Trane TUHMB060ACV3VA, TUHMB080ACV3VA, TUHMC100ACV4VA, TUHMD120ACV5VA, TDHMB060BCV3VA Installer's Manual

...
18- CD30D1- 9
Installer’s Guide
Upflow/ Horizontal and Downflow/ Horizontal, Gas-Fired, Direct Vent, Variable Speed Inducer, Modulating Condensing Communicating Furnaces
*UHMB060ACV3VA *UHMB080ACV3VA *UHMC100ACV4VA *UHMD120ACV5VA
ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES
IMPORTANT — This Document is customer property and is to remain with this unit.
Please return to service information pack upon completion of work.
NOTE:
This furnace can be configured for Communicating or 24 VAC modes. Using fully Communicating or 24 VAC modes, the furnace can support single or multi-stage heat pump, AC, or heating only applications. Com­bined with a communicating Comfort Control only, the furnace will support a single stage 24 VAC cooling outdoor unit only.
*UHM
*DHMB060BCV3VA *DHMB080ACV3VA *DHMC100ACV4VA *DHMD120BCV5VA
*DHM
* First letter may be “A” or “T"
DOWNFLOW
UPFLOW
UPFLOW/HORIZONTAL
Safety signal words are used to designate a degree or level of seriousness associated with a particular hazard. The signal words for safety markings are WARNING, and CAUTION.
a. WARNING indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. b. CAUTION indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury.
It is also used to alert against unsafe practices and hazards involving only property damage.
DOWNFLOW/HORIZONTAL
A341624P14
SAFETY SECTION
Installer’s Guide
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon monoxide poisoning or death.
The following steps shall be followed for each appliance connected to the venting system being placed into operation, while all other appliances connected to the venting system are not in operation:
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and horizontal pitch, as required in the National Fuel Gas Code, ANSI Z223.1/NFPA 54 or the CSA B149.1
Natural Gas and Propane Installation Code
instructions. Determine that there is no blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition.
3. As far as practical, close all building doors and windows and all doors between the space in which the appliance(s) connected to the venting system are located and other deficiencies which could cause an unsafe condition.
4. Close fireplace dampers.
5. Turn on clothes dryers and any appliance not connected to the venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they are operating at maximum speed. Do not operate a summer exhaust fan.
6. Follow the lighting instructions. Place the appliance being inspected into operation. Adjust the thermostat so appliance is operating continuously.
7. Test for spillage from draft hood equipped appliances at the draft hood relief opening after 5 minutes of main burner operation. Use the flame of a match or candle.
8. If improper venting is observed during any of the above tests, the venting system must be corrected in accordance with the National Fuel Gas Code, ANSI Z221.1/NFPA 54 and/or CSA B149.1
Gas and Propane Installation Code
9. After it has been determined that each appliance connected to the venting system properly vents where
when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas-fired burning appliance to their previous condition of use.
FIRE OR EXPLOSION HAZARD FAILURE TO FOLLOW THE SAFETY WARNINGS EX­ACTLY COULD RESULT IN SERIOUS PERSONAL IN­JURY, PROPERTY DAMAGE, OR DEATH. IMPROPER SERVICING COULD RESULT IN DANGEROUS OPERA­TION, SERIOUS PERSONAL INJURY , PROPERTY DAM­AGE, OR DEATH.
The following warning complies with State of California law, Proposition 65.
!
WARNING
and these
Natural
.
!
WARNING
Failure to follow safety warnings exactly, could result in a fire or explosion causing property damage, personal injury or loss of life.
— Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any other appliance.
— WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
— Installation and service must be performed by
a qualified installer, service agency or the gas supplier.
!
WARNING
EXPLOSION HAZARD!
PROPANE GAS IS HEAVIER THAN AIR AND MAY COLLECT IN ANY LOW AREAS OR CONFINED SPACES. IN ADDITION, ODORANT FADE MAY MAKE THE GAS UNDETECTABLE EXCEPT WITH A WARN­ING DEVICE. IF THE GAS FURNACE IS INSTALLED IN A BASEMENT, AN EXCAVATED AREA OR A CON­FINED SPACE, IT IS STRONGLY RECOMMENDED TO CONTACT A GAS SUPPLIER TO INSTALL A GAS DETECTING WARNING DEVICE IN CASE OF A GAS LEAK.
NOTE: The manufacturer of your furnace does NOT test
any detectors and makes no representations regarding any brand or type of detector.
!
WARNING
SAFETY HAZARD THIS INFORMATION IS INTENDED FOR USE BY INDIVIDUALS POSSESSING ADEQUATE BACK­GROUNDS OF ELECTRICAL AND MECHANICAL EXPE­RIENCE. ANY ATTEMPT TO REPAIR A CENTRAL AIR CONDITIONING PRODUCT MAY RESULT IN PER­SONAL INJURY AND OR PROPERTY DAMAGE. THE MANUFACTURER OR SELLER CANNOT BE RESPON­SIBLE FOR THE INTERPRETATION OF THIS INFORMA­TION, NOR CAN IT ASSUME ANY LIABILITY IN CON­NECTION WITH ITS USE.
!
WARNING
Hazardous Gases!
Exposure to fuel substances or by-products of incomplete fuel combustion is believed by the state of California to cause cancer, birth defects, or other reproductive harm.
© 2011 Trane All Rights Reserved 18-CD30D1-9
!
CAUTION
Sharp Edge Hazard. Be careful of sharp edges on equipment or any cuts made on sheet metal while installing or servicing. Personal injury may result.
Installer’s Guide
!
WARNING
EXPLOSION HAZARD! NEVER USE AN OPEN FLAME TO DETECT GAS
LEAKS. EXPLOSIVE CONDITIONS MAY OCCUR. USE A LEAK TEST SOLUTION OR OTHER AP­PROVED METHODS FOR LEAK TESTING. FAILURE TO FOLLOW THIS WARNING COULD RESULT IN PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
!
CAUTION
To prevent shortening its service life, the Furnace should NOT be used as a “Construction Heater” during the finishing phases of construction until the require­ments listed in item 9, a-h of the safety section of this publication have been met. Condensate in the pres­ence of chlorides and fluorides from paint, varnish, stains, adhesives, cleaning compounds, and cement create a corrosive condition which may cause rapid deterioration of the heat exchanger.
!
WARNING
SAFETY HAZARD DO NOT USE SEMI-RIGID METALLIC GAS CONNEC­TORS (flexible GAS lines) within the Furnace cabinet. Failure to follow this warning could result in property damage, personal injury or death.
!
CAUTION
Do NOT install the furnace in a corrosive or contaminated atmosphere. Failure to follow this caution could result in early equipment failure.
NOTE: The furnace must be installed level. The only allowable variation would be slightly to the left and/ or forward in upflow installations or slightly toward the front in horizontal installations. This is necessary for proper condensate drainage.
!
WARNING
SAFETY HAZARD DO NOT INSTALL THE FURNACE DIRECTLY ON CAR­PETING, TILE OR OTHER COMBUSTIBLE MATERIAL OTHER THAN WOOD FLOORING. FOR VERTICAL DOWNFLOW APPLICATIONS, SUBBASE (BAYBASE205) MUST BE USED BETWEEN THE FUR­NACE AND COMBUSTIBLE FLOORING. WHEN THE DOWNFLOW FURNACE IS INSTALLED VERTICALLY WITH A CASED COIL, A SUBBASE IS NOT REQUIRED. FAILURE TO FOLLOW THE WARNING EXACTLY COULD RESULT IN SERIOUS PERSONAL INJURY, PROPERTY DAMAGE OR DEATH.
The following safety practices and precautions must be followed during the installation, servicing, and opera­tion of this furnace.
1. Use only with the type of gas approved for this Fur­nace. Refer to the furnace rating plate.
2. Install this furnace only in a location and position as specified in “Location and Clearances” on page 6 of these instructions.
Contents
Safety Section ................................................................................... 2
Installation Instructions .......................................... 6
Outline Drawing ................................................................................. 4
Locations and Clearances ................................................................ 6
General Installation Instructions ....................................................... 6
Upflow Installation ............................................................................. 7
Downflow Installations ...................................................................... 7
Horizontal Installation ....................................................................... 7
Air for Combustion and Ventilation ................................................... 8
Duct Connections .............................................................................. 9
Return Air Filters .............................................................................. 11
General Venting Information ........................................................... 15
Venting Materials ............................................................................. 18
Vent Length Table ............................................................................ 19
Venting Through the Roof ............................................................... 20
Horizontal Venting Through the Wall .............................................. 21
Downward Venting .......................................................................... 21
Venting Routed Through a Masonry Chimney .............................. 27
Electrical Connections .................................................................... 28
Field Wiring Diagrams ..................................................................... 28
Condensate Drain Instructions ....................................................... 32
Gas Piping ....................................................................................... 34
Combustion and Input Check ......................................................... 36
High Altitude Derate ........................................................................ 36
Start-up and Adjustment....................................... 39
Preliminary Inspections ................................................................... 39
Lighting Instructions ........................................................................ 39
User Interface Menu ........................................................................ 40
Sequence of Operation ................................................................... 43
Unit Test Mode ................................................................................. 46
Simple ........................................................................................ 4 6
Gas Valve Setup (Manifold Pressure Adjustment).................... 46
Control and Safety Switch Adjustments ......................................... 52
Airflow Adjustment ........................................................................... 52
Conditions Effecting Furnace Operation ........................................ 53
Alert Code Recovery ....................................................................... 54
Furnace Alert Codes ............................................. 55
3. Provide adequate combustion and ventilation air to the Furnace space as specified in “Air for Combus­tion and Ventilation” of these instructions.
4. Combustion products must be discharged outdoors. Connect this furnace to an approved vent system only, as specified in the “Venting” section (pages 15-
27), of these instructions.
5. Never test for gas leaks with an open flame. Use a commercially available soap solution made specifi­cally for the detection of leaks to check all connec­tions, as specified in the “Gas Piping” section start­ing on page 34.
6. Always install the furnace to operate within the furnace’s intended temperature-rise range with a duct system which has an external static pressure within the allowable range, as specified on the unit rating plate. Airflow with temperature rise for cfm versus static is shown in the Service Facts accom­panying this Furnace.
18-CD30D1-9 3
Installer’s Guide
MODEL
(SEE NOTE 1)
DIM "A" DIM "B" DIM "C" DIM "D" DIM "E" DIM "F"
*UHMB060ACV3VA
*UHMB080ACV3VA
17-1/2" 2-1/4" 16-1/4" 16" 7-1/2" 2"
*UHMC100ACV4VA 21" 2-1/2" 19-3/4" 19-1/2" 9" 3"
*UHMD120ACV5VA 24-1/2" 2-15/16" 23-1/4" 23" 10" 3"
(ALL DIMENSIONS ARE IN INCHES)
NOTES:
1. DIAMETER OF VENT PIPE MAY BE LIMITED
TO 2-1/2" OR 3" ON SOME MODELS AT DIFFERENT
ALTITUDES. REFER TO THE VENT LENGTH TABLE
FOR PROPER APPLICATION.
*UHM-ACV OUTLINE DRAWING
4 18-CD30D1-9
Installer’s Guide
(ALL DIMENSIONS ARE IN INCHES)
*DHM-ACV DOWNFLOW/ HORIZONTAL OUTLINE DRAWING
17-1/2" 2-1/4" 16-1/4" 16"
DIM "A" DIM "B" DIM "C" DIM "D"
MODEL
(SEE NOTE 1)
*DHMB060ACV3VB
*DHMB080ACV3VA
*DHMB060BCV3VA
24-1/2" 2-15/16" 23-1/4" 23"
*DHMC100ACV4VA 21" 2-1/2" 19-3/4" 19-1/2"
*DHMD120BCV5VA
*DHMD120ACV5VB
18-CD30D1-9 5
Installer’s Guide
7. When a furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by a duct(s) sealed to the fur­nace casing and terminating outside the space con­taining the furnace.
8. A gas-fired furnace for installation in a residential garage must be installed as specified in “Location and Clearances” section of these instructions.
9. The furnace may be used for temporary heating of buildings or structures under construction when the following conditions have been met:
a. The furnace venting system must be complete
and installed per manufacturers instructions.
b. The furnace is controlled only by a room Com-
fort Control (no field jumpers).
c. The furnace return air duct must be complete
and sealed to the furnace.
d. The furnace input rate and temperature rise
must be verified to be within nameplate mark­ing.
e. 100% of the furnace combustion air require-
ment must come from outside the structure.
f. The Furnace return air temperature range is
between 55
g. Clean the Furnace, duct work, and components
upon substantial completion of the construction process, and verify Furnace operating condition including ignition, input rate, temperature rise and venting, according to the manufacturer's instructions.
h. An external field supplied air filter must be
used during construction.
10. This product must be gas piped by a Licensed Plumber or Gas Fitter in the Commonwealth of Massachusetts.
0
and 800 Fahrenheit.
only
LOCATION AND CLEARANCES
The location of the furnace is normally selected by the architect, the builder, or the installer. However, before the furnace is moved into place, be sure to consider the following requirements:
1. Is the location selected as near the chimney or vent and as centralized for heat distribution as practical?
2. Do all clearances between the furnace and enclosure equal or exceed the minimums stated in Clearance Table on the Outline Drawings on pages 4 and 5?
3. Is there sufficient space for servicing the furnace and other equipment? A minimum of 24 inches front accessibility to the furnace must be provided. Any access door or panel must permit removal of the largest component.
4. Are there at least 3 inches of clearance between the furnace combustion air openings in the front panel and any closed panel or door provided?
5. Are the ventilation and combustion air openings large enough and will they remain unobstructed? If outside air is used, are the openings at least 12" above the highest expected snow accumulation level (18" minimum for Canadian applications)?
6. Allow sufficient height in supply plenum above the furnace to provide for cooling coil installation, if the cooling coil is not installed at the time of this furnace installation.
7. A furnace shall be installed so electrical components are protected from water.
8. If the furnace is installed in a residential garage, it must be installed so that the burners, and the ignition source are located not less than 18 inches above the floor and the furnace must be located or protected to avoid physical damage from vehicles.
GENERAL INSTALLATION INSTRUCTIONS
The manufacturer assumes no responsibility for equip­ment installed in violation of any code or regulation.
It is recommended that Manual J of the Air Condition­ing Contractors Association (ACCA) or A.R.I. 230 be followed in estimating heating requirements. When estimating heating requirements for installation at Altitudes above 2000 ft., remember the gas input must be reduced (See GAS INPUT ADJUSTMENT).
Material in this shipment has been inspected at the factory and released to the transportation agency without known damage. Inspect exterior of carton for evidence of rough handling in ship­ment. Unpack carefully after moving equipment to approximate location. If damage to contents is found, report the damage immediately to the delivering agency.
Codes and local utility requirements governing the installation of gas fired equipment, wiring, plumbing, and flue connections must be adhered to. In the ab­sence of local codes, the installation must conform with latest edition of the National Fuel Gas Code ANSI Z223.1 • National Installation Code, CAN/CGA B149.1. The latest code may be obtained from the American Gas Association Laboratories, 400 N. Capitol St. NW, Wash­ington D.C. 20001. 1-800-699-9277 or www.aga.org
These furnaces have been classified as CATEGORY IV furnaces in accordance with latest edition of ANSI Z21.47 standards • CAN/CGA 2.3. Category IV furnaces operate with positive vent static pressure and with a flue loss less than 17 percent. These conditions require special venting systems, which must be gas tight and water tight. These Category IV Direct Vent furnaces are not approved for installation in Manufactured/ Mobile housing.
6 18-CD30D1-9
Installer’s Guide
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
!
WARNING
SAFETY HAZARD DO NOT INSTALL THE FURNACE DIRECTLY ON CAR­PETING, TILE OR OTHER COMBUSTIBLE MATERIAL OTHER THAN WOOD FLOORING. FOR VERTICAL DOWNFLOW APPLICATIONS, SUBBASE (BAYBASE205) MUST BE USED BETWEEN THE FURNACE AND COM­BUSTIBLE FLOORING. WHEN THE DOWNFLOW FURNACE IS INSTALLED VERTICALLY WITH A CASED COIL, A SUBBASE IS NOT REQUIRED. FAILURE TO FOLLOW THE WARNING EXACTLY COULD RESULT IN SERIOUS PERSONAL INJURY, PROPERTY DAMAGE OR DEATH.
UPFLOW INSTALLATION
Standoffs and screws (See Figure 1) are included with the cased coils for attachment to the furnace. There are clearance alignment holes near the bottom of the coil wrapper. Drill screws are used to engage the furnace top flanges. The standoff is inserted into the cabinet alignment hole. The drill screws are inserted through the standoffs then screwed into the furnace flange. The coil is always placed downstream of the furnace airflow.
STANDOFFS (4)
DRILL SCREWS (4)
1
CASED
COIL
FOR VERTICAL
INSTALLATIONS:
DOWNFLOW INSTALLATIONS
REQUIRED FLOOR OPENING: (DOWNFLOW) SEE FIGURE 2 AND FIGURE 3, AND TABLE 1
HORIZONTAL INSTALLATION
IMPORTANT: The 2/4TXC cased coil must be placed downstream of the furnace. In horizontal installations, the apex of the coil may point either toward or away from the furnace. See the 2/4TXC coil Installer's Guide for more details.
The coil and furnace must be fully supported when used in the horizontal position. It is always recommended that an auxiliary drain pan be installed under a horizon­tally installed evaporator coil or 90% or greater Gas Furnace. Connect the auxiliary drain line to a separate drain line (no trap is needed in this line).
Three brackets (with screws) are included with down­flow furnaces for installation to stabilize and secure the furnace and TXC cased coil in the horizontal posi- tion. See Figure 4. The coil is placed downstream of the furnace, with the apex of the coil pointing in either direction of the airflow for horizontal installation. The cased coil is secured to the furnace and both the furnace and the cased coil must be properly supported.
4
CASED COIL CONNECTION
BRACKET FOR DOWNFLOW
FURNACE IN HORIZONTAL
SCREWS
U
P
F
F
L
U
O
R
W
N
A
C
E
STANDOFFS
(BOTH SIDES)
(BOTH SIDES)
2
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
3
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
FURNACE
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
CABINET
WIDTH
FRONT
RETURN
DUCT WIDTH
17-1/2" 16-1/4" 16-5/8" 20-1/8" 15-5/8" 19-3/8"
21" 19-3/4" 20-1/8" 20-1/8" 19-1/8" 19-3/8"
24-1/2" 23-1/4" 23-5/8" 20-1/8" 22-5/8" 19-3/8"
18-CD30D1-9 7
A (width)
B (depth)
TABLE 1
FLOOR OPENING PLENUM OPENING
"A" "B" "C" "D"
DOWNFLOW ONLY
The brackets mount using the rear screws on the coil case and use the screws provided to secure the bracket to the furnace. The remaining bracket is placed as close to center as possible (horizontally) between the coil case front and the furnace bottom channel (for downflow/ horizontal furnace). Use four of the screws provided to secure the bracket. The coil requires additional support.
The furnace may be installed in an attic or crawl space in the horizontal position by placing the furnace on the left side (as viewed from the front in the vertical posi­tion). The horizontal furnace installation in an attic should be on a service platform large enough to allow for proper clearances on all sides and service access to the front of the furnace (See Figure 5 & Clearance
D
C
Tables, on the Outline drawings on pages 4-5). Line con­tact is only permissible between lines formed by inter­sections of the top and two sides of the furnace casing and building joists, studs, or framing.
The furnace may be placed horizontally in a crawl space on a pad or other noncombustible material which will raise the unit for sufficient protection from moisture.
Installer’s Guide
5
UPFLOW/ HORIZONTAL SHOWN WITH DIRECT VENT
The furnace must be supported at both ends and the middle when installed horizontally. The fur­nace must also be elevated approximately 4-6 inches to allow clearance for the condensate drain to exit the cabinet in the horizontal position.
The horizontal furnace may also be suspended from the joists using all-thread rods with a substantial metal support frame that supports the entire length of the fur­nace. The rods need to be of sufficient length to allow for proper clearances from combustible materials. The frame needs to be at least 32" in length to allow for ac­cess to service panels.
If the furnace is suspended using steel strap, it must be supported at all four corners and in the middle at the front of the furnace.
AIR FOR COMBUSTION AND VENTILATION
If these furnaces are installed in a nondirect vent capac­ity then the adequate flow of combustion and ventilat­ing air must not be obstructed from reaching the fur­nace. Air openings provided for combustion air must be kept free of obstructions which restrict the flow of air. Airflow restrictions affect the efficiency and safe opera­tion of the furnace. Keep this in mind should you choose to remodel or change the area which contains your furnace. Furnaces must have a free flow of air for proper performance.
Provisions for combustion and ventilation air shall be made in accordance with latest edition of Section 5.3, Air for Combustion and Ventilation, of the National Fuel Gas Code, ANSI Z223.1 — CAN/CGA B149.1 or ap­plicable provisions of the local building codes. Special conditions created by mechanical exhausting of air and
fireplaces must be considered to avoid unsatisfactory furnace operation.
OUTSIDE AIR IS RECOMMENDED
The use of indoor air for most applications is acceptable, unless there is the presence of corrosive chemicals or contamination. Certain types of installation will require the use of outside air for combustion.
The following types of installations will require use of OUTDOOR AIR for combustion, due to chemical expo­sures:
* Commercial buildings * Buildings with indoor pools * Furnaces installed in “confined” laundry rooms * Furnaces installed in “confined” hobby or craft
rooms
* Furnaces installed near chemical storage areas.
Exposure to the following substances in the combustion air supply will also require OUTDOOR AIR for combus­tion:
* Permanent wave solutions * Chlorinated waxes and cleaners * Chlorine based swimming pool chemicals * Water softening chemicals * Deicing salts or chemicals * Carbon Tetrachloride * Halogen type refrigerants * Cleaning solvents (such as perchloroethylene) * Printing inks, paint removers, varnish, etc. * Hydrochloric acid * Cements and glues * Antistatic fabric softeners for clothes dryers * Masonry acid washing materials
Furnace locations may be in a “confined space” or an “unconfined space”.
Unconfined space is defined in Figure 6. These spaces may have adequate air by infiltration to provide air for combustion and ventilation. Buildings with tight construction (for example, weather stripping, heavily insulated, caulked, vapor barrier, etc.), may need addi­tional air to be provided as described for confined space. See Table 2 for minimum area.
TABLE 2
6
50 CU. FT. OR MORE PER 1000 BTU/HR. INPUT ALL EQUIP. INSTALLED
UNCONFINED
8 18-CD30D1-9
MINIMUM AREA IN SQUARE FEET
FOR UNCONFINED SPACE INSTALLATIONS
FURNACE
MAXIMUM BTUH
INPUT RATING
60,000
80,000 100,000 120,000
MINIMUM AREA IN SQUARE FEET
WITH 8 FT. CEILING
OF UNCONFINED SPACE
375 500 625 875
Installer’s Guide
7
CONFINED
SPACE
Confined spaces are installations with less than 50 cu. ft. of space per 1000 BTU/hr input from all equipment installed. Air for combustion and ventilation require­ments can be supplied from inside the building as in Figure 8 or from the outdoors, as in Figure 9.
1.
All air from inside the building as in Figure 8: The confined space shall be provided with two perma­nent openings communicating directly with an addi­tional room(s) of sufficient volume so that the com­bined volume of all spaces meets the criteria for an unconfined space. The total input of all gas utiliza­tion equipment installed in the combined space shall be considered in making this determination. Refer to Table 3 for minimum open areas require­ments.
2.
All air from outdoors as in Figure 9: The confined space shall be provided with two permanent open­ings, one commencing within 12 inches of the top and one commencing within 12 inches of the bot­tom of the enclosure. The openings shall communi­cate directly, or by ducts, with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors. Refer to Table 3, for minimum open areas requirements.
TABLE 3
MINIMUM FREE AREA IN SQUARE INCHES
EACH OPENING (FURNACE ONLY)
8
9
Furnace
Maximum
BTUH/INPUT
Rating
60,000
80,000 100,000 120,000
Air
From
Inside
100 100 100 120
Vertical
Duct
DUCT CONNECTIONS
Air duct systems should be installed in accordance with standards for air conditioning systems, National Fire Protection Association Pamphlet No. 90. They should be sized in accordance with ACCA Manual D or which­ever is applicable.
Central furnaces, when used in connection with cooling units, shall be installed in parallel or on the upstream side of the cooling coil to avoid condensation in the heat exchanger.
18-CD30D1-9 9
Air From Outside
Horizontal
15 20 25 30
Duct
30 40 50 60
Installer’s Guide
With a parallel flow arrangement, the dampers or other means used to control flow of air shall be adequate to prevent chilled air from entering the Furnace, and if manually operated, must be equipped with means to prevent operation of either unit unless the damper is in full heat or cool position.
On any job, flexible connections of nonflammable mate­rial may be used for return air and discharge connections to prevent transmission of vibration. Though these units have been specifically designed for quiet, vibration free operation, air ducts can act as sounding boards and could, if poorly installed, amplify the slightest vibration to the annoyance level.
When the furnace is located in a utility room adjacent to the living area, the system should be carefully de­signed with returns to minimize noise transmission through the return air grille. Although these furnaces are designed with large blowers operating at moderate speeds, any blower moving a high volume of air will produce audible noise which could be objectionable when the unit is located very close to a living area. It is often advisable to route the return air ducts under the floor or through the attic. Such design permits the in­stallation of air return remote from the living area (i.e. central hall).
When the furnace is installed so that the supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by a duct(s) sealed to the furnace and termi­nating outside the space containing the furnace.
RETURN AIR DUCT SYSTEMS
!
CAUTION
Safety Hazard
Sharp Edge Hazard
Be careful of sharp edges on equipment or any cuts made on sheet metal while installing or servicing. Personal injury may result.
Where there is no complete return duct system, the return connection must be run full size from the furnace to a location outside the utility room, basement, attic, or crawl space.
Do NOT install return air through the back of the furnace cabinet.
Do NOT install return air through the side of the furnace cabinet on horizontal applications.
PREPARATION FOR UPFLOW BOTTOM AND SIDE RETURN AIR FILTER INSTALLATION
All return air duct systems should provide for installa­tion of return air filters.
1. Determine the appropriate position to set the furnace in order to connect to existing supply and return ductwork.
2. The return air filter is shipped in either the bottom or side location. Remove the filter by first turning the two latches on the blower door and tilting the door forward to remove. Remove the filter by sliding it out.
3. For upflow side return installations, remove the insulation around the opening in the blower compart­ment.
4. The side panels of the upflow furnace include locating notches that are used as guides for cutting an opening for return air, refer to Figure 10 and the outline drawing on page 4 for duct connection dimensions for various furnaces.
0
LOCATING NOTCHES PRO­VIDED FOR SIDE RETURN CUTOUT
SEE OUTLINE DRAWING
*
5. If a 3/4" flange is to be used for attaching the air
inlet duct, add to cut where indicated by dotted lines in Figure 10. Cut corners diagonally and bend outward to form flange.
6. If flanges are not required, and a filter frame is
installed, cut between locating notches (See Figure
10).
7. The bottom panel of the upflow furnace must be
removed for bottom return air. After removing the filter, lay the furnace on its back. Remove the two 5/16" hex screws securing the front of the bottom channel to the cabinet.
UPFLOW FURNACE ONLY
CUT OUT FOR SIDE FILTER
FRONT of Furnace
NOTE: Minimum return air temperature is 55°F.
10 18-CD30D1-9
Rotate the channel downward (or remove by lower­ing the front edge of the channel and pulling for­ward). Slide the bottom return air panel out of the cabinet. Rotate the front channel to its original position and reinstall the two 5/16” screws.
8. The horizontal installation of the upflow
furnace requires an external filter section. Do NOT use the bottom return filter within the furnace. Filter kits are available for horizon­tal applications.
9. Connect duct work to furnace. See Outline Drawing for supply and return duct size and location. Flex­ible duct connectors are recommended to connect both supply and return air ducts to the furnace. If only the front of the furnace is accessible, it is recommended that both supply and return air plenums are removable.
RETURN AIR FILTERS
TYPICAL UPFLOW RETURN AIR FILTER INSTALLATIONS
Filters are factory supplied for these furnaces. These furnaces require high velocity type air filters. The fil­ters may be installed within the furnace blower com­partment for UPFLOW furnaces in either a BOTTOM or SIDE (left side or right side) return air inlet. Some filters may need to be trimmed for side or bottom filter use.
TABLE 4
MODELS
NUMBERS
*UHMB060ACV3VA *UHMB080ACV3VA
*UHMC100ACV4VA 21" 1 - 20" X 25" X 1" *UHMD120ACV5VA 24-1/2" 1 - 24" X 25" X 1"
* First letter may be "A" or "T"
NOTE: For upflow 5 ton airflow models where the airflow requirement exceeds 1800 CFM - Models will require return air openings and filters on: (1) both sides, or (2) one side and the bottom, or (3) just the bottom. The filter rack installation is not allowed for right side return on the following models: *UHMB060ACV3V, *UHMB080ACV3V & *UHMC100ACV4V.
CABINET
WIDTH
17-1/2" 1 - 17" X 25" X 1"
FILTER
QTY & SIZE
Installer’s Guide
q
Airflow
BOTTOM FILTER RACK INSTALLATION
w
FILTER RACK ASSEMBLY
e
Blower Deck Engagement
Hole
The furnace and the bottom filter rack, BAYRACK960, installation can be seen in Figure 11.
The furnace filter in the bottom or side configuration can be removed by simply turning the two latches on the blower door and tilting the door forward.
The Filter rails are spring loaded for automatic adjust­ment to allow standard size, locally obtainable replace­ment filters. The filter rack itself slides to adjust to the required width needed for bottom or side return (See Figure 12).
18-CD30D1-9 11
VIEW
ENGAGEMENT
HOLE DETAIL
(Typical both sides and blower deck)
Installer’s Guide
k
Airfl
ow
Airflow
ALTERNATE FILTER RACK INSTALLATION FOR BOT­TOM RETURN - BAYRACK960
The following checklist should be used when installing a bottom return filter on an upflow furnace:
a. Remove the filter. b. Remove the bottom panel. c. With the filter removed, the filter rack is
compressed and then inserted into the bottom of the furnace. The retaining screw/pin on each side inserts into engagement holes at the bottom of the furnace cabinet side. See Figure
14.
d. Reinstall the furnace filter in the bottom
position by inserting the chamfer end first into the filter rack. See Figure 19.
ALTERNATE FILTER RACK INSTALLATION FOR SIDE RETURN AIR ON UPFLOW FURNACES (LEFT OR RIGHT) - BAYRACK960
NOTE: The filter rack installation is not allowed for right side return on the following models: *UHMB060ACV3V, *UHMB080ACV3V & *UHMC100ACV4V. See Figure 21 for alternate upflow filter clip/ bracket installation.
The following checklist should be used when installing a right or left side return filter on an upflow furnace:
a. Remove the filter. b. Leave the bottom panel in place. c. Make side cutout by following the directions in
the “Return Air Duct Connections” section on page 10,
d. Compress the filter rack and reinstall in the side
position on the furnace. Confirm that the upper retaining pin/screw locks into the engagement hole in the blower deck and the lower pin/screw rests against the side of the bottom panel. See Figures 13, 15-18.
e. Reinstall the furnace filter in the side position by
inserting the chamfer end first into the filter rack.
t
BOTTOM ENGAGEMENT
Filter Rack Retaining
Furnace
Cabinet
Side
Engagement Hole
For
Filter Rack
Installation With
Bottom Return
Screw/Pin
Filter Rack
Bottom Panel
y
Typical Upflow Left Side Return Filter Rack Installation
u
SIDE
CUTOUT
RETAINING
PIN
(Both Sides)
SPRINGS
FILTER
RACK
RAILS
Airflow
BOTTOM
PANEL
INSTALLED
SIDE
CUTOUT
r
SIDE ENGAGEMENT
Furnace
Cabinet
Side
Engagement Hole For
Filter Rack Installation With Bottom Return
12 18-CD30D1-9
Filter Rack
Filter Rac Retaining Screw/Pin
Airflow
SPRINGS
BOTTOM
PANEL
INSTALLED
Typical Upflow Right Side Return Filter Rack Installation
FILTER
RACK RAILS
RETAINING
PIN
(Both Sides)
Installer’s Guide
SIDE
CUT-OUT
ALTERNATE SIDE
FILTER CLIPS
LOCATIONS
ALTERNATE BOTTOM
FILTER CLIPS LOCATIONS
i
BLOWER DECK
Furnace
Cabinet
o
Side
Engagement Hole For
Filter Rack Installation With Side
Return
Filter Rack Retaining Screw/Pin
Airflow
Furnace Blower Deck
Filter Rack Assembly
CHAMFER
END OF
FILTER GOES
INTO FILTER RACK FIRST
RETURN AIR FILTERS FOR UPFLOW FURNACE IN HORIZONTAL CONFIGURATION
When the upflow furnace is installed in the horizontal configuration, the return air filters must be installed exterior to the furnace cabinet. Remote filter grilles may be used for homeowner convenience or the filters may be installed in the duct work upstream of the fur­nace. See Figure 20. Conversion kits for horizontal fil­ter installation are shown in Table 4A.
Conversion kits for horizontal filters are BAYFLTR203 for 17 1/2" width cabinets, BAYFLTR204 for 21" width cabinets, and BAYFLTR205 for 24" width cabinets. These include filters and brackets necessary for hori­zontal filters. In addition, optional door kit BAYFLTR206 is also available. See Figures 20 and 22.
UPFLOW FILTER CLIP/ BRACKET INSTALLATION
1. Determine the location to be used. The furnace cabinet has dimples for location of the alternate furnace clips (Side return only). Pre-drill clearance holes with a 3/16" drill. Bottom return holes are pre-drilled. Attach clip to bottom channel and rear of unit with screws provided for bottom return.
2. Install the clips in front and rear of the desired location using the screws provided. The filter clip with the leaf spring mounts in the rear of the cabinet. See Figure 21.
p
Optional door kit BAYFLTR206
Typical Horizontal Filter Installation
Table 4A CONVERSION KITS FOR HORIZONTAL FILTERS
MODEL NUMBERS
*UHMB060ACV3VA *UHMB080ACV3VA
*UHMC100ACV4VA
*UHMD120ACV5VA
1. *First letter may be "A" or "T"
2. Kit includes Filters and Brackets necessary for Horizontal Filters.
3. Optional Door Kit BAYFLTR206 is also available.
18-CD30D1-9 13
CABINET
WIDTH
17-1/2" BAYFLTR203
21" BAYFLTR204
24-1/2" BAYFLTR205
a
Airflow
CONVERSION
KIT NUMBER
Installer’s Guide
INSTALLING THE FILTER
The filter may need to be cut to fit the unit depending on the location of the return air filter.
A score line and the words “CUT HERE” are located on the end of the filter. If your application requires cutting the filter, do so as indicted by the score mark.
TABLE 5
UNIT SIZE
RETURN AIR
BOTTOM SIDE
17-1/2" DO NOT CUT DO NOT CUT
21" DO NOT CUT CUT ON LINE
24-1/2" DO NOT CUT CUT ON LINE
TYPICAL DOWNFLOW FURNACE RETURN AIR FILTER INSTALLATIONS
Two filters are factory supplied for each downflow fur­nace. These furnaces require high velocity type air fil­ters.
Downflow furnace filters must be located outside the furnace cabinet. Typical installations are shown in Fig­ure 22. Tables 6 and 7 provide information for installa­tion of the filter retaining brackets shipped with down­flow furnaces.
TABLE 6
MODELS
NUMBERS
*DHMB060ACV3VB *DHMB060BCV3VA *DHMB080ACV3VA
*DHMC100ACV4VA 21" 2 - 16" X 20" X 1" *DHMD120ACV5VB
*DHMD120BCV5VA
*First letter may be "A" or "T"
LOCATING FILTER RETAINER BRACKETS IN DUCTWORK
CABINET
WIDTH
17-1/2" 16-1/4" 15" 14" 14-3/8"
21" 19-3/4" 19-1/2" 14" 13-1/8"
24-1/2" 23-1/4" 22" 14" 13-5/8"
* LOCATION DIMENSION IS FROM END OF DUCT AGAINST THE FURNACE TO THE SCREW HOLES FOR THE BRACKET.
RETURN
DUCT
WIDTH
CABINET
WIDTH
17-1/2" 2 - 14" X 20" X 1"
24-1/2" 2 - 16" X 20" X 1"
TABLE 7
DIMENSION
"A"
FILTER
QTY & SIZE
DIMENSION
"B"
FILTER
BRACKET
LOCATION*
s
Optional
BAYFLTR206
Door Kit
Airflow
DOWNFLOW
MINIMUM CLEARANCE FROM COMBUSTIBLE MATERIALS FOR
UPFLOW/HORIZONTAL AND DOWNFLOW/ HORIZONTAL FURNACES
FURNAC E SURFACE
SIDES 0" 1" 0"
BACK 0" 3" 6"
TOP 1" 1" 1"
FRONT 3" 3" 18"
VENT 0" 0" 0"
: CLEARANCE REQUIRED AT TOP OF PLENUM IS 1"
NOTE
VERTICAL
CLOSET
TABLE 8
Optional
BAYFLTR206
Door Kit
Airflow
UNIT LOCATION
HORIZONTAL
CLOSET
DOWNFLOW/ HORIZONTAL
HORIZONTAL
ALCOVE / ATTIC
14 18-CD30D1-9
Installer’s Guide
GENERAL VENTING INFORMATION
THIS FURNACE MUST BE VENTED TO THE OUT­DOORS. THESE FURNACES ARE INDUCED DRAFT VENTED AND MUST NOT BE CONNECTED TO ANY VENT SERVING ANOTHER APPLIANCE. PLEASE NOTE THAT THESE FURNACES USE POSITIVE-
PRESSURE VENT SYSTEMS.
!
WARNING
CARBON MONOXIDE HAZARD FURNACE MUST BE VENTED PROPERLY. FAILURE TO FOLLOW THIS WARNING COULD RESULT IN CARBON MONOXIDE, FIRE OR SMOKE THAT CAN CAUSE SERIOUS BODILY INJURY, DEATH OR PROP­ERTY DAMAGE.
IMPORTANT:
The building owner/maintenance provider must keep the area around the vent clear from snow.
Proper venting is essential to obtain maximum effi­ciency from a condensing furnace. Proper installation of the vent system is necessary to assure drainage of the condensate and prevent deterioration of the vent sys­tem.
American Gas Association has certified the design of condensing Furnaces for a minimum of 0" clearance from combustible materials with a single wall plastic vent pipe. See Table 8.
The recommended system is assembled from 2", 2-1/ 2", or 3" plastic pipe and fittings (See Table 9, page
18) for material specifications. Where the system is routed to the outdoors through an existing masonry chimney containing flue products from another gas appliance, or where required by local codes, then 3" venting of Type 29-4C stainless steel must be used in place of PVC material.
These furnaces have been classified as CATEGORY IV Furnaces in accordance with ANSI Z21.47 “latest edi­tion” standards. Category IV Furnaces operate with positive vent pressure and with a vent gas temperature less than 140°F. above the dewpoint. These conditions require special venting systems, which must be gas tight and water tight.
NOTE: When an existing furnace is removed from a venting system serving other gas appliances, the venting sys­tem is likely to be too large to properly vent t maining attached appliances.
The following steps shall be followed with each appli­ance remaining connected to the common venting sys­tem placed in operation, while the other appliances re­maining connected to the common venting system are not in operation.
he re-
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon monoxide poisoning or death.
The following steps shall be followed for each appliance connected to the venting system being placed into operation, while all other appliances connected to the venting system are not in operation:
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and horizontal pitch, as required in the National Fuel Gas Code, ANSI Z223.1/NFPA 54 or the CSA B149.1
Natural Gas and Propane Installation Code
instructions. Determine that there is no blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition.
3. As far as practical, close all building doors and windows and all doors between the space in which the appliance(s) connected to the venting system are located and other deficiencies which could cause an unsafe condition.
4. Close fireplace dampers.
5. Turn on clothes dryers and any appliance not connected to the venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they are operating at maximum speed. Do not operate a summer exhaust fan.
6. Follow the lighting instructions. Place the appliance being inspected into operation. Adjust the thermostat so appliance is operating continuously.
7. Test for spillage from draft hood equipped appliances at the draft hood relief opening after 5 minutes of main burner operation. Use the flame of a match or candle.
8. If improper venting is observed during any of the above tests, the venting system must be corrected in accordance with the National Fuel Gas Code, ANSI Z221.1/NFPA 54 and/or CSA B149.1
Gas and Propane Installation Code
9. After it has been determined that each appliance connected to the venting system properly vents where
when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas-fired burning appliance to their previous condition of use.
WHEN THE FACTORY SUPPLIED "OFF-SET" (2X3 REDUCING COUPLING) IS USED FOR 3" VENT PIPE INSTALLATION, MAKE SURE THE MARKING "TOP" IS
#CPL00938
FACTORY SUPPLIED ONLY WITH THE FOLLOWING MODELS: ALL 100,000 BTUH UPFLOW MODELS, ALL 120,000 BTUH UPFLOW MODELS, AND ALL DOWNFLOW MODELS
LOCATED ON THE TOP SIDE OF THE PIPE.
LABEL SAYS "TOP"
STRAIGHT SIDE MUST BE ON BOTTOM FOR PROPER CONDENSATE DRAINAGE.
.
and these
Natural
d
18-CD30D1-9 15
Installer’s Guide
Furnace
Air Inlet
Vent
2" TO 3" COUPLING
f
FACTORY SUPPLIED ONLY WITH THE FOLLOWING MODELS: ALL 100,000 BTUH UPFLOW MODELS, ALL 120,000 BTUH UPFLOW MODELS, THE UX1C080A9601 MODEL, AND ALL DOWNFLOW MODELS
FURNACE VENT
HORIZONTAL INSTALLATION
(UPFLOW/ HORIZONTAL OR DOWNFLOW/ HORIZONTAL)
NOTE: See Figures 23 & 24. In horizontal venting when the factory supplied “off-set” (2X3 reducing coupling) is used for 3” vent pipe installation, make sure the mark­ing “Top” is located on the top side of the pipe. The straight side must be on bottom for proper condensate drainage. This coupling is factory supplied with the fol­lowing models: *UHMC100, *UHMD120, & all downflow
models.
!
WARNING
Carbon monoxide, fire or smoke can cause serious bodily injury, death, and/ or property damage.
A variety of potential sources of carbon monoxide can be found in a building or dwelling such as gas-fired clothes dryers, gas cooking stoves, water heaters, Furnaces and fireplaces. The U.S. Consumer Product Safety Commis­sion recommends that users of gas-burning appliances install carbon monoxide detectors as well as fire and smoke detectors per the manufacturer’s installation in­structions to help alert dwelling occupants of the pres­ence of fire, smoke or unsafe levels of carbon monoxide. These devices should meet Underwriters Laboratories, Inc. Standards for Single and Multiple Station Carbon Monoxide Alarms, UL 2034 or CSA International Standard, Residential Carbon Monoxide Alarming De- vices, CSA 6.19
NOTE: The manufacturer of your furnace does not test any de­tectors and makes no representations regarding any brand or type of detector.
IMPORTANT:
These furnaces may be installed as Direct Vent (sealed combustion) or as Nondirect Vent (single pipe). The fur­naces are shipped DIRECT VENT with sealed combustion. For DIRECT VENT APPLICATION: The furnaces must be vented to the exterior of the house and combustion air MUST come through the inlet air pipe FROM OUTSIDE AIR. The pipes DO NOT have to exit the
exterior of the house together or on the same side of the house.
16 18-CD30D1-9
#CPL00938
For NONDIRECT VENT APPLICATION: The furnace shall be vented to the exterior of the house, but combustion air may enter from the surrounding area as long as combustion air requirements are met. (See AIR FOR COMBUSTION AND VENTILATION)
FURNACE VENT/ INLET PIPE INSTALLATION
!
WARNING
CARBON MONOXIDE POISONING HAZARD Failure to follow the installation instructions for the venting system being placed into operation could re-
sult in carbon monoxide poisoning or death.
There are many different variations of the vent/ inlet air pipe combination. The vent/ inlet air combination used for installation of these furnaces depends on the needs of the location. However, these guidelines must be followed:
1. The Furnace must vent outside the structure.
2. Furnace combustion air requirements must be met for nondirect, single pipe applications (See example 2 ).
3. For direct vent application of these furnaces, the vent pipe and air inlet pipe do not have to exit in the same air space or even on the same surface of the structure.
However, the longest individual pipe will decide the value for the longest allowable equivalent vent/ inlet air length as shown in the vent length table.
NOTE: BAYVENT200B accessories can be used for inlet and outlet terminals when the pipes do not exit the struc­ture together. For Canadian applications ONLY, IPEX 196006 may be used for horizontal and vertical termi­nations. IPEX 081216, IPEX 081218, and IPEX 081219 may be only used for horizontal vent terminations.
The following are EXAMPLES ONLY:
EX. 1 —
Example 1 shows that the vent may go vertical while the inlet air may be on any side of the structure. The Vent Pipe would decide the maximum equivalent length for the pipe depending on the furnace and pipe size.
Installer’s Guide
EX. 2 —
Example 2 shows the vent pipe exhausting through the roof and the inlet air coming from the interior of the house (See Note). The inlet air coming from the inte­rior of the house must meet combustion requirements for area, etc., as shown in the section AIR FOR COM­BUSTION AND VENTILATION in this Installer’s Guide.
Vent
Air
Inlet
(See Note)
Furnace
EX. 3 —
Example 3 shows the vent exiting one side of the house while the inlet air is on the opposite side of the struc­ture. Here the Vent Pipe length must be within the al­lowable length for the size of Furnace and size of the Vent Pipe. This example demonstrates that the pipes do not have to exit on the same side of the structure.
NOTE: If only the flue gas pipe is to the outside of the struc­ture, a straight section of pipe (long enough to exit the Furnace cabinet) must be attached to the inlet air side with an elbow (which is 5 to 10 equivalent feet) in­stalled on the end to prevent dust and debris from fall­ing directly into the Furnace.
VENT FITTING MATERIAL – PLASTIC
Gas and liquid tight single wall vent fittings, designed for resistance to corrosive flue condensate, MUST be used throughout.
Listed in Table 9 are materials that meet these require­ments. The materials listed are various grades of PVC and ABS plastic.
PIPE JOINTS: All joints must be fastened and sealed to prevent escape of combustion products into the build­ing. These materials are acceptable for U.S. applica­tions only. All Canadian installations must conform to ULC S636.
NOTE: It is recommended that the first joints from the furnace be connected and sealed with high temperature RTV. This will enable the pipes to be removed later without cutting. Be sure to properly support these joints.
Air
Vent
Inlet
Furnace
EX. 4 —
The inlet air does not have to come from outside the structure. Example 4 shows the inlet air (See Note), may come from the attic if the requirements for com­bustion air are met as shown in the section AIR FOR COMBUSTION AND VENTILATION.
Attic Vent
Vent
Air
Inlet
(See Note)
Furnace
BONDING OF PVC
Commercially available solvent cement for PVC must be used to join PVC pipe fittings. Follow instructions on container carefully for U.S. applications only. Canadian applications require primer and cement that are from a single system manufacturer.
For U.S. applications only:
Pipe and Fittings – ASTM D1785, D2466, D2661, & D2665
PVC Primer and Solvent Cement – ASTM D2564.
Procedure for Cementing Joints Ref – ASTM D2855
1. Cut pipe square, remove ragged edges and burrs. Chamfer end of pipe, then clean fitting socket and pipe joint area of all dirt, grease, moisture or chips.
2. After checking pipe and socket for proper fit, wipe socket and pipe with cleaner-primer. Apply a liberal coat of primer to inside surface of socket and out­side of pipe.
DO NOT ALLOW PRIMER TO DRY BEFORE AP­PLYING CEMENT.
3. Apply a thin coat of cement evenly in the socket. Quickly apply a heavy coat of cement to the pipe end and insert pipe into fitting with a slight twisting movement until it bottoms out.
4. Hold the pipe in the fitting for 30 seconds to pre­vent tapered socket from pushing the pipe out of the fitting.
18-CD30D1-9 17
Loading...
+ 39 hidden pages