ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES
IMPORTANT — This Document is customer property and is to remain with this unit.
Please return to service information pack upon completion of work.
*UX2*DX2
UPFLOW
UPFLOW / HORIZONTAL LEFT
DOWNFLOW
DOWNFLOW / HORIZONTAL RIGHT
A341624P03
Page 2
Installer’s Guide
▲
▲
▲
SAFETY SECTION
The following safety practices and precautions must be
followed during the installation, servicing, and operation of
this furnace.
1. Use only with the type of gas approved for this furnace.
Refer to the furnace rating plate.
2. Install this furnace only in a location and position as
specified in “Location and Clearances” (page 3), of these
instructions.
3. Provide adequate combustion and ventilation air to the
furnace space as specified in “Air for Combustion and
Ventilation” (pages 7-8), of these instructions.
4. Combustion products must be discharged outdoors.
Connect this furnace to an approved vent system only, as
specified in the “Venting” section (pages 13-23), of these
instructions.
5. Never test for gas leaks with an open flame. Use a
commercially available soap solution made specifically
for the detection of leaks to check all connections, as
specified in “Gas Piping” (page 31), of these instructions.
6. Always install the furnace to operate within the furnace’s
intended temperature-rise range with a duct system
which has an external static pressure within the allowable range, as specified on the unit rating plate. Airflow
with temperature rise for cfm versus static is shown in
the Service Facts accompanying this furnace.
7. When a furnace is installed so that supply ducts carry air
circulated by the furnace to areas outside the space
containing the furnace, the return air shall also be
handled by a duct(s) sealed to the furnace casing and
terminating outside the space containing the furnace.
8. A gas-fired furnace for installation in a residential
garage must be installed as specified in “Location and
Clearances” section (page 3), of these instructions.
9. The furnace may be used for temporary heating of
buildings or structures under construction only when the
following conditions have been met:
a. The furnace venting system must be complete and
installed per manufacturer’s instructions.
b. The furnace is controlled only by a room thermostat
(no field jumpers).
c. The furnace return air duct must be complete and
sealed to the furnace and clean air filters are in place.
d. The furnace input rate and temperature rise must be
verified to be within nameplate marking.
e. 100% of the furnace combustion air requirement must
come from outside the structure.
f. The furnace return air temperature range is between
55 and 80 degrees Fahrenheit.
g. Clean the furnace, duct work, and components upon
substantial completion of the construction process,
and verify furnace operating conditions including
ignition, input rate, temperature rise and venting,
according to the manufacturer’s instructions.
10. This product must be gas piped by a Licensed Plumber or
Gas Fitter in the Commonwealth of Massachusetts.
!
CAUTION
To prevent shortening its service life, the furnace should
not be used as a “Construction Heater” during the finishing
phases of construction until the requirements listed in item
9, a-g of the safety section of this publication have been
met. Condensate in the presence of chlorides and fluorides from paint, varnish, stains, adhesives, cleaning
compounds, and cement create a corrosive condition which
may cause rapid deterioration of the heat exchanger.
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each
appliance connected to the venting system being
placed into operation could result in carbon monoxide
poisoning or death.
The following steps shall be followed for each appliance
connected to the venting system being placed into
operation, while all other appliances connected to the
venting system are not in operation:
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and
horizontal pitch, as required in the National Fuel Gas
Code, ANSI Z223.1/NFPA 54 or the CAN/CGA B149
Installation Codes and these instructions. Determine
that there is no blockage or restriction, leakage,
corrosion and other deficiencies which could cause an
unsafe condition.
3. As far as practical, close all building doors and
windows and all doors between the space in which the
appliance(s) connected to the venting system are
located and other deficiencies which could cause an
unsafe condition.
4. Close fireplace dampers.
5. Turn on clothes dryers and any appliance not
connected to the venting system. Turn on any exhaust
fans, such as range hoods and bathroom exhausts, so
they are operating at maximum speed. Do not operate
a summer exhaust fan.
6. Follow the lighting instructions. Place the appliance
being inspected into operation. Adjust the thermostat
so appliance is operating continuously.
7. If improper venting is observed during any of the above
tests, the venting system must be corrected in
accordance with the National Fuel Gas Code,
ANSI Z221.1/NFPA 54 and/or CAN/CGA B149
Installation Codes.
8. After it has been determined that each appliance
connected to the venting system properly vents where
tested as outlined above, return doors, windows,
exhaust fans, fireplace dampers and any other gas-fired
burning appliance to their previous conditions of use.
Safety signal words are used to designate a degree or level
of seriousness associated with a particular hazard. The
signal words for safety markings are DANGER, WARNING,
and CAUTION.
a. DANGER indicates an imminently hazardous situation
which, if not avoided, will result in death or serious injury.
This signal word is limited to the most extreme situations.
b. WARNING indicates a potentially hazardous situation
which, if not avoided, could result in death or serious injury.
c. CAUTION indicates a potentially hazardous situation
which, if not avoided, may result in minor or moderate
!
WARNING
FIRE OR EXPLOSION HAZARD
Failure to follow the safety warnings exactly could result in
serious injury, death or property damage.
Improper servicing could result in dangerous operation,
serious injury, death, or property damage.
The manufacturer assumes no responsibility for equipment
installed in violation of any code or regulation.
It is recommended that Manual J of the Air Conditioning
Contractors Association (ACCA) or A.R.I. 230 be followed in
estimating heating requirements. When estimating heating
requirements for installation at Altitudes above 2000 ft.,
remember the gas input must be reduced (See GAS INPUT
ADJUSTMENT).
Material in this shipment has been inspected at the
factory and released to the transportation agency
without known damage. Inspect exterior of carton for
evidence of rough handling in shipment. Unpack
carefully after moving equipment to approximate
location. If damage to contents is found, report the
damage immediately to the delivering agency.
Codes and local utility requirements governing the installation of gas fired equipment, wiring, plumbing, and flue
connections must be adhered to. In the absence of local codes,
the installation must conform with latest edition of the
National Fuel Gas Code ANSI Z223.1 • National Installation
Code, CAN/CGA B149.1. The latest code may be obtained
from the American Gas Association Laboratories, 400 N.
Capitol St. NW, Washington D.C. 20001. 1-800-699-9277 or
www.aga.org
These furnaces have been classified as CATEGORY IV
furnaces in accordance with latest edition of ANSI Z21.47
standards • CAN/CGA 2.3. Category IV furnaces operate
with positive vent static pressure and with a flue loss less
than 17 percent. These conditions require special venting
systems, which must be gas tight and water tight. These
Category IV Direct Vent furnaces are approved for installation in Manufactured/Mobile housing when used with
BAYMFGH001A.
LOCATION AND CLEARANCES
The location of the furnace is normally selected by the
architect, the builder, or the installer. However, before the
furnace is moved into place, be sure to consider the following
requirements:
1. Is the location selected as near the chimney or vent and
as centralized for heat distribution as practical?
2. Do all clearances between the furnace and enclosure
equal or exceed the minimums stated in Clearance Table
on the Outline Drawings.
3. Is there sufficient space for servicing the furnace and
other equipment? A minimum of 24 inches front accessibility to the furnace must be provided. Any access door
or panel must permit removal of the largest component.
4. Are there at least 3 inches of clearance between the
furnace combustion air openings in the front panel and
any closed panel or door provided?
5. Are the ventilation and combustion air openings large
enough and will they remain unobstructed? If outside
air is used, are the openings set above the highest snow
accumulation level? (See the Air for Combustion and
Ventilation section.)
6. Allow sufficient height in supply plenum above the
furnace to provide for cooling coil installation, if the
cooling coil is not installed at the time of this furnace
installation.
7. A furnace shall be installed so electrical components are
protected from water.
8. If the furnace is installed in a residential garage, it
must be installed so that the burners, and the ignition
Contents
Installation Instructions3
General3
Location and Clearances3
Outline Drawings4-5
Upflow Installation6
Downflow Installations6
Air For Combustion and Ventilation7
Duct Connections8
Return Air Filters9
General Venting13
Venting Materials14
Vent Tables16-22
Horizontal Venting Through Wall18
Venting Through the Roof20
Venting Routed Through a Masonry Chimney20
Downward Venting22
Condensate Drain Instructions24
Field Wiring Diagrams26-29
Electrical Connections29
Gas Piping31
Combustion and Input Check31
High Altitude Derate33
Start-up and Adjustment34
Preliminary Inspections34
Lighting Instructions34
Sequence of Operation34
Control and Safety Switch Adjustments35
Abnormal Conditions36
IFC Error Flash Codes37
Fault Code Recovery37
source are located not less than 18 inches above the floor
and the furnace must be located or protected to avoid
physical damage from vehicles.
IMPORTANT:
The furnace must be installed level. The only allowable variation
would be slightly to the left and/or forward in upflow installations
or slightly toward the front in horizontal installations. This is
necessary for proper condensate drainage.
!
CAUTION
Do not install the furnace in a corrosive or contaminated
atmosphere. Failure to follow this warning could result in
early equipment failure.
!
WARNING
Do not install the furnace directly on carpeting, tile or other
combustible material other than wood flooring. For vertical
downflow application, subbase (BAYBASE205) must be
used between the furnace and combustible flooring. When
the downflow furnace is installed vertically with a cased
coil, a subbase is not required.
2. Diameter of Vent PIpe may be limited to 2-1/2" or 3" on some
models at different altitudes. Refer to the Vent Length Table for
proper application.
Page 5
18-CD19D8-185
Installer’s Guide
From Dwg. 21C341885 Rev. 1
*DX2 DOWNFLOW / HORIZONTAL OUTLINE DRAWING
(ALL DIMENSIONS ARE IN INCHES)
Model
(See Note 1)
DIM "A" DIM "B" DIM "C" DIM "D"
*DX2B060A9362A
*DX2B080A9422A
17-1/2"2-1/4"16-1/4"16"
*DX2C100A9482A21"2-1/2"19-3/4"19-1/2"
*DX2D120A9602A24-1/2" 2-15/16" 23-1/4"23"
* Prefix May Be "A" or "T"Notes:
1. Diameter of Vent Pipe may be limited
to 2-1/2" or 3" on some models at
different altitudes. Refer to the Vent
Length Table for proper application.
Page 6
Installer’s Guide
▲
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
UPFLOW INSTALLATION
Standoffs and screws (See Figure 1) are included with the
cased coils for attachment to the furnace. There are clearance alignment holes near the bottom of the coil wrapper.
Drill screws are used to engage the furnace top flanges. The
standoff is inserted into the cabinet alignment hole. The drill
screws are inserted through the standoffs then screwed into
the furnace flange. The coil is always placed downstream of
the furnace airflow.
1
CASED
UPFLOW
FURNACE
COIL
STANDOFFS (4)
STANDOFFS
(BOTH SIDES)
SCREWS
(BOTH SIDES)
DOWNFLOW INSTALLATIONS
2
!
WARNING
Do not install the furnace directly on carpeting, tile or other
combustible material other than wood flooring. For
vertical downflow application, subbase (BAYBASE205)
must be used between the furnace and combustible
flooring. When the downflow furnace is installed vertically
with a cased coil, a subbase is not required.
The coil and furnace must be fully supported when used in
the horizontal position. It is always recommended that an
auxiliary drain pan be installed under a horizontally installed evaporator coil or 90% gas furnace. Connect the
auxiliary drain line to a separate drain line (no trap is
needed in this line).
Three brackets (with screws) are included with downflow
furnaces for installation to stabilize and secure the furnace
and TXC cased coil in the horizontal position. See Figure 4.
4
CASED COIL CONNECTION
BRACKET FOR DOWNFLOW
FURNACE IN HORIZONTAL
DOWNFLOW ONLY
IMPORTANT:
The 2/4TXC cased coil must be placed downstream of the
furnace. In horizontal installations, the apex of the coil
may point either toward or away from the furnace. See
the 2/4TXC coil Installer's Guide for more details.
The cased coil is secured to the furnace and both the furnace
and the cased coil must be properly supported. The brackets
mount using the rear screws on the coil case and use the
screws provided to secure the bracket to the furnace. The
remaining bracket is placed as close to center as possible
(horizontally) between the coil case front and the furnace
bottom channel (for downflow/horizontal furnace). Use four of
the screws provided to secure the bracket. The upflow furnace,
converted to horizontal, aligns and attaches the TXC coil as in
Figure 1. However, the coil requires additional support.
The furnace may be installed in an attic or crawl space in the
horizontal position by placing the furnace on the left side (as
viewed from the front in the vertical position). The horizontal
furnace installation in an attic should be on a service platform large enough to allow for proper clearances on all sides
and service access to the front of the furnace (See Figure 5 &
Clearance Tables, pages 4-5). Line contact is only permissible between lines formed by intersections of the top and two
sides of the furnace casing and building joists, studs, or
framing.
The furnace may be placed horizontally in a crawl space on a
pad or other noncombustible material which will raise the
unit for sufficient protection from moisture.
5
UPFLOW/
HORIZONTAL
SHOWN WITH
DIRECT VENT
Page 7
6
50 CU. FT. OR MORE
UNCONFINED
The furnace must be supported at both ends and the
middle when installed horizontally. The furnace must
also be elevated approximately 4-6 inches to allow
clearance for the condensate drain to exit the cabinet in
the horizontal position.
The horizontal furnace may also be suspended from the joists
using 3/8" all-thread rods with pieces of angle iron underneath the furnace to form a hanging rack at both ends and
the midpoint. The rods need to be of sufficient length to
allow for proper clearances from combustible materials. The
angle iron needs to be at least 32" in length to allow for
access to service panels.
AIR FOR COMBUSTION AND VENTILATION
If these furnaces are installed in a nondirect vent capacity
then the adequate flow of combustion and ventilating air
must not be obstructed from reaching the furnace. Air
openings provided for combustion air must be kept free of
obstructions which restrict the flow of air. Airflow restrictions affect the efficiency and safe operation of the furnace.
Keep this in mind should you choose to remodel or change
the area which contains your furnace. Furnaces must have a
free flow of air for proper performance.
Provisions for combustion and ventilation air shall be made
in accordance with latest edition of Section 5.3, Air for
Combustion and Ventilation, of the National Fuel Gas Code,
ANSI Z223.1 — CAN/CGA B149.1 or applicable provisions of
the local building codes. Special conditions created by
mechanical exhausting of air and fireplaces must be considered to avoid unsatisfactory furnace operation.
OUTSIDE AIR IS RECOMMENDED
The use of indoor air for most applications is acceptable,
unless there is the presence of corrosive chemicals orcontamination. Certain types of installation will require
the use of outside air for combustion.
The following types of installations will require use of
OUTDOOR AIR for combustion, due to chemical exposures:
* Commercial buildings
* Buildings with indoor pools
* Furnaces installed in “confined” laundry rooms
* Furnaces installed in “confined” hobby or craft rooms
* Furnaces installed near chemical storage areas.
Exposure to the following substances in the combustion air
supply will also require OUTDOOR AIR for combustion:
* Permanent wave solutions
* Chlorinated waxes and cleaners
* Chlorine based swimming pool chemicals
* Water softening chemicals
* Deicing salts or chemicals
* Carbon Tetrachloride
* Halogen type refrigerants
* Cleaning solvents (such as perchloroethylene)
* Printing inks, paint removers, varnish, etc.
* Hydrochloric acid
* Cements and glues
* Antistatic fabric softeners for clothes dryers
* Masonry acid washing materials
Installer’s Guide
Furnace locations may be in a “confined space” or an
“unconfined space”.
Unconfined space is defined in Figure 6. These spaces may
have adequate air by infiltration to provide air for combustion
and ventilation. Buildings with tight construction (for
example, weather stripping, heavily insulated, caulked, vapor
barrier, etc.), may need additional air to be provided as
described for confined space.
Confined spaces are installations with less than 50 cu. ft. of
space per 1000 BTU/hr input from all equipment installed.
Air for combustion and ventilation requirements can be
supplied from inside the building as in Figure 8 or from the
outdoors, as in Figure 9.
TABLE 2
MINIMUM AREA IN SQUARE FEET
FOR UNCONFINED SPACE INSTALLATIONS
FURNACE
MAXIMUM BTUH
INPUT RATING
60,000
80,000
100,000
120,000
7
CONFINED
SPACE
1. All air from inside the building as in Figure 8: The
confined space shall be provided with two permanent
openings communicating directly with an additional
room(s) of sufficient volume so that the combined volume
of all spaces meets the criteria for an unconfined space.
The total input of all gas utilization equipment installed
in the combined space shall be considered in making this
determination. Refer to Table 2 for minimum open areas
requirements.
2.
All air from outdoors as in Figure 9: The confined space
shall be provided with two permanent openings, one
commencing within 12 inches of the top and one commencing within 12 inches of the bottom of the enclosure.
The openings shall communicate directly, or by ducts,
with the outdoors or spaces (crawl or attic) that freely
communicate with the outdoors. Refer to Table 3, for
minimum open areas requirements.
MINIMUM FREE AREA IN SQUARE INCHES
EACH OPENING (FURNACE ONLY)
Furnace
Maximum
BTUH/INPUT
Rating
60,000
80,000
100,000
120,000
WITH 8 FT. CEILING
MINIMUM AREA IN SQUARE FEET
OF UNCONFINED SPACE
375
500
625
875
TABLE 3
Air
From
Inside
100
100
100
120
Air From Outside
Vertical
Duct
15
20
25
30
Horizontal
Duct
30
40
50
60
18-CD19D8-187
Page 8
Installer’s Guide
8
9
DUCT CONNECTIONS
Air duct systems should be installed in accordance with
standards for air conditioning systems, National Fire Protection Association Pamphlet No. 90. They should be sized in
accordance with ACCA Manual D or whichever is applicable.
Central furnaces, when used in connection with cooling units,
shall be installed in parallel or on the upstream side of the
cooling coil to avoid condensation in the heat exchanger. With
a parallel flow arrangement, the dampers or other means used
to control flow of air shall be adequate to prevent chilled air
from entering the furnace, and if manually operated, must be
equipped with means to prevent operation of either unit
unless the damper is in full heat or cool position.
On any job, flexible connections of nonflammable material may
be used for return air and discharge connections to prevent
transmission of vibration. Though these units have been
specifically designed for quiet, vibration free operation, air ducts
can act as sounding boards and could, if poorly installed,
amplify the slightest vibration to the annoyance level.
When the furnace is located in a utility room adjacent to the
living area, the system should be carefully designed with
returns to minimize noise transmission through the return
air grille. Although these furnaces are designed with large
blowers operating at moderate speeds, any blower moving a
high volume of air will produce audible noise which could be
objectionable when the unit is located very close to a living
area. It is often advisable to route the return air ducts under
the floor or through the attic. Such design permits the
installation of air return remote from the living area (i.e.
central hall).
When the furnace is installed so that the supply ducts carry
air circulated by the furnace to areas outside the space
containing the furnace, the return air shall also be handled
by a duct(s) sealed to the furnace and terminating outside
the space containing the furnace.
RETURN AIR DUCT CONNECTION
NOTE:
On upflow 5 or 6 ton airflow models where the airflow
requirement exceeds 1800 CFM - Models will require
return air openings and filters on: (1) both sides; or (2)
one side and the bottom; or (3) just the bottom.
818-CD19D8-18
All return air duct systems should provide for installation of
return air filters.
1. Determine the appropriate position to set the furnace in
order to connect to the existing supply and return
ductwork.
2. For side return installations on upflow models, remove
the insulation around the opening in the blower
compartment.
3. The side panels of the upflow furnace include locating
notches that are used as guides for cutting an opening
for return air, refer to Figure 10 and the outline
drawing on page 4 for duct connection dimensions for
various furnaces.
Page 9
Installer’s Guide
▲
▲
4. If a 3/4" flange is to be used for attaching the air inlet
duct, add to cut where indicated by dashed lines in
Figure 11. Cut corners diagonally and bend outward to
form flange.
5. If flanges are not required, and a filter frame is installed,
cut along knockout guidelines.
6. Upflow Furnaces: Use the optional filter rack on either
side or on the bottom if the filter is to be used within the
furnace cabinet.
When the upflow furnace is installed in the horizontal
right or left application and a return duct is attached to
the top side as shown in Figure 10, install the filter in a
remote location.
!
WARNING
Do not install the filter in the return duct directly above the
furnace in horizontal applications. Install the filter remotely.
Installing the filter directly above the furnace in horizontal
applications may cause property damage, serious injury or
death.
!
WARNING
TO PREVENT INJURY OR DEATH DUE TO CONTACT
WITH MOVING PARTS, TURN THE POWER TO THE
FURNACE OFF BEFORE SERVICING FILTERS.
Do not install the filter in the return duct directly above
the furnace in horizontal applications.
When the upflow furnace is installed in the horizontal
right or left application and a close coupled (less than
36") return duct is attached to the bottom side of the
furnace as shown in Figure 10, securely attach a 1/2"
mesh metal hardware cloth protective screen to the
inside bottom of the filter grill to prevent personal
injury from contacting moving parts when reaching
into the return opening to replace the filter.
REMOVE FILTER FROM UPFLOW
FURNACE WHEN RETURN DUCT IS
ATTACHED TO FURNACE TOP SIDE
(HORIZONTAL LEFT OR RIGHT
APPLICATIONS) AS SHOWN.
FILTER
0
Close coupled (less than 36") return (filter directly
beneath bottom side return) is not recommended due to
noise considerations.
Downflow Furnaces: Brackets are factory supplied to
mount filters in the return air duct work.
7. Connect the duct work to the furnace. See Outline
Drawing (pages 4&5) for supply and return duct size and
location. Flexible duct connectors are recommended to
connect both supply and return air ducts to the furnace.
If only the front of the furnace is accessible, it is
recommended that both supply and return air plenums
are removable.
8. When replacing a furnace, old duct work should be
cleaned out. Thin cloths should be placed over the
registers and the furnace fan should be run for 10 minutes. Don’t forget to remove the cloths before you start
the furnace.
Return Air Filters
(Filter and filter rack are not supplied with
unit)
TYPICAL UPFLOW RETURN AIR FILTER INSTALLATIONS
These furnaces require high velocity type air filters. The
optional filters may be located within the furnace blower
compartment for UPFLOW furnaces in either a BOTTOM or
SIDE (left side or right side) return air inlet. Some optional
filters may need to be trimmed for side or bottom filter use.
NOTE:
On upflow 5 or 6 ton airflow models where the airflow
requirement exceeds 1800 CFM - Models will require
return air openings and filters on: (1) both sides; or (2)
one side and the bottom; or (3) just the bottom.
q
LOCATING
NOTCHES
PROVIDED
FOR SIDE
RETURN
CUTOUT
SEE OUTLINE DRAWING
*
*
*
*
*
CUT OUT
FOR
SIDE
FILTER
FRONT
of Furnace
Close coupled (less than 36")
return (filter directly beneath bottom
side return) not recommended due to
noise considerations. If used, securely
attach 1/2" mesh metal hardware cloth
protective screen to the inside bottom of
filter grill.
18-CD19D8-189
The furnace and the blower filter rack installation can be seen
in Figures 12 & 13.
The optional furnace filter in the bottom or side configuration
can be removed by simply turning the two latches on the
blower door and tilting the door forward.
The filter rails are spring loaded for automatic adjustment to
allow standard size, locally obtainable replacement filters.
The filter rack itself slides to adjust to the required width
needed for bottom or side return.
Page 10
Installer’s Guide
TABLE 4
UPFLOW FURNACE RETURN AIR FILTERS
CABINET
WIDTH
14-1/2"114" X 25" X 1"17-1/2" X 25" X 1"
17-1/2"117" X 25" X 1"17-1/2" X 25" X 1"
21"120" X 25" X 1"17-1/2" X 25" X 1"
24-1/2"124" X 25" X 1"17-1/2" X 25" X 1"
**NOTE: For upflow 5 ton airflow models where the airflow
requirement exceeds 1800 CFM - Models will require return air
openings and filters on: (1) both sides, or (2) one side and the
bottom, or (3) just on the bottom
QTY*
CABINET
BOTTOM FILTER
CABINET
SIDE FILTER
w
Airflow
NOTE: The narrow 14.5" width furnace cabinet prevents use
of the filter rack for right side return. Pre-drill clearance
holes and then attach filter clips with the screws provided.
The filter clip with the leaf spring mounts in the rear of the
cabinet
OPTIONAL FILTER RACK INSTALLATION FOR BOTTOM
RETURN
With the filter removed, the filter rack is compressed and
then inserted into the bottom of the furnace. The retaining
screw/pin on each side inserts into engagement holes at the
bottom of the furnace cabinet side. See Figures 13, 14 & 16.
NOTE: Remove the bottom front channel to install the filter
rack in the 14-1/2" width cabinet furnaces.
t
Blower Deck
Engagement
Hole
r
e
Airflow
BOTTOM FILTER RACK INSTALLATION
ENGAGEMENT
HOLE DETAIL
(Typical both sides
and blower deck)
y
Furnace
Cabinet
Side
Engagement Hole
For
Filter Rack
Installation With
Bottom Return
VIEW
Filter
Rack
Filter Rack
Retaining
Screw/Pin
Optional Filter Rack Accessory Kit
BAYRACK960A
1018-CD19D8-18
Page 11
Installer’s Guide
Airflow
Airflow
TABLE 5
Cabinet Width Left Side BottomRight Side
14.5X
17.5XXX
21XXX
24.5XXX
1. UD060C/R936K0 has 10x7 blower which requires use of alternate
filter clips for left side filter. "K1" and later use the filter rack.
2. Remove bottom front channel to install or reposition filter rack.
X - All Models
OPTIONAL FILTER RACK INSTALLATION FOR SIDE
RETURN AIR ON UPFLOW FURNACES (Left or Right)
If side air return is desired, the following instructions should
be used:
a. Open or remove the blower door.
b. Leave the bottom panel in place. (Some models
require field supplied bottom panels.)
c. After the side cutout is made following the directions
in the “Return Air Duct Connections” section on
pages 8 and 9; compress the filter rack and reinstall in
the side of the furnace. Confirm that the upper
retaining pin/screw locks into the engagement hole in
the blower deck and the lower pin/screw rests against
the side of the bottom panel. See Figures 14, 15, &
17-20.
d. Install the furnace filter on the side. See Figures 14,
15, & 17-20.
u
Furnace
Cabinet
Side
1
BOTTOM ENGAGEMENT
X2Use Alternate Filter Clips Only
Filter Rack
Retaining
Screw/Pin
Filter
Rack
o
Typical Upflow Left Side Return Filter Rack Installation
p
SIDE
CUTOUT
RETAINING
PIN
(Both Sides)
SPRINGS
Airflow
FILTER
RACK
RAILS
Airflow
BOTTOM
PANEL
INSTALLED
SIDE
CUTOUT
RETAINING
PIN
(Both Sides)
SPRINGS
Engagement Hole
For
Installation With
Bottom Return
i
BLOWER
DECK
Furnace
Cabinet
Side
Filter Rack
Engagement Hole
For
Filter Rack
Installation With
Side
Return
Filter Rack
Retaining
Screw/Pin
Bottom Panel
Furnace
Blower
Deck
Filter
Rack
Assembly
BOTTOM
PAN EL
INSTALLED
Typical Upflow Right Side Return Filter Rack Installation
FILTER
RACK
RAILS
a
Airflow
Optional door kit
BAYFLTR206
Typical Horizontal Filter Installation
18-CD19D8-1811
Page 12
Installer’s Guide
RETURN AIR FILTERS FOR UPFLOW FURNACE
IN HORIZONTAL CONFIGURATION
When the Upflow Furnace is installed in a horizontal configuration, the filter must never be installed inside or outside the
cabinet directly above the blower assembly. See Figure 11
(page 9). Remote filter grilles may be used for homeowner
convenience or the filters may be installed in the duct work
upstream of the furnace. See Figures 11 (page 9) and 21 (page
1. Determine the location to be used. The furnace cabinet
has dimples for location of the alternate furnace clips
(Side return only). Pre-drill clearance holes with a
3/16" drill. Bottom return holes are pre-drilled.
2. Install the clips in front and rear of the desired location
using the screws provided. The filter clip with the leaf
spring mounts in the rear of the cabinet. See Figure 22.
s
REAR
SIDE
CUT-OUT
TYPICAL DOWNFLOW FURNACE
RETURN AIR FILTER INSTALLATIONS
d
Airflow
f
ALTERNATE FILTER
CLIPS LOCATION
Optional horizontal filter conversion kits are BAYFLTR203
for 17 1/2" width cabinets, BAYFLTR204 for 21" width
cabinets, and BAYFLTR205 for 24" width cabinets. These
include filters and brackets necessary for horizontal filters.
In addition, optional door kit BAYFLTR206 is also available.
See Figures 21 and 24.
INSTALLING THE OPTIONAL FILTER
The filter may need to be cut to fit the unit depending on the
location of the return air filter.
A score line and the words “CUT HERE” are located on the
end of the filter. If your application requires cutting the filter,
do so as indicted by the score mark.
TABLE 6
UNIT
SIZE
RETURN AIR
BOTTOMSIDE
14-1/2"CUT ON LINE DO NOT CUT
17-1/2"DO NOT CUT DO NOT CUT
21"DO NOT CUT CUT ON LINE
24-1/2"DO NOT CUT CUT ON LINE
Airflow
Optional door kit
BAYFLTR206
Two high velocity type air filters are required for each downflow furnace. Downflow furnace filters must be located
outside the furnace cabinet. Typical installations are shown
in Figures 23 and 24. Tables 7 and 8 provide information for
installation of the filter retaining brackets shipped with
downflow furnaces.
* Location dimension is from end of duct to the screw holes for the bracket.
CABINET
WIDTH
14-1/2"13-1/4"12"14"
17-1/2"16-1/4"15"14"
21"19-3/4"19-1/2"14"
24-1/2"23-1/4"22"14"
RETURN
DUCT
WIDTH
FILTER
SIZE
TABLE 8
FILTER ACCESS
OPENING -
DIMENSION "A"
FILTER BRACKET
LOCATION *
FILTER ACCESS
OPENING -
DIMENSION "B"
1218-CD19D8-18
Page 13
Installer’s Guide
▲
The following warning complies with State of California law, Proposition 65.
!
WARNING
Hazardous Gases!
Exposure to fuel substances or by-products of incomplete
fuel combustion is believed by the state of California to
cause cancer, birth defects, or other reproductive harm.
Carbon monoxide, fire or smoke can cause serious bodily
injury, death, and/or property damage.
A variety of potential sources of carbon monoxide can be found
in a building or dwelling such as gas-fired clothes dryers, gas
cooking stoves, water heaters, furnaces and fireplaces. The
U.S. Consumer Product Safety Commission recommends
that users of gas-burning appliances install carbon monoxide
detectors as well as fire and smoke detectors per the
manufacturer’s installation instructions to help alert dwelling occupants of the presence of fire, smoke or unsafe levels of
carbon monoxide. These devices should be listed by Underwriters Laboratories, Inc. Standards for Single and Mul-tiple Station Carbon Monoxide Alarms, UL 2034 or CSA
International Standard, Residential Carbon MonoxideAlarming Devices, CSA 6.19
NOTE:
The manufacturer of your furnace does not test any detectors and makes no representations regarding any brand or
type of detector.
GENERAL VENTING
THIS FURNACE MUST BE VENTED TO THE OUTDOORS.
THESE FURNACES ARE INDUCED DRAFT VENTED
AND MUST NOT BE CONNECTED TO ANY VENT
SERVING ANOTHER APPLIANCE. PLEASE NOTE THAT
THESE FURNACES USE POSITIVE-PRESSURE VENT
SYSTEMS.
Proper venting is essential to obtain maximum efficiency
from a condensing furnace. Proper installation of the vent
system is necessary to assure drainage of the condensate
and prevent deterioration of the vent system.
American Gas Association has certified the design of condensing furnaces for a minimum of 0" clearance from combustible
materials with a single wall plastic vent pipe.
The recommended system is assembled from 2", 2-1/2", or 3"
plastic pipe and fittings (See Table 9, page 15). Where the
system is routed to the outdoors through an existing masonry
chimney containing flue products from another gas appliance,
or where required by local codes, then 3" venting of Type 29-4C
stainless steel must be used in place of PVC material.
These furnaces have been classified as CATEGORY IV
furnaces in accordance with ANSI Z21.47 “latest edition”
standards. Category IV furnaces operate with positive vent
pressure and with a vent gas temperature less than 140° F.
above the dewpoint. These conditions require special venting
systems, which must be gas tight and water tight.
NOTE:
When an existing furnace is removed from a venting
system serving other gas appliances, the venting system is
likely to be too large to properly vent
attached appliances.
the remaining
The following steps shall be followed with each appliance
remaining connected to the common venting system placed in
operation, while the other appliances remaining connected to
the common venting system are not in operation.
1. Seal any unused openings in the common venting system.
2. Visually inspect the venting system for proper size and
horizontal pitch and determine there is no blockage or
restriction, leakage, corrosion or other deficiencies which
could cause an unsafe condition.
3. Insofar as is practical, close all building doors and
windows and all doors between the space in which the
appliances remaining connected to the common venting
system are located and other spaces of the building. Turn
on clothes dryers and any appliances not connected to
the common venting system. Turn on any exhaust fans,
such as range hoods and bathroom exhausts, so they will
operate at maximum speed. Do not operate a summer
exhaust fan, close fireplace dampers.
4. Follow the lighting instructions. Place the appliance
being inspected in operation. Adjust thermostat so
appliance will operate continuously.
5. After it has been determined that each appliance remaining connected to the common venting system properly
vents when tested as outlined above, return door, windows, exhaust fans, fireplace dampers and any other gasburning appliance to their previous conditions of use.
If improper venting is observed during any of the above tests,
the remaining common venting system must be corrected.
Correction could require rerouting or resizing the remaining
vent system.
IMPORTANT:
These furnaces may be installed as Direct Vent (sealed
combustion) or as Nondirect vent (single pipe). The furnaces
are shipped DIRECT VENT with sealed combustion.
For DIRECT VENT APPLICATION: The furnaces must be
vented to the exterior of the house and combustion air MUST
come through the inlet air pipe FROM OUTSIDE AIR. The pipes
DO NOT have to exit the exterior of the house together or on
the same side of the house.
For NONDIRECT VENT APPLICATION: The furnace shall be
vented to the exterior of the house, but combustion air may
enter from the surrounding area as long as combustion air
requirements are met. (See AIR FOR COMBUSTION AND
VENTILATION)
FURNACE VENT/INLET PIPE INSTALLATION
There are many different variations of the vent/inlet air pipe
combination. The vent/inlet air combination used for installation of these furnaces depends on the needs of the location.
However, these guidelines must be followed:
1. The furnace must vent outside the structure.
2. Furnace combustion air requirements must be met for
nondirect, single pipe applications (See example on
next page).
3. For direct vent application of these furnaces, the vent
pipe and air inlet pipe do not have to exit in the same air
space or even on the same surface of the structure.
However, the longest individual pipe will decide the value
for the longest allowable equivalent vent/inlet air length as
shown in the vent length table.
18-CD19D8-1813
Page 14
Installer’s Guide
NOTE:
BAYVENT200* accessories can be used for inlet and outlet
terminals when the pipes do not exit the structure together.
The following are EXAMPLES ONLY:
EX. 1 —
Example 1 shows that the vent may go vertical while the inlet
air may be on any side of the structure. The vent pipe would
decide the maximum equivalent length for the pipe depending
on the furnace and pipe size.
ent
V
Air
Inlet
Furnace
EX. 2 —
Example 2 shows the vent pipe exhausting through the roof
and the inlet air coming from the interior of the house (See
Note). The inlet air coming from the interior of the house
must meet combustion requirements for area, etc., as shown
in the section AIR FOR COMBUSTION AND VENTILATION in this Installer’s Guide.
Vent
Air
Inlet
(See Note)
Furnace
EX. 4 —
The inlet air does not have to come from outside the structure.
Example 4 shows the inlet air (See Note), may come from the
attic if the requirements for combustion air are met as shown
in the section AIR FOR COMBUSTION AND VENTILATION.
Attic
Vent
Vent
Air
Inlet
(See Note)
Furnace
NOTE:
If only the flue gas pipe is to the outside of the structure, a
straight section of pipe (long enough to exit the furnace
cabinet) must be attached to the inlet air side with an elbow
(which is 5 to 10 equiv. ft.) installed on the end to prevent
dust and debris from falling directly into the furnace.
VENT FITTING MATERIAL – PLASTIC
Gas and liquid tight single wall vent fittings, designed for
resistance to corrosive flue condensate, MUST be used
throughout.
Listed in Table 9 are 2", 2-1/2", and 3" size fittings that meet
these requirements. The materials listed are various grades
of PVC and ABS plastic.
PIPE JOINTS: All joints must be fastened and sealed to
prevent escape of combustion products into the building.
NOTE:
It is recommended that the first joints from the furnace be
connected and sealed with high temperature RTV. This will
enable the pipes to be removed later without cutting.
EX. 3 —
Example 3 shows the vent exiting one side of the house while
the inlet air is on the opposite side of the structure. Here the
vent pipe length must be within the allowable length for the
size of furnace and size of the vent pipe. This example
demonstrates that the pipes do not have to exit on the same
side of the structure.
Air
Inlet
Furnace
1418-CD19D8-18
Be sure to properly support these joints.
BONDING OF PVC
Commercially available solvent cement for PVC must be
used to join PVC pipe fittings. Follow instructions on container carefully.
Pipe and Fitting – ASTM D1785, D2466, D2661, & D2665
PVC Primer and Solvent Cement – ASTM D2564
Procedure for Cementing Joints – Ref ASTM D2855
1. Cut pipe square, remove ragged edges and burrs. Chamfer end of pipe, then clean fitting socket and pipe joint
area of all dirt, grease, moisture or chips.
2. After checking pipe and socket for proper fit, wipe socket
and pipe with cleaner-primer. Apply a liberal coat of
primer to inside surface of socket and outside of pipe.
DO NOT ALLOW PRIMER TO DRY BEFORE APPLY-
V
ent
ING CEMENT.
3. Apply a thin coat of cement evenly in the socket. Quickly
apply a heavy coat of cement to the pipe end and insert
pipe into fitting with a slight twisting movement until it
bottoms out.
Page 15
Installer’s Guide
4. Hold the pipe in the fitting for 30 seconds to prevent
tapered socket from pushing the pipe out of the fitting.
5. Wipe all excess cement from the joint with a rag. Allow
15 minutes before handling. Cure time varies according
to fit, temperature and humidity.
NOTE:
Follow venting instructions carefully when using PVC
cement.
IMPORTANT:
All joints must be water tight. Flue condensate is somewhat
acidic, and leaks can cause equipment damage.
TABLE 9
PVC VENT FITTING MATERIAL These fittings are available from your Gas Furnace Distributors.
* - Allowable temperatures based on classifications covered in ASTM D4396 [Deflection Temps Under Load (264 PSI)]
** - Allowable temperatures based on classifications covered in ASTM D1784 [Deflection Temps Under Load (264 PSI)]
*** - Allowable temperatures based on classifications covered in ASTM D3965 [Deflection Temps Under Load (264 PSI)]
Connection of the pipe and collar of the combustion air inlet
should just be a friction fit. It is recommended that the inlet
air joint be sealed with RTV type sealant to allow the joint to
be separated for possible future service. The inlet and vent
pipes must be properly supported throughout the entire
length.
Connection of the vent pipe to the vent collar should also be
accomplished using RTV type sealant. This type sealant
provides a connection which remains flexible and can be
separated in the future if service needs require the removal of
the vent pipe for service or clearance.
NOTE:
Vent termination kit BAYAIR30AVENTA or BAYVENT200B
may be used in addition to the horizontal and vertical
termination options shown in the following figures.
18-CD19D8-1815
g
VENT AND INLET AIR CONNECTIONS
Seal INLET AIR PIPE
with RTV sealant
Seal VENT PIPE
with RTV sealant
Front of Furnace
Page 16
VENT TABLES
Installer’s Guide
TABLE 10 VENT LENGTH TABLE
ALTITUDE
0-7,000 Feet2 INCH PIPE2.5 INCH PIPE3 or 4 INCH PIPE
UX2/DX2B060A9362A200200200
UX2/DX2B080A9422A50120200
UX2/DX2C100A9482ANot Allowed60200
UX2/DX2D120A9602ANot AllowedNot Allowed200
7,000-9,500 Feet2 INCH PIPE2.5 INCH PIPE3 or 4 INCH PIPE
UX2/DX2B060A9362A100100100
UX2/DX2B080A9422A2560100
UX2/DX2C100A9482ANot Allowed30100
UX2/DX2D120A9602ANot AllowedNot Allowed100
9,500-12,000 Feet2 INCH PIPE2.5 INCH PIPE3 or 4 INCH PIPE
UX2/DX2B060A9362A505050
UX2/DX2B080A9422ANot Allowed3050
UX2/DX2C100A9482ANot AllowedNot Allowed50
UX2/DX2D120A9602ANot AllowedNot Allowed50
NOTES: * - First letter may be "A" or "T"
1. Minimum vent length for all models: 3' horizontal or 3' vertical.
2. DO NOT MIX PIPE DIAMETERS IN THE SAME LENGTH OF PIPE OUTSIDE THE FURNACE CABINET (Except
adapters at the top of the furnace). If different inlet and vent pipe sizes are used, the vent pipe must adhere to the
maximum length limit shown in the table above (See note 6 below for exception). The inlet pipe can be of a larger
diameter, but never smaller than the vent pipe.
3. MAXIMUM PIPE LENGTHS MUST NOT BE EXCEEDED! THE LENGTH SHOWN IS NOT A COMBINED TOTAL, IT IS
THE MAXIMUM LENGTH OF EACH (Vent or Inlet air pipes).
4. One SHORT radius 90° elbow is equivalent to 10' of 3" pipe and one LONG radius elbow is equivalent to 6' of 3" pipe.
One 90° elbow is equivalent to 7½' of 2½" pipe or 5' of 2" pipe. Two 45° elbows equal one 90°elbow.
5. The termination tee or bend must be included in the total number of elbows. If the BAYAIR30AVENTA termination kit is
used, the equivalent length of pipe is 5 feet. BAYVENT200B equivalent length is 0 feet.
6. Pipe adapters are field supplied (except 120).
MAXIMUM TOTAL EQUIVALENT LENGTH IN FEET
FOR VENT AND INLET AIR (SEE NOTES)
HORIZONTAL INSTALLATION
(Upflow / Horizontal or Downflow / Horizontal)
NOTE:
In horizontal venting when the factory supplied “off-set” (2X3
reducing coupling) is used for 3” vent pipe installation, make
sure the marking “Top” is located on the top side of the pipe.
The straight side must be on bottom for proper condensate
drainage. This coupling is factory supplied only with the
following models: *UC120 & *DC120, *UX120 & *UY120
*UX100 & *UY100, *UX808C960, and all *DX & *DY models.
h
FURNACE
VENT
OUTLET
2" TO 3" COUPLING
FACTORY SUPPLIED ONLY WITH
THE FOLLOWING MODELS:
UC120 & DC120
UX120 & UY120
UX100 & UY100
UX080C960
ALL DX & DY MODLES
1618-CD19D8-18
Page 17
3" PIPING
2", 2-1/2"
or 3" PIPING
REDUCING
COUPLING,
FIELD SUPPLIED
IF NEEDED
SEAL ALL
WALL CAVITIES
HORIZONTAL VENTING THROUGH WALL
j
9" MINIMUM
9" MINIMUM
ELBOW AND TEE MUST BE
AS CLOSE TOGETHER
AS POSSIBLE
Installer’s Guide
9" MINIMUM
k
40" UPFLOW OR
DOWNFLOW MODELS
9" MINIMUM
COMBUSTION
AIR INLET
9" MINIMUM
POSSIBLE CONFIGURATIONS FOR TWO PIPE VENTING SYSTEMS
NOTE: VENT AND INLET MUST BE SUPPORTED
SEE VENTING TABLE
STRAPS OR OTHER SUITABLE SUPPORTS
AT MAXIMUM OF 3'-0" INTERVALS
UPWARD PITCH -- 1/4" PER FOOT
FIRST SUPPORT SHOULD BE AS
CLOSE TO FURNACE CONNECTION
AS POSSIBLE.
NOTE: ANY FITTINGS PASSING
THROUGH AN UNHEATED SPACE
MUST BE INSULATED.
USE ONLY
APPROVED
TERMINATION
OUTSIDE
WALL
AT A MAXIMUM OF 3' INTERVALS
STRAP
(FIELD SUPPLIED)
VENT
COMBUSTION AIR
ELBOW
(FIELD
SUPPLIED)
BAYAIR30AVENTA
COMBUSTION
AIR
RAIN CAP
VENT
1" + 1/2"
18-CD19D8-1817
TEE
BAYVENT200B
Page 18
Installer’s Guide
▲
l
;
7.2"
3.2"
COMBUSTION
AIR
ANCHORS
(4 req.)
VENT
VENT
VENT
CAP
PLATE
VENT
MAINTAIN 12" (18" FOR CANADA) MINIMUM
CLEARANCE ABOVE HIGHEST ANTICIPATED
SNOW LEVEL OR GRADE WHICHEVER IS GREATER
BAYVENT200B
12" MINIMUM
TO OVERHANG
SCREWS
(4 req.)
z
x
BAYAIR30AVENTA
(Sidewall)
!
CAUTION
When the vent pipe is exposed to temperatures below
freezing, i.e., when it passes through unheated spaces, etc.,
the pipe must be insulated with 1/2 inch (22.7 mm) thick
Armaflex-type insulation or equal.
If the space is heated sufficiently to prevent freezing, then
the insulation would not be required. If domestic water
pipes are not protected from freezing then it is assumed the
space meets the condition of a heated space.
HORIZONTAL VENTING THROUGH WALL
These furnaces may be installed as direct vent (as
shipped) or as nondirect vent. Installation must
conform to national, state, and local codes.
The vent & inlet terminals must be located at least 12"
minimum above normally expected snow accumulation level.
Avoid areas where staining or condensate drippage may be
a problem.
Location of the vent/wind terminal should be chosen to meet
the requirements of Figure 39 for either direct or nondirect
vent applications.
PITCH — Venting through the wall must maintain 1/4" per
foot pitched upward to insure that condensate drains back to
the furnace.
FLUE GAS DEGRADATION — The moisture content of
the flue gas may have a detrimental effect on some building
materials. This can be avoided by using the roof or chimney
venting option. When wall venting is used on any surface that
can be affected by this moisture, it is recommended that a
corrosion resistant shield (24 inches square) be used behind
the vent terminal. This shield can be wood, plastic, sheet
metal, etc. Also, silicone caulk all cracks, seams and joints
within 3 feet of the vent terminal.
COMBUSTIBLE MATERIAL WALL
A minimum clearance of 1" to combustible materials must be
maintained when using single wall stainless steel venting.
See Figure 31.
Shield material to be a minimum of 24 gauge stainless or
aluminized sheet metal. Minimum dimensions are 12"x12".
Shield must be fastened to both inside and outside of wall.
Use screws or anchor type fasteners suited to the outside or
inside wall surfaces.
NONCOMBUSTIBLE MATERIAL WALL
The hole through the wall must be large enough to maintain
pitch of vent and properly seal.
Use cement mortar seal on inside and outside of wall. See
Figure 32.
1818-CD19D8-18
Page 19
VENTING THROUGH THE ROOF
Installer’s Guide
c
v
SUPPORT HORIZONTAL PIPE EVERY 3' 0"
WITH THE FIRST SUPPORT AS CLOSE TO
THE FURNACE AS POSSIBLE. INDUCED
DRAFT BLOWER, HOUSING, AND
FURNACE MUST NOT SUPPORT THE
WEIGHT OF THE FLUE PIPE.
REMOVE RIBS
FROM CAP
VENT
b
REMOVE RIBS
FROM CAP
COMBUSTION
AIR
ROOF BOOT
(FIELD SUPPLIED)
VENT
VENT
MAINTAIN 12 IN.
(18 IN. FOR CANADA)
MINIMUM CLEARANCE
ABOVE HIGHEST
ANTICIPATED SNOW
LEVEL. MAXIMUM OF
24 IN. ABOVE ROOF
SUPPORT
(FIELD SUPPLIED)
COMBUSTION
AIR
ELBOW
(FIELD SUPPLIED)
MAINTAIN 12 IN.
(18 IN. FOR CANADA)
MINIMUM CLEARANCE
ABOVE HIGHEST
ANTICIPATED SNOW
LEVEL. MAXIMUM OF
24 IN. ABOVE ROOF.
n
SEAL BETWEEN FLANGE, PIPE,
COUPLING AND METAL PANEL
WITH HI TEMP RTV SILICONE SEALANT
SUPPORT
FLANGE
GALVANIZED FIRESTOP SHOULD
BE FABRICATED WITH 3-7/8" DIA.
HOLE FOR SUPPORT FLANGE
(12" x 12" PANEL OR 12" DIA MIN.)
( 1" ACCEPTABLE FOR TYPE 29-4C STAINLESS STEEL VENT PIPE )
COMBUSTION
AIR
FLUE PIPE
COUPLING
CEILING
CLEARANCE ( 0" ACCEPTABLE FOR PVC VENT PIPE )
BAYAIR30AVENTA (VERTICAL)
18-CD19D8-1819
VENTING THROUGH CEILING
Page 20
Installer’s Guide
▲
▲
VENTING THROUGH THE ROOF
When penetrating roof with a 2" PVC vent pipe, a 2" electrical
conduit flashing may be used for a weather tight seal.
Lubricate flexible seal on flashing before PVC pipe is pushed
through the seal. (Field Supplied)
NOTE:
No vent cap as shown in Figure 34 is the preferred method
for vertical vent termination in extremely cold climates.
In extreme climate conditions, insulate the exposed pipe
above the roof line with Armaflex type insulation.
VENT FITTING MATERIAL – STAINLESS STEEL
Gas and liquid tight single wall metal vent fitting, designed
for resistance to corrosive flue condensate such as Type
29-4C MUST be used throughout.
These fittings and fitting accessories are to be supplied
locally.
DIRECTION OF STAINLESS STEEL FITTING
All stainless steel fitting must be installed with male end
towards the furnace.
All horizontal stainless steel sections must be positioned
with the seam on top.
All long horizontal sections must be supported to prevent
sagging.
All pipe joints must be fastened and sealed to prevent escape
of combustion products into the building.
,
FLUE PIPE
COUPLING TO SUPPORT
PIPE FROM ANGLES
OR OTHER SUITABLE
SUPPORT METHOD
PVC PLASTIC VENTING – ONLY
THROUGH UNUSED CHIMNEY
STAINLESS
STAINLESS STEEL
STEEL
VENT CAP
VENT CAP
(OPTIONAL)
SEE CAUTION
FLUE PIPE
6 IN. MIN.
SUPPORT THE SINGLE
WALL FLUE PIPE AND
CENTER IT IN THE
CHIMNEY OPENING WITH
ANGLES AS SHOWN OR
ANOTHER EQUIVALENT
MANNER.
COUPLING
AS REQUIRED
m
m
TYPE 29-4C STAINLESS STEEL VENTING –
USED THROUGH CHIMNEY THAT VENTS
ANOTHER GAS APPLIANCE
STAINLESS STEEL
STAINLESS
VENT CAP
STEEL
(OPTIONAL)
VENT CAP
SEE CAUTION
6 IN. MIN.
SUPPORT THE SINGLE WALL
STAINLESS STEEL GAS
VENTING AND CENTER IT IN
THE CHIMNEY OPENING WITH
ANGLES AS SHOWN OR
ANOTHER EQUIVALENT
MANNER.
NOTE:
HORIZONTAL VENTING
TO VERTICAL VENTING
NOTE:
HORIZONTAL VENTING
TO VERTICAL VENTING
!
CAUTION
Do not run vent through chimney for wood burning or
oil furnaces or incinerators or any other gas appliance.
IMPORTANT –
The single wall flue pipe joints must be sealed.
The 90° elbow connection to vertical pipe must be sealed to
prevent condensate leakage to base of masonry chimney.
VENTING ROUTED THROUGH A MASONRY CHIMNEY
2018-CD19D8-18
!
CAUTION
Do not run vent through chimney for wood burning or oil
furnaces or incinerators.
If remaining free area between single wall flue pipe and
masonry chimney is to be used for another gas appliance
venting area must be sufficient to vent that appliance and
that appliance must be connected to chimney with
separate entry openings.
IMPORTANT –
The single wall flue pipe joints must be sealed.
The 90° elbow connection to vertical pipe must be sealed to
prevent condensate leakage to base of masonry chimney.
Vertical clearance to ventilated soffit located above
D=
the terminal within a horizontal distance of 2 feet
(61 cm) from the center line of the terminal
E=Clearance to unventilated soffit**
F=Clearance to outside corner**
G= Clearance to inside corner**
Clearance to each side of center line extended
H=
above meter/regulator assembly
I=Clearance to service regulator vent outlet3 feet (91 cm)*
Clearance to nonmechanical air supply inlet to
J=
building or the combustion air inlet to any other
appliance
K=Clearance to a mechanical air supply inlet6 feet (1.83m)
Clearance above a paved sidewalk or paved
L=
driveway located on public property
M= Clearance under veranda, porch, deck, or balcony12 inches (30 cm) ‡*
Notes:
1. In accordance with the current CSA B149.1 Natural Gas and Propane Installation Code.
2. In accordance with the current ANSI Z223.1/NFPA 54 National Fuel Gas Code.
†. A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwelling and serves both dwellings.
‡. Pemitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.
* Clearance in accordance with local installation codes and the requirements of the gas supplier and the manufacturer's Installation Instructions.
12 inches (30 cm) for appliances > 10,000 Btuh (3 kw)
and =/< 100,000 Btuh (30 kw),
36 inches (91 cm) for appliances > 100,000 Btuh (30 kw)
3 feet (91 cm) with a height 15 feet (4.5 m) above the
6 inches (15 cm) for appliances =/< 10,000 Btuh (3 kw),
12 inches (30 cm) for appliances > 10,000 Btuh (3 kw)
and =/< 100,000 Btuh (30 kw),
36 inches (91 cm) for appliances > 100,000 Btuh (30 kw)
12 inches (30 cm)12 inches (30 cm)
4 feet (1.2m) below or to the side of opening;
1 foot (0.3m) above opening.
**
meter/regulator assembly
4 feet (1.2 m) below or to side of opening;
1 foot (300 m) above opening
3 feet (91 cm) above if within
10 feet (3m) horizontally
7 feet (2.13 m) †7 feet (2.13 m)
*
18-CD19D8-1821
Page 22
Installer’s Guide
TABLE 12 Direct Vent Terminal Clearances
Canadian InstallationsUS Installations
Clearance above grade, veranda, porch,
A=
deck, or balcony
Clearance to window or door that may be
B=
opened
C=Clearance to permanently closed window**
Vertical clearance to ventilated soffit
located above the terminal within a
D=
horizontal distance of 2 feet (61 cm)
from the center line of the terminal
E=Clearance to unventilated soffit**
F=Clearance to outside corner**
G= Clearance to inside corner**
Clearance to each side of center line
H=
extended above meter/regulator assembly
I=Clearance to service regulator vent outlet3 feet (91 cm)*
Clearance to nonmechanical air supply
J=
inlet to building or the combustion air
inlet to any other appliance
K=Clearance to a mechanical air supply inlet6 feet (1.83m)3 feet (91 cm) above if within 10 feet (3m) horizontally
Clearance above a paved sidewalk or
L=
paved driveway located on public property
Clearance under veranda, porch, deck,
M=
or balcony
Notes:
1. In accordance with the current CSA B149.1 Natural Gas and Propane Installation Code.
2. In accordance with the current ANSI Z223.1/NFPA 54 National Fuel Gas Code.
†. A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwelling and serves both dwellings.
‡. Pemitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.
* Clearance in accordance with local installation codes and the requirements of the gas supplier and the manufacturer's Installation Instructions.
and =/< 100,000 Btuh (30 kw),
36 inches (91 cm) for appliances > 100,000 Btuh (30 kw)
12 inches (30 cm)12 inches (30 cm)
6 inches (15 cm) for appliances =/< 10,000 Btuh (3 kw),
9 inches (23 cm) for appliances > 10,000 Btuh (3 kw)
and =/< 50,000 Btuh (15 kw),
12 inches (30 cm) for appliances > 50,000 Btuh (15 kw)
**
meter/regulator assembly
6 inches (15 cm) for appliances =/< 10,000 Btuh (3 kw),
9 inches (23 cm) for appliances > 10,000 Btuh (3 kw)
and =/< 50,000 Btuh (15 kw),
12 inches (30 cm) for appliances > 50,000 Btuh (15 kw)
7 feet (2.13 m) †*
12 inches (30 cm) ‡*
*
/
DOWNWARD VENTING
Furnace may be in vertical or horizontal configuration.
All horizontal pipes must be
supported at maximum of 3
foot intervals
Slope 1/4" per ft.
Slope 1/4" per ft.
NOTES:
A) Condensate trap for vent pipe must be a minimum of 6 inches in height.
B) Condensate trap for vent and inlet pipe must be connected into a condensate drain pump; an open or
vented drain; or it can be connected to the outlet hose of the furnace's condensate trap. Outdoor draining of the furnace and coil condensate is permissible if allowed by local codes. Caution should be taken
to prevent drains from freezing or causing slippery conditions that could lead to personal injury. Excessive draining of condensate may cause saturated ground conditions that may result in damage to plants.
C) The condensate trap should be primed at initial start up prior to heating season operation.
DOWNWARD VENT LENGTH IS
LIMITED TO A MAXIMUM OF
EQUIVALENT FEET.
40 Inch
Upflow or
Downflow
Furnace
6" Min.
15
2218-CD19D8-18
Page 23
Installer’s Guide
IMPORTANT:
The Commonwealth of Massachusetts requires compliance
with regulation 248 CMR 4.00 and 5.00 for installation of
through – the – wall vented gas appliances as follows:
For all side wall horizontally vented gas fueled equipment
installed in every dwelling, building or structure used in
whole or in part for residential purposes, including those
owned or operated by the Commonwealth and where the
side wall exhaust vent termination is less than seven (7)
feet above finished grade in the area of the venting,
including but not limited to decks and porches, the
following requirements shall be satisfied:
1.INSTALLATION OF CARBON MONOXIDE
DETECTORS. At the time of installation of the side wall
horizontal vented gas fueled equipment, the installing
plumber or gasfitter shall observe that a hard wired
carbon monoxide detector with an alarm and battery backup is installed on the floor level where the gas equipment
is to be installed. In addition, the installing plumber or
gasfitter shall observe that a battery operated or hard
wired carbon monoxide detector with an alarm is installed
on each additional level of the dwelling, building or
structure served by the side wall horizontal vented gas
fueled equipment. It shall be the responsibility of the
property owner to secure the services of qualified licensed
professionals for the installation of hard wired carbon
monoxide detectors
a.In the event that the side wall horizontally vented
gas fueled equipment is installed in a crawl space or an
attic, the hard wired carbon monoxide detector with alarm
and battery back-up may be installed on the next adjacent
floor level.
b.In the event that the requirements of this
subdivision can not be met at the time of completion of
installation, the owner shall have a period of thirty (30)
days to comply with the above requirements; provided,
however, that during said thirty (30) day period, a battery
operated carbon monoxide detector with an alarm shall be
installed.
2.APPROVED CARBON MONOXIDE
DETECTORS. Each carbon monoxide detector as required
in accordance with the above provisions shall comply with
NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
3.SIGNAGE. A metal or plastic identification plate
shall be permanently mounted to the exterior of the
building at a minimum height of eight (8) feet above grade
directly in line with the exhaust vent terminal for the
horizontally vented gas fueled heating appliance or
equipment. The sign shall read, in print size no less than
one-half (1/2) inch in size, “GAS VENT DIRECTLY
BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS”.
4.INSPECTION. The state or local gas inspector of
the side wall horizontally vented gas fueled equipment
shall not approve the installation unless, upon inspection,
the inspector observes carbon monoxide detectors and
signage installed in accordance with the provisions of 248
CMR 5.08(2)(a)1 through 4.
This appliance requires a special venting system. If
BAYAIR30AVENTA or BAYVENT200B are used, a copy of
the installation instructions for the kit shall remain with
the appliance or equipment at the completion of
installation. The venting system installation instructions
can be obtained from the manufacturer by writing to the
following address:
American Standard, Inc.
6200 Troup Highway
Tyler, TX 75707
Attention: Manager of Field Operations Excellence
IMPORTANT:
Products installed in Canada must use vent systems that
are certified to the Standard for Type BH Gas Venting Systems (ULC S636) for Class II-A venting systems (up to
65°C). Components of the vent system must not be interchanged with other vent systems or unlisted pipe or fittings.
Plastic components, specified primers, and glues must be
from a single system manufacturer and not intermixed with
other system manufacturer's vent system parts. In addition, the first three feet of the vent pipe must be visible for
inspection.
18-CD19D8-1823
Page 24
Installer’s Guide
▲
CONDENSATE DRAIN INSTRUCTIONS
!
CAUTION
▲
It is recommended that a drain pan be installed under the
furnace to prevent property damage, personal injury or
death from leaking condensate.
!
VERTICAL APPLICATIONS
Upflow furnace - The connection tubing for left and right
side drainage is shipped in the blower compartment. Install
the connection tubing from the trap to the side of the unit and
trim all excess tubing to avoid kinks.
Downflow furnace - The furnace is shipped with the left
side drainage setup. To change the right side drain, remove
the drain lines from the trap, rotate the trap 180° so it exits
to the right, reconnect the lines, and run a 1/2" CPVC pipe
from the trap out through the right side knock-out. Use RTV
silicone sealant to connect the CPVC pipe to the trap for ease
of removing to clean the trap.
#
UPFLOW (VERTICAL)
Left side
Right side
UPFLOW (VERTICAL)
Use
extension
hose here
Use Inducer Drain
hose without
extension
@
UPFLOW HORIZONTAL 17" UNITS
(Left side only)
2418-CD19D8-18
UPFLOW HORIZONTAL 21" & 24" UNITS
$
(Left side only)
Page 25
HORIZONTAL APPLICATIONS
Installer’s Guide
Upflow and Downflow furnaces - All horizontal applications are left side only. It is always recommended that the
auxiliary drain pan be installed under a horizontally installed evaporator and/or 90% gas furnace. Connect the
auxiliary drain pan to a separate drain line (no trap is needed
in this line).
The trap must be repositioned to the exterior of the cabinet.
Remove the trap from its present location and reposition the
trap outside of the unit, through the long circular hole, next to
the secondary recuperative cell. Remove the larger drain line
(from the secondary cell) and trim to fit between the secondary cell and the new trap location. On upflow units, plug the
hole in the blower deck where the tube went through.
%
Left
side
&
Cut off curved end of
Inducer drain hose
DOWNFLOW (HORIZONTAL)
Remove the hose from the induced blower and reposition into
the other drain tap of the inducer, which is located 90°
clockwise around the inducer. Move the cap from that drain
tap to the unused drain tap. On upflow units, plug the hole in
the blower deck where the tube went through. This tube on
downflow units will need to be cut to fit between the inducer
and the trap. On upflow units, this tube may need to be
extended, using the tubing shipped with the furnace.
Connections must be made to an OPEN/VENTED DRAIN.
Outdoor draining of the furnace and coil condensate is
permissible if allowed by local codes. Caution should be taken
to prevent drains from freezing or causing slippery conditions
that could lead to personal injury. Excessive draining of
condensate may cause saturated ground conditions that may
result in damage to plants.
^
DOWNFLOW (VERTICAL)
Use CPVC tubing from Trap outlet,
over burner box to cabinet exit
DOWNFLOW (VERTICAL)
Right
side
NOTE:
Use 1/2" or larger PVC or CPVC pipe and fittings as required
for drain connections (fittings, pipe and solvent cement not
provided).
NOTE:
A corrosion resistant condensate pump must be used if a
pump is required for a specific drain system.
IMPORTANT:
The condensate drain should be installed with provisions to
prevent winter freeze-up of the condensate drain line. Frozen
condensate will block drains, resulting in furnace shutdown. If
the drain line cannot be installed in a conditioned space, then
UL listed heat tape should be applied as required to prevent
freezing (per manufacturer’s instructions). The heat tape should
be rated at 5 or 6 watts per foot at 120 volts. Self-regulating
(preferred) or thermostatically controlled heat tape is required.
Evaporator and furnace condensate drain piping may be
manifolded together. A primary drain vent stack must be
installed and terminated below the outlet of the secondary
heat exchanger drain connection to prevent water from
damaging furnace controls if the primary drain outlet plugs
up. Where the furnace is installed above a finished ceiling,
the primary drain vent stack must be installed such that
overflow from the vent stack opening will flow into an axillary
drain pan in order to prevent water damage to the finished
ceiling below.
18-CD19D8-1825
Page 26
Installer’s Guide
*
Field Wiring Diagr
If upflow furnace is installed
over a finished ceiling, overflow
from the primary drain vent
stack must flow into an auxillary
drain pan to prevent damage to
the finished ceiling below.
TO 115 V 1 PH.,
60 HZ., POWER
SUPPLY PER
LOCAL CODES
HUM SEE
NOTE 5
EAC SEE
NOTE 5
From Dwg. 21B341333 Rev. 1
B/C
SEE
NOTE 7
SEE
NOTE 6
2 STAGE
FURNACE
TWIN
B/C
FIELD WIRING DIAGRAM FOR 2 STAGE FURNACE
2 STAGE HEATING
USING A 2 STAGE HEATING THERMOSTAT
NO COOLING
TO 115 V 1 PH.,
60 HZ., POWER
SUPPLY PER
LOCAL CODES
HUM SEE
NOTE 5
EAC SEE
NOTE 5
From Dwg. 21B342024 Rev. 0
2618-CD19D8-18
Page 27
OUTDOOR UNIT
(NO TRANSFORMER)
Installer’s Guide
FIELD WIRING DIAGRAM FOR 2 STAGE FURNACE
2 STAGE HEATING, 1 STAGE COOLING
USING A 2 STAGE HEATING, 1 STAGE COOLING THERMOSTAT
(OUTDOOR SECTION WITHOUT TRANSFORMER)
2 STAGE
FURNACE
SEE
B/C
NOTE 7
SEE
NOTE 8
SEE
NOTE 6
TWIN
B/C
TO 115 V 1 PH.,
60 HZ., POWER
SUPPLY PER
LOCAL CODES
OUTDOOR UNIT
(NO TRANSFORMER)
HUM SEE
NOTE 5
EAC SEE
NOTE 5
FIELD WIRING DIAGRAM FOR 2 STAGE FURNACE
2 STAGE HEATING, 1 STAGE COOLING
USING A 1 STAGE HEATING, 1 STAGE COOLING THERMOSTAT
(OUTDOOR SECTION WITHOUT TRANSFORMER)
2 STAGE
FURNACE
SEE
B/C
NOTE 7
SEE
NOTE 8
SEE
NOTE 6
TWIN
B/C
FIELD ADDED
JUMPER (NOTE 9)
TO 115 V 1 PH.,
60 HZ., POWER
SUPPLY PER
LOCAL CODES
From Dwg. B342021 Rev. 0
18-CD19D8-1827
HUM SEE
NOTE 5
EAC SEE
NOTE 5
From Dwg. B342019 Rev. 0
Page 28
Installer’s Guide
OUTDOOR UNIT NO. 1
(WITH TRANSFORMER)
SEE NOTE 3
RC
ISOLATION RELAY
(FIELD SUPPLIED)
ALTERNATE CONNECTION
OUTDOOR UNIT NO. 1
(NO TRANSFORMER)
1 STAGE
HEATING / COOLING
THERMOSTATFURNACE NO. 1
TWINNING CONNECTION DIAGRAM
FOR TWINNING UX/DX-R FURNACES
1 STAGE HEAT / 1 STAGE COOLING THERMOSTAT
FURNACE NO. 2
BLOWER OPERATION OF
UNIT NO. 2 IS SYNCRONIZED
WITH UNIT NO. 1 VIA SIGNALS
FROM TWIN CONNECTION.
TWIN
SEE NOTE 4
JUMPER W1 TO W2
ON BOTH UNITS.
2ND STAGE WILL FIRE
10 MINUTES AFTER 1ST.
TWIN
R1
ISOLATION RELAY
SEE NOTE 4
OUTDOOR UNIT NO. 1
(WITH TRANSFORMER)
SEE NOTE 3
RC
ISOLATION RELAY
(FIELD SUPPLIED)
ALTERNATE CONNECTION
OUTDOOR UNIT NO. 1
(NO TRANSFORMER)
B/C
SEE NOTE 5
2 STAGE HEAT / 1 STAGE COOLING THERMOSTAT
2 STAGE HEATING
1 STAGE COOLING
THERMOSTATFURNACE NO. 1
B/C
TWINNING CONNECTION DIAGRAM
FOR TWINNING UX/DX-R FURNACES
TWIN
R1
ISOLATION RELAY
(FIELD SUPPLIED)
SEE NOTE 4
ISOLATION RELAY
(FIELD SUPPLIED)
SEE NOTE 4
R1
R2
B/C
FURNACE NO. 2
BLOWER OPERATION OF
UNIT NO. 2 IS SYNCRONIZED
WITH UNIT NO. 1 VIA SIGNALS
FROM TWIN CONNECTION.
TWIN
SEE NOTE 4
ISOLATION RELAY
SEE NOTE 4
R1
R2
From Dwg. 21B341336 Rev. 2
B/C
2818-CD19D8-18
SEE NOTE 5
B/C
From Dwg. 21B341337 Rev. 2
B/C
Page 29
OUTDOOR UNIT NO. 2
▲
(NO TRANSFORMER)
SEE NOTE 3
TWINNING CONNECTION DIAGRAM
FOR TWINNING UX/DX-R FURNACES
2 STAGE HEATING
1 STAGE COOLING
THERMOSTATFURNACE NO. 1
2 STAGE HEAT / 2 STAGE COOLING THERMOSTAT
TWIN
FURNACE NO. 2
BLOWER OPERATION OF
UNIT NO. 2 IS SYNCRONIZED
WITH UNIT NO. 1 VIA SIGNALS
FROM TWIN CONNECTION.
TWIN
Installer’s Guide
OUTDOOR UNIT NO. 1
(NO TRANSFORMER)
!
WARNING
SEE NOTE 5
B/CB/C
CARBON MONOXIDE POISONING HAZARD
Failure to follow the installation instructions for the venting
system being placed into operation could result in carbon
monoxide poisoning or death.
ISOLATION RELAY
(FIELD SUPPLIED)
SEE NOTE 4
R1
R2
SEE NOTE 4
From Dwg. 21B341338 Rev. 2
B/C
ISOLATION RELAY
SEE NOTE 4
R1
R2
OUTDOOR UNIT
(WITH TRANSFORMER)
SEE NOTE 3
RC
ISOLATION RELAY
(FIELD SUPPLIED)
ALTERNATE CONNECTION
ELECTRICAL CONNECTIONS
Make wiring connections to the unit as indicated on enclosed
wiring diagram. As with all gas appliances using electrical
power, this furnace shall be connected into a permanently
live electric circuit. It is recommended that furnace be
provided with a separate “circuit protection device” electric
circuit. The furnace must be electrically grounded in accordance with local codes or in the absence of local codes with
the National Electrical Code, ANSI/NFPA 70 or CSA C22.1
Electrical Code, if an external electrical source is utilized.
The integrated furnace control is polarity sensitive.
The hot leg of the 120V power supply must be connected to
the black power lead as indicated on the wiring diagram.
Provision for hooking up an electronic air cleaner and or
humidifier is provided on the integrated control.
Refer to the SERVICE FACTS literature and unit wiring
diagram attached to furnace.
18-CD19D8-1829
Page 30
Installer’s Guide
(
AUTOMATIC GAS VALVE
WITH MANUAL SHUT-OFF
MAIN MANUAL
SHUT-OFF VALVE
GROUND
UNION
JOINT
)
MAIN MANUAL
SHUT-OFF VALVE
GROUND
UNION
JOINT
DRIP
LEG
AUTOMATIC GAS VALVE
WITH MANUAL SHUT-OFF
DRIP
LEG
UPFLOW MAY BE LEFT OR
RIGHT HAND GAS PIPING
AUTOMATIC GAS VALVE
Q
WITH MANUAL SHUT-OFF
MAIN MANUAL
SHUT-OFF VALVE
GROUND
UNION JOINT
THE DOWNFLOW (VERTICAL) MAY BE INSTALLED
LEFT OR RIGHT SIDE GAS PIPING
GROUND UNION JOINT
DRIP
LEG
MAIN MANUAL
SHUT-OFF
VALVE
AUTOMATIC GAS VALVE WITH
MANUAL SHUT-OFF
HORIZONTAL FURNACE GAS PIPING MAY BE FROM EITHER SIDE
(Typical UPFLOW Furnace in horizontal configuration shown)
DRIP
LEG
3018-CD19D8-18
Page 31
GAS PIPING
▲
The upflow/horizontal furnace is shipped standard for left
side installation of gas piping. A knockout is provided on the
right side for an alternate gas piping arrangement. See Figure
49.
The installation of piping shall be in accordance with piping
codes and the regulations of the local gas company. Pipe joint
compound must be resistant to the chemical reaction with
liquefied petroleum gases.
Refer to piping Table 13, for delivery sizes. Connect gas
supply to the unit, using a ground joint union and a manual
shut-off valve as shown in Figures 49 & 50. National codes
require a condensation drip leg to be installed ahead of the
controls as shown in Figures 49-51.
!
CAUTION
Use a backup wrench on the gas valve when installing gas
piping to prevent damage to the gas valve and manifold
assembly.
The furnace and its individual shut-off valve must be disconnected from the gas supply piping system during any pressure
testing of that system at test pressures in excess of 1/2 psig
(3.5 kPa).
The furnace must be isolated from the gas supply piping by
closing its individual manual shut-off valve during any
pressure testing of the gas supply piping system at test
pressures equal to or less than 1/2 psig (3.5 kPa).
NOTE:
Maximum pressure to the gas valve for natural gas is 13.8"
W.C. Minimum pressure is 5.0" W.C. Maximum pressure to
the gas valve for propane is 13.8" W.C. Minimum pressure
is 11.0" W.C.
All gas fittings must be checked for leaks using a soapy
solution before lighting the furnace. DO NOT CHECK
WITH AN OPEN FLAME!
Installer’s Guide
TABLE 13 NATURAL GAS ONLY
TABLE OF CUBIC FEET PER HOUR OF GAS
FOR VARIOUS PIPE SIZES AND LENGTHS
PIPE
SIZE
1/2132927363565046
3/427819015213011510596
1-1/41050730590520440400370
This table is based on pressure drop of 0.3 inch W.C. and 0.6 SP.GR. gas
10203040506070
1520350285245215195180
TABLE 14 ORIFICE SIZES
INPUT
RATING
BTUH
60,000
80,000
100,000
120,000
COMBUSTION AND INPUT CHECK
(See also High Altitude Derate)
1. Make sure all gas appliances are off except the furnace.
2. Clock the gas meter with the furnace operating (determine the dial rating of the meter) for one revolution.
3. Match the “Sec” column in the gas flow (in cfh) Table 15
with the time clocked.
4. Read the “Flow” column opposite the number of seconds
clocked.
5. Use the following factors
For 1 Cu. Ft. Dial Gas Flow CFH =
For 1/2 Cu Ft. Dial Gas Flow CFH =
For 5 Cu. Ft. Dial Gas Flow CFH =
NUMBER
BURNERS
LENGTH OF PIPE
MAIN BURNER ORIFICE
OF
NAT. GASLP GAS
3
4
5
6
if necessary:
Chart Flow Reading ÷ 2
Chart Flow Reading ÷ 4
10X Chart Flow Reading ÷ 4
45
45
45
45
DRILL SIZE
56
56
56
56
W
▲
CAUTION:
18-CD19D8-1831
Return all tubing, caps, and/or plugs to original positions when pressure checks are completed.
Page 32
Installer’s Guide
▲
6. Multiply the final figure by the heating value of the gas
obtained from the utility company and compare to the
nameplate rating. This must not exceed the nameplate rating.
!
WARNING
HAZARD OF EXPLOSION
REPLACE AND/ OR TIGHTEN ALL PLUGS REMOVED OR
LOOSENED WHEN ADJUSTING GAS PRESSURE. LEAK
CHECK THE FITTINGS BEFORE PLACING THE FURNACE
INTO REGULAR SERVICE.
FAILURE TO FOLLOW THIS WARNING COULD RESULT IN
FIRE, EXPLOSION, PROPERTY DAMAGE, OR DEATH.
Gas Valve Adjustment
Changes can be made by adjusting the manifold pressure
(See Table 16), or changing orifices (orifice change may
not always be required). To adjust the manifold pressure:
1. Turn off all electrical power to the system.
2. Attach a manifold pressure gauge with flexible tubing to
the outlet pressure boss marked “OUT P” on WhiteRodgers gas valve model 36G or 36J. See Figure 53 for
White-Rodgers gas valve model 36J. See Figure 54 for
White-Rodgers gas valve model 36G.
3. Loosen (Do Not remove) the pressure tap test set screw
one turn with 3/32" hex wrench.
a. The pressure tap adjustment kit (KIT07611)
contains a 3/32" hex wrence, a 5/16" hose and a
connector and can be ordered through Global Parts.
NOTE:
The manifold pressure must be referenced to the burner
box. The burner box pressure tap equalizes the gas valve
pressure regulator. Manifold pressure is checked by
installing a tee (field supplied) in the tubing, between the tee
coming from the burner box tube and the gas valve,
addition to
the regular gas valve pressure tap on the
in
outlet side of the gas valve. See Figure 52.
TABLE 18
Orifice
Twist Dr ill
Size If
Installed
At Sea
Level
42
43
44
45
46
47
54
55
56
57
58
Outlet
Pressure
Boss
2000 3000 4000 5000 6000 7000 8000 9000 10000
42
44
45
46
47
48
54
55
56
58
59
From National Fuel Gas Code - Table F-4
2nd Stage (HI) Manifold
Pressure Adjustment
ALTITUDE ABOVE SEA LEVEL
and Orifice Required At Other Elevations
43
43
43
44
44
45
44
45
47
47
48
55
55
56
59
60
44
45
47
47
49
55
55
57
59
60
45
46
47
48
49
55
56
57
60
61
45
47
48
48
49
55
56
57
60
62
46
47
48
49
50
55
56
58
61
62
47
48
49
49
50
56
56
59
62
63
46
47
48
49
50
51
56
56
59
63
63
1st Stage (LO)
Manifold Pressure
Adjustment
47
48
50
50
51
52
56
57
60
63
64
T
ROTATE THE FRONT
COVER AS SHOWN
INSERT THE TOP FLANGE
OF THE FRONT COVER
UNDER THE LIP INSIDE
THE BOX
ALL SIDE FLANGES MUST
BE OUTSIDE OF THE BOX
ROTATE THE FRONT
COVER INWARD MAKING
SURE THAT ALL SIDE
FLANGES ARE OUTSIDE
OF THE BOX.
See Table 18 for help in selecting orifices if orifice change is
required. Furnace input rate and temperature rise should be
checked again after changing orifices to confirm the proper rate
for the altitude.
The vent length table on page 16 shows the required vent
lengths for installations at various altitudes. An optional
high altitude kit is available for installations above 5000 feet
Installations above 12,000 feet are not allowed).
Inlet Pressure
Boss
Figure 53. White-Rodgers 36J
Gas Valve On / Off
Toggle Switch
Figure 54. White-Rodgers 36G
Gas Valve On / Off
Toggle Switch
2nd Stage (HI) Manifold
Pressure Adjustment
1st Stage (LO)
Manifold Pressure
Adjustment
HIGH ALTITUDE DERATE
Input ratings (BTUH) of these furnaces are based on sea
level operation and should not be changed at elevations up to
2,000 ft.
If the installation is 2,000 ft. or above, the furnace input rate
(BTUH) shall be reduced 4% for each 1,000 ft. above sea level.
The furnace input rate shall be checked by clocking the gas
flow rate (CFH) and multiplying by the heating value
obtained from the local utility supplier for the gas being
delivered at the installed altitude. Input rate changes can be
made by adjusting the manifold pressure (min 3.0 - max
3.7 in. W.C. - Natural Gas) or changing orifices (orifice change
may not always be required).
If the desired input rate cannot be achieved with a change in
manifold pressure, then the orifices must be changed. LP
installations will require an orifice change.
IMPORTANT:
Reinstall the propane orifices to the same depth as the orifices
supplied with the equipment.
Installation of this furnace at altitudes above 2,000 ft.
(610m) shall be in accordance with the local codes, or in the
absence of local codes, the National Fuel Gas Code, ANSI
Z223.1/ NFPA 54 or National Standard of Canada, Natural
Gas and Propane Installation Code, CSA 149.1. Installation of
this furnace at altitudes above 2,000 ft. (610m) shall be made
in accordance with the listed high Altitude Conversion Kit
available with this furnace.
18-CD19D8-1833
Page 34
Installer’s Guide
▲
▲
▲
▲
▲
!
WARNING
EXPLOSION HAZARD!
PROPANE GAS IS HEAVIER THAN AIR AND MAY COLLECT IN ANY LOW AREAS OR CONFINED SPACES. IN
ADDITION, ODORANT FADE MAY MAKE THE GAS
UNDETECTABLE EXCEPT WITH A WARNING DEVICE. IF
THE GAS FURNACE IS INSTALLED IN A BASEMENT, AN
EXCAVATED AREA OR A CONFINED SPACE, IT IS
STRONGLY RECOMMENDED TO CONTACT A GAS
SUPPLIER TO INSTALL A GAS DETECTING WARNING
DEVICE IN CASE OF A GAS LEAK.
NOTE: The manufacturer of your furnace does NOT test any
detectors and makes no representations regarding any
brand or type of detector.
!
CAUTION
Replace and/or tighten all plugs removed or loosened
when adjusting gas pressure. Leak check the fittings
before placing the furnace into regular service. Failure
to follow this warning could result in fire, explosion, or
property damage.
Table 17 lists the main burner orifices used with the furnace.
If a change of orifices is required to correct the furnace input
rating refer to Table 18.
REINSTALLATION OF THE BURNER BOX COVER
Figure 55 shows the correct way to reinstall the burner box
cover if adjustment or replacement of the flame sensor, hot
surface igniter, or main burner orifices have required removal
of the cover.
START-UP AND ADJUSTMENT
PRELIMINARY INSPECTIONS
!
WARNING
Disconnect power to the unit before removing the blower
door. Allow a minimum of 10 seconds for IFC power supply
to drain to 0 volts. Failure to follow this warning could
result in property damage, personal injury or death.
With gas and electrical power “OFF”
1. Duct connections are properly sealed
2. Filters are in place
3. Venting is properly assembled
4. Blower door is in place
Turn the main gas valve toggle switch (See Figures 53 & 54)
within the unit to the “OFF” position. Turn the external gas
valve to “ON”. Purge the air from the gas lines. After purging,
check all gas connections for leaks with a soapy solution — DONOT CHECK WITH AN OPEN FLAME. Allow 5 minutes
for any gas that might have escaped to dissipate.
LP Gas being heavier than air may require forced ventilation.
Turn the toggle switch on the gas valve in the unit to the
“ON” position.
LIGHTING INSTRUCTIONS
!
WARNING
DO NOT attempt to manually light the burner. Failure to
follow this warning could result in property damage,
personal injury or death.
Lighting instructions appear on each unit. Each installation
must be checked out at the time of initial start up to insure
proper operation of all components. Check out should include
putting the unit through one complete cycle as outlined below.
Turn on the main electrical supply and set the thermostat
above the indicated temperature. The ignitor will automatically heat, then the gas valve is energized to permit the flow
of gas to the burners. After ignition and flame is established,
the flame control module monitors the flame and supplies
power to the gas valve until the thermostat is satisfied.
To shut off
For complete shutdown: Turn the gas cock knob on the main
gas valve to the “OFF” position (See Figure 49). Disconnect
the electrical supply to the unit.
!
CAUTION
If this is done during the cold weather months, provisions
must be taken to prevent freeze-up of all water pipes and
water receptacles.
Whenever your house is to be vacant, arrange to have
someone inspect your house for proper temperature.
This is very important during freezing weather. If for
any reason your furnace should fail to operate damage could result, such as frozen water pipes.
SEQUENCE OF OPERATION
Thermostat call for heat (2-stage thermostat)
Call for 1st stage only:
W1 thermostat contacts close signaling the control module to
run its self-check routine. After the control module has
verified that the 1st stage pressure switch contacts are open
and the limit switch(es) contacts are closed, the draft blower
will be energized.
As the induced draft blower comes up to speed, the pressure
switch contacts will close and the ignitor warm up period will
begin. The ignitor will heat for approx. 20 seconds, then the
gas valve is energized in 1st stage to permit gas flow to the
burners.
The flame sensor confirms that ignition has been achieved
within the 4 second ignition trial period.
As the flame sensor confirms that ignition has been achieved,
the delay to fan ON period begins timing and after approx.
45 seconds the indoor blower motor will be energized at low
speed and will continue to run during the heating cycle.
Call for 2nd stage after 1st stage:
W2 thermostat contacts close signaling a call for 2nd stage
heat. After a 30 second delay, the induced draft blower will
be energized on high speed and the 2nd stage pressure
switch contacts will close. The gas valve is energized in 2nd
stage and the indoor blower motor in high speed.
2nd stage satisfied, 1st stage still called:
W2 thermostat contacts open signaling that 2nd stage
heating requirements are satisfied.
The induced draft blower is reduced to low speed allowing
the 2nd stage pressure switch contacts to open and the gas
valve is reduced to 1st stage. The indoor blower motor is
reduced to low speed.
1st stage satisfied:
W1 thermostat contacts open signaling that 1st stage
heating requirements are satisfied. The gas valve will close
and the induced draft blower will be de-energized. The
indoor blower motor will continue to run for the fan off period
(Field selectable at 60, 100, 140 or 180 seconds), then will be
de-energized by the control module.
3418-CD19D8-18
Page 35
Installer’s Guide
▲
Thermostat call for heat (1-stage Thermostat)
W1/W2 (jumpered) thermostat contacts close signaling a call
for heat. 1st stage sequence of operation remains the same
as above. 2nd stage heat will energize after the stage delay
timer (field selectable at .5, 5, 10 or 15 minutes) has expired.
Thermostat satisfied:
W1/W2 (jumpered) contacts open signaling the control
module to close the gas valve. The induced draft blower is
switched to low speed and de-energized after the post purge
timer has expired. The indoor blower motor will continue to
operate after the flames are extinguished and then is
switched to low heat speed for the FAN-OFF period.
CONTROL AND SAFETY SWITCH ADJUSTMENTS
LIMIT SWITCH CHECK OUT
The limit switch is a safety device designed to close the gas
valve should the furnace become overheated. Since proper
operation of this switch is important to the safety of the unit, it
must be checked out on initial start up by the installer.
To check for proper operation of the limit switches, set the
thermostat to a temperature higher than the indicated
temperature to bring on the gas valve. Restrict the airflow
by blocking the return air (disconnecting the indoor blower
may trip the inducer limit). When the furnace reaches the
maximum outlet temperature as shown on the rating plate,
the burners must shut off. If they do not shut off after a
reasonable time and overheating is evident, a faulty limit
switch is probable and the limit switch must be replaced.
After checking the operation of the limit control, be sure to
remove the paper or cardboard from the return air inlet. Refer
to Service Facts for additional instructions.
NOTE TO INSTALLER
Review the following warnings with the owner. Review contents of USER’S INFORMATION MANUAL with the owner.
AIRFLOW ADJUSTMENT
Check inlet and outlet air temperatures to make sure they
are within the ranges specified on the furnace rating nameplate. If the airflow needs to be increased or decreased, see
the wiring diagram for information on changing the speed of
the blower motor.
ROOM AIR THERMOSTAT
HEAT ANTICIPATOR ADJUSTMENT
Set the thermostat heat anticipator according to the current
flow measured, or the settings found in the notes on the
furnace wiring diagram (found in the SERVICE FACTS or
inside the furnace casing).
INSTRUCTIONS TO THE OWNERS
In the event that electrical, fuel, or mechanical failures
occur, the owner should immediately turn the gas
supply off at the manual gas valve, located in the
burner compartment. Also turn off electrical power to
the furnace and contact the service agency designated
by your dealer.
BURNER BOX TEMPERATURE LIMIT DEVICE
All models are equipped with a manual reset temperature
limit located on the burner box. In case of excessive temperature, the limit will open and cause the circuit to open which
shuts off all flow of gas.
!
WARNING
Disconnect power to the unit before removing the blower
door. Allow a minimum of 10 seconds for IFC power supply
to drain to 0 volts. Failure to follow this warning could
result in property damage, personal injury or death.
This unit is equipped with a blower door switch which cuts
power to the blower and gas valve causing shutdown when
the door is removed. Operation with the door removed or ajar
can permit the escape of dangerous fumes. All panels must be
securely closed at all times for safe operation of the furnace.
INDOOR BLOWER TIMING
Heating: The integrated furnace control module controls the
indoor blower. The blower start is fixed at 45 seconds after
ignition. The FAN-OFF period is field selectable by dip
switches SW-2, #1 and #2 at 60, 100, 140, or 180 seconds.
The factory setting is 100 seconds.
W1-W2 stage delay (jumpered together) is field selectable by
dip switch SW-1, #1 and #2 at .5, 5, 10 or 15 minutes. The
factory setting is 10 minutes. (See wiring diagram).
Cooling: The fan delay off period is factory set at 0 seconds.
The option for 80 second delay off is field selectable by dip
switch SW-2, #3 (See wiring diagram).
18-CD19D8-1835
Page 36
IFC Error Flash Codes
Installer’s Guide
ABNORMAL CONDITIONS
1. EXCESSIVE COMBUSTION PRESSURE (WIND IN
EXCESS OF 40 M.P.H.) VENT OR FLUE BLOCKAGE
On a call for heat, the variable speed draft inducer must
first ramp up to speed and close the pressure switch
before the ignition sequence is allowed to begin. If the
pressure switch does not close, the motor will ramp up to
maximum speed and continue to operate there for about
1 minute.
After one minute the integrated furnace control will turn
the motor off for about 30 seconds then back on in an
attempt to reestablish proper operation. This condition
is indicative of a highly restricted or blocked inlet or
outlet vent pipe or a failed pressure switch.
If pressure against induced draft blower outlet becomes
excessive, the pressure switch will open. If the pressure
switch is open for more than 3.5 seconds, the variable
speed draft inducer will speed up and attempt to close
the pressure switch. If the pressure switch is not closed
within 12 seconds or if the maximum speed of the motor
is reached, the draft inducer sends a fault signal to the
integrated furnace control. If the unit is operating in
second stage, an inducer fault will cause the furnace
control to transition the system to first stage and it will
operate there for 10 minutes before attempting to run
again in second stage. If the unit is operating in first
stage, an inducer fault will cause the furnace control to
shut the system down and wait 30 seconds before
attempting to reestablish operation in first stage.
2. LOSS OF FLAME
If loss of flame occurs during a heating cycle, or flame is
not present at the sensor, the flame control module will
close the gas valve. The flame control module will then
recycle the ignition sequence, then if ignition is not
achieved, it will shut off the gas valve and lock out the
system.
3. POWER FAILURE
If there is a power failure during a heating cycle, the
system will restart the ignition sequence automatically
when power is restored, if the thermostat still calls for
heat.
4. GAS SUPPLY FAILURE
If loss of flame occurs during a heating cycle, the system
integrated control module will recycle the ignition sequence,
then if ignition is not achieved, the integrated control
module will shut off the gas valve and lock out the system.
5. INDUCED DRAFT BLOWER FAILURE
Please refer to the variable speed draft inducer
troubleshooting manual for diagnostic assistance.
6. CONDENSATE DRAIN BLOCKAGE
If the condensate drain is blocked, either by debris,
improper draining, or by freezing condensate, the
pressure switch will sense the accumulation of condensate in the furnace drain pan. The unit will not operate
properly until the condensate drain has been cleared, and
the condensate flows freely.
7. RESET AFTER LOCKOUT
When the integrated control module has shut the system
down and gone into lockout, the system must be manually reset before the unit will restart. The system can be
reset by turning the system power off for more than
1 second, or by removing 24VAC from the control for more
than 1 second, or by removing the thermostat call for
heat for more than 1 second but less than 20 seconds.
8. RESET AFTER BURNER BOX LIMIT SHUTDOWN
If the furnace shuts down, one thing that can be checked
is the burner box temperature limit switch. It is located
on the bottom of the burner box. The vent and combustion air inlet terminations should be checked for blockage. If blockage exists, clear the problem and then the
reset button may be depressed. If there is no block-
age of the terminations, the limit switch must be
reset by a qualified servicer.
3618-CD19D8-18
Page 37
FAULT CODE RECOVERY
On power up, last 4 faults, if any, will be flashed on the red
LED. The newest fault detected will flash first and the oldest
last. There will be a 2 second delay between fault code
flashes. Solid red LED error codes will not be displayed.
The Green LED will be on solid during last fault recovery.
At any other time the control is powered, the Green LED
indicator light will operate as shown in Table 19 and the red
LED will flash LitePort data (one flash) every 20 seconds.
Fault Code Reset
The last 4 fault codes can be erased from memory by powering up the control with “G” energized and then applying “R”
to the “W1” terminal 3 times within 6 seconds. The control
will acknowledge the reset by turning on the red LED for
2 seconds.
TABLE 19
INTEGRATED FURNACE CONTROL
GREEN "STATUS" LED FLASH CODES
Flashing Slow ---Normal - No call for Heat
Flashing Fast ---Normal - Call for Heat
Installer’s Guide
Q
Red LitePort™ LED
Green Status LED
*UX / DX Integrated Furnace Control
INTEGRATED FURNACE CONTROL RED LED "ERROR" FLASH CODES
2 Flashes ---System Lockout (Retries or Recycles exceeded)
Draft Pressure Error - Possible problems:
3 Flashes ---
a) Venting problem
b) Pressure switch problem
c) Inducer problem
4 Flashes ---Open Temperature Limit Switch
5 Flashes ---Flame sensed when no flame should be present
6 Flashes ---
115 volt AC power reversed, ignitor (Triac) fault, poor grounding or
system voltage too low
7 Flashes ---Gas valve circuit error
8 Flashes ---Low flame sense
9 Flashes ---Open Inducer Limit switch
10 Flashes ---Inducer communication error
Solid ---Internal GV error or Low TH voltage
Solid Red w/Solid
Green "STATUS" LED
Continuous Reset caused by a blown fuse or internal error.
18-CD19D8-1837
Page 38
Trane
6200 Troup Highway
Tyler, TX 75707
For more information contact
your local dealer (distributor)
Literature Order Number 18-CD18D8-18
File Number18-CD18D8-18
Supersedes18-CD18D8-17
Date01/09
Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to
change design and specifications without notice.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.