ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES
IMPORTANT — This Document is customer property and is to remain with this unit.
Please return to service information pack upon completion of work.
NOTE:
This furnace can be configured for Communicating or 24 VAC modes. Using fully Communicating or 24 VAC
modes, the furnace can support single or multi-stage heat pump, AC, or heating only applications. Combined with a communicating Comfort Control only, the furnace will support a single stage 24 VAC cooling
outdoor unit only.
Safety signal words are used to designate a degree or level of seriousness associated with a particular hazard.
The signal words for safety markings are WARNING, and CAUTION.
a. WARNING indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
b. CAUTION indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury.
It is also used to alert against unsafe practices and hazards involving only property damage.
DOWNFLOW/HORIZONTAL
A341624P14
SAFETY SECTION
▲
▲
▲
▲
▲
▲
▲
Installer’s Guide
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each
appliance connected to the venting system being
placed into operation could result in carbon monoxide
poisoning or death.
The following steps shall be followed for each appliance
connected to the venting system being placed into
operation, while all other appliances connected to the
venting system are not in operation:
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and
horizontal pitch, as required in the National Fuel Gas
Code, ANSI Z223.1/NFPA 54 or the CSA B149.1
Natural Gas and Propane Installation Code
instructions. Determine that there is no blockage or
restriction, leakage, corrosion and other deficiencies
which could cause an unsafe condition.
3. As far as practical, close all building doors and
windows and all doors between the space in which the
appliance(s) connected to the venting system are
located and other deficiencies which could cause an
unsafe condition.
4. Close fireplace dampers.
5. Turn on clothes dryers and any appliance not
connected to the venting system. Turn on any exhaust
fans, such as range hoods and bathroom exhausts, so
they are operating at maximum speed. Do not operate
a summer exhaust fan.
6. Follow the lighting instructions. Place the appliance
being inspected into operation. Adjust the thermostat
so appliance is operating continuously.
7. Test for spillage from draft hood equipped appliances
at the draft hood relief opening after 5 minutes of main
burner operation. Use the flame of a match or candle.
8. If improper venting is observed during any of the above
tests, the venting system must be corrected in
accordance with the National Fuel Gas Code,
ANSI Z221.1/NFPA 54 and/or CSA B149.1
Gas and Propane Installation Code
9. After it has been determined that each appliance
connected to the venting system properly vents where
when tested as outlined above, return doors, windows,
exhaust fans, fireplace dampers and any other gas-fired
burning appliance to their previous condition of use.
FIRE OR EXPLOSION HAZARD
FAILURE TO FOLLOW THE SAFETY WARNINGS EXACTLY COULD RESULT IN SERIOUS PERSONAL INJURY, PROPERTY DAMAGE, OR DEATH. IMPROPER
SERVICING COULD RESULT IN DANGEROUS OPERATION, SERIOUS PERSONAL INJURY , PROPERTY DAMAGE, OR DEATH.
The following warning complies with State of California law, Proposition 65.
!
WARNING
and these
Natural
.
!
WARNING
Failure to follow safety warnings exactly, could result
in a fire or explosion causing property damage,
personal injury or loss of life.
— Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any
other appliance.
— WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch;
do not use any phone in your building.
• Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s
instructions.
• If you cannot reach your gas supplier,
call the fire department.
— Installation and service must be performed by
a qualified installer, service agency or the gas
supplier.
!
WARNING
EXPLOSION HAZARD!
PROPANE GAS IS HEAVIER THAN AIR AND MAY
COLLECT IN ANY LOW AREAS OR CONFINED
SPACES. IN ADDITION, ODORANT FADE MAY MAKE
THE GAS UNDETECTABLE EXCEPT WITH A WARNING DEVICE. IF THE GAS FURNACE IS INSTALLED
IN A BASEMENT, AN EXCAVATED AREA OR A CONFINED SPACE, IT IS STRONGLY RECOMMENDED TO
CONTACT A GAS SUPPLIER TO INSTALL A GAS
DETECTING WARNING DEVICE IN CASE OF A GAS
LEAK.
NOTE: The manufacturer of your furnace does NOT test
any detectors and makes no representations regarding
any brand or type of detector.
!
WARNING
SAFETY HAZARD
THIS INFORMATION IS INTENDED FOR USE BY
INDIVIDUALS POSSESSING ADEQUATE BACKGROUNDS OF ELECTRICAL AND MECHANICAL EXPERIENCE. ANY ATTEMPT TO REPAIR A CENTRAL AIR
CONDITIONING PRODUCT MAY RESULT IN PERSONAL INJURY AND OR PROPERTY DAMAGE. THE
MANUFACTURER OR SELLER CANNOT BE RESPONSIBLE FOR THE INTERPRETATION OF THIS INFORMATION, NOR CAN IT ASSUME ANY LIABILITY IN CONNECTION WITH ITS USE.
!
WARNING
Hazardous Gases!
Exposure to fuel substances or by-products of incomplete
fuel combustion is believed by the state of California to
cause cancer, birth defects, or other reproductive harm.
Sharp Edge Hazard. Be careful of sharp edges on
equipment or any cuts made on sheet metal while
installing or servicing. Personal injury may result.
Installer’s Guide
▲
▲
▲
▲
▲
!
WARNING
EXPLOSION HAZARD!
NEVER USE AN OPEN FLAME TO DETECT GAS
LEAKS. EXPLOSIVE CONDITIONS MAY OCCUR.
USE A LEAK TEST SOLUTION OR OTHER APPROVED METHODS FOR LEAK TESTING. FAILURE
TO FOLLOW THIS WARNING COULD RESULT IN
PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
!
CAUTION
To prevent shortening its service life, the Furnace
should NOT be used as a “Construction Heater” during
the finishing phases of construction until the requirements listed in item 9, a-h of the safety section of this
publication have been met. Condensate in the presence of chlorides and fluorides from paint, varnish,
stains, adhesives, cleaning compounds, and cement
create a corrosive condition which may cause rapid
deterioration of the heat exchanger.
!
WARNING
SAFETY HAZARD
DO NOT USE SEMI-RIGID METALLIC GAS CONNECTORS (flexible GAS lines) within the Furnace cabinet.
Failure to follow this warning could result in property
damage, personal injury or death.
!
CAUTION
Do NOT install the furnace in a corrosive or
contaminated atmosphere.
Failure to follow this caution could result in early
equipment failure.
NOTE: The furnace must be installed level. The only
allowable variation would be slightly to the left and/
or forward in upflow installations or slightly toward
the front in horizontal installations. This is
necessary for proper condensate drainage.
!
WARNING
SAFETY HAZARD
DO NOT INSTALL THE FURNACE DIRECTLY ON CARPETING, TILE OR OTHER COMBUSTIBLE MATERIAL
OTHER THAN WOOD FLOORING. FOR VERTICAL
DOWNFLOW APPLICATIONS, SUBBASE
(BAYBASE205) MUST BE USED BETWEEN THE FURNACE AND COMBUSTIBLE FLOORING. WHEN THE
DOWNFLOW FURNACE IS INSTALLED VERTICALLY
WITH A CASED COIL, A SUBBASE IS NOT REQUIRED.
FAILURE TO FOLLOW THE WARNING EXACTLY COULD
RESULT IN SERIOUS PERSONAL INJURY, PROPERTY
DAMAGE OR DEATH.
The following safety practices and precautions must be
followed during the installation, servicing, and operation of this furnace.
1. Use only with the type of gas approved for this Furnace. Refer to the furnace rating plate.
2. Install this furnace only in a location and position
as specified in “Location and Clearances” on page 6
of these instructions.
3. Provide adequate combustion and ventilation air to
the Furnace space as specified in “Air for Combustion and Ventilation” of these instructions.
4. Combustion products must be discharged outdoors.
Connect this furnace to an approved vent system
only, as specified in the “Venting” section (pages 15-
27), of these instructions.
5. Never test for gas leaks with an open flame. Use a
commercially available soap solution made specifically for the detection of leaks to check all connections, as specified in the “Gas Piping” section starting on page 34.
6. Always install the furnace to operate within the
furnace’s intended temperature-rise range with a
duct system which has an external static pressure
within the allowable range, as specified on the unit
rating plate. Airflow with temperature rise for cfm
versus static is shown in the Service Facts accompanying this Furnace.
18-CD30D1-93
Installer’s Guide
MODEL
(SEE NOTE 1)
DIM "A" DIM "B" DIM "C" DIM "D" DIM "E" DIM "F"
*UHMB060ACV3VA
*UHMB080ACV3VA
17-1/2"2-1/4"16-1/4"16"7-1/2"2"
*UHMC100ACV4VA21"2-1/2"19-3/4"19-1/2"9"3"
*UHMD120ACV5VA 24-1/2" 2-15/16" 23-1/4"23"10"3"
(ALL DIMENSIONS ARE IN INCHES)
NOTES:
1. DIAMETER OF VENT PIPE MAY BE LIMITED
TO 2-1/2" OR 3" ON SOME MODELS AT DIFFERENT
ALTITUDES. REFER TO THE VENT LENGTH TABLE
FOR PROPER APPLICATION.
*UHM-ACV OUTLINE DRAWING
418-CD30D1-9
Installer’s Guide
(ALL DIMENSIONS ARE IN INCHES)
*DHM-ACV DOWNFLOW/ HORIZONTAL OUTLINE DRAWING
17-1/2"2-1/4"16-1/4"16"
DIM "A" DIM "B" DIM "C" DIM "D"
MODEL
(SEE NOTE 1)
*DHMB060ACV3VB
*DHMB080ACV3VA
*DHMB060BCV3VA
24-1/2"2-15/16"23-1/4"23"
*DHMC100ACV4VA21"2-1/2"19-3/4"19-1/2"
*DHMD120BCV5VA
*DHMD120ACV5VB
18-CD30D1-95
Installer’s Guide
7. When a furnace is installed so that supply ducts
carry air circulated by the furnace to areas outside
the space containing the furnace, the return air
shall also be handled by a duct(s) sealed to the furnace casing and terminating outside the space containing the furnace.
8. A gas-fired furnace for installation in a residential
garage must be installed as specified in “Location
and Clearances” section of these instructions.
9. The furnace may be used for temporary heating of
buildings or structures under construction
when the following conditions have been met:
a.The furnace venting system must be complete
and installed per manufacturers instructions.
b.The furnace is controlled only by a room Com-
fort Control (no field jumpers).
c.The furnace return air duct must be complete
and sealed to the furnace.
d.The furnace input rate and temperature rise
must be verified to be within nameplate marking.
e.100% of the furnace combustion air require-
ment must come from outside the structure.
f.The Furnace return air temperature range is
between 55
g.Clean the Furnace, duct work, and components
upon substantial completion of the construction
process, and verify Furnace operating condition
including ignition, input rate, temperature rise
and venting, according to the manufacturer's
instructions.
h. An external field supplied air filter must be
used during construction.
10. This product must be gas piped by a Licensed
Plumber or Gas Fitter in the Commonwealth of
Massachusetts.
0
and 800 Fahrenheit.
only
LOCATION AND CLEARANCES
The location of the furnace is normally selected by
the architect, the builder, or the installer. However,
before the furnace is moved into place, be sure to
consider the following requirements:
1. Is the location selected as near the chimney or
vent and as centralized for heat distribution as
practical?
2. Do all clearances between the furnace and
enclosure equal or exceed the minimums stated in
Clearance Table on the Outline Drawings on pages 4
and 5?
3. Is there sufficient space for servicing the furnace
and other equipment? A minimum of 24 inches front
accessibility to the furnace must be provided. Any
access door or panel must permit removal of the
largest component.
4. Are there at least 3 inches of clearance between
the furnace combustion air openings in the front
panel and any closed panel or door provided?
5. Are the ventilation and combustion air openings
large enough and will they remain unobstructed? If
outside air is used, are the openings at least 12"
above the highest expected snow accumulation level
(18" minimum for Canadian applications)?
6. Allow sufficient height in supply plenum above the
furnace to provide for cooling coil installation, if the
cooling coil is not installed at the time of this furnace
installation.
7. A furnace shall be installed so electrical
components are protected from water.
8. If the furnace is installed in a residential garage,
it must be installed so that the burners, and the
ignition source are located not less than 18 inches
above the floor and the furnace must be located or
protected to avoid physical damage from vehicles.
GENERAL INSTALLATION INSTRUCTIONS
The manufacturer assumes no responsibility for equipment installed in violation of any code or regulation.
It is recommended that Manual J of the Air Conditioning Contractors Association (ACCA) or A.R.I. 230 be
followed in estimating heating requirements. When
estimating heating requirements for installation at
Altitudes above 2000 ft., remember the gas input must
be reduced (See GAS INPUT ADJUSTMENT).
Material in this shipment has been inspected at
the factory and released to the transportation
agency without known damage. Inspect exterior
of carton for evidence of rough handling in shipment. Unpack carefully after moving equipment
to approximate location. If damage to contents is
found, report the damage immediately to the
delivering agency.
Codes and local utility requirements governing the
installation of gas fired equipment, wiring, plumbing,
and flue connections must be adhered to. In the absence of local codes, the installation must conform with
latest edition of the National Fuel Gas Code ANSI
Z223.1 • National Installation Code, CAN/CGA B149.1.
The latest code may be obtained from the American Gas
Association Laboratories, 400 N. Capitol St. NW, Washington D.C. 20001.
1-800-699-9277 or www.aga.org
These furnaces have been classified as CATEGORY IV
furnaces in accordance with latest edition of ANSI
Z21.47 standards • CAN/CGA 2.3. Category IV furnaces
operate with positive vent static pressure and with a
flue loss less than 17 percent. These conditions require
special venting systems, which must be gas tight and
water tight. These Category IV Direct Vent furnaces
are not approved for installation in Manufactured/
Mobile housing.
618-CD30D1-9
Installer’s Guide
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
▲
!
WARNING
SAFETY HAZARD
DO NOT INSTALL THE FURNACE DIRECTLY ON CARPETING, TILE OR OTHER COMBUSTIBLE MATERIAL
OTHER THAN WOOD FLOORING. FOR VERTICAL
DOWNFLOW APPLICATIONS, SUBBASE (BAYBASE205)
MUST BE USED BETWEEN THE FURNACE AND COMBUSTIBLE FLOORING. WHEN THE DOWNFLOW
FURNACE IS INSTALLED VERTICALLY WITH A CASED
COIL, A SUBBASE IS NOT REQUIRED. FAILURE TO
FOLLOW THE WARNING EXACTLY COULD RESULT IN
SERIOUS PERSONAL INJURY, PROPERTY DAMAGE
OR DEATH.
UPFLOW INSTALLATION
Standoffs and screws (See Figure 1) are included with
the cased coils for attachment to the furnace. There are
clearance alignment holes near the bottom of the coil
wrapper. Drill screws are used to engage the furnace
top flanges. The standoff is inserted into the cabinet
alignment hole. The drill screws are inserted through
the standoffs then screwed into the furnace flange. The
coil is always placed downstream of the furnace airflow.
STANDOFFS (4)
DRILL SCREWS (4)
1
CASED
COIL
FOR VERTICAL
INSTALLATIONS:
DOWNFLOW INSTALLATIONS
REQUIRED FLOOR OPENING: (DOWNFLOW)
SEE FIGURE 2 AND FIGURE 3, AND TABLE 1
HORIZONTAL INSTALLATION
IMPORTANT:
The 2/4TXC cased coil must be placed downstream of the
furnace. In horizontal installations, the apex of the coil
may point either toward or away from the furnace. See
the 2/4TXC coil Installer's Guide for more details.
The coil and furnace must be fully supported when used
in the horizontal position. It is always recommended
that an auxiliary drain pan be installed under a horizontally installed evaporator coil or 90% or greater Gas
Furnace. Connect the auxiliary drain line to a separate
drain line (no trap is needed in this line).
Three brackets (with screws) are included with downflow furnaces for installation to stabilize and secure the
furnace and TXC cased coil in the horizontal posi-tion. See Figure 4. The coil is placed downstream of
the furnace, with the apex of the coil pointing in either
direction of the airflow for horizontal installation.
The cased coil is secured to the furnace and both the
furnace and the cased coil must be properly supported.
4
CASED COIL CONNECTION
BRACKET FOR DOWNFLOW
FURNACE IN HORIZONTAL
SCREWS
U
P
F
F
L
U
O
R
W
N
A
C
E
STANDOFFS
(BOTH SIDES)
(BOTH SIDES)
2
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
3
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
FURNACE
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
CABINET
WIDTH
FRONT
RETURN
DUCT WIDTH
17-1/2"16-1/4"16-5/8"20-1/8"15-5/8"19-3/8"
21"19-3/4"20-1/8"20-1/8"19-1/8"19-3/8"
24-1/2"23-1/4"23-5/8"20-1/8"22-5/8"19-3/8"
18-CD30D1-97
A (width)
B (depth)
TABLE 1
FLOOR OPENING PLENUM OPENING
"A""B""C""D"
DOWNFLOW ONLY
The brackets mount using the rear screws on the coil
case and use the screws provided to secure the bracket
to the furnace. The remaining bracket is placed as close
to center as possible (horizontally) between the coil case
front and the furnace bottom channel (for downflow/
horizontal furnace). Use four of the screws provided to
secure the bracket. The coil requires additional support.
The furnace may be installed in an attic or crawl space
in the horizontal position by placing the furnace on theleft side (as viewed from the front in the vertical position). The horizontal furnace installation in an attic
should be on a service platform large enough to allow
for proper clearances on all sides and service access to
the front of the furnace (See Figure 5 & Clearance
D
C
Tables, on the Outline drawings on pages 4-5). Line contact is only permissible between lines formed by intersections of the top and two sides of the furnace casing
and building joists, studs, or framing.
The furnace may be placed horizontally in a crawl space
on a pad or other noncombustible material which will
raise the unit for sufficient protection from moisture.
Installer’s Guide
5
UPFLOW/
HORIZONTAL
SHOWN WITH
DIRECT VENT
The furnace must be supported at both ends and
the middle when installed horizontally. The furnace must also be elevated approximately 4-6
inches to allow clearance for the condensate drain
to exit the cabinet in the horizontal position.
The horizontal furnace may also be suspended from the
joists using all-thread rods with a substantial metal
support frame that supports the entire length of the furnace. The rods need to be of sufficient length to allow
for proper clearances from combustible materials. The
frame needs to be at least 32" in length to allow for access to service panels.
If the furnace is suspended using steel strap, it must be
supported at all four corners and in the middle at the
front of the furnace.
AIR FOR COMBUSTION AND VENTILATION
If these furnaces are installed in a nondirect vent capacity then the adequate flow of combustion and ventilating air must not be obstructed from reaching the furnace. Air openings provided for combustion air must be
kept free of obstructions which restrict the flow of air.
Airflow restrictions affect the efficiency and safe operation of the furnace. Keep this in mind should you
choose to remodel or change the area which contains
your furnace. Furnaces must have a free flow of air for
proper performance.
Provisions for combustion and ventilation air shall be
made in accordance with latest edition of Section 5.3,
Air for Combustion and Ventilation, of the National
Fuel Gas Code, ANSI Z223.1 — CAN/CGA B149.1 or applicable provisions of the local building codes. Special
conditions created by mechanical exhausting of air and
fireplaces must be considered to avoid unsatisfactory
furnace operation.
OUTSIDE AIR IS RECOMMENDED
The use of indoor air for most applications is acceptable,
unless there is the presence of corrosive chemicals or
contamination. Certain types of installation will require
the use of outside air for combustion.
The following types of installations will require use of
OUTDOOR AIR for combustion, due to chemical exposures:
* Commercial buildings
* Buildings with indoor pools
* Furnaces installed in “confined” laundry rooms
* Furnaces installed in “confined” hobby or craft
rooms
* Furnaces installed near chemical storage areas.
Exposure to the following substances in the combustion
air supply will also require OUTDOOR AIR for combustion:
* Permanent wave solutions
* Chlorinated waxes and cleaners
* Chlorine based swimming pool chemicals
* Water softening chemicals
* Deicing salts or chemicals
* Carbon Tetrachloride
* Halogen type refrigerants
* Cleaning solvents (such as perchloroethylene)
* Printing inks, paint removers, varnish, etc.
* Hydrochloric acid
* Cements and glues
* Antistatic fabric softeners for clothes dryers
* Masonry acid washing materials
Furnace locations may be in a “confined space” or an
“unconfined space”.
Unconfined space is defined in Figure 6. These spaces
may have adequate air by infiltration to provide air for
combustion and ventilation. Buildings with tight
construction (for example, weather stripping, heavily
insulated, caulked, vapor barrier, etc.), may need additional air to be provided as described for confined space.
See Table 2 for minimum area.
TABLE 2
6
50 CU. FT. OR MORE
PER 1000 BTU/HR. INPUT
ALL EQUIP. INSTALLED
UNCONFINED
818-CD30D1-9
MINIMUM AREA IN SQUARE FEET
FOR UNCONFINED SPACE INSTALLATIONS
FURNACE
MAXIMUM BTUH
INPUT RATING
60,000
80,000
100,000
120,000
MINIMUM AREA IN SQUARE FEET
WITH 8 FT. CEILING
OF UNCONFINED SPACE
375
500
625
875
Installer’s Guide
7
CONFINED
SPACE
Confined spaces are installations with less than 50 cu.
ft. of space per 1000 BTU/hr input from all equipment
installed. Air for combustion and ventilation requirements can be supplied from inside the building as in
Figure 8 or from the outdoors, as in Figure 9.
1.
All air from inside the building as in Figure 8: The
confined space shall be provided with two permanent openings communicating directly with an additional room(s) of sufficient volume so that the combined volume of all spaces meets the criteria for an
unconfined space. The total input of all gas utilization equipment installed in the combined space
shall be considered in making this determination.
Refer to Table 3 for minimum open areas requirements.
2.
All air from outdoors as in Figure 9: The confined
space shall be provided with two permanent openings, one commencing within 12 inches of the top
and one commencing within 12 inches of the bottom of the enclosure. The openings shall communicate directly, or by ducts, with the outdoors or
spaces (crawl or attic) that freely communicate with
the outdoors. Refer to Table 3, for minimum open
areas requirements.
TABLE 3
MINIMUM FREE AREA IN SQUARE INCHES
EACH OPENING (FURNACE ONLY)
8
9
Furnace
Maximum
BTUH/INPUT
Rating
60,000
80,000
100,000
120,000
Air
From
Inside
100
100
100
120
Vertical
Duct
DUCT CONNECTIONS
Air duct systems should be installed in accordance with
standards for air conditioning systems, National Fire
Protection Association Pamphlet No. 90. They should
be sized in accordance with ACCA Manual D or whichever is applicable.
Central furnaces, when used in connection with cooling
units, shall be installed in parallel or on the upstream
side of the cooling coil to avoid condensation in the heat
exchanger.
18-CD30D1-99
Air From Outside
Horizontal
15
20
25
30
Duct
30
40
50
60
Installer’s Guide
▲
With a parallel flow arrangement, the dampers or other
means used to control flow of air shall be adequate to
prevent chilled air from entering the Furnace, and if
manually operated, must be equipped with means to
prevent operation of either unit unless the damper is in
full heat or cool position.
On any job, flexible connections of nonflammable material may be used for return air and discharge connections
to prevent transmission of vibration. Though these units
have been specifically designed for quiet, vibration free
operation, air ducts can act as sounding boards and could,
if poorly installed, amplify the slightest vibration to the
annoyance level.
When the furnace is located in a utility room adjacent
to the living area, the system should be carefully designed with returns to minimize noise transmission
through the return air grille. Although these furnaces
are designed with large blowers operating at moderate
speeds, any blower moving a high volume of air will
produce audible noise which could be objectionable
when the unit is located very close to a living area. It is
often advisable to route the return air ducts under the
floor or through the attic. Such design permits the installation of air return remote from the living area
(i.e. central hall).
When the furnace is installed so that the supply ducts
carry air circulated by the furnace to areas outside the
space containing the furnace, the return air shall also
be handled by a duct(s) sealed to the furnace and terminating outside the space containing the furnace.
RETURN AIR DUCT SYSTEMS
!
CAUTION
Safety Hazard
Sharp Edge Hazard
Be careful of sharp edges on equipment or any cuts
made on sheet metal while installing or servicing.
Personal injury may result.
Where there is no complete return duct system,
the return connection must be run full size from
the furnace to a location outside the utility room,
basement, attic, or crawl space.
Do NOT install return air through the back of the
furnace cabinet.
Do NOT install return air through the side of the
furnace cabinet on horizontal applications.
PREPARATION FOR UPFLOW BOTTOM AND SIDE
RETURN AIR FILTER INSTALLATION
All return air duct systems should provide for installation of return air filters.
1. Determine the appropriate position to set the
furnace in order to connect to existing supply and
return ductwork.
2. The return air filter is shipped in either the bottom
or side location. Remove the filter by first turning
the two latches on the blower door and tilting the
door forward to remove. Remove the filter by
sliding it out.
3. For upflow side return installations, remove the
insulation around the opening in the blower compartment.
4. The side panels of the upflow furnace include
locating notches that are used as guides for cutting
an opening for return air, refer to Figure 10 and the
outline drawing on page 4 for duct connection
dimensions for various furnaces.
0
LOCATING
NOTCHES PROVIDED FOR SIDE
RETURN CUTOUT
SEE OUTLINE DRAWING
*
5. If a 3/4" flange is to be used for attaching the air
inlet duct, add to cut where indicated by dotted
lines in Figure 10. Cut corners diagonally and bend
outward to form flange.
6. If flanges are not required, and a filter frame is
installed, cut between locating notches (See Figure
10).
7. The bottom panel of the upflow furnace must be
removed for bottom return air. After removing the
filter, lay the furnace on its back. Remove the two
5/16" hex screws securing the front of the bottom
channel to the cabinet.
UPFLOW FURNACE ONLY
CUT OUT FOR
SIDE FILTER
FRONT
of Furnace
NOTE:
Minimum return air temperature is 55°F.
1018-CD30D1-9
Rotate the channel downward (or remove by lowering the front edge of the channel and pulling forward). Slide the bottom return air panel out of the
cabinet. Rotate the front channel to its original
position and reinstall the two 5/16” screws.
8. The horizontal installation of the upflow
furnace requires an external filter section. Do
NOT use the bottom return filter within the
furnace. Filter kits are available for horizontal applications.
9. Connect duct work to furnace. See Outline Drawing
for supply and return duct size and location. Flexible duct connectors are recommended to connect
both supply and return air ducts to the furnace. If
only the front of the furnace is accessible, it is
recommended that both supply and return air
plenums are removable.
RETURN AIR FILTERS
TYPICAL UPFLOW RETURN AIR FILTER
INSTALLATIONS
Filters are factory supplied for these furnaces. These
furnaces require high velocity type air filters. The filters may be installed within the furnace blower compartment for UPFLOW furnaces in either a BOTTOM
or SIDE (left side or right side) return air inlet. Some
filters may need to be trimmed for side or bottom filter
use.
TABLE 4
MODELS
NUMBERS
*UHMB060ACV3VA
*UHMB080ACV3VA
*UHMC100ACV4VA21"1 - 20" X 25" X 1"
*UHMD120ACV5VA24-1/2"1 - 24" X 25" X 1"
* First letter may be "A" or "T"
NOTE: For upflow 5 ton airflow models where the
airflow requirement exceeds 1800 CFM - Models will
require return air openings and filters on: (1) both
sides, or (2) one side and the bottom, or (3) just the
bottom. The filter rack installation is not allowed for
right side return on the following models:
*UHMB060ACV3V, *UHMB080ACV3V & *UHMC100ACV4V.
CABINET
WIDTH
17-1/2"1 - 17" X 25" X 1"
FILTER
QTY & SIZE
Installer’s Guide
q
Airflow
BOTTOM FILTER RACK INSTALLATION
w
FILTER RACK ASSEMBLY
e
Blower Deck
Engagement
Hole
The furnace and the bottom filter rack, BAYRACK960,
installation can be seen in Figure 11.
The furnace filter in the bottom or side configuration
can be removed by simply turning the two latches on
the blower door and tilting the door forward.
The Filter rails are spring loaded for automatic adjustment to allow standard size, locally obtainable replacement filters. The filter rack itself slides to adjust to the
required width needed for bottom or side return (See
Figure 12).
18-CD30D1-911
VIEW
ENGAGEMENT
HOLE DETAIL
(Typical both sides
and blower deck)
Installer’s Guide
k
Airfl
ow
Airflow
ALTERNATE FILTER RACK INSTALLATION FOR BOTTOM RETURN - BAYRACK960
The following checklist should be used when installing a
bottom return filter on an upflow furnace:
a. Remove the filter.
b. Remove the bottom panel.
c. With the filter removed, the filter rack is
compressed and then inserted into the bottom
of the furnace. The retaining screw/pin on
each side inserts into engagement holes at the
bottom of the furnace cabinet side. See Figure
14.
d. Reinstall the furnace filter in the bottom
position by inserting the chamfer end first into
the filter rack. See Figure 19.
ALTERNATE FILTER RACK INSTALLATION FOR SIDE
RETURN AIR ON UPFLOW FURNACES (LEFT OR
RIGHT) - BAYRACK960
NOTE:
The filter rack installation is not allowed for right side
return on the following models: *UHMB060ACV3V,
*UHMB080ACV3V & *UHMC100ACV4V. See Figure 21 for
alternate upflow filter clip/ bracket installation.
The following checklist should be used when installing a
right or left side return filter on an upflow furnace:
a. Remove the filter.
b. Leave the bottom panel in place.
c. Make side cutout by following the directions in
the “Return Air Duct Connections” section on
page 10,
d. Compress the filter rack and reinstall in the side
position on the furnace. Confirm that the upper
retaining pin/screw locks into the engagement
hole in the blower deck and the lower pin/screw
rests against the side of the bottom panel. See
Figures 13, 15-18.
e. Reinstall the furnace filter in the side position by
inserting the chamfer end first into the filter
rack.
t
BOTTOM ENGAGEMENT
Filter Rack
Retaining
Furnace
Cabinet
Side
Engagement Hole
For
Filter Rack
Installation With
Bottom Return
Screw/Pin
Filter
Rack
Bottom Panel
y
Typical Upflow Left Side Return Filter Rack Installation
u
SIDE
CUTOUT
RETAINING
PIN
(Both Sides)
SPRINGS
FILTER
RACK
RAILS
Airflow
BOTTOM
PANEL
INSTALLED
SIDE
CUTOUT
r
SIDE ENGAGEMENT
Furnace
Cabinet
Side
Engagement Hole
For
Filter Rack
Installation With
Bottom Return
1218-CD30D1-9
Filter
Rack
Filter Rac
Retaining
Screw/Pin
Airflow
SPRINGS
BOTTOM
PANEL
INSTALLED
Typical Upflow Right Side Return Filter Rack Installation
FILTER
RACK
RAILS
RETAINING
PIN
(Both Sides)
Installer’s Guide
SIDE
CUT-OUT
ALTERNATE SIDE
FILTER CLIPS
LOCATIONS
ALTERNATE BOTTOM
FILTER CLIPS LOCATIONS
i
BLOWER
DECK
Furnace
Cabinet
o
Side
Engagement Hole
For
Filter Rack
Installation With
Side
Return
Filter Rack
Retaining
Screw/Pin
Airflow
Furnace
Blower
Deck
Filter
Rack
Assembly
CHAMFER
END OF
FILTER GOES
INTO FILTER
RACK FIRST
RETURN AIR FILTERS FOR UPFLOW FURNACE IN
HORIZONTAL CONFIGURATION
When the upflow furnace is installed in the horizontal
configuration, the return air filters must be installed
exterior to the furnace cabinet. Remote filter grilles
may be used for homeowner convenience or the filters
may be installed in the duct work upstream of the furnace. See Figure 20. Conversion kits for horizontal filter installation are shown in Table 4A.
Conversion kits for horizontal filters are BAYFLTR203
for 17 1/2" width cabinets, BAYFLTR204 for 21" width
cabinets, and BAYFLTR205 for 24" width cabinets.
These include filters and brackets necessary for horizontal filters. In addition, optional door kit
BAYFLTR206 is also available. See Figures 20 and 22.
UPFLOW FILTER CLIP/ BRACKET INSTALLATION
1. Determine the location to be used. The furnace
cabinet has dimples for location of the alternate
furnace clips (Side return only). Pre-drill clearance
holes with a 3/16" drill. Bottom return holes are
pre-drilled. Attach clip to bottom channel and rear
of unit with screws provided for bottom return.
2. Install the clips in front and rear of the desired
location using the screws provided. The filter clip
with the leaf spring mounts in the rear of the
cabinet. See Figure 21.
p
Optional door kit
BAYFLTR206
Typical Horizontal Filter Installation
Table 4A CONVERSION KITS FOR
HORIZONTAL FILTERS
MODEL NUMBERS
*UHMB060ACV3VA
*UHMB080ACV3VA
*UHMC100ACV4VA
*UHMD120ACV5VA
1. *First letter may be "A" or "T"
2. Kit includes Filters and Brackets necessary for Horizontal Filters.
3. Optional Door Kit BAYFLTR206 is also available.
18-CD30D1-913
CABINET
WIDTH
17-1/2"BAYFLTR203
21"BAYFLTR204
24-1/2"BAYFLTR205
a
Airflow
CONVERSION
KIT NUMBER
Installer’s Guide
INSTALLING THE FILTER
The filter may need to be cut to fit the unit depending
on the location of the return air filter.
A score line and the words “CUT HERE” are located on
the end of the filter. If your application requires cutting
the filter, do so as indicted by the score mark.
TABLE 5
UNIT
SIZE
RETURN AIR
BOTTOMSIDE
17-1/2"DO NOT CUT DO NOT CUT
21"DO NOT CUT CUT ON LINE
24-1/2"DO NOT CUT CUT ON LINE
TYPICAL DOWNFLOW FURNACE RETURN AIR FILTER
INSTALLATIONS
Two filters are factory supplied for each downflow furnace. These furnaces require high velocity type air filters.
Downflow furnace filters must be located outside the
furnace cabinet. Typical installations are shown in Figure 22. Tables 6 and 7 provide information for installation of the filter retaining brackets shipped with downflow furnaces.
TABLE 6
MODELS
NUMBERS
*DHMB060ACV3VB
*DHMB060BCV3VA
*DHMB080ACV3VA
*DHMC100ACV4VA21"2 - 16" X 20" X 1"
*DHMD120ACV5VB
*DHMD120BCV5VA
*First letter may be "A" or "T"
LOCATING FILTER RETAINER BRACKETS IN DUCTWORK
CABINET
WIDTH
17-1/2"16-1/4"15"14"14-3/8"
21"19-3/4"19-1/2"14"13-1/8"
24-1/2"23-1/4"22"14"13-5/8"
* LOCATION DIMENSION IS FROM END OF DUCT AGAINST THE FURNACE TO THE
SCREW HOLES FOR THE BRACKET.
RETURN
DUCT
WIDTH
CABINET
WIDTH
17-1/2"2 - 14" X 20" X 1"
24-1/2"2 - 16" X 20" X 1"
TABLE 7
DIMENSION
"A"
FILTER
QTY & SIZE
DIMENSION
"B"
FILTER
BRACKET
LOCATION*
s
Optional
BAYFLTR206
Door Kit
Airflow
DOWNFLOW
MINIMUM CLEARANCE FROM COMBUSTIBLE MATERIALS FOR
UPFLOW/HORIZONTAL AND DOWNFLOW/ HORIZONTAL FURNACES
FURNAC E SURFACE
SIDES0"1"0"
BACK0"3"6"
TOP1"1"1"
FRONT3"3"18"
VENT0"0"0"
: CLEARANCE REQUIRED AT TOP OF PLENUM IS 1"
NOTE
VERTICAL
CLOSET
TABLE 8
Optional
BAYFLTR206
Door Kit
Airflow
UNIT LOCATION
HORIZONTAL
CLOSET
DOWNFLOW/
HORIZONTAL
HORIZONTAL
ALCOVE / ATTIC
1418-CD30D1-9
Installer’s Guide
▲
▲
GENERAL VENTING INFORMATION
THIS FURNACE MUST BE VENTED TO THE OUTDOORS. THESE FURNACES ARE INDUCED DRAFT
VENTED AND MUST NOT BE CONNECTED TO ANY
VENT SERVING ANOTHER APPLIANCE. PLEASE
NOTE THAT THESE FURNACES USE POSITIVE-
PRESSURE VENT SYSTEMS.
!
WARNING
CARBON MONOXIDE HAZARD
FURNACE MUST BE VENTED PROPERLY.
FAILURE TO FOLLOW THIS WARNING COULD RESULT
IN CARBON MONOXIDE, FIRE OR SMOKE THAT CAN
CAUSE SERIOUS BODILY INJURY, DEATH OR PROPERTY DAMAGE.
IMPORTANT:
The building owner/maintenance provider must
keep the area around the vent clear from snow.
Proper venting is essential to obtain maximum efficiency from a condensing furnace. Proper installation of
the vent system is necessary to assure drainage of the
condensate and prevent deterioration of the vent system.
American Gas Association has certified the design of
condensing Furnaces for a minimum of 0" clearance
from combustible materials with a single wall plastic
vent pipe. See Table 8.
The recommended system is assembled from 2", 2-1/
2", or 3" plastic pipe and fittings (See Table 9, page
18) for material specifications. Where the system is
routed to the outdoors through an existing masonry
chimney containing flue products from another gas
appliance, or where required by local codes, then
3" venting of Type 29-4C stainless steel must be used
in place of PVC material.
These furnaces have been classified as CATEGORY IV
Furnaces in accordance with ANSI Z21.47 “latest edition” standards. Category IV Furnaces operate with
positive vent pressure and with a vent gas temperature
less than 140°F. above the dewpoint. These conditions
require special venting systems, which must be gas
tight and water tight.
NOTE:
When an existing furnace is removed from a venting
system serving other gas appliances, the venting system is likely to be too large to properly vent t
maining attached appliances.
The following steps shall be followed with each appliance remaining connected to the common venting system placed in operation, while the other appliances remaining connected to the common venting system are
not in operation.
he re-
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each
appliance connected to the venting system being
placed into operation could result in carbon monoxide
poisoning or death.
The following steps shall be followed for each appliance
connected to the venting system being placed into
operation, while all other appliances connected to the
venting system are not in operation:
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and
horizontal pitch, as required in the National Fuel Gas
Code, ANSI Z223.1/NFPA 54 or the CSA B149.1
Natural Gas and Propane Installation Code
instructions. Determine that there is no blockage or
restriction, leakage, corrosion and other deficiencies
which could cause an unsafe condition.
3. As far as practical, close all building doors and
windows and all doors between the space in which the
appliance(s) connected to the venting system are
located and other deficiencies which could cause an
unsafe condition.
4. Close fireplace dampers.
5. Turn on clothes dryers and any appliance not
connected to the venting system. Turn on any exhaust
fans, such as range hoods and bathroom exhausts, so
they are operating at maximum speed. Do not operate
a summer exhaust fan.
6. Follow the lighting instructions. Place the appliance
being inspected into operation. Adjust the thermostat
so appliance is operating continuously.
7. Test for spillage from draft hood equipped appliances
at the draft hood relief opening after 5 minutes of main
burner operation. Use the flame of a match or candle.
8. If improper venting is observed during any of the above
tests, the venting system must be corrected in
accordance with the National Fuel Gas Code,
ANSI Z221.1/NFPA 54 and/or CSA B149.1
Gas and Propane Installation Code
9. After it has been determined that each appliance
connected to the venting system properly vents where
when tested as outlined above, return doors, windows,
exhaust fans, fireplace dampers and any other gas-fired
burning appliance to their previous condition of use.
WHEN THE FACTORY SUPPLIED "OFF-SET" (2X3
REDUCING COUPLING) IS USED FOR 3" VENT PIPE
INSTALLATION, MAKE SURE THE MARKING "TOP" IS
#CPL00938
FACTORY SUPPLIED
ONLY WITH THE
FOLLOWING MODELS:
ALL 100,000 BTUH
UPFLOW MODELS, ALL
120,000 BTUH UPFLOW
MODELS, AND ALL
DOWNFLOW MODELS
LOCATED ON THE TOP SIDE OF THE PIPE.
LABEL
SAYS
"TOP"
STRAIGHT SIDE MUST BE
ON BOTTOM FOR PROPER
CONDENSATE DRAINAGE.
.
and these
Natural
d
18-CD30D1-915
Installer’s Guide
▲
▲
Furnace
Air
Inlet
Vent
2" TO 3" COUPLING
f
FACTORY SUPPLIED ONLY
WITH THE FOLLOWING
MODELS:
ALL 100,000 BTUH UPFLOW
MODELS, ALL 120,000 BTUH
UPFLOW MODELS, THE
UX1C080A9601 MODEL, AND
ALL DOWNFLOW MODELS
FURNACE
VENT
HORIZONTAL INSTALLATION
(UPFLOW/ HORIZONTAL OR DOWNFLOW/ HORIZONTAL)
NOTE:
See Figures 23 & 24. In horizontal venting when the
factory supplied “off-set” (2X3 reducing coupling) is
used for 3” vent pipe installation, make sure the marking “Top” is located on the top side of the pipe. The
straight side must be on bottom for proper condensate
drainage. This coupling is factory supplied with the following models: *UHMC100, *UHMD120, & all downflow
models.
!
WARNING
Carbon monoxide, fire or smoke can cause serious
bodily injury, death, and/ or property damage.
A variety of potential sources of carbon monoxide can be
found in a building or dwelling such as gas-fired clothes
dryers, gas cooking stoves, water heaters, Furnaces and
fireplaces. The U.S. Consumer Product Safety Commission recommends that users of gas-burning appliances
install carbon monoxide detectors as well as fire and
smoke detectors per the manufacturer’s installation instructions to help alert dwelling occupants of the presence of fire, smoke or unsafe levels of carbon monoxide.
These devices should meet Underwriters Laboratories,
Inc. Standards for Single and Multiple Station CarbonMonoxide Alarms, UL 2034 or CSA International
Standard, Residential Carbon Monoxide Alarming De-vices, CSA 6.19
NOTE:
The manufacturer of your furnace does not test any detectors and makes no representations regarding any
brand or type of detector.
IMPORTANT:
These furnaces may be installed as Direct Vent (sealed
combustion) or as Nondirect Vent (single pipe). The furnaces are shipped DIRECT VENT with sealed combustion.
For DIRECT VENT APPLICATION:
The furnaces must be vented to the exterior of the house
and combustion air MUST come through the inlet air pipe
FROM OUTSIDE AIR. The pipes DO NOT have to exit the
exterior of the house together or on the same side of the
house.
1618-CD30D1-9
#CPL00938
For NONDIRECT VENT APPLICATION:
The furnace shall be vented to the exterior of the house,
but combustion air may enter from the surrounding area as
long as combustion air requirements are met. (See AIR
FOR COMBUSTION AND VENTILATION)
FURNACE VENT/
INLET PIPE INSTALLATION
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow the installation instructions for the
venting system being placed into operation could re-
sult in carbon monoxide poisoning or death.
There are many different variations of the vent/ inlet
air pipe combination. The vent/ inlet air combination
used for installation of these furnaces depends on the
needs of the location. However, these guidelines must
be followed:
1.The Furnace must vent outside the structure.
2.Furnace combustion air requirements must be met
for nondirect, single pipe applications (See example
2 ).
3.For direct vent application of these furnaces, the
vent pipe and air inlet pipe do not have to exit in
the same air space or even on the same surface of
the structure.
However, the longest individual pipe will decide the
value for the longest allowable equivalent vent/ inlet air
length as shown in the vent length table.
NOTE:
BAYVENT200B accessories can be used for inlet and
outlet terminals when the pipes do not exit the structure together. For Canadian applications ONLY, IPEX
196006 may be used for horizontal and vertical terminations. IPEX 081216, IPEX 081218, and IPEX 081219
may be only used for horizontal vent terminations.
The following are EXAMPLES ONLY:
EX. 1 —
Example 1 shows that the vent may go vertical while
the inlet air may be on any side of the structure. The
Vent Pipe would decide the maximum equivalent length
for the pipe depending on the furnace and pipe size.
Installer’s Guide
EX. 2 —
Example 2 shows the vent pipe exhausting through the
roof and the inlet air coming from the interior of the
house (See Note). The inlet air coming from the interior of the house must meet combustion requirements
for area, etc., as shown in the section AIR FOR COMBUSTION AND VENTILATION in this Installer’s
Guide.
Vent
Air
Inlet
(See Note)
Furnace
EX. 3 —
Example 3 shows the vent exiting one side of the house
while the inlet air is on the opposite side of the structure. Here the Vent Pipe length must be within the allowable length for the size of Furnace and size of the
Vent Pipe. This example demonstrates that the pipes
do not have to exit on the same side of the structure.
NOTE:
If only the flue gas pipe is to the outside of the structure, a straight section of pipe (long enough to exit the
Furnace cabinet) must be attached to the inlet air side
with an elbow (which is 5 to 10 equivalent feet) installed on the end to prevent dust and debris from falling directly into the Furnace.
VENT FITTING MATERIAL – PLASTIC
Gas and liquid tight single wall vent fittings, designed
for resistance to corrosive flue condensate, MUST be
used throughout.
Listed in Table 9 are materials that meet these requirements. The materials listed are various grades of PVC
and ABS plastic.
PIPE JOINTS: All joints must be fastened and sealed to
prevent escape of combustion products into the building. These materials are acceptable for U.S. applications only. All Canadian installations must conform to
ULC S636.
NOTE:
It is recommended that the first joints from the furnace
be connected and sealed with high temperature RTV.
This will enable the pipes to be removed later without
cutting. Be sure to properly support these joints.
Air
Vent
Inlet
Furnace
EX. 4 —
The inlet air does not have to come from outside the
structure. Example 4 shows the inlet air (See Note),
may come from the attic if the requirements for combustion air are met as shown in the section AIR FOR
COMBUSTION AND VENTILATION.
Attic
Vent
Vent
Air
Inlet
(See Note)
Furnace
BONDING OF PVC
Commercially available solvent cement for PVC must
be used to join PVC pipe fittings. Follow instructions on
container carefully for U.S. applications only. Canadian
applications require primer and cement that are from a
single system manufacturer.
For U.S. applications only:
Pipe and Fittings – ASTM D1785, D2466, D2661, &
D2665
PVC Primer and Solvent Cement – ASTM D2564.
Procedure for Cementing Joints Ref – ASTM D2855
1.Cut pipe square, remove ragged edges and burrs.
Chamfer end of pipe, then clean fitting socket and
pipe joint area of all dirt, grease, moisture or chips.
2.After checking pipe and socket for proper fit, wipe
socket and pipe with cleaner-primer. Apply a liberal
coat of primer to inside surface of socket and outside of pipe.
DO NOT ALLOW PRIMER TO DRY BEFORE APPLYING CEMENT.
3.Apply a thin coat of cement evenly in the socket.
Quickly apply a heavy coat of cement to the pipe
end and insert pipe into fitting with a slight twisting
movement until it bottoms out.
4.Hold the pipe in the fitting for 30 seconds to prevent tapered socket from pushing the pipe out of
the fitting.
18-CD30D1-917
Loading...
+ 39 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.