CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each
appliance connected to the venting system being
placed into operation could result in carbon monoxide
poisoning or death.
The following steps shall be followed for each appliance
connected to the venting system being placed into
operation, while all other appliances connected to the
venting system are not in operation:
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and
horizontal pitch, as required in the National Fuel Gas
Code, ANSI Z223.1/NFPA 54 or the CSA B149.1
Natural Gas and Propane Installation Code and these
instructions. Determine that there is no blockage or
restriction, leakage, corrosion and other deficiencies
which could cause an unsafe condition.
3. As far as practical, close all building doors and
windows and all doors between the space in which the
appliance(s) connected to the venting system are
located and other deficiencies which could cause an
unsafe condition.
4. Close fireplace dampers.
5. Turn on clothes dryers and any appliance not
connected to the venting system. Turn on any exhaust
fans, such as range hoods and bathroom exhausts, so
they are operating at maximum speed. Do not operate
a summer exhaust fan.
6. Follow the lighting instructions. Place the appliance
being inspected into operation. Adjust the thermostat
so appliance is operating continuously.
7. Test for spillage from draft hood equipped appliances
at the draft hood relief opening after 5 minutes of main
burner operation. Use the flame of a match or candle.
8. If improper venting is observed during any of the above
tests, the venting system must be corrected in
accordance with the National Fuel Gas Code,
ANSI Z221.1/NFPA 54 and/or CSA B149.1 Natural Gas and Propane Installation Code.
9. After it has been determined that each appliance
connected to the venting system properly vents where
when tested as outlined above, return doors, windows,
exhaust fans, fireplace dampers and any other gas-fired
burning appliance to their previous condition of use.
!
CAUTION
To prevent shortening its service life, the Furnace should not
be used as a “Construction Heater” during the finishing
phases of construction until the requirements listed in item
9, a-g of the safety section of this publication have been met.
Condensate in the presence of chlorides and fluorides from
paint, varnish, stains, adhesives, cleaning compounds, and
cement create a corrosive condition which may cause rapid
deterioration of the heat exchanger.
!
WARNING
FIRE & EXPLOSIVE HAZARD. DO NOT USE SEMI-RIGID
METALLIC GAS CONNECTORS (FLEXIBLE GAS LINES)
WITHIN THE FURNACE CABINET.
FAILURE TO FOLLOW THIS WARNING COULD RESULT IN
PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
218-CD26D1-10
SAFETY SECTION
!
WARNING
Failure to follow safety warnings exactly, could result
in a fire or explosion causing property damage,
personal injury or loss of life.
— Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any
other appliance.
— WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch;
do not use any phone in your building.
• Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s
instructions.
• If you cannot reach your gas supplier,
call the fire department.
— Installation and service must be performed by
a qualified installer, service agency or the gas
supplier.
!
WARNING
FIRE OR EXPLOSION HAZARD
FAILURE TO FOLLOW THE SAFETY WARNINGS EXACT LY
COULD RESULT IN SERIOUS INJURY, DEATH OR PROPERTY DAMAGE.
IMPROPER SERVICING COULD RESULT IN DANGEROUS
OPERATION, SERIOUS INJURY, DEATH, OR PROPERTY
DAMAGE.
!
WARNING
▲
AZARD OF EXPLOSION!
EVER USE AN OPEN FLAME TO DETECT GAS LEAKS.
XPLOSIVE CONDITIONS MAY OCCUR. USE A LEAK TEST
OLUTION OR OTHER APPROVED METHODS FOR LEAK
ESTING. FAILURE TO FOLLOW RECOMMENDED SAFE LEA
EST PROCEDURES COULD RESULT IN DEATH OR SERIOU
NJURY OR EQUIPMENT OR PROPERTY-ONLY-DAMAGE.
!
WARNING
SAFETY HAZARD
THIS INFORMA TION IS INTENDED FOR USE BY INDIVIDUALS POSSESSING ADEQUATE BACKGROUNDS OF
ELECTRICAL AND MECHANICAL EXPERIENCE. ANY
ATTEMPT TO REPAIR A CENTRAL AIR CONDITIONING
PRODUCT MAY RESULT IN PERSONAL INJURY AND OR
PROPERTY DAMAGE. THE MANUFACTURER OR SELLER
CANNOT BE RESPONSIBLE FOR THE INTERPRET ATION OF
THIS INFORMATION, NOR CAN IT ASSUME ANY LIABILITY
IN CONNECTION WITH ITS USE.
!
CAUTION
Sharp Edge Hazard. Be careful of sharp edges on equipment or any cuts made on sheet metal while installing or
servicing. Personal injury may result.
Page 3
Installer’s Guide
▲
.
▲
The following warning complies with State of California law, Proposition 65
!
WARNING
This product contains fiberglass wool insulation!
Fiberglass dust and ceramic fibers are believed by the
State of California to cause cancer through inhalation.
Glasswool fibers may also cause respiratory, skin, or
eye irritation.
PRECAUTIONARY MEASURES
●
Avoid breathing fiberglass dust.
●
Use a NIOSH approved dust/mist respirator.
●
Avoid contact with the skin or eyes. Wear long-sleeved,
loose-fitting clothing, gloves, and eye protection.
●
Wash clothes separately from other clothing: rinse
washer thoroughly.
●
Operations such as sawing, blowing, tear-out, and
spraying may generate fiber concentrations requiring
additional respiratory protection. Use the appropriate
NIOSH approved respirator in these situations.
FIRST AID MEASURES
Eye Contact – Flush eyes with water to remove dust.
Skin Contact – Wash affected areas gently with soap
If symptoms persist, seek medical
attention.
and warm water after handling.
Careful consideration must be taken in the installation
process to avoid personal injury, property damage or equipment damage. These instructions do not cover all variations
in systems or provide for every possible contingency. Should
further information be desired or particular problems arise
which are not covered sufficiently by this manual, contact your
local distributor or the manufacturer as listed on the Furnace
nameplate.
In addition, these Furnaces are suitable for installation in an
attic, garage or crawl space with ducted supply and return air.
Safety signal words are used to designate a degree or level of
seriousness associated with a particular hazard. The signal
words for safety markings are WARNING, and CAUTION.
a. WARNING indicates a potentially hazardous situation
which, if not avoided, could result in death or serious
injury.
b. CAUTION indicates a potentially hazardous situation
which, if not avoided, may result in minor or moderate
injury. It is also used to alert against unsafe practices
and hazards involving only property damage.
!
WARNING
▲
WARNING EXPLOSION HAZARD
PROPANE GAS IS HEAVIER THAN AIR AND MAY
COLLECT IN ANY LOW AREAS OR CONFINED SPACES.
IN ADDITION, ODORANT FADE MAY MAKE THE GAS
UNDETECTABLE EXCEPT WITH A WARNING DEVICE. IF
THE GAS FURNACE IS INSTALLED IN A BASEMENT, AN
EXCAVATED AREA OR A CONFINED SPACE, IT IS
STRONGLY RECOMMENDED TO CONTACT A GAS
SUPPLIER TO INSTALL A GAS DETECTING WARNING
DEVICE IN CASE OF A GAS LEAK. THE
MANUFACTURER OF YOUR FURNACE DOES NOT TEST
ANY DETECTORS AND MAKES NO REPRESENTATIONS
REGARDING ANY BRAND OR TYPE OF DETECTOR.
18-CD26D1-103
Page 4
Installer’s Guide
The following safety practices and precautions must be
followed during the installation, servicing, and operation of
this Furnace.
1. Use only with the type of gas approved for this Furnace.
Refer to the Furnace rating plate.
2. Install this Furnace only in a location and position as
specified in “Location and Clearances” (page 5) of these
instructions.
3. Provide adequate combustion and ventilation air to the
Furnace space as specified in “Air for Combustion and
Ventilation” (page 9), of these instructions.
4. Combustion products must be discharged outdoors.
Connect this Furnace to an approved vent system only, as
specified in the “Venting” section (page 15), of these
instructions.
5. Never test for gas leaks with an open flame. Use a
commercially available soap solution made specifically
for the detection of leaks to check all connections, as
specified in the “Gas Piping” section of these instructions
on page 31.
6. Always install the Furnace to operate within the
Furnace’s intended temperature-rise range with a duct
system which has an external static pressure within the
allowable range, as specified on the unit rating plate.
Airflow with temperature rise for cfm versus static is
shown in the Service Facts accompanying this Furnace.
7. When a Furnace is installed so that supply ducts carry
air circulated by the Furnace to areas outside the space
containing the Furnace, the return air shall also be
handled by a duct(s) sealed to the Furnace casing and
terminating outside the space containing the Furnace.
8. A gas-fired Furnace for installation in a residential
garage must be installed as specified in “Location and
Clearances” section (page 5) , of these instructions.
9. The Furnace may be used for temporary heating of
buildings or structures under construction
following conditions have been met:
a.The Furnace venting system must be complete and
installed per manufacturers instructions.
b.The Furnace is controlled only by a room Comfort
Control (no field jumpers).
c.The Furnace return air duct must be complete and
sealed to the Furnace.
d.The Furnace input rate and temperature rise must
be verified to be within nameplate marking.
e.100% of the Furnace combustion air requirement
must come from outside the structure.
f.The Furnace return air temperature range is between 550 and 800 Fahrenheit.
g.Clean the Furnace, duct work, and components upon
substantial completion of the construction process, and
verify Furnace operating conditions including ignition,
input rate, temperature rise and venting, according to the
manufacturer's instructions.
10. This product must be gas piped by a Licensed Plumber or
Gas Fitter in the Commonwealth of Massachusetts.
only when the
Contents
Safety Section2
Installation Instructions5
General5
Location and Clearances5
Outline Drawings6
Upflow Installation8
Downflow Installation8
Horizontal Installation8
Air For Combustion and Ventilation9
Duct Connections10
Return Air Filters11
General Venting15
Vent Tables19
Horizontal Venting20
Horizontal Venting Through a Wall21
Venting Through The Roof23
Venting Routed Through a Masonry Chimney24
Downward Venting26
Condensate Drain Instructions27
Gas Piping32
Combustion and Input Check32
High Altitude Derate35
Electrical Connections36
Field Wiring Diagrams36
Start-up and Adjustment41
Preliminary Inspections41
Lighting Instructions41
Sequence of Operation41
Control and Safety Switch Adjustments42
Conditions Affecting System Operation43
IFC Error Flash Codes44
418-CD26D1-10
Page 5
Installer’s Guide
▲
▲
GENERAL INSTALLATION INSTRUCTIONS
The manufacturer assumes no responsibility for equipment
installed in violation of any code or regulation.
It is recommended that Manual J of the Air Conditioning
Contractors Association (ACCA) or A.R.I. 230 be followed in
estimating heating requirements. When estimating heating
requirements for installation at Altitudes above 2000 ft.,
remember the gas input must be reduced (See combustion
and input check page 31).
Material in this shipment has been inspected at the
factory and released to the transportation agency
without known damage. Inspect exterior of carton for
evidence of rough handling in shipment. Unpack
carefully after moving equipment to approximate
location. If damage to contents is found, report the
damage immediately to the delivering agency.
Codes and local utility requirements governing the installation of gas fired equipment, wiring, plumbing, and flue
connections must be adhered to. In the absence of local codes,
the installation must conform with latest edition of the
National Fuel Gas Code ANSI Z223.1• National Installation
Code, CAN/CGA B149.1. The latest code may be obtained
from the American Gas Association Laboratories, 400 N.
Capitol St. NW, Washington D.C. 20001.
1-800-699-9277 or www.aga.org.
These Furnaces have been classified as CATEGORY IV
furnaces in accordance with latest edition of ANSI Z21.47
standards • CSA 2.3. Category IV furnaces operate with
positive vent static pressure and with a flue loss less than 17
percent. These conditions require special venting systems,
which must be gas tight and water tight. These Category IV
Direct Vent Furnaces are approved for installation in Manufactured/ Mobile housing when used with BAYMFGH001A.
LOCATION AND CLEARANCES
4. Are there at least 3 inches of clearance between the
Furnace combustion air openings in the front panel and
any closed panel or door provided?
5. Are the ventilation and combustion air openings large
enough and will they remain unobstructed? If outside air
is used, are the openings set 12" above the highest snow
accumulation level (18" minimum in Canadian applications)?
6. Allow sufficient height in supply plenum above the
Furnace to provide for cooling coil installation, if the
cooling coil is not installed at the time of this Furnace
installation.
IMPORTANT: The Furnace must be installed level.
The only allowable variation would be slightly to
the left and/ or forward in upflow installations or
slightly toward the front in horizontal installations.
This is necessary for proper condensate drainage.
7. A Furnace shall be installed so electrical components are
protected from water.
8. If the Furnace is installed in a garage, it must be
installed so that the burners, and the ignition source are
located not less than 18 inches above the floor and the
Furnace must be located or protected to avoid physical
damage from vehicles.
!
WARNING
FIRE HAZARD. DO NOT INST ALL THE FURNACE DIRECTLY
ON CARPETING, TILE OR OTHER COMBUSTIBLE MA TERIAL OTHER THAN WOOD FLOORING.
!
CAUTION
Do NOT install the Furnace in a corrosive or contaminated
atmosphere.
Failure to follow this caution could result in early equipment
failure.
The location of the Furnace is normally selected by the
architect, the builder, or the installer. However, before the
Furnace is moved into place, be sure to consider the following
requirements:
1. Is the location selected as near the chimney or vent and
as centralized for heat distribution as practical?
2. Do all clearances between the Furnace and enclosure
equal or exceed the minimums stated in Clearance Table
on the Outline Drawings?
3. Is there sufficient space for servicing the Furnace and
other equipment? A minimum of 24 inches front accessibility to the Furnace must be provided. Any access door
or panel must permit removal of the largest component.
18-CD26D1-105
Page 6
Installer’s Guide
Figure 2. Upflow Outline Drawing
618-CD26D1-10
Page 7
Installer’s Guide
Figure 3. Downflow Outline Drawing
18-CD26D1-107
Page 8
Installer’s Guide
▲
S
)
S
4)
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
INSTALLATION INSTRUCTIONS
!
WARNING
FIRE HAZARD. DO NOT INST ALL THE FURNACE DIRECTLY
ON CARPETING, TILE OR OTHER COMBUSTIBLE MA TERIAL OTHER THAN WOOD FLOORING. FOR VERTICAL
DOWNFLOW APPLICA TION, SUBBASE (BAYBASE205)
MUST BE USED BETWEEN THE FURNACE AND COMBUSTIBLE FLOORING. WHEN THE DOWNFLOW FURNACE IS
INSTALLED VERTICALLY WITH A CASED COIL, A SUBBASE IS NOT REQUIRED.
The bottom panel of the upflow furnace must be removed for
bottom return air.
Remove the filter and lay the furnace on its back. Remove the
two 5/16" hex screws securing the bottom front channel to the
cabinet. Lower the front edge of the bottom front channel and
pull forward to remove the channel. The bottom return air
panel will now easily slide out of the cabinet. Reinstall the
bottom front channel and filter for upflow bottom return
installations.
UPFLOW INSTALLATION
Standoffs and screws (See Figure 4) are included with the
cased coils for attachment to the Furnace. There are clearance alignment holes near the bottom of the coil wrapper.
Drill screws are used to engage the Furnace top flanges. The
standoff is inserted into the cabinet alignment hole. The drill
screws are inserted through the standoffs then screwed into
the Furnace flange. The coil is always placed downstream of
the Furnace airflow. The above instructions apply only if the
coil is on top of an upflow Furnace
FOR VERTICAL
CASED
UPFLOW
FURNACE
COIL
STANDOFFS
(BOTH SIDES)
TANDOFFS (4)
SCREW
(BOTH SIDES
Figure 4
DOWNFLOW INST ALLATION
Figure 5
MINIMUM CLEARANCE FROM COMBUSTIBLE MATERIALS FOR
UPFLOW/HORIZONTAL AND DOWNFLOW/ HORIZONTAL FURNACES
FURNACE SURFACE
SIDES0"1"0"
BACK0"3"6"
TOP1"1"1"
FRONT3"3"18"
VENT0"0"0"
: CLEARANCE REQUIRED AT TOP OF PLENUM IS 1"
NOTE
818-CD26D1-10
VERTICAL
CLOSET
Table 2
DRILL SCREWS (
UNIT LOCATION
HORIZONTAL
CLOSET
Table 1 Required floor opening: (DOWNFLOW)
CABINET
WIDTH
RETURN
DUCT WIDTH
17-1/2"16-1/4"16-5/8"20-1/8"15-5/8"19-3/8"
21"19-3/4"20-1/8"20-1/8"19-1/8"19-3/8"
24-1/2"23-1/4"23-5/8"20-1/8"22-5/8"19-3/8"
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
FURNACE
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
FRONT
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
FLOOR OPENING PLENUM OPENING
"A""B""C""D"
A (width)
B (depth)
D
C
Figure 6
HORIZONTAL INSTALLATION
The coil and Furnace must be fully supported when used in
the horizontal position. It is always recommended that an
auxiliary drain pan be installed under a horizontally installed evaporator coil or 90% Gas Furnace. Connect the
auxiliary drain line to a separate drain line (no trap is needed
in this line).
Three brackets (with screws) are included with downflow
furnaces for installtion to stabilize and secure the 2/4TXC
cased coil in the horizontal position. See Figure 8.
The cased coil is secured to the Furnace. The brackets mount
using the rear screws on the coil case. Use the screws provided
to secure the bracket to the Furnace. The remaining bracket
is placed as close to horizontal center as possible between the
coil and the Furnace, converted to horizontal, aligns and
attaches to the TXC coil.
The Furnace and the cased coil must be properly supported.
The Furnace may be installed in an attic or crawl space in the
horizontal position by placing the Furnace on the left side (as
viewed from the front in the vertical position). The horizontal
Furnace installation in an attic should be on a service
platform large enough to allow for proper clearances on all
sides and service access to the front of the Furnace (See
Figure 6 & Table 1). Line contact is only permissible between
lines formed by intersections of the top and two sides of the
furnace casing and building joists, studs, or framing.
The Furnace may be placed horizontally in a crawl space on a
pad or other noncombustible material which will raise the
unit for sufficient protection from moisture.
The Furnace must be supported at both ends and the
middle when installed horizontally. The Furnace must
also be elevated approximately 4-6 inches to allow
clearance for the condensate drain to exit the cabinet in
the horizontal position.
IMPORTANT:
The 2/4TXC cased coil must
HORIZONTAL
ALCOVE / ATTIC
be placed downstream of the
furnace. In horizontal installations, the apex of the coil
may point either toward or
away from the furnace. See
the 2/4TXC coil Installer's
Guide for more details.
Page 9
The horizontal Furnace may also be suspended from the
E
.
▲
joists using all-thread rods with a substantial metal support
frame that supports the entire length of the furnace. The
rods need to be of sufficient length to allow for proper clearances from combustible materials. The frame needs to be at
least 32" in length to allow for access to service panels.
If the Furnace is suspended using steel strap, it must be
supported at all four corners and in the middle at the front of
the Furnace.
UPFLOW/
HORIZONTAL
SHOWN WITH
DIRECT VENT
Figure 7
CASED COIL CONNECTION
BRACKET FOR DOWNFLOW
FURNACE IN HORIZONTAL
DOWNFLOW ONLY
Figure 8
AIR FOR COMBUSTION AND VENTILATION
The following warning complies with State of California law, Proposition 65
!
WARNING
HAZARDOUS GASES!
EXPOSURE TO FUEL SUBSTANCES OR BY-PRODUCTS
OF INCOMPLETE FUEL COMBUSTION IS BELIEVED BY
THE STATE OF CALIFORNIA TO CAUSE CANCER,
BIRTH DEFECTS, OR OTHER REPRODUCTIVE HARM.
Adequate flow of combustion and ventilating air must not be
obstructed from reaching the Furnace. Air openings provided
in the Furnace casing must be kept free of obstructions which
restrict the flow of air. Airflow restrictions affect the efficiency
and safe operation of the Furnace. Keep this in mind should
you choose to remodel or change the area which contains your
Furnace. Furnaces must have a free flow of air for proper
performance.
Provisions for combustion and ventilation air shall be made
in accordance with “latest edition” of Section 5.3, Air for
Combustion and Ventilation, of the National Fuel Gas Code,
ANSI Z223.1, or Sections 7.2, 7.3 or 7.4 of CSA B149.1
Installation Codes, and applicable provisions of the local
building codes. Special conditions created by mechanical
exhausting of air and fireplaces must be considered to avoid
unsatisfactory Furnace operation.
UNCONFINED
50 CU. FT. OR MORE
PER 1000 BTU/ HR. INPUT
ALL EQUIP. INSTALLED
Figure 9
Furnace locations may be in a confined space (see Figure 10)
or an unconfined space (See Figure 9).
Installer’s Guide
Table 3
MINIMUM AREA IN SQUARE FEET
FOR UNCONFINED SPACE INSTALLATIONS
FURNACE
MAXIMUM BTUH
INPUT RATING
60,000
80,000
100,000
120,000
140,000
Unconfined space is defined in Table 3 and Figure 9. These
spaces may have adequate air by infiltration to provide air
for combustion, ventilation, and dilution of flue gases.
Buildings with tight construction (for example, weather
stripping, heavily insulated, caulked, vapor barrier, etc.), may
need additional air provided as described for confined space.
1.
All air from inside the building as in Figure 11: The con-
fined space shall be provided with two permanent
openings communicating directly with an additional
room(s) of sufficient volume so that the combined volume
of all spaces meets the criteria for an unconfined space.
The total input of all gas utilization equipment installed
in the combined space shall be considered in making this
determination. Refer to Table 4, for minimum open
areas required.
2.
All air from outdoors as in Figure 12: The confined space
shall be provided with two permanent openings, one
commencing within 12 inches of the top and one commencing within 12 inches of the bottom of the enclosure.
The openings shall communicate directly, or by ducts,
with the outdoors or spaces (crawl or attic) that freely
communicate with the outdoors. Refer to Table 4, for
minimum open areas required.
CONFINED
LESS THAN 50 CU. FT.
PER 1000 BTU/HR. INPUT
ALL EQUIP INSTALLED
MINIMUM FREE AREA IN SQUARE INCHES
EACH OPENING (FURNACE ONLY)
Furnace
Maximum
BTUH/INPUT
Rating
60,000
80,000
100,000
120,000
140,000
Confined spaces are installations with less than 50 cu. ft. of
space per 1000 BTU/ hr input from all equipment installed.
Confined space is defined in Figure 10. Air for combustion
and ventilation requirements can be supplied from inside the
building as in Figure 11 or from the outdoors, as in Figure 12.
3. The following types of installations will require use of
OUTDOOR AIR for combustion, due to chemical
exposures:
* Commercial buildings
* Buildings with indoor pools
* Furnaces installed in commercial laundry rooms
* Furnaces installed in hobby or craft rooms
From
Inside
WITH 8 FT. CEILING
MINIMUM AREA IN SQUARE
FEET OF UNCONFINED SPAC
375
500
625
750
875
Figure 10
Table 4
Air
100
100
100
120
140
Air From Outside
Vertical
Duct
15
20
25
30
35
Horizontal
Duct
30
40
50
60
70
18-CD26D1-109
Page 10
Installer’s Guide
▲
* Furnaces installed near chemical storage areas.
Exposure to the following substances in the combus-
tion air supply will also require OUTDOOR AIR for
combustion:
* Permanent wave solutions
* Chlorinated waxes and cleaners
* Chlorine based swimming pool chemicals
* Water softening chemicals
* Deicing salts or chemicals
* Carbon Tetrachloride
* Halogen type refrigerants
* Cleaning solvents (such as perchloroethylene)
* Printing inks, paint removers, varnish, etc.
* Hydrochloric acid
* Cements and glues
* Antistatic fabric softeners for clothes dryers
* Masonry acid washing materials
NOTE: Extended warranties are not available in some
instances. Extended warranty does not cover repairs to
equipment installed in establishments with corrosive
atmospheres, including but limited to, dry cleaners, beauty
shops, and printing facilities.
DUCT CONNECTIONS
Figure 11
!
CAUTION
▲
SAFETY HAZARD
Sharp Edge Hazard. Be careful of sharp edges on equipment or any cuts made on sheet metal while installing or
servicing. Personal injury may result.
Air duct systems should be installed in accordance with
standards for air conditioning systems, National Fire
Protection Association Pamphlet No. 90. They should be
sized in accordance with ACCA Manual D.
Central Furnaces, when used in connection with cooling units,
shall be installed in parallel or on the upstream side of the
cooling coil to avoid condensation in the heat exchanger. With a
parallel flow arrangement, the dampers or other means used to
control flow of air shall be adequate to prevent chilled air from
entering the Furnace, and if manually operated, must be
equipped with means to prevent operation of either unit unless
the damper is in full heat or cool position.
Flexible connections of nonflammable material may be used for
return air and discharge connections to reduce the transmission
of vibration. Though these units have been specifically designed
for quiet, vibration free operation, air ducts can act as sounding
boards and could, if poorly installed, result in vibration to the
annoyance level.
When the Furnace is located in a utility room adjacent to the
living area, the system should be carefully designed with
returns to minimize noise transmission through the return
air grille. Although these Furnaces are designed with large
blowers operating at moderate speeds, any blower moving a
high volume of air will produce audible noise which could be
objectionable when the unit is located very close to a living
area. It is often advisable to route the return air ducts under
the floor or through the attic. Such design permits the
installation of air return remote from the living area (i.e.
central hall).
When the Furnace is installed so that the supply ducts carry
air circulated by the Furnace to areas outside the space
containing the Furnace, the return air shall also be handled
by a duct(s) sealed to the Furnace and terminating outside
the space containing the Furnace.
Figure 12
1018-CD26D1-10
Page 11
Installer’s Guide
Where there is no complete return duct system, the
return connection must be run full size from the Furnace to a location outside the utility room, basement,
attic, or crawl space.
Do Not install return air through the back of the Furnace
cabinet.
Carbon monoxide, fire or smoke can cause serious bodily
injury, death, and/or property damage.
A variety of potential sources of carbon monoxide can be found
in a building or dwelling such as gas-fired clothes dryers, gas
cooking stoves, water heaters, furnaces and fireplaces. The
U.S. Consumer Product Safety Commission recommends
that users of gas-burning appliances install carbon monoxide
detectors as well as fire and smoke detectors per the manufactures installation instructions to help alert dwelling
occupants of the presence of fire, smoke or unsafe levels of
carbon monoxide. These devices should be listed by Underwriters Laboratories, Inc. Standards for Single and MultipleStation Carbon Monoxide Alarms, UL 2034 or CSA International Standard, Residential Carbon Monoxide AlarmingDevices, CSA 6.19.
NOTE: The manufacturer of your Furnace DOES NOT test
any detectors and makes no representations regarding any
brand or type of detector.
All return air duct systems should provide for installation of
return air filters.
PREPARATION FOR UPFLOW BO TTOM AND SIDE RETURN
AIR FILTER INST ALLATION
All return air duct systems should provide for installation of
return air filters.
1. Determine the appropriate position to set the furnace in
order to existing supply and return ductwork.
2. The return air filter and rack are shipped in either the
bottom or side location. Remove the filter and filter rack
by first turning the two latches on the blower door and
tilting the door forward to remove. Remove the filter by
sliding it out of the rack. Compress the spring loaded
filter rack to disengage the retaining pins/screws from
the furnace sides and slide the filter rack out.
The filter rails are spring loaded for automatic adjustment to allow standard size, locally obtainable replacement filters. The filter rack itself slides to adjust to the
required width needed for bottom or side return (See
Figure 15).
3. For upflow side return installations, remove the insulation
around the opening in the blower compartment.
4. The side panels of the upflow furnace include locating
notches that are used as guides for cutting an opening for
return air, refer to Figure 13 and the outline drawing on
page 6 for duct connection dimensions for various
furnaces.
5. If a 3/4" flange is to be used for attaching the air inlet
duct, add to cut where indicated by dotted lines in
Figure 13. Cut corners diagonally and bend outward to
form flange.
6. If flanges are not required, and a filter frame is installed,
cut between locating notches (See Figure 13).
7. The bottom panel of the upflow furnace must be removed
for bottom return air. After removing the filter and filter
rack, lay the furnace on its back. Remove the two 5/16"
hex screws securing the front of the bottom channel to the
cabinet. Rotate the channel downward (or remove by
lowering the front edge of the channel and pulling
forward).
Slide the bottom return air panel out of the cabinet.
Rotate the front channel to its original position and
reinstall the two 5/16” screws.
8. The horizontal installation of the upflow furnace
requires an external filter section. Do NOT use the
bottom return filter within the furnace. Filter kits
are available for horizontal applications.
9. Connect duct work to furnace. See Outline Drawing for
supply and return duct size and location. Flexible duct
connectors are recommended to connect both supply and
return air ducts to the furnace. If only the front of the
furnace is accessible, it is recommended that both supply
and return air plenums are removable.
Return Air Filters
TYPICAL UPFLOW RETURN AIR FILTER INSTALLATIONS
Filters are factory supplied for these furnaces. These furnaces require high velocity type air filters. The filters may be
installed within the furnace blower compartment for UPFLOW furnaces in either a BOTTOM or SIDE (left side or
right side) return air inlet. Some filters may need to be
trimmed for side or bottom filter use.
Table 5
MODELS
NUMBERS
*UH2B060A9V3VA
*UH2B080A9V3VA
*UH2B080A9V4VA
*UH2C100A9V4VA
*UH2C100A9V5VA
*UH2D120A9V5VA24-1/2"1 - 24" X 25 X 1"
*First letter may be "A" or "T"
**NOTE: For upflow 5 ton airflow models where the airflow
requirement exceeds 1800 CFM - Modles will require return air
openings and filters on: (1) both sides, or (2) one side and the
bottom, or (3) just on the bottom
NOTE: For upflow 5 ton airflow models where the airflow
requirement exceeds 1800 CFM - Models will require return
air openings and filters on: (1) both sides, or (2) one side and
the bottom, or (3) just the bottom.
UPFLOW FURNACE ONLY
LOCATING
NOTCHES
PROVIDED FOR
SIDE RETURN
CUTOUT
SEE OUTLINE DRAWING
*
CABINET
WIDTH
17-1/2"1 - 17" X 25" X 1"
21"1 - 20" X 25" X 1"
FILTER
QTY & SIZE
FRONT
of Furnace
Figure 13
18-CD26D1-1011
Page 12
Installer’s Guide
E
(
a
F
k
n
The furnace and the bottom filter rack installation can be
seen in Figure 14.
Airflow
Blower Door Hinge and Bottom Filter Rack Installation
Figure 14
OPTIONAL FILTER RACK INSTALLATION FOR BOTTOM
RETURN
The following checklist should be used when installing a
return filter on an upflow furnace:
a. Remove the filter.
b. Remove the filter rack.
c. Remove the bottom panel.
e. With the filter removed, the filter rack is compressed
and then inserted into the bottom of the furnace. The
retaining screw/pin on each side inserts into engagement
holes at the bottom of the furnace cabinet side. See
Figure 17.
f. Reinstall the furnace filter in the bottom position by
inserting the chamfer end first into the filter rack.
FILTER RACK INST ALLATION FOR SIDE RETURN AIR
ON UPFLOW FURNACES (Left or Right)
The following checklist should be used when installing a right
or left side return filter on an upflow furnace:
a. Remove the filter.
b. Remove the filter rack.
c. Leave the bottom panel in place.
e. Make side cutout by following the directions in the
“Return Air Duct Connections” section on page 11.
e. Compress the filter rack and reinstall in the side
position on the furnace. Confirm that the upper
retaining pin/screw locks into the engagement hole in
the blower deck and the lower pin/screw rests against
the side of the bottom panel. See Figures 16, 18-21.
f. Reinstall the furnace filter in the side position by
inserting the chamfer end first into the filter rack.
Filter Rack Assembly
Figure 15
Blower Deck
Engagement
Hole
VIEW
NGAGEMENT
HOLE DETAIL
Typical both sides
nd blower deck)
Figure 16
1218-CD26D1-10
Filter
urnace
Rack
Cabinet
Side
Filter Rac
Retaining
Screw/Pi
Engagement Hole
For
Filter Rack
Installation With
Bottom Return
Figure 17
Conversion kits for horizontal filters are BAYFLTR203 for 17
1/2" width cabinets, BAYFLTR204 for 21" width cabinets,
and BAYFLTR205 for 24" width cabinets. These include
filters and brackets necessary for horizontal filters. In
addition, optional door kit BAYFLTR206 is also available.
See Figures 23 and 25.
Page 13
Installer’s Guide
ly
F
CHAMFER
END OF
FILTER GOES
INTO FILTER
RACK FIRST
l
er
k
E
(
SIDE
Airflow
s)
Airflow
Furnace
Cabinet
Side
ngagement Hole
For
Filter Rack
Installation With
Bottom Return
BOTTOM ENGAGEMENT
BLOWER
DECK
urnace
Cabinet
Side
Filter Rack
Retaining
Screw/Pin
Figure 18
Engagement Hole
For
Filter Rack
Installation With
Return
Side
Filt
Rac
Bottom Pane
Furnace
Blower
Deck
SIDE
CUTOUT
Airflow
BOTTOM
PANEL
INSTALLED
SPRINGS
FILTER
RACK
RAILS
RETAINING
PIN
(Both Side
Figure 21
Typical Upflow Right Side Return Filter Rack Installation
Airflow
Filter Rack
Retaining
Screw/Pin
Filter
Rack
Assemb
Figure 19
Figure 22
CUTOUT
Airflow
RETAINING
PIN
Both Sides)
Typical Upflow Left Side Return Filter Rack Installation
SPRINGS
FILTER
RACK
RAILS
Figure 20
BOTTOM
PANEL
INSTALLED
RETURN AIR FILTERS FOR UPFLOW FURNACE IN
HORIZONTAL CONFIGURATION
When the Upflow Furnace is installed in the horizontal
configuration, the return air filters must be installed exterior
to the furnace cabinet. Remote filter grilles may be used for
homeowner convenience or the filters may be installed in the
duct work upstream of the furnace. See Figure 23.
1. Determine the location to be used. The furnace cabinet
has dimples for location of the alternate furnace clips
(Side return only). Pre-drill clearance holes with a
3/16" drill. Bottom return holes are pre-drilled.
2. Install the clips in front and rear of the desired location
using the screws provided. The filter clip with the leaf
spring mounts in the rear of the cabinet. See Figure 24.
REAR
SIDE
CUT-OUT
ALTERNATE FILTE
CLIPS LOCATION
Figure 24
INSTALLING THE FILTER
The filter may need to be cut to fit the unit depending on the
location of the return air filter.
A score line and the words “CUT HERE” are located on the
end of the filter. If your application requires cutting the filter,
do so as indicted by the score mark.
Table 6
UNIT
SIZE
RETURN AIR
BOTTOMSIDE
17-1/2"DO NOT CUT DO NOT CUT
21"DO NOT CUT CUT ON LINE
24-1/2"DO NOT CUT CUT ON LINE
TYPICAL DOWNFLOW FURNACE
RETURN AIR FILTER INSTALLATIONS
Two filters are factory supplied for each downflow furnace.
These furnaces require high velocity type air filters. Downflow furnace filters must be located outside the furnace
cabinet. Typical installations are shown in Figure 25. Table
8 provides information for installation of the filter retaining
brackets shipped with downflow furnaces.
Table 7
MODELS
NUMBERS
*DH2B060A9V3VA
*DH2B080A9V3VA
*DH2B080A9V4VA
*DH2C100A9V4VA21"2 - 16" X 20" X 1"
*DH2D120A9V5VA24-1/2"2 - 16" X 20 X 1"
* First letter may be "A" or "T"
CABINET
WIDTH
17-1/2"2 - 14" X 20" X 1"
FILTER
QTY & SIZE
Optional
BAYFLTR206
Door Kit
DOWNFLOW
Table 8
LOCATING FILTER RETAINER BRACKETS IN DUCTWORK
CABINET
WIDTH
17-1/2"16-1/4"15"14"14-3/8"
21"19-3/4"19-1/2"14"13-1/8"
24-1/2"23-1/4"22"14"13-5/8"
* LOCATION DIMENSION IS FROM END OF DUCT AGAINST THE FURNACE TO THE
SCREW HOLES FOR THE BRACKET.
RETURN
DUCT
WIDTH
DIMENSION
"A"
DIMENSION
"B"
FILTER
BRACKET
LOCATION
Optional door
kit
BAYFLTR206
Figure 25
DOWNFLOW/
HORIZONTAL
1418-CD26D1-10
Page 15
Installer’s Guide
▲
▲
GENERAL VENTING
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each
appliance connected to the venting system being
placed into operation could result in carbon monoxide
poisoning or death.
The following steps shall be followed for each appliance
connected to the venting system being placed into
operation, while all other appliances connected to the
venting system are not in operation:
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and
horizontal pitch, as required in the National Fuel Gas
Code, ANSI Z223.1/NFPA 54 or the CSA B149.1
Natural Gas and Propane Installation Code and these
instructions. Determine that there is no blockage or
restriction, leakage, corrosion and other deficiencies
which could cause an unsafe condition.
3. As far as practical, close all building doors and
windows and all doors between the space in which the
appliance(s) connected to the venting system are
located and other deficiencies which could cause an
unsafe condition.
4. Close fireplace dampers.
5. Turn on clothes dryers and any appliance not
connected to the venting system. Turn on any exhaust
fans, such as range hoods and bathroom exhausts, so
they are operating at maximum speed. Do not operate
a summer exhaust fan.
6. Follow the lighting instructions. Place the appliance
being inspected into operation. Adjust the thermostat
so appliance is operating continuously.
7. Test for spillage from draft hood equipped appliances
at the draft hood relief opening after 5 minutes of main
burner operation. Use the flame of a match or candle.
8. If improper venting is observed during any of the above
tests, the venting system must be corrected in
accordance with the National Fuel Gas Code,
ANSI Z221.1/NFPA 54 and/or CSA B149.1 Natural Gas and Propane Installation Code.
9. After it has been determined that each appliance
connected to the venting system properly vents where
when tested as outlined above, return doors, windows,
exhaust fans, fireplace dampers and any other gas-fired
burning appliance to their previous condition of use.
!
WARNING
CARBON MONOXIDE POISONING HAZARD
FAILURE TO FOLLOW THE INSTALLATION INSTRUCTIONS
FOR THE VENTING SYSTEM BEING PLACED INTO OPERATION COULD RESULT IN CARBON MONOXIDE POISONING
OR DEATH.
Do Not install return air through the side of the furnace
cabinet on horizontal applications.
NOTE: Minimum return air temperature is 55° F.
FURNACE EXHAUST MUST BE VENTED TO THE
OUTDOORS. THESE FURNACES ARE INDUCED DRAFT
VENTED AND MUST NOT BE CONNECTED TO ANY
VENT SERVING ANOTHER APPLIANCE. PLEASE NOTE
THAT THESE FURNACES USE POSITIVE-PRESSURE
VENT SYSTEMS.
Proper venting is essential to obtain maximum efficiency
from a condensing Furnace. Proper installation of the vent
system is necessary to assure drainage of the condensate and
prevent deterioration of the vent system.
American Gas Association has certified the design of condensing Furnaces for a minimum of 0" clearance from combustible
materials with a single wall plastic vent pipe.
The recommended system is assembled from 2", 2-1/2", or 3"
plastic pipe and fittings (See Table 10, page 19). Where the
system is routed to the outdoors through an existing masonry
chimney containing flue products from another gas appliance,
or where required by local codes, then 3" venting of Type 29-4C
stainless steel must be used in place of PVC material.
These Furnaces have been classified as CATEGORY IV
Furnaces in accordance with ANSI Z21.47 “latest edition”
standards. Category IV Furnaces operate with positive vent
pressure and with a vent gas temperature less than 140°F
above the dewpoint. These conditions require special venting
systems, which must be gas tight and water tight.
NOTE: When an existing Furnace is removed from a venting
system serving other gas appliances, the venting system is
likely to be too large to properly vent the remaining attached
appliances.
The following steps shall be followed with each appliance
remaining connected to the common venting system placed in
operation, while the other appliances remaining connected to
the common venting system are not in operation.
1. Seal any unused openings in the common venting system.
2. Visually inspect the venting system for proper size and
horizontal pitch and determine there is no blockage or
restriction, leakage, corrosion or other deficiencies which
could cause an unsafe condition.
3. In so far as is practical, close all building doors and
windows and all doors between the space in which the
appliances remaining connected to the common venting
system are located and other spaces of the building. Turn
on clothes dryers and any appliances not connected to the
common venting system. Turn on any exhaust fans, such
as range hoods and bathroom exhausts, so they will
operate at maximum speed. Do not operate a summer
exhaust fan, close fireplace dampers.
4. Follow the lighting instructions. Place the appliance
being inspected in operation. Adjust Comfort Control so
appliance will operate continuously.
5. After it has been determined that each appliance remaining connected to the common venting system properly
vents when tested as outlined above, return door, windows,
exhaust fans, fireplace dampers and any other gasburning appliance to their previous conditions of use.
If improper venting is observed during any of the above tests,
the remaining common venting system must be corrected.
Correction could require rerouting or resizing the remaining
vent system.
IMPORTANT: These Furnaces may be installed as Direct
Vent (sealed combustion) or as Nondirect Vent (single pipe).
The Furnaces are shipped DIRECT VENT with sealed
combustion.
18-CD26D1-1015
Page 16
Installer’s Guide
A
I
Vent
Vent
(
A
I
nt
nt
Attic
For DIRECT VENT APPLICATION: The Furnaces must
be vented to the exterior of the house and combustion air
MUST come through the inlet air pipe FROM OUTSIDE
AIR.
NOTE: BAYVENT200* accessories can be used for inlet and
outlet terminals when the pipes do not exit the structure
together. For Canadian applications ONLY, IPEX 196006
may be used for horizontal and vertical terminations. IPEX
081216, IPEX 081218, and IPEX 081219 may only be used
for horizontal vent terminations.
For NONDIRECT VENT APPLICATION: The Furnace
shall be vented to the exterior of the house, but combustion
air may enter from the surrounding area as long as combustion air requirements are met. (See AIR FOR COMBUSTION AND VENTILATION)
FURNACE VENT / INLET PIPE INST ALLATION
There are many different variations of the vent / inlet air pipe
combination. The vent / inlet air combination used for
installation of these Furnaces depends on the needs of the
location. However, these guidelines must be followed:
1. The Furnace must vent outside the structure.
2. Furnace combustion air requirements must be met for
non-direct, single pipe applications.
3. For direct vent application of these Furnaces, the vent
pipe and air inlet pipe do not have to exit in the same air
space or even on the same surface of the structure.
However, the longest individual pipe will decide the value
for the longest allowable equivalent vent/ inlet air length as
shown in the vent length table on page 19.
Air
Inlet
See Note)
Furnace
Example 2
EX. 3 —
Example 3 shows the vent exiting one side of the house while
the inlet air is on the opposite side of the structure. Here the
vent pipe length must be within the allowable length for the
size of Furnace and size of the vent pipe. This example
demonstrates that the pipes do not have to exit on the same
side of the structure.
NOTE: Vent termination kit BA YAIR30AVENTA or
BAYVENT200B may be used in addition to the horizontal and
vertical termination options shown in the following examples. For Canadian applications ONLY, IPEX 196006 may
be used for horizontal and vertical terminations. IPEX
081216, IPEX 081218, and IPEX 081219 may only be used
for horizontal vent terminations.
The following are EXAMPLES ONLY:
EX. 1 —
Example 1 shows that the vent may go vertical while the inlet
air may be on any side of the structure. The vent pipe would
decide the maximum equivalent length for the pipe depending
on the furnace and pipe size.
Example 1
ir
nlet
Furnace
Example 3
EX. 4 —
The inlet air does not have to come from outside the structure.
Example 4 shows the inlet air, may come from the attic if the
requirements for combustion air are met as shown in the
section AIR FOR COMBUSTION AND VENTILATION.
NOTE: If only the flue gas pipe is to the outside of the
structure, a straight section of pipe (long enough to exit the
Furnace cabinet) must be attached to the inlet air side with
an elbow (which is 5 to 10 equiv. ft.) installed on the end to
prevent dust and debris from falling directly into the Furnace.
Vent
Ve
V
e
ir
EX. 2 —
Example 2 shows the vent pipe exhausting through the roof
and the inlet air coming from the interior of the house. The
inlet air coming from the interior of the house must meet
combustion requirements for area, etc., as shown in the
section AIR FOR COMBUSTION AND VENTILATION in
this Installer’s Guide.
1618-CD26D1-10
nlet
Furnace
Air
Inlet
(See Note)
Furnace
Example 4
Page 17
Installer’s Guide
E
nt
S
VENT FITTING MATERIAL – PLASTIC
Gas and liquid tight single wall vent fittings, designed for
resistance to corrosive flue condensate, MUST be used
throughout.
Listed in Table 9, page 18, are designations for different
types of 2" and 3" size pipe and fittings that meet these
requirements. The materials listed are various grades of
PVC, CPVC, and ABS plastic.
PIPE JOINTS: All joints must be fastened and sealed to
prevent escape of combustion products into the building.
NOTE: It is recommended that the first joints from the
Furnace be connected and sealed with high temperature
RTV. This will enable the pipes to be removed later without
cutting.
Be sure to properly support these joints.
BONDING OF PVC
Commercially available solvent cement for PVC must be
used to join PVC pipe fittings. Follow instructions on
container carefully.
Pipe and Fitting – ASTM D1785, D2466, D2661, & D2665
PVC Primer and Solvent Cement – ASTM D2564
Procedure for Cementing Joints – Ref ASTM D2855
1. Cut pipe square, remove ragged edges and burrs. Chamfer end of pipe, then clean fitting socket and pipe joint
area of all dirt, grease, moisture or chips.
2. After checking pipe and socket for proper fit, wipe socket
and pipe with cleaner-primer. Apply a liberal coat of
primer to inside surface of socket and outside of pipe.
DO NOT ALLOW PRIMER TO DRY BEFORE APPLYING CEMENT.
3. Apply a thin coat of cement evenly in the socket. Quickly
apply a heavy coat of cement to the pipe end and insert
pipe into fitting with a slight twisting movement until it
bottoms out.
4. Hold the pipe in the fitting for 30 seconds to prevent
tapered socket from pushing the pipe out of the fitting.
5. Wipe all excess cement from the joint with a rag. Allow
15 minutes before handling. Cure time varies according
to fit, temperature and humidity.
NOTE: Follow venting instructions carefully when using PVC
cement.
IMPORTANT: All joints must be water tight. Flue condensate
is somewhat acidic, and leaks can cause equipment
damage.
Connection of the pipe and collar of the combustion air inlet
should just be a friction fit. It is recommended that the inlet
air joint be sealed with RTV type sealant to allow the joint to
be separated for possible future service. The inlet and vent
pipes must be properly supported throughout the entire
length. See Figure 26.
NOTE: Vent termination kit BA YAIR30AVENTA or
BA YVENT200B may be used in addition to the horizontal
and vertical termination options shown in the following
figures. For Canadian applications ONLY, IPEX 196006 may
be used for horizontal and vertical terminations. IPEX
081216, IPEX 081218, and IPEX 081219 may only be used
for horizontal vent terminations.
VENT AND INLET AIR CONNECTIONS
Seal VENT PIP
with RTV seala
Front of Furnace
eal INLET AIR PIPE
with RTV sealant
Figure 26
Important: Products installed in Canada must use vent
systems that are certified to the Standard for Type BH Gas
Venting Systems (ULC S636) for Class II-A venting systems (up to 65°C). Components of the vent system must
not be interchanged with other vent systems or unlisted
pipe or fittings. Plastic components, specified primers, and
glues must be from a single system manufacturer and not
intermixed with other system manufacturer's vent system
parts. In addition, the first three feet of the vent pipe must
be visible for inspection.
18-CD26D1-1017
Page 18
Installer’s Guide
Table 9
PVC VENT FITTING MATERIAL These fittings are available from your Gas Furnace Distributors.
* - Allowable temperatures based on classifications covered in ASTM D4396 [Deflection Temps Under Load (264 PSI)]
** - Allowable temperatures based on classifications covered in ASTM D1784 [Deflection Temps Under Load (264 PSI)]
*** - Allowable temperatures based on classifications covered in ASTM D3965 [Deflection Temps Under Load (264 PSI)]
1818-CD26D1-10
Page 19
Installer’s Guide
0
Table 10
ALTITUDE
0-7,000 Feet2 INCH PIPE2.5 INCH PIPE3 INCH PIPE
*UH/DH2B060A9V3VA200200200
*UH/DH2B080A9V3VA
*UH/DH2B080A9V4VA
*UH/DH2C100A9V4VA
*UH2C100A9V5VA
50120200
Not Allowed60200
*UH/DH2D120A9V5VANot AllowedNot Allowed200
7,000-9,500 Feet2 INCH PIPE2.5 INCH PIPE3 INCH PIPE
*UH/DH2B060A9V3VA100100100
*UH/DH2B080A9V3VA
*UH/DH2B080A9V4VA
*UH/DH2C100A9V4VA
*UH2C100A9V5VA
2560100
Not Allowed30100
*UH/DH2D120A9V5VANot AllowedNot Allowed100
9,500-12,000 Feet2 INCH PIPE2.5 INCH PIPE3 INCH PIPE
*UH/DH2B060A9V3VA505050
*UH/DH2B080A9V3VA
*UH/DH2B080A9V4VA
*UH/DH2C100A9V4VA
*UH2C100A9V5VA
Not Allowed3050
Not AllowedNot Allowed50
*UH/DH2D120A9V5VANot AllowedNot Allowed50
NOTES: * - First letter may be "A" or "T"
1. Minimum vent length for all models: 3' horizontal or 3' vertical.
2. DO NOT MIX PIPE DIAMETERS IN THE SAME LENGTH OF PIPE OUTSIDE THE FURNACE CABINET (Except
adapters at the top of the furnace). If different inlet and vent pipe sizes are used, the vent pipe must adhere to the
maximum length limit shown in the table above (See note 6 below for exception). The inlet pipe can be of a larger diameter,
but never smaller than the vent pipe.
3. MAXIMUM PIPE LENGTHS MUST NOT BE EXCEEDED! THE LENGTH SHOWN IS NOT A COMBINED TOTAL, IT IS
THE MAXIMUM LENGTH OF EACH (Vent or Inlet air pipes).
4. One SHORT radius 90° elbow is equivalent to 10' of 3" pipe and one LONG radius elbow is equivalent to 6' of 3" pipe.
One 90° elbow is equivalent to 7½' of 2½" pipe or 5' of 2" pipe. Two 45° elbows equal one 90°elbow.
5. The termination tee or bend must be included in the total number of elbows. If the BAYAIR30AVENTA termination kit is
used, the equivalent length of pipe is 5 feet. BAYVENT200B equivalent length is 0 feet.
6. Pipe adapters are field supplied (except for the *UH/DH2D120 models).
7. For Canadian applications ONLY, IPEX 196006 may be used for horizontal and vertical ter minations. IPEX 081216, IPEX
081218, and IPEX 081219 may only be used for horizontal vent terminations. Equivalent lengths are IPEX 196009 = 5
feet, IPEX 081216 = 11 feet, IPEX 081218 = 16 feet, and IPEX 081219 = 21 feet
If the desired input rate cannot be achieved with a change in
manifold pressure, then the orifices must be changed. LP
installations will require an orifice change.
Important: Reinstall the propane orifices to the same depth as
the orifices supplied with the equipment.
See Table 11 for help in selecting orifices if orifice change is
required. Furnace input rate and temperature rise should be
checked again after changing orifices to confirm the proper
rate for the altitude. For information on high altitude derating, refer to page 34.
VENT LENGTH TABLE
MAXIMUM TOTAL EQUIVALENT LENGTH IN FEET
FOR VENT AND INLET AIR (SEE NOTES)
The Vent Length Table (Table 10) above shows the required
vent lengths for installations at various altitudes. An
optional high altitude kit is available for installations above
5000 feet (Installations above 12,000 feet are not allowed).
Table 12
Orifice
Tw ist D r ill
Size If
Installed
At Sea
Level
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
2000 3000 4000 5000 6000 7000 8000 9000 1000
42
44
45
46
47
48
49
50
51
51
52
54
54
55
56
58
59
From National Fuel Gas Code - Table F-4
ALTITUDE ABOVE SEA LEVEL
and Orifice Required At Other Elevations
43
43
43
44
44
44
45
47
47
48
49
50
51
52
53
54
55
55
56
59
60
44
45
47
47
49
49
50
51
52
53
54
55
55
57
59
60
45
46
47
48
49
50
51
51
52
53
54
55
56
57
60
61
45
47
48
48
49
50
51
52
52
53
54
55
56
57
60
62
46
47
48
49
50
50
51
52
53
53
54
55
56
58
61
62
45
47
48
49
49
50
51
52
52
53
54
55
56
56
59
62
63
46
47
48
49
50
51
51
52
53
53
54
55
56
56
59
63
63
47
48
50
50
51
52
52
52
53
54
54
55
56
57
60
63
64
18-CD26D1-1019
Page 20
Installer’s Guide
▲
HORIZONTAL VENTING
(Upflow/ Horizontal)
!
CAUTION
When the vent pipe is exposed to temperatures below
freezing, e.g., when it passes through unheated spaces, etc.,
the pipe must be insulated with 1/2 inch (22.7 mm) thick
Armaflex-type insulation or equal.
If the space is heated sufficiently to prevent freezing, then
the insulation will not be required. If domestic water pipes
are not protected from freezing then the space meets the
condition of a heated space.
Figure 27
NOTE: If your furnace comes with a factory supplied 2" X 3"
offset reducing coupling is used for 3" vent pipe installation,
make sure the marking “TOP” is located on the top side of
the pipe.
The straight side of the coupling must be on bottom for
proper drainage of condensate. See Figure 27.
Horizontal Venting
NOTE:
Vent termination kit BAYAIR30AVENTA or BAYVENT200B
may be used in addition to the horizontal and vertical
termination options shown in the following figures.
For
Canadian applications ONLY: IPEX 196006 may be
used for horizontal and vertical terminations. IPEX
081216, IPEX 081218, and IPEX 081219 may only be
used for horizontal vent terminations.
9" MINIMUM
9" MINIMUM
Figure 28
FURNACE
VENT
OUTLET
9" MINIMUM
2" TO 3" COUPLING
#CPL00938
FACTORY SUPPLIED ONLY
WITH THE FOLLOWING
MODELS:
ALL 100,000 BTUH UPFLOW
MODELS, ALL 120,000 BTUH
UPFLOW MODELS, THE
UX1C080A9601 MODEL, AND
ALL DOWNFLOW MODELS
9" MINIMUM
POSSIBLE CONFIGURA TIONS FOR TWO PIPE VENTING SYSTEMS
2018-CD26D1-10
ELBOW AND TEE MUST
BE AS CLOSE TOGETHER
AS POSSIBLE
9" MINIMUM
Figure 30
Page 21
7.2"
P
▲
3.2"
COMBUSTION
AIR
ANCHORS
(4 req.)
VENT
VENT
PLATE
12" MINIMUM
TO OVERHANG
SCREWS
(4 req.)
Installer’s Guide
!
CAUTION
The vent for this appliance shall not terminate
(1) Over public walways; or
(2) Near sofit vents or crawl space vents or other areas
where condensate or vapor could create a nuisance or
hazard or cause property damage; or
(3) Where condensate vapor could cause damage or could be
detrimental to the operation of regulators, relief valves.
or other equipment.
VENT
VENT
CAP
MAINTAIN 12" (18" FOR CANADA) MINIMUM
CLEARANCE ABOVE HIGHEST ANTICIPATED
SNOW LEVEL OR GRADE WHICHEVER IS GREATER
Figure 32. BA YVENT200B
For Canadian applications only, IPEX 196006, IPEX 081216, IPEX
081218, and IPEX 081219 may be used for horizontal vent terminations.
BA YAIR30A VENTA
(Sidewall)
STRAP
(FIELD SUPPLIED)
VENT
COMBUSTION AIR
For Canadian applications only, IPEX 196006, IPEX 081216, IPEX 081218,
and IPEX 081219 may be used for horizontal vent terminations.
ELBOW
(FIELD
SUPPLIED)
Figure 33
COMBUSTION
AIR
RAIN CA
VENT
1" + 1/2"
HORIZONT AL VENTING THROUGH WALL
These Furnaces may be installed as direct vent (as
shipped) or as nondirect vent. Installation must conform to national, state, and local codes.
The vent & inlet terminals must be located at least 12"
minimum (18" minimum in Canadian applications) above
normally expected snow accumulation level.
Avoid areas where staining or condensate drippage may be a
problem.
Location of the vent/wind terminal should be chosen to meet
the requirements of Figure 42 for either direct or non-direct
vent applications.
PITCH — Venting through the wall must maintain 1/4" per
foot pitched upward to insure that condensate drains back to
the Furnace.
FLUE GAS DEGRADATION — The moisture content of the
flue gas may have a detrimental effect on some building
materials. This can be avoided by using the roof or chimney
venting option. When wall venting is used on any surface that
can be affected by this moisture, it is recommended that a
corrosion resistant shield (24 inches square) be used behind
the vent terminal. This shield can be wood, plastic, sheet
metal, etc. Also, silicone caulk all cracks, seams and joints
within 3 feet of the vent terminal.
Important: The Commonwealth of Massachusetts
requires compliance with regulation 248 CMR 4.00 and
5.00 for installation of through – the – wall vented gas
appliances as follows:
For all side wall horizontally vented gas fueled
equipment installed in every dwelling, building or
structure used in whole or in part for residential
purposes, including those owned or operated by the
Commonwealth and where the side wall exhaust vent
termination is less than seven (7) feet above finished
grade in the area of the venting, including but not limited
to decks and porches, the following requirements shall be
satisfied:
1. INSTALLATION OF CARBON MONOXIDE
DETECTORS. At the time of installation of the
side wall horizontal vented gas fueled
equipment, the installing plumber or gasfitter
shall observe that a hard wired carbon monoxide
detector with an alarm and battery back-up is
installed on the floor level where the gas
equipment is to be installed. In addition, the
installing plumber or gasfitter shall observe that
a battery operated or hard wired carbon
monoxide detector with an alarm is installed on
each additional level of the dwelling, building or
structure served by the side wall horizontal
vented gas fueled equipment. It shall be the
responsibility of the property owner to secure the
services of qualified licensed professionals for
the installation of hard wired carbon monoxide
detectors
a. In the event that the side wall
horizontally vented gas fueled
equipment is installed in a crawl space
or an attic, the hard wired carbon
monoxide detector with alarm and
battery back-up may be installed on the
next adjacent floor level.
b. In the event that the requirements of
this subdivision can not be met at the
time of completion of installation, the
owner shall have a period of thirty (30)
days to comply with the above
requirements; provided, however, that
during said thirty (30) day period, a
battery operated carbon monoxide
detector with an alarm shall be
installed.
2. APPROVED CARBON MONOXIDE
DETECTORS. Each carbon monoxide detector as
required in accordance with the above provisions
shall comply with NFPA 720 and be ANSI/UL
2034 listed and IAS certified.
18-CD26D1-1021
Page 22
VENT TABLES
T
Installer’s Guide
3. SIGNAGE. A metal or plastic identification
plate shall be permanently mounted to the
exterior of the building at a minimum height of
eight (8) feet above grade directly in line with the
exhaust vent terminal for the horizontally vented
gas fueled heating appliance or equipment. The
sign shall read, in print size no less than one-half
(1/2) inch in size, “GAS VENT DIRECTLY
BELOW. KEEP CLEAR OF ALL
OBSTRUCTIONS”.
4. INSPECTION. The state or local gas inspector
of the side wall horizontally vented gas fueled
equipment shall not approve the installation
unless, upon inspection, the inspector observes
carbon monoxide detectors and signage installed
in accordance with the provisions of 248 CMR
5.08(2)(a)1 through 4.
This appliance requires a special venting system. If
BAYAIR30AVENTA or BAYVENT200B are used, a
copy of the installation instructions for the kit shall
remain with the appliance or equipment at the
completion of installation. The venting system
installation instructions can be obtained from the
manufacturer by writing to the following address:
Trane
6200 Troup Highway
Tyler, TX 75707
Attention: Manager of Field Operations Excellence
COMBUSTIBLE MA TERIAL WALL
A minimum clearance of 1" to combustible materials must be
maintained when using single wall stainless steel venting.
Shield material to be a minimum of 24 gauge stainless or
aluminized sheet metal. Minimum dimensions are 12"x12".
Shield must be fastened to both inside and outside of wall.
Use screws or anchor type fasteners suited to the outside or
inside wall surfaces.
NONCOMBUSTIBLE MA TERIAL WALL
The hole through the wall must be large enough to maintain
pitch of vent and properly seal.
Use cement mortar seal on inside and outside of wall. See
Figure 35.
COUPLING
(PLASTIC
VENTING)
6 IN. MIN.
(TO JOINT)
1” CLEARANCE
(AIR SPACE)
VENTING THROUGH COMBUSTIBLE WALLS
Pitch - 1/4 Inch Per Foot
CLEARANCE (0” ACCEPTABLE FOR PVC VENT PIPE)
(1” ACCEPTABLE FOR TYPE 29-4C STAINLESS STEEL VEN
SUPPORT HORIZONTAL PIPE EVERY 3' 0"
WITH THE FIRST SUPPORT AS CLOSE TO
THE FURNACE AS POSSIBLE. INDUCED
DRAFT BLOWER, HOUSING, AND
FURNACE MUST NOT SUPPORT THE
WEIGHT OF THE FLUE PIPE.
Installer’s Guide
Figure 36
REMOVE RIBS
FROM CAP
COMBUSTION
AIR
OOF FLASHING BOOT
FIELD SUPPLIED)
VENT
SUPPORT
(FIELD SUPPLIED)
12 INCHES MIN. CLEARANCE MUST BE
MAINTAINED ABOVE HIGHEST
ANTICIPATED SNOW LEVEL.
MAXIMUM NOT TO EXCEED
24 INCHES ABOVE ROOF.
AINTAIN 12 IN.
18 IN. FOR CANADA)
INIMUM CLEARANCE
BOVE HIGHEST
NTICIPATED SNOW
LEVEL. MAXIMUM OF
4 IN. ABOVE ROOF.
Figure 37 BAYAIR30AVENTA (VERTICAL)
For Canadian applications only, IPEX 196006
may be used for vertical vent terminations.
SEAL BETWEEN FLANGE, PIPE,
COUPLING AND METAL PANEL
(18 IN. FOR CANADA)
MINIMUM CLEARANCE
ABOVE HIGHEST
ANTICIPATED SNOW
LEVEL. MAXIMUM OF
24 IN. ABOVE ROOF
WITH HI TEMP RTV SILICONE SEALANT
SUPPORT
FLANGE
VENT
COMBUSTION
AIR
FLUE PIPE
COUPLING
VENT
Figure 38. BAYAIR30AVENTA (VERTICAL)
For Canadian applications only, IPEX 196006 may be used
for vertical vent terminations.
18-CD26D1-1023
ELBOW
(FIELD SUPPLIED
COMBUSTION
AIR
GALVANIZED FIRESTOP SHOULD
BE FABRICATED WITH 3-7/8" DIA.
HOLE FOR SUPPORT FLANGE
(12" x 12" PANEL OR 12" DIA MIN.)
CLEARANCE ( 0" ACCEPTABLE FOR PVC VENT PIPE )
( 1" ACCEPTABLE FOR TYPE 29-4C STAINLESS STEEL VENT PIPE )
CEILING
VENTING THROUGH CEILING
Figure 39
Page 24
Installer’s Guide
H
C
P
O
S
S
▲
▲
CAUTION
!
VENTING THROUGH THE ROOF
When penetrating roof with a 2" PVC vent pipe, a 2" electrical
conduit flashing may be used for a weather tight seal.
Lubricate flexible seal on flashing before PVC pipe is pushed
through the seal. (Field Supplied)
NOTE: No vent cap as shown in Figure 37 is the preferred
method for vertical vent termination in extremely cold
climates.
In extreme climate conditions, insulate the exposed pipe
above the roof line with Armaflex type insulation.
VENT FITTING MATERIAL – STAINLESS STEEL
Gas and liquid tight single wall metal vent fitting, designed
for resistance to corrosive flue condensate such as Type 29-4C
MUST be used throughout.
These fittings and fitting accessories are to be field supplied.
DIRECTION OF STAINLESS STEEL FITTING
All stainless steel fitting must be installed with male end
towards the Furnace.
All horizontal stainless steel sections must be positioned
with the seam on top.
All long horizontal sections must be supported to prevent
sagging.
All pipe joints must be fastened and sealed to prevent escape
of combustion products into the building.
PVC PLASTIC VENTING - ONLY
THROUGH UNUSED CHIMNEY
STAINLESS STEEL VENT CAP
FLUE PIPE
OUPLING TO SUPPORT
IPE FROM ANGLES
R OTHER SUITABLE
UPPORT METHOD
STAINLESSSTEEL
(OPTIONAL)
VENT CAP
SEE CAUTION
FLUE PIPE
6 IN. MIN.
SUPPORT THE SINGLE
WALL FLUE PIPE AND
CENTER IT IN THE
CHIMNEY OPENING WIT
ANGLES AS SHOWN OR
ANOTHER EQUIVALENT
MANNER.
COUPLING
AS REQUIRED
Figure 40
TYPE 29-4C ST AINLESS STEEL VENTING - USED
THROUGH CHIMNEY THA T VENTS ANOTHER GAS
APPLIANCE
STAINLESS
STAINLESS STEEL VENT CAP
STEELVENT CAP
(OPTIONAL)
EE CAUTION
6 IN. MIN.
SUPPORT THE SINGLE WALL
STAINLESS STEEL GAS
VENTING AND CENTER IT IN
THE CHIMNEY OPENING WITH
ANGLES AS SHOWN OR
ANOTHER EQUIVALENT
MANNER.
NOTE:
HORIZONTAL VENTING
TO VERTICAL VENTING
!
Do NOT run vent through chimney for wood burning or
oil Furnaces or incinerators or any other gas appliance.
CAUTION
NOTE:
HORIZONTAL VENTING
TO VERTICAL VENTING
IMPORTANT –
The single wall flue pipe joints must be sealed.
The 90° elbow connection to vertical pipe must be sealed to
prevent condensate leakage to base of masonry chimney.
Figure 41. VENTING ROUTED THROUGH A MASONRY CHIMNEY
2418-CD26D1-10
Do NOT run vent through chimney for wood burning or oil
Furnaces or incinerators.
If remaining free area between single wall flue pipe and
masonry chimney is to be used for another gas appliance
venting area must be sufficient to vent that appliance and
that appliance must be connected to chimney with
separate entry openings.
IMPORTANT –
The single wall flue pipe joints must be sealed.
The 90° elbow connection to vertical pipe must be sealed to
prevent condensate leakage to base of masonry chimney.
Vertical clearance to ventilated soffit located above
D=
the terminal within a hor izontal dist ance of 2 feet
(61 cm) from the center line of the ter mi nal
E=Clearance to unventilated soffit**
F=Clearance to outside corner**
G=Clearance to inside corner**
Clearance to each side of center line extended
H=
above meter/regulator assembly
I=Clearance to service regulator vent outlet3 feet (91 cm)*
Clearance to nonmechanical air supply inlet t o
J=
building or the combustion air inlet to any other
appliance
K=Clearance to a mechanical air su pply in let6 feet (1.83m)
Clearance above a paved sidewalk or paved
L=
driveway located on public property
M=Clearance under veranda, porch, deck, or balcony12 inches (30 cm) ‡*
Notes:
1. In accordance with the current CSA B149.1 Natural Gas and Propan e Instal lation C ode.
2. In accordance with the current ANSI Z223.1/NFPA 54 National Fuel Gas Code.
†. A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwelling and serves both dwellings.
‡. Pemitted only if veranda, porch, deck, or balcony is fu lly open on a minimum of t wo sides beneat h the floor.
* Clearance in accordance with local installation codes and t he requirements of the gas supplier an d the manufacturer's Installat ion Ins truc tions.
and =/< 100,000 Btuh (30 kw),
36 inches (91 cm) for appliances > 100,000 Btuh (30 kw)
12 inches (30 cm)12 inches (30 cm)
4 feet (1.2m) below or to the side of opening;
1 foot (0.3m) above opening.
**
meter/regulator assembly
4 feet (1.2 m) below or to side of opening;
1 foot (300 m) above opening
3 feet (91 cm) above if within
10 feet (3m) horizontally
7 feet (2.13 m) †7 feet (2.13 m)
*
X
V
K
18-CD26D1-1025
Page 26
Installer’s Guide
S
▲
Table 14
Direct Vent Terminal Clearances
Canadian InstallationsUS Installations
Clearance above grade, veranda, porch,
A=
deck, or balcony
Clearance to window or door that may be
B=
opened
C=Clearance to permanently closed window**
Vertical clearance to ventilated soffit
located above the terminal within a
D=
horizontal dist anc e of 2 feet (61 cm)
from the center line of the terminal
E=Clearance to unventilated soffit**
F=Clearance to outside corner**
G=Clearance to inside corner**
Clearance to each side of center line
H=
extended above meter/regulator assembly
I=Clearance to service regulator vent outlet3 feet (91 cm)*
Clearance to nonmechanical air supply
J=
inlet to building or the combustion air
inlet to any other appliance
K=Clearance to a mechanical air supply inlet6 feet (1.83m)3 feet (91 cm) above if within 10 feet (3m) horizontally
Clearance above a paved sidewalk or
L=
paved driveway located on public property
Clearance under veranda, porch, deck,
M=
or balcony
Notes:
1. In accordance with the current CSA B149.1 Natural Gas and Propane Installation Code.
2. In accordance with the current ANSI Z223.1/NFPA 54 National Fuel Gas Code.
†. A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwelling and serves both dwellings.
‡. Pemitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.
* Clearance in accordance with local installation codes and the requirements of the gas supplier and the manufacturer's Installation Instructions.
6 inches (15 cm) for appliances =/< 10,000 Btuh (3 kw),
12 inches (30 cm) for appliances > 10,000 Btuh (3 kw)
and =/< 100,000 Btuh (30 kw),
36 inches (91 cm) for appliances > 100,000 Btuh (30 kw)
3 feet (91 cm) with a height 15 feet (4.5 m) above the
6 inches (15 cm) for appliances =/< 10,000 Btuh (3 kw),
12 inches (30 cm) for appliances > 10,000 Btuh (3 kw)
and =/< 100,000 Btuh (30 kw),
36 inches (91 cm) for appliances > 100,000 Btuh (30 kw)
12 inches (30 cm)12 inches (30 cm)
6 inches (15 cm) for appliances =/< 10,000 Btuh (3 kw),
9 inches (23 cm) for appliances > 10,000 Btuh (3 kw)
and =/< 50,000 Btuh (15 kw),
12 inches (30 cm) for appliances > 50,000 Btuh (15 kw)
**
meter/regulator assembly
6 inches (15 cm) for appliances =/< 10,000 Btuh (3 kw),
9 inches (23 cm) for appliances > 10,000 Btuh (3 kw)
and =/< 50,000 Btuh (15 kw),
12 inches (30 cm) for appliances > 50,000 Btuh (15 kw)
7 feet (2.13 m) †*
12 inches (30 cm) ‡*
*
DOWNWARD VENTING
Furnace may be in vertical or horizontal configuration.
All horizontal pipes must be
supported at maximum of 3
foot intervals
Slope 1/4" per ft.
lope 1/4" per ft.
NOTES:
A) Condensate trap for vent pipe must be a minimum of 6 inches in height.
B) Condensate trap for vent and inlet pipe must be connected into a condensate drain pump; an open or
vented drain; or it can be connected to the outlet hose of the Furnace condensate trap. Outdoor draining
of the Furnace and coil condensate is permissible if allowed by local codes.
!
CAUTION
Caution should be taken to prevent drains from freezing or causing slippery conditions that could lead to
personal injury. Excessive draining of condensate may cause saturated ground conditions that may result
in damage to plants.
C) The condensate trap should be primed at initial start up prior to heating season operation.
Figure 43
DOWNWARD VENT LENGTH IS
LIMITED TO A MAXIMUM OF
EQUIVALENT FEET.
40 Inch
Upflow or
Downflow
Furnace
6" Min.
15
2618-CD26D1-10
Page 27
CONDENSATE DRAIN INSTRUCTIONS
▲
Knock outs are provided on the left and right hand side of
both furnace cabinets for drain connections IN VERTICALA PPLICA TIONS . The standard arrangement is for the drain
connection on the left side. The tubing may have to be
trimmed in this application to avoid kinking.
The upflow (vertical application) has provisions for right
side drain connections by turning the trap and extending the
tubing to the lower right front corner of the Furnace. Trim all
excess tubing to avoid kinking. The connecting tubing for left
or right side condensate drain shown in Figure 44 is shipped
in the blower compartment.
It is always recommended that an auxiliary drain pan be
installed under a horizontally installed evaporator or 90%
Gas Furnace. Connect the auxiliary drain line to a separate
drain line (no trap is needed in this line).
All horizontal applications are left side only and
require repositioning the condensate canister trap to
the exterior of the cabinet. Additionally the drain
tubing connected to the inducer housing must be repositioned for removing the plug and reconnecting the
tubing to the lower connection on the inducer housing.
See Figure 45.
For horizontal installation, remove the condensate trap and
position the trap outside the cabinet through the slotted
opening next to the secondary cell. On upflow/ horizontal
models, remove lines from the blower section and pull
through the blower deck. Cut and reattach the line from the
secondary cell (use the spring to prevent kinking).
Installer’s Guide
The inducer housing has a secondary drain opening at its
9 o’clock position. Remove the plug and use the plug to cover
the hole at the 6 o’clock position. Reposition the Inducer drain
tube from 6 o’clock to the 9 o’clock location. Cut and reattach
the tube to the canister trap. Plug openings in Blower deck,
Inducer and Blower section. See Figure 45.
Connections must be made to an OPEN/ VENTED DRAIN.
NOTE: All condensate drain piping supplies included with
the furnace are intended for internal piping only and
should not be applied external to the furnace. All external
piping should use 1/2" size PVC pipe and fittings throughout for drain connections (fittings, pipe and PVC solvent
cement not provided with furnace, must be field supplied).
NOTE: A corrosion resistant condensate pump must be
used if a pump is required for a specific drain system.
!
CAUTION
▲
It is recommended that a drain pan be installed under the
furnace to prevent property damage or personal injury
from leaking condensate.
THE UPFLOW (VERTICAL) MA Y BE INSTALLED
LEFT OR RIGHT SIDE CONDENSA TE DRAIN
UPFLOW FURNACE
(Vertical)
HEADER
HEADER
TO DRAIN
LEFT SIDE
18-CD26D1-1027
TO DRAIN
RIGHT SIDE
Figure 44
Page 28
Installer’s Guide
I
o
f
s
d
t
ALL HORIZONT AL APPLICATIONS
ARE LEFT SIDE DRAIN ONLY
UPFLOW FURNACE ON LEFT SIDE
WITH LEFT DRAIN SHOWN
Figure 45
HEADER
TO
OPEN/
VENTED
DRAIN
f upflow furnace is installed
ver a finished ceiling, overflow
rom the primary drain vent
tack must flow into an auxillary
rain pan to prevent damage to
he finished ceiling below.
IMPORTANT: The condensate drain should be installed with
provisions to prevent winter freeze-up of the condensate
drain line. Frozen condensate will block drains, resulting in
furnace shutdown. If the drain line cannot be installed in a
conditioned space and/ or its surrounding ambient temperature is expected to fall below freezing, then heat tape should
be applied as required to prevent freezing (per
manufacturer’s instructions). The heat tape should be rated
at 5 or 6 watts per foot at 120 volts. Self-regulating (preferred) or thermostatically controlled heat tape is required.
Typical sources of UL listed heat tapes are W.W. Granger, Inc.
(Wintergard Plus
TM
Series), McMaster Carr Supply Co.
(3554 Series), or your equipment supplier.
The condensate drain may be cleaned or inspected by re-
Evaporator and Furnace condensate drain piping may be
manifolded together as shown in Figure 46. A primary drain
vent stack must be installed and terminated below the
outlet of the secondary heat exchanger drain connection to
prevent water from damaging Furnace controls if the primary
drain outlet plugs up.
Where the Furnace is installed above a finished ceiling,
the primary drain vent stack must be installed such
that overflow from the vent stack opening will flow into
an auxiliary drain pan in order to prevent water damage to the finished ceiling below.
2818-CD26D1-10
Page 29
Installer’s Guide
VERTICAL APPLICATIONS
Upflow furnace - The connection tubing for left and right
side drainage is shipped in the blower compartment. Install
the connection tubing from the trap to the side of the unit and
trim all excess tubing to avoid kinks.
Downflow furnace - The furnace is shipped with the left
side drainage setup. To change the right side drain, remove
the drain lines from the trap, rotate the trap 180° so it exits
to the right, reconnect the lines, and run a 1/2" CPVC pipe
from the trap out through the right side knock-out. Use RTV
silicone sealant to connect the CPVC pipe to the trap for ease
of removing to clean the trap.
HORIZONTAL APPLICATIONS
Upflow and Downflow furnaces - All horizontal applications are left side only. It is always recommended that the
auxiliary drain pan be installed under a horizontally installed evaporator and/or 90% gas furnace. Connect the
auxiliary drain pan to a separate drain line (no trap is needed
in this line).
The trap must be repositioned to the exterior of the cabinet.
Remove the trap from its present location and reposition the
trap outside of the unit, through the long circular hole, next to
Right side
Figure 47. UPFLOW (VERTICAL)
Use Inducer Drain
hose without
extension
Figure 48. UPFLOW HORIZONT AL 17" UNITS
(Left side only)
Left side
Figure 49. UPFLOW (VERTICAL)
Use
extension
hose here
Figure 50. UPFLOW HORIZONT AL 21" & 24" UNITS
(Left side only)
18-CD26D1-1029
Page 30
Installer’s Guide
the secondary recuperative cell. Remove the larger drain line
(from the secondary cell) and trim to fit between the secondary cell and the new trap location. On upflow units, plug the
hole in the blower deck where the tube went through.
Remove the hose from the induced blower and reposition into
the other drain tap of the inducer, which is located 90°
clockwise around the inducer. Move the cap from that drain
tap to the unused drain tap. On upflow units, plug the hole in
the blower deck where the tube went through. This tube on
downflow units will need to be cut to fit between the inducer
and the trap. On upflow units, this tube may need to be
extended, using the tubing shipped with the furnace.
Connections must be made to an OPEN/VENTED DRAIN.
Outdoor draining of the furnace and coil condensate is
permissible if allowed by local codes. Caution should be taken
Cut off curved end of
Inducer drain hose
Figure 53. DOWNFLOW (HORIZONT AL)
to prevent drains from freezing or causing slippery conditions
that could lead to personal injury. Excessive draining of
condensate may cause saturated ground conditions that may
result in damage to plants.
Left
side
Figure 51. DOWNFLOW (VERTICAL)
NOTE: Use 1/2" or larger PVC or CPVC pipe and fittings as
required for drain connections (fittings, pipe and solvent
cement not provided).
NOTE: A corrosion resistant condensate pump must be
used if a pump is required for a specific drain system.
IMPORTANT: The condensate drain should be installed with
provisions to prevent winter freeze-up of the condensate drain
line. Frozen condensate will block drains, resulting in furnace
shutdown. If the drain line cannot be installed in a conditioned
space, then UL listed heat tape should be applied as required
to prevent freezing (per manufacturer’s instructions). The heat
tape should be rated at 5 or 6 watts per foot at 120 volts. Selfregulating (preferred) or thermostatically controlled heat tape is
required.
Use CPVC tubing from Trap outlet,
over burner box to cabinet exit
Figure 52. DOWNFLOW (VERTICAL)
3018-CD26D1-10
Right
side
Page 31
Installer’s Guide
▲
MAIN MANUAL
SHUT-OFF VALVE
GROUND
UNION
JOINT
DRIP
LEG
AUTOMA TIC GAS VALVE
WITH MANUAL SHUT-OFF
AUTOMA TIC GAS VALVE
WITH MANUAL SHUT-OFF
Figure 54. UPFLOW MA Y BE LEFT OR RIGHT HAND GAS PIPING
AUTOMA TIC
GAS V ALVE
WITH MANUAL
SHUT-OFF
MAIN MANUAL
SHUT-OFF VALVE
GROUND
UNION
JOINT
DRIP
LEG
AUTOMATIC
GAS VALVE
WITH MANUAL
SHUT-OFF
Figure 55. THE DOWNFLOW (VERTICAL) MA Y BE INSTALLED LEFT OR RIGHT SIDE GAS PIPING
AUTOMA TIC GAS VALVE
WITH MANUAL SHUT-OFF
MAIN MANUAL
SHUT-OFF VALVE
GROUND
UNION JOINT
DRIP
LEG
Figure 56. HORIZONT AL FURNACE GAS PIPING MAY BE FROM EITHER SIDE
(Typical UPFLOW Furnace in horizontal configuration shown)
!
CAUTION
Use a backup wrench on the gas valve when installing gas
piping to prevent damage to the gas valve and manifold
assembly.
MAIN MANUAL
SHUT-OFF
VALVE
AUTOMA TIC GAS VALVE
WITH MANUAL SHUT-OFF
GROUND UNION JOINT
DRIP
LEG
18-CD26D1-1031
Page 32
Installer’s Guide
▲
H
N
E
S
T
K
T
S
I
▲
▲
Gas Piping
!
WARNING
▲
AZARD OF EXPLOSION!
EVER USE AN OPEN FLAME TO DETECT GAS LEAKS.
XPLOSIVE CONDITIONS MAY OCCUR. USE A LEAK TEST
OLUTION OR OTHER APPROVED METHODS FOR LEAK
ESTING. FAILURE TO FOLLOW RECOMMENDED SAFE LEA
EST PROCEDURES COULD RESULT IN DEATH OR SERIOU
NJURY OR EQUIPMENT OR PROPERTY-ONLY-DAMAGE.
!
WARNING
HAZARD OF EXPLOSION
REPLACE AND/ OR TIGHTEN ALL PLUGS REMOVED OR
LOOSENED WHEN ADJUSTING GAS PRESSURE. LEAK
CHECK THE FITTINGS BEFORE PLACING THE FURNACE
INTO REGULAR SERVICE.
FAILURE TO FOLLOW THIS WARNING COULD RESULT IN
FIRE, EXPLOSION, PROPERTY DAMAGE, OR DEA TH.
!
WARNING
HAZARD OF EXPLOSION
DO NOT USE SEMI-RIGID MET ALLIC GAS CONNECTORS
(FLEXIBLE GAS LINES) WITHIN THE FURNACE CABINET.
FAILURE TO FOLLOW THIS WARNING COULD RESULT IN
PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
The upflow/horizontal furnace is shipped standard for left
side installation of gas piping. A knockout is provided on the
right side for an alternate gas piping arrangement. See Figure
54.
The installation of piping shall be in accordance with piping
codes and the regulations of the local gas company. Pipe joint
compound must be resistant to the chemical reaction with
liquefied petroleum gases.
Refer to piping Table 15, for delivery sizes. Connect gas
supply to the unit, using a ground joint union and a manual
shut-off valve as shown in Figures 43 & 44. National codes
require a condensation drip leg to be installed ahead of the
controls as shown in Figures 55 & 56.
The furnace and its individual shut-off valve must be disconnected from the gas supply piping system during any pressure
testing of that system at test pressures in excess of 1/2 psig
(3.5 kPa).
The furnace must be isolated from the gas supply piping by
closing its individual manual shut-off valve during any
pressure testing of the gas supply piping system at test
pressures equal to or less than 1/2 psig (3.5 kPa).
NOTE: Maximum pressure to the gas valve for natural gas
is 13.8" W.C. Minimum pressure is 5.0" W.C. Maximum
pressure to the gas valve for propane is 13.8" W.C. Minimum pressure is 11.0" W.C.
Table 15
NATURAL GAS ONLY
TABLE OF CUBIC FEET PER HOUR OF GAS
FOR VARIOUS PIPE SIZES AND LENGTHS
PIPE
SIZE
1/2132927363565046
3/427819015213011510596
1-1/41050730590520440400370
This table is based on Pressure Drop of 0.3 inch W.C. and 0.6 SP.GR. Gas
3218-CD26D1-10
10203040506070
1520350285245215195180
LENGTH OF PIPE
All gas fittings must be checked for leaks using a soapy solution
before lighting the furnace. DO NOT CHECK WITH AN
OPEN FLAME!
Table 16
ORIFICE SIZES
INPUT
RATING
BTUH
60,000
80,000
100,000
120,000
NUMBER
OF
BURNERS
3
4
5
6
MAIN BURNER ORIFICE
DRILL SIZE
NAT. GASLP GAS
45
45
45
45
56
56
56
56
Combustion and Input Check
(See also High Altitude Derate, page 34)
1. Make sure all gas appliances are off except the furnace.
2. Clock the gas meter with the furnace operating (determine the dial rating of the meter) for one revolution.
3. Match the “Sec” column in the gas flow (in cfh) Table 13
with the time clocked.
4. Read the “Flow” column opposite the number of seconds
clocked.
5. Use the following factors
For 1 Cu. Ft. Dial Gas Flow CFH =
For 1/2 Cu Ft. Dial Gas Flow CFH =
For 5 Cu. Ft. Dial Gas Flow CFH =
6. Multiply the final figure by the heating value of the gas
obtained from the utility company and compare to the
nameplate rating. This must not exceed the nameplate
rating.
if necessary:
Chart Flow Reading ÷ 2
Chart Flow Reading ÷ 4
10X Chart Flow Reading ÷ 4
Gas Valve Adjustment
Changes can be made by adjusting the manifold pressure
(See Table 17), or changing orifices (orifice change may
not always be required). To adjust the manifold pressure:
1. Turn off all electrical power to the system.
2. Attach a manifold pressure gauge with flexible tubing to
the outlet pressure boss marked “OUT P” on WhiteRodgers gas valve model 36G or 36J. See Figure 57A for
White-Rodgers gas valve model 36J. See Figure 57B for
White-Rodgers gas valve model 36G.
3. Loosen (Do Not remove) the pressure tap test set screw
one turn with 3/32" hex wrench.
a. The pressure tap adjustment kit (KIT07611)
contains a 3/32" hex wrence, a 5/16" hose and a
connector and can be ordered through Global Parts.
4. Turn on system power and energize valve.
Page 33
Installer’s Guide
5. Adjust 1st stage gas heat by removing the low (LO)
adjustment regulator cover screw.
a. To increase outlet pressure, turn the regulator adjust
screw clockwise.
b. To decrease outlet pressure, turn the regulator adjust
screw counterclockwise.
c. Adjust regulator until pressure shown on manometer
matches the pressure specified in Table 17.
1. The input of no more than nameplate rating and no
less than 93% of the nameplate rating, unless the unit
is derated for high altitude.
d. Replace and tighten the regulator cover screw securely.
6 . Adjust 2nd stage gas heat by removing the high (HI)
adjustment regulator cover screw.
a. To increase outlet pressure, turn the regulator adjust
screw clockwise.
b. To decrease outlet pressure, turn the regulator adjust
screw counterclockwise.
c. Adjust regulator until pressure shown on manometer
matches the pressure specified in Table 17.
1. The input of no more than nameplate rating and no
less than 93% of the nameplate rating, unless the unit
is derated for high altitude.
d. Replace and tighten the regulator cover screw securely.
7. Cycle the valve several times to verify regulator setting.
a. Repeat steps 5-7 if needed.
8. Turn off all electrical power to the system.
9. Remove the manometer and flexible tubing and tighten
the pressure tap screw.
10. Using a leak detection solution or soap suds, check for
leaks at the pressure outlet boss and pressure tap test
screw.
11. Turn on system power and check operation of the unit.
2nd Stage (HI) Manifold
Pressure Adjustment
1st Stage (LO)
Gas Valve On / Off
Toggle Switch
Figure 57B. White-Rodgers 36G
Table 17
FINAL MANIFOLD PRESSURE SETTINGS (inches w.c.)
FUEL2nd Stage Ma x.1st Stage Max.
NATURAL GAS3.5" W.C.1.7" W.C.
LP GAS10.5" W.C.6.0" W.C.
ROT ATE THE FRONT
COVER AS SHOWN
INSERT THE TOP FLANGE
OF THE FRONT COVER
UNDER THE LIP INSIDE
THE BOX
Manifold Pressure
Adjustment
2nd Stage (HI) Manifold
Outlet
Pressure
Boss
Inlet Pressure
Boss
18-CD26D1-1033
Pressure Adjustment
Gas Valve On / Off
Toggle Switch
Figure 57A. White-Rodgers 36J
1st Stage (LO)
Manifold Pressure
Adjustment
ALL SIDE FLANGES MUST
BE OUTSIDE OF THE BOX
ROT ATE THE FRONT
COVER INWARD MAKING
SURE THAT ALL SIDE
FLANGES ARE OUTSIDE
OF THE BOX.
Figure 58
Page 34
Installer’s Guide
▲
Figure 59
!
WARNING
HAZARD OF EXPLOSION
REPLACE AND/ OR
TIGHTEN ALL PLUGS
REMOVED OR LOOSENED WHEN ADJUSTING GAS PRESSURE.
LEAK CHECK THE
FITTINGS BEFORE
PLACING THE FURNACE
INTO REGULAR SERVICE.
FAILURE TO FOLLOW
THIS WARNING COULD
RESULT IN FIRE, EXPLOSION, PROPERTY
DAMAGE, OR DEATH.
NOTE: The manifold pressure must be referenced to the
burner box. The burner box pressure tap equalizes the gas
valve pressure regulator. Manifold pressure is checked by
installing a tee (field supplied) in the tubing, between the tee
coming from the burner box tube and the gas valve,
addition to the regular gas valve pressure tap on the outlet
side of the gas valve. See Figure 59.
Table 21 lists the main burner orifices used with the furnace.
If a change of orifices is required to correct the furnace input
rating refer to Table 19.
REINSTALLATION OF THE BURNER BOX COVER
Figure 59 shows the correct way to reinstall the burner box
cover if adjustment or replacement of the flame sensor, hot
surface igniter, or main burner orifices have required removal
of the cover.
Input ratings (BTUH) of these Furnaces are based on sea
level operation and should not be changed at elevations up to
2,000 ft.
If the installation is 2,000 ft. or above, the Furnace input rate
(BTUH) shall be reduced 4% for each 1,000 ft. above sea level.
The Furnace input rate shall be checked by clocking the gas
flow rate (CFH) and multiplying by the heating value obtained from the local utility supplier for the gas being delivered at the installed altitude. Input rate changes can be
made by adjusting the Manifold Pressure (min 3.0 - max 3.7
in. W.C. - Natural Gas) or changing orifices (orifice change
may not always be required).
If the desired input rate can not be achieved with a change in
Manifold Pressure, then the orifices must be changed. LP
installations will require an orifice change.
IMPORTANT: Reinstall the replacement orifices to the same
depth as the orifices supplied with the equipment.
See Table 19 for help in selecting orifices if orifice change is
required. Furnace input rate and temperature rise should be
checked again after changing orifices to confirm the proper rate
for the altitude.
The vent length table on page 19 shows the required vent
lengths for installations at various altitudes. An optional
high altitude kit is available for installations above 5000
feet. Installations above 12,000 feet are not allowed.
Table 19
PART NUMBERS FOR REPLACEMENT ORIFICES
DRILL
SIZE
44
45
46
47
48
49
50
Turn the main Gas Valve toggle switch (See Figures 30 & 31)
within the unit to the “OFF” position. Turn the external gas
valve to “ON”. Purge the air from the gas lines. After purging,
check all gas connections for leaks with a soapy solution -- DONOT CHECK WITH AN OPEN FLAME. Allow 5 minutes
for any gas that might have escaped to dissipate.
LP Gas being heavier than air may require forced ventilation.
Turn the toggle switch on the Gas Valve in the unit to the “ON”
position.
Installation of this furnace at altitudes above 2000 ft
(610m) shall be in accordance with local codes, or in the
absence of local codes, the National Fuel Gas Code, ANSI
Z223.1/NFPA 54 or National Standard of Canada, Natural
Gas and Propane Installation Code, CSA B149.1.
Installation of this furnace at altitudes above 2000 ft (610
m) shall be made in accordance with the listed high
Altitude Conversion Kit available with this furnace.
If your application requires a high altitude pressure switch
use Table 20 to select the appropriate kit for your model
furnace.
Table 20
High Altitude Kits Used With
*UH2B/*DH2B080A9V3VA
*UH2B/*DH2B080A9V4VA
BAYSWT08AHALTA
*UH2C/*DH2C100A9V4VA
*UH2C100A9V5VA
*UH2D/*DH2D120A9V5VA
BAYSWT10AHALTA*UH2B/*DH2B060A9V3VA
18-CD26D1-1035
Page 36
Installer’s Guide
FIELD WIRING DIAGRAM FOR VARIABLE SPEED 2 STAGE FURNACE
Electrical Connections
Make wiring connections to the unit as indicated on enclosed
wiring diagram. As with all gas appliances using electrical
power, this furnace shall be connected into a permanently live
electric circuit. It is recommended that furnace be provided
with a separate “circuit protection device” electric circuit. The
furnace must be electrically grounded in accordance with local
codes or in the absence of local codes with the National
Electrical Code, ANSI/NFPA 70 or CSA C22.1 Electrical Code,
if an external electrical source is utilized. The integratedfurnace control is polarity sensitive. The hot leg of the
120V power supply must be connected to the black power lead
as indicated on the wiring diagram.
Refer to the SERVICE FACTS literature and unit wiring
diagram attached to furnace.
1 STAGE HEATING
USING A 1 STAGE HEATING THERMOSTAT
NO COOLING
1. Be sure power agrees with equipment nameplates.
2. Low voltage (24 volt wiring) to be No. 18 A.W.G. min.
3. Grounding of equipment must comply with local codes.
4. Set thermostat heat anticipator per unit wiring diagram.
5. These leads provide 115V. power for connection of electronic
W14
W14 JUMPER
SEE NOTE 11
Y1/Ylo
SEE
SEE
NOTE 6
NOTE 9
FIELD ADDED JUMPER
SEE FURNACE WIRING DIAGRAM
FOR 2ND STAGE TIMING.
air cleaner and humidifier MAX. load 1.0 amps each.
6. When a single stage heating thermostat without fan switch
is used, no wiring on "G" terminal is used.
7. W1 and W2 must be jumpered together for proper operation.
Second stage heat will begin based on IFC switch setting.
8. Set dip switches with power off per installation instructions
to set airflow and indoor fan off delays.
9. Continuous fan airflow can be increased by adding this jumper.
10. This wire is only for thermostats requiring connection to
transformer common terminal.
11. Optional humidistat is to be connected between R and BK. Factory installed jumper R
to BK on the circuit board must be cut if optional humidistat is used. The jumper must
also be cut when applying an airflow command signal to the BK input such as with the
variable speed single-zone and multi-zone system controllers. On single speed cooling
only/non-heat pump systems, jumper Y to O for proper operation of the delay profiles
and the humidistat. For two compressor or two speed systems, jumper YLo to O.
W1 TO W2.
SEE
B/C
NOTE 10
B/C
3618-CD26D1-10
TO 115 V 1 PH.,
60 HZ., POWER
SUPPLY PER
LOCAL CODES
HUM SEE
NOTE 5
EAC SEE
NOTE 5
From Dwg. B342027 Rev. 1
Figure 60
Page 37
Installer’s Guide
t.
FIELD WIRING DIAGRAM FOR VARIABLE SPEED 2 STAGE FURNACE
2 STAGE HEATING
USING A 2 STAGE HEATING THERMOSTAT
NO COOLING
1. Be sure power agrees with equipment nameplates.
2. Low voltage (24 volt wiring) to be No. 18 A.W.G. min.
3. Grounding of equipment must comply with local codes.
4. Set thermostat heat anticipator per unit wiring diagram.
5. These leads provide 115V. power for connection of electronic
air cleaner and humidifier MAX. load 1.0 amps each.
6. This wire is only for thermostats requiring connection to
transformer common terminal.
7. Continuous fan airflow can be increased by adding this jumper.
8. Set dip switches with power off per installation instructions
to set airflow and indoor fan off delays.
9. Optional humidistat is to be connected between R and BK. Factory
installed jumper R to BK on the circuit board must be cut if optional
humidistat is used. The jumper must also be cut when applying an airflow
command signal to the BK input such as with the variable speed single-zone
and multi-zone system controllers. On single speed cooling only/non-heat pump
systems, jumper Y to O for proper operation of the delay profiles and the humidista
For two compressor or two speed systems, jumper YLo to O.
Y1/Ylo
W14
W14 JUMPER
SEE NOTE 9
SEE
NOTE 7
B/C
SEE
NOTE 6
B/C
TO 115 V 1 PH.,
60 HZ., POWER
SUPPLY PER
LOCAL CODES
HUM SEE
NOTE 5
EAC SEE
NOTE 5
From Dwg. B342025 Rev. 0
Figure 61
18-CD26D1-1037
Page 38
Installer’s Guide
FIELD WIRING DIAGRAM FOR VARIABLE SPEED 2 STAGE FURNACE
USING A 1 STAGE HEATING, 1 STAGE COOLING THERMOSTAT
(OUTDOOR SECTION WITHOUT TRANSFORMER)
OUTDOOR UNIT
(NO TRANSFORMER)
B/C
SEE
NOTE 7
SEE
NOTE 6
Y1/Ylo
B/C
1 STAGE HEATING, 1 STAGE COOLING
W14
W14 JUMPER
SEE NOTE 9
FIELD ADDED JUMPER
W1 TO W2.
SEE FURNACE WIRING DIAGRAM
FOR 2ND STAGE TIMING.
TO 115 V 1 PH.,
60 HZ., POWER
SUPPLY PER
LOCAL CODES
HUM SEE
NOTE 5
EAC SEE
NOTE 5
Figure 62
From Dwg. B342022 Rev. 1
3818-CD26D1-10
Page 39
OUTDOOR UNIT
(NO TRANSFORMER)
Installer’s Guide
FIELD WIRING DIAGRAM FOR VARIABLE SPEED 2 STAGE FURNACE
2 STAGE HEATING, 1 STAGE COOLING
USING A 2 STAGE HEATING, 1 STAGE COOLING THERMOSTAT
(OUTDOOR SECTION WITHOUT TRANSFORMER)
W14
SEE
NOTE 9
SEE
NOTE 7
Y1/Ylo
W14 JUMPER
SEE NOTE 9
B/C
SEE
NOTE 6
B/C
TO 115 V 1 PH.,
60 HZ., POWER
SUPPLY PER
LOCAL CODES
HUM SEE
NOTE 5
EAC SEE
NOTE 5
Figure 63
From Dwg. B342020 Rev. 0
18-CD26D1-1039
Page 40
Installer’s Guide
FIELD WIRING DIAGRAM FOR VARIABLE SPEED 2 STAGE FURNACE
(OUTDOOR SECTION WITHOUT TRANSFORMER)
OUTDOOR UNIT NO. 1
(NO TRANSFORMER)
SEE NOTE 3
SEE
NOTE 7
OUTDOOR UNIT NO. 2
(NO TRANSFORMER)
SEE
NOTE 6
B/C
2 STAGE HEATING, 2 STAGE COOLING
W14
TO 115 V 1 PH.,
60 HZ., POWER
SUPPLY PER
LOCAL CODES
B/C
HUM SEE
NOTE 5
EAC SEE
NOTE 5
Figure 64
HUMIDISTAT HOOKUP
If an optional Humidistat is to be connected between “R”
and “BK”, the factory installed jumper between “R” and “BK”
on the circuit board must be cut. If an optional Humidistat is
used, the jumper must also be cut when applying an airflow
command signal to the “BK” input such as with the variable
speed single-zone and multi-zone system controller. On single
speed cooling only/ non-heat pump systems, jumper “Y” to “O”
for proper operation of the delay profiles and the Humidistat.
For two compressor or two speed systems, jumper “YLO” to
“O”.
From Dwg. B342018 Rev. 0
The factory installed jumper between
“R” and “BK” on the circuit board
must be cut if an optional Humidistat
is installed.
BLK
4018-CD26D1-10
BLK
Figure 65
Page 41
Installer’s Guide
▲
▲
▲
Start-up and Adjustment
Preliminary Inspections
!
WARNING
ELECTRIC SHOCK HAZARD
DISCONNECT POWER TO THE UNIT BEFORE REMOVING
THE BLOWER DOOR. ALLOW A MINIMUM OF 10 SECONDS
FOR IFC POWER SUPPLY TO DISCHARGE TO 0 VOLTS.
FAILURE TO FOLLOW THIS WARNING COULD RESULT IN
PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
With gas and electrical power “OFF”
1. Duct connections are properly sealed
2. Filters are in place
3. Venting is properly assembled
4. Blower door is in place
Turn the toggle switch on the main gas valve within the unit
to the “OFF” position (See Figures 54 - 56) . Turn the
external main gas shutoff valve to “ON”. Purge the air from
the gas lines. After purging, Check all gas connections for
leaks with a soapy solution — DO NOT CHECK WITH ANOPEN FLAME. Allow 5 minutes for any gas that might
have escaped to dissipate. LP Gas being heavier than air
may require forced ventilation. Turn the toggle switch on the
main gas valve within the unit to the “ON” position.
Lighting Instructions
!
WARNING
BURN HAZARD
DO NOT ATTEMPT TO MANUALLY LIGHT THE BURNER.
FAILURE TO FOLLOW THIS WARNING COULD RESULT IN
PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
Lighting instructions appear on each unit. Each installation
must be checked out at the time of initial start up to insure
proper operation of all components. Check out should include
putting the unit through one complete cycle as outlined below.
Turn on the main electrical supply and set the comfort control
above the indicated temperature. The ignitor will automatically heat, then the gas valve is energized to permit the flow
of gas to the burners. After ignition and flame is established,
the flame control module monitors the flame and supplies
power to the gas valve until the comfort control is satisfied.
To shut off
For complete shutdown: Turn the toggle switch located on the
main gas valve inside the unit to the "OFF" position and the
external main gas shutoff valve to the “OFF” position (See
Figures 54-56). Disconnect the electrical supply to the unit.
!
CAUTION
If shutoff is done during the cold weather months, provisions
must be taken to prevent freeze-up of all water pipes and
water receptacles.
Whenever your house is to be vacant, arrange to have someone inspect your house for proper temperature. This is very
important during freezing weather. If for any reason your
furnace should fail to operate damage could result, such as
frozen water pipes.
Control and Safety Switch Adjustments
LIMIT SWITCH CHECK OUT
The limit switch is a safety device designed to close the gas
valve should the furnace become overheated. Since proper operation of this switch is important to the safety of the unit, it
must be checked out on initial start up by the installer.
To check for proper operation of the limit switches, set the
thermostat to a temperature higher than the indicated
temperature to bring on the gas valve.
SEQUENCE OF OPERATION
Comfort Control call for heat (2-Stage Comfort Control)
Call for 1st Stage only:
W1 Comfort Control contacts close signaling the control
module to run its self-check routine. After the control module
has verified that the 1st Stage Pressure Switch contacts are
open and the Limit Switch(es) contacts are closed, the draft
blower will be energized.
As the induced draft blower comes up to speed, the Pressure
Switch contacts will close and the ignitor warm up period will
begin. The ignitor will heat for approx. 20 seconds, then the
Gas Valve is energized in 1st Stage to permit gas flow to the
burners.
The flame sensor confirms that ignition has been achieved
within the 4 second ignition trial period.
As the flame sensor confirms that ignition has been achieved,
the delay to fan ON period begins timing and after approx. 45
seconds the indoor blower motor will be energized at low
speed and will continue to run during the heating cycle.
Call for 2nd Stage after 1st Stage:
W2 Comfort Control contacts close signaling a call for 2nd
Stage Heat. After a 30 second delay, the induced draft blower
will be energized on high speed and the 2nd Stage Pressure
Switch contacts will close. The Gas Valve is energized in 2nd
Stage and the indoor blower motor in high speed.
2nd Stage satisfied, 1st Stage still called:
W2 Comfort Control contacts open signaling that 2nd Stage
Heating requirements are satisfied.
The induced draft blower is reduced to low speed allowing the
2nd Stage Pressure Switch contacts to open and the Gas
Valve is reduced to 1st Stage. The indoor blower motor is
reduced to low speed.
1st stage satisfied:
W1 Comfort Control contacts open signaling that 1st Stage
heating requirements are satisfied. The Gas Valve will close
and the induced draft blower. The indoor blower motor will
continue to run for the fan off period (Field selectable at 60,
100, 140 or 180 seconds), then will be de-energized by the
control module.
Comfort Control call for heat (1-Stage Comfort Control)
W1/ W2 (jumpered) Comfort Control contacts close signaling
a call for heat. 1st Stage sequence of operation remains the
same as above. 2nd Stage Heat will energize after the Stage
delay timer (10 minutes) has expired.
Comfort Control satisfied:
W1/ W2 (jumpered) contacts close signaling the control
module to close the Gas Valve. The induced draft blower is
switched to low speed and de-energized after the post purge
timer has expired. The indoor blower motor will continue to
operate after the flames are extinguished and then is
switched to low heat speed for the FAN-OFF period.
18-CD26D1-1041
Page 42
Installer’s Guide
▲
▲
NOTE TO INSTALLER
Review warnings and the contents of USER’S INFORMATION MANUAL with the homeowner when installation is
complete and equipment is ready to be turned over to the
homeowner for normal operation.
CONTROL AND SAFETY SWITCH
ADJUSTMENT
LIMIT SWITCH CHECK OUT
The limit switch is a safety device designed to close the Gas
Valve should the Furnace become overheated. Since proper
operation of this switch is important to the safety of the unit,
it must be checked out on initial start up by theinstaller.
To check for proper operation of the Limit Switches, set the
Comfort Control to a temperature higher than the indicated
temperature to bring on the Gas Valve. Restrict the airflow
by blocking the return air or by disconnecting the blower.
When the Furnace reaches the maximum outlet temperature
as shown on the rating plate, the burners must shut off. If
they do not shut off after a reasonable time and overheating
is evident, a faulty Limit Switch is probable and the Limit
Switch must be replaced. After checking the operation of the
Limit Control, be sure to remove the paper or cardboard from
the return air inlet, or reconnect the blower. Refer to the
Service Facts for additional instructions.
INDOOR BLOWER TIMING
Table 22. FAN OFF -- DELAY OPTIONS
SWITCH SETTINGSSELECTION
5 - OFF6 - OFFNON ESAME
5 - ON6 - OFF1.5 MINUTES100 % *
5 - OFF6 - ON3 MINUTES50%
5 - ON6 - ON
Enhanced
Mode**
NOMINAL
AIRFLOW
50 - 100%
* - This setting is equivalent to BA Y24X045 relay
benefit.
** - This selection provides ENHANCED MODE,
which is a ramping up and ramping down of the
blower speed to provide improved comfort, quietness, and potential energy savings. See Wiring
Diagram notes on the unit or in the Service Facts
for complete wiring setup for ENHANCED MODE.
The graph which follows, shows the ramping
process.
See Wiring Diagram on the unit or in the Service Facts
for complete wiring setup for Enhanced Mode.
!
WARNING
ELECTRIC SHOCK HAZARD
DISCONNECT POWER TO THE UNIT BEFORE REMOVING
THE BLOWER DOOR. ALLOW A MINIMUM OF 10 SECONDS
FOR IFC POWER SUPPLY TO DISCHARGE TO 0 VOLTS.
FAILURE TO FOLLOW THIS WARNING COULD RESULT IN
PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
Heating: The Integrated Furnace Control (IFC) controls the
Variable Speed Indoor Blower. The blower “on” time is fixed
at 45 seconds after ignition. The FAN-OFF period is field
selectable by dip switches #1 and #2 located on the Integrated Furnace Control between the 5-pin and 9-pin wire
connectors. The delay may be set at 60, 100, 140, or 180 seconds. The factory setting is 100 seconds (See unit wiring
diagram).
Cooling: The fan delay-off period is set by dip switches on the
Integrated Furnace Control. The options for cooling delay off
is field selectable by dip switches #5 and #6.
The following table and graph explain the delay-off settings:
This unit is equipped with a blower door switch which cuts
power to the blower and Gas Valve causing shutdown when
the door is removed.
ROOM AIR COMFORT CONTROL
HEAT ANTICIPATOR ADJUSTMENT
Set the Comfort Control heat anticipator according to the
current flow measured, or the settings found in the notes on
the Furnace wiring diagram (found in the SERVICE FACTS
or inside the furnace casing).
100% if necessary
80%
Fast Cooling
1
minute
Dehumidify
7.5
minutes
Figure 66
!
WARNING
50%
Efficiency
OFF
3
minutes
50%
OFF
AIRFLOW ADJUSTMENT
CARBON MONOXIDE HAZARD
OPERATION WITH THE DOOR REMOVED OR AJAR CAN
PERMIT THE ESCAPE OF DANGEROUS FUMES. ALL
PANELS MUST BE SECURELY CLOSED AT ALL TIMES FOR
SAFE OPERATION OF THE FURNACE.
FAILURE TO FOLLOW THIS WARNING COULD RESULT IN
PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
Check inlet and outlet air temperatures to make sure they
are within the ranges specified on the Furnace rating nameplate. If the airflow needs to be increased or decreased, see
the Service Facts for information on changing the speed of the
blower motor.
4218-CD26D1-10
Page 43
Installer’s Guide
▲
INSTRUCTIONS TO THE OWNERS
!
WARNING
EXPLOSION HAZARD
IN THE EVENT THAT ELECTRICAL, FUEL OR MECHANICAL FAILURES OCCUR, SHUT OFF THE GAS
SUPPLY AT THE MANUAL GAS SHUT OFF VALVE,
LOCATED ON THE SUPPLY GAS PIPING COMING
INTO THE FURNACE, BEFORE TURNING OFF THE
ELECTRICAL POWER TO THE FURNACE. CONTACT
SERVICER.
FAILURE TO FOLLOW THIS WARNING COULD RESULT IN PROPERTY DAMAGE, PERSONAL INJURY
OR DEATH.
BURNER BOX TEMPERATURE LIMIT DEVICE
All models are equipped with a manual reset temperature
limit located on the Burner Box. In case of excessive temperature, the limit will open and cause the circuit to open which
shuts off all flow of gas.
CONDITIONS THAT AFFECT SYSTEM
OPERA TION
1. EXCESSIVE COMBUSTION PRESSURE (WIND IN
EXCESS OF 40 M.P.H.) VENT OR FLUE BLOCKAGE
On a call for heat, the Variable Speed Draft Inducer must
first ramp up to speed and close the Pressure Switch
before the ignition sequence is allowed to begin. If the
Pressure Switch does not close, the motor will ramp up to
maximum speed and continue to operate there for about
1 minute.
After one minute, the Integrated Furnace Control will
turn the motor off for about 30 seconds and then back on
in an attempt to reestablish proper operation. This
condition is indicative of a highly restricted or blocked
inlet or outlet vent pipe or a failed Pressure Switch.
If pressure against induced draft blower outlet becomes
excessive, the Pressure Switch will open. If the Pressure
Switch is open for more than 3.5 seconds, the variable
speed draft inducer will speed up and attempt to close
the Pressure Switch. If the Pressure Switch is not closed
within 12 seconds or if the maximum speed of the motor
is reached, the draft inducer sends a Fault signal to the
Integrated Furnace Control. If the unit is operating in
Second Stage, an Inducer Fault will cause the Furnace
Control to transition the system to First Stage and it
will operate there for 10 minutes before attempting to
run again in Second Stage. If the unit is operating in
First Stage, an Inducer Fault will cause the Furnace
Control to shut the system down and wait 30 seconds
before attempting to reestablish operation in First
Stage.
2. LOSS OF FLAME
If loss of flame occurs during a heating cycle, or flame is
not present at the sensor, the flame control module will
close the Gas Valve. The Integrated Furnace Control will
then recycle the ignition sequence, then if ignition is not
achieved, it will shut off the Gas Valve and lock out the
system.
3. POWER FAILURE
If there is a power failure during a heating cycle, the
system will restart the ignition sequence automatically
when power is restored, if the Comfort Control still calls
for heat.
4. GAS SUPPLY FAILURE
If loss of flame occurs during a heating cycle, the system
Integrated Control Module will recycle the ignition sequence,
then if ignition is not achieved, the Integrated Control
Module will shut off the Gas Valve and lock out the system.
5. INDUCED DRAFT BLOWER FAILURE
Please refer to the Variable Speed Draft Inducer
troubleshooting manual for diagnostic assistance.
6. CONDENSATE DRAIN BLOCKAGE
If the condensate drain is blocked, either by debris,
improper draining, or by freezing condensate, the pressure switch will receive a signal warning of the accumulation of condensate in the heat exchanger assembly. The
pressure switch contacts will open and remain open, not
allowing unit operation. The unit will not operate until
the condensate drain has been cleared, and the condensate flows freely.
7. RESET AFTER LOCKOUT
When the Integrated Furnace Control has shut the
system down and gone into lockout, the system must be
manually reset before the unit will restart. The system
can be reset by turning the system power off for more
than 1 second, or by removing 24VAC from the control for
more than 1 second, or by removing the Comfort Control
call for heat for more than 1 second but less than 20
seconds.
8. RESET AFTER BURNER BOX LIMIT SHUTDOWN
If the furnace shuts down, one thing that can be checked
is the burner box temperature limit switch. It is located
on the bottom of the burner box. The vent and combustion air inlet terminations should be checked for blockage. If blockage exists, clear the problem and then the
reset button may be depressed. If there is no blockage
of the terminations, the limit switch must be reset
by a qualified servicer.
INDOOR MOTOR MAINTENANCE
Direct drive motors have bearings which are permanently
lubricated and under normal use, lubrication is not recommended.
18-CD26D1-1043
Page 44
Installer’s Guide
IFC Error Flash Codes
Table 23
INTEGRATED F URNACE CONTROL LED FLASH CODES
TM
RED LED - LitePort
DATA - 1 FLASH EVERY 20 SECONDS
2 Flashes ---RETRIES OR RECYCLES EXCEEDED
3 Flashes ---INDUCER OR PRESSURE SWITCH ERROR
4 Flashes ---OPEN LIMIT OR ROLLOUT SWITCH
5 Flashes ---FLAME SENSED WHEN NO FLAME SHOULD BE PRESENT
6 Flashes ---LINE REVERSE POLARITY
7 Flashes ---GAS VALVE CIRCUIT ERROR
8 Flashes ---WEAK FLAME
9 Flashes ---OPEN INDUCER LIMI T ERROR
GREEN LED - STATUS
Slow FlashNORMAL, NO CALL FOR HEAT
Fast FlashNORMAL, CALL FOR HEAT PRESENT
GREEN and RED
LED's on Continuously
FUSE OPEN OR INTERNAL CONTROL FAILURE
Fault Code Recovery
On power up, last 4 faults, if any, will be flashed on the red
LED. The newest fault detected will flash first and the oldest
last. There will be a 2 second delay between fault code
flashes. Solid red LED error codes will not be displayed.
The Green LED will be on solid during last fault recovery.
At any other time the control is powered, the Green LED
indicator light will operate as shown in Table 14 and the red
LED will flash LitePort data (one flash) every 20 seconds.
Table 25
INTEGRATED FURNACE CONTROL
GREEN "STATUS" LED FLASH CODES
Flashing Slow ---Normal - No call for Heat
Flashing Fast ---Normal - Call for Heat
Fault Code Reset
The last 4 fault codes can be erased from memory by powering up the control with “G” energized and then applying “R” to
the “W1” terminal 3 times within 6 seconds. The control will
acknowledge the reset by turning on the red LED for 2 seconds.
Red LitePort
Green Status LED
TM
LED
Figure 67
4418-CD26D1-10
Page 45
Notes
Installer’s Guide
18-CD26D1-1045
Page 46
Trane
6200 Troup Highway
Tyler, TX 75707
For more information contact
your local dealer
Literature Order Number 18-CD26D1-10
File Number18-CD26D1-10
Supersedes18-CD26D1-9
Date09/10
The manufacturer has a policy of continuous product and product data improvement; it reserves the right to
change design and specifications without notice.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.