ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES
IMPORTANT — This Document is customer property and is to remain with this unit.
Please return to service information pack upon completion of work.
NOTE:
This furnace can be configured for Communicating or 24 VAC modes. Using fully Communicating or 24 VAC
modes, the furnace can support single or multi-stage heat pump, AC, or heating only applications. Combined with
a communicating Comfort Control only, the furnace will support a single stage 24 VAC cooling outdoor unit only.
1. Safety signal words are used to designate a degree or level of seriousness associated with a particular hazard.
2. The signal words for safety markings are WARNING, and CAUTION.
3. a. WARNING indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
4. b. CAUTION indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It
is also used to alert against unsafe practices and hazards involving only property damage.
DOWNFLOW/HORIZONTAL
A341624P14
Installer’s Guide
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each
appliance connected to the venting system being
placed into operation could result in carbon monoxide
poisoning or death.
The following steps shall be followed for each appliance
connected to the venting system being placed into
operation, while all other appliances connected to the
venting system are not in operation:
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and
horizontal pitch, as required in the National Fuel Gas
Code, ANSI Z223.1/NFPA 54 or the CSA B149.1
Natural Gas and Propane Installation Code and these
instructions. Determine that there is no blockage or
restriction, leakage, corrosion and other deficiencies
which could cause an unsafe condition.
3. As far as practical, close all building doors and
windows and all doors between the space in which the
appliance(s) connected to the venting system are
located and other deficiencies which could cause an
unsafe condition.
4. Close fireplace dampers.
5. Turn on clothes dryers and any appliance not
connected to the venting system. Turn on any exhaust
fans, such as range hoods and bathroom exhausts, so
they are operating at maximum speed. Do not operate
a summer exhaust fan.
6. Follow the lighting instructions. Place the appliance
being inspected into operation. Adjust the thermostat
so appliance is operating continuously.
7. Test for spillage from draft hood equipped appliances
at the draft hood relief opening after 5 minutes of main
burner operation. Use the flame of a match or candle.
8. If improper venting is observed during any of the above
tests, the venting system must be corrected in
accordance with the National Fuel Gas Code,
ANSI Z221.1/NFPA 54 and/or CSA B149.1 Natural Gas and Propane Installation Code.
9. After it has been determined that each appliance
connected to the venting system properly vents where
when tested as outlined above, return doors, windows,
exhaust fans, fireplace dampers and any other gas-fired
burning appliance to their previous condition of use.
▲
WARNING
!
Failure to follow safety warnings exactly, could result
in a fire or explosion causing property damage,
personal injury or loss of life.
— Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any
other appliance.
— WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch;
do not use any phone in your building.
• Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s
instructions.
• If you cannot reach your gas supplier,
call the fire department.
— Installation and service must be performed by
a qualified installer, service agency or the gas
supplier.
▲
WARNING
!
The following warning complies with State of California law, Proposition 65.
Hazardous Gases!
Exposure to fuel substances or by-products of incomplete
fuel combustion is believed by the state of California to
cause cancer, birth defects, or other reproductive harm.
▲
WARNING
!
▲
WARNING
!
▲
CAUTION
!
▲
WARNING
!
▲
WARNING
!
FIRE OR EXPLOSION HAZARD
FAILURE TO FOLLOW THE SAFETY WARNINGS
EXACTLY COULD RESULT IN SERIOUS PERSONAL
INJURY, PROPERTY DAMAGE, OR DEATH.
IMPROPER SERVICING COULD RESULT IN
DANGEROUS OPERATION, SERIOUS PERSONAL
INJURY, PROPERTY DAMAGE, OR DEATH.
EXPLOSION HAZARD!
PROPANE GAS IS HEAVIER THAN AIR AND MAY
COLLECT IN ANY LOW AREAS OR CONFINED SPACES. IN ADDITION, ODORANT FADE MAY MAKE THE
GAS UNDETECTABLE EXCEPT WITH A WARNING
DEVICE. IF THE GAS FURNACE IS INSTALLED IN A
BASEMENT, AN EXCAVATED AREA OR A CONFINED
SPACE, IT IS STRONGLY RECOMMENDED TO CONTACT A GAS SUPPLIER TO INSTALL A GAS DETECTING WARNING DEVICE IN CASE OF A GAS LEAK.
NOTE: The manufacturer of your furnace does NOT test
any detectors and makes no representations regarding
any brand or type of detector.
SAFETY HAZARD
THIS INFORMATION IS INTENDED FOR USE BY INDIVIDUALS POSSESSING ADEQUATE BACKGROUNDS
OF ELECTRICAL AND MECHANICAL EXPERIENCE.
ANY ATTEMPT TO REPAIR A CENTRAL AIR CONDITIONING PRODUCT MAY RESULT IN PERSONAL
INJURY AND OR PROPERTY DAMAGE. THE MANUFACTURER OR SELLER CANNOT BE RESPONSIBLE
FOR THE INTERPRETATION OF THIS INFORMATION,
NOR CAN IT ASSUME ANY LIABILITY IN CONNECTION WITH ITS USE.
Sharp Edge Hazard. Be careful of sharp edges on
equipment or any cuts made on sheet metal while
installing or servicing. Personal injury may result.
▲
CAUTION
!
▲
WARNING
!
▲
WARNING
!
▲
CAUTION
!
▲
WARNING
!
EXPLOSION HAZARD!
NEVER USE AN OPEN FLAME TO DETECT GAS
LEAKS. EXPLOSIVE CONDITIONS MAY OCCUR. USE
A LEAK TEST SOLUTION OR OTHER APPROVED
METHODS FOR LEAK TESTING. FAILURE TO FOLLOW THIS WARNING COULD RESULT IN PROPERTY
DAMAGE, PERSONAL INJURY OR DEATH.
To prevent shortening its service life, the Furnace
should NOT be used as a “Construction Heater”
during the finishing phases of construction until the
requirements listed in item 9, a-h of the safety section of this publication have been met. Condensate
in the presence of chlorides and fluorides from paint,
varnish, stains, adhesives, cleaning compounds, and
cement create a corrosive condition which may cause
rapid deterioration of the heat exchanger
.
SAFETY HAZARD
DO NOT USE SEMI-RIGID METALLIC GAS
CONNECTORS (flexible GAS lines) within the Furnace
cabinet. Failure to follow this warning could result in
property damage, personal injury or death.
Do NOT install the furnace in a corrosive or
contaminated atmosphere. Failure to follow this
caution could result in early equipment failure.
NOTE: The furnace must be installed level. The only
allowable variation would be slightly to the left and/
or forward in upflow installations or slightly toward
the front in horizontal installations. This is necessary
for proper condensate drainage.
3. Provide adequate combustion and ventilation air to the
Furnace space as specified in “Air for Combustion
SAFETY HAZARD
DO NOT INSTALL THE FURNACE DIRECTLY ON
CARPETING, TILE OR OTHER COMBUSTIBLE MATERIAL OTHER THAN WOOD FLOORING. FOR VERTICAL DOWNFLOW APPLICATIONS, SUBBASE (BAYBASE205) MUST BE USED BETWEEN THE FURNACE
AND COMBUSTIBLE FLOORING. WHEN THE DOWNFLOW FURNACE IS INSTALLED VERTICALLY WITH A
CASED COIL, A SUBBASE IS NOT REQUIRED. FAILURE TO FOLLOW THE WARNING EXACTLY COULD
RESULT IN SERIOUS PERSONAL INJURY, PROPERTY
DAMAGE OR DEATH.
The following safety practices and precautions must be
followed during the installation, servicing, and operation
of this furnace.
1. Use only with the type of gas approved for this
Furnace. Refer to the furnace rating plate.
2. Install this furnace only in a location and position as
specified in “Location and Clearances” on page 6 of
these instructions.
18-CD30D1-12 3
and Ventilation” of these instructions.
4. Combustion products must be discharged outdoors.
Connect this furnace to an approved vent system
only, as specified in the “Venting” section (pages 15-
27), of these instructions.
5. Never test for gas leaks with an open flame. Use
a commercially available soap solution made
specifically for the detection of leaks to check all
connections, as specified in the “Gas Piping” section
starting on page 34.
6. Always install the furnace to operate within the
furnace’s intended temperature-rise range with a duct
system which has an external static pressure within
the allowable range, as specified on the unit rating
plate. Airflow with temperature rise for cfm versus
static is shown in the Service Facts accompanying
this Furnace.
continued on page 6
Installer’s Guide
(ALL DIMENSIONS ARE IN INCHES)
*UHM-ACV OUTLINE DRAWING
DIM "A" DIM "B" DIM "C" DIM "D" DIM "E" DIM "F"
MODEL
(SEE NOTE 1)
17-1/2"2-1/4"16-1/4"16"7-1/2"2"
*UHMB060ACV3VB
*UHMB080ACV3VB
NOTES:
1. DIAMETER OF VENT PIPE MAY BE LIMITED
TO 2-1/2" OR 3" ON SOME MODELS AT DIFFERENT
ALTITUDES. REFER TO THE VENT LENGTH TABLE
FOR PROPER APPLICATION.
*UHMC100ACV4VB21"2-1/2"19-3/4"19-1/2"9"3"
*UHMD120ACV5VB24-1/2" 2-15/16" 23-1/4"23"10"3"
4 18-CD30D1-12
Installer’s Guide
(ALL DIMENSIONS ARE IN INCHES)
*DHM-ACV DOWNFLOW/ HORIZONTAL OUTLINE DRAWING
17-1/2"2-1/4"16-1/4"16"
DIM "A"DIM "B"DIM "C"DIM "D"
MODEL
(SEE NOTE 1)
*DHMB080ACV3VB
*DHMB060BCV3VB
*DHMC100ACV4VB21"2-1/2"19-3/4"19-1/2"
*DHMD120BCV5VB24-1/2"2-15/16"23-1/4"23"
18-CD30D1-12 5
Installer’s Guide
7. When a furnace is installed so that supply ducts carry
air circulated by the furnace to areas outside the
space containing the furnace, the return air shall also
be handled by a duct(s) sealed to the furnace casing
and terminating outside the space containing the
furnace.
8. A gas-fired furnace for installation in a residential
garage must be installed as specified in “Location
and Clearances” section of these instructions.
9. The furnace may be used for temporary heating of
buildings or structures under construction only when
the following conditions have been met:
a. The furnace venting system must be complete
and installed per manufacturers instructions.
b. The furnace is controlled only by a room Comfort
Control (no field jumpers).
c. The furnace return air duct must be complete
and sealed to the furnace.
d. The furnace input rate and temperature rise must
be verified to be within nameplate marking.
e. 100% of the furnace combustion air requirement
must come from outside the structure.
f. The Furnace return air temperature range is
between 550 and 800 Fahrenheit.
g. Clean the Furnace, duct work, and components
upon substantial completion of the construction
process, and verify Furnace operating condition
including ignition, input rate, temperature rise and
venting, according to the manufacturer's instructions.
h. An external field supplied air filter must be used
during construction.
10. This product must be gas piped by a
Licensed Plumber or Gas Fitter in the
Commonwealth of Massachusetts.
LOCATION AND CLEARANCES
The location of the furnace is normally selected by the
architect, the builder, or the installer. However, before
the furnace is moved into place, be sure to consider the
following requirements:
1. Is the location selected as near the chimney or vent
and as centralized for heat distribution as practical?
2. Do all clearances between the furnace and enclosure
equal or exceed the minimums stated in Clearance
Table on the Outline Drawings provided in this
document?
3. Is there sufficient space for servicing the furnace and
other equipment? A minimum of 24 inches front
accessibility to the furnace must be provided. Any
access door or panel must permit removal of the
largest component.
4. Are there at least 3 inches of clearance between the
furnace combustion air openings in the front panel
and any closed panel or door provided?
5. Are the ventilation and combustion air openings large
enough and will they remain unobstructed? If outside
air is used, are the openings at least 12" above the
highest expected snow accumulation level (18"
minimum for Canadian applications)?
6. Allow sufficient height in supply plenum above the
furnace to provide for cooling coil installation, if the
cooling coil is not installed at the time of this furnace
installation.
7. A furnace shall be installed so electrical components
are protected from water.
8. If the furnace is installed in a residential garage, it
must be installed so that the burners, and the ignition
source are located not less than 18 inches above the
floor and the furnace must be located or protected to
avoid physical damage from vehicles.
GENERAL INSTALLATION
INSTRUCTIONS
The manufacturer assumes no responsibility for
equipment installed in violation of any code or regulation.
It is recommended that Manual J of the Air Conditioning
Contractors Association (ACCA) or A.R.I. 230 be followed
in estimating heating requirements. When estimating
heating requirements for installation at Altitudes above
2000 ft., remember the gas input must be reduced (See
GAS INPUT ADJUSTMENT).
Material in this shipment has been inspected at the
factory and released to the transportation agency
without known damage. Inspect exterior of carton
for evidence of rough handling in shipment. Unpack
carefully after moving equipment to approximate
location. If damage to contents is found, report the
damage immediately to the delivering agency.
Codes and local utility requirements governing the
installation of gas fired equipment, wiring, plumbing,
and flue connections must be adhered to. In the
absence of local codes, the installation must conform
with latest edition of the National Fuel Gas Code ANSI
Z223.1 • National Installation Code, CAN/CGA B149.1.
The latest code may be obtained from the American
Gas Association Laboratories, 400 N. Capitol St. NW,
Washington D.C. 20001.
1-800-699-9277 or www.aga.org
These furnaces have been classified as CATEGORY IV
furnaces in accordance with latest edition of ANSI Z21.47
standards • CAN/CGA 2.3. Category IV furnaces operate
with positive vent static pressure and with a flue loss less
than 17 percent. These conditions require special venting
systems, which must be gas tight and water tight. These
Category IV Direct Vent furnaces are not approved for
installation in Manufactured/Mobile housing.
6 18-CD30D1-12
▲
WARNING
!
SAFETY HAZARD
UPFLOW
FURNACE
CASED
COIL
SCREWS
(BOTH SIDES)
STANDOFFS
(BOTH SIDES)
STANDOFFS (4)
DRILL SCREWS (4)
DO NOT INSTALL THE FURNACE DIRECTLY ON
CARPETING, TILE OR OTHER COMBUSTIBLE
MATERIAL OTHER THAN WOOD FLOORING. FOR
VERTICAL DOWNFLOW APPLICATIONS, SUBBASE
(BAYBASE205) MUST BE USED BETWEEN THE
FURNACE AND COMBUSTIBLE FLOORING. WHEN THE
DOWNFLOW FURNACE IS INSTALLED VERTICALLY
WITH A CASED COIL, A SUBBASE IS NOT REQUIRED.
FAILURE TO FOLLOW THE WARNING EXACTLY COULD
RESULT IN SERIOUS PERSONAL INJURY, PROPERTY
DAMAGE OR DEATH.
UPFLOW INSTALLATION
Standoffs and screws (See Figure 1) are included with
the cased coils for attachment to the furnace. There are
clearance alignment holes near the bottom of the coil
wrapper. Drill screws are used to engage the furnace
top flanges. The standoff is inserted into the cabinet
alignment hole. The drill screws are inserted through the
standoffs then screwed into the furnace flange. The coil is
always placed downstream of the furnace airflow.
1
FOR VERTICAL
INSTALLATIONS:
Installer’s Guide
DOWNFLOW INSTALLATIONS
REQUIRED FLOOR OPENING: (DOWNFLOW)
SEE FIGURE 2 AND FIGURE 3, AND TABLE 1
HORIZONTAL INSTALLATION
IMPORTANT:
The 2/4TXC cased coil must be placed downstream of the
furnace. In horizontal installations, the apex of the coil
may point either toward or away from the furnace. See the
2/4TXC coil Installer's Guide for more details.
The coil and furnace must be fully supported when used
in the horizontal position. It is always recommended that
an auxiliary drain pan be installed under a horizontally
installed evaporator coil or 90% or greater Gas Furnace.
Connect the auxiliary drain line to a separate drain line
(no trap is needed in this line).
Three brackets (with screws) are included with downflow
furnaces for installation to stabilize and secure the
furnace and TXC cased coil in the horizontal position.
See Figure 4. The coil is placed downstream of the
furnace, with the apex of the coil pointing in either
direction of the airflow for horizontal installation. The
cased coil is secured to the furnace and both the furnace
and the cased coil must be properly supported.
CASED COIL CONNECTION
4
BRACKET FOR DOWNFLOW
FURNACE IN HORIZONTAL
DOWNFLOW ONLY
2
3
A (width)
FURNACE
FRONT
TABLE 1
CABINET
WIDTH
17-1/2"16-1/4"16-5/8"20-1/8"15-5/8"19-3/8"
21"19-3/4"20-1/8"20-1/8"19-1/8"19-3/8"
24-1/2"23-1/4"23-5/8"20-1/8"22-5/8"19-3/8"
RETURN
DUCT WIDTH
FLOOR OPENING PLENUM OPENING
B (depth)
"A""B"
D
C
"C""D"
The brackets mount using the rear screws on the coil
case and use the screws provided to secure the bracket
to the furnace. The remaining bracket is placed as close
to center as possible (horizontally) between the coil case
front and the furnace bottom channel (for downflow/
horizontal furnace). Use four of the screws provided to
secure the bracket. The coil requires additional support.
The furnace may be installed in an attic or crawl space
in the horizontal position by placing the furnace on the left side (as viewed from the front in the vertical position).
The horizontal furnace installation in an attic should be
on a service platform large enough to allow for proper
clearances on all sides and service access to the front
of the furnace (See Figure 5 & Clearance Tables, on
the Outline drawings on pages 4-5). Line contact is only
permissible between lines formed by intersections of
the top and two sides of the furnace casing and building
joists, studs, or framing.
The furnace may be placed horizontally in a crawl space
on a pad or other noncombustible material which will
raise the unit for sufficient protection from moisture.
18-CD30D1-12 7
Installer’s Guide
5
UPFLOW/
HORIZONTAL
SHOWN WITH
DIRECT VENT
The furnace must be supported at both ends and the
middle when installed horizontally. The furnace must
also be elevated approximately 4-6 inches to allow
clearance for the condensate drain to exit the cabinet
in the horizontal position.
The horizontal furnace may also be suspended from
the joists using all-thread rods with a substantial metal
support frame that supports the entire length of the
furnace. The rods need to be of sufficient length to
allow for proper clearances from combustible materials.
The frame needs to be at least 32" in length to allow for
access to service panels.
If the furnace is suspended using steel strap, it must be
supported at all four corners and in the middle at the front
of the furnace.
AIR FOR COMBUSTION AND VENTILATION
If these furnaces are installed in a nondirect vent capacity
then the adequate flow of combustion and ventilating
air must not be obstructed from reaching the furnace.
Air open ings provided for combustion air must be kept
free of obstructions which restrict the flow of air. Airflow
restrictions affect the efficiency and safe operation
of the furnace. Keep this in mind should you choose
to remodel or change the area which contains your
furnace. Furnaces must have a free flow of air for proper
performance.
Provisions for combustion and ventilation air shall be
made in accordance with latest edition of Section 5.3, Air
for Combustion and Ventilation, of the National Fuel Gas
Code, ANSI Z223.1 — CAN/CGA B149.1 or applicable
provisions of the local building codes. Special conditions
created by mechanical exhausting of air and fireplaces
must be con sidered to avoid unsatisfactory furnace
operation.
6
50 CU. FT. OR MORE
PER 1000 BTU/HR. INPUT
ALL EQUIP. INSTALLED
OUTSIDE AIR IS RECOMMENDED
The use of indoor air for most applications is acceptable,
unless there is the presence of corrosive chemicals or
contamination. Certain types of installation will require
the use of outside air for combustion.
The following types of installations will require use
of OUTDOOR AIR for combustion, due to chemical
exposures:
1. * Commercial buildings
2. * Buildings with indoor pools
3. * Furnaces installed in “confined” laundry rooms
4. * Furnaces installed in “confined” hobby or craft rooms
5. * Furnaces installed near chemical storage areas.
Exposure to the following substances in the combustion
air supply will also require OUTDOOR AIR for
combustion:
1. * Permanent wave solutions
2. * Chlorinated waxes and cleaners
3. * Chlorine based swimming pool chemicals
4. * Water softening chemicals
5. * Deicing salts or chemicals
6. * Carbon Tetrachloride
7. * Halogen type refrigerants
8. * Cleaning solvents (such as perchloroethylene)
9. * Printing inks, paint removers, varnish, etc.
10. * Hydrochloric acid
11. * Cements and glues
12. * Antistatic fabric softeners for clothes dryers
13. * Masonry acid washing materials
Furnace locations may be in a “confined space” or an
“unconfined space”.
Unconfined space is defined in Figure 6. These spaces
may have adequate air by infiltration to provide air
for combustion and ventilation. Buildings with tight
construction (for example, weather stripping, heavily
insulated, caulked, vapor barrier, etc.), may need
additional air to be provided as described for confined space. See Table 2 for minimum area.
TABLE 2
MINIMUM AREA IN SQUARE FEET
FOR UNCONFINED SPACE INSTALLATIONS
FURNACE MAXI-
MUM BTUH INPUT
RATING
60,000
80,000
100,000
120,000
WITH 8 FT. CEILING
MINIMUM AREA IN SQUARE FEET
OF UNCONFINED SPACE
375
500
625
875
UNCONFINED
8 18-CD30D1-12
Installer’s Guide
7
CONFINED
SPACE
Confined spaces are installations with less than 50 cu.
ft. of space per 1000 BTU/hr input from all equipment
installed. Air for combustion and ventilation requirements
can be supplied from inside the building as in Figure 8 or
from the outdoors, as in Figure 9.
1. All air from inside the building as in Figure 8: The
confined space shall be provided with two permanent
openings communicating directly with an additional
room(s) of sufficient volume so that the combined
volume of all spaces meets the criteria for an
unconfined space. The total input of all gas utilization
equipment installed in the combined space shall be
considered in making this determination. Refer to
Table 3 for minimum open areas requirements.
2. All air from outdoors as in Figure 9: The confined
space shall be provided with two permanent
openings, one commencing within 12 inches of
the top and one commencing within 12 inches of
the bottom of the enclosure. The openings shall
communicate directly, or by ducts, with the outdoors
or spaces (crawl or attic) that freely communicate
with the outdoors. Refer to Table 3, for minimum open
areas requirements.
TABLE 3
MINIMUM FREE AREA IN SQUARE INCHES
EACH OPENING (FURNACE ONLY)
8
9
Furnace
Maximum
BTUH/INPUT
Rating
60,000
80,000
100,000
120,000
Air
From
Inside
100
100
100
120
Vertical
Duct
DUCT CONNECTIONS
Air duct systems should be installed in accordance with
standards for air conditioning systems, National Fire
Protection Association Pamphlet No. 90. They should be
sized in accordance with ACCA Manual D or whichever is
applicable.
Central furnaces, when used in connection with cooling
units, shall be installed in parallel or on the upstream
side of the cooling coil to avoid condensation in the heat
exchanger.
18-CD30D1-12 9
Air From Outside
Horizontal
15
20
25
30
Duct
30
40
50
60
Installer’s Guide
▲
CAUTION
!
With a parallel flow arrangement, the dampers or other
means used to control flow of air shall be adequate to
prevent chilled air from entering the Furnace, and if
manually operated, must be equipped with means to
prevent operation of either unit unless the damper is in
full heat or cool position.
On any job, flexible connections of nonflammable material
may be used for return air and discharge connections to
prevent transmission of vibration. Though these units
have been specifically designed for quiet, vibration free
operation, air ducts can act as sounding boards and could,
if poorly installed, amplify the slightest vibration to the
annoyance level.
When the furnace is located in a utility room adjacent to
the living area, the system should be carefully designed
with returns to minimize noise transmission through the
return air grille. Although these furnaces are designed
with large blowers operating at moderate speeds, any
blower moving a high volume of air will produce audible
noise which could be objectionable when the unit is
located very close to a living area. It is often advisable
to route the return air ducts under the floor or through
the attic. Such design permits the installation of air return
remote from the living area (i.e. central hall).
When the furnace is installed so that the supply ducts
carry air circulated by the furnace to areas outside
the space containing the furnace, the return air shall
also be handled by a duct(s) sealed to the furnace and
terminating outside the space containing the furnace.
RETURN AIR DUCT SYSTEMS
Safety Hazard
Sharp Edge Hazard
Be careful of sharp edges on equipment or any cuts
made on sheet metal while installing or servicing.
Personal injury may result.
Where there is no complete return duct system,
the return connection must be run full size from
the furnace to a location outside the utility room,
basement, attic, or crawl space.
Do NOT install return air through the back of the furnace
cabinet.
Do NOT install return air through the side of the furnace
cabinet on horizontal applications.
NOTE:
Minimum return air temperature is 55°F.
PREPARATION FOR UPFLOW BOTTOM AND SIDE
RETURN AIR FILTER INSTALLATION
All return air duct systems should provide for installation
of return air filters.
1. Determine the appropriate position to set the furnace
in order to connect to existing supply and return
ductwork.
2. The return air filter is shipped in either the bottom or
side location. Remove the filter by first turning the
two latches on the blower door and tilting the door
forward to remove. Remove the filter by sliding it out.
3. For upflow side return installations, remove the
insulation around the opening in the blower
compartment.
4. The side panels of the upflow furnace include
locating notches that are used as guides for cutting
an opening for return air, refer to Figure 10 and
the outline drawing on page 4 for duct connection
dimensions for various furnaces.
UPFLOW FURNACE ONLY
0
LOCATING NOTCHES PROVIDED FOR
SIDE RETURN
CUTOUT
*SEE OUTLINE DRAWING
5. If a 3/4" flange is to be used for attaching the air inlet
duct, add to cut where indicated by dotted lines in
Figure 10. Cut corners diagonally and bend outward
to form flange.
6. If flanges are not required, and a filter frame is
installed, cut between locating notches (See Figure
10).
7. The bottom panel of the upflow furnace must be
removed for bottom return air. After removing the
filter, lay the furnace on its back. Remove the two
5/16" hex screws securing the front of the bottom
channel to the cabinet.
CUT OUT FOR
SIDE FILTER
FRONT
of Furnace
10 18-CD30D1-12
Rotate the channel downward (or remove by lowering
VIEW
ENGAGEMENT
HOLE DETAIL
(Typical both sides
and blower deck)
Blower Deck
Engagement
Hole
the front edge of the channel and pulling forward).
Slide the bottom return air panel out of the cabinet.
Rotate the front channel to its original position and
reinstall the two 5/16” screws.
8. The horizontal installation of the upflow furnace
requires an external filter section. Do NOT use
the bottom return filter within the furnace. Filter
kits are available for horizontal applications.
9. Connect duct work to furnace. See Outline Drawing for
supply and return duct size and location. Flexible duct
con nectors are recommended to connect both supply
and return air ducts to the furnace. If only the front
of the furnace is accessible, it is recommended that
both supply and return air plenums are removable.
RETURN AIR FILTERS
TYPICAL UPFLOW RETURN AIR FILTER
INSTALLATIONS
Filters are factory supplied for these furnaces. These
furnaces require high velocity type air filters. The filters
may be installed within the furnace blower compartment
for UPFLOW furnaces in either a BOTTOM or SIDE (left
side or right side) return air inlet. Some filters may need
to be trimmed for side or bottom filter use.
TABLE 4
MODELS
NUMBERS
*UHMB060BCV3VB
*UHMB080ACV3VB
*UHMC100ACV4VB21"1 - 20" X 25" X 1"
*UHMD120BCV5VB24-1/2"1 - 24" X 25" X 1"
* First letter may be "A" or "T"
CABINET
WIDTH
17-1/2"1 - 17" X 25" X 1"
FILTER
QTY & SIZE
Installer’s Guide
q
Airflow
BOTTOM FILTER RACK INSTALLATION
w
FILTER RACK ASSEMBLY
NOTE: For upflow 5 ton airflow models where the
airflow requirement exceeds 1800 CFM - Models
will require return air openings and filters on:
(1) both sides, or (2) one side and the bottom, or
(3) just the bottom. The filter rack installation is
not allowed for right side return on the following
models: *UHMB060ACV3V, *UHMB080ACV3V &
*UHMC100ACV4V.
The furnace and the bottom filter rack, BAYRACK960,
installation can be seen in Figure 11. The furnace filter
in the bottom or side configuration can be removed by
simply turning the two latches on the blower door and
tilting the door forward.
The Filter rails are spring loaded for automatic
adjustment to allow standard size, locally obtainable
replacement filters. The filter rack itself slides to adjust to
the required width needed for bottom or side return (See
Figure 12).
18-CD30D1-12 11
e
Installer’s Guide
Bottom Panel
Filter
Rack
Furnace
Cabinet
Side
Filter Rack
Retaining
Screw/Pin
Engagement Hole
For
Bottom Return
Filter Rack
Installation With
RETAINING
PIN
(Both Sides)
SPRINGS
SIDE
CUTOUT
FILTER
RACK
RAILS
BOTTOM
PANEL
INSTALLED
Airflow
RETAINING
PIN
(Both Sides)
SPRINGS
SIDE
CUTOUT
FILTER
RACK
RAILS
BOTTOM
PANEL
INSTALLED
Airflow
Filter
Rack
Furnace
Cabinet
Side
Filter Rac
k
Retaining
Screw/Pin
Engagement Hole
For
Bottom Return
Filter Rack
Installation With
ALTERNATE FILTER RACK INSTALLATION FOR
BOTTOM RETURN - BAYRACK960
The following checklist should be used when installing a
bottom return filter on an upflow furnace:
a. Remove the filter.
b. Remove the bottom panel.
c. With the filter removed, the filter rack is
compressed and then inserted into the bottom
of the furnace. The retaining screw/pin on each
side inserts into engagement holes at the bottom
of the furnace cabinet side. See Figure 14.
d. Reinstall the furnace filter in the bottom position
by inserting the chamfer end first into the filter
rack. See Figure 19.
ALTERNATE FILTER RACK INSTALLATION FOR SIDE
RETURN AIR ON UPFLOW FURNACES (LEFT OR
RIGHT) - BAYRACK960
NOTE:
The filter rack installation is not allowed for right side
return on the following models: *UHMB060ACV3V,
*UHMB080ACV3V & *UHMC100ACV4V. See Figure 21
for alternate upflow filter clip/ bracket installation.
The following checklist should be used when installing a
right or left side return filter on an upflow furnace:
a. Remove the filter.
b. Leave the bottom panel in place.
c. Make side cutout by following the directions in the
“Return Air Duct Connections” section on page 10,
d. Compress the filter rack and reinstall in the side
position on the furnace. Confirm that the upper
retaining pin/screw locks into the engagement hole in
the blower deck and the lower pin/screw rests against
the side of the bottom panel. See Figures 13, 15-18.
e. Reinstall the furnace filter in the side position by
inserting the chamfer end first into the filter rack.
t
BOTTOM ENGAGEMENT
y
Typical Upflow Left Side Return Filter Rack Installation
u
r
12 18-CD30D1-12
SIDE ENGAGEMENT
Typical Upflow Right Side Return Filter Rack Installation
i
Filter
Rack
Assembly
Furnace
Blower
Deck
Filter Rack
Retaining
Screw/Pin
Engagement Hole
For
Return
Filter Rack
Installation With
Side
Furnace
Cabinet
Side
CHAMFER
END OF
FILTER GOES
INTO FILTER
RACK FIRST
SIDE
CUT-OUT
ALTERNATE SIDE
FILTER CLIPS
LOCATIONS
ALTERNATE BOTTOM
FILTER CLIPS LOCATIONS
BLOWER
DECK
o
Airflow
Installer’s Guide
RETURN AIR FILTERS FOR UPFLOW FURNACE IN
HORIZONTAL CONFIGURATION
When the upflow furnace is installed in the horizontal
configuration, the return air filters must be installed
exterior to the furnace cabinet. Remote filter grilles may
be used for homeowner convenience or the filters may be
installed in the duct work upstream of the furnace. See
Figure 20. Conversion kits for horizontal filter installation
are shown in Table 4A.
Conversion kits for horizontal filters are BAYFLTR203
for 17 1/2" width cabinets, BAYFLTR204 for 21" width
cabinets, and BAYFLTR205 for 24" width cabinets. These
include filters and brackets necessary for horizontal
filters. See Figure 20.
UPFLOW FILTER CLIP/ BRACKET INSTALLATION
1. Determine the location to be used. The furnace
cabinet has dimples for location of the alternate
furnace clips (Side return only). Pre-drill clearance
holes with a 3/16" drill. Bottom return holes are predrilled. Attach clip to bottom channel and rear of unit
with screws provided for bottom return.
2. Install the clips in front and rear of the desired location
using the screws provided. The filter clip with the leaf
spring mounts in the rear of the cabinet. See Figure
21.
p
Accessory filter kit BAYFLTR203, 204, or 205 used
for Upflow Horizontal
furnaces.
Typical Horizontal Filter Installation
Table 4A CONVERSION KITS FOR
HORIZONTAL FILTERS
MODEL NUMBERS
*UHMB060ACV3VB
*UHMB080ACV3VB
*UHMC100ACV4VB
*UHMD120ACV5VB
1. *First letter may be "A" or "T"
2. Kit includes Filters and Brackets necessary for Horizontal Filters.
18-CD30D1-12 13
CABINET
WIDTH
17-1/2"BAYFLTR203
21"BAYFLTR204
24-1/2"BAYFLTR205
Airflow
a
CONVERSION
KIT NUMBER
Installer’s Guide
INSTALLING THE FILTER
The filter may need to be cut to fit the unit depending on
the location of the return air filter.
A score line and the words “CUT HERE” are located
on the end of the filter. If your application requires
cutting the filter, do so as indicted by the score mark.
UNIT
SIZE
TABLE 5
RETURN AIR
BOTTOMSIDE
17-1/2"DO NOT CUTDO NOT CUT
21"DO NOT CUT CUT ON LINE
24-1/2"DO NOT CUT CUT ON LINE
TYPICAL DOWNFLOW FURNACE RETURN AIR
FILTER INSTALLATIONS
Two filters are factory supplied for each downflow
furnace. These furnaces require high velocity type air
filters.
Downflow furnace filters must be located outside the
furnace cabinet. Typical installations are shown in Figure
22. Tables 6 and 7 provide information for installation
of the filter retaining brackets shipped with downflow
furnaces.
TABLE 6
MODELS
NUMBERS
*DHMB060BCV3VB
*DHMB080ACV3VB
*DHMC100ACV4VB21"2 - 16" X 20" X 1"
*DHMD120BCV5VB24-1/2"2 - 16" X 20" X 1"
*First letter may be "A" or "T"
LOCATING FILTER RETAINER BRACKETS IN DUCTWORK
CABINET
WIDTH
17-1/2"16-1/4"15"14"14-3/8"
21"19-3/4"19-1/2"14"13-1/8"
24-1/2"23-1/4"22"14"13-5/8"
* LOCATION DIMENSION IS FROM END OF DUCT AGAINST THE FURNACE TO THE
SCREW HOLES FOR THE BRACKET.
RETURN
DUCT
WIDTH
CABINET
WIDTH
17-1/2"2 - 14" X 20" X 1"
TABLE 7
DIMENSION
"A"
DIMENSION
FILTER
QTY & SIZE
"B"
FILTER
BRACKET
LOCATION*
DOWNFLOW
s
Airflow
TABLE 8
MINIMUM CLEARANCE FROM COMBUSTIBLE MATERIALS FOR
UPFLOW/HORIZONTAL AND DOWNFLOW/ HORIZONTAL FURNACES
FURNACE SURFACE
SIDES0"1"0"
BACK0"3"6"
TOP1"1"1"
FRONT3"3"18"
VENT0"0"0"
NOTE: CLEARANCE REQUIRED AT TOP OF PLENUM IS 1"
VERTICAL
CLOSET
DOWNFLOW/
HORIZONTAL
Airflow
UNIT LOCATION
HORIZONTAL
CLOSET
HORIZONTAL
ALCOVE / ATTIC
14 18-CD30D1-12
GENERAL VENTING INFORMATION
▲
WARNING
!
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each
appliance connected to the venting system being
placed into operation could result in carbon monoxide
poisoning or death.
The following steps shall be followed for each appliance
connected to the venting system being placed into
operation, while all other appliances connected to the
venting system are not in operation:
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and
horizontal pitch, as required in the National Fuel Gas
Code, ANSI Z223.1/NFPA 54 or the CSA B149.1
Natural Gas and Propane Installation Code and these
instructions. Determine that there is no blockage or
restriction, leakage, corrosion and other deficiencies
which could cause an unsafe condition.
3. As far as practical, close all building doors and
windows and all doors between the space in which the
appliance(s) connected to the venting system are
located and other deficiencies which could cause an
unsafe condition.
4. Close fireplace dampers.
5. Turn on clothes dryers and any appliance not
connected to the venting system. Turn on any exhaust
fans, such as range hoods and bathroom exhausts, so
they are operating at maximum speed. Do not operate
a summer exhaust fan.
6. Follow the lighting instructions. Place the appliance
being inspected into operation. Adjust the thermostat
so appliance is operating continuously.
7. Test for spillage from draft hood equipped appliances
at the draft hood relief opening after 5 minutes of main
burner operation. Use the flame of a match or candle.
8. If improper venting is observed during any of the above
tests, the venting system must be corrected in
accordance with the National Fuel Gas Code,
ANSI Z221.1/NFPA 54 and/or CSA B149.1 Natural Gas and Propane Installation Code.
9. After it has been determined that each appliance
connected to the venting system properly vents where
when tested as outlined above, return doors, windows,
exhaust fans, fireplace dampers and any other gas-fired
burning appliance to their previous condition of use.
▲
WARNING
!
FACTORY SUPPLIED
ONLY WITH THE
FOLLOWING MODELS:
ALL 100,000 BTUH
UPFLOW MODELS, ALL
120,000 BTUH UPFLOW
MODELS, AND ALL
DOWNFLOW MODELS
#CPL00938
LABEL
SAYS
"TOP"
STRAIGHT SIDE MUST BE
ON BOTTOM FOR PROPER
CONDENSATE DRAINAGE.
WHEN THE FACTORY SUPPLIED "OFF-SET" (2X3
REDUCING COUPLING) IS USED FOR 3" VENT PIPE
INSTALLATION, MAKE SURE THE MARKING "TOP" IS
LOCATED ON THE TOP SIDE OF THE PIPE.
THIS FURNACE MUST BE VENTED TO THE
OUTDOORS. THESE FURNACES ARE INDUCED
DRAFT VENTED AND MUST NOT BE CONNECTED TO
ANY VENT SERVING ANOTHER APPLIANCE. PLEASE
NOTE THAT THESE FURNACES USE POSITIVE-
PRESSURE VENT SYSTEMS.
CARBON MONOXIDE HAZARD
FURNACE MUST BE VENTED PROPERLY.
FAILURE TO FOLLOW THIS WARNING COULD
RESULT IN CARBON MONOXIDE, FIRE OR SMOKE
THAT CAN CAUSE SERIOUS BODILY INJURY, DEATH
OR PROPERTY DAMAGE.
IMPORTANT:
The building owner/maintenance provider must keep
the area around the vent clear from snow.
Proper venting is essential to obtain maximum efficiency
from a condensing furnace. Proper installation of the
vent system is necessary to assure drainage of the
condensate and prevent deterioration of the vent system.
American Gas Association has certified the design of
condensing Furnaces for a minimum of 0" clearance from
combustible materials with a single wall plastic vent pipe.
See Table 8.
The recommended system is assembled from 2", 2-1/2",
or 3" plastic pipe and fittings (See Table 9, page 18) for
material specifications. Where the system is routed
to the outdoors through an existing masonry chimney
containing flue products from another gas appliance, or
where required by local codes, then 3" venting of Type
29-4C stainless steel must be used in place of PVC
material.
These furnaces have been classified as CATEGORY IV
Furnaces in accordance with ANSI Z21.47 “latest edition”
standards. Category IV Furnaces operate with positive
vent pressure and with a vent gas temperature less than
140°F. above the dewpoint. These conditions require
special venting systems, which must be gas and water
tight.
NOTE: When an existing furnace is removed from a
venting system serving other gas appliances, the
venting system is likely to be too large to properly vent
the remaining attached appliances.
The following steps shall be followed with each appliance
remaining connected to the common venting system
placed in operation, while the other appliances remaining
connected to the common venting system are not in
operation.
18-CD30D1-12 15
Installer’s Guide
d
Installer’s Guide
▲
WARNING
!
▲
WARNING
!
Furnace
Air
Inlet
Vent
2" TO 3" COUPLING
FURNACE
VENT
OUTLET
FACTORY SUPPLIED ONLY
WITH THE FOLLOWING
MODELS:
ALL 100,000 BTUH UPFLOW
MODELS, ALL 120,000 BTUH
UPFLOW MODELS, THE
UX1C080A9601 MODEL, AND
ALL DOWNFLOW MODELS
#CPL00938
f
HORIZONTAL INSTALLATION
(UPFLOW/ HORIZONTAL OR DOWNFLOW/ HORIZONTAL)
NOTE:
See Figures 23 & 24. In horizontal venting when the
factory supplied “off-set” (2X3 reducing coupling)
is used for 3” vent pipe installation, make sure the
marking “Top” is located on the top side of the pipe.
The straight side must be on bottom for proper
condensate drainage. This coupling is factory supplied
with the following models: *UHMC100, *UHMD120, & all
downflow models.
Carbon monoxide, fire or smoke can cause serious bodily
injury, death, and/ or property damage.
A variety of potential sources of carbon monoxide can
be found in a building or dwelling such as gas-fired
clothes dryers, gas cooking stoves, water heaters,
Furnaces and fireplaces. The U.S. Consumer Product
Safety Commission recommends that users of gasburning appliances install carbon monoxide detectors as
well as fire and smoke detectors per the manufacturer’s
installation instructions to help alert dwelling occupants
of the presence of fire, smoke or unsafe levels of carbon
monoxide. These devices should meet Underwriters
Laboratories, Inc. Standards for Single and Multiple Station Carbon Monoxide Alarms, UL 2034 or CSA
International Standard, Residential Carbon Monoxide
Alarming Devices, CSA 6.19
For NONDIRECT VENT APPLICATION: The furnace shall
be vented to the exterior of the house, but combustion
air may enter from the surrounding area as long as
combustion air requirements are met. (See AIR FOR
COMBUSTION AND VENTILATION).
FURNACE VENT/INLET PIPE INSTALLATION
CARBON MONOXIDE POISONING HAZARD
Failure to follow the installation instructions for the
venting system being placed into operation could
result in carbon monoxide poisoning or death.
There are many different variations of the vent/ inlet air
pipe combination. The vent/ inlet air combination used for
installation of these furnaces depends on the needs of
the location. However, these guidelines must be followed:
1. The Furnace must vent outside the structure.
2. Furnace combustion air requirements must be met
for nondirect, single pipe applications (See ex. 2 ).
3. For direct vent application of these furnaces, the vent
pipe and air inlet pipe do not have to exit in the same air
space or even on the same surface of the structure.
However, the longest individual pipe will decide the value
for the longest allowable equivalent vent/ inlet air length
as shown in the vent length table.
NOTE:
BAYVENT200B accessories can be used for inlet
and outlet terminals when the pipes do not exit
the structure together. For Canadian applications
ONLY, IPEX 196006 may be used for horizontal and
vertical terminations. IPEX 081216, IPEX 081218, and
IPEX 081219 may be only used for horizontal vent
terminations.
The following are EXAMPLES ONLY:
EX. 1 —
Example 1 shows that the vent may go vertical while the
inlet air may be on any side of the structure. The Vent
Pipe would decide the maximum equivalent length for the
pipe depending on the furnace and pipe size.
NOTE: The manufacturer of your furnace does not test
any detectors and makes no representations regarding
any brand or type of detector.
IMPORTANT: These furnaces may be installed as Direct
Vent (sealed combustion) or as Nondirect Vent (single
pipe). The furnaces are shipped DIRECT VENT with sealed
combustion.
For DIRECT VENT APPLICATION: The furnaces must
be vented to the exterior of the house and combustion air
MUST come through the inlet air pipe FROM OUTSIDE
AIR. The pipes DO NOT have to exit the exterior of the
house together or on the same side of the house.
16 18-CD30D1-12
Installer’s Guide
Furnace
Air
Inlet
Vent
Attic
Vent
(See Note)
Furnace
Air
Inlet
Vent
Furnace
Vent
Air
Inlet
(See Note)
EX. 2 —
Example 2 shows the vent pipe exhausting through the
roof and the inlet air coming from the interior of the house
(See Note). The inlet air coming from the interior of the
house must meet combustion requirements for area, etc.,
as shown in the section AIR FOR COMBUSTION AND
VENTILATION in this Installer’s Guide.
EX. 3 —
Example 3 shows the vent exiting one side of the house
while the inlet air is on the opposite side of the structure.
Here the Vent Pipe length must be within the allowable
length for the size of Furnace and size of the Vent Pipe.
This example demonstrates that the pipes do not have to
exit on the same side of the structure.
EX. 4 —
The inlet air does not have to come from outside the
structure. Example 4 shows the inlet air (See Note), may
come from the attic if the requirements for combustion air
are met as shown in the section AIR FOR COMBUSTION
AND VENTILATION.
NOTE:
If only the flue gas pipe is to the outside of the
structure, a straight section of pipe (long enough to
exit the Furnace cabinet) must be attached to the inlet
air side with an elbow (which is 5 to 10 equivalent feet)
installed on the end to prevent dust and debris from
falling directly into the Furnace.
VENT FITTING MATERIAL – PLASTIC
Gas and liquid tight single wall vent fittings, designed for
resistance to corrosive flue condensate, MUST be used
throughout.
Listed in Table 9 are materials that meet these
requirements. The materials listed are various grades of
PVC and ABS plastic.
PIPE JOINTS: All joints must be fastened and sealed to
prevent escape of combustion products into the building.
These materials are acceptable for U.S. applications only.
All Canadian installations must conform to ULC S636.
NOTE:
It is recommended that the first joints from the furnace
be connected and sealed with high temperature RTV.
This will enable the pipes to be removed later without
cutting. Be sure to properly support these joints.
BONDING OF PVC
Commercially available solvent cement for PVC must
be used to join PVC pipe fittings. Follow instructions on
container carefully for U.S. applications only. Canadian
applications require primer and cement that are from a
single system manufacturer.
For U.S. applications only:
Pipe and Fittings – ASTM D1785, D2466, D2661, &
D2665. PVC Primer and Solvent Cement – ASTM D2564.
Procedure for Cementing Joints Ref – ASTM D2855
1. Cut pipe square, remove ragged edges and burrs.
Chamfer end of pipe, then clean fitting socket and pipe
joint area of all dirt, grease, moisture or chips.
2. After checking pipe and socket for proper fit, wipe
socket and pipe with cleaner-primer. Apply a liberal coat
of primer to inside surface of socket and outside of pipe.
DO NOT ALLOW PRIMER TO DRY BEFORE
APPLYING CEMENT.
3. Apply a thin coat of cement evenly in the socket.
Quickly apply a heavy coat of cement to the pipe end and
insert pipe into fitting with a slight twisting movement until
it bottoms out.
4. Hold the pipe in the fitting for 30 seconds to prevent
tapered socket from pushing the pipe out of the fitting.
18-CD30D1-12 17