These instructions are given as a guide to good practice
in the installation, start-up, operation, and maintenance
by the user, of Trane CGAX chillers or CXAX heat pumps.
They do not contain full service procedures necessary
for the continued successful operation of this equipment.
The services of a qualified technician should be
employed through the medium of a maintenance
contract with a reputable service company. Read this
manual thoroughly before unit start-up.
Units are assembled, pressure tested, dehydrated,
charged and tested in accordance with factory standard
before shipment.
Warnings and cautions
Warnings and Cautions appear at appropriate sections
throughout this manual. Your personal safety and the
proper operation of this machine require that you follow
them carefully. The constructor assumes no liability
for installations or servicing performed by unqualified
personnel.
WARNING!: Indicates a potentially hazardous situation
which, if not avoided, could result in death or serious
injury.
CAUTION!: Indicates a potentially hazardous situation
which, if not avoided, may result in minor or moderate
injury. It may also be used to alert against unsafe
practices or for equipment or property-damage only
accidents.
CAUTION!: Time before to work on the electrical panel
of the unit with Low Ambient option: once the unit is
off (confirmed by the extinction of the display), it is
mandatory to wait five minutes before working on the
electrical panel.
Reception
On arrival, inspect the unit before signing the delivery
note. Specify any visible damage on the delivery note,
and send a registered letter of protest to the last carrier
of the goods within 7 days of delivery.
Notify the local TRANE sales office at the same
time. The delivery note must be clearly signed and
countersigned by the driver.
Any concealed damage shall be notified by a registered
letter of protest to the last carrier of the goods within
7 days of delivery. Notify the local TRANE sales office
at the same time.
Important notice: No shipping claims will be accepted
by TRANE if the above mentioned procedure is not
respected.
For more information, refer to the general sales
conditions of your local TRANE sales office.
Note: Unit inspection in France.
Delay to send registered letter in case of visible and
concealed damage is only 72 hours.
Warranty
Warranty is based on the general terms and conditions
of the manufacturer. The warranty is void if the
equipment is repaired or modified without the written
approval of the manufacturer, if the operating limits are
exceeded or if the control system or the electrical wiring
is modified. Damage due to misuse, lack of maintenance
or failure to comply with the manufacturer’s instructions
or recommendations is not covered by the warranty
obligation. If the user does not conform to the rules of
this manual, it may entail cancellation of warranty and
liabilities by the manufacturer.
Safety recommendations
To avoid death, injury, equipment or property damage,
the following recommendations should be observed
during maintenance and service visits:
1. The maximum allowable pressures for system leak
testing on low and high pressure side are given in the
chapter “Installation”. Do not exceed test pressure by
using an appropriate device.
2. Disconnect the main power supply before any
servicing on the unit.
3. Service work on the refrigeration system and the
electrical system should be carried out only by
qualified and experienced personnel.
CG-SVX027D-GB
3
General Information
Maintenance contract
It is strongly recommended that you sign a maintenance
contract with your local Service Agency. This contract
provides regular maintenance of your installation by a
specialist in our equipment.
Regular maintenance ensures that any malfunction is
detected and corrected in good time and minimizes
the possibility that serious damage will occur. Finally,
regular maintenance ensures the maximum operating
life of your equipment.
We would remind you that failure to respect these
installation and maintenance instructions may result in
immediate cancellation of the warranty.
Training
To assist you in obtaining the best use of it and
maintaining it in perfect operating condition over a long
period of time, the manufacturer has at your disposal a
refrigeration and air conditioning service school.
The principal aim of this is to give operators and
technicians a better knowledge of the equipment they
are using, or that is under their charge. Emphasis is
particularly given to the importance of periodic checks on
the unit operating parameters as well as on preventive
maintenance, which reduces the cost of owning the unit
by avoiding serious and costly breakdown.
2 = Contactors for single pump external to the unit
4 = Contactor for twin pump external to the unit
5 = Single pump package low pressure
6 = Single pump package high pressure
7 = Twin pump package low pressure
8 = Twin pump package high pressure
Digit 36 — Pump Flow Control
X = Constant Flow (no pump flow control)
B = Manual Flow Setpoint on VFD
C = Variable primary Flow (constant delta T)
Digit 37 — Buffer Tank
X = No Tank
1 = With Tank
Digit 44 — Literature language
B = Spanish
C = German
D = English
E = French
H = Dutch
J = Italian
M = Swedish
N = Turkish
P = Polish
R = Russian
T = Czech
U = Greek
V = Portuguese
Y = Romanian
3 = Hungarian
Digit 45 — Under/Over Voltage Protection
X = None
1 = With
Digit 46 — Open for future options
Digit 38 — Open digit for future options
Digit 39 — Installation Accessories
1 = None
4 = Neoprene pads
Digit 40 — Open digit for future options
Digit 41 — Acoustical options
2 = High external static pressure
3 = Standard
4 = Low Noise
Digit 42 — Condenser Protection
X = Without
A = Condenser Guard Grill
Digit 43 — Open digit for future options
Digit 47 — Customer witness performance test
X = None
Digit 48 — Open for future options
Digit 49 — Supplementary Heat Control
X = None
1 = With
Digit 50 — Special design
X = Standard
S = Special design
6
CG-SVX027D-GB
Unit Description
Conquest chillers, CGAX, air cooled scroll compressor
type liquid chillers and CXAX heat pumps, are
designed for outdoor installation. Units can have one
or two independent refrigerant circuits, two or more
compressors per circuit. Unit are packaged with an
evaporator made with a braze plate heat exchanger, and
one or more condenser coils.
Each unit is completely assembled, hermetic package,
refrigerant circuit factory piped, electrical components
wired, leak tested, dehydrated, charged and tested
for proper control operations prior to shipment. The
chilled water inlet and outlet openings are covered for
shipment.
A new generation of chiller control systems, providing
improved control capabilities. Integrated safety protocols
to protect both compressor and motor from electrical
faults like thermal overload and phase reversal.
Each refrigerant circuit is provided with filter, electronic
expansion valve, and charging valves.
In cooling mode on the CXAX or on the CGAX, the
evaporator is a brazed plate and frame heat exchanger
equipped with water drain and vent connections on the
water piping.
Condenser coil is available in four different
configurations: fin and tube with aluminium fins, or
black epoxy pre-coating aluminum fins for the heat
pump versions, and MicroChannel type or E-coating
Microchannel type for the cooling only versions.
Accessory/options information
Check all the accessories and loose parts which are
shipped with the unit against the original order. Included
in these items will be rigging diagrams, wiring diagrams,
and service literature, which are placed inside the control
panel and/or starter panel for shipment. Also check for
optional components, such as couplings and pipe stubs
or neoprene pads.
The following pictograms can be found on the unit. Take
necessary precautions to avoid damage and injury.
Figure 1 - Warning pictograms
1 = Risk that unit is powered up
2 = Risk hazard due to fan rotation
3 = Risk hazard of burns on compressors or refrigeration
piping
4 = Unit contains refrigerant gas. See specific warnings.
5 = Risk of residual voltage when speed drive or
softstarter or Low Ambient options are present
6 = Unit under pressure
7 = Risk to cut, particularly on heat exchanger fins
8 = Read instructions before installation
9 = Disconnect all electric power before servicing
10 = Read technical instructions
CG-SVX027D-GB
7
Pre-Installation
Mandatory Start-up Checklist
This checklist is not intended to be a substitution for
the contractors installation instruction. This checklist is
intended to be a guide for the Trane technician just prior
to unit ‘start-up’. Many of the recommended checks and
actions could expose the technician to electrical and
mechanical hazards. Refer to the appropriate sections in
the unit manual for appropriate procedures, component
specifications and safety instructions.
Except where noted; it is implied that the technician is to
use this checklist for inspection / verification of prior task
completed by the general contractor at installation.
1. Unit clearances adequate for service and to avoid air
recirculation, etc.
2. Unit exterior inspected. CXAX condensor coil will not
be obstructed at any time by snow or ice during winter
conditions.
3. Unit properly grounded
4. Crankcase heaters working for 24 hours prior to arrival
of Trane technician performing start up
5. Correct voltage supplied to unit and electric heaters
(imbalance not to exceed 2%)
6. Unit power phasing (A-B-C sequence) proper for
compressor rotation
7. Copper power wiring meets sizing requirement in job
submittal
8. All automation and remote controls installed/wired
9. All wiring connections tight
10. Prove chilled water side Interlock and Interconnecting
Wiring Interlock and externals (chilled water pump)
11. Field installed control wiring landed on correct
terminals (external start/stop, emergency stop, chilled
water reset…)
12. Verify all refrigerant and oil valves are open/back
seated
13. Compressor oil levels (1/2 -3/4 high in glass) proper
14. Verify chilled water strainer is clean and free of debris
and evaporator chilled water circuits are filled
15. A pressure switch device to detect lack of water is
not included in the pump package. Installation of
this type of device is highly recommended to avoid
sealing damage due to operation of pump without
enough water.
16. Close the fused-disconnect switches that supplies
power to the chilled water pump starter
17. Start the chilled water pump to begin circulation
of the water. Inspect piping for leaks and repair as
necessary. Check the physical presence of the water
pressure switch.
18. With water circulating through the system, adjust
water flow and check water pressure drop through
evaporator
19. Return chilled water pump to auto
20. Verify all the chiller controller Menu Items.
21. All panels/doors secured prior to start-up
22. All coil fins inspected and straightened
23. Rotate fans before starting unit to inspect for
potential audible and visual signs of rubbing.
Start unit
24. Press AUTO key. The unit will start if the chiller
control calls for cooling and the safety interlocks are
closed
25. Check the evaporator and the condenser refrigerant
pressure on the chiller controller.
26. Confirm Superheat and subcooling values are normal
27. Compressor operation normal and within amperage
rating
28. Operating log completed
29. Press stop key
30. Inspect fans again after being under load to ensure
no signs or rubbing exist
31. Verify the chilled water pump runs for at least
1 minute (possibility to configure maxi 10 mn) after
the chiller is commanded to stop (for normal chilled
water systems)
Unit storage
If the chiller is to be stored for more than one month
prior to installation, observe the following precautions:
• Store the chiller in a dry, vibration-free, secure area.
• Units charged with refrigerant should not be stored
where temperatures exceed 68°C.
• At least every three months, attach a gauge and
manually check the pressure in the refrigerant circuit.
If the refrigerant pressure is below 13 bar at 20°C
(or 10 bar at 10°C), call a qualified service organization
and the appropriate Trane sales office.
Note: if the unit is stored before servicing near a
construction site it is highly recommended to protect
micro channel coils from any concrete and iron element.
Failure to do so may considerably reduce reliablity of
the unit.
8
CG-SVX027D-GB
Pre-Installation
Installation requirements and
contractor responsibilities
A list of the contractor responsibilities typically
associated with the unit installation process is provided.
• Wiring sizes per submittals and local codes
and regulations
• Terminal lugs
• Disconnect Switch
• Unit mounted starter
• Grooved pipes coupling
and stub pipe (Optional)
• Control voltage wiring
• Ground connection(s)
• BAS Wiring (optional)
• Chilled water pump contactor and wiring
including interlock
• Option relays and wiring
• Taps for thermometers and gauges
• Thermometers
• Waterowpressuregauges
• Isolation and balancing valves in water
piping
• Vents and rains
• Pressure relief valves
• Pressure switch device to detect lack of
water
CG-SVX027D-GB
9
General Data
Table 1 - CGAX 015-036 General Data
CGAX
015
Net Cooling Capacity (1)(kW)43495965748299
Total Power input in cooling (1)(kW)15171922262933
Unit electrical data (2) (3) (4)
Short Circuit Unit Capacity (9)(kA)12121212121215
Power Cable Cross Section (max)mm²353535353535150
Disconnect switch size(A)8080100100100100250
Digit 12=2 or Digit 12=1 and Digit 41=2
Maximum Power input(kW)20.423.227.931.635.439.145.1
Unit rated amps(A)34.539.246.952.057.165.575.4
Unit start up amps (w/o soft starter - Digit 26=A) (4) (A)117.0161.0168.7184.7189.8191.0199.5
Unit start up amps (with soft starter - Digit 26=B) (4)77.8104.2111.9121.5126.6129.0140.7
Power factor0.8680.8660.8700.8880.9020.8700.873
Digit 12=1 and Digit 15=A
Maximum Power input(kW)19.422.125.829.533.337.043.0
Unit rated amps(A)33.838.545.450.555.664.073.8
Unit start up amps (w/o soft starter - Digit 26=A) (4) (A)116.3160.3167.2183.2188.3189.5197.9
Unit start up amps (with soft starter - Digit 26=B) (4)77.1103.5110.4120.0125.1127.5139.1
Power factor0.8450.8460.8360.8610.8800.8470.854
Digit 12=1 and Digit 15=C
Maximum Power input(kW)20.423.226.830.634.338.144.1
Unit rated amps(A)34.539.246.251.356.464.874.6
Unit start up amps (w/o soft starter - Digit 26=A) (4) (A)117.0161.0168.0184.0189.1190.3198.7
Unit start up amps (with soft starter - Digit 26=B) (4)77.8104.2111.2120.8125.9128.3139.9
Power factor0.8680.8660.8540.8750.8920.8590.864
Compressor
Compressor Number per Circuit#2222223
TypeScrollScrollScrollScrollScrollScrollScroll
Model Circuit1 / Circuit 27,5+7,57,5+1010+1010+1313+1315+1512+12+12
Max Compr Power input Circuit 1/Circuit 2kW9,2 + 9,29,2+ 1212 + 1212 + 15,715,7 + 15,7 17,61 + 17,6
Quantity#1111111
TypeStainless steel Copper Brazed plate Heat exchanger
Evaporator modelP80x66P80x92P80x92P80x92P120Tx76P120Tx76 P120Tx104
Evaporator Water Content volume(l)3.85.35.35.39.29.212.5
Nominal water connection size
(Grooved coupling) - Without HYM
Nominal water connection size
(Grooved coupling) - With HYM
Hydraulic Module Components
Single pump - Standard head pressure option
Max available Head Pressure(kPa)9610086113120110103
Motor Power(kW)1.201.201.201.501.501.501.50
Rated Amps(A)2.442.442.443.503.503.503.50
Single pump - High head pressure option
Max available Head Pressure(kPa)170174162152161152190
Motor Power(kW)2.302.302.302.302.302.303.00
Rated Amps(A)5.035.035.035.035.035.036.23
Twin pump - Standard head pressure option
Max available Head Pressure(kPa)9610086113120110103
Motor Power(kW)1.201.20
Rated Amps(A)2.442.442.443.503.503.503.50
Twin pump - High head pressure option
Max available Head Pressure(kPa)170174162152161152190
Motor Power(kW)2.302.302.302.302.302.303.00
Rated Amps(A)5.035.035.035.035.035.036.23
Expansion Tank Volume(l)25252525252535
Max User water loop Volume for factory mounted
expansion tank (1)
Optionnal water Buffer tank volume(l)324324324324324324444
Antifreeze Heater without pump package(W)120120120120120120180
Antifreeze Heater with pump package(W)280280280280280280340
Condenser
TypeFull aluminum Micro channel heat exchanger
Quantity of coil#1111112
Face area per circuit(m²)2.232.232.962.962.962.964.46
Quantity#1122222
Diameter(mm)800
Fan / motor TypePropeller fan : Fixed speed AC motor / Variable speed - EC motor / HESP MAX SPEED
Digit 12=2 or Digit 12=1 and Digit 41=2
Fan / motor TypeEC motor / HESP MAX SPEED
Airowperfanm3/h13753137181224812231122111219313727
Max Power InputKw1,951,951,95 + 1,95 1,95 + 1,95 1,95 + 1,95 1,95 + 1,95 1,95 + 1,95
Max AmpsA333 + 33 + 33 + 33 + 33 + 3
Motor RPM(rpm)915915915915915915915
Digit 12=1 and Digit 15=A
Fan / motor TypeFixed speed AC motor / Variable speed - EC motor
Airowperfanm3/h13788138281236212362123701237513827
Max Power InputKw0,890,890,89 + 0,89 0,89 + 0,89 0,89 + 0,89 0,89 + 0,89 0,89 + 0,89
Max AmpsA2,222,222,22 + 2,22 2,22 + 2,22 2,22 + 2,22 2,22 + 2,22 2,22 + 2,22
Motor RPM(rpm)686686686686686686686
Digit 12=1 and Digit 15=C
Fan / motor TypeFixed speed AC motor / Variable speed - EC motor
Airowperfanm3/h13788138281236212362123701237513827
Max Power InputKw1,951,951,95 + 0,89 1,95 + 0,89 1,95 + 0,89 1,95 + 0,89 1,95 + 0,89
Max AmpsA333 + 2,223 + 2,223 + 2,223 + 2,223 + 2,22
Motor RPM(rpm)686686686686686686686
Water content volume(l)0.140.140.140.140.350.350.35
Dimensions (7)
Unit Length(mm)2346234623462346234623462327
Unit Width(mm)1285128512851285128512852250
Std Unit Height(mm)1524152415241524152415241524
LN or External SP unit -
Single pump - Standard head pressure(kg)46464649494945
Single pump - High head pressure(kg)51515151515149
Twin pump - Standard head pressure(kg)70707075757571
Twin pump - High head pressure(kg)82828282828286
Pump VFD option(kg)0
Partial heat recovery option(kg)1.481.481.481.483.823.823.82
Water Buffer tank option(kg)319319319319319319425
System data
Nb of refrigerant circuit#1111111
Minimum cooling load % (6)%50435043505033
(1) Indicative performance at Evaporator water temperature : 12°C / 7°C - Condenser air temperature 35°C - for detailled performances, on a given unit,
consult Order Write Up.
(2) under 400V/3/50Hz.
(3) Rated Condition without Pump Package.
(4) Electrical & system data are indicative and subject to change without notice. Please refer to unit nameplate data.
(5) If the power line of the unit is protected by fuses gG of the same size as the disconnect switch.
(6) OIL058E or 0IL057E are European reference for POE oil and can be mixed in any proportion with OIL00078 or OIL 00080 (same oil with US reference on
Net Cooling Capacity (1)(kW)11112797116129147164
Total Power input in cooling (1)(kW)38413539475158
Unit electrical data (2) (3) (4)
Short Circuit Unit Capacity (9)(kA)15151515151515
Power Cable Cross Section (max)mm²150150150150150150150
Disconnect switch size(A)250250250250250250250
Digit 12=2 or Digit 12=1 and Digit 41=2
Maximum Power input(kW)51.158.746.455.863.370.778.2
Unit rated amps(A)82.698.278.193.5103.7113.9130.7
Unit start up amps (w/o soft starter - Digit 26=A) (4) (A)215.3223.7199.9215.3236.4246.6256.2
Unit start up amps (with soft starter - Digit 26=B) (4)152.1161.7143.1158.5173.2183.4194.2
Power factor0.9010.8700.8660.8700.8880.9020.870
Digit 12=1 and Digit 15=A
Maximum Power input(kW)49.055.544.251.659.066.574.0
Unit rated amps(A)81.095.876.590.4100.6110.8127.6
Unit start up amps (w/o soft starter - Digit 26=A) (4) (A)213.7221.3198.3212.2233.3243.5253.1
Unit start up amps (with soft starter - Digit 26=B) (4)150.5159.3141.5155.4170.1180.3191.1
Power factor0.8860.8470.8460.8360.8610.8800.847
Digit 12=1 and Digit 15=C
Maximum Power input(kW)50.056.646.453.761.268.676.1
Unit rated amps(A)81.896.678.191.9102.1112.3129.1
Unit start up amps (w/o soft starter - Digit 26=A) (4) (A)214.5222.1199.9213.7234.8245.0254.6
Unit start up amps (with soft starter - Digit 26=B) (4)151.3160.1143.1156.9171.6181.8192.6
Power factor0.8940.8550.8660.8540.8750.8920.859
Compressor
Compressor Number per Circuit#3322222
TypeScrollScrollScrollScrollScrollScrollScroll
Quantity#1111111
TypeStainless steel Copper Brazed plate Heat exchanger
Evaporator modelP120Tx104P120Tx104DP300x82DP300x82DP300x82 DP300x114 DP300x114
Evaporator Water Content volume(l)12.512.58.58.58.511.811.8
Nominal water connection size
(Grooved coupling) - Without HYM
Nominal water connection size
(Grooved coupling) - With HYM
Hydraulic Module Components
Single pump - Standard head pressure option
Max available Head Pressure(kPa)131104111133114113178
Motor Power(kW)2.302.301.502.302.302.302.30
Rated Amps(A)5.035.033.505.035.035.035.03
Single pump - High head pressure option
Max available Head Pressure(kPa)176151198179162162138
Motor Power(kW)3.003.003.003.003.003.003.00
Rated Amps(A)6.236.236.236.236.236.236.23
Twin pump - Standard head pressure option
Max available Head Pressure(kPa)131104111133114113178
Motor Power(kW)2.302.301.502.302.302.302.30
Rated Amps(A)5.035.033.505.035.035.035.03
Twin pump - High head pressure option
Max available Head Pressure(kPa)176151198179162162138
Motor Power(kW)3.003.003.003.003.003.003.00
Rated Amps(A)6.236.236.236.236.236.236.23
Expansion Tank Volume(l)35353535353535
Max User water loop Volume for factory mounted
expansion tank (1)
Optionnal water Buffer tank volume(l)444444444444444444444
Antifreeze Heater without pump package(W)180180120120120180180
Antifreeze Heater with pump package(W)340340280280280340340
Condenser
TypeFull aluminum Micro channel heat exchanger
Quantity of coil#2222222
Face area per circuit(m²)5.935.932.232.962.962.962.96
(in) -
(mm)
(in) -
(mm)
SE-SN
15,7 +
15,7 + 15,7
25,3 +
25,3 + 25,3
158 +
158 + 158
2" - 60,32" - 60,33" OD - 76,1 3" OD - 76,1 3" OD - 76,1 3" OD - 76,1 3" OD - 76,1
3" OD - 76,1 3" OD - 76,1 3" OD - 76,1 3" OD - 76,1 3" OD - 76,1 3" OD - 76,1 3" OD - 76,1
(l)2000200020002000200020002000
CGAX
045
SE-SN
17,6 +
17,6 + 17,6
29,5 +
29,5 + 29,5
155 +
155 + 155
CGAX
035
SE-SN
7,5+10 /
7,5+10
9,2 + 12 /
9,2 + 12
15,5 + 20,2 /
15,5 + 20,2
98 + 142 /
98 + 142
CGAX
040
SE-SN
10+10 /
10+10
12 + 12 /
12 + 12
20,2 + 20,2 /
20,2 + 20,2
142 + 142 /
142 + 142
CGAX
046
SE-SN
10+13
/10+13
12 + 15,7 /
12 + 15,7
20,2 + 25,3 /
20,2 + 25,3
142 + 158 /
142 + 158
CGAX
052
SE-SN
13+13 /
13+13
15,7 + 15,7 /
15,7 + 15,7
25,3 + 25,3 /
25,3 + 25,3
158 + 158 /
158 + 158
CGAX
060
SE-SN
15+15 /
15+15
17,6 + 17,6 /
17,6 + 17,6
29,5 + 29,5 /
29,5 + 29,5
155 + 155 /
155 + 155
12
CG-SVX027D-GB
General Data
Table 1 - CGAX 039-060 General Data (continued)
CGAX
039
Condenser Fan
Quantity#2324444
Diameter(mm)800
Fan / motor TypePropeller fan : Fixed speed AC motor / Variable speed - EC motor / HESP MAX SPEED
Digit 12=2 or Digit 12=1 and Digit 41=2
Fan / motor TypeEC motor / HESP MAX SPEED
Airowperfanm3/h14660135951468612249122331244712205
Water content volume(l)0.50.52x 0.142x 0.142x 0.142x 0.352x 0.35
Dimensions (7)
Unit Length(mm)2327232723272327232723272327
Unit Width(mm)2250225022502250225022502250
Std Unit Height(mm)1524152415241524152415241524
LN or External SP unit -
Single pump - Standard head pressure(kg)47474547474747
Single pump - High head pressure(kg)49494949494949
Twin pump - Standard head pressure(kg)75757575757575
Twin pump - High head pressure(kg)86868484848484
Pump VFD option(kg)0
Partial heat recovery option(kg)4.64.62x 1.482x 1.482x 1.482x 3.822x 3.82
Water Buffer tank option(kg)425425425425
System data
Nb of refrigerant circuit#1122222
Minimum cooling load % (6)%33332225222525
(1) Indicative performance at Evaporator water temperature : 12°C / 7°C - Condenser air temperature 35°C - for detailled performances, on a given unit,
consult Order Write Up.
(2) under 400V/3/50Hz.
(3) Rated Condition without Pump Package.
(4) Electrical & system data are indicative and subject to change without notice. Please refer to unit nameplate data.
(5) If the power line of the unit is protected by fuses gG of the same size as the disconnect switch.
(6) OIL058E or 0IL057E are European reference for POE oil and can be mixed in any proportion with OIL00078 or OIL 00080 (same oil with US reference on
Net Cooling Capacity (1)(kW)43495965748299
Total Power input in cooling (1)(kW)15171922262933
Unit electrical data (2) (3) (4)
Short Circuit Unit Capacity (9)(kA)12121212121215
Power Cable Cross Section (max)mm²353535353535150
Disconnect switch size(A)8080100100100100250
Digit 12=2 or Digit 12=1 and Digit 41=2
Maximum Power input(kW)20.423.227.931.635.439.145.1
Unit rated amps(A)34.539.246.952.057.165.575.4
Unit start up amps (w/o soft starter - Digit 26=A) (4) (A)117.0161.0168.7184.7189.8191.0199.5
Unit start up amps (with soft starter - Digit 26=B) (4)77.8104.2111.9121.5126.6129.0140.7
Power factor0.8680.8660.8700.8880.9020.8700.873
Digit 12=1 and Digit 15=A
Maximum Power input(kW)19.422.125.829.533.337.043.0
Unit rated amps(A)33.838.545.450.555.664.073.8
Unit start up amps (w/o soft starter - Digit 26=A) (4) (A)116.3160.3167.2183.2188.3189.5197.9
Unit start up amps (with soft starter - Digit 26=B) (4)77.1103.5110.4120.0125.1127.5139.1
Power factor0.8450.8460.8360.8610.8800.8470.854
Digit 12=1 and Digit 15=C
Maximum Power input(kW)20.423.226.830.634.338.144.1
Unit rated amps(A)34.539.246.251.356.464.874.6
Unit start up amps (w/o soft starter - Digit 26=A) (4) (A)117.0161.0168.0184.0189.1190.3198.7
Unit start up amps (with soft starter - Digit 26=B) (4)77.8104.2111.2120.8125.9128.3139.9
Power factor0.8680.8660.8540.8750.8920.8590.864
Compressor
Compressor Number per Circuit#2222223
TypeScrollScrollScrollScrollScrollScrollScroll
Model Circuit1 / Circuit 27,5+7,57,5+1010+1010+1313+1315+1512+12+12
Max Compr Power input Circuit 1/Circuit 2kW9,2 + 9,29,2+ 1212 + 1212 + 15,7 15,7 + 15,7 17,61 + 17,6
Max available Head Pressure(kPa)9610086113120110103
Motor Power(kW)1.201.201.201.501.501.501.50
Rated Amps(A)2.442.442.443.503.503.503.50
Single pump - High head pressure option
Max available Head Pressure(kPa)170174162152161152190
Motor Power(kW)2.302.302.302.302.302.303.00
Rated Amps(A)5.035.035.035.035.035.036.23
Twin pump - Standard head pressure option
Max available Head Pressure(kPa)9610086113120110103
Motor Power(kW)1.201.201.201.50
Rated Amps(A)2.442.442.443.503.503.503.50
Twin pump - High head pressure option
Max available Head Pressure(kPa)170174162152161152190
Motor Power(kW)2.302.302.302.302.302.303.00
Rated Amps(A)5.035.035.035.035.035.036.23
Expansion Tank Volume(l)25252525252535
Max User water loop Volume for factory mounted
expansion tank (1)
Optionnal water Buffer tank volume(l)324324324324324324444
Antifreeze Heater without pump package(W)120120120120120120180
Antifreeze Heater with pump package(W)280280280280280280340
Condenser
TypeFull aluminum Micro channel heat exchanger
Quantity of coil#1111112
Face area per circuit(m²)2.232.232.962.962.962.964.46
Quantity#1122222
Diameter(mm)800
Fan / motor TypePropeller fan : Fixed speed AC motor / Variable speed - EC motor / HESP MAX SPEED
Digit 12=2 or Digit 12=1 and Digit 41=2
Fan / motor TypeEC motor / HESP MAX SPEED
Airowperfanm3/h13753137181224812231122111219313727
Max Power InputKw1,951,951,95 + 1,95 1,95 + 1,95 1,95 + 1,95 1,95 + 1,95 1,95 + 1,95
Max AmpsA333 + 33 + 33 + 33 + 33 + 3
Motor RPM(rpm)915915915915915915915
Digit 12=1 and Digit 15=A
Fan / motor TypeFixed speed AC motor / Variable speed - EC motor
Airowperfanm3/h13788138281236212362123701237513827
Max Power InputKw0,890,890,89 + 0,89 0,89 + 0,89 0,89 + 0,89 0,89 + 0,89 0,89 + 0,89
Max AmpsA2,222,222,22 + 2,22 2,22 + 2,22 2,22 + 2,22 2,22 + 2,22 2,22 + 2,22
Motor RPM(rpm)686686686686686686686
Digit 12=1 and Digit 15=C
Fan / motor TypeFixed speed AC motor / Variable speed - EC motor
Airowperfanm3/h13788138281236212362123701237513827
Max Power InputKw1,951,951,95 + 0,89 1,95 + 0,89 1,95 + 0,89 1,95 + 0,89 1,95 + 0,89
Max AmpsA333 + 2,223 + 2,223 + 2,223 + 2,223 + 2,22
Motor RPM(rpm)686686686686686686686
Water content volume(l)0.140.140.140.140.350.350.35
Dimensions (7)
Unit Length(mm)2346234623462346234623462327
Unit Width(mm)1285128512851285128512852250
Std Unit Height(mm)1524152415241524152417241524
LN or External SP unit -
Single pump - Standard head pressure(kg)46464649494945
Single pump - High head pressure(kg)51515151515149
Twin pump - Standard head pressure(kg)70707075757571
Twin pump - High head pressure(kg)82828282828286
Pump VFD option(kg)0
Partial heat recovery option(kg)1.481.481.481.483.823.823.82
Water Buffer tank option(kg)319319319319319319425
System data
Nb of refrigerant circuit#1111111
Minimum cooling load % (6)%50435043505033
(1) Indicative performance at Evaporator water temperature : 12°C / 7°C - Condenser air temperature 35°C - for detailled performances, on a given unit,
consult Order Write Up.
(2) under 400V/3/50Hz.
(3) Rated Condition without Pump Package.
(4) Electrical & system data are indicative and subject to change without notice. Please refer to unit nameplate data.
(5) If the power line of the unit is protected by fuses gG of the same size as the disconnect switch.
(6) OIL058E or 0IL057E are European reference for POE oil and can be mixed in any proportion with OIL00078 or OIL 00080 (same oil with US reference on
Net Cooling Capacity (1)(kW)11112797116129147164
Total Power input in cooling (1)(kW)38413539475158
Unit electrical data (2) (3) (4)
Short Circuit Unit Capacity (9)(kA)15151515151515
Power Cable Cross Section (max)mm²150150150150150150150
Disconnect switch size(A)250250250250250250250
Digit 12=2 or Digit 12=1 and Digit 41=2
Maximum Power input(kW)51.158.746.455.863.370.778.2
Unit rated amps(A)82.698.278.193.5103.7113.9130.7
Unit start up amps (w/o soft starter - Digit 26=A) (4)(A)215.3223.7199.9215.3236.4246.6256.2
Unit start up amps (with soft starter - Digit 26=B) (4)152.1161.7143.1158.5173.2183.4194.2
Power factor0.9010.8700.8660.8700.8880.9020.870
Digit 12=1 and Digit 15=A
Maximum Power input(kW)49.055.544.251.659.066.574.0
Unit rated amps(A)81.095.876.590.4100.6110.8127.6
Unit start up amps (w/o soft starter - Digit 26=A) (4)(A)213.7221.3198.3212.2233.3243.5253.1
Unit start up amps (with soft starter - Digit 26=B) (4)150.5159.3141.5155.4170.1180.3191.1
Power factor0.8860.8470.8460.8360.8610.8800.847
Digit 12=1 and Digit 15=C
Maximum Power input(kW)50.056.646.453.761.268.676.1
Unit rated amps(A)81.896.678.191.9102.1112.3129.1
Unit start up amps (w/o soft starter - Digit 26=A) (4)(A)214.5222.1199.9213.7234.8245.0254.6
Unit start up amps (with soft starter - Digit 26=B) (4)151.3160.1143.1156.9171.6181.8192.6
Power factor0.8940.8550.8660.8540.8750.8920.859
Compressor
Compressor Number per Circuit#3322222
TypeScrollScrollScrollScrollScrollScrollScroll
Without HYM
Nominal water connection size (Grooved coupling) -
With HYM
Hydraulic Module Components
Single pump - Standard head pressure option
Max available Head Pressure(kPa)131104111133114113178
Motor Power(kW)2.302.301.502.302.302.302.30
Rated Amps(A)5.035.033.505.035.035.035.03
Single pump - High head pressure option
Max available Head Pressure(kPa)176151198179162162138
Motor Power(kW)3.003.003.003.003.00
Rated Amps(A)6.236.236.236.236.236.236.23
Twin pump - Standard head pressure option
Max available Head Pressure(kPa)131104111133114113178
Motor Power(kW)2.302.301.502.302.302.302.30
Rated Amps(A)5.035.033.505.035.035.035.03
Twin pump - High head pressure option
Max available Head Pressure(kPa)176151198179162162138
Motor Power(kW)3.003.003.003.003.003.003.00
Rated Amps(A)6.236.236.236.236.236.236.23
Expansion Tank Volume(l)35353535353535
Max User water loop Volume for factory mounted
expansion tank (1)
Optionnal water Buffer tank volume(l)444444444444444444444
Antifreeze Heater without pump package(W)180180120120120180180
Antifreeze Heater with pump package(W)340340280280280340340
Condenser
TypeFull aluminum Micro channel heat exchanger
Quantity of coil#2222222
Face area per circuit(m²)5.935.932.232.962.962.962.96
(in) -
(mm)
(in) -
(mm)
SE-SN
15,7 +
15,7 + 15,7
25,3 +
25,3 + 25,3
158 +
158 + 158
2" - 60,32" - 60,3 3" OD - 76,1 3" OD - 76,1 3" OD - 76,1 3" OD - 76,1 3" OD - 76,1
3" OD - 76,1 3" OD - 76,1 3" OD - 76,1 3" OD - 76,1 3" OD - 76,1 3" OD - 76,1 3" OD - 76,1
(l)2000200020002000200020002000
CXAX
045
SE-SN
17,6 +
17,6 + 17,6
29,5 +
29,5 + 29,5
155 +
155 + 155
CXAX
035
SE-SN
7,5+10 /
7,5+10
9,2 + 12 /
9,2 + 12
15,5 + 20,2 /
15,5 + 20,2
98 + 142 /
98 + 142
CXAX
040
SE-SN
10+10 /
10+10
12 + 12 /
12 + 12
20,2 + 20,2 /
20,2 + 20,2
142 + 142 /
142 + 142
CXAX
046
SE-SN
10+13
/10+13
12 + 15,7 /
12 + 15,7
20,2 + 25,3 /
20,2 + 25,3
142 + 158 /
142 + 158
CXAX
052
SE-SN
13+13 /
13+13
15,7 + 15,7 /
15,7 + 15,7
25,3 + 25,3 /
25,3 + 25,3
158 + 158 /
158 + 158
3.003.00
CXAX
060
SE-SN
15+15 /
15+15
17,6 + 17,6 /
17,6 + 17,6
29,5 + 29,5 /
29,5 + 29,5
155 + 155 /
155 + 155
16
CG-SVX027D-GB
General Data
Table 2 - CXAX 039-060 General Data (continued)
CXAX
039
Condenser Fan
Quantity#2324444
Diameter(mm)800
Fan / motor TypePropeller fan : Fixed speed AC motor / Variable speed - EC motor / HESP MAX SPEED
Digit 12=2 or Digit 12=1 and Digit 41=2
Fan / motor TypeEC motor / HESP MAX SPEED
Airowperfanm3/h14660135951468612249122331244712205
Water content volume(l)0.50.52x 0.142x 0.142x 0.142x 0.352x 0.35
Dimensions (7)
Unit Length(mm)2327232723272327232723272327
Unit Width(mm)2250225022502250225022502250
Std Unit Height(mm)1524152415241524152415241724
LN or External SP unit -
Single pump - Standard head pressure(kg)47474547474747
Single pump - High head pressure(kg)49494949494949
Twin pump - Standard head pressure(kg)75757575757575
Twin pump - High head pressure(kg)86868484848484
Pump VFD option(kg)0
Partial heat recovery option(kg)4.64.62x 1.482x 1.482x 1.482x 3.822x 3.82
Water Buffer tank option(kg)425425425425425425425
System data
Nb of refrigerant circuit#
Minimum cooling load % (6)%33332225222525
(1) Indicative performance at Evaporator water temperature : 12°C / 7°C - Condenser air temperature 35°C - for detailled performances, on a given unit,
consult Order Write Up.
(2) under 400V/3/50Hz.
(3) Rated Condition without Pump Package.
(4) Electrical & system data are indicative and subject to change without notice. Please refer to unit nameplate data.
(5) If the power line of the unit is protected by fuses gG of the same size as the disconnect switch.
(6) OIL058E or 0IL057E are European reference for POE oil and can be mixed in any proportion with OIL00078 or OIL 00080 (same oil with US reference on
The most effective form of acoustical isolation is to
locate the unit away from any sound sensitive area.
Structurally transmitted sound can be reduced by
elastomeric vibration eliminators. Spring isolators are
not recommended. Consult an acoustical engineer in
critical sound applications.
Foundation
Figure 2 - Installation example
For maximum isolation effect, water lines and electrical
conduit should also be isolated. Wall sleeves and rubber
isolated piping hangers can be used to reduce the sound
transmitted through water piping. To reduce the sound
transmitted through electrical conduit, use flexible
electrical conduit.
EU and Local codes on sound emissions should always
be considered. Since the environment in which a sound
source is located affects sound pressure, unit placement
must be carefully evaluated. Consult an acoustical
engineer for critical applications.
Provide rigid, non-warping mounting pads or a concrete
foundation of sufficient strength and mass to support
the applicable operating weight (i.e. including completed
piping, and full operating charges of refrigerant, oil and
water). Refer to the chapter on Unit Dimensions/Weights
for unit operating weights. Once in place, the unit must
be level with 3 mm over its length and width. Trane is not
responsible for equipment problems resulting from an
improperly designed or constructed foundation.
Clearances
Provide enough space around the unit to allow the
installation and maintenance personnel unrestricted
access to all service points. Refer to submittal drawings
for the unit dimensions, to provide sufficient clearance
for the opening of control panel doors and unit service.
Refer to the chapter on Unit Dimensions/Weights for
minimum clearances. In all cases, local codes which
require additional clearances will take precedence over
these recommendations.
If the installation includes several units or if units are
close to walls, contact your local Trane Sales Office for
additional requirements.
Winter operation : CXAX coil will not be obstructed at
any time by snow or ice.
Specifc attention should be paid to avoid accumulation
of ice and snow at the bottom of the coil.
Rigging
Refer to weights tables for typical unit lifting weights.
Refer to the rigging label attached to the unit for further
details.
Lifting Procedure
Refer to the lifting label affixed to the unit. Lifting beam
crossbars MUST be positioned so lifting cables do not
contact the sides of the unit. Adjust as necessary for
even level lift.
1- Use the four rigging points which are built into the
unit.
2- Slings and a spreader bar are to be provided by the
rigger.
3 - The minimum lifting capacity of each sling as well
as the spreader bar must be equal or higher than the
tabulated unit shipping weight.
4- Caution: this unit must be lifted and handled with care.
Avoid shocks while handling.
Unit isolation and Leveling
Mounting
Construct an isolated concrete pad for the unit or provide
concrete footings at each of the four unit mounting
points. Mount the unit directly to the concrete pads or
footings. Level the unit using the base rail as a reference.
The unit must be level within 5 mm over the entire
length. Use shims as necessary to level the unit.
Isolation Pads installation (Optional)
Install the optional neoprene pads at each mounting
location. Refer to unit submittals for further details
on location. Consult a vibration engineer for critical
applications.
Evaporator piping
Evaporator water connections are grooved. Thoroughly
flush all water piping to the CGAX or CXAX units
before making the final piping connections to the unit.
Components and layout will vary slightly, depending on
the location of connections and the water source.
CAUTION Equipment Damage!
If using an acidic commercial flushing solution, construct
a temporary bypass around the unit to prevent damage
to internal components of the evaporator.
CAUTION Proper Water Treatment!
The use of untreated or improperly treated water in a
chiller may result in scaling, erosion, corrosion, algae or
slime. It is recommended that the services of a qualified
water treatment specialist be engaged to determine
what water treatment, if any, is required. Trane assumes
no responsibility for equipment failures which result
from untreated or improperly treated water, or saline or
brackish water.
18
CG-SVX027D-GB
Installation – Mechanical
Drainage
Locate the unit near a large capacity drain for water
vessel draindown during shutdown or repair. Water
piping is provided with drain connections. Refer to
“Water Piping.” All local and national codes apply.
Piping
A vent is provided on the top of the evaporator at the
return end. Be sure to provide additional vents at high
points in the piping to bleed air from the chilled water
system. Install necessary pressure gauges to monitor the
entering and leaving chilled water pressures.
Figure 3 - Unit typical water circuit
Provide shutoff valves in lines to the gauges to isolate
them from the system when they are not in use. Use
rubber vibration eliminators to prevent vibration
transmission through the water lines. If desired, install
thermometers in the lines to monitor entering and
leaving water temperatures. Install a balancing valve
in the leaving water line to control water flow balance.
Install shutoff valves on both the entering and leaving
water lines so that the evaporator can be isolated for
service. Make sure the water circuit includes all devices
and controls used to provide proper water system
operation and unit operating safety.
1 = Pressure gauges: show entering and leaving water
pressure
2 = Balancing valve: adjusts water flow.
3 = Air purge allows to remove the air from the water
circuit during fill up.
4 = Stop valves: isolate chillers and water circuiting
pump during maintenance operations.
5 = Thermometers: indicate chilled water entering and
7 = Stop valve located on the outlet connection: used
to measure the water pressure inlet or outlet of
evaporator.
8 = Strainer: avoid to get heat exchangers dirty. All
installation must be equipped with efficient strainer
in order that only clean water enters into exchanger.
If there is no strainer, reserve will be formulated by
the Trane technician at the start-up of the unit. The
trainer used must be able to stop all particles with a
diameter greater than 1 mm.
9 = Draining: used as the draining the plate heat
exchanger.
10 = Do not start the unit with low water volume or not
enough pressurized circuit.
Note: A pressure switch device to detect lack of water
is not included in the pump package. Installation of this
type of device is highly recommended to avoid sealing
damage due to operation of pump without enough
water.
Minimal installation water content
The water volume is an important parameter because
it allows as table chilled water temperature and avoids
short cycle operation of the compressors.
Parameters which influence the water temperature
stability
• Water loop volume
• Load fluctuation
• Number of capacity steps
• Compressors rotation
• Dead band (adjusted on chiller controller)
• Minimum time between 2 starts of a compressor
Minimum water volume for a comfort application
For comfort application we can allow water temperature
fluctuation at part load. The parameter to take into
account is the minimum operating time of the
compressor. In order to avoid lubrication problem
on a scroll compressor it must run at least 2 minutes
120 seconds) before it stops.
CG-SVX027D-GB
19
Installation – Mechanical
The minimum volume can be determined by using the
following formula:
Volume = Cooling capacity x Time x highest capacity step
(%) / Specific heat / Dead band
Minimum operating time = 120 seconds
Specific heat = 4.18 kJ / kg
Average Dead band = 3°C (or 2°C)
Table 3 - Minimum water volumes for comfort applications
Unit Size Capacity (KW)Biggest Step (%)
154250301201
174857393262
205850416278
236556522348
267450531354
308250589392
369433445297
3910733507338
4512333583388
359633455303
4011425409273
4612628506338
5214325513342
6016025574383
Note: To estimate the biggest step, it is usually
more reliable to make a selection at lower ambient
temperature where efficiency is higher and compressors
steps bigger. It is also essential to take into account the
brine specific heat, in case of the use of glycol.
Process applications will need more water volume to
minimize the water temperature fluctuation at part load.
Minimum Water
Volume (l) Dead
band = 2 °C
Minimum Water
Volume (l) Dead
band = 3 °C
Expansion tank (option)
The factory-installed expansion tank initial pressure
should be adjusted about 0.2 bar lower than the static
pressure of the circuit at the pump inlet. The expansion
tank volume has been selected for typical loop volume.
It is recommended to check the expansion tank volume
with the installation information.
The following data is required:
- C = Water capacity of the circuit
- e = Expansion coefficient (difference between max and
min water temperature, in operation or not)
- Pi = Initial pressure of the expansion tank
- Pf = Final pressure: Max is given by the pressure relief
valve
Minimum Volume of expansion tank = (C x e)/(1-Pi/Pf)
Expansion coefficient of water at various temperatures
°Ce
00.00013
100.00027
200.00177
300.00435
400.00782
500.01210
20
CG-SVX027D-GB
Installation – Mechanical
Freeze Protection
If the unit is exposed to ambient temperatures below
0°C, the chilled water system must be protected from
freezing following one of the options shown below:
1. Heaters
a. Heaters can be factory-installed (option) on the
evaporator and water piping and will protect it from
freezing in ambient temperatures down to -18°C.
AND
b. Install, outside the unit, heat tape on all water piping,
pumps, and other components that may be damaged
if exposed to freezing temperatures. Heat tape must be
designed for low ambient temperature applications. Heat
tape selection should be based on the lowest expected
ambient temperature.
OR
2. Freeze inhibitor
a. Add a freeze inhibitor fluid to the chilled water
system. The solution must be strong enough to provide
protection against ice formation at the lowest anticipated
ambient temperature.
Note: Use of a freeze inhibitor fluid reduces the cooling
capacity of the unit and must be considered in the
design of the system specifications.
3. Water pump
a: Chiller controller can start the pump to prevent
freezing. This function needs to be validated, pump has
to be controlled by the unit and water circuit valves
need to stay open at all times. This protection will be
efficient to protect the unit, if the water loop is reduced.
The installation of a bypass is advised.
If ambient temperatures below -18°C, the water circuit
must be protected against freezing.
Add a freeze inhibitor fluid and activate the heat tape on
the unit; do not shut the unit down.
It is not recommended to drain the water circuit for the
following reasons:
1. The water circuit will rust and its lifetime could be
reduced.
2. Water will remain in the bottom of the plate heat
exchangers and freeze damage could occur.
Note: If water pump control is enabled form the chiller
controller, it will request start of customer pump during
ambient air temperatures below freezing.
CAUTION! When using freeze inhibitor, never fill the
system with pure glycol. Always fill the system with
diluted solution. Maximum concentration of glycol is
40%. Higher glycol concentration will damage pump
seal.
Note: Never fill high Glycol concentration at the pump
suction as there is a high risk to damage pump seal.
In case of winter water drainage for freeze protection, it
is compulsory to disconnect the evaporators heaters to
protect them from burning due to overheat.
Note: Water pump control and heater combination will
protect the evaporator down to any ambient temperature
provided power is available to the pump and the
controller. This option will NOT protect the evaporator
in the event of power failure to the chiller unless backup
power is supplied to the necessary components.
The warranty will be void, in case of freezing due to the
lack of use of either of these protections.
Low refrigeration temperature setpoint and antifreeze
setpoint on chiller controller
CAUTION! The chiller is provided with standard factory
settings. It can be necessary to modify the Low Pressure
saturation Temperature and the Antifreeze Setpoint
on the unit control. Based on the following examples,
it is necessary to modify on the chiller controller the
following settings:
• The LP saturation temperature (LRTC)
• The antifreeze setpoint (LWTC)
Examples:
For:
• 7°C, the LP setting must be -4°C where the antifreeze
setting shall be 2°C
• 2°C, the LP setting must be -9°C where the antifreeze
setting shall be -4°C
• -12°C, the LP setting must be -23°C where the
antifreeze setting shall be -17°C
Freeze protection with glycol
It is mandatory to use a freeze inhibitor for leaving
water setpoint less or equal to 5°C. On the glycol
recommended concentration figure, you must select
concentration on or above the curve. For example, for
-4°C brine temperature, a concentration of 25% ethylene
glycol is not sufficient. The concentration must be 28%
ethylene glycol or 33% propylene glycol.
Using glycol with hydraulic module
If the glycol brine percentage is not at the recommended
percentage (greyed area), corrosion inhibitor present
in the glycol may not be efficient enough. For instance,
a glycol concentration of 15% will provide freeze
protection to the unit down to -5°C, but it might generate
additional corrosion.
CG-SVX027D-GB
21
Installation – Mechanical
Figure 4 - LP setting vs. Leaving Water Temperature setpoint
2
15
Figure 5 - Glycol percentage recommendation curve
1 = Critical risks of freezing
2 = Efficient freeze protection
3 = Ethylene glycol
4 = Propylene glycol
% = Glycol percentage (mass concentration)
°C = Glycol or water temperature
22
CG-SVX027D-GB
Hydraulic Data
CGAX Unit without pump package
(Pressure drop)
100
90
80
70
60
50
40
30
20
Water pressure drop (kPa)Water pressure drop (kPa)Water pressure drop (kPa)
10
0
051015202530354045
015
017 - 020 - 023
026 -030
Water flow (m3/h)
CGAX Single/Twin pump - Standard head pressure
(Avail. pressure)
250
200
150
100
50
0
051015202530354045
-50
015
017 -020
023
026 -030
Water flow (m3/h)
035
036
036 -039 -045
039
040 - 046
035 -040 -046
052 - 060
052 - 060
CGAX Single/Twin pump - High head pressure
(Avail. pressure)
250
200
150
100
50
0
051015202530354045
-50
015
017 -020 -023
026 - 030
Water flow (m3/h)
036
035 - 040 - 046
039 -045
Note: Extremity of the curves represents minimum and maximum water flow.
052 - 060
CG-SVX027D-GB
23
Hydraulic Data
CXAX Unit without pump package
(Pressure drop)
100
90
80
70
60
50
40
30
20
Water pressure drop (kPa)Water pressure drop (kPa)Water pressure drop (kPa)
10
0
051015202530354045
015 -017
020 -023 - 026 - 030
040
Water flow (m3/h)
036 -039 -045
CXAX Single/Twin pump - Standard head pressure
(Avail. pressure)
250
200
150
100
50
0
051015202530354045
015 -017
020
023 - 026 -030
Water flow (m3/h)
035
036
045
035 -046
045 - 035 -040 -046
052 -060
052 -060
CXAX Single/Twin pump - High head pressure
(Avail. pressure)
250
200
150
100
50
0
051015202530354045
015 - 017
020 -023 -026 -030
Water flow (m3/h)
040
036
035 -046
039 -045
Note: Extremity of the curves represents minimum and maximum water flow.
052 -060
24
CG-SVX027D-GB
Operating Map
50
50
-25
-20
-15
-10
-5
0
5
10
15
20
25
1520253035404550556065
Heating Mode
A
LWT (°C)
Amb Air T °C
CGAX
Minimum Starting Operating Ambient
- Std Ambient unit = 5°C
- Low Ambient unit = -18°C
Maximum Ambient = 46°C
Evaporator Outlet Temperature
- Comfort application [5°C; 20°C]
- Process application [-12°C; 5°C]
Figure 6 - Operating map- Cooling-only Model CGAX
45
45
40
40
35
35
30
30
25
25
20
20
15
15
10
10
Amb Air T °C
5
5
0
0
-5
-5
-10
-10
-15
-15
-20
-20
-15-10-50510152025
-15-10-50510152025
A
B
LWT (°C)
CXAX
Minimum Starting Operating Ambient
- Std Ambient unit
Cooling mode = 5°C
Heating mode = -15°C
- Low Ambient unit
Cooling mode = -10°C
Heating mode = -15°C
Maximum Ambient = 46°C
Evaporator outlet temperature
- Comfort Application [5°C; 20°C]
- Process Application [-10°C; 5°C]
Figure 7 - Heat Pump Model CXAX operating map
Cooling Mode
50
45
40
35
30
25
20
15
Amb Air T °C
10
5
0
-5
-10
-15
-15-10-50510152025
A
B
LWT (°C)
LWT = Leaving water temperature
Amb Air T = Ambient air temperature
A = Standard operating map
B = Low ambient operating map (Variable air flow control)
Minimum start-up/operation ambient based on a 2.22 m/s (5mph) wind across the condenser
CG-SVX027D-GB
25
20
15
10
5
0
-5
Amb Air T °C
-10
-15
-20
-25
15 20 25 30 35 40 45 50 55 60 65
Heating Mode
A
LWT (°C)
25
1
10
100
110100
Pressure drop (kPa)
Water fl ow rat es (l/s)
A: CGAX015, CGAX017,CGAX020,
CGAX023
B: CGAX035, CGAX040,CGAX046
C: CGAX026, CGAX030,CGAX036
D: CGAX052, CGAX060
E: CGAX039, CGAX045
A
B
C
D
E
1
10
100
110100
Pressure drop (kPa)
Water fl ow rat es (l/s)
A: CGAX015
B: CXAX017, CXAX020, CXAX023
C: CXAX035, CXAX040, CXAX046
D: CXAX026, CXAX030, CXAX036
E: CXAX052, CXAX060
F: CXAX039, CXAX045
A
B
C
-
MAX (7m3/h -117kPa
)
D
E
F
Partial Heat Recovery
Heat recovery option is made with a plate heat exchanger in series with the air-cooled condenser. This heat
exchanger benefits the discharge gas superheat as well as a part of the condensing gas heat to be transferred to
hot water system.
All submittals, lifting diagrams, neoprene pads, positioning and wiring diagrams have been supplied with the
chiller order.
Water pressure - Cooling only CGAX Heat Exchanger
Water pressure - Heat Recovery CXAX Heat Exchanger
26
CG-SVX027D-GB
Supplemental heat
The scope of Supplemental heat is to produce addtional capacity by energizing customer supplied electric heaters
when the Heat Pump alone cannot achieved customer requested capacity. this option is only available for Heat Pump
units and is only enabled in heating mode. Trane supplies software control and does not propose any hardware.
3 digitals output are available (configurable for 1 to 3) and can be enabled or disabled. Heaters remain energized
during defrost and start only when all the compressors are on.
CG-SVX027D-GB
27
Installation – Electrical
General Recommendations
When reviewing this manual keep in mind:
• All field-installed wiring must be in accordance with
local regulations and CE directives and guidelines.
Be sure to satisfy proper equipment grounding
requirements according CE
• The following standardized values - Maximum Amps Short Circuit Amps - Starting Amps are displayed on
unit nameplate.
• All field-installed wiring must be checked for proper
terminations, and for possible shorts or grounds.
Note: always refer to wiring diagrams shipped with
chiller or unit submittal for specific electrical schematic
and connection information.
WARNING Hazardous Voltage!
Disconnect all electric power, including remote
disconnects before servicing. Follow proper lockout/
tagout procedures to ensure the power can not be
inadvertently energized. Failure to disconnect power
before servicing could result in death or serious injury.
CAUTION! Time before to work on the electrical panel
of the unit with Low Ambient option: once the unit is
off (confirmed by the extinction of the display), it is
mandatory to wait five minutes before working on the
electrical panel.
CAUTION! To avoid corrosion, overheating or general
damage, at terminal connections, unit is designed for
copper conductors only. In case of aluminum conductors
an intermediate connection box must be added. In case
of aluminum cable bi material connecting device is
mandatory. Cable routing inside control panel should
be made case by case by installer.
Important!
Do not allow conduit to interfere with other components,
structural members or equipment. Control voltage
(230 V) wiring in conduit must be separate from conduit
carrying low voltage (<30V) wiring. To prevent control
malfunctions, do not run low voltage wiring (<30V) in
conduit with conductors carrying more than 30 volts.
Soft starter recommended settings
Acceleration time: 0.5 second speed Start-up torque: 50%
Deceleration time: 0 second
CAUTION! Inverters are equipped with integrated filters.
They are not compatible with insulated neutral load
earthing arrangements.
WARNING! High voltage!
Any contact with electric components , even after the
unit has been switched off, can cause serious injury or
death. Wait at least 4 minutes after switching off the unit,
until the current dissipates.
Grounding
Note the fan speed inverter has a high leakage current.
Be sure to ground the unit and take this into account
when installing the differiential protection device.
Differential protection should be suited for industrial
machinery with current leak which can be higher than
100 mA (several motors and frequency drives).
Installer-Supplied Components
Customer wiring interface connections are shown in
the electrical schematics and connection diagrams that
are shipped with the unit. The installer must provide the
following components if not ordered ith the unit:
• Power supply wiring (in conduit) for all field-wired
connections.
• All control (interconnecting) wiring (in conduit) for
field supplied devices.
• Circuit breakers.
Power Supply Wiring
WARNING Ground Wire!
All field-installed wiring must be completed by qualified
personnel. All field-installed wiring must comply with
local codes and regulations. Failure to follow this
instruction could result in death or serious injury.
All power supply wiring must be sized and selected
accordingly by the project engineer in accordance with
local codes and regulations.
WARNING Hazardous Voltage!
Disconnect all electric power, including remote
disconnects before servicing. Follow proper lockout/
tagout procedures to ensure the power can not be
inadvertently energized. Failure to disconnect power
before servicing could result in death or serious injury.
All wiring must comply with local codes and regulations.
The installing (or electrical) contractor must provide
and install the system interconnecting wiring, as well
as the power supply wiring. It must be properly sized
and equipped with the appropriate fused disconnect
switches. The type and installation location(s) of the
fused disconnects must comply with all applicable
codes. Knock-outs for wiring are located on the bottom
right side of the control panel. The wiring is passed
through these conduits and connected to the disconnect
switch. To provide proper phasing of 3-phase input, make
connections as shown in field wiring diagrams and as
stated on the WARNING label in the starter panel. For
additional information on proper phasing, refer to “Unit
Voltage Phasing.” Proper equipment ground must be
provided to each ground connection in the panel (one
for each customer supplied conductor per phase). High
voltage field-provided connections are made through
knockouts on the right side of the panel.
28
CG-SVX027D-GB
Figure 8 - Power Entrance
1x Ø4
1x Ø2
1x Ø46
1x Ø29
Installation – Electrical
1
2
1
2
6
9
1
2
1
2
1 = Incoming power (left side or right side to best suit
installation)
2 = Low voltage power (left side or right side to best suit
installation)
CG-SVX027D-GB
29
Electrical Data
For electrical data details, refer to General Data tables for each unit configuration and size.
- Maximum Power input (kW)
- Unit rated amps (Max compr Fan+Control)
- Unit start up amps (Starting Amps of the largest compr+RLA of 2nd compr+RLA of all fans+ control)
- Compressor Power factor
- Disconnect switch size (A)
Wiring diagrams are shipped with unit and can be found in the unit control panel.
Note : Rating is made for 400 V, 3 phases, 50 Hz power supply.
30
CG-SVX027D-GB
Electrical Data
Control Power Supply
Note: it is highly recommendable to read this section
within the wiring diagrams, where the different
components mentioned here are referenced.
General
Unit is equipped with a control transformer (1T1), factory
mounted, wired and tested, therefore it is not necessary
to provide additional control power voltage to the unit.
No other loads should be connected to the control
power transformer. All units are factory-connected for
appropriate labelled voltages.
On top of the main unit controller (1A2), when chosing
digit 32 = A (with customer input/output options), an
auxiliary processor module (1A4) will be mounted on the
unit to host the options described on the follow chapter.
Interconnecting Wiring /
Low Voltage Wiring
WARNING Ground Wire!
All field-installed wiring must be completed by a
qualified personnel, and must comply with local codes
and regulations. Failure to follow those instructions
could result on death or serious injury. The remote
devices described on the sections ahead require low
voltage wiring. All wiring to and from these remote
input devices to the Control Panel must be made with
shielded, twisted pair conductors. Be sure to ground the
shielding only at the panel.
Note : To prevent control malfunctions, do not run
low voltage wiring (< 30V) in conduit with conductors
carrying more than 30V.
Customer Options
Alarm and Status Relay Outputs (Programmable Relays)
A programmable relay concept provides for enunciation
of certain events or states of the chiller, selected
from a list of likely needs, while only using physical
ouputs relays, as shown on the field diagram. Four
electromechanical relays are provided, integrated on the
auxiliary module 1A4, connected on blocks J5-6-7-8, as
part of the customer input/ouput option. There is a main
insulation among the relays; the double-insulation does
exist towards the rest of the control.
The digital outputs must be properly protected against
short circuits and overloads. Moreover, they must feature
the same voltage, all 24 Vac or all 230 Vac., otherwise
24 Vac utilized must be a main insulation.
The minimum cross-section of the cables used for the
digital outputs must be 1.5 mm2.
Relay characteristics
relay ratings 2000 VA, 250 Vac, 8 A
approvals related to pCOE 2A FLA, 12A LRA, D300
according to UL, (30.000 cycles)
2 A resistive, 2 A inductive, cosj= 0.4, 2(2)A according to
EN 60730-1, (100.000 cycles)
The list of events/states that can be assigned to the
programmable relays can be found on the follow table.
The relay will be energized when the event/state occurs:
Table 4 - Alarm and Status Relay Output Configuration Table (see also wiring diagram)
Device
Designation
6K1
6K2
6K3
6K4
Relays, customer provided, unit status (Compressor running) : This output is true
whenever any compressor for the unit is running or commanded to be running, and
false when no compressor running or commanded to be running on the unit
Relays, customer provided, unit status (programmable) Default is Latching Alarm
CKT1: This output is true whenever there is any active diagnostic that requires a
manual reset to clear, that affects the Chiller, the refrigerant circuit, or any of the
Relays, customer provided, unit status (programmable) Default is Latching Alarm
CKT2: This output is true whenever there is any active diagnostic that requires a
manual reset to clear, that affects the Chiller, the refrigerant circuit, or any of the
Relays, customer provided, unit status (programmable) Default is Chiller limit mode:
This output is true, whenever the chiller has been running in one of the unloading
types of limit modes (condenser, evaporator, compressor) continoulsy for 20 minutes
on any circuits
Description
Location
conn block
J5-N01/C1
J6 –N02/C2
J7 –N03/C3
J8-N04/C4
CG-SVX027D-GB
31
Electrical Data
External Auto/Stop
If the unit requires external auto/stop function, the
installer must provide leads from the remote contacts on
unit main controller 1A2 – 1A3:
Chiller will run normally when the contacts are closed.
When they open, the compressor(s), if operating, will
cycle off. Unit operation will be inhibited. Closure of
the contacts will permit the unit to return to normal
operation. Field-supplied contacts for a low voltage
connections must be compatible with dry circuit 24 VDC
for a 12 mA resistive load. Refer to the field diagrams
shipped with the unit for further information.
Heat Pump Control and Heating /
Cooling Selection
On Heat Pump version units (CXAX), change for Heating/
Cooling can be done remotely, from a remote contact
on unit main controller 1A2, Terminal block J5 – ID7,
identified on the wiring diagram as 6S4.
A setpoint, contact closure, or communicated command
can select the unit heat/cool mode to be heat or cool. The
contact closure or communicated command allows the
user to remotely change the Heat/Cool operating mode.
The Setpoint can be changed from the Unit Controller
Front Panel. By changing this setpoint to ‘Heat’ the unit
will then switch to heating mode and control the leaving
water temperature to the hot water setpoint. By changing
this setpoint to ‘Cool’ the unit will switch to the cooling
mode, and control the leaving water temperature to the
Chilled water setpoint.
The operation of the unit is controlled by the Heat/Cool
command. Switching from cooling to heating will stop
all running compressors. After a 10 second delay the
4-way reversing valve will be switched into the heating
mode direction and the unit will run based on the
evaporator leaving water temperature compared to the
hot water setpoint.
Switching from heating to cooling will stop all running
compressors. After a 10 second delay the 4-way
reversing valve will be switched into the cooling mode
direction and the unit will run based on the evaporator
leaving water temperature compared to the chilled water
setpoint.
When the unit is stopped and there is a command to
switch from cooling to heating or heating to cooling the
10 second delay will been forced when switching the
4-way reversing valve.
Auxiliary Setpoint
If the unit requires an external Auxiliary Leaving Water
Temperature Setpoint, the installer must provide leads
from the remote contacts on unit main controller 1A4:
• 6S5: Terminal block J4 – ID1/IDC1
Chiller will operate normally, using the LWT Setpoint,
stablished on the unit controller, whenever the 6S5
contact will be closed, the unit will move to the Auxiliary
LWT Setpoint.
External Chilled Water Setpoint
(ECWS/EHWS) Option
Unit auxiliary controller (1A4) provides inputs that accept
either 0-20mA or 4-20mA signals to set the external
chilled/hot water setpoint (ECWS/EHWS). Important,
this is not a setpoint, this input defines a reset function.
This input is primarily used with generic BAS (Building
Automation Systems).
The chilled water setpoint may be changed from a
remote location by sending either 0-20mA or 4-20mA
signal to the the terminal block on 1A4: J9-B1/GND. The
0-20mA or 4-20mA each corresponds to a reset of 0-20°C
applied on the water setpoint (added on the chilled water
setpoint, subtracted on the hot water setpoint.
Following equation
Current Signal (0-20mA)
As processed by
Chiller Controller
If the ECWS/EWHS input develops an open or short,
the LLID willl report either a very high or very low
value back to the main processor. This will generate
an informational diagnostic and the unit will default to
using the main unit controller chilled water setpoint.
32
Water Setpoint Reset (°C) =
current(mA)
Current Signal (4-20mA)
(Default setting)
Water Setpoint Reset (°C) =
20*(mA – 4) / 16
CG-SVX027D-GB
Electrical Data
External Demand Limit Setpoint
(EDLS) Option
Unit auxiliary controller (1A4) provides a means to
limit the capacity of the chiller by limiting the number
of compressors or stages than are allowed to run. The
maximum number of compressors allowed to run can
vary from one to the number of stages on the unit. The
staging algorithm is free to decide which compressor or
stage shall be turned off of prevented from running to
meet the requirement.
ECWS and EDLS Analog Input Signal
Wiring Details
Both the ECWS and EDLS can be connected and set up as
either a 2-10 Vdc (factory default) , 4-20 mA, or resistance
input (also a form of 4-20 mA) as indicated below. (Need
to indicate here how to switch from Vdc to mA on PC05)
B1/B2
GND
Potentiometer
I = 20/(R+200)
Unit auxiliary controller (1A4) shall accept either 0-20mA
or 4-20mA signals. Each signal corresponds to an EDLS
range with a minimum of 1 compressor and a maximum
of all compressors. The following tables exist:
Nb of CMP allowed
Percent
0.0%0111
25.0%5112
33.3%6.7122
50.0%10223
66.7%13.3233
75.0%15234
100.0%20234
Current
0-20mA
Simplex
Duo
Simplex
Trio
Duplex
B1/B2
GND
(EWCS)
(EDLS)
Resistor
I = 20/(R+200)
Nb of CMP allowed
Percent
20.0%4111
40.0%8112
46.7%9.3122
60.0%12223
73.4%14.7233
80.0%16234
100.0%20234
Current
4-20mA
(Default
setting)
Simplex
Duo
Simplex
Trio
Duplex
CG-SVX027D-GB
33
Communication Interface Options
Percent capacity output
The controller provides an analog voltage output
(0-10 VDC) to communicate active unit capacity [%].
This signal is available on option module 1A4, Terminal
block J2 – Y1, identified on the wiring diagram as S1.
General
WARNING Ground wire! All field-installed wiring must
be complete by qualified personnel, and comply with
the local codes and regulations. Failure to follow this
instruction could resut in death or serious injury.
Field wiring for the communication link must meet the
following requirements:
• All wiring must be in accordance with local codes and
regulations.
Communication wiring
A
BCD
• Communication link wiring must be shielded, twisted
pair wiring (Belden 8760 or equivalent), below table
provides recommendation for wire size selection:
• The communication link cannot pass between
buildings
• All units on the communication link can be connected
in a “daisy chain” configuration.
Note: to prevent control malfunctions, do not run low
voltage wiring (< 30 V) in conduit with conductors
carrying more than 30 V.
Table 5 - Wire Size
Ø
2.5 mm²1525 m
1.5 mm²610 m
1.0 mm²305 m
Wire Size Maximum Length
of Communication Wire
A = LonTalk communication
B = BACnet communication
C = ModBus Communication
D = pCOWeb Communication
LonTalk Communication
Unit chiller controller provides integrated LonTalk
communication between chiller and the Building
Automation System (BAS). The input/outputs include
both mandatory and optional network variables
as established by the LonMark Functional Chiller
Profile 8040.
Installation Recommendations
The Lon interface uses an Echelon FTT-10 transceiver,
which is approved to be used on the TP/FT-10 channel.
This channel is characterized by the following main
features:
• It consists of up to 60 nodes on a single network
segment
• Data rate : 78 125 kbps
• Maximum distance : 1400 meters
• Recommended topology : daisy chain with double end
terminator (105 ohms)
For futher details, refer to the official documentation
LonWorks® FTT-10A free topology transeiver user’s
guide and to the official LonWorks® guidelines
LonMark® layer 1-6 interoperability guidelines
version 3.0.
These documents and additional information are
available on the internet site www.lonmark.org
BACnet Communication
Unit chiller controller provides integrated BACnet
communication between chiller and the Building
Automation System (BAS).
ModBus Communication
Unit chiller controller provides integrated ModBus
communication between chiller and the Building
Automation System (BAS).
pCOWeb Communication
Unit chiller controller provides integrated pCOWeb
communication between chiller and the Building
Automation System (BAS).
34
CG-SVX027D-GB
This section contains an overview of the operation of
CGAX and CXAX air cooled chillers, equipped with
microprocessor based control systems.
Note: To ensure proper diagnosis and repair, contact a
qualified service organization if a problem should occur.
General
CGAX and CXAX chillers are scroll compressor, single or
dual circuit air-cooled chillers. These units are equipped
with unit-mounted starter/control panels and operate
with R410A refrigerant.
The basic components on the CGAX/CXAX are:
• Unit-mounted panel containing starter and unit
controller
• Scroll compressors
• Brazed plate evaporator
• Air-cooled condenser with sub-cooler
• Electronic expansion valve
• Related interconnecting piping
Refrigerant Cycle
Refrigerant cycle is similar to other Trane Scroll
compressor chillers. Conquest chillers use brazed plate
evaporator and air-cooled condenser. Compressors
use suction gas cooled motors and an oil management
system to provide almost oil-free refrigerant to the
condenser and evaporator for maximum heat transfer
while lubricating and sealing compressor rotors and
bearings. The lubrication system helps to assure long
compressor life and contributes to quite operation.
Liquid refrigerant coming from the condenser coils,
are metered into the brazed plate evaporator using an
electronic expansion valve to maximize chiller efficiency
at full and part load operation.
Chillers are equipped with a unit-mounted starter and
control panel. Microprocessor-based unit controller
provide accurate chilled water control an monitoring,
protection and limit functions. If problems occurs the
unit controller provide diagnostic messages to help the
operator in troubleshooting.
Operating Principles
CG-SVX027D-GB
35
Operating Principles
This section describes the overall operating principle of the CGAX design (duplex cooling unit).
Figure 9 - Example of Typical Refrigerant System Schematic & Oil Lube Circuit Schematic
Note: Due to unit design there is no need to validate oil cycle while operating a reversible unit a long time in
cooling mode.
CG-SVX027D-GB
37
Operating Principles
Oil System
The oil is efficiently separated inside the scroll
compressor and will remain in the scroll compressor
during all run cycles. Between 1-2% of the oil circulates
around with the refrigerant. See on the compressor
section for oil level information.
Hydraulic Module water charts
Figure 11 - Hydraulic Module water chart - unit without
pump package
38
CG-SVX027D-GB
Figure 12 - Hydraulic Module water chart - unit with pump package
Operating Principles
CG-SVX027D-GB
39
Variable Primary Flow
Impact on unit design :
Add either differential pressure sensor or 2 water temperatures sensor.
Pump selection remains unchanged.
A variable speed drive to be added into the control box.
2 or 3 options of variable water flow :
Manual flow adjustment
Constant delta T
Constant delta P
VPF Constant delta T:
Principle :
If 1 Compressor switch off then Delta T decrease --> pump speed decrease.
If 1 Compressor switch On then Delta T increase --> pump speed increase.
Min pump speed = 30Hz
Require 3 ways valve on customer side.
40
CG-SVX027D-GB
General Start up
Start Up Preparation
Carry out all operations on check list so that the unit is
correctly installed and ready to operate. The installer
must check all the following points before calling in Trane
Service to put the equipment into service:
• Check position of unit.
• Check unit is level.
• Check type and position of rubber pads.
• Check clearance required for maintenance access
(Refer to certified drawings).
• Check clearance around condenser (Refer to certified
drawings).
• Chilled water circuit ready to operate, filled with water,
pressure test carried out and air purged.
• Chilled water circuit must be rinsed.
• Check the presence of water strainer ahead of
evaporator.
• The strainers must be cleaned after 2 hours of pumps
operation.
• Check the thermometers and manometers position.
• Check chilled water pumps interconnection to control
panel.
• Open the vent on the pump body to fill the pump with
water.
• Ensure that the isolation resistance of all power supply
terminals to ground complies with standards and
regulations in force.
• Check that unit voltage and frequency supplied match
rated input voltage and frequency.
• Check that all electrical connections are clean.
• Check that main power supply switch is sound.
• Check the unit power phasing to be sure that it has
been installed in an “ABC” sequence.
• Check Ethylene glycol or Propylene glycol % in the
chilled water circuit.
• Water flow control checking: decrease the water flow
and check the electrical contact in the control panel.
• Check chilled water pressure drop through
evaporator (unit without hydraulic module) or unit
available pressure (unit with hydraulic module) are
in accordance with the Trane order write-up (See
graphics…..).
• On start-up of each motor in the system, check
the direction of rotation and operation of all the
components they drive.
• Check that there is enough demand for cooling on the
day of the start-up (around 50% of the nominal load as
minimum).
Some parameters can not be adjusted with Deluxe Touch
Display. An additional Standard display PGD1 is needed
for such operation.
Water System Flow Rates
Establish a balanced chilled water flow through the
evaporator. The flow rates must fall between the
minimum and maximum values. Chilled water flow
rates below the minimum values will result in laminar
flow, which reduces heat transfer and causes either loss
of EXV control or repeated nuisance, low temperature
cutouts.
Water System Pressure Drop Measure water pressure
drop through the evaporator at the field-installed
pressure taps on the system water piping. Use the same
gauge for each measurement. Measure flow at the
field-installed supply and return. This will include valves,
strainers, and fittings in the pressure drop readings.
Pressure drop readings should be approximately those
shown in the Pressure Drop Charts in the InstallationMechanical section.
WARNING Hazardous Voltage!
Disconnect all electric power, including remote
disconnects before servicing. Follow proper lockout/
tagout procedures to ensure the power can not be
inadvertently energized. Failure to disconnect power
before servicing could result in death or serious injury.
Time before working on the electrical panel of the unit
with Low Ambient option
Once the unit is off (confirmed by the extinction of the
display), it is mandatory to wait five minutes before
working on the electrical panel.
WARNING Live Electrical Components!
During installation, testing, servicing and
troubleshooting of this product, it may be necessary to
work with live electrical components. Have a qualified
licensed electrician or other individual who has been
properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety
precautions when exposed to live electrical components
could result in death or serious injury
CAUTION! When using freeze inhibitor, never fill the
system with pure glycol. Always fill the system with
diluted solution. Maximum concentration of Glycol is
40%. Higher glycol concentration will damage pump
seal.
CAUTION! The pump must not run dry. Dry-running will
damage the mechanical seal.
CAUTION! Proper Water Treatment! The use of untreated
or improperly treated water in the chiller may result
in scaling, erosion, corrosion, algae or slime. It is
recommended that the services of a qualified water
treatment specialist be engaged to determine what
water treatment, if any, is required. Trane assumes no
responsibility for equipment failures which result from
untreated or improperly treated water, or saline or
brackish water.
CAUTION! Strainer should be cleaned after water flow
has been established for the first time, as it is likely that
it collects all the particles left after field installation.
CG-SVX027D-GB
41
General Start up
Start Up
Follow the instructions below to correctly start-up the
unit.
Installation and chiller inspection
• Ensure that all the operations above (start-up
preparation), are followed. Follow the instruction stuck
inside the electrical cabinet
• Put the plexiglass supplied by Trane in front of the
power terminal
• Ensure all water and refrigerant valves are in service
positions
• Ensure that the unit is not damaged
• Ensure that sensors are properly installed in their bulbwells and submerged in heat conducting product
• Check fixing of capillary tubes (protection from
vibration and from wear) and ensure that they are not
damaged
• Reset all manually set control devices
• Check refrigerating circuits tightness
Checking and setting
Compressors
• Check oil level at rest. The level should reach at least
halfway up indicator located on housing. See Figure 16
for correct level.
Figure 13 - Compressor oil level
1 = Max. oil level
2 = Min. oil level
• Reset all manually set control devices
• Check refrigerating circuits tightness
• Check electrical terminals tightening of the motors and
in the control panel
• Check the isolation of the motors using a 500V
DC megohmeter which meets manufacturer’s
specifications (minimum value 2 megohms)
• Check the direction of the rotation using phasemeter
Electrical power wiring
• Check all the electrical terminals tightening
• Set-up compressors overload relays
• Set-up fan-motors overload relays
Electrical control wiring
• Check all the electrical terminals tightening
• Check all the pressostats
• Check and set-up the chiller unit control module
• Test and start-up without the electrical power
Condenser
• Check direction of the rotation of fans
• Check the isolation of the motors using a 500V
DC megohmeter which meets manufacturer’s
specifications (minimum value 500 megohms)
Operating parameters statement
• Switch on main power supply switch
• Start the water pump(s) and check there is no
cavitation
• Start-up the unit following procedure described in the
CH535 controller user guide. The unit and the chilled
water pumps contactor must be connected together
• After unit start up, leave in operation for at least
15 minutes, to ensure pressures are stabilized
Then check:
• voltage
• compressors and fan-motors currents
• leaving and return chilled water temperature
• suction temperature and pressure
• ambient air temperature
• blowing air temperature
• discharge pressure and temperature
• liquid refrigerant temperature and pressure
• operating parameters
• chilled water pressure drop through
evaporator (if no hydraulic module is installed)
or unit available pressure. It must be in
accordance with Trane order write-up
• superheat: difference between suction
temperature and dew point temperature.
Normal superheat should be within 5 and 7 °C
with R410A in cooling mode
• sub-cooling: difference between liquid
temperature and bubble point temperature.
Normal sub-cooling should be within 2 and
15°C with R410A in cooling mode
• difference between dew point temperature
in high pressure and condenser air inlet
temperature. Normal value on standard unit
with R410A should be 15 to 23°C
• difference between outlet water temperature
and dew point temperature in low pressure.
Normal value on standard unit, without
Ethylene glycol in chilled water, should be
about 3.5°C
42
CG-SVX027D-GB
Final check
When the unit is operating correctly:
• Check that the unit is clean and clear of any debris,
tools, etc…
• All valves are in operating position
• Close control and starter panel doors and check panels
fixation
CAUTION!
• For the warranty to apply, any start-up carried out
directly by the customer must be recorded in a detailed
report, which must be sent as soon as possible to the
nearest Trane office.
• Do not start-up a motor whose insulation resistance is
less than 2 meghoms
• Phase imbalance should not be greater than 2%
• The voltage supplied to motors should be within 5% of
the rated voltage on the compressor nameplate.
• Excessive emulsion of the oil in the compressor shows
that refrigerant is present in the oil and the result will
be that compressor is not lubricated enough.. Shut
down compressor and wait for 60 minutes for the
sump heaters to heat oil and start again. Should this
not work, consult Trane technician.
• Excess oil in compressor can damage the compressor.
Before adding oil, consult Trane technician. Use only
Trane products recommended.
• The compressors must operate in a single direction of
rotation. If refrigerant high pressure remains stable in
the 30 seconds after compressor start-up, immediately
shut down unit and check the direction of rotation
using phasemeter.
WARNING!
• The chilled water circuit may be under pressure. Bring
down this pressure before opening up the system to
rise out or fill up the water circuit. Failure to comply
with this instruction may cause accidental injury to
maintenance personnel.
• If a cleaning solution is used in the chilled water circuit,
the chiller must be isolated from the water circuit to
avoid all the damage risks of the chiller and evaporator
water pipes.
General Start up
CG-SVX027D-GB
43
Pre-Start Check List (Sample)
UNIT
Check clearance around condenser
Check clearance required for maintenance access
Check type and position of the rubbers pads
Check unit is level
CHILLED WATER CIRCUIT
Check thermometers and manometers presence and position
Unit operation is intergrally managed by the
microprocessor-based unit controller.
Unit Operation
• Check that the chilled water pump(s) operates correctly
• Start up the unit following procedure described in
the unit controller user guide. The unit will operate
correctly when there is sufficient water flow. The
compressors will start up if the evaporator water
leaving temperature is above the control module
setpoint.
Weekly start up
• Check that the chilled water pump(s) operates correctly
• Start up the unit following procedure described in the
unit controller user guide
Weekend shutdown
• If the unit needs to be shut down for a short period of
time, stop the unit following procedure described in
the unit controller user guide. (See «Clock» menu)
• If the unit is shut down for a longer period, see under
«Seasonal shutdown», below
• Ensure that all safeties are taken to prevent frost
damages during negative ambient temperature
• Do not put the general disconnect switches to
off, except if the unit is drained. Trane does not
recommend draining the unit, due to the fact that it
increases corrosion
Seasonal shutdown
• Check water flows and interlocks
• Check glycol % in the chilled water circuit if glycol
presence is required
• Carry out leak test
• Carry out oil analysis
• Record operating pressures, temperatures, amperages
and voltage
• Check operation of machines/ compare conditions of
operation against original commissioning data
• Stop the unit following procedure described on the
unit controller user guide
• Ensure that all safeties are taken to prevent frost
damages during negative ambient temperature
• Fill out the visit log sheet and review with the
operator - Do not put the general disconnect switch to
off, except if the unit is drained
• Trane does not recommend draining the unit, due to
the fact that it increases corrosion
Seasonal start-up
• Check water flows and interlocks
• Check Ethylene glycol % in the chilled water circuit if
glycol presence is required
• Check operational setpoints and performance
• Calibrate controls
• Check operation of all safety devices
• Inspect contacts and tighten terminals.
• Megger the motor compressor windings
• Record operating pressures, temperatures, amperages
and voltage
• Carry out leak test
• Check configuration of unit control module
• Change the oil as required based upon results of the
oil analysis made during seasonal shutdown Get the
8 condition easurements at the same time, on each
circuit
• HP
• LP
• Suction temperature
• Discharge temperature
• Liquid temperature
• Water entering temperature
• Water leaving temperature
• Outdoor ambient temperature Then calculate the subcooling and superheat. No diagnosis can be accurate
with one of these recordsmissing
• Check operation of machines/compare conditions of
operation against original commissioning data
• Fill out the visit log sheet and review with the operator
CG-SVX027D-GB
45
Maintenance
Maintenance Instructions
The following maintenance instructions are part of
maintenance operations required for this equipment.
A qualified technician is needed for regular maintenance
as part of a regular maintenance contract. Carry out all
operations as required by schedule. This will ensure long
unit service life and reduce the possibility of serious
and costly breakdown. Keep service records up to date,
showing monthly information on unit operations. These
records can be of great help to aintenance personnel
diagnostics.
Similarly, if machine operator keeps a log of changes in
unit operating conditions, problems can be identified
and solutions found before more serious problems arise.
Inspection visit after the first 500 hours of operation
from unit start up
• Carry out oil analysis
• Carry out leak test
• Inspect contacts and tighten terminals
• Record operating pressures, temperatures, amperages
and voltage
• Check operation of machines/ compare conditions of
operation against original commissioning data
• Fill out inspection visit log sheet and review with the
operator
• Check and clean the strainer
Monthly preventive visit
• Carry out leak test
• Oil test of acidity
• Check Ethylene glycol % in the chilled water circuit if
glycol presence is required
• Inspect contacts and tighten terminals
• Record operating pressures, temperatures, amperages
and voltage
• Check operation of machines/ compare conditions of
operation against original commissioning data
• Fill out visit log sheet and review with the operator
• Check and clean the water strainer
Annual preventive visit
• Check water flows and interlocks
• Check expansion tank pressure
• Check glycol % in the chilled water circuit if glycol
presence is required
• Check operational setpoints and performance
• Calibrate controls and pressure transducer
• Check operation of all safety devices
• Inspect contacts and tighten terminals
• Megger the motor compressor windings
• Record operating pressures, temperatures, amperages
and voltage
• Carry out leak test
• Check configuration of unit control module
• Carry out oil analysis
• Change the oil as required based upon results of the
oil analysis
• Check operation of machines/ compare conditions of
operation against original commissioning data
• Fill out the annual start up visit log sheet and review
with the operator
• Check and clean the water strainer
CAUTION!
• Refer to specific Trane documentation on oil, available
from your nearest Trane office. Oils recommended
by Trane have been exhaustively tested in Trane
laboratories to the specific requirement of Trane chiller
and hence the user’s requirements. Any use of oils not
meeting specifications recommended by Trane is the
responsibility of the user only, who thereby is liable to
warranty loss.
• Oil analysis and oil test acidity must be carried out by
a qualified technician. Poor interpretation of results
may cause unit operating problems. Also, oil analysis
must follow the correct procedures, to avoid accidental
injury to maintenance personnel.
• If the condensers are dirty, clean them with a soft
brush and water. If the coils are too dirty, consult a
cleaning professional. Never use high pressure water
to clean condenser coils.
• Contact Trane Service for information on maintenance
contracts.
WARNING!
• Switch off unit main power supply before to any
intervention. Failure to follow this safety instruction
can lead to accident death of the maintenance
personnel and may also destroy equipment.
• Never use steam or hot water above 60°C to clean
condenser coils. The resulting increasing pressure
could cause refrigerant lost through the safety valve.
46
CG-SVX027D-GB
Maintenance
Pump maintenance
Pumps motor bearings and mechanical seals have
a designed life expectancy of 20000-25000 hours of
operation. For critical applications it might be necessary
to change the components as a preventive measure.
Compressors Service Information
Oil Equalizer line
CSHD Compressors
The oil equalizer line is equipped with a Rotolock fitting
for easy removal. Torque value for tightening these
fitting is 90 N.m. Before removing the oil equalizer line,
the system refrigerant charge must be recovered before
draining the oil. Use a catch pan to catch the oil when
the compressor oil equalizer line is loosened to ensure
that oil does not spill out of the compressor when the
equalizer line is removed.
Tandem and Trio Compressor Suction Restrictors
Since most uneven tandem and trio compressor sets
require the use of a restrictor in the suction line of one
or more compressors in order to provide correct oil level
balance between compressors when they are operating.
Compressor Replacement
If the CGAX/CXAX chiller suffers a failed compressor,
use these steps for replacement:
Each compressor has lifting eyes. Both lifting eyes must
be used to lift the failed compressor. DO NOT LIFT A
COMPRESSOR USING A SINGLE LIFTING EYE. Use
proper lifting techniques, a spreader bar and rigging as
for lifting both compressors simultaneously.
Compressor weights by compressor model are:
CSHD 092 – 58 kg.
CSHD 125 – 64 kg.
CSHD 142 – 67 kg.
CSHD 161 – 69 kg.
CSHD 183 – 76 kg.
After a mechanical failure of a compressor, it is
necessary to change the oil in the remaining compressor
and also replace the liquid line filter drier. After an
electrical failure of a compressor, it will also be
necessary to change the oil in the remaining compressor,
replace the liquid line filter drier and add a suction filter
drier with cleanup cores.
Refrigerant System Open Time
Model CGAX/CXAX chillers use POE oil (Trane
recommended oil OIL 048E or OIL 023E) and therefore
refrigerant system open time must be kept to a
minimum. The following procedure is recommended:
• Leave a new compressor sealed until it is ready to
be installed in the unit. Maximum system open time
is dependent upon ambient conditions, but do not
exceed one hour open time.
• Plug the open refrigerant line to minimize moisture
absorption. Always change the liquid line filter drier.
• Evacuate the system to 500 microns or below.
• Do not leave POE oil containers open to the
atmosphere. Always keep them sealed.
Mechanical Compressor Failure
Replace the failed compressor(s) and change the oil in
the remaining compressor(s) along with the refrigerant
system liquid line filter drier.
Electrical Compressor Failure
Replace the failed compressor and change the oil in
the other compressor(s). Also add a suction filter with
cleanup cores and change the liquid line filter drier.
Change filters and oil until the oil no longer test acidic.
See “Oil Testing.”
Compressor Motor Megging
Motor megging determines the electrical integrity of the
compressor motor winding insulation. Use a 500 volt
megger. A less than 1 meg-ohm reading is acceptable
and 1000 ohms per nameplate volts is required to safely
start the compressor.
Compressor Current Imbalance
Normal current imbalance could be 4 to 15 percent
with balanced voltage due to motor design. Each phase
should register .3 to 1.0 ohms and each phase should
be within 7 percent of the other two phases. Phase to
ground resistance must be infinity.
Note: Maximum allowable voltage imbalance is
2 percent.
Note: Do not alter the refrigerant piping in any way as
this can affect compressor lubrication.
Note: Do not add a suction filter drier within 250mm of
the elbow for CSHD compressors.
CG-SVX027D-GB
47
Maintenance
Refrigerant Piping
The compressor suction and discharge connections
and piping are copper clad steel for easy brazing. In
most instances, piping may be reused. If piping is not
reusable, order the correct service parts. Cut all tubing
with a tubing cutter to prevent copper filings from
entering the system. Cut the tubing in a straight length
of pipe after the compressor connection has been
unsweated. The line can then be reinstalled using a slip
coupling and brazing.
Note: The compressor suction line configuration must
not be changed in any way. Changing compressor
suction line configuration will compromise proper oil
return to the compressor(s).
Compressor Electrical Terminal Box
Be sure to protect the terminal box when unbrazing or
brazing compressor refrigerant piping connections
Compressor Crankcase Heaters
Compressor crankcase heaters must be energized
at least eight hours before starting the chiller. This is
required to boil refrigerant out of the oil before startup.
Ambient temperature is not a factor and the crankcase
heaters must always be energized prior to startup.
Evaporator Maintenance
The Trane Model CGAX liquid chiller uses a brazed plate
heat paddle (BPHE) evaporator with factory installed
flow switch that is positioned in the evaporator water
pipe. The evaporator inlet also includes a water strainer
that must be kept in place to keep debris out of the
evaporator.
Note: Strainer maintenance is critical to proper operation
and reliability. Any particles larger than 1.6 mm entering
the BPHE evaporator may cause the evaporator to fail,
requiring replacement.
Acceptable BPHE evaporator water flow rate is 1.4 to
4.2 l/ min per nominal unit kW capacity. To maintain
12-7°C in/out chilled water temperatures, the nominal
water flow rate is 2.8 l/min per cooling kW. Minimum
water flow rate must be maintained to avoid laminar
flow, potential evaporator freezing, scaling and poor
temperature control. Maximum water flow is 6 m/s. Flow
rates greater than this will cause excessive erosion. The
BPHE evaporator is difficult to clean should it become
plugged with debris. Indications of a plugged BPHE
evaporator include “wet” suction due to lack of heat
exchange, loss of superheat control, discharge superheat
less than 35°C, compressor oil dilution and/or starvation
and premature compressor failure.
Condenser Maintenance
Condenser Coil Cleaning
Clean the condenser coils at least once a year or
more frequently if the unit is in a “dirty” environment.
A clean condenser coil will help to maintain chiller
operating efficiency. Follow the detergent manufacturer’s
instructions to avoid damaging the condenser coils.
Black epoxy coil protection (option on heat pump units)
It is recommended to clean the coils at unit start-up and
regularly to obtain optimum protection and life span of
the condenser coils. To clean the condenser coils use a
soft brush and a sprayer such as a garden pump type or
a high pressure type. A high quality detergent such as
Trane Coil Cleaner is recommended.
Note: If detergent mixture is strongly alkaline (pH value
greater than 8 .5), an inhibitor must be added.
Evaporator replacement
If the CGAX evaporator requires replacement, it is very
important that the new evaporator be replaced correctly
and with the correct refrigerant and water piping
connections. The refrigerant inlet/ liquid connection is at
the bottom of the evaporator and the refrigerant outlet/
suction connection is at the top of the evaporator and
both are on the same side. Pay particular attention to
evaporators with dual circuits. Avoid cross-circuiting
when installing the new evaporator.
48
CG-SVX027D-GB
Maintenance
Cleaning Procedures
It is mandatory to clean regularly the coils for a proper
unit operation. Eliminate pollution and other residual
material help to extend the life of the coils and the unit
CAUTION! Equipment Damage! Do not use coil cleaning
agents to clean uncoated CGAX coils. Use clean water
only. Use of coil cleaning agents on uncoated CGAX
coils could cause damage to coils.
Regular coil maintenance, including frequent cleaningenhances the unit’s operating efficiency by minimizing
compressor head pressure and amperage draw. The
condenser coil (non-coated and e-coated) should be
cleaned at least once each quarter or more if the unit is
located in a “dirty” or corrosive environment. Cleaning
with cleansers or detergents is strongly discouraged due
to the all-aluminum construction; straight water should
prove sufficient. Any breach in the tubes can result in
refrigerant leaks
Important: Only in extreme cases should any type of
chemical cleaner or detergent be used on micro channel
coils. If it becomes absolutely necessary because water
alone did not clean the coil, specify a cleaner that is:
• A is pH neutral cleaner.
• An alkaline cleaner that is no higher than 8 on
the pH scale.
• An acidic cleaner that is no lower than 6 on the
pH scale.
• Does not contain any hydrofluoric acids.
Be sure to follow the instructions provided with any
cleaner chosen. Keep in mind that it is still MANDATORY
that the coils are thoroughly rinsed with water after the
application of the cleaner even if the instructions specify
a “No Rinse” cleaner. Cleaners or detergents that are
left on the coil due to improper rinsing will significantly
increase the possibility of corrosion damage on the
micro channel coil.
Note: Quarterly cleaning (or more for harsh
environment) is essential to extend the life of a MCHE
coil and is required to maintain warranty coverage.
Failure to clean a MCHE coil will void the warranty and
may result in reduced efficiency and durability in the
environment.
WARNING! Hazardous Voltage! Disconnect all electric
power, including remote disconnects before servicing.
Follow proper lockout/ tagout procedures to ensure the
power cannot be inadvertently energized. Failure to
disconnect power before servicing could result in death
or serious injury.
1. Disconnect Power to the unit.
2. Wear proper personal protection equipment such
as a face shield, gloves and waterproof clothing.
3. Remove enough panels from the unit to gain safe
access to the micro channel coil.
Note: It is better to clean the coil from the opposite
direction of normal air flow (inside of unit out) because
this allows the debris to be pushed out rather than
forced further into the coil.
1. Use a soft brush or vacuum to remove base debris
or surface loaded fibers from both sides of the coil.
Note: Remove solid residue is essential to preserve
performance of the coil and avoid corrosion over the
length of the product life.
2. Using a sprayer and water ONLY, clean the coil
following the guidelines below.
a. Sprayer nozzle pressure should not exceed
40 bars.
b. The maximum source angle should not exceed
25 degrees (Figure 22) to the face of the coil.
For best results spray the micro channel
perpendicular to face of the coil.
c. Spray nozzle should be approximately 5 to 10 cm
from the coil surface.
d. Use at least a 15º fan type of spray nozzle.
Figure 14 - Sprayer source angle
To avoid damage from the spray wand contacting the
coil, make sure the 90º attachment does not come in
contact with the tube and fin as abrasion to the coil
could result.
Maintenance of Flanges Connection
It is mandatory to apply marine grease all around the
coil flange connections to the piping on a regular basis
(for instance twice a year) to avoid traps of moisture and
dirt in the gasket recess.
Repair / Replacement of Micro
channel Coil
Micro channel coils are considerably more robust in
design than tube and fin condenser coils, however they
are not indestructible. When damage or a leak occurs in
the field, it is possible to temporarily repair the coil until
another coil can be ordered.
If the leak is found to be within the tube area of the coil,
a field repair kit (KIT16112) is available through your
local Trane parts center. Because of the all-aluminum
construction and aluminum’s high thermal expansion
rate, a leak located at or on the header assembly cannot
be repaired.
CG-SVX027D-GB
49
Maintenance
Water pump maintenance
WARNING! Before starting work on the pump, make sure
that the power supply has been switched off and that it
cannot be accidentally switched on. The internal pump
parts are maintenance-free. It is important to keep the
motor clean in order to ensure adequate cooling of the
motor. If the pump is installed in dusty environments,
it must be cleaned and checked regularly. Take the
enclosure class of the motor into account when cleaning.
The motor has maintenance-free, greased-for-life
bearings.
If the water loop must be emptied during period of frost,
the pump has to be drained to avoid damage.
Remove the filling and drain plugs.
Do not refit the plugs until the pump is taken into
operation again.
Figure 15 - Water pump plug locations
A = Filling plug
B = Drain plug
50
CG-SVX027D-GB
Troubleshooting Guide
This troubleshooting guide is not a comprehensive analysis of the Scroll compressor refrigeration system. The aim is
to give operators simple instructions on basic unit processes so that they have the technical knowledge to identify and
bring defective operations to the notice of qualified technicians.
Problems SymptomsProblem causesAction Recommended
(A) Compressor does not start up
Compressor terminals are live but
motor does not start
Contactor motor no operational
No current ahead of motor
contactor
Current ahead of fuse, but not on
contactor side
Low Voltage reading on
voltameter
Starter coil not excitedRegulation circuit open
Compressor does not run.
Compressor motor “groans”
High pressure switch tripped to
contacts open on high pressure.
Discharger pressure too high
Excess cooling demand on
evaporator:
(a) Expansion valve too far open
(b) Expansion valve locked in an
open position
Filter drier clogged.
Expansion valve not operating
properly
Excessive pressure drops through
evaporator
Lowwaterowrate
ContactTraneofcebefore
ordering oil
Adjust superheat and check bulb
xingoftheexpansionvalve
(a) Check superheat setting
(b) Repair or replace EXV
Check refrigerant circuit tightness
and add refrigerant
Check adjustment of superheat
and adjust expansion valve
Purgeuncondensableuidsand
drain off excess refrigerant
Reduce load on system.
Reducewaterowifnecessary
Cleanandreplaceairlters.Clean
coils. Check operation of the fan
motors
Check system:
(a) Check the superheat and check
that expansion valve
(b) Replace EXV
Replacelterdrier
Replace EXV
Check adjustment of superheat an
adjust EXV
Checkwaterowrate.Check
state of strainer, check for
obstruction in chilled water pipes,
check pressure switch contact in
water
52
CG-SVX027D-GB
Notes
CG-SVX027D-GB
53
Notes
54
CG-SVX027D-GB
Notes
CG-SVX027D-GB
55
Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the leader
in creating and sustaining safe, comfortable and energy efficient environments, Trane offers a broad portfolio
of advanced controls and HVAC systems, comprehensive building services and parts. For more information visit
www.Trane.com