Trane AUX2B060AFV3VA, AUX2C100AFV4VA, TUX2B060AFV3VA, AUX2D120AFV5VA, AUX2B080AFV3VA Installer's Manual

...
Page 1
18- CD25D1- 2
Installer’s Guide
Upflow/ Horizontal, Gas-Fired, Direct Vent, 2-Stage Condensing Furnaces with Variable Speed Inducer and Whole House Air Cleaner
*UX2B060AFV3VA *UX2C100AFV4VA *UX2B080AFV3VA *UX2D120AFV5VA
*__First letter may be “A” or “T”
ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES
Available in French Canadian (FC)
IMPORTANT — This Document is customer property and is to remain with this unit.
Please return to service information pack upon completion of work.
UPFLOW/ HORIZONTAL
UPFLOW
Bottom Return ONLY
This unit is equipped with an integrated high efficiency Whole House Air Cleaner. Careful consideration must be taken in the installation process to avoid personal in­jury, property damage or equipment damage. These in­structions do not cover all variations in systems or pro­vide for every possible contingency. Should further in­formation be desired or particular problems arise which are not covered sufficiently by this manual, contact your local distributor or the manufacturer as listed on the Furnace nameplate. In addition, these Furnaces are suitable for installation in an attic, garage or crawl space with ducted supply and return air.
Safety signal words are used to designate a degree or level of seriousness associated with a particular hazard. The signal words for safety markings are WARNING, and CAUTION.
a. WARNING indicates a potentially hazardous situa-
tion which, if not avoided, could result in death or serious injury.
b. CAUTION indicates a potentially hazardous situation
which, if not avoided, may result in minor or mod­erate injury. It is also used to alert against unsafe practices and hazards involving only property dam­age.
Page 2
Installer’s Guide
SAFETY SECTION
!
WARNING
CARBON MONOXIDE POISONING HAZARD Failure to follow the steps outlined below for each ap­pliance connected to the venting system being placed into operation could result in serious carbon monox­ide poisoning or death.
The following steps shall be followed for each appliance connected to the venting system being placed into op­eration while all other appliances connected to the venting system are not in operation.
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and hori­zontal pitch, as required in the National Fuel Gas Code, ANSI Z223.1/NFPA 54 or the CSA B149.1 Natural Gas and Propane Installation Code and these instruction. Determine that there is no blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe con­dition.
3. As far as practical, close all building doors and win­dows and all doors between the space in which the appliance(s) connected to the venting system are lo­cated and other deficiencies which could cause an unsafe condition.
4. Close fireplace dampers.
5. Turn on clothes dryer and any appliance not con­nected to the venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they are operating at maximum speed. Do not operate a summer exhaust fan.
6. Follow the lighting instructions. Place the appli­ance being inspected into operation. Adjust the thermostat so appliance is running continuously.
7. Test for spillage from draft hood equipped appli­ances at the draft hood relieve opening after 5 min­utes of main burner operation. Use the flame of a match or candle.
8. If improper venting is observed during any of the above tests, the venting system must be corrected in accordance with the National Fuel Gas Code, ANSI Z221.1/NFPA 54 and/or CSA B149.1 Natural Gas and Propane Installation Code.
9. After it has been determined that each appliance connected to the venting system properly vents where tested as outlined above, return doors, win­dows, exhaust fans, fireplace dampers and any other gas-fired appliances to their previous condi­tion of use.
!
WARNING
Failure to follow the safety warnings exactly could re­sult in a fire or explosion causing property damage, personal injury or loss of life.
-- Do not store or use gasoline or flammable vapors and liquids in the vicinity of this or any other appliance.
-- WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance
Do not touch any electrical switch;
do not use any phone in your building
Immediately call your gas supplier from a neighbor's
phone. Follow the gas supplier's instructions.
If you cannot reach your gas supplier.
call the fire department.
-- Installation and service must be performed by a qualified installer, service agency or the gas supplier.
!
WARNING
FIRE OR EXPLOSION HAZARD Failure to follow the safety warnings exactly could re­sult in serious injury, death or property damage. Improper servicing could result in dangerous opera­tion, serious injury, death, or property damage.
The following safety practices and precautions must be followed during the installation, servicing, and operation of this Furnace.
1. Use only with the type of gas approved for this Fur­nace. Refer to the Furnace rating plate.
2. Install this Furnace only in a location and position as specified in “Location and Clearances” (page 4) of these instructions.
3. Provide adequate combustion and ventilation air to the Furnace space as specified in “Air for Combus­tion and Ventilation” (page 9), of these instructions.
4. Combustion products must be discharged outdoors. Connect this Furnace to an approved vent system only, as specified in the “Venting” section (pages 11-
23), of these instructions.
5. Never test for gas leaks with an open flame. Use a commercially available soap solution made specifi­cally for the detection of leaks to check all connec­tions, as specified in the “Gas Piping” section of these instructions on page 31.
6. Always install the Furnace to operate within the Furnace’s intended temperature-rise range with a duct system which has an external static pressure within the allowable range, as specified on the unit rating plate. Airflow with temperature rise for cfm versus static is shown in the Service Facts accompa­nying this Furnace.
© 2008 Trane All Rights Reserved 18-CD25D1-2
Page 3
Installer’s Guide
7. When a Furnace is installed so that supply ducts carry air circulated by the Furnace to areas outside the space containing the Furnace, the return air shall also be handled by a duct(s) sealed to the Fur­nace casing and terminating outside the space con­taining the Furnace.
8. A gas-fired Furnace for installation in a residential garage must be installed as specified in “Location and Clearances” section (page 4) , of these instruc­tions.
9. The Furnace may be used for temporary heating of buildings or structures under construction when the following conditions have been met: a. The Furnace venting system must be complete and installed per manufacturers instructions. b. The Furnace is controlled only by a room Com­fort Control (no field jumpers). c. The Furnace return air duct must be complete and sealed to the Furnace. d. The Furnace input rate and temperature rise must be verified to be within nameplate marking. e. 100% of the Furnace combustion air require­ment must come from outside the structure. f. The Furnace return air temperature range is between 55 g. Clean the Furnace, duct work, and components upon substantial completion of the construction pro­cess, and verify Furnace and whole house air cleaner operating conditions including ignition, in­put rate, temperature rise and venting, according to the manufacturer's instructions. h. Remove the Whole House Air Cleaner and store in clean dry location during the construction process. To be reinstalled when construction is com­plete. See page 39 for proper air cleaner removal. i. An external field supplied air filter must be used during construction.
0
and 800 Fahrenheit.
only
Contents
Safety Section 2
Installation Instructions 4
General 4 Location and Clearances 4
Outline Drawings 6
Upflow Installation 7 Horizontal Installation 7 Air For Combustion and Ventilation 9 Duct Connections 10 General Venting 11 Venting Materials 12 Vent Tables 15 Horizontal Venting Through Wall 17 Venting Through The Roof 19 Venting Routed Through a Masonry Chimney 20 Downward Venting 22 Condensate Drain Instructions 24
Field Wiring Diagrams 26
Electrical Connections 31 Gas Piping 31 Combustion and Input Check 33 High Altitude Derate 34
Start-up and Adjustment 35
Preliminary Inspections 35 Lighting Instructions 35 Sequence of Operation 36 Control and Safety Switch Adjustments 36
Conditions Affecting System Operation 38
Whole House Air Cleaner Maintenance 39
IFC Error Flash Codes 41
Checkout Procedure 43
10. This product must be gas piped by a Licensed
!
Plumber or Gas Fitter in the Commonwealth of Massachusetts.
!
CAUTION
To prevent shortening its service life, the Furnace should not be used as a “Construction Heater” during the finishing phases of construction until the require­ments listed in item 9, a-i of the safety section of this publication have been met. Condensate in the pres­ence of chlorides and fluorides from paint, varnish, stains, adhesives, cleaning compounds, and cement create a corrosive condition which may cause rapid deterioration of the heat exchanger.
!
CAUTION
Chemicals used to during construction may cause damage to the COLLECTION CELL.
18-CD25D1-2 3
DO NOT USE SEMI-RIGID METALLIC GAS CONNEC­TORS (FLEXIBLE GAS LINES) WITHIN THE FURNACE CABINET. FAILURE TO FOLLOW THIS WARNING COULD RESULT IN PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
WARNING
Page 4
Installer’s Guide
GENERAL INSTALLATION INSTRUCTIONS
The manufacturer assumes no responsibility for equip­ment installed in violation of any code or regulation. It is recommended that Manual J of the Air Condition­ing Contractors Association (ACCA) or A.R.I. 230 be fol­lowed in estimating heating requirements. When esti­mating heating requirements for installation at Alti­tudes above 2000 ft., remember the gas input must be reduced (See combustion and input check page 31).
Material in this shipment has been inspected at the factory and released to the transportation agency without known damage. Inspect exterior of carton for evidence of rough handling in ship­ment. Unpack carefully after moving equipment to approximate location. If damage to contents is found, report the damage immediately to the de­livering agency.
Codes and local utility requirements governing the installation of gas fired equipment, wiring, plumbing, and flue connections must be adhered to. In the ab­sence of local codes, the installation must conform with latest edition of the National Fuel Gas Code ANSI Z223.1 • National Installation Code, CAN/CGA B149.1. The latest code may be obtained from the American Gas Association Laboratories, 400 N. Capitol St. NW, Washington D.C. 20001. 1-800-699-9277 or www.aga.org These Furnaces have been classified as CATEGORY IV furnaces in accordance with latest edition of ANSI Z21.47 standards • CSA 2.3. Category IV furnaces oper­ate with positive vent static pressure and with a flue loss less than 17 percent. These conditions require spe­cial venting systems, which must be gas tight and water tight. These Category IV Direct Vent Furnaces are ap­proved for installation in Manufactured/ Mobile housing when used with BAYMFGH001A.
LOCATION AND CLEARANCES
!
WARNING
Do NOT install the Furnace directly on carpeting, tile or other combustible material other than wood flooring.
!
CAUTION
Do NOT install the Furnace in a corrosive or contami­nated atmosphere. Failure to follow this warning could result in early equipment failure.
The location of the Furnace is normally selected by the architect, the builder, or the installer. However, before the Furnace is moved into place, be sure to consider the following requirements:
1. Is the location selected as near the chimney or vent and as centralized for heat distribution as practical?
2. Do all clearances between the Furnace and enclo­sure equal or exceed the minimums stated in Clearance Table on the Outline Drawings?
3. Is there sufficient space for servicing the Furnace and other equipment? A minimum of 24 inches front accessibility to the Furnace must be provided. Any access door or panel must permit removal of the largest component.
4. Are there at least 3 inches of clearance between the Furnace combustion air openings in the front panel and any closed panel or door provided?
5. Are the ventilation and combustion air openings large enough and will they remain unobstructed? If outside air is used, are the openings set above the highest snow accumulation level? (See the Air for Combustion and Ventilation section, page 8)
6. A heavy gauge steel plate is attached to the
bottom of the unit for protection during ship­ping and handling prior to the unit installa­tion. Leave this plate in place until the unit is ready to be connected to the ductwork.
7. A Pre-filter is the furnace containing a Whole House Air Clean­er. If the use of a Pre-Filter is desired, it must be installed at least 6" away from the Whole House Air Cleaner. The additional pressure drop of the Pre-Filter must be considered during duct design or evaluation to ensure proper airflow.
8. Allow sufficient height in supply plenum above the Furnace to provide for cooling coil installation, if the cooling coil is not installed at the time of this Furnace installation.
IMPORTANT: The Furnace must be installed level. The only allow­able variation would be slightly to the left and/ or for­ward in upflow installations or slightly toward the front in horizontal installations. This is necessary for proper condensate drainage.
9. A Furnace shall be installed so electrical compo­nents are protected from water.
10. DO NOT use silicon based sealant in the airstream. This causes a coating on the FIELD CHARGER pins that will decrease the efficiency of the air cleaner.
11. Allow a minimum of 24 inches clearance in front of the air cleaner to permit removal of COLLECTION CELL and FIELD CHARGER.
12. Do Not install furnace where the air cleaner can be exposed to UV light.
not required to be installed with
4 18-CD25D1-2
Page 5
Installer’s Guide
NOTE: Do NOT install an atomizing style humidifier in the return plenum of this unit.
13. Flow-through Bypass Humidifiers
Excessive bypass air may cause water blow-off, which will adversely affect system operation and air cleaner performance. To verify bypass airflow, fol­low the Bypass Humidifier Pre-Installation Check­out and Set-Up Procedures available through your local distributor. Ask for publication number 18­CH37D1-1.
Steam and Flow-through Fan Power Duct­mounted Humidifiers
Follow the humidifier installation instructions. These should only be installed on the supply air side of the system.
Other Duct Mounted Humidifiers are not rec­ommended for installation with the air cleaner.
Figure 1. COMPONENTS OF THE INTEGRATED WHOLE HOUSE AIR CLEANER
14. If the Furnace is installed in a residential garage,
it must be installed so that the burners, and the ig­nition source are located not less than 18 inches above the floor and the Furnace must be located or protected to avoid physical damage from vehicles.
15. The whole house air cleaner is designed to run at a maximum indoor relative humidity of 65%.
1
Components of the integrated Whole House Air Cleaner:
1) FIELD CHARGER - Charges the contaminants
2) COLLECTION CELL - removes and collects very small
impurities from the air.
3) Power Supply - the solid state power supply converts the 24 Volt AC to the high-voltage, direct current required to power the FIELD CHARGER and COLLECTION CELL.
Check carefully for any shipping damage. This must be reported to and claims made against the transpor­tation company immediately. Check to be sure all major components are in the unit. Any missing parts should be reported to your supplier at once, and replaced with authorized parts only.
3
2
18-CD25D1-2 5
Page 6
Installer’s Guide
(ALL DIMENSIONS ARE IN INCHES)
*UX2 UPFLOW/ HORIZONTAL OUTLINE DRAWING
6 18-CD25D1-2
Page 7
Installer’s Guide
INSTALLATION INSTRUCTIONS
!
CAUTION
Bottom panel for furnace to remain in place until unit reaches final installation location. If bottom panel is removed before installation the COLLEC­TION CELL and FIELD CHARGER must also be re­moved to protect installation personnel.
!
CAUTION
Remove the COLLECTION CELL and remove and dis­card the cardboard over the cell.
NOTE: No sheetmetal screws may be used from 0-4" from the bottom of the unit. Screws will interfere with the Air Cleaner. See Figure 4.
REMOVING THE BOTTOM PLATE
a. Once the furnace is in place, remove the two screws
located at the front bottom corners of the furnace.
b. Lean the furnace back slightly and remove the bot-
tom panel.
c. Replace the two screws removed in step a.
REMOVING THE COLLECTION CELL AND FIELD CHARGER
When COLLECTION CELLS and FIELD CHARGER must be removed, follow the steps below. a. Remove the lower furnace door. b. Remove the four screws holding the inner blower
panel and remove panel. Set aside in a safe place until the unit is set in place and ready to start up.
d. Remove the COLLECTION CELL by sliding for-
ward. TION CELL and discard. Set aside in a safe place until the unit is set in place and ready to start up.
e. Disconnect the Green return wire and the Red high
voltage wire. Twist and pull the connector on the Red wire to release.
f. Remove the two hold down screws on the bottom of
the FIELD CHARGER and retain.
g. Remove the Field Charger. Set aside in a safe place
until the unit is set in place and ready to start up.
h. Set furnace in place. Repeat step a-g in reverse or-
der. Do Not put cardboard back in furnace. Inner blower door MUST be put back into place.
UPFLOW INSTALLATION
Standoffs and screws (See Figure 2) are included with the cased coils for attachment to the Furnace. There are clearance alignment holes near the bottom of the coil wrapper. Drill screws are used to engage the Furnace top flanges. The standoff is inserted into the cabinet align­ment hole. The drill screws are inserted through the standoffs then screwed into the Furnace flange. The coil is always placed downstream of the Furnace airflow. The above instructions apply only if the coil is on top of an upflow Furnace.
Remove the cardboard from the COLLEC-
C
UPFLOW
FURNACE
A
S
E
D
C
O
IL
SCREWS
(BOTH SIDES)
STANDOFFS
(BOTH SIDES)
FOR VERTICAL
STANDOFFS (4)
DRILL SCREWS (4)
Figure 2
HORIZONTAL INSTALLATION
The coil and Furnace must be fully supported when used in the horizontal position. It is always recom­mended that an auxiliary drain pan be installed under a horizontally installed evaporator coil or 90% Gas Fur­nace. Connect the auxiliary drain line to a separate drain line (no trap is needed in this line).
IMPORTANT: The 2/4TXC cased coil must be placed downstream of the furnace. In horizontal installations, the apex of the coil may point either toward or away from the furnace. See the 2/4TXC coil Installer's Guide for more details.
The cased coil is secured to the Furnace and both the Furnace and the cased coil must be properly supported. The brackets mount using the rear screws on the coil case and use the screws provided to secure the bracket to the Furnace. The remaining bracket is placed as close to center as possible (horizontally) between the coil case front and the upflow Furnace, converted to horizontal, aligns and attaches to the TXC coil. How­ever, the coil requires additional support. The Furnace may be installed in an attic or crawl space in the horizontal position by placing the Furnace on the left side (as viewed from the front in the vertical posi­tion). The horizontal Furnace installation in an attic should be on a service platform large enough to allow for proper clearances on all sides and service access to the front of the Furnace (See Figure 3 & Clearance Table 1). Line contact is only permissible between lines formed by intersections of the top and two sides of the furnace casing and building joists, studs, or framing.
Figure 3
UPFLOW/ HORIZONTAL SHOWN WITH DIRECT VENT
18-CD25D1-2 7
Page 8
Installer’s Guide
The Furnace may be placed horizontally in a crawl space on a pad or other noncombustible material which will raise the unit for sufficient protection from mois­ture.
The Furnace must be supported at both ends and the middle when installed horizontally. The Furnace must also be elevated approximately 4-6 inches to allow clearance for the condensate drain to exit the cabinet in the horizontal position.
The horizontal Furnace may also be suspended from the joists using all-thread rods with a substantial metal support frame that supports the entire length of the furnace. The rods need to be of sufficient length to allow for proper clearances from combustible materials. The frame needs to be at least 32" in length to allow for access to service panels. If the Furnace is suspended using steel strap, it must be supported at all four corners and in the middle at the front of the Furnace.
NOTE: No sheet­metal screws may be used from 0-4" from the bottom of the unit. Screws will in­terfere with the air cleaner.
2. Attach flanges 1, 2, and 3 (Fig 7) to the unit using the factory provided screws and the pre-drilled holes in the wrapper. Flanges 1 and 2 are the
23.5" flanges that are generic to all units. Flange 3 will be one of two short flanges and the length of which is dependent on the cabinet size.
3. Attach flange 4 (Fig 7) to the duct work (Flanges should be inside duct work). Flange 4 is the remaining short flange.
4. Place duct work with single flange over the flanges that are currently attached to the unit
5. Attach duct work to remaining 3 flanges.
6. Attach the front flange from step 3 to the unit by drilling 1/8" holes into the bottom channel. Use the factory provided 5/16" blunt tip screws to attach.
7. Use field supplied material to make an adequate seal.
DO NOT use silicon based sealant in the airstream.
Figure 5: Horizontal Left
Figure 4
NOTE: Do NOT install screws to the bottom of the unit except with Duct Flanges and Screws provided.
GUIDE FOR THE INSTALLATION OF DUCT FLANGES
Failure to use pre-drilled holes and the factory provided screws can potentially damage air cleaner components.
Materials
Duct Flanges Two 23.5" Flanges Two Additional Flanges
15.92" (for 17.5" cabinet)
19.42" (for 21" cabinet)
21.92" (for 24.5" cabinet)
Screws Eight 5/16" Blunt Tip Screws with 5/16" Hex Head
Steps
1. See Figures 5, 6, and 7 for flange orientation.
"
!
CAUTION
Use pre-drilled holes
1
4
Figure 6: Bottom View - Pre-drilled holes
Use pre­drilled holes
3
2
Use pre­drilled holes
8 18-CD25D1-2
Page 9
1
3
4
2
Figure 7: Bottom View ­Flange Attachment
Tab le 1
Minimum Clearance to Cumbustible Materials
Upflow Closet
Left Side 0 inches Front 3 inches (note 1)
Right Side 0 inches Back 0 inches
Flue 6 inches * Top 1 inch
Horizontal Closet
(see note 2)
Top 2 inches Back 3 inches
Flue 6 inches * Sides 1 inch
Front 18 inches (note 1)
Horizontal Alcove
(see note 2)
To p 1 i n c h B a c k 0 i n c h e s
Flue 6 inches Sides 0 inches
Front 18 inches
* May be 1" when type B-1 vent is used NOTES:
1) Minumum clearance to front on *UD2D120 is 6 inches
2) May be installed on combustible floor when type B-1 vent is used.
AIR FOR COMBUSTION AND VENTILATION
Adequate flow of combustion and ventilating air must not be obstructed from reaching the Furnace. Air open­ings provided in the Furnace casing must be kept free of obstructions which restrict the flow of air. Airflow re­strictions affect the efficiency and safe operation of the Furnace. Keep this in mind should you choose to re­model or change the area which contains your Furnace. Furnaces must have a free flow of air for proper perfor­mance.
Installer’s Guide
Provisions for combustion and ventilation air shall be made in accordance with “latest edition” of Section 5.3, Air for Combustion and Ventilation, of the National Fuel Gas Code, ANSI Z223.1, or Sections 7.2, 7.3 or 7.4 of CSA B149.1 Installation Codes, and applicable provi­sions of the local building codes. Special conditions cre­ated by mechanical exhausting of air and fireplaces must be considered to avoid unsatisfactory Furnace op­eration. Furnace locations may be in “confined space” or “uncon­fined space”. Unconfined space is defined in Table 2 and Figure 8. These spaces may have adequate air by infil­tration to provide air for combustion, ventilation, and dilution of flue gases. Buildings with tight construction (for example, weather stripping, heavily insulated, caulked, vapor barrier, etc.), may need additional air provided as described for confined space.
UNCONFINED
50 CU. FT. OR MORE PER 1000 BTU/ HR. INPUT ALL EQUIP. INSTALLED
Figure 8
TABLE 2
MINIMUM AREA IN SQUARE FEET
FOR UNCONFINED SPACE INSTALLATIONS
FURNACE
MAXIMUM BTUH
INPUT RATING
60,000
80,000 100,000 120,000 140,000
All air from inside the building as in Figure 10: The
1. confined space shall be provided with two perma­nent openings communicating directly with an addi­tional room(s) of sufficient volume so that the com­bined volume of all spaces meets the criteria for an unconfined space. The total input of all gas utiliza­tion equipment installed in the combined space shall be considered in making this determination. Refer to Table 3, for minimum open areas required.
2.
All air from outdoors as in Figure 11: The confined space shall be provided with two permanent open­ings, one commencing within 12 inches of the top and one commencing within 12 inches of the bot­tom of the enclosure. The openings shall communicate directly, or by ducts, with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors. Refer to Table 3, for minimum open areas required.
WITH 8 FT. CEILING
MINIMUM AREA IN SQUARE
FEET OF UNCONFINED SPACE
375 500 625 750 875
18-CD25D1-2 9
Page 10
Installer’s Guide
CONFINED
LESS THAN 50 CU. FT. PER 1000 BTU/ HR. INPUT ALL EQUIP INSTALLED
Figure 9
Air
From
Inside
100 100 100 120 140
TABLE 3
Air From Outside
Vertical
Duct
15 20 25 30 35
Horizontal
Duct
30 40 50 60 70
MINIMUM FREE AREA IN SQUARE INCHES
EACH OPENING (FURNACE ONLY)
Furnace
Maximum
BTUH/INPUT
Rating
60,000 80,000
100,000
120,000 140,000
Confined spaces are installations with less than 50 cu. ft. of space per 1000 BTU/ hr input from all equipment installed. Confined space is defined in Figure 9. Air for combustion and ventilation requirements can be sup­plied from inside the building as in Figure 10 or from the outdoors, as in Figure 11.
3. The following types of installations will require use
of OUTDOOR AIR for combustion, due to chemical exposures: * Commercial buildings * Buildings with indoor pools * Furnaces installed in commercial laundry rooms * Furnaces installed in hobby or craft rooms * Furnaces installed near chemical storage areas. Exposure to the following substances in the com­bustion air supply will also require OUTDOOR AIR for combustion: * Permanent wave solutions * Chlorinated waxes and cleaners * Chlorine based swimming pool chemicals * Water softening chemicals * Deicing salts or chemicals * Carbon Tetrachloride * Halogen type refrigerants * Cleaning solvents (such as perchloroethylene) * Printing inks, paint removers, varnish, etc. * Hydrochloric acid * Cements and glues * Antistatic fabric softeners for clothes dryers * Masonry acid washing materials
DUCT CONNECTIONS
Air duct systems should be installed in accordance with standards for air conditioning systems, National Fire Protection Association Pamphlet No. 90. They should be sized in accordance with ACCA Manual D or which­ever is applicable. Central Furnaces, when used in connection with cooling units, shall be installed in parallel or on the upstream side of the cooling coil to avoid condensation in the heat exchanger. With a parallel flow arrangement, the damp­ers or other means used to control flow of air shall be ad­equate to prevent chilled air from entering the Furnace, and if manually operated, must be equipped with means to prevent operation of either unit unless the damper is in full heat or cool position. On any job, flexible connections of nonflammable material may be used for return air and discharge connections to prevent transmission of vibration. Though these units have been specifically designed for quiet, vibration free op­eration, air ducts can act as sounding boards and could, if poorly installed, result in vibration to the annoyance level. When the Furnace is located in a utility room adjacent to the living area, the system should be carefully de­signed with returns to minimize noise transmission through the return air grille. Although these Furnaces are designed with large blowers operating at moderate speeds, any blower moving a high volume of air will produce audible noise which could be objectionable when the unit is located very close to a living area. It is often advisable to route the return air ducts under the floor or through the attic. Such design permits the in­stallation of air return remote from the living area (i.e. central hall). When the Furnace is installed so that the supply ducts carry air circulated by the Furnace to areas outside the space containing the Furnace, the return air shall also be handled by a duct(s) sealed to the Furnace and termi­nating outside the space containing the Furnace.
Where there is no complete return duct system, the return connection must be run full size from the Furnace to a location outside the utility room, basement, attic, or crawl space. Do NOT install return air through the back of the Fur-
nace cabinet.
Bottom Return Only
NOTE: Minimum return air temperature is 55° F.
NOTE: Extended warranties are not available in some instances. Extended warranty does not cover repairs to equipment installed in establishments with corrosive
NOTE: No sheetmetal screws may be used from 0-4" from the bottom of the unit. Screws will interfere with the air cleaner. See Figure 4.
atmospheres, including but limited to, dry cleaners, beauty shops, and printing facilities.
10 18-CD25D1-2
Page 11
Installer’s Guide
Figure 10
Figure 11
The following warning complies with State of California law, Proposition 65.
!
WARNING
Hazardous Gases!
Exposure to fuel substances or by-products of incomplete fuel combustion is believed by the state of California to cause cancer, birth defects, or other reproductive harm.
Carbon monoxide, fire or smoke can cause serious bodily injury, death, and/ or property damage. A variety of potential sources of carbon monoxide can be found in a building or dwelling such as gas-fired clothes dryers, gas cooking stoves, water heaters, Furnaces and fireplaces. The U.S. Consumer Product Safety Commis­sion recommends that users of gas-burning appliances install carbon monoxide detectors as well as fire and smoke detectors per the manufacturers installation in­structions to help alert dwelling occupants of the pres­ence of fire, smoke or unsafe levels of carbon monoxide. These devises should be listed by Underwriters Labora­tories, Inc. Standards for Single and Multiple Station Carbon Monoxide Alarms, UL 2034 or CSA Interna­tional Standard, Residential Carbon Monoxide Alarming Devices, CSA 6.19
NOTE: The manufacturer of your Furnace does NOT test any detectors and makes no representations regarding any brand or type of detector.
Connect duct work to Furnace. See Outline Drawing for supply and return duct size and location. Flexible duct connectors are recommended to connect both supply and return air ducts to the Furnace. If only the front of the Furnace is accessible, it is recommended that both supply and return air plenums are removable.
GENERAL VENTING
THIS FURNACE EXHAUST MUST BE VENTED TO THE OUTDOORS. THESE FURNACES ARE INDUCED DRAFT VENTED AND MUST NOT BE CONNECTED TO ANY VENT SERVING ANOTHER APPLIANCE. PLEASE NOTE THAT THESE FURNACES USE POSITIVE-PRESSURE VENT SYSTEMS. Proper venting is essential to obtain maximum effi­ciency from a condensing Furnace. Proper installation of the vent system is necessary to assure drainage of the condensate and prevent deterioration of the vent system. American Gas Association has certified the design of condensing Furnaces for a minimum of 0" clearance from combustible materials with a single wall plastic vent pipe.
18-CD25D1-2 11
Page 12
Installer’s Guide
The recommended system is assembled from 2", 2-1/2", or 3" plastic pipe and fittings (See Table 4, page 12). Where the system is routed to the outdoors through an existing masonry chimney containing flue products from another gas appliance, or where required by local codes, then 3" venting of Type 29-4C stainless steel must be used in place of PVC material. These Furnaces have been classified as CATEGORY IV Furnaces in accordance with ANSI Z21.47 “latest edi­tion” standards. Category IV Furnaces operate with positive vent pressure and with a vent gas temperature less than 140°F above the dewpoint. These conditions require special venting systems, which must be gas tight and water tight.
NOTE: When an existing Furnace is removed from a venting system serving other gas appliances, the vent­ing system is likely to be too large to properly vent remaining attached appliances.
The following steps shall be followed with each appli­ance remaining connected to the common venting sys­tem placed in operation, while the other appliances re­maining connected to the common venting system are not in operation.
1. Seal any unused openings in the common venting system.
2. Visually inspect the venting system for proper size and horizontal pitch and determine there is no blockage or restriction, leakage, corrosion or other deficiencies which could cause an unsafe condition.
3. In so far as is practical, close all building doors and windows and all doors between the space in which the appliances remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dryers and any appliances not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maxi­mum speed. Do not operate a summer exhaust fan, close fireplace dampers.
4. Follow the lighting instructions. Place the appliance being inspected in operation. Adjust Comfort Con­trol so appliance will operate continuously.
5. After it has been determined that each appliance re­maining connected to the common venting system properly vents when tested as outlined above, return door, windows, exhaust fans, fireplace dampers and any other gas-burning appliance to their previous conditions of use.
If improper venting is observed during any of the above tests, the remaining common venting system must be corrected. Correction could require rerouting or resizing the remaining vent system.
the
IMPORTANT:
These Furnaces may be installed as Direct Vent (sealed combustion) or as Nondirect Vent (single pipe). The Fur­naces are shipped DIRECT VENT with sealed combus­tion.
For DIRECT VENT APPLICATION: The Furnaces must be vented to the exterior of the house and com­bustion air MUST come through the inlet air pipe FROM OUTSIDE AIR.
NOTE: BAYVENT200* accessories can be used for inlet and outlet terminals when the pipes do not exit the structure together.
For NON-DIRECT VENT APPLICATION: The Fur- nace shall be vented to the exterior of the house, but combustion air may enter from the surrounding area as long as combustion air requirements are met. (See AIR FOR COMBUSTION AND VENTILATION)
FURNACE VENT/ INLET PIPE INSTALLATION
There are many different variations of the vent/ inlet air pipe combination. The vent/ inlet air combination used for installation of these Furnaces depends on the needs of the location. However, these guidelines must be followed:
1. The Furnace must vent outside the structure.
2. Furnace combustion air requirements must be met for non-direct, single pipe applications.
3. For direct vent application of these Furnaces, the vent pipe and air inlet pipe do not have to exit in the same air space or even on the same surface of the structure. However, the longest individual pipe
will decide the value for the longest allowable equivalent vent/ inlet air length as shown in the vent length table on page 14.
The following are EXAMPLES ONLY:
EX. 1 —
Example 1 shows that the vent may go vertical while the inlet air may be on any side of the structure. The vent pipe would decide the maximum equivalent length for the pipe depending on the furnace and pipe size.
VENT FITTING MATERIAL – PLASTIC
Gas and liquid tight single wall vent fittings, designed for resistance to corrosive flue condensate, MUST be used throughout. Listed in Table 4 are 2" and 3" size fittings that meet these requirements. The materials listed are various grades of PVC and ABS plastic. PIPE JOINTS: All joints must be fastened and sealed to prevent escape of combustion products into the build­ing.
12 18-CD25D1-2
Page 13
ent
V
Air Inlet
Furnace
EX. 2 —
Example 2 shows the vent pipe exhausting through the roof and the inlet air coming from the interior of the house (See Note 1). The inlet air coming from the inte­rior of the house must meet combustion requirements for area, etc., as shown in the section AIR FOR COM­BUSTION AND VENTILATION in this Installer’s Guide.
Vent
Installer’s Guide
EX. 4 —
The inlet air does not have to come from outside the structure. Example 4 shows the inlet air (See Note 1), may come from the attic if the requirements for com­bustion air are met as shown in the section AIR FOR COMBUSTION AND VENTILATION.
NOTE: If only the flue gas pipe is to the outside of the structure, a straight section of pipe (long enough to exit the Furnace cabinet) must be attached to the inlet air side with an elbow (which is 5 to 10 equiv. ft.) in­stalled on the end to prevent dust and debris from fall­ing directly into the Furnace.
Attic Vent
s
Air
Inlet
(See Note)
Vent
Air
Inlet
(See Note)
Furnace
EX. 3 —
Example 3 shows the vent exiting one side of the house while the inlet air is on the opposite side of the struc­ture. Here the vent pipe length must be within the al­lowable length for the size of Furnace and size of the vent pipe. This example demonstrates that the pipes do not have to exit on the same side of the structure.
V
Air
ent
Inlet
Furnace
Furnace
NOTE: It is recommended that the first joints from the Furnace be connected and sealed with high tempera­ture RTV. This will enable the pipes to be removed later without cutting.
Be sure to properly support these joints.
BONDING OF PVC
Commercially available solvent cement for PVC must be used to join PVC pipe fittings. Follow instructions on container carefully. Pipe and Fitting – ASTM D1785, D2466, D2661, & D2665 PVC Primer and Solvent Cement – ASTM D2564 Procedure for Cementing Joints – Ref ASTM D2855
1. Cut pipe square, remove ragged edges and burrs. Chamfer end of pipe, then clean fitting socket and pipe joint area of all dirt, grease, moisture or chips.
2. After checking pipe and socket for proper fit, wipe socket and pipe with cleaner-primer. Apply a liberal coat of primer to inside surface of socket and out­side of pipe. DO NOT ALLOW PRIMER TO DRY BEFORE AP­PLYING CEMENT.
3. Apply a thin coat of cement evenly in the socket. Quickly apply a heavy coat of cement to the pipe end and insert pipe into fitting with a slight twisting movement until it bottoms out.
18-CD25D1-2 13
Page 14
Installer’s Guide
4. Hold the pipe in the fitting for 30 seconds to pre­vent tapered socket from pushing the pipe out of the fitting.
5. Wipe all excess cement from the joint with a rag. Allow 15 minutes before handling. Cure time varies according to fit, temperature and humidity.
NOTE: Follow venting instructions carefully when us­ing PVC cement.
IMPORTANT: All joints must be water tight. Flue condensate is somewhat acidic, and leaks can cause equipment dam­age.
Connection of the pipe and collar of the combustion air inlet should just be a friction fit. It is recommended that the inlet air joint be sealed with RTV type sealant to al­low the joint to be separated for possible future service. The inlet and vent pipes must be properly supported throughout the entire length. See Figure 12.
TABLE 4
PVC VENT FITTING MATERIAL These fittings are available from your Gas Furnace Distributors.
NOTE: Vent termination kit BAYAIR30AVENTA or BAYVENT200B may be used in addition to the horizon­tal and vertical termination options shown in the fol­lowing figures.
A variety of potential sources of carbon monoxide can be found in a building or dwelling such as gas-fired clothes dryers, gas cooking stoves, water heaters, furnaces and fireplaces. The U.S. Consumer Product Safety Commis­sion recommends that users of gas-burning appliances install carbon monoxide detectors as well as fire and smoke detectors, listed by a nationally recognized agency (e.g. Underwriters Laboratories or International Approval Services), to help alert dwelling occupants of the presence of fire, smoke or unsafe levels of carbon monoxide.
NOTE: The manufacturer of your furnace does not test any detectors and makes no representations regarding any brand or type of detector.
PLASTIC PIPE DESIGNATIONS
PVC
ASTM STANDARD PIPE TYPE ALLOWABLE TEMPERATURE MARKING
F891 CELLULAR CORE *158 ASTM F891
D2665 DWV PIPE **158 ASTM D2665
D1785 SCH 40, 80, 120 **158 ASTM D1785
D2241 SDR SERIES **158 ASTM D2241
CPVC
ASTM STANDARD PIPE TYPE ALLOWABLE TEMPERATURE MARKING
D2846 CPVC 41 **212 ASTM D2846
F441 SCH 40, 80 **212 ASTM F441
F442 SDR SERIES **212 ASTM F442
ABS
ASTM STANDARD PIPE TYPE ALLOWABLE TEMPERATURE MARKING
D2661 SCH 40 DWV ***180 ASTM D2661
F628 SCH 40 DWV CELLULAR CORE ***180 ASTM F628
* - Allowable temperatures based on classifications covered in ASTM D4396 [Deflection Temps Under Load (264 PSI)] ** - Allowable temperatures based on classifications covered in ASTM D1784 [Deflection Temps Under Load (264 PSI)] *** - Allowable temperatures based on classifications covered in ASTM D3965 [Deflection Temps Under Load (264 PSI)]
14 18-CD25D1-2
Page 15
Installer’s Guide
IMPORTANT:
Products installed in Canada must use vent systems that are certified to the Standard for Type BH Gas Vent-
VENT AND INLET AIR CONNECTIONS
Seal VENT PIPE with RTV sealant
ing Systems (ULC S636) for Class II-A venting systems (up to 65°C). Components of the vent system must not be interchanged with other vent systems or unlisted pipe or fittings. Plastic components, specified primers, and glues must be from a single system manufacturer and not intermixed with other system manufacturer's vent system parts. In addition, the first three feet of the vent pipe must be visible for inspection.
Seal INLET AIR PIPE
with RTV sealant
TABLE 5
Front of Furnace
Figure 12
VENT LENGTH TABLE
ALTITUDE
0-7,000 Feet 2 INCH PIPE 2.5 INCH PIPE 3 INCH PIPE
UX2B060AFV3VA 200 200 200
UX2B080AFV3VA 50 120 200
UX2C100AFV4VA Not Allowed 60 200
UX2D120AFV5VA Not Allowed Not Allowed 200
7,000-9,500 Feet 2 INCH PIPE 2.5 INCH PIPE 3 INCH PIPE
UX2B060AFV3VA 100 100 100
UX2B080AFV3VA 25 60 100
UX2C100AFV4VA Not Allowed 30 100
UX2D120AFV5VA Not Allowed Not Allowed 100
9,500-12,000 Feet 2 INCH PIPE 2.5 INCH PIPE 3 INCH PIPE
UX2B060AFV3VA 50 50 50
UX2B080AFV3VA Not Allowed 30 50
UX2C100AFV4VA Not Allowed Not Allowed 50
UX2D120AFV5VA Not Allowed Not Allowed 50
NOTES: * - First letter may be "A" or "T"
1. Minimum vent length for all models: 3' horizontal or 3' vertical.
2. DO NOT MIX PIPE DIAMETERS IN THE SAME LENGTH OF PIPE OUTSIDE THE FURNACE CABINET (Except adapters at the top of the furnace). If different inlet and vent pipe sizes are used, the vent pipe must adhere to the maximum length limit shown in the table above (See note 6 below for exception). The inlet pipe can be of a larger diameter, but never smaller than the vent pipe.
3. MAXIMUM PIPE LENGTHS MUST NOT BE EXCEEDED! THE LENGTH SHOWN IS NOT A COMBINED TOTAL, IT IS THE MAXIMUM LENGTH OF EACH (Vent or Inlet air pipes).
4. One SHORT radius 90° elbow is equivalent to 10' of 3" pipe and one LONG radius elbow is equivalent to 6' of 3" pipe. One 90° elbow is equivalent to 7½' of 2½" pipe or 5' of 2" pipe. Two 45° elbows equal one 90°elbow.
5. The termination tee or bend must be included in the total number of elbows. If the BAYAIR30AVENTA termination kit is used, the equivalent length of pipe is 5 feet. BAYVENT200B equivalent length is 0 feet.
6. Pipe adapters are field supplied (except 120).
MAXIMUM TOTAL EQUIVALENT LENGTH IN FEET
FOR VENT AND INLET AIR (SEE NOTES)
18-CD25D1-2 15
Page 16
Installer’s Guide
HORIZONTAL INSTALLATION (Upflow/ Horizontal)
NOTE: When the factory supplied 2X3" offset reducing coupling is used for 3" vent pipe installation, make sure the marking “TOP” is located on the top side of the pipe. The straight side of the coupling must be on bottom for proper drainage of condensate. See Figure 13.
Figure 13
!
CAUTION
When the vent pipe is exposed to temperatures below freezing, i.e., when it passes through unheated spaces, etc., the pipe must be insulated with 1/2 inch (22.7 mm) thick Armaflex-type insulation or equal. If the space is heated sufficiently to prevent freezing, then the insulation would not be required. If domestic water pipes are not protected from freezing then it is assumed the space meets the condition of a heated space.
Figure 14
9" MINIMUM
9" MINIMUM
9" MINIMUM
ELBOW AND TEE MUST BE AS CLOSE TOGETHER AS POSSIBLE
9" MINIMUM
9" MINIMUM
POSSIBLE CONFIGURATIONS FOR TWO PIPE VENTING SYSTEMS
16 18-CD25D1-2
Page 17
Installer’s Guide
P
3" PIPING
2", 2-1/2"
or 3" PIPING
REDUCING COUPLING, FIELD SUPPLIED IF NEEDED
SEAL ALL
WALL CAVITIES
Figure 15
COMBUSTION AIR INLET
40" UPFLOW OR DOWNFLOW MODELS
SEE VENTING TABLE
STRAPS OR OTHER SUITABLE SUPPORTS AT MAXIMUM OF 3'-0" INTERVALS
UPWARD PITCH -- 1/4" PER FOOT
FIRST SUPPORT SHOULD BE AS CLOSE TO FURNACE CONNECTION AS POSSIBLE.
NOTE: ANY FITTINGS PASSING THROUGH AN UNHEATED SPACE MUST BE INSULATED.
TEE
NOTE: VENT AND INLET MUST BE SUP­PORTED AT A MAXIMUM OF 3' INTERVALS
USE ONLY
APPROVED
TERMINATION
OUTSIDE
WALL
VENT
COMBUSTION AIR
BAYAIR30AVENTA
STRAP (FIELD SUPPLIED)
ELBOW (FIELD SUPPLIED)
COMBUSTION AIR
RAIN CA
VENT
1" + 1/2"
HORIZONTAL VENTING THROUGH WALL
These Furnaces may be installed as direct vent (as shipped) or as nondirect vent. Installation must conform to national, state, and local codes.
The vent & inlet terminals must be located at least 12" minimum above normally expected snow accumulation level. Avoid areas where staining or condensate drippage may be a problem. Location of the vent/ wind terminal should be chosen to meet the requirements of Figure 16 for either direct or non-direct vent applications. PITCH — Venting through the wall must maintain 1/4" per foot pitched upward to insure that condensate drains back to the Furnace. FLUE GAS DEGRADATION — The moisture content of the flue gas may have a detrimental effect on some building materials. This can be avoided by using the roof or chimney venting option. When wall venting is used on any surface that can be affected by this mois­ture, it is recommended that a corrosion resistant shield (24 inches square) be used behind the vent termi­nal. This shield can be wood, plastic, sheet metal, etc. Also, silicone caulk all cracks, seams and joints within 3 feet of the vent terminal.
7.2"
3.2"
COMBUSTION AIR
Figure 16
BAYVENT200B
ANCHORS (4 req.)
VENT
VENT CAP
SNOW LEVEL OR GRADE WHICHEVER IS GREATER
BAYVENT200B
VENT PLATE
12" MINIMUM TO OVERHANG
SCREWS (4 req.)
VENT
MAINTAIN 12" (18" FOR CANADA) MINIMUM
CLEARANCE ABOVE HIGHEST ANTICIPATED
18-CD25D1-2 17
Page 18
Installer’s Guide
P
Figure 17
COMBUSTION AIR
RAIN CA
VENT
1" + 1/2"
VENT
COMBUSTION AIR
STRAP (FIELD SUPPLIED)
ELBOW (FIELD SUPPLIED)
BAYAIR30AVENTA
(Sidewall)
COMBUSTIBLE MATERIAL WALL
A minimum clearance of 1" to combustible materials must be maintained when using single wall stainless steel venting. See Figure 18.
Shield material to be a minimum of 24 gauge stainless or aluminized sheet metal. Minimum dimensions are 12"x12". Shield must be fastened to both inside and out­side of wall. Use screws or anchor type fasteners suited to the outside or inside wall surfaces.
NONCOMBUSTIBLE MATERIAL WALL
The hole through the wall must be large enough to maintain pitch of vent and properly seal. Use cement mortar seal on inside and outside of wall. See Figure 19.
Figure 18
Figure 19
Figure 20
SUPPORT HORIZONTAL PIPE EVERY 3' 0" WITH THE FIRST SUPPORT AS CLOSE TO THE FURNACE AS POSSIBLE. INDUCED DRAFT BLOWER, HOUSING, AND FURNACE MUST NOT SUPPORT THE WEIGHT OF THE FLUE PIPE.
18 18-CD25D1-2
Page 19
Installer’s Guide
Figure 21
Figure 22
REMOVE RIBS FROM CAP
COMBUSTION AIR
ROOF BOOT (FIELD SUPPLIED)
VENT
BAYAIR30AVENTA (VERTICAL)
SEAL BETWEEN FLANGE, PIPE, COUPLING AND METAL PANEL WITH HI TEMP RTV SILICONE SEALANT
VENT
MAINTAIN 12 IN. (18 IN. FOR CANADA) MINIMUM CLEARANCE ABOVE HIGHEST ANTICIPATED SNOW LEVEL. MAXIMUM OF 24 IN. ABOVE ROOF
SUPPORT (FIELD SUPPLIED)
ELBOW (FIELD SUPPLIED)
COMBUSTION AIR
Figure 23
FLUE PIPE
COUPLING
VENT
MAINTAIN 12 IN. (18 IN. FOR CANADA) MINIMUM CLEARANCE ABOVE HIGHEST ANTICIPATED SNOW LEVEL. MAXIMUM OF 24 IN. ABOVE ROOF.
COMBUSTION AIR
VENTING THROUGH THE ROOF
When penetrating roof with a 2" PVC vent pipe, a 2" electrical conduit flashing may be used for a weather tight seal. Lubricate flexible seal on flashing before PVC pipe is pushed through the seal. (Field Supplied)
NOTE: No vent cap as shown in Figure 21 is the pre­ferred method for vertical vent termination in extremely cold climates. In extreme climate conditions, insulate the exposed pipe above the roof line with Armaflex type insulation.
VENT FITTING MATERIAL – STAINLESS STEEL
Gas and liquid tight single wall metal vent fitting, de­signed for resistance to corrosive flue condensate such as Type 29-4C MUST be used throughout. These fittings and fitting accessories are to be field sup­plied.
DIRECTION OF STAINLESS STEEL FITTING
All stainless steel fitting must be installed with male end towards the Furnace. All horizontal stainless steel sections must be posi­tioned with the seam on top. All long horizontal sections must be supported to pre­vent sagging. All pipe joints must be fastened and sealed to prevent escape of combustion products into the building.
SUPPORT
FLANGE
GALVANIZED FIRESTOP SHOULD BE FABRICATED WITH 3-7/8" DIA. HOLE FOR SUPPORT FLANGE (12" x 12" PANEL OR 12" DIA MIN.)
CLEARANCE ( 0" ACCEPTABLE FOR PVC VENT PIPE )
( 1" ACCEPTABLE FOR TYPE 29-4C STAINLESS STEEL VENT PIPE )
CEILING
VENTING THROUGH CEILING
18-CD25D1-2 19
Page 20
Installer’s Guide
Figure 23
FLUE PIPE
COUPLING TO SUPPORT PIPE FROM ANGLES OR OTHER SUITABLE SUPPORT METHOD
PVC PLASTIC VENTING - ONLY THROUGH UNUSED CHIMNEY
STAINLESS STEEL
STAINLESS
VENT CAP (OP-
STEEL
TIONAL)
VENT CAP
SEE CAUTION
6 IN. MIN.
Figure 24
SUPPORT THE SINGLE WALL FLUE PIPE AND CENTER IT IN THE CHIMNEY OPENING WITH ANGLES AS SHOWN OR ANOTHER EQUIVALENT MANNER.
COUPLING AS REQUIRED
TYPE 29-4C STAINLESS STEEL VENTING - USED
THROUGH CHIMNEY THAT VENTS ANOTHER GAS
APPLIANCE
STAINLESS STEEL
STAINLESS
VENT CAP (OP-
STEEL
TIONAL)
VENT CAP
SEE CAUTION
6 IN. MIN.
SUPPORT THE SINGLE WALL STAINLESS STEEL GAS VENTING AND CENTER IT IN THE CHIMNEY OPENING WITH ANGLES AS SHOWN OR ANOTHER EQUIVALENT MANNER.
FLUE PIPE
NOTE: HORIZONTAL VENTING TO VERTICAL VENTING
!
NOTE: HORIZONTAL VENTING TO VERTICAL VENTING
!
CAUTION
Do NOT run vent through chimney for wood burn­ing or oil Furnaces or incinerators or any other gas appliance.
IMPORTANT –
The single wall flue pipe joints must be sealed. The 90° elbow connection to vertical pipe must be sealed to prevent condensate leakage to base of ma­sonry chimney.
Do NOT run vent through chimney for wood burning or oil Furnaces or incinerators. If remaining free area between single wall flue pipe and masonry chimney is to be used for another gas appliance venting area must be sufficient to vent that appliance and that appliance must be connected to chimney with separate entry openings.
IMPORTANT –
The single wall flue pipe joints must be sealed. The 90° elbow connection to vertical pipe must be sealed to prevent condensate leakage to base of ma­sonry chimney.
CAUTION
VENTING ROUTED THROUGH A MASONRY CHIMNEY
20 18-CD25D1-2
Page 21
Installer’s Guide
Figure 25
D
HORIZONTAL VENT CLEARANCES
INSIDE
CORNER DETAIL
G
V
H
EE
V
CLO
J
B
FIXED
S
ED
V
I
X
M
X
V
K
V
L
B
V
VENT TERMINAL
C
FIXED
V
CLOSED
ABLE
OPER
V
F
B
X
AIR SUPPLY INLET
B
OPERABLE
V
B
V
B
A
AREA WHERE TERMINAL IS NOT PERMITTED
Non-Direct Vent Terminal Clearances
Canadian Installations US Installations
Clearance above grade, veranda, porch, deck, or
A=
balcony
6 inches (15 cm) for appliances =/< 10,000 Btuh (3 kw),
Clearance to window or door that may be
B=
opened
C= Clearance to permanently closed window * *
Vertical clearance to ventilated soffit located above the terminal within a horizontal distance of
D=
2 feet
(61 cm) from the center line of the terminal
E= Clearance to unventilated soffit * *
F= Clearance to outside corner * *
G= Clearance to inside corner * *
Clearance to each side of center line extended
H=
above meter/regulator assembly
I= Clearance to service regulator vent outlet 3 feet (91 cm) *
Clearance to nonmechanical air supply inlet to
J=
building or the combustion air inlet to any other
appliance
K= Clearance to a mechanical air supply inlet 6 feet (1.83m)
Clearance above a paved sidewalk or paved
L=
driveway located on public property
M-=Clearance under veranda, porch, deck, or
balcony
Notes:
1. In accordance with the current CSA B149.1 Natural Gas and Propane Installation Code.
2. In accordance with the current ANSI Z223.1/NFPA 54 National Fuel Gas Code. †. A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwelling and serves both dwellings. ‡. Pemitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor. * Clearance in accordance with local installation codes and the requirements of the gas supplier and the manufacturer's Installation Instructions.
12 inches (30 cm) for appliances > 10,000 Btuh (3 kw) and =/< 100,000 Btuh (30 kw), 36 inches (91 cm) for appliances > 100,000 Btuh (30 kw)
3 feet (91 cm) with a height 15 feet (4.5 m) above the
6 inches (15 cm) for appliances =/< 10,000 Btuh (3 kw), 12 inches (30 cm) for appliances > 10,000 Btuh (3 kw) and =/< 100,000 Btuh (30 kw), 36 inches (91 cm) for appliances > 100,000 Btuh (30 kw)
12 inches (30 cm) 12 inches (30 cm)
4 feet (1.2m) below or to the side of
**
meter/regulator assembly
4 feet (1.2 m) below or to side of opening;
1 foot (300 m) above opening
3 feet (91 cm) above if within
7 feet (2.13 m) † 7 feet (2.13 m)
12 inches (30 cm) ‡ *
opening;
1 foot (0.3m) above opening.
10 feet (3m) horizontally
*
18-CD25D1-2 21
Page 22
Installer’s Guide
Clearance above grade, veranda,
A=
porch, deck, or balcony
Clearance to window or door that may
B=
be opened
Clearance to permanently closed
C=
window
Vertical clearance to ventilated soffit located above the terminal within a
D=
horizontal distance of 2 feet (61 cm) from the center line of the terminal
E= Clearance to unventilated soffit * *
F= Clearance to outside corner * *
G= Clearance to inside corner * *
Clearance to each side of center line
H=
extended above meter/regulator assembly
Clearance to service regulator vent
I=
outlet
Clearance to nonmechanical air supply
J=
inlet to building or the combustion air inlet to any other appliance
Clearance to a mechanical air supply
K=
inlet
Clearance above a paved sidewalk or
L=
paved driveway located on public property
M-=Clearance under veranda, porch, deck,
or balcony
Notes:
1. In accordance with the current CSA B149.1 Natural Gas and Propane Installation Code.
2. In accordance with the current ANSI Z223.1/NFPA 54 National Fuel Gas Code. †. A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwelling and serves both dwellings. ‡. Pemitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor. * Clearance in accordance with local installation codes and the requirements of the gas supplier and the manufacturer's Installat ion Instructions.
Direct Vent Ter minal Clearances
Canadian Installations US Installations
12 inches (30 cm) 12 inches (30 cm)
6 inches (15 cm) for appliances =/< 10,000 Btuh (3 kw), 12 inches (30 cm) for appliances > 10,000 Btuh (3 kw) and =/< 100,000 Btuh (30 kw), 36 inches (91 cm) for appliances > 100,000 Btuh (30 kw)
**
**
3 feet (91 cm) with a height 15 feet (4.5 m) above the
6 inches (15 cm) for appliances =/< 10,000 Btuh (3 kw), 12 inches (30 cm) for appliances > 10,000 Btuh (3 kw) and =/< 100,000 Btuh (30 kw), 36 inches (91 cm) for appliances > 100,000 Btuh (30 kw)
meter/regulator assembly
3 feet (91 cm) *
6 feet (1.83m)
7 feet (2.13 m) † *
12 inches (30 cm) ‡ *
6 inches (15 cm) for appliances =/< 10,000 Btuh (3 kw), 9 inches (23 cm) for appliances > 10,000 Btuh (3 kw) and =/< 50,000 Btuh (15 kw), 12 inches (30 cm) for appliances > 50,000 Btuh (15 kw)
*
6 inches (15 cm) for appliances =/< 10,000 Btuh (3 kw), 9 inches (23 cm) for appliances > 10,000 Btuh (3 kw) and =/< 50,000 Btuh (15 kw), 12 inches (30 cm) for appliances > 50,000 Btuh (15 kw)
3 feet (91 cm) above if within 10 feet (3m)
horizontally
Figure 26
DOWNWARD VENTING
Furnace may be in vertical or horizontal configuration.
All horizontal pipes must be supported at maximum of 3
foot intervals
Slope 1/4" per ft.
Slope 1/4" per ft.
NOTES: A) Condensate trap for vent pipe must be a minimum of 6 inches in height. B) Condensate trap for vent and inlet pipe must be connected into a condensate drain pump; an open or vented drain;
or it can be connected to the outlet hose of the Furnace condensate trap. Outdoor draining of the Furnace and coil condensate is permissible if allowed by local codes.
!
CAUTION
!
Caution should be taken to prevent drains from freezing or causing slippery conditions that could lead to personal in­jury. Excessive draining of condensate may cause saturated ground conditions that may result in damage to plants.
C) The condensate trap should be primed at initial start up prior to heating season operation.
DOWNWARD VENT LENGTH IS LIMITED TO A MAXIMUM OF
EQUIVALENT FEET.
40 Inch Upflow or Downflow
Furnace
6" Min.
CAUTION
15
22 18-CD25D1-2
Page 23
Installer’s Guide
IMPORTANT:
The Commonwealth of Massachusetts requires compliance with regulation 248 CMR 4.00 and 5.00 for installation of through – the – wall vented gas appliances as follows:
For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back­up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level. b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, “GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS”.
4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4. This appliance requires a special venting system. If BAYAIR30AVENTA or BAYVENT200B are used, a copy of the installation instructions for the kit shall remain with the appliance or equipment at the completion of installation. The venting system installation instructions can be obtained from the manufacturer by writing to the following address:
American Standard, Inc. 6200 Troup Highway Tyler, TX 75707 Attention: Manager of Field Operations Excellence
18-CD25D1-2 23
Page 24
Installer’s Guide
CONDENSATE DRAIN INSTRUCTIONS
!
WARNING
CARBON MONOXIDE POISONING HAZARD Failure to follow the installation instructions for the venting system being placed into operation could re­sult in carbon monoxide poisoning or death.
!
It is recommended that a drain pan be installed under the furnace to prevent property damage, or personal injury.
Knock outs are provided on the left and right hand side of both furnace cabinets for drain connections IN VER- TICAL APPLICATIONS. The standard arrangement is for the drain connection on the left side. The tubing may have to be trimmed in this application to avoid kinking. The upflow (vertical application) has provisions for right side drain connections by turning the trap and ex­tending the tubing to the lower right front corner of the Furnace. Trim all excess tubing to avoid kinking. The connecting tubing for left or right side condensate drain shown in Figure 27 is shipped in the blower com­partment. It is always recommended that an auxiliary drain pan be installed under a horizontally installed evaporator or 90% Gas Furnace. Connect the auxiliary drain line to a separate drain line (no trap is needed in this line).
CAUTION
All horizontal applications are left side only and require repositioning the condensate canister trap to the exterior of the cabinet. Additionally the drain tubing connected to the inducer housing must be repositioned for removing the plug and re­connecting the tubing to the lower connection on the inducer housing. See Figure 28.
For horizontal installation, remove the condensate trap and position the trap outside the cabinet through the slotted opening next to the secondary cell. On upflow/ horizontal models, remove lines from the blower sec­tion and pull through the blower deck. Cut and reattach the line from the secondary cell (use the spring to pre­vent kinking). The inducer housing has a secondary drain opening at its 9 o’clock position. Remove the plug and use the plug to cover the hole at the 6 o’clock position. Reposition the Inducer drain tube from 6 o’clock to the 9 o’clock lo­cation. Cut and reattach the tube to the canister trap. Plug openings in Blower deck, Inducer and Blower sec­tion. See Figure 28. Connections must be made to an OPEN/ VENTED DRAIN.
NOTE: Use 1/2" size PVC pipe and fittings through­out for drain connections (fittings, pipe and PVC sol­vent cement not provided).
THE UPFLOW (VERTICAL) MAY BE INSTALLED
Figure 27
HEADER
TO DRAIN
LEFT SIDE
24 18-CD25D1-2
LEFT OR RIGHT SIDE CONDENSATE DRAIN
UPFLOW FURNACE
(Vertical)
HEADER
TO DRAIN
RIGHT SIDE
Page 25
Installer’s Guide
Primary drain vent stack must terminate below secondary heat exchanger condensate drain outlet.
To drain opening
If upflow furnace is installed over a finished ceiling, overflow from the primary drain vent stack must flow into an auxillary drain pan to prevent damage to the finished ceiling below.
Figure 28
ALL HORIZONTAL APPLICATIONS
ARE LEFT SIDE DRAIN ONLY
HEADER
TO
OPEN/
VENTED
DRAIN
UPFLOW FURNACE ON LEFT SIDE WITH LEFT DRAIN SHOWN
NOTE: A corrosion resistant condensate pump must be used if a pump is required for a specific drain system.
IMPORTANT:
The condensate drain should be installed with provisions to prevent winter freeze-up of the condensate drain line. Frozen condensate will block drains, resulting in furnace shutdown. If the drain line cannot be installed in a condi­tioned space and/ or its surrounding ambient tempera­ture is expected to fall below freezing, then heat tape should be applied as required to prevent freezing (per manufacturer’s instructions). The heat tape should be rated at 5 or 6 watts per foot at 120 volts. Self-regulating (preferred) or thermostatically controlled heat tape is re­quired.
Typical sources of UL listed heat tapes are W.W. Granger, Inc. (Wintergard Plus
TM
Series), McMaster Carr Supply Co. (3554 Series), or your equipment sup­plier. The condensate drain may be cleaned or inspected by removal of the drain tube at the header.
Figure 29
Evaporator and Furnace condensate drain piping may be manifolded together as shown in Figure 29. A pri­mary drain vent stack must be installed and terminated below the outlet of the secondary heat exchanger drain connection to prevent water from damaging Furnace controls if the primary drain outlet plugs up.
Where the Furnace is installed above a finished ceiling, the primary drain vent stack must be in­stalled such that overflow from the vent stack opening will flow into an auxiliary drain pan in order to prevent water damage to the finished ceiling below.
18-CD25D1-2 25
Page 26
Installer’s Guide
FIELD WIRING DIAGRAM FOR VARIABLE SPEED 2 STAGE FURNACE
USING A 1 STAGE HEATING THERMOSTAT
W14
W14 JUMPER SEE NOTE 11
Y1/Ylo
SEE
NOTE 6
1 STAGE HEATING
NO COOLING
1. Be sure power agrees with equipment nameplates.
2. Low voltage (24 volt wiring) to be No. 18 A.W.G. min.
3. Grounding of equipment must comply with local codes.
4. Set thermostat heat anticipator per unit wiring diagram.
5. These leads provide 115V. power for connection of humidifier MAX. load 1.0 amp.
6. When a single stage heating thermostat without fan switch is used, no wiring on "G" terminal is used.
7. W1 and W2 must be jumpered together for proper operation. Second stage heat will begin 10 minutes after first stage.
8. Set dip switches with power off per installation instructions to set airflow and indoor fan off delays.
9. Continuous fan airflow can be increased by adding this jumper.
10. This wire is only for thermostats requiring connection to transformer common terminal.
11. Optional humidistat is to be connected between R and BK. Factory installed jumper R to BK on the circuit board must be cut if optional humidistat is used. The jumper must
SEE
NOTE 9
FIELD ADDED JUMPER
W1 TO W2.
2ND STAGE WILL FIRE
10 MINUTES AFTER 1ST.
also be cut when applying an airflow command signal to the BK input such as with the variable speed single-zone and multi-zone system controllers. On single speed cooling only/non-heat pump systems, jumper Y to O for proper operation of the delay profiles and the humidistat. For two compressor or two speed systems, jumper YLo to O.
B/C
SEE
NOTE 10
B/C
TO 115 V 1 PH., 60 HZ., POWER SUPPLY PER LOCAL CODES
HUM SEE NOTE 5
From Dwg. B342027 Rev. 0
26 18-CD25D1-2
Page 27
Installer’s Guide
FIELD WIRING DIAGRAM FOR VARIABLE SPEED 2 STAGE FURNACE
2 STAGE HEATING
USING A 2 STAGE HEATING THERMOSTAT
NO COOLING
1. Be sure power agrees with equipment nameplates.
2. Low voltage (24 volt wiring) to be No. 18 A.W.G. min.
3. Grounding of equipment must comply with local codes.
4. Set thermostat heat anticipator per unit wiring diagram.
5. These leads provide 115V. power for connection of humidifier MAX. load 1.0 amp.
6. This wire is only for thermostats requiring connection to transformer common terminal.
7. Continuous fan airflow can be increased by adding this jumper.
8. Set dip switches with power off per installation instructions to set airflow and indoor fan off delays.
9. Optional humidistat is to be connected between R and BK. Factory installed jumper R to BK on the circuit board must be cut if optional humidistat is used. The jumper must also be cut when applying an airflow command signal to the BK input such as with the variable speed single-zone and multi-zone system controllers. On single speed cooling only/non-heat pump systems, jumper Y to O for proper operation of the delay profiles and the humidistat. For two compressor or two speed systems, jumper YLo to O.
Y1/Ylo
W14
W14 JUMPER
SEE NOTE 9
SEE
NOTE 7
B/C
SEE
NOTE 6
B/C
TO 115 V 1 PH., 60 HZ., POWER SUPPLY PER LOCAL CODES
HUM SEE NOTE 5
From Dwg. B342025 Rev. 0
18-CD25D1-2 27
Page 28
Installer’s Guide
FIELD WIRING DIAGRAM FOR VARIABLE SPEED 2 STAGE FURNACE
1 STAGE HEATING, 1 STAGE COOLING
USING A 1 STAGE HEATING, 1 STAGE COOLING THERMOSTAT
(OUTDOOR SECTION WITHOUT TRANSFORMER)
OUTDOOR UNIT
(NO TRANSFORMER)
B/C
SEE
NOTE 7
SEE
NOTE 6
Y1/Ylo
B/C
W14
W14 JUMPER
SEE NOTE 9
FIELD ADDED JUMPER
W1 TO W2.
2ND STAGE WILL FIRE
10 MINUTES AFTER 1ST.
TO 115 V 1 PH., 60 HZ., POWER SUPPLY PER LOCAL CODES
HUM SEE NOTE 5
From drawing B342022 Rv 0
28 18-CD25D1-2
Page 29
OUTDOOR UNIT
(NO TRANSFORMER)
Installer’s Guide
FIELD WIRING DIAGRAM FOR VARIABLE SPEED 2 STAGE FURNACE
2 STAGE HEATING, 1 STAGE COOLING
USING A 2 STAGE HEATING, 1 STAGE COOLING THERMOSTAT
(OUTDOOR SECTION WITHOUT TRANSFORMER)
W14
SEE
NOTE 9
SEE
NOTE 7
Y1/Ylo
W14 JUMPER
SEE NOTE 9
B/C
SEE
NOTE 6
B/C
TO 115 V 1 PH., 60 HZ., POWER SUPPLY PER LOCAL CODES
HUM SEE NOTE 5
From Dwg. B342020 Rev. 0
18-CD25D1-2 29
Page 30
Installer’s Guide
FIELD WIRING DIAGRAM FOR VARIABLE SPEED 2 STAGE FURNACE
(OUTDOOR SECTION WITHOUT TRANSFORMER)
OUTDOOR UNIT NO. 1
(NO TRANSFORMER)
SEE NOTE 3
SEE
NOTE 7
OUTDOOR UNIT NO. 2
(NO TRANSFORMER)
SEE
NOTE 6
B/C
2 STAGE HEATING, 2 STAGE COOLING
W14
TO 115 V 1 PH., 60 HZ., POWER SUPPLY PER LOCAL CODES
B/C
HUM SEE NOTE 5
HUMIDISTAT HOOKUP
If an optional Humidistat is to be connected between “R” and “BK”, the factory installed jumper between “R” and “BK” on the circuit board must be cut. If an optional Humidistat is used, the jumper must also be cut when applying an airflow command signal to the “BK” input such as with the variable speed single-zone and multi­zone system controller. On single speed cooling only/ non-heat pump systems, jumper “Y” to “O” for proper operation of the delay profiles and the Humidistat. For two compressor or two speed systems, jumper “Ylo” to “O”.
From Dwg. B342018 Rev. 0
The factory installed jumper be­tween “R” and “BK” on the circuit board must be cut if an optional Humidistat is installed.
30 18-CD25D1-2
Page 31
Installer’s Guide
ELECTRICAL CONNECTIONS
Make wiring connections to the unit as indicated on en­closed wiring diagram. As with all gas appliances using electrical power, this Furnace shall be connected into a permanently live electric circuit. It is recommended that Furnace be provided with a separate “circuit pro­tection device” electric circuit. The Furnace must be electrically grounded in accordance with local codes or in the absence of local codes with the National Electri­cal Code, ANSI/ NFPA 70 or CSA C22.1 Electrical Code, if an external electrical source is utilized. The inte- grated Furnace control is polarity sensitive. The hot leg of the 120V power supply must be connected to the black power lead as indicated on the wiring dia­gram. Provision for hooking up a humidifier is provided on the integrated control. Refer to the SERVICE FACTS literature and unit wiring diagram attached to furnace.
GAS PIPING
!
WARNING
DO NOT USE SEMI-RIGID METALLIC GAS CONNEC­TORS (FLEXIBLE GAS LINES) WITHIN THE FURNACE CABINET. FAILURE TO FOLLOW THIS WARNING COULD RESULT IN PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
The following warning complies with State of California law, Proposition 65.
!
WARNING
Hazardous Gases!
Exposure to fuel substances or by-products of incomplete fuel combustion is believed by the state of California to cause cancer, birth defects, or other reproductive harm.
!
WARNING
EXPLOSION HAZARD! PROPANE GAS IS HEAVIER THAN AIR AND MAY
COLLECT IN ANY LOW AREAS OR CONFINED SPACES. IF THE GAS FURNACE IS INSTALLED IN A BASEMENT, AN EXCAVATED AREA OR A CONFINED SPACE, IT IS STRONGLY RECOMMENDED TO CON­TACT A GAS SUPPLIER TO INSTALL A GAS DETECT­ING WARNING DEVICE IN CASE OF A GAS LEAK.
NOTE: The manufacturer of your furnace does NOT test
any detectors and makes no representations regarding any brand or type of detector.
NOTE: The manufacturer of your furnace does not test any detectors and makes no representations regarding any brand or type of detector.
TABLE 6
NATURAL GAS ONLY
TABLE OF CUBIC FEET PER HOUR OF GAS
FOR VARIOUS PIPE SIZES AND LENGTHS
PIPE SIZE
1/2 132 92 73 63 56 50 46
3/4 278 190 152 130 115 105 96
1-1/4 1050 730 590 520 440 400 370
This table is based on pressure drop of 0.3 inch W.C. and 0.6 SP.GR. gas
Use a backup wrench on the Gas Valve when installing gas piping to prevent damage to the Gas Valve and Manifold Assembly.
The installation of piping shall be in accordance with piping codes and the regulations of the local gas com­pany. Pipe joint compound must be resistant to the chemical reaction with liquefied petroleum gases. Refer to piping Table 6, for delivery sizes. Connect gas supply to the unit, using a ground joint union and a manual shut-off Valve as shown in Figure 31. National codes require a condensation drip leg to be installed ahead of the controls as shown in Figures 31 & 32. The Furnace and its individual shut-off valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psig (3.5 kPa). The Furnace must be isolated from the gas supply pip­ing by closing its individual manual shut-off Valve dur­ing any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig (3.5 kPa).
10 20 30 40 50 60 70
1 520 350 285 245 215 195 180
INPUT
RATING
BTUH
60,000
80,000 100,000 120,000
NUMBER
BURNERS
LENGTH OF PIPE
TABLE 7
ORIFICE SIZES
MAIN BURNER ORIFICE
OF
NAT. GAS LP GAS
3 4 5 6
!
CAUTION
DRILL SIZE
45 45 45 45
56 56 56 56
!
EXPLOSION HAZARD! ODORANT FADE MAY MAKE THE GAS UNDETECT­ABLE EXCEPT WITH A WARNING DEVICE. IF THE GAS FURNACE IS INSTALLED IN A BASEMENT, AN EXCAVATED AREA OR A CONFINED SPACE, IT IS STRONGLY RECOMMENDED TO CONTACT A GAS SUPPLIER TO INSTALL A GAS DETECTING WARN­ING DEVICE IN CASE OF A GAS LEAK.
18-CD25D1-2 31
WARNING
NOTE: Maximum pressure to the Gas Valve for natural gas is 13.8" W.C. Minimum pressure is 5.0" W.C. Maxi­mum pressure to the Gas Valve for propane is 13.8" W.C. Minimum pressure is 11.0" W.C.
All gas fittings must be checked for leaks using a soapy solution before lighting the Furnace. DO NOT CHECK
WITH AN OPEN FLAME!
Page 32
Installer’s Guide
Figure 30
AUTOMATIC GAS VALVE
WITH MANUAL SHUTOFF
AUTOMATIC GAS VALVE
WITH MANUAL SHUTOFF
MAIN MANUAL
SHUTOFF VALVE
GROUND
UNION
JOINT
MAIN MANUAL
SHUTOFF VALVE
GROUND
UNION
JOINT
DRIP
LEG
DRIP
LEG
UPFLOW MAY BE LEFT OR
RIGHT HAND GAS PIPING
AUTOMATIC GAS VALVE
WITH MANUAL SHUTOFF
MAIN MANUAL
SHUTOFF VALVE
GROUND
UNION JOINT
Figure 31
GROUND UNION JOINT
DRIP
LEG
MAIN MANUAL
SHUTOFF VALVE
AUTOMATIC GAS VALVE WITH
MANUAL SHUTOFF
HORIZONTAL FURNACE GAS PIPING MAY BE FROM EITHER SIDE
(Typical UPFLOW Furnace in horizontal configuration shown)
DRIP
LEG
32 18-CD25D1-2
Page 33
Installer’s Guide
COMBUSTION AND INPUT CHECK (See also High Altitude Derate)
!
WARNING
Replace and/ or tighten all plugs removed or loosened when adjusting gas pressure. Leak check the fittings before placing the Furnace into regular service. Failure to follow this warning could result in fire, ex­plosion, property damage, or death.
1. Make sure all gas appliances are off except the Fur­nace.
2. Clock the gas meter with the Furnace operating (determine the dial rating of the meter) for one revolution.
3. Match the “Sec” column in the gas flow (in cfh) Table 8 with the time clocked.
4. Read the “Flow” column opposite the number of sec­onds clocked.
5. Use the following factors For 1 Cu. Ft. Dial Gas Flow CFH =
For 1/2 Cu Ft. Dial Gas Flow CFH =
For 5 Cu. Ft. Dial Gas Flow CFH =
6. Multiply the final figure by the heating value of the gas obtained from the utility company and compare to the nameplate rating. This must not exceed the nameplate rating.
7. Changes can be made by adjusting the Manifold Pressure (See Table 9), or changing orifices (orifice change may not always be required). To adjust the Manifold Pressure:
if necessary:
Chart Flow Reading ÷2
Chart Flow Reading ÷4
10X Chart Flow Reading ÷4
a. Turn off all electrical power to the system. b. Attach a Manifold Pressure gauge to the outlet
pressure tap marked “OUT PRESS TAP” on White-Rodgers gas valve model 36G. (see Fig­ure 33 for White-Rodgers gas valve model 36G). Attach flexible tubing and a Manometer to the barbed fitting. For the Gas Valve model 36G, do not remove the pressure tap test screw. Loosen the pressure tap test screw one turn and install flexible tubing and a Manometer di­rectly onto the outlet pressure boss.
c. The other side of the Manifold Pressure Gauge
must be referenced to the Burner Box as shown
in Figure 32. d. Turn on system power and energize Valve. e. For the White-Rodgers Gas Valve model 36G:
1. Adjust low fire by removing the low adjust­ment regulator cover screw (See Figure
33).
2. To increase outlet pressure, turn the regu­lator adjust screw clockwise. To decrease outlet pressure, turn the regulator adjust screw counter-clockwise. Adjust regulator until pressure shown on Manometer matches the pressure specified in Table 9.
3. Replace and tighten the regulator cover screw securely.
4. Cycle the Valve several times to verify regulator setting.
5. Adjust high fire by removing the high ad­justment regulator cover screw (See Figure
33).
Figure 32
CAUTION:
18-CD25D1-2 33
Return all tubing, caps, and/or plugs to original positions when pressure checks are completed.
Page 34
Installer’s Guide
6. To increase outlet pressure, turn the regu lator adjust screw clockwise. To decrease outlet pressure, turn the regulator adjust screw counter-clockwise. The final Manifold Pressure setting shall be as specified in Table 9 with an input of no more than nameplate rating and no less than 93% of the nameplate rating, unless the unit is de­rated for high altitude.
7. Replace high adjustment regulator cover screw and tighten securely.
8. Cycle the Valve several times to verify regulator setting.
g. Turn off all electrical power to the system. h. Remove the Manometer and flexible tubing.
Remove the barbed fitting and replace the plug or tighten the pressure test screw.
i. Turn on electrical power to the system and en-
ergize valve.
j. Using a leak detection solution or soap suds,
check for leaks at plug or pressure boss screw.
NOTE: The Manifold Pressure must be referenced to the Burner Box. The Burner Box pressure tap equalizes the Gas Valve pressure regulator. Manifold Pressure is checked by installing a tee (field supplied) in the tub­ing, between the tee coming from the Burner Box tube and the Gas Valve,
in addition to
the regular Gas Valve pressure tap on the outlet side of the Gas Valve. See Figure 32.
Table 7 lists the main burner orifices used with the Fur­nace. If a change of orifices is required to correct the Furnace input rating refer to Table 10.
REINSTALLATION OF THE BURNER BOX COVER
Figure 34 shows the correct way to reinstall the Burner Box cover if adjustment or replacement of the flame sensor, hot surface igniter, or main burner orifices have required removal of the cover.
HIGH ALTITUDE DERATE
Input ratings (BTUH) of these Furnaces are based on sea level operation and should not be changed at eleva­tions up to 2,000 ft. If the installation is 2,000 ft. or above, the Furnace input rate (BTUH) shall be reduced 4% for each 1,000 ft. above sea level. Installation of this furnace at altitudes above 2,000 ft. (610m) shall be in accordance with local codes, or in the absence of local codes, the National Fuel Gas Code,
ANSI Z223.1/ NFPA 54 or National Standard of Canada, Natural Gas and Propane Installation Code, CSA B149.1. Installation of this furnace at altitudes
above 2,000 ft. (610m) shall be made in accordance with the listed high Altitude Conversion Kit available with this furnace.
The Furnace input rate shall be checked by clocking the gas flow rate (CFH) and multiplying by the heating value obtained from the local utility supplier for the gas being delivered at the installed altitude. Input rate changes can be made by adjusting the Manifold Pres­sure (min 3.0 - max 3.7 in. W.C. - Natural Gas) or changing orifices (orifice change may not always be re­quired). If the desired input rate can not be achieved with a change in Manifold Pressure, then the orifices must be changed. LP installations will require an orifice change.
IMPORTANT:
Reinstall the propane orifices to the same depth as the ori­fices supplied with the equipment.
TABLE 8
GAS FLOW IN CUBIC FEET PER HOUR
2 CUBIC FOOT DIAL
SEC. FLOW SEC. FLOW SEC. FLOW SEC. FLOW
8 900 29 248 50 144 82 88 9 800 30 240 51 141 84 86
10 720 31 232 52 138 86 84
11 655 32 225 53 136 88 82 12 600 33 218 54 133 90 80 13 555 34 212 55 131 92 78 14 514 35 206 56 129 94 76 15 480 36 200 57 126 96 75 16 450 37 195 58 124 98 73 17 424 38 189 59 122 100 72 18 400 39 185 60 120 104 69 19 379 40 180 62 116 108 67 20 360 41 176 64 112 112 64
21 343 42 172 66 109 116 62 22 327 43 167 68 106 120 60 23 313 44 164 70 103 124 58 24 300 45 160 72 100 128 56 25 288 46 157 74 97 132 54 26 277 47 153 76 95 136 53 27 267 48 150 78 92 140 51 28 257 49 147 80 90 144 50
TABLE 9
FINAL MANIFOLD PRESSURE SETTINGS (inches w.c.)
FUEL 2nd Stage Max. 1st Stage Max.
NATURAL GAS 3.5" W.C. 1.7" W.C.
LP GAS 10.5" W.C. 6.0" W.C.
See Table 10 for help in selecting orifices if orifice change is required. Furnace input rate and temperature rise should be checked again after changing orifices to con­firm the proper rate for the altitude. The vent length table on page 14 shows the required vent lengths for installations at various altitudes. An op­tional high altitude kit is available for installations above 5000 feet. Installations above 12,000 feet are not allowed.
34 18-CD25D1-2
Page 35
Installer’s Guide
TABLE 10
PART NUMBERS FOR REPLACEMENT ORIFICES
DRILL
SIZE
44 45 46 47 48 49 50
PA RT
NUMBER
ORF00501 ORF00644 ORF00909 ORF00910 ORF01099 ORF00503 ORF00493
DRILL
SIZE
54 55 56 57 58 59
PA RT
NUMBER
ORF00555 ORF00693 ORF00907 ORF00908 ORF01338 ORF01339
Turn the main Gas Valve toggle switch (See Figures 30 & 31) within the unit to the “OFF” position. Turn the ex­ternal gas valve to “ON”. Purge the air from the gas lines. After purging, check all gas connections for leaks with a soapy solution -- DO NOT CHECK WITH AN OPEN FLAME. Allow 5 minutes for any gas that might have escaped to dissipate. LP Gas being heavier than air may require forced ventila­tion. Turn the toggle switch on the Gas Valve in the unit to the “ON” position.
START-UP AND ADJUSTMENT
PRELIMINARY INSPECTIONS
!
WARNING
Disconnect power to the unit before removing the blower door. Allow a minimum of 15 seconds for IFC power supply to discharge to 0 volts. Failure to follow this warning could result in property damage, personal injury or death.
With gas and electrical power “OFF”
1. Duct connections are properly sealed
2. Air cleaner and filters(if applicable) are in place
3. Venting is properly assembled
4. Blower door is in place
TABLE 11
Orifice
Twist Drill
Size If
Installed
At Sea
Level
42
43
44 45 46
47
54
55
56
57
58
2000 3000 4000 5000 6000 7000 8000 9000 10000
42 44 45 46 47 48
54 55 56 58 59
From National Fuel Gas Code - Table F-4
ALTITUDE ABOVE SEA LEVEL
and Orifice Required At Other Elevations
43
43
43
44
44
45 44 45 47 47 48
55 55
56
59 60
44 45 47 47 49
55 55 57 59 60
45 46 47 48 49
55 56 57 60
61
45 47 48 48 49
55 56 57 60 62
46 47 48 49 50
55 56 58 61 62
47
48
49
49
50
56
56
59
62
63
46 47 48 49 50
51
56 56 59 63 63
47 48 50 50 51
52
56 57
60
63
64
Figure 33
Gas Valve On / Off Toggle Switch
2nd Stage (HI) Manifold Pressure Adjustment
1st Stage (LO) Manifold Pressure Adjustment
White-Rodgers 36G
LIGHTING INSTRUCTIONS
!
WARNING
DO NOT ATTEMPT TO MANUALLY LIGHT THE BURNER. FAILURE TO FOLLOW THIS WARNING COULD RESULT IN PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
!
CAUTION
If this is done during the cold weather months, provi­sions must be taken to prevent freeze-up of all water pipes and water receptacles.
Figure 34
ROTATE THE FRONT COVER AS SHOWN
INSERT THE TOP FLANGE OF THE FRONT COVER UNDER THE LIP INSIDE THE BOX
ALL SIDE FLANGES MUST BE OUTSIDE OF THE BOX
ROTATE THE FRONT COVER INWARD MAKING SURE THAT ALL SIDE FLANGES ARE OUTSIDE OF THE BOX.
Lighting instructions appear on each unit. Each installa­tion must be checked out at the time of initial start up to insure proper operation of all components. Check out should include putting the unit through one complete cycle as outlined below.
18-CD25D1-2 35
Page 36
Installer’s Guide
Turn on the main electrical supply and set the Comfort Control above the indicated temperature. The ignitor will automatically heat, then the Gas Valve is energized to permit the flow of gas to the burners. After ignition and flame is established, the flame control module monitors the flame and supplies power to the Gas Valve until the Comfort Control is satisfied.
To shut off.
For complete shutdown: Turn the gas cock knob on the main Gas Valve to the “OFF” position (See Figures 30 &
31). Disconnect the electrical supply to the unit.
SEQUENCE OF OPERATION
NOTE: Whole House Air Cleaner is energized when blower is operating and there is a call for heat or cool. This can result in brief periods of blower operation with the whole house air cleaner off. This can occur during the heat fan off period or if the enhanced mode of operation is chosen for cooling.
Comfort Control call for heat (2-Stage Comfort Control)
Call for 1st Stage only:
W1 Comfort Control contacts close signaling the control module to run its self-check routine. After the control module has verified that the 1st Stage Pressure Switch contacts are open and the Limit Switch(es) contacts are closed, the draft blower will be energized. As the induced draft blower comes up to speed, the Pressure Switch contacts will close and the ignitor warm up period will begin. The ignitor will heat for approx. 20 seconds, then the Gas Valve is energized in 1st Stage to permit gas flow to the burners. The flame sensor confirms that ignition has been achieved within the 4 second ignition trial period. As the flame sensor confirms that ignition has been achieved, the delay to fan ON period begins timing and after approx. 45 seconds the indoor blower motor will be energized at low speed and will continue to run during the heating cycle. The whole house air cleaner will en­ergize.
Call for 2nd Stage after 1st Stage:
W2 Comfort Control contacts close signaling a call for 2nd Stage Heat. After a 30 second delay, the induced draft blower will be energized on high speed and the 2nd Stage Pressure Switch contacts will close. The Gas Valve is energized in 2nd Stage and the indoor blower motor in high speed.
2nd Stage satisfied, 1st Stage still called:
W2 Comfort Control contacts open signaling that 2nd Stage Heating requirements are satisfied. The induced draft blower is reduced to low speed allow­ing the 2nd Stage Pressure Switch contacts to open and the Gas Valve is reduced to 1st Stage. The indoor blower motor is reduced to low speed.
1st stage satisfied:
W1 Comfort Control contacts open signaling that 1st Stage heating requirements are satisfied. The Gas Valve will close and the induced draft blower and the whole house air cleaner will be de-energized. The in­door blower motor will continue to run for the fan off period (Field selectable at 60, 100, 140 or 180 seconds), then will be de-energized by the control module.
Comfort Control call for heat (1-Stage Comfort Control)
W1/ W2 (jumpered) Comfort Control contacts close sig­naling a call for heat. 1st Stage sequence of operation remains the same as above. 2nd Stage Heat will ener­gize after the Stage delay timer (10 minutes) has ex­pired.
Comfort Control satisfied:
W1/ W2 (jumpered) contacts close signaling the control module to close the Gas Valve. The induced draft blower is switched to low speed and de-energized after the post purge timer has expired. The indoor blower motor will continue to operate after the flames are extinguished and then is switched to low heat speed for the FAN­OFF period. The whole house air cleaner will be de-en­ergized.
NOTE TO INSTALLER: Review warnings and the contents of USER’S INFOR­MATION MANUAL with the homeowner when installa­tion is complete and equipment is ready to be turned over to the homeowner for normal operation.
CONTROL AND SAFETY SWITCH ADJUSTMENT
LIMIT SWITCH CHECK OUT
The limit switch is a safety device designed to close the Gas Valve should the Furnace become overheated. Since proper operation of this switch is important to the safety of the unit, it must be checked out on initial start up by the installer. To check for proper operation of the Limit Switches, set the Comfort Control to a temperature higher than the indicated temperature to bring on the Gas Valve. Re­strict the airflow by blocking the return air or by dis­connecting the blower. When the Furnace reaches the maximum outlet temperature as shown on the rating plate, the burners must shut off. If they do not shut off after a reasonable time and overheating is evident, a faulty Limit Switch is probable and the Limit Switch must be replaced. After checking the operation of the Limit Control, be sure to remove the paper or card­board from the return air inlet, or reconnect the blower. Refer to the Service Facts for additional instruc­tions.
36 18-CD25D1-2
Page 37
Installer’s Guide
INDOOR BLOWER TIMING
!
WARNING
DISCONNECT POWER TO THE UNIT BEFORE REMOV­ING THE BLOWER DOOR. FAILURE TO FOLLOW THIS WARNING COULD RESULT IN PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
Heating: The Integrated Furnace Control (IFC) con­trols the Variable Speed Indoor Blower. The blower “on” time is fixed at 45 seconds after ignition. The FAN-OFF period is field selectable by dip switches #1 and #2 lo­cated on the Integrated Furnace Control between the 5­pin and 9-pin wire connectors. The delay may be set at 60, 100, 140, or 180 seconds. The factory setting is 100 seconds (See unit wiring diagram). Cooling: The fan delay-off period is set by dip switches on the Integrated Furnace Control. The options for cooling delay off is field selectable by dip switches #5 and #6. The following table and graph explain the delay-off set­tings:
TABLE 12 FAN OFF - DELAY OPTIONS
SWITCH SETTINGS SELECTION
5 - OFF 6 - OFF NONE SAME
5 - ON 6 - OFF 1.5 MINUTES 100% *
5 - OFF 6 - ON 3 MINUTES 50%
NOMINAL AIRFLOW
AIRFLOW ADJUSTMENT
!
WARNING
Disconnect power to the unit before removing the blower door. Allow a minimum of 15 seconds for IFC power supply to discharge to 0 volts. Failure to follow this warning could result in property damage, personal injury or death.
!
WARNING
Operation with the door removed or ajar can permit the escape of dangerous fumes. All panels must be se­curely closed at all times for safe operation of the Fur­nace. Failure to follow this warning could result in property damage, personal injury or death.
Check inlet and outlet air temperatures to make sure they are within the ranges specified on the Furnace rat­ing nameplate. If the airflow needs to be increased or decreased, see the Service Facts for information on changing the speed of the blower motor.
100% if necessary
80%
Fast Cooling
1
minute
Dehumidify
7.5
minutes
50%
Efficiency
OFF
3
minutes
50%
OFF
5 - ON 6 - ON
Enhanced
Mode**
50 - 100%
This unit is equipped with a blower door switch which cuts power to the blower and Gas Valve causing shut­down when the door is removed. Operation with the door removed or ajar can permit the escape of danger­ous fumes. All panels must be securely closed at all times for safe operation of the Furnace.
* - This setting is equivalent to BAY24X045 relay ben-
efit.
** - This selection provides ENHANCED MODE, which
is a ramping up and ramping down of the blower speed to provide improved comfort, quietness, and potential energy savings. See Wiring Diagram notes on the unit or in the Service Facts for com­plete wiring setup for ENHANCED MODE. The graph which follows, shows the ramping process.
See Wiring Diagram on the unit or in the Service Facts for complete wiring setup for Enhanced Mode.
This unit is equipped with a blower door switch which cuts power to the blower and Gas Valve causing shut­down when the door is removed.
ROOM AIR COMFORT CONTROL HEAT ANTICIPATOR ADJUSTMENT
Set the Comfort Control heat anticipator according to the current flow measured, or the settings found in the notes on the Furnace wiring diagram (found in the SER­VICE FACTS or inside the furnace casing).
INSTRUCTIONS TO THE OWNERS
In the event that electrical, fuel, or mechanical failures occur, the owner should immediately turn the gas supply off at the manual Gas Valve, located in the burner compartment. Also turn off electrical power to the Furnace and contact a qualified service technician.
BURNER BOX TEMPERATURE LIMIT DEVICE
All models are equipped with a manual reset tempera­ture limit located on the Burner Box. In case of exces­sive temperature, the limit will open and cause the cir­cuit to open which shuts off all flow of gas.
18-CD25D1-2 37
Page 38
Installer’s Guide
CONDITIONS THAT AFFECT SYSTEM OPERATION
1. EXCESSIVE COMBUSTION PRESSURE (WIND IN EXCESS OF 40 M.P.H.) VENT OR FLUE BLOCKAGE
On a call for heat, the Variable Speed Draft Inducer must first ramp up to speed and close the Pressure Switch before the ignition sequence is allowed to be­gin. If the Pressure Switch does not close, the motor will ramp up to maximum speed and continue to op­erate there for about 1 minute. After one minute, the Integrated Furnace Control will turn the motor off for about 30 seconds and then back on in an attempt to reestablish proper op­eration. This condition is indicative of a highly re­stricted or blocked inlet or outlet vent pipe or a failed Pressure Switch. If pressure against induced draft blower outlet be­comes excessive, the Pressure Switch will open. If the Pressure Switch is open for more than 3.5 sec­onds, the variable speed draft inducer will speed up and attempt to close the Pressure Switch. If the Pressure Switch is not closed within 12 seconds or if the maximum speed of the motor is reached, the draft inducer sends a Fault signal to the Integrated Furnace Control. If the unit is operating in Second Stage, an Inducer Fault will cause the Furnace Control to transition the system to First Stage and it will operate there for 10 minutes before attempt­ing to run again in Second Stage. If the unit is oper­ating in First Stage, an Inducer Fault will cause the Furnace Control to shut the system down and wait 30 seconds before attempting to reestablish opera­tion in First Stage.
2. LOSS OF FLAME
If loss of flame occurs during a heating cycle, or flame is not present at the sensor, the flame control module will close the Gas Valve. The Integrated Furnace Control will then recycle the ignition se­quence, then if ignition is not achieved, it will shut off the Gas Valve and lock out the system.
3. POWER FAILURE
If there is a power failure during a heating cycle, the system will restart the ignition sequence auto­matically when power is restored, if the Comfort Control still calls for heat.
4. GAS SUPPLY FAILURE
If loss of flame occurs during a heating cycle, the system Integrated Control Module will recycle the ig­nition sequence, then if ignition is not achieved, the Integrated Control Module will shut off the Gas Valve and lock out the system.
5. INDUCED DRAFT BLOWER FAILURE
Please refer to the Variable Speed Draft Inducer troubleshooting manual for diagnostic assistance.
6. CONDENSATE DRAIN BLOCKAGE
If the condensate drain is blocked, either by debris, improper draining, or by freezing condensate, the Pressure Switch will sense the accumulation of con­densate in the Furnace drain trap. The unit will not operate properly until the condensate drain has been cleared, and the condensate flows freely.
7. RESET AFTER LOCKOUT
When the Integrated Furnace Control has shut the system down and gone into lockout, the system must be manually reset before the unit will restart. The system can be reset by turning the system power off for more than 1 second, or by removing 24VAC from the control for more than 1 second, or by removing the Comfort Control call for heat for more than 1 second but less than 20 seconds.
8. RESET AFTER BURNER BOX LIMIT SHUTDOWN
If the Furnace shuts down, one thing that can be checked is the Burner Box temperature Limit Switch. It is located on the bottom of the Burner Box. The vent and combustion air inlet termina­tions should be checked for blockage. If blockage ex­ists, clear the problem and then the reset button may be depressed. If there is no blockage of the ter-
minations, the Limit Switch must be reset by quali­fied service personnel.
WHOLE HOUSE AIR CLEANER CHECKOUT
!
CAUTION
Before changing the position of the High Voltage se­lector switch on the High Voltage power supply, make sure the power has been removed from the fur­nace and the High Voltage power supply.
Check out the Furnace Whole House Air Cleaner instal­lation in accordance with this instructions page 40. Ad­just ozone setting if needed. See figure 38 on page 40.
NOTE: Whole House Air Cleaner is energized when blower is operating and there is a call for heat or cool. This can result in brief periods of blower operation with the whole house air cleaner off. This can occur during the heat fan off period or if the enhanced mode of operation is chosen for cooling.
38 18-CD25D1-2
Page 39
Installer’s Guide
WHOLE HOUSE AIR CLEANER MAINTENANCE
1. For maximum efficiency the COLLECTION CELL should be inspected and cleaned on a regular basis.
NOTE: A 30 to 90 day cleaning interval is normal for the COLLECTION CELL and should be ad­justed based upon unit run time and the home environment.
2. The FIELD CHARGER must be removed and cleaned only by a qualified service professional.
3. The FIELD CHARGER must be cleaned at least once a year.
4. The FIELD CHARGER may require more frequent cleaning in homes with high indoor relative humid­ity (greater than 65% RH).
5. Consult your service professional about cleaning intervals.
!
WARNING
TO PREVENT INJURY OR DEATH DUE TO CONTACT WITH MOVING PARTS, TURN THE POWER TO THE FURNACE OFF BEFORE CLEANING OR SERVICING THE WHOLE HOUSE AIR CLEANER. FAILURE TO FOLLOW THIS WARNING COULD RE­SULT IN PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
CLEANING THE COLLECTION CELL
1. Turn the air conditioning system off at the Comfort Control and turn off service disconnect.
2. Remove top furnace door.
3. Slide COLLECTION CELL out of Furnace.
CLEANING
The COLLECTION CELL may be cleaned either by vacuuming (recommended method) or by washing.
VACUUM CLEANING
Remove the COLLECTION CELL from the condi­tioned space before vacuuming. Vacuum both sides of the COLLECTION CELL to clean.
WASHING
Use low-pressure water spray, such as a sink sprayer or garden hose to clean the COLLECTION CELL. Some residue may require warm water to be re­moved.
• Do NOT use soap or detergent in cleaning
the COLLECTION CELL.
• Do NOT immerse the COLLECTION CELL
completely in water.
• Do NOT place the COLLECTION CELL into
a dishwasher to clean.
• ALLOW THE COLLECTION CELL TO DRY
THOROUGHLY BEFORE REINSTALLING.
!
WARNING
RISK OF ELECTRIC SHOCK: THESE SERVICING INSTRUCTIONS ARE FOR USE BY QUALIFIED PERSONNEL ONLY. TO REDUCE THE RISK OF ELECTRIC SHOCK, DO NOT PERFORM ANY SERVICING OTHER THAN THAT CONTAINED IN THESE OPERATING INSTRUCTIONS UNLESS YOU ARE QUALIFIED TO DO SO. FAILURE TO FOLLOW THIS WARNING COULD RE­SULT IN PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
!
CAUTION
High Voltage is present within the air cleaner for opera­tion. Turn the power off and wait at least 15 seconds to allow voltage to discharge.
NOTE: System Information
Before cleaning the coil or ducts in the furnace, re­move the COLLECTION CELL and FIELD CHARGER from the air cleaner. Chemicals used during the cleaning of the Furnace, or ductwork can damage the air cleaner components and degrade the perfor­mance of the air cleaner.
Slightly tap the COLLECTION CELL to remove wa­ter retained in the filter. Allow the COLLECTION CELL to dry thoroughly before reinstalling.
CLEANING THE FIELD CHARGER
!
CAUTION
FIELD CHARGER PINS ARE SHARP. DO NOT BEND FIELD CHARGER PINS. WEAR APPROPRIATE GLOVES WHEN HANDLING THE FIELD CHARGER.
1. Turn off the Comfort Control and the service dis­connect.
2. Turn off power to the Furnace and remove the top furnace door panel.
3. Remove COLLECTION CELL.
4. Remove the inner blower door panel by removing four screws.
5. Disconnect green return wire and red high voltage wire. To remove high voltage wire, twist and pull connecter apart.
6. Remove the two 5/16" hold down screws at the front center.
7. Lift up the front of the FIELD CHARGER and slide forward to remove from the case. Lay the FIELD CHARGER on a secured flat surface.
8. Wipe down the face Plate of the FIELD CHARGER with a dry shop towel or use a vacuum cleaner. Do not disassemble the FIELD CHARGER.
18-CD25D1-2 39
Page 40
Installer’s Guide
IFC Error Flash Codes
NOTE: Do NOT use water, soap, detergent, or chemi­cals to clean the FIELD CHARGER.
Figure 35
Figure 36
INDOOR MOTOR MAINTENANCE
NOTE: Direct drive motors have bearings which are permanently lubricated and under normal use, lubri­cation is not recommended.
ROOM AIR COMFORT CONTROL HEAT ANTICIPATOR ADJUSTMENT
Set the Comfort Control heat anticipator according to the current flow measured, or the settings found in the notes on the Furnace wiring diagram (found inside the Furnace casing).
Also turn off electrical power to the Furnace and contact the service agency designated by your dealer.
!
WARNING
Should overheating occur, or the gas supply fail to shut off, shut off the Gas Valve to the unit before shut­ting off the electrical supply. Failure to follow this warning could result in property damage, personal injury, or death.
!
WARNING
Failure to follow safety warnings exactly, could result in a fire or explosion causing property damage, personal injury or loss of life.
9. To clean pins, push a block of foam down over the FIELD CHARGER Pin.
10. Rotate the foam block on the FIELD CHARGER Pin.
11. Use the foam block to clean the faceplate opening edges.
12. Repeat steps 9 and 10 for each FIELD CHARGER Pin.
13. Reverse steps to reassemble the air cleaner. The inner blower door MUST be reinstalled.
— Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any other appliance.
— WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
— Installation and service must be performed by
a qualified installer, service agency or the gas supplier.
40 18-CD25D1-2
Page 41
The following warning complies with State of California law, Proposition 65.
!
WARNING
This product contains fiberglass wool insulation!
Fiberglass dust and ceramic fibers are believed by the State of California to cause cancer through inhalation. Glasswool fibers may also cause respiratory, skin, or eye irritation.
PRECAUTIONARY MEASURES
Avoid breathing fiberglass dust.
Use a NIOSH approved dust/mist respirator.
Avoid contact with the skin or eyes. Wear long-sleeved, loose-fitting clothing, gloves, and eye protection.
Wash clothes separately from other clothing: rinse
washer thoroughly.
Operations such as sawing, blowing, tear-out, and spraying may generate fiber concentrations requiring additional respiratory protection. Use the appropriate NIOSH approved respirator in these situations.
FIRST AID MEASURES
Eye Contact – Flush eyes with water to remove dust.
Skin Contact – Wash affected areas gently with soap
If symptoms persist, seek medical attention.
and warm water after handling.
Installer’s Guide
INTEGRATED FURNACE CONTROL RED LED "ERROR" FLASH CODES
2 Flashes --- System Lockout (Retries or Recycles exceeded)
Draft Pressure Error - Possible problems:
3 Flashes ---
a) Venting problem b) Pressure switch problem c) Inducer problem
4 Flashes --- Open Temperature Limit Switch
5 Flashes --- Flame sensed when no flame should be present
6 Flashes ---
115 volt AC power reversed, ignitor (Triac) fault, poor grounding or
system voltage too low 7 Flashes --- Gas valve circuit error 8 Flashes --- Low flame sense 9 Flashes --- Open Inducer Limit switch 10 Flashes --- Inducer communication error Solid --- Internal GV error or Low TH voltage Solid Red w/Solid
Green "STATUS" LED
Continuous Reset caused by a blown fuse or internal error.
18-CD25D1-2 41
Page 42
Installer’s Guide
FAULT CODE RECOVERY
On power up, last 4 Faults, if any, will be flashed on the Red LED. The newest Fault detected will flash first and the oldest last. There will be a 2 second delay between Fault Code flashes. Solid Red LED error codes will not be displayed. The Green LED will be on solid during last Fault Re­covery. At any other time the control is powered, the Green LED indicator light will operate as shown in Table 13 and the Red LED will flash LitePort data (one flash) every 20 seconds.
TABLE 13
NATURAL GAS ONLY
TABLE OF CUBIC FEET PER HOUR OF GAS
FOR VARIOUS PIPE SIZES AND LENGTHS
PIPE
SIZE
1/2 132 92 73 63 56 50 46
3/4 278 190 152 130 115 105 96
1-1/4 1050 730 590 520 440 400 370
This table is based on pressure drop of 0.3 inch W.C. and 0.6 SP.GR. gas
10 20 30 40 50 60 70
1 520 350 285 245 215 195 180
LENGTH OF PIPE
Figure 37
*UX2/ DX2 Integrated Furnace Control
Red LitePort Green Status LED
TM
LED
Fault Code Reset
The last 4 Fault Codes can be erased from memory by powering up the control with "G" energized and then ap­plying "R" to the "W1" terminal 3 times within 6 sec­onds. The control will acknowledge the reset by turning on the Red LED for 2 seconds.
High Voltage switch
Return from air cleaner
9.6 to 8.0 KVDC
9.6 KVDC is top down |\
8.0 KVDC is bottom down |/
NOTE: In normal operation, the furnace makes a slight sound as the air passes through and is cleaned. In some applications, you may notice this sound coming from the return air vent(s). If desired, this sound level can be reduced with minimal impact on air cleaning ef­ficiency by reducing the power setting of the FIELD CHARGER. The unit is shipped with the power set at
9.6KV (high). If sound is heard, reduce power level to
8.0KV (low) at the switch on the power supply. See Fig­ure 38.
Figure 38
Green
High voltage power lead
Pink
24 VAC Hot
Red
LED
24 VAC Common
Blue
42 18-CD25D1-2
Page 43
Installer’s Guide
CHECKOUT PROCEDURES
After installation has been completed, it is recommended that the Furnace be checked against the following checklist.
1. Make sure power is “OFF” at power
disconnect switch ............................................... [ ]
2. Check all field wiring for tight connections. See that grounding of unit is in accord with code.
........................................................................... [ ]
3. Make sure unit suspension (if used) is secure and that there are no tools or loose debris in,
around or on top of the unit .............................. [ ]
4. Check all duct outlets; they must be open
and unrestricted ................................................ [ ]
5. Check drain lines and be sure all joints are tight ..
........................................................................... [ ]
6. Make sure secondary drain pan is installed ..... [ ]
7. Check power supply for correct requirements
per unit nameplate ............................................ [ ]
8. Energize the system and carefully observe its operation; make any necessary adjustment [ ]
9. Adjust ozone setting, if needed ......................... [ ]
10. Instruct owner on proper operating procedure and
leave Use and Care Manual with owner .......... [ ]
11. Check the Whole House Air Cleaner power output by the Green LED illumination. If the LED is on, this indicates High Voltage output to the air
cleaner. .............................................................. [ ]
a) Turn the Comfort Control to fan only. b) Remove blower door panel.
!
WARNING
RISK OF ELECTRICAL SHOCK: ELECTRICAL POWER IS PRESENT FOR THE NEXT 2 STEPS. THESE STEPS SHOULD BE PERFORMED ONLY BY QUALIFIED PERSON­NEL. FAILURE TO FOLLOW THIS WARNING COULD RESULT IN PERSONAL INJURY, ELECTRICAL SHOCK, OR DEATH.
c) Depress blower door switch. d) Verify with Fan running that Green LED is il-
luminated.
e) Release Blower Door Switch and put Blower
Door back on.
f) Turn Comfort Control to desired position.
18-CD25D1-2 43
Page 44
Trane 6200 Troup Highway Tyler, TX 75707
For more information contact your local dealer (distributor)
Literature Order Number 18-CD25D1-2
File Number 18-CD25D1-2
Supersedes 18-CD25D1-1
Date 03/08
3/08
Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change design and specifications without notice.
Loading...