifold Pressure Settings Table 21 for the correct
manifold pressure setting in Inches of Water Column.
m. Once the 40% manifold pressure has been adjusted;
push the Enter button on the user interface. This will
stop the gas valve setup mode and take you back to
the home screen.
3) Setting “MAX” manifold gas pressure
To enter the Gas Valve Setup mode:
a. Scroll down on the user interface to Unit Test.
b. Scroll to the right and select “Gas Val Setup”.
c. Push the Enter button.
d. Scroll to the right and select MAX; then push the Enter
button.
e. Select “MAX” and push the Enter button.
f. When asked “Are You Sure”, select Yes, and push the
Enter button.
g. The furnace will now begin another ignition sequence.
h. If pressure switch 2 & 3 learning routines have not
been performed; after successful ignition, the inducer
will go through this operation. (see Inducer Learning
Routine section).
i. Allow 5 minutes to pass before attempting to adjust
the 100% manifold pressure. This will insure that the
learning routine is complete and that the heat rise is
stable.
j. Read the 100% manifold pressure.
k. If needed, remove the high heat manifold adjustment
cover and adjust to obtain the correct manifold pressure. See Figure 59.
100% (HIGH) HEAT ADJUSTMENT: COUNTERCLOCKWISE TO DECREASE MANIFOLD PRESSURE OR
CLOCKWISE TO INCREASE MANIFOLD PRESSURE.
l. Use Manifold Pressure Settings Table 22 for the correct
manifold pressure setting in Inches of Water Column.
m. Replace and tighten the adjustment cover for the high
heat and read the manifold pressure again. This
procedure may need to be repeated until the correct
manifold pressure is obtained.
NOTE: The adjustment cover over the high heat must
be in place during manifold gas pressure readings.
See Figure 53.
n. If the firing rate cannot be obtained with the manifold
pressures specified in Table 22, the orifices must be
changed. If a change of orifices is required to correct
the furnace input rating, refer to Table 17 on page 37.
o. Once the 100% manifold pressure has been adjusted;
push the Enter button on the user interface. This will
stop the gas valve setup mode and take you back to
the home screen.
EXPLOSION HAZARD
REPLACE AND/OR TIGHTEN ALL PLUGS
REMOVED OR LOOSENED WHEN ADJUSTING GAS
PRESSURE. LEAK CHECK THE FITTINGS BEFORE
PLACING INTO REGULAR SERVICE.
FAILURE TO FOLLOW THIS WARNING COULD
RESULT IN SERIOUS PERSONAL INJURY,
PROPERTY DAMAGE, OR DEATH.
p. Remove all field supplied tubing and measurement
devices. Reinstall and tighten all covers and outlet
pressure tap screw.
q. Leak test all gas fittings using a leak detection solution
or soap suds.
r. Turn comfort control to home owners desired
temperature.
48 18-CD30D1-12
Page 49
Installer’s Guide
TABLE 22
Furnace
Input rate
(KBTU/
hr)
1000.7 + 0.2 / - 0.0Not Adjustable3.5 ± 0.2
Downflow
120
Upflow
120
For upflow 120KBTU/hr model, 1st stage is 45%
Manifold pressures apply for Natural Gas applications ONLY
Furnace
Input rate
(KBTU/hr)
1002.1 ± 0.5Not Adjustable10.0 ± 0.5
Downflow
120
Upflow 1202.9 ± 0.5Not Adjustable10.0 ± 0.5
For upflow 120KBTU/hr model, 1st stage is 45%
Manifold pressures apply for Propane applications ONLY
FINAL NG MANIFOLD PRESSURE SETTINGS (inches
w.c.)
40%65%100%
600.7 + 0.2 / - 0.0Not Adjustable3.5 ± 0.2
800.7 + 0.2 / - 0.0Not Adjustable3.5 ± 0.2
0.7 + 0.2 / - 0.0Not Adjustable3.5 ± 0.2
0.9 + 0.2 / - 0.0Not Adjustable3.5 ± 0.2
FINAL LP MANIFOLD PRESSURE SETTINGS (inches
w.c.)
40%65%100%
602.1 ± 0.5Not Adjustable10.0 ± 0.5
802.1 ± 0.5Not Adjustable10.0 ± 0.5
2.1 ± 0.5Not Adjustable10.0 ± 0.5
PERSONALITY MODULE
The Personality Module is a removable memory device,
on which is stored model specific data required for proper
furnace operation. The Personality Module is tethered to
the unit and must remain with the furnace at all times. The
Personality module must remain plugged into the furnace
IFC.
STAND ALONE OPERATION (CONTINGENCY MODE)
The Contingency Mode allows the installer to set the
equipment to operate in an ON/ OFF Duty Cycle mode.
This mode will be activated using the User Interface.
Contingency Mode is NOT available in 24VAC mode. The
user will select the desired level of capacity required,
Stage 1 (40%) or 2 (100%). The user will select the
desired ON/ OFF Duty Cycle, 10% minimum to 50%
maximum, (10% increments, 10% = 2 minutes On, 18
minutes Off; 50% = 10 minutes on, 10 minutes off).
Note:
If a communicating comfort control is detected to be
present and the contingency mode is selected, NOT
AVAILABLE will be displayed on the User Interface.
• Stand alone operation can only be entered at the user
interface.
• Stand alone operation can be set up to operate the
furnace in Heating Only.
• The contingency mode is used when the communicating
comfort Control is not communicating with the furnace or
when setting gas manifold pressures.
• Before attempting to enter contingency mode, disconnect
the Data wire "D" from the Furnace IFC terminal block.
• The contingency mode will function only when the
Furnace IFC is not flashing a fault code at its Fault
LED.
• To enter the contingency mode of operation, turn 115
VAC power off. When the Green LED on the variable
speed inducer drive goes out, turn 115 VAC power
back on.
• Scroll down using the down arrow at the User Interface
until you see CNTNGNCY Mode, then press the Enter
button.
•CNTNGNCY MODE and STAGE will now be
displayed. Press the Enter button.
•STAGE and OFF [OFF] will now be displayed. First or
Second heat stage must be selected. Use the or
arrows to select the stage of heat wanted and then push
the Enter button and then the button.
•DUTY CYCLE and 10% [10%] will now be displayed.
A duty cycle must now be selected from 10 to 50%. A
10% duty cycle will run the furnace for 2 minutes and
then off for 18 minutes. A 50% duty cycle will run the
furnace for 10 minutes and then be off for 10 minutes.
These duty cycles will be repeated 3 times per hour.
Use the or arrows to select a duty cycle and then
push the Enter button and then the button.
18-CD30D1-12 49
Page 50
Installer’s Guide
•Start and NO[NO] will now be displayed. With a NO/NO
question being asked, use the or arrows to select the
YES and then press the ENTER button.
•Are you Sure and NO [NO] will now be displayed. With
a NO/ NO question being asked, use the or arrows
to select the YES and then press the ENTER button.
• Turn 115VAC power off. When the Green LED on the
variable speed inducer drive goes out, turn 115 VAC
power back on.
• When the furnace is operating in the contingency mode
(stand alone operating cycle), the user interface will
display the following information. The top line will say
CNTNGNCY MODE. The bottom line will show the duty
cycle stage number STG (1 or 2) selected, and the
percent number 10-50 % selected.
• All furnace operating controls, pressure switches and
communications between the IFC and the variable speed
inducer drive and the variable speed indoor blower will
be functional during contingency mode operation of the
furnace.
• The and ENTER buttons do not function in the
contingency mode of operation.
• To exit the contingency mode of operation turn off the
115 VAC power to the furnace.
• The contingency mode will stop for any of the following
reasons:
(1) If the furnace IFC receives a signal from the
communicating comfort control. This will only happen
if the data wire "D" from the comfort control has been
reconnected to the furnace IFC terminal board terminal
"D".
(2) Power is removed from the furnace and then turned
back on.
(3) The Furnace IFC enters a RESET mode of operation.
(4) A fault is detected by the furnace IFC. Fault LED will
be flashing an Alert Code.
24V CONTINGENCY MODE
An alternative method for the contingency mode can be
used by changing the mode of operation in the Use
Interface to 24V mode and installing a conventional
24V comfort control.
To set this mode of operation:
Remove all wiring from the *CONT900 comfort control
and install a 24V comfort control. If the comfort
control requires a 24V common; connect R and B
to respective terminals. Connect a third wire to "W".
At the IFC, connect the same three wires to the
corresponding terminals. Jumper W1 to W2 at the
IFC. The stage delay between W1 and W2 can be set
by scrolling through the User Interface. It is factory
set to zero minutes but can be adjusted to 5, 10, or
15 minutes.
IFC INDUCER LEARNING ROUTINE SEQUENCE
• The furnace IFC will go through an inducer learning routine
for three pressure switches.
• The learning routine is done to determine the correct
amount of ventilation air for complete combustion.
• The inducer motor speed may be different for each
installation due to the different length and size of the
ventilation pipe, exhaust vent pipe, number of pipe
fittings used, and the type of vent cap installed.
• The inducer learning routine is repeated each time the
power to the furnace is interrupted. Once power is
restored and the furnace receives a call for heat, the
PS-1, PS-2 inducer learning routine will be initiated. The
furnace IFC will not go through a PS-3 inducer learning
routine until it receives a call for 100% (high) heat.
• To ensure the furnace heating efficiency is maintained
the furnace IFC will repeat the inducer motor learning
routine after :
150 Cycles at 40% (low) heat
100 Cycles at 65% (medium) heat
50 Cycles at 100% (high) heat
PS-1, PS-2 Inducer Learning Routine
• The furnace IFC checks pressure switches PS-1, PS-2,
and PS-3. They all have to be open before a heating
cycle can begin.
• The furnace IFC sends a digital signal to the variable
speed inducer drive to run the inducer motor at the
preset factory 65% (medium) heat RPM.
• The furnace IFC waits for the PS-1 and PS-2 pressure
switches to close. A 24 Volt AC signal is sent to the
furnace IFC when a pressure switch closes.
• If PS-1 and PS-2 do not close at the preset factory 65%
(medium) heat RPM, the furnace IFC will continue to
signal the variable speed inducer drive to increase the
inducer speed in steps until PS-1 and PS-2 close or until
the maximum RPM for 65% (medium) heat is reached.
• When PS-1 and PS-2 switches close, the furnace IFC will
then start the ignition cycle.
• The IFC now starts the igniter warm up cycle.
• Approximately 20 seconds later, the furnace IFC will turn
on the gas valve.
50 18-CD30D1-12
Page 51
Installer’s Guide
NOTE: The furnace lights at approximately 65% of
capacity.
• When the burner flame is detected by the furnace IFC, a
forty-five second time delay for indoor blower operation
begins. The forty-five second time delay allows theheat
exchanger and the recuperative cell to warm up.
• The furnace IFC will now start its 65% (medium) heat
inducer learning routine.
• The furnace IFC will signal the variable speed inducer
drive beginning to reduce the inducer motor speed in
steps until the furnace IFC detects that PS-2 is open.
• When PS-2 opens, the furnace IFC will NOTE the inducer
motor RPM.
• The furnace IFC then adds an additional number of RPM
to the 65% (medium) heat inducer motor NOTED RPM
until PS-2 closes.
• The additional number of RPM plus this NOTED RPM is
the learned 65% (medium) heat inducer operating RPM.
• The furnace IFC now stores this learned operating inducer
RPM for 65% (medium) heat in its memory.
• The furnace IFC will use this stored learned operating
inducer RPM for 65% (medium) heat calls it receives
in the future.
• If the furnace IFC is still receiving a call for low heat
operation it will now start the learning routine for 40%
(low) heat.
• The furnace IFC will then continue to reduce the inducer
motor RPM in steps until the furnace IFC detects that
PS-1 is open.
• When PS-1 opens, the furnace IFC will NOTE the inducer
motor RPM.
• The furnace IFC then adds an additional number of RPM
to the 40% (low) heat inducer motor NOTED RPM until
PS-1 closes.
• The additional number of RPM plus this NOTED RPM is
the learned 40% (low) heat inducer operating RPM.
• The furnace IFC now stores this learned inducer operating
RPM for 40% (low) heat in its memory.
• The furnace IFC will use this stored learned inducer
operating RPM for 40% (low) heat calls it receives in
the future.
• Whenever the furnace is powered up or after a RESET,
the furnace IFC will not go through a learning routine
for 100% (high) heat until it receives a call for 100%
(high) heat.
PS-3 INDUCER LEARNING ROUTINE
• When the furnace IFC receives a digital signal for 100%
(high) heat from the comfort control it will begin the
PS-3 inducer learning routine.
• The furnace will start the heating cycle in 65% (medium)
heat, if not already on, and then begins the PS-3 inducer
learning routine.
• The furnace IFC will send a digital signal to the variable
speed inducer drive to run the inducer motor at the
preset factory 100% (high) heat RPM.
• The furnace IFC waits for PS-3 pressure switch to close.
A 24 Volt AC signal is sent to the furnace IFC when the
pressure switch closes.
• If PS-3 does not close at the factory preset 100% (high)
heat RPM, the furnace IFC will continue to signal the
variable speed inducer drive to increase the inducer
speed in steps until PS-3 closes or until the maximum
RPM for 100% (high) heat is reached.
• The furnace IFC enters a time delay so that the heat
exchanger and the recuperative cell warm up to their
high heat operating temperature. At the end of this time
delay, the inducer discharge air temperature will be at
its high heat operating temperature and the density of
the products of combustion will be stabilized.
• The furnace will now signal the variable speed inducer
drive to reduce the inducer speed in steps until PS-3
opens.
• When PS-3 opens, the furnace IFC will NOTE the inducer
motor RPM.
• The furnace IFC then adds an additional number of RPM
to the 100% (high) heat inducer motor NOTED RPM
until PS-3 closes.
• The furnace IFC now stores this learned inducer
operating RPM for 100% (high) heat in its memory.
• The furnace IFC will use this stored learned inducer
operating RPM for 100% (high) heat calls it receives
in the future.
• If PS-3 is not closed when the inducer reaches its
maximum RPM, the furnace IFC will signal the variable
speed inducer drive to reduce the inducer Motor speed
in steps to its low heat LEARNED SPEED.
• The furnace IFC flashes its Red Fault LED three times
repeatedly. The furnace IFC will keep operating at low
heat for 10 minutes and then retry the PS-3 learning
routine.
18-CD30D1-12 51
Page 52
Installer’s Guide
▲
WARNING
!
▲
WARNING
!
▲
WARNING
!
▲
WARNING
!
CONTROL AND SAFETY SWITCH
ADJUSTMENTS
LIMIT SWITCH CHECK OUT
The Limit Switch is a safety device designed to close the
Gas Valve should the Furnace become overheated. Since
proper operation of this switch is important to the safe
operation of the unit, it must be checked out on initial
start up by the installer.
To check for proper operation of the Limit Switches, set
the Comfort Control to a temperature higher than the indicated room temperature to start the furnace. Restrict
the airflow by blocking the return air (disconnecting the
Indoor Blower may trip the Inducer Limit). When the Furnace reaches the maximum outlet temperature as shown
on the rating plate, the burners must shut off. If they do
not shut off after a reasonable time and overheating is
evident, a faulty Limit Switch is probable and the Limit
Switch must be replaced. After checking the operation of
the Limit Control, be sure to remove the restriction from
the return air inlet.
AIRFLOW ADJUSTMENT
Check inlet and outlet air temperatures to make sure
they are within the range specified on the Furnace rating nameplate. If the airflow needs to be increased or
decreased, see the Airflow Label on the Furnace or
the unit’s Service Facts for information on changing the
speed of the Blower Motor for your specific model. Blower
speed changes are made on the User Interface.
ELECTRICAL SHOCK HAZARD
DO NOT TOUCH ANY COMPONENTS OTHER THAN THE
DISPLAY ASSEMBLY AND THE DOOR SWITCH DURING
THIS PROCEDURE.
FAILURE TO FOLLOW WARNING COULD RESULT IN
SERIOUS PERSONAL INJURY OR DEATH.
ELECTRICAL SHOCK HAZARD
DISCONNECT POWER TO THE UNIT BEFORE REMOVING THE BLOWER DOOR. ALLOW A MINIMUM OF 10
SECONDS FOR IFC POWER SUPPLY TO DISCHARGE
TO 0 VOLTS.
FAILURE TO FOLLOW THIS WARNING COULD RESULT IN PROPERTY DAMAGE, PERSONAL INJURY OR
DEATH.
INDOOR BLOWER TIMING
Heating: The Integrated Furnace Control module con-
trols the Indoor Blower. The Blower start is
fixed at 45 seconds after ignition. The FANOFF period is field selectable via the User Interface menu at 60, 100, 140, or 180 seconds.
The factory setting is 100 seconds.
Cooling: Continuous Fan mode is 50% of the cooling
CFM. This is a selectable range on the Comfort Control menu.
When in communicating mode, see Use Interface Menu
in furnace Installer's Guide.
SAFETY HAZARD
MAKE SURE THAT THE BLOWER DOOR IS IN PLACE
AND NOT AJAR. DANGEROUS FUMES COULD ESCAPE.
FAILURE TO FOLLOW WARNING COULD RESULT IN
SERIOUS PERSONAL INJURY OR DEATH.
This unit is equipped with a Blower Door Switch which
cuts power to the Furnace causing shutdown when the
door is removed. Operation with the door removed or ajar
can permit the escape of dangerous fumes. All panels
must be securely closed at all times for safe operation of
the Furnace.
NOTE TO INSTALLER
Review the following instructions with the homeowner.
Review contents of USER’S INFORMATION MANUAL
with the homeowner.
INSTRUCTIONS TO THE HOMEOWNER
52 18-CD30D1-12
EXPLOSION HAZARD
In the event that electrical, fuel, or mechanical failures occur, shut off the gas supply off at the manual
gas valve, located on the supply gas piping coming into the furnace, before turning off the electrical
power to the furnace. Contact the service agency
designated by your dealer.
Page 53
Installer’s Guide
CONDITIONS AFFECTING FURNACE
OPERATION
NOTE:
CONTINUOUS fan mode during COOLING operation
may not be appropriate in humid climates. If the indoor air exceeds 60% relative humidity or simply feels
uncomfortably humid, it is recommended that the fan
only be used in the AUTO mode.
1. EXCESSIVE COMBUSTION PRESSURE (WIND
IN EXCESS OF 40 M.P.H.) VENT OR FLUE
BLOCKAGE
On a call for heat, the Variable Speed Draft Inducer must
first ramp up to speed and close the Pressure Switch
before the Ignition Sequence is allowed to begin. If the
Pressure Switch does not close, the Motor will ramp up
to maximum speed and continue to operate at maximum
speed for about one minute. After one minute, the Integrated Furnace Control will turn the Motor off for about 30
seconds then back on in an attempt to reestablish proper
operation. This condition is indicative of a highly restricted
or blocked inlet or outlet Vent Pipe or a failed Pressure
Switch.
If pressure against induced draft Blower outlet becomes
excessive, the Pressure Switch will open. If the Pressure
Switch is open for more than 3.5 seconds, the Variable
Speed Draft Inducer will speed up and attempt to close
the Pressure Switch.
If the Pressure Switch is not closed within 12 to 15 seconds or if the maximum speed of the Motor is reached,
the Draft Inducer sends a Fault Signal to the Integrated
Furnace Control. If the unit is operating in high heat, an
Inducer Fault will cause the Furnace control to transition
the system to medium heat and it will operate there for
10 minutes before attempting to run again in high heat.
If the unit is operating in medium heat, an Inducer Fault
will cause the Furnace control to transition the system to
low heat and it will operate there for 10 minutes before attempting to run again in medium heat. If the unit is operating in low heat, an Inducer Fault will cause the Furnace
control to shut the system down and wait 30 seconds before attempting to reestablish operation in low heat.
2. LOSS OF FLAME
If loss of flame occurs during a Heating Cycle, or flame is
not present at the sensor, the Integrated Furnace Control
(IFC) will close the Gas Valve. The Integrated Furnace
Control will then recycle the Ignition Sequence. If Ignition
is not achieved, it will shut off the Gas Valve and lock out
the system.
3. POWER FAILURE
If there is a power failure during a Heating Cycle, the
system will restart the Ignition Sequence automatically
when power is restored, if the Comfort Control still calls
for heat.
4. GAS SUPPLY FAILURE
If a gas supply failure occurs during a Heating Cycle, the
system Integrated Furnace Control will recycle the Ignition Sequence, then if Ignition is not achieved, the Integrated Furnace Control will shut off the Gas Valve and
lock out the system.
5. INDUCED DRAFT BLOWER FAILURE
Please refer to the "Communicating Controls Service
Manual," publication number 34-4093 (latest revision), for
diagnostic assistance.
6. CONDENSATE DRAIN BLOCKAGE
If the condensate drain is blocked, either by debris, improper draining, or by freezing condensate, the pressure
switch will receive a signal warning of the accumulation
of condensate in the heat exchanger assembly. The pressure switch contacts will open and remain open, not allowing unit operation. The unit will not operate until the
condensate drain has been cleared, and the condensate
flows freely.
7. RESET AFTER LOCKOUT
When the Integrated Furnace Control has shut the system down and gone into lockout, the system may be
manually reset. The system can be reset by turning the
system power off.
8. RESET AFTER BURNER BOX LIMIT SHUT- DOWN
BURNER BOX TEMPERATURE LIMIT DEVICE
All models are equipped with a Manual Reset Temperature Limit located on the Burner Box. In case of excessive
temperature, the Limit will open and cause the circuit to
open which shuts off all flow of gas. If the Furnace shuts
down check the Burner Box Temperature Limit Switch. It
is located on the bottom of the Burner Box. The Vent and
Combustion Air Inlet terminations must first be checked
for blockage. If blockage exists, clear the problem and
then the Reset Button may be depressed. If there is no
blockage of the terminations, do not reset the Burner
Box Limit Switch. A qualified service professional
should be called to determine the problem and reset
the Limit Switch.
18-CD30D1-12 53
Page 54
Installer’s Guide
ALERT CODE RECOVERY
On power up, last 4 Alerts, if any, will be flashed on the
Red Alert LED. The newest Alert detected will flash first
and the oldest last. There will be a 2 second delay between Alert Code flashes. Solid Red LED error codes will
not be displayed.
The Green BM LED will be on solid when the control is
powered. The Green status LED indicator light will operate as shown in the table and the Red LED will flash (one
flash) every 20 seconds.
NOTE:
Use the flash code menu for detail of the alerts. Alert
codes also are displayed on the User Interface menu
using a descriptive text message and on the comfort
control display using an alert code number. A complete list of the alert codes is included with the comfort
control.
Line voltage connections
Table 23
LEDDESCRIPTIONFUNCTION
FAST FLASH - CALL
GREENSTATUS LED
REDALERT LED
GREEN
(BM)
AMBERCOM
BITMASTER
FOR HEAT
SLOW FLASH - NO
CALL FOR HEAT
NO. OF FLASHES
- SEE DIAGNOSTIC
CODES
ON SOLID WHEN UNIT
POWERED
FLASHES DEVICE
COUNT
Neutral connections
"Com" LED
(Amber)
Bitmaster (BM)
LED (Green)
24V furnace component connections
Low voltage
terminal board
5 Amp control
fuse
Motor bus
connections
Motor bus
connections
User Interface
connection
Status LED
(Green)
Personality
module connection
Fault LED
(Red)
BK jumper
54 18-CD30D1-12
P
IFC BOARD
Page 55
Installer’s Guide
Furnace Fault CodesD802247P01rev08[1].xls
REVISION: 9CN: 9108T00DATE: 2009-6-12
Fault LED COM LED User Interface Display Control Display
Solid ON Device countCNTRL FAULTERR 1818Control FailureInternal control failure
NoneDevice countTWIN ERRORN/A
19
Twinning Fault
Twinning Not Allowed with Variable
Speed
PM DATA ERR
Data Section is Corrupt but PM is
useable
CAP MISMATCH
Compressor size does not match
capacity in PM
ID MTR ERR
Blower HP/OEM does not match PM
Data
PM MISSINGNo PM
PM UNIT ERRN/A
Primary Copy of Unit Data File is
Corrupt.
PM MEM ERRORERR 114
Primary and Secondary copies of Unit
Data File are Corrupt
AC VOLTS LOWVoltage too low
AC VOLTS HIVoltage too high
NoneDevice countCHECK FUSEN/A92Fuse24V Fuse Open
Y1 OFF ERRY1 Output OFF when it should be ON
Y1 ON ERRY1 Output ON when it should be OFF
TS 1 SHORTTemperature sensor 1 shorted.
TS 1 OPENTemperature sensor 1 open.
TS 2 SHORTTemperature sensor 2 shorted.
TS 2 OPENTemperature sensor 2 open.
Notes:
D342960P01
PRINTED FROM: D802247P01 Rev 9
Communication FaultERR 91
Fast Flash
91
¹ Comfort Control will switch system to "OFF" until this fault condition clears
7 Flash
Control senses 24V present at the gas
valve when it should not be present.
EXT GV ERR
NoneDevice count
Device count
NoneDevice count
2 Flash
4 Flash
6 Flash
Device count
3 FlashDevice count
Device count
ERR 101
10
90
93ERR 93
ERR 10
Alert Description
22
Alert Group
Shorted Pressure Switch, first stage
Ignition Means Fault
High Temp Limit Fault
20
Alert Notification
Alert
Code
Flame lost or Ignition
failure
N/A
Device count
1
Device count
87
Y1 Relay Failure
N/A
Communication Busy
Fault
Gas Valve Fault
AC Line Fault
Bad or Missing PM
59
N/A
HIGH LIMIT
Solid ONINT GV ERR
ERR 87
ERR 26
10 Flash
Device count
Device count
Temperature Sensor
Failure
N/A
NoneDevice countN/A
119
None114
ERR 114
101
Open High Limit - Heat exchanger
temperature too high. Could be
caused by low airflow or fan failure.
ROLLOUT OPENOpen flame rollout
Soft lockout due to
flame lost or ignition
retries
Pressure Switch
Failure
Roll Out Fault
ERR 22
N/A
PS1 CLOSED
26
TABLE 24- FURNACE
ALERT CODES
18-CD30D1-12 55
Page 56
Trane
6200 Troup Highway
Tyler, TX 75707
Literature Order Number 18-CD30D1-12
Number 18-CD30D1-12
Supersedes
Date 01/13
For more information contact
your local dealer (distributor)
The manufacturer has a policy of continuous product and product data improvement and reserves the right to
change design and specifications without notice.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.