Trane BAYHTRS409, BAYHTRS318, BAYHTRS418, BAYHTRS427, BAYHTRS436 Installer's Manual

...
Installer’s Guide
Electric Heaters
6-10 Ton Packaged Cooling
November 2009
Model Number Used With
See ‘General Information’ section in this guide
ACC-SVN67D-EN
Warnings, Cautions and Notices. Note that warnings, cautions and notices appear at
appropriate intervals throughout this manual. Warnings are provided to alert installing contractors to potential hazards that could result in personal injury or death. Cautions are designed to alert personnel to hazardous situations that could result in personal injury, while notices indicate a situation that could result in equipment or property-damage-only accidents.\ Your personal safety and the proper operation of this machine depend upon the strict observance of these precautions.
ATTENTION: Warnings, Cautions and Notices appear at appropriate sections throughout
this literature. Read these carefully.
WARNING: Indicates a potentially hazardous situation which, if not avoided, could
result in death or serious injury.
CAUTION: Indicates a potentially hazardous situation which, if not avoided, could
result in minor or moderate injury. It could also be used to alert against unsafe practices.
NOTICE: Indicates a situation that could result in equipment or property-damage-only
accidents.
Important Environmental Concerns!
Scientific research has shown that certain man-made chemicals can affect the earth's naturally occurring stratospheric ozone layer when released to the atmosphere. In particular, several of the identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact to the environment. Trane advocates the responsible handling of all refrigerants-including industry replacements for CFCs such as HCFCs and HFCs.
Responsible Refrigerant Practices!
Trane believes that responsible refrigerant practices are important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified. The Federal Clean Air Act (Section 608) sets forth the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these service procedures. In addition, some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them.
WARNING
Personal Protective Equipment (PPE) Required!
Installing/servicing this unit could result in exposure to electrical, mechanical and chemical hazards.
Before installing/servicing this unit, technicians MUST put on all Personal Protective Equipment (PPE) recommended for the work being undertaken. ALWAYS refer to appropriate MSDS sheets and OSHA guidelines for proper PPE.
When working with or around hazardous chemicals, ALWAYS refer to the appropriate MSDS sheets and OSHA guidelines for information on allowable personal exposure levels, proper respiratory protection and handling recommendations.
If there is a risk of arc or flash, technicians MUST put on all necessary Personal Protective Equipment (PPE) in accordance with NFPA70E for arc/flash protection PRIOR to servicing the unit.
Failure to follow recommendations could result in death or serious injury.
© 2009 Trane All rights reserved ACC-SVN67D-EN
Table of Contents
General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Table 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Table 2. TCO-A replaced for Horizontal Duct Configuration . . . . . . . . . . . . . . . 8
Table 3. Air temperature rise (60 hz). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Table 4. Unit wiring with electric heat (single point connection) - standard effi­ciency Table 5. Unit wiring with electric heat - heat pump - (single point connection) ­standard efficiency Table 6. Unit wiring with electric heat (single point connection) - high efficiency
- 6-10 tons
Table 7. Air temperature rise 380/415 Volt (50 hz) . . . . . . . . . . . . . . . . . . . . . 18
Table 8. Air temperature rise 380/415 Volt (50 hz) . . . . . . . . . . . . . . . . . . . . . 18
Table 9. Cooling only units with electric heater — single power source — 380/415 Volt (50hz) Table 10. Heat pump units with electric heater — single power source — 380/415 Volt (50hz)
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
ACC-SVN67D-EN 3
General Information
Ta b le 1 .
Model Number Used With
BAYHTRS309
BAYHTRS318
BAYHTRS327
BAYHTRS336
BAYHTRS409
BAYHTRS418
BAYHTRS436
BAYHTRSW09
BAYHTRSW18
BAYHTRSW27
BAYHTRSW36
BAYHTRT309
BAYHTRT318
BAYHTRT327
BAYHTRT336
BAYHTRT409
BAYHTRT418
BAYHTRT427 TSC092E4 TSC102E4 TSC102ED
BAYHTRT436 TSC120ED WSC120ED
BAYHTRT454
BAYHTRTW18
BAYHTRTW36
BAYHTRA318
BAYHTRA327 TSC120E3
BAYHTRA336 TSC120E3
BAYHTRA354 TSC120E3
BAYHTRA418 TSC120E4
BAYHTRA427 TSC120E4
BAYHTRA436 TSC120E4
BAYHTRA454 TSC120E4
BAYHTRAW18 TSC120EW
BAYHTRAW36 TSC120EW
BAYHTRAW54 TSC120EW
BAYHTRB318 WSC120E3
BAYHTRB327 WSC120E3
BAYHTRB336 WSC120E3
BAYHTRB354 WSC120E3
BAYHTRB418 WSC120E4
BAYHTRB427 WSC120E4
BAYHTRB436 WSC120E4
BAYHTRB454 WSC120E4
TSC072E3
TSC072E4
TSC072E4
TSC072EW
TSC092E3 TSC102E3
TSC092E4 TSC102E4
TSC120ED WSC120ED
TSC092EW TSC102EWBAYHTRTW27
TSC120E3
TSC072ED
WSC072ED
WSC090ED
TSC090EDBAYHTRS427
4 ACC-SVN67D-EN
Ta b le 1 .
BAYHTRBW18 WSC120EW
BAYHTRBW36 WSC120EW
BAYHTRBW54 WSC120EW
BAYHTRD309 THC092E3 THC102E3
BAYHTRD318 THC092E3 THC102E3 THC120E3
BAYHTRD327 THC092E3 THC102E3 THC120E3
BAYHTRD336 THC092E3 THC102E3 THC120E3
BAYHTRD354 THC120E3
BAYHTRD409 THC092E4 THC102E4
BAYHTRD418 THC092E4 THC102E4 THC120E4
BAYHTRD427 THC092E4 THC102E4 THC120E4
BAYHTRD436 THC092E4 THC102E4 THC120E4
BAYHTRD454 THC120E4
BAYHTRU309 THC072E3 WSC090E3
BAYHTRU318 THC072E3 WSC090E3
BAYHTRU327 THC072E3 WSC090E3
BAYHTRU336 THC072E3 WSC090E3
BAYHTRU409 THC072E4 WSC090E4
BAYHTRU418 THC072E4 WSC090E4
BAYHTRU427 THC072E4 WSC090E4
BAYHTRU436 THC072E4 WSC090E4
BAYHTRUW18 THC072EW WSC090EW
BAYHTRUW27 THC072EW WSC090EW
BAYHTRUW36 THC072EW WSC090EW
BAYHTRW309 TSC090E3 WSC072E3
BAYHTRW318 TSC090E3 WSC072E3
BAYHTRW327 TSC090E3 WSC072E3
BAYHTRW336 TSC090E3 WSC072E3
BAYHTRW409 TSC090E4 WSC072E4
BAYHTRW418 TSC090E4 WSC072E4
BAYHTRW427 TSC090E4 WSC072E4
BAYHTRW436 TSC090E4 WSC072E4
BAYHTRWW18 TSC090EW WSC072EW
BAYHTRWW27 TSC090EW WSC072EW
BAYHTRWW36 TSC090EW WSC072EW
General Information
ACC-SVN67D-EN 5
General Information
General
ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES. Installer must mark unit nameplate with Heater Information per instructions on nameplate.
Note: If digit 9 in the unit model number equals "E" (Electro Mechanical Control), accessory relay
Figure 1. Electro Mechanical wiring diagram
BAY24X042 is required if the thermostat does not energize the fan circuit in the heating mode. See Figure 1 for wiring information.
Inspection
1. Unpack all components of the kit.
2. Check carefully for any shipping damage. If any damage is found it must be reported immediately and a claim made against the transportation company.
3. Check the heater nameplate model number and compare with Tab l e 4 , p . 14 , Table 5, p. 16,
Table 6, p. 17, Table 9, p. 19, or Tab le 10 , p . 1 9. Ensure that the available power supply and unit's
model number complies with the particular heater being used.